PARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS
|
|
- Barbra Austin
- 6 years ago
- Views:
Transcription
1 PARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS by K.K.JEMBU KAILAS and W. ADITHYA KUMAR L&T CONSTRUCTION L&T CONSTRUCTION
2 Objective Partial Discharge detection & location in Power transformers and to evaluate the most important property of UHF sensor i.e. SENSITIVITY through preliminary testing. To de-noise the captured signals and to extract the original PD signal after de-noising. To evaluate the approximate location of PD source
3 Partial Discharge (PD) PD - Intermittent nanosecond range pulses Causes of PD. Weak insulation - When electric field across the insulation > dielectric strength of the insulation = PD. Arcing due to poor contacts 3. Corona 4. Surface discharges Effects of PD. Insulation degradation over a period of time. Equipment failure, Effect on men & materials, Disruption of economic activities, Customer dissatisfaction, Penalty clauses 3
4 PD Detection using UHF Principle and aspects Electrons accelerated under high electric field and immediately brought to rest (nano sec range pulses) produce Ultra High Frequency (UHF) EM waves. UHF waves = 300 MHz MHz Non conventional method energy from EM waves can be captured using sensors and their outputs can be shown in V or mv PD pulses can be detected if wave length of UHF signals < tank dimensions Narrow pulse, more spectral energy & vice versa 4
5 UHF sensors & UHF PD Detector Module Internal & External sensor respectively, internal sensor placed inside the drain valve, while external sensor placed in specially designed dielectric windows on the transformer, both require modifications on transformer tank. 5
6 Conventional Method (IEC 6070) UHF Method Offline measurements Online measurements Measurements at factory Measurements at factory and site Considers the transformer as a single unit. Hence fault location is not possible Able to locate multiple faults as the system considers each fault location as a localized unit Basic method to analyze the Can be coupled with conventional method overall strength of insulation for diagnosis, while testing transformers in in the factory the factory. Highly sensitive to noise Less sensitive to noise, as this operates in UHF range. Even corona and other noises happen only below this range. Hence sensitivity is high 7
7 Types of Sensors Patch antenna Internal sensor External sensor 8
8 Preliminary testing of Sensors Before inserting the sensor directly in to the drain valve of Transformer it is necessary to evaluate the performance of antenna. More over the charge levels in a transformer will be in the order of some thousand pc. So the sensitivity of the sensor is evaluated by keeping the antenna at a relative distance from PD source. 9
9 Sensitivity verification of UHF Conical Monopole Antenna Experimental Set-up LDIC PD measuring system 0
10 Applied voltage (KV) v/s charge (pc) The charge (pc) was linearly varying with applied voltage i.e. it has a linear relationship. The center frequency of received signals at PD inception voltage was 963MHz. The minimum energy of the PD signal is 60μJ with sensitivity 90pC.
11 Experimental Set-up
12 Preliminary testing in Oil Internal UHF sensor Signal captured at 0.KV Signals captured by all the 4 sensors at KV 3
13 De-noised signal 4
14 Results Type of sensor Distance Max Peak to test (m) voltage peak (mv) voltage (mv) Frequency Energy Time Phase Power (MHz) (pj) period (degre (dbm) (ns) es) Time difference t s s s s s s s s Triggering Triggering voltage Channel (mv) t3 t C C in Air in Oil 5
15 Observations from Oil test The Internal sensor (conical monopole antenna) has detected the corona discharge at an inception of voltage of 0.KV where as all the other external antennas (Patch antennas) did not capture it. As the distance between internal sensor and the electrodes was 8cm where as the distance between external sensors and the electrodes is m, the UHF internal sensor detected the signal. After repeating the experiment keeping all the sensors at same positions and with voltage being increased, external sensors detected corona at KV, where as the UHF internal sensor detected at 0.6KV. The results show that the UHF internal sensor is more sensitive than the external sensors when placed very close to the PD source without actually knowing the level of PD. As the test was carried out under controlled conditions and without any ground noise de-noising the signal was done in oscilloscope. 6
16 Experiment on real time Transformer Internal Sensor Mounted in to one of the valves 7
17 UHF FFToutput 0.35 De-Noising Wavelet De-noising Principle Amplitude(volts) 0.3 FFT of original signal Maximum Amplitude = volts at a frequency of 979 MHz Original signaluhfcaptured by sensor output Time(seconds) x FFT offrequency(hz) Denoised signal 0 9 x 0 Maximum Amplitude is 0.53 at 000 MHz Amplitude(volts) Amplitude(volts) Amplitude(volts) 0. De-noised signal using wavelets in MATLAB Denoised signal Time(seconds) x Frequency(Hz) x 0 8
18 PD location using UHF Time of Arrival Approach There will be definite time difference between arrival of signal from a particular PD source at each sensor. The time difference governed by minimum time delay path traveled by the EM wave front to reach each sensor. Distance traveled (D) = EM Wave speed (v) x time (t) or more distinct but repeatable time period = multiple PD sources 9
19 Flow Chart of TDOA Enter the sensor coordinates in D/3D Calculate the sensor position values Call TDOA Read the time domain signal from each sensor Cross correlation TDOA values Solve the non-linear equations Newton Raphson Iterative method Non-Iterative method Source location 0
20 Evaluation of -Dimensional PD source Location using MATLAB Sl.no Applied Sensor Sensor Sensor 3 Time Computed Source Computed Error Error voltage Position Position Position Difference Of Velocity of position position in in (KV) (x,y) cm (x,y) cm (x3,y3) cm Arrival (TDOA) electromagneti (x,y) cm (xc,yc) cm X (%) Y (%) 50, , (50,00) (50,75) (50,0) T T3 c waves (ns) (ns) Cm/sec...3*0^ (50,00) (50,75) (50,0)...3*0^0 50, , (50,00) (50,75) (50,0)...3*0^0 50, , (50,00) (50,75) (50,0)...3*0^0 50, , (50,00) (50,75) (50,0)...3*0^0 50, , (50,00) (50,75) (50,0)...3*0^0 50, , Comparison of actual source and evaluated source with sensor as reference
21 Evaluation of -Dimensional PD source Location using MATLAB Sl.no Applied Sensor Sensor Sensor 3 Time Difference Computed Source Computed Error in Error voltage Position Position Position Of Arrival Velocity of position position X (%) in (KV) (x,y) cm (x,y) cm (x3,y3) cm (TDOA) electromagnetic (x,y) cm (xc,yc) cm T3 T3 waves (ns) (ns) Cm/sec Y (%) 0.4 (50,00) (50,75) (50,50) *0^0 50, , (50,00) (50,75) (50,50).5 5 *0^0 50, , (50,00) (50,75) (50,50) *0^0 50, , (50,00) (50,75) (50,50) *0^0 50, , (50,00) (50,75) (50,50) *0^0 50, , (50,00) (50,75) (50,50) *0^0 50, , (50,00) (50,75) (50,50) *0^0 50, ,0.4 Comparison of actual source and evaluated source with sensor 3 as reference
22 Results When the FFT of original signal was performed, the dominant frequency was 979MHz and the dominant frequency in denoised signal was found to be 000MHz. This shows that the noise which the sensor captured even between 900MHz-000MHz is eliminated The amplitude of denoised signal is less than that of the original signal amplitude. This gives clear information that noise levels are generally higher than PD signal amplitude. Wavelet de-noising using Daubechey s filter is the best method among different techniques -D source has been located in a steel tank with an error of 8% using iteration method (Newton-Raphson method). The accuracy of Dimensional source location has been improved to 96% when NewtonRaphson method is implemented on denoised signals 3
23 Conclusion UHF method has numerous applications and one of them is transformer. The sensor designed for inserting it in to the drain valve of transformer has very good sensitivity of 90pC under controlled conditions. So the UHF sensors can be installed at sites, factories without de-energizing the transformers and the approximate location of PD source can be traced such that the insulation strength of that particular area is increased and also the life of transformer is increased. -D PD source has been located in steel tank using iteration method (Newton-Raphson method) with a error of 8%, where as 3Dimensional source localization is done with non-iterative method like TDOA, PRPA. 3Dimensional PD source is also localized but with a certain error 4
24 FUTURE SCOPE This research is vast and can be extended to on-line monitoring of the transformer with a suitable hardware. The best way to implement this technique on-line is by using DAQ unit along with LABVIEW. This gives important information about condition monitoring and diagnostics of power transformers for a full day, week, month depending upon the size of data to be analyzed. So the best way to implement this technique on-line is to reduce the amount of data recorded in the hardware every second by erasing unnecessary data 5
25 6
PD Solutions. On-Line PD Measurement Devices
On-Line PD Measurement Devices 1. Longshot Device (see Figure 1) The measurement system applied is based around the wideband (0-400 MHz) HVPD- Longshot partial discharge test unit which utilizes a high-speed
More informationSoftware for Partial Discharge and Localization
48 PIERS Proceedings, Taipei, March 25 28, 2013 Software for Partial Discharge and Localization M. Cap, P. Drexler, P. Fiala, and R. Myska Department of Theoretical and Experimental Electrical Engineering
More informationIN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY
IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY Avinash Raj 1, Chandan Kumar Chakrabarty 1, Rafidah Ismail 1 and Basri Abdul Ghani 2 1 College of Engineering, University Tenaga
More informationCHAPTER 3 ACOUSTIC EMISSION TECHNIQUE FOR DETECTION AND LOCATION OF PD
63 CHAPTER 3 ACOUSTIC EMISSION TECHNIQUE FOR DETECTION AND LOCATION OF PD 3.1 INTRODUCTION PD measurements on high-voltage equipment, e.g. transformers, could be grouped into two major tasks. First, evidence
More information1409. Comparison study between acoustic and optical sensors for acoustic wave
1409. Comparison study between acoustic and optical sensors for acoustic wave Malik Abdulrazzaq Alsaedi Department of Electrical, Faculty of Engineering, University of Misan, Amarah, Iraq E-mail: maliksaady@yahoo.com
More informationEvaluation of Partial Discharge in Power Transformers by Acoustic Emission Method and Propagation Modeling of Acoustic Signal
Evaluation of Partial Discharge in Power Transformers by Acoustic Emission Method and Propagation Modeling of Acoustic Signal Abdolrahman Peimankar, Arman Kazemi, and Seyed Mohammad Taghi Bathaee Khaje
More informationTECHIMP Power Transformer Monitoring
TECHIMP Power Transformer Monitoring Kontakt: Martin Hesse Techimp Germany GmbH i.g. E-Mail: mhesse@techimp.com Tel.: +49 5724 391 007 Mobil: +49 170 2364 735 PD Monitoring of Power Transformers Power
More informationBasics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015
Basics of Partial Discharge Prepared for 2015 Phenix RSM Meeting January 2015 Definitions and History Standard Definitions Fundamentally, what is a Partial Discharge An electric discharge which only partially
More informationIEEE Transactions on Power Delivery. 15(2) P.467-P
Title Author(s) Citation Detection of wide-band E-M signals emitted from partial discharge occurring in GIS using wavelet transform Kawada, Masatake; Tungkanawanich, Ampol; 河崎, 善一郎 ; 松浦, 虔士 IEEE Transactions
More informationWAVELET DE-NOISING AND ANALYSIS OF UHF PARTIAL DISCHARGES IN HIGH VOLTAGE POWER TRANSFORMER
Volume, Issue 9, PP: - 9, FEB. WAVELET DE-NOISING AND ANALYSIS OF UHF PARTIAL DISCHARGES IN HIGH VOLTAGE POWER TRANSFORMER K V RAMPRASAD *. Professor, Dept of ECE, KALLAM HARANADHA REDDY INSTITUTE OF TECHNOLOGY,
More informationCHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN
75 CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 5.1 INTRODUCTION Partial Discharge (PD) detection is an important tool for monitoring insulation conditions in high voltage (HV) devices in power systems.
More informationPARTIAL DISCHARGE MEASUREMENT
PARTIAL DISCHARGE MEASUREMENT Partial Discharges are small electrical sparks which occur predominantly at insulation imperfection. It is the phenomenon which occurs in the insulation on application of
More informationOpen Access Application of Partial Discharge Online Monitoring Technology in ± 660kV Converter Transformer
Send Orders for Reprints to reprints@benthamscience.ae 784 The Open Automation and Control Systems Journal, 2015, 7, 784-791 Open Access Application of Partial Discharge Online Monitoring Technology in
More informationThe Application of Partial Discharge Measurement and Location on CGIS
International Journal on Electrical Engineering and Informatics Volume 4, Number 3, October 2012 The Application of Partial Discharge Measurement and Location on CGIS Min-Yen Chiu¹, Keng-Wei Liang¹, Chang-Hsing
More informationPartial Discharge Monitoring and Diagnosis of Power Generator
Partial Discharge Monitoring and Diagnosis of Power Generator Gao Wensheng Institute of High Voltage & insulation tech. Electrical Eng. Dept., Tsinghua University Wsgao@tsinghua.edu.cn Currently preventive
More informationTECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets
TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets Who we are TECHIMP is one of the leading providers of Condition Assessment Services Data Acquisition and Test Equipment
More informationStrathprints Institutional Repository
Strathprints Institutional Repository Given, M and Mason, Ronald and Judd, Martin and Mcglone, Phillip and Timoshkin, Igor and Wilson, Mark () Comparison between RF and electrical signals from the partial
More informationAPPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS
APPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS David Larochelle NDB Technologies Reasons leading to acoustic testing are different weather it is a manufacturing or field environment
More informationCVVOZE Power Laboratories (CVVOZEPowerLab)
CVVOZE Power Laboratories (CVVOZEPowerLab) BRNO, SEPTEMBER 2016 1 Centre for Research and Utilization of Renewable Energy Centre for Research and Utilization of Renewable Energy (CVVOZE) was established
More informationCONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES
CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES Hao ZHANG, Transgrid, (Australia), hao.zhang@transgrid.com.au Zhao LIU, University of NSW, (Australia), z.liu@unsw.edu.au Toan
More informationTesting and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl
Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May 26 2011 St Pete Beach, Fl HDW ELECTRONICS, INC. THE BEST IN CABLE FAULT LOCATING TECHNOLOGY by Henning Oetjen Frank
More informationKEYWORDS On-line diagnostics, cable termination, partial discharge (PD), ultra-high frequency (UHF), sensitivity check.
2, rue d Artois, F-758 PARIS B-2 CIGRE 28 http : //www.cigre.org Application of UHF method for on-line PD diagnostics of cable terminations T. KLEIN Pfisterer Kontaktsysteme GmbH Germany D. DENISSOV, W.
More informationTHE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.
THE POWER OF LIFE WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk. Mr. Neal Yang Pro.E.E. Engineer About Us The flaw of dielectric material
More informationCoherence and time-frequency analysis of impulse voltage and current measurements
Coherence and time-frequency analysis of impulse voltage and current measurements Jelena Dikun Electrical Engineering Department, Klaipeda University, Klaipeda, Lithuania Emel Onal Electrical Engineering
More informationPractical aspects of PD localization for long length Power Cables
Practical aspects of PD localization for long length Power Cables M. Wild, S. Tenbohlen University of Stuttgart Stuttgart, Germany manuel.wild@ieh.uni-stuttgart.de E. Gulski, R. Jongen onsite hv technology
More informationDigital Signal Processing for the Detection and Location of Acoustic and Electric Signals from Partial Discharges
, June 30 - July 2, 2010, London, U.K. Digital Signal Processing for the Detection and Location of Acoustic and Electric Signals from Partial Discharges Jesus Rubio-Serrano, Member, IAENG, Julio E. Posada
More informationWhy partial discharge testing makes good sense
Why partial discharge testing makes good sense PD measurement and analysis have proven to be reliable for detecting defects in the insulation system of electrical assets before major damage or a breakdown
More informationAdvancements in online partial discharge monitoring and assessment of MV through EHV Substation assets
Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets Abstract: For decades it has been recognized that partial discharge assessment is an excellent method
More informationPartial Discharge Monitoring of Power Transformers by UHF Sensors
Partial Discharge Monitoring of Power Transformers by UHF Sensors S. Tenbohlen 1, M. Siegel², M. Beltle² 1 Institute of Power Transmission and High Voltage Technology (IEH), University of Stuttgart Pfaffenwaldring
More informationNEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY
NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY Lorenzo PERETTO Luigi FODDAI Simone ORRU Luigi PUDDU Altea Switzerland ENEL Italy ENEL Italy REPL Italy lperetto@alteasolutions.com
More informationAutomated PRPD Pattern Analysis using Image Recognition
International Journal on Electrical Engineering and Informatics Volume 4, Number 3, October 2012 Automated PRPD Pattern Analysis using Image Recognition A. Müller, M. Beltle and S. Tenbohlen Institute
More informationParameters influencing Partial Discharge Measurements and their Impact on Diagnosis, Monitoring and Acceptance Tests of Power Transformers
21, rue d Artois, F-75008 PARIS A2-111 CIGRE 2016 http : //www.cigre.org Parameters influencing Partial Discharge Measurements and their Impact on Diagnosis, Monitoring and Acceptance Tests of Power Transformers
More informationThe University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge
The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits
More informationCHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES
23 CHAPTER 2 v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 2.1 INTRODUCTION For reliable design of power system, proper insulation coordination among the power system equipment is necessary. Insulation
More informationCONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS
136 CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS H. van Jaarsveldt* and R. Gouws** School of Electrical, Electronic and Computer Engineering, North-West
More informationPULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS
PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS Anne Pfeffer 1*, Stefan Tenbohlen 1 and Stefan Kornhuber 2 1 Institute of Power Transmission and High Voltage Technology, Pfaffenwaldring
More informationUHF PARTIAL DISCHARGE DIAGNOSIS OF PLUG-IN CABLE TERMINATIONS
UHF PARTIAL DISCHARGE DIAGNOSIS OF PLUG-IN CABLE TERMINATIONS Denis DENISSOV, University of Stuttgart, (Germany), denis.denissov@ieh.uni-stuttgart.de Ruben GRUND, PFISTERER Kontaktsysteme GmbH, (Germany),
More informationAbstract. 1 Introduction
Using optical couplers to monitor the condition of electricity infrastructure S.G. Swingler, L. Hao, P.L. Lewin and D.J. Swaffield The Tony Davies High Voltage Laboratory, University of Southampton, Southampton
More informationMONTRANO. Continuous monitoring system for power transformers
MONTRANO Continuous monitoring system for power transformers Condition monitoring to extend transformer life Knowing the dielectric condition of insulation is vital Dielectric flashover of insulation in
More informationMeasurement of Partial Discharge inside Metal Enclosed Power Apparatus using Internal Sensor
Measurement of Partial Discharge inside Metal Enclosed Power Apparatus using Internal Sensor Umar Khayam 1, Yushan 2 1 School of Electrical Engineering and Informatics Bandung Institute of Technology Bandung,
More informationHigh Sensitivity Interferometric Detection of Partial Discharges for High Power Transformer Applications
High Sensitivity Interferometric Detection of Partial Discharges for High Power Transformer Applications Carlos Macià-Sanahuja and Horacio Lamela-Rivera Optoelectronics and Laser Technology group, Universidad
More informationAnalysis of Propagation Paths of Partial Discharge Acoustic Emission Signals
Analysis of Propagation Paths of Partial Discharge Acoustic Emission Signals Prathamesh Dhole, Tanmoy Sinha, Sumeet Nayak, Prasanta Kundu, N.K.Kishore Abstract Transformers are one of the most important
More information6 - Stage Marx Generator
6 - Stage Marx Generator Specifications - 6-stage Marx generator has two capacitors per stage for the total of twelve capacitors - Each capacitor has 90 nf with the rating of 75 kv - Charging voltage used
More informationInvesti ations Into the Use of Temperature Detectors as # tator Winding Partial Discharge Detectors
Conference Record of the 2006 IEEE International Symposium on Electrical Insulation Investi ations Into the Use of Temperature Detectors as # tator Winding Partial Discharge Detectors S.R. Campbell, G.C.
More informationPartial Discharge, Survey or Monitor?
July 2014 Partial Discharge, Survey or Monitor? 24-7 Partial Discharge monitoring is the ultimate tool for finding insulation weaknesses before they fail. Introduction It s well established that Partial
More informationPDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics
PDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics CASE STUDY 1 (Doble Client Conference 2011, ACCA committee meeting) Dissolved Gas Analysis (DGA)
More informationPartial Discharge Classification Using Acoustic Signals and Artificial Neural Networks
Proc. 2018 Electrostatics Joint Conference 1 Partial Discharge Classification Using Acoustic Signals and Artificial Neural Networks Satish Kumar Polisetty, Shesha Jayaram and Ayman El-Hag Department of
More informationInternational Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer
Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 7, July -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 Comparison
More informationSimulation Model of Partial Discharge in Power Equipment
Simulation Model of Partial Discharge in Power Equipment Pragati Sharma 1, Arti Bhanddakkar 2 1 Research Scholar, Shri Ram Institute of Technology, Jabalpur, India 2 H.O.D. of Electrical Engineering Department,
More informationDoble Solutions for Partial Discharge. Greg Topjian Solutions Manager
Doble Solutions for Partial Discharge Greg Topjian Solutions Manager 617-393-3129 gtopjian@doble.com Why do we need to conduct PD measurements PD a major cause of early failure for HV insulation. Partial
More informationELEC-E8409 High Voltage Engineering. Condition Monitoring of Power Cables
ELEC-E8409 High Voltage Engineering Condition Monitoring of Power Cables ON-SITE DC MEASUREMENTS Measurements quick and simple, several kv voltage, does not require expensive equipment Insulation Resistance
More informationMulti-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements
Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements EMEL ONAL Electrical Engineering Department Istanbul Technical University 34469 Maslak-Istanbul TURKEY onal@elk.itu.edu.tr http://www.elk.itu.edu.tr/~onal
More informationPartial discharge diagnostics on very long and branched cable circuits
11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA
More informationOnline Localisation of Partial Discharge Using Pulse Propagation Parameters in Medium Voltage Cable Network
2015 17th UKSIM-AMSS International Conference on Modelling and Simulation Online Localisation of Partial Discharge Using n Parameters in Medium Voltage Cable Network Tauqeer Ahmed Shaikh, Abdulrehman Al-Arainy,
More informationEFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento
Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of
More informationComparison of measurement methods for partial discharge measurement in power cables
Comparison of measurement methods for partial discharge measurement in power cables L. W. van Veen Supervisor: Prof. dr. J. J. Smit Daily supervisor: Dr.ir. A. Rodrigo Mor April 2014 INTELLIGENT ELECTRICAL
More informationPartial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink
ISSN (Online) 2321 24 Vol. 4, Issue 6, June 2 Partial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink C Sunil kumar 1, Harisha K S 2, Gouthami N 3, Harshitha V 4, Madhu C Assistant Professor,
More informationEffect of coupling conditions on ultrasonic echo parameters
J. Pure Appl. Ultrason. 27 (2005) pp. 70-79 Effect of coupling conditions on ultrasonic echo parameters ASHOK KUMAR, NIDHI GUPTA, REETA GUPTA and YUDHISTHER KUMAR Ultrasonic Standards, National Physical
More informationDesign of Meander Antenna for UHF Partial Discharge Detection of Transformers
Sensors & Transducers 204 by IFSA Publishing, S. L. http://www.sensorsportal.com Design of Meander Antenna for UHF Partial Discharge Detection of Transformers Mengjie Li, Chuangxin Guo, 2 Ziping Peng College
More informationA Reflectometer for Cable Fault Location with Multiple Pulse Reflection Method
2014 by IFSA Publishing, S. L. http://www.sensorsportal.com A Reflectometer for Cable Fault Location with Multiple Pulse Reflection Method Zheng Gongming Electronics & Information School, Yangtze University,
More informationA STUDY ON THE PERFORMANCE OF IMPEDANCE MATCHING CIRCUIT IN PARTIAL DISCHARGE MEASURING SYSTEM
BORNEO SCIENCE 30: MARCH 2012 A STUDY ON THE PERFORMANCE OF IMPEDANCE MATCHING CIRCUIT IN PARTIAL DISCHARGE MEASURING SYSTEM 1 Wan Akmal Izzati W. M. Zawawi, 2 Mohamad Zul Hilmey Makmud, & 3 Yanuar Z.
More informationUHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES
UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES D. Götz*, H.T. Putter* *Megger Germany INTRODUCTION High voltage termintions are essential components in high voltage cable
More informationINVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES
INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES Gonzalo MAIZ, Iberdrola Distribución, (Spain), gmaiz@iberdrola.es Armando RODRIGO, Instituto
More informationInternational Conference on Information Sciences, Machinery, Materials and Energy (ICISMME 2015)
International Conference on Information Sciences Machinery Materials and Energy (ICISMME 2015) Research on the visual detection device of partial discharge visual imaging precision positioning WANG Tian-zheng
More informationBY JASON SOUCHAK, Megger
IMPROVING SYSTEM RELIABILITY WITH OFFLINE PD TESTING BY JASON SOUCHAK, Megger Partial discharge (PD) testing is a new generation of diagnostic testing for medium- and high-voltage underground power cable
More informationprocess has few stages and is highly repeatable. Excellent mechanic properties and electro-magnetic compatibility. Planar design gives the height lowe
PARTIAL DISCHARGE IN PLANAR TRANSFORMER Ing. Anar MAMMADOV, Doctoral Degreee Programme (1) Dept. of Microelectronics, FEEC, BUT E-mail: xmamed00@stud.feec.vutbr.cz Supervised by Dr. Jaroslav Boušek ABSTRACT
More informationON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS
ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS Pantelis D. AGORIS 1, Sander MEIJER 1, Edward GULSKI 1, Johan J. SMIT 1, A. Jos L.M. KANTERS 2 1 Delft University of Technology - The Netherlands 2 TenneT
More informationApplication of Wavelet Transform Technique for Extraction of Partial Discharge Signal in a Transformer
International Journal of Engineering Studies. ISSN 0975-6469 Volume 8, Number 2 (2016), pp. 247-258 Research India Publications http://www.ripublication.com Application of Wavelet Transform Technique for
More informationThe importance of partial discharge testing throughout the development and operation of power transformers
The importance of partial discharge testing throughout the development and operation of power transformers Ulrike Broniecki OMICRON Energy Solutions GmbH, Berlin Power transformers are exposed to intense
More informationPARTIAL DISCHARGE DETECTION - AN OVERVIEW
PARTIAL DISCHARGE DETECTION - AN OVERVIEW 1 MR. N. J. PATEL, 2 PROF. K. K. DUDANI, 3 PROF. A. K. JOSHI 1 M.E. [Power System] P.G. Student, Department of Electrical Engineering, L. E. College of Engineering,
More informationNew Techniques for the Monitoring of Transformer Condition
New Techniques for the Monitoring of Transformer Condition Thomas Prevost OMICRON electronics USA IEEE T&D Conference Chicago, Illinois April 17, 2014 Agenda Monitoring Expectations & Needs Bushing Monitoring
More informationNJ. ISBN (2017) , /URSIGASS
Jaber, A. and Lazaridis, P. and Saeed, B. and Mather, P. and Vieira, M. F. Q. and Atkinson, R. and Tachtatzis, C. and Iorkyase, E. and Judd, M. and Glover, I. A. (2017) Diagnostic potential of free-space
More informationPartial Discharge Patterns in High Voltage Insulation
22 IEEE International Conference on Power and Energy (PECon), 2-5 December 22, Kota Kinabalu Sabah, Malaysia Partial Discharge Patterns in High Voltage Insulation Hazlee Illias, Teo Soon Yuan, Ab Halim
More informationAfrica Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound
Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences
More informationRESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS
RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS Authored by: Sanjay Srivastava, Chief Engineer (HE&RM), Rakesh Kumar, Director (HE&RM), R.K. Jayaswal, Dy. Director (HE&RM)
More informationEvaluation and Limitations of Corona Discharge Measurements An Application Point of View
Evaluation and Limitations of Corona Discharge Measurements An Application Point of View P. Mraz, P. Treyer, U. Hammer Haefely Hipotronics, Tettex Instruments Division 2016 International Conference on
More informationFurther Experience in the Use of Existing RTDs in Windings of Motors and Generators for the Measurement of Partial Discharges
Further Experience in the Use of Existing RDs in Windings of Motors and Generators for the Measurement of Partial Discharges Claude Kane Eaton Electrical Predicative Diagnostics 5421 Feltl Road Suite 190
More informationStatistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage
Journal of Energy and Power Engineering 9 () 3-3 doi:.7/93-897/.3. D DAVID PUBLISHIG Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage
More informationChapter 5. Signal Analysis. 5.1 Denoising fiber optic sensor signal
Chapter 5 Signal Analysis 5.1 Denoising fiber optic sensor signal We first perform wavelet-based denoising on fiber optic sensor signals. Examine the fiber optic signal data (see Appendix B). Across all
More informationComparison of capacitive and inductive sensors designed for partial discharges measurements in electrical power apparatus
Comparison of capacitive and inductive sensors designed for partial discharges measurements in electrical power apparatus Michał Kunicki 1,* 1 Opole University of Technology, ul. Prószkowska 76, 45-758
More informationPower Frequency Withstand Voltage On-site testing of 400 kv GIS
Power Frequency Withstand Voltage On-site testing of 400 kv GIS D. Anaraki Ardakani, A. Omidkhoda, M. Solati High Voltage Engineering Center ACECR Tehran, Iran Da_ardakani@yahoo.com Paper Reference Number:
More information3.003 Lab 3 Part A. Measurement of Speed of Light
3.003 Lab 3 Part A. Measurement of Speed of Light Objective: To measure the speed of light in free space Experimental Apparatus: Feb. 18, 2010 Due Mar. 2, 2010 Components: 1 Laser, 4 mirrors, 1 beam splitter
More informationWAVELET TRANSFORM ANALYSIS OF PARTIAL DISCHARGE SIGNALS. B.T. Phung, Z. Liu, T.R. Blackburn and R.E. James
WAVELET TRANSFORM ANALYSIS OF PARTIAL DISCHARGE SIGNALS B.T. Phung, Z. Liu, T.R. Blackburn and R.E. James School of Electrical Engineering and Telecommunications University of New South Wales, Australia
More informationEQUIPMENT AND MOBILE LABORATORIES FOR NDT AND DIAGNOSTICS OF UNDERGROUND COMMUNICATION LINES.
17th World Conference on Nondestructive Testing, 25-28 Oct 2008, Shanghai, China EQUIPMENT AND MOBILE LABORATORIES FOR NDT AND DIAGNOSTICS OF UNDERGROUND COMMUNICATION LINES. Vasily N. KOLTSOV 1, Yury
More informationTransient calibration of electric field sensors
Transient calibration of electric field sensors M D Judd University of Strathclyde Glasgow, UK Abstract An electric field sensor calibration system that operates in the time-domain is described and its
More informationSignal and Noise Measurement Techniques Using Magnetic Field Probes
Signal and Noise Measurement Techniques Using Magnetic Field Probes Abstract: Magnetic loops have long been used by EMC personnel to sniff out sources of emissions in circuits and equipment. Additional
More informationPartial Discharge Detection of High Voltage Switchgear Using a Ultra High Frequency Sensor
TRANSACTIONS ON ELECTRICAL AND ELECTRONIC MATERIALS Vol. 14, No. 4, pp. 211-215, August 25, 2013 Regular Paper pissn: 1229-7607 eissn: 2092-7592 DOI: http://dx.doi.org/10.4313/teem.2013.14.4.211 Partial
More informationExperimental Observation of RF Radiation Generated by an Explosively Driven Voltage Generator
Naval Research Laboratory Washington, DC 20375-5320 NRL/FR/5745--05-10,112 Experimental Observation of RF Radiation Generated by an Explosively Driven Voltage Generator MARK S. RADER CAROL SULLIVAN TIM
More informationDetection of Obscured Targets: Signal Processing
Detection of Obscured Targets: Signal Processing James McClellan and Waymond R. Scott, Jr. School of Electrical and Computer Engineering Georgia Institute of Technology Atlanta, GA 30332-0250 jim.mcclellan@ece.gatech.edu
More informationGFT1504 4/8/10 channel Delay Generator
Features 4 independent Delay Channels (10 in option) 100 ps resolution (1ps in option) 25 ps RMS jitter (channel to channel) 10 second range Channel Output pulse 6 V/50 Ω, 3 ns rise time Independent control
More information3 - Using the Telecoms-Trainer 101 to model equations
Name: Class: 3 - Using the Telecoms-Trainer 101 to model equations Experiment 3 Using the Telecoms-Trainer 101 to model equations Preliminary discussion This may surprise you, but mathematics is an important
More informationSources of transient electromagnetic disturbance in medium voltage switchgear
Sources of transient electromagnetic disturbance in medium voltage switchgear Dennis Burger, Stefan Tenbohlen, Wolfgang Köhler University of Stuttgart Stuttgart, Germany dennis.burger@ieh.uni-stuttgart.de
More informationMPD 600. High-End Measurement and Analysis System for Partial Discharges (PD)
MPD 600 High-End Measurement and Analysis System for Partial Discharges (PD) Partial Discharge Analysis The MPD 600 partial discharge analysis system is a precise and modular high-end toolbox for detecting,
More informationPartial Discharge Measurements on 110kV Current Transformers. Case Study. Results
2016 International Conference on Electrical Engineering and Automation (ICEEA 2016) ISBN: 978-1-60595-407-3 Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results Cristian DAN
More informationProduct Datasheet P MHz RF Powerharvester Receiver
GND GND GND NC NC NC Product Datasheet DESCRIPTION The Powercast P2110 Powerharvester receiver is an RF energy harvesting device that converts RF to DC. Housed in a compact SMD package, the P2110 receiver
More informationHYUNDAI HEAVY INDUSTRIES CO. LTD
HiPDS-G HYUNDAI HEAVY INDUSTRIES CO. LTD Hyundai Intelligent Preventive Diagnostic System for GIS User s Manual Version: 1.20 / 2010.02.10 File: HiPDS-G_UsersManual(ENG).doc Hyundai Heavy Industry HiPDS-G
More informationApplication of HFCT and UHF Sensors in On-Line Partial Discharge Measurements for Insulation Diagnosis of High Voltage Equipment
Sensors 2015, 15, 7360-7387; doi:10.3390/s150407360 Article OPEN ACCESS sensors ISSN 1424-8220 www.mdpi.com/journal/sensors Application of HFCT and UHF Sensors in On-Line Partial Discharge Measurements
More informationUWB Type High Power Electromagnetic Radiating System for Use as an Intentional EMI Source
(J) 3/23/217 Abstract: UWB Type High Power Electromagnetic Radiating System for Use as an Intentional EMI Source Bhosale Vijay H. and M. Joy Thomas Pulsed Power and EMC Lab, Department of Electrical Engineering,
More informationNOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV
NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV Paul P. SEITZ, Seitz Instruments AG, (Switzerland), pps@seitz-instruments.ch Ben QUAK, Seitz Instruments AG, (Switzerland),
More informationVLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing
Cable Testing & Diagnostics Solutions for Medium Voltage Networks (1 kv - 36 kv) VLF Partial Discharge DC DAC tandelta Cable Testing Cable Diagnostics? There are two main applications for cable testing:
More information