SITRANS T measuring instruments for temperature

Size: px
Start display at page:

Download "SITRANS T measuring instruments for temperature"

Transcription

1 SITRANS T measuring instruments for temperature /2 Product overview /6 Transmitter for mounting in sensor head /6 SITRANS TH100, two-wire system (Pt100) /9 SITRANS TH200, two-wire system universal /15 SITRANS TH00, two-wire system universal, HART /21 SITRANS TH400, fieldbus transmitter /26 Transmitter for rail mounting /26 SITRANS TR200, two-wire system universal /2 SITRANS TR00, two-wire system universal, HART /8 SITRANS TW, four-wire system, universal, HART /50 Transmitter for field mounting with temperature sensor /50 SITRANS TF2, Digital display thermometer /5 SITRANS TF, two-wire system /5 Field indicator /5 SITRANS TF, Field indicator for 4 to 20 ma /60 Resistance thermometers /60 Technical description /62 Protective tubes, installation /64 Temperature transmitters for mounting in the connection head /65 Questionnaire for temperature sensors (resistance thermometers and thermocouples) /66 Flue gas resistance thermometers, with connection head /67 Low-pressure screw-in resistance thermometers, with connection head /67 - without neck tube /68 - with neck tube /69 High-pressure screw-in resistance thermometers /70 High-pressure welding-type resistance thermometer /71 Flange-type resistance thermometer /71 - with connection head /72 - with reduced response time, with connection head /7 Resistance thermometers for damp rooms /74 Accessories /74 - Measuring inserts, not explosion protected /76 - Measuring inserts, explosion protected /77 - Welding-type protective tubes, neck tubes and connection heads /79 Thermocouples /79 Technical description /8 Temperature transmitters for mounting in the connection head /84 Questionnaire for temperature sensors (resistance thermometers and thermocouples) /85 Straight thermocouples /85 - to DIN 47, with connection head /86 - Individual parts and accessories /88 Jacket thermocouples /88 - with extension lead /89 - with connection head, form B /90 - with socket /87 Individual parts /92 Accessories /92 - Cold junction with built-in power supply unit /9 - Cold junction thermostat for 6 or 12 measuring points /94 - Cold junction thermostat for 12 or 24 measuring points /95 Resistance thermometers for food, pharmaceuticals and biotechnology /95 Resistance thermometers for installation in pipelines and tanks /99 Resistance thermometers with clamp-on system You can download all instructions, catalogs and certificates for SITRANS T free of charge at the following Internet address: Siemens FI

2 SITRANS T Measuring instruments for temperature Product overview Overview Application Mounting of transmitter with Ex protection Page Software for parameterization Transmitters for temperature for mounting in sensor heads Transmitter Sensor SITRANS TH100 Transmitters for Pt100 Mounting in sensor head Zone 2, zone 1 Zone 2, zone 1, zone 0 /6 SIPROM T SITRANS TH200 Transmitters for connection to resistance thermometers, resistance-based sensors, thermocouples and DC voltages up to 1.1 V Zone 2, zone 1 Zone 2, zone 1, zone 0 /9 SIPROM T Two-wire system Universal SITRANS TH00 Transmitters for connection to resistance thermometers, resistance-based sensors, thermocouples and DC voltages up to 1.1 V Two-wire system Universal HART Zone 2, zone 1 Zone 2, zone 1, zone 0 /15 SIMATIC PDM SITRANS TH400 Transmitters for connection to resistance thermometers, resistance-based sensors, thermocouples and DC voltages up to 0.9 V Zone 2, zone 1, zone 21 Zone 2, zone 1, zone 0, zone 21, zone 20 /21 SIMATIC PDM for TH 400 with PROFIBUS PA Fieldbus transmitter PROFIBUS PA FOUNDATION Fieldbus /2 Siemens FI

3 SITRANS T Measuring instruments for temperature Product overview Application Mounting of transmitter with Ex protection Page Software for parameterization Transmitters for temperature for rail mounting Transmitter Sensor SITRANS TR200 Transmitters for connection to resistance thermometers, resistance-based sensors, thermocouples and DC voltages up to 1.1 V Two-wire system Zone 2, zone 1, zone 21 Zone 2, zone 1, zone 0, zone 21, zone 20 /26 SIPROM T Universal SITRANS TR00 Transmitters for connection to resistance thermometers, resistance-based sensors, thermocouples and DC voltages up to 1.1 V Two-wire system Universal, Zone 2, zone 1, zone 21 Zone 2, zone 1, zone 0, zone 21, zone 20 /2 SIMATIC PDM HART SITRANS TW Transmitters for connection to resistance thermometers, resistance-based sensors, thermocouples, DC voltages and DC currents for: Four-wire system Safe area Zone 1, zone 0, zone 21, zone 20 /8 SIMATIC PDM Transmitter for temperature for field mounting SITRANS TF2 Digital display thermometer Transmitter with LCD display and mounted Pt /50 Local programming using keys SITRANS TF Transmitters for connection to resistance thermometers, resistance-based sensors, thermocouples and DC voltages up to 1.1 V In field housing for heavy industrial use Zone 2, zone 1 Zone 2, zone 1, zone 0 /5 Depends on mounted transmitter TH200/TH00 Field indicator for 4 to 20 ma signals SITRANS TF Field indicator for 4 to 20 ma signals Display of units can be userdefined Zone 2, zone 1 - /5 - Siemens FI /

4 SITRANS T Measuring instruments for temperature Product overview Resistance thermometers Device Largest measuring range Page Temperature transmitters factory-installed in connection head of a resistance thermometer (selection list) SITRANS TH400 PA or FF SITRANS TH200/TH00 SITRANS TH100 /64 Flue gas resistance thermometers C ( F) /66 Low-pressure screw-in resistance thermometers /67 Without neck tube With neck tube C ( F) C ( F) High-pressure screw-in resistance thermometers C ( F) /69 High-pressure welding-type resistance thermometers C ( F) /70 Flange-type resistance thermometers C ( F) /71 Resistance thermometers for damp rooms C ( F) /7 /4 Siemens FI

5 SITRANS T Measuring instruments for temperature Product overview Device Largest measuring range Page Thermocouples Temperature transmitters factory-installed in connection head of a thermocouple (selection list) SITRANS TH400 PA or FF SITRANS TH200/TH00 /8 Straight thermocouples C ( F) /85 Jacket thermocouples with extension lead C ( F) /88 Jacket thermocouples with connection head, form B C ( F) /89 Jacket thermocouples with socket C ( F) /90 Cold junction/cold junction thermostat Cold junction with built-in power supply unit Reference temperature 0 or 20 C ( F) /92 Cold junction thermostat Reference temperature For max. 6 or 12 measuring points 50, C (122, F) For max. 12 or 24 measuring points 50, 60 or 70 C (122, 144 or 158 F) /9 /94 Resistance thermometers for food, pharmaceuticals and biotechnology Resistance thermometers For installation in pipelines and tanks For temperature measurements with hygienic requirements C ( F) /95 Resistance thermometers with clamp-on system The temperature sensors with pipe sleeve are primarily used for temperature monitoring in sterile applications in the food and pharmaceutical industries C ( F) /99 Siemens FI /5

6 Transmitters for mounting in sensor head SITRANS TH100 two-wire system (Pt100) Overview Application Used in conjunction with Pt100 resistance thermometers, the SITRANS TH100 transmitters are ideal for measuring temperatures in all industries. Due to its compact size it can be installed in the connection head type B (DIN 4729) or larger. The output signal is a direct current from 4 to 20 ma that is proportional to the temperature. Parameterization is implemented over the PC using the parameterization software SIPROM T and the modem for SITRANS TH100/TH200. If you already have a "modem for SITRANS TK" (Order No. 7NG190-6KB), you can continue using this to parameterize the SITRANS TH100. Transmitters of the "intrinsically-safe" type of protection can be installed within potentially explosive atmospheres. The devices comply with the Directive 94/9/EC (ATEX), as well as FM and CSA regulations. The SITRANS TH100 dispenses with electrical isolation and universal sensor connection to provide a low-cost alternative for Pt100 measurements. For the parameterization, the SIPROM T software is used in combination with the modem for SITRANS TH100/TH200. Its extremely compact design makes the SITRANS TH100 ideal for the retrofitting of measuring points or for the use of analog transmitters. The transmitter is available as a non-ex version as well as for use in potentially explosive atmospheres. Benefits Two-wire transmitter Assembly in connection head type B (DIN 4729) or larger, or on a standard DIN rail Can be programmed, which means that the sensor connection, measuring range, etc. can also be programmed Intrinsically-safe version for use in potentially explosive areas Function Mode of operation The measured signal supplied by a Pt100 resistance thermometer (2, or 4-wire system) is amplified in the input stage. The voltage, which is proportional to the input variable, is then converted into digital signals by a multiplexer in an analog/digital converter. They are converted in the microcontroller in accordance with the sensor characteristics and further parameters (measuring range, damping, ambient temperature etc.). The signal prepared in this way is converted in a digital/analog converter into a load-independent direct current of 4 to 20 ma. An EMC filter protects the input and output circuits against electromagnetic interferences. Input Output Microcontroller SITRANS TH100, function diagram /6 Siemens FI

7 Siemens AG 2008 Transmitters for mounting in sensor head SITRANS TH100 two-wire system (Pt100) Technical specifications Input Resistance thermometer Measured variable Temperature Sensor type PT100 to IEC Characteristic Temperature-linear Type of connection 2, or 4-wire circuit Resolution 14 bit Measuring accuracy Span <250 C (450 F) < 0.25 C (0.45 F) Span >250 C (450 F) < 0.1% of span Repeatability < 0.1 C (0.18 F) Measuring current approx. 0.4 ma Measuring cycle < 0.7 s Range C ( F) Measured span C ( F) Unit C or F Offset programmable: C ( F) Line resistance Max. 20 Ω (total from feeder and return conductor) Noise rejection 50 and 60 Hz Output Output signal ma, two-wire Power supply V DC (0 V for Ex) Max. load (U aux V)/0.02 A Overrange ma, continuously adjustable (default value: ma) Error signal (in the event of sensor breakage) ma, continuously adjustable (default value:.6 ma or 22.8 ma) Damping time s (default value: 0 s) Protection Against reversed polarity Resolution 12 bit Accuracy at 2 C (7.4 F) < 0.1% of span Temperature effect < 0.1%/10 C (0.1%/18 F) Effect of auxiliary power < 0.01% of span/v Effect of load impedance < 0.025% of max. span/100 Long-term drift in the first month < 0.025% of max. span after one year < 0.05% of max. span after 5 years < 0.05% of max. span Ambient temperature Ambient temperature range C ( F) Storage temperature range C ( F) Relative humidity 98%, with condensation Electromagnetic compatibility According to EN 6126 and NAMUR NE21 Construction Approx. weight 50 g Dimensions See dimension drawing Material Molded plastic Cross-section of cables Max. 2.5 mm 2 (AWG 1) Degree of protection to EN Enclosure IP40 Terminals IP00 Certificate and approvals Explosion protection ATEX EC type test certificate PTB 05 ATEX 2049X Intrinsically-safe" type of protection Operating equipment that is nonignitable and has limited energy type of protection Factory setting: Pt100 (IEC 751) with three-wire circuit Measuring range: C ( F) Error signal in the event of sensor breakage: 22.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s Selection and Ordering data II 1G EEx ia IIC T6/T4 II 2(1)G EEx ia/ib IIC T6/T4 II G EEx nal IIC T6/T4 Explosion protection to FM for USA and Canada (cfm US ) FM approval PID Degree of protection IS Cl I, II, III, Div 1, GP ABCDEFG T4/T5/T6 IS Cl I, ZN 0, 1 AEx ia IIC T4/T5/T6 Nl Cl I, II, III, Div 2, GP ABCDFG T4/T5/T6 Cl I, ZN 2, GP IIC T4/T5/T6 Software requirements for SIPROM T PC operating system: Windows ME, 2000 and XP; also Windows 95, 98 and 98SE, but only in connection with RS-22 modem. SITRANS TH100 temperature transmitters for Pt100 For installation in the connection head, Type B (DIN 4729) Two-wire system ma, programmable, without electrical isolation Order-No. Without explosion protection } 7NG211-0NN00 C) With explosion protection, "Intrinsic safety" and for zone 2 - to ATEX } 7NG211-0AN00 C) - to FM (cfm US ) } 7NG211-0BN00 C) Further designs Please add "-Z" to Order No. and specify Order code(s) Customer-defined operating data Test protocol (5 measuring points) Accessories Modem for SITRANS TH100 and TH200 incl. SIPROM T parameterization software Order code Y01 C11 Order-No. with USB connection } 7NG092-8KU C) with RS 22 connection } 7NG092-8KM C) CD for measuring instruments } A5E G) for temperature With documentation in German, English, French, Spanish, Italian, Portuguese and SIPROM T parameterization software DIN rail adapters for head transmitters (Quantity delivered: 5 units) } 7NG092-8KA } Available ex stock. C) Subject to export regulations AL: N, ECCN: EAR99. G) Subject to export regulations AL: N, ECCN: 5D992B1. Power supply units see "SITRANS I supply units and input isolators". Siemens FI /7

8 Transmitters for mounting in sensor head SITRANS TH100 two-wire system (Pt100) Dimensional drawings Siemens AG 2007 Mounting on DIN rail 44 (1.7) SITRANS TH100, mounting of transmitter on DIN rail 14 (0.55) 50,5 (1.99) (1.0) (1.) 59,6 (2.5) SITRANS TH100, dimensions in mm (inch) Schematics DIN rail adaptor, dimensions in mm (inch) SITRANS TH100, sensor connection assignment /8 Siemens FI

9 Overview Siemens AG 2007 Transmitters for mounting in sensor head SITRANS TH200 two-wire system, universal Configuration status stored in EEPROM Expanded diagnostic functions, such as slave pointer, operating hours counter, etc. Special characteristic Electromagnetic compatibility to EN 6126 and NE21 Ultra flexible - with the universal SITRANS TH200 transmitter Two-wire devices for 4 to 20 ma Mounting in the connection head of the temperature sensor Universal input for virtually any type of temperature sensor Configurable over PC Benefits Compact design Flexible mounting and center hole allow you to select your preferred type of installation Electrically isolated Test sockets for multimeters Diagnostics LED (green/red) Sensor monitoring open circuits and short-circuits Self-monitoring Application SITRANS TH200 transmitters can be used in all industrial sectors. Due to their compact size they can be installed in the connection head type B (DIN 4729) or larger. The following sensors/signal sources can be connected over their universal input module: Resistance thermometers (two, three or four-wire system) Thermocouple elements Resistance-based sensors and DC voltage sources The output signal is a direct current from 4 to 20 ma in accordance with the sensor characteristic. Transmitters of the "Intrinsically-safe" type of protection can be installed within potentially explosive atmospheres (zone 0). Type of protection Ex n (zone 2) can also be achieved. Explosionproof versions for Europe, USA and Canada are also available. Function The SITRANS TH200 is configured over a PC. A USB or RS 22 modem is linked to the output terminals for this purpose. The configuration data can now be edited using the SIPROM T software tool. The configuration data are then permanently stored in the non-volatile memory (EEPROM). Once the sensors and power supply have been correctly connected, the transmitter outputs a temperature-linear output signal and the diagnostics LED displays a green light. In the case of a sensor short-circuit, the LED flashes red, an internal device fault is indicated by a steady red light. The test socket can be used to connect an ammeter at any time for monitoring purposes and plausibility checks. The output current can be read without any interruption, or even without opening the current loop. µ µ Input Output SITRANS TH200 function diagram Siemens FI /9

10 Transmitters for mounting in sensor head SITRANS TH200 two-wire system, universal Technical specifications Input Resistance thermometer Measured variable Sensor type to IEC to JIS C 1604; a = K -1 to IEC Special type Sensor factor Temperature Pt25 to Pt1000 Pt25 to Pt1000 Ni25 to Ni1000 Units C or F Connection Standard connection Generation of average value Generation of difference Interface Two-wire system Three-wire system Four-wire system Sensor current Response time Open-circuit monitoring Short-circuit monitoring Measuring range Min. measured span Characteristic curve Resistance-based sensors Measured variable Sensor type Units Connection Normal connection Generation of average value Generation of difference Interface Two-wire system Three-wire system Four-wire system Sensor current Response time over special characteristic (max. 0 points) (adaptation of the basic type, e.g. Pt100 to version Pt25... Pt1000) 1 resistance thermometer (RTD) in 2-wire, -wire or 4-wire system 2 identical resistance thermometers in 2-wire system for generation of average temperature 2 identical resistance thermometers (RTD) in 2-wire system (RTD 1 RTD 2 or RTD 2 RTD 1) Parameterizable line resistance 100 Ω (loop resistance) No balancing required No balancing required 0.45 ma 250 ms for 1 sensor with opencircuit monitoring can be switched off can be switched off (value is adjustable) Parameterizable (see table "Digital measuring errors") 10 C (18 F) Temperature-linear or special characteristic Actual resistance Resistance-based, potentiometers Ω 1 resistance-based sensor (R) in 2-wire, -wire or 4-wire system 2 resistance-based sensors in 2-wire system for generation of average value 2 resistance thermometers in 2-wire system (R1 R2 or R2 R1) Parameterizable line resistance 100 Ω (loop resistance) No balancing required No balancing required 0.45 ma 250 ms for 1 sensor with opencircuit monitoring Open-circuit monitoring Short-circuit monitoring Measuring range Min. measured span Characteristic curve Thermocouple elements Measured variable Sensor type (thermocouples) can be switched off can be switched off (value is adjustable) Parameterizable, max Ω (see Table "Digital measuring errors") 5 Ω Ω (see Table "Digital measuring errors") Resistance-linear or special characteristic Temperature Type B Pt0Rh-Pt6Rh to DIN IEC 584 Type C W5%-Re to ASTM 988 Type D W%-Re to ASTM 988 Type E NiCr-CuNi to DIN IEC 584 Type J Fe-CuNi to DIN IEC 584 Type K NiCr-Ni to DIN IEC 584 Type L Fe-CuNi to DIN 4710 Type N NiCrSi-NiSi to DIN IEC 584 Type R Pt1Rh-Pt to DIN IEC 584 Type S Pt10Rh-Pt to DIN IEC 584 Type T Cu-CuNi to DIN IEC 584 Type U Cu-CuNi to DIN 4710 Units C or F Connection Standard connection Generation of average value Generation of difference Response time Open-circuit monitoring Cold junction compensation Internal 1 thermocouple element (TC) 2 thermocouple elements (TC) 2 thermocouple elements (TC) TC1 TC2 or TC2 TC1) 250 ms for 1 sensor with opencircuit monitoring can be switched off With integrated Pt100 resistance thermometer External With external Pt100 IEC (2-wire or -wire connection) External fixed Measuring range Min. measured span Characteristic curve mv sensor Measured variable Sensor type Units Response time Open-circuit monitoring Short-circuit monitoring Cold junction temperature can be set as fixed value Parameterizable (see table "Digital measuring errors") Min C ( F) (see table "Digital measuring errors") Temperature-linear or special characteristic DC voltage DC voltage source (DC voltage source possible over an externally connected resistor) mv 250 ms for 1 sensor with opencircuit monitoring can be switched off can be switched off (value is adjustable) /10 Siemens FI

11 Transmitters for mounting in sensor head SITRANS TH200 two-wire system, universal Measuring range Min. measured span Overload capability of the input Input resistance Characteristic curve Output Output signal Auxiliary power supply Max. load Overrange Error signal (e.g. in the event of sensor breakage) Sample cycle Damping Protection mv mv 2 mv or 20 mv V DC 1 MΩ Voltage-linear or special characteristic ma, 2-wire V DC (to 0 V with EEx) (U aux 11 V)/0.02 A ma, infinitely adjustable (default range:.84 ma ma) ma, infinitely adjustable (default value: 22.8 ma) 0.25 s nominal Software filter 1st order s (parameterizable) Against reversed polarity Electrically isolated Input against output (1 kv eff ) Measuring accuracy Digital measuring errors Reference conditions Auxiliary power supply 24 V ± 1 % Load See Table "Digital measuring errors" 500 Ω Ambient temperature 2 C Warming-up time Error in the analog output (digital/analog converter) Error due to internal cold junction > 5 min < 0.1 % of span < 0.5 C (0.9 F) Temperature effect < 0.1 % of max. span/10 C (18 F) Power supply effect Effect of load impedance Long-term drift in the first month after one year after 5 years Rated conditions Ambient conditions Ambient temperature range Storage temperature range Relative humidity Electromagnetic compatibility Construction Material Weight Dimensions < % of span/v < % of span/100 Ω < 0.02 % of max. span < 0.0 % of max. span < 0.04 % of max. span C ( F) C ( F) < 98 %, with condensation acc. to EN 6126 and NE21 Molded plastic 50 g (0.11 lb) See "Dimensional drawings" Cross-section of cables Max. 2.5 mm² (AWG 1) Degree of protection to IEC Enclosure Terminals IP40 IP00 Certificates and approvals Explosion protection ATEX EC type test certificate "Intrinsic safety" type of protection "Operating equipment that is nonignitable and has limited energy" type of protection Explosion protection to FM for USA and Canada (cfm US ) Factory setting: Pt100 (IEC 751) with three-wire circuit Measuring range: C ( F) Fault current: 22.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s Digital measuring errors Resistance thermometer PTB 05 ATEX 2040X II 1G EEx ia IIC T6/T4 II 2(1)G EEx ia/ib IIC T6/T4 II G EEx nal IIC T6/T4 FM approval PID Degree of protection Software requirements for SIPROM T PC operating system Input Measuring range Min. measured span to IEC Pt ( ) Pt ( ) Pt Pt ( ) Pt ( ) Pt ( ) to JIS C Pt ( ) Pt ( ) Pt Pt ( ) Pt ( ) Pt ( ) Ni 25 to Ni ( ) IS Cl I, II, III, Div 1, GP ABCDEFG T4/T5/T6 IS Cl I, ZN 0, 1 AEx ia IIC T4/T5/T6 NI Cl I, II, III, Div 2, GP ABCDFG T4/T5/T6 Cl I, ZN2, GP IIC T4/T5/T6 Windows ME, 2000 and XP; also Windows 95, 98 and 98 SE, but only in connection with RS 22 modem. Digital accuracy C ( F) C ( F) C ( F) 10 (18) 0,2 (0.6) 10 (18) 0,15 (0.27) 10 (18) 0,1 (0.18) 10 (18) 0,15 (0.27) 10 (18) 0,15 (0.27) 10 (18) 0,2 (0.6) 10 (18) 0,15 (0.27) 10 (18) 0,1 (0.18) 10 (18) 0,15 (0.27) 10 (18) 0,15 (0.27) 10 (18) 0,1 (0.18) Siemens FI /11

12 Transmitters for mounting in sensor head SITRANS TH200 two-wire system, universal Resistance-based sensors Input Thermocouple elements mv sensor Measuring range Min. measured span Ω Ω Ω Resistance ,05 Resistance ,25 Input Measuring range Type B ( ) Type C (W5) ( ) Type D (W) ( ) Type E ( ) Type J ( ) Type K ( ) Type L ( ) Type N ( ) Type R ( ) Type S ( ) Type T ( ) Type U ( ) Input Min. measured span Digital accuracy Digital accuracy C ( F) C ( F) C ( F) Measuring range 100 (180) 2 (5.40) 100 (180) 2 (.60) 100 (180) 2 (.60) 50 (90) 1 (1.80) 50 (90) 1 (1.80) 50 (90) 1 (1.80) 50 (90) 1 (1.80) 50 (90) 1 (1.80) 100 (180) 2 (.60) 100 (180) 2 (.60) 40 (72) 1 (1.80) 50 (90) 2 (.60) Min. measured span mv mv µv mv sensor mv sensor Digital accuracy The digital accuracy is the accuracy after the analog/digital conversion including linearization and calculation of the measured value. An additional error is generated in the output current 4 to 20 ma as a result of the digital/analog conversion of 0.1% of the set span (digital-analog error). The total error under reference conditions at the analog output is the sum from the digital error and the digital-analog error (poss. with the addition of cold junction errors in the case of thermocouple measurements). Siemens AG 2008 Selection and Ordering Data Temperature transmitter SITRANS TH200 for installation in the connection head type B (DIN 4729) 2-wire connection ma, programmable, with electrical isolation Without explosion protection } C) With explosion protection, "Intrinsic safety" and zone 2 - acc. to ATEX } C) - acc. to FM (cfm US ) } C) Further designs Please add "-Z" to Order No. and specify Order code(s) Customer-specific setting of operating data (specify operating data in plain text) with test protocol (5 measuring points) Accessories Modem for SITRANS TH100, TH200 and TR200 incl. SIPROM T parameterization software With USB connection } C) With RS 22 connection } C) CD for measuring instruments for temperature with documentation in German, English, French, Spanish, Italian, Portuguese and SIPROM T parameterization software DIN rail adapters for head transmitters (Quantity delivered: 5 units) } G) Order No. 7NG211-1NN00 7NG211-1AN00 7NG211-1BN00 Order code Y01 C11 Order No. 7NG092-8KU 7NG092-8KM A5E } 7NG092-8KA } Available ex stock. C) Subject to export regulations AL: N, ECCN: EAR99. G) Subject to export regulations AL: N, ECCN: 5D992B1. Power supply units see "SITRANS I supply units and isolation amplifiers". Factory setting: Pt100 (IEC 751) with three-wire circuit Measuring range: C ( F) Fault current: 22.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s /12 Siemens FI Modification 01/2008

13 Dimensional drawings Siemens AG 2008 Transmitters for mounting in sensor head SITRANS TH200 two-wire system, universal Mounting on DIN rail (1) (1) (2) (2) SITRANS TH200, mounting of transmitter on DIN rail () (4) 14 (0.55) 50,5 (1.99) (1.0) 59,6 (2.5) DIN rail adaptor, dimensions in mm (inch) SITRANS TH200, dimensions and pin assignment, dimensions in mm (inch) Siemens FI /1

14 Transmitters for mounting in sensor head SITRANS TH200 two-wire system, universal Schematics Siemens AG 2008 Resistance thermometer Resistance Thermocouple Voltage measurement Current measurement Connection of auxiliary power supply (U aux ) SITRANS TH200, sensor connection assignment /14 Siemens FI

15 Overview Siemens AG 2007 Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal, HART Expanded diagnostic functions, such as slave pointer, operating hours counter, etc. Special characteristic Electromagnetic compatibility to EN 6126 and NE21 "HART" to beat - the universal SITRANS TH00 transmitter Two-wire devices for 4 to 20 ma, HART Mounting in the connection head of the temperature sensor Universal input for virtually any type of temperature sensor Configurable over HART Benefits Compact design Flexible mounting and center hole allow you to select your preferred type of installation Electrically isolated Test sockets for multimeters Diagnostics LED (green/red) Sensor monitoring open circuits and short-circuits Self-monitoring Configuration status stored in EEPROM Application SITRANS TH00 transmitters can be used in all industrial sectors. Due to their compact size they can be installed in the connection head type B (DIN 4729) or larger. The following sensors/signal sources can be connected over their universal input module: Resistance thermometers (two, three or four-wire system) Thermocouple elements Resistance-based sensors and DC voltage sources The output signal is a direct current from 4 to 20 ma in accordance with the sensor characteristic, superimposed by the digital HART signal. Transmitters of the "Intrinsically-safe" type of protection can be installed within potentially explosive atmospheres (zone 0). Type of protection Ex n (Zone 2) can also be achieved. Explosionproof versions for Europe, USA and Canada are also available. Function The SITRANS TH00 is configured over HART. This can be done using a handheld communicator or even more conveniently with a HART modem and the SIMATIC PDM parameterization software. The configuration data are then permanently stored in the non-volatile memory (EEPROM). Once the sensors and power supply have been correctly connected, the transmitter outputs a temperature-linear output signal and the diagnostics LED displays a green light. In the case of a sensor short-circuit, the LED flashes red, an internal device fault is indicated by a steady red light. The test socket can be used to connect an ammeter at any time for monitoring purposes and plausibility checks. The output current can be read without any interruption, or even without opening the current loop. µ µ Input Output SITRANS TH 00 function diagram Siemens FI /15

16 Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal, HART Technical specifications Input Resistance thermometer Measured variable Sensor type to IEC to JIS C 1604; a = K -1 to IEC Special type Sensor factor Temperature Pt25 to Pt1000 Pt25 to Pt1000 Ni25 to Ni1000 Units C or F Connection Standard connection Generation of average value Generation of difference Interface Two-wire system Three-wire system Four-wire system Sensor current Response time Open-circuit monitoring Short-circuit monitoring Measuring range Min. measured span Characteristic curve Resistance-based sensors Measured variable Sensor type Units Connection Normal connection Generation of average value over special characteristic (max. 0 points) (adaptation of the basic type, e.g. Pt100 to version Pt25... Pt1000) 1 resistance thermometer (RTD) in 2-wire, -wire or 4-wire system 2 identical resistance thermometers in 2-wire system for generation of average temperature 2 identical resistance thermometers (RTD) in 2-wire system (RTD 1 RTD 2 or RTD 2 RTD 1) Parameterizable line resistance 100 Ω (loop resistance) No balancing required No balancing required 0.45 ma 250 ms for 1 sensor with opencircuit monitoring can be switched off can be switched off (value is adjustable) Parameterizable (see table "Digital measuring errors") 10 C (18 F) Temperature-linear or special characteristic Actual resistance Resistance-based, potentiometers Ω 1 resistance-based sensor (R) in 2-wire, -wire or 4-wire system 2 resistance-based sensors in 2-wire system for generation of average value Generation of difference 2 resistance thermometers in 2- wire system (R1 R2 or R2 R1) Interface Two-wire system Three-wire system Four-wire system Sensor current Response time Parameterizable line resistance 100 Ω (loop resistance) No balancing required No balancing required 0.45 ma 250 ms for 1 sensor with opencircuit monitoring Open-circuit monitoring Short-circuit monitoring Measuring range Min. measured span Characteristic curve Thermocouples Measured variable Sensor type (thermocouples) can be switched off can be switched off (value is adjustable) Parameterizable, max Ω (see Table "Digital measuring errors") Ω (see Table "Digital measuring errors") Resistance-linear or special characteristic Temperature Type B Pt0Rh-Pt6Rh to DIN IEC 584 Type C W5%-Re to ASTM 988 Type D W%-Re to ASTM 988 Type E NiCr-CuNi to DIN IEC 584 Type J Fe-CuNi to DIN IEC 584 Type K NiCr-Ni to DIN IEC 584 Type L Fe-CuNi to DIN 4710 Type N NiCrSi-NiSi to DIN IEC 584 Type R Pt1Rh-Pt to DIN IEC 584 Type S Pt10Rh-Pt to DIN IEC 584 Type T Cu-CuNi to DIN IEC 584 Type U Cu-CuNi to DIN 4710 Units C or F Connection Standard connection Generation of average value Generation of difference Response time Open-circuit monitoring Cold junction compensation Internal 1 thermocouple (TC) 2 thermocouples (TC) 2 thermocouples (TC) TC1 TC2 or TC2 TC1) 250 ms for 1 sensor with opencircuit monitoring can be switched off With integrated Pt100 resistance thermometer External With external Pt100 IEC (2-wire or -wire connection) External fixed Measuring range Min. measured span Characteristic curve mv sensor Measured variable Sensor type Units Response time Open-circuit monitoring Short-circuit monitoring Cold junction temperature can be set as fixed value Parameterizable (see table "Digital measuring errors") Min C ( F) (see table "Digital measuring errors") Temperature-linear or special characteristic DC voltage DC voltage source (DC voltage source possible over an externally connected resistor) mv 250 ms for 1 sensor with opencircuit monitoring can be switched off can be switched off (value is adjustable) /16 Siemens FI

17 Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal, HART Measuring range Min. measured span Overload capacity of the input Input resistance Characteristic curve Output Output signal Auxiliary power supply Max. load Overrange Error signal (e.g. in the event of sensor breakage) Sample cycle Damping Protection mv mv 2 mv or 20 mv V DC 1 MΩ Voltage-linear or special characteristic ma, 2-wire with communication to HART Rev V DC (to 0 V with EEx) (U aux 11 V)/0.02 A ma, continuously adjustable (default range:.84 ma ma) ma, continuously adjustable (default value: 22.8 ma) 0.25 s nominal Software filter 1st order s (parameterizable) Against reversed polarity Electrically isolated Input against output (1 kv eff ) Measuring accuracy Digital measuring errors Reference conditions Auxiliary power supply 24 V ± 1% Load See Table "Digital measuring errors" 500 Ω Storage temperature 2 C Warming-up time Error in the analog output (digital/analog converter) Error due to internal cold junction > 5 min < 0.1% of span < 0.5 C (0.9 F) Temperature effect < 0.1% of max. span/10 C (18 F) Power supply effect Effect of load impedance Long-term drift in the first month after one year after 5 years Rated conditions Ambient temperature Ambient temperature range Storage temperature range Relative humidity Electromagnetic compatibility Construction Material Weight Dimensions < 0.005% of span/v < 0.012% of span/100 Ω < 0.02% of max. span < 0.0% of max. span < 0.04% of max. span C ( F) C ( F) < 98%, with condensation acc. to EN 6126 and NE21 Molded plastic 50 g (0.11 lb) See "Dimensional drawings" Cross-section of cables Max. 2.5 mm² (AWG 1) Degree of protection to IEC Enclosure Terminals IP40 IP00 Certificate and approvals Explosion protection ATEX EC type test certificate "Intrinsic safety" type of protection "Operating equipment that is nonignitable and has limited energy" type of protection Explosion protection to FM for USA and Canada (cfm US ) Factory setting: Pt100 (IEC 751) with three-wire circuit Measuring range: C ( F) Fault current: 22.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s Digital measuring errors Resistance thermometer PTB 05 ATEX 2040X II 1G EEx ia IIC T6/T4 II 2(1)G EEx ia/ib IIC T6/T4 II G EEx nal IIC T6/T4 FM approval PID Degree of protection Input Measuring range Min. measured span to IEC Pt ( ) Pt ( ) Pt Pt ( ) Pt ( ) Pt ( ) to JIS C Pt ( ) Pt ( ) Pt Pt ( ) Pt ( ) Pt ( ) Ni 25 to Ni ( ) IS Cl I, II, III, Div 1, GP ABCDEFG T4/T5/T6 IS Cl I, ZN 0, 1 AEx ia IIC T4/T5/T6 NI Cl I, II, III, Div 2, GP ABCDFG T4/T5/T6 Cl I, ZN2, GP IIC T4/T5/T6 Digital accuracy C ( F) C ( F) C ( F) 10 (18) 0.2 (0.6) 10 (18) 0.15 (0.27) 10 (18) 0.1 (0.18) 10 (18) 0.15 (0.27) 10 (18) 0.15 (0.27) 10 (18) 0.2 (0.6) 10 (18) 0.15 (0.27) 10 (18) 0.1 (0.18) 10 (18) 0.15 (0.27) 10 (18) 0.15 (0.27) 10 (18) 0.1 (0.18) Siemens FI /17

18 Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal, HART Resistance-based sensors Input Thermocouples mv sensor Measuring range Min. measured span Ω Ω Ω Resistance Resistance Input Measuring range Type B ( ) Type C (W5) ( ) Type D (W) ( ) Type E ( ) Type J ( ) Type K Min. measured span Digital accuracy Digital accuracy C ( F) C ( F) C ( F) ( ) Type L ( ) Type N ( ) Type R ( ) Type S ( ) Type T ( ) Type U ( ) Input Measuring range 100 (180) 2 (5.40) 100 (180) 2 (.60) 100 (180) 2 (.60) 50 (90) 1 (1.80) 50 (90) 1 (1.80) 50 (90) 1 (1.80) 50 (90) 1 (1.80) 50 (90) 1 (1.80) 100 (180) 2 (.60) 100 (180) 2 (.60) 40 (72) 1 (1.80) 50 (90) 2 (.60) Min. measured span mv mv µv mv sensor mv sensor Digital accuracy The digital accuracy is the accuracy after the analog/digital conversion including linearization and calculation of the measured value. An additional error is generated in the output current 4 to 20 ma as a result of the digital/analog conversion of 0.1% of the set span (digital-analog error). The total error under reference conditions at the analog output is the sum from the digital error and the digital-analog error (poss. with the addition of cold junction errors in the case of thermocouple measurements). Selection and Ordering Data Temperature transmitter SITRANS TH00 for installation in the connection head type B (DIN 4729) 2-wire connection ma, communication-capable acc. to HART, with electrical isolation Without explosion protection } C) With explosion protection; type of protection: "Intrinsic safety" and EEx n - acc. to ATEX } C) - acc. to FM (cfm US ) } C) Further designs Please add "-Z" to Order No. and specify Order code(s) Customer-specific setting of operating data (specify operating data in plain text) with test protocol (5 measuring points) Accessories CD for measuring instruments for temperature with documentation in German, English, French, Spanish, Italian, Portuguese and SIPROM T parameterization software HART modem } G) With RS 22 connection } D) With USB connection } D) SIMATIC PDM operating software DIN rail adapters for head transmitters (Quantity delivered: 5 units) Order No. 7NG212-0NN00 7NG212-0AN00 7NG212-0BN00 Order code Y01 C11 Order No. A5E MF4997-1DA 7MF4997-1DB See Section 9 } 7NG092-8KA } Available ex stock. C) Subject to export regulations AL: N, ECCN: EAR99. D) Subject to export regulations AL: N, ECCN: EAR99H. G) Subject to export regulations AL: N, ECCN: 5D992B1. Power supply units see "SITRANS I supply units and isolation amplifiers". /18 Siemens FI

19 Dimensional drawings Siemens AG 2008 Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal, HART Mounting on DIN rail (1) (1) (2) (2) SITRANS TH00, mounting of transmitter on DIN rail () (4) 14 (0.55) 50,5 (1.99) (1.0) 59,6 (2.5) DIN rail adapter, dimensions in mm (inch) SITRANS TH00, dimensions and pin assignment, dimensions in mm (inch) Siemens FI /19

20 Transmitters for mounting in sensor head SITRANS TH00 two-wire system, universal, HART Schematics Siemens AG 2008 Resistance thermometer Resistance Thermocouple Voltage measurement Current measurement Connection of auxiliary power supply (U aux ) SITRANS TH200/TH00, sensor connection assignment /20 Siemens FI

21 Overview Siemens AG 2008 Transmitters for mounting in sensor head SITRANS TH400 fieldbus transmitter Application Linearized temperature measurement with resistance thermometers or thermocouple elements Differential, mean-value or redundant temperature measurement with resistance thermometers or thermocouple elements Linear resistance and bipolar millivolt measurements Differential, mean-value or redundant resistance and bipolar millivolt measurements SITRANS TH400 fieldbus transmitters Versions: for FOUNDATION Fieldbus and for PROFIBUS PA The SITRANS TH400 temperature transmitter is a small field bus transmitter for mounting in the connection head of form B. Extensive functionality enables the temperature transmitter to be precisely adapted to the plant s requirements. Operation is very simple in spite of the numerous setting options. Thanks to its universal concept it can be used in all industries and is easy to integrate in Totally Integrated Automation applications. Temperature transmitters with type of protection "Intrinsic safety" may be installed within potentially explosive atmospheres (zone 1) or in zone 0. The devices have an EC type test certificate and meet the appropriate harmonized European standards (ATEX). In addition they offer approvals for USA (FM) and Canada (CSA). Installing SITRANS TH400 in temperature sensors turns them into complete, bus-capable measuring points; compact - and in a single device. Function Features common Mounting in connection head, type B, to DIN 4729, or larger Polarity-neutral bus connection 24-bit analog-digital converter for high resolution Electrically isolated Intrinsically-safe version for use in potentially explosive areas Special characteristic Sensor redundance Transmitter with PROFIBUS PA communication Function blocks: 2 x analog Transmitter with FOUNDATION Fieldbus communication Function blocks: 2 x analog and 1 x PID Functionality: Basic or LAS Mode of operation The following function plan explains the mode of operation of the transmitter. The only difference between the two versions of the SITRANS TH400 (7NG and 7NG ) is the type of fieldbus protocol used (PROFIBUS PA or FOUNDATION fieldbus). SITRANS TH400, function diagram Siemens FI /21

22 Transmitters for mounting in sensor head SITRANS TH400 fieldbus transmitter System communication SITRANS TH400, communication interface Technische Daten Input Analog-to-digital conversion Measurement rate Resolution Resistance thermometer Pt25... Pt1000 to IEC 60751/JIS C 1604 < 50 ms 24 Bit Measuring range C ( F) Ni25... Ni1000 to DIN 4760 Measuring range C ( F) Cu10... Cu1000, α = 0,00427 Measuring range C ( F) Line resistance per sensor cable Sensor current Sensor fault detection Sensor break detection Sensor short-circuit detection Resistance-based sensors Measuring range Line resistance per sensor cable Sensor current Sensor fault detection Sensor break detection Sensor short-circuit detection s s Max. 50 Ω Nominal 0.2 ma Yes Yes, < 15 Ω 0 Ω kω Max. 50 Ω Nominal 0.2 ma Yes Yes, < 15 Ω Siemens AG 2007 Thermocouple to IEC 584 Type B Type E Type J Type K Type N Type R Type S Type T to DIN 4710 Type L Type U to ASTM E Type W Type W5 to IEC External cold junction compensation Sensor fault detection Sensor break detection Sensor short-circuit detection Sensor current in the event of open-circuit monitoring mv sensor - voltage input Measuring range Input resistance Output Filter time (programmable) Update time Measuring accuracy Measuring range C ( F) C ( F) C ( F) C ( F) C ( F) C ( F) C ( F) C ( F) C ( F) C ( F) C ( F) C ( F) C ( F) Yes Yes, < mv 4 µa mv 10 MΩ s < 400 ms Accuracy is defined as the higher value of general values and basic values. General values Type of input All Basic values Type of input Absolute accuracy Temperature coefficient ±0,05% of ±0,002% of measured value measured value/ C Basic accuracy Temperature coefficient Pt100 and Pt1000 ±0.1 C ±0.002 C/ C Ni100 ±0.15 C ±0.002 C/ C Cu10 ±1. C ±0.02 C/ C Resistance-based sensors ±0.05 Ω ±0.002 Ω/ C Voltage source ±10 µv ±0.2 µv/ C Thermal element, type: E, J, K, L, N, T, U Thermal element, type: B, R, S, W, W5 ±0.5 C ±1 C Cold junction compensation ±0.5 C Reference conditions Warming-up time Signal-to-noise ratio Calibration condition 0 s Min. 60 db C ( F) ±0.01 C/ C ±0.025 C/ C /22 Siemens FI

23 Transmitters for mounting in sensor head SITRANS TH400 fieldbus transmitter Rated conditions Ambient temperature Permissible ambient temperature Permissible storage temperature Relative humidity Insulation resistance Test voltage Continuous operation Mechanical testing Vibrations (DIN class B) to Electromagnetic compatibility EMC noise voltage influence Extended EMC noise immunity: NAMUR NE 21, criterion A, Burst EMC 2004/108/EC Emission and Noise Immunity to Construction Dimensions Degree of protection Transmitter enclosure Terminal Approx. weight Auxiliary power supply Power supply Standard ATEX, FM, UL and CSA In FISCO installation Power consumption Max. increase in power consumption in the event of a fault Certificate and approvals C ( F) C ( F) 98%, with condensation 500 V AC for 60 s 50 V AC/75 V DC IEC and IEC g/ Hz < ±0,1% of span < ±1% of span EN 6126 Ø 44 x 26. mm (Ø 1.7 x 1.04 inch) IP40 IP00 55 g (0.12 lb) DC V DC V DC V < 11 ma < 7 ma ATEX 94/9/EG to EN 50014, EN 50020, EN , EN 50284, IEC (FISCO) FM to 600, 610, 611 CSA, CAN/CSA to C22.2 No. 142, No. 157, No. 21 CAN/CAS to E79-0, -11, -15 Explosion protection ATEX for 7NG214-0AN00 or 7NG215-0AN00 - Type of protection: "Approved for operation in potentially explosive atmospheres, Zone 0 and Zone 1" II 1 GD or II 2 (1) GD, T65 C... T105 C EEx ia IIC or EEx ib [ia] IIC T4... T6 - EC type test certificate KEMA 06 ATEX 0264 X for 7NG214-0NN00 or 7NG215-0NN00 - Type of protection: "Approved for operation in potentially explosive atmospheres, Zone 2" EEx na [nl] IIC T4... T6 - EC type test certificate KEMA 06 ATEX 026 X Explosion protection: FM for USA for 7NG214-0AN00 or 7NG215-0AN00 - FM approval FM Degree of protection IS Class I, Div 1 Groups A, B, C, D T4/T5/T6, FISCO IS Class I, Zone 0, AEx ia, IIC T4/T5/T6, FISCO for 7NG214-0NN00 or 7NG215-0NN00 - FM approval FM NI Class I, Div. 2, Groups A, B, C, D T4/T5/T6, FNICO - Degree of protection NI Class I, Div 2, Groups A, B, C, D T4/T5/T6, FNICO Explosion protection for Canada for 7NG214-0AN00 or 7NG215-0AN00 - CSA approval CSA Degree of protection IS Class I, Groups A, B, C, D T4/T5/T6 Ex ia IIC T4/T5/T6 und Ex ib [ia] IIC T4/T5/T6 for 7NG214-0NN00 or 7NG215-0NN00 - CSA approval CSA Degree of protection Class I, Div 2, Groups A, B, C, D T4/T5/T6 Communication Parameterization interface PROFIBUS PA connection - Protocol Profile.0 - Address (for delivery) 126 FOUNDATION Fieldbus connection - Protocol FF Protocoll Ex na IIC T4/T5/T6 und Ex ib [ia] IIC T4/T5/T6 - Functionality Basic or LAS - Version ITK Function blocks 2 x Analog and 1 x PID Factory setting for SITRANS TH400 PA and SITRANS TH400 FF Sensor Type of connection Unit C Failure mode Filter time only for SITRANS TH400 PA Pt100 (IEC) Three-wire system Last valid value 0 s PA address 126 PROFIBUS Ident No. only for SITRANS TH400 FF Node address 22 Manufacturer-specific Siemens FI /2

24 Transmitters for mounting in sensor head SITRANS TH400 fieldbus transmitter Selection and Ordering data Order No. Temperature transmitter SITRANS TH400 for installation in the sensor head, with electrical isolation, order instruction manual separately. Bus-capable to PROFIBUS PA - without explosion protection, EEx n for zone 2 - with explosion protection intrinsic safety to ATEX/FM/CSA Bus-capable to FOUNDATION Fieldbus - without explosion protection, EEx n for zone 2 - with explosion protection intrinsic safety to ATEX/FM/CSA Further designs Please add -Z to Order No. and specifiy Order code (s) and plain text. Customer-specific setting of operating data (specify in plain text) } 7NG214-0NN00 } 7NG214-0AN00 } 7NG215-0NN00 } 7NG215-0AN00 Order code Y01 1) With test protocol (5 measuring points) C11 1) Accessories CD for measuring instruments for temperature with documentation in German, English, French, Spanish, Italian, Portuguese and SIPROM T parameterization software Order No. } A5E G) SIMATIC PDM operating software see chapter 9 For additional PA components } Available ex stock. see catalog IK PI 1) For TH400 FF available soon. G) Subject to export regulations AL: N, ECCN: 5D992B1. Dimensional drawings s W SITRANS TH400 dimensions in mm (inches) and connections /24 Siemens FI

25 Transmitters for mounting in sensor head SITRANS TH400 fieldbus transmitter Schematics Resistance thermometer Thermocouple Resistance Voltage measurement SITRANS TH400, sensor connection assignment Siemens FI /25

26 Transmitters for rail mounting SITRANS TR200 two-wire system, universal Overview Application SITRANS TR200 transmitters can be used in all industrial sectors. Their compact design enables simple mounting on standard DIN rails on-site in protective boxes or in control cabinets. The following sensors/signal sources can be connected over their universal input module: Resistance thermometers (two, three or four-wire system) Thermocouple elements Resistance-based sensors and DC voltage sources The output signal is a direct current from 4 to 20 ma in accordance with the sensor characteristic. Transmitters of the "Intrinsically-safe" or Ex nal (zone 2) type of protection can be installed within potentially explosive atmospheres. Ultra flexible - with the universal SITRANS TR200 transmitter Two-wire devices for 4 to 20 ma Enclosure for rail mounting Universal input for virtually any type of temperature sensor Configurable over PC Benefits Compact design Electrically isolated Test sockets for multimeters Diagnostics LED (green/red) Sensor monitoring open circuits and short-circuits Self-monitoring Configuration status stored in EEPROM Expanded diagnostic functions, such as slave pointer, operating hours counter, etc. Special characteristic Electromagnetic compatibility to EN 6126 and NE21 Function The SITRANS TR200 is configured over a PC. A USB or RS 22 modem is linked to the output terminals for this purpose. The configuration data can now be edited using the SIPROM T software tool. The configuration data are then permanently stored in the non-volatile memory (EEPROM). Once the sensors and power supply have been correctly connected, the transmitter outputs a temperature-linear output signal and the diagnostics LED displays a green light. In the case of a sensor short-circuit, the LED flashes red, an internal device fault is indicated by a steady red light. The test socket can be used to connect an ammeter at any time for monitoring purposes and plausibility checks. The output current can be read without any interruption, or even without opening the current loop µ 4 µ 5 6 SITRANS TR200 function diagram /26 Siemens FI

27 Transmitters for rail mounting SITRANS TR200 two-wire system, universal Technical specifications Input Resistance thermometer Measured variable Sensor type to IEC to JIS C 1604; a= K -1 to IEC Special type Sensor factor Temperature Pt25 to Pt1000 Pt25 to Pt1000 Ni25 to Ni1000 Units C or F Connection Standard connection Generation of average value Generation of difference Interface Two-wire system Three-wire system Four-wire system Sensor current Response time T 6 Open-circuit monitoring Short-circuit monitoring Measuring range Min. measured span Characteristic curve Resistance-based sensors Measured variable Sensor type Units Connection Normal connection Generation of average value Generation of difference Interface Two-wire system Three-wire system Four-wire system Sensor current Over special characteristic (max. 0 points) (adaptation of the basic type, e.g. Pt100 to version Pt25... Pt1000) 1 resistance thermometer (RTD) in 2-wire, -wire or 4-wire system 2 identical resistance thermometers in 2-wire system for generation of average temperature 2 identical resistance thermometers (RTD) in 2-wire system (RTD 1 RTD 2 or RTD 2 RTD 1) Parameterizable line resistance 100 Ω (loop resistance) No balancing required No balancing required 0.45 ma 250 ms for 1 sensor with opencircuit monitoring Always active (cannot be disabled) Can be switched off (value is adjustable) Parameterizable (see table "Digital measuring errors") 10 C (18 F) Temperature-linear or special characteristic Actual resistance Resistance-based, potentiometers Ω 1 resistance-based sensor (R) in 2-wire, -wire or 4-wire system 2 resistance-based sensors in 2-wire system for generation of average value 2 resistance thermometers in 2-wire system (R1 R2 or R2 R1) Parameterizable line resistance 100 Ω (loop resistance) No balancing required No balancing required 0.45 ma Response time T 6 Open-circuit monitoring Short-circuit monitoring Measuring range Min. measured span Characteristic curve Thermocouple elements Measured variable Sensor type (thermocouples) 250 ms for 1 sensor with opencircuit monitoring Always active (cannot be disabled) Can be switched off (value is adjustable) Parameterizable, max Ω (see Table "Digital measuring errors") Ω (see Table "Digital measuring errors") Resistance-linear or special characteristic Temperature Type B Pt0Rh-Pt6Rh to DIN IEC 584 Type C W5%-Re to ASTM 988 Type D W%-Re to ASTM 988 Type E NiCr-CuNi to DIN IEC 584 Type J Fe-CuNi to DIN IEC 584 Type K NiCr-Ni to DIN IEC 584 Type L Fe-CuNi to DIN 4710 Type N NiCrSi-NiSi to DIN IEC 584 Type R Pt1Rh-Pt to DIN IEC 584 Type S Pt10Rh-Pt to DIN IEC 584 Type T Cu-CuNi to DIN IEC 584 Type U Cu-CuNi to DIN 4710 Units C or F Connection Standard connection Generation of average value Generation of difference Response time T 6 Open-circuit monitoring Cold junction compensation Internal 1 thermocouple element (TC) 2 identical thermocouple elements (TC) 2 identical thermocouple elements (TC) TC1 TC2 or TC2 TC1 250 ms for 1 sensor with opencircuit monitoring Can be switched off With integrated Pt100 resistance thermometer External With external Pt100 IEC (2-wire or -wire connection) External fixed Measuring range Min. measured span Characteristic curve mv sensor Measured variable Sensor type Units Response time T 6 Cold junction temperature can be set as fixed value Parameterizable (see table "Digital measuring errors") Min C ( F) (see table "Digital measuring errors") Temperature-linear or special characteristic DC voltage DC voltage source (DC voltage source possible over an externally connected resistor) mv 250 ms for 1 sensor with opencircuit monitoring Siemens FI /27

28 Transmitters for rail mounting SITRANS TR200 two-wire system, universal Open-circuit monitoring Measuring range Min. measured span Overload capability of the input Input resistance Characteristic curve Output Output signal Auxiliary power supply Max. load Overrange Error signal (e.g. in the event of sensor breakage) Sample cycle Damping Protection Electrically isolated Measuring accuracy Digital measuring errors Reference conditions Can be switched off Parameterizable max mv 2 mv or 20 mv V DC 1 MΩ Voltage-linear or special characteristic ma, 2-wire V DC (to 0 V with Ex) (U aux 11 V)/0.02 A ma, infinitely adjustable (default range:.84 ma ma) ma, infinitely adjustable (default value: 22.8 ma) 0.25 s Auxiliary power supply 24 V ± 1 % Load Software filter 1st order s (parameterizable) Against reversed polarity Input against output 2.12 kv DC (1.5 kv AC) See Table "Digital measuring errors" 500 Ω Ambient temperature 2 C Warming-up time Error in the analog output (digital/analog converter) Error due to internal cold junction > 5 min < 0.1 % of span < 0.55 C (0.9 F) Temperature effect < 0.1 % of max. span/10 C (18 F) Power supply effect Effect of load impedance Long-term drift in the first month after one year after 5 years Rated conditions Ambient conditions Ambient temperature range Storage temperature range Relative humidity Electromagnetic compatibility Construction Material Weight Dimensions < % of span/v < % of span/100 Ω < 0.02 % of max. span < 0.0 % of max. span < 0.04 % of max. span C ( F) C ( F) < 98 %, with condensation According to EN 6126 and NAMUR NE21 Plastic, electronic module potted 122 g See "Dimensional drawings" Cross-section of cables Max. 2.5 mm² (AWG 1) Degree of protection to IEC Enclosure IP20 Certificates and approvals Explosion protection ATEX EC type test certificate "Intrinsic safety" type of protection Type of protection, "equipment has limited energy" Type of protection, "equipment is non-arcing" Type of protection, "associated equipment" Software requirements for SIPROM T PC operating system Factory setting: Pt100 (IEC 751) with three-wire circuit Measuring range: C ( F) Fault current: 22.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s Digital measuring errors Resistance thermometer PTB 07 ATEX 202X II 2(1)GD EEx ia/ib/ic IIC T6/T4 II G EEx nl IIC T6/T4 II G EEx na T6/T4 II (1)GD [EEx ia] IIC T6/T4 Input Measuring range Min. measured span to IEC Pt ( ) Pt ( ) Pt Pt ( ) Pt ( ) Pt ( ) to JIS C Pt ( ) Pt ( ) Pt Pt ( ) Pt ( ) Pt ( ) Ni 25 to Ni ( ) Windows ME, 2000 and XP; also Windows 95, 98 and 98 SE, but only in connection with RS 22 modem. Digital accuracy C ( F) C ( F) C ( F) 10 (18) 0.2 (0.6) 10 (18) 0.15 (0.27) 10 (18) 0.1 (0.18) 10 (18) 0.15 (0.27) 10 (18) 0.15 (0.27) 10 (18) 0.2 (0.6) 10 (18) 0.15 (0.27) 10 (18) 0.1 (0.18) 10 (18) 0.15 (0.27) 10 (18) 0.15 (0.27) 10 (18) 0.1 (0.18) /28 Siemens FI

29 Resistance-based sensors Input Measuring range Thermocouple elements Transmitters for rail mounting SITRANS TR200 two-wire system, universal Min. measured span Ω Ω Ω Resistance Resistance Input Measuring range C ( F) Type B ( ) Type C (W5) ( ) Type D (W) ( ) Type E ( ) Type J ( ) Type K ( ) Type L ( ) Type N ( ) Type R ( ) Type S ( ) Type T ( ) Type U ( ) Min. measured span Digital accuracy Digital accuracy C ( F) C ( F) 100 (180) 2 (.60) 1) 100 (180) 2 (.60) 100 (180) 1 (1.80) 2) 50 (90) 1 (1.80) 50 (90) 1 (1.80) 50 (90) 1 (1.80) 50 (90) 1 (1.80) 50 (90) 1 (1.80) 100 (180) 2 (.60) 100 (180) 2 (.60) 40 (72) 1 (1.80) 50 (90) 2 (.60) 1) The digital accuracy in the range 0 to 00 C (2 to 572 F) is C (5.4 F). 2) The digital accuracy in the range 1750 to 200 C (182 to 4172 F) is 2 C (.6 F). Siemens AG 2007 Selection and Ordering Data Temperature transmitter SITRANS TR200 for mounting on a standard DIN rail, two-wire system, 4 to 20 ma, programmable, with electrical isolation, with documentation on CD Without explosion protection } D) With explosion protection to } ATEX; type of protection: "Intrinsic safety" EEx ia/ib, non-arcing D) (na), limited energy (nl) Further designs Please add "-Z" to Order No. and specify Order code(s) Customer-specific setting of operating data (specify operating data in plain text) with test protocol (5 measuring points) Accessories Modem for SITRANS TH100, TH200 and TR200 incl. SIPROM T parameterization software With USB connection } C) With RS 22 connection } C) CD for measuring instruments for temperature with documentation in German, English, French, Spanish, Italian, Portuguese and SIPROM T parameterization software } G) Order No. 7NG02-0JN00 7NG02-1JN00 Order code Y01 C11 Order No. 7NG092-8KU 7NG092-8KM A5E } Available ex stock. C) Subject to export regulations AL: N, ECCN: EAR99. D) Subject to export regulations AL: N, ECCN: EAR99H. G) Subject to export regulations AL: N, ECCN: 5D992B1. Power supply units see "SITRANS I supply units and isolation amplifiers". mv sensor Input Measuring range Min. measured span mv mv µv mv sensor mv sensor Digital accuracy The digital accuracy is the accuracy after the analog/digital conversion including linearization and calculation of the measured value. An additional error is generated in the output current 4 to 20 ma as a result of the digital/analog conversion of 0.1% of the set span (digital-analog error). The total error under reference conditions at the analog output is the sum from the digital error and the digital-analog error (poss. with the addition of cold junction errors in the case of thermocouple measurements). Siemens FI /29

30 Transmitters for rail mounting SITRANS TR200 two-wire system, universal Dimensional drawings Schematics TEST 4..20mA SIEMENS SITRANS TR TEST 4..20mA SIEMENS SITRANS TR200 TC sensor with external W RTD CJC Made in Croatia TC sensor with external 2W RTD CJC TC sens. with int./fixed CJC U sensor S1 S mA loop & test S1 2x RTD or R 2W sensor 2x TC sensor with int./fixed CJC RTD or R 2W sensor RTD or R W sensor RTD or R 4W sensor 5 6 S UB s Connection Plan TEST + - A SITRANS TR200, dimensions in mm (inch) SITRANS pin assignment, TR200 /0 Siemens FI

31 Transmitters for rail mounting SITRANS TR200 two-wire system, universal Resistance thermometer Resistance Thermocouple Voltage measurement Current measurement Test terminals Power supply/ ma (U aux ) SITRANS TR200, sensor connection assignment Siemens FI /1

32 Transmitters for rail mounting SITRANS TR00 two-wire system, universal, HART Overview Siemens AG 2007 Special characteristic Electromagnetic compatibility to EN 6126 and NE21 "HART" to beat - the universal SITRANS TR00 transmitter Two-wire devices for 4 to 20 ma, HART Device for rail mounting Universal input for virtually any type of temperature sensor Configurable over HART Benefits Compact design Electrically isolated Test sockets for multimeters Diagnostics LED (green/red) Sensor monitoring open circuits and short-circuits Self-monitoring Configuration status stored in EEPROM Expanded diagnostic functions, such as slave pointer, operating hours counter etc. Application SITRANS TR00 transmitters can be used in all industrial sectors. Their compact design enables simple mounting on standard DIN rails on-site in protective boxes or in control cabinets. The following sensors/signal sources can be connected over their universal input module: Resistance thermometers (two, three or four-wire system) Thermocouple elements Resistance-based sensors and DC voltage sources The output signal is a direct current from 4 to 20 ma in accordance with the sensor characteristic, superimposed by the digital HART signal. Transmitters of the "Intrinsically-safe" or Ex nal (zone 2) type of protection can be installed within potentially explosive atmospheres. Function The SITRANS TR00 is configured over HART. This can be done using a handheld communicator or even more conveniently with a HART modem and the SIMATIC PDM parameterization software. The configuration data are then permanently stored in the non-volatile memory (EEPROM). Once the sensors and power supply have been correctly connected, the transmitter outputs a temperature-linear output signal and the diagnostics LED displays a green light. In the case of a sensor short-circuit, the LED flashes red, an internal device fault is indicated by a steady red light. The test socket can be used to connect an ammeter at any time for monitoring purposes and plausibility checks. The output current can be read without any interruption, or even without opening the current loop µ 4 µ 5 6 SITRANS TR00 function diagram /2 Siemens FI

33 Transmitters for rail mounting SITRANS TR00 two-wire system, universal, HART Technical specifications Input Resistance thermometer Measured variable Sensor type to IEC to JIS C 1604; a= K-1 to IEC Special type Sensor factor Temperature Pt25 to Pt1000 Pt25 to Pt1000 Ni25 to Ni1000 Units C or F Connection Standard connection Generation of average value Generation of difference Interface Two-wire system Three-wire system Four-wire system Sensor current Response time T 6 Open-circuit monitoring Short-circuit monitoring Range Min. measured span Characteristic Resistance-based sensors Measured variable Sensor type Units Connection Normal connection Generation of average value Generation of difference Interface Two-wire system Three-wire system Four-wire system Sensor current Response time T 6 over special characteristic (max. 0 points) (adaptation of the basic type, e.g. Pt100 to version Pt25... Pt1000) 1 resistance thermometer (RTD) in 2-wire, -wire or 4-wire system 2 identical resistance thermometers in 2-wire system for generation of average temperature 2 identical resistance thermometers (RTD) in 2-wire system (RTD 1 RTD 2 or RTD 2 RTD 1) Parameterizable line resistance 100 Ω (loop resistance) No balancing required No balancing required 0.45 ma 250 ms for 1 sensor with opencircuit monitoring can be switched off can be switched off (value is adjustable) Parameterizable (see table "Digital measuring errors") 10 C (18 F) Temperature-linear or special characteristic Actual resistance Resistance-based, potentiometers Ω 1 resistance-based sensor (R) in 2-wire, -wire or 4-wire system 2 resistance-based sensors in 2-wire system for generation of average value 2 resistance thermometers in 2-wire system (R1 R2 or R2 R1) Parameterizable line resistance 100 Ω (loop resistance) No balancing required No balancing required 0.45 ma 250 ms for 1 sensor with opencircuit monitoring Open-circuit monitoring Short-circuit monitoring Range Min. measured span Characteristic Thermocouple elements Measured variable Sensor type (thermocouples) Can be switched off Can be switched off (value is adjustable) Parameterizable, max Ω (see Table "Digital measuring errors") 5 Ω Ω (see Table "Digital measuring errors") Resistance-linear or special characteristic Temperature Type B Pt0Rh-Pt6Rh to DIN IEC 584 Type C W5%-Re to ASTM 988 Type D W%-Re to ASTM 988 Type E NiCr-CuNi to DIN IEC 584 Type J Fe-CuNi to DIN IEC 584 Type K NiCr-Ni to DIN IEC 584 Type L Fe-CuNi to DIN 4710 Type N NiCrSi-NiSi to DIN IEC 584 Type R Pt1Rh-Pt to DIN IEC 584 Type S Pt10Rh-Pt to DIN IEC 584 Type T Cu-CuNi to DIN IEC 584 Type U Cu-CuNi to DIN 4710 Units C or F Connection Standard connection Generation of average value Generation of difference Response time Open-circuit monitoring Cold junction compensation Internal 1 thermocouple (TC) 2 thermocouples (TC) 2 thermocouples (TC) TC1 TC2 or TC2 TC1 250 ms for 1 sensor with opencircuit monitoring Can be switched off With integrated Pt100 resistance thermometer External With external Pt100 IEC (2-wire or -wire connection) External fixed Range Min. measured span Characteristic mv Sensor Measured variable Sensor type Units Response time T 6 Open-circuit monitoring Short-circuit monitoring Cold junction temperature can be set as fixed value Parameterizable (see table "Digital measuring errors") Min C ( F) (see table "Digital measuring errors") Temperature-linear or special characteristic DC voltage DC voltage source (DC voltage source possible over an externally connected resistor) mv 250 ms for 1 sensor with opencircuit monitoring Can be switched off Can be switched off (value is adjustable) Siemens FI /

34 Transmitters for rail mounting SITRANS TR00 two-wire system, universal, HART Range Min. measured span Overload capacity of the input Input resistance Characteristic Output Output signal Power supply Max. load Overrange Error signal (e.g. in the event of sensor breakage) Sample cycle Damping Protection mv mv 2 mv or 20 mv V DC 1 MΩ Voltage-linear or special characteristic ma, 2-wire Communication acc. to HART Rev V DC (to 0 V with EEx) (U aux 11 V)/0.02 A ma, continuously adjustable (default range: ma) ma, continuously adjustable (default value: 22.8 ma) 0.25 s nominal Software filter 1st order s (parameterizable) Against reversed polarity Electrically isolated Input against output (1 kv eff ) Measuring accuracy Digital measuring errors Reference conditions Power supply 24 V ± 1% Load See Table "Digital measuring errors" 500 Ω Storage temperature 2 C Warming-up time Error in the analog ouput (digital/analog converter) Error due to internal cold junction Temperature effect Power supply effect Effect of load impedance Long-term drift in the first month after one year after 5 years Rated conditions Ambient temperature Storage temperature Functional temperature Relative humidity Electromagnetic compatibility Construction Material Approx. weight Dimensions > 5 min < 0.1 % of span < 0.5 C (0.9 F) < 0.1% der max. span/10 C (18 F) < 0.005% of span/v < 0.012% of span/100 Ω < 0.02% of max. span < 0.0% of max. span < 0.04% of max. span C ( F) C ( F) < 98%, with condensation acc. to DIN EN 6126 and NE21 Molded plastic 50 g (0.11 lb) See "Dimension drawings" Cross-section of cables Max. 2.5 mm² (AWG 1) Degree of protection to EN Enclosure Terminals IP40 IP00 Certificate and approvals Explosion protection ATEX EC type test certificate "Intrinsically-safe" type of protection "Operating equipment that is nonignitable and has limited energy" type of protection Type of protection, "equipment is non-arcing" Type of protection, "associated equipment" Explosion protection to FM for USA and Canada (cfm US ) Factory setting: Pt100 (IEC 751) with three-wire circuit Measuring range: C ( F) Fault current: 22.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s Digital measuring errors Resistance thermometer PTB 07 ATEX 202X II 2(1)GD EEx ia/ib/ic IIC T6/T4 II G EEx nl IIC T6/T4 II G EEx na T6/T4 FM approval PID Degree of protection Software requirements for SIPROM T PC operating system: II (1)GD [EEx ia] IIC T6/T4 input Range Min. measured span to IEC Pt ( ) Pt ( ) Pt Pt ( ) Pt ( ) Pt ( ) to JIS C Pt ( ) Pt ( ) Pt Pt ( ) Pt ( ) Pt ( ) Ni 25 to Ni ( ) IS Cl I, II, III, Div 1, GP ABCDEFG T4/T5/T6 IS Cl I, ZN 0, 1 AEx ia IIC T4/T5/T6 NI Cl I, II, III, Div 2, GP ABCDFG T4/T5/T6 Cl I, ZN2, GP IIC T4/T5/T6 Windows ME, 2000 and XP; also Windows 95, 98 and 98 SE, but only in connection with RS 22 modem. Digital accuracy C ( F) C ( F) C ( F) 10 (18) 0.2 (0.6) 10 (18) 0.15 (0.27) 10 (18) 0.1 (0.18) 10 (18) 0.15 (0.27) 10 (18) 0.15 (0.27) 10 (18) 0.2 (0.6) 10 (18) 0.15 (0.27) 10 (18) 0.1 (0.18) 10 (18) 0.15 (0.27) 10 (18) 0.15 (0.27) 10 (18) 0.1 (0.18) /4 Siemens FI

35 Resistance-based sensors Input Range Min. measured span Thermocouple elements Transmitters for rail mounting SITRANS TR00 two-wire system, universal, HART Ω Ω Ω Resistance Resistance input Range Min. measured span C ( F) Type B ( ) Type C (W5) ( ) Type D (W) ( ) Type E ( ) Type J ( ) Type K ( ) Type L ( ) Type N ( ) Type R ( ) Type S ( ) Type T ( ) Type U ( ) Digital accuracy Digital accuracy C ( F) C ( F) 100 (180) 2 (5.4) 100 (180) 2 (.6) 100 (180) 2 (.6) 50 (90) 1 (1.8) 50 (90) 1 (1.8) 50 (90) 1 (1.8) 50 (90) 1 (1.8) 50 (90) 1 (1.8) 100 (180) 2 (.6) 100 (180) 2 (.6) 40 (72) 1 (1.8) 50 (90) 2 (.6) Siemens AG 2007 Selection and Ordering Data Temperature transmitter SITRANS TR00 for mounting on a standard DIN rail, two-wire system, ma, HART, with electrical isolation, with documentation on CD Without explosion protection } D) With explosion protection to } ATEX; type of protection: "Intrinsic safety" EEx ia/ib, non-arcing D) (na), limited energy (nl) Further designs Please add "-Z" to Order No. and specify Order code(s) Customer-specific setting of operating data (specify operating data in plain text) with test protocol (5 measuring points) Accessories CD for measuring instruments for temperature with documentation in German, English, French, Spanish, Italian, Portuguese and SIPROM T parameterization software HART modem } G) With RS 22 connection } D) With USB connection } D) Order No. 7NG0-0JN00 7NG0-1JN00 Order code Y01 C11 Order No. A5E MF4997-1DA 7MF4997-1DB SIMATIC PDM operating software See Section 9 } Available ex stock. D) Subject to export regulations AL: N, ECCN: EAR99H. G) Subject to export regulations AL: N, ECCN: 5D992B1. Power supply units see "SITRANS I supply units and isolation amplifiers". mv Sensor input Range Min. measured span mv mv µv mv Sensor mv Sensor Digital accuracy The digital accuracy is the accuracy after the analog/digital conversion including linearization and calculation of the measured value. An additional error is generated in the output current 4 to 20 ma as a result of the digital/analog conversion of 0.1% of the set span (digital-analog error). The total error under reference conditions at the analog output is the sum from the digital error and the digital-analog error (poss. with the addition of cold junction errors in the case of thermocouple measurements). Siemens FI /5

36 Transmitters for rail mounting SITRANS TR00 two-wire system, universal, HART Dimensional drawings Schematics TEST 4..20mA SIEMENS SITRANS TR TEST 4..20mA SIEMENS SITRANS TR00 TC sensor with external W RTD CJC Made in Croatia TC sensor with external 2W RTD CJC TC sens. with int./fixed CJC U sensor S1 S mA loop & test S1 2x RTD or R 2W sensor 2x TC sensor with int./fixed CJC RTD or R 2W sensor RTD or R W sensor RTD or R 4W sensor 5 6 S UB s Connection Plan TEST + - A SITRANS TR00, dimensions in mm (inch) SITRANS TR00, pin assignment /6 Siemens FI

37 Transmitters for rail mounting SITRANS TR00 two-wire system, universal, HART Resistance thermometer Resistance Thermocouple Voltage measurement Current measurement Test terminals Power supply/ ma (U aux ) SITRANS TR00, sensor connection assignment Siemens FI /7

38 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Overview Siemens AG 2007 Temperature-linear characteristic can be selected for all temperature sensors Automatic correction of zero and span Monitoring of sensor and cable for open-circuit and short-circuit Sensor fault and/or limit can be output via an optional sensor fault/limit monitor Hardware write protection for HART communication Diagnostic functions Slave pointer functions Mode of operation TC RTD 9 The user-friendly transmitters for the control room The SITRANS TW universal transmitter is a further development of the service-proven SITRANS T for the 4-wire system in a mounting rail housing. With numerous new functions it sets new standards for temperature transmitters. With its diagnostics and simulation functions the SITRANS TW provides the necessary insight during commissioning and operation. And using its HART interface the SITRANS TW can be conveniently adapted with SIMATIC PDM to every measurement task. All SITRANS TW control room devices are available in a non-intrinsically safe version as well as in an intrinsically safe version for use with the most stringent requirements. Application The SITRANS TW transmitter is a four-wire rail-mounted device with a universal input circuit for connection to the following sensors and signal sources: Resistance thermometers Thermocouple elements Resistance-based sensors/potentiometers mv sensors As special version: - V sources - Current sources The 4-wire rail-mounted SITRANS TW transmitter wire is designed for control room installation. It must not be mounted in potentially explosive atmospheres. All SITRANS TW control room devices are available in a non-intrinsically safe version as well as in an intrinsically safe version for use with the most stringent requirements. Function Features Transmitter in four-wire system with HART interface Housing can be mounted on 5 mm rail or 2 mm G rail Screw plug connector All circuits electrically isolated Output signal: 0/4 to 20 ma or 0/2 to 10 V Power supplies: 115/20 V AC/DC or 24 V AC/DC Explosion protection [EEx ia] or [EEx ib] for measurements with sensors in the hazardous area Temperature-linear characteristic for all temperature sensors A 8 D µc EEPROM The signal output by a resistance-based sensor (two-wire, threewire, four-wire system), voltage source, current source or thermocouple is converted by the analog-to-digital converter (1, function diagram) into a digital signal. This is evaluated in the microcontroller (2), corrected according to the sensor characteristic, and converted by the digital-to-analog converter (6) into an output current (0/4 to 20 ma) or output voltage (0/2 to 10 V). The sensor characteristics as well as the electronics data and the data for the transmitter parameters are stored in the non-volatile memory (). AC or DC voltages can be used as the power supply (1). Any terminal connections are possible for the power supply as a result of the bridge rectifier in the power supply unit. The PE conductor is required for safety reasons. A HART modem or a HART communicator permit parameterization of the transmitter using a protocol according to the HART specification. The transmitter can be directly parameterized at the point of measurement via the HART output terminals (10). The operation indicator (4) identifies a fault-free or faulty operating state of the transmitter. The limit monitor (9) enables the signaling of sensor faults and/or limit violations. In the case of a current output, the current can be checked on a meter connected to test socket (12). Diagnosis and simulation functions 5 7 D Power supply unit A The SITRANS TW comes with extensive diagnosis and simulation functions. Physical values can be defined with the simulation function. It is thus possible to check the complete signal path from the sensor input to inside the control system without additional equipment. The slave pointer functions are used to record the minimum and maximum of the plant s process variable Output U or I U H A HART modem/ communicator Current test 0/ ma /8 Siemens FI

39 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Integration System configuration U H ma SITRANS TW transmitter SIMATIC S7-400 Control system HART communicator or Possible system configurations A HART modem ET 200M RS-22-C SIMATIC PDM The SITRANS TW transmitter as a four-wire rail-mounted device can be used in a number of system configurations: as a standalone version or as part of a complex system environment, e.g. with SIMATIC S7. All device functions are available via HART communication. Communication options through the HART interface: HART communicator HART modem connected to PC/laptop on which the appropriate software is available, e.g. SIMATIC PDM HART-compatible control system (e.g. SIMATIC S7-400 with ET 200M) or Load PC/laptop with SIMATIC PDM Technical specifications Input Selectable filters to suppress the line frequency Resistance thermometer Measured variable Measured range Measured span Sensor type 50 Hz, 60 Hz, also 10 Hz for special applications (line frequency filter is similar with measuring frequency) Temperature Parameterizable Min. 25 C (45 F) x 1/scaling factor DIN IEC 751 Pt100 (DIN IEC 751) Acc. to JIS C Pt100 (JIS C ) Acc. to DIN 4760 Ni100 (DIN 4760) Special type (R RTD 500 Ω) Voltage measurement Type of connection Connection Measuring range limits Sensor breakage monitoring Sensor short-circuit monitoring Resistance-based sensors, potentiometers Measured variable Measured range Measured span Voltage measurement Type of connection Connection Multiples or parts of the defined characteristic values can be parameterized (e.g. Pt500, Ni120) Temperature-linear, resistance-linear or customer-specific Normal connection Sum or parallel connection Mean-value or differential connection 2, or 4-wire circuit Depending on type of connected thermometer (defined range of resistance thermometer) Monitoring of all connections for open-circuit (function can be switched off) Parameterizable response threshold (function can be switched off) Ohmic impedance Parameterizable Min. 10 Ω Resistance-linear or customerspecific Normal connection Differential connection Mean-value connection 2, or 4-wire circuit Input range Ω; with mean-value and difference circuits: Ω; Sensor breakage monitoring Sensor short-circuit monitoring Monitoring of all connections for open-circuit (function can be switched off) Parameterizable response threshold (function can be switched off) Siemens FI /9

40 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Thermocouple elements Measured variable Measured range Measured span Measuring range limits Thermocouple Voltage measurement Type of connection Cold junction compensation Sensor breakage monitoring mv sensors Measured variable Measured range Measured span Input range Voltage measurement Overload capacity of inputs Input resistance Temperature Parameterizable Min. 50 C (2.22 F) x 1/scaling factor Depend. on type of thermocouple element Type B: Pt0%Rh/Pt6%Rh (DIN IEC 584) Type C W5%-Re (ASTM 988) Type D W%-Re (ASTM 988) Type E: NiCr/CuNi (DIN IEC 584) Type J: Fe/CuNi (DIN IEC 584) Type K: NiCr/Ni (DIN IEC 584) Type L Fe-CuNi (DIN 4710) Type N: NiCrSi-NiSi (DIN IEC 584) Type R: Pt1%Rh/Pt (DIN IEC 584) Type S: Pt10%Rh/Pt (DIN IEC 584) Type T: Cu/CuNi (DIN IEC 584) Type U: Cu/CuNi (DIN 4710) Special type (-10 mv UTC 100 mv) Temperature-linear, voltage-linear or customer-specific Normal connection Sum connection Mean-value connection Differential connection None, internal measurement, external measurement or predefined fixed value Function can be switched off DC voltage Parameterizable Min. 4 mv mv Voltage-linear or customer-specific Max. ±.5 V 1 MΩ Sensor current Approx. 180 µa Sensor breakage monitoring V sources Measured variable Measured range Voltage measurement Input range/min. span Devices with 7NG242-xxxx1 or 7NG242-xxxx 0 with U/I plug Devices with 7NG242-xxxx2 Devices with 7NG242-xxxx Sensor breakage monitoring Function can be switched off DC voltage Parameterizable Voltage-linear or customer-specific -1.2 V V/0.04 V -12 V V/0.4 V -120 V V/4.0 V Not possible µa, ma sources Measured variable Measured range Voltage measurement Input range/min. span DC voltage Parameterizable Current-linear or customerspecific Devices with 7NG242-xxxx4-12 µa µa/0.4 µa Devices with 7NG242-xxxx5-120 µa µa/4 µa Devices with 7NG242-xxxx6 Devices with 7NG242-xxxx7 or 7NG242-xxxx 0 with U/I plug Devices with 7NG242-xxxx8 Sensor breakage monitoring Output Output signal Current 0/ ma Overrange Output range following sensor fault Load Open-circuit voltage Voltage 0/ V Overrange Output range following sensor fault Load resistance Load capacitance Short-circuit voltage Electrical damping -1.2 ma ma/0.04 ma -12 ma ma/0.4 ma -120 ma ma/4 ma Not possible Load-independent direct current 0/ ma, can be switched to load-independent DC voltage 0/ V using plug-in jumpers ma, continuously adjustable ma, continuously adjustable 650 Ω 0 V V, continuously adjustable V, continuously adjustable 1 kω 10 nf 100 ma (not permanently shortcircuit-proof) - Adjustable time constant T s, in steps of 0.1 s Current source/voltage source Sensor fault/limit signalling Operation indicator Limit violation Overrange Relay output Switching capacity Switching voltage Switching current Overrange Limit monitoring Operating delay Monitoring functions of limit module Hysteresis Continuously adjustable within the total operating range By operation indicator, relay output or HART interface Flashing signal Flashing frequency 5 Hz Flashing frequency 1 Hz Either as NO or NC contact with 1 changeover contact 150 W, 625 VA 125 V DC, 250 V AC DC 2.5 A Signalling of sensor or line breakage and sensor short-circuit s Sensor fault (breakage and/or short-circuit) Lower and upper limit Window (combination of lower and upper limits) Limit and sensor fault detection can be combined Parameterizable between 0 and 100% of measuring range /40 Siemens FI

41 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Power supply Universal power supply unit Tolerance range for power supply With 115/20 V AC/DC PSU With 24 V AC/DC PSU Tolerance range for mains frequency Power consumption with 20 V AC 20 V DC 24 V AC 24 V DC Electrical isolation Electrically isolated circuits Working voltage between all electrically isolated circuits Measuring accuracy Measurement error 115/20 V AC/DC or 24 V AC/DC V DC; V AC V DC; V AC (in each case interruption-resistant up to 20 ms in the complete tolerance range) Hz 5 VA 5 W 5 VA 5 W Input, output, power supply and sensor fault/limit monitoring output are electrically isolated from one another. The HART interface is electrically connected to the output. The voltage U eff between any two terminals must not exceed 00 V Error in the internal cold junction C ± 0,1 C/10 C ( 5.4 F ± 0,18 F/18 F) Error of external cold junction terminal 7NG092-8AV Digital output Analog output I AN or U AN Influencing effects (referred to the digital output) Temperature drift Long-term drift Influencing effects referred to the analog output I AN or U AN Temperature drift Power supply Load with current output Load with voltage output Long-term drift (start-of-scale value, span) Response time (T 6 without electrical damping) Electromagnetic compatibility Certificate and approvals 0.5 C ± 0,1 C/10 C ( 0.9 F ± 0.18 F/18 F) See "Digital error" 0.05% of span in addition to digital error Compared to the max. span: 0.08%/10 C ( 0.08%/18 F) 0.2% in the range C ( F) 0.1%/year Compared to the span: 0.08%/10 C ( 0.08%/18 F) 0.2% in the range C ( F) 0.05%/10 V 0.05% with change from Ω 0.1% with change in load current from ma 0.0%/month 0.2 s According to EN 6126 and NAMUR NE21 ATEX To DIN EN 50014: 1997, EN 50020: 1994 Intrinsic safety to EN for 7NG242-xAxxx for 7NG242-xBxxx EC-Type Examination Certificate II (1) G D [EEx ia/ib ] IIB II (1) G D [EEx ia/ib ] IIC TÜV (German Technical Inspectorate) 01 ATEX 1675 Rated conditions Installation conditions Location (for devices with explosion protection) Transmitters Sensor Ambient conditions Permissible ambient temperature Permissible storage temperature Climatic class Relative humidity Design Weight Enclosure material Degree of protection to IEC 529 Degree of protection to VDE 0100 Type of installation Electrical connection/process connection Parameterization interface Outside the potentially explosive atmosphere Within the potentially explosive atmosphere zone 1 (also in zone 0 in conjunction with the prescribed protection requirements for the sensor) C ( F) C ( F) %, no condensation Approx kg (0.5 lb) PBT, glass-fibre reinforced IP20 Protection class I 5-mm top hat rail (1.8 inch) (DIN EN 50022) or 2-mm G-type rail (1.26 inch) (DIN EN 5005) Screw plug connectors, max. 2.5 mm² (0.01 inch²) Protocol HART, version 5.9 Load with connection of HART communicator HART modem Software for PC/laptop Ω Ω SIMATIC PDM version V5.1 and later Siemens FI /41

42 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Digital error Resistance thermometer Input Measured range Max. permissible line resistance DIN IEC 751 Resistance-based sensors Digital error C ( F) Ω C ( F) Pt ( ) Pt ( ) Pt ( ) Pt ( ) Pt ( ) Pt ( ) JIS C Pt ( ) Pt ( ) Pt ( ) DIN 4760 Ni ( ) Ni ( ) Ni ( ) Ni ( ) Input Resistance (linear) Measured range 20.0 (5.4) (1.1) (0.5) (1.1) (1.8) (1.8) 20.0 (5.4) (1.1) (0.5) (0.5) (0.5) (0.5) (0.5) Max. permissible line resistance Ω Ω Ω Digital error Siemens AG 2007 Thermocouple elements Input Measured range Digital error 1) 1) Accuracy data refer to the largest error in the complete measuring range Voltage/current sources C ( F) C ( F) Type B ( ) Type C ( ) Type D ( ) Type E ( ) Type J ( ) Type K ( ) Type L ( ) Type N ( ) Type R ( ) Type S ( ) Type T ( ) Type U ( ) (5.4) 2 (.6) 1 (1.8) 1 (1.8) 1 (1.8) 1 (1.8) 2 (.6) 1 (1.8) 2 (.6) 2 (.6) 1 (1.8) 2 (.6) Input Measuring range Digital error mv sources (linear) mv µv V sources (linear) V mv µa/ma sources (linear) µa/ma µa µa µa ma ma ma 500 /42 Siemens FI

43 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Ordering examples Desired transmitter Parameter: Ordering design Standard Special Example 1: SITRANS TW, transmitter in four-wire system with explosion protection ATEX 20 V AC/DC power supply current output without sensor fault/limit monitor - Sensor PT100, three-wire circuit X - Measuring range C X - Temperature-linear characteristic X - Filter time 1 s X - Output ma, line filter 50 Hz X - Output driven to full-scale in event X of like breakage Example 2: SITRANS TW, transmitter in four-wire system without explosion protection 24 V AC/DC power supply Voltage output Sensor fault/limit monitor - Rating plate in English S76 - Sensor NiCr/Ni, type K A05 - Cold junction internal X - Measuring range C Y0 - Temperature-linear characteristic X - Filter time 1 s X - Output V, line filter 50 Hz H10 - Output driven to full-scale in event X of like breakage - Limit monitoring switched off X Example : SITRANS TW, transmitter in four-wire system without explosion protection 24 V AC/DC power supply Current output without sensor fault/limit monitor - Voltage input, measuring A40 range -1.2 V V - Measuring range V Y2 - Source-proportional characteristic X - Filter time 10 s G07 - Output ma, line filter 60 Hz H11 - No monitoring for sensor fault (X) J0 7NG242-1AA00 (stock item) 7NG242-0BB10-Z Y01 + S76 + A05 + Y0 + H10 Y01: see Order code Y0: MA=0; ME= 950; D=C 7NG242-0BA01-Z Y01 + A40 + Y2 + G07 + H11 + J0 Y01: see Order code Y2: MA=0; ME= 5; D=V Ordering information The order number structure shown below is used to specify a fully functioning transmitter. The selection of the operating data (type of source, measuring range, characteristic etc.) is made according to the following rules: Operating data already set in factory to default values: The default settings can be obtained from the list of parameterizable operating data (see "Special operating data"). The presets can be modified by the customer to match the requirements precisely. Operating data set on delivery according to customer requirements: Supplement the Order No. by "-Z" and add the Order code "Y01". The operating data to be set can be obtained from the list of parameterize operating data. The Order codes A 7 7 to K 7 7 for operating data to be set need only be specified in the order if they deviate from the default setting. The default setting is used if no Order code is specified for operating data. The selected parameters are printed on the transmitter's rating plate. Siemens FI /4

44 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Selection and Ordering data SITRANS TW universal transmitter for rail mounting, in four-wire system (order instruction manual separately) } Available ex stock. Order No. } 7 N G Explosion protection without } 0 for inputs [EEx ia] or [EEx ib] } 1 Power supply 115/20 V AC/DC } A 24 V AC/DC } B Output signal 0/ ma (can be switched to 0/ V)} 0/ V (can be switched to 0/ ma) Sensor fault/limit monitor without (retrofitting not possible) } 0 relay with changeover contact 1 Input for Temperature sensor, resistance-based sensor and mv sensor with measuring range } mv DC and with U/I plug Voltage input (V sources) 1) Measuring range: - DC V 1 - DC V (not Ex version) 2 - DC V (not Ex version) Current input (µa, ma sources) 1) Measuring range: - DC µa 4 - DC µa 5 - DC ma 6 - DC ma 7 - DC ma 8 Further designs Please add "-Z" to Order No. and specify Order code(s) (see "List of parameterizable operating data"). Customer-specific setting of operating data (see "List of parameterizable operating data") Note: specify in plain text: see Order code Meas. point description (max. 16 char.) Text on front of device (max. 2 char.) HART tag (max. 8 characters) with test report with shorting plug to HART communication for 0 ma or 0 V with plug for external cold junction compensation with U/I plug ( V DC or ma) Language of rating plate (together with Y01 order code only) Italian English French Spanish 1) Observe max. values with Ex version. Order code Y01 Y2 Y24 Y25 P01 S01 S02 S0 S72 S76 S77 S78 A B Selection and Ordering data Accessories Instruction Manual for SITRANS TW German/English French/Italian/Spanish Cold junction terminal U/I plug ( V DC pr ma) Order No. } A5E } A5E } 7NG092-8AV } 7NG092-8AW SIMATIC PDM operating software see Chapter 9 HART modem with RS22 interface } 7MF4997-1DA D) with USB interface } 7MF4997-1DB D) D) Subject to export regulations AL:N, ECCN: EAR99H. /44 Siemens FI

45 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART List of parameterizable operating data (Order codes A B E 7 7) Operating data acc. to default setting Order No. with Order code: 7NG Z Y01 Order codes: A E Sensor Thermocouples Connection Cold junction Type Temperature range compensation Measuring ranges B: Pt0%Rh/Pt6%Rh C A 0 0 Standard B 0 1 None C C C C C:W5%Re C A 0 1 Sum n 1) n = 2 B 0 2 Internal C 1 0 D:W%Re C A Fixed val. 0 C C 2 0 E:NiCr/CuNi C A 0 n = 10 B C C C E 0 J:Fe/CuNi (IEC) C A 0 4 Difference 2) Diff1 B 1 50 C C C E 0 4 K:NiCr/Ni L: Fe/CuNi (DIN) C C A 0 5 A 0 6 Diff2 Mean-val. 2) MW B 2 B C 70 C C 2 6 C C C E 0 5 E 0 6 N:NiCrSi/NiSi C A 0 7 Special value 7) Y C E 0 7 R:Pt1%Rh/Pt C A 0 8 External meas. Y C E 0 8 S:Pt10%Rh/Pt C A 0 9 T:Cu/CuNi (IEC) C A 1 0 U:Cu/CuNi (DIN) C A 1 1 Resistance thermometer (or max. permissible line resistance see Technical specifications ) (through Pt100 DIN IEC 751) 7) Connection Connection Line resistance ) Pt100 (DIN IEC) C A 2 0 Standard B wire-system C 2 0 Ω D 0 0 Pt100 (JIS) C A 2 1 Sum n 4) n = 2 B 0 2 -wire-system C 10 Ω D 1 0 Ni100 (DIN) C A wire-system C 4 20 Ω D 2 0 n = 10 B Ω D 5 0 Parallel n 5) n = 0.1 B 2 1 Special val. 7) Y 2 0 n= 0.2 B 2 2 n= 0.5 B 2 5 Special value 6) 7) Y 0 0 Difference 2) Diff1 B 5 1 Diff2 B 5 2 Mean-val. 2) MW B C C C C C C C C C C C C C C C C C C C C C C C C C C C Special range 7) E 0 0 E 0 1 E 0 2 E 0 9 E 1 0 E 1 1 E 1 2 E 1 E 1 4 E 1 5 E 1 6 E 1 7 E 1 8 E 1 9 E 2 0 E 2 1 E 2 2 E 2 E 2 4 E 2 5 E 2 6 E 2 7 E 2 8 E 2 9 E 0 E 1 E 2 E E 4 E 5 Y 0 Resistance-based sensors, potentiometers (or max. permissible line resistance see Technical specifications ) Connection Connection Line resistance ) Measuring ranges A 0 Standard B wire-system C 2 0 Ω D Ω E 4 0 Difference 2) Diff1 B 5 1 -wire-system C 10 Ω D Ω E 4 1 Diff2 B wire-system C 4 20 Ω D Ω E 4 2 Mean val. 2) MW B Ω D Ω E 4 Special val. 7) Y Ω E Ω 8) E Ω 8) E 4 6 Special range 7) Y 2 1 mv, V and µa, ma sensors 9) A 4 0 Meas. range with Order No. 7NG Z Y01 E 5 0 1) n = number of thermocouple elements to be connected in series 2) See Circuit diagrams for meaning of type circuit ) Line resistance of channels 1 and 2, for max. permissible line resistance see Technical specifications (only with C2, not with C and C4) 4) n = number of resistance thermometers to be connected in series 5) 1/n = number of resistance thermometers to be connected in parallel 6) Combination of series and parallel connection of resistance thermometers 7) Operating data: see Special operating data 8) This range does not apply to mean-value and difference circuits. 9) The max. permissible currents and voltages according to conformity certificate must be observed in devices with explosion protection. 10) Without detection of line breakage mv 1-1, V 10) V 10) V 10) µa 10) µa 10) 6-1, ma 10) ma 10) ma 10) Special range 7) Y 2 Siemens FI /45

46 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART List of parameterizable operating data (Order codes F K 7 7) Operating data according to default setting Order No. with Order code: 7NG Z Y01 Order codes: F K Sensor Thermocouple elements Type Temperature range Voltage measurement Filter time 1) Output signal and line filter 2) Failure signal B: Pt0%Rh/ C A 0 0 Temperaturelinear F s G ma/ with line break- C:W5%Re C A s G V age/fault: D:W%Re C A 0 2 Voltage- F s G 0 2 with line filter: E:NiCr/CuNi C A 0 linear 0.5 s G 0 50 Hz H 0 0 to full scale J 0 0 J:Fe/CuNi (IEC) C A s G Hz H 0 1 to start of scale J 0 1 K:NiCr/Ni C A s G Hz 4) H 0 2 hold last value J 0 2 Limit monitor ) Limit monitoring ineffective K 0 0 (but sensor fault signalling with closedcircuit operation) L: Fe/CuNi (DIN) C A s G ma/ N:NiCrSi/NiSi C A s G V no monitoring J 0 R:Pt1%Rh/Pt C A s G 0 8 with line filter: Effective 5) Y 7 0 S:Pt10%Rh/Pt C A s G Hz H 1 0 Safety value 5) Y 6 0 T:Cu/CuNi (IEC) C A s G Hz H 1 1 U:Cu/CuNi (DIN) C A 1 1 Special time 5) Y Hz H 1 2 Resistance thermometer (max. permissible line resistances see Technical specifications ) Voltage measurment Failure signal Pt100 (DIN IEC) C A 2 0 Temperaturelinear F 0 0 Pt100 (JIS) C A 2 1 Ni100 (DIN) C A 2 2 Resistancelinear with line breakage/fault: F 2 0 to full scale J 0 0 to start of scale J 0 1 hold last value J 0 2 no monitoring J 0 Safety value 5) Y 6 0 with line breakage or short-circuit/fault: to full scale J 1 0 to start of scale J 1 1 hold last value J 1 2 no monitoring J 1 Safety value 5) Y 6 1 (max. permissible line resistances see Technical specifications ) A 0 Voltage measurment Resistance-based sensors, potentiometers Resistancelinear F 2 0 Failure signal with line breakage/fault: to full scale J 0 0 to start of scale J 0 1 hold last value J 0 2 no monitoring J 0 mv, V and µa, ma sources A 4 0 Voltage measurment Source proportional 1) Software filter to smooth the result 2) Filter to suppress line disturbances on the measured signal. ) If signalling relay present 4) for special appliciations 5) Operating data: see Special operating data F 0 Safety value 5) Y 6 0 /46 Siemens FI

47 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Special operating data Order code Plain text required Options Y00 N=. Factor N for multiplication with the characteristic values of resistance thermometers Range of values: 0.10 to Example: x Pt500 parallel: N = 5/ = 1.667; 2. Example: Ni120: N = 1.2 Y10 TV=. Temperature TV of the fixed cold junction D= Dimension; range of values: C, K, F, R Y11 RL=. Line resistance RL in Ω for compensation of cold junction line of external Pt100 DIN IEC 751 Range of values: 0.00 to Y20 Y0 Y1 Y2 RL1=. RL2=. MA=. ME=. Line resistances RL of channel 1 (RL1) and channel 2 (RL2) in Ω if the resistance thermometer or the resistance-based sensor is connected in a two-wire system Range of values depending on type of sensor: 0.00 to Start-of-scale value MA and full-scale value ME for thermocouples and resistance thermometers (Range of values depending on type of sensor) D= Dimension, range of values: C, K, F, R) MA=. ME=. MA=. ME=. Start-of-scale value MA and full-scale value ME for resistance-based sensors or potentiometers in Ω Range of values: 0.00 to 6, Start-of-scale value MA and full-scale value ME for mv, V, µa and ma sources Range of values depending on type of sensor: to 1, D= Dimension (mv entered as MV, V as V, µa as UA, ma as MA) Y50 T6=. Response time T6 of software filter in s Range of values: 0.0 to Safety value S of signal output in ma or in V corresponding to the set type of output. Range of values - with current output: to with voltage output: to Y60 S=. Safety value S with line breakage of sensor Y61 S=. Safety value S with line breakage or shortcircuit of sensor Y70 UG=. Lower limit value (dimension as defined by measuring range) OG=. H=. K= A= T=. Upper limit value (dimension as defined by measuring range) Hysteresis (dimension as defined by measuring range) Switch on/off combination of limit function and sensor fault detection; J=on; N=off (standard: J) Type of relay output: A=open-circuit operation; R=closed-circuit operation (standard: R) Switching delay T of relay output in s Range of values: 0.0 to 10.0 (standard: 0.0) Siemens FI /47

48 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Schematics Sensor input connections Siemens AG R, RTD R, RTD R, RTD R2, RTD2 R1, RTD TC TC Pt100 Pt TC 7NG092-8AV - + TC1 + - TC mv U+ U- I+ I- 7NG092-8AW , V ma + - Resistance thermometers, resistance-based sensors, potentiometers: 1 Two-wire system; resistance can be parameterized for line compensation 2 Three-wire system Four-wire system 4 Difference/mean-value circuit; 2 resistors can be parameterized for line compensation Thermocouples: 5 Determination of cold junction temperature using built-in Pt100 or fixed reference temperature 6 Determination of cold junction temperature using external Pt100; resistance can be parameterized for line compensation 7 Determination of cold junction temperature using cold junction terminal 7NG092-8AV 8 Difference/mean-value circuit with internal cold junction temperature Further sources: 9 mv sources with two-wire system (7NG242-xxxx0) 10 V sources with two-wire system (7NG242-xxxx[1-]) 11 ma/ma sources with two-wire system (7NG242-xxxx[4-8]) 12 Voltage measurement -1,2 to 10 V with U/I plug 7NG092-8AW (7NG242-xxxx0) 1 Current measurement -12 to 100 ma with U/I plug 7NG092-8AW (7NG242-xxxx0) Connection diagram for the input signal Channel 1 is the measured variable between the terminals 2 and on the input plug. With a difference or mean-value circuit, the calculation of the measured value is defined by the type of measurement. Otherwise the measured value is determined via channel 1. The following code is used for the type of measurement: Type of measurement Calculation of measured value Single channel Channel 1 Differential connection 1 Channel 1 - Channel 2 Differential connection 2 Channel 2 - Channel 1 Mean-value 1 ½ (Channel 1 + Channel 2) The short-circuit jumpers shown in the circuits must be inserted in the respective system on site. /48 Siemens FI

49 Transmitters for rail mounting SITRANS TW four-wire system, universal, HART Power supply connection Limit monitor HART/ Sensor ~ + U H ~ - Relay output HART to 4 Signal input (see "Sensor input connections" for possible types of connection) 5, 6 Analog output (U or I output parameterizable using plug-in jumpers) 7, 8 Connection with HART communication for local parameterization 9 to 11 Output for sensor fault/limit monitor as relay contact (see below for possible parameterization) 12 PE connection 1, 14 Power supply input (protected against reverse polarity) Connection diagram for power supply, input and outputs Relay output Closed-circuit operation (relay opens when error) Device switched off 10 and 11 Device switched on and no error 9 and 11 Device switched on and error 10 and 11 Open-circuit operation (relay closes when error) Device switched off 10 and 11 Device switched on and no error 10 and 11 Device switched on and error 9 and 11 Connected terminals Dimensional drawings Dimensions for control room mounting, rail mounting in mm (inches) Siemens FI /49

50 Transmitter for field mounting with temperature sensor SITRANS TF2 Digital display thermometer Overview The temperature transmitter SITRANS TF2 integrates three elements in one device: a Pt100 resistance thermometer in a stainless steel protective tube, a stainless steel housing with a high degree of protection, and a built-in transmitter with LCD and three keys for parameterization. It is used to indicate and monitor the temperature measured at the point of installation. The SITRANS TF2 is available in an axial and a radial version. Benefits Robust stainless steel housing with two connection versions High measuring accuracy Precise display with a resolution of 1 / 100 C in the highest measuring range Measuring ranges from -50 to +200 C ( F) parameterizable Customer-specific lengths and materials possible for the protective tube Stainless steel protective tube with high resistance to chemicals Signaling of limit violation in the LCD as well as with a red LED Application The SITRANS TF2 is used for indicating and monitoring a temperature variable at the point of installation. Applications are all process engineering branches, e.g.: Chemical industry Energy industry Long-distance heating Water supply Sewage works Food industry Steelworks and the cement industry Pharmaceutical industry Biotechnology Design The SITRANS TF2 has a stainless steel housing (diam. 80 mm) with protective glass. The stainless steel protective tube with screw socket contains the temperature sensor Pt100. By using stainless steel for the protective tube it displays high chemical resistance, which means that the temperature sensor is well protected against external effects The protective tube is supplied as standard in lengths of 170 mm or 260 mm; a customer-specific version is also possible. Similarly, the protective tube can be supplied in the material of the customer s choice. At the rear of the housing is the electrical connection for the voltage supply using a current loop of 4 to 20 ma. The connection is made with plug connectors to EN A. At the front of the housing is the 5-digit display behind a glass cover. Underneath the display are the keys for parameterizing the SITRANS TF2. Above the display are a green and a red LED for indicating the operating status. The SITRANS TF2 is available in two versions (see "Dimensional drawings ): In the radial version (type A) the display is fitted in parallel with the protective tube. The display can be rotated by up to ±120 relative to the protective tube. In the axial version (type B) the display is at right angles to the protective tube. The display can be rotated by 60 relative to the protective tube. Function Mode of operation RTD IK A/D EEPROM D/A Green LED µc Red LED keys U K U A U I EMV keys Configuring of parameters A/D Analog-to-digital converter D/A Digital-to-analog converter EEPROM Memory for all parameters EMC Output stage with protective components I A Current output I K Constant-current source LCD Display of measured values with dimension Green LED Display of normal mode Red LED Display of error messages or limit violation RTD Pt100 resistance thermometer U H Power supply µc Microcontroller for computing functions ond monitoring C The outside lying temperature sensor Pt100 is supplied with current from the constant current course I k. A temperature-related voltage drop is thus created over the sensor. The voltage drop is converted on the analog/digital converter (A/D) into a digital signal. In the microcontroller (µc) the digital signal is linearized and evaluated in accordance with the data saved in the EEPROM. The processed data are shown in the display. In addition the values are converted on the digital/analog converter (D/A) and the voltage/current transformer (U/I) into a temperature-linear current signal I A (4 to 20 ma). LCD ma U H, I A - /50 Siemens FI

51 Transmitter for field mounting with temperature sensor SITRANS TF2 Digital display thermometer Display Display The SITRANS TF2 has a 5-digit display behind a glass cover. The following data are shown on the display: measured temperature unit ( C, F, R or K and ma or %) limit violation, indicated by LED and arrow symbols in the display Settings The SITRANS TF2 is set using the input keys behind the glass cover underneath the display. The key "M" is used to selected the operating mode. Following modes of operation are available: Measured value Password Unit of measurement Start of scale and end Upper and lower limit value Offset Output current calibration Upper and lower current saturation limit Electrical damping The other two keys are used to set the values in the individual operating modes. Monitoring Two LED indicators are fitted above the display to monitor the set range and the status: The green LED signals that the measured temperature lies within the set limits. The red LED lights up when the measured temperature lies outside the set limits and when there is an error. Technical specifications Measuring principle Resistance thermometer Pt100 class B acc. to DIN IEC 751 Input Measured variable Temperature Max. measuring range -50 C C ( F) Min. measured span Output Output signal Lower current limit Upper current limit Output protected against max. load Voltage measurement Measuring accuracy Error in measurement at 2 C ± 5 K (7.4 ± 9 F) Measuring cycle time Temperature effect Power supply effect Vibration influence 50 K (90 F) ma, 2-wire min..6 ma max. 2 ma reversed polarity, overvoltage and short-circuiting (U H 12 V) / 0.02 A Temperature-linear < ± (0.45 K + 0.2% of full-scale value in K + 1 digit in K) (< ± (0.81 F + 0.2% of full-scale value in F + 1 digit in F) 100 ms < ± 0.15%/10 K (< ± 0.15%/18 F) < ±0,01% of full-scale value/v < ±0.05%/g to 500 Hz in all directions (to IEC ) Rated conditions Ambient conditions Ambient temperature Temperature range for best readability Storage temperature C ( F) C ( F) C ( F) Degree of protection IP65 to EN Electromagnetic compatibility EN 6126/A2 Appendix A (2001) Displays and controls Display Resolution at max. measuring range Decimal point Limit values Limit violation display Parameterization Units Damping Design Weight Non-wetted parts materials Field housing LCD, max. 5 digits, digit height 9 mm (0.54 inch) 0.01 C (0.01 F) Freely parameterizable Freely parameterizable Red LED and message on LCD ( symbol / symbol in case of limit violation in upward/downward direction) With keys ma or % or Ω or physical variable: C, F, R, K Between 0.1 and 100 s (increment: 0.1 s) freely parameterizable 0.7 kg ( 1.54 lb) Diam. 80 mm (diam..15 inch), stainless steel, mat. No Cover Stainless steel, mat. No with glass Wetted parts materials Protective tube To DIN 4772 form 8 (March 2000), diam. 14 x 1.5 mm (diam x 0.06 inch) - Material Stainless steel (mat. No /16Ti) Protective tube screw socket G½B to DIN form A or ½ -14 NPT - Material Stainless steel (mat. No /16Ti) Measuring insert Connection of display to the protective tube Length of the protective tube(u 1 ) Electrical connection Power supply Terminal voltage on temperature transmitter (U H ) Operating limits Pressure Length to fit the ordered protective tube, stainless steel radial (type A), can be swiveled by max. ±120 (α) axial (type B), can be swiveled by max. ± 60 see Ordering data Using 2-pole plug connector made of plastic with M16x1.5-cable entry to EN A or ½ -14 NPT V DC max. 40 bar (580 psi) Siemens FI /51

52 Siemens AG 2008 Transmitter for field mounting with temperature sensor SITRANS TF2 Digital display thermometer Selection and ordering data Order No. Order code Temperature transmitter SITRANS TF2, field device Temperature transmitter with LCD in stainless steel housing, degree of protection IP65, stainless steel protective tube, resistance thermometer with Pt100 sensor, measuring range C ( F), local parameterization, output signal ma Display/cable entry Radial version (type A), parallel to protective tube/m16x1.5 Axial version (type B), at right angles to protective tube/m16x1.5 Radial version (type A), parallel to protective tube/½"-npt Axial version (type B), at right angles to protective tube/½"-npt } 1 Process connection Connection shank G½B } A Connection shank ½"-14 NPT B Other version (on request) Z add Order code and plain text: connection shank:... Length of the protective tube (U 1 ) 170 mm (6.70 inch) } A 260 mm (10.24 inch) } B 4.5" (114 mm) K 7.5" (190 mm) P 10.5" (266 mm) T Other version (on request) Z add Order code and plain text: length:... 7 N G J 1 Y K 1 Y Material of the protective tube Stainless steel (mat. No /16Ti) } 0 Other version (on request) 9 L 1 Y add Order code and plain text: mat. No.:... } Available ex stock Selection and ordering data Further design Manufacturer s test certificate M to DIN 5540, Part 18 and ISO 8402 (calibration certificate points), add "-Z" to Order No. and Order code. Manufacturer s test certificate M to DIN 5540, Part 18 and ISO 8402 (calibration certificate 1 point) supplied later, specify factory no. of transmitter. Additional data Add -Z to Order No. and specify Order code and plain text Measuring range to be set Y01:... Measuring point label made of stainless steel, please specify inscription in plain text. Schematics U B R L I Power supply Load Output current 1 (+) 2 (-) SITRANS TF2, connection diagram I 0 Order code C11 Order No. 7MF1564-8CC11 Order code Y01 Y15 R L + U B Dimensional drawings Ø 82 (.2) Ø 82 (.2) 45 (1.77) 48,5 (1.91) SW 27 Ø 80 (.15) M16x1.5 or ½"-NPT M16x1.5 or ½"-NPT 48,5 (1.99) 45 (1.77) SW (2.64) Ø 14 (0.55) G½B or ½"-14 NPT G½B or ½"-14 NPT U 1 U 1 Type A Type B SITRANS TF2, dimensions in mm (inches) /52 Siemens FI Modification 01/2008

53 Transmitter for field mounting / field indicator SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 20 ma Overview Our field devices for heavy industrial use HART, Universal 4 to 20 ma, universal Field indicator for 4 to 20 ma signals The temperature transmitter SITRANS TF works where others feel uncomfortable. Benefits Universal use - as transmitter for resistance thermometer, thermoelement, Ω or mv signal - as field indicator for any 4 to 20 ma signals Local sensing of measured values over digital display Rugged two-chamber enclosure in die-cast aluminium or stainless steel Type of protection IP68 Test terminals for direct read-out of the output signal without breaking the current loop Can be mounted elsewhere if the measuring point - is not easily accessible - is subject to high temperatures - is subject to vibrations from the system - or if you want to avoid long neck tubes and/or protective tubes Can be mounted directly on American-design sensors Wide range of approvals for use in potentially explosive atmospheres. "Intrinsically safe, non-sparking and flameproof" type of protection, for Europe and USA. Function Configuration The communication capability over the HART protocol V 5.9 of the SITRANS TF with an integrated SITRANS TH00 permits parameterization using a PC or HART communicator (hand-held communicator). The SIMATIC PDM makes it easy. Parameterization is carried out using a PC for SITRANS TF - with the integrated and programmable SITRANS TH200. Available for this purpose are a special modem and the software tool SIPROM T. Mode of operation Mode of operation of SITRANS TF as temperature transmitter The sensor signal, whether resistance thermometer, thermocouple or Ω and/or V signal, is amplified and linearized. Sensor and output side are electrically isolated. An internal cold junction is integrated for measurements with thermocouples. The device outputs a temperature-linear direct current of 4 to 20 ma. As well as the analog transmission of measured values from 4 to 20 ma, the HART model also supports digital communication for online diagnostics, measured value transmission and configuration. SITRANS TF automatically detects when a sensor should should be interrupted or is indicating a short-circuit. The practical test terminals allow direct measurement of 4 to 20 ma signals over an ammeter without interrupting the output current loop. Mode of operation of SITRANS TF as field indicator Any 4 to 20 ma signal can be applied to the generous terminal block. As well as a range of predefined measurement units, the adjustable indicator also supports the input of customized units. This means that any 4 to 20 ma signal can be represented as any type of unit, e.g. pressure, flow rate, filling level or temperature. Sensor TC RTD SITRANS TF SITRANS TH00 1 Analog-to-digital converter 2 Electrical isolation Microprocessor 4 Digital-to-analog converter 5 Power supply 6 PC/Laptop 7 HART modem 8 Digital display (option) 9 Test connector A D µp D A C Operating principle: SITRANS TF with an integrated transmitter and digital display Power supply 5 7 Load Application SITRANS TF can be used everywhere where temperatures need to be measured under particularly adverse conditions, or where a convenient local display is ideal. Which is why users from all industries have opted for this field device. The rugged enclosure protects the electronics. The stainless steel model is even resistant to sea water and other aggressive elements The inner workings offer high measuring accuracy, universal input and a wide range of diagnostic options. Siemens FI /5

54 Transmitter for field mounting / field indicator SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 20 ma Technical specifications Input Resistance thermometer Measured variable Sensor type to IEC to JIS C 1604; a= K-1 to IEC Temperature Pt25 to Pt1000 Pt25 to Pt1000 Ni25 to Ni1000 Units C and F Connection Normal connection Generation of average value Generation of difference Interface Two-wire system Three-wire system Four-wire system Sensor current Response time Open-circuit monitoring Short-circuit monitoring Measuring range Min. measured span Characteristic Resistance-based sensors Measured variable Sensor type Units Connection Normal connection Generation of average value Generation of difference Interface Two-wire system Three-wire system Four-wire system Sensor current Response time Open-circuit monitoring Short-circuit monitoring 1 resistance thermometer (RTD) in 2-wire, -wire or 4-wire system Series or parallel connection of several resistance thermometers in a two-wire system for the generation of average temperatures or for adaptation to other device types 2 resistance thermometers (RTD) in 2-wire system (RTD 1 RTD 2 or RTD 2 RTD 1) Parameterizable line resistance 100 Ω (loop resistance) No balancing required No balancing required 0.45 ma 250 ms for 1 sensor with opencircuit monitoring Can be switched off Can be switched off (value is adjustable) Parameterizable (see table "Digital measuring errors") 10 C (18 F) Temperature-linear or special characteristic Actual resistance Resistance-based, potentiometers Ω 1 resistance-based sensor (R) in 2-wire, -wire or 4-wire system 2 resistance-based sensors in 2-wire system for generation of average value 2 resistance-based sensor in 2-wire system (R 1 R 2 or R 2 R 1) Parameterizable line resistance 100 Ω (loop resistance) No balancing required No balancing required 0.45 ma 250 ms for 1 sensor with opencircuit monitoring Can be switched off Can be switched off (value is adjustable) Measuring range Min. measured span Characteristic Thermocouple Measured variable Sensor type (thermocouples) Parameterizable (see table "Digital measuring errors") Ω (see table "Digital measuring errors") Resistance-linear or special characteristic Temperature Type B Pt0Rh-Pt6Rh to DIN IEC 584 Type C W5%-Re to ASTM 988 Type D W%-Re to ASTM 988 Type E NiCr-CuNi to DIN IEC 584 Type J Fe-CuNi to DIN IEC 584 Type K NiCr-Ni to DIN IEC 584 Type L Fe-CuNi to DIN 4710 Type N NiCrSi-NiSi to DIN IEC 584 Type R Pt1Rh-Pt to DIN IEC 584 Type S Pt10Rh-Pt to DIN IEC 584 Type T Cu-CuNi to DIN IEC 584 Type U Cu-CuNi to DIN 4710 Units C or F Connection Standard connection Generation of average value Generation of difference Response time Open-circuit monitoring Cold junction compensation Internal 1 thermocouple (TC) 2 thermocouples (TC) 2 thermocouples (TC) (TC 1 TC 2 or TC 2 TC 1) 250 ms for 1 sensor with opencircuit monitoring Can be switched off With integrated Pt100 resistance thermometer External With external Pt100 IEC (2- wire or -wire connection) External fixed Measuring range Min. measured span Characteristic mv Sensor Measured variable Sensor type Units Response time Open-circuit monitoring Short-circuit monitoring Measuring range Min. measured span Overload capacity of the input Input resistance Characteristic Cold junction temperature can be set as fixed value Parameterizable (see table "Digital measuring errors") Min C ( F) (see table "Digital measuring errors") Temperature-linear or special characteristic DC voltage DC voltage source (DC voltage source possible over an externally connected resistor) mv 250 ms for 1 sensor with opencircuit monitoring Can be switched off Can be switched off (value is adjustable) mv mv 2 mv or 20 mv V DC 1 MΩ Voltage-linear or special characteristic /54 Siemens FI

55 Siemens AG 2008 Transmitter for field mounting / field indicator SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 20 ma Output Output signal Communication with SITRANS TH00 Digital display Digital display (optional) Display ma, 2-wire to HART Rev. 5.9 in current loop max. 5 digits Digit height 9 mm (0.5") Display range Units Setting: Zero point, upper range value and unit Measuring accuracy Digital measuring errors Reference conditions Any (max. 5 char.) With keys Auxiliary power supply 24 V ± 1 % Load Storage temperature Warming-up time Error in the analog ouput (digital/analog converter) Error due to internal cold junction See table "Dig. measuring errors" 500 Ω 2 C (7.4 F) > 5 min < 0.1% of span < 0.5 C (0.9 F) Temperature effect < 0.1% of max. span/10 C (18 F) Power supply effect Long-term drift in the first month after one year after 5 years Rated conditions Ambient temperature Storage temperature Condensation Electromagnetic compatibility Degree of protection to EN Design Approx. weight Dimensions Enclosure material Electrical connection, sensor connection Mounting bracket (optional) Power supply Without digital display < 0.005% of span/v < 0.02% of max. span < 0.0% of max. span < 0.04% of max. span C ( F) Permissible According to EN 6126 and NAMUR NE21 IP68 Approx. 1.5 kg (. lb), without options See "Dimensional drawings" Die-cast aluminum, low in copper, GD-AlSi 12 or stainless steel, polyester-based lacquer, stainless steel rating plate Screw terminals, cable inlet via M20 x 1.5 or ½-14 NPT threaded gland Steel, galvanized and chromeplated or stainless steel V DC (0 V with Ex) Certificate and approvals Explosion protection ATEX "Intrinsically-safe" type of protection With digital indicator: II 2 (1) G EEx ia IIC T4 Without digital indicator: II 2 (1) G EEx ia IIC T6 - EC type test certificate ZELM 99 ATEX 0007 "Operating equipment that is II G EEx nal IIC T6/T4 non-sparking and has limited energy for zone 2" type of protection - EC type test certificate ZELM 99 ATEX 0007 Flame-proof enclosure" type of protection II 2 G EEx d IIC T5/T6 - EC type test certificate CESI 99 ATEX 079 Explosion protection to FM Certificate of Compliance Identification (XP, DIP, NI, S) XP / I / 1/BCD / T5 Ta = 85 C (185 F), T6 Ta = 50 C (112 F), Type 4X DIP / II, III / 1 / EFG / T5 Ta = 85 C (185 F), T6 Ta = 50 C (112 F), Type 4X NI / I / 2 / ABCD / T5 Ta = 85 C (185 F), T6 Ta = 50 C (112 F), Type 4X S / II, III / 2 / FG / T5 Ta = 85 C (185 F), T6 Ta = 50 C (112 F), Type 4X Hardware and software requirements For the parameterization software SIPROM T for SITRANS TH200 - Personal computer PC with CD-ROM drive and USB/RS 22 interface - PC operating system Windows 98, NT, 2000, XP For the parameterization software SIMATIC PDM for SITRANS TH00 Communication Load for HART connection Two-core shielded Multi-core shielded See chapter 9, "Software", "SIMATIC PDM" Ω.0 km (1.86 mi) 1.5 km (0.9 mi) Protocol HART protocol, version 5.x Factory setting (transmitter): Pt100 (IEC 751) with three-wire circuit Measuring range: C ( F) Fault current 22.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s With digital display Electrically isolated Test voltage V DC (0 V with Ex) Between input and output U eff = 1 kv, 50 Hz, 1 min Modification 01/2008 Siemens FI /55

56 Transmitter for field mounting / field indicator SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 20 ma Digital measuring errors Resistance thermometer Input Measuring range Min. measured span according to IEC Pt ( ) Pt ( ) Pt Pt ( ) Pt ( ) Pt ( ) according to JIS C Pt ( ) Pt ( ) Pt Pt ( ) Pt ( ) Pt ( ) Ni Ni ( ) Digital accuracy C ( F) C ( F) C ( F) 10 (18) 0,2 (0.6) 10 (18) 0,15 (0.27) 10 (18) 0,1 (0.18) 10 (18) 0,15 (0.27) 10 (18) 0,15 (0.27) 10 (18) 0,2 (0.6) 10 (18) 0,15 (0.27) 10 (18) 0,1 (0.18) 10 (18) 0,15 (0.27) 10 (18) 0,15 (0.27) 10 (18) 0,1 (0.18) Siemens AG 2007 Thermocouple elements Input Measuring range Min. measured span Type B ( ) Digital accuracy C ( F) C ( F) C ( F) ( ) Type C (W5) ( ) Type D (W) ( ) ( ) Type E ( ) Type J ( ) Type K ( ) Type L ( ) Type N ( ) Type R ( ) Type S ( ) Type T ( ) Type U ( ) 100 (180) (5.4) 100 (180) 2 (.6) 100 (180) 2 (.6) 100 (180) 1 (1.8) 100 (180) 2 (.6) 50 (90) 1 (1.8) 50 (90) 1 (1.8) 50 (90) 1 (1.8) 50 (90) 1 (1.8) 50 (90) 1 (1.8) 100 (180) 2 (.6) 100 (180) 2 (.6) 40 (72) 1 (1.8) 50 (90) 2 (.6) Resistance-based sensors Input Measuring range Min. measured span Ω Ω Ω Resistance ,05 Resistance ,25 Digital accuracy mv sensors Input Measuring range Min. measured span mv mv µv mv sensors mv sensors Digital accuracy The digital accuracy is the accuracy after the analog/digital conversion including linearization and calculation of the measured value. An additional error is generated in the output current 4 to 20 ma as a result of the digital/analog conversion of 0.1% of the set span (digital-analog error). The total error under reference conditions at the analog output is the sum from the digital error and the digital-analog error (poss. with the addition of cold junction errors in the case of thermocouple measurements). /56 Siemens FI

57 Transmitter for field mounting / field indicator SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 20 ma Dimensional drawings 1 (0.51) 144 (5.67) 15* (0.59) 18* (5.4) 52 (2.05) 50* (1.97) 55 (2.17) 28 (1.10) 20 (0.79) b 80 (.15) 100* (.94) (.15) a: max. 164 (6.46) (M20x1.5) max. 189 (7.44) (½-14 NPT) 1 72 (2.8) 50 (1.97) 68 (2.68) 117 (4.61) 120 (4.72) a 6,5 (1.44) 27 (9.) b: max. 25 (0.98) (M20x1.5) max. 50 (1.97) (½-14 NPT) *) Dimensions for stainless steel enclosure 12 (4.84) Æ ( ) 7 1 Sensor connection (screwed gland M20x1,5 or ½-14 NPT) 2 Blanking plug Electrical connection (screwed gland M20x1,5 or ½-14 NPT) 4 Terminal side, output signal 5 Terminal side, sensor 105 (4.1) 6 Protective cover (without function) 7 Mounting bracket (option) with clamp for securing to a vertical or horizontal pipe 8 Cover with window for digital display SITRANS TF, dimensions in mm (inches) Siemens FI /57

58 Siemens AG 2008 Transmitter for field mounting / field indicator SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 20 ma Selection and Ordering data Temperature transmitter in field housing Two-wire system ma, with electrical isolation, with documentation on CD-ROM Order No. D) 7 N G Integrated transmitter SITRANS TH200, programmable - without Ex protection with EEx ia with EEx nal for zone total device SITRANS TF EEx d 1) total device SITRANS TF according to FM 5 5 (XP, DIP, NI, S) 1) SITRANS TH00, communication capability according to HART V without Ex-protection with EEx ia with EEx nal for zone total device SITRANS TF EEx d 1) total device SITRANS TF according to FM 6 5 (XP, DIP, NI, S) 1) SITRANS TF field indicator for ma signals, with documentation on CD-ROM 7 N G without Ex-protection with EEx ia with EEx nal for zone total device SITRANS TF EEx d 1) total device SITRANS TF according to FM (XP, DIP, NI, S) 1) Enclosure die-cast aluminium stainless steel precision casting Connections/cable inlet screwed glands M20x1.5 screwed glands ½-14 NPT Digital indicator without 0 with 1 Mounting bracket and securing parts without 0 made of steel 1 made of stainless steel 2 Further designs Please add "-Z" to Order No. and specify Order code(s) and plain text. Order code Customer-specific setting of operating data Y 0 1 2) Inscription on measuring-point label measuring range (max. 27 characters) Y2 2 ) meas. point description (max. 16 char.) Y2 ) measuring point text (max. 27 char.) Y2 4 ) Test protocol (5 measuring points) C1 1 Power supply units see "SITRANS I supply units and input isolators". 1) Without cable gland. 2) Y01: Please specify all data that does not correspond to factory settings (see above) (e.g. Y01 = thermocouple element type K; internal cold junction; C; fault current.6 ma). ) Y22, Y2, Y24: If no order is placed for Y01, these data are only noted on the measuring point label and are not programmed in the transmitter. A E B C Selection and Ordering data Accessories Modem for SITRANS TH200 incl. parameterization software T C) Subject to export regulations AL: N, ECCN: EAR99. D) Subject to export regulations AL: N, ECCN: EAR99H. G) Subject to export regulations AL: N, ECCN: 5D992B1. Factory setting (transmitter): Pt100 (IEC 751) with three-wire circuit Measuring range: C ( F) Fault current 22.8 ma Sensor offset: 0 C (0 F) Damping 0.0 s Order No. with USB interface } 7NG092-8KU C) with RS 22 interface } 7NG092-8KM C) CD for measuring instruments } A5E for temperature G) with documentation in German, English, French, Spanish, Italian and Portuguese, and parameterization software SIPROM T (included in delivery with SITRANS TF) HART modem with RS 22 interface } 7MF4997-1DA D) with USB interface } 7MF4997-1DB D) SIMATIC PDM parameterization software also for SITRANS TH00 Mounting bracket and securing parts made of steel for 7NG1.-..B.. made of steel for 7NG1.-..C.. made of stainless steel for 7NG1.-..B.. made of stainless steel for 7NG1.-..C.. Digital indicator 1) 1) It is not possible to upgrade devices with Ex protection see chap. 9 7MF4997-1AC 7MF4997-1AB } 7MF4997-1AJ 7MF4997-1AH 7MF4997-1BS } Available ex stock. Power supply units see "SITRANS I supply units and input isolators". /58 Siemens FI Modification 01/2008

59 Transmitter for field mounting / field indicator SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 20 ma Schematics Resistance thermometer Resistance Thermocouple Voltage measurement Current measurement SITRANS TF, sensor connection assignment Siemens FI /59

60 Resistance thermometers Technical description Siemens AG 2007 Design A resistance thermometer comprises the measuring resistor (metal; platinum, Pt or nickel, Ni) and the mounting and connection parts required in each case. In the standard version, the measuring resistors are embedded in ceramic. In the case of special vibration resistance requirements, the Pt measuring resistors are double-wound and fused into glass. Measuring resistors of class B are supplied. A range of resistors of class A or 1/ to 1/10 class B is available on request. Single and double resistance thermometers are available. Components and circuitry of a resistance thermometer To protect the measuring resistor for industrial measurements and to enable easy replacement, it is fixed in a measuring insert (4) which in turn is fitted in a protective tube (5). The measuring insert is spring-mounted in the connection head (1) of the protective tube using two screws. The internal conductor (10) in the measuring insert connects the measuring resistor (11) to the terminals on the terminal block. Depending on the measuring range and the accuracy required, the thermometers are connected in two-wire, three-wire or fourwire systems to the output devices. The measuring inserts are therefore available with two, three or four internal conductors. If the resistance of the internal conductor is negligibly small, measuring inserts with only two internal conductors can be used for the three-wire and four-wire systems. Exact balancing of the internal conductor under operating conditions is only possible with three conductors. If the resistance of the internal conductor is greater than 0.2 Ω, its magnitude is indicated on the mounting flange of the measuring insert. Function Measuring resistor Measuring resistors The measuring resistor changes with the temperature in accordance with a certain reproducible series of calibration data (see the table "Calibration data for platinum measuring resistors (to DIN EN 60751) under "Technical data ). The changes in resistance are transmitted as changes in voltage to indicators, recorders or controllers directly via copper wires or via transmitters. The type of measuring circuit depends on the instrument to be connected and the required measuring range. The measuring resistors are balanced at 0 C (2 F) to 100 Ω ± 0.12 Ω. The calibration values of the resistors (i.e. the dependence of the resistor on the temperature) and the permissible deviations are specified in DIN EN (IEC 751) (see the table "Error limits according to DIN EN under "Technical Specifications ). Measuring resistors of class B are supplied. A range of resistors of class A or 1/ to 1/10 class B is available on request. Measuring principle of the resistance temperature measurement The thermometer is heated up by the thermometer current compared to the material to be measured. The heating-up error thus produced increases with the square of the thermometer current and linearly with the resistance of the measuring resistor. Apart from the magnitude of the thermometer current, the error depends on the design of the thermometer and on the heat transfer between the protective tube and the medium. A high measuring power is required for output instruments operating according to the deflection method. To keep the heating-up error within permissible limits, the thermometer current should not be greater than 10 ma in this case. When measuring the temperature of gases with very small flow velocities, a considerably greater heating-up error occurs than in measurements with very fast gases or liquids. The heating-up error is negligibly small with high flow velocities. Protection fitting/protective tubes Measuring resistors are suitable for temperatures from Made of platinum C ( F) Made of nickel C ( F), briefly up to 180 C (56 F) Suitable protective fittings are used for installation in pipelines, tanks etc. depending on the mechanical or chemical requirements. The materials for the protective tubes or combinations of different protective tube materials must be carefully selected in order to meet the requirements due to static pressure, flow and temperature Furthermore, the indication response should be as fast as possible. Installation examples with the suitable protective tube materials can be found under "Technical data" in the table "Installation examples and material of protective tubes". The type of installation of the protective tubes depends on the application. The protective tubes are screwed into the pipelines in the case of operating pressures up to approx. 90 bar. Tapered protective tubes which can be welded in are available for higher pressures. Thermometers for measuring furnace temperatures are fixed using flanges. Owing to the different operating conditions, no guarantee can be given for protective fittings. The manufacturer is responsible for damages and measuring errors caused by wrong installation in compliance with the General Terms of Delivery if the instruments have been installed by the manufacturer and if the specifications for the operating conditions furnished by the customer were correct and sufficiently detailed. /60 Siemens FI

61 Integration Resistance thermometers Instrument combination for measuring and controlling temperature Siemens AG 2007 Technical description Sense Match Resistance thermometer Electric transmitter Catalog FI 01 Output Control Electric Catalog indicator MP 12 limit monitor recorder MP 20 controller MP 1 Instrument combination with resistance thermometer as sensor Installation examples and materials of protective tubes Measuring point A. Steam power plants Water and steam lines (Screw-in and weldingtype thermometers) Max. operating temp. Protective tube material C ( F) name No. 00 (572) Bronze Sn Bz 6 (only for water) 400 (752) St (1004) 1 CrMo (1058) 10 CrMo Flue gas 550 (1022) St 5.8, enamelled Pulverized coal/air mixture line 100 (212) St 5.8 (with baffle rod) Water treatment 0 (86) X 6 CrNiTi or X 6 CrNiMoTi B. Paper mills In paper pulp (cylindrical paper mills, handmade paper, refiner) (140) X 6 CrNiMoTi C. Pulp production For all tanks with internal lining: only flangetype thermometers 1. Sulfite pulp Boiling acid in vat, peetz tank and acid tower Hypochlorite tower, alkali tower Sulphite lye evaporation, heat exchanger, preheater and lye collecting tank 2. Sulfate pulp Vat, lye heater Black, green and white lye tanks Cellulose multiplestage bleaching (moist chloric gases present) Sulfate lye evaporation, heat exchanger, preheater and lye collecting tank 150 (02) X 6 CrNiMoTi (104) X 6 CrNiMoTi (284) X 6 CrNiMoTi In vat 180 (56) otherwise 80 (176) X 6 CrNiTi or X 6 CrNiMoTi Ti (104) Hastelloy C (59 Ni; 16 Mo; 15,5 Cr; 5,5 Fe;,8 W) or X 6 CrNiMoTi with Ti protective sleeve (284) X 6 CrNiMoTi Measuring point D. Dye works Jigger, automatic yarn skein dying machine E. Food and drink industries 1. Breweries 110 (20) X 6 CrNiMoTi Brewing water 80 (176) Bronze Sn Bz 6 or X 6 CrNiTi Mash Hot wort 100 (212) Bronze or X 6 CrNiTi Cold wort 4 (9,2) X 6 CrNiTi Sugar factories Salt removal in sugar juice. Cereals production 100 (212) X 6 CrNiTi Salt removal in whey 20 (68) X 6 CrNiTi Malt houses Steeping water 100 (212) Bronze Sn Bz Yeast production Max. operating temp. Yeast cooling 4 (9,2) X 6 CrNiTi Yeast fermentation (91,4) X 6 CrNiMoTi F. Chemical and petrochemical industries Protective tube material C ( F) name No. Corrosion-resistant steel, material Nos and , can be used for many applications. The numerous substances to be measured in these industrial branches render it sometimes difficult to recommend suitable protective tube materials. If required, please contact our representatives in these cases. Siemens FI /61

62 Resistance thermometers Protective tubes, installation Siemens AG 2007 Technical specifications Calibration data for platinum measuring resistors (to DIN EN 60751) C ( F) Ω -200 (-28) (-292) (-256) (-220) (-184) (-148) (-112) (-76) (-40) (-22) (-4) (14) (2) (50) (68) (86) (104) (122) (140) (176) (212) (248) (284) (20) (56) (92) (428) (464) (500) (56) (572) (608) (644) (680) (716) (752) (788) (824) (860) (896) (92) (968) (1004) (1040) (1076) (1112) (1148) (1184) (1220) (1292) (182) (1472) (1562) Error limits acc. to DIN EN The resistance thermometers are divided into two classes according to their error limits: Class Error limits in C A 0,15 + 0,002 t 1) B 1) t is the numerical value of the temperature in C without consideration of the sign Integration Protective tubes in a pipeline Flue gas resistance thermometer 0, + 0,005 t Fitted in a sheet-metal duct (top) and a flue gas duct (bottom) /62 Siemens FI

63 Resistance thermometers Protective tubes, installation Screw-in resistance thermometer Welding-type protective tubes, mounted In a pulverized coal line, with baffle rod Welding-type protective tubes, mounted Top: Wall thickness 5 mm; mounting using welded coupling; bottom: Wall thickness > 5 mm At top for low-pressure, with screw socket G½; at bottom for high-pressure, with screw socket G1 It must be possible to weld the pipe coupling and pipeline. Material according to data provided by pipeline or vessel manufacturer. Siemens FI /6

64 Resistance thermometers Temperature transmitters for mounting in the connection head Overview Selection and Ordering Data Detailed information on the transmitters can be found for the respective products under "Transmitters for temperature. The following temperature transmitters are available for mounting in the connection head: SITRANS TH100 Programmable two-wire temperature transmitter (4 to 20 ma), without electrical isolation, only for Pt100 resistance thermometers. SITRANS TH200 Programmable two-wire temperature transmitter (4 to 20 ma), electrical isolation for resistance thermometers and thermocouple elements. SITRANS TH00 Two-wire temperature transmitter with HART communication (4 to 20 ma), electrical isolation for resistance thermometers and thermocouple elements. SITRANS TH400 Temperature transmitter with PROFIBUS PA or FOUNDATION Fieldbus connection, electrical isolation for resistance thermometers and thermocouple elements. Note: SITRANS TH100/TH200/TH00/TH400 can be fitted instead of the terminal block or in the high hinged cover. Additional fitting only possible in high hinged cover. If using intrinsically-safe temperature sensors any installed temperature transmitters must also be intrinsically-safe. Transmitter to be fitted To order the sensor with a built-in temperature transmitter, add "-Z" to the Order No. of the sensor, and supplement by the following Order code: SITRANS TH100 - without Ex T10 - EEx ia IIC and EEx n for zone 2 T11 - FM T1 SITRANS TH200 - without Ex T20 - EEx ia IIC and EEx n for zone 2 T21 - FM (IS, I, NI) T2 SITRANS TH00 - without Ex T0 - EEx ia IIC und EEx n for zone 2 T1 - FM (IS, I, NI) T SITRANS TH400 PA - without Ex T40 - EEx ia T41 SITRANS TH400 FF - without Ex T45 - EEx ia T46 Customer-specific setting of the built-in transmitter (specify settings in plain text) 1) For TH400 FF available soon Order code Y11 1) /64 Siemens FI

65 Resistance thermometers Questionnaire for temperature sensors (resistance thermometers and thermocouples) General information Customer:... Address:... Contact partner:... Purchasing dept.:... Tel.:... Sales dept.:... Tel.:... Process dept.:... Tel.:... Inquiry:... Quotation:... Place and date:... Operating conditions 1. Application:... (e.g. exhaust gas measurement) 2. Location:... (e.g. pipe bend, tank). Mounting position:... (e.g. vertical, 45 against flow) 4. Temperature (measuring point):... Operating temperature:... Temperature range: Medium: Pressure:... Nominal pressure:... Operating pressure: Flow: Vibrations: Miscellaneous:... (e.g. vessel or pipe materials, PTFE lining) Ambient conditions (e.g. seawater atmosphere, chemical plant) Definition: Special information 1. Mounting of temperature transmitter in connection head: Packaging regulations: Miscellaneous Please additionally provide the following: rough sketch, installation diagram, section of drawing, photo Sensor design 1. Measuring element... (type and standard) (e.g. Pt100 or TC type K) 1.1. Tolerance: Design:... (e.g. Pt100 or 2, or 4-wire system) 1.. Degree of protection/type of protection: Protective fitting: Protective tube:... (dimensions/material) 2.2. Mounting:... (dimensions/material) 2.. Neck tube:... (dimensions/material) 2.4. Mounting length/nominal length:.... Material certificates: Connection: Connection head/box: Cable:... (dimensions/insulation/standard) 4.. Other: Tests: Accessories: Supplementary requirements: Siemens FI /65

66 Resistance thermometers Flue gas resistance thermometers with connection head Overview The flue gas resistance thermometer with connection head is suitable for the temperature range from -50 to +600 C (-58 to F) and can also be supplied with a built-in temperature transmitter. Please order mounting flange or threaded sleeve separately. Technical specifications Design According to DIN 4764: Thermometer without mount Protective tube Form Material Loading capacity Measuring insert Dimensional drawings 1, DIN 4772; cylindrical, 15 mm diameter (0.59 inch), wall thickness mm (0.12 inch), seamless St 5.8, mat. No , enamelled 1 bar (14.5 psi) above atmospheric, to DIN 4772 Replaceable, with measuring insert tube (8 mm diameter (0.1 inch)) made of stainless steel; terminal block with clamping springs Selection and Ordering data Flue gas resistance thermometer Measuring resistor (winding) embedded in ceramic 1 Pt100 measuring resistor, three-wire circuit Order No. Mounting length/ mm (inch): Weight/ kg (lb): 500 (19.7) 0.9 (1.98) 7 M C B A (28.0) 1.1 (2.4) 7 M C B A (9.4) 1.5 (.1) 7 M C B A (55.1) 1.9 (4.19) 7 M C B A (78.7) 2.7 (5.95) 7 M C B A 27 Connection head, form B, made of cast light alloy, with 1 cable inlet and screw cover 1 standard hinged cover 4 high hinged cover 6 Further designs Please add "-Z" to Order No. and specify Order code(s) and plain text. Different design (mounting length, protective tube material etc.), specify in plain text. TAG plate made of stainless steel specify TAG No. in plain text Calibration carried out at one point, specify desired temperature in plain text (order equivalent number of times for several calibration points). Accessories Mounting flange Adjustable, to DIN 474; Material: GTW 5, mat. No , for protective tube diameter 15 mm (0.59 inch), 0. kg (0.66 lb) Order code Y01 Y15 Y Order No. 7 M C C A Gas-tight threaded sleeve Material: 9 SMnPb 28 Material No , for protective tube diameter 15 mm (0.59 inch), 0.4 kg (0.88 lb) G¾ internal thread with gasket 7 M C D A G½ internal thread with gasket 7 M C D C To order a temperature transmitter installed in the connection head, see "Temperature transmitters for installation in the connection head" (page /64). Individual parts: Measuring inserts, see "Accessories". Flue gas resistance thermometer with connection head, dimensions in mm (inches) /66 Siemens FI

67 Resistance thermometers Low-pressure screw-in resistance thermometers with connection head, without neck tube Overview The low-pressure screw-in resistance thermometer with connection head (no neck tube) is suitable for the temperature range from -50 to +400 C (-58 to +752 F) and can also be supplied with a built-in temperature transmitter. Technical specifications Design According to DIN 4765: Screw-in thermometer Protective tube Form Loading capacity Dimensional drawings Similar to 2G, DIN 4772; cylindrical, 9 mm (0.5 inch) diameter, wall thickness 1 mm (0.04 inch) to 20 bar (290.1 psi) (loading capacity dependent on material, temperature, flow rate, mounting length etc., see DIN 4772 for details) Screw socket G½; suitable is gasket 21 x 26, similar to form C or D, DIN 760 Measuring insert Response times (to VDI/VDE 522) In water with flow velocity v = 0.4 m/s (1.1 ft/s) In air with flow velocity v = 1 m/s (.28 ft/s) Explosion protection Replaceable, with measuring insert tube (6 mm diameter (0.24 inch) made of stainless steel; terminal block with clamping springs t 0.5 = 25 s, t 0.9 = 75 s t 0.5 = 2 min, t 0.9 = 6. min II 1/2G EEx ia IIC T4/T6 Low-pressure screw-in resistance thermometer with connection head, without neck tube, dimensions in mm (inches) Selection and Ordering data Low-pressure screw-in resistance thermometer with connection head, without neck tube Protective tube and screw socket X 6 CrNiMoTi , mat. No Protective tube to DIN 4,772, form: similar to 2G Measuring resistors embedded in ceramic, one Pt100 measuring resistor: three-wire circuit, Two Pt100 measuring resistors: two-wire circuit Order No. Measuring insert not explosion protected One Pt100 measuring resistor, Mounting length U 1 / mm (inch): Weight/ kg (lb): 100 (.9) 0.6 (1.2) } 7 M C D A (6.) 0.7 (1.54) 7 M C D A (9.1) 0.8 (1.76) 7 M C D A (14.2) 0.9 (1.98) 7 M C D A (20.1) 1.0 (2.20) 7 M C D A 17 Two Pt100 measuring resistors Mounting length U 1 / mm (inch): Weight/ kg (lb): 100 (.9) 0.6 (1.2) 7 M C D B (6.) 0.71 (1.57) 7 M C D B (9.1) 0.81 (1.79) 7 M C D B (14.2) 0.91 (2.01) 7 M C D B (20.1) 1.01 (2.2) 7 M C D B 17 Measuring insert with explosion protection One Pt100 measuring resistor Mounting length U 1 / mm (inch): Weight/ kg (lb): 100 (.9) 0.6 (1.2) } 7 M C D E (6.) 0.7 (1.54) 7 M C D E (9.1) 0.8 (1.76) 7 M C D E (14.2) 0.9 (1.98) 7 M C D E (20.1) 1.0 (2.20) 7 M C D E 17 Two Pt100 measuring resistors Mounting length U 1 / mm (inch): Weight/ kg (lb): 100 (.9) 0.6 (1.2) 7 M C D F (6.) 0.71 (1.57) 7 M C D F (9.1) 0.81 (1.79) 7 M C D F (14.2) 0.91 (2.01) 7 M C D F (20.1) 1.01 (2.2) 7 M C D F 17 Connection head, form B, made of cast light alloy, with 1 cable inlet and - screw cover 1 - standard hinged cover 4 - high hinged cover } 6 made of stainless steel, with 1 cable inlet and screw cover 7 Further designs Please add "-Z" to Order No. and specify Order code(s) and plain text. Order code Different design (mounting length, protective tube material etc.), specify in plain text. Y01 TAG plate made of stainless steel Y15 specify TAG No. in plain text Calibration carried out at one point, specify Y desired temperature in plain text (order equivalent number of times for several calibration points). } Available ex stock To order a temperature transmitter installed in the connection head, see "Temperature transmitters for installation in the connection head" (page /64). Individual parts: Measuring inserts and connection heads, see "Accessories". Siemens FI /67

68 Resistance thermometers Low-pressure screw-in resistance thermometers with connection head, with neck tube Overview The low-pressure screw-in resistance thermometer with connection head and neck tube is suitable for the temperature range from -50 to +600 C (-58 to F) and can also be supplied with a built-in temperature transmitter. Technical specifications Design According to DIN 4765: Screw-in thermometer Protective tube Form Loading capacity Dimensional drawings 2G, DIN 4772; cylindrical, 9 mm (0.5 inch) diameter, wall thickness 1 mm (0.04 inch) to 20 bar (290.1 psi) (loading capacity dependent on material, temperature, flow rate, mounting length etc., see DIN 4772 for details) Screw socket G½; suitable is gasket 21 x 26, similar to form C or D, DIN 760 Measuring insert Response times (to VDI/VDE 522) In water with flow velocity v = 0.4 m/s (1.1 ft/s) In air with flow velocity v = 1 m/s (.28 ft/s) Explosion protection Replaceable, with measuring insert tube (6 mm diameter (0.24 inch) made of stainless steel; terminal block with clamping springs t 0.5 = 25 s, t 0.9 = 75 s t 0.5 = 2 min, t 0.9 = 6. min II 1/2G EEx ia IIC T4/T6 Low-pressure screw-in resistance thermometer with neck tube, dimensions in mm (inches) Selection and Ordering data Low-pressure screw-in resistance thermometer with connection head and neck tube Protective tube and screw socket X 6 CrNiMoTi , mat. No Protective tube to DIN 4772, form: 2G Measuring resistors embedded in ceramic, one Pt100 measuring resistor: three-wire circuit, Two Pt100 measuring resistors: two-wire circuit Order No. Measuring insert not explosion protected One Pt100 measuring resistor Mounting length U 1 / mm (inch): Weight/ kg (lb): 160 (6.) 0.8 (1.76) 7 M C D A (9.84) 0.9 (1.98) 7 M C D A (15.7) 1.0 (2.20) 7 M C D A 17 Two Pt100 measuring resistors Mounting length U 1 / mm (inch): Weight/ kg (lb): 160 (6.) 0.9 (1.98) 7 M C D B (9.84) 1.0 (2.20) 7 M C D B (15.7) 1.1 (2.4) 7 M C D B 17 Measuring insert with explosion protection One Pt100 measuring resistor Mounting length U 1 / mm (inch): Weight/ kg (lb): 160 (6.) 0.8 (1.76) 7 M C D E (9.84) 0.9 (1.98) 7 M C D E (15.7) 1.0 (2.20) 7 M C D E 17 Two Pt100 measuring resistors Mounting length U 1 / mm (inch): Weight/ kg (lb): 160 (6.) 0.9 (1.98) 7 M C D F (9.84) 1.0 (2.20) 7 M C D F (15.7) 1.1 (2.4) 7 M C D F 17 Connection head, form B, made of cast light alloy, with 1 cable inlet and - screw cover 1 - standard hinged cover 4 - high hinged cover 6 made of stainless steel, 7 with 1 cable inlet and screw cover Further designs Please add "-Z" to Order No. and specify Order code(s) and plain text. Different design (mounting length, protective tube material etc.), specify in plain text. TAG plate made of stainless steel specify TAG No. in plain text Calibration carried out at one point, specify desired temperature in plain text (order equivalent number of times for several calibration points). Order code To order a temperature transmitter installed in the connection head, see "Temperature transmitters for installation in the connection head" (page /64). Individual parts: Measuring inserts and connection heads, see "Accessories". Y01 Y15 Y /68 Siemens FI

69 Resistance thermometers High-pressure screw-in resistance thermometers Overview The high-pressure screw-in resistance thermometer with connection head and neck tube is suitable for the temperature range from -50 to +600 C (-58 to F) and can also be supplied with a built-in temperature transmitter. Technical specifications Design According to DIN 4765: Screw-in thermometer Protective tube Form Loading capacity 2G, DIN 4772; cylindrical, 11 mm (0.4 inch) diameter, wall thickness 2 mm (0.08 inch) to 50 bar (725.2 psi) (loading capacity dependent on material, temperature, flow rate, mounting length etc., see DIN 4772 for details) Screw socket G1; suitable is gasket x 9, similar to form C or D, DIN 760 Measuring insert Response times (to VDI/VDE 522) In water with flow velocity v = 0.4 m/s (1.1 ft/s) In air with flow velocity v = 1 m/s (.28 ft/s) Replaceable, with measuring insert tube (6 mm diameter (0.24 inch) made of stainless steel; terminal block with clamping springs t 0.5 = 2 s, t 0.9 = 96 s t 0.5 = 2.2 min, t 0.9 = 6.8 min Selection and Ordering data High-pressure screw-in resistance thermometer with connection head and neck tube Protective tube and screw socket X 6 CrNiMoTi , mat. No Protective tube to DIN 4772, form: 2G Order No. One Pt100 measuring resistor embedded in ceramic, three-wire circuit Mounting length U 1 / Weight/ mm (inch): kg (lb): 160 (6.) 0.8 (1.8) 7 M C D A (9.84) 0.9 (2.05) 7 M C D A 17 Two Pt100 measuring resistors embedded in ceramic, two-wire circuit Mounting length U 1 / Weight/ mm (inch): kg (lb): 160 (6.) 0.86 (1.20) 7 M C D B (9.84) 0.94 (2.07) 7 M C D B 17 Connection head, form B, made of cast light alloy, with 1 cable inlet and - screw cover 1 - standard hinged cover 4 - high hinged cover 6 made of stainless steel, 7 with 1 cable inlet and screw cover Further designs Please add "-Z" to Order No. and specify Order code(s) and plain text. Different design (mounting length, protective tube material etc.), specify in plain text. TAG plate made of stainless steel specify TAG No. in plain text Calibration carried out at one point, specify desired temperature in plain text (order equivalent number of times for several calibration points). Order code To order a temperature transmitter installed in the connection head, see "Temperature transmitters for installation in the connection head" (page /64). Individual parts: Measuring inserts and connection heads, see "Accessories". Y01 Y15 Y Dimensional drawings High-pressure screw-in resistance thermometer with neck tube, dimensions in mm (inches) Siemens FI /69

70 Resistance thermometers High-pressure welding-type resistance thermometers Overview The high-pressure welding type resistance thermometer with connection head and neck tube is suitable for the temperature range from -50 to 540 or 550 C (-58 to 1004 or 1022 F) and can also be supplied with a built-in temperature transmitter. Technical specifications Design According to DIN 4767: Welding-type thermometer Protective tube Form Loading capacity Neck tube Measuring insert Response times (to VDI/VDE 522) In water with flow velocity v = 0.4 m/s (1.1 ft/s) Explosion protection Dimensional drawings 4, DIN 4772; tapered, for welding in; with female thread M18 x 1.5 for neck tube to 450 bar (6527 psi) (loading capacity dependent on material, temperature, flow rate, mounting length etc., see DIN 4772 for details) Stainless steel, unscrewable Replaceable, with measuring insert tube made of stainless steel; terminal block with clamping springs t 0.5 = 25 s, t 0.9 = 80 s II 1/2G EEx ia IIC T4/T6 High-pressure welding-type resistance thermometer with connection head and neck tube, dimensions in mm (inches) u Selection and Ordering data High-pressure welding-type resistance thermometer Measuring resistor: Winding embedded in ceramic, protective tube to DIN 4772, form 4 1 Pt100 measuring resistor/three-wire circuit Measuring insert not explosion protected - max. 540 C (1004 F), protective tube 1 CrMo 44, mat. No max. 550 C (1022 F), protective tube X 6 CrNiMoTi , mat. No Measuring insert with explosion protection - max. 550 C (1022 F), protective tube X 6 CrNiMoTi , mat. No Pt100 measuring resistors/two-wire circuit Measuring insert not explosion protected - max. 540 C (1004 F), protective tube 1 CrMo 44, mat. No max. 550 C (1022 F), protective tube X 6 CrNiMoTi , mat. No Measuring insert with explosion protection - max. 550 C (1022 F), protective tube X 6 CrNiMoTi , mat. No Mounting Protective Total length Weight with length U tube without one/two length L connection measuring head l 5 resistors mm (inch) mm (inch) mm (inch) kg (lb) 65 (2.6) 125 (4.9) 140 (5.5) 200 (7.9) 200 (7.9) 05 (12.0) 0.78 (1.7)/ 0.79 (1.7) 65 (14.4) 0.82 (1.8)/ 0.8 (1.8) 95 (15.6) 0.85 (1.9)/ 0.86 (1.9) 65 (14.4) 0.95 (2.1)/ 0.96 (2.1) 95 (15.6) 0.98 (2.2)/ 1.00 (2.2) 65 (14.4) 0.95 (2.1)/ 0.96 (2.1) 95 (15.6) 0.98 (2.2)/ 1.00 ( (10.2) 95 (15.6) 1.15 (2.5)/ 1.20 (2.7) Connection head, form B made of cast light alloy, with 1 cable bushing and Order No. 7 M C G A 27 7 M C F A 27 7 M C F E 27 7 M C G B 27 7 M C F B 27 7 M C F F 27 - screw cover 1 - standard hinged cover 4 - high hinged cover 6 made of stainless steel, with 1 cable bushing and screw cover Further designs Please add "-Z" to Order No. and specify Order code(s) and plain text. Different design (mounting length, protective tube material etc.), specify in plain text. TAG plate made of stainless steel specify TAG No. in plain text Calibration carried out at one point, specify desired temperature in plain text (order equivalent number of times for several calibration points). Order code To order a temperature transmitter installed in the connection head, see "Temperature transmitters for installation in the connection head" (page /64). Individual parts: Measuring inserts and connection heads, see "Accessories". Y01 Y15 Y /70 Siemens FI

71 Resistance thermometers Flange-type resistance thermometer with connection head Overview The flange-type resistance thermometer with connection head can be installed in tanks and pipelines; it is suitable for a temperature range from -50 to +600 C (-58 to F) and can also be supplied with a built-in temperature transmitter. Technical specifications Protective tube Form Material Loading capacity Flange Measuring insert Response times (to VDI/VDE 522) In water with flow velocity v = 0.4 m/s (1.1 ft/s) In air with flow velocity v = 1 m/s (.28 ft/s) Explosion protection Dimensional drawings 2F, DIN 4772; cylindrical, 11 mm (0.4 inch) diameter, wall thickness 2 mm (0.08 inch) X 6 CrNiMoTi , mat. No to 40 bar (580 psi) (loading capacity dependent on material, temperature, flow rate, mounting length etc., see DIN 4772 for details) Nominal diameter DN 25, nominal pressure PN 40 (ASME on request) Replaceable, with measuring insert tube (6 mm diameter (0.24 inch) made of stainless steel; terminal block with clamping springs t 0.5 = 2 s, t 0.9 = 96 s t 0.5 = 2.2 min, t 0.9 = 6.8 min II 1/2G EEx ia IIC T4/T6 Selection and Ordering data Flange-typeresistance thermometer With connection head Protective tube to DIN 4772, form: 2F one Pt100 measuring resistor: three-wire circuit, two Pt100 measuring resistors: two-wire circuit Order No. Measuring insert not explosion protected One Pt100 measuring resistor Mounting length/ Weight/ mm (inch): kg (lb): 160 (6.) 1.5 (.1) } 7 M C F A (9.84) 1.5 (.1) 7 M C F A 17 Two Pt100 measuring resistors Mounting length/ Weight/ mm (inch): kg (lb): 160 (6.) 1.6 (.5) 7 M C F B (9.84) 1.6 (.5) 7 M C F B 17 Measuring insert with explosion protection One Pt100 measuring resistor Mounting length/ Weight/ mm (inch): kg (lb): 160 (6.) 1.5 (.1) } 7 M C F E (9.84) 1.5 (.1) 7 M C F E 17 Two Pt100 measuring resistors Mounting length/ Weight/ mm (inch): kg (lb): 160 (6.) 1.6 (.5) 7 M C F F (9.84) 1.6 (.5) 7 M C F F 17 Connection head, form B made of cast light alloy, with 1 cable inlet and - screw cover 1 - standard hinged cover 4 - high hinged cover } 6 made of stainless steel, with 1 cable inlet and screw cover 7 Further designs Please add "-Z to Order No. and specify Order code(s) and plain text. Order code Different design (mounting length, protective tube material etc.), specify in plain text. Y01 TAG plate made of stainless steel Y15 specify TAG No. in plain text Calibration carried out at one point, specify Y desired temperature in plain text (order equivalent number of times for several calibration points). } Available ex stock To order a temperature transmitter installed in the connection head, see "Temperature transmitters for installation in the connection head" (page /64). Individual parts: Measuring inserts and connection heads, see "Accessories". Flange-type resistance thermometer with connection head, dimensions in mm (inches) Siemens FI /71

72 Resistance thermometers Flange-type resistance thermometer with reduced response time, with connection head Overview The flange-type resistance thermometer with connection head with reduced response time can be installed in tanks and pipelines; it is suitable for a temperature range from -50 to +600 C (-58 to F). The sensor is also available with a built-in temperature transmitter. Technical specifications Protective tube Form Material Loading capacity Flange Measuring insert Response times (to VDI/VDE 522) In water with flow velocity v = 0.4 m/s (1.1 ft/s) In air with flow velocity v = 1 m/s (.28 ft/s) Explosion protection Dimensional drawings, DIN 4772; cylindrical, 12 mm (0.47 inch) diameter, wall thickness 2.5 mm (0.1 inch), tapered towards tip; tip cylindrical over length of 47 mm (1.85 inch), 9 mm (0.5 inch) diameter, wall thickness 1.5 mm (0.06 inch) X 6 CrNiMoTi , mat. No to 40 bar (580 psi) (loading capacity dependent on material, temperature, flow rate, mounting length etc., see DIN 4772 for details) Nominal diameter DN 25, nominal pressure PN 40 (ASME on request) Replaceable, with measuring insert tube (6 mm diameter (0.24 inch) made of stainless steel; terminal block with clamping springs t 0.5 = 22 s, t 0.9 = 66 s t 0.5 = 2.1 min, t 0.9 = 6.5 min II 1/2G EEx ia IIC T4/T6 Selection and Ordering data Flange-type resistance thermometer with reduced response time with connection head Protective tube to DIN 4772, form: one Pt100 measuring resistor: three-wire circuit, two Pt100 measuring resistors: two-wire circuit Order No. Measuring insert not explosion protected One Pt100 measuring resistor Mounting length/ mm (inch): Weight/ kg (lb): 225 (8.9) 1.5 (.1) 7 M C A A (11.2) 1.5 (.1) 7 M C A A (1.6) 1.5 (.1) 7 M C A A 07 Two Pt100 measuring resistors Mounting length/ mm (inch): Weight/ kg (lb): 225 (8.9) 1.6 (.5) 7 M C A B (11.2) 1.6 (.5) 7 M C A B (1.6) 1.6 (.5) 7 M C A B 07 Measuring insert with explosion protection One Pt100 measuring resistor Mounting length/ mm (inch): Weight/ kg (lb): 225 (8.9) 1.5 (.1) 7 M C E A (11.2) 1.5 (.1) 7 M C E A (1.6) 1.5 (.1) 7 M C E A 07 Two Pt100 measuring resistors Mounting length/ mm (inch): Weight/ kg (lb): 225 (8.9) 1.6 (.5) 7 M C E B (11.2) 1.6 (.5) 7 M C E B (1.6) 1.6 (.5) 7 M C E B 07 Connection head, form B made of cast light alloy, with 1 cable inlet and - screw cover 1 - standard hinged cover 4 - high hinged cover 6 made of stainless steel, 7 with 1 cable inlet and screw cover Further designs Please add "-Z" to Order No. and specify Order code(s) and plain text. Different design (mounting length, protective tube material etc.), specify in plain text. TAG plate made of stainless steel specify TAG No. in plain text Calibration carried out at one point, specify desired temperature in plain text (order equivalent number of times for several calibration points). Order code To order a temperature transmitter installed in the connection head, see "Temperature transmitters for installation in the connection head" (page /64). Y01 Y15 Y Individual parts: Measuring inserts and connection heads, see "Accessories". Flange-type resistance thermometer with reduced response time; with connection head, dimensions in mm (inches) /72 Siemens FI

73 Resistance thermometers for damp rooms Overview The resistance thermometer for damp rooms is suitable for a temperature range from -0 to +60 C (-22 to +140 F). Technical specifications Protective tube Connection head Measuring insert Dimensional drawings Made of stainless steel Made of cast light alloy, with cable bushing; made of plastic on request 1 or 2 Pt measuring resistors to DIN EN 60751, connection in three-wire or two-wire system, class B Degree of protection IP65 acc. to DIN EN Selection and Ordering data Resistance thermometer for damp rooms stainless steel protective tube with one Pt100 measuring resistor 0.1 kg (0.22 kg) with two Pt100 measuring resistors 0.1 kg (0.22 kg) Further designs Please add "-Z" to Order No. and specify Order code(s) and plain text. Order No. } 7MC1027-1AA 7MC1027-1AB Order code Different design (mounting length, protective tube material etc.), specify in plain text. Y01 TAG plate made of stainless steel Y15 specify TAG No. in plain text Calibration carried out at one point, specify Y desired temperature in plain text (order equivalent number of times for several calibration points). } Available ex stock To order a temperature transmitter installed in the connection head, see "Temperature transmitters for installation in the connection head" (page /64). Note: Additional fitting of head mounted transmitter of SITRANS TH series is possible. Resistance thermometer for moist rooms, dimensions in mm (inches) Siemens FI /7

74 Resistance thermometers Accessories Measuring inserts, not explosion protected Design Components (design to DIN 4762) Measuring insert with resistor, insert tube with retaining plate, terminal block with clamping springs and 2 or internal conductors of Cu-Ni sheathed wire for each Pt100 measuring resistor. The resistance of the internal conductors is stated on the measuring insert if it is greater than 0.2 Ω. The measuring inserts have a filling of Al 2 O powder which surrounds the measuring resistor and the internal conductors and results in a high vibration resistance (for temperatures up to 600 C (1112 F). The winding is embedded in a ceramic body. If the vibrations at the measuring location are greater than normal, the special vibration-proof measuring inserts should be used (for temperatures up to 450 C (842 F)). The measuring resistor is embedded in an homogeneous, fused glass body. Dimensional drawings Measuring insert for flue gas resistance thermometers, dimensions in mm (inches) Measuring insert for low-pressure, high-pressure and flange-type resistance thermometers, dimensions in mm (inches) Selection and Ordering data Measuring insert for flue gas resistance thermometer 7MC1000 for temperatures to 600 C (1112 F), stainless steel measuring insert tube Measuring resistor: Winding embedded in ceramic Measuring insert not explosion protected One Pt100 measuring resistor/three-wire circuit Order No. Measuring insert length mm (inch): Mounting length of the resistance thermometer mm (inch): Weight kg (lb): 525 (20.7) 500 (19.7) 0.22 (0.49) 7MC1900-1EA 75 (28.9) 710 (28.0) 0.27 (0.60) 7MC1900-2EA 1025 (40.4) 1000 (9.4) 0.2 (0.71) 7MC1900-EA 1425 (56.1) 1400 (55.1) 0.42 (0.9) 7MC1900-4EA 2025 (79.7) 2000 (78.7) 0.62 (1.7) 7MC1900-5EA Selection and Ordering data Measuring insert for low-pressure, high-pressure and flange-type resistance thermometers Measuring resistor: Winding embedded in ceramic (max. 600 C (1112 F)) Measuring insert not explosion protected One Pt100 measuring resistor/three-wire circuit Measuring insert length mm (inch) Screw-in thermometer without neck tube, 7MC1006 Mounting length mm (inch) Screw-in thermometer with neck tube, 7MC1007 and 7MC1008 Mounting length mm (inch) Screw-in thermometer 7MC1010 Total length without connection head mm (inch) Flange-type thermometer 7MC1017 Mounting length mm (inch) Flange-type thermometer 7MC1041 Mounting length mm (inch) Weight kg (lb) Order No. 145 (5.7) 100 (.9) 0.15 (0.) 7MC1910-1JA 205 (8.1) 160 (6.) 0.16 (0.5) 7MC1910-2JA 275 (10.8) 20 (9.1) 0.17 (0.7) 7MC1910-JA 15 (12.4) 160 (6.) 05 (12.0) 160 (6.) 225 (8.9) 0.18 (0.40) 7MC1910-4JA 75 (14.8) 65 (14.4) 285 (11.2) 0.19 (0.42) 7MC1910-5JA 405 (15.9) 60 (14.2) 250 (9.8) 95 (15.6) 250 (9.8) 0.20 (0.44) 7MC1910-6JA 45 (17.1) 45 (1.6) 0.20 (0.44) 7MC1910-8JA 555 (21.1) 510 (20.1) 400 (15.8) 0.21 (0.46) 7MC1910-7JA /74 Siemens FI

75 Resistance thermometers Accessories Measuring inserts, not explosion protected Selection and Ordering data Measuring insert for low-pressure, high-pressure and flange-type resistance thermometers Measuring resistor: Winding embedded in ceramic (max. 600 C (1112 F)) Two Pt100 measuring resistors/three-wire circuit Measuring insert Screw-in therlength mometer without neck tube, 7MC1006 mm (inch) Mounting length mm (inch) Screw-in thermometer with neck tube, 7MC1007 and 7MC1008 Mounting length mm (inch) Screw-in thermometer 7MC1010 Flange-type thermometer 7MC1017 Total length Mounting without connection head length mm (inch) mm (inch) Flange-type thermometer 7MC1041 Mounting length mm (inch) Weight 145 (5.7) 100 (.9) 0.15 (0.) 7MC1910-1JB 205 (8.1) 160 (6.) 0.16 (0.5) 7MC1910-2JB 275 (10.8) 20 (9.1) 0.17 (0.7) 7MC1910-JB 15 (12.4) 160 (6.) 05 (12.0) 160 (6.) 225 (8.9) 0.18 (0.40) 7MC1910-4JB 75 (14.8) 65 (14.4) 285 (11.2) 0.19 (0.42) 7MC1910-5JB 405 (15.9) 60 (14.2) 250 (9.8) 95 (15.6) 250 (9.8) 0.20 (0.44) 7MC1910-6JB 45 (17.1) 45 (1.6) 0.20 (0.44) 7MC1910-8JB 555 (21.1) 510 (20.1) 400 (15.8) 0.21 (0.46) 7MC1910-7JB Further measuring inserts on request. kg (lb) Order No. Siemens FI /75

76 Resistance thermometers Accessories Measuring inserts, explosion protected Overview An explosion protected measuring insert is suitable for installation in a protective fitting and for connection to a certified intrinsically-safe circuit of category "ia" or "ib". The measuring insert may only be used if the protective fitting has the degree of protection IP20 according to DIN Design The measuring resistor is fitted in a 60 mm (2.6 inch) long stainless steel sleeve with an outer diameter of 6 mm (0.24 inch). The sleeve and the sheath of the supply cable are welded. The sheath of the supply cable is also made of stainless steel, and its outer diameter is 5 mm (0.2 inch). The conductors are made of special copper and are embedded in highly compacted magnesium oxide powder. The connection points between the measuring resistor and the conductors are additionally isolated. The conductors are potted in the terminal base. The rating plate is located underneath the retaining plate. Technical specifications Measuring temperature Resistance of internal conductor Resistance of measuring insert Outer diameter of sleeve Explosion protection Dimensional drawings C ( F) The temperature depends on the maximum measuring current which can flow in the connected measuring circuit if an error occurs. Per measuring circuit, i.e. for both conductors of the two-wire system: 0.17 Ω/m measuring insert 1000 MΩ at room temperature 6 mm (0.24 inch) II 2G EEx ia IIC T4/T6 Selection and Ordering data Measuring insert for low-pressure, high-pressure and flange-type resistance thermometers Stainless steel measuring insert Measuring resistor: Winding embedded in ceramic (max. 450 C (842 F)) Outer diameter of sleeve: 6 mm (0.24 inch) Measuring insert with explosion protection One Pt100 measuring resistor/three-wire circuit Measuring insert length mm (inch) Screw-in thermometer without mometer with Screw-in ther- neck tube, neck tube, 7MC1006 7MC1007 Mounting length Mounting length mm (inch) mm (inch) Screw-in thermometer 7MC1010 Total length without connection head mm (inch) Flange-type thermometer 7MC1017 Mounting length mm (inch) Explosion protected measuring insert for resistance thermometers, dimensions in mm (inches) Flange-type thermometer 7MC1041 Mounting length mm (inch) Weight kg (lb) Order No. 145 (5.7) 100 (.9) 0.15 (0.) 7MC191-1AA (8.1) 160 (6.) 0.16 (0.5) 7MC191-2AA (10.8) 20 (9.1) 0.17 (0.7) 7MC191-AA22 15 (12.4) 160 (6.) 05 (12.0) 160 (6.) 225 (8.9) 0.18 (0.40) 7MC191-4AA22 75 (14.8) 65 (14.4) 285 (11.2) 0.19 (0.42) 7MC191-5AA (15.9) 60 (14.2) 250 (9.8) 95 (15.6) 250 (9.8) 0.20 (0.44) 7MC191-6AA22 45 (17.1) 45 (1.6) 0.20 (0.44) 7MC191-7AA (21.1) 510 (20.1) 400 (15.8) 0.21 (0.46) 7MC191-8AA22 Two Pt100 measuring resistors/two-wire circuit Measuring insert Screw-in length thermometer without neck tube, 7MC1006 mm (inch) Mounting length mm (inch) Screw-in thermometer with neck tube, 7MC1007 Mounting length mm (inch) Screw-in thermometer 7MC1010 Flange-type thermometer 7MC1017 Total length Mounting without length connection head mm (inch) mm (inch) Flange-type thermometer 7MC1041 Mounting length mm (inch) 145 (5.7) 100 (.9) 0.15 (0.) 7MC191-1AB (8.1) 160 (6.) 0.16 (0.5) 7MC191-2AB (10.8) 20 (9.1) 0.17 (0.7) 7MC191-AB12 15 (12.4) 160 (6.) 05 (12.0) 160 (6.) 225 (8.9) 0.18 (0.40) 7MC191-4AB12 75 (14.8) 65 (14.4) 285 (11.2) 0.19 (0.42) 7MC191-5AB (15.9) 60 (14.2) 250 (9.8) 95 (15.6) 250 (9.8) 0.20 (0.44) 7MC191-6AB12 45 (17.1) 45 (1.6) 0.20 (0.44) 7MC191-7AB (21.1) 510 (20.1) 400 (15.8) 0.21 (0.46) 7MC191-8AB12 Further measuring inserts on request. Weight kg (lb) /76 Siemens FI

77 Resistance thermometers Accessories Welding-type protective tubes, neck tubes and connection heads Welding-type protective tube Welding-type protective tube for high-pressure resistance thermometers to DIN 4 767, without neck tube, without connection head Tapered shank with cylindrical welding stubs For measuring insert tube with 6 mm (0.24 inch) OD female thread M18 x 1.5 (including steel screw plug) Neck tube Neck tube for high-pressure screw-in resistance thermometer Made of stainless steel, mat. No With threads at both ends For measuring insert tube with 6 mm (0.24 inch) OD Dimensional drawings Connection heads for low and high-pressure resistance thermometers, flue gas and flange-type resistance thermometers Connection head, form B, degree of protection IP54, made of cast light alloy, with screw cover, dimensions in mm (inches) Connection head, form B, degree of protection IP65, made of cast light alloy, with high hinged cover, dimensions in mm (inches) Connection head, form B, degree of protection IP54, made of plastic, with screw cover, dimensions in mm (inches) Connection head, form B-VA, degree of protection IP65, made of stainless steel, with screw cover, dimensions in mm (inches) Connection head, form B, degree of protection IP65, made of cast light alloy, with standard hinged cover, dimensions in mm (inches) Siemens FI /77

78 Resistance thermometers Accessories Welding-type protective tubes, neck tubes and connection heads Selection and Ordering data Welding protective tube for high-pressure resistance thermometers according to DIN 4767, without neck tube, without connection head tapered shank with cylindrical welding stub, for measuring insert tube with 6 mm (0.24 inch) OD; female thread M18 x 1.5 (including steel screw plug) Up to 540 C (1004 F) Protective tube to DIN 4772, form 4 made of 1 CrMo 44, mat. No Mounting length U mm (inch) Protective tube length L mm (inch) Weight mm (inch) Order No. 65 (2.56) 140 (5.51) 0. (0.66) 7MC1905-1GA 65 (2.56) 200 (7.87) 0.5 (1.1) 7MC1905-2GA 125 (4.92) 200 (7.87) 0.5 (1.1) 7MC1905-GA 125 (4.92) 260 (10.24) 0.6 (1.2) 7MC1905-4GA Up to 550 C (1022 F) Protective tube to DIN 4772, form 4 made of 6 CrNiMoTi 17122, mat. No Mounting length U mm (inch) Protective tube length L mm (inch) Weight kg (lb) 65 (2.56) 140 (5.51) 0. (0.66) 7MC1905-1DA 65 (2.56) 200 (7.87) 0.5 (1.1) 7MC1905-2DA 125 (4.92) 200 (7.87) 0.5 (1.1) 7MC1905-DA 125 (4.92) 260 (10.24) 0.6 (1.2) 7MC1905-4DA Selection and Ordering data Neck tube for high-pressure screw-in resistance thermometer made of stainless steel, mat. No , with thread at both ends, for measuring insert tube with 6 mm (0.24 inch) OD Neck tube Total length of the resistance thermometer, Protective Weight length without connection head tube length mm (inch) mm (inch) mm (inch) kg (lb) Order No. 15 (5.1) 95 (15.55) 260 (10.24) 0.14 (0.1) 7MC1906-1AA 165 (6.50) 05/65 (12.01/14.7) 140/200 (5.51/7.87) 0.15 (0.) 7MC1906-2AA 195 (7.68) 95 (15.55) 200 (7.87) 0.18 (0.40) 7MC1906-AA 225 (8.86) 65 (14.7) 140 (5.51) 0.20 (0.44) 7MC1906-4AA 255 (10.04) 95 (15.55) 140 (5.51) 0.22 (0.49) 7MC1906-5AA Selection and Ordering data Connection heads for low-pressure, high-pressure, flue gas and flange-type resistance thermometers Connection head, form B, degree of protection IP54 made of cast light alloy, with screw cover and with 1 cable bushing, weight: 0.14 kg (0.1 lb) made of plastic, with screw cover and with 1 cable bushing, weight: 0.08 kg (0.18 lb) Connection head, form B, degree of protection IP65 Weight: 0. kg (0.66 lb) made of cast light alloy, with standard hinged cover and with 1 cable bushing made of cast light alloy, with high hinged cover and with 1 cable bushing Connection head, form B-VA, degree of protection IP65 made of stainless steel, with screw cover and with 1 cable bushing, weight: 0.65 kg (1.4 lb) Accessories for connection head, form B, degree of protection IP65 Quick-release clamp (degree of protection of connection head reduced to IP54) Weight: 0.02 kg (0.04 lb) Order No. 7MC1907-1BA 7MC1907-1BK 7MC1907-1BF 7MC1907-1BL 7MC1907-1BV 7MC1907-1BS Connection heads with a drilled hole of 15.5 mm diameter (0.61 inch) instead of the female thread M24 x 1.5 on request. /78 Siemens FI

79 Thermocouples Technical description Design A thermocouple comprises The thermocouple element (sensor) and The mounting and connection parts required in each case. The thermocouple element is formed by two conductors of dissimilar metals or metal alloys which are soldered or welded together at one end, the measuring junction: Thermocouple element Function Measuring principle of the thermocouple element If the measuring junction is exposed to a temperature different from that at the free ends of the thermocouple, a voltage (the thermoelectric voltage, Seebeck effect) is produced at these free ends. The magnitude of the thermoelectric voltage depends on the difference in temperature between the measuring junction and the free ends, and on the combination of materials in the thermocouple. Since a thermocouple always measures a temperature difference, the free ends of the thermocouple must be connected to a reference junction (cold conjunction) and held constant at a known temperature. Calibration data for thermoelectric voltages and permissible deviations The calibration data and the permissible deviations for commonly used thermocouples are defined isee Technical Data, Table "Calibration data for thermoelectric voltages and error limits"). The thermocouples Cu-CuNi and Fe-CuNi to DIN 4710 are used for replacement purposes. Thermocouples of class 2 are supplied as standard. For more accurate measurements, thermocouples are available with half the DIN tolerance or with a test certificate. The tolerances only apply to the condition upon delivery. During operation at high temperatures, the tolerances of the thermocouples may change due to absorption of foreign matter, oxidation or evaporation of alloy components. Mode of operation The thermocouples are extended from the connection point to a point whose temperature is as constant as possible (the cold junction) by means of extension leads. The extension leads have the same color code as the associated thermocouple elements; the positive pole is marked in red. Correct polarity must be ensured since otherwise large errors will occur. Up to 200 C, the same calibration data and tolerances apply to the extension leads as to the corresponding thermocouples. The influence of temperature changes at the cold junction can be balanced by means of a compensating circuit, e.g. a compensating box. The reference temperature is 0 (2 F ) or 20 C (68 F). It is also possible to keep the cold junctions at a constant temperature of 50, 60 or 70 C (122, 140 or 158 F) using a thermostat (for several measuring junctions). The connections from the cold junction to the measuring or process instrument are made using copper leads. With energy-consuming instruments such as indicators or multipoint recorders, the complete measuring circuit (thermocouple, extension lead and copper lead) must be balanced in the operating condition using a resistor. SITRANS T transmitters and KOMPENSOGRAPH servo recorders for connection to thermocouple elements have a built-in compensating circuit for balancing the effect of the ambient temperature on the cold junction. Lead balancing is not necessary in this case because of the high input impedance. Protection fitting/protective tubes The thermocouple can be protected against mechanical stress and chemical attack by a ceramic or metal protective tube which may be mounted using flanges, screwed glands or by welding into the pipeline or tank. The thermocouple element terminates in the connection head. Installation examples with specification of the recommended thermocouples and protective tube materials are listed on pages "Technical Data"and "Installation Examples". Owing to the different operating conditions, no guarantee can be given for protective fittings. The manufacturer is responsible for damages and measuring errors caused by wrong installation in compliance with the General Terms of Delivery if the instruments have been installed by the manufacturer and if the specifications for the operating conditions furnished by the customer were correct and sufficiently detailed. Thermocouple elements are very compatible since it is almost always possible to adapt them in shape and size to the particular problem. The temperature-responsive part is almost pointshaped. Thermocouple elements are therefore particularly suitable for measuring rapidly changing temperatures. Siemens FI /79

80 Thermocouples Technical description Integration Siemens AG 2007 Instrument combination for measuring and controlling temperature, with thermocouple element as sensor Sense Thermocouple Match Cold junction thermostat Catalog FI 01 Cold junction with power supply unit Catalog FI 01 Electric transmitter Catalog FI 01 Output Control Electric Catalog digital indicator digital limit monitor recorder MP 20 controller MP 1 Electric Catalog analog indicator MP 12 analog limit monitor MP 12 Installation examples with specification of appropriate thermocouples and protective tubes Measuring point Permissible operating temperature C ( F) A. Iron and steel works 1. Blast furnace Thermocouple Protective tube Hot blast 1000 (182) Ni Cr/Ni Open protective tube X 10 CrAl 24, mat. No , bare soldering point, cemented Crude gas 00 (572) Ni Cr/Ni X 10 CrAl 24, mat. No , dished 2. Air preheater Dome 1200 (2192) Pt 10% Rh/Pt Outside: X 15 CrNiSi 24 19, mat. No , inside: KER 710 Exhaust gas 00 (572) Ni Cr/Ni St 5.8, mat. No , seamless, enamelled. Open-hearth furnace Exhaust gas ducts 600 (1112) Ni Cr/Ni X 10 CrAl 24, mat. No , dished Checkers 150 (2462) Pt 10% Rh/Pt Outside: Silicon carbide inside: KER 710 Melt (for short periods) 4. Soaking pit Furnace chamber 1600 (2912) Pt 10% Rh/Pt Immersion-type thermocouple element of special design 150 (2462) Pt 10% Rh/Pt Outside: Silicon carbide inside: KER 710 Measuring point Exhaust gas before or behind recuperator Combustion air behind recuperator 1000 (182) Ni Cr/Ni X 10 CrAl 24, mat. No , dished; installation with gas-tight screw socket 700 (1292) Ni Cr/Ni X 10 CrAl 24, mat. No , dished; installation with gas-tight screw socket 5. Pusher, rotating hearth furnace, and other types of rolling mill furnace Preheating zone 800 (1472) Pt 10% Rh/Pt or Ni Cr/Ni Heating zone 1250 (2282) Pt 10% Rh/Pt As above Outside: Silicon carbide inside: KER 710 or outside: Silicon carbide inside: KER 610 Soaking zone 150 (2462) Pt 10% Rh/P Outside: Silicon carbide inside: KER 710 Exhaust gas before air recuperator Exhaust gas before and behind gas recuperator Permissible operating temperature C ( F) Preheated air behind recuperator Thermocouple Protective tube 900 (1652) Ni Cr/Ni X 10 CrAl 24, mat. No , dished; installation with gas-tight screw socket 700 (1292) Ni Cr/Ni As above or KER (1292) Ni Cr/Ni As above /80 Siemens FI

81 Thermocouples Installation examples with specification of appropriate thermocouples and protective tubes (continued) Technical description Measuring point Permissible operating temperature C ( F) Thermocouple 6. Annealing furnace, roller-hearth furnace Furnace chamber Exhaust gas duct 7. Bell-type anneal. furn. Directly heated furnace Stack for tin plates Stack for motorcar body sheet Protective tube 800 (1472) Ni Cr/Ni X 10 CrAl 24, mat. No , dished 600 (1112) Ni Cr/Ni As above 950 (1742) Ni Cr/Ni X 10 CrAl 24, mat. No , dished ( ) ( ) Ni Cr/Ni Ni Cr/Ni Special design, bare thermocouple element with thermal contact plate As above Protective gas 650 (1202) Ni Cr/Ni Bare thermocouple element 8. Sinter belts (Sucking boxes) 400 (752) Fe/Cu Ni (Jacket thermocouple element) X 10 CrAl 24, mat. No For temperature maximum computing circuit 9. Tinning plants Palm nut oil, pickling vat, tin bath 400, 500 (752, 92) 10. Zinc coating plants Fe/Cu Ni As above, with double thermocouple 650 (1202) Ni Cr/Ni St 5.8, mat. No , seamless, enamelled Zinc bath 480 (896) Fe/Cu Ni St 5.8, mat. No , seamless 11. Heat treatment plants 11.1 In gases Tempering furnaces Annealing in oxidizing gases containing sulphur and carbon Annealing in reducing gases containing sulphur Annealing in nitrogen-containing gases poor in oxygen, also nitriding furnaces with ammonia 550 (1022) Ni Cr/Ni St 5.8, mat. No , seamless 1050 (1922) Pt 10% Rh/Pt (Ni Cr/Ni) Outside: X 10 CrAl 24, mat. No , dished inside: KER (2192) Pt 10% Rh/Pt Outside: X 10 CrAl 24, mat. No , dished inside: KER (2192) Pt 10% Rh/Pt As above 1200 (2192) Pt 10% Rh/Pt Outside: X 15 CrNiSi 24 19, mat. No , dished; inside: KER 710 Measuring point 11.2 In hardening shop baths (protective tubes bored from the solid are recommended) Salt and nitre 550 (1022) Ni Cr/Ni Soft iron, mat. No Cyanogen 950 (1742) Ni Cr/Ni Soft iron or X 15 CrNiSi 24 19, mat. No Baths containing chloride 1050 (1922) Pt 10% Rh/Pt Outside: X 10 CrAl 24, mat. No , inside: KER 710 Lead baths 1200 (2192) Pt 10% Rh/P Outside: Chromium nickel alloy NiCr 60 15, mat. No , inside: KER 710; bored from the solid Barium chloride baths 100 (272) Pt 10% Rh/Pt Outside: Chromium nickel alloy NiCr 60 15, mat. No , inside: KER 710; B. Metallurgical plants (only limited life time in molten metals) Copper melt 1250 (2282) Pt 10% Rh/Pt Outside: X 10 CrSi 29, mat. No , bored from the solid inside: KER 710 Exhaust of copper melting furnaces 100 (272) Pt 10% Rh/Pt Outside: Silicon carbide inside: KER 710 Brass melts 900 (1652) Ni Cr/Ni X 10 CrAl 29, mat. No , bored from the solid Aluminium melts 700 (1292) Ni Cr/Ni Pearlite iron GG 22, bored from the solid Die-casting, magnesium Bearing metal, lead and tin melting houses 700 (1292) Ni Cr/Ni Soft iron, mat. No , bored from the solid 600 (1112) Fe/Cu Ni St 5.8, mat. No , seamless, enamelled Lead foundries 700 (1292) Fe/Cu Ni Chromium nickel alloy NiCr 60 15, mat. No , bored from the solid Zinc foundries 480 (878) Fe/Cu Ni St 5.8, mat. No , seamless Exhaust gases of zinc melting furnaces C. Ceramic industry Ring kiln for standard bricks Ring kiln for clinkers, retort furnace, tunnel furnace, glazing kiln Permissible operating temperature C ( F) 600 (1112) Fe/Cu Ni Silicon carbide 100 (272) Pt 10% Rh/Pt Outside: Silicon carbide inside: KER ( ) ( ) Thermocouple Ni Cr/Ni X 10 CrAl 24, mat. No , dished Pt 10% Rh/Pt Protective tube Outside and inside: KER 710 Siemens FI /81

82 Thermocouples Technical description Siemens AG 2007 Installation examples with specification of appropriate thermocouples and protective tubes (continued) Measuring point D. Glass industry Permissible operating temperature C ( F) 1. Glass trough furnace Checkers of the regenerative chambers, above Checkers of the regenerative chambers, below Lateral walls, roof, bottom (in drilled channels down to 50 mm below the bath) Thermocouple Protective tube 100 (272) Pt 10% Rh/Pt Outside: KER 50 Inside: KER (1112) Ni Cr/Ni Thermocouple porcelain 1550 (2822) 1400 (2552) Pt 0% Rh/ Pt 6% Rh Outside and inside: KER 710 Leer 800 (1472) Ni Cr/Ni X 10 CrAl 24, mat. No , dished Annealing furnace 2. Pot furnace. Gas generators 1200 (2192) Pt 10% Rh/Pt KER (272) Pt 0% Rh/ Pt 6% Rh Outside and inside: KER 710 Crude gas 750 (182) Ni Cr/Ni X 10 CrAl 24, mat. No , dished Rotary grate (Grate head) ( ) For short periods: 500 to 1000 (92 to 182) E. Cement industry Rotary kilns Secondary air at cooler Fe/Cu Ni Special design on request (to be manufactured on site according to specifications) 900 (1652) Ni Cr/Ni X 10 CrAl 24, mat. No Hot chamber 900 (1652) Ni Cr/Ni X 10 CrAl 24, mat. No Drying chamber 400 (752) Fe/Cu Ni St 5.8, mat. No , or similar, enamelled F. Cellulose factories Sulphur combustion furnaces, pyrite burnerr Behind waste heat boiler to 1500 (272) Pt 0% Rh/ Pt 6% Rh Outside: Silicon carbide inside: KER (1112) Ni Cr/Ni X 10 CrAl 24, mat. No Measuring point G. Steam power parts Water and steam lines (screw-in and welding-type thermocouple elements) Screw-in thermocouple element Screw-in thermocouple element Welding-type thermocouple element Welding-type thermocouple element Technical specifications 00 (572) Fe/Cu Ni Sn Bz 6 bronze, to DIN 1726 (only for air or water) 400 (752) Fe/Cu Ni St 5.8, mat. No (92) Fe/Cu Ni 11 CrMo 44, mat. No (1004) Fe/Cu Ni 11 CrMo 44, mat. No (1058) Ni Cr/Ni 10 CrMo 9 10, mat. No (182) Fe/Cu Ni (Ni Cr/Ni) X 8 CrMoNb 16 16, mat. No Flue gas 1000 (182) Pt 10% Rh/Pt Megapyr, Cr Al 20 5, mat. No or outside: X 10 CrAl 24, mat. No , inside: KER 710 St Pulverized coal/air mixture line 600 (1112) (Ni Cr/Ni) St 5.8, mat. No , enamelled 100 (212) Fe/Cu Ni St 5.8, mat. No , (with baffle rod) Thermocouple designations to DIN 4710 and DIN IEC 584 DIN 4710, release Cu-CuNi Fe-CuNi DIN IEC Cu/Cu Ni Fe/Cu Ni Ni Cr/Ni Ni Cr Si-NiSi Pt 10% Rh/Pt Pt 1% Rh/Pt Pt 0% Rh/ Pt 6% Rh Permissible operating temperature C ( F) Screw-in thermocouple element Thermocouple Type U Type L Type T Type J Type K Type N Type S Type R Type B Protective tube /82 Siemens FI

83 Thermocouples Temperature transmitters for mounting in the connection head Overview Selection and Ordering Data Detailed information on the transmitters can be found for the respective products under "Transmitters for temperature. The following temperature transmitters are available for mounting in the connection head: SITRANS TH200 Programmable two-wire temperature transmitter (4 to 20 ma), electrical isolation for resistance thermometers and thermocouple elements. SITRANS TH00 Two-wire temperature transmitter with HART communication (4 to 20 ma), electrical isolation for resistance thermometers and thermocouple elements. SITRANS TH400 Temperature transmitter with PROFIBUS-PA or FOUNDATION fieldbus connection, electrical isolation for resistance thermometers and thermocouple elements. Note: SITRANS TH200/TH00/TH400 can be fitted instead of the terminal block (not with 7MC ) or in the high hinged cover. Additional fitting only possible in high hinged cover. If using intrinsically-safe temperature sensors any installed temperature transmitters must also be intrinsically-safe. Transmitter to be fitted To order the sensor with a built-in temperature transmitter, add "-Z" to the Order No. of the sensor, and supplement by the following Order code: SITRANS TH200 - without Ex T20 - EEx ia IIC and EEx n for zone 2 T21 - FM (IS, I, NI) T2 SITRANS TH00 - without Ex T0 - EEx ia IIC und EEx n for zone 2 T1 - FM (IS, I, NI) T SITRANS TH400 PA - without Ex T40 - EEx ia T41 SITRANS TH400 FF - without Ex T45 - EEx ia T46 Customer-specific setting of the built-in transmitter (specify settings in plain text) 1) For TH400 FF available soon. Order code Y11 1) Siemens FI /8

84 Thermocouples Questionnaire for temperature sensors (resistance thermometers and thermocouples) General information Customer:... Address:... Contact partner:... Purchasing dept.:... Tel.:... Sales dept.:... Tel.:... Process dept.:... Tel.:... Inquiry:... Quotation:... Place and date:... Operating conditions 1. Application:... (e.g. exhaust gas measurement) 2. Location:... (e.g. pipe bend, tank). Mounting position:... (e.g. vertical, 45 against flow) 4. Temperature (measuring point):... Operating temperature:... Temperature range: Medium: Pressure:... Nominal pressure:... Operating pressure: Flow: Vibrations: Miscellaneous:... (e.g. vessel or pipe materials, PTFE lining) Ambient conditions (e.g. seawater atmosphere, chemical plant) Definition: Special information 1. Mounting of temperature transmitter in connection head: Packaging regulations: Miscellaneous Please additionally provide the following: rough sketch, installation diagram, section of drawing, photo Sensor design 1. Measuring element... (type and standard) (e.g. Pt100 or TC type K) 1.1. Tolerance: Design:... (e.g. Pt100 or 2, or 4-wire system) 1.. Degree of protection/type of protection: Protective fitting: Protective tube:... (dimensions/material) 2.2. Mounting:... (dimensions/material) 2.. Neck tube:... (dimensions/material) 2.4. Mounting length/nominal length:.... Material certificates: Connection: Connection head/box: Cable:... (dimensions/insulation/standard) 4.. Other: Tests: Accessories: Supplementary requirements: /84 Siemens FI

85 Thermocouples Straight thermocouples to DIN 47, with connection head Overview The straight thermocouple together with a metal protective tube is suitable for temperatures from 0 to 1250 C (2 to 2282 F) and can be supplied with a built-in temperature transmitter. Technical specifications Thermocouples Number 1 or 2 Leg diameter Insulation of legs Protective tube Connection head Dimensional drawings Straight thermocouple, dimensions in mm (inches) Design Ni Cr/Ni type K 2... mm ( inch) Insulating beads Metal Form A, DIN 4729; made of cast light alloy, with one cable bushing Straight thermocouple with base-metal element Ni Cr/Ni with metal protective tube Selection and Ordering data Straight thermocouple with Ni Cr/Ni thermocouple (type K) with metallic protective tube Order No. to 1000 C (182 F) X 10 CrAl 24, mat. No mm Ø x 2 mm (0.87 inch x inch) 1 thermocouple Leg diameter 2 mm (0.08 inch) Weight: kg ( lb) Nominal length in mm (inch): 500 (19.7) 7 M C D C (28.0) 7 M C D C (9.4) 7 M C D C 07 2 thermocouples Leg diameter 2 mm (0.08 inch) Weight: kg ( lb) Nominal length in mm (inch) 500 (19.7) 7 M C D D (28.0) 7 M C D D (9.4) 7 M C D D 07 to 1100 C (2012 F) X 18 CrN28, material No mm Ø x 4 mm (1.02 inch x 0.16 inch) 1 thermocouple Leg diameter mm (0.12 inch) Weight: kg ( lb) Nominal length in mm (inch): 500 (19.7) 7 M C E C (28.0) 7 M C E C (9.4) 7 M C E C 07 2 thermocouples Leg diameter mm (0.12 inch) Weight: kg ( lb) Nominal length in mm (inch): 500 (19.7) 7 M C E D (28.0) 7 M C E D (9.4) 7 M C E D 07 to 1200 C (2192 F) X 15 CrNi Si 24 19, material No mm Ø x 2 mm (0.87 inch x inch) 1 thermocouple Leg diameter 2 mm (0.08 inch) Weight: kg ( lb) Nominal length in mm (inch): 500 (19.7) 7 M C F C (28.0) 7 M C F C (9.4) 7 M C F C 07 2 thermocouples Leg diameter 2 mm (0.08 inch) Weight: kg ( lb) Nominal length in mm (inch): 500 (19.7) 7 M C F D (28.0) 7 M C F D (9.4) 7 M C F D 07 To 1250 C (2282 F) CrAl 205 (Megapyr), material No mm Ø x 2 mm (0.87 inch x inch) 1 thermocouple Leg diameter mm (0.12 inch) Weight: kg ( lb) Nominal length in mm (inch): 500 (19.7) 7 M C H C (28.0) 7 M C H C (9.4) 7 M C H C 07 2 thermocouples Leg diameter mm (0.12 inch) Weight: kg ( lb) Nominal length in mm (inch): 500 (19.7) 7 M C H D (28.0) 7 M C H D (9.4) 7 M C H D 07 Connection head, form A, made of cast light alloy, with 1 cable inlet and - screw cover 1 - high hinged cover 6 Siemens FI /85

86 Thermocouples Straight thermocouples Individual parts and accessories Selection and Ordering data Straight thermocouple with Ni Cr/Ni thermocouple (type K) for temperatures to 1250 C (2282 F); with metallic protective tube Further designs Please add "-Z" to Order No. and specify Order code(s) and plain text. Different design (mounting length, protective tube material etc.), specify in plain text. TAG plate made of stainless steel specify TAG No. in plain text Calibration carried out at one point, specify desired temperature in plain text (order equivalent number of times for several calibration points). Order No. Order code To order a temperature transmitter installed in the connection head, see "Temperature transmitters for installation in the connection head" (page /8). Installation of a transmitter is only possible here in the versions with a high hinged cover (7MC ). Selection and Ordering data Metallic protective tubes for straight thermocouple elements according to DIN 47 Y01 Y15 Y Order No. X 10 CrAl 24, material No ; 22 mm x 2 mm (; 0.87 inch x 0.08 inch), kg ( lb), dished Nominal length Protective tube length in mm (inch): in mm (inch): 500 (19.7) 520 (20.5) 7MC2900-1DA 710 (28.0) 70 (28.7) 7MC2900-2DA 1000 (9.4) 1020 (40.2) 7MC2900-DA X 10 CrAl 24, material No ; 26 mm x 4 mm (; 1.02 inch x 0.16 inch), kg ( lb), dished Nominal length Protective tube length in mm (inch): in mm (inch): 500 (19.7) 520 (20.5) 7MC2900-1EC 710 (28.0) 70 (28.7) 7MC2900-2EC 1000 (9.4) 1020 (40.2) 7MC2900-EC X 15 CrNiSi 25 20, material No ; 22 mm x 2 mm (; 0.87 inch x 0.08 inch), 1.05 kg (2.1 lb), dished Nominal length Protective tube length in mm (inch): in mm (inch): 1000 (9.4) 1020 (40.2) 7MC2900-FA CrAl 205 (Megapyr), material No ; 22 mm x 2 mm (; 0.87 inch x 0.05 inch), kg ( lb) Nominal length Protective tube length in mm (inch): in mm (inch): 500 (19.7) 520 (20.5) 7MC2900-1HA 710 (28.0) 70 (28.7) 7MC2900-2HA 1000 (9.4) 1020 (40.2) 7MC2900-HA Selection and Ordering data Thermocouples elements for straight thermocouple according to DIN 47 Base-metal thermocouple with insulating beads Wire diameter mm (0.12 inch) Ni Cr/Ni, to 1000 C (maximal 100 C), (to 182 F (max. 272 F)) kg ( lb) Nominal length L1 in mm (inch): Thermocouple length L2 in mm (inch): Order No. 500 (19.7) 540 (21.) 7MC290-1CA 710 (28.0) 750 (29.5) 7MC290-2CA 1000 (9.4) 1040 (40.9) 7MC290-CA /86 Siemens FI

87 Thermocouples Straight thermocouples Individual parts and accessories Connection heads Connection head, form A (without terminal block and terminals) for protective tube diameter (bore = protective tube diameter +0.5 mm (0.02 inch)) Selection and Ordering data Connection head, form A, (without terminal block and terminals) 1 Cable inlet, degree of protection IP5, 0.5 kg (0.77 lb) Cast light alloy fastener, unscrewable for protective tube diameter in mm (inch) (bore = protective tube diam mm) (0.02 inch): 22 (0.87) 26 (1.02) Cast light alloy high hinged cover for protective tube diameter in mm (inch) (bore = protective tube diam mm) (0.02 inch): 22 (0.87) 26 (1.02) Order No. 7MC2905-1AA 7MC2905-1BA 7MC2905-4AA 7MC2905-4BA Mounting accessories for connection heads Terminal block Terminal Set of gaskets Set of washers Mounting flange Threaded sleeve Selection and Ordering data Mounting accessories Terminal block without terminals for base-metal thermocouples; 0.06 kg (0.1 lb) Terminal for base-metal thermocouples; 0.01 kg (0.02 lb) Set of gaskets (100 off) for the connection head cover; 0.01 kg (0.02 lb) Set of washers (100 off) for the terminal block; 0.01 kg (0.02 lb) Mounting flange, adjustable; made of GTW for protective tube outer diameters 22 mm (0.87 inch); 0.5 kg (0.77 lb) for protective tube outer diameters 26 mm (1.02 inch); 0.2 kg (0.71 lb) Threaded sleeve Gas-tight up to bar (14.5 psi), adjustable, materiall No , with gasket; 0.40 kg (0.88 lb) for protective tube outer diameters 22 mm (0.87 inch), G1 for protective tube outer diameters 26 mm (1.02 inch), G1 Order No. 7MC2998-1AA 7MC2998-1BA 7MC2998-1CA 7MC2998-1CB 7MC2998-2CB 7MC2998-2CC 7MC2998-2DB 7MC2998-2DC Dimensional drawings Mounting flange to DIN 474 (left) and threaded sleeve (right) for installing straight thermocouples, dimensions in mm (inches) Siemens FI /87

88 Thermocouples Jacket thermocouples with extension lead Siemens AG 2007 Overview The jacket thermocouple with extension lead is suitable for a temperature range from 0 to 700, 1000 or 1100 C (2 to 1292, 182 or 2012 F); a temperature of 80 to 260 C (176 to 500 F) is permissible for the extension lead. Technical specifications Thermocouple Jacket Form Minimum bending radius Material Extension lead Number of conductors: 2 Conductor cross-section: 0.22 mm 2 ( inch 2 ) Length: m (9.84 ft) Type Max. temperature Dimensional drawings Conductor material Ni Cr/Ni, type K, one off Outer diameter 0.5, 1.0, 1.5 or mm (0.02, 0.04, 0.06 or 0.12 inch) fivefold outer diameter Inconel; NiCr 15 Fe, mat. No Insulation C ( F) single common L2SS 180 (56) Ni Cr/Ni Silicon Silicon L2KK 80 (176) Ni Cr/Ni PVC PVC L2TGD 260 (500) Ni Cr/Ni PTFE Glass-filament and external stainless steel braiding Selection and Ordering data Jacket thermocouple element with extension lead Maximum temperature of medium 700 C (1292 F), jacket outer diameter 0.5 mm (0.02 inch) Extension lead type L2KK Nominal length in mm (inch): 00 (11.8) Maximum temperature of medium 1000 C (182 F), jacket outer diameter 1 mm (0.04 inch) Extension lead type L2SS Nominal length in mm (inch): 100 (.94) 00 (11.8) 500 (19.7) Extension lead type L2KK Nominal length in mm (inch): 100 (.94) 00 (11.8) 500 (19.7) Maximum temperature of medium 1100 C (2012 F), jacket outer diameter 1.5 mm (0.06 inch) Extension lead type L2SS Nominal length in mm (inch): 100 (.94) 00 (11.8) 500 (19.7) Extension lead type L2KK Nominal length in mm (inch): 100 (.94) 00 (11.8) 500 (19.7) Order No. 7MC2027-2BA10 7MC2027-1AA20 7MC2027-2AA20 7MC2027-AA20 7MC2027-1BA20 7MC2027-2BA20 7MC2027-BA20 7MC2027-1AA0 7MC2027-2AA0 7MC2027-AA0 7MC2027-1BA0 7MC2027-2BA0 7MC2027-BA0 Jacket thermocouple with extension lead, dimensions in mm (inches) Jacket outer diameter.0 mm (0.12 inch) Extension lead type L2SS Nominal length in mm (inch): 100 (.94) 00 (11.8) 500 (19.7) Extension lead type L2KK Nominal length in mm (inch): 100 (.94) 00 (11.8) 500 (19.7) Extension lead type L2TGD Nominal length in mm (inch): 100 (.94) 00 (11.8) 500 (19.7) 7MC2027-1AA40 7MC2027-2AA40 7MC2027-AA40 7MC2027-1BA40 7MC2027-2BA40 7MC2027-BA40 7MC2027-1CA40 7MC2027-2CA40 7MC2027-CA40 Further designs Please add "-Z" to Order No., and specify Order code(s) and plain text. Order code Different design (mounting length, protective tube material etc.), specify in plain text. TAG plate made of stainless steel specify TAG No. in plain text Calibration carried out at one point, specify desired temperature in plain text (order equivalent number of times for several calibration points). Y01 Y15 Y /88 Siemens FI

89 Thermocouples Jacket thermocouples with connection head, form B Overview Dimensional drawings The jacket thermocouple with connection head, form B is suitable for the temperature range from 0 to 800 or 1,100 C (2 to 1472 or 2012 F) and can also be supplied with a built-in temperature transmitter. Technical specifications Jacket thermocouple with connection head, form B Thermocouple Jacket Material Fe/Cu Ni, Fe-CuNi or Ni Cr/Ni Measuring junction insulated from base of jacket X 6 CrNiTi 18 10, mat. No Inconel Temperature Up to 800 C (1472 F) Up to 1100 C (2012 F) Connection head Form B to DIN 4729 Material Temperature Cable inlet Terminal block Cast light alloy C ( F) is permissible For cables up to 15 mm (0.59 inch) diameter Without clamping springs Thermocouple Insulation resistance between conductors and jacket: 1000 MΩ/m at 20 C ( 05 MΩ/ft at 68 F) Minimum bending radius: 5 x outer diameter of jacket Leak resistance of measuring junction: Tested at 40 bar (580 psi) Thermocouple Fe/Cu Ni (type J) and Fe-CuNi (type L) Ni Cr/Ni (type K) Jacket Outer diameter Wall thickness No. of thermocouples Thermocouple wire diameter Resistance (for double conductor) mm (inch) mm (inch) mm (inch) Ω/m (Ω/ft).0 (0.12) 0.42 (0.017) 0.42 (0.017) 6.0 (0.24) 0.55 (0.022) 0.89 (0.05).0 (0.12) 0.42 (0.017) 0.42 (0.017) 6.0 (0.24) 0.55 (0.022) 0.89 (0.05) (0.02) 2.7 (8.9) (0.02).5 (11.5) (0.04) 0.66 (2.2) (0.0) 1.14 (.7) (0.02) 4. (14.1) (0.02) 5.5 (18.0) (0.04) 1.12 (.7) (0.0) 1.94 (6.4) Jacket thermocouple with connection head, form B, made of cast light alloy, dimensions in mm (inches) Selection and Ordering data Jacket thermocouple element with connection head, form B Fe/Cu Ni type J thermocouple Jacket made of X 6 CrNiTi 18 10, material No , temperature up to 800 C (1472 F) 1 thermocouple Jacket outer diameter/mm (inch):.0 (0.12) 6.0 (0.24) 2 thermocouples Jacket outer diameter/mm (inch):.0 (0.12) 6.0 (0.24) Fe/Cu Ni type L thermocouple Jacket made of X 6 CrNiTi 18 10, material No , temperature up to 800 C (1472 F) 1 thermocouple Jacket outer diameter/mm (inch):.0 (0.12) 6.0 (0.24) 2 thermocouples Jacket outer diameter/mm (inch):.0 (0.12) 6.0 (0.24) Ni Cr/Ni type K thermocouple Jacket made of Inconel, temperature up to 1,100 C (2012 F) 1 thermocouple Jacket outer diameter/mm (inch):.0 (0.12) 6.0 (0.24) 2 thermocouples Jacket outer diameter/mm (inch):.0 (0.12) 6.0 (0.24) Further designs Please specify Order code(s) and plain text. Order No. Length L in m (ft) (0.82) A01-1 (.28) A02-5 (16.4) A0-10 (2.8) A04 Different design (mounting length, protective tube material etc.), specify in plain text. Y01 TAG plate made of stainless steel Y15 specify TAG No. in plain text Calibration carried out at one point, specify Y desired temperature in plain text (order equivalent number of times for several calibration points). 7MC2021-2CE-Z 7MC2021-4CE-Z 7MC2021-2CF-Z 7MC2021-4CF-Z 7MC2021-2CA-Z 7MC2021-4CA-Z 7MC2021-2CB-Z 7MC2021-4CB-Z 7MC2021-2LC-Z 7MC2021-4LC-Z 7MC2021-2LD-Z 7MC2021-4LD-Z Order code To order a temp. transmitter installed in the connection head, see "Temp. transm. for installation in the connection head" (page /8). Note: SITRANS TK PA can only be used in a connection head with high hinged cover. Can be ordered als special version (...-Z Y01). Example of ordering: The following is required: Jacket thermocouple element jacket made of X 6 CrNiTi 18 10; outer diameter.0 mm (0.12 inch); - with 1 Fe/Cu Ni thermocouple, type J; nominal length 5 m (16.4 ft) Order as follows: 1 jacket thermocouple 7MC2021-2CE-Z A0 Siemens FI /89

90 Thermocouples Jacket thermocouples with socket Siemens AG 2007 Overview The sensor is suitable for a temperature range from 0 to 800, 1000 or 1100 C (2 to 1472, 182 or 2012 F); a maximum temperature of 10 C (266 F) is permissible for the plug connection. Technical specifications Thermocouple Jacket Material Temperature Coupling socket Housing Contact Coupling plug Dimensional drawings Ni Cr/Ni X 6 CrNiTi 18 10, mat. No Inconel, NiCr 15 Fe, mat. No Up to 800 C (1472 F) Up to 1100 C (2012 F) Made of polyamide Made of temperature-resistant material See "Jacket thermocouples", "Individual parts"; incorrect connection impossible Jacket thermocouple with socket; at top with one thermocouple, at bottom with two thermocouples; dimensions in mm (inches) Selection and Ordering data Jacket thermocouple element with coupling socket Ni Cr/Ni type K thermocouple Order No. Jacket material No Temperature of medium 800 C (1472 F) 1 thermocouple Jacket outer dia./ Length L/m (ft): mm (inch):.0 (0.12) 0. (0.98) 7MC2028-1AC1.0 (0.12) 0.5 (1.64) 7MC2028-2AC1 2 thermocouples Jacket outer dia./ Length L/m (ft): mm (inch):.0 (0.12) 0. (0.98) 7MC2028-1AD1.0 (0.12) 0.5 (1.64) 7MC2028-2AD1 6.0 (0.24) 0. (0.98) 7MC2028-1AD (0.24) 0.5 (1.64) 7MC2028-2AD41 Jacket material No Temperature of medium 1000 C (182 F) 1 thermocouple Jacket outer Length L/m (ft): diameter/mm (inch): 1.0 (0.04) 0. (0.98) 7MC2028-1AC (0.04) 0.5 (1.64) 7MC2028-2AC12 Jacket material No Temperature of medium 1100 C (2012 F) 1 thermocouple Jacket outer dia./ Length L/m (ft): mm (inch): 1.5 (0.06) 0. (0.98) 7MC2028-1AC (0.06) 0.5 (1.64) 7MC2028-2AC22.0 (0.12) 0. (0.98) 7MC2028-1AC2.0 (0.12) 0.5 (1.64) 7MC2028-2AC2 6.0 (0.24) 0. (0.98) 7MC2028-1AC (0.24) 0.5 (1.64) 7MC2028-2AC42 2 thermocouples Jacket outer dia./ Length L/m (ft): mm (inch):.0 (0.12) 0. (0.98) 7MC2028-1AD2.0 (0.12) 0.5 (1.64) 7MC2028-2AD2 6.0 (0.24) 0. (0.98) 7MC2028-1AD (0.24) 0.5 (1.64) 7MC2028-2AD42 Further designs Please add "-Z" to Order No. and specify Order code(s) and plain text. Different design (mounting length, protective tube material etc.), specify in plain text. TAG plate made of stainless steel specify TAG No. in plain text Calibration carried out at one point, specify desired temperature in plain text (order equivalent number of times for several calibration points). Order code Y01 Y15 Y Different designs (mounting length, protective tube material etc.) on request: Add Order code "Y01" and specify in plain text. (Please order coupling plug separately (see "Individual parts")) /90 Siemens FI

91 Thermocouples Individual parts Selection and Ordering data Extension lead for jacket thermocouple with coupling socket (7MC2028); twisted cores for Ni Cr/Ni thermocouple, color code: green Outer diameter 4 mm (0.16 inch) PVC isolation Number of conductors and cross-section: 2 x 0.22 mm² (2 x inch²) Temperature range C ( F) Outer diameter 4 mm (0.16 inch) Silicone-silicone isolation Number of conductors and cross-section: 2 x 0.22 mm² (2 x inch²) Silicone-silicone isolation Temperature range C ( F) Outer diameter 6 mm (0.24 inch) PVC isolation Number of conductors and cross-section: 4 x 0.22 mm² (2 x inch²) Temperature range C ( F) Outer diameter 6 mm (0.24 inch) Silicone-silicone isolation Number of conductors and cross-section: 4 x 0.22 mm² (2 x inch²) Temperature range C ( F) Further designs Please specify Order code(s) and plain text. Length of extension lead in m (ft) (0.82) A01-1 (.28) A02-5 (16.4) A0-10 (2.8) A04 Other individual parts Screw nipple Compression joint Coupling socket Coupling plug Dimensional drawings Order No. 7MC2921-1AC-Z 7MC2921-2AC-Z 7MC2921-AC-Z 7MC2921-4AC-Z Order code Screw nipple with M8 x 1 thread (left) or G¼ (right), dimensions in mm (inches) d D l L SW mm (inch) mm (inch) mm (inch) 1,5 (0.06) M8x1 8 (0.) 2 (1.) 12,0 (0.12) M8x1 8 (0.) 2 (1.) 12 6,0 (0.24) G¼ 10 (0.4) 48 (1.9) 19 Compression joint with M8 x 1 or G¼ thread dimensions in mm (inches) Coupling socket, dimensions in mm (inches) Selection and Ordering data Screw nipple for soldering jacket thermocouple elements The screw nipple has a centering hole and must be drilled according to the outer diameter of the jacket thermocouple element. The thermocouple must be protected from excessive heat when soldering (e.g. by blowing with air). with M8 x 1 thread, for jacket outer diameter up to.0 mm (0.12 inch); 0.01 kg (0.02 lb) with G¼ thread, for all jacket outer diameters listed in the catalog, 0.02 kg (0.04 lb) Order No. 7MC2922-1EA 7MC2922-1FB Compression joint, gas-tight Temperature up to 50 C (662 F) Pressure-tight up to 80 bar (1160 psi) Subsequent release and movement is not possible, material X6 CrNi Mo Ti , material No ; tapered ring like compression joint Thread M8 x 1; 0.0 kg (0.06 lb) - jacket outer diameter 1.5 mm (0.06 inch) 7MC2922-AA - jacket outer diameter.0 mm (0.12 inch) 7MC2922-BA Thread G¼; 0.04 kg (0.08 lb) - jacket outer diameter 6 mm (0.24 inch) 7MC2922-DB Coupling socket of jacket thermocouple 7MC2028 (one per element); for Ni Cr/Ni thermocouple element, type K; 0.05 kg (0.11 lb) Coupling plug matching the jacket thermocouple 7MC2028 with socket; one plug is required per thermocouple element; for Ni Cr/Ni thermocouple, type K; 0.05 kg (0.11 lb) 7MC2922-4BB 7MC2922-4BD Coupling plug, dimensions in mm (inches) Siemens FI /91

92 Thermocouples Accessories Cold junction with built-in power supply unit Overview The cold junction is suitable for a thermocouple element of type J, K, L, R, S, T or U. A correction circuit is fitted which compensates the influence of changes in the cold junction temperature. The device can be mounted on a rail. Note: positioning of the cold junction in the vicinity of the measuring point saves expensive extension leads. Design The cold junction has a terminal housing made of plastic which is suitable for mounting on a standard rail DIN EN x 7.5. The sensor for the cold junction temperature is positioned directly on the terminals for the extension lead. The device is matched to the type of thermocouple using built-in function plugs and adjusted according to the reference temperature. The built-in power supply unit provides the cold junction with power. Function Mode of operation Power supply Hz, 220 V, 110 V or 24 V AC, - 25%, + % Power consumption Approx. 0.1 VA 0.1 W Residual ripple < 10% Permissible ambient temperature Permissible storage temperature Degree of protection DIN Housing Terminals Weight C ( F) C ( F) IP40 IP20 Selection and Ordering data Approx. 0.1 kg (0.22 lb) 24 V DC, - 25%, + % Order No. Cold junction M with built-in power supply unit, for rail mounting Power supply 220 V AC B V AC B 2 24 V AC B 24 V DC B 4 Connection to thermocouple element Fe-CuNi Type L 1 Fe/Cu Ni Type J 2 Ni Cr/Ni Type K Pt10% Rh/Pt Type S 4 Pt 1% Rh/Pt Type R 5 Cu-CuNi Type U 6 Cu/Cu Ni Type T 7 Ref. temperature 0 C (2 F) C (68 F) 2 0 Caution! Compensation of changes in the cold junction temperature should not be carried out for Pt 0% Rh/Pt 6% Rh thermocouple elements. The extension leads should be routed to a position where a temperature between 10 and +60 C (14 to 140 F) exists. Dimensional drawings Function diagram of cold junction The power supply (1) stabilized in constant-voltage transformer (4) the feeds a bridge containing a precision temperature sensor (5) in one of its branches. The resistance of the temperature sensor changes with the temperature of the terminals, and thus also the diagonal voltage of the bridge. The bridge is designed according to the characteristic of the respective thermocouple element. Technical specifications Signal input Ref. temperature Error limits Temperature error For thermocouple elements acc. to DIN IEC 584 and DIN or 20 C (2 or 68 F) 0.5 K (0.9 F) <0.1 K / 10 K change (0.18 F/18 F) Cold conjunction, dimensions in mm (inches) Schematics Connection diagram of cold junction /92 Siemens FI

93 Thermocouples Accessories - Cold junction thermostat for 6 or 12 measuring points Overview The cold junction thermostat is used to keep the cold junction temperature constant when measuring temperature using thermocouples. Design The cold junction thermostat consists of an aluminium block in which 6 or 12 reference elements are fitted, a controller, a heater and a power supply unit. The aluminium block, controller, heater and power supply unit are arranged in two blocks potted in synthetic resin. In this manner, uniform temperature distribution and protection against external effects are ensured. The cast blocks are fitted to the base plate using metal brackets, thus ensuring high resistance to vibration. The device has a red lamp visible on the outside of the door to permit checking of the temperature in the aluminium block (thermostat). It is also possible to fit a Pt100 resistance thermometer or an electronic monitoring unit with relay output whose NC contact opens if there is a fault. The cold junction thermostat has a sheet-steel housing. Selection and Ordering data Dimensional drawings Order No. Cold junction thermostat 7 M C Ref. temperature 50 C (112 F) 1 60 C (140 F) 2 70 C (158 F) Thermocouple Fe-CuNi Type L A Ni Cr/Ni Type K B Pt 10% Rh/Pt Type S C Cu-CuNi Type U D Number of cold junctions 6 A 12 B Power supply 220 V AC V AC 2 24 V AC 24 V DC, 0 W 4 24 V DC, 17 W 5 Temperature control without 0 with resistance thermometer 1 with electronic monitoring unit 2 Function The temperature of the aluminium block is held constant at a reference temperature of 50, 60 or 70 C (122, 140 or 158 F) by an electronic two-step controller with low hysteresis. With a constant cold junction temperature, the difference between the voltage of the measuring element and that of the reference element is a measure of the temperature at the measuring point. The thermocouples are electrically isolated from one another and from the power supply. Technical specifications Number of measuring points Ref. temperature Error limits 6 or 12 50, 60 or 70 C (122, 140 or 158 F) 0.5 C (0.9 F) Effect of ambient temperature 0.2 C / 10 K (0.6 F/18 F) temperature change Error limits of control Permissible ambient temperature 0.05 C (0.09 F) C ( F) Power supply (depending Warm-up time on version) Hz, 24, 110 or 220 VAC ± 15%, Approx. 0 VA Approx. 10 min 24 V DC, approx. 0 W Approx. 10 min 24 V DC, approx. 17 W Approx. 20 min Degree of protection IP54 to DIN Resistance to vibration Frequency Acceleration Test period Weight Hz 1 g, constant 4 min 0 Hz 10 g 1 min Approx. 9.5 kg (20.9 lb) Cold junction thermostat 7MC29, dimensions in mm (inches) Schematics Cold junction thermostat 7MC29, connection diagram Siemens FI /9

94 Thermocouples Accessories - Cold junction thermostat for 12 or 24 measuring points Overview The cold junction thermostat is used to keep the cold junction temperature constant when measuring temperature using thermocouples. Design The cold junction thermostat consists of an aluminium block in which 12 or 24 reference elements are fitted, a controller, a heater and a power supply unit. The aluminium block, controller, heater and power supply unit are designed as crystal modules. In this manner, uniform temperature distribution and protection against external effects are ensured. A Pt100 resistance thermometer or an electronic monitoring unit with relay output or 24 V DC output are fitted to permit checking of the temperature in the aluminium block (thermostat). The monitoring unit is triggered when the maximum or minimum temperature of the cold junction block is violated or if the power supply fails. A signalling lamp "Operation" is present in the door. The cold junction thermostat has a sheet-steel housing. Selection and Ordering data Dimensional drawings Order No. Cold junction thermostat 7 M C Ref. temperature 50 C (112 F) 1 60 C (140 F) 2 70 C (158 F) Thermocouple Fe-CuNi Type L A Ni Cr/Ni Type K B Pt10% Rh/Pt Type S C Cu-CuNi Type U D Number of cold junctions 12 A 24 B Power supply 220 V AC V AC 2 24 V AC 24 V DC 4 Temperature control with resistance thermometer; electronic monitoring of the temperature in the thermostat - with relay output 1 - without 24 V DC output 2 Function The temperature of the aluminium block is held constant at a reference temperature of 50, 60 or 70 C (122, 140 or 158 F) by an electronic two-step controller with low hysteresis. With a constant cold junction temperature, the difference between the voltage of the measuring element and that of the reference element is a measure of the temperature at the measuring point. The thermocouples are electrically isolated from one another and from the power supply. Technical specifications Number of measuring points 12 or 24 Ref. temperature 50, 60 or 70 C (122, 140 or 158 F) Error limits 0.5 K (0.9 F) Permissible ambient temperature with ref. temperature: 50 C (122 F) 60 or 70 C (2 or 158 F) Effect of ambient temperature Error limits of temperature control Monitoring circuit Upper switching point Lower switching point Signalling relais Switching capacity Power supply Warm-up time C ( F) C ( F) 0.2 K (0.6 F) per 10 K (1.8 F) temperature change 0.05 K (0.09 F) Ref. temperature + 5 K (9 F) Ref. temperature 5 K (-9 F) NC contact opens in case of error Max. 10 VA (max. 240 V AC, max. 0.5 A) Hz, 24, 110 or 220 V AC ± 15%, approx. 0 VA; 24 V DC ± 10%, approx. 0 W Approx. 10 min Degree of protection IP55 to DIN Weight Approx. 1 kg (28.7 lb) Cold junction thermostat 7MC290, dimensions in mm (inches) Schematics Cold junction thermostat 7MC290, connection diagram /94 Siemens FI

95 Resistance thermometers for food, pharmaceuticals and biotechnology Resistance thermometers for installation in pipelines and tanks Overview The resistance thermometer is designed for installation in tanks and pipelines as well as for the measurement of temperature with hygiene requirements. The usual process connections are available. The rugged design means that it is suitable for a wide range of process applications in the food, pharmaceutical and biotechnology industries. The resistance thermometer is also available with a built-in transmitter. A versatile range of head transmitters is available for this application. Design Pt100 measuring resistor Stainless steel measuring insert Replaceable measuring insert Process connections for food/pharmaceuticals/biotechnology Hygiene version, design corresponds to EHEDG recommendations Fast response available with reduced tip Transmitter can be integrated (4 to 20 ma or PROFIBUS PA) The resistance thermometer has a replaceable measuring insert. The measuring insert contains either one or two Pt100 measuring resistors which are connected to the base in the connection head with a two-wire, three-wire or four-wire system. The change in resistance dependent on the measured temperature can be recorded by a transmitter and converted into a standardized signal. Technical specifications Design Connection head Protective tube Measuring insert Accuracy of measuring resistor Integration of transmitter Process connections Surface properties Replaceable measuring insert with connection head and protection fitting Either: Form B standard, screw cover, stainless steel 1.401, IP67 Form B, cover with 2 slotted screws, aluminium, IP54, standard Form B, screw cover, plastic, IP54 (BK) Form B, hinged cover with slotted screws, aluminium, IP65 (BUZ) Form B, hinged cover with quick-release, aluminium, IP65 (BUS) Form B, high hinged cover with slotted screw, aluminium, IP65 (BUZH) Stainless steel /16L 6 or 9 mm (0.24 or 0.5 inch) diam., optionally with tapered tip, see Selection and Ordering data for mounting length U1 Stainless steel, replaceable Pt100 measuring resistor to DIN 4762 Rigid design or as jacket element (mineral-insulated, flexible, increased vibration resistance) Class A according to DIN EN Suitable Pt100 transmitters for head mounting can be fitted in the connection head, see Selection and Ordering data DIN with slotted union nut Clamp connection to DIN 2676 Clamp connection to ISO 2852 Tri-clamp Varivent Neumo BioControl Spherical welding-type sleeve cyl./sph. 0 x 40 mm (1.18 x 1.57 inch) Aseptic connections The gasket is not included in the standard scope of delivery! Further process connections on request. Process connection material: Stainless steel /16L Standard Surface roughness Ra < 1.5 µm (5.9 x 10-5 inch) Hygiene Surface roughness Ra < 0.8 µm (.1 x 10-5 inch) Welded seam < 1.5 µm (5.9 x 10-5 inch) Siemens FI /95

96 Resistance thermometers for food, pharmaceuticals and biotechnology Resistance thermometers for installation in pipelines and tanks Selection and Ordering data Order No. Order code Pt100 resistance thermometer for food, pharmaceuticals and biotechnology Connection head Form B, cast light alloy, screw cover, IP54, cable gland Form B, plastic, screw cover, IP54, cable gland Form BUZ, cast light alloy, screw cover, IP65, cable gland Form BUZH, cast light alloy, high hinged cover, IP 65, cable gland Form B, stainless steel, standard, IP67, cable gland Special version: (add Order code and plain text) Process connection, material /16L Milk pipe union to DIN with slotted union nut and nominal diameter/pressure - DN 25 / PN 40 A A - DN 2 / PN 40 A B - DN 40 / PN 40 A C - DN 50 / PN 25 A D Clamp connection: ISO 2852 DIN 2676 Tri-Clamp Outer diameter D ½ / ¾ 25.0 mm C A DN 25/.7/8 DN 25/2/40 1, 1½ 50.5 mm C B DN 40/51 DN mm C C DN 6.5 2½ 77.5 mm C D DN 88.9 DN mm C E Varivent connection (Tuchenhagen) - D = 50 mm (1.97 inch), K U for Varivent housing DN 25 and DN 1" - D = 68 mm (2.68 inch), K V for Varivent housing DN DN 125 and 1½"... 6" Welding piece L A (sphere diameter 0 x 40 mm (1.2 x 1.6 inch) long) Special version: Z A Type of screwed gland and nominal diameter (add Order code and plain text) Protective tube Ø F1=6 mm (0.24 inch) Ø F1=9 mm (0.5 inch) Ø F1=9 mm (0.5 inch) Ø F1=9 mm (0.5 inch) tapered tip F=5 Ø x 20 mm (0.2 x 0.79 inch) Special version: (add Order code and plain text) 7 M C Measuring insert Ø /.2 mm, 1 (0.12/0.1 inch) miner. insul. Ø 6 mm (0.24 inch) 2 Ø 6 mm (0.24 inch) miner. insul. Ø /.2 mm, (0.12/0.12 inch) miner. insul H 1 Y 4 J 1 Y 9 L 1 Y Selection and Ordering data Order No. Order code Pt100 resistance thermometer for food, pharmaceuticals and biotechnology Neck tube length M 80 mm (.15 inch) mm (5.71 inch) 2 Special version: (add Order code and plain text) 9 N 1 Y Mounting length U1 15 mm (0.59 inch) 5 mm (1.8 inch) 50 mm (1.97 inch) 100 mm (.94 inch) 160 mm (6.0 inch) 250 mm (9.84 inch) 400 mm (15.75 inch) 4 inch 6 inch 9 inch Special version: (add Order code and plain text) Sensor Thin-film technology: measuring range C ( F) 1 x Pt100, class A, three-wire 2 x Pt100, class A, three-wire 1 x Pt100, class A, four-wire Special version: (add Order code and plain text) Further designs Add "-Z" to Order No. and add Order code. Process connection completely electropolished P01 Hygiene version H01 (R a < 0.8 µm (.1 x 10-5 inch)) Certificates - Roughness depth measurement R a C18 certified by factory certificate to EN B - Material certificate to EN C19 Specify special version in plain text TAG plate made of stainless steel specify TAG No. in plain text Test report (at 0, 50 and 100%) specify measuring range in plain text 7 M C Order code Y01 Y15 Y B C D E F G H J K L Z F G H Z P 1 Y Q 1 Y To order a temperature transmitter installed in the connection head, see "Temperature transmitters for installation in the connection head" (page /64). /96 Siemens FI

97 Dimensional drawings Siemens AG 2007 Resistance thermometers for food, pharmaceuticals and biotechnology Resistance thermometers for installation in pipelines and tanks Connection heads Process connections Connection heads and process connections, dimensions in mm (inches) Siemens FI /97

98 Resistance thermometers for food, pharmaceuticals and biotechnology Resistance thermometers for installation in pipelines and tanks Schematics Siemens AG 2007 PT100 two-wire PT100 three-wire PT100 four-wire 2xPT100 two-wire 2xPT100 three-wire red red yellow yellow red red yellow yellow red red black black yellow Connection diagram /98 Siemens FI

99 Overview Siemens AG 2007 Resistance thermometers for food, pharmaceuticals and biotechnology Resistance thermometers with clamp-on system Response time / accuracy Application example Measured medium: Steam T1: Conventional welding-type protective tube form 2 acc. to DIN 4772 (pipe 9 x 1mm (0.5 to 0.04 inch)) T2: Pipe collar for tube OD 25.4 mm (1.0 inch) acc. to BS 4825 with measuring insert (fast response) 10 (266) Temp. C ( F) 100 (212) T1 T2 10 C (266 F) 129,5 C (265.1 F) 40 (104) Result The pipe collar provides almost identical results compared to an inline temperature 0 (2) Time [sec] The temperature sensor with pipe collar is used for temperature monitoring, particularly for sterile applications in the food and pharmaceutical industries. Temperature measurement is possible following simple, fast assembly on any existing pipeline system. It is not necessary to interrupt the pipeline or to carry out welding. Assembly on the pipeline is simply carried out by adapting the two halves of the collar. The device can be optionally supplied with an integral transmitter. Function Features Temperature measurement free of dead space Can be retrofitted onto existing pipelines Matches all common nominal pipe diameters Optimum temperature measurement using metallic pressing system Insulating collar made of temperature-resistant plastic, easy to clean Measuring range -20 to +200 C (-4 to +92 F) Replaceable Pt100 measuring insert; thus no changes in measuring setup Calibration possible Transmitter can be integrated (4 to 20 ma or PROFIBUS PA) Mode of operation The temperature measurement is carried out using a Pt100 measuring element. An integral metallic pressing system guarantees optimum heat transfer between the pipeline and Pt100. The measuring insert is protected by an insulating sleeve made of temperature-resistant plastic. The complete Pt100 unit can be easily dismounted at any time for calibration; it is not necessary to disconnect the cables from the sensor. The temperature sensor with pipe collar is available with all standard DIN connection heads. Results with steam as measured medium Medium T Schematic representation The result for the actual temperature of the medium T depends on several parameters: Heat transfer of temperature sensor/pipe Conductivity of medium Flow velocity Pipe wall thickness Pipe material Ambient temperature Installation and operating instructions Assembly of the two halves of the pipe collar to the pipe is carried out simply and rapidly by connection of the two M6 hexagon screws. Any positioning is possible, but the Pt100 measurement should preferably be made "underneath" the pipeline to achieve an optimum result. Following mounting on the pipeline, the complete Pt100 housing unit can be dismounted on site by loosening a clamping screw. It is not necessary to disconnect the cable during the usual calibration procedures. T2 T1 Siemens FI /99

Temperature Measurement

Temperature Measurement Overview Application transmitters can be used in all industrial sectors. Due to their compact size they can be installed in the connection head type B (DIN 4729) or larger. The following sensors/signal

More information

Temperature Measurement Transmitters for mounting in sensor head

Temperature Measurement Transmitters for mounting in sensor head Siemens AG 015 Overview SITANS TH00 two-wire system, universal, HAT Application SITANS TH00 transmitters can be used in all industrial sectors. Due to their compact size they can be installed in the connection

More information

Temperature Measurement Transmitters for mounting in sensor head

Temperature Measurement Transmitters for mounting in sensor head Siemens AG 015 SITANS TH00 two-wire system, universal Overview Application SITANS TH00 transmitters can be used in all industrial sectors. Due to their compact size they can be installed in the connection

More information

Temperature Measurement

Temperature Measurement Siemens AG 015 / Product overview Transmitters for mounting in sensor head /4 SITRANS TH100 two-wire system (Pt100) /8 SITRANS TH00 two-wire system universal /15 SITRANS TH00 two-wire system universal,

More information

Temperature Measurement

Temperature Measurement Temperature Measurement SITANS T00 Overview Application SITANS T00 transmitters can be used in all industrial sectors. Their compact design enables simple mounting on standard DIN rails on-site in protective

More information

Temperature Measurement

Temperature Measurement Siemens AG 017 / Product overview Transmitters for mounting in sensor head /4 SITRANS TH100 two-wire system (Pt100) /8 SITRANS TH00 two-wire system universal /15 SITRANS TH00 two-wire system universal,

More information

SITRANS T measuring instruments for temperature

SITRANS T measuring instruments for temperature Overview Our field devices for heavy industrial use HART, Universal 4 to 20 ma, universal Field indicator for 4 to 20 ma signals The temperature transmitter SITRANS TF works where others feel uncomfortable.

More information

SITRANS T measuring instruments for temperature

SITRANS T measuring instruments for temperature SITRANS T measuring instruments for temperature /2 Product overview / SITRANS T transmitters for mounting in sensor head / SITRANS TK PA, with PROFIBUS connection /8 SITRANS TH100, two-wire system (Pt100)

More information

Temperature Measurement

Temperature Measurement Siemens AG 00 - Transmitter, two-wire system and - Field indicator for 4 to 0 ma Overview Our field devices for heavy industrial use HART, Universal 4 to 0 ma, universal Field indicator for 4 to 0 ma signals

More information

Temperature Measurement

Temperature Measurement Siemen AG 00 Temperature Meaurement Overview Application Linearized temperature meaurement with reitance thermometer or thermal element Differential, mean-value or redundant temperature meaurement with

More information

itemp HART DIN rail TMT112

itemp HART DIN rail TMT112 Temperature transmitter itemp HART DIN rail TMT112 Universal temperature transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage transmitters, incorporating HART protocol Application

More information

itemp PA TMT184 Technical information

itemp PA TMT184 Technical information Technical information itemp PA TMT184 Temperature head transmitter with PROFIBUS-PA interface. Supply and digital communication using PROFIBUS-PA, for installation in a Form B sensor head. Features and

More information

0 2 1 â Ó. itemp HART TMT182. Technical Information

0 2 1 â Ó. itemp HART TMT182. Technical Information Technical Information itemp HART TMT182 Temperature head transmitter Head transmitter for resistance thermometers (RTD), thermocouples (TC), resistance and voltage transmitters (mv), HART -protocol, for

More information

Temperature transmitter itemp PCP DIN rail TMT 121

Temperature transmitter itemp PCP DIN rail TMT 121 Technical information TI 087R/09/en 510 03671 Temperature transmitter itemp PCP DIN rail TMT 121 Universal temperature transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage

More information

Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting

Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting Electrical Temperature Measurement Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting WIKA Data Sheet TE 12.03

More information

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C 34-TT-03-07 3/06 PRODUCT SPECIFICATION SHEET OVERVIEW The Honeywell STT170 series of programmable temperature

More information

Temperature head transmitter itemp PCP TMT 181

Temperature head transmitter itemp PCP TMT 181 Technical information TI 070R/09/en Mat.-Nr.: 510 01110 Temperature head transmitter itemp PCP TMT 181 Universal head transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage

More information

Temperature Measurement Transmitter for field mounting/field indicator

Temperature Measurement Transmitter for field mounting/field indicator Siemens AG 017 SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 0 ma Overview Our field devices for heavy industrial use HART, Universal 4 to 0 ma, universal Field indicator

More information

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C 6/07 PRODUCT SPECIFICATION SHEET OVERVIEW The Honeywell STT170 series of programmable temperature transmitters

More information

0 2 1 â Ó. itemp HART TMT182. Technical Information

0 2 1 â Ó. itemp HART TMT182. Technical Information Technical Information itemp HART TMT182 Temperature head transmitter Head transmitter for resistance thermometers (RTD), thermocouples (TC), resistance and voltage transmitters (mv), HART -protocol, for

More information

FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex

FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex Data Sheet 10/-8.54 EN Level 0: Information FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex HART programmable, Pt 100 (RTD), thermocouples, electrical isolation Resistance thermometer (2,

More information

PROGRAMMABLE FIELD TEMPERATURE TRANSMITTER

PROGRAMMABLE FIELD TEMPERATURE TRANSMITTER Configuration Code TM01 Series 642 Programmable HART Field Temperature The Series 642 programmable HART field temperature transmitter is a 2-wire unit with analog output. It includes input for RTDs; resistance

More information

C330 / C330X PC-Programmable Universal, 2-wire Transmitter

C330 / C330X PC-Programmable Universal, 2-wire Transmitter C330 / C330X PC-Programmable Universal, 2-wire Transmitter The IPAQ C330 transmitter is a universal, isolated, temperature transmitter with additional voltage and resistance input. Its robust design and

More information

C520 / C520X /C520S / C520XS HART Compatible, Universal, Dual-input 2-wire Transmitters

C520 / C520X /C520S / C520XS HART Compatible, Universal, Dual-input 2-wire Transmitters C520 / C520X /C520S / C520XS HART Compatible, Universal, Dual-input 2-wire Transmitters The 520 transmitters are universal, isolated, dual-input temperature transmitters with additional voltage and resistance

More information

TF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels

TF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels TF 0 / TF 0-Ex Head mounted temperature transmitters, FOUNDATION Fieldbus (H), Pt 00 (RTD), thermocouples, or independent channels 0/-8.5 EN Input Resistance thermometer (,, wire circuit) Thermocouples

More information

Rail mounted Temperature Transmitter TH102/TH102-Ex

Rail mounted Temperature Transmitter TH102/TH102-Ex Data Sheet 10/-8.54 EN Rail mounted Temperature Transmitter TH102/TH102-Ex HART programmable, Pt 100 (RTD), thermocouples, electrical isolation Input Resistance thermometer (2, 3, 4 wire circuit) Thermocouples

More information

Temperature head transmitter itemp TC TMT 188

Temperature head transmitter itemp TC TMT 188 Technical information TI 077R/24/ae No.: 510 06145 Temperature head transmitter itemp TC TMT 188 Universal head transmitter for thermocouples for an economical, high accuracy temperature monitoring. Fixed

More information

Temperature head transmitter itemp PCP TMT 181

Temperature head transmitter itemp PCP TMT 181 Technical information TI 070R/09/en Mat.-Nr.: 510 01110 Temperature head transmitter itemp PCP TMT 181 Universal head transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage

More information

HART field temperature transmitter Models TIF50, TIF52, TIF62

HART field temperature transmitter Models TIF50, TIF52, TIF62 Electrical temperature measurement HART field temperature transmitter Models TIF50, TIF52, TIF62 WIKA data sheet TE 62.01 Applications Plant construction Process engineering General industrial applications

More information

09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i

09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i Temperature Transmitter Series 9182 www.stahl.de > One unit for nearly all temperature sensors indivdually configurable > Intrinsically safe input [Ex ia] IIC > Signal duplication possible > Galvanic isolation

More information

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5.

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5. Ex i Isolators Temperature Transmitter with Output 0/4... 20 ma, without Limit Value Contact Field Circuit Ex i) One unit for nearly all temperature sensors indivdually configurable Intrinsically safe

More information

3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/.

3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/. Ex i Isolators Temperature Transmitter without Output 0/4... 20 ma, with Limit Value Contact Field Circuit Ex i) One unit for nearly all temperature sensors indivdually configurable Intrinsically safe

More information

Head mounted Temperature Transmitter TF02/TF02-Ex

Head mounted Temperature Transmitter TF02/TF02-Ex Data Sheet Head mounted Temperature Transmitter TF0/TF0-Ex FOUNDATION Fieldbus H, Pt 00 (RTD), thermocouples, or independent channels Input Resistance thermometer (-, -, -wire circuit) Thermocouples Resistance

More information

SITRANS F flowmeters SITRANS F M. Transmitter Transmag 2 with sensor 911/E 4/77. Overview

SITRANS F flowmeters SITRANS F M. Transmitter Transmag 2 with sensor 911/E 4/77. Overview Overview Design The complete flowmeter consists of a flow sensor and an associated transmitter from the Transmag 2 for pulsed alternating field. These are available as remote and compact versions ( 911/E

More information

Isolators A3/1.

Isolators A3/1. Temperature Transmitter Series 9182 > One unit for nearly all temperature sensors indivdually configurable > Signal duplication possible > Galvanic isolation between input, output, power supply and configuration

More information

MODEL: B3HU. Space-saving Two-wire Signal Conditioners B3-UNIT

MODEL: B3HU. Space-saving Two-wire Signal Conditioners B3-UNIT Space-saving Two-wire Signal Conditioners B3-UNIT 2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER (HART communication, intrinsically safe) Functions & Features Universal input: mv, V, T/C, RTD, resistance, potentiometer

More information

STT 3000 Smart Temperature Transmitter Series STT170 Specifications

STT 3000 Smart Temperature Transmitter Series STT170 Specifications STT 3000 Smart Temperature Transmitter Series STT170 Specifications Model STT171, STT173, STT17H, STT17F, STT17C 34-TT-03-07 November 2010 Overview STT17H Features The Honeywell STT170 series of programmable

More information

SINEAX V 624 Programmable Temperature Transmitter for RTD and TC inputs

SINEAX V 624 Programmable Temperature Transmitter for RTD and TC inputs SINEAX V 6 for rail mounting in housing P/7 or P/7 St 00 II () GD Application SINEAX V 6 (Figs. and ) is designed for measuring temperature in combination with thermocouples or resistance thermometers.

More information

RMA42. Technical Information

RMA42. Technical Information Technical Information RMA42 Process transmitter with control unit Digital process transmitter for mounting on a top-hat rail for monitoring and visualizing analog measured values Application Plant and

More information

Digital temperature transmitter with HART protocol Model T32.1S, head mounting version Model T32.3S, rail mounting version

Digital temperature transmitter with HART protocol Model T32.1S, head mounting version Model T32.3S, rail mounting version Electrical temperature measurement Digital temperature transmitter with HART protocol Model T32.1S, head mounting version Model T32.3S, rail mounting version WIKA data sheet TE 32.04 Applications Process

More information

SITRANS F flowmeters SITRANS F US. Transmitter FUS060. Overview

SITRANS F flowmeters SITRANS F US. Transmitter FUS060. Overview Overview Function Displays and keypad Operation of the SITRANS FUS060 transmitter can be carried out using: Keypad and display unit HART communicator PC/laptop and SIMATIC PDM software via HART communication

More information

Universal Intelligent 2-wire DIN Rail Transmitters

Universal Intelligent 2-wire DIN Rail Transmitters Universal Intelligent 2-wire DIN Rail Transmitters IPAQ-L is a universal and intelligent 2-wire DIN rail transmitter for temperature and other measurement applications. IPAQ-LX is the Intrinsic Safe version

More information

Temperature Input Module for Zone 1 Series 9482/32

Temperature Input Module for Zone 1 Series 9482/32 www.stahl.de > 8 channels for temperature sensors > Intrinsically safe inputs Ex ia > For Pt-, Ni- and Cu-resistance temperature detectors according to DIN, IEC and GOST in 2-, 3- and 4-wire circuits >

More information

â Ó itemp TC TMT128 Technical information DIN rail mounted Temperature Transmitter for Thermocouples (TC)

â Ó itemp TC TMT128 Technical information DIN rail mounted Temperature Transmitter for Thermocouples (TC) Technical information itemp TC TMT128 DIN rail mounted Temperature Transmitter for Thermocouples (TC) Application Temperature transmitter with fixed measuring ranges for converting TC input signals into

More information

Isolators A3/1.

Isolators A3/1. > Compact limit value switch with 2 configurable limiting values and 4... 20 ma output > Suitable for 2-, 3-wire transmitters, 2-wire HART transmitters and ma sources > Intrinsically safe input [Ex ia]

More information

Assembly. Front view. Parametrization interface. Power Bus

Assembly. Front view. Parametrization interface. Power Bus Temperature Converter Features Assembly 1-channel signal conditioner 24 V DC supply Thermocouple, RTD, potentiometer or mv input Input for PTC thermistor Current and voltage output Line fault (LFD) and

More information

FieldIT Temperature Transmitter, head mounted TH02/TH02-Ex

FieldIT Temperature Transmitter, head mounted TH02/TH02-Ex Data Sheet 0/-8.9 EN Level 0: Information FieldIT Temperature Transmitter, head mounted TH0/TH0-Ex HART programmable, Pt 00 (RTD), thermocouples, electrical isolation Input Resistance thermometer (,, wire

More information

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter)

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter) JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net

More information

Isolators A3/1. Temperature Transmitter Field Circuit Non-Ex i Series

Isolators A3/1. Temperature Transmitter Field Circuit Non-Ex i Series Temperature Transmitter Series 9182 > One unit for nearly all temperature sensors indivdually configurable > Signal duplication possible > Galvanic isolation between input, output, power supply and configuration

More information

Plug-in module SIRAX V 606, 1 or 2 channels Programmable Temp. Transmitter for RTD and TC inputs

Plug-in module SIRAX V 606, 1 or 2 channels Programmable Temp. Transmitter for RTD and TC inputs Plug-in module, or channels Application The programmable transmitter (Fig. ) is designed for measuring temperature in combination with thermocouples or resistance thermometers. Thermocouple non-linearities

More information

Universal Intelligent 2-wire In-head Transmitters

Universal Intelligent 2-wire In-head Transmitters Universal Intelligent 2-wire In-head Transmitters Actual size IPAQ-H is a universal and intelligent 2-wire In-head transmitter for temperature and other measurement applications. IPAQ-HX is the Intrinsic

More information

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter)

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter) JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net

More information

Temperature transmitter with local display RIT 261

Temperature transmitter with local display RIT 261 Technical Information TI 091R/2/ae Temperature transmitter with local display RIT 261 Universal field mounted transmitter provides an exceptional backlit temperature indication with five large digits and

More information

Multifunction Intelligent 4-wire Isolated Signal Conditioner

Multifunction Intelligent 4-wire Isolated Signal Conditioner Multifunction Intelligent 4-wire Isolated Signal Conditioner IPAQ-4L is a fully universal and intelligent 4- wire (mains powered) transmitter for temperature measurement and signal conditioning applications.

More information

Transmitter. Configuration Code TM01 Series 440 Programmable RTD Temperature Transmitter. Application Areas. Features and Benefits

Transmitter. Configuration Code TM01 Series 440 Programmable RTD Temperature Transmitter. Application Areas. Features and Benefits Configuration Code TM01 Series 440 Programmable RTD Temperature Transmitter The Series 440 programmable RTD temperature transmitter is a 2-wire transmitter with an analog output. It has measurement input

More information

FieldIT Temperature Transmitter, field mounted TH202/TH202-Ex

FieldIT Temperature Transmitter, field mounted TH202/TH202-Ex Data Sheet 0/-8.6 EN Level 0: Information FieldIT Temperature Transmitter, field mounted TH0/TH0-Ex HART programmable, Pt 00 (RTD), thermocouples, electrical isolation Input Resistance thermometer (,,

More information

Technical Information RMA42

Technical Information RMA42 TI00150R/09/EN/05.16 71315973 Products Solutions Services Technical Information RMA42 Process transmitter with control unit Digital process transmitter for monitoring and visualizing analog measured values

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F

Isolators A3/1.  Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F Series 9160 Rev. F > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de

More information

Universal Intelligent 2-wire DIN Rail Transmitters

Universal Intelligent 2-wire DIN Rail Transmitters Universal Intelligent 2-wire DIN Rail Transmitters IPAQ-L is a universal and intelligent 2-wire DIN rail transmitter for temperature and other measurement applications. IPAQ-LX is the Intrinsic Safe version

More information

Level Measurement. Continuous level measurement - Radar transmitters SITRANS LR400 5/229. Overview

Level Measurement. Continuous level measurement - Radar transmitters SITRANS LR400 5/229. Overview Overview Application It provides excellent results on low dielectric media. is available for standard applications and for applications that require explosion proof protection. features robust enclosure,

More information

Operating Instructions Edition 04/2007. Temperature Transmitter SITRANS TR200/TR300 7NG3032-*JN00 SITRANS TR200 7NG3033-*JN00 SITRANS TR300.

Operating Instructions Edition 04/2007. Temperature Transmitter SITRANS TR200/TR300 7NG3032-*JN00 SITRANS TR200 7NG3033-*JN00 SITRANS TR300. Operating Instructions Edition 04/2007 Temperature Transmitter 7NG3032-*JN00 SITRANS TR200 7NG3033-*JN00 SITRANS TR300 sitrans Introduction 1 General safety notes 2 SITRANS Temperature transmitter Operating

More information

HART Compatible Intelligent 2-wire In-head Transmitters

HART Compatible Intelligent 2-wire In-head Transmitters HART Compatible Intelligent 2-wire In-head Transmitters Actual size MESO-H is a Smart and universal 2-wire Inhead transmitter for temperature and other measurement applications. MESO-HX is the Intrinsic

More information

Temperature measurement TMD 832 head transmitter

Temperature measurement TMD 832 head transmitter Technical information TI 062R/09/en Mat.-Nr. 510 00782 Temperature measurement TMD 832 head transmitter SMART head transmitter with HART protocol for RTD, Thermocouple and mv input signals Applications

More information

HART Compatible Intelligent 2-wire DIN Rail Transmitters

HART Compatible Intelligent 2-wire DIN Rail Transmitters HART Compatible Intelligent 2-wire DIN Rail Transmitters MESO-L is a Smart and universal 2-wire DIN Rail transmitter for temperature and other measurement applications. MESO-LX is the Intrinsic Safe version

More information

Isolating Repeater Input Series 9163

Isolating Repeater Input Series 9163 > For 4-wire HART transmitters and voltage sources > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2 (IEC 61508) > High accuracy www.stahl.de

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series Transmitter Supply Unit Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > Open-circuit and short-circuit monitoring and messaging for input

More information

SITRANS T measuring instruments for temperature

SITRANS T measuring instruments for temperature Overview SITNS T measuring instruments for temperature SITNS T transmitter for field mounting / field indicator SITNS TF Mode of operation Sensor TC TD SITNS TF 1 nalogtodigital converter 2 Electrical

More information

Level Measurement. Continuous level measurement - Radar transmitters SITRANS LR400 5/229. Overview

Level Measurement. Continuous level measurement - Radar transmitters SITRANS LR400 5/229. Overview Overview Application It provides excellent results on low dielectric media. is available for standard applications and for applications that require explosion proof protection. features robust enclosure,

More information

TTH200 Head-mount temperature transmitter

TTH200 Head-mount temperature transmitter Change from one to two columns Data Sheet DS/TTH200-EN Rev. B TTH200 Head-mount temperature transmitter Temperature transmitter for HART protocol. Suitable for all standard requirements. Measurement made

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160

Isolators A3/1.  Transmitter Supply Unit Field Circuit Ex i Series 9160 Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de

More information

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals Accessories High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals WIKA data sheet AC 80.03 Applications Machine building

More information

P5201 Universal Programmable Transmitters with Galvanic Isolation

P5201 Universal Programmable Transmitters with Galvanic Isolation Transmitters - KB0288-2012/09 P5201 Universal Programmable Transmitters with Galvanic Isolation One type of transmitter for all regular resistance and thermocouple sensors. Linearized output signal 4 to

More information

MODEL: B6U-B B6-UNIT. [2] LCD DISPLAY 0: Without 1: With

MODEL: B6U-B B6-UNIT. [2] LCD DISPLAY 0: Without 1: With Field-mounted Two-wire Signal Conditioners B6-UNIT 8: TIIS flameproof (CE not available) Confirm selectable combinations of approval and wiring conduit types in the table. 2-WIRE UNIVERSAL TEMPERATURE

More information

Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version

Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version Electrical temperature measurement Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version WIKA data sheet TE 15.01 Applications Process industry Machine building

More information

Positioner with HART Communication Type 3780

Positioner with HART Communication Type 3780 Positioner with HART Communication Type 780 Application Single-acting or double-acting positioner for attachment to pneumatic control valves. Supplied with an electric input signal from to 20 ma Travels

More information

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/ > 4 channels for 2-wire HART transmitters and 4 channels for 4-wire HART transmitters > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit

More information

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: 49 661 60030 Fax: 49 661 6003607 Email: mail@jumo.net Internet: www.jumo.net JUMO

More information

Temperature Transmitters - DIN Rail Mounted

Temperature Transmitters - DIN Rail Mounted XTD Features - Non-programmable Models Sensor Types: Models for thermocouple Types J, K, or T Models for RTD Type Pt100 3-wire Select from a variety of pre-configured measuring ranges Internal cold junction

More information

Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version

Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version Temperature Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version WIKA data sheet TE 15.01 for further approvals see page 10 Applications

More information

OPTITEMP TT 20 Technical Datasheet

OPTITEMP TT 20 Technical Datasheet OPTITEMP TT 20 Technical Datasheet Analog PC-programmable two-wire transmitters for Pt100 Efficient PC-configuration without recalibration Very stable output Very fast response time The documentation is

More information

IPAQ C530/R530 Technical Datasheet

IPAQ C530/R530 Technical Datasheet IPAQ C530/R530 Technical Datasheet Smart 2-wire universal transmitter with HART 7 and NFC technology NFC - Configuration of the transmitter via a portable device such as a smartphone. HART 7 protocol High

More information

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted Electrical temperature measurement Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted WIKA data sheet TE 60.34 Applications Machine building, plant and vessel construction

More information

Temperature Transmitter itemp RTD DIN rail TMT 127

Temperature Transmitter itemp RTD DIN rail TMT 127 Technical Information TI 095R/09/en No. 51004790 Temperature Transmitter itemp RTD DIN rail TMT 127 Temperature Transmitter for Pt100 Resistance Thermometer Application Temperature transmitter with fixed

More information

for DC currents or voltages, temperature sensors, remote sensors or potentiometers II (1) G Application Features / Benefits

for DC currents or voltages, temperature sensors, remote sensors or potentiometers II (1) G Application Features / Benefits SINEAX VC 603, Programmable for DC currents or voltages, temperature sensors, remote sensors or potentiometers 0102 II (1) G Application The SINEAX VC 603 (Figs. 1 and 2) converts the input variable a

More information

General Specifications

General Specifications General Specifications YTA70 Temperature Transmitter The YTA70 is the highly accurate temperature transmitter that accepts Thermocouple, RTD, ohms or DC millivolts inputs and converts it to a to 0 ma DC

More information

Isolators A3/1. Ex i Power Supply Field Circuit Ex i Series

Isolators A3/1. Ex i Power Supply Field Circuit Ex i Series > Intrinsically safe output [Ex ib] IIC/IIB > Stable output voltage > Galvanic isolation between output and power supply > Power supply or 85... 230 V AC > Compact design www.stahl.de 07673E00 Basic function:

More information

Level Measurement. Continuous level measurement Radar transmitters SITRANS LR460. 4/258 Siemens FI

Level Measurement. Continuous level measurement Radar transmitters SITRANS LR460. 4/258 Siemens FI Overview The is a -wire, 2 GHz FMCW radar level transmitter with extremely high signal-to-noise ratio and advanced signal processing for continuous monitoring of solids up to 100 m (328 ft). It is ideal

More information

A BB ME ASU R E ME NT & AN AL Y T ICS D AT A S H E ET. TTR200 Rail-mount temperature transmitter

A BB ME ASU R E ME NT & AN AL Y T ICS D AT A S H E ET. TTR200 Rail-mount temperature transmitter A BB ME ASU R E ME NT & AN AL Y T ICS D AT A S H E ET TTR200 Rail-mount temperature transmitter 2 TTR200 RAIL-MOUNT TEMPERATURE TRANSMITTER DS/TTR200-EN REV. D Measurement made easy Temperature transmitter

More information

Temperature Transmitters - Head Mounted

Temperature Transmitters - Head Mounted XTH Features - Non-programmable Models Sensor Types: Models for thermocouple Types J, K, or T Models for RTD Type Pt100 3-wire Select from a variety of pre-configured measuring ranges Internal cold junction

More information

Digital I/O Coupler (4-wire) Series 9413/21

Digital I/O Coupler (4-wire) Series 9413/21 Digital /O Coupler (4wire) > The digital /O coupler is used to connect 8 intrinsically safe contacts or proximity initiators and 4 intrinsically safe solenoid valves to a FOUNDATON TM fieldbus H1. > Galvanic

More information

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: 49 661 60030 Fax: 49 661 6003607 Email: mail@jumo.net Internet: www.jumo.net JUMO

More information

DSCL, DSCP, SCTP. Industrial Loop Isolators and Transmitters DSCL, DSCP, SCTP. Industrial Loop Isolators and Transmitters

DSCL, DSCP, SCTP. Industrial Loop Isolators and Transmitters DSCL, DSCP, SCTP. Industrial Loop Isolators and Transmitters Industrial Loop Isolators and Transmitters DSCL,, SCTP DSCL,, SCTP Industrial Loop Isolators and Transmitters Description Dataforth s DSCL,, and SCTP series of products is a complete family of loop and

More information

Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting

Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting Electrical Temperature Measurement Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting WIKA Data Sheet TE 24.01 Applications T Machinery, plant construction T Process industry

More information

Fieldbus Isolating Repeater Series 9185/11

Fieldbus Isolating Repeater Series 9185/11 www.stahl.de > For operation of the intrinsically safe Profibus DP (RS-485 IS to PNO standard) > Intrinsically safe fieldbus RS-422, RS-485 [Ex ib] IIC > Galvanic isolation between RS-422 / RS-485, RS-232,

More information

Resistance thermometer Model TR30, compact design

Resistance thermometer Model TR30, compact design Electrical temperature measurement Resistance thermometer Model TR30, compact design WIKA data sheet TE 60.30 Applications Machine building, plant and vessel construction Propulsion technology, hydraulics

More information

Temperature transmitter itemp RTD DIN rail TMT 127

Temperature transmitter itemp RTD DIN rail TMT 127 Technical information TI 095R/24/ae Nr. 510 06165 Temperature transmitter itemp RTD DIN rail TMT 127 Pt100 transmitter for an economical, high accuracy temperature monitoring. Fixed range measurement,

More information

Advanced Temperature Transmitter

Advanced Temperature Transmitter No. SS2-ATT082-0100 Advanced Temperature Transmitter ATT082 HART protocol Model Application Temperature transmitter with 2 input channels and HART communication for the conversion of different input signals

More information

MCR-T-UI(/NC) MCR-T-UI-E(/NC)

MCR-T-UI(/NC) MCR-T-UI-E(/NC) MCR-T-UI(/) MCR-T-UI-E(/) Programmable Temperature Transducers for Resistance Thermometers and Thermocouples INTERFACE ata Sheet 00_0_en PHOENIX CONTACT - 0/00 escription A universal temperature measuring

More information

06528E00. ATEX / IECEx NEC 505 NEC 506 NEC 500

06528E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Switching Repeater Series 9170 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > Open-circuit / short-circuit monitoring and messaging (can be switched

More information

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted Electrical temperature measurement OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted WIKA data sheet TE 60.31 further approvals see page 10 Applications Machine building, plant

More information