Temperature Measurement

Size: px
Start display at page:

Download "Temperature Measurement"

Transcription

1 Siemens AG 017 / Product overview Transmitters for mounting in sensor head /4 SITRANS TH100 two-wire system (Pt100) /8 SITRANS TH00 two-wire system universal /15 SITRANS TH00 two-wire system universal, HART / SITRANS TH400 fieldbus transmitter Transmitters for rail mounting /8 SITRANS TR00 two-wire system universal /5 SITRANS TR00 two-wire system universal, HART /4 SITRANS TW four wire system, universal, HART Transmitters for field mounting /54 SITRANS TF80 WirelessHART /59 SITRANS TF two-wire system /8 SITRANS TF fieldbus transmitter Field indicator /59 SITRANS TF Field indicator for 4 to 0 ma Multipoint temperature transmitter /75 SITRANS TO500 SITRANS TS500 /78 Technical Description /80 - Types ST, SS, SR threaded process connection /8 - Types FT, FS, FR flanged process connection /8 - Types SWT, SWS, SWR socketwell process connection /85 - Type GP general purpose no thermowell /85 - Type GP /90 Selection and Ordering Data /94 Schematics You can download all instructions, catalogs and certificates for SITRANS T free of charge at the following Internet address: Siemens FI US Edition

2 Siemens AG 017 Product overview Overview Application Mounting of transmitter with Ex protection Page Software for parameterization Temperature transmitter for head mounting SITRANS TH100 Transmitters for Pt100 Two-wire system Transmitter Zone and zone 1 Sensor Zone, zone 1 and zone 0 /4 SIPROM T SITRANS TH00 Transmitters for connection to resistance thermometers, resistance-based sensors, thermocouples and DC voltages up to 1.1 V Two-wire system Universal Zone and zone 1 Zone, zone 1 and zone 0 /8 SIPROM T SITRANS TH00 Transmitters for connection to resistance thermometers, resistance-based sensors, thermocouples and DC voltages up to 1.1 V Two-wire system Universal HART SITRANS TH400 Transmitters for connection to resistance thermometers, resistance-based sensors, thermocouples and DC voltages up to 0.9 V Fieldbus transmitters PROFIBUS PA FOUNDATION fieldbus Temperature transmitters for rail mounting SITRANS TR00 Transmitters for connection to resistance thermometers, resistance-based sensors, thermocouples and DC voltages up to 1.1 V Two-wire system Universal Zone and zone 1 Zone, zone 1 and zone 1 Zone, zone 1 and zone 1 Zone, zone 1 and zone 0 Zone, zone 1, zone 0, zone 1, zone 0 Zone, zone 1, zone 0, zone 1, zone 0 /15 SIMATIC PDM / SIMATIC PDM for TH 400 with PROFIBUS PA /8 SIPROM T SITRANS TR00 Transmitters for connection to resistance thermometers, resistance-based sensors, thermocouples and DC voltages up to 1.1 V Two-wire system Universal HART Zone, zone 1 and zone 1 Zone, zone 1, zone 0, zone 1, zone 0 /5 SIMATIC PDM SITRANS TW Transmitters for connection to resistance thermometers, resistance-based sensors, thermocouples, DC voltages and DC currents for: Four-wire system Safe area Zone 1, zone 0, zone 1, zone 0 /4 SIMATIC PDM / Siemens FI US Edition

3 Siemens AG 017 Product overview Application Temperature transmitters for field mounting SITRANS TF80 Transmitter for connection to resistance-based sensor In field enclosure for heavy industrial use battery-operated WirelessHART Mounting of transmitter with Ex protection Transmitter Sensor Page Software for parameterization - - /54 Local operation via buttons SIMATIC PDM local with HART modem and wireless via WirelessHART Field indicator for 4 to 0 ma signals SITRANS TF Transmitters for connection to resistance thermometers, resistance-based sensors, thermocouples and DC voltages up to 1.1 V In field enclosure for heavy industrial use HART, Universal SITRANS TF Fieldbus transmitters for connection to resistance thermometers, resistance-based sensors, thermocouples and DC voltages up to 0.8 V In field enclosure for heavy industrial use PROFIBUS PA FOUNDATION fieldbus Zone and zone 1 Zone and zone 1 Zone, zone 1 and zone 0 Zone, zone 1 and zone 0 /59 depending on the installed TH00/TH00 transmitter /8 SIMATIC PDM for PROFIBUS PA SITRANS TF Field indicator for 4 to 0 ma signals Display of units can be userdefined Zone and zone 1 - /59 -- Multipoint temperature transmitter SITRANS TO500 Multipoint temperature transmitter for measuring temperatures and temperature profiles using fiber optic Multipoint temperature measurement lances. Zone, Zone Zone 0, Zone 0 /75 Via Ethernet with the supplied parameter assignment software Type Description Page Temperature sensors SITRANS TS500 Temperature Sensor Assemblies Include thermowell, sensor, head and transmitters Integrated temperature assemblies Include thermowell, sensor, head and transmitter in single model number. Various options include configuration, calibration and certificates. /78 Product documentation on DVD and Safety Note Siemens products for process instrumentation will be delivered with a multi-language Safety note and a Mini DVD - Process Instrumentation and Weighing Systems. On the DVD, customers can find many important operating instructions and certificates of our Siemens portfolio for process instrumentation and weighing systems. Additionally, product or order-specific print material might be part of the delivery. For further information see appendix page 10/9. Siemens FI US Edition /

4 Siemens AG 017 Transmitters for mounting in sensor head SITRANS TH100 two-wire system (Pt100) Overview Application Used in conjunction with Pt100 resistance thermometers, the SITRANS TH100 transmitters are ideal for measuring temperatures in all industries. Due to its compact size it can be installed in the connection head type B (DIN 479) or larger. The output signal is a direct current from 4 to 0 ma that is proportional to the temperature. Parameterization is implemented over the PC using the parameterization software SIPROM T and the modem for SITRANS TH100/TH00. If you already have a "modem for SITRANS TK" (Article No. 7NG190-KB), you can continue using this to parameterize the SITRANS TH100. Transmitters of the "intrinsically-safe" type of protection can be installed within potentially explosive atmospheres. The devices comply with the Directive 94/9/EC (ATEX), as well as FM and CSA regulations. The SITRANS TH100 dispenses with electrical isolation and universal sensor connection to provide a low-cost alternative for Pt100 measurements. For the parameterization, the SIPROM T software is used in combination with the modem for SITRANS TH100/TH00. Its extremely compact design makes the SITRANS TH100 ideal for the retrofitting of measuring points or for the use of analog transmitters. The transmitter is available as a non-ex version as well as for use in potentially explosive atmospheres. Benefits Two-wire transmitter Assembly in connection head type B (DIN 479) or larger, or on a standard DIN rail Can be programmed, which means that the sensor connection, measuring range, etc. can also be programmed Intrinsically-safe version for use in potentially explosive areas Function Mode of operation The measured signal supplied by a Pt100 resistance thermometer (, or 4-wire system) is amplified in the input stage. The voltage, which is proportional to the input variable, is then converted into digital signals by a multiplexer in an analog/digital converter. They are converted in the microcontroller in accordance with the sensor characteristics and further parameters (measuring range, damping, ambient temperature etc.). The signal prepared in this way is converted in a digital/analog converter into a load-independent direct current of 4 to 0 ma. An EMC filter protects the input and output circuits against electromagnetic interferences. I c U ref Input Pt100 EMC_1 IC MUX A/D Resistance thermometer Input level with protective components Constant current source Multiplexer Analog-digital converter Pt EMC_1 MUX U ref A/D D/A μc Output D/A U/I EMC_ U aux I out Digital-analog converter Voltage transformers, current transformers, constant voltage and reference voltage source Output level with protective components Auxiliary power supply Output current Microcontroller μc Linearization functions and storage of all data + U I EMC_ ma - U aux, I out SITRANS TH100, function diagram /4 Siemens FI US Edition

5 Siemens AG 017 Technical specifications Input Resistance thermometer Measured variable Temperature Sensor type PT100 to IEC 0751 Characteristic curve Type of connection Resolution Measuring accuracy Span <50 C (450 F) Span >50 C (450 F) Repeatability Measuring current Measuring cycle Temperature-linear -, - or 4-wire circuit 14 bit < 0.5 C (0.45 F) < 0.1 % of span < 0.1 C (0.18 F) approx. 0.4 ma < 0.7 s Measuring range C F) Measuring span C ( F) Unit C or F Offset programmable: C ( F) Line resistance Max. 0 Ω (total from feeder and return conductor) Noise rejection 50 and 0 Hz Output Output signal ma, two-wire Auxiliary power V DC (0 V for Ex ia and ib; V for Ex nl/ic; 5 V for Ex na) Max. load (U aux V)/0.0 A Overrange.... ma, infinitely adjustable (default range: ma) Error signal (following sensor fault) (conforming to NE4).... ma, infinitely adjustable (default range:. ma or.8 ma) Damping time s (default value: 0 s) Protection Against reversed polarity Resolution 1 bit Accuracy at C (7.4 F) < 0.1 % of span Temperature effect < 0.1 %/10 C (0.1 %/18 F) Effect of auxiliary power < 0.01 % of span/v Effect of load impedance < 0.05 % of max. span/100 Ω Long-term drift < 0.05 % of the max. span in the first month < 0.05 % of the max. span after one year < 0.05 % of the max. span after 5 years Ambient conditions Ambient temperature range C( F) Storage temperature range C ( F) Relative humidity 98 %, with condensation Electromagnetic compatibility According to EN 1 and NAMUR NE1 Construction Weight 50 g Dimensions See dimensional drawing Material Molded plastic Cross-section of cables Max..5 mm (AWG 1) Degree of protection to IEC 059 Enclosure IP40 Terminals IP00 Transmitters for mounting in sensor head SITRANS TH100 two-wire system (Pt100) Certificates and approvals Explosion protection ATEX EC type test certificate PTB 05 ATEX 049X "Intrinsic gas safety" type of protection II (1) G Ex ib [ia Ga] IIC T/T4 Gb II 1 G Ex ia IIC T/T4 II (1) G Ex ic [ia Ga] IIC T/T4 Gc II G Ex ic IIC T/T4 Gc "Non-sparking" type of protection II G Ex na IIC T/T4 Gc II G Ex na[ic] IIC T/T4 Gc "Intrinsic dust safety" type of protection II 1 D Ex ia IIIC T115 C Da Explosion protection FM for USA and Canada ( c FM US ) FM approval PID 0419 Degree of protection IS Cl I, II, III, Div 1, GP ABCDEFG T4/T5/T Cl I, ZN 0,1 AEx ia IIC T4/T5/T NI Cl I, II, III, Div, GP ABCDFG T4/T5/T Cl I, ZN, NI IIC T4/T5/T Other certificates GOST, NEPSI, PESO Software requirements for SIPROM T PC operating system Windows ME, 000, XP, Win 7 and Win 8; can also be used in connection with RS modem under Windows 95, 98 and 98SE Siemens FI US Edition /5

6 Siemens AG 017 Transmitters for mounting in sensor head SITRANS TH100 two-wire system (Pt100) Selection and Ordering data Article No. SITRANS TH100 temperature transmitters for Pt100 for installation in connection head, type B (DIN 479), two-wire system, ma, programmable, without electrical isolation Without explosion protection 7NG11-0NN00 With explosion protection "Intrinsic safety" type of protection and for zone -to ATEX 7NG11-0AN00 - to FM ( c FM US ) 7NG11-0BN00 Further designs Order code Add "-Z" to Article No. and specify Order code(s) Test report (5 measuring points) C11 Customer-specific programming Add "-Z" to Article No. and specify Order code(s) Measuring range to be set Y01 1) Specify in plain text (max. 5 digits): Y01:... to... C, F Measuring point no. (TAG), max. 8 characters Y17 ) Measuring point descriptor, max. 1 characters Y ) Pt100 (IEC) -wire, R L = 0 Ω U0 ) Pt100 (IEC) -wire U0 ) Pt100 (IEC) 4-wire U04 ) Special differing customer-specific programming, specify in plain text Y09 4) Fail-safe value. ma (instead of,8 ma) U ) Accessories Article No. Modem for SITRANS TH100, TH00, TR00 7NG09-8KU and TF with TH00 incl. SIPROM T parameterization software With USB connection MiniDVD for temperature measuring instruments A5E00451 With documentation in German, English, French, Spanish, Italian, Portuguese and SIPROM T parameterization software DIN rail adapters for head transmitters 7NG09-8KA (Quantity delivered: 5 units) Connecting cable 7NG09-8KC 4-wire, 150 mm, for sensor connections when using head transmitters in the high hinged cover (set with 5 units) 1) For customer-specific programming for RTD and TC, the start value and the end value of the required measuring span must be specified here. ) For this selection, Y01 or Y09 must also be selected. ) For this selection, Y01 must also be selected. 4) For customer-specific programming, for example mv and ohm, the start value and the end value of the required measuring span and the unit must be entered here. Supply units see Chapter "Supplementary Components". Ordering example 7NG11-0NN00-Z Y01+Y+U0 Y01: C Y: TICA14HEAT Factory setting: Pt100 (IEC 751) with -wire circuit Measuring range: C ( 1 C) Error signal in the event of sensor breakage:.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s Dimensional drawings 1 SIEMENS + 1 SITRANS TH100, dimensions in mm (inch) Mounting on DIN rail 44 (1.7) 4..0mA SITRANS TH100, mounting of transmitter on DIN rail DIN rail adaptor, dimensions in mm (inch) -W (1.) 0.8 (0.8) Internal diameter Center hole. (0.5) Mounting screw M4x5 1(+) and (-) Auxiliary power supply U aux, output current I Out, 4, 5 and Pt100 sensor (for connection, see sensor connection assignment) 14 (0.55) 50.5 (1.99) (1.0) 59. (.5) / Siemens FI US Edition

7 Siemens AG 017 Transmitters for mounting in sensor head SITRANS TH100 two-wire system (Pt100) Schematics 4 -W 5 4 -W 5 Pt100 Pt100 Two-wire system (parameterizable line resistance) Three-wire system 4 -W 5 + U aux 4..0mA - 1 SIEMENS + 1 Pt100 5 Four-wire system Connection of auxiliary power supply (U aux ) power supply (Uaux) SITRANS TH100, sensor connection assignment Siemens FI US Edition /7

8 Siemens AG 017 Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal Overview Application SITRANS TH00 transmitters can be used in all industrial sectors. Due to their compact size they can be installed in the connection head type B (DIN 479) or larger. The following sensors/signal sources can be connected over their universal input module: Resistance thermometers (, or 4-wire system) Thermocouples Resistance-based sensors and DC voltage sources The output signal is a direct current from 4 to 0 ma in accordance with the sensor characteristic. Transmitters of the "intrinsically safe" type of protection can be installed within potentially explosive atmospheres. The devices comply with the Directive 94/9/EC (ATEX), as well as FM and CSA regulations. Ultra flexible - with the universal SITRANS TH00 transmitter Two-wire devices for 4 to 0 ma Mounting in the connection head of the temperature sensor Universal input for virtually any type of temperature sensor Configurable over PC Benefits Compact design Flexible mounting and center hole allow you to select your preferred type of installation Electrically isolated Test sockets for multimeters Diagnostics LED (green/red) Sensor monitoring open circuits and short-circuits Self-monitoring Configuration status stored in EEPROM SIL (with Order Code C0), SIL/ (with C) Expanded diagnostic functions, such as slave pointer, operating hours counter, etc. Special characteristic Electromagnetic compatibility to EN 1 and NE1 Function The SITRANS TH00 is configured over a PC. A USB or RS modem is linked to the output terminals for this purpose. The configuration data can now be edited using the SIPROM T software tool. The configuration data are then permanently stored in the non-volatile memory (EEPROM). Once the sensors and power supply have been correctly connected, the transmitter outputs a temperature-linear output signal and the diagnostics LED displays a green light. In the case of a sensor short-circuit, the LED flashes red, an internal device fault is indicated by a steady red light. The test socket can be used to connect an ammeter at any time for monitoring purposes and plausibility checks. The output current can be read without any interruption, or even without opening the current loop. SITRANS TH00/TH00 () TC/RTD sensor A D μc1 (1) μc D A Test ma U aux, I out - Input A/D Sensors μc1 Analog-digital converter Resistance thermometer, thermocouple, resistance-based sensor, mv sensor Microcontroller, secondary circuit Output μc D/A U aux I out Microcontroller, primary circuit Digital-analog converter Auxiliary power supply Output current (1) Electrically isolated () LED SITRANS TH00 function diagram /8 Siemens FI US Edition

9 Siemens AG 017 Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal Technical specifications Input Resistance thermometer Measured variable Sensor type to IEC 0751 To JIS C 104; a = K -1 to IEC 0751 Temperature Pt5 Pt1000 Pt5 Pt1000 Ni5 Ni1000 Special type over special characteristic (max. 0 points) Sensor factor (adaptation of the basic type, e.g. Pt100 to version Pt ) Units C or F Connection Standard connection 1 resistance thermometer (RTD) in -wire, -wire or 4-wire system Generation of average value identical resistance thermometers in -wire system for generation of average temperature Generation of difference identical resistance thermometers (RTD) in -wire system (RTD 1 RTD or RTD RTD 1) Interface Two-wire system Parameterizable line resistance 100 Ω (loop resistance) Three-wire system No balancing required Four-wire system No balancing required Sensor current 0.45 ma Response time 50 ms for 1 sensor with opencircuit monitoring Open-circuit monitoring Always active (cannot be disabled) Short-circuit monitoring can be switched on/off (default value: ON) Measuring range parameterizable (see table "Digital measuring errors") Min. measured span 10 C (18 F) Characteristic curve Temperature-linear or special characteristic Resistance-based sensors Measured variable Actual resistance Sensor type Resistance-based, potentiometers Units Ω Connection Normal connection 1 resistance-based sensor (R) in -wire, -wire or 4-wire system Generation of average value resistance-based sensors in -wire system for generation of average value Generation of difference resistance thermometers in -wire system (R1 R or R R1) Interface Two-wire system Parameterizable line resistance 100 Ω (loop resistance) Three-wire system No balancing required Four-wire system No balancing required Sensor current 0.45 ma Response time 50 ms for 1 sensor with opencircuit monitoring Open-circuit monitoring Always active (cannot be disabled) Short-circuit monitoring can be switched on/off (default value: OFF) Measuring range parameterizable max Ω (see table "Digital measuring errors") Min. measured span 5 Ω... 5 Ω (see Table "Digital measuring errors") Characteristic curve Resistance-linear or special characteristic Thermocouples Measured variable Temperature Sensor type (thermocouples) Type B Pt0Rh-PtRh to DIN IEC 584 Type C W5 %-Re acc. to ASTM 988 Type D W %-Re acc. to ASTM 988 Type E NiCr-CuNi to DIN IEC 584 Type J Fe-CuNi to DIN IEC 584 Type K NiCr-Ni to DIN IEC 584 Type L Fe-CuNi to DIN 4710 Type N NiCrSi-NiSi to DIN IEC 584 Type R Pt1Rh-Pt to DIN IEC 584 Type S Pt10Rh-Pt to DIN IEC 584 Type T Cu-CuNi to DIN IEC 584 Type U Cu-CuNi to DIN 4710 Units C or F Connection Standard connection 1 thermocouple (TC) Generation of average value thermocouples (TC) Generation of difference thermocouples (TC) (TC1 TC or TC TC1) Response time 50 ms for 1 sensor with opencircuit monitoring Open-circuit monitoring Can be switched off Cold junction compensation Internal With integrated Pt100 resistance thermometer External With external Pt100 IEC 0571 (-wire or -wire connection) External fixed Cold junction temperature can be set as fixed value Measuring range Parameterizable (see table "Digital measuring errors") Min. measured span Min C ( F) (see table "Digital measuring errors") Characteristic curve Temperature-linear or special characteristic mv sensor Measured variable DC voltage Sensor type DC voltage source (DC voltage source possible over an externally connected resistor) Units mv Response time 50 ms for 1 sensor with opencircuit monitoring Open-circuit monitoring Can be switched off Measuring range mv mv Siemens FI US Edition /9

10 Siemens AG 017 Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal Min. measured span mv or 0mV Overload capability of the input V DC Input resistance 1MΩ Characteristic curve Voltage-linear or special characteristic Output Output signal ma, -wire Auxiliary power V DC ((to 0 V for Ex ia and ib; to V for Ex na / nl / ic) Max. load (U aux 11 V)/0.0 A Overrange.... ma, infinitely adjustable (default range:.80 ma ma) Error signal (e.g. following sensor.... ma, infinitely adjustable fault) (conforming to NE4) (default value:.8 ma) Sample cycle 0.5 s nominal Damping Software filter 1st order s (parameterizable) Protection Against reversed polarity Electrically isolated Input against output (1 kv eff ) Measuring accuracy Digital measuring errors See table "Digital measuring errors" Reference conditions Auxiliary power 4 V ± 1 % Load 500 Ω Ambient temperature C Warming-up time > 5 min Error in the analog output (digital/analog converter) < 0.05 % of span Error due to internal cold junction < 0.5 C (0.9 F) Influence of ambient temperature Analog measuring error 0.0 % of span/10 C (18 F) Digital measuring errors - with resistance thermometers 0.0 C (0.11 F)/10 C (18 F) - with thermocouples 0. C (1.1 F)/10 C (18 F) Auxiliary power effect < % of span/v Effect of load impedance < 0.00 % of span/100 Ω Long-term drift In the first month < 0.0 % of span After one year < 0. % of span After 5 years < 0. % of span Conditions of use Ambient conditions Ambient temperature range C ( F) Storage temperature range C ( F) Relative humidity < 98 %, with condensation Electromagnetic compatibility acc. to EN 1 and NE1 Construction Material Molded plastic Weight 50 g (0.11 lb) Dimensions See "Dimensional drawings" Cross-section of cables Max..5 mm² (AWG 1) Degree of protection to IEC 059 Enclosure IP40 Terminals IP00 Certificates and approvals Explosion protection ATEX EC type test certificate "Intrinsic safety" type of protection "Operating equipment that is nonignitable and has limited energy" type of protection Explosion protection: FM for USA PTB 05 ATEX 040X II 1 G Ex ia IIC T/T4 II (1) G Ex ia/ib IIC T/T4 II (1) G Ex ia/ic IIC T/T4 II 1D Ex iad 0 T115 C II G Ex nl IIC T/T4 II G Ex na IIC T/T4 FM approval FM 0419 Degree of protection IS / Cl I, II, III / Div 1 / GP ABC- DEFG T, T5, T4 Cl I / ZN 0 / AEx ia IIC T, T5, T4 NI / Cl I / Div / GP ABCDFG T, T5, T4 NI / Cl I / ZN / IIC T, T5, T4 Explosion protection to FM for Canada ( c FM US ) FM approval FM 0419C Degree of protection IS / Cl I, II, III / Div 1/ GP ABC- DEFG T, T5, T4 NI / Cl I / DIV / GP ABCD T, T5, T4 NIFW / Cl I, II, III / DIV / GP ABCDFG T, T5, T4 DIP / Cl II, III / Div / GP FG T, T5, T4 Cl I / ZN 0 / Ex ia IIC T, T5, T4 Cl I / ZN / Ex na nl IIC T, T5, T4 Other certificates GOST, NEPSI, PESO, IEC, EXPOLABS Software requirements for SIPROM T PC operating system Windows ME, 000, XP, Win 7 and Win 8; can also be used in connection with RS modem under Windows 95, 98 and 98SE Factory setting: Pt100 (IEC 751) with -wire circuit Measuring range: C (... 1 F) Fault current:.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s /10 Siemens FI US Edition

11 Siemens AG 017 Digital measuring errors Resistance thermometer Input Measuring range Min. measured span Digital accuracy C / ( F) C ( F) C ( F) to IEC 0751 Pt (18) 0. (0.54) ( ) Pt (18) 0.15 (0.7) ( ) Pt Pt (18) 0.1 (0.18) ( ) Pt (18) 0.15 (0.7) ( ) Pt (18) 0.15 (0.7) ( ) to JIS C Pt (18) 0. (0.54) ( ) Pt (18) 0.15 (0.7) ( ) Pt Pt (18) 0.1 (0.18) ( ) Pt (18) 0.15 (0.7) ( ) Pt (18) 0.15 (0.7) ( ) Ni 5... Ni (18) 0.1 (0.18) ( ) Resistance-based sensors Input Measuring range Min. measured span Digital accuracy Ω Ω Ω Resistance ,05 Resistance ,5 Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal Thermocouples Input Measuring range Min. measured span Digital accuracy C/( F) C ( F) C ( F) Type B (180) 1) (.0) 1) (... 08) Type C (W5) (180) (.0) ( ) Type D (W) (180) 1 ) (1.80) ) ( ) Type E (90) 1 (1.80) ( ) Type J (90) 1 (1.80) ( ) Type K (90) 1 (1.80) ( ) Type L (90) 1 (1.80) ( ) Type N (90) 1 (1.80) ( ) Type R (180) (.0) ( ) Type S (180) (.0) ( ) Type T (7) 1 (1.80) ( ) Type U (90) (.0) ( ) 1) The digital accuracy in the range 0 to 00 C ( to 57 F) is C (5.4 F). ) The digital accuracy in the range 1750 to 00 C (18 to 417 F) is C (. F). mv sensor Input Measuring Min. measured Digital range span accuracy mv mv μv mv sensor mv sensor The digital accuracy is the accuracy after the analog/digital conversion including linearization and calculation of the measured value. An additional error is generated in the output current 4 to 0 ma as a result of the digital/analog conversion of 0.05 % of the set span (digital-analog error). The total error under reference conditions at the analog output is the sum from the digital error and the digital-analog error (poss. with the addition of cold junction errors in the case of thermocouple measurements). Siemens FI US Edition /11

12 Siemens AG 017 Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal Selection and Ordering data Article No. Temperature transmitter SITRANS TH00 for installation in connection head, type B (DIN 479), two-wire system, ma, programmable, with electrical isolation Without explosion protection 7NG11-1NN00 With explosion protection -to ATEX 7NG11-1AN00 - to FM ( c FM US ) 7NG11-1BN00 Further designs Order code Add "-Z" to Article No. and specify Order code(s) With test protocol (5 measuring points) C11 Functional safety SIL C0 Functional safety SIL/ C Customer-specific programming Add "-Z" to Article No. and specify Order code(s) Measuring range to be set Y01 1) Specify in plain text (max. 5 digits): Y01:... to... C, F Measuring point no. (TAG), max. 8 characters Y17 ) Measuring point descriptor, max. 1 characters Y ) Measuring point message, max. characters Y4 ) Pt100 (IEC) -wire, R L = 0 Ω U0 ) Pt100 (IEC) -wire U0 ) Pt100 (IEC) 4-wire U04 ) Thermocouple type B U0 )4) Thermocouple type C (W5) U1 )4) Thermocouple type D (W) U )4) Thermocouple type E U )4) Thermocouple type J U4 )4) Thermocouple type K U5 )4) Thermocouple type L U )4) Thermocouple type N U7 )4) Thermocouple type R U8 )4) Thermocouple type S U9 )4) Thermocouple type T U0 )4) Thermocouple type U U1 )4) With TC: CJC external (Pt100, -wire) U41 With TC: CJC external with fixed value, specify Y50 in plain text Special differing customer-specific programming, Y09 5) specify in plain text Fail-safe value. ma (instead of,8 ma) U ) Cable extension W01 Transmitter with installed cable extension 00 mm (7.81 inch), for Pt100 in four-wire system Accessories Modem for SITRANS TH100, TH00, TR00 and TF with TH00 incl. SIPROM T parameterization software With USB connection MiniDVD for temperature measuring instruments With documentation in German, English, French, Spanish, Italian, Portuguese and SIPROM T parameterization software DIN rail adapters for head transmitters (Quantity delivered: 5 units) Connecting cable 4-wire, 150 mm, for sensor connections when using head transmitters in the high hinged cover (set with 5 units) Supply units see Chapter "Supplementary Components". Ordering example 1: 7NG11-1NN00-Z Y01+Y17+U0 Y01: C Y17: TICA1 Ordering example : 7NG11-1NN00-Z Y01+Y+U5 Y01: C Y: TICA14HEAT Factory setting: Pt100 (IEC 751) with -wire circuit Measuring range: C ( 1 F) Fault current:.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s Article No. 7NG09-8KU A5E NG09-8KA 7NG09-8KC 1) For customer-specific programming for RTD and TC, the start value and the end value of the required measuring span must be specified here. ) For this selection, Y01 or Y09 must also be selected. ) For this selection, Y01 must also be selected. 4) Internal cold junction compensation is selected as the default for TC. 5) For customer-specific programming, for example mv and ohm, the start value and the end value of the required measuring span and the unit must be entered here. /1 Siemens FI US Edition

13 Siemens AG 017 Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal Dimensional drawings Mounting on DIN rail Ø 44 (1.7) (1.0) (1) Test ma Test (1) () 1 SIEMENS + 1 () () 4 -W 5 (4) SITRANS TH00, mounting of transmitter on DIN rail 14 (0.55) 50.5 (1.99) (1.0) M4 x 0. (1.04) 59. (.5) 1(+) and (-) Auxiliary power supply U aux, output current I Out, 4, 5 and Pt100 sensor (for connections, see Sensor connection assignment) Test (+), Test (-) Measurement of the output current with a multimeter (1) Test terminal () Mounting screw M4x0 () LED for operation indication (4) Internal diameter of center hole. (0.5) DIN rail adapter, dimensions in mm (inch) SITRANS TH00, dimensions and pin assignment, dimensions in mm (inch) Siemens FI US Edition /1

14 Siemens AG 017 Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal Schematics Resistance thermometer Resistance Thermocouple -W -W -W RTD R + TC - Two-wire system 1) Two-wire system 1) Cold junction compensation Internal/fixed value -W -W -W RTD R RTD + TC - Three-wire system Three-wire system Cold junction compensation with external Pt100 in two-wire system 1) -W -W -W RTD R RTD + TC - Four-wire system Four-wire system Cold junction compensation with external Pt100 in three-wire system -W -W -W RTD R + TC - + TC1 - R1 RTD1 Generation of average value / difference 1) 1) Programmable line resistance for the purpose of correction. Generation of average value / difference 1) Generation of average value / difference with internal cold junction compensation Voltage measurement Current measurement Connection of auxiliary power supply (U aux ) -W -W U aux Test 4..0mA Test U I R 1 SIEMENS SITRANS TH00, sensor connection assignment /14 Siemens FI US Edition

15 Siemens AG 017 Overview Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal, HART Application SITRANS TH00 transmitters can be used in all industrial sectors. Due to their compact size they can be installed in the connection head type B (DIN 479) or larger. The following sensors/signal sources can be connected over their universal input module: Resistance thermometers (, or 4-wire system) Thermocouples Resistance-based sensors and DC voltage sources The output signal is a direct current from 4 to 0 ma in accordance with the sensor characteristic, superimposed by the digital HART signal. Transmitters of the "intrinsically safe" type of protection can be installed within potentially explosive atmospheres. The devices comply with the Directive 94/9/EC (ATEX), as well as FM and CSA regulations. "HART" to beat - the universal SITRANS TH00 transmitter Two-wire devices for 4 to 0 ma, HART Mounting in the connection head of the temperature sensor Universal input for virtually any type of temperature sensor Configurable over HART Benefits Compact design Flexible mounting and center hole allow you to select your preferred type of installation Electrically isolated Test sockets for multimeters Diagnostics LED (green/red) Sensor monitoring open circuits and short-circuits Self-monitoring Configuration status stored in EEPROM SIL (with Order Code C0), SIL/ (with C) Expanded diagnostic functions, such as slave pointer, operating hours counter, etc. Special characteristic Electromagnetic compatibility to EN 1 and NE1 Function The SITRANS TH00 is configured over HART. This can be done using a handheld communicator or even more conveniently with a HART modem and the SIMATIC PDM parameterization software. The configuration data are then permanently stored in the non-volatile memory (EEPROM). Once the sensors and power supply have been correctly connected, the transmitter outputs a temperature-linear output signal and the diagnostics LED displays a green light. In the case of a sensor short-circuit, the LED flashes red, an internal device fault is indicated by a steady red light. The test socket can be used to connect an ammeter at any time for monitoring purposes and plausibility checks. The output current can be read without any interruption, or even without opening the current loop. SITRANS TH00/TH00 () TC/RTD sensor A D μc1 (1) μc D A Test ma U aux, I out - Input A/D Sensors μc1 Analog-digital converter Resistance thermometer, thermocouple, resistance-based sensor, mv sensor Microcontroller, secondary circuit Output μc D/A U aux I out Microcontroller, primary circuit Digital-analog converter Auxiliary power supply Output current (1) Electrically isolated () LED SITRANS TH 00 function diagram Siemens FI US Edition /15

16 Siemens AG 017 Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal, HART Technical specifications Input Resistance thermometer Measured variable Temperature Sensor type to IEC 0751 Pt5 Pt1000 To JIS C 104; a = K -1 Pt5 Pt1000 to IEC 0751 Ni5 Ni1000 Special type over special characteristic (max. 0 points) Sensor factor (adaptation of the basic type, e.g. Pt100 to version Pt ) Units C or F Connection Standard connection 1 resistance thermometer (RTD) in -wire, -wire or 4-wire system Generation of average value identical resistance thermometers in -wire system for generation of average temperature Generation of difference identical resistance thermometers (RTD) in -wire system (RTD 1 RTD or RTD RTD 1) Interface Two-wire system Parameterizable line resistance 100 Ω (loop resistance) Three-wire system No balancing required Four-wire system No balancing required Sensor current 0.45 ma Response time 50 ms for 1 sensor with opencircuit monitoring Open-circuit monitoring Always active (cannot be disabled) Short-circuit monitoring can be switched on/off (default value: ON) Measuring range parameterizable (see table "Digital measuring errors") Min. measured span 10 C (18 F) Characteristic curve Temperature-linear or special characteristic Resistance-based sensors Measured variable Actual resistance Sensor type Resistance-based, potentiometers Units Ω Connection Normal connection 1 resistance-based sensor (R) in -wire, -wire or 4-wire system Generation of average value resistance-based sensors in -wire system for generation of average value Generation of difference resistance thermometers in - wire system (R1 R or R R1) Interface Two-wire system Parameterizable line resistance 100 Ω (loop resistance) Three-wire system No balancing required Four-wire system No balancing required Sensor current 0.45 ma Response time 50 ms for 1 sensor with opencircuit monitoring Open-circuit monitoring Always active (cannot be disabled) Short-circuit monitoring can be switched on/off (default value: OFF) Measuring range parameterizable max Ω (see table "Digital measuring errors") Min. measured span Ω (see table "Digital measuring errors") Characteristic curve Resistance-linear or special characteristic Thermocouples Measured variable Temperature Sensor type (thermocouples) Type B Pt0Rh-PtRh to DIN IEC 584 Type C W5 %-Re acc. to ASTM 988 Type D W %-Re acc. to ASTM 988 Type E NiCr-CuNi to DIN IEC 584 Type J Fe-CuNi to DIN IEC 584 Type K NiCr-Ni to DIN IEC 584 Type L Fe-CuNi to DIN 4710 Type N NiCrSi-NiSi to DIN IEC 584 Type R Pt1Rh-Pt to DIN IEC 584 Type S Pt10Rh-Pt to DIN IEC 584 Type T Cu-CuNi to DIN IEC 584 Type U Cu-CuNi to DIN 4710 Units C or F Connection Standard connection 1 thermocouple (TC) Generation of average value thermocouples (TC) Generation of difference thermocouples (TC) (TC1 TC or TC TC1) Response time 50 ms for 1 sensor with opencircuit monitoring Open-circuit monitoring can be switched off Cold junction compensation Internal With integrated Pt100 resistance thermometer External With external Pt100 IEC 0571 (-wire or -wire connection) External fixed Cold junction temperature can be set as fixed value Measuring range parameterizable (see table "Digital measuring errors") Min. measured span Min C ( F) (see table "Digital measuring errors") Characteristic curve Temperature-linear or special characteristic mv sensor Measured variable DC voltage Sensor type DC voltage source (DC voltage source possible over an externally connected resistor) Units mv Response time 50 ms for 1 sensor with opencircuit monitoring /1 Siemens FI US Edition

17 Siemens AG 017 Open-circuit monitoring Measuring range Min. measured span Overload capability of the input Input resistance Characteristic curve Output Output signal Auxiliary power Max. load Overrange Error signal (e.g. following sensor fault) (conforming to NE4) Sample cycle Damping Can be switched off mv mv mv or 0mV V DC 1 MΩ Voltage-linear or special characteristic ma, -wire with communication acc. to HART Rev V DC (to 0 V for Ex ia and ib; to V for Ex na/nl/ic) (U aux 11 V)/0.0 A.... ma, infinitely adjustable (default range:.80 ma ma).... ma, infinitely adjustable (default value:.8 ma) 0.5 s nominal Software filter 1st order s (parameterizable) Protection Against reversed polarity Electrically isolated Input against output (1 kv eff ) Measuring accuracy Digital measuring errors See Table "Digital measuring errors" Reference conditions Auxiliary power 4 V ± 1 % Load 500 Ω Ambient temperature C Warming-up time > 5 min Error in the analog output (digital/analog converter) < 0.05 % of span Error due to internal cold junction < 0.5 C (0.9 F) Influence of ambient temperature Analog measuring error 0.0 % of span/10 C (18 F) Digital measuring errors - with resistance thermometers 0.0 C (0.11 F)/10 C (18 F) - with thermocouples 0. C (1.1 F)/10 C (18 F) Auxiliary power effect < % of span/v Effect of load impedance < 0.00 % of span/100 Ω Long-term drift In the first month < 0.0 % of span After one year < 0. % of span After 5 years < 0. % of span Conditions of use Ambient conditions Ambient temperature range C ( F) Storage temperature range C ( F) Relative humidity < 98 %, with condensation Electromagnetic compatibility acc. to EN 1 and NE1 Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal, HART Construction Material Molded plastic Weight 50 g (0.11 lb) Dimensions See "Dimensional drawings" Cross-section of cables Max..5 mm² (AWG 1) Degree of protection to IEC 059 Enclosure IP40 Terminals IP00 Certificates and approvals Explosion protection ATEX EC type test certificate PTB 05 ATEX 040X "Intrinsic safety" type of protection II 1 G Ex ia IIC T/T4 II (1) G Ex ia/ib IIC T/T4 II (1) G Ex ia/ic IIC T/T4 II 1D Ex iad 0 T115 C "Operating equipment that is nonignitable and has limited energy" type of protection Explosion protection: FM for USA II G Ex nl IIC T/T4 II G Ex na IIC T/T4 FM approval FM 0419 Degree of protection IS / Cl I, II, III / Div 1 / GP ABC- DEFG T, T5, T4 Cl I / ZN 0 / AEx ia IIC T, T5, T4 NI / Cl I / Div / GP ABCDFG T, T5, T4 NI / Cl I / ZN / IIC T, T5, T4 Explosion protection to FM for Canada ( c FM US ) FM approval FM 0419C Degree of protection IS / Cl I, II, III / Div 1/ GP ABC- DEFG T, T5, T4 NI / Cl I / DIV / GP ABCD T, T5, T4 NIFW / Cl I, II, III / DIV / GP ABCDFG T, T5, T4 DIP / Cl II, III / Div / GP FG T, T5, T4 Cl I / ZN 0 / Ex ia IIC T, T5, T4 Cl I / ZN / Ex na nl IIC T, T5, T4 Other certificates GOST, NEPSI, PESO, IEC, EXPOLABS Factory setting: Pt100 (IEC 751) with -wire circuit Measuring range: C (... 1 F) Fault current:.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s Siemens FI US Edition /17

18 Siemens AG 017 Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal, HART Digital measuring errors Resistance thermometer Input Measuring range Min. measured span Digital accuracy C/( F) C ( F) C ( F) to IEC 0751 Pt (18) 0. (0.54) ( ) Pt (18) 0.15 (0.7) ( ) Pt Pt (18) 0.1 (0.18) ( ) Pt (18) 0.15 (0.7) ( ) Pt (18) 0.15 (0.7) ( ) to JIS C Pt (18) 0. (0.54) ( ) Pt (18) 0.15 (0.7) ( ) Pt Pt (18) 0.1 (0.18) ( ) Pt (18) 0.15 (0.7) ( ) Pt (18) 0.15 (0.7) ( ) Ni 5 to Ni (18) 0.1 (0.18) ( ) Resistance-based sensors Input Measuring range Min. measured span Digital accuracy Ω Ω Ω Resistance ,05 Resistance ,5 Thermocouples Input Measuring range Min. measured span Digital accuracy C/( F) C ( F) C ( F) Type B (180) 1) (.0) 1) (... 08) Type C (W5) (180) (.0) ( ) Type D (W) (180) 1 ) (1.80) ) ( ) Type E (90) 1 (1.80) ( ) Type J (90) 1 (1.80) ( ) Type K (90) 1 (1.80) ( ) Type L (90) 1 (1.80) ( ) Type N (90) 1 (1.80) ( ) Type R (180) (.0) ( ) Type S (180) (.0) ( ) Type T (7) 1 (1.80) ( ) Type U (90) (.0) ( ) 1) The digital accuracy in the range 0 to 00 C ( to 57 F) is C (5.4 F). ) The digital accuracy in the range 1750 to 00 (18 to 417 F) is C (. F). mv sensor Input Measuring range Min. measured span mv mv μv mv sensor mv sensor Digital accuracy The digital accuracy is the accuracy after the analog/digital conversion including linearization and calculation of the measured value. An additional error is generated in the output current 4 to 0 ma as a result of the digital/analog conversion of 0.05 % of the set span (digital-analog error). The total error under reference conditions at the analog output is the sum from the digital error and the digital-analog error (poss. with the addition of cold junction errors in the case of thermocouple measurements). /18 Siemens FI US Edition

19 Siemens AG 017 Selection and Ordering data Article No. Temperature transmitter SITRANS TH00 for installation in connection head, type B (DIN 479), two-wire system ma, communication capable to HART, with galvanic isolation Without explosion protection 7NG1-0NN00 With explosion protection -to ATEX 7NG1-0AN00 - to FM ( C FM US ) 7NG1-0BN00 Further designs Order code Add "-Z" to Article No. and specify Order code(s) with test protocol (5 measuring points) C11 Functional safety SIL C0 Functional safety SIL/ C Customer-specific programming Add "-Z" to Article No. and specify Order code(s) Measuring range to be set Y01 1) Specify in plain text (max. 5 digits): Y01:... to... C, F Measuring point no. (TAG), max. 8 characters Y17 ) Measuring point descriptor, max. 1 characters Y ) Measuring point message, max. characters Y4 ) Pt100 (IEC) -wire, R L = 0 Ω U0 ) Pt100 (IEC) -wire U0 ) Pt100 (IEC) 4-wire U04 ) Thermocouple type B U0 )4) Thermocouple type C (W5) U1 )4) Thermocouple type D (W) U )4) Thermocouple type E U )4) Thermocouple type J U4 )4) Thermocouple type K U5 )4) Thermocouple type L U )4) Thermocouple type N U7 )4) Thermocouple type R U8 )4) Thermocouple type S U9 )4) Thermocouple type T U0 )4) Thermocouple type U U1 )4) With TC: CJC external (Pt100, -wire) U41 With TC: CJC external with fixed value, specify Y50 in plain text Special differing customer-specific programming, Y09 5) specify in plain text Fail-safe value. ma (instead of,8 ma) U ) Cable extension W01 Transmitter with installed cable extension 00 mm (7.87 inch), for Pt100 in four-wire system Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal, HART Accessories Article No. MiniDVD for temperature measuring instruments A5E00451 With documentation in German, English, French, Spanish, Italian, Portuguese and SIPROM T parameterization software HART modem With USB connection 7MF4997-1DB SIMATIC PDM operating software See Section 8 DIN rail adapters for head transmitters 7NG09-8KA (Quantity delivered: 5 units) Connecting cable 7NG09-8KC 4-wire, 150 mm, for sensor connections when using head transmitters in the high hinged cover (set with 5 units) 1) For customer-specific programming for RTD and TC, the start value and the end value of the required measuring span must be specified here. ) For this selection, Y01 or Y09 must also be selected. ) For this selection, Y01 must also be selected. 4) Internal cold junction compensation is selected as the default for TC. 5) For customer-specific programming, for example mv and ohm, the start value and the end value of the required measuring span and the unit must be entered here. Supply units see Chapter "Supplementary Components". Ordering example 1: 7NG1-0NN00-Z Y01+Y17+U0 Y01: C Y17: TICA1 Ordering example : 7NG1-0NN00-Z Y01+Y+U5 Y01: C Y: TICA14HEAT Factory setting: Pt100 (IEC 751) with -wire circuit Measuring range: C (... 1 F) Fault current:.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s Siemens FI US Edition /19

20 Siemens AG 017 Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal, HART Dimensional drawings Mounting on DIN rail Ø 44 (1.7) (1.0) (1) Test ma Test (1) () 1 SIEMENS + 1 () () 4 -W 5 (4) SITRANS TH00, mounting of transmitter on DIN rail 14 (0.55) 50.5 (1.99) (1.0) M4 x 0. (1.04) 59. (.5) 1(+) and (-) Auxiliary power supply U aux, output current I Out, 4, 5 and Pt100 sensor (for connections, see Sensor connection assignment) Test (+), Test (-) Measurement of the output current with a multimeter (1) Test terminal () Mounting screw M4x0 () LED for operation indication (4) Internal diameter of center hole. (0.5) DIN rail adapter, dimensions in mm (inch) SITRANS TH00, dimensions and pin assignment, dimensions in mm (inch) /0 Siemens FI US Edition

21 Siemens AG 017 Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal, HART Schematics Resistance thermometer Resistance Thermocouple -W -W -W RTD R + TC - Two-wire system 1) Two-wire system 1) Cold junction compensation Internal/fixed value -W -W -W RTD R RTD + TC - Three-wire system Three-wire system Cold junction compensation with external Pt100 in two-wire system 1) -W -W -W RTD R RTD + TC - Four-wire system Four-wire system Cold junction compensation with external Pt100 in three-wire system -W -W -W RTD R + TC - + TC1 - R1 RTD1 Generation of average value / difference 1) 1) Programmable line resistance for the purpose of correction. Generation of average value / difference 1) Generation of average value / difference with internal cold junction compensation Voltage measurement Current measurement Connection of auxiliary power supply (U aux ) -W -W U aux Test 4..0mA Test U I R 1 SIEMENS SITRANS TH00, sensor connection assignment Siemens FI US Edition /1

22 Siemens AG 017 Transmitters for mounting in sensor head SITRANS TH400 fieldbus transmitter Overview Application Linearized temperature measurement with resistance thermometers or thermal elements Differential, mean-value or redundant temperature measurement with resistance thermometers or thermal elements Linear resistance and bipolar millivolt measurements Differential, mean-value or redundant resistance and bipolar millivolt measurements SITRANS TH400 fieldbus transmitters Versions: For FOUNDATION fieldbus For PROFIBUS PA The SITRANS TH400 temperature transmitter is a small field bus transmitter for mounting in the connection head of form B. Extensive functionality enables the temperature transmitter to be precisely adapted to the plant s requirements. Operation is very simple in spite of the numerous setting options. Thanks to its universal concept it can be used in all industries and is easy to integrate in the context of Totally Integrated Automation applications. Transmitters of the "intrinsically safe" type of protection can be installed within potentially explosive atmospheres. The devices comply with the Directive 94/9/EC (ATEX), as well as FM and CSA regulations. Installing SITRANS TH400 in temperature sensors turns them into complete, bus-capable measuring points; compact - and in a single device. Function Features Mounting in connection head, type B, to DIN 479, or larger Polarity-neutral bus connection 4-bit analog-digital converter for high resolution Electrically isolated Intrinsically-safe version for use in potentially explosive areas Special characteristic Sensor redundance With PROFIBUS PA communication Function blocks: x analog With FOUNDATION fieldbus communication Function blocks: x analog and 1 x PID Functionality: Basic or LAS Mode of operation The following function diagram explains the mode of operation of the transmitter. The only difference between the two versions of the SITRANS TH400 (7NG and 7NG15-...) is the type of fieldbus protocol used (PROFIBUS PA or FOUNDATION fieldbus). Optional inputs: - Resistance thermometer - Thermocouple - mv sensor - Resistance-based sensors Transformer Input 1 Input Differential Mean value Redundancy Terminal temperature Engineering units Diagnostic functions Table linearization Polynomial linearization Process calibration Input 1 Input 5 4 A/D converter Electrically isolated CPU Communication Ex power circuit 1 Bus connection Internal Pt100 EEPROM Complex configuration Correction coefficient Factory settings - PROFIBUS protocol (7NG14) or - Foundation Fieldbus protocol (7NG15) SITRANS TH400, function diagram / Siemens FI US Edition

23 Siemens AG 017 System communication SITRANS TH400, communication interface Technical specifications Input Bus terminator Bus terminator Analog-to-digital conversion Measurement rate Resolution SITRANS TH400 PA SITRANS TH400 FF Resistance thermometer Output: <50ms 4-bit Pt5... Pt1000 to IEC 0751/JIS C 104 Measuring range C ( F) Ni5... Ni1000 to DIN 470 Measuring range C ( F) Cu10... Cu1000, α = Measuring range C ( F) Line resistance per sensor cable Max. 50 Ω Sensor current Nominal 0. ma Sensor fault detection Sensor break detection Yes Sensor short-circuit detection Yes, < 15 Ω Resistance-based sensors Measuring range 0 Ω kω Line resistance per sensor cable Max. 50 Ω Sensor current Nominal 0. ma Sensor fault detection Sensor break detection Yes Sensor short-circuit detection Yes, < 15 Ω s Bus connection s 1 1 Bus connection PROFIBUS PA Segment coupler FOUNDATION Fieldbus Segment coupler Transmitters for mounting in sensor head Thermocouple to IEC 584 Type B Type E Type J Type K Type N Type R Type S Type T to DIN 4710 Type L Type U to ASTM E Type W Type W5 External cold junction compensation Sensor fault detection Sensor break detection Sensor short-circuit detection Sensor current in the event of open-circuit monitoring mv sensor - voltage input Measuring range Input resistance Output Filter time (programmable) Update time Measuring accuracy Accuracy is defined as the higher value of general values and basic values. General values Type of input All SITRANS TH400 fieldbus transmitter Measuring range C ( F) C ( F) C ( F) C ( F) C ( F) C ( F) C ( F) C ( F) C ( F) C ( F) C ( F) C ( F) C ( F) Yes Yes, < mv 4 μa mv 10 MΩ s < 400ms Absolute accuracy ±0.05 % of the measured value Temperature coefficient ±0.00 % of the measured value/ C Basic values Type of input Basic accuracy Temperature coefficient Pt100 and Pt1000 ±0.1 C ±0.00 C/ C Ni100 ±0.15 C ±0.00 C/ C Cu10 ±1. C ±0.0 C/ C Resistance-based sensors ±0.05 Ω ±0.00 Ω/ C Voltage source ±10 μv ±0. % μv/ C Thermocouple, type: ±0.5 C ±0.01 C/ C E, J, K, L, N, T, U Thermocouple, type: ±1 C ± 0.05 C/ C B, R, S, W, W5 Cold junction compensation ±0.5 C Reference conditions Warming-up time 0 s Signal-to-noise ratio Min. 0 db Calibration condition C ( F) Siemens FI US Edition /

24 Siemens AG 017 Transmitters for mounting in sensor head SITRANS TH400 fieldbus transmitter Conditions of use Ambient conditions Permissible ambient temperature Permissible storage temperature Relative humidity Insulation resistance Test voltage Mechanical testing Vibrations (DIN class B) to C ( F) C ( F) 98 %, with condensation 500 V AC for 0 s IEC and IEC g/ Hz Electromagnetic compatibility EMC noise voltage influence < ± 0.1 % of span Extended EMC noise immunity: < ± 1 % of span NAMUR NE 1, criterion A, Burst EMC 004/108/EC Emission and EN 1 Noise Immunity to Construction Material Molded plastic Weight 55 g (0.1 lb) Dimensions See Dimensional drawings Cross-section of cables Max..5 mm (AWG 1) Degree of protection Transmitter enclosure IP40 Terminal IP00 Auxiliary power Power supply Standard, Ex "na", Ex "nl", NI V DC ATEX, FM, UL and CSA V DC In FISCO/FNICO installations V DC Power consumption < 11 ma Max. increase in power consumption in the event of a < 7 ma fault Certificates and approvals Explosion protection ATEX EC type test certificate KEMA 0 ATEX 04 "Intrinsic safety" type of protection II 1 G Ex ia IIC T4...T II (1) G Ex ib[ia] IIC T4...T II 1 D Ex iad EC type test certificate KEMA 0 ATEX 0 X Type of protection for "equipment is non-arcing" II GD Ex na[nl] IIC T4...T II GD Ex nl IIC T4...T II GD Ex na[ic] IIC T4...T II GD Ex ic IIC T4...T Explosion protection: FM for USA FM approval FM Degree of protection IS Class I, Div 1, Groups A, B, C, D T4/T5/T, FISCO IS Class I, Zone 0, AEx ia, IIC T4/T5/T, FISCO NI Class I, Div, Groups A, B, C, D T4/T5/T, FNICO Explosion protection CSA for Canada CSA approval CSA Degree of protection IS Class I, Div 1, Groups A, B, C, D T4/T5/T Ex ia IIC T4/T5/T and Ex ib [ia] IIC T4/T5/T NI Class I, Div, Groups A, B, C, D T4/T5/T Ex na II T4/T5/T Other certificates GOST, PESO Communication Parameterization interface PROFIBUS PA connection -Protocol Profile.0 - Address (for delivery) 1 FOUNDATION fieldbus connection -Protocol FF protocol - Functionality Basic or LAS - Version ITK 4. - Function blocks x analog and 1 x PID Factory setting only for SITRANS TH400 PA Sensor Pt100 (IEC) Type of connection -wire circuit Unit C Failure mode Last valid value Filter time 0 s PA address 1 PROFIBUS Ident No. Manufacturer-specific only for SITRANS TH400 FF Sensor Pt100 (IEC) Type of connection -wire circuit Unit C Failure mode Last valid value Filter time 0 s Node address /4 Siemens FI US Edition

25 Siemens AG 017 Selection and Ordering data Article No. Temperature transmitter SITRANS TH400 for installation in connection head, with electrical isolation, order operating instructions separately. Bus-compatible to PROFIBUS PA - No explosion protection or Zone /Div 7NG14-0NN00 to ATEX/FM/CSA/IECEX/NEPSI - With explosion protection "Intrinsically 7NG14-0AN00 safe to ATEX/FM/CSA/IECEX/NEPSI" Bus-compatible to FOUNDATION Fieldbus - No explosion protection or Zone /Div 7NG15-0NN00 to ATEX/FM/CSA/IECEX/NEPSI - With explosion protection "Intrinsically 7NG15-0AN00 safe to ATEX/FM/CSA/IECEX/NEPSI" Further designs Order code Please add "-Z" to Article No. and specify Order code(s) and plain text. With test protocol (5 measuring points) C11 Customer-specific programming Add "-Z" to Article No. and specify Order code(s) Measuring range to be set Y01 1) Specify in plain text (max. 5 digits): Y01:... to... C, F Measuring point no. (TAG), max. characters Y17 ) Measuring point descriptor, max. characters Y ) Measuring point message, max. characters Y4 ) Bus address, specify in plain text Y5 ) Pt100 (IEC) -wire, R L = 0 Ω U0 ) Pt100 (IEC) -wire U0 ) Pt100 (IEC) 4-wire U04 ) Thermocouple type B U0 )4) Thermocouple type C (W5) U1 )4) Thermocouple type D (W) U )4) Thermocouple type E U )4) Thermocouple type J U4 )4) Thermocouple type K U5 )4) Thermocouple type L U )4) Thermocouple type N U7 )4) Thermocouple type R U8 )4) Thermocouple type S U9 )4) Thermocouple type T U0 )4) Thermocouple type U U1 )4) With TC: CJC external (Pt100, -wire) U41 With TC: CJC external with fixed value, specify in plain text Y50 Special differing customer-specific programming, specify in plain Y09 5) text Transmitters for mounting in sensor head Ordering example 1: SITRANS TH400 fieldbus transmitter Accessories Article No. MiniDVD for temperature measuring A5E00451 instruments With documentation in German, English, French, Spanish, Italian, Portuguese and SIPROM T parameterization software SIMATIC PDM operating software See Chapter 8 DIN rail adapters for head transmitters 7NG09-8KA (Quantity delivered: 5 units) Connecting cable 7NG09-8KC 4-wire, 150 mm, for sensor connections when using head transmitters in the high hinged cover (set with 5 units) for additional PA components See Catalog IK PI 1) For customer-specific programming for RTD and TC, the start value and the end value of the required measuring span must be specified here. ) For this selection, Y01 or Y09 must also be selected. ) For this selection, Y01 must also be selected. 4) Internal cold junction compensation is selected as the default for TC. 5) For customer-specific programming, for example mv and ohm, the start value and the end value of the required measuring span and the unit must be entered here. 7NG14-0NN00-Z Y01+Y17+U0 Y01: C Y17: TICA14HEAT Ordering example : 7NG14-0NN00-Z Y01+Y17+Y5+U5 Y01: C Y17: TICA578HEAT Y5: Factory setting: For SITRANS TH400 PA: - Pt100 (IEC 751) with -wire circuit - Unit: C - Failure mode: Last valid value - Filter time: 0 s - PA address: 1 - PROFIBUS Ident No.: Manufacturer-specific For SITRANS TH400 FF: - Pt100 (IEC 751) with -wire circuit - Unit: C - Failure mode: Last valid value - Filter time: 0 s - Node address: Siemens FI US Edition /5

26 Siemens AG 017 Transmitters for mounting in sensor head SITRANS TH400 fieldbus transmitter Dimensional drawings s 1 4 -W 5 M4 x 0 (1.) Ø 44 (1.7) Ø. (0.5). (1.04) Terminals 1, : fieldbus connection Terminals... : sensor connection SITRANS TH400 dimensions in mm (inches) and connections Mounting on DIN rail SITRANS TH400, mounting of transmitter on DIN rail 14 (0.55) 50.5 (1.99) (1.0) 59. (.5) DIN rail adaptor, dimensions in mm (inch) / Siemens FI US Edition

27 Siemens AG 017 Transmitters for mounting in sensor head SITRANS TH400 fieldbus transmitter Schematics Resistance thermometer Thermocouple Resistance Two-wire system 1) Internal cold junction compensation Two-wire system 1) Three-wire system Cold junction compensation with external Pt100 in two-wire system 1) Three-wire system Four-wire system Cold junction compensation with external Pt100 in three-wire system Four-wire system Mean-value/differential or redundancy generation x two-wire system 1) Mean value, differential or redundancy generation with internal cold junction compensation Mean value, differential or redundancy generation 1 resistor in two-wire system 1) 1 resistor in three-wire system Voltage measurement 1 1 Mean-value/differential or redundancy generation 1 sensor in two-wire system 1) 1 sensor in three-wire system Mean value, differential or redundancy generation and cold junction compensation with internal Pt100 in two-wire system 1) One voltage source 1) Programmable line resistance for the purpose of correction. 1 Measurement of mean value, differential and redundancy with voltage sources SITRANS TH400, sensor connection assignment Siemens FI US Edition /7

28 Siemens AG 017 Transmitters for rail mounting SITRANS TR00 two-wire system, universal Overview Application SITRANS TR00 transmitters can be used in all industrial sectors. Their compact design enables simple mounting on standard DIN rails on-site in protective boxes or in control cabinets. The following sensors/signal sources can be connected over their universal input module: Resistance thermometers (, or 4-wire system) Thermocouples Resistance-based sensors and DC voltage sources The output signal is a direct current from 4 to 0 ma in accordance with the sensor characteristic. Transmitters of the "intrinsically safe" type of protection can be installed within potentially explosive atmospheres. The devices comply with the Directive 94/9/EC (ATEX). Ultra flexible - with the universal SITRANS TR00 transmitter Two-wire devices for 4 to 0 ma Enclosure for rail mounting Universal input for virtually any type of temperature sensor Configurable over PC Benefits Compact design Electrically isolated Test sockets for multimeters Diagnostics LED (green/red) Sensor monitoring open circuits and short-circuits Self-monitoring Configuration status stored in EEPROM Expanded diagnostic functions, such as slave pointer, operating hours counter, etc. Special characteristic Electromagnetic compatibility to EN 1 and NE1 SIL (with Order Code C0), SIL/ (with C) Function The SITRANS TR00 is configured over a PC. A USB or RS modem is linked to the output terminals for this purpose. The configuration data can now be edited using the SIPROM T software tool. The configuration data are then permanently stored in the non-volatile memory (EEPROM). Once the sensors and power supply have been correctly connected, the transmitter outputs a temperature-linear output signal and the diagnostics LED displays a green light. In the case of a sensor short-circuit, the LED flashes red, an internal device fault is indicated by a steady red light. The test socket can be used to connect an ammeter at any time for monitoring purposes and plausibility checks. The output current can be read without any interruption, or even without opening the current loop. SITRANS TR00/TR00 Sensor TC/RTD 1 7 Test A D µc1 µc 4 5 D A ma U aux, I out 1 Sensor such as resistance thermometer, thermocouple, resistance-based, sensor, mv sensor Analog-digital converter Microcontroller, secondary circuit 4 Electrical isolation 5 Microcontroller, primary circuit Digital-analog converter 7 LED Auxiliary power supply Output current Test Test terminals for temporary connection of an amperemeter U aux I out SITRANS TR00 function diagram /8 Siemens FI US Edition

29 Siemens AG 017 Transmitters for rail mounting SITRANS TR00 two-wire system, universal Technical specifications Input Resistance thermometer Measured variable Sensor type Temperature to IEC 0751 Pt to JIS C 104; a=0.009 K -1 Pt to IEC 0751 Ni Special type over special characteristic (max. 0 points) Sensor factor (adaptation of the basic type, e.g. Pt100 to version Pt ) Units C or F Connection Standard connection 1 resistance thermometer (RTD) in -wire, -wire or 4-wire system Generation of average value resistance thermometers in -wire system for generation of average temperature Generation of difference resistance thermometers (RTD) in -wire system (RTD 1 RTD or RTD RTD 1) Interface Two-wire system Parameterizable line resistance 100 Ω (loop resistance) Three-wire system No balancing required Four-wire system No balancing required Sensor current 0.45 ma Response time T 50 ms for 1 sensor with open-circuit monitoring Open-circuit monitoring Always active (cannot be disabled) Short-circuit monitoring can be switched on/off (default value: ON) Measuring range parameterizable (see table "Digital measuring errors") Min. measured span 10 C (18 F) Characteristic curve Temperature-linear or special characteristic Resistance-based sensors Measured variable Actual resistance Sensor type Resistance-based, potentiometers Units Ω Connection Normal connection 1 resistance-based sensor (R) in - wire, -wire or 4-wire system Generation of average value resistance-based sensors in -wire system for generation of average value Generation of difference resistance thermometers in -wire system (R1 R or R R1) Interface Two-wire system Parameterizable line resistance 100 Ω (loop resistance) Three-wire system No balancing required Four-wire system No balancing required Sensor current 0.45 ma Response time T 50 ms for 1 sensor with open-circuit monitoring Open-circuit monitoring Always active (cannot be disabled) Short-circuit monitoring can be switched on/off (default value: OFF) Measuring range parameterizable max Ω (see table "Digital measuring errors") Min. measured span Ω (see table "Digital measuring errors") Characteristic curve Resistance-linear or special characteristic Thermocouples Measured variable Temperature Sensor type (thermocouples) Type B Pt0Rh-PtRh to DIN IEC 584 Type C W5 %-Re acc. to ASTM 988 Type D W %-Re acc. to ASTM 988 Type E NiCr-CuNi to DIN IEC 584 Type J Fe-CuNi to DIN IEC 584 Type K NiCr-Ni to DIN IEC 584 Type L Fe-CuNi to DIN 4710 Type N NiCrSi-NiSi to DIN IEC 584 Type R Pt1Rh-Pt to DIN IEC 584 Type S Pt10Rh-Pt to DIN IEC 584 Type T Cu-CuNi to DIN IEC 584 Type U Cu-CuNi to DIN 4710 Units C or F Connection Standard connection 1 thermocouple (TC) Generation of average value thermocouples (TC) Generation of difference thermocouples (TC) (TC1 TC or TC TC1) Response time T 50 ms for 1 sensor with open-circuit monitoring Open-circuit monitoring Can be switched off Cold junction compensation Internal With integrated Pt100 resistance thermometer External With external Pt100 IEC 0571 (-wire or -wire connection) External fixed Cold junction temperature can be set as fixed value Measuring range parameterizable (see table "Digital measuring errors") Min. measured span Min C ( F) (see table "Digital measuring errors") Characteristic curve Temperature-linear or special characteristic mv sensor Measured variable DC voltage Sensor type DC voltage source (DC voltage source possible over an externally connected resistor) Units mv Response time T 50 ms for 1 sensor with open-circuit monitoring Open-circuit monitoring Can be switched off Measuring range parameterizable max mv Min. measured span mv or 0mV Overload capability of the input V DC Input resistance 1 MΩ Characteristic curve Voltage-linear or special characteristic Siemens FI US Edition /9

30 Siemens AG 017 Transmitters for rail mounting SITRANS TR00 two-wire system, universal Output Output signal ma, -wire Auxiliary power V DC (to 0 V for Ex i/ic; to V for Ex na) Max. load (U aux 11 V)/0.0 A Overrange.... ma, infinitely adjustable (default range:.84 ma ma) Error signal (e.g. following sensor.... ma, infinitely adjustable fault) (conforming to NE4) (default value:.8 ma) Sample cycle 0.5 s nominal Damping Software filter 1st order s (parameterizable) Protection Against reversed polarity Electrically isolated Input against output.1 kv DC (1.5 kv eff AC) Measuring accuracy Digital measuring errors See Table "Digital measuring errors" Reference conditions Auxiliary power 4 V ± 1 % Load 500 Ω Ambient temperature C Warming-up time > 5 min Error in the analog output (digital/analog converter) < 0.05 % of span Error due to internal cold junction < 0.5 C (0.9 F) Influence of ambient temperature Analog measuring error 0.0 % of span/10 C (18 F) Digital measuring errors - With resistance thermometer 0.0 C (0.11 F)/10 C (18 F) - with thermocouples 0. C (1.1 F)/10 C (18 F) Auxiliary power effect < % of span/v Effect of load impedance < 0.00 % of span/100 Ω Long-term drift In the first month < 0.0 % of span in the first month After one year < 0. % of span after one year After 5 years < 0. % of span after 5 years Conditions of use Ambient conditions Ambient temperature range C ( F) Storage temperature range C ( F) Relative humidity < 98 %, with condensation Electromagnetic compatibility acc. to EN 1 and NE1 Construction Material Plastic, electronic module potted Weight 1 g Dimensions See "Dimensional drawings" Cross-section of cables Max..5 mm² (AWG 1) Degree of protection to IEC 059 Enclosure IP0 Certificates and approvals Explosion protection ATEX EC type test certificate "Intrinsic safety" type of protection Type of protection, "equipment is non-arcing" Other certificates Software requirements for SIPROM T PC operating system PTB 07 ATEX 0X II (1) G Ex ia/ib IIC T/T4 II (1) G Ex ia/ic IIC T/T4 II G Ex ic IIC T/T4 II (1) D Ex iad/ibd 0/1 T115 C II G Ex na IIC T/T4 NEPSI Windows ME, 000, XP, Win 7 and Win 8; can also be used in connection with RS modem under Windows 95, 98 and 98SE Factory setting: Pt100 (IEC 751) with -wire circuit Measuring range: C (... 1 F) Error signal in the event of sensor breakage:.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s Digital measuring errors Resistance thermometer Input Measuring range Min. measured Digital span accuracy C/( F) C ( F) C ( F) to IEC 0751 Pt (18) 0. (0.54) ( ) Pt (18) 0.15 (0.7) ( ) Pt Pt (18) 0.1 (0.18) ( ) Pt (18) 0.15 (0.7) ( ) Pt (18) 0.15 (0.7) ( ) to JIS C Pt (18) 0. (0.54) ( ) Pt (18) 0.15 (0.7) ( ) Pt Pt (18) 0.1 (0.18) ( ) Pt (18) 0.15 (0.7) ( ) Pt (18) 0.15 (0.7) ( ) Ni 5 to Ni (18) 0.1 (0.18) ( ) /0 Siemens FI US Edition

31 Siemens AG 017 Resistance-based sensors Input Measuring range Min. measured span Digital accuracy Ω Ω Ω Resistance Resistance Transmitters for rail mounting SITRANS TR00 two-wire system, universal Thermocouples Input Measuring range Min. measured Digital span accuracy C/( F) C ( F) C ( F) Type B (180) 1) (.) 1) (... 08) Type C (W5) (180) (.) ( ) Type D (W) (180) 1 ) (1.8) ) ( ) Type E (90) 1 (1.8) ( ) Type J (90) 1 (1.8) ( ) Type K (90) 1 (1.8) ( ) Type L (90) 1 (1.8) ( ) Type N (90) 1 (1.8) ( ) Type R (180) (.) ( ) Type S (180) (.) ( ) Type T (7) 1 (1.8) ( ) Type U (90) (.) ( ) 1) The digital accuracy in the range 0 to 00 C ( to 57 F) is C (5.4 F). ) The digital accuracy in the range 1750 to 00 C (18 to 417 F) is C (. F). mv sensor Input Measuring range Min. measured span mv mv μv mv sensor mv sensor Digital accuracy The digital accuracy is the accuracy after the analog/digital conversion including linearization and calculation of the measured value. An additional error is generated in the output current 4 to 0 ma as a result of the digital/analog conversion of 0.05 % of the set span (digital-analog error). The total error under reference conditions at the analog output is the sum from the digital error and the digital-analog error (poss. with the addition of cold junction errors in the case of thermocouple measurements). Siemens FI US Edition /1

32 Siemens AG 017 Transmitters for rail mounting SITRANS TR00 two-wire system, universal Selection and Ordering data Temperature transmitter SITRANS TR00 For mounting on a standard DIN rail, two-wire system, 4 to 0 ma, programmable, with electrical isolation, with documentation on MiniDVD Without explosion protection With explosion protection to ATEX Further designs Please add "-Z" to Article No. with and specify Order codes(s). With test protocol (5 measuring points) Functional safety SIL Functional safety SIL/ Customer-specific programming Add "-Z" to Article No. and specify Order code(s) Article No. 7NG0-0JN00 7NG0-1JN00 Order code C11 C0 C Measuring range to be set Y01 1) Specify in plain text (max. 5 digits): Y01:... to... C, F Measuring point no. (TAG), max. 8 characters Y17 ) Measuring point descriptor, max. 1 characters Y ) Measuring point message, max. characters Y4 ) Text on front label, max. 1 characters Y9 )) Pt100 (IEC) -wire, R L = 0 Ω U0 4) Pt100 (IEC) -wire U0 4) Pt100 (IEC) 4-wire U04 4) Thermocouple type B U0 4)5) Thermocouple type C (W5) U1 4)5) Thermocouple type D (W) U 4)5) Thermocouple type E U 4)5) Thermocouple type J U4 4)5) Thermocouple type K U5 4)5) Thermocouple type L U 4)5) Thermocouple type N U7 4)5) Thermocouple type R U8 4)5) Thermocouple type S U9 4)5) Thermocouple type T U0 4)5) Thermocouple type U U1 4)5) With TC: CJC external (Pt100, -wire) U41 With TC: CJC external with fixed value, specify Y50 in plain text Special differing customer-specific programming, Y09 ) specify in plain text Fail-safe value. ma (instead of.8 ma) U ) Accessories Modem for SITRANS TH100, TH00, TR00 and TF with TH00 incl. SIPROM T parameterization software With USB connection MiniDVD for temperature measuring instruments for With documentation in German, English, French, Spanish, Italian, Portuguese and SIPROM T parameterization software Supply units see Chapter "Supplementary Components". Ordering example 1: 7NG0-0JN00-Z Y01+Y17+Y9+U0 Y01: C Y17: TICA1 Y9: TICA1 Ordering example : 7NG0-0JN00-Z Y01+Y17+Y+Y9+U5 Y01: C Y17: TICA1 Y: TICA1HEAT Y9: TICA1HEAT Factory setting: Pt100 (IEC 751) with -wire circuit Measuring range: C ( 1 F) Fault current:.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s Article No. 7NG09-8KU A5E ) For customer-specific programming for RTD and TC, the start value and the end value of the required measuring span must be specified here. ) For this selection, Y01 or Y09 must also be selected. ) Text on front plate is not saved in the device. 4) For this selection, Y01 must also be selected. 5) Internal cold junction compensation is selected as the default for TC. ) For customer-specific programming, for example mv and ohm, the start value and the end value of the required measuring span and the unit must be entered here. / Siemens FI US Edition

33 Siemens AG 017 Transmitters for rail mounting SITRANS TR00 two-wire system, universal Dimensional drawings Schematics.5 (0.89) 4 1 TEST 4..0mA SIEMENS SITRANS TR TEST 4..0mA SIEMENS 99 (.9) SITRANS TR00 Made in Croatia x TC sensor with int./fixed CJC + + S1 S RTD or R W sensor RTD or R W sensor RTD or R 4W sensor TC sens. with int./fixed CJC U sensor + TC sensor with external W RTD CJC S1 x RTD or R W sensor S 5 s Connection Plan mA loop & test +UB TC sensor with external W RTD CJC 114 (4.49) TEST A Asssignments 1 (+) and (-) Test terminals (test) for measurement of the output current with a multimeter (+) and 4 (-) Power supply U aux, output current I out 5,, 7 and 8 Sensor assignment, see schematics SITRANS TR00, dimensions in mm (inch) SITRANS TR00, pin assignment Siemens FI US Edition /

34 Siemens AG 017 Transmitters for rail mounting SITRANS TR00 two-wire system, universal Resistance thermometer Resistance Thermocouple RTD Two-wire system 1) Two-wire system R TC - + 1) Cold junction compensation internal/fixed value TC - + RTD Three-wire system R Three-wire system RTD Cold junction compensation with external Pt100 in two-wire system 1) RTD Four-wire system R Four-wire system TC - + RTD Cold junction compensation with external Pt100 in three-wire system RTD RTD1 Generation of average value/difference 1) 1) Programmable line resistance for the purpose of correction. R R1 Generation of average value/difference 1) TC1 TC - + Generation of average value / difference with internal cold junction compensation Voltage measurement Current measurement Test terminals Power supply/ ma (U aux ) + A - U aux U R - + I SITRANS TR00, sensor connection assignment /4 Siemens FI US Edition

35 Siemens AG 017 Overview Transmitters for rail mounting SITRANS TR00 two-wire system, universal, HART Application SITRANS TR00 transmitters can be used in all industrial sectors. Their compact design enables simple mounting on standard DIN rails on-site in protective boxes or in control cabinets. The following sensors/signal sources can be connected over their universal input module: Resistance thermometers (, or 4-wire system) Thermocouples Resistance-based sensors and DC voltage sources The output signal is a direct current from 4 to 0 ma in accordance with the sensor characteristic, superimposed by the digital HART signal. Transmitters of the "intrinsically safe" type of protection can be installed within potentially explosive atmospheres. The devices comply with the Directive 94/9/EC (ATEX). "HART" to beat - the universal SITRANS TR00 transmitter Two-wire devices for 4 to 0 ma, HART Device for rail mounting Universal input for virtually any type of temperature sensor Configurable over HART Benefits Compact design Electrically isolated Test sockets for multimeters Diagnostics LED (green/red) Sensor monitoring open circuits and short-circuits Self-monitoring Configuration status stored in EEPROM Expanded diagnostic functions, such as slave pointer, operating hours counter, etc. Special characteristic Electromagnetic compatibility to EN 1 and NE1 SIL (with Order Code C0), SIL/ (with C) Function The SITRANS TR00 is configured over HART. This can be done using a handheld communicator or even more conveniently with a HART modem and the SIMATIC PDM parameterization software. The configuration data are then permanently stored in the non-volatile memory (EEPROM). Once the sensors and power supply have been correctly connected, the transmitter outputs a temperature-linear output signal and the diagnostics LED displays a green light. In the case of a sensor short-circuit, the LED flashes red, an internal device fault is indicated by a steady red light. The test socket can be used to connect an ammeter at any time for monitoring purposes and plausibility checks. The output current can be read without any interruption, or even without opening the current loop. SITRANS TR00/TR00 Sensor TC/RTD 1 7 Test A D µc1 µc 4 5 D A ma U aux, I out 1 Sensor such as resistance thermometer, thermocouple, resistance-based, sensor, mv sensor Analog-digital converter Microcontroller, secondary circuit 4 Electrical isolation 5 Microcontroller, primary circuit Digital-analog converter 7 LED Auxiliary power supply Output current Test Test terminals for temporary connection of an amperemeter U aux I out SITRANS TR00 function diagram Siemens FI US Edition /5

36 Siemens AG 017 Transmitters for rail mounting SITRANS TR00 two-wire system, universal, HART Technical specifications Input Resistance thermometer Measured variable Temperature Sensor type to IEC 0751 Pt5 Pt1000 to JIS C 104; a=0.009 K -1 Pt5 Pt1000 to IEC 0751 Ni5 Pt1000 Special type over special characteristic (max. 0 points) Sensor factor (adaptation of the basic type, e.g. Pt100 to version Pt ) Units C or F Connection Standard connection 1 resistance thermometer (RTD) in -wire, -wire or 4-wire system Generation of average value identical resistance thermometers in -wire system for generation of average temperature Generation of difference identical resistance thermometers (RTD) in -wire system (RTD 1 RTD or RTD RTD 1) Interface Two-wire system Parameterizable line resistance 100 Ω (loop resistance) Three-wire system No balancing required Four-wire system No balancing required Sensor current 0.45 ma Response time T 50 ms for 1 sensor with opencircuit monitoring Open-circuit monitoring Always active (cannot be isabled) Short-circuit monitoring can be switched on/off (default value: ON) Measuring range parameterizable (see table "Digital measuring errors") Min. measured span 10 C (18 F) Characteristic curve Temperature-linear or special characteristic Resistance-based sensors Measured variable Actual resistance Sensor type Resistance-based, potentiometers Units Ω Connection Normal connection 1 resistance-based sensor (R) in -wire, -wire or 4-wire system Generation of average value resistance-based sensors in -wire system for generation of average value Generation of difference resistance thermometers in -wire system (R1 R or R R1) Interface Two-wire system Parameterizable line resistance 100 Ω (loop resistance) Three-wire system No balancing required Four-wire system No balancing required Sensor current 0.45 ma Response time T 50 ms for 1 sensor with opencircuit monitoring Open-circuit monitoring Always active (cannot be disabled) Short-circuit monitoring can be switched on/off (default value: OFF) Measuring range parameterizable max Ω (see table "Digital measuring errors") Min. measured span Ω (see table "Digital measuring errors") Characteristic curve Resistance-linear or special characteristic Thermocouples Measured variable Temperature Sensor type (thermocouples) Type B Pt0Rh-PtRh to DIN IEC 584 Type C W5 %-Re acc. to ASTM 988 Type D W %-Re acc. to ASTM 988 Type E NiCr-CuNi to DIN IEC 584 Type J Fe-CuNi to DIN IEC 584 Type K NiCr-Ni to DIN IEC 584 Type L Fe-CuNi to DIN 4710 Type N NiCrSi-NiSi to DIN IEC 584 Type R Pt1Rh-Pt to DIN IEC 584 Type S Pt10Rh-Pt to DIN IEC 584 Type T Cu-CuNi to DIN IEC 584 Type U Cu-CuNi to DIN 4710 Units C or F Connection Standard connection 1 thermocouple (TC) Generation of average value thermocouples (TC) Generation of difference thermocouples (TC) (TC1 TC or TC TC1) Response time T 50 ms for 1 sensor with opencircuit monitoring Open-circuit monitoring Can be switched off Cold junction compensation Internal With integrated Pt100 resistance thermometer External With external Pt100 IEC 0571 (-wire or -wire connection) External fixed Cold junction temperature can be set as fixed value Measuring range parameterizable (see table "Digital measuring errors") Min. measured span Min C ( F) (see table "Digital measuring errors") Characteristic curve Temperature-linear or special characteristic mv sensor Measured variable DC voltage Sensor type DC voltage source (DC voltage source possible over an externally connected resistor) Units mv Response time T 50 ms for 1 sensor with opencircuit monitoring Open-circuit monitoring Can be switched off / Siemens FI US Edition

37 Siemens AG 017 Measuring range Min. measured span Overload capability of the input Input resistance Characteristic curve Output Output signal Auxiliary power Max. load Overrange Error signal (e.g. following sensor fault) (conforming to NE4) Sample cycle Damping parameterizable max mv mv or 0mV V DC 1MΩ Voltage-linear or special characteristic ma, -wire with communication acc. to HART Rev V DC (to 0 V for Ex i/ic; to V for Ex na) (U aux 11 V)/0.0 A.... ma, infinitely adjustable (default range: ma).... ma, infinitely adjustable (default value:.8 ma) 0.5 s nominal Software filter 1st order s (parameterizable) Against reversed polarity Protection Electrical isolation Input against output (1 kv eff ) Measuring accuracy Digital measuring errors see table "Digital measuring errors" Reference conditions Auxiliary power 4 V ± 1 % Load 500 Ω Ambient temperature C Warming-up time > 5 min Error in the analog output (digital/analog converter) < 0.05 % of span Error due to internal cold junction < 0.5 C (0.9 F) Ambient temperature effect Analog measuring errors of span < 0. % of max. span/10 C (18 F) Digital measuring errors - at resistance thermometers 0.0 C (0.11 F)/10 C (18 F) - at thermocouples 0. C (1.1 F)/10 C (18 F) Auxiliary power effect < % of span/v Effect of load impedance < 0.00 % of span/100 Ω Long-term drift In the first month < 0.0 % of span in the first month After one year < 0. % of span after one year After 5 years < 0. % of span after 5 years Conditions of use Ambient conditions Ambient temperature range C( F) Storage temperature range C( F) Relative humidity < 98 %, with condensation Electromagnetic compatibility acc. to EN 1 and NE1 Design Material Plastic, electronic module potted Weight 1 g Dimensions See "Dimensional drawings" Cross-section of cables Max..5 mm² (AWG 1) Degree of protection to IEC 059 Enclosure IP0 Transmitters for rail mounting SITRANS TR00 two-wire system, universal, HART Certificates and approvals Explosion protection ATEX EC type test certificate "Intrinsic safety" type of protection Type of protection, "equipment is non-arcing" Other certificates PTB 07 ATEX 0X II (1) G Ex ia/ib IIC T/T4 II (1) G Ex ia/ic IIC T/T4 II G Ex ic IIC T/T4 II (1) D Ex iad/ibd 0/1 T115 C II G Ex na IIC T/T4 NEPSI Factory setting: Pt100 (IEC 751) with -wire circuit Measuring range: C (... 1 F) Error signal in the event of sensor breakage:.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s Siemens FI US Edition /7

38 Siemens AG 017 Transmitters for rail mounting SITRANS TR00 two-wire system, universal, HART Digital measuring errors Resistance thermometer Input Measuring range Min. measured span Digital accuracy C / ( F) C ( F) C ( F) to IEC 0751 Pt (18) 0. (0.54) ( ) Pt (18) 0.15 (0.7) ( ) Pt Pt (18) 0.1 (0.18) ( ) Pt (18) 0.15 (0.7) ( ) Pt (18) 0.15 (0.7) ( ) to JIS C Pt (18) 0. (0.54) ( ) Pt (18) 0.15 (0.7) ( ) Pt Pt (18) 0.1 (0.18) ( ) Pt (18) 0.15 (0.7) ( ) Pt (18) 0.15 (0.7) ( ) Ni 5 to Ni (18) 0.1 (0.18) ( ) Resistance-based sensors Input Measuring range Min. measured span Digital accuracy Ω Ω Ω Resistance Resistance Thermocouples Input Measuring range Min. measured span Digital accuracy C / ( F) C ( F) C ( F) Type B (180) 1) (.) 1) (... 08) Type C (W5) (180) (.) ( ) Type D (W) (180) 1 ) (1.8) ) ( ) Type E (90) 1 (1.8) ( ) Type J (90) 1 (1.8) ( ) Type K (90) 1 (1.8) ( ) Type L (90) 1 (1.8) ( ) Type N (90) 1 (1.8) ( ) Type R (180) (.) ( ) Type S (180) (.) ( ) Type T (7) 1 (1.8) ( ) Type U (90) (.) ( ) 1) The digital accuracy in the range 0 to 00 C ( to 57 F) is C (5.4 F). ) The digital accuracy in the range 1750 to 00 C (18 to 417 F) is C (. F). mv sensor Input Measuring range Min. measured span mv mv μv mv sensor mv sensor Digital accuracy The digital accuracy is the accuracy after the analog/digital conversion including linearization and calculation of the measured value. An additional error is generated in the output current 4 to 0 ma as a result of the digital/analog conversion of 0,05 % of the set span (digital-analog error). The total error under reference conditions at the analog output is the sum from the digital error and the digital-analog error (poss. with the addition of cold junction errors in the case of thermocouple measurements). /8 Siemens FI US Edition

39 Siemens AG 017 Selection and Ordering data Temperature transmitter SITRANS TR00 For mounting on a standard DIN rail, two-wire system, 4 0 ma, HART, with electrical isolation, with documentation on MIniDVD Without explosion protection With explosion protection to ATEX Further designs Please add "-Z" to Article No. with and specify Order codes(s). With test protocol (5 measuring points) Functional safety SIL Functional safety SIL/ Customer-specific programming Add "-Z" to Article No. and specify Order code(s) Article No. 7NG0-0JN00 7NG0-1JN00 Order code C11 C0 C Measuring range to be set Y01 1) Specify in plain text (max. 5 digits): Y01:... to... C, F Measuring point no. (TAG), max. 8 characters Y17 ) Measuring point descriptor, max. 1 characters Y ) Measuring point message, max. characters Y4 ) Text on front label, max. 1 characters Y9 )) Pt100 (IEC) -wire, R L = 0 Ω U0 4) Pt100 (IEC) -wire U0 4) Pt100 (IEC) 4-wire U04 4) Thermocouple type B U0 4)5) Thermocouple type C (W5) U1 4)5) Thermocouple type D (W) U 4)5) Thermocouple type E U 4)5) Thermocouple type J U4 4)5) Thermocouple type K U5 4)5) Thermocouple type L U 4)5) Thermocouple type N U7 4)5) Thermocouple type R U8 4)5) Thermocouple type S U9 4)5) Thermocouple type T U0 4)5) Thermocouple type U U1 4)5) With TC: CJC external (Pt100, -wire) U41 With TC: CJC external with fixed value, specify Y50 in plain text Special differing customer-specific programming, Y09 ) specify in plain text Fail-safe value. ma (instead of.8 ma) U ) Transmitters for rail mounting SITRANS TR00 two-wire system, universal, HART Accessories Article No. MiniDVD for temperature measuring instruments A5E00451 With documentation in German, English, French, Spanish, Italian, Portuguese and SIPROM T parameterization software HART modem With USB connection 7MF4997-1DB Simatic PDM operating software See Section 8 1) For customer-specific programming for RTD and TC, the start value and the end value of the required measuring span must be specified here. ) For this selection, Y01 or Y09 must also be selected. ) Text on front plate is not saved in the device. 4) For this selection, Y01 must also be selected. 5) Internal cold junction compensation is selected as the default for TC. ) For customer-specific programming, for example mv and ohm, the start value and the end value of the required measuring span and the unit must be entered here. Supply units see Chapter "Supplementary Components". Ordering example 1: 7NG0-0JN00-Z Y01+Y17+Y9+U0 Y01: C Y17: TICA1 Y9: TICA1 Ordering example : 7NG0-0JN00-Z Y01+Y17+Y+Y9+U5 Y01: C Y17: TICA1 Y: TICA1HEAT Y9: TICA1HEAT Factory setting: Pt100 (IEC 751) with -wire circuit Measuring range: C (... 1 F) Error signal in the event of sensor breakage:.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s Siemens FI US Edition /9

40 Siemens AG 017 Transmitters for rail mounting SITRANS TR00 two-wire system, universal, HART Dimensional drawings.5 (0.89) 99 (.9) TEST +UB A S + S1 S S1 x RTD or R W sensor TC sens. with int./fixed CJC U sensor (4.49) 1 4 TEST 4..0mA SIEMENS SITRANS TR s Connection Plan 4..0mA loop & test x TC sensor with int./fixed CJC RTD or R W sensor RTD or R W sensor RTD or R 4W sensor TC sensor with external W RTD CJC TC sensor with external W RTD CJC Made in Croatia SITRANS TR00, dimensions in mm (inch) Schematics 1 TEST mA SIEMENS SITRANS TR Assignments 1 (+) and (-) Test terminals (Test) for measurement of the output current with a multimeter (+) and 4 (-) Power supply U aux, Output current I out 5,, 7 and 8 Sensor assignment, see schematics SITRANS TR00, pin assignment /40 Siemens FI US Edition

41 Siemens AG 017 Transmitters for rail mounting SITRANS TR00 two-wire system, universal, HART Resistance thermometer Resistance Thermocouple RTD Two-wire system 1) Two-wire system R TC - + 1) Cold junction compensation internal/fixed value TC - + RTD Three-wire system R Three-wire system RTD Cold junction compensation with external Pt100 in two-wire system 1) RTD Four-wire system R Four-wire system TC - + RTD Cold junction compensation with external Pt100 in three-wire system RTD RTD1 Generation of average value/difference 1) 1) Programmable line resistance for the purpose of correction. R R1 Generation of average value/difference 1) TC1 TC - + Generation of average value / difference with internal cold junction compensation Voltage measurement Current measurement Test terminals Power supply/ ma (U aux ) + A - U aux U R - + I SITRANS TR00, sensor connection assignment Siemens FI US Edition /41

42 Siemens AG 017 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Overview Temperature-linear characteristic can be selected for all temperature sensors Automatic correction of zero and span Monitoring of sensor and cable for open-circuit and short- circuit Sensor fault and/or limit can be output via an optional sensor fault/limit monitor Hardware write protection for HART communication Diagnostic functions Slave pointer functions SIL1 Mode of operation TC RTD 9 The user-friendly transmitters for the control room The SITRANS TW universal transmitter is a further development of the service-proven SITRANS T for the 4-wire system in a mounting rail housing. With numerous new functions it sets new standards for temperature transmitters. With its diagnostics and simulation functions the SITRANS TW provides the necessary insight during commissioning and operation. And using its HART interface the SITRANS TW can be conveniently adapted with SIMATIC PDM to every measurement task. All SITRANS TW control room devices are available in a non-intrinsically safe version as well as in an intrinsically safe version for use with the most stringent requirements. Application The SITRANS TW transmitter is a four-wire rail-mounted device with a universal input circuit for connection to the following sensors and signal sources: Resistance thermometer Thermocouples Resistance-based sensors/potentiometers mv sensors As special version: -V sources - Current sources The 4-wire rail-mounted SITRANS TW transmitter wire is designed for control room installation. It must not be mounted in potentially explosive atmospheres. All SITRANS TW control room devices are available in a non-intrinsically safe version as well as in an intrinsically safe version for use with the most stringent requirements. Function Features Transmitter in four-wire system with HART interface Housing can be mounted on 5 mm rail or mm G rail Screw plug connector All circuits electrically isolated Output signal: 0/4to0mA or 0/to10V Power supplies: 115/0 V AC/DC or 4 V AC/DC Explosion protection [EEx ia] or [EEx ib] for measurements with sensors in the hazardous area Temperature-linear characteristic for all temperature sensors 8 4 A μc D 1 EEPROM 5 Power supply unit 7 D A Output U or I HART modem/ communicator Current test 0/ ma The signal output by a resistance-based sensor (two-wire, threewire, four-wire system), voltage source, current source or thermocouple is converted by the analog-to-digital converter (1, function diagram) into a digital signal. This is evaluated in the microcontroller (), corrected according to the sensor characteristic, and converted by the digital-to-analog converter () into an output current (0/4 to 0 ma) or output voltage (0/ to 10 V). The sensor characteristics as well as the electronics data and the data for the transmitter parameters are stored in the non-volatile memory (). AC or DC voltages can be used as the power supply (1). Any terminal connections are possible for the power supply as a result of the bridge rectifier in the power supply unit. The PE conductor is required for safety reasons. A HART modem or a HART communicator permit parameterization of the transmitter using a protocol according to the HART specification. The transmitter can be directly parameterized at the point of measurement via the HART output terminals (10). The operation indicator (4) identifies a fault-free or faulty operating state of the transmitter. The limit monitor (9) enables the signaling of sensor faults and/or limit violations. In the case of a current output, the current can be checked on a meter connected to test socket (1). Diagnosis and simulation functions The SITRANS TW comes with extensive diagnosis and simulation functions. Physical values can be defined with the simulation function. It is thus possible to check the complete signal path from the sensor input to inside the control system without additional equipment. The slave pointer functions are used to record the minimum and maximum of the plant s process variable A U H /4 Siemens FI US Edition

43 Siemens AG 017 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Integration System configuration U H ma SITRANS TW transmitter SIMATIC S7-400 Control system HART communicator or A HART modem Possible system configurations The SITRANS TW transmitter as a four-wire rail-mounted device can be used in a number of system configurations: as a standalone version or as part of a complex system environment, e.g. with SIMATIC S7. All device functions are available via HART communication. Communication options through the HART interface: HART communicator HART modem connected to PC/laptop on which the appropriate software is available, e.g. SIMATIC PDM HART-compatible control system (e.g. SIMATIC S7-400 with ET 00M) or ET 00M Load RS--C SIMATIC PDM PC/laptop with SIMATIC PDM Technical specifications Input Selectable filters to suppress the line frequency 50 Hz, 0 Hz, also 10 Hz for special applications (line frequency filter is similar with measuring frequency) Resistance thermometer Measured variable Temperature Measuring range Parameterizable Measuring span min. 5 C (45 F) x 1/scaling factor Sensor type Acc. to IEC 751 Pt100 (IEC 751) Acc. to JIS C Pt100 (JIS C104-81) to DIN 470 Ni100 (DIN 470) Special type (R RTD 500 Ω) Multiples or parts of the defined characteristic values can be parameterized (e.g. Pt500, Ni10) Characteristic curve Temperature-linear, resistance-linear or customer-specific Type of connection Normal connection Sum or parallel connection Mean-value or differential connection Interface, or 4-wire circuit Measuring range limits Depending on type of connected thermometer (defined range of resistance thermometer) Sensor breakage monitoring Monitoring of all connections for open-circuit (function can be switched off) Sensor short-circuit monitoring Parameterizable response threshold (function can be switched off) Resistance-based sensor, potentiometer Measured variable Actual resistance Measuring range Parameterizable Measuring span min. 10 Ω Characteristic curve Resistance-linear or customerspecific Type of connection Normal connection Differential connection Mean-value connection Interface, or 4-wire circuit Input range Ω; with mean-value and difference circuits: Ω Sensor breakage monitoring Monitoring of all connections for open-circuit (function can be switched off) Sensor short-circuit monitoring Parameterizable response threshold (function can be switched off) Siemens FI US Edition /4

44 Siemens AG 017 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Thermocouples μa-, ma sources Measured variable Temperature Measured variable DC voltage Measuring range Parameterizable Measuring range Parameterizable Measuring span Measuring range limits Thermocouple element min. 50 C (90 F) x 1/scaling factor Depend. on type of thermocouple element Type B: Pt0 %Rh/Pt %Rh (DIN IEC 584) Characteristic curve Input range/min. span Devices with 7NG4-xxxx4 Devices with 7NG4-xxxx5 Devices with 7NG4-xxxx Current-linear or customer- specific μa/0.4 μa μa/4 μa ma/0.04 ma Type C: W5 %-Re (ASTM 988) Type D: W %-Re (ASTM 988) Type E: NiCr/CuNi (DIN IEC 584) Type J: Fe/CuNi (DIN IEC 584) Type K: NiCr/Ni (DIN IEC 584) Type L: Fe-CuNi (DIN 4710) Type N: NiCrSi-NiSi (DIN IEC 584) Type R: Pt1 %Rh/Pt (DIN IEC 584) Devices with 7NG4-xxxx7 or 7NG4-xxxx0 with U/I plug Devices with 7NG4-xxxx8 Sensor breakage monitoring Output Output signal Current 0/ ma ma/0.4 ma ma/4 ma Not possible Load-independent direct current 0/ ma, can be switched to load-independent DC voltage 0/ V using plug-in jumpers Type S: Pt10 %Rh/Pt (DIN IEC 584) Overrange ma, continuously adjustable Type T: Cu/CuNi (DIN IEC 584) Type U: Cu/CuNi (DIN 4710) Special type (-10 mv UTC 100 mv) Output range following sensor fault (conforming to NE4) Load No-load voltage ma, continuously adjustable 50 Ω 0 V Characteristic curve Type of connection Temperature-linear, voltage-linear or customer-specific Normal connection Averaging connection Mean-value connection Differential connection Voltage 0/ V Overrange Output range following sensor fault Load resistance V, continuously adjustable V, continuously adjustable 1 kω Cold junction compensation Sensor breakage monitoring mv sensors Measured variable Measuring range None, internal measurement, external measurement or predefined fixed value Function can be switched off DC voltage Parameterizable Load capacitance 10 nf Short-circuit current 100 ma (not permanently shortcircuit-proof) Electrical damping - adjustable time constant T s, in steps of 0.1 s Current source/voltage source Continuously adjustable within the total operating range Measuring span Input range Characteristic curve min. 4 mv mV Voltage-linear or customer-specific Sensor fault/limit signalling Operation indicator Limit violation By operation indicator, relay output or HART interface Flashing signal Flashing frequency 5 Hz Overload capacity of inputs max. ±.5 V Sensor fault monitoring Flashing frequency 1 Hz Input resistance Sensor current Sensor breakage monitoring V sources Measured variable Measuring range Characteristic curve Input range/min. span Devices with 7NG4-xxxx1 or 7NG4-xxxx0 with U/I plug Devices with 7NG4-xxxx Devices with 7NG4-xxxx Sensor breakage monitoring 1MΩ Approx. 180 μa Function can be switched off DC voltage Parameterizable Voltage-linear or customer-specific V/0.04 V V/0.4 V V/4.0 V Not possible Relay outputs Switching capacity Switching voltage Switching current Sensor fault monitoring Limit monitoring Operating delay Monitoring functions of limit module Either as NO or NC contact with 1 changeover contact 150 W, 5 VA 15 V DC, 50 V AC.5 A DC Signalling of sensor or line breakage and sensor short-circuit s Sensor fault (breakage and/or short-circuit) Lower and upper limit Window (combination of lower and upper limits) Limit and sensor fault detection can be combined Hysteresis Parameterizable between 0 and 100 % of measuring range /44 Siemens FI US Edition

45 Siemens AG 017 Auxiliary power Universal power supply unit 115/0 V AC/DC or 4 V AC/DC Tolerance range for power supply With 115/0 V AC/DC PSU V DC; V AC With 4 V AC/DC PSU V DC; V AC (in each case interruption-resistant up to 0 ms in the complete tolerance range) Tolerance range for mains frequency Hz Power consumption with 0 V AC 5 VA 0 V DC 5W 4 V AC 5 VA 4 V DC 5W Electrically isolated Electrically isolated circuits Input, output, power supply and sensor fault/limit monitoring output are electrically isolated from one another. The HART interface is electrically connected to the output. Working voltage between all electrically isolated circuits The voltage U rms between any two terminals must not exceed 00 V Measuring accuracy Accuracy Error in the internal cold junction C ± 0.1 C / 10 C ( 5.4 F ± 0.18 F / 18 F) Error of external cold junction terminal 7NG09-8AV Digital output Analog output I AN or U AN Influencing effects (referred to the digital output) Temperature drift Long-term drift Influencing effects referred to the analog output I AN or U AN Temperature drift Power supply Load with current output Load with voltage output Long-term drift (start-of-scale value, span) Response time (T without electrical damping) Electromagnetic compatibility 0.5 C ± 0.1 C / 10 C ( 0.9 F ± 0.18 F / 18 F) See "Digital error" 0.05 % of the span plus digital error Compared to the max. span: 0.08 % / 10 C ( 0.08 % /18 F) 0. % in the range C( F) 0.1 % / year Compared to the span: 0.08 % / 10 C ( 0.08 % / 18 F) 0. % in the range C( F) 0.05 % / 10 V 0.05 % on change from 50 Ω to 50 Ω 0.1 % on change in the load current from 0 ma to 10 ma 0.0 % / month 0. s According to EN 1 and NAMUR NE1 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Certificates and approvals ATEX To DIN EN 50014: 1997, EN 5000: 1994 Intrinsic safety to EN for 7NG4-xAxxx II (1) G D [EEx ia/ib ] IIB for 7NG4-xBxxx II (1) G D [EEx ia/ib ] IIC EC type-examination certificate TÜV (German Technical Inspectorate) 01 ATEX 175 Other certificates GOST, NEPSI Conditions of use Installation conditions Location (for devices with explosion protection) Transmitters Outside the potentially explosive atmosphere Sensor Within the potentially explosive atmosphere zone 1 (also in zone 0 in conjunction with the prescribed protection requirements for the sensor) Ambient conditions Permissible ambient temperature C ( F) Permissible storage temperature C ( F) Climatic class Relative humidity %, no condensation Design Weight Approx. 0.4 kg (0.5 lb) Enclosure material PBT, glass-fibre reinforced Degree of protection to IEC 59 IP0 Degree of protection to VDE 0100 Protection class I Type of installation 5-mm DIN rail (1.8 inch) (EN 500) or -mm G-type rail (1. inch) (EN 5005) Electrical connection / process connection Parameterization interface Screw plug connectors, max..5 mm² (0.01 inch²) Protocol HART, version 5.9 Load with connection of HART communicator Ω HART modem Ω Software for PC/laptop SIMATIC PDM version V5.1 and later Siemens FI US Edition /45

46 Siemens AG 017 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Digital error Resistance thermometer Input Measuring range Max. permissible Digital error line resis- tance C / ( F) Ω C / ( F) IEC 751 Pt (5.4) ( ) Pt (1.1) ( ) Pt (0.5) ( ) Pt (1.1) ( ) Pt (1.8) ( ) Pt (1.8) ( ) JIS C Pt (5.4) ( ) Pt (1.1) ( ) Pt (0.5) ( ) DIN 470 Ni (0.5) ( ) Ni (0.5) ( ) Ni (0.5) ( ) Ni (0.5) ( ) Resistance-based sensors Input Resistance (linear) Measuring range Max. permissible line resistance Ω Ω Ω Digital error Thermocouples Input Measuring range Digital error 1) C / ( F) C ( F) Type B (5.4) ( ) Type C (.) ( ) Type D (1.8) ( ) Type E (1.8) ( ) Type J (1.8) ( ) Type K (1.8) ( ) Type L (.) ( ) Type N (1.8) ( ) Type R (.) ( ) Type S (.) ( ) Type T (1.8) ( ) Type U (.) ( ) 1) Accuracy data refer to the largest error in the complete measuring range Voltage/current sources Input Measuring range Digital error mv sources (linear) mv μv V sources (linear) V mv μa/ma sources μa/ma μa (linear) μa μa ma ma ma 500 /4 Siemens FI US Edition

47 Siemens AG 017 Ordering examples Desired transmitter Parameter: Ordering Standard Special design Example 1: SITRANS TW, transmitter in four-wire system with explosion protection ATEX 0 V AC/DC power supply current output without sensor fault/limit monitor - Sensor PT100, three-wire circuit X - Measuring range C X - Temperature-linear characteristic X - Filter time 1 s X - Output ma, line filter 50 Hz X - Output driven to full-scale in event X of like breakage Example : SITRANS TW, transmitter in four-wire system without explosion protection 4 V AC/DC power supply Voltage output Sensor fault/limit monitor - Rating plate in English S7 - Sensor NiCr/Ni, type K A05 - Cold junction internal X - Measuring range C Y0 - Temperature-linear characteristic X - Filter time 1 s X - Output V, line filter 50 Hz H10 - Output driven to full-scale in event X of like breakage - Limit monitoring switched off X Example : SITRANS TW, transmitter in four-wire system without explosion protection 4 V AC/DC power supply Current output without sensor fault/limit monitor - Voltage input, measuring A40 range -1. V V - Measuring range V Y - Source-proportional characteristic X - Filter time 10 s G07 - Output ma, line filter 0 Hz H11 - No monitoring for sensor fault (X) J0 7NG4-1AA00 (stock item) 7NG4-0BB10-Z Y01 + S7 + A05 + Y0 + H10 Y01: see Order code Y0: MA=0; ME= 950; D=C 7NG4-0BA01-Z Y01 + A40 + Y + G07 + H11 + J0 Y01: see Order code Y: MA=0; ME= 5; D=V Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Ordering information The article number structure shown below is used to specify a fully functioning transmitter. The selection of the operating data (type of source, measuring range, characteristic etc.) is made according to the following rules: Operating data already set in factory to default values: The default settings can be obtained from the list of parameterizable operating data (see "Special operating data"). The presets can be modified by the customer to match the requirements precisely. Operating data set on delivery according to customer requirements: Supplement the Article No. by "-Z" and add the Order code "Y01". The operating data to be set can be obtained from the list of parameterize operating data. The Order codes A 7 7 to K 7 7 for operating data to be set need only be specified in the order if they deviate from the default setting. The default setting is used if no Order code is specified for operating data. The selected parameters are printed on the transmitter's rating plate. Siemens FI US Edition /47

48 Siemens AG 017 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Selection and Ordering data Article No. SITRANS TW universal transmitter 7 N G for rail mounting, in four-wire system (order instruction manual separately) Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Explosion protection Without 0 For inputs [EEx ia] or [EEx ib] 1 Power supply 115/0 V AC/DC A 4 V AC/DC B Output signal 0/ ma (can be switched to A 0/ V) 0/ V (can be switched to B 0/ ma) Sensor fault/limit monitor Without (retrofitting not possible) 0 Relay with changeover contact 1 Input for Temperature sensor, resistance-based sensor and mv sensor with measuring range mv DC and with U/I plug Voltage input (V sources) 1) Measuring range: V DC V DC (not Ex version) V DC (not Ex version) Current input (μa, ma sources) 1) Measuring range: μa DC μa DC ma DC ma DC ma DC 8 Further designs Order code Please add "-Z" to Article No. and specify Order code(s) (see "List of parameterizable operating data"). Customer-specific setting of operating data Y01 (see "List of parameterizable operating data") Note: specify in plain text: see Order code Meas. point description (max. 1 char.) Y Text on front of device (max. char.) Y4 HART tag (max. 8 characters) Y5 With test report P01 With shorting plug to HART communication S01 for 0 ma or 0 V With plug for external cold junction compensation S0 With U/I plug S0 ( V DC or ma) Language of rating plate (together with Y01 Order Code only) Italian S7 English S7 French S77 Spanish S78 1) Observe max. values with Ex version. Selection and Ordering data Article No. Accessories MiniDVD for temperature measuring A5E00451 instruments With documentation in German, English, French, Spanish, Italian, Portuguese and SIPROM T parameterization software Instruction Manual for SITRANS TW German/English A5E French/Italian/Spanish A5E Cold junction terminal 7NG09-8AV U/I plug 7NG09-8AW ( V DC pr ma) SIMATIC PDM operating software See Chapter 8 HART modem With USB interface 7MF4997-1DB /48 Siemens FI US Edition

49 Siemens AG 017 List of parameterizable operating data (Order codes A B E 7 7) Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Operating data acc. to default setting Article No. with Order code: 7NG Z Y01 Order codes: A E Sensor Thermocouples Connection Cold junction Measuring Type Temperature range compensation ranges B: Pt0 %Rh/Pt %Rh C A 0 0 Standard B 0 1 None C C E 0 0 C:W5 %Re C A 0 1 Sum n 1) n = B 0 Internal C C E 0 1 D:W %Re C A Fixed val. 0 C C C E 0 E:NiCr/CuNi C A 0 n = 10 B C C C E 0 J:Fe/CuNi (IEC) C A 0 4 Difference ) Diff1 B 1 50 C C C E 0 4 K:NiCr/Ni C A 0 5 Diff B 0 C C C E 0 5 L: Fe/CuNi (DIN) C A 0 Mean-val. ) MW B C C C E 0 N:NiCrSi/NiSi C A 0 7 Special value 7) Y C E 0 7 R:Pt1 %Rh/Pt C A 0 8 External meas. Y C E 0 8 S:Pt10 %Rh/Pt C A 0 9 (through Pt100 DIN IEC 751) 7) C E 0 9 T:Cu/CuNi (IEC) C A C E 1 0 U:Cu/CuNi (DIN) C A C E 1 1 Resistance thermometer (or max. permissible line resistance see Technical specifications ) Connection Connection Line resistance C C C C E 1 E 1 E 1 4 E 1 5 Pt100 (DIN IEC) C A 0 Standard B 0 1 -wire-system C 0 Ω D C E 1 Pt100 (JIS) C A 1 Sum n 4) n = B 0 -wire-system C 10 Ω D C E 1 7 Ni100 (DIN) C A wire-system C 4 0 Ω D C E 1 8 n = 10 B Ω D C E 1 9 Parallel n 5) n = 0.1 B 1 Special val. 7) Y C E 0 n= 0. B C E 1 n= 0.5 B C E Special value ) 7) Y C E Difference ) Diff1 B 5 1 Diff B C E C E 5 Mean-val. ) MW B C E C C C C C C C C C Special range 7) E 7 E 8 E 9 E 0 E 1 E E E 4 E 5 Y 0 Resistance-based sensors, potentiometers (or max. permissible line resistance see Technical specifications ) Connection Connection Line resistance ) Measuring ranges A 0 Standard B 0 1 -wire-system C 0 Ω D Ω E 4 0 Difference ) Diff1 B 5 1 -wire-system C 10 Ω D Ω E 4 1 Diff B 5 4-wire-system C 4 0 Ω D Ω E 4 Mean val. ) MW B 1 50 Ω D Ω E 4 Special val. 7) Y Ω E Ω 8) E Ω 8) E 4 Special range 7) Y 1 mv, V and μa, ma sensors 9) A 4 0 Meas. range with Article No. 7NG Z Y01 E mv 1-1, V 10) 1) n = number of thermocouple elements to be connected in series V 10) ) See Circuit diagrams for meaning of type circuit V 10) ) Line resistance of channels 1 and, for max. permissible line resistance see μa 10) Technical specifications (only with C, not with C and C4) 4) μa 10) n = number of resistance thermometers to be connected in series 5) -1, ma 10) 1/n = number of resistance thermometers to be connected in parallel ) ma 10) Combination of series and parallel connection of resistance thermometers 7) ma 10) Operating data: see Special operating data 8) Special range 7) Y This range does not apply to mean-value and difference circuits. 9) The max. permissible currents and voltages according to conformity certificate must be observed in devices with explosion protection. 10) Without detection of line breakage Siemens FI US Edition /49

50 Siemens AG 017 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART List of parameterizable operating data (Order codes F K 7 7) Operating data according to default setting Article No. with Order code: 7NG Z Y01 Order codes: F K Sensor Thermocouple elements Voltage measurement Filter time 1) Output signal and line filter ) Failure signal Limit monitor ) Type Temperature range B: Pt0 %Rh/ C A 0 0 Temperaturelinear F s G ma/ with line break- C:W5 %Re C A s G V age/fault: D:W %Re C A 0 Voltage- F s G 0 with line filter: E:NiCr/CuNi C A 0 linear 0.5 s G 0 50 Hz H 0 0 to full scale J 0 0 J:Fe/CuNi (IEC) C A s G Hz H 0 1 to start of scale J 0 1 K:NiCr/Ni C A 0 5 s G Hz 4) H 0 hold last value J 0 Limit monitoring ineffective K 0 0 (but sensor fault signalling with closedcircuit operation) L: Fe/CuNi (DIN) C A 0 5 s G ma/ N:NiCrSi/NiSi C A s G V no monitoring J 0 R:Pt1 %Rh/Pt C A s G 0 8 with line filter: Effective 5) Y 7 0 S:Pt10 %Rh/Pt C A s G Hz H 1 0 Safety value 5) Y 0 T:Cu/CuNi (IEC) C A s G Hz H 1 1 U:Cu/CuNi (DIN) C A 1 1 Special time 5) Y Hz H 1 Resistance thermometer (max. permissible line resistances see Technical specifications ) Voltage measurement Pt100 (DIN IEC) C A 0 Temperaturelinear F 0 0 Pt100 (JIS) C A 1 Ni100 (DIN) C A Resistancelinear Filter time 1) same as for thermocouple elements Failure signal with line breakage/fault: Output signal and line filter ) same as for thermocou- F 0 ple elements to full scale J 0 0 to start of scale J 0 1 hold last value J 0 no monitoring J 0 Safety value 5) Y 0 with line breakage or short-circuit/fault: to full scale J 1 0 to start of scale J 1 1 hold last value J 1 no monitoring J 1 Safety value 5) Y 1 Limit monitor ) same as for thermocouple elements Resistance-based sensors, potentiometers (max. permissible line resistances see Technical specifications ) A 0 Voltage measurement Resistancelinear F 0 Filter time 1) same as for thermocouple elements Output signal and line filter ) same as for thermocouple elements Failure signal with line breakage/fault: to full scale J 0 0 to start of scale J 0 1 hold last value J 0 Limit monitor ) same as for thermocouple elements no monitoring J 0 Safety value 5) Y 0 mv, V and μa, ma sources A 4 0 Voltage measurement Source proportional F 0 Filter time 1) same as for thermocouple elements Output signal and line filter ) same as for thermocouple elements Limit monitor ) same as for thermocouple elements 1) Software filter to smooth the result ) Filter to suppress line disturbances on the measured signal. ) If signalling relay present 4) for special appliciations 5) Operating data: see Special operating data /50 Siemens FI US Edition

51 Siemens AG 017 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Special operating data Order code Plain text required Options Y00 N=. Factor N for multiplication with the characteristic values of resistance thermometers Range of values: 0.10 to Example: x Pt500 parallel: N = 5/ = 1.7;. Example: Ni10: N = 1. Y10 TV=. Temperature TV of the fixed cold junction D= Dimension; range of values: C, K, F, R Y11 RL=. Line resistance RL in Ω for compensation of cold junction line of external Pt100 DIN IEC 751 Range of values: 0.00 to Y0 Y0 Y1 Y RL1=. RL=. MA=. ME=. Line resistances RL of channel 1 (RL1) and channel (RL) in Ω if the resistance thermometer or the resistance-based sensor is connected in a two-wire system Range of values depending on type of sensor: 0.00 to Start-of-scale value MA and full-scale value ME for thermocouples and resistance thermometers (Range of values depending on type of sensor) D= Dimension, range of values: C, K, F, R) MA=. ME=. MA=. ME=. D= Start-of-scale value MA and full-scale value ME for resistance-based sensors or potentiometers in Ω Range of values: 0.00 to, Start-of-scale value MA and full-scale value ME for mv, V, µa and ma sources Range of values depending on type of sensor: to 1, Dimension (mv entered as MV, V as V, µa as UA, ma as MA) Y50 T=. Response time T of software filter in s Range of values: 0.0 to Safety value S of signal output in ma or in V corresponding to the set type of output. Range of values - with current output: to.00 - with voltage output: -0.5 to Y0 S=. Safety value S with line breakage of sensor Y1 S=. Safety value S with line breakage or shortcircuit of sensor Y70 UG=. OG=. H=. K= A= T=. Lower limit value (dimension as defined by measuring range) Upper limit value (dimension as defined by measuring range) Hysteresis (dimension as defined by measuring range) Switch on/off combination of limit function and sensor fault detection; J=on; N=off (standard: J) Type of relay output: A=open-circuit operation; R=closed-circuit operation (standard: R) Switching delay T of relay output in s Range of values: 0.0 to 10.0 (standard: 0.0) Siemens FI US Edition /51

52 Siemens AG 017 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Schematics Sensor input connections Connection diagram for the input signal Channel 1 is the measured variable between the terminals and on the input plug. With a difference or mean-value circuit, the calculation of the measured value is defined by the type of measurement. Otherwise the measured value is determined via channel 1. The following code is used for the type of measurement: type of measurement Calculation of measured value The short-circuit jumpers shown in the circuits must be inserted in the respective system on site. Single channel Channel 1 Differential connection 1 Channel 1 - Channel Differential connection Channel - Channel 1 Mean-value 1 ½ (Channel 1 + Channel ) /5 Siemens FI US Edition

53 Siemens AG 017 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Power supply connection Limit monitor HART/ Sensor ~ ~ U H Relay output HART 1 to 4 Signal input (see "sensor input connections" for possible types of connection) 5, Analog output (U or I output parameterizable using plug-in jumpers) 7, 8 Connection with HART communication for local parameterization 9 to 11 Output for sensor fault/limit monitor as relay contact (see below for possible parameterization) 1 PE connection 1, 14 Power supply input (protected against reverse polarity) Connection diagram for power supply, input and outputs Relay outputs Closed-circuit operation (relay opens when error) Device switched off 10 and 11 Device switched on and no error 9 and 11 Device switched on and error 10 and 11 Open-circuit operation (relay closes when error) Device switched off 10 and 11 Device switched on and no error 10 and 11 Device switched on and error 9 and 11 Connected terminals Dimensional drawings 1 (0.47) 11.5 (4.4) 8 (1.5). (1.04) (4.5) 15 (5.) 1 In devices with explosion protection Dimensions for control room mounting, rail mounting in mm (inches) Siemens FI US Edition /5

54 Siemens AG 017 Transmitters for field mounting SITRANS TF80 WirelessHART Overview Application The SITRANS TF80 is a WirelessHART field device for temperature measurement with a Pt100 sensor. This sensor can be installed directly on the field device, or connected at an offset with a cable connection. On the wireless communication side, the transmitter supports the WirelessHART standard. A HART modem can be connected to the transmitter particularly for initial parameterization. Alternatively the device can be commissioned comfortably by means of the local pushbuttons w/o any additional handset devices. It can be used in all industries and applications in non-explosive areas. SITRANS TF80 for flexible and cost-effective temperature measurements Supports the WirelessHART standard (HART V 7.1) Very high security level for wireless data transmission Built-in local user interface (LUI) with -button operation Optimum representation and readability using graphical display (104 x 80 pixels) with integrated backlight Stand-by (deep sleep phase) mode can be turned on and off with push of a button Battery power supply Battery life time up to 5 years Extend battery life time with HART modem interface which can be switch off Optimized power consumption through new design, and increase in battery life time Simple configuration thanks to SIMATIC PDM Housing meets IP5 degree of protection Supports all Pt100 sensors as per IEC 751/DIN EN 0751 Design The SITRANS TF80 has a robust aluminum enclosure and is suitable for outside use. It conforms with the IP5 safety class. The operation temperature range is -40 to +80 C (-40 to +17 F). Power supply is provided through an integrated battery, which is available as an accessory. The device is only approved for operation with this battery. The antenna features a rotatable joint which can be used for directional alignment. Wireless signals can thus be optimally received and transmitted. A special highlight is the possibility to operate directly on the device with push buttons. It perfectly matches the strategy of all new Siemens field devices. Using the device s push buttons, it is easy to turn the HART modem interface of the device on and off. The device can be put to passive status and reactivated at any time. This helps to extend the life time of the battery. The SITRANS TF80 transmitter features a cable gland or a Pt100 sensor including protective piping. Function The SITRANS TF80 can join to a WirelessHART network. It can be parameterized and operated through this network. Measured process values are transmitted via the network to the SIEMENS IE/WSN-PA LINK. Benefits The SITRANS TF80 is a temperature transmitter that features WirelessHART as the standard communication interface. Also available is a wired interface to connect a HART modem: Flexible temperature measurement Save costs on wiring at difficult installation conditions. Wireless technology offers cost advantages in cases where extensive wiring costs would normally apply. Integration It enables additional hitherto unfeasible measuring points, particularly for monitoring purposes Connecting to SIMATIC PCS 7 Easy installation also on moveable equipment parts Enables cost-effective temporary measurements, for example for process optimizations. Optimum solution in addition to wired communication and for system solutions in process automation Field device data received by the IE/WSN-PA LINK is transmitted to the connected systems, for example the process control system SIMATIC PCS 7. For an introduction of WirelessHART, please see the FI 01 catalogue Sec. 8 or Detailed information on IE/WSN-PA LINK can be found in the FI 01 catalogue Sec. 7 or The integration of field devices in SIMATIC PCS 7 and other process control systems can be now done seamlessly and cost-effectively with wireless technology, especially in situations where high wiring costs may be expected. Of particular interest are measuring points which are to be added and for which no wiring is available. Where larger distances between the IE/WSN-PA LINK and control systems need to be overcome, this connection can also be implemented on a wireless and cost-effective basis using the SCALANCE W series of products. Siemens WirelessHART devices operate with optimum coexistence to SCALANCE W family products. /54 Siemens FI US Edition

55 Siemens AG 017 Transmitters for field mounting SITRANS TF80 WirelessHART ES OS MS Industrial Ethernet SITRANS AW10 SITRANS P80 Wireless HART SITRANS TF80 SITRANS AW00 IE/WSN- PA LINK SITRANS AW10 Integration of a meshed network into SIMATIC PCS 7 SIMATIC system SIMATIC ET 00 with HART support DP/PA LINK Configuration Configuration of the SITRANS TF80 transmitter may be carried out as follows: Initial commissioning for the SITRANS TF80 with SIMATIC PDM is generally carried out via a HART modem or the integrated local user interface, since the network ID and join Key must be set up on the device before it can be accepted and integrated into the WirelessHART network. Once it is integrated into the network, the device can be conveniently operated with the WirelessHART network or onsite with a HART modem or via the local user interface. PROFIBUS PROFIBUS PA Technical specifications The SITRANS TF80 can be mechanically installed in two ways: Direct at the measuring point with a M0x1.5 thread. A connection to other threads can be done via the adapter. Remotely from the Pt100 sensor, which is connected to the transmitter via a cable. The data in the following table refer to the transmitter only excluding a connected sensor, except as noted otherwise. Input Sensor Sensor type Pt100 as per IEC 751/DIN EN ) Connection Two, three or four-wire system Measuring range C ( F) Cable length SITRANS TF80 and m Pt100 sensor element Measuring accuracy ) Accuracy < 0.04 % of the measuring range Long-term drift < 0.05 % of the measuring range in first year Ambient temperature effect max. 0.1 C/10 K Rated conditions Ambient temperature C( F) Storage temperature C ( F) Relative humidity <95% Climatic class 4K4H in accordance with EN (stationary use at locations not protected against weather) Degree of protection IP5/NEMA 4 Max. permissible temperature at 80 C (17 F) transmitter for directly mounted Pt100 Design Enclosure Die-cast aluminum Shock resistance in accordance with DIN EN / 0.95 Resistance to vibration DIN EN 008--/1.07 Weight without battery 1.5 kg (. lb) with battery 1. kg (.5 lb) Dimensions (W x H x D) See "Dimensional drawing" Thread for cable gland/ sensor connection Material of protective tubes and process connection (only for premounted sensor pipe) Cable between transmitter and sensor element Sensor break M0x1.5 other threads via adapter Stainless steel (AISI 1L, UNS S 10, XCrNiMo17-1-) m für two-, three- or four-wire connections Cable resistance < 1 Ω (setting range in mω ) Recognized Siemens FI US Edition /55

56 Siemens AG 017 Transmitters for field mounting SITRANS TF80 WirelessHART Displays and controls Display (with illumination) Size of display 104 x 80 pixels Number of digits Adjustable Number of spaces after comma Adjustable Setting options on site with push buttons with SIMATIC PDM or HART Communicator Auxiliary power Battery. V DC Communication Wireless standard WirelessHART V7.1 conforming Transmission frequency band.4 GHz (ISM-Band) Range under reference conditions Up to 50 m (line of sight) in outside areas Up to 50 m (greatly dependent on obstacles) in Inside areas Communication interfaces HART communication with HART modem WirelessHART Certificates and approvals Wireless communication approvals R&TTE, FCC General Product Safety CSA US/C, CE, UL Pressure equipment directive This device is not included in the pressure device guideline; classification according to pressure device guideline (PED 97//EC), Directive 1/40; article 1, paragraph.1.4 1) Pre-mounted Pt100: Class A (maximum MES: * t C) ) Calculation for errors: Probable total error = (MES + AET + LTD + ATE ) Max. error = MES + AET + LTD + ATE t : Absolut value of measured temperature MES: Measurement error of sensor AET: Accuracy error transmitter LTD: Long term drift ATE: Ambient temperature drift Selection and Ordering data Article No. SITRANS TF80 WirelessHART Temperature 7 M P transmitter 0 A (Required battery not included with delivery, see accessories) Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Connections/cable entry Cable gland M0x1.5 1) C Sensor pipe with Pt100, G½" male thread, premounted and connected D Display Digital display, visible 1 Enclosure Die-cast aluminum 1 Explosion protection Not included A Antenna Variable, attached to device A Further designs Order code Please add "-Z" to Article No. and specify Order code(s) and plain text. Measuring point number (TAG Nr.) Y15 max. 1 digits entered in plain text Y15:... Measuring point message Y1 max. 7 characters entered in plain text: Y1:... Accessories Article No. Lithium battery for SITRANS TF80/P80 7MP1990-0AA00 Mounting bracket, steel 7MF4997-1AC Mounting bracket, stainless steel 7MF4997-1AJ Cover, die-cast aluminum, without window 7MF4997-1BB Cover, die-cast aluminum, with window 7MF4997-1BE Thread adapter M0x1.5 (male thread) on 7MP1990-0BA00 ½-14 NPT (female thread) Thread adapter M0x1.5 (male thread) on 7MP1990-0BB00 G½ (female thread) IE/WSN-PA Link See Sec. 7 HART modem with USB interface 7MF4997-1DB SIMATIC PDM See Sec. 8 1) Please order sensor separately. /5 Siemens FI US Edition

57 Siemens AG 017 Transmitters for field mounting SITRANS TF80 WirelessHART Dimensional drawings Antenna 10 (5.1) 90 SW7 Pt (4.4) 4 (9.5) Ø 80 (.15) 154 (.0) Ø 80 (.15) 5 (.05) G½B 101 (.98) Ø 8 (0.) 14 (0.55) 5 (1.9) SITRANS TF80 WirelessHART temperature transmitter with Pt100, dimensions in mm (inch). Please see the dimensional drawing of the mounting bracket on page 1/19. Siemens FI US Edition /57

58 Siemens AG 017 Transmitters for field mounting SITRANS TF80 WirelessHART Antenna (5.1) 11 (4.4) 4 (9.5) Ø 80 (.15) 154 (.0) Ø 80 (.15) 5 (.05) Cable gland for cable... 1 mm ( inch) 4 (10.4) SITRANS TF80 WirelessHART temperature transmitter, dimensions in mm (inch) Please see the dimensional drawing of the mounting bracket on page 1/19. /58 Siemens FI US Edition

59 Siemens AG 017 Transmitter for field mounting/field indicator SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 0 ma Overview Our field devices for heavy industrial use HART, Universal 4 to 0 ma, universal Field indicator for 4 to 0 ma signals The temperature transmitter SITRANS TF works where others feel uncomfortable. Benefits Universal use - as transmitter for resistance thermometer, thermocouple element, Ω or mv signal - as field indicator for any 4 to 0 ma signals Local sensing of measured values over digital display Rugged two-chamber enclosure in die-cast aluminium or stainless steel Degree of protection IP7 Test terminals for direct read-out of the output signal without breaking the current loop Can be mounted elsewhere if the measuring point - is hard to access, - is subject to high temperatures, - is subject to vibrations from the system, - or if you want to avoid long neck tubes and/or protective tubes. Can be mounted directly on American-design sensors Wide range of approvals for use in potentially explosive atmospheres. "Intrinsically safe, non-sparking and flameproof" type of protections, for Europe and USA. SIL (with Order Code C0), SIL/ (with C) Application SITRANS TF can be used everywhere where temperatures need to be measured under particularly adverse conditions, or where a convenient local display is ideal. Which is why users from all industries have opted for this field device. The rugged enclosure protects the electronics. The stainless steel model is almost completely resistant to sea water and other aggressive elements. The inner workings offer high measuring accuracy, universal input and a wide range of diagnostic options. Function Configuration The communication capability over the HART protocol V 5.9 of the SITRANS TF with an integrated SITRANS TH00 permits parameterization using a PC or HART communicator (hand-held communicator). The SIMATIC PDM makes it easy. Parameterization is carried out using a PC for SITRANS TF with the integrated and programmable SITRANS TK. Available for this purpose are a special modem and the software tool SIPROM T. Mode of operation Mode of operation of SITRANS TF as temperature transmitter The sensor signal, whether resistance thermometer, thermocouple element or Ω or mv signal, is amplified and linearized. Sensor and output side are electrically isolated. An internal cold junction is integrated for measurements with thermocouple elements. The device outputs a temperature-linear direct current of 4 to 0 ma. As well as the analog transmission of measured values from 4 to 0 ma, the HART version also supports digital communication for online diagnostics, measured value transmission and configuration. SITRANS TF automatically detects when a sensor should be interrupted or is indicating a short-circuit. The practical test terminals allow direct measurement of 4 to 0 ma signals over an ammeter without interrupting the output current loop. Mode of operation of SITRANS TF as field indicator Any 4 to 0 ma signal can be applied to the generous terminal block. As well as a range of predefined measurement units, the adjustable indicator also supports the input of customized units. This means that any 4 to 0 ma signal can be represented as any type of unit, e.g. pressure, flow rate, filling level or temperature. Sensor TC RTD SITRANS TF SITRANS TH Analog-to-digital converter Electrical isolation Microprocessor 4 Digital-to-analog converter 5 Power supply PC/laptop 7 HART modem 8 Digital display (option) 9 Test connector C 9 5 A D D μp Power supply Load Mode of operation: SITRANS TF with integrated transmitter and digital display A 7 Siemens FI US Edition /59

60 Siemens AG 017 Transmitter for field mounting/field indicator SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 0 ma Technical specifications Input Resistance thermometer Measured variable Temperature Sensor type to IEC 0751 Pt5 Pt1000 to JIS C 104; a=0.009 K-1 Pt5 Pt1000 to IEC 0751 Ni5 Ni1000 Units C and F Connection Normal connection 1 resistance thermometer (RTD) in -wire, -wire or 4-wire system Generation of average value Series or parallel connection of several resistance thermometers in a two-wire system for the generation of average temperatures or for adaptation to other device types Generation of difference resistance thermometers (RTD) in -wire system (RTD 1 RTD or RTD RTD 1) Interface Two-wire system Parameterizable line resistance 100 Ω (loop resistance) Three-wire system No balancing required Four-wire system No balancing required Sensor current 0.45 ma Response time 50 ms for 1 sensor with opencircuit monitoring Open-circuit monitoring Always active (cannot be disabled) Short-circuit monitoring can be switched on/off (default value: ON) Measuring range parameterizable (see table "Digital measuring errors") Min. measured span 10 C (18 F) Characteristic curve Temperature-linear or special characteristic Resistance-based sensors Measured variable Actual resistance Sensor type Resistance-based, potentiometers Units Ω Connection Normal connection 1 resistance-based sensor (R) in -wire, -wire or 4-wire system Generation of average value resistance-based sensors in -wire system for generation of average value Generation of difference resistance-based sensor in -wire system (R 1 R or R R1) Interface Two-wire system Parameterizable line resistance 100 Ω (loop resistance) Three-wire system No balancing required Four-wire system No balancing required Sensor current 0.45 ma Response time 50 ms for 1 sensor with opencircuit monitoring Open-circuit monitoring Can be switched off Short-circuit monitoring Can be switched off (value is adjustable) Measuring range parameterizable max Ω (see table "Digital measuring errors") Min. measured span Ω (see Table "Digital measuring errors") Characteristic curve Resistance-linear or special characteristic Thermocouples Measured variable Temperature Sensor type (thermocouples) Type B Pt0Rh-PtRh to DIN IEC 584 Type C W5 %-Re acc. to ASTM 988 Type D W %-Re acc. to ASTM 988 Type E NiCr-CuNi to DIN IEC 584 Type J Fe-CuNi to DIN IEC 584 Type K NiCr-Ni to DIN IEC 584 Type L Fe-CuNi to DIN 4710 Type N NiCrSi-NiSi to DIN IEC 584 Type R Pt1Rh-Pt to DIN IEC 584 Type S Pt10Rh-Pt to DIN IEC 584 Type T Cu-CuNi to DIN IEC 584 Type U Cu-CuNi to DIN 4710 Units C or F Connection Normal connection 1 thermocouple (TC) Generation of average value thermocouples (TC) Generation of difference thermocouples (TC) (TC 1 TC or TC TC 1) Response time 50 ms for 1 sensor with opencircuit monitoring Open-circuit monitoring Can be switched off Cold junction compensation Internal With integrated Pt100 resistance thermometer External With external Pt100 IEC 0751 (-wire or -wire connection) External fixed Cold junction temperature can be set as fixed value Measuring range parameterizable (see table "Digital measuring errors") Min. measured span Min C ( F) (see table "Digital measuring errors") Characteristic curve Temperature-linear or special characteristic mv sensor Measured variable DC voltage Sensor type DC voltage source (DC voltage source possible over an externally connected resistor) Units mv Response time 50 ms for 1 sensor with opencircuit monitoring Open-circuit monitoring Can be switched off Measuring range mv mv Min. measured span mv or 0mV Overload capability of the input V DC Input resistance 1MΩ Characteristic curve Voltage-linear or special characteristic /0 Siemens FI US Edition

61 Siemens AG 017 Transmitter for field mounting/field indicator SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 0 ma Output Output signal ma, -wire Communication with SITRANS acc. to HART Rev. 5.9 TH00 Digital display Digital display (optional) In current loop Display Max. 5 digits Digit height 9 mm (0.5 inch) Display range Units any (max. 5 char.) Setting: with buttons Zero point, full-scale value and unit Load voltage.1 V Measuring accuracy Digital measuring errors See table "Digital measuring errors" Reference conditions Auxiliary power 4 V ± 1 % Load 500 Ω Ambient temperature C (7.4 F) Warming-up time > 5 min Error in the analog output (digital/analog converter) < 0.05 % of span Error due to internal cold junction < 0.5 C (0.9 F) Influence of ambient temperature Analog measuring error 0.0 % of span/10 C (18 F) Digital measuring errors - with resistance thermometers 0.0 C (0.11 F)/10 C (18 F) - with thermocouples 0. C (1.1 F)/10 C (18 F) Auxiliary power effect < % of span/v Effect of load impedance < 0.00 % of span/100 Ω Long-term drift In the first month < 0.0 % of span After one year < 0. % of span After 5 years < 0.4 % of span Conditions of use Ambient conditions Storage temperature C ( F) Condensation Permissible Electromagnetic compatibility According to EN 1 and NAMUR NE1 Degree of protection to EN 059 IP7 Construction Weight Approx. 1.5 kg (. lb) without options Dimensions See "Dimensional drawings" Enclosure material Die-cast aluminum, low in copper, GD-AlSi 1 or stainless steel, polyester-based lacquer, stainless steel rating plate Electrical connection, sensor connection Mounting bracket (optional) Screw terminals, cable inlet via M0 x 1.5 or ½-14 NPT screwed gland Steel, galvanized and chromeplated or stainless steel Auxiliary power Without digital display With digital display Electrically isolated Test voltage Certificates and approvals Explosion protection ATEX "Intrinsic safety" type of protection V DC (0 V for Ex ib; V for Ex ic and Ex na) V DC (0 V for Ex ib; V for Ex ic and Ex na) Between input and output U eff = 1 kv, 50 Hz, 1 min with digital display: II (1) G EEx ia IIC T4 without digital display: II (1) G EEx ia IIC T - EC type test certificate ZELM 11 ATEX 0471 X "Operating equipment that is nonignitable and has limited energy II G EEx nal IIC T/T4 for zone " type of protection - EC type test certificate ZELM 11 ATEX 0471 X "Flame-proof enclosure" type of protection II G EEx d IIC T5/T II 1D Ex td A0 IP5 T100 C, T85 C - EC type test certificate ZELM 11 ATEX 047 X Explosion protection to FM Certificate of Compliance Identification (XP, DIP, NI, S) XP/I/1/BCD/T5 Ta = 85 C (185 F), T Ta = 50 C (11 F), Type 4X DIP/II, III/1/EFG/T5 Ta = 85 C (185 F), T Ta = 50 C (11 F), Type 4X NI/I//ABCD/T5 Ta = 85 C (185 F), T Ta = 50 C (11 F), Type 4X S/II, III//FG/T5 Ta = 85 C (185 F), T Ta = 50 C (11 F), Type 4X Other certificates IECEx, GOST, INMETRO, NEPSI, KOSHA Hardware and software requirements For the parameterization software SIPROM T for SITRANS TF with TH00 - Personal computer PC with CD-ROM drive and USB - PC operating system Windows 98, NT, 000, XP, 7 and Win 8 For the parameterization software SIMATIC PDM for SITRANS TH00 Communication Load for HART connection Two-core shielded Multi-core shielded See chapter 8 "Software", "SIMATIC PDM" Ω.0 km (1.8 mi) 1.5 km (0.9 mi) Protocol HART protocol, version 5.9 Factory setting (transmitter): Pt100 (IEC 751) with -wire circuit Measuring range: C (... 1 F) Error signal in the event of sensor breakage:.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s Siemens FI US Edition /1

62 Siemens AG 017 Transmitter for field mounting/field indicator SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 0 ma Digital measuring errors Thermocouples Resistance thermometer Input Measuring range Min. measured span Digital accuracy C / ( F) C) ( F) C ( F) to IEC 0751 Pt (18) 0. (0.54) ( ) Pt (18) 0.15 (0.7) ( ) Pt Pt (18) 0.1 (0.18) ( ) Pt (18) 0.15 (0.7) ( ) Pt (18) 0.15 (0.7) ( ) to JIS C Pt (18) 0. (0.54) ( ) Pt (18) 0.15 (0.7) ( ) Pt Pt (18) 0.1 (0.18) ( ) Pt (18) 0.15 (0.7) ( ) Pt (18) 0.15 (0.7) ( ) Ni 5 to Ni ( ) 10 (18) 0.1 (0.18) Resistance-based sensors Input Measuring range Min. measured Digital span accuracy Ω Ω Ω Resistance Resistance Input Measuring range Min. measured span Digital accuracy C / ( F) C ( F) C ( F) Type B (180) 1) (.) 1) (... 08) Type C (W5) (180) 1 ) (1.8) ) ( ) Type D (W) (180) 1 ) (1.8) ) ( ) Type E (90) 1 (1.8) ( ) Type J (90) 1 (1.8) ( ) Type K (90) 1 (1.8) ( ) Type L (90) 1 (1.8) ( ) Type N (90) 1 (1.8) ( ) Type R (180) (.) ( ) Type S (180) (.) ( ) Type T (7) 1 (1.8) ( ) Type U (90) (.) ( ) 1) The digital accuracy in the range 0 to 00 C ( to 57 F) is C (5.4 F). ) The digital accuracy in the range 1750 to 00 C (18 to 417 F) is C (. F). mv sensor Input Measuring span Min. measured Digital span accuracy mv mv μv mv sensor mv sensor The digital accuracy is the accuracy after the analog/digital conversion including linearization and calculation of the measured value. An additional error is generated in the output current 4 to 0 ma as a result of the digital/analog conversion of 0.05 % of the set span (digital-analog error). The total error under reference conditions at the analog output is the sum from the digital error and the digital-analog error (poss. with the addition of cold junction errors in the case of thermocouple measurements). / Siemens FI US Edition

63 Siemens AG 017 Transmitter for field mounting/field indicator SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 0 ma Selection and Ordering data Article No. Temperature transmitter in field housing 7 N G Two-wire system ma, with electrical isolation, with documentation on MiniDVD Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Integrated transmitter SITRANS TH00, programmable Without Ex protection 5 0 With Ex ia 5 1 With Ex nal for zone 5 Total device SITRANS TF Ex d 1) 5 4 Total device SITRANS TF according to FM 5 5 (XP, DIP, NI, S) 1) SITRANS TH00, communication capability according to HART V 5.9 Without Ex-protection 0 With Ex ia 1 With Ex nal for zone Total device SITRANS TF Ex d 1) 4 Total device SITRANS TF according to FM 5 (XP, DIP, NI, S) 1) Enclosure Die-cast aluminium A Stainless steel precision casting E Connections/cable inlet Screwed glands M0x1.5 B Screwed glands ½-14 NPT C Digital indicator Without 0 With 1 Mounting bracket and securing parts Without 0 Made of steel 1 Made of stainless steel Further designs Order code Please add "-Z" to Article No. and specify Order code(s) and plain text. Test protocol (5 measuring points) C11 Functional safety SIL C0 Functional safety SIL/ C Explosion protection Explosion protection Ex ia to INMETRO E5 (Brazil) (only with 7NG ) Explosion protection Ex d to INMETRO E (Brazil) (only with 7NG ) Explosion protection Ex na to INMETRO E7 (Brazil) (only with 7NG1.-...) Explosion protection Ex i to NEPSI E55 (China) (only with 7NG ) Explosion protection Ex d to NEPSI E5 (China) (only with 7NG ) Explosion protection Ex na to NEPSI E57 (China) (only with 7NG1.-...) Explosion protection Ex d to KOSHA E70 (Korea) (only with 7NG ) Two coats of lacquer on casing and cover G10 (PU on epoxy) Transient protection J01 Cable gland CAPRI 1/ NPT ADE 4F, D57 nickle-plated brass (CAPRI and 8104) included Cable gland 1/ NPT ADE 1F, D58 cable diam (CAPRI and 81054) included Cable gland 1/ NPT ADE 4F, stainless steel D59 (CAPRI and 8104) included Cable gland 1/ NPT ADE 1F, D0 cable diam (CAPRI and 81054) included Selection and Ordering data Order Code Customer-specific programming Add "-Z" to Article No. and specify Order code(s) Measuring range to be set Y01 ) Specify in plain text (max. 5 digits): Y01:... to... C, F Measuring point no. (TAG), max. 8 characters Y17 ) Meas. point descriptor, max. 1 characters Y 4) Meas. point message, max. characters Y4 4) Only inscription on measuring point label: Y 4) specify in plain text: Measuring range Pt100 (IEC) -wire, R L = 0 Ω U0 5) Pt100 (IEC) -wire U0 5) Pt100 (IEC) 4-wire U0) Thermocouple type B U0 5)) Thermocouple type C (W5) U1 5)) Thermocouple type D (W) U 5)) Thermocouple type E U 5)) Thermocouple type J U)) Thermocouple type K U5 5)) Thermocouple type L U 5)) Thermocouple type N U7 5)) Thermocouple type R U8 5)) Thermocouple type S U9 5)) Thermocouple type T U0 5)) Thermocouple type U U1 5)) With TC: CJC external (Pt100, -wire) U41 With TC: CJC external with fixed value, specify Y50 in plain text Special differing customer-specific programming, Y09 7) specify in plain text Fail-safe value. ma (instead of.8 ma) U ) Supply units see Chapter "Supplementary Components". 1) Without cable gland. ) For customer-specific programming for RTD and TC, the start value and the end value of the required measuring span must be specified here. ) For this selection, Y01 or Y09 must also be selected. 4) If only Y, Y or Y4 are ordered and the label only has to be on the tag plate, Y01 does not have to be specified. 5) For this selection, Y01 must also be selected. ) Internal cold junction compensation is selected as the default for TC. 7) For customer-specific programming, for example mv and ohm, the start value and the end value of the required measuring span and the unit must be entered here. Siemens FI US Edition /

64 Siemens AG 017 Transmitter for field mounting/field indicator SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 0 ma Selection and Ordering data Accessories Modem for SITRANS TH100, TH00, TR00 and TF with TH00 incl. parameterization software T with USB interface MiniDVD for temperature measuring instruments with documentation in German, English, French, Spanish, Italian and Portuguese, and parameterization software SIPROM T (included in delivery with SITRANS TF) HART modem With USB interface SIMATIC PDM parameterization software also for SITRANS TH00 Mounting bracket and securing parts Made of steel for 7NG1.-..B.. Made of steel for 7NG1.-..C.. Made of stainless steel for 7NG1.-..B.. Made of stainless steel for 7NG1.-..C.. Digital indicator 1) Connection board Supply units see Chapter "Supplementary Components". Article No. 7NG09-8KU A5E MF4997-1DB See chapter 8 7MF4997-1AC 7MF4997-1AB 7MF4997-1AJ 7MF4997-1AH 7MF4997-1BS A5E04 1) It is not possible to upgrade devices with Ex protection Ordering example 1: 7NG15-0AB11-Z Y01+Y+U0 Y01: C Y: TICA14HEAT Ordering example : 7NG1-0AC11-Z Y01+Y+Y4+U5 Y01: C Y: TICA 14 ABC Y4: HEATING BOILER 5789 Factory setting (transmitter): Pt100 (IEC 751) with three-wire circuit Measuring range: C (... 1 F) Fault current.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s /4 Siemens FI US Edition

65 Siemens AG 017 Transmitter for field mounting/field indicator SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 0 ma Selection and Ordering data Article No. SITRANS TF field indicator 7 N G for ma signals, with documentation on MiniDVD Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Without Ex-protection 0 1 With Ex ia 1 1 With Ex nal for zone 1 Total device SITRANS TF Ex d 1) 4 1 Total device SITRANS TF according to FM 5 1 (XP, DIP, NI, S) 1) Enclosure Die-cast aluminium A Stainless steel precision casting E Connections/cable inlet Screwed glands M0x1.5 B Screwed glands ½-14 NPT C Digital indicator With 1 Mounting bracket and securing parts Without 0 Made of steel 1 Made of stainless steel Further designs Order code Please add "-Z" to Article No. and specify Order code(s) and plain text. Test protocol (5 measuring points) C11 Explosion protection Explosion protection Ex ia to INMETRO E5 (Brazil) (only with 7NG ) Explosion protection Ex d to INMETRO E (Brazil) (only with 7NG ) Explosion protection Ex na to INMETRO E7 (Brazil) (only with 7NG1.-...) Explosion protection Ex i to NEPSI E55 (China) (only with 7NG ) Explosion protection Ex d to NEPSI E5 (China) (only with 7NG ) Explosion protection Ex na to NEPSI E57 (China) (only with 7NG1.-...) Explosion protection Ex d to KOSHA E70 (Korea) (only with 7NG ) Two coats of lacquer on casing and cover G10 (PU on epoxy) Transient protection J01 Cable gland CAPRI 1/ NPT ADE 4F, D57 nickle-plated brass (CAPRI and 8104) included Cable gland 1/ NPT ADE 1F, D58 cable diam (CAPRI and 81054) included Cable gland 1/ NPT ADE 4F, stainless steel D59 (CAPRI and 8104) included Cable gland 1/ NPT ADE 1F, D0 cable diam (CAPRI and 81054) included Selection and Ordering data Order Code Customer-specific programming Add "-Z" to Article No. and specify Order code(s) Measuring range to be set Y01 ) Specify in plain text (max. 5 digits): Y01:... to... C, F Only inscription on TAG plate: specify in plain Y ) text: Measuring range Only inscription on TAG plate: Measuring Y ) point descriptor, max. 1 characters Only inscription on TAG plate: Measuring Y4 ) point message, max. 7 characters Special differing customer-specific programming, specify in plain text Y09 4) Supply units see Chapter "Supplementary Components". 1) Without cable gland. ) For customer-specific programming for RTD and TC, the start value and the end value of the required measuring span must be specified here. ) If only Y, Y or Y4 are ordered and the label only has to be on the tag plate, Y01 does not have to be specified. 4) For customer-specific programming, for example mv and ohm, the start value and the end value of the required measuring span and the unit must be entered here. Selection and Ordering data Accessories MiniDVD for temperature measuring instruments with documentation in German, English, French, Spanish, Italian and Portuguese, and parameterization software SIPROM T (included in delivery with SITRANS TF) Mounting bracket and securing parts Made of steel for 7NG1.-..B.. Made of steel for 7NG1.-..C.. Made of stainless steel for 7NG1.-..B.. Made of stainless steel for 7NG1.-..C.. Digital indicator 1) Connection board 1) It is not possible to upgrade devices with Ex protection Ordering example 1: 7NG10-0AB10-Z Y01+Y Y01: C Y: TICA14HEAT Ordering example : 7NG10-0AC10-Z Y01+Y+Y4 Y01: BAR Y: PICA 14 ABC Y9: HEATING BOILER 7890 Factory setting (field indicator): ma Article No. A5E MF4997-1AC 7MF4997-1AB 7MF4997-1AJ 7MF4997-1AH 7MF4997-1BS A5E04 Siemens FI US Edition /5

66 Siemens AG 017 Transmitter for field mounting/field indicator SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 0 ma Dimensional drawings 1 (0.51) 144 (5.7) 15* (0.59) 18* (5.4) 5 (.05) 50* (1.97) 55 (.17) 8 (1.10) 0 (0.79) b 80 (.15) 100* (.94) 80 (.15) 8 a: max. 14 (.4) (M0x1.5) max. 189 (7.44) (½-14 NPT) b: max. 5 (0.98) (M0x1.5) max. 50 (1.97) (½-14 NPT) *) Dimensions for stainless steel enclosure (.8) 1 (4.84) Ø ( ) 50 (1.97) 78 (.8) 117 (4.1) 10 (4.7) a.5 (1.44) 7 (9.) 1 Sensor connection (screwed gland M0x1.5 or ½-14 NPT) Blanking plug Electrical connection (screwed gland M0x1.5 or ½-14 NPT) 4 Terminal side, output signal 5 Terminal side, sensor 105 (4.1) Protective cover (without function) 7 Mounting bracket (option) with clamp for securing to a vertical or horizontal pipe 8 Cover with window for digital display SITRANS TF, dimensions in mm (inches) / Siemens FI US Edition

67 Siemens AG 017 Transmitter for field mounting/field indicator SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 0 ma Schematics Resistance thermometer Resistance Thermocouple -W -W -W RTD R + TC - Two-wire system 1) Two-wire system 1) Cold junction compensation Internal/fixed value -W -W -W RTD R RTD + TC - Three-wire system Three-wire system Cold junction compensation with external Pt100 in two-wire system 1) -W -W -W RTD R RTD + TC - Four-wire system Four-wire system Cold junction compensation with external Pt100 in three-wire system -W -W -W RTD R + TC - + TC1 - R1 RTD1 Generation of average value / difference 1) 1) Programmable line resistance for the purpose of correction. Generation of average value / difference 1) Generation of average value / difference with internal cold junction compensation Voltage measurement Current measurement -W -W U I R SITRANS TF, sensor connection assignment Siemens FI US Edition /7

68 Siemens AG 017 Transmitters for field mounting SITRANS TF fieldbus transmitter Overview Application The SITRANS TF can be used everywhere where temperatures need to be measured under particularly harsh conditions. Which is why users from all industries have opted for this field device. The rugged enclosure protects the electronics. The stainless steel model is almost completely resistant to sea water and other aggressive elements. The inner workings offer high measuring accuracy, universal input and a wide range of diagnostic options. Our field devices for heavy industrial use FOUNDATION fieldbus PROFIBUS PA The SITRANS TF temperature transmitter works where others can t cope. Benefits For universal use as a transmitter for resistance thermometers, thermocouple elements, Ω or mv signals Rugged two-chamber enclosure in die-cast aluminium or stainless steel Degree of protection IP7 Can be mounted elsewhere if the measuring point - is hard to access, - is subject to high temperatures, - is subject to vibrations from the system, - or if you want to avoid long neck tubes and/or protective tubes. Can be mounted directly on American-design sensors Wide range of approvals for use in potentially explosive atmospheres. "Intrinsically safe, non-sparking and flameproof" type of protection, for Europe and USA Function Features Polarity-neutral bus connection 4-bit analog-digital converter for high resolution Electrically isolated Version for use in hazardous areas Special characteristic Sensor redundance Transmitter with PROFIBUS PA communication Function blocks: x analog Transmitter with FOUNDATION fieldbus communication Function blocks: x analog and 1 x PID Functionality: Basic or LAS Mode of operation The following function diagram explains the mode of operation of the transmitter. The only difference between the two versions of the SITRANS TF (7NG and 7NG18-...) is the type of field bus protocol used (PROFIBUS PA or FOUNDATION fieldbus). Optional inputs: - Resistance thermometer - Thermocouple - mv sensor - Resistance-based sensors Transformer Input 1 Input Differential Mean value Redundancy Terminal temperature Engineering units Diagnostic functions Table linearization Polynomial linearization Process calibration Electrically isolated Input 1 Input 5 4 A/D converter CPU Communication Ex power circuit 1 Bus connection Internal Pt100 EEPROM Complex configuration Correction coefficient Factory settings - PROFIBUS PA protocol (7NG17) or - FOUNDATION Fieldbus protocol (7NG18) SITRANS TF with TH400, function diagram /8 Siemens FI US Edition

69 Siemens AG 017 System communication Bus terminator Bus terminator SITRANS TF with TH400, communication interface Technical specifications Input Analog/digital conversion Measurement rate Resolution SITRANS TF with TH400 PA SITRANS TF with TH400 FF Resistance thermometer <50ms 4-bit PROFIBUS PA Segment coupler FOUNDATION Fieldbus Segment coupler Pt to IEC 0751/JIS C 104 Measuring range C ( F) Ni to DIN 470 Measuring range C ( F) Cu , α = Measuring range C ( F) Line resistance per sensor cable Max. 50 Ω Sensor current Nominal 0. ma Sensor fault detection Sensor break detection Yes Sensor short-circuit detection Yes, < 15 Ω Resistance-based sensors Measuring range kω Line resistance per sensor cable Max. 50 Ω Sensor current Nominal 0. ma Sensor fault detection Sensor break detection Yes Sensor short-circuit detection Yes, < 15 Ω Thermocouple to IEC 584 Measuring range Type B C ( F) Type E C ( F) Type J C ( F) Type K C ( F) Type N C ( F) Type R Type S Type T to DIN 4710 Transmitters for field mounting SITRANS TF fieldbus transmitter C ( F) C ( F) C ( F) Type L C ( F) Type U C ( F) to ASTM E Type W C ( F) Type W C ( F) External cold junction compensation C ( F) Sensor fault detection Sensor break detection Yes Sensor short-circuit detection Yes, < mv Sensor current in the event of 4 μa open-circuit monitoring mv sensor - voltage input Measuring range mv Input resistance 10 MΩ Output Filter time (programmable) s Update time < 400ms Measuring accuracy Accuracy is defined as the higher value of general values and basic values. General values Type of input All Absolute accuracy ±0.05 % of the measured value Temperature coefficient ±0.00 % of the measured value/ C Basic values Type of input Basic accuracy Temperature coefficient Pt100 and Pt1000 ± 0.1 C ± 0.00 C/ C Ni100 ± 0.15 C ± 0.00 C/ C Cu10 ± 1. C ± 0.0 C/ C Resistance-based sensors ± 0.05 Ω ± 0.00 Ω/ C Voltage source ± 10 μv ± 0. μv/ C Thermocouple, type: ± 0.5 C ± 0.01 C/ C E, J, K, L, N, T, U Thermocouple, type: ± 1 C ± 0.05 C/ C B, R, S, W, W5 Cold junction compensation ± 0.5 C Reference conditions Warming-up time 0 s Signal-to-noise ratio Min. 0 db Calibration condition C ( F) Siemens FI US Edition /9

70 Siemens AG 017 Transmitters for field mounting SITRANS TF fieldbus transmitter Conditions of use Ambient conditions Permissible ambient temperature Permissible storage temperature Relative humidity Insulation resistance Test voltage Continuous operation Electromagnetic compatibility NAMUR EMC 004/108/EC Emission and Noise Immunity Construction Weight Dimensions Enclosure materials Electrical connection, sensor connection Mounting bracket (optional) C ( F) C ( F) 98 %, with condensation 500 V AC for 0 s 50 V AC/75 V DC NE1 EN 1-1, EN 1--5 Approx. 1.5 kg (. lb) without options See "Dimensional drawings" Die-cast aluminum, low in copper, GD-AlSi 1 or stainless steel Polyester-based lacquer for GD AlSi 1 enclosure Stainless steel rating plate screw terminals Cable inlet via M0 x 1.5 or ½ -14 NPT screwed gland Bus connection with M1 plug (optional) Steel, galvanized and chromeplated or stainless steel Degree of protection IP7 to EN 059 Auxiliary power Power supply Standard, Ex "d", Ex "na", Ex "nl", V DC XP, NI Ex "ia", Ex "ib" V DC In FISCO/FNICO installations V DC Power consumption < 11 ma Max. increase in power consumption in the event of a fault < 7 ma Certificates and approvals Explosion protection ATEX EC type test certificate ZELM 11 ATEX 0471 X Type of protection "intrinsic safety i" II (1) G Ex ia IIC T4/T (version: 7NG1x-1xxxx) Conformity statement ZELM 11 ATEX 0471 X "Operating equipment that is nonignitable and has limited energy" type of protection (version: 7NG1x-xxxx) EC type test certificate "Flame-proof enclosure" type of protection (version: 7NG1x- 4xxxx) Explosion protection: FM for USA FM approval FM Type of protection XP, DIP, NI and S (version 7NG1x-5xxxx) Other certificates II G Ex na [nl] IIC T4/T II G Ex nl IIC T4/T ZELM 11 ATEX 047 X II G Ex d IIC T5/T II 1D Ex td A0 IP5 T100 C, T85 C XP / I / 1 / BCD / T5,T; Type 4X DIP / II, III / 1 / EFG / T5,T; Type 4X NI / I / / ABCD / T5,T; Type 4X S / II, III / / FG T5,T; Type 4X GOST, INMETRO, NEPSI, KOSHA Communication Parameterization interface PROFIBUS PA connection -Protocol A&D profile, Version.0 -Protocol EN Volume - Address (for delivery) 1 - Function blocks x analog FOUNDATION fieldbus connection -Protocol FF protocol -Protocol FF design specifications - Functionality Basic or LAS - Version ITK 4. - Function blocks x analog and 1 x PID Factory setting for SITRANS TH400 PA Sensor Pt100 (IEC) Type of connection -wire circuit Unit C Failure mode Last valid value Filter time 0 s PA address 1 PROFIBUS Ident No. Manufacturer-specific for SITRANS TH400 FF Sensor Pt100 (IEC) Type of connection -wire circuit Unit C Failure mode Last valid value Filter time 0 s Node address /70 Siemens FI US Edition

71 Siemens AG 017 Selection and Ordering data Article No. Temperature transmitter in field enclosure 7 N G with fieldbus communication and electrical isolation, with documentation on MiniDVD Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Integrated transmitter SITRANS TH400 with PROFIBUS PA Without Ex protection 7 0 With Ex ia (ATEX) 7 1 With Ex nal for zone (ATEX) 7 Total device SITRANS TF Ex d 1) 7 4 Total device SITRANS TF according to FM 7 5 (XP, DIP, NI, S) 1) SITRANS TH400, with FOUNDATION fieldbus Without Ex protection 8 0 With Ex ia (ATEX) 8 1 With Ex nal for zone (ATEX) 8 Total device SITRANS TF Ex d 1) 8 4 Total device SITRANS TF according to FM 8 5 (XP, DIP, NI, S) 1) Enclosure Die-cast aluminium A Stainless steel precision casting E Connections/cable inlet Screwed glands M0x1.5 B Screwed gland s ½-14 NPT C Mounting bracket and fastening parts None 0 Made of steel 1 Stainless steel Further designs Order code Please add "-Z" to Article No. and specify Order code(s) and plain text. Test report (5 measuring points) C11 Bus connection M1 plug (metal), without mating connector M00 ) M1 plug (metal), with mating connector M01 ) Explosion protection Explosion protection Ex ia to INMETRO E5 (Brazil) (only with 7NG ) Explosion protection Ex d to INMETRO E (Brazil) (only with 7NG ) Explosion protection Ex na to INMETRO E7 (Brazil) (only with 7NG1.-...) Explosion protection Ex i to NEPSI E55 (China) (only with 7NG ) Explosion protection Ex d to NEPSI E5 (China) (only with 7NG ) Explosion protection Ex na to NEPSI E57 (China) (only with 7NG1.-...) Explosion protection Ex d to KOSHA E70 (Korea) (only with 7NG ) Two coats of lacquer on casing and cover G10 (PU on epoxy) Transient protection J01 Cable gland CAPRI 1/ NPT ADE 4F, D57 nickle-plated brass (CAPRI and 8104) included Cable gland 1/ NPT ADE 1F, D58 cable diam (CAPRI and 81054) included Cable gland 1/ NPT ADE 4F, stainless steel D59 (CAPRI and 8104) included Cable gland 1/ NPT ADE 1F, D0 cable diam (CAPRI and 81054) included Transmitters for field mounting SITRANS TF fieldbus transmitter Selection and Ordering data Order Code. Customer-specific programming Add "-Z" to Article No. and specify Order code(s) Measuring range to be set Y01 ) Specify in plain text (max. 5 digits): Y01:... to... C, F Meas. point no. (TAG), max. characters Y15 4) Meas. point descriptor, max. characters Y 4) Meas. point message, max. characters Y) Bus address, specify in plain text Y5 4) Pt100 (IEC) -wire, R L = 0 Ω U0 ) Pt100 (IEC) -wire U0 ) Pt100 (IEC) 4-wire U04 ) Thermocouple type B U0 )7) Thermocouple type C (W5) U1 )7) Thermocouple type D (W) U )7) Thermocouple type E U )7) Thermocouple type J U4 )7) Thermocouple type K U5 )7) Thermocouple type L U )7) Thermocouple type N U7 )7) Thermocouple type R U8 )7) Thermocouple type S U9 )7) Thermocouple type T U0 )7) Thermocouple type U U1 )7) With TC: CJC: external (Pt100, -wire) U41 With TC: CJC: external with fixed value, specify Y50 in plain text Special differing customer-specific programming, Y09 8) specify in plain text 1) Without cable gland ) Not available for explosion protection Ex d or XP. ) For customer-specific programming for RTD and TC, the start value and the end value of the required measuring span must be specified here. 4) If only Y15, Y or Y5 are ordered and the label only has to be on the tag plate, Y01 does not have to be specified. 5) For this selection, Y01 or Y09 must also be selected. ) For this selection, Y01 must also be selected. 7) Internal cold junction compensation is selected as the default for TC. 8) For customer-specific programming, for example mv and ohm, the start value and the end value of the required measuring span and the unit must be entered here. Siemens FI US Edition /71

72 Siemens AG 017 Transmitters for field mounting SITRANS TF fieldbus transmitter Selection and Ordering data Accessories MiniDVD for temperature measuring instruments with documentation in German, English, French, Spanish, Italian and Portuguese, and parameterization software SIPROM T (included in delivery with SITRANS TF) SIMATIC PDM parameterization software also for SITRANS TF with TH400 PA Mounting bracket and fastening parts Made of steel for 7NG1.-..B.. Made of steel for 7NG1.-..C.. Made of stainless steel for 7NG1.-..B.. Made of stainless steel for 7NG1.-..C.. Connection board Article No. Ordering example 1: 7NG17-0AB01-Z Y01+Y15+Y5+U0 Y01: C Y15: TICA14HEAT Y5: Ordering example : 7NG17-0AC01-Z Y01+Y15+Y5+U5 Y01: C Y15: TICA 14 ABC 578 Y5: 5 Factory setting: for SITRANS TH400 PA: - Pt100 (IEC) with -wire circuit - Unit: C - Failure mode: last valid value - Filter time: 0 s - PA address: 1 - PROFIBUS Ident No.: manufacturer-specific for SITRANS TH400 FF: - Pt100 (IEC) with -wire circuit - Unit: C - Failure mode: last valid value - Filter time: 0 s - Node address: A5E00451 See Sec. 8 7MF4997-1AC 7MF4997-1AB 7MF4997-1AJ 7MF4997-1AH A5E /7 Siemens FI US Edition

73 Siemens AG 017 Transmitters for field mounting SITRANS TF fieldbus transmitter Dimensional drawings Ø 80 (.15) 144 (5.7) 18* (5.4) 5 (.05) 50* (1.97) 55 (.17) 8 (1.10) 0 (0.79) 50 (1.97) 117 (4.1) b 80 (.15) 100* (.94) a a: max. 14 (.4) (M0x1.5) max. 189 (7.44) (½-14 NPT) b: max. 5 (0.98) (M0x1.5) max. 50 (1.97) (½-14 NPT) *) Dimensions for stainless steel enclosure (.8) 1 (4.84) Ø ( ) 1 Sensor connection (screwed gland M0x1.5 or ½-14 NPT) Blanking plug Electrical connection (screwed plug M0x1.5 orr ½-14 NPT), optional M1 plug 4 Terminal side, bus connection 8 (.8) 7 10 (4.7) 105 (4.1) 5 Terminal side, sensor Protective cover (without function) 7 Mounting bracket (optional) with clamp securing to a vertical or horizontal pipe.5 (1.44) 7 (9.) SITRANS TF with TH400, dimensions in mm (inches) Siemens FI US Edition /7

74 Siemens AG 017 Transmitters for field mounting SITRANS TF fieldbus transmitter Schematics Resistance thermometer Thermocouple Resistance Two-wire system 1) Internal cold junction compensation Two-wire system 1) Three-wire system Cold junction compensation with external Pt100 in two-wire system 1) Three-wire system Four-wire system Cold junction compensation with external Pt100 in three-wire system Four-wire system Mean-value/differential or redundancy generation x two-wire system 1) Mean value, differential or redundancy generation with internal cold junction compensation Mean value, differential or redundancy generation 1 resistor in two-wire system 1) 1 resistor in three-wire system Voltage measurement 1 1 Mean-value/differential or redundancy generation 1 sensor in two-wire system 1) 1 sensor in three-wire system Mean value, differential or redundancy generation and cold junction compensation with internal Pt100 in two-wire system 1) One voltage source 1) Programmable line resistance for the purpose of correction. 1 Measurement of mean value, differential and redundancy with voltage sources SITRANS TF with TH400, sensor connection assignment /74 Siemens FI US Edition

75 Siemens AG 017 Overview Multipoint temperature transmitter SITRANS TO500 Design The SITRANS TO500 multipoint temperature transmitter is located in the control cabinet in a compact aluminum enclosure for mounting onto DIN rails. The connectors are easy to access on the front: 4 x connector for measurement lances 1 x connector for power supply 1 x connector PROFIBUS DP 1 x connector Ethernet The status displays are also located on the front. SITRANS TO500 is a multipoint temperature transmitter for measuring temperatures and temperature profiles using fiber optic multipoint temperature measurement lances. Benefits Evaluation of a large number of sensors (fiber Bragg grating (FBG)) in one temperature transmitter Low space requirement of the measurement lances 4 measuring lance channels per transmitter Easy to install PROFIBUS DP - Simple integration into control system Fast response to temperature changes Exact, no recalibration required due to internal reference Also suitable for high process temperatures Application The SITRANS TO500 is used for evaluating a large number of sensors arranged on a fiber optic multipoint temperature measurement lance. Up to 4 measurement lances with up to 48 sensors (fiber Bragg grating (FBG)) each can be processed simultaneously by a SITRANS TO500. Accurate and fast determination of temperature profiles enables process optimization in terms of service life, quality and output. Locations of excessive temperature rise are quickly and accurately detected, thereby preventing damage to the process, equipment and environment. Wherever temperature profiles must be determined and installation space is limited, the SITRANS TO500 with fiber-optic temperature measurement is the right choice. Mode of operation In the SITRANS TO500 multipoint temperature transmitter, light is generated in the wavelength of 1500 to 100 nm and output to the measurement lance by means of a continuously tunable laser light. Fiber Bragg gratings (FBG) are mounted at defined measurement points on the measurement lances. Each FBG reflects light of a defined wavelength. The wavelength reflected by the FBGs varies as a function of temperature. The reflection at the FBG is thus a measure of the temperature at the respective measurement point. Up to 48 FBGs gratings per channel can be evaluated, depending on the temperature range. A gas cell with fixed absorption line serves as a reference in the SITRANS TO500 and the wavelength determination is continuously adjusted by it. Function The SITRANS TO500 has 4 channels which are evaluated simultaneously. The wavelength reflected at each sensor in the multipoint temperature measurement lance depends on the temperature, and this wavelength is output in the multipoint temperature transmitter. The temperature can be determined and displayed accurately at up to 48 sensors per channel. The positions of the sensors can be specified by the customer. This leads to a flexible and application-specific solution for the customer. The measured temperatures are transferred to the control system via PROFIBUS DP. The parameters of the SITRANS TO500 are set via the integrated Ethernet interface. Siemens FI US Edition /75

76 Siemens AG 017 Multipoint temperature transmitter SITRANS TO500 Technical specifications Selection and Ordering data Article-No. Input Channels 4 Measured variable Temperature Input type Max. 48 sensors (FBGs) per channel Characteristics Temperature-linear Resolution 0.1 K Measuring accuracy < 0.5 K Repeatability < 0.5 K Measuring cycle < 1 s Measuring range C ( F) depending on the measurement lance Unit C Power supply 4 V DC + 0 % Power consumption Max. 15 W Protection Against reverse polarity Measuring velocity Measurement rate 1 Hz independent of the number of FBGs Output Output signal PROFIBUS DP Optical power 1 mw per channel Laser protection class Class 1 Rated conditions Ambient conditions Ambient temperature C (... 1 F) Storage temperature C ( F) Relative humidity < 80%, non condensing at 50 C (1 F) Electromagnetic compatibility According to EN 1 and NAMUR NE1 Degree of protection to EN 059 Enclosure IP0 Design Weight.4 kg (5. lb) Dimensions See "Dimensional drawings" DIN rail adapter Rear-mounted Material Aluminum Displays and control elements LEDs "Power-on" (continuous light) "Status" (flashing during startup; otherwise continuous light) Pushbutton "Reset" (system restart or address reset) SITRANS TO500 multipoint temperature transmitter Communication: PROFIBUS DP Channels: 4 Power supply: 4 V DC Optical connection: FC/APC plug Enclosure: Aluminum, IP0 7NG9551-4AA00-0AA0 /7 Siemens FI US Edition

77 Siemens AG 017 Multipoint temperature transmitter SITRANS TO500 Dimensionsal drawings 50 (9.84) 10 (5.11) s SITRANS TO (5.51) POWER STATUS RESET + - GND CH1 CH CH POWER ETHERNET PROFIBUS DP CH4 110 (4.) SITRANS TO500, front, rear and side view; dimensions in mm (inch) Installation length 100 (.94) Cable length Ø 10 (0.94) Ø 0.8 (0.01) Pigtail with FC/APC plug Handpiece Glass fiber Measuring lance with FC/APC connector, pigtail and handpiece; dimensions in mm (inch) Schematics s SITRANS TO500 Connector measurement lances "Power" and "Status" LEDs "Reset" pushbutton POWER STATUS RESET CH1 CH Channel 1 Channel Connector power supply 4 V DC + - GND POWER ETHERNET PROFIBUS DP CH CH4 Channel Channel 4 Connector PROFIBUS DP V0/V1 RS485 Connector Ethernet RJ45 for LAN (TCP/IP) SITRANS TO500, connector assignment Siemens FI US Edition /77

78 Siemens AG 017 SITRANS TS500 Technical description Overview Temperature sensors of the SITRANS TS500 product family are used to measure temperatures in industrial equipment. Benefits The modular design makes it possible to customize the temperature sensor for most applications, while still being able to use many standardized individual components. SITRANS TS500 Temperature sensors as a modular system Due to their modular design, temperature sensors of the SITRANS TS500 series are well suited to a large number of applications. The replaceable measuring insert makes it possible to conduct maintenance work even during ongoing operations. These devices are used particularly frequently in vessels and pipelines of the following industries: Power plants Chemical industry Petrochemical industry General process engineering Water, waste water /78 Siemens FI US Edition

Temperature Measurement Transmitters for mounting in sensor head

Temperature Measurement Transmitters for mounting in sensor head Siemens AG 015 Overview SITANS TH00 two-wire system, universal, HAT Application SITANS TH00 transmitters can be used in all industrial sectors. Due to their compact size they can be installed in the connection

More information

Temperature Measurement

Temperature Measurement Overview Application transmitters can be used in all industrial sectors. Due to their compact size they can be installed in the connection head type B (DIN 4729) or larger. The following sensors/signal

More information

Temperature Measurement Transmitters for mounting in sensor head

Temperature Measurement Transmitters for mounting in sensor head Siemens AG 015 SITANS TH00 two-wire system, universal Overview Application SITANS TH00 transmitters can be used in all industrial sectors. Due to their compact size they can be installed in the connection

More information

Temperature Measurement

Temperature Measurement Siemens AG 015 / Product overview Transmitters for mounting in sensor head /4 SITRANS TH100 two-wire system (Pt100) /8 SITRANS TH00 two-wire system universal /15 SITRANS TH00 two-wire system universal,

More information

Temperature Measurement

Temperature Measurement Temperature Measurement SITANS T00 Overview Application SITANS T00 transmitters can be used in all industrial sectors. Their compact design enables simple mounting on standard DIN rails on-site in protective

More information

SITRANS T measuring instruments for temperature

SITRANS T measuring instruments for temperature SITRANS T measuring instruments for temperature /2 Product overview /6 Transmitter for mounting in sensor head /6 SITRANS TH100, two-wire system (Pt100) /9 SITRANS TH200, two-wire system universal /15

More information

SITRANS T measuring instruments for temperature

SITRANS T measuring instruments for temperature Overview Our field devices for heavy industrial use HART, Universal 4 to 20 ma, universal Field indicator for 4 to 20 ma signals The temperature transmitter SITRANS TF works where others feel uncomfortable.

More information

SITRANS T measuring instruments for temperature

SITRANS T measuring instruments for temperature SITRANS T measuring instruments for temperature /2 Product overview / SITRANS T transmitters for mounting in sensor head / SITRANS TK PA, with PROFIBUS connection /8 SITRANS TH100, two-wire system (Pt100)

More information

Temperature Measurement

Temperature Measurement Siemens AG 00 - Transmitter, two-wire system and - Field indicator for 4 to 0 ma Overview Our field devices for heavy industrial use HART, Universal 4 to 0 ma, universal Field indicator for 4 to 0 ma signals

More information

Temperature Measurement Transmitter for field mounting/field indicator

Temperature Measurement Transmitter for field mounting/field indicator Siemens AG 017 SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 0 ma Overview Our field devices for heavy industrial use HART, Universal 4 to 0 ma, universal Field indicator

More information

0 2 1 â Ó. itemp HART TMT182. Technical Information

0 2 1 â Ó. itemp HART TMT182. Technical Information Technical Information itemp HART TMT182 Temperature head transmitter Head transmitter for resistance thermometers (RTD), thermocouples (TC), resistance and voltage transmitters (mv), HART -protocol, for

More information

PROGRAMMABLE FIELD TEMPERATURE TRANSMITTER

PROGRAMMABLE FIELD TEMPERATURE TRANSMITTER Configuration Code TM01 Series 642 Programmable HART Field Temperature The Series 642 programmable HART field temperature transmitter is a 2-wire unit with analog output. It includes input for RTDs; resistance

More information

itemp HART DIN rail TMT112

itemp HART DIN rail TMT112 Temperature transmitter itemp HART DIN rail TMT112 Universal temperature transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage transmitters, incorporating HART protocol Application

More information

0 2 1 â Ó. itemp HART TMT182. Technical Information

0 2 1 â Ó. itemp HART TMT182. Technical Information Technical Information itemp HART TMT182 Temperature head transmitter Head transmitter for resistance thermometers (RTD), thermocouples (TC), resistance and voltage transmitters (mv), HART -protocol, for

More information

itemp PA TMT184 Technical information

itemp PA TMT184 Technical information Technical information itemp PA TMT184 Temperature head transmitter with PROFIBUS-PA interface. Supply and digital communication using PROFIBUS-PA, for installation in a Form B sensor head. Features and

More information

Temperature transmitter itemp PCP DIN rail TMT 121

Temperature transmitter itemp PCP DIN rail TMT 121 Technical information TI 087R/09/en 510 03671 Temperature transmitter itemp PCP DIN rail TMT 121 Universal temperature transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage

More information

Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting

Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting Electrical Temperature Measurement Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting WIKA Data Sheet TE 12.03

More information

Temperature Measurement

Temperature Measurement Siemen AG 00 Temperature Meaurement Overview Application Linearized temperature meaurement with reitance thermometer or thermal element Differential, mean-value or redundant temperature meaurement with

More information

09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i

09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i Temperature Transmitter Series 9182 www.stahl.de > One unit for nearly all temperature sensors indivdually configurable > Intrinsically safe input [Ex ia] IIC > Signal duplication possible > Galvanic isolation

More information

Temperature head transmitter itemp PCP TMT 181

Temperature head transmitter itemp PCP TMT 181 Technical information TI 070R/09/en Mat.-Nr.: 510 01110 Temperature head transmitter itemp PCP TMT 181 Universal head transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage

More information

C520 / C520X /C520S / C520XS HART Compatible, Universal, Dual-input 2-wire Transmitters

C520 / C520X /C520S / C520XS HART Compatible, Universal, Dual-input 2-wire Transmitters C520 / C520X /C520S / C520XS HART Compatible, Universal, Dual-input 2-wire Transmitters The 520 transmitters are universal, isolated, dual-input temperature transmitters with additional voltage and resistance

More information

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C 34-TT-03-07 3/06 PRODUCT SPECIFICATION SHEET OVERVIEW The Honeywell STT170 series of programmable temperature

More information

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5.

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5. Ex i Isolators Temperature Transmitter with Output 0/4... 20 ma, without Limit Value Contact Field Circuit Ex i) One unit for nearly all temperature sensors indivdually configurable Intrinsically safe

More information

Isolators A3/1.

Isolators A3/1. Temperature Transmitter Series 9182 > One unit for nearly all temperature sensors indivdually configurable > Signal duplication possible > Galvanic isolation between input, output, power supply and configuration

More information

3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/.

3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/. Ex i Isolators Temperature Transmitter without Output 0/4... 20 ma, with Limit Value Contact Field Circuit Ex i) One unit for nearly all temperature sensors indivdually configurable Intrinsically safe

More information

C330 / C330X PC-Programmable Universal, 2-wire Transmitter

C330 / C330X PC-Programmable Universal, 2-wire Transmitter C330 / C330X PC-Programmable Universal, 2-wire Transmitter The IPAQ C330 transmitter is a universal, isolated, temperature transmitter with additional voltage and resistance input. Its robust design and

More information

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C 6/07 PRODUCT SPECIFICATION SHEET OVERVIEW The Honeywell STT170 series of programmable temperature transmitters

More information

MODEL: B3HU. Space-saving Two-wire Signal Conditioners B3-UNIT

MODEL: B3HU. Space-saving Two-wire Signal Conditioners B3-UNIT Space-saving Two-wire Signal Conditioners B3-UNIT 2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER (HART communication, intrinsically safe) Functions & Features Universal input: mv, V, T/C, RTD, resistance, potentiometer

More information

Assembly. Front view. Parametrization interface. Power Bus

Assembly. Front view. Parametrization interface. Power Bus Temperature Converter Features Assembly 1-channel signal conditioner 24 V DC supply Thermocouple, RTD, potentiometer or mv input Input for PTC thermistor Current and voltage output Line fault (LFD) and

More information

Temperature head transmitter itemp PCP TMT 181

Temperature head transmitter itemp PCP TMT 181 Technical information TI 070R/09/en Mat.-Nr.: 510 01110 Temperature head transmitter itemp PCP TMT 181 Universal head transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage

More information

Digital temperature transmitter with HART protocol Model T32.1S, head mounting version Model T32.3S, rail mounting version

Digital temperature transmitter with HART protocol Model T32.1S, head mounting version Model T32.3S, rail mounting version Electrical temperature measurement Digital temperature transmitter with HART protocol Model T32.1S, head mounting version Model T32.3S, rail mounting version WIKA data sheet TE 32.04 Applications Process

More information

RMA42. Technical Information

RMA42. Technical Information Technical Information RMA42 Process transmitter with control unit Digital process transmitter for mounting on a top-hat rail for monitoring and visualizing analog measured values Application Plant and

More information

TF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels

TF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels TF 0 / TF 0-Ex Head mounted temperature transmitters, FOUNDATION Fieldbus (H), Pt 00 (RTD), thermocouples, or independent channels 0/-8.5 EN Input Resistance thermometer (,, wire circuit) Thermocouples

More information

Isolators A3/1.

Isolators A3/1. > Compact limit value switch with 2 configurable limiting values and 4... 20 ma output > Suitable for 2-, 3-wire transmitters, 2-wire HART transmitters and ma sources > Intrinsically safe input [Ex ia]

More information

Operating Instructions Edition 04/2007. Temperature Transmitter SITRANS TR200/TR300 7NG3032-*JN00 SITRANS TR200 7NG3033-*JN00 SITRANS TR300.

Operating Instructions Edition 04/2007. Temperature Transmitter SITRANS TR200/TR300 7NG3032-*JN00 SITRANS TR200 7NG3033-*JN00 SITRANS TR300. Operating Instructions Edition 04/2007 Temperature Transmitter 7NG3032-*JN00 SITRANS TR200 7NG3033-*JN00 SITRANS TR300 sitrans Introduction 1 General safety notes 2 SITRANS Temperature transmitter Operating

More information

Technical Information RMA42

Technical Information RMA42 TI00150R/09/EN/05.16 71315973 Products Solutions Services Technical Information RMA42 Process transmitter with control unit Digital process transmitter for monitoring and visualizing analog measured values

More information

Rail mounted Temperature Transmitter TH102/TH102-Ex

Rail mounted Temperature Transmitter TH102/TH102-Ex Data Sheet 10/-8.54 EN Rail mounted Temperature Transmitter TH102/TH102-Ex HART programmable, Pt 100 (RTD), thermocouples, electrical isolation Input Resistance thermometer (2, 3, 4 wire circuit) Thermocouples

More information

FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex

FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex Data Sheet 10/-8.54 EN Level 0: Information FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex HART programmable, Pt 100 (RTD), thermocouples, electrical isolation Resistance thermometer (2,

More information

â Ó itemp TC TMT128 Technical information DIN rail mounted Temperature Transmitter for Thermocouples (TC)

â Ó itemp TC TMT128 Technical information DIN rail mounted Temperature Transmitter for Thermocouples (TC) Technical information itemp TC TMT128 DIN rail mounted Temperature Transmitter for Thermocouples (TC) Application Temperature transmitter with fixed measuring ranges for converting TC input signals into

More information

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter)

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter) JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net

More information

Head mounted Temperature Transmitter TF02/TF02-Ex

Head mounted Temperature Transmitter TF02/TF02-Ex Data Sheet Head mounted Temperature Transmitter TF0/TF0-Ex FOUNDATION Fieldbus H, Pt 00 (RTD), thermocouples, or independent channels Input Resistance thermometer (-, -, -wire circuit) Thermocouples Resistance

More information

HART field temperature transmitter Models TIF50, TIF52, TIF62

HART field temperature transmitter Models TIF50, TIF52, TIF62 Electrical temperature measurement HART field temperature transmitter Models TIF50, TIF52, TIF62 WIKA data sheet TE 62.01 Applications Plant construction Process engineering General industrial applications

More information

Temperature head transmitter itemp TC TMT 188

Temperature head transmitter itemp TC TMT 188 Technical information TI 077R/24/ae No.: 510 06145 Temperature head transmitter itemp TC TMT 188 Universal head transmitter for thermocouples for an economical, high accuracy temperature monitoring. Fixed

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series Transmitter Supply Unit Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > Open-circuit and short-circuit monitoring and messaging for input

More information

TTH200 Head-mount temperature transmitter

TTH200 Head-mount temperature transmitter Change from one to two columns Data Sheet DS/TTH200-EN Rev. B TTH200 Head-mount temperature transmitter Temperature transmitter for HART protocol. Suitable for all standard requirements. Measurement made

More information

Transmitter. Configuration Code TM01 Series 440 Programmable RTD Temperature Transmitter. Application Areas. Features and Benefits

Transmitter. Configuration Code TM01 Series 440 Programmable RTD Temperature Transmitter. Application Areas. Features and Benefits Configuration Code TM01 Series 440 Programmable RTD Temperature Transmitter The Series 440 programmable RTD temperature transmitter is a 2-wire transmitter with an analog output. It has measurement input

More information

Isolators A3/1. Temperature Transmitter Field Circuit Non-Ex i Series

Isolators A3/1. Temperature Transmitter Field Circuit Non-Ex i Series Temperature Transmitter Series 9182 > One unit for nearly all temperature sensors indivdually configurable > Signal duplication possible > Galvanic isolation between input, output, power supply and configuration

More information

Temperature transmitter with local display RIT 261

Temperature transmitter with local display RIT 261 Technical Information TI 091R/2/ae Temperature transmitter with local display RIT 261 Universal field mounted transmitter provides an exceptional backlit temperature indication with five large digits and

More information

Universal Intelligent 2-wire DIN Rail Transmitters

Universal Intelligent 2-wire DIN Rail Transmitters Universal Intelligent 2-wire DIN Rail Transmitters IPAQ-L is a universal and intelligent 2-wire DIN rail transmitter for temperature and other measurement applications. IPAQ-LX is the Intrinsic Safe version

More information

HART Compatible Intelligent 2-wire DIN Rail Transmitters

HART Compatible Intelligent 2-wire DIN Rail Transmitters HART Compatible Intelligent 2-wire DIN Rail Transmitters MESO-L is a Smart and universal 2-wire DIN Rail transmitter for temperature and other measurement applications. MESO-LX is the Intrinsic Safe version

More information

Advanced Temperature Transmitter

Advanced Temperature Transmitter No. SS2-ATT082-0100 Advanced Temperature Transmitter ATT082 HART protocol Model Application Temperature transmitter with 2 input channels and HART communication for the conversion of different input signals

More information

HART Compatible Intelligent 2-wire In-head Transmitters

HART Compatible Intelligent 2-wire In-head Transmitters HART Compatible Intelligent 2-wire In-head Transmitters Actual size MESO-H is a Smart and universal 2-wire Inhead transmitter for temperature and other measurement applications. MESO-HX is the Intrinsic

More information

Temperature Input Module for Zone 1 Series 9482/32

Temperature Input Module for Zone 1 Series 9482/32 www.stahl.de > 8 channels for temperature sensors > Intrinsically safe inputs Ex ia > For Pt-, Ni- and Cu-resistance temperature detectors according to DIN, IEC and GOST in 2-, 3- and 4-wire circuits >

More information

A BB ME ASU R E ME NT & AN AL Y T ICS D AT A S H E ET. TTR200 Rail-mount temperature transmitter

A BB ME ASU R E ME NT & AN AL Y T ICS D AT A S H E ET. TTR200 Rail-mount temperature transmitter A BB ME ASU R E ME NT & AN AL Y T ICS D AT A S H E ET TTR200 Rail-mount temperature transmitter 2 TTR200 RAIL-MOUNT TEMPERATURE TRANSMITTER DS/TTR200-EN REV. D Measurement made easy Temperature transmitter

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F

Isolators A3/1.  Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F Series 9160 Rev. F > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de

More information

MODEL: B6U-B B6-UNIT. [2] LCD DISPLAY 0: Without 1: With

MODEL: B6U-B B6-UNIT. [2] LCD DISPLAY 0: Without 1: With Field-mounted Two-wire Signal Conditioners B6-UNIT 8: TIIS flameproof (CE not available) Confirm selectable combinations of approval and wiring conduit types in the table. 2-WIRE UNIVERSAL TEMPERATURE

More information

Isolating Repeater Input Series 9163

Isolating Repeater Input Series 9163 > For 4-wire HART transmitters and voltage sources > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2 (IEC 61508) > High accuracy www.stahl.de

More information

STT 3000 Smart Temperature Transmitter Series STT170 Specifications

STT 3000 Smart Temperature Transmitter Series STT170 Specifications STT 3000 Smart Temperature Transmitter Series STT170 Specifications Model STT171, STT173, STT17H, STT17F, STT17C 34-TT-03-07 November 2010 Overview STT17H Features The Honeywell STT170 series of programmable

More information

Fieldbus Isolating Repeater Series 9185/11

Fieldbus Isolating Repeater Series 9185/11 www.stahl.de > For operation of the intrinsically safe Profibus DP (RS-485 IS to PNO standard) > Intrinsically safe fieldbus RS-422, RS-485 [Ex ib] IIC > Galvanic isolation between RS-422 / RS-485, RS-232,

More information

Universal Intelligent 2-wire In-head Transmitters

Universal Intelligent 2-wire In-head Transmitters Universal Intelligent 2-wire In-head Transmitters Actual size IPAQ-H is a universal and intelligent 2-wire In-head transmitter for temperature and other measurement applications. IPAQ-HX is the Intrinsic

More information

Multifunction Intelligent 4-wire Isolated Signal Conditioner

Multifunction Intelligent 4-wire Isolated Signal Conditioner Multifunction Intelligent 4-wire Isolated Signal Conditioner IPAQ-4L is a fully universal and intelligent 4- wire (mains powered) transmitter for temperature measurement and signal conditioning applications.

More information

Universal Intelligent 2-wire DIN Rail Transmitters

Universal Intelligent 2-wire DIN Rail Transmitters Universal Intelligent 2-wire DIN Rail Transmitters IPAQ-L is a universal and intelligent 2-wire DIN rail transmitter for temperature and other measurement applications. IPAQ-LX is the Intrinsic Safe version

More information

Level Measurement. Continuous level measurement Radar transmitters SITRANS LR460. 4/258 Siemens FI

Level Measurement. Continuous level measurement Radar transmitters SITRANS LR460. 4/258 Siemens FI Overview The is a -wire, 2 GHz FMCW radar level transmitter with extremely high signal-to-noise ratio and advanced signal processing for continuous monitoring of solids up to 100 m (328 ft). It is ideal

More information

06528E00. ATEX / IECEx NEC 505 NEC 506 NEC 500

06528E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Switching Repeater Series 9170 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > Open-circuit / short-circuit monitoring and messaging (can be switched

More information

General Specifications

General Specifications General Specifications YTA70 Temperature Transmitter The YTA70 is the highly accurate temperature transmitter that accepts Thermocouple, RTD, ohms or DC millivolts inputs and converts it to a to 0 ma DC

More information

FieldIT Temperature Transmitter, head mounted TH02/TH02-Ex

FieldIT Temperature Transmitter, head mounted TH02/TH02-Ex Data Sheet 0/-8.9 EN Level 0: Information FieldIT Temperature Transmitter, head mounted TH0/TH0-Ex HART programmable, Pt 00 (RTD), thermocouples, electrical isolation Input Resistance thermometer (,, wire

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160

Isolators A3/1.  Transmitter Supply Unit Field Circuit Ex i Series 9160 Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de

More information

IPAQ C530/R530 Technical Datasheet

IPAQ C530/R530 Technical Datasheet IPAQ C530/R530 Technical Datasheet Smart 2-wire universal transmitter with HART 7 and NFC technology NFC - Configuration of the transmitter via a portable device such as a smartphone. HART 7 protocol High

More information

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/ > 4 channels for 2-wire HART transmitters and 4 channels for 4-wire HART transmitters > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit

More information

Isolators A3/1. Ex i Power Supply Field Circuit Ex i Series

Isolators A3/1. Ex i Power Supply Field Circuit Ex i Series > Intrinsically safe output [Ex ib] IIC/IIB > Stable output voltage > Galvanic isolation between output and power supply > Power supply or 85... 230 V AC > Compact design www.stahl.de 07673E00 Basic function:

More information

SITRANS F flowmeters SITRANS F M. Transmitter Transmag 2 with sensor 911/E 4/77. Overview

SITRANS F flowmeters SITRANS F M. Transmitter Transmag 2 with sensor 911/E 4/77. Overview Overview Design The complete flowmeter consists of a flow sensor and an associated transmitter from the Transmag 2 for pulsed alternating field. These are available as remote and compact versions ( 911/E

More information

SINEAX V 624 Programmable Temperature Transmitter for RTD and TC inputs

SINEAX V 624 Programmable Temperature Transmitter for RTD and TC inputs SINEAX V 6 for rail mounting in housing P/7 or P/7 St 00 II () GD Application SINEAX V 6 (Figs. and ) is designed for measuring temperature in combination with thermocouples or resistance thermometers.

More information

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: 49 661 60030 Fax: 49 661 6003607 Email: mail@jumo.net Internet: www.jumo.net JUMO

More information

Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version

Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version Temperature Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version WIKA data sheet TE 15.01 for further approvals see page 10 Applications

More information

Resistance thermometer Model TR30, compact design

Resistance thermometer Model TR30, compact design Electrical temperature measurement Resistance thermometer Model TR30, compact design WIKA data sheet TE 60.30 Applications Machine building, plant and vessel construction Propulsion technology, hydraulics

More information

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter)

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter) JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net

More information

FieldIT Temperature Transmitter, field mounted TH202/TH202-Ex

FieldIT Temperature Transmitter, field mounted TH202/TH202-Ex Data Sheet 0/-8.6 EN Level 0: Information FieldIT Temperature Transmitter, field mounted TH0/TH0-Ex HART programmable, Pt 00 (RTD), thermocouples, electrical isolation Input Resistance thermometer (,,

More information

Binary Output Series 9175

Binary Output Series 9175 Binary Output > Intrinsically safe output [Ex ia] IIC / [Ex ib] IIC > Galvanic isolation between input, output and power supply > Open-circuit and short-circuit monitoring (can be switched off) > For use

More information

Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version

Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version Electrical temperature measurement Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version WIKA data sheet TE 15.01 Applications Process industry Machine building

More information

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted Electrical temperature measurement Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted WIKA data sheet TE 60.34 Applications Machine building, plant and vessel construction

More information

SITRANS F flowmeters SITRANS F US. Transmitter FUS060. Overview

SITRANS F flowmeters SITRANS F US. Transmitter FUS060. Overview Overview Function Displays and keypad Operation of the SITRANS FUS060 transmitter can be carried out using: Keypad and display unit HART communicator PC/laptop and SIMATIC PDM software via HART communication

More information

P5201 Universal Programmable Transmitters with Galvanic Isolation

P5201 Universal Programmable Transmitters with Galvanic Isolation Transmitters - KB0288-2012/09 P5201 Universal Programmable Transmitters with Galvanic Isolation One type of transmitter for all regular resistance and thermocouple sensors. Linearized output signal 4 to

More information

SITRANS T measuring instruments for temperature

SITRANS T measuring instruments for temperature Overview SITNS T measuring instruments for temperature SITNS T transmitter for field mounting / field indicator SITNS TF Mode of operation Sensor TC TD SITNS TF 1 nalogtodigital converter 2 Electrical

More information

MCR-FL-TS-LP-I-EX SIL IEC Programmable Intrinsically Safe Loop-Powered Temperature Measuring Transducer With HART Protocol

MCR-FL-TS-LP-I-EX SIL IEC Programmable Intrinsically Safe Loop-Powered Temperature Measuring Transducer With HART Protocol SIL IEC 6 508 Programmable Intrinsically Safe Loop-Powered Temperature Measuring Transducer With HART Protocol Data Sheet 0068_en_03 PHOENIX CONTACT 0-07-09 Description Temperature FL ϑ Universal PC programmable

More information

Temperature measurement TMD 832 head transmitter

Temperature measurement TMD 832 head transmitter Technical information TI 062R/09/en Mat.-Nr. 510 00782 Temperature measurement TMD 832 head transmitter SMART head transmitter with HART protocol for RTD, Thermocouple and mv input signals Applications

More information

SEM210 SERIES. Programmable In-head Universal Temperature Transmitter INDEX SECTION CONTENTS PAGE NO.

SEM210 SERIES. Programmable In-head Universal Temperature Transmitter INDEX SECTION CONTENTS PAGE NO. INDEX SECTION CONTENTS PAGE NO. SEM210 SERIES 1.0 DESCRIPTION 1 2.0 SPECIFICATION 15 3.0 INSTALLATION 67 Programmable Inhead Universal Temperature Transmitter Status Instruments Ltd, Green Lane Business

More information

Analog Universal Module HART for Zone 2 Series 9468/33

Analog Universal Module HART for Zone 2 Series 9468/33 > 8 channels can be adjusted individually as analog inputs or outputs > Intrinsically safe inputs/outputs Ex ia > For 0/4 20 ma + HART signals > Line fault monitoring per channel > Diagnostics based on

More information

600T Series Transmitters. Specification Sheet. Model 653T Electronic temperature transmitter (PC programmable)

600T Series Transmitters. Specification Sheet. Model 653T Electronic temperature transmitter (PC programmable) Specification Sheet 600T Series Transmitters Model 65T Electronic temperature transmitter (PC programmable) High flexibility and wide rangeability Single transmitter accepts RTD/THC/mV/ohm Galvanically

More information

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: 49 661 60030 Fax: 49 661 6003607 Email: mail@jumo.net Internet: www.jumo.net JUMO

More information

Binary Output without Power Supply Series 9176

Binary Output without Power Supply Series 9176 Binary Output without Power Supply Series 9176 > For intrinsically safe operation of Ex i solenoid valves, indicators and horns > Power supply by control circuit, loop powered > Intrinsically safe output

More information

SEM210 SEM210X UNIVERSAL TEMPERATURE TRANSMITTER

SEM210 SEM210X UNIVERSAL TEMPERATURE TRANSMITTER UNIVERSAL INPUT, DUAL CHANNEL ATEX & IEC Ex Version MATHS FUNCTIONS SENSOR CHARACTERISTICS DOWNLOAD VIA USB PORT ALLOWS FOR CUSTOM TYPES FLASH TESTED TO 4 KV DC INTRODUCTION The SEM210 is a universal transmitter

More information

Temperature Transmitter itemp RTD DIN rail TMT 127

Temperature Transmitter itemp RTD DIN rail TMT 127 Technical Information TI 095R/09/en No. 51004790 Temperature Transmitter itemp RTD DIN rail TMT 127 Temperature Transmitter for Pt100 Resistance Thermometer Application Temperature transmitter with fixed

More information

Positioner with HART Communication Type 3780

Positioner with HART Communication Type 3780 Positioner with HART Communication Type 780 Application Single-acting or double-acting positioner for attachment to pneumatic control valves. Supplied with an electric input signal from to 20 ma Travels

More information

Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting

Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting Electrical Temperature Measurement Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting WIKA Data Sheet TE 24.01 Applications T Machinery, plant construction T Process industry

More information

Level Measurement Continuous level measurement Radar transmitters

Level Measurement Continuous level measurement Radar transmitters Overview Configuration Mounting on a nozzle is a 2-wire 25 GHz pulse radar level transmitter for continuous monitoring of solids and liquids in storage vessels including extreme levels of dust and high

More information

Paperless Recorder PR20

Paperless Recorder PR20 Technical Information TI 075R/24/ae Paperless Recorder PR20 Economical and time saving recorder operates without the need for paper or pens and is exceedingly simple to operate Application Areas Technological

More information

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted Electrical temperature measurement OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted WIKA data sheet TE 60.31 further approvals see page 10 Applications Machine building, plant

More information

Remote I/O. 74 Remote I/O. Remote I/O System

Remote I/O. 74 Remote I/O. Remote I/O System System Overview of the System Components IS1+ 76 General Information IS1+ 77 CPU & Power Modules CPU & Power Modules for Zone 1 / Div. 1 IS1+ 9440/22 78 Sockets for CPU & Power Module IS1+ 9490 78 CPU

More information

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals Accessories High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals WIKA data sheet AC 80.03 Applications Machine building

More information

SITRANS TH200/TH300 SITRANS T. Temperature transmitter SITRANS TH200/TH300. Introduction 1. Safety information. Description.

SITRANS TH200/TH300 SITRANS T. Temperature transmitter SITRANS TH200/TH300. Introduction 1. Safety information. Description. Introduction 1 Safety information 2 SITRANS T Temperature transmitter Operating Instructions Description 3 Installation 4 Connecting 5 Operation 6 Functional safety 7 Commissioning 8 Functions 9 Technical

More information