New Techniques for the Monitoring of Transformer Condition
|
|
- Brianne Hawkins
- 5 years ago
- Views:
Transcription
1 New Techniques for the Monitoring of Transformer Condition Thomas Prevost OMICRON electronics USA IEEE T&D Conference Chicago, Illinois April 17, 2014
2 Agenda Monitoring Expectations & Needs Bushing Monitoring Capacitance Power Factor Transformer Monitoring Partial Discharge Voltage Transients Summary & Conclusions
3 Failure Rate Scope of Monitoring Expectations and Needs Classical 5a Diagnostics Temporary Monitoring Permanent Monitoring 3a time / a Continuous Diagnostics Condition based maintenance Full utilization of life span
4 Scope of Monitoring Expectations and Needs Arguments and user expectations > Continuous monitoring under service conditions Reliable measurement data > Diagnostic of errors before they appear Condition based maintenance > Knowledge about historical use Fully utilize life span of equipment
5 Transformer Failure Statistics [Viereck, Hillinger, Transform 2011]
6 Agenda Monitoring Expectations & Needs Bushing Monitoring Capacitance Power Factor Transformer Monitoring Partial Discharge Voltage Transients Summary & Conclusions
7 According to the data from various researches and electric power utilities, bushings failures make 5 to 50 %, or in average, one quarter of the total number of transformer failures.these failures most commonly cause transformer fires which may result in huge collateral damages of switchyard. Reference [3] indicates that 30 % of generator step-up transformer failures are caused by a bushing malfunction, and that they also cause 56 % of failures accompanied by fire.
8 Failure Mechanisms and Diagnostics Partial breakdowns Capacitance Partial discharges Voltage [kv] No. of layers % change E max = high A without layers E max = low with layers A
9 Dissipation Factor (%) Power Factor (%) Failure Mechanisms and Diagnostics Voids, cracks Partial discharges Capacitance Ageing by-products, moisture Dissipation factor / power factor 1,0 0,8 IEC60137 max: 0,7 % 1,0 0,8 IEEE C max: 0,85 0,6 0,4 0,2 0,0 typ: 0,25 OIP typ: 0,35 RIP 0,6 0,4 0,2 0,0 max: 0,5 typ: 0,25 OIP typ: 0,35 RIP
10 Where Can I Get the Reference from? Off-line test: Reference from HQ capacitor Im C R C X, I R I X I R I X u 0 (t) d U R (t) Z 1 Z 2 U X (t) j Uo Reference Measurement path On-line test: Reference?
11 Relative C/DF Measurement > Sum of the bushing currents > Three phase vectors are added up > Bushing-to-bushing comparison > Vectors of bushings in same phase are compared L1 L3 L2
12 DF (%) from to Systematic error 0.65 % plus instrument inaccuracy 0.5 % Capacitance? DF impossible! 1,0 0,8 Systematic error 0,6 0,4 0,2 0,0 typ: 0,25 OIP typ: 0,35 RIP [P. Picher Integration of New Transformer Monitoring Technologies... TechCon Asia-Pazific 2011] PAGE 12
13 Connection Diagram VT Reference U VT + 90 d I B j VT Bushing Data Storage and Analysis Unit
14 TanDelta Measurement Phase U Comparison to accurate off-line tests: DF E-3 C (pf) 467.1
15 Capacitance (pf) DF (%) C/DF Measurement over 1.75 Years 1,0 0,8 0.7 % IEC Warning 0,6 0,4 0,2 0,0 typ: 0,25 OIP RIP 0,27 +/- 0,05 % Measurement pf Warning 467 +/- 2 pf Measurement 400
16 DF Temperature Correction [ABB Guide for Bushing diagnostics and conditioning, Ludvika 2000]
17 Agenda Monitoring Expectations & Needs Bushing Monitoring Capacitance Power Factor Transformer Monitoring Partial Discharge Voltage Transients Summary & Conclusions
18 Reasons and Effects of Partial Discharges Reasons Failures of design or during manufacturing process Aging of equipment Electrical stress Thermal stress Mechanical stress Effects of PDs: Heating Creeping destruction of the insulation material Treeing, chain reaction Insulation breakdown, short circuit Treeing in polyethylene
19 Q in nc PD Activity over 4 Days 10 1 L1 L2 L :00:00 01:00:00 02:00:00 03:00:00 04:00:00 05:00:00 t in dd:hh:min
20 Fighting PD Noise: UHF Gating Corona Electr. PD Internal PD UHF PD EM Field
21 Combination of the Methods IEC UHF IEC PD Measurement & UHF PD Measurement Corrected IEC PD Measurement
22 3PARD: PD Discrimination by Amplitude Corona 1 MPD1 MPD2 MPD3 3 2 Internal PD EM Field
23 3PARD and Back Transformation
24 3FREQ: PD Discrimination by Spectrum A Corona 0.5M 0.5M 2M 8M f MPD1 8M 2M Internal PD EM Field
25 PD Risk Assessment Noise rejection Source separation Pattern classification PD localization Galvanic decoupling Gating UHF RTD 3 PARD 3 FREQ Manual Automatic Asset Phase Acoustic localization
26 Agenda Monitoring Expectations & Needs Bushing Monitoring Capacitance Power Factor Transformer Monitoring Partial Discharge Voltage Transients Summary & Conclusions
27 Switching Transients IEEE PES Transformers Committee Tutorial March 2014 Dr. Robert Degenneff
28 Voltage in kv Voltage in kv Switching Transients t in ms t in ms t in ms t in ms 29
29 Case Study: Combined Generator and Transformer Monitoring Generator 900 MW 21 kv GSU 1100 MVA Transmission line 400 kv 6 km Substation Grid 400 kv G UMTS Voltag Transformers Generator OMS843 - C/DF (Reference) PDM600 ca. 10 m OMS843 - PD - Transients - C/DF OMS843 - PD - Transients - C/DF Transformer 1 Transformer 2 UHF620 + UVS UHF620 + UVS
30 C/DF and PD Couplers Generator: Capacitive couplers Transformer: Capacitive bushing adapters and UHF drain valve sensor
31 U in µv P in dbm DF / % Monitoring Results 1,0% 0,8% UMTS U Voltage Transformers V W Generator 0,6% 0,4% OMS843 - C/DF (Reference) 1 Q IEC in nc 10 PDM600 0,2% 0,0% t in ms ca. 10 m OMS843 - PD --60 Transients - C/DF OMS843 - PD - Transients - C/DF 1 Transformer UHF620 + UVS UHF620 + UVS Transformer t in ms f in MHz 1000
32 dissipation factor in % temperature in C Influence of Environmental Conditions IEC60137 max: 0,7 % V-phase U-phase W-phase time / days
33 Voltage in kv Voltage in kv Transient Over-Voltages > Oszillation frequency 10 khz, beat frequency 600 Hz > Several times a day C Phase BAT20 Generator 900 MW 21 kv G GSU 1100 MVA Transmission line 400 kv 6 km Substation Grid 400 kv B Phase A Phase t in ms BAT10 BAT t in ms t in ms 18
34 Agenda Monitoring Expectations & Needs Bushing Monitoring Capacitance Power Factor Transformer Monitoring Partial Discharge Voltage Transients Summary & Conclusions
35 Summary On-line monitoring as future trend C/DF monitoring The reference problem Solution: VT reference Accuracy +/- 2pF On-line PD monitoring The noise problem Possible solutions: UHF-gating Software separation Pattern recognition Voltage Transients
36 Questions?? Thomas Prevost
MONTRANO. Continuous monitoring system for power transformers
MONTRANO Continuous monitoring system for power transformers Condition monitoring to extend transformer life Knowing the dielectric condition of insulation is vital Dielectric flashover of insulation in
More informationOMICRON Seminar on Partial Discharge Diagnostics on HV Assets. January 30, 2018 Beirut, Lebanon
OMICRON Seminar on Partial Discharge Diagnostics on HV Assets January 30, 2018 Beirut, Lebanon Substation Asset Testing and Diagnosis LOW ACCURACY LEVEL HIGH Take better maintenance decisions through accurate
More informationThe University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge
The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits
More informationAfrica Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound
Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences
More informationOMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates
OMICRON Seminar on Substation Testing and Diagnosis October 23, 2017 Dubai, United Arab Emirates October 24, 2017 Abu Dhabi, United Arab Emirates Time Optimized Substation Asset Testing and Diagnosis Agenda
More informationDoble Solutions for Partial Discharge. Greg Topjian Solutions Manager
Doble Solutions for Partial Discharge Greg Topjian Solutions Manager 617-393-3129 gtopjian@doble.com Why do we need to conduct PD measurements PD a major cause of early failure for HV insulation. Partial
More informationAdvancements in online partial discharge monitoring and assessment of MV through EHV Substation assets
Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets Abstract: For decades it has been recognized that partial discharge assessment is an excellent method
More informationA New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol
A New Approach for Transformer Bushing Monitoring Emilio Morales Technical Application Specialist Qualitrol Abstract Transformer bushings are one of the most critical components of a transformer. Up to
More informationTECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets
TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets Who we are TECHIMP is one of the leading providers of Condition Assessment Services Data Acquisition and Test Equipment
More informationWhy partial discharge testing makes good sense
Why partial discharge testing makes good sense PD measurement and analysis have proven to be reliable for detecting defects in the insulation system of electrical assets before major damage or a breakdown
More informationPartial Discharge Measurements on 110kV Current Transformers. Case Study. Results
2016 International Conference on Electrical Engineering and Automation (ICEEA 2016) ISBN: 978-1-60595-407-3 Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results Cristian DAN
More informationDispersing the clouds gain clear insight into your bushings using advanced diagnostic methods
Topic Dispersing the clouds gain clear insight into your bushings using advanced diagnostic methods Abstract: Bushing diagnosis can include various methods, from a simple visual inspection or a conventional
More informationThe importance of partial discharge testing throughout the development and operation of power transformers
The importance of partial discharge testing throughout the development and operation of power transformers Ulrike Broniecki OMICRON Energy Solutions GmbH, Berlin Power transformers are exposed to intense
More informationCondition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology
Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of
More informationMPD 600. High-end partial discharge measurement and analysis system
MPD 600 High-end partial discharge measurement and analysis system Partial discharge analysis Partial discharges: weak points in insulation systems Partial discharges, as defined by IEC 60270, are localized
More informationPD Solutions. On-Line PD Measurement Devices
On-Line PD Measurement Devices 1. Longshot Device (see Figure 1) The measurement system applied is based around the wideband (0-400 MHz) HVPD- Longshot partial discharge test unit which utilizes a high-speed
More informationPARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES
PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES Engr. IÑIGO V. ESCOPETE, JR. ITC Level 2 Certified Thermographer PHIL-NCB NDT-UT Level 2 Partial Discharge testing is a Condition Based Maintenance tool
More informationTECHIMP Power Transformer Monitoring
TECHIMP Power Transformer Monitoring Kontakt: Martin Hesse Techimp Germany GmbH i.g. E-Mail: mhesse@techimp.com Tel.: +49 5724 391 007 Mobil: +49 170 2364 735 PD Monitoring of Power Transformers Power
More informationUSING DAMPED AC VOLTAGES
MODERN & TESTING DIAGNOSIS OF POWER CABLES USING DAMPED AC VOLTAGES BY EDWARD GULSKI AND ROGIER JONGEN, Onsite HV Solutions ag, Switzerland AND RALPH PATTERSON, Power Products & Solutions LLC, United States
More informationInternational Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer
Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 7, July -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 Comparison
More informationPartial Discharge Monitoring and Diagnosis of Power Generator
Partial Discharge Monitoring and Diagnosis of Power Generator Gao Wensheng Institute of High Voltage & insulation tech. Electrical Eng. Dept., Tsinghua University Wsgao@tsinghua.edu.cn Currently preventive
More informationMPD 600. High-End Measurement and Analysis System for Partial Discharges (PD)
MPD 600 High-End Measurement and Analysis System for Partial Discharges (PD) Partial Discharge Analysis The MPD 600 partial discharge analysis system is a precise and modular high-end toolbox for detecting,
More informationMPD 600. High-end measurement and analysis system for partial discharges
MPD 600 High-end measurement and analysis system for partial discharges Partial discharge analysis Partial discharges: weak points in insulation systems Partial discharges, as defined by IEC 60270, are
More informationIMPORTANCE OF ACCURATE MEASUREMENTS DURING THE LIFE CYCLE OF UTILITIES
IMPORTANCE OF ACCURATE MEASUREMENTS DURING THE LIFE CYCLE OF UTILITIES Thomas Steiner HIGHVOLT Prüftechnik Dresden GmbH Lifecycle of utilities time schedule utilities Tests during life cycle of utilities
More informationAutotransformer Condition Monitoring Systems
Autotransformer Condition Monitoring Systems The Bidders shall offer separately the following systems of par.1 Integrated Condition Monitoring System and par.2 UHF PD Monitoring System. Two systems following
More informationCHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN
75 CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 5.1 INTRODUCTION Partial Discharge (PD) detection is an important tool for monitoring insulation conditions in high voltage (HV) devices in power systems.
More informationNETWORK INNOVATION COMPETITION ANGLE-DC PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT
NETWORK INNOVATION COMPETITION PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT NOVEMBER 17 Version: 1.0 Authored by: Andrew Moon Engineering Consultant and Project Manager Kevin Smith Lead
More informationPartial Discharge Monitoring of Power Transformers by UHF Sensors
Partial Discharge Monitoring of Power Transformers by UHF Sensors S. Tenbohlen 1, M. Siegel², M. Beltle² 1 Institute of Power Transmission and High Voltage Technology (IEH), University of Stuttgart Pfaffenwaldring
More information10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY
9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor
More informationMitigating Murphy s Law While Test. Frédéric Dollinger
Mitigating Murphy s Law While Test Frédéric Dollinger Curriculum Vitae Frédéric Dollinger HAEFELY HIPOTRONICS factory Basel Switzerland Area Sales & Marketing Manager Dipl. Ing. / M.Sc. Mechatronic Language:
More informationAdvanced Test Equipment Rentals ATEC (2832)
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) MPD 500 Partial Discharge Measuring System for Routine Test Applications Partial Discharge Measurement The MPD 500 partial
More informationMPD 500. Partial Discharge Measuring System for Routine Test Applications
MPD 500 Partial Discharge Measuring System for Routine Test Applications Partial Discharge Measurement The MPD 500 partial discharge measuring system has been specially designed for providing fast and
More informationVLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing
Cable Testing & Diagnostics Solutions for Medium Voltage Networks (1 kv - 36 kv) VLF Partial Discharge DC DAC tandelta Cable Testing Cable Diagnostics? There are two main applications for cable testing:
More informationDiagnostic testing of cast resin transformers
Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com
More informationTesting and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl
Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May 26 2011 St Pete Beach, Fl HDW ELECTRONICS, INC. THE BEST IN CABLE FAULT LOCATING TECHNOLOGY by Henning Oetjen Frank
More informationComparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137
ITEM Power factor (tanδ) & Capacitance Measurement Dry 1-minute Power frequency with partial discharge measurement CAN/CSA C88.1-96 IEEE C57.19.00/01 IEC 60137 Requirement Requirement Requirement Clause
More informationCNY17 Series. Optocoupler with Phototransistor Output. Description. Applications. TELEFUNKEN Semiconductors
TELEFUNKEN Semiconductors CNY17 Series Optocoupler with Phototransistor Output Order Nos. and Classification table is on sheet 2. Description The CNY17 Series consist of a phototransistor optically coupled
More informationPrimary Test Manager (PTM) Testing and management software for primary assets
Primary Test Manager (PTM) Testing and management software for primary assets Asset diagnostics now easier than ever How well do you know your assets? High-voltage assets are subjected to aging and wear
More informationEffective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers
Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Alexander Dierks, Herman Viljoen, Alectrix (Pty) Ltd, South Africa
More informationInvestigation of PD Detection on XLPE Cables
Investigation of PD Detection on XLPE Cables Hio Nam O, T.R. Blackburn and B.T. Phung School of Electrical Engineering and Telecommunications The University New South Wales, Australia Abstract- The insulation
More informationPARTIAL DISCHARGE MEASUREMENT
PARTIAL DISCHARGE MEASUREMENT Partial Discharges are small electrical sparks which occur predominantly at insulation imperfection. It is the phenomenon which occurs in the insulation on application of
More informationIRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.
IRIS POWER PDTracII Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear. We have not found another test method that produces as much
More informationPartial discharge diagnostics on very long and branched cable circuits
11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA
More informationPD Diagnostic Applications and TechImp solutions
PD Diagnostic Applications and TechImp solutions Condition Assessment Solutions for Electrical Systems. PD based innovative tools for the Condition Based Maintenance. MD-04.05.004 - rev. 00-29/08/2006
More informationAdvanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) CP RC Resonance circuit for GIS testing A new approach to testing gas-insulated switchgear Testing gas-insulated switchgear
More informationINSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES
INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES Edward GULSKI, Delft University of Technology, (The Netherlands), e.gulski@tudelft.nl Johan J SMIT, Delft University of Technology, (The Netherlands),
More informationIRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.
IRIS POWER PDTracII Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear. We have not found another test method that produces as much
More informationKončar TMS - Bushing monitoring
Končar TMS - Bushing monitoring Many recent studies have shown that bushing failure is one of the most common causes of transformer failure. Thus need for bushing diagnostic and monitoring system has risen.
More informationIRIS POWER TGA-B. Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors
IRIS POWER TGA-B Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors We have not found another test method that produces as much decision support data for generator
More informationMPD 600. High-end partial discharge measurement and analysis system
MPD 600 High-end partial discharge measurement and analysis system Partial discharge analysis Partial discharges: weak points in insulation systems Partial discharges, as defined by IEC 60270, are localized
More informationComparison of capacitive and inductive sensors designed for partial discharges measurements in electrical power apparatus
Comparison of capacitive and inductive sensors designed for partial discharges measurements in electrical power apparatus Michał Kunicki 1,* 1 Opole University of Technology, ul. Prószkowska 76, 45-758
More informationEffective maintenance test techniques for power transformers
Effective maintenance test techniques for power transformers by Alexander Dierks, Herman Viljoen, Alectrix, South Africa, and Dr. Michael Krüger, Omicron Electronics, Austria Due to ever-increasing pressure
More informationA1-209 EXPERIENCES IN IDENTIFICATION OF PARTIAL DISCHARGE PATTERNS IN LARGE HYDROGENERATORS
21, rue d'artois, F-75008 Paris http://www.cigre.org A1-209 Session 2004 CIGRÉ EXPERIENCES IN IDENTIFICATION OF PARTIAL DISCHARGE PATTERNS IN LARGE HYDROGENERATORS CARLOS AZUAJE* WILLIAM TORRES C.V.G.
More informationFor the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.
Current Transducer CAS 25-NP/SP2 N = 25 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Closed loop (compensated)
More informationPARTIAL DISCHARGE DETECTION - AN OVERVIEW
PARTIAL DISCHARGE DETECTION - AN OVERVIEW 1 MR. N. J. PATEL, 2 PROF. K. K. DUDANI, 3 PROF. A. K. JOSHI 1 M.E. [Power System] P.G. Student, Department of Electrical Engineering, L. E. College of Engineering,
More informationON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS
ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS Pantelis D. AGORIS 1, Sander MEIJER 1, Edward GULSKI 1, Johan J. SMIT 1, A. Jos L.M. KANTERS 2 1 Delft University of Technology - The Netherlands 2 TenneT
More informationInnovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers
Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Dr. Michael Krüger, Alexander Kraetge, OMICRON electronics GmbH, Austria Alexander
More information- Continuous real-time measurement and PD trend analysis; not multiplexed data collection.
QTMS The transformer monitor shall provide data integration platform, cooling supervision & monitoring. User configurable without need of a technician, a 100% configurable to specific customer requirement.
More informationCHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES
23 CHAPTER 2 v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 2.1 INTRODUCTION For reliable design of power system, proper insulation coordination among the power system equipment is necessary. Insulation
More informationFlorian Predl and GK Papneja OMICRON
One-day Workshop on HV insulation diagnosis by means of PD detection/measurement methods by Florian Predl and GK Papneja OMICRON Date: Time: Venue: 28 November 2016 (Monday) 9:00 17:00 (8:30 for registration)
More informationKnowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators
Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery Application of EMI Diagnostics to Hydro Generators James Timperley Doble Global Power Services Columbus, Ohio jtimperley@doble.com
More informationBasics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015
Basics of Partial Discharge Prepared for 2015 Phenix RSM Meeting January 2015 Definitions and History Standard Definitions Fundamentally, what is a Partial Discharge An electric discharge which only partially
More informationHigh Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland
High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland Company HV Diagnostics Sarl is a Swiss based company in the field of high voltage test equipment for cable testing and diagnosis.
More informationII. TRADITIONAL APPROACH OF PD MEASUREMENTS
Advantages of Continuous Monitoring of Partial Discharges in Rotating Equipment and Switchgear Claude Kane Cutler Hammer Predictive Diagnostics 5421 Feltl Road, Suite 190 Minnetonka, MN 55343 Phone: 952-912-1358
More informationHigh Frequency Voltage Stress. Presented by: Flore Chiang Date: March 30, 2012
High Frequency Voltage Stress Presented by: Flore Chiang Date: March 30, 2012 Now the additional data is available! ground rules: 1. intro to PD. 2. experimental results. 3. comparison with current practice.
More informationFor the electronic measurement of current: DC, AC, pulsed..., with galvanic isolation between the primary and the secondary circuit.
Current Transducer CASR series I PN = 6, 5, 25, 5 A Ref: CASR 6-NP, CASR 5-NP, CASR 25-NP, CASR 5-NP For the electronic measurement of current: DC, AC, pulsed..., with galvanic isolation between the primary
More informationSPECIFICATION Item no.: T60404-N4646-X764
Customer: Standard type Customers Part no: Page 1 of 4 Description Closed loop (compensation) Current Sensor with magnetic field probe Printed circuit board mounting Casing and materials UL-listed Electrical
More informationInvestigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages
Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages F. Petzold, H.T. Putter, D. Götz, H. Schlapp, S. Markalous SebaKMT GmbH Baunach/Radeburg,
More informationAdamantios Marinakis, Scientist, 12 th IEEE SB Power Engineering Symposium, Leuven, Enhancing Power System Operation with WAMS
Adamantios Marinakis, Scientist, 12 th IEEE SB Power Engineering Symposium, Leuven, 24.03.2016 Enhancing Power System Operation with WAMS Presentation Outline 1. Introduction to WAMS 2. Present WAMS applications:
More informationProgress Report on Failures of High Voltage Bushings with Draw Leads By Jim McBride and Larry Coffeen, JMX Services / NEETRAC 7/26/2010
The Team: Jim McBride: IEEE Member Larry Coffeen: IEEE Senior Member President, JMX Services, Inc. Senior Research Engineer, NEETRAC BS EE Georgia Tech BS EE Georgia Tech Testing, DAQ, and Measurement
More informationMPD 500. Partial discharge measurement system for routine test applications
MPD 500 Partial discharge measurement system for routine test applications Partial discharge testing The MPD 500 partial discharge measuring system has been specially designed for providing fast and reliable
More informationCNY17 Series. Optocoupler with Phototransistor Output. Description. Applications. Order Nos. and Classification table is on sheet 2.
Optocoupler with Phototransistor Output Order Nos. and Classification table is on sheet 2. Description The CNY17 series consists of a phototransistor optically coupled to a gallium arsenide infrared-emitting
More informationOptocoupler, Phototransistor Output, High Temperature
TCET, TCETG Optocoupler, Phototransistor Output, 797_4 DESCRIPTION The TCET. consists of a phototransistor optically coupled to a gallium arsenide infrared-emitting diode in a 4-lead plastic dual inline
More informationPARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM
Abstract PARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM Q. SU Department of Electrical & Computer Systems Engineering Monash University, Clayton VIC 3168 Email: qi.su@eng.monash.edu.au
More informationPHG 70 TD PD / PHG 80 TD PD
PHG 70 TD PD / PHG 80 TD PD BAUR VLF test and diagnostics system Functions Universal test and diagnostics system flexible, modular, extendable Cutting-edge testing and diagnostics technology: VLF truesinus
More informationCable testing and diagnostics
Cable testing and diagnostics To ensure the flow Cost-optimised maintenance through cable diagnostics The sheath and cable testing supports you in assessing whether a cable system is safe and ready to
More informationFor the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.
Current transducer CKSR series N = 6, 5, 25, 5 A Ref: CKSR 6-NP, CKSR 5-NP, CKSR 25-NP, CKSR 5-NP For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary
More informationPARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS
PARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS by K.K.JEMBU KAILAS and W. ADITHYA KUMAR L&T CONSTRUCTION L&T CONSTRUCTION KKJK@LNTECC.COM
More informationPartial Discharge Measurement and Monitoring on High Voltage XLPE Cables
21, rue d Artois, F-75008 PARIS AUCKLAND 2013 http : //www.cigre.org Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables Michael Krüger, Rene Hummel, Stefan Böhler, OMICRON Austria
More informationFault Detection in Transformer Using Frequency (Sweep) Response Analysis
Fault Detection in Transformer Using Frequency (Sweep) Response Analysis Miss. Kajal R. Pachbhai PG Student at Ballarpur Institute of Technology, Ballarpur-442701 India kajalpachbhai86@gmail.com Mr. Sagar
More informationRevision of C Guide for Application of Monitoring Equipment to Liquid Immersed Transformers and Components. Mike Spurlock Chairman
Revision of C57.143-2012 Guide for Application of Monitoring Equipment to Liquid Immersed Transformers and Components Mike Spurlock Chairman All participants in this meeting have certain obligations under
More informationTHE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.
THE POWER OF LIFE WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk. Mr. Neal Yang Pro.E.E. Engineer About Us The flaw of dielectric material
More informationAT5210 FEATURES DESCRIPTION APPLICATION. 150mA High PSRR LDO. AT X.X KE R Shipping: IAT R: Tape & Reel Circuit Type. Immense Advance Tech.
FEATURES DESCRIPTION V IN Range: 2.0V to 6.0V Low Dropout Voltage: 0.22V (Typ) (V OUT = 3.3V, I OUT = 150mA) Output Current: 150mA High Ripple Rejection: 75dB (Typ)(f= 1kHz) Excellent Line Regulation:
More informationRef: HO 50-S/SP33, HO 100-S/SP33, HO 150-S/SP33, HO 200-S/SP33, HO 250-S/SP33
Current Transducer HO-S/SP33 series I PN = 50, 100, 150, 200, 250 A Ref: HO 50-S/SP33, HO 100-S/SP33, HO 150-S/SP33, HO 200-S/SP33, HO 250-S/SP33 For the electronic measurement of current: DC, AC, pulsed...,
More informationDielectric response and partial discharge measurements on stator insulation at varied low frequency. Nathaniel Taylor
Dielectric response and partial discharge measurements on stator insulation at varied low frequency Nathaniel Taylor Rotating Electrical Machines : The Stator and its Windings turbo-generator motor hydro-generator
More informationType 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s
Designed for Partial Discharge Analyzers (PDA s) monitoring rotating machinery or other medium-voltage equipment from 1 to 35 kvac RMS at power-line frequencies of 10 Hz to 1 khz, Mica Capacitor Type 297
More informationCA723, CA723C. Voltage Regulators Adjustable from 2V to 37V at Output Currents Up to 150mA Without External Pass Transistors. Description.
SEMICONDUCTOR CA73, CA73C April 199 Voltage Regulators Adjustable from V to 37V at Output Currents Up to 1mA Without External Pass Transistors Features Up to 1mA Output Current Positive and Negative Voltage
More informationMonitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers
in cooperation with Monitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers BZ-MS/1 pazifik power Complete Transformer Monitoring System (TMS) ZVCM-1001 Bushing Monitoring
More informationCNY75(G) Series. Optocoupler with Phototransistor Output. Vishay Telefunken. Description. Applications. VDE Standards.
Optocoupler with Phototransistor Output Description The CNY75(G) series consists of a phototransistor optically coupled to a gallium arsenide infraredemitting diode in a 6-lead plastic dual inline package.
More informationPRY-CAM BREAKTHROUGH TECHNOLOGY FOR CONDITION ASSESSMENT AND ASSET MANAGEMENT
PRY-CAM BREAKTHROUGH TECHNOLOGY FOR CONDITION ASSESSMENT AND ASSET MANAGEMENT WELCOME TO PRY-CAM A REVOLUTION IN PARTIAL DISCHARGE MANAGEMENT The worlds of partial discharge (PD) measurement, asset management
More informationWIRE AND CABLE ENGINEERING GUIDE
Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime
More information1409. Comparison study between acoustic and optical sensors for acoustic wave
1409. Comparison study between acoustic and optical sensors for acoustic wave Malik Abdulrazzaq Alsaedi Department of Electrical, Faculty of Engineering, University of Misan, Amarah, Iraq E-mail: maliksaady@yahoo.com
More informationOptocoupler, Phototransistor Output
72_4 DESCRIPTION 8537_4 C E 5 4 The series consists of a phototransistor optically coupled to a gallium arsenide infrared-emitting diode in a 6-lead plastic dual inline package. VDE STANDARDS These couplers
More informationFor the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.
Current Transducer ITL 4000-S I PN = 4000 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. I > 0 P Features Closed
More informationGENERATOR TESTING APPLICATION GUIDE. reliable. precision.
GENERATOR TESTING APPLICATION GUIDE www.haefely-hipotronics.com reliable. precision. 2 GENERATOR TESTING CONTENTS Product Line Overview 3 AC Hipot Testing 4 Partial Discharge Measurement 5 DC Hipot Testing
More informationRTD as a Valuable Tool in Partial Discharge Measurements on Rotating Machines
RTD as a Valuable Tool in Partial Discharge Measurements on Rotating Machines Z. Berler, I. Blokhintsev, A. Golubev, G. Paoletti, A. Romashkov Cutler Hammer Predictive Diagnostics Abstract: This paper
More informationSENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES
SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES Frank WESTER, Edward GULSKI, Johan SMIT, Edwin GROOT*, Mark VAN VLIET* Delft University of Technology The Netherlands * NUON The Netherlands
More informationHVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N
S C I E N C E P A S S I O N T E C H N O L O G Y HVDC Transmission Michael Muhr Graz University of Technology Austria www.tugraz.at 1 Definition HV High Voltage AC Voltage > 60kV 220kV DC Voltage > 60kV
More informationMartin Stoessl R&D Manager Siemens Transformers Austria - Weiz
Martin Stoessl R&D Manager Siemens Transformers Austria - Weiz 2007 1979 1892 Transformer reliability Ability to perform its required functions under stated conditions for a specified period of time Failure
More informationDATA SHEET. J111; J112; J113 N-channel silicon field-effect transistors DISCRETE SEMICONDUCTORS
DISCRETE SEMICONDUCTORS DATA SHEET N-channel silicon field-effect transistors File under Discrete Semiconductors, SC07 July 1993 DESCRIPTION Symmetrical silicon n-channel junction FETs in plastic TO-92
More information