Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F

Size: px
Start display at page:

Download "Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F"

Transcription

1 Series 9160 Rev. F > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy Series 9160 Rev. F 09745E00 Basic function: analogue input 0/4 ma ma, 1 and 2 channels. Transmitter supply units are used for intrinsically safe operation or 2- and 3-wires transmitters or for connection to intrinsically safe ma sources (4-wires transmitter). 2- and 3-wires transmitters are supplied with power via transmitter supply unit. In 2-wires transmitters the devices transmit HART communication signal bidirectionally. ATEX / IECEx Zone Ex i interface x x x x x x Installation in x x WebCode 9160A Isolators /1

2 Series 9160 Rev. F Selection Table Output version (control) 0/ ma active / source with HART 0/ ma passive / sink with HART Note Channels Input Output A Output B SIL LFD* Order number Art. Nr. Tech. data see page 1 0/ ma 0/ ma 2 no 9160/ s /3 3 yes 9160/ s /11 0/ ma 2 no 9160/ s /3 0/ ma 0/ ma 2 yes 9160/ s /7 High Power 2 0/ ma 0/ ma 0/ ma 2 no 9160/ s /3 1 0/ ma passive 2 no 9160/ s /14 passiv passiv 2 nein 9160/ s /14 2 0/ ma passive passive 2 no 9160/ s /14 The order numbers listed in the table are for devices equipped with screw-type terminals. For devices equipped with spring-type terminals, replace the ending "s" for screw-type terminals with "k" for spring-type terminals. * LFD - line fault diagnosis no - Device transmits line fault on the field side via the ma signal. Without LED / relay contact. yes - Device transmits line fault on the field side via the ma signal. With LED / relay contact. Further variants with line fault diagnosis are available on request. /2 Isolators

3 Series 9160/xx Rev. F Series 9160/xx Rev. F Explosion Protection Design 9160/xx Rev. F Global (IECEx) Gas, dust and mining IECEx BVS X Ex na [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I Europe (ATEX) Gas, dust and mining DMT 03 ATEX E 010 X E II 3 (1) G Ex na [ia Ga] IIC T4 Gc E II (1) D [Ex ia Da] IIIC E I (M1) [Ex ia Ma] I Certifications and certificates Certificates Ship approval Safety data Max. voltage U o Max. current I o Max. power P o Max. connectable capacitance C o IIC IIB / IIIC Max. connectable inductance L o IIC IIB / IIIC Internal capacitance C i Internal inductance L i Insulation voltage U m When connecting a current source Max. output voltage U o Max. connectable voltage U i Max. connectable current I i Internal capacitance C i Internal inductance L i Further parameters Installation Further information Functional safety (IEC 61508) IECEx, ATEX, Brasil (INMETRO), Canada (cfm), Kazakhstan (TR), Russia (TR), Serbia (SRPS), Ukraine (TR), USA (FM), Belarus (TR) DNV 27 V 88 ma 576 mw 90 nf 705 nf 2.3 mh 17 mh 253 V 4.1 V 30 V 100 ma in Zone 2 and in the safe area see respective certificate and operating instructions Test report Exida STAHL 10/02-01 R027 Max. SIL 2 Safe Failure Fraction SFF 85 % PFD AVG at T [Proof] T [Proof] PFD AVG 1 year 2.29 x years 3.38 x 10-4 Further information 5 years 6.64 x 10-4 For further information see safety test report. Isolators /3

4 Series 9160/xx Rev. F Design Electrical data Auxiliary power Nominal voltage U N Voltage range Residual ripple 9160/xx Rev. F 24 V DC V ( 3.6 V SS Nominal current at U N, 20 ma 1 channel 75 ma 2 channels 131 ma Power consumption at U N, 20 ma 1 channel 1.8 W 2 channels 3.1 W Power dissipation at U N, R L = 250 Ω 1 channel 1.4 W 2 channels 2.0 W Polarity reversal protection yes Operation indication LED green "PWR" Undervoltage monitoring yes (no faulty module / output states) Galvanic separation Test voltages acc. to standard EN Ex i input to output 1.5 kv AC Ex i input to auxiliary power 1.5 kv AC Ex i input to 1.5 kv AC error message contact Ex i inputs interconnected 500 V AC acc. to standard EN Output to auxiliary power 350 V AC Outputs interconnected 350 V AC Error message contact to 350 V AC auxiliary power and outputs Ex i input Input signal 0/ ma with HART Functional range ma Max. input current for ma sources 50 ma Supply voltage for transmitter ) 16 V at 20 ma (for 2-, 3-wire) Residual ripple of supply voltage Open-circuit voltage Short-circuit current Input resistance (AC impedance HART) Input resistance for ma sources ( 25 mv eff ( 26 V ( 35 ma» 500 O 30 O Communication signal bi-directional HART transmission, khz (at 2-wire transformer) Output Output signal 0/ ma with HART Load resistance R L O (terminal 1+ / 2- or 5+ / 6-) O (terminal 3+ / 2- or 4+ / 6-) (with internal 221 O resistor for HART) Residual ripple Open-circuit voltage Communication signal Response time ( %) Error detection Ex i input Behaviour of the output 40 μa eff ( 15.5 V bi-directional HART transmission, khz (at 9160/19 only output A) ( 100 μs (at 9160/19 output A: 4 ms) = Input signal /4 Isolators

5 Series 9160/xx Rev. F Design 9160/xx Rev. F Electrical data Error limits Accuracy, typical data expressed as % of calibrated span at U N, 23 C Linearity error ( 0.05 % Offset error ( 0.05 % Temperature effect ( 0.05 % / 10 K Power supply effect within ( 0.01 % voltage range Load resistance influence ( 0.02 % Cross-talk Channel 1 ( 0.01 % Channel 2 ( 0.01 % Electromagnetic compatibility Tested under the following standards and regulations: EN Use in industrial environment; NAMUR NE 21 Ambient conditions Ambient temperature Single device C Group assembly C The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide". Storage temperature C Relative humidity (no condensation) ( 95 % Isolators /5

6 Series 9160/xx Rev. F Electrical connection Connection diagram 1 channel, output: active / source 9160/ Division 1 Zone 0 / 1 Division 2 Zone E02 1 channel, output: active / source 9160/ Division 1 Zone 0 / 1 Division 2 Zone E02 2 channels, outputs: active / source 9160/ Division 1 Zone 0 / 1 Division 2 Zone 2 /6 Isolators

7 Series 9160/xx Rev. F Series 9160/xx Rev. F Explosion Protection Global (IECEx) Gas, dust and mining IECEx BVS X Ex na nc [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I Europe (ATEX) Gas, dust and mining DMT 03 ATEX E 010 X E II 3 (1) G Ex na nc [ia Ga] IIC T4 Gc E II (1) D [Ex ia Da] IIIC E I (M1) [Ex ia Ma] I Certifications and certificates Certificates IECEx, ATEX, Brasil (INMETRO), Canada (cfm), Kazakhstan (TR), Russia (TR), Serbia (SRPS), Ukraine (TR), USA (FM), Belarus (TR) Ship approval DNV Safety data Design 9160/ Rev. F 9160/ Rev. F Max. voltage U o 27 V 27 V Max. current I o 88 ma ma Max. power P o 576 mw 731 mw Max. connectable capacitance C o IIC 90 nf 90 nf IIB / IIIC 705 nf 705 nf Max. connectable inductance L o IIC 2.3 mh 0.31 mh IIB / IIIC 17 mh 9.2 mh Internal capacitance C i Internal inductance L i Insulation voltage U m 253 V 253 V When connecting a current source Max. output voltage U o 4.1 V 4.1 V Max. connectable voltage U i 30 V 30 V Max. connectable current I i 100 ma 100 ma Internal capacitance C i Internal inductance L i Further parameters Installation Further information Functional safety (IEC 61508) in Zone 2, Div. 2 and in the safe area see respective certificate and operating instructions Test report Exida STAHL 10/02-01 R027 Max. SIL 2 Safe Failure Fraction SFF 85 % PFD AVG at T [Proof] T [Proof] PFD AVG 1 year 2.29 x years 3.38 x 10-4 Further information 5 years 6.64 x 10-4 For further information see safety test report. Isolators /7

8 Series 9160/xx Rev. F Electrical data Auxiliary power Design 9160/ Rev. F 9160/ Rev. F Nominal voltage U N 24 V DC 24 V DC Voltage range V V Residual ripple ( 3.6 V SS ( 3.6 V SS Nominal current at U N, 20 ma 1 channel 88 ma 87 ma 2 channels 148 ma Power consumption at U N, 20 ma 1 channel 2.1 W 2.1 W 2 channels 3.6 W Power dissipation at U N, R L = 250 Ω 1 channel 1.4 W 1.4 W 2 channels 2.3 W Polarity reversal protection yes yes Operation indication LED green "PWR" LED green "PWR" Undervoltage monitoring yes (no faulty module / output states) Galvanic separation Test voltages acc. to standard EN Ex i input to output 1.5 kv AC Ex i input to auxiliary power 1.5 kv AC Ex i input to 1.5 kv AC error message contact Ex i inputs interconnected 500 V AC acc. to standard EN Output to auxiliary power 350 V AC Outputs interconnected 350 V AC Error message contact to 350 V AC auxiliary power and outputs Ex i input Design 9160/ Rev. F 9160/ Rev. F Input signal 0/ ma with HART 0/ ma with HART Functional range ma ma Max. input current for ma sources 50 ma 50 ma Supply voltage for transmitter ) 16 V at 20 ma (for 2-, 3-wire) ) 18 V at 20 ma (for 2-, 3-wire) Residual ripple of supply voltage ( 25 mv eff ( 25 mv eff Open-circuit voltage ( 26 V ( 26 V Short-circuit current 35 ma 45 ma Input resistance» 500 O» 500 O (AC impedance HART) Input resistance for ma sources 30 O 30 O Communication signal bi-directional HART transmission, khz (at 2-wire transformer) Output Output signal 0/ ma with HART Load resistance R L O (terminal 1+ / 2- or 5+ / 6-) O (terminal 3+ / 2- or 4+ / 6-) (with internal 221 O resistor for HART) Residual ripple Open-circuit voltage Communication signal Response time ( %) 40 μa eff ( 15.5 V bi-directional HART transmission, khz (at 9160/19 only output A) ( 100 μs (at 9160/19 output A: 4 ms) /8 Isolators

9 Series 9160/xx Rev. F Electrical data Error detection Ex i input Wire breakage Short circuit Behaviour of the output Output current at I E = 0 Fault detection output Open-circuit Fault message Ex i input/output Settings (switch LF) Indication of faulty line Message faulty line and power supply failure < 3.6 ma > 20.5 ma = Input signal I A = 0 ma < 3.6 ma activated / deactivated LED red "LF" per channel - Contact (30 V / 100 ma) closed to ground in case of fault -, floating contact (30 V / 100 ma) Error limits Ausführung 9160/ Rev. F 9160/ Rev. F Accuracy, typical data expressed as % of calibrated span at U N, 23 C Linearity error ( 0.05 % ( 0.05 % Offset error ( 0.05 % ( 0.05 % Temperature effect ( 0.05 % / 10 K ( 0.05 % / 10 K Power supply effect within ( 0.01 % ( 0.01 % voltage range Load resistance influence ( 0.02 % ( 0.02 % Cross-talk Channel 1 ( 0.01 % ( 0.01 % Channel 2 ( 0.01 % Electromagnetic compatibility Tested under the following standards and regulations: EN Use in industrial environment; NAMUR NE 21 Ambient conditions Ambient temperature Single device C Group assembly C The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide". Storage temperature C Relative humidity (no condensation) ( 95 % Isolators /9

10 Series 9160/xx Rev. F Electrical connection Connection diagram 1 channel, output: active / source 9160/ Division 1 Zone 0 / 1 Division 2 Zone E02 1 channel, outputs 9160/ Division 1 Zone 0 / 1 Division 2 Zone E02 2 channels, outputs: active / source 9160/ Division 1 Zone 0 / 1 Division 2 Zone E02 /10 Isolators

11 Series 9160/ Rev. F Series 9160/ Rev. F Explosion Protection Design 9160/ Rev. F Global (IECEx) Gas, dust and mining IECEx BVS X Ex na nc [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I Europe (ATEX) Gas, dust and mining DMT 03 ATEX E 010 X E II 3 (1) G Ex na nc [ia Ga] IIC T4 Gc E II (1) D [Ex ia Da] IIIC E I (M1) [Ex ia Ma] I Certifications and certificates Certificates Ship approval Safety data Max. voltage U o Max. current I o Max. power P o Max. connectable capacitance C o IIC IIB / IIIC Max. connectable inductance L o IIC IIB / IIIC Internal capacitance C i Internal inductance L i Insulation voltage U m When connecting a current source Max. output voltage U o Max. connectable voltage U i Max. connectable current I i Internal capacitance C i Internal inductance L i Further parameters Installation Further information Functional safety (IEC 61508) IECEx, ATEX, Brasil (INMETRO), Canada (cfm), Kazakhstan (TR), Russia (TR), Serbia (SRPS), Ukraine (TR), USA (FM), Belarus (TR) DNV 27 V 88 ma 576 mw 90 nf 705 nf 2.3 mh 17 mh 253 V 4.1 V 30 V 100 ma in Zone 2, Div. 2 and in the safe area see respective certificate and operating instructions Test report Exida STAHL 10/02-01 R027 Max. SIL 3 Safe Failure Fraction SFF 95 % PFD AVG at T [Proof] T [Proof] PFD AVG 1 year 5.96 x years 8.76 x years 1.72 x 10-4 Further information For further information see safety test report. Isolators /11

12 Series 9160/ Rev. F Design Electrical data Auxiliary power Nominal voltage U N Voltage range Residual ripple Nominal current at U N, 20 ma 9160/ Rev. F 24 V DC V ( 3.6 V SS 113 ma Power consumption at U N, 20 ma 2.7 W Power dissipation at U N, 1.8 W R L = 250 Ω Polarity reversal protection yes Operation indication LED green "PWR" Undervoltage monitoring yes (no faulty module / output states) Galvanic separation Test voltages acc. to standard EN Ex i input to output 1.5 kv AC Ex i input to auxiliary power 1.5 kv AC Ex i input to error message 1.5 kv AC contact Ex i inputs interconnected 500 V AC acc. to standard EN Output to auxiliary power 350 V AC Outputs interconnected 350 V AC Error message contact to 350 V AC auxiliary power and outputs Ex i input Input signal 0/ ma with HART Functional range ma Max. input current for ma sources 50 ma Supply voltage for transmitter ) 16 V at 20 ma (for 2-, 3-wire) Residual ripple of supply voltage Open-circuit voltage Short-circuit current Input resistance (AC impedance HART) Input resistance for ma sources ( 25 mv eff ( 26 V 35 ma» 500 O 30 O Communication signal bi-directional HART transmission, khz (at 2-wire transformer) Output Output signal 0/ ma with HART Load resistance R L O (terminal 1+ / 2-) O (terminal 3+ / 2-) (with internal 221 O resistor for HART) Residual ripple Open-circuit voltage Communication signal Response time ( %) Error detection Ex i input Wire breakage Short circuit Behaviour of the output Output current at I E = 0 Fault detection output Open-circuit 40 μa eff ( 15.5 V bi-directional HART transmission, khz ( 100 μs < 3.6 ma > 20.5 ma = Input signal I A = 0 ma < 3.6 ma /12 Isolators

13 Series 9160/ Rev. F Design Electrical data Fault message Ex i input/output Settings (switch LF) Indication of faulty line Message faulty line and power supply failure Error limits 9160/ Rev. F activated / deactivated LED red "LF" per channel - Contact (30 V / 100 ma) closed to ground in case of fault -, floating contact (30 V / 100 ma) Accuracy, typical data expressed as % of calibrated span at U N, 23 C Linearity error ( 0.05 % Offset error ( 0.05 % Temperature effect ( 0.05 % / 10 K Power supply effect within ( 0.01 % voltage range Load resistance influence ( 0.02 % Cross-talk Channel 1 ( 0.01 % Channel 2 ( 0.01 % Electromagnetic compatibility Tested under the following standards and regulations: EN Use in industrial environment; NAMUR NE 21 Ambient conditions Ambient temperature Single device C Group assembly C The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide". Storage temperature C Relative humidity (no condensation) ( 95 % Electrical connection Connection diagram 1 channel, output: active / source 9160/ Division 1 Zone 0 / 1 Division 2 Zone E02 Isolators /13

14 Series 9160/xx Rev. F Series 9160/xx Rev. F Explosion Protection Design 9160/xx Rev. F Global (IECEx) Gas, dust and mining IECEx BVS X Ex na nc [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I Europe (ATEX) Gas, dust and mining DMT 03 ATEX E 010 X E II 3 (1) G Ex na nc [ia Ga] IIC T4 Gc E II (1) D [Ex ia Da] IIIC E I (M1) [Ex ia Ma] I Certifications and certificates Certificates Ship approval Safety data Max. voltage U o Max. current I o Max. power P o IECEx, ATEX, Brasil (INMETRO), Canada (cfm), Kazakhstan (TR), Russia (TR), Serbia (SRPS), Ukraine (TR), USA (FM), Belarus (TR) DNV 27 V 88 ma 576 mw Max. connectable capacitance C o IIC IIB / IIIC 90 nf 705 nf Max. connectable inductance L o IIC IIB / IIIC Internal capacitance C i Internal inductance L i Insulation voltage U m When connecting a current source Max. output voltage U o Max. connectable voltage U i Max. connectable current I i Internal capacitance C i Internal inductance L i Further parameters Installation Further information Functional safety (IEC 61508) 2.3 mh 17 mh 253 V 4.1 V 30 V 100 ma in Zone 2, Div. 2 and in the safe area see respective certificate and operating instructions Test report Exida STAHL 10/02-01 R027 Max. SIL 2 Safe Failure Fraction SFF 85 % PFD AVG at T [Proof] T [Proof] PFD AVG 1 year 2.29 x years 3.38 x years 6.64 x 10-4 Further information For further information see safety test report. /14 Isolators

15 Series 9160/xx Rev. F Design Electrical data Auxiliary power Nominal voltage U N Voltage range Residual ripple 9160/xx Rev. F 24 V DC V ( 3.6 V SS Nominal current at U N, 20 ma 1 channel 57 ma 2 channels 97 ma Power consumption at U N, 20 ma 1 channel 1.4 W 2 channels 2.3 W Power dissipation at U N, R L = 250 Ω 1 channel 0.8 W 2 channels 1.1 W Polarity reversal protection yes Operation indication LED green "PWR" Undervoltage monitoring yes (no faulty module / output states) Galvanic separation Test voltages acc. to standard EN Ex i input to output 1.5 kv AC Ex i input to auxiliary power 1.5 kv AC Ex i input to 1.5 kv AC error message contact Ex i inputs interconnected 500 V AC acc. to standard EN Output to auxiliary power 350 V AC Outputs interconnected 350 V AC Error message contact to 350 V AC auxiliary power and outputs Ex i input Input signal 0/ ma with HART Functional range ma Max. input current for ma sources 50 ma Supply voltage for transmitter ) 16 V at 20 ma (for 2-, 3-wire) Residual ripple of supply voltage Open-circuit voltage Short-circuit current Input resistance (AC impedance HART) Input resistance for ma sources Communication signal ( 25 mv eff ( 26 V 35 ma» 500 O 30 O bi-directional HART transmission, khz (at 2-wire transformer) Isolators /15

16 Series 9160/xx Rev. F Design Electrical data Output Output signal Load resistance R L 9160/xx Rev. F Current sink, max. 30 V with HART R max [Ω] R max R [Ω] R min [Ω] R minr [Ω] U S: Supply voltage R L: Load resistance R max: Max. load resistance terminal 1, 2 & 5, 6 R min: Min. load resistance terminal 1, 2 & 5, 6 R max R: Max. load resistance terminal 1, 3 & 4, 6 R min R: Min. load resistance terminal 1, 3 & 4, 6 Residual ripple Open-circuit voltage Communication signal Response time ( %) Error detection Ex i input Behaviour of the output Output current at I E = 0 R [ Ω ] L U S [ V ] 40 μa eff ( 15.5 V bi-directional HART transmission, khz (at 9160/19 only output A) ( 100 μs (at 9160/19 output A: 4 ms) = Input signal I A = 0 ma Error limits Accuracy, typical data expressed as % of calibrated span at U N, 23 C Linearity error ( 0.05 % Offset error ( 0.05 % Temperature effect ( 0.05 % / 10 K Power supply effect within ( 0.01 % voltage range Load resistance influence ( 0.02 % Cross-talk Channel 1 ( 0.01 % Channel 2 ( 0.01 % Electromagnetic compatibility Tested under the following standards and regulations: EN Use in industrial environment; NAMUR NE 21 Ambient conditions Ambient temperature Single device C Group assembly C The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide". Storage temperature C Relative humidity (no condensation) ( 95 % 15403E00 /16 Isolators

17 Series 9160/xx Rev. F Electrical connection Connection diagram 1 channel, output: passive / sink 9160/ Division 1 Zone 0 / 1 Division 2 Zone 2 1 channel, outputs: passive / sink 9160/ Division1 Zone0 / 1 Division2 Zone E E02 2 channels, outputs: passive / sink 9160/ Division1 Zone0 / 1 Division2 Zone2 Isolators /17

18 Series 9160 Rev. F Series 9160 Rev. F Mechanical data Connection single-wire connection - rigid - flexible - flexible with core end sleeves (without / with plastic sleeve) two-wire connection - rigid - flexible - flexible with core end sleeves screw terminals mm mm mm 2 spring clamp terminal mm mm mm mm mm mm mm 2 Weight approx. 160 g Mounting type on top hat rail (NS35/15, NS35/7.5) or in pac-carrier Mounting orientation horizontal or vertical Enclosure IP30 Terminals IP20 Enclosure material PA 6.6 Fire resistance (UL-94) V0 Dimensional Drawings (All Dimensions in mm [inches]) - Subject to Alterations X 99 [ 3, 90 ] 17,6 [0,69] Screw terminals Spring clamp terminals Dimension X 108 mm [ mm [ ,5 [ 4, 51 ] 122 [ 4, 80 ] 09685E00 We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding. /18 Isolators

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160

Isolators A3/1.  Transmitter Supply Unit Field Circuit Ex i Series 9160 Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de

More information

Isolating Repeater Input Series 9163

Isolating Repeater Input Series 9163 > For 4-wire HART transmitters and voltage sources > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2 (IEC 61508) > High accuracy www.stahl.de

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series Transmitter Supply Unit Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > Open-circuit and short-circuit monitoring and messaging for input

More information

Binary Output Series 9175

Binary Output Series 9175 Binary Output > Intrinsically safe output [Ex ia] IIC / [Ex ib] IIC > Galvanic isolation between input, output and power supply > Open-circuit and short-circuit monitoring (can be switched off) > For use

More information

06528E00. ATEX / IECEx NEC 505 NEC 506 NEC 500

06528E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Switching Repeater Series 9170 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > Open-circuit / short-circuit monitoring and messaging (can be switched

More information

Isolators A3/1. Vibration Transducer Supply Unit Series

Isolators A3/1. Vibration Transducer Supply Unit Series > For vibration, acceleration and speed sensors in 2- and 3-wire design > Space-saving dual-channel version > Signal frequencies up to 50 khz > Easy setting by means of front-side rotary switch > Galvanic

More information

Isolators A3/1.

Isolators A3/1. > Compact limit value switch with 2 configurable limiting values and 4... 20 ma output > Suitable for 2-, 3-wire transmitters, 2-wire HART transmitters and ma sources > Intrinsically safe input [Ex ia]

More information

Binary Output without Power Supply Series 9176

Binary Output without Power Supply Series 9176 Binary Output without Power Supply Series 9176 > For intrinsically safe operation of Ex i solenoid valves, indicators and horns > Power supply by control circuit, loop powered > Intrinsically safe output

More information

09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i

09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i Temperature Transmitter Series 9182 www.stahl.de > One unit for nearly all temperature sensors indivdually configurable > Intrinsically safe input [Ex ia] IIC > Signal duplication possible > Galvanic isolation

More information

Isolators A3/1.

Isolators A3/1. Temperature Transmitter Series 9182 > One unit for nearly all temperature sensors indivdually configurable > Signal duplication possible > Galvanic isolation between input, output, power supply and configuration

More information

Isolators A3/1. Ex i Power Supply Field Circuit Ex i Series

Isolators A3/1. Ex i Power Supply Field Circuit Ex i Series > Intrinsically safe output [Ex ib] IIC/IIB > Stable output voltage > Galvanic isolation between output and power supply > Power supply or 85... 230 V AC > Compact design www.stahl.de 07673E00 Basic function:

More information

Isolators A3/1. Temperature Transmitter Field Circuit Non-Ex i Series

Isolators A3/1. Temperature Transmitter Field Circuit Non-Ex i Series Temperature Transmitter Series 9182 > One unit for nearly all temperature sensors indivdually configurable > Signal duplication possible > Galvanic isolation between input, output, power supply and configuration

More information

3 Ex i Isolators. Switching Repeater with Power Relay (250 V / 4 A) Type 9170/ Type 9170/

3 Ex i Isolators. Switching Repeater with Power Relay (250 V / 4 A) Type 9170/ Type 9170/ 3 Ex i Isolators Switching Repeater with Power Relay Intrinsically safe input [Ex ia] IIC Galvanic isolation between input, output and power supply Open-circuit / short-circuit monitoring and messaging

More information

Analog Universal Module HART for Zone 2 Series 9468/33

Analog Universal Module HART for Zone 2 Series 9468/33 > 8 channels can be adjusted individually as analog inputs or outputs > Intrinsically safe inputs/outputs Ex ia > For 0/4 20 ma + HART signals > Line fault monitoring per channel > Diagnostics based on

More information

Fieldbus Isolating Repeater Series 9185/11

Fieldbus Isolating Repeater Series 9185/11 www.stahl.de > For operation of the intrinsically safe Profibus DP (RS-485 IS to PNO standard) > Intrinsically safe fieldbus RS-422, RS-485 [Ex ib] IIC > Galvanic isolation between RS-422 / RS-485, RS-232,

More information

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5.

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5. Ex i Isolators Temperature Transmitter with Output 0/4... 20 ma, without Limit Value Contact Field Circuit Ex i) One unit for nearly all temperature sensors indivdually configurable Intrinsically safe

More information

3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/.

3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/. Ex i Isolators Temperature Transmitter without Output 0/4... 20 ma, with Limit Value Contact Field Circuit Ex i) One unit for nearly all temperature sensors indivdually configurable Intrinsically safe

More information

Isolators Isolating Repeater Field Circuit Ex i ISpac 9165/ s Art. No

Isolators Isolating Repeater Field Circuit Ex i ISpac 9165/ s Art. No 9165/16-11-10s 207909 Compact one- and two-channel Ex i output isolating repeater wire-breakage and short-circuit monitoring system, which can be disconnected and features a signalling contact can be used

More information

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/ > 4 channels for 2-wire HART transmitters and 4 channels for 4-wire HART transmitters > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit

More information

Digital Input Output Module for Zone 2 Series 9470/33

Digital Input Output Module for Zone 2 Series 9470/33 www.stahl.de > 16 channels can be adjusted in pairs as digital input or output > Intrinsically safe inputs/outputs Ex ia > For contacts, NAMUR proximity switches and low-power solenoid valves > Up to 8

More information

Digital Input Output Module for Zone 2 Series 9470/33

Digital Input Output Module for Zone 2 Series 9470/33 www.stahl.de > 16 can be adjusted in pairs as digital input or output > Intrinsically safe inputs/outputs Ex ia > For contacts, NAMUR proximity switches and low-power solenoid valves > Up to 8 can be used

More information

Digital Input Module NAMUR Ex i / I.S. Inputs, 16 Channels for Zone 1 / Div. 1 Series 9470/22

Digital Input Module NAMUR Ex i / I.S. Inputs, 16 Channels for Zone 1 / Div. 1 Series 9470/22 www.stahl.de > 16 channels for contacts and NAMUR proximity switches (EN 60947-5-6) > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit

More information

Digital Input Output Module for Zone 1 Series 9470/32

Digital Input Output Module for Zone 1 Series 9470/32 www.stahl.de > 16 can be adjusted in pairs as digital input or output > Intrinsically safe inputs/outputs Ex ia > For contacts, NAMUR proximity switches and low-power solenoid valves > Up to 8 can be used

More information

Temperature Input Module for Zone 1 Series 9482/32

Temperature Input Module for Zone 1 Series 9482/32 www.stahl.de > 8 channels for temperature sensors > Intrinsically safe inputs Ex ia > For Pt-, Ni- and Cu-resistance temperature detectors according to DIN, IEC and GOST in 2-, 3- and 4-wire circuits >

More information

Single-Channel Safety Barriers with Electronic Current Limitation Series 9004

Single-Channel Safety Barriers with Electronic Current Limitation Series 9004 Single-Channel Safety Barriers with Electronic Current Limitation > Broad product range for all standard applications in the world of automation > Flexible and space saving > Time saving installation due

More information

Digital Input Output Module 24 V for Ex n Zone 2 Series 9472/35

Digital Input Output Module 24 V for Ex n Zone 2 Series 9472/35 www.stahl.de > 16 channels can be adjusted in pairs as digital inputs or outputs > Suitable for NAMUR proximity switches, 3-wire PNP proximity switches, contacts and solenoid valves (24 V / 0.5 A). > Up

More information

Two-channel safety barriers Series 9002

Two-channel safety barriers Series 9002 Two-channel safety s Series 00 > Wide product range for all standard applications of the automation > Flexible and space-saving available in single and double channel versions > Time-saving installation

More information

Two-channel safety barriers Series 9002

Two-channel safety barriers Series 9002 Two-channel safety s Series 00 > Wide product range for all standard applications of the automation > Flexible and space-saving available in single and double channel versions > Time-saving installation

More information

Digital I/O Coupler (4-wire) Series 9413/21

Digital I/O Coupler (4-wire) Series 9413/21 Digital /O Coupler (4wire) > The digital /O coupler is used to connect 8 intrinsically safe contacts or proximity initiators and 4 intrinsically safe solenoid valves to a FOUNDATON TM fieldbus H1. > Galvanic

More information

Single-Channel Safety Barriers Series 9001

Single-Channel Safety Barriers Series 9001 Single-Channel Safety Barriers Series 9001 > Broad product range for all standard applications in the world of automation > Flexible and space saving single and dual channel versions available > Time saving

More information

Digital Input Module 24 V Ex n Inputs, 16 Channels Series 9471

Digital Input Module 24 V Ex n Inputs, 16 Channels Series 9471 > 16 channels for active 0 / 24 V signals > Zone 2 / Division 2 version for connection of circuits acc. to Ex nl, Ex na, Nonincendive and Non-Ex > Galvanic separation between inputs and system > Two channels

More information

Remote I/O. 74 Remote I/O. Remote I/O System

Remote I/O. 74 Remote I/O. Remote I/O System System Overview of the System Components IS1+ 76 General Information IS1+ 77 CPU & Power Modules CPU & Power Modules for Zone 1 / Div. 1 IS1+ 9440/22 78 Sockets for CPU & Power Module IS1+ 9490 78 CPU

More information

Assembly. Front view. LED yellow: Relay output. LED red: LB/SC

Assembly. Front view. LED yellow: Relay output. LED red: LB/SC Switch Amplifier Features Assembly -channel isolated barrier 30 V AC supply Dry contact or NAMUR inputs Relay contact output Line fault detection (LFD) Reversible mode of operation Up to SIL acc. to IEC

More information

Inductive sensor slot-type SI2-K08-AP7

Inductive sensor slot-type SI2-K08-AP7 SI2-K08-AP7 Slot sensor, height 8 mm Plastic, polypropylene Mechanical end stop, removable, for analog pointer instruments 3-wire DC, 10 30 VDC NO contact, PNP output Cable connection Wiring diagram Type

More information

Assembly. Front view. HiC2441. SL2 1b. Termination Board

Assembly. Front view. HiC2441. SL2 1b. Termination Board SMART Universal Barrier HiC Features Assembly channel isolated barrier V DC supply (bus powered) Analog input, digital input, analog output, digital output No configuration required, device is selfadapting

More information

Technical Information Barrier RB223

Technical Information Barrier RB223 TI00132R/09/EN/13.14 71275790 Products Solutions Services Technical Information Barrier RB223 One or two-channel barrier Loop-powered barrier for the safe separation of 4 to 20 ma standard signal circuits

More information

2 Safety Barriers. Single-Channel Safety Barriers with Electronic Current Limitation Series 9004

2 Safety Barriers. Single-Channel Safety Barriers with Electronic Current Limitation Series 9004 2 Safety Barriers Single-Channel Safety Barriers with Electronic Current Limitation Series 9004 Broad product range for all standard applications in the world of automation Flexible and space saving Time

More information

Engineering Guideline. pac-carriers Type for Yokogawa Centum VP

Engineering Guideline. pac-carriers Type for Yokogawa Centum VP Engineering Guideline pac-carriers Type 9195 for Yokogawa Centum VP pac-carrier Type 9195 2 Engineering Guideline / Yokogawa Centum VP 26.0.2018 pac-carrier Type 9195 Integrated solutions for Yokogawa

More information

MACX MCR-EX-SL-RPSSI-I

MACX MCR-EX-SL-RPSSI-I Extract from the online catalog MACX MCR-EX-SL-RPSSI-I Order No.: 2865340 Ex-i repeater power supply and input isolation amplifier, HART. Sends fed or active 0/4-20 ma signals from the Ex area to a load

More information

MACX MCR-EX-SL-RPSSI-I-UP(-SP)

MACX MCR-EX-SL-RPSSI-I-UP(-SP) Supply and input signal conditioner, Ex-i, with wide range supply Data sheet 103561_en_00 PHOENIX CONTACT 2014-08-19 1 Description The MACX MCR-EX-SL-RPSSI-I-UP(-SP) repeater power supply and input signal

More information

SINEAX TI 807 Passive DC signal isolator. SINEAX TI 807 Passive DC signal isolator

SINEAX TI 807 Passive DC signal isolator. SINEAX TI 807 Passive DC signal isolator SINEAX TI 807 without power supply, Ex- and non-ex version, in housing N17 or S17 for rail and wall mounting 0102 II (1) G resp. II (2) G Application The signal isolator SINEAX TI 807 serves to electrically

More information

ISOLATING SWITCHING AMPLIFIERS POWER SUPPLIES

ISOLATING SWITCHING AMPLIFIERS POWER SUPPLIES ISOLATING SWITCHING AMPLIFIERS POWER SUPPLIES RoHS Compliant Registration No.: 1327-01 For all transactions, the newest version of the General Conditions of Sale and Delivery for Products and Services

More information

SINEAX TI 807 Passive DC signal isolator

SINEAX TI 807 Passive DC signal isolator without power supply, Ex- and non-ex version, in housing N17 or S17 for rail and wall mounting 0102 II (1) G resp. II (2) G Application The signal isolator SINEAX TI 807 serves to electrically insulate

More information

Assembly. Front view. Switch Power Rail

Assembly. Front view. Switch Power Rail Switch Amplifier Features Assembly 1-channel isolated barrier 24 V DC supply (Power Rail) Dry contact or NAMUR input 2 passive transistor outputs (resistive acc. to EN 60947-5-6) Line fault transparency

More information

Temperature transmitter itemp PCP DIN rail TMT 121

Temperature transmitter itemp PCP DIN rail TMT 121 Technical information TI 087R/09/en 510 03671 Temperature transmitter itemp PCP DIN rail TMT 121 Universal temperature transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage

More information

itemp HART DIN rail TMT112

itemp HART DIN rail TMT112 Temperature transmitter itemp HART DIN rail TMT112 Universal temperature transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage transmitters, incorporating HART protocol Application

More information

Data Sheet KFD2-UFC-EX1.D. Supplied by. .com. Call us on +44 (0)

Data Sheet KFD2-UFC-EX1.D. Supplied by. .com. Call us on +44 (0) Data Sheet KFD-UFC-EX1.D Supplied by.com Call us on +44 (0)118 916 940 Email info@47able.com Frequency Converter with Trip Values Features Assembly 1-channel isolated barrier 4 V DC supply (Power Rail)

More information

Temperature Transmitter itemp RTD DIN rail TMT 127

Temperature Transmitter itemp RTD DIN rail TMT 127 Technical Information TI 095R/09/en No. 51004790 Temperature Transmitter itemp RTD DIN rail TMT 127 Temperature Transmitter for Pt100 Resistance Thermometer Application Temperature transmitter with fixed

More information

Assembly. Front view. LED yellow: Relay output I. LED red: LB/SC channel I. LED yellow: Relay output II. LED red: LB/SC channel II

Assembly. Front view. LED yellow: Relay output I. LED red: LB/SC channel I. LED yellow: Relay output II. LED red: LB/SC channel II Switch Amplifier Features Assembly -channel isolated barrier 30 V AC supply Dry contact or NAMUR inputs Relay contact output Line fault detection (LFD) Reversible mode of operation Up to SL acc. to EC

More information

Assembly. Front view. Parametrization interface. Power Bus

Assembly. Front view. Parametrization interface. Power Bus Temperature Converter Features Assembly 1-channel signal conditioner 24 V DC supply Thermocouple, RTD, potentiometer or mv input Input for PTC thermistor Current and voltage output Line fault (LFD) and

More information

Assembly. Front view. Switch Power Rail

Assembly. Front view. Switch Power Rail Switch Amplifier Features Assembly 1-channel isolated barrier 24 V DC supply (Power Rail) Dry contact or NAMUR input 2 passive transistor outputs (resistive) Application-specific outputs Line fault transparency

More information

0 2 1 â Ó. itemp HART TMT182. Technical Information

0 2 1 â Ó. itemp HART TMT182. Technical Information Technical Information itemp HART TMT182 Temperature head transmitter Head transmitter for resistance thermometers (RTD), thermocouples (TC), resistance and voltage transmitters (mv), HART -protocol, for

More information

0 2 1 â Ó. itemp HART TMT182. Technical Information

0 2 1 â Ó. itemp HART TMT182. Technical Information Technical Information itemp HART TMT182 Temperature head transmitter Head transmitter for resistance thermometers (RTD), thermocouples (TC), resistance and voltage transmitters (mv), HART -protocol, for

More information

Signal conditioner - MACX MCR-UI-UI-NC

Signal conditioner - MACX MCR-UI-UI-NC Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid

More information

Assembly. Front view. LED yellow: Relay output I. LED red: LB/SC channel I. LED yellow: Relay output II. LED red: LB/SC channel II

Assembly. Front view. LED yellow: Relay output I. LED red: LB/SC channel I. LED yellow: Relay output II. LED red: LB/SC channel II Switch Amplifier Features Assembly -channel isolated barrier 5 V AC supply Dry contact or NAMUR inputs Relay contact output Line fault detection (LFD) Reversible mode of operation Up to SL acc. to EC 6508/EC

More information

Temperature transmitter itemp RTD DIN rail TMT 127

Temperature transmitter itemp RTD DIN rail TMT 127 Technical information TI 095R/24/ae Nr. 510 06165 Temperature transmitter itemp RTD DIN rail TMT 127 Pt100 transmitter for an economical, high accuracy temperature monitoring. Fixed range measurement,

More information

Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version

Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version Temperature Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version WIKA data sheet TE 15.01 for further approvals see page 10 Applications

More information

TR 104, TR 104-Ex Rail mounted Temperature Transmitters

TR 104, TR 104-Ex Rail mounted Temperature Transmitters Data Sheet 10/-8.48-EN Rev. A TR 104, TR 104-Ex Rail mounted Temperature Transmitters Analog, Pt 100 (RTD), fixed measuring ranges Input Resistance thermometer (two-wire and three-wire circuit) Optionally

More information

â itemp Pt100 TMT127 Technical information Pt100 transmitter for DIN rail mounting for high accuracy temperature monitoring

â itemp Pt100 TMT127 Technical information Pt100 transmitter for DIN rail mounting for high accuracy temperature monitoring Technical information itemp Pt100 TMT127 Pt100 transmitter for DIN rail mounting for high accuracy temperature monitoring Application Temperature transmitter with fixed measuring range for converting a

More information

Temperature Measurement

Temperature Measurement Overview Application transmitters can be used in all industrial sectors. Due to their compact size they can be installed in the connection head type B (DIN 4729) or larger. The following sensors/signal

More information

D1072. SIL 2 Temperature Signal Converter, Duplicator, Adder/Subtractor DIN-Rail Models D1072S, D1072D. Front Panel and Features:

D1072. SIL 2 Temperature Signal Converter, Duplicator, Adder/Subtractor DIN-Rail Models D1072S, D1072D. Front Panel and Features: Characteristics: Front Panel and Features: Ordering Information: Model: D7 D7 General Description: The single and dual channel DIN Rail Temperature Signal Converter D7S and D7D accepts a low level dc signal

More information

Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting

Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting Electrical Temperature Measurement Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting WIKA Data Sheet TE 12.03

More information

Safety Instructions Nivotester FTC625, FTC325

Safety Instructions Nivotester FTC625, FTC325 XA01351F-A/00/EN/01.14 71273077 Products Solutions Services Safety Instructions FTC625, FTC325 [Ex ia Ga] IIC/IIB TÜV 13.0903 X Segurança TÜV INMETRO OCP 0004 Document: XA01351F-A Safety instructions for

More information

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted Electrical temperature measurement OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted WIKA data sheet TE 60.31 further approvals see page 10 Applications Machine building, plant

More information

A BB ME ASU R E ME NT & AN AL Y T ICS D AT A S H E ET. TTR200 Rail-mount temperature transmitter

A BB ME ASU R E ME NT & AN AL Y T ICS D AT A S H E ET. TTR200 Rail-mount temperature transmitter A BB ME ASU R E ME NT & AN AL Y T ICS D AT A S H E ET TTR200 Rail-mount temperature transmitter 2 TTR200 RAIL-MOUNT TEMPERATURE TRANSMITTER DS/TTR200-EN REV. D Measurement made easy Temperature transmitter

More information

Rail mounted Temperature Transmitter TH102/TH102-Ex

Rail mounted Temperature Transmitter TH102/TH102-Ex Data Sheet 10/-8.54 EN Rail mounted Temperature Transmitter TH102/TH102-Ex HART programmable, Pt 100 (RTD), thermocouples, electrical isolation Input Resistance thermometer (2, 3, 4 wire circuit) Thermocouples

More information

SINEAX B 811 Power Pack with additional Functions

SINEAX B 811 Power Pack with additional Functions SINEA B 8 for intelligent and conventional s, in housing S7 for rail and wall mounting 002 II () G Application The power supply unit SINEA B 8 (Figure ) provides the DC power supply for s and transfers

More information

Technical Data. General specifications. Rated operating distance s n 3 mm

Technical Data. General specifications. Rated operating distance s n 3 mm 0102 Model Number Features Direct mounting on standard actuators Compact and stable housing with terminal compartment connection Fixed setting EC-Type Examination Certificate TÜV99 ATEX 1479X Usable up

More information

Temperature Measurement Transmitters for mounting in sensor head

Temperature Measurement Transmitters for mounting in sensor head Siemens AG 015 Overview SITANS TH00 two-wire system, universal, HAT Application SITANS TH00 transmitters can be used in all industrial sectors. Due to their compact size they can be installed in the connection

More information

Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version

Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version Electrical temperature measurement Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version WIKA data sheet TE 15.01 Applications Process industry Machine building

More information

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted Temperature OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted WIKA data sheet TE 60.31 further approvals see page 11 Applications Machine building, plant and vessel construction

More information

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted Electrical temperature measurement Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted WIKA data sheet TE 60.34 Applications Machine building, plant and vessel construction

More information

Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting

Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting Electrical Temperature Measurement Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting WIKA Data Sheet TE 24.01 Applications T Machinery, plant construction T Process industry

More information

Specifications. Specifications. Transfer Characteristics Accuracy at 20 C (68 F) Temperature Drift

Specifications. Specifications. Transfer Characteristics Accuracy at 20 C (68 F) Temperature Drift Appendix A Specifications 1797-IE8 and -IE8NF Input Modules Specifications Number of Inputs IS Input Type IS Module Type Resolution Transfer Characteristics Accuracy at 20 C (68 F) Temperature Drift Functional

More information

Resistance thermometer Model TR30, compact design

Resistance thermometer Model TR30, compact design Electrical temperature measurement Resistance thermometer Model TR30, compact design WIKA data sheet TE 60.30 Applications Machine building, plant and vessel construction Propulsion technology, hydraulics

More information

Head mounted Temperature Transmitter TF02/TF02-Ex

Head mounted Temperature Transmitter TF02/TF02-Ex Data Sheet Head mounted Temperature Transmitter TF0/TF0-Ex FOUNDATION Fieldbus H, Pt 00 (RTD), thermocouples, or independent channels Input Resistance thermometer (-, -, -wire circuit) Thermocouples Resistance

More information

TTH200 Head-mount temperature transmitter

TTH200 Head-mount temperature transmitter Change from one to two columns Data Sheet DS/TTH200-EN Rev. B TTH200 Head-mount temperature transmitter Temperature transmitter for HART protocol. Suitable for all standard requirements. Measurement made

More information

FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex

FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex Data Sheet 10/-8.54 EN Level 0: Information FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex HART programmable, Pt 100 (RTD), thermocouples, electrical isolation Resistance thermometer (2,

More information

TF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels

TF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels TF 0 / TF 0-Ex Head mounted temperature transmitters, FOUNDATION Fieldbus (H), Pt 00 (RTD), thermocouples, or independent channels 0/-8.5 EN Input Resistance thermometer (,, wire circuit) Thermocouples

More information

Assembly. Front view. Power Rail

Assembly. Front view. Power Rail Thermometer Resistance Repeater Features Assembly 1-channel isolated barrier 24 V DC supply (Power Rail) RTD/resistance input Resistance output Accuracy 0.1 % Front view Removable terminals blue Function

More information

PRetrans Table of contents

PRetrans Table of contents HART TRANSPARENT REPEATER PRetrans 5106 Table of contents Warnings 16 Safety instructions 17 EC Declaration of Conformity 19 How to demount SYSTEM 5000 20 Application 21 Technical characteristics 21 Mounting

More information

â Ó itemp TC TMT128 Technical information DIN rail mounted Temperature Transmitter for Thermocouples (TC)

â Ó itemp TC TMT128 Technical information DIN rail mounted Temperature Transmitter for Thermocouples (TC) Technical information itemp TC TMT128 DIN rail mounted Temperature Transmitter for Thermocouples (TC) Application Temperature transmitter with fixed measuring ranges for converting TC input signals into

More information

MACX MCR-EX-T-UI-UP. Extract from the online catalog. Order No.:

MACX MCR-EX-T-UI-UP. Extract from the online catalog. Order No.: Extract from the online catalog MACX MCR-EX-T-UI-UP Order No.: 2865654 Freely programmable Ex-i temperature transducer with analog output and 1 limit value relay, standard configuration, resistance thermometer

More information

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 20 ms. 60 ms. 60 ms. Approx. 1.3 kg. Approx. 0.9 kg. Approx. 5.

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 20 ms. 60 ms. 60 ms. Approx. 1.3 kg. Approx. 0.9 kg. Approx. 5. General data Mounting On linear actuators On quarter turn actuators ARCA-integrated or to VDI/VDE 3847-1 or IEC 534-6 (NAMUR) Range of stroke: 3... 130 mm Integrated to VDI/VDE 3847-2 or VDI/VDE 3845 Angle

More information

MACX MCR-UI-UI-UP(-SP)(-NC)

MACX MCR-UI-UI-UP(-SP)(-NC) Configurable 3-way isolating amplifier with safe isolation and wide-range power supply Data sheet 04247_en_02 PHOENIX CONTACT 203-04-0 Description MACX MCR-UI-UI 3-way isolating amplifiers are used to

More information

INSTRUCTION MANUAL. SIL 3 - SIL 2 Digital Output Loop/Bus Powered DIN-Rail Models D1040Q, D1041Q, D1042Q, D1043Q, D1040Q - D1041Q - D1042Q - D1043Q

INSTRUCTION MANUAL. SIL 3 - SIL 2 Digital Output Loop/Bus Powered DIN-Rail Models D1040Q, D1041Q, D1042Q, D1043Q, D1040Q - D1041Q - D1042Q - D1043Q DQ DQ DQ D3Q INSTRUCTION MANUAL SIL 3 SIL Digital Output Loop/Bus Powered DINRail Models DQ, DQ, DQ, D3Q, D* SIL 3 SIL Digital Output Loop / Bus Powered ISM SIL Applications For Safety Related System and

More information

Temperature Measurement

Temperature Measurement Temperature Measurement SITANS T00 Overview Application SITANS T00 transmitters can be used in all industrial sectors. Their compact design enables simple mounting on standard DIN rails on-site in protective

More information

INSTRUCTION MANUAL. SIL 3 - SIL 2 Digital Output Loop/Bus Powered DIN-Rail Models D1040Q, D1041Q, D1042Q, D1043Q, D1040Q - D1041Q - D1042Q - D1043Q

INSTRUCTION MANUAL. SIL 3 - SIL 2 Digital Output Loop/Bus Powered DIN-Rail Models D1040Q, D1041Q, D1042Q, D1043Q, D1040Q - D1041Q - D1042Q - D1043Q DQ DQ DQ D3Q INSTRUCTION MANUAL SIL 3 SIL Digital Output Loop/Bus Powered DINRail Models DQ, DQ, DQ, D3Q, D* SIL 3 SIL Digital Output Loop / Bus Powered ISM SIL Applications For Safety Related System and

More information

DMP 343. Industrial Pressure Transmitter. Without Media Isolation. appmeas.co.uk +44 (0)

DMP 343. Industrial Pressure Transmitter. Without Media Isolation. appmeas.co.uk +44 (0) DMP 4 Industrial Pressure Transmitter Without Media Isolation accuracy according to IEC 60770: 0.5 % FSO Nominal pressure from 0... 0 mbar up to 0... 000 mbar Product characteristics excellent linearity

More information

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1.

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1. General data Mounting On linear actuators On quarter turn actuators ARCA-integrated or to VDI/VDE 3847-1 or IEC 534-6 (NAMUR) Range of stroke: 3... 130 mm Integrated to VDI/VDE 3847-2 or VDI/VDE 3845 Angle

More information

Temperature Measurement Transmitters for mounting in sensor head

Temperature Measurement Transmitters for mounting in sensor head Siemens AG 015 SITANS TH00 two-wire system, universal Overview Application SITANS TH00 transmitters can be used in all industrial sectors. Due to their compact size they can be installed in the connection

More information

Design and applications

Design and applications Design and applications The measuring device operates largely independent of viscosity and is suitable for indicating the flow rate of water, acids, alkaline solutions and gases. Every device is calibrated

More information

KSR-Level sensor KSR-Schwimmer-Magnetschalter KSR Contact Protection Relays

KSR-Level sensor KSR-Schwimmer-Magnetschalter KSR Contact Protection Relays KSR-Level sensor KSR-Schwimmer-Magnetschalter 1001-5 KSR Contact Protection s 1 KSR Contact Protection Type KR230-Ex and KR24-Ex General Description The contact protection relays KR230-Ex and KR24-Ex transmit

More information

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter)

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter) JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net

More information

Temperature head transmitter itemp TC TMT 188

Temperature head transmitter itemp TC TMT 188 Technical information TI 077R/24/ae No.: 510 06145 Temperature head transmitter itemp TC TMT 188 Universal head transmitter for thermocouples for an economical, high accuracy temperature monitoring. Fixed

More information

SINEAX / EURAX 2I1 Passive DC signal isolator

SINEAX / EURAX 2I1 Passive DC signal isolator SINEAX / EURAX I without power supply 0 II () G resp. II () G Application The DC signal isolator SINEAX/EURAX I (Figs. and ) serve to isolate load-independent DC current signals. It suppressed noise voltages

More information

INSTRUCTION MANUAL. SIL 3 Switch/Proximity Detector Interface DIN-Rail Models D1034S, D1034D D1034S - D1034D

INSTRUCTION MANUAL. SIL 3 Switch/Proximity Detector Interface DIN-Rail Models D1034S, D1034D D1034S - D1034D D034S D034D INSTRUCTION MANUAL SIL 3 Switch/Proximity Detector Interface DINRail Models D034S, D034D D034 SIL 3 Switch / Proximity Detector Interface ISM0053 SIL Applications For Safety Related System

More information

Connection. Input EEx ia IIC. Sense. Fine tuning adjustment. Fine tuning amplifying. Amplifying. Adjustment. Output. Composition

Connection. Input EEx ia IIC. Sense. Fine tuning adjustment. Fine tuning amplifying. Amplifying. Adjustment. Output. Composition Converter Connection 1-channel EEx ia IIC for 4-wire and 6-wire bridges Analogue output 0/4 ma... 20 ma or 4mA...-12mA Full bridge load cells and strain gauges circuit for resistance bridges up to 17 Ω

More information

Field indicator for current loops with HART communication Models DIH50, DIH52

Field indicator for current loops with HART communication Models DIH50, DIH52 Accessories Field indicator for current loops with HART communication Models DIH50, DIH52 WIKA data sheet AC 80.10 for further approvals see page 7 Applications Process engineering Plant construction General

More information

Remote Switching Unit nivotester FTL 320

Remote Switching Unit nivotester FTL 320 Technical Information TI 203F/24/ae Remote Switching Unit nivotester For connection to intrinsically safe Liquiphant level limit switches Applications Limit detection of fluids and bulk solids in tanks

More information