MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

Size: px
Start display at page:

Download "MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions"

Transcription

1 conduit? 9/8/10 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. Can branch circuits of different services be installed in the same Yes, see 300.3(C)(1) for conductors of different systems rated 600 volts, nominal, or less that states, Conductors of circuits rated 600 volts, nominal, or less, ac circuits, and dc circuits shall be permitted to occupy the same equipment wiring enclosure, cable, or raceway. All conductors shall have an insulation rating equal to at least the maximum circuit voltage applied to any conductor within the enclosure, cable, or raceway. See 300.3(C)(2) for over 600 volt, nominal, conductors occupying the same equipment wiring enclosure, cable, or raceway with conductors of circuits rated 600 volts, nominal, or less which states, conductors of circuits rated over 600 volts, nominal, shall not occupy the same equipment wiring enclosure, cable, or raceway with conductors of circuits rated 600 volts, nominal, or less unless otherwise permitted in (C)(2)(a) through (C)(2)(e). The provisions of (C)(2)(a) through (C)(2)(e) were discussed. 2. Is it permissible to land my grounding electrode conductor in a fieldinstalled lug on either the inside or outside of the bottom of the service panel? No, unless it s listed for the use. See (A) that states, A premises wiring system supplied by a grounded ac service shall have a grounding electrode conductor connected to the grounded service conductor, at each service, in accordance with (A)(1) through (A)(5). Section (A)(1) states, The connection shall be made at any accessible point from the load end of the service drop or service lateral to and including the terminal or bus to which the grounded service conductor is connected at the service disconnecting means. Also, see that states, Nonconductive coatings (such as paint, lacquer, and enamel) on equipment to be grounded shall be removed from threads and other contact surfaces to ensure good electrical continuity or be connected by means

2 of fittings designed so as to make such removal unnecessary. Also, see 300.6(A) that states, Ferrous metal raceways, cable trays, cablebus, auxiliary gutters, cable armor, boxes, cable sheathing, cabinets, metal elbows, couplings, nipples, fittings, supports, and support hardware shall be suitable protected against corrosion inside and outside by a coating of listed corrosion resistant material. Both panelboard and switch equipment come with or have available neutral (grounded conductor) kits and provisions, which are listed for specific applications. 3. Is redundant grounding required in a feeder to a 200-ampere panel in a critical care area in a hospital? No, as this is strictly a branch-circuit requirement covered in However, (D), panelboard grounding and Bonding states, Where a grounded electrical distribution system is used and metal feeder raceway or Type MC or MI cable that qualifies as an equipment grounding conductor in accordance with is installed, grounding of a panelboard or switchboard shall be ensured by one of the following bonding means at each termination or junction point of the metal raceway or Type MC or MI cable: (1) A grounding bushing and a continuous copper bonding jumper, sized in accordance with , with the bonding jumper connected to the junction enclosure or the ground bus of the panel (2) Connection of feeder raceways or Type MC or MI cable to threaded hubs or bosses on terminating enclosures (3) Other approved devices such as bonding-type locknuts or bushings Concerning branch circuit redundant grounding requirements of , Code-Making Panel 17, currently Code-Making Panel 15, stated in their substantiation to Proposal to the 1996 NEC that, the intent of (a) is to provide two separate grounding paths the metal raceway and the conductor. They also stated that, Type MC Cable with two paralleled equipment grounding conductors [one green insulated and the other green with yellow stripes insulated] does not satisfy the requirement of Section (a). Also, see Code- Making Panel 17 s panel statement to Proposal to the 1996 NEC that states, The addition of a second equipment grounding conductor does not introduce a redundant path, it merely increases the capacity of the equipment grounding conductor. The intent

3 of Section (b) is to provide two separate means of grounding the raceway and the conductor. 4. 1) Can more than one receptacle in a laundry room be on the required laundry circuit? 2) If the laundry equipment (washer/dryer) is in one room but the owner irons clothes in another room, can the circuit go to the two rooms? 1) Yes, see (F) that states, In dwelling units, at least one receptacle outlet shall be installed for the laundry. See (C)(2) that states, In addition to the number of branch circuits required by other parts of this section, at least one 20-ampere branch circuit shall be provided to supply the laundry receptacle outlet(s) required by (F). 2) No, (C)(2) requires at least one 20-ampere branch circuit shall be provided to supply the laundry receptacle outlet(s), and it states, This circuit shall have no other outlets (A) and basically state the any circuit leading to or through dispensing equipment and each dispensing device shall be provided with means to remove all external voltage sources. Does this include intrinsically safe circuits? NO. If the intrinsically safe circuit(s) are properly installed in accordance with article 504 of the NEC then it is not necessary to include them in the requirements of (A) and For further clarification, consult NFPA 30A section 6.7 exception. 6. Can the same equipment grounding conductor be used for the pool motor and the pool lights? Someone told me we need a separate EGC for each light and for the motor. Yes, No, and maybe. The pool motor must be separate from the pool lights; however the pool lights may be combined on the same equipment ground with restrictions. See Underwater Luminaires (Lighting Fixtures), subsection (F) (3) Conductors, that states, Conductors on the load side of a ground-fault circuit interrupter or of a transformer, used to comply with the provisions of (A)(8), shall not occupy raceways, boxes, or enclosures

4 containing other conductors unless one of the following conditions applies: (1) The other conductors are protected by ground-fault circuit interrupters, (2) The other conductors are grounding conductors, or (3) The other conductors are supply conductors to a feed-through type ground-fault circuit interrupter. Also see subsection (F)(2) Equipment Grounding, that states, Through-wall lighting assemblies, wet-niche, dry-niche, or no-niche luminaires (lighting fixtures) shall be connected to an insulated copper equipment grounding conductor installed with the circuit conductors. The equipment-grounding conductor shall be installed without joint or splice except as permitted in (F)(2)(a) and (F)(2)(b). The equipment-grounding conductor shall be sized in accordance with Table but shall not be smaller than 12 AWG. Section (F)(2)(a) states, that where more than one underwater luminaire (lighting fixture) is supplied by the same branch circuit, the equipment grounding conductor, installed between the junction boxes, transformer enclosures, or other enclosures in the supply circuit to wet-niche luminaires (fixtures), or between the field-wiring compartments of dry-niche luminaires (fixtures), shall be permitted to be terminated on grounding terminals. Section (F)(2)(b) states that the underwater luminaire (lighting fixture) is supplied from a transformer, ground-fault circuit interrupter, clock-operated switch, or a manual snap switch that is located between the panelboard and a junction box connected to the conduit that extends directly to the underwater luminaire (lighting fixture), the equipment grounding conductor shall be permitted to terminate on grounding terminals on the transformer, ground-fault circuit interrupter, clock-operated switch enclosure, or an outlet box used to enclose a snap switch. As to motors, see (A)(1) Wiring Methods, General that states, The branch circuits for pool-associated motors shall be installed in rigid metal conduit, intermediate metal conduit, rigid nonmetallic conduit, or Type MC cable listed for the location. Other wiring methods and materials shall be permitted in specific locations or applications as covered in this section. Any wiring method employed shall contain an insulated copper equipment-grounding conductor sized in accordance with but not smaller than 12 AWG. Also, see (A)(4) One-Family Dwellings that states, In the interior of one-family dwellings, or in the interior of accessory buildings associated with a one-family dwelling, any of the wiring methods recognized in Chapter 3 of this Code that comply with the provisions of this paragraph shall be permitted. Where run in a cable assembly, the equipment grounding conductor shall be permitted to be uninsulated, but it shall

5 be enclosed within the outer sheath of the cable assembly. Also, see (A) Area Lighting, Receptacles, and Equipment, Receptacles, subsection (5) GFCI Protection that states, All 15- and 20-ampere, single-phase, 125-volt receptacles located within 6.0 m (20 ft) of the inside walls of a pool shall be protected by a ground-fault circuit interrupter. Receptacles that supply pool pump motors and that are rated 15 or 20 amperes, 125 volts through 250 volts, single phase, shall be provided with GFCI protection. 7. I have installed a dedicated 20-ampere branch circuit to a microwave receptacle mounted in the cabinet space above the microwave oven. On the finish I installed a 15-ampere duplex receptacle. The inspector red tagged the job, and requested that I install a single 20- ampere receptacle. Is this a violation and if so what section of the 2008 NEC applies? First, the NEC does not define the term dedicated branch circuit. See Article 100, page 25 that states an individual branch circuit is, A branch circuit that supplies only one utilization equipment. Section (B)(1) states, A single receptacle installed on an individual branch circuit shall have an ampere rating not less than that of the branch circuit. Note that the exceptions to this section do not bear in this installation. Also, note that Section (B)(1) does not require an individual branch circuit to serve a single receptacle exclusively. Section (B)(3) states, where connected to a branch circuit supplying two or more receptacles or outlets, receptacle ratings shall conform to the values listed in Table (B)(3). Table (B)(3) allows receptacle ratings of both 15- and 20-ampere on a 20-ampere rated circuit. Also, note that (B)(2) for cord-and-plugconnected loads requires that, where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle shall not supply a total cord-and-plug-connected load in excess of 12-amperes for a 15-ampere rated receptacle supplied by a 20-ampere rated circuit and 16-amperes for a 20-ampere rated receptacle supplied by a 20-ampere rated circuit. Also, see (A)(1) that states, the rating of any one cord-and-plug-connected utilization equipment shall not exceed 80% of the branch-circuit ampere rating, which compliments the requirements in (B)(2). Also see (A) that states, the rating of an individual branch circuit shall not be less than the marked rating of the appliance or

6 the marked rating of an appliance having combined loads as provided in See that states, Each electric appliance shall be provided with a nameplate giving the identifying name and rating in volts and amperes, or in volts and watts (B)(1) states, in addition to the marking required in , the marking on an appliance consisting of a motor with other load(s) or motors with or without other load(s) shall specify the minimum supply circuit overcurrent protective devices. Therefore, a 15 ampere rated duplex receptacle is acceptable where the load is limited to 12 amperes or less and a 20-ampere rated receptacle would be required for loads exceeding 12-amperes up to 16- amperes. If the microwave range also has a range hood built into it, look at (B)(4) that states, range hoods shall be permitted to be cord-and-plug connected with a flexible cord identified as suitable for use on range hoods in the installation instructions of the appliance manufacturer, where all of the following conditions are met: 1) The flexible cord is terminated with a grounding-type attachment plug where the range hood is not identified as one utilizing a system of double insulation, 2) The length of the cord is not less than 18 inches and not more than 36 inches, 3) receptacles are located to avoid physical damage to the flexible cord, 4) the receptacles is accessible, and 4) the receptacle is supplied by an individual branch circuit. 8. Is it permissible to parallel MC Cable? What about the sizing of the equipment grounding conductor? Yes, MC Cable can be paralleled as permitted in Article and The sizing if the equipment grounding conductor is done in accordance with 310.4(E). There are some manufacturers who have listed MC cables made specifically for paralleling. 9. The secondary side of a step-down transformer is fed with steel flex and attached to a panelboard, with the neutral and grounding electrode conductors landed at the transformer. What are my bonding and /or grounding requirements in my steel flex and to the panel? See Grounding Separately Derived Alternating-Current Systems. (A) Grounded Systems that states, A separately derived ac system that is grounded shall comply with

7 250.30(A)(1) through (A)(8). Except as otherwise permitted in this article, a grounded conductor shall not be connected to normally non current-carrying metal parts of equipment, to equipment grounding conductors, or be reconnected to ground on the load side of the point of grounding of a separately derived system (A)(1), System Bonding Jumper states, An unspliced system bonding jumper in compliance with (A) through (D) that is sized based on the derived phase conductors shall be used to connect the equipment grounding conductors of the separately derived system to the grounded conductor. This connection shall be made at any single point on the separately derived system from the source to the first system disconnecting means or overcurrent device, or it shall be made at the source of a separately derived system that has no disconnecting means or overcurrent devices. However, see Exception No. 2 that states, A system bonding jumper at both the source and the first disconnecting means shall be permitted where doing so does not establish a parallel path for the grounded conductor. If the steel flex meets all the requirements of ; then you may pull three hots and the grounded conductor (neutral) to the secondary panel where the grounded conductor (neutral) is isolated from the can. If the steel flex does not meet the requirements of an equipment bonding jumper must be pulled with your three hots and the grounded conductor (neutral) to the secondary panel and the grounded conductor (neutral) is isolated from the can. 10. I recently inspected a job where the electrician installed the grounded conductor and the grounding conductor in the same terminal of the panelboard. Is this a violation? Yes, see and 110.3(B). Section states, Each grounded conductor shall terminate within the panelboard in an individual terminal that is not also used for another conductor. However, also see the exception that states, Grounded conductors of circuits with parallel conductors shall be permitted to terminate in a single terminal if the terminal is identified for connection of more than one conductor. 11. Is a service installed correctly if a meter and service disconnect breaker are installed on a pedestal 100 feet from the house and bonded at the pedestal and a four-wire feeder piped directly into a MLO panel located 20 ft inside the house?

8 No, the service may be 100 feet from the house however see, that states, The disconnecting means shall be installed either inside or outside of the building or structure

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I have a 500 KVA generator, with no overcurrent protection

More information

NOTICE OF RULE MAKING PROCEEDINGS AND PUBLIC HEARING

NOTICE OF RULE MAKING PROCEEDINGS AND PUBLIC HEARING 1 1 1 1 1 NOTICE OF RULE MAKING PROCEEDINGS AND PUBLIC HEARING NORTH CAROLINA BUILDING CODE COUNCIL Notice of Rule-making Proceedings is hereby given by NC Building Code Council in accordance with G.S.

More information

Wisconsin Contractors Institute Continuing Education

Wisconsin Contractors Institute Continuing Education IMPORTANT NOTE: You should have received an email from us with a link and password to take your final exam online. Please check your email for this link. Be sure to check your spam folder as well. If you

More information

American Electrical Institute

American Electrical Institute American Electrical Institute Oregon Electricians Continuing Education Grounding & Bonding (Article 250) 4 Hours American Electrical Institute PO Box 31131 Spokane, WA 99223 www.aeitraining.com Article

More information

NEC 2014 Code Changes

NEC 2014 Code Changes NEC 2014 Code Changes Articles 200-215.3 CHANGES FROM 2011 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 200 Use and Identification of Grounded Conductors 200.2 General Grounded Conductors

More information

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit Current will always try to return to its source In order for there to be current, there must be a complete circuit Current will take as many paths or circuits available to it to return to the source The

More information

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5 Applied Grounding and Bonding Paul Dobrowsky Member NEC Panel 5 1 Introduction This presentation is a representative sample from the following Chapters of Applied Grounding and Bonding. Chapter 1, Introduction

More information

Article 250 Grounding & Bonding

Article 250 Grounding & Bonding Article 250 Grounding & Bonding AMERICAN ELECTRICAL INSTITUTE N16 W23217 Stone Ridge Dr. Waukesha, WI 53188 855-780-5046 www.aeitraining.com DISCLAIMER NOTE: This course is APPROVED for continuing education

More information

Electrical Wiring: Commercial, Seventh Canadian Edition

Electrical Wiring: Commercial, Seventh Canadian Edition Electrical Wiring Commercial Canadian 7th Edition Mullin SOLUTIONS MANUAL Full download at: https://testbankreal.com/download/electrical-wiring-commercialcanadian-7th-edition-mullin-solutions-manual/ Unit

More information

1 Exam Prep NFPA 70: National Electric Code 2011 Tabs and Highlights

1 Exam Prep NFPA 70: National Electric Code 2011 Tabs and Highlights 1 Exam Prep NFPA 70: National Electric Code 2011 Tabs and Highlights These 1 Exam Prep Tabs are based on NFPA 70: National Electrical Code, 2011. Each 1 Exam Prep Tabs sheet has five rows of Tabs. Start

More information

Part VIII Electrical GENERAL REQUIREMENTS CHAPTER 33

Part VIII Electrical GENERAL REQUIREMENTS CHAPTER 33 Part VIII Electrical CHAPTER 33 GENERAL REQUIREMENTS < SECTION E3301 GENERAL E3301.1 Scope. The installation of electrical systems, equipment and components indoors and outdoors that are within the scope

More information

CONTINUING EDUC ATION

CONTINUING EDUC ATION 3 CONTINUING EDUC ATION FOR WISCONSIN ELECTRICIANS 2017 NEC Article 250 2 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive Suite 290 Waukesha, WI 53188 262-409-4282 www.wcitraining.com

More information

Jake Leahy s Electrical Code Connection. A look at Grounding and Bonding of Electrical Services Article Florida Building Code 5 th Edition

Jake Leahy s Electrical Code Connection. A look at Grounding and Bonding of Electrical Services Article Florida Building Code 5 th Edition Jake Leahy s Electrical Code Connection A look at Grounding and Bonding of Electrical Services Article 250 2014 Florida Building Code 5 th Edition Wiring Integrity. Completed wiring installations shall

More information

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4 SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: 16.10 Document Number: KUCSH0039 Rev: 4 16.10.1 INTRODUCTION 16.10.1.1 The intent of this standard is to ensure that continuity

More information

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56 1. Two Electrical Technicians are discussing markings that are required for AC wiring. Tech A says that AC conductors must be rated for 600 volts and must have their jackets and individual conductors marked

More information

Journeyman's Practice Exam

Journeyman's Practice Exam Journeyman's Practice Exam [Time limit 4.0 hrs.] (The test is open book. I've started at the front of the Code Book and worked toward the back for instructional purposes. The real test will not be in order

More information

SOLAR PV MICROINVERTER/ACM STANDARD PLAN - COMPREHENSIVE Microinverter and ACM Systems for One- and Two- Family Dwellings

SOLAR PV MICROINVERTER/ACM STANDARD PLAN - COMPREHENSIVE Microinverter and ACM Systems for One- and Two- Family Dwellings SOLAR MICROINVERTER/M STANDARD PLAN - COMPREHENSIVE Microinverter and M Systems for One- and Two- Family Dwellings SCOPE: Use this plan ONLY for systems using utility-interactive Microinverters or Modules

More information

2017 NEC TABLE OF CONTENTS

2017 NEC TABLE OF CONTENTS Article 90 Introduction 90.1 Purpose (A) Practical Safeguarding (B) Adequacy (C) Relation to Other International Standards 90.2 Scope (A Covered (B) Not Covered (C) Special Permission 90.3 Code Arrangement

More information

FTTH ENGINEERING AND INSTALLATION INTRODUCTION

FTTH ENGINEERING AND INSTALLATION INTRODUCTION 1 FTTH ENGINEERING AND INSTALLATION INTRODUCTION GROUNDING FTTH SYSTEMS AT THE HOME. By Dean Mischke, P.E., V.P. Grounding and bonding. Why are we worried about such an old school concept in the modern

More information

SECTION CABLE TRAYS

SECTION CABLE TRAYS SECTION 16139 CABLE TRAYS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION! PREFACE This publication has been prepared as a guide for Architectural and Engineering (A&E) firms in the preparation of documents for the design and construction of new structures and the remodeling

More information

a) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit.

a) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit. ECET4520 Exam II Sample Exam Problems Instructions: This exam is closed book, except for the reference booklet provided by your instructor and one (8.5 x11 ) sheet of handwritten notes that may not contain

More information

CHAPTER 2 Wiring and Protection. Article 200 Use and Identification of Grounded Conductors

CHAPTER 2 Wiring and Protection. Article 200 Use and Identification of Grounded Conductors ARTICLE 200 USE AND IDENTIFICATION OF GROUNDED CONDUCTORS 70 35 CHAPTER 2 Wiring and Protection Article 200 Use and Identification of Grounded Conductors 200-1. Scope. This article provides requirements

More information

Article 225: Outside Branch Circuits And Feeders

Article 225: Outside Branch Circuits And Feeders Part C: Code Book Questions Article 225: Outside Branch Circuits And Feeders 1.! Open (individual) aerial overhead conductors shall be insulated or covered when within! feet of a building.! (a) 10! (c)

More information

2014 NEC Changes Part 1

2014 NEC Changes Part 1 www.garyklinka.com Page 1 of 8 Instructions: Fee $20 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

B. Manufacturers: Square-D, G.E. or Westinghosue.

B. Manufacturers: Square-D, G.E. or Westinghosue. SECTION 16470 - PANELBOARDS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

ELECTRIC GROUNDING AND WIRING REQUIREMENTS BOOTHS-METAL

ELECTRIC GROUNDING AND WIRING REQUIREMENTS BOOTHS-METAL BELL SYSTEM PRACTICES Plant Series SECTION 508-100-100 Issue 3, October 1970 AT&TCo Standard ELECTRIC GROUNDING AND WIRING REQUIREMENTS BOOTHS-METAL I. GENERAL 1.01 This section is reissued to: Revise

More information

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT A. General In a hazardous location grounding of an electrical power system and bonding of enclosures of circuits and electrical equipment in the

More information

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality. PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02

More information

Chapter 1 Electrical Theory and Part C Series Parallel and Code Questions Multiwire Branch Circuits Unit 1 Electrician s Math

Chapter 1 Electrical Theory and Part C Series Parallel and Code Questions Multiwire Branch Circuits Unit 1 Electrician s Math Chapter 1 Electrical Theory and Code Questions 1 Unit 1 Electrician s Math and Basic Electrical Formulas 3 Part A Electrician s Math 3 1 1 Fractions 3 1 2 Kilo 4 1 3 Knowing Your Answer 4 1 4 Multiplier

More information

SECTION BUILDING WIRE AND CABLE

SECTION BUILDING WIRE AND CABLE SECTION 260519 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Building wire and cable. 2. Wiring connectors and connections. B. RELATED SECTIONS 1. Section 26 05 53 Electrical Identification. 2. Section

More information

A. Product Description: Stranded conductor insulated wire.

A. Product Description: Stranded conductor insulated wire. SECTION 16120CPPR CONDUCTORS AND CABLE PART 1 - GENERAL 1.1 SYSTEM DESCRIPTION A. Product Requirements: Provide products as follows: 1. All building wire shall be stranded copper (no aluminum wire). 2.

More information

Continued from Part 1 Rules 1 25.

Continued from Part 1 Rules 1 25. Continued from Part 1 Rules 1 25. 26 225.32 Disconnect Location The disconnecting means for a building or structure must be installed at a readily accessible location, either outside the building or structure

More information

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL PART I: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. a.

More information

Department of Labor and Industry Electrical Licensing

Department of Labor and Industry Electrical Licensing Department of Labor and Industry Electrical Licensing License Examination Guide The information in this guide is provided by the Licensing Unit of the Department of Labor and Industry to ensure that applicants

More information

SECTION WIRE AND CABLES. A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents.

SECTION WIRE AND CABLES. A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents. SECTION 26 05 19 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents. 1.2 CONTRACTOR SUBMITTALS A. The

More information

UNION COUNTY ENGINEER DIVISION OF BUILDING REGULATIONS

UNION COUNTY ENGINEER DIVISION OF BUILDING REGULATIONS UNION COUNTY ENGINEER DIVISION OF BUILDING REGULATIONS Residential Pool Permit Requirements FEES: A nonrefundable permit application fee of $25.25 and a nonrefundable plan review fee of $40.40 will be

More information

Page Electric Utility Service Specifications

Page Electric Utility Service Specifications T Y P I C A L U N D E R G R O U N D S E R V I C E R E Q U I R E M E N T S 200 Amps Maximum - UG-1 Sheet 1 of 3 87 T Y P I C A L U N D E R G R O U N D S E R V I C E R E Q U I R E M E N T S 200 Amps Maximum

More information

Grounding and Bonding of Service Equipment

Grounding and Bonding of Service Equipment Grounding and Bonding of Service Equipment 1. Grounding means: attached to an earth ground. 2. Bonding means: physically connected to insure electrical continuity. NEC 250.4 1. Grounding: Electrical Systems

More information

SECTION PANELBOARDS

SECTION PANELBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section

More information

ELPT 1429 RESIDENTIAL WIRING

ELPT 1429 RESIDENTIAL WIRING SYLLABUS ELPT 1429 RESIDENTIAL WIRING INDUSTRIAL AND COMMERCIAL ELECTRICITY BRAZOSPORT COLLEGE LAKE JACKSON TEXAS PREPARED BY: Larry Grable DATE: September 13, 2005 INSTRUCTOR RECOMMENDED BY: RECOMMENDED

More information

STANDARD COMMENTS 2016 ELECTRICAL PLAN REVIEW CHECK LIST

STANDARD COMMENTS 2016 ELECTRICAL PLAN REVIEW CHECK LIST STANDARD COMMENTS 2016 ELECTRICAL PLAN REVIEW CHECK LIST Item Comments 1. The electrical plan check is approved and ready to have the electrical permit issued, pending the building permit being issued.

More information

Wiring of the Main Distribution Panelboard

Wiring of the Main Distribution Panelboard Job Sheet 4 Wiring of the Main Distribution Panelboard OBJECTIVE To connect the service-entrance conductors. To ground the main distribution panelboard (MDP). To wire a branch circuit supplying a three-phase

More information

ECET Fall 2017 Name: _ Lab Assignment #01

ECET Fall 2017 Name: _ Lab Assignment #01 ECET 4520 - Fall 2017 Name: _ Lab Assignment #01 General Instructions: This assignment is to be completed individually. All answers/work required for each problem should be neatly written in the space

More information

Electrical requirements for plans on all new homes, additions, remodels & Service upgrades

Electrical requirements for plans on all new homes, additions, remodels & Service upgrades CHERRY HILLS VILLAGE COLORADO Electrical requirements for plans on all new homes, additions, remodels & Service upgrades Due to the size and uniqueness of homes built in Cherry Hills Village, a policy

More information

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE PAGE 262400-1 SECTION 262400 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

We have 3 ways to help you prepare

We have 3 ways to help you prepare P a g e 2 Texas Electrical Excel is your source for obtaining your license state exam. Call us if you have questions regarding your applications, exam preparation, exam registration and more. We have reached

More information

SECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION

SECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION SECTION 16715 COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION PART 1 - GENERAL 1.01 SECTION DESCRIPTION AND BASIC REQUIREMENTS A. The Electrical Power Distribution System provides power distribution from

More information

Article 700: Emergency Systems. 2.! Audible and visual signal devices shall be provided, where practicable to indicate.

Article 700: Emergency Systems. 2.! Audible and visual signal devices shall be provided, where practicable to indicate. Part N: Code Book Questions Article 700: Emergency Systems 1.! For emergency systems, the authority having jurisdiction shall conduct or witness a test on the! complete system upon installation and periodically

More information

SECTION WIREWAYS FOR RADIOLOGY EQUIPMENT

SECTION WIREWAYS FOR RADIOLOGY EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 36 WIREWAYS FOR RADIOLOGY EQUIPMENT SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable

More information

FINAL - IT 30 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (2 marks) EA 2

FINAL - IT 30 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (2 marks) EA 2 FINAL - IT 30 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination

More information

SECTION DISTRIBUTION SWITCHBOARDS

SECTION DISTRIBUTION SWITCHBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 13 DISTRIBUTION SWITCHBOARDS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

Grounding and Bonding

Grounding and Bonding Grounding and Bonding 2017 Communications Academy Joe Blaschka Jr., PE Grounding/Bonding What is it? Why do we do it? What does the National Electrical Code say? What about fixed locations? What about

More information

SECTION DISTRIBUTION SWITCHBOARDS

SECTION DISTRIBUTION SWITCHBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 11 SPEC WRITER NOTES: Use this section only for NCA projects. Delete between // -- // if not applicable to project. Also delete any other item or paragraph

More information

PROVINCE.OF BRITISH COLUMBIA. ORDER OF THE LIEUTENANfelOVERNOR IN COUNCIL

PROVINCE.OF BRITISH COLUMBIA. ORDER OF THE LIEUTENANfelOVERNOR IN COUNCIL PROVINCE.OF BRITISH COLUMBIA ORDER OF THE LIEUTENANfelOVERNOR IN COUNCIL Order in Council No. 0640 Approved and Oidered a -1.1995 cieuisvunigott3mor Executive Council Chambers, Victoria On the recommendation

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: Members of the NEC-Code Making Panel 16 FROM:

More information

Licensed Electricians Practical Assessment (LEP)

Licensed Electricians Practical Assessment (LEP) Licensed Electricians Practical Assessment (LEP) Surname: Date: Given Names: Time: Assessment Time (includes 10 minutes reading time): At the end of this time you will be asked to stop. 4 hours Have you

More information

INTRODUCTION...xiii Author s Comments...xiii Exam Preparation...xiii Difficult Concepts...xiv Textbook Errors and Corrections...xv Internet...

INTRODUCTION...xiii Author s Comments...xiii Exam Preparation...xiii Difficult Concepts...xiv Textbook Errors and Corrections...xv Internet... INTRODUCTION...xiii Author s Comments...xiii Exam Preparation...xiii Difficult Concepts...xiv Textbook Errors and Corrections...xv Internet...xv UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1

More information

SECTION TRANSFORMERS

SECTION TRANSFORMERS SECTION 16460 - TRANSFORMERS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Section

More information

UNITY/I TM. Installation Manual. UT3K, UT4K, UT5K and UT8K. Single-Phase Uninterruptible Power Systems

UNITY/I TM. Installation Manual. UT3K, UT4K, UT5K and UT8K. Single-Phase Uninterruptible Power Systems UNITY/I TM UT3K, UT4K, UT5K and UT8K Single-Phase Uninterruptible Power Systems Installation Manual MLS-0351C-OL Copyright 1994-1997 Best Power. All rights reserved. å IMPORTANT SAFETY INSTRUCTIONS! SAVE

More information

Wiring Methods, Components, and Equipment for General Use -- OSHA Standard

Wiring Methods, Components, and Equipment for General Use -- OSHA Standard ABE285 Wiring Methods, Components, and Equipment for General Use -- OSHA Standard 1910.305 1 Carol J. Lehtola, Charles M. Brown, and William J. Becker 2 The Impact of Safety on Florida Agriculture Florida

More information

Basic Information Required for Photovoltaic Plan Check Submittal *Informational Purposes Only*

Basic Information Required for Photovoltaic Plan Check Submittal *Informational Purposes Only* 1444 West Garvey Avenue West Covina, CA 91793 Phone: 626-939-8425 Basic Information Required for Photovoltaic Plan Check Submittal *Informational Purposes Only* ADMINISTRATIVE 1. The following clearances

More information

Licensed Electricians Practical Assessment (LEP)

Licensed Electricians Practical Assessment (LEP) Licensed Electricians Practical Assessment (LEP) Surname: Given Names: Date: Time: Location: Assessment Time (includes reading and preparation time): At the end of this time you will be asked to stop.

More information

Code Check Electrical is a field guide to common code issues in residential

Code Check Electrical is a field guide to common code issues in residential INTRODUCTION u CODES u ABBREVIATIONS Code 3Check Electrical 5th Edition By Redwood Kardon & DOUGLAS HANSEN Illustrations & Layout: Paddy Morrissey 2008 by The Taunton Press, Inc. ISBN 978-1-60085-012-7

More information

Chapter 25. Lighting Plans

Chapter 25. Lighting Plans Chapter 25 Lighting Plans The following are changes, additions or deletions to the January 2014, Topic #625-000-008, Plans Preparation Manual (PPM), for use on Turnpike projects only. 25.1 General Replace

More information

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com AN EXAMPLE OF A STANDARD ARC

More information

SECTION EQUIPMENT WIRING

SECTION EQUIPMENT WIRING PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 26 27 17 EQUIPMENT WIRING A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General Provisions,

More information

Continuing Education, For UDC Electrical Inspectors, Commercial Electrical Inspectors, Master Electricians and Journeyman Electricians.

Continuing Education, For UDC Electrical Inspectors, Commercial Electrical Inspectors, Master Electricians and Journeyman Electricians. Continuing Education, For UDC Electrical Inspectors, Commercial Electrical Inspectors, Master Electricians and Journeyman Electricians. The following test is for Continuing Education Credits for the abovementioned

More information

Bulletin Filming in Minnesota

Bulletin Filming in Minnesota 443 Lafayette Road N. St. Paul, Minnesota 55155 www.doli.state.mn.us www.electricity.state.mn.us MINNESOTA DEPARTMENT OF LABOR & INDUSTRY (651) 284-5064 1-800-DIAL-DLI Fax: (651) 284-5749 TTY: (651) 297-4198

More information

12.6 Delta Phase versus Line Current

12.6 Delta Phase versus Line Current Unit 12 Delta/Delta and Delta/Wye Transformers Electrical NEC Exam Preparation 12.6 Delta Phase versus Line Current Since each line conductor from a delta transformer is actually connected to two transformer

More information

DESIGN CHECKLIST INTRODUCTION

DESIGN CHECKLIST INTRODUCTION INTRODUCTION 1 The checklist is intended to serve as a convenient guide in design development as well as the final checking of plans and specifications for construction projects. Its main usefulness for

More information

Electrical Inspectors

Electrical Inspectors International Association of Electrical Inspectors Western Section 114th Annual Meeting September 16-19, 2018 Appleton, Wisconsin The answers to these questions are the opinion of the person that answered

More information

Installation Manual. Jandy Housing for Wet Niche Fixtures WARNING. For Vinyl and Fiberglass Pool Installations Model No.

Installation Manual. Jandy Housing for Wet Niche Fixtures WARNING. For Vinyl and Fiberglass Pool Installations Model No. H0284300 Rev C Installation Data Installation Manual Jandy Housing for Wet Niche Fixtures For Vinyl and Fiberglass Pool Installations Model No. PLNICVFLRG WARNING FOR YOUR SAFETY - This product must be

More information

Module 2 Unit 6, 7, 8

Module 2 Unit 6, 7, 8 Module 2 Unit 6, 7, 8 1. What is the definition of an ideal conductor? Material that will carry the greatest current with the lowest temperature rise 2. How much does copper weigh compared to aluminum?

More information

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011 NATIONAL RULES FOR ELECTRICAL INSTALLATIONS Fourth Edition ET 101:2008 Extracts from Amendment No.1:2011 22 June 2011 Page vi: Insert after 1 st Paragraph: Section 710: Medical Locations was prepared by

More information

Box Fill. We have learned how to fill or NOT overfill a conduit. We must also determine how to fill boxes and conduit bodies.

Box Fill. We have learned how to fill or NOT overfill a conduit. We must also determine how to fill boxes and conduit bodies. Box Fill We have learned how to fill or NOT overfill a conduit. We must also determine how to fill boxes and conduit bodies. Box Fill This falls into four categories: 1. Small box fill (NEC 314.16) 2.

More information

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER GROUNDED ELECTRICAL POWER DISTRIBUTION Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER .0 Conductors for Electrical Power Distribution For single-phase transmission of AC power or

More information

SPECIAL SPECIFICATION LIGHTNING PROTECTION SYSTEM

SPECIAL SPECIFICATION LIGHTNING PROTECTION SYSTEM 2004 Specifications CSJ 3622-01-001, ETC. SPECIAL SPECIFICATION 8398 LIGHTNING PROTECTION SYSTEM 1. Description. This Special Specification governs the design and installation of Lightning Protection System

More information

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS

More information

EPG. by Chris C. Kleronomos

EPG. by Chris C. Kleronomos April 1994 EFFECTIVE EQUIPMENT GROUNDING ECOS Electronics Corporation by Chris C. Kleronomos The quality of the electrical wiring and grounding in a facility containing sensitive electronic equipment is

More information

Quality Control Checklist - Design Drawings

Quality Control Checklist - Design Drawings Quality Control Checklist - Design Drawings Date Company Name Address Telephone Fax Email Job Number 1) Drawing Set a) Drawing one is site/location/incoming power i) Should contain location map if not

More information

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web: Phone: (818) 734-5300 Fax: (818) 734-5320 Web: www.capstoneturbine.com Technical Reference Capstone MicroTurbine Electrical Installation 410009 Rev F (October 2013) Page 1 of 31 Capstone Turbine Corporation

More information

A. Product Data: For each electrical identification product indicated.

A. Product Data: For each electrical identification product indicated. SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

POWER SERVICE DETAILS

POWER SERVICE DETAILS POWER SOURCE # POLE MOUNTED SERVICE TRANSFORMER BY POWER HANDHOLE 0/0V, -PHASE, SERVICE CONDUCTORS; -# AWG SERVICE CONDUCTOR AND -# AWG GROUNDED SERVICE CONDUCTOR (NEUTRAL) SERVICE XFMR SECONDARY. A 0V

More information

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS) WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS) 1 PART 1: GENERAL This section describes materials and installation requirements for low voltage

More information

Grounding Systems and Their Implementation By: Charles Atkinson Canadian Broadcasting Corporation Toronto, Canada

Grounding Systems and Their Implementation By: Charles Atkinson Canadian Broadcasting Corporation Toronto, Canada Grounding Systems and Their Implementation By: Charles Atkinson Canadian Broadcasting Corporation Toronto, Canada and Philip Giddings Engineering Harmonics Toronto, Canada The original document and figures

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

INTELLIMETER REGISTER

INTELLIMETER REGISTER INTELLIMETER REGISTER MODEL RG2 INSTALLATION AND CONNECTIONS INSTALLATION MANUAL WARNING: Any work on or near energized metering equipment can present a danger of electrical shock. All work on these products

More information

CATALOG OF PRODUCTS. Your Best Supplier of Electrical Cables

CATALOG OF PRODUCTS. Your Best Supplier of Electrical Cables CATALOG OF PRODUCTS Isolated Copper Wire THHN/MTW/THWN-2 600V, single conductor having flame-retardant and heat-resistant thermoplastic insulation with a jacket of extruded nylon or equivalent material.

More information

SINGLE-PHASE VSV SWITCH

SINGLE-PHASE VSV SWITCH May 2006 Supercedes: March 2006 SINGLE-PHASE VSV SWITCH INSTALLATION AND OPERATING MANUAL Table of Content: Page I. General...2 II. Specifications...2 III. Installation...2 IV. Maintenance...4 V. VSV Power

More information

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS 1.0 SCOPE The following specification describes the features, design, and application of the Series 7200A

More information

Thank you for your interest in the Electrical Technician program. Following is the application process:

Thank you for your interest in the Electrical Technician program. Following is the application process: Thank you for your interest in the Electrical Technician program. Following is the application process: Information Session: Attendance at an Information Session is a prerequisite to acceptance into EHOVE

More information

TEACHER ASSESSMENT BLUEPRINT ELECTRICAL CONSTRUCTION TECHNOLOGY. Test Code: 5171 Version: 01

TEACHER ASSESSMENT BLUEPRINT ELECTRICAL CONSTRUCTION TECHNOLOGY. Test Code: 5171 Version: 01 TEACHER ASSESSMENT BLUEPRINT ELECTRICAL CONSTRUCTION TECHNOLOGY Test Code: 5171 Version: 01 Specific Competencies and Skills Tested in this Assessment: OSHA Regulations and Electrical Safety Practices

More information

Digital Lighting Systems, Inc. PD804-DMX. Eight Channel DMX Pack. (includes information for PD804-DMX-S) USER'S MANUAL. PD804-DMX-UM Rev.

Digital Lighting Systems, Inc. PD804-DMX. Eight Channel DMX Pack. (includes information for PD804-DMX-S) USER'S MANUAL. PD804-DMX-UM Rev. , Inc. Eight Channel DMX Pack (includes information for -S) S S S S 4 8 USER'S MANUAL -UM User's Manual - Page GENERAL DESCRIPTION The is an 8-channel DMX- compatible dimmer pack. It contains three printed

More information

SureTest Model ST-1THD & ST-1THDC Instructions

SureTest Model ST-1THD & ST-1THDC Instructions #61-156 #61-157 #61-158 SureTest Model ST-1THD & ST-1THDC Instructions Introduction The SureTest family of Circuit/distortion analyzers identify problems common to electrical circuits and harmonic distortion

More information

Datawave Magnetic Synthesizer

Datawave Magnetic Synthesizer POWER PROTECTION Datawave Magnetic Synthesizer 100 kva to 200 kva; 50 and 60 Hz Installation, Operation, & Maintenance Manual TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS............................................1

More information

ELECTRIC RANGE INSTALLATION MANUAL. Please read these instructions thoroughly before installing and operating the range.

ELECTRIC RANGE INSTALLATION MANUAL. Please read these instructions thoroughly before installing and operating the range. ENGLISH ESPAÑOL INSTALLATION MANUAL ELECTRIC RANGE Please read these instructions thoroughly before installing and operating the range. MODELS LRE30955S LRE30755S LRE30757S LSE3094S LSE3092S LSRE307ST

More information

Regal Series Recessed Flatwalls

Regal Series Recessed Flatwalls Regal Series Recessed Flatwalls General Specifications The Amico Regal Series Recessed Flatwall shall be manufactured by Amico Corporation, in accordance with job specific shop drawings and documents.

More information

Single-Family Dwelling Submittal Requirements

Single-Family Dwelling Submittal Requirements Single-Family Dwelling Submittal Requirements The purpose of this guideline is to assist our customers in preparing for plan submittal. The items listed must be included before your plans can be accepted

More information