1 Page Introduction Current Repeaters/Drivers (Single-channel) KFD0-CS-Ex1.50P (Transmitter, positioner and indicator) KFD0-CS-Ex1.51P (Positioner and fire detector) KFD0-CS-Ex1.52 (Current source) KFD0-CS-Ex1.53 (Positioner) KFD0-CS-Ex1.54 (SMART fire detector) Current Repeaters/Drivers (Dual-channel) KFD0-CS-Ex2.50P (Transmitter, positioner and indicator) KFD0-CS-Ex2.51P (Positioner and fire detector) KFD0-CS-Ex2.52 (Current source) KFD0-CS-Ex2.53 (Positioner) KFD0-CS-Ex2.54 (SMART fire detector) Converters KFD0-TR-Ex1 (Pt100) KFD0-TT-Ex1 (Thermocouple) KFD0-RC-Ex1 (Resistance) KFD0-CC-Ex1 (Current/voltage) Smart Repeaters KFD0-SCS-Ex
2 Introduction Pepperl+Fuchs loop-powered isolators consist of current repeaters/drivers and converters. Repeaters and drivers transfer unaltered signals from safe areas to hazardous areas or vice versa. Converters change signals from one unit to an appropriate measuring signal such as the 0/ or 0/1-5 V. P+F offers converters for RTDs, thermocouples, current and resistance. Since isolators in this section are loop-powered, use the specifications listed in the technical data to verify that proper voltage is available to the field devices. 95
3 Current Repeater/Driver Input/Output (not intrinsically safe) Terminals 11+, VDC Nominal current Output/Input (intrinsically safe) Terminals 1+, 2- Minimum output voltage 10 V < V IN < 26.4 V 0.9 x V IN - (0.4 x current in ma) V IN > 26.4 V 23 V - (0.4 x current in ma) Maximum short circuit current 65 ma (V IN > 26.1 V) Maximum transfer current 20 ma Loop-powered Isolators KFD0-CS-Ex1.50P Reverse polarity protection KFD0-CS-Ex1.50P is a loop-powered isolator that transfers DC signals from fire and smoke alarms, transmitters and temperature sensors in hazardous areas. It can also be used to control I/P converters, power solenoids, LEDs and audible alarms. Dual channels enable interfacing of two independent circuits. Since this isolator is loop-powered, use the technical data on this page to verify that proper voltage is available to the field devices. Calibrated accuracy ±20 µa Temperature drift <2 µa / ºC (0ºC to +50ºC) <5 µa / ºC (-20ºC to +60ºC) 5 ms at (V IN < 26 V) Entity Parameters Terminals 1+, 2-: 28.5 V 96 ma ) 0.17 µf 0.51 µf 1.36 µf ) 4.20 mh mh mh Dimensions (mm) 107 x 20 x VDC 96
4 Loop-powered Isolators 2002 IS Catalog Input/Output (not intrinsically safe) Terminals 11+, VDC Nominal current 0-40 ma Current Repeater/Driver Output / Input (intrinsically safe) Terminals 1+, 2- Minimum output voltage 4 V < V IN < 24 V V IN - (0.4 x current in ma) - 1 V IN > 24 V 23 V - (0.4 x current in ma) Maximum short circuit current 65 ma (V IN > 24 V) Maximum transfer current 40 ma Calibrated accuracy ± 200 µa Temperature drift < 2 µa / ºC (0ºC to +50ºC) < 5 µa / ºC (-20ºC to +60ºC) 20 ms at and 250Ω load Entity Parameters Terminals 1+, V 96 ma ) 0.17 µf 0.51 µf 1.36 µf ) 4.20 mh mh 33.4 mh Dimensions (mm) 115 x 20 x 107 KFD0-CS-Ex1.51P Reverse polarity protection KFD0-CS-Ex1.51P is a loop-powered isolator that transfers DC signals from fire alarms, smoke alarm transmitters and temperature sensors in hazardous areas. It can also be used to control I/P converters, power solenoids, LEDs and audible alarms. Reverse polarity protection prevents the isolator from damage caused by faulty wiring. Since this isolator is looppowered, use the technical data on this page to verify that proper voltage is available to the field devices. 97
5 Current Repeater Input (intrinsically safe) Terminals 1+, VDC Current range Output / (not intrinsically safe) Terminals 11+, 12- Voltage range 0-24 VDC Current range Output voltage (4 V<V IN <24 V) 0.9 x V IN - (0.11 x current in ma) Loop-powered Isolators KFD0-CS-Ex % accuracy Transfer range KFD0-CS-Ex1.52 is a single-channel, intrinsic safety isolator that repeats a signal from a current source inside a hazardous area. (It does not provide power for transmitters inside the hazardous area.) The 28 V, 0 ma entity parameters make it easy to design intrinsically safe systems. Since this isolator is loop-powered, use the technical data on this page to verify that proper voltage is available to the field devices. Calibrated accuracy ±20 µa Temperature drift per ºC ±1 µa / K (0ºC to +50ºC) ±2 µa / K (0ºC to +60ºC) ±5 µa / K (-20ºC to +60ºC) 10 ms at and 250 Ω load Entity Parameters Terminals 1+, V 0 ma ) 0.14 µf 0.43 µf 1.14 µf ) 1000 mh 1000 mh 1000 mh Dimensions (mm) 115 x 20 x 107 I 98
6 Loop-powered Isolators 2002 IS Catalog Input (not intrinsically safe) Terminals 1+, 2- Output voltage V IN - (0.2 x current in ma) Short circuit current 95 ma Maximum transfer current 40 ma Current Driver Output (intrinsically safe) Terminals 11+, VDC Current range 0-40 ma Calibrated accuracy ±200 µa Temperature drift per ºC ±2 µa / ºC (0ºC to +60ºC) ±5 µa / ºC (-20ºC to +60ºC) 20 ms at and 250 Ω load Entity Parameters Terminals 1+, V 97.2 ma ) 2.40 µf 7.20 µf µf ) 4.0 mh 12.0 mh 32.0 mh Dimensions (mm) 115 x 20 x 107 KFD0-CS-Ex ma transfer range 1% accuracy KFD0-CS-Ex1.53 is a single-channel isolator that controls I/P converters. It is ideal for applications where the control system in the safe area handles a small load. Since this isolator is loop-powered, use the technical data on this page to verify that proper voltage is available to the field devices. 99
7 Smart Current Repeater Input (not intrinsically safe) Terminals 11+, 12- Voltage range 4-26 V, 0-6 V ss AC Current range 1-20 ma Output voltage (4V V IN 26V) V IN - (0.38 x current in ma) Output (intrinsically safe) Terminals 1+, VDC Nominal current 1-20 ma Short circuit current 65 ma Calibrated accuracy Temperature drift -1.6 ma to 0 ma ±20 µa / ºC (0ºC to +60ºC) 50 µs (load current 1 ma) Loop-powered Isolators KFD0-CS-Ex ma transfer range 1% accuracy KFD0-CS-Ex1.54 is a single-channel isolator that provides control and signal transfer for intelligent fire and smoke alarm transmitters inside hazardous areas. This isolator can also superimpose an AC signal (up to 6 V) on the DC signal to enable digital communication to the hazardous area. Since this isolator is loop-powered, use the technical data on this page to verify that proper voltage is available to the field devices. Entity Parameters Terminals 1+, V 95 ma ) 0.14 µf 0.41 µf 1.10 µf ) 4.09 mh mh mh Dimensions (mm) 115 x 20 x mA 100
8 Loop-powered Isolators 2002 IS Catalog Input /Output (not intrinsically safe) Terminals 11+, 12-; 8-, 9+, VDC Nominal current Current Repeater/Driver Output / Input (intrinsically safe) Terminals 1+, 2-: 4+, 5- Minimum output voltage 10 V < V IN < 26.1 V 0.9 x V IN - (0.4 x current in ma) V IN > 26.1 V 23 V - (0.4 x current in ma) Maximum short circuit current 65 ma (V IN > 26.1 V) Maximum transfer current 40 ma Calibrated accuracy ±20 µa Temperature drift <2 µa / ºC (0ºC to +50ºC) <5 µa / ºC (-20ºC to +60ºC) 5 ms at (V E < 26 V) Entity Parameters Terminals 1+, 2-; 4+, V 96 ma ) 0.17 µf 0.51 µf 1.36 µf ) 4.20 mh mh mh Dimensions (mm) 115 x 20 x 107 KFD0-CS-Ex2.50P Dual-channel Reverse polarity protection KFD0-CS-Ex2.50P is a loop-powered isolator that transfers DC signals from fire alarms, smoke alarm transmitters and temperature sensors in hazardous areas. It can also be used to control I/P converters, power solenoids, LEDs and audible alarms. Dual channels enable interfacing of two independent circuits. Reverse polarity protection prevents the isolator from damage caused by faulty wiring. Since this isolator is loop-powered, use the technical data on this page to verify that proper voltage is available to the field devices VCD 10-35VCD 101
9 Current Repeater/Driver Input /Output (not intrinsically safe) Terminals 11+, 12-; 8-, 9+, VDC Nominal current 0-40 ma Output / Input (intrinsically safe) Terminals 1+, 2-; 4+, 5- Minimum output voltage 4 V < V IN < 24 V V IN - (0.4 x current in ma) - 1 V IN > 24 V 23 V - (0.4 x current in ma) Maximum short circuit current 65 ma (V E >24 V) Maximum transfer current 40 ma Loop-powered Isolators KFD0-CS-Ex2.51P Dual-channel Reverse polarity protection KFD0-CS-Ex2.51P is a loop-powered isolator that transfers DC signals from fire alarms, smoke alarm transmitters and temperature sensors in hazardous areas. It can also be used to control I/P converters, power solenoids, LEDs and audible alarms. Reverse polarity protection prevents the isolator from damage caused by faulty wiring. Since this isolator is looppowered, use the technical data on this page to verify that proper voltage is available to the field devices. Calibrated accuracy ±200 µa Temperature drift < 2 µa / ºC (0ºC to +50ºC) < 5 µa / ºC (-20ºC to +60ºC) 5 ms at and 250 Ω load Entity Parameters Terminals 1+, 2-; 4+, V 96 ma ) 0.13 µf 0.41 µf 1.09 µf ) 3.93 mh mh mh Dimensions (mm) 115 x 20 x 107 KFD0-CS-Ex2.51P 4-35VCD 4-35VCD 102
10 Loop-powered Isolators 2002 IS Catalog Input (intrinsically safe) Terminals 1+, 2-; 4+, VDC Current range Current Repeater Output / (not intrinsically safe) Terminals 11+, 12-; 9+, 10- Voltage range 0-24 VDC Current range Output voltage (4 V<V IN <24 V) 0.9 x V IN - (0.11 x current in ma) Calibrated accuracy ±20 µa Temperature drift ±1 µa / ºC (0ºC to +50ºC) ±2 µa / ºC (0ºC to +60ºC) ±5 µa / ºC (-20ºC to +60ºC) 10 ms at and 250 Ω load Entity Parameters Terminals 1+, 2-; 4+, V 0 ma ) 0.14 µf 0.43 µf 1.14 µf ) 1000 mh 1000 mh 1000 mh Dimensions (mm) 115 x 20 x 107 KFD0-CS-Ex2.52 Dual-channel 0.1% accuracy KFD0-CS-Ex2.52 is a dual-channel isolator that repeats a signal from a current source inside a hazardous area. (It does not provide power for transmitters inside the hazardous area.) The 28 V, 0 ma entity parameters make it easy to design intrinsically safe systems. Since this isolator is loop-powered, use the technical data on this page to verify that proper voltage is available to the field devices. I I 103
11 Current Driver Input (not intrinsically safe) Terminals 11+, 12-; 9+, 8-, VDC Current range 0-40 ma Output (intrinsically safe) Output voltage V IN - (0.2 x current in ma) Short circuit current 95 ma Maximum transfer current 40 ma Calibrated accuracy ±200 µa Temperature drift ±2 µa / ºC (0ºC to +60ºC) ±5 µa / ºC (-20ºC to +60ºC) 20 ms at and 250 Ω load Loop-powered Isolators KFD0-CS-Ex2.53 Dual-channel 0-40 ma transfer range KFD0-CS-Ex2.53 is a dual-channel isolator that controls I/P converters. This isolator is ideal for applications where the control system in the safe area handles a small load. Since this isolator is loop-powered, use the technical data on this page to verify that proper voltage is available to the field devices. Entity Parameters Terminals 1+, 2-; 4+, V 97.2 ma ) 2.40 µf 7.20 µf µf ) 4.0 mh 12.0 mh 32.0 mh Dimensions (mm) 115 x 20 x
12 Loop-powered Isolators 2002 IS Catalog Input (intrinsically safe) Terminals 11+, 12-; 9+, 8-, 10- Voltage range 4-26 V. 0-6 V SS AC Current range 1-20 ma Smart Current Repeater Output (not intrinsically safe) Terminals 1+, 2-; 4+, VDC Nominal current 1-20 ma Short circuit current 65 ma Min. output voltage (4V V IN 26V) V IN - (0.38 x current in ma) Calibrated accuracy Temperature drift -1.6 ma to 0 ma ± 20 µa / ºC (0ºC to +60ºC) 50 µs (load current 1 ma) Entity Parameters Terminals 1+, 2-; 4+, V 95 ma ) 0.14 µf 0.41 µf 1.10 µf ) 4.09 mh mh mh Dimensions (mm) 115 x 20 x 107 KFD0-CS-Ex2.54 Dual-channel 1-20 ma transfer range The KFD0-CS-Ex2.54 is a dual-channel isolator that provides control and signal transfer for intelligent fire and smoke alarm transmitters inside hazardous areas. This isolator can also superimpose an AC signal (up to 6 V) on the DC signal to enable digital communication to the hazardous area. Since this isolator is loop-powered, use the technical data on this page to verify that proper voltage is available to the field devices. KFD0-CS-Ex
13 RTD Converter Power Supply Loop powered VDC Input (intrinsically safe) Terminals 1+, 2-, 3+ Lead resistance 100 Ω / lead Test current 1 ma Output (not intrinsically safe) Terminals 8-, 9+ Current output Fault signal (lead breakage) 22 ma Load (V s - 12 V) / 0.02 A Loop-powered Isolators KFD0-TR-Ex1 Adjustable span for easy calibration Burnout monitoring Suitable for Pt100, 2- and 3- wire connections The KFD0-TR-Ex1 is a single-channel isolator that converts the resistance from a 3-wire RTD in the hazardous area to a signal in the safe area. This converter also features conveniently located DIP switches and potentiometers to make field calibration easy. 1 0 Dip switch functions on side of unit Lead monitoring Thermocouple type Switch Position Function S1.1 1 Pt100 with linearization S1.2 0 (-30 C to 375 C) S1.1 0 Pt100 with linearization S1.2 0 (-200 C to 800 C) Voltage influence 6.5 ppm /V Calibrated accuracy 0.1% Voltage influence % / V Temperature drift 0.015% of span / ºC or ±10 mω / ºC Measuring range +25ºC to +800ºC (span w/linearization) +25ºC to +430ºC (span w/o linearization) -200ºC to +466ºC (zero point linearization) -86ºC to +405ºC (zero point w/linearization) Entity Parameters Terminals 1, 2, 3 CSA control drawing no V 33 ma ) 0.59 µf 1.77 µf 4.72 µf ) 30 mh 113 mh 268 mh Housing Type C (see page 387) Dimensions (mm) 115 x 20 x g (5.3 oz.) KFDO-TR-EX1 106
14 Loop-powered Isolators 2002 IS Catalog Power Supply Loop powered VDC Thermocouple Converter Inputs (intrinsically safe) Input current Terminals 1+, 2-, 3+ cold junction measurement reference 0ºC 15 na (lead monitoring on) 1 na (lead monitoring off) Output (not intrinsically safe) Terminals 9+, 8- Current output (35 ma max.) Fault signal (lead breakage) Downscale 3 ma, upscale 22 ma Load (V s - 12 V) / 0.02 A Measuring range span 4-10 mv, zero point 12 mv to 60 mv Calibrated accuracy 0.1% Temperature drift 0.015% of span / ºC or 1.5 µv / ºC Voltage influence 6.5 ppm / V or % / V Entity Parameters Terminals 1, 2, 3 CSA control drawing no V 0.8 ma ) 0.59 µf 1.77 µf 4.72 µf ) 1000 mh 1000 mh 1000 mh Housing Type C (see page 387) Dimensions (mm) 115 x 20 x g (5.3 oz.) KFD0-TT-Ex1 Adjustable span and zero point Lead breakage monitoring For thermocouple types E, J, K, N, R, S and T The KFD0-TT-Ex1 is a single-channel isolator that converts the voltage from a thermocouple (or any other device with a millivolt signal) inside the hazardous area to a signal in the safe area. Seven types of thermocouples can be connected to this isolator. KFD0-TT-Ex1 also features conveniently located DIP switches and potentiometers to make field calibration easy. mv 1 0 Lead monitoring Dip switch functions on side of unit Thermocouple type Switch Position Function S1.1 1/0 LB UP-upscaled* S1.2 0/1 LB DOWN-downscaled* S1.3 1 Thermocouple Type E S1.4 1 Thermocouple Type J S2.1 1 Thermocouple Type K, T S2.2 1 Thermocouple Type N S2.3 1 Thermocouple Type R, S 1 0 Lead monitoring * other combinations not allowed/defined Thermocouple type
15 Resistance Converter Power Supply Loop powered VDC Input (intrinsically safe) Terminals 1+, 2-, 3+ Lead resistance 100 Ω/lead Test current 1 ma Output (not intrinsically safe) Terminals 8-, 9+ Current output Fault signal (lead breakage) 22 ma Load (V S - 12 V) / 0.02 A Loop-powered Isolators KFD0-RC-Ex1 Lead breakage monitoring Adjustable span for easy calibration Suitable for Pt100, 2- and 3- wire connections This single-channel isolator converts a ,000 Ω resistance in the hazardous area to a signal in the safe area. Additional features include lead resistance compensation and DIP switches and potentiometers on the isolator for easy field calibration. Adjustment instructions Example: Input KOhm Output signal 1. Enter resistance 0 Ohm at the input, (Short circuit the input) 2. Span coarse adjustment (Switch SPAN Position 2) 3. Adjust output: zero point fine adjustment (20-4 ma) kohm enter at the input 5. Span fine adjustments (20 ma), If necessary repeat steps 3, -5. Switch SPAN Measurement rang end value (Ohm) A B C D E F Rotary switch function on the devices F 9 E A D C B Span coarse adjustment Final sensing range 500 Ω to 11 kω Zero point 0-10% of final value Calibrated accuracy 0.1% of final value Linearity 0.04% of final value Temperature drift span, zero point 4.8 µa / ºC 250 ms Certificate of Conformity Terminals 1+, 2-, 3+ Certification no. TÜV 98 ATEX 1381 Voltage U o 16.2V Current I o 13.1 ma Explosion group [EEx ia/ib] II B II C ) 2.63 µf µf ) 600 mh 160 mh Housing Type C (see page 387) Dimensions (mm) 115 x 20 x g (5.3 oz.) 108
16 Loop-powered Isolators 2002 IS Catalog Power Supply Loop powered VDC Current/Voltage Converter Input (intrinsically safe) Terminals 1+, 2- Current range/load 0-20 ma /50 Ω max. Voltage range/load 0-10 V /100 kω min. Output (not intrinsically safe) Terminals8-, 9+ Current output Fault signal (lead breakage) 3 ma Load (V S - 12 V) / 0.02 A Voltage surge 6.5 ppm / V Calibrated accuracy 0.1% Linearity 0.04% of final value Temperature drift 0.05% of span / ºC Voltage influence 0.060% of span/ ºC (zero point) 250 ms Entity Parameters Terminals 1, 2 CSA control drawing no V 0.5 ma ) 3.5 µf 10.5 µf 28 µf ) 1000 mh 1000 mh 1000 mh Housing Type C (see page 387) Dimensions (mm) 115 x 20 x 118 KFD0-CC-Ex1 Current and voltage inputs Adjustable span for easy calibration This single-channel isolator converts a 2-wire voltage or current in the hazardous area to a signal in the safe area. DIP switches and potentiometers on the isolator make field calibration easy. I 1 0 Lead monitoring S1 Dip switch functions on side of unit Thermocouple type Measurement Switch S1 (Range) Switch S1 (Zero Point) Range S1.1 S1.2 S1.3 S1.4 S2.1 S2.2 S2.3 S2.4 0 to 20mA to 20mA to 5V to 5V to 10V to 10V Lead monitoring S2 0 Thermocouple type 109
17 SMART Repeater Inputs (intrinsically safe) Terminals 1+, 2-, 3+ Current (linear transmission 1-22 ma) Output (not intrinsically safe) Terminals 9+, 8- Maximum voltage 250 V Voltage range 0-30 VDC Load (V S - 12 V) / 0.02 A Deviation after calibration after calibration: 80µA linearity, load and voltage dependence at 20ºC Deviation temperature < 0.5 µa / ºC 20 µs at 0Ω, 600 µs with 800Ω load Loop-powered Isolators KFD0-SCS-Ex1.55 Lead breakage monitoring Single channel HART compatible The KFD0-SCS-Ex1.55 universal module does not require auxiliary power for the isolation of a signal. It is loop powered and has a noticeably lower power loss compared to active isolator modules. The module isolates signals for transmitters and positioners and is bidirectionally HART compatible. The HART transmitters and HART positioners can be configured in the safe area as well as in the hazardous area. The low 5 V voltage drop also allows for transmitter applications with unstable power sources in the range of VDC. Please note that the voltage drop across the resistor in the active measurement circuit must be included when calculating the available field voltage (Terminals 1+ and 2) Lead breakage monitoring is possible by means of the reaction of the field current signal to the safe area, which means the control system has to monitor for an underscale or overscale condition. The module can also be used for controlling solenoid valves and discrete outputs, such as LEDs based on the internal voltage limits (safe area). Terminals 8- and 9+ in this case are driven with a 24 V signal. Certificate of Conformity Terminals 1+, 2-, 3+ Certification no. PTB no. Ex-97.D.2048 Voltage U o 23.1 V Current I o 28 ma Explosion group [EEx ib] II C ) 0.06 µf ) 0.5 mh Housing Type C (see page 387) Dimensions (mm) 115 x 20 x g (5.3 oz.) KFD0-SCS-Ex1.55 I 110
18 111
Miniature Temptran RTD Transmitters
Miniature Temptran RTD Transmitters TT111 only TT211 only TT111, TT211 Overview Two models: TT111: UL-recognized component for Canada and United States. TT211: Wider ambient rating; Factory Mutual (FM)
More informationAssembly. Front view. Parametrization interface. Power Bus
Temperature Converter Features Assembly 1-channel signal conditioner 24 V DC supply Thermocouple, RTD, potentiometer or mv input Input for PTC thermistor Current and voltage output Line fault (LFD) and
More informationSTT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C
STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C 34-TT-03-07 3/06 PRODUCT SPECIFICATION SHEET OVERVIEW The Honeywell STT170 series of programmable temperature
More informationTemperature Measurement
Overview Application transmitters can be used in all industrial sectors. Due to their compact size they can be installed in the connection head type B (DIN 4729) or larger. The following sensors/signal
More informationEngineer s Guide. Section 9. Practical Solutions. Switches and NAMUR Sensors
Section Practical Solutions Intrinsic safety barriers are the core of Pepperl+Fuchs product portfolio. We offer the widest selection of products for protection of electrical signals located in hazardous
More informationSTT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C
STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C 6/07 PRODUCT SPECIFICATION SHEET OVERVIEW The Honeywell STT170 series of programmable temperature transmitters
More informationMODEL: B3HU. Space-saving Two-wire Signal Conditioners B3-UNIT
Space-saving Two-wire Signal Conditioners B3-UNIT 2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER (HART communication, intrinsically safe) Functions & Features Universal input: mv, V, T/C, RTD, resistance, potentiometer
More informationSEM210 SERIES. Programmable In-head Universal Temperature Transmitter INDEX SECTION CONTENTS PAGE NO.
INDEX SECTION CONTENTS PAGE NO. SEM210 SERIES 1.0 DESCRIPTION 1 2.0 SPECIFICATION 15 3.0 INSTALLATION 67 Programmable Inhead Universal Temperature Transmitter Status Instruments Ltd, Green Lane Business
More informationFC-33, DC SELECTABLE SIGNAL CONDITIONER
FC-33, DC SELECTABLE SIGNAL CONDITIONER Description. The FC-33 is a DIN rail or side mount, selectable input/output signal conditioner with 1500VDC isolation between input and output, and 1500VDC isolation
More informationPROGRAMMABLE FIELD TEMPERATURE TRANSMITTER
Configuration Code TM01 Series 642 Programmable HART Field Temperature The Series 642 programmable HART field temperature transmitter is a 2-wire unit with analog output. It includes input for RTDs; resistance
More informationTemperature measurement TMD 832 head transmitter
Technical information TI 062R/09/en Mat.-Nr. 510 00782 Temperature measurement TMD 832 head transmitter SMART head transmitter with HART protocol for RTD, Thermocouple and mv input signals Applications
More informationitemp HART DIN rail TMT112
Temperature transmitter itemp HART DIN rail TMT112 Universal temperature transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage transmitters, incorporating HART protocol Application
More informationTemperature Measurement
Temperature Measurement SITANS T00 Overview Application SITANS T00 transmitters can be used in all industrial sectors. Their compact design enables simple mounting on standard DIN rails on-site in protective
More informationC520 / C520X /C520S / C520XS HART Compatible, Universal, Dual-input 2-wire Transmitters
C520 / C520X /C520S / C520XS HART Compatible, Universal, Dual-input 2-wire Transmitters The 520 transmitters are universal, isolated, dual-input temperature transmitters with additional voltage and resistance
More informationAssembly. Front view. HiC2441. SL2 1b. Termination Board
SMART Universal Barrier HiC Features Assembly channel isolated barrier V DC supply (bus powered) Analog input, digital input, analog output, digital output No configuration required, device is selfadapting
More informationSafetyNet IO Modules. Safety and Distributed Control. PAC8000 SafetyNet.
SafetyNet IO Modules SafetyNet IO Modules interface to safety system field wiring via Field Terminals. The IO Modules and the Field Terminals mount on Carriers that provide mechanical support, but also
More informationRail mounted Temperature Transmitter TH102/TH102-Ex
Data Sheet 10/-8.54 EN Rail mounted Temperature Transmitter TH102/TH102-Ex HART programmable, Pt 100 (RTD), thermocouples, electrical isolation Input Resistance thermometer (2, 3, 4 wire circuit) Thermocouples
More informationIsolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160
Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de
More informationTemperature transmitter itemp PCP DIN rail TMT 121
Technical information TI 087R/09/en 510 03671 Temperature transmitter itemp PCP DIN rail TMT 121 Universal temperature transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage
More informationSafety Barriers 2/1. Hazardous area. 250 V max I.S.
/0 Safety barriers Exchangeable back-up fuse for all safety barriers Snap-on mounting on rails: simultaneous connection to potential equalisation/ ground Simple selection: application specific single and
More informationFieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex
Data Sheet 10/-8.54 EN Level 0: Information FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex HART programmable, Pt 100 (RTD), thermocouples, electrical isolation Resistance thermometer (2,
More informationR88000 T (including ATEX)
INSTRUCTION MANUAL R88000 T88000 (including ATEX) Factory set transmitters are ready to use. Connect according the labels. Otherwise follow the calibration instructions. Input signals ṮC RTD CONTENTS:
More informationTemperature Measurement Transmitters for mounting in sensor head
Siemens AG 015 Overview SITANS TH00 two-wire system, universal, HAT Application SITANS TH00 transmitters can be used in all industrial sectors. Due to their compact size they can be installed in the connection
More informationIsolators A3/1.
Temperature Transmitter Series 9182 > One unit for nearly all temperature sensors indivdually configurable > Signal duplication possible > Galvanic isolation between input, output, power supply and configuration
More informationConnection. Composition
Converters Connection e. g. t1 nput EEx ia C 1channel nput EEx ia C 24 V DC supply voltage Current output: /4 m... 2 m (optional voltage output) ccuracy ±.1 % User can use D switch to adjust: emperature
More information0 2 1 â Ó. itemp HART TMT182. Technical Information
Technical Information itemp HART TMT182 Temperature head transmitter Head transmitter for resistance thermometers (RTD), thermocouples (TC), resistance and voltage transmitters (mv), HART -protocol, for
More informationIsolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F
Series 9160 Rev. F > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de
More informationSingle-Channel Safety Barriers Series 9001
Single-Channel Safety Barriers Series 9001 > Broad product range for all standard applications in the world of automation > Flexible and space saving single and dual channel versions available > Time saving
More informationIsolating Repeater Input Series 9163
> For 4-wire HART transmitters and voltage sources > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2 (IEC 61508) > High accuracy www.stahl.de
More information09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i
Temperature Transmitter Series 9182 www.stahl.de > One unit for nearly all temperature sensors indivdually configurable > Intrinsically safe input [Ex ia] IIC > Signal duplication possible > Galvanic isolation
More informationTemperature Input Module for Zone 1 Series 9482/32
www.stahl.de > 8 channels for temperature sensors > Intrinsically safe inputs Ex ia > For Pt-, Ni- and Cu-resistance temperature detectors according to DIN, IEC and GOST in 2-, 3- and 4-wire circuits >
More informationDIN Rail Devices. CEAG Sicherheitstechnik GmbH 194
DIN Rail Devices Description DIN rail devices serve as low cost signal conditioning modules between the field device and the control system. The new enclosures mounted on the 35 mm standard rail are equipped
More informationOperator Manual. Transmitters Series KAT-... Analog transmitters in 2-wire technique
Operator Manual Transmitters Series KAT-... Analog transmitters in 2-wire technique Important Safety Notes! In the case of non-observance of the installation and safety notes or improper use of the transmitter
More information3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/.
Ex i Isolators Temperature Transmitter without Output 0/4... 20 ma, with Limit Value Contact Field Circuit Ex i) One unit for nearly all temperature sensors indivdually configurable Intrinsically safe
More informationSTT 3000 Smart Temperature Transmitter Series STT170 Specifications
STT 3000 Smart Temperature Transmitter Series STT170 Specifications Model STT171, STT173, STT17H, STT17F, STT17C 34-TT-03-07 November 2010 Overview STT17H Features The Honeywell STT170 series of programmable
More informationSMART TEMPERATURE TRANSMITTERS. smar
SMART TEMPERATURE TRANSMITTERS FEATURES Single unit accepts signal from: - Standart RTDs and Thermocouples - Single ended or differential sensing - mv signals from radiation pyrometers, load cells, etc.
More informationOuput Loop Powered Products Section C
Ouput Loop Powered Products Section C An output loop powered (or signal powered) isolator derives its power from the voltage drop across the device's current loop output. Because they require no separate
More informationMTL4000 SERIES. isolating IS interface units. For close integration of IS circuits into processconnected
For close integration of S circuits into processconnected systems 1 MTL4000 SERES isolating S interface units Compact modular design with plug-in connections High module/channel packing densities System
More informationIsolators A3/1. Vibration Transducer Supply Unit Series
> For vibration, acceleration and speed sensors in 2- and 3-wire design > Space-saving dual-channel version > Signal frequencies up to 50 khz > Easy setting by means of front-side rotary switch > Galvanic
More informationZener barriers - operating instructions Application examples
Информационный лист DSe_IB_Zexamples Zener barriers - operating instructions. Temperature measurement Z0 Not grounded Temperature monitoring or control The simplest and most favourably priced solution
More information3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5.
Ex i Isolators Temperature Transmitter with Output 0/4... 20 ma, without Limit Value Contact Field Circuit Ex i) One unit for nearly all temperature sensors indivdually configurable Intrinsically safe
More informationHART Compatible Intelligent 2-wire DIN Rail Transmitters
HART Compatible Intelligent 2-wire DIN Rail Transmitters MESO-L is a Smart and universal 2-wire DIN Rail transmitter for temperature and other measurement applications. MESO-LX is the Intrinsic Safe version
More informationTransmitter. Configuration Code TM01 Series 440 Programmable RTD Temperature Transmitter. Application Areas. Features and Benefits
Configuration Code TM01 Series 440 Programmable RTD Temperature Transmitter The Series 440 programmable RTD temperature transmitter is a 2-wire transmitter with an analog output. It has measurement input
More informationContrans T TEU 471, TEU 471-Ex. Intelligent four-wire temperature transmitters EN
Contrans T TEU 471, TEU 471-Ex Intelligent four-wire temperature transmitters Input/sensor connection: Resistance thermometers (2-, 3-, 4-wire circuit) Thermocouples (without, with internal/external reference
More informationTemperature Measurement Transmitters for mounting in sensor head
Siemens AG 015 SITANS TH00 two-wire system, universal Overview Application SITANS TH00 transmitters can be used in all industrial sectors. Due to their compact size they can be installed in the connection
More informationConnection. Thermocouple. Output (4 ma ma) Power supply Power Rail. Composition
Converters Connection 1channel nput EEx ia C 24 V DC supply voltage Current output: /4 ma... 2 ma (optional voltage output) Characteristic curve deviation +.1;% Adjustment option via DP switch for temperature
More informationTemperature transmitter with local display RIT 261
Technical Information TI 091R/2/ae Temperature transmitter with local display RIT 261 Universal field mounted transmitter provides an exceptional backlit temperature indication with five large digits and
More informationMODEL: B6U-B B6-UNIT. [2] LCD DISPLAY 0: Without 1: With
Field-mounted Two-wire Signal Conditioners B6-UNIT 8: TIIS flameproof (CE not available) Confirm selectable combinations of approval and wiring conduit types in the table. 2-WIRE UNIVERSAL TEMPERATURE
More informationConnection. Input EEx ia IIC. Sense. Fine tuning adjustment. Fine tuning amplifying. Amplifying. Adjustment. Output. Composition
Converter Connection 1-channel EEx ia IIC for 4-wire and 6-wire bridges Analogue output 0/4 ma... 20 ma or 4mA...-12mA Full bridge load cells and strain gauges circuit for resistance bridges up to 17 Ω
More informationMODEL: M6SXU MODEL: M6SXU [1][2] [3][4]
Tension-Clamp Ultra-Slim Signal Conditioners M6S Series UNIVERSAL TRANSMITTER (PC programmable) Functions & Features Maintenance-free tension clamp connection Universal input (mv, V, ma, T/C, RTD and potentiometer)
More informationUniversal Intelligent 2-wire In-head Transmitters
Universal Intelligent 2-wire In-head Transmitters Actual size IPAQ-H is a universal and intelligent 2-wire In-head transmitter for temperature and other measurement applications. IPAQ-HX is the Intrinsic
More informationUniversal Intelligent 2-wire DIN Rail Transmitters
Universal Intelligent 2-wire DIN Rail Transmitters IPAQ-L is a universal and intelligent 2-wire DIN rail transmitter for temperature and other measurement applications. IPAQ-LX is the Intrinsic Safe version
More informationIsolated DIN Rail Mount Loop-Powered 2-Wire Signal Conditioners. DRLP Series
Isolated DIN Rail Mount Loop-Powered 2-Wire Signal Conditioners DRLP Series U ±0.03% Accuracy (Typical) U ±0.01% Linearity U 1500Vrms Transformer Isolation and 240Vrms Field-Side Protection U Wide Loop
More informationDigital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting
Electrical Temperature Measurement Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting WIKA Data Sheet TE 12.03
More informationIsolated 4 to 20 ma Transmitters For Demanding Applications Thermocouples, RTD (Pt100) or Ohms, Millivolts, Milliamps, Volts
Isolated Transmitters For Demanding Applications Thermocouples, RTD (Pt100) or Ohms, Millivolts, Milliamps, Volts TX1500 Series U Isolated to 1500 Vrms U 2Wire Operation U 9 to 50V Compliance U Turndown
More information0 2 1 â Ó. itemp HART TMT182. Technical Information
Technical Information itemp HART TMT182 Temperature head transmitter Head transmitter for resistance thermometers (RTD), thermocouples (TC), resistance and voltage transmitters (mv), HART -protocol, for
More informationD5072. SIL 2 Temperature Signal Converter, Multifunction, DIN-Rail and Termination Board, Models D5072S, D5072D. Characteristics: Technical Data:
Characteristics: Front Panel and Features: 5 6 3 1 SIL 11 1 Ordering Information: Model: 1 channel channels D50 D50 SIL according to IEC 6150 for Tproof 5 years ( % of total SIF). Input from Zone 0 (Zone
More informationUniversal Intelligent 2-wire DIN Rail Transmitters
Universal Intelligent 2-wire DIN Rail Transmitters IPAQ-L is a universal and intelligent 2-wire DIN rail transmitter for temperature and other measurement applications. IPAQ-LX is the Intrinsic Safe version
More informationTwo-Wire Programmable Transmitter for:
TM Smart Process Instrumentation Revision 2 Two-Wire Programmable Transmitter for: Industrial Thermocouple or RTD Temperature Measurements Highlights: Exceptional speed and accuracy Guaranteed measurement
More informationMODEL: R30US4. Remote I/O R30 Series
Remote I/O R30 Series UNIVERSAL INPUT MODULE (4 points, isolated) Functions & Features 4 points universal input I/O module Isolation between the channels Input range of each channel is individually adjustable
More informationTemperature Transmitter ZTT series
BT.11.13 ZT/I ZTT series The ZTT series transmitter accepts the most commonly used temperature sensors (RTD, T/C) as well as mv and slide wire signals. All the models adopt a 2 wire 4...20mA output signal
More informationTF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels
TF 0 / TF 0-Ex Head mounted temperature transmitters, FOUNDATION Fieldbus (H), Pt 00 (RTD), thermocouples, or independent channels 0/-8.5 EN Input Resistance thermometer (,, wire circuit) Thermocouples
More informationMultifunction Intelligent 4-wire Isolated Signal Conditioner
Multifunction Intelligent 4-wire Isolated Signal Conditioner IPAQ-4L is a fully universal and intelligent 4- wire (mains powered) transmitter for temperature measurement and signal conditioning applications.
More informationTwo-channel safety barriers Series 9002
Two-channel safety s Series 00 > Wide product range for all standard applications of the automation > Flexible and space-saving available in single and double channel versions > Time-saving installation
More informationDigital temperature transmitter with HART protocol Model T32.1S, head mounting version Model T32.3S, rail mounting version
Electrical temperature measurement Digital temperature transmitter with HART protocol Model T32.1S, head mounting version Model T32.3S, rail mounting version WIKA data sheet TE 32.04 Applications Process
More informationAdvanced Temperature Transmitter
No. SS2-ATT082-0100 Advanced Temperature Transmitter ATT082 HART protocol Model Application Temperature transmitter with 2 input channels and HART communication for the conversion of different input signals
More informationIsolators A3/1.
> Compact limit value switch with 2 configurable limiting values and 4... 20 ma output > Suitable for 2-, 3-wire transmitters, 2-wire HART transmitters and ma sources > Intrinsically safe input [Ex ia]
More informationTwo Wire Temperature Transmitter LTX-3000-H-2 LTX-3000-H LTX-3000-W LTX-3000-D
Two Wire Temperature Transmitters (Product Code 18.1 To 18.8) LTX-3000-H-2 LTX-3000-H LTX-3000-W LTX-3000-D Model Wise Description: Sr.No Model Product Description 18.1 LTX-3000-H Two Wire Temperature
More informationSPT. Description. Features. Site-Programmable, Isolated Temperature Transmitter
SPT June 1999 Data Sheet 3.45 Description Moore Industries SPT Site-Programmable Transmitter is an advanced signal conditioner that packs exceptional flexibility, accuracy, and ease-of-use into a compact,
More informationIndicomp 2, Indicomp 2-Ex. Indicator and alarm signalling unit 10/ EN
Indicator and alarm signalling unit 10/30-2.10 EN Dimensions 36 mm x 144 mm Can either stand vertically or lie horizontally Comprehensively explosion-protected Robust moving-coil system Contactless alarm
More informationTemperature head transmitter itemp PCP TMT 181
Technical information TI 070R/09/en Mat.-Nr.: 510 01110 Temperature head transmitter itemp PCP TMT 181 Universal head transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage
More informationSITRANS T measuring instruments for temperature
SITRANS T measuring instruments for temperature /2 Product overview /6 Transmitter for mounting in sensor head /6 SITRANS TH100, two-wire system (Pt100) /9 SITRANS TH200, two-wire system universal /15
More informationAlphaline Temperature Transmitters
Alphaline Temperature Transmitters Accepts RTD and thermocouple inputs Available with an integral meter Dual compartment housing provides the highest reliability in harsh industrial environments Offers
More informationSITRANS T measuring instruments for temperature
Overview Our field devices for heavy industrial use HART, Universal 4 to 20 ma, universal Field indicator for 4 to 20 ma signals The temperature transmitter SITRANS TF works where others feel uncomfortable.
More informationTwo-channel safety barriers Series 9002
Two-channel safety s Series 00 > Wide product range for all standard applications of the automation > Flexible and space-saving available in single and double channel versions > Time-saving installation
More informationD1072. SIL 2 Temperature Signal Converter, Duplicator, Adder/Subtractor DIN-Rail Models D1072S, D1072D. Front Panel and Features:
Characteristics: Front Panel and Features: Ordering Information: Model: D7 D7 General Description: The single and dual channel DIN Rail Temperature Signal Converter D7S and D7D accepts a low level dc signal
More informationHART Compatible Intelligent 2-wire In-head Transmitters
HART Compatible Intelligent 2-wire In-head Transmitters Actual size MESO-H is a Smart and universal 2-wire Inhead transmitter for temperature and other measurement applications. MESO-HX is the Intrinsic
More informationC330 / C330X PC-Programmable Universal, 2-wire Transmitter
C330 / C330X PC-Programmable Universal, 2-wire Transmitter The IPAQ C330 transmitter is a universal, isolated, temperature transmitter with additional voltage and resistance input. Its robust design and
More informationIPAQ C530/R530 Technical Datasheet
IPAQ C530/R530 Technical Datasheet Smart 2-wire universal transmitter with HART 7 and NFC technology NFC - Configuration of the transmitter via a portable device such as a smartphone. HART 7 protocol High
More informationMODEL: M2XU MODEL: M2XU [1][2] [3][4]
Super-mini Signal Conditioners Mini-M Series UNIVERSAL TRANSMITTER (PC programmable) Functions & Features Accepts direct inputs from various sensors and provides a standard process signal I/O types and
More informationIsolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series
Transmitter Supply Unit Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > Open-circuit and short-circuit monitoring and messaging for input
More informationTIY Programmable, Isolated Thermocouple Transmitter combines
April 2016 Description Moore Industries unique digital/analog hybrid the combines smart digital technology with advanced analog operation to deliver superior reliability, accuracy and ease of use. Microprocessor-based,
More informationIsolators A3/1. Temperature Transmitter Field Circuit Non-Ex i Series
Temperature Transmitter Series 9182 > One unit for nearly all temperature sensors indivdually configurable > Signal duplication possible > Galvanic isolation between input, output, power supply and configuration
More informationMZB SERIES. Intrinsically Safe Shunt Diode Safety Barriers. Phone: Fax: Web: -
MZB SERIES Intrinsically Safe Shunt Diode Safety Barriers Turck of Intrinsically Safe Shunt Diode Safety Barriers New series of Zener Barriers include a wider product range for more flexibility in more
More informationSpecifications. 744 Users Manual
80T-150U Temperature Probe 80PK series thermocouples 80i-410 Clamp-on DC/AC Current Probe 80i-1010 Clamp-on DC/AC Current Probe 80i-500s Clamp-on AC Current Probe (requires the Y9108 adapter) 80i-1000s
More informationHead mounted Temperature Transmitter TF02/TF02-Ex
Data Sheet Head mounted Temperature Transmitter TF0/TF0-Ex FOUNDATION Fieldbus H, Pt 00 (RTD), thermocouples, or independent channels Input Resistance thermometer (-, -, -wire circuit) Thermocouples Resistance
More informationFieldIT Temperature Transmitter, head mounted TH02/TH02-Ex
Data Sheet 0/-8.9 EN Level 0: Information FieldIT Temperature Transmitter, head mounted TH0/TH0-Ex HART programmable, Pt 00 (RTD), thermocouples, electrical isolation Input Resistance thermometer (,, wire
More informationBinary Output Series 9175
Binary Output > Intrinsically safe output [Ex ia] IIC / [Ex ib] IIC > Galvanic isolation between input, output and power supply > Open-circuit and short-circuit monitoring (can be switched off) > For use
More informationFC Series Signal Conditioners
FC Series Signal Conditioners FC-33 DC Selectable Signal Conditioner with 3-way isolation Field configurable input and output ranges of 0-5V, 0-10 V, 0-20 ma and 4-20 ma with 1500 VDC isolation between
More informationTemperature Transmitters TMT 136, TMT 137
Technical Information TI 066R/09/en Part No. 51000855 Temperature Transmitters TMT 136, TMT 137 For Pt100 Resistance Thermometers 2-wire head transmitter Standard- and instrinsically safe versions Head
More informationTemperature Measurement
Siemens AG 017 / Product overview Transmitters for mounting in sensor head /4 SITRANS TH100 two-wire system (Pt100) /8 SITRANS TH00 two-wire system universal /15 SITRANS TH00 two-wire system universal,
More informationDigital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version
Temperature Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version WIKA data sheet TE 15.01 for further approvals see page 10 Applications
More informationTransmitter for temperature and direct current variables in four-wire circuit. Contrans T TEU 315, TEU 315-Ex, TEU 325, TEU 325-Ex 11-3.
TEU 315, TEU 315-Ex, TEU 325, TEU 325-Ex Transmitter for temperature and direct current variables in four-wire circuit Transmitters TEU 315 and TEU 325 are designed for direct and alternating voltage measurement
More informationTxBlock-USB Transmitter
Transmitter TEMPERATURE TRANSMITTER - OPERATING MANUAL V1.0x I INTRODUCTION The TxBlock-USB is a 4-20 ma 2-wire temperature transmitter for head mount, powered by the current loop. The output current is
More informationALM42 ALM46 ALM48 ALM43
INSTRUCTION MANUAL ALM42 ALM46 ALM48 ALM43 CONTENTS Specifications Connection diagram Location of solderlinks Programming instructions Dimensions INSTALLATION REQUIREMENTS - The ALM series does not have
More informationitemp PA TMT184 Technical information
Technical information itemp PA TMT184 Temperature head transmitter with PROFIBUS-PA interface. Supply and digital communication using PROFIBUS-PA, for installation in a Form B sensor head. Features and
More informationAssembly. Front view. Power Rail
Thermometer Resistance Repeater Features Assembly 1-channel isolated barrier 24 V DC supply (Power Rail) RTD/resistance input Resistance output Accuracy 0.1 % Front view Removable terminals blue Function
More informationGeneral Specifications
General Specifications Signal Conditioner Cards OUTLINE Signal Conditioner Cards, which interface to the process, are installed in Signal Conditioner Nests. [Release 6] The signal conditioner cards can
More informationCALYS 150. Advanced documenting multifunction calibrator thermometer
Advanced documenting multifunction calibrator thermometer , most advanced documenting multifunction instrument of the range, works not only as a simulator (IN / OUT) but also as a dual channel thermometer
More informationSINEAX B 811 Power Pack with additional Functions
SINEA B 8 for intelligent and conventional s, in housing S7 for rail and wall mounting 002 II () G Application The power supply unit SINEA B 8 (Figure ) provides the DC power supply for s and transfers
More information