APPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS
|
|
- Patricia Page
- 6 years ago
- Views:
Transcription
1 APPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS David Larochelle NDB Technologies
2 Reasons leading to acoustic testing are different weather it is a manufacturing or field environment
3 Trigger for field testing DGA IEEE C Duval Triangle
4 Trigger for field testing Acoustic localization becomes the next thing to know for decision making
5 Possible Actions No Actions (non critical) Onsite repair Lower the load Replacement
6 Field Challenges Mechanical noise o Pumps o Fans o Core vibration o Rain Electrical noise o Corona o Radio Frequencies Physical restrictions o Radiators o Control Cabinets o Unknown internal structure Others o No control on voltage applied
7 Field Challenges Acoustic waves from PD are often very small in amplitude, even lower that noise baseline Combining electrical signals with acoustic signals enables noise reduction methods
8 PrPd Phase Resolved Partial Discharge PrPd Gives an overview of electrical or acoustic activity Acoustic pattern Electric pattern
9 Sensors RFCT : Sensitive to small current peaks created by PD Pros : Convenient to install Cons : Sensitive to electrical noise from the surroundings
10 Sensors UHF : Sensitive to electromagnetic emissions from PD UHF Antenna is inserted inside the transformer tank Pros : Immunity to environment (Uses tank as faraday cage) Cons : Installation requires fittings that can be different in each transformer.
11 Phase Angle Windowing Multiple PrPd patterns can be seen Localization efficiency depends on the ability to focus on one pattern at a time
12 Phase Angle Window Phase angle can be used to focus on one pattern at a time
13 Phase Angle Window Phase angle can be used to focus on one pattern at a time
14 Phase Angle Window Phase angle can be used to focus on one pattern at a time
15 Phase Angle Window Phase angle can be used to focus on one pattern at a time
16 Averaging Accumulate a number of waveforms Adding all waveforms together (point to point) Reduces noise while PD signal will remain.
17 Averaging Example Key is synchronization of each waveform. Propagation from PD source to the sensor is repeatable.
18 Averaging Example Let s take a simulated waveforms And add noise to it
19 Averaging Example Average by 2 +
20 Averaging Example Average by 4 +
21 Averaging Example Original signal Average by 8 Average by 64 Average by 1024
22 Averaging Example Real life example of averaging efficiency on a single phase power transformer Acoustic background noise was greater than the acoustic PD amplitude Use electrical PD event as the synchronization source for the overlay of acoustic signals.
23 Averaging = 1 (no averaging) Averaging The noise is high, there is no indication of any acoustic wave.
24 Averaging = 4 Averaging Noise is still high, but a peak can be distinguished.
25 Averaging = 32 Averaging The waveform is still noisy, but it is clear that an acoustic wave was captured.
26 Averaging = 1024 Averaging The noise level is very low. The acoustic waveform is clear, and its time of arrival can be easily found.
27 Averaging Synchronization can be achieved with one acoustic signals if electrical signal is too noisy Synchronization made on acoustic channel (upper blue waveform) Electrical PD was highlighted from noise
28 Case Study DGA indicating severe overheating Gases increasing for the past 3 years
29 RFCT was placed on transformer ground Case Study
30 Case Study Averaged acoustic signal (1024)
31 Localization pointed to a lead connection Case Study
32 Case Study Motive: DGA increase indicating PD.
33 RFCT clamp was used to acquire electrical signal Case Study
34 Acoustic peaks show relation between acoustic and network frequency Case Study
35 Sensors are gradually moved toward the source of PD Case Study Acoustic Waves are acquired and denoised
36 Acoustic provided localization area Case Study
37 Case Study At this point, given the relatively slow rate of gassing and confirmation of a source of PD, it was decided to put the transformer back into service while options were weighted as to how to resolve the issue. Before doing so, the inspection cover was opened to see if the PD source could be visually located.
38 Case Study There were a few small spots in the lead insulation that the technician described as mushy. These spots were reinforced with insulating material. The unit was closed and put back into service.
39 Case Study a few days after energization, the transformer tripped off causing an unplanned outage. Failure investigation showed a deterioration of the insulation between the core and the X1 conductor, in the same area given by acoustic waves.
40 Case Study
41 Case Study In a manufacturing environment, the induced test will confirm if a repair was successful If an onsite repair was done, another acoustic investigation should be done, trying to get the before and after acoustic test.
PD Solutions. On-Line PD Measurement Devices
On-Line PD Measurement Devices 1. Longshot Device (see Figure 1) The measurement system applied is based around the wideband (0-400 MHz) HVPD- Longshot partial discharge test unit which utilizes a high-speed
More informationPartial Discharge Monitoring of Power Transformers by UHF Sensors
Partial Discharge Monitoring of Power Transformers by UHF Sensors S. Tenbohlen 1, M. Siegel², M. Beltle² 1 Institute of Power Transmission and High Voltage Technology (IEH), University of Stuttgart Pfaffenwaldring
More informationAutomated PRPD Pattern Analysis using Image Recognition
International Journal on Electrical Engineering and Informatics Volume 4, Number 3, October 2012 Automated PRPD Pattern Analysis using Image Recognition A. Müller, M. Beltle and S. Tenbohlen Institute
More informationAdvancements in online partial discharge monitoring and assessment of MV through EHV Substation assets
Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets Abstract: For decades it has been recognized that partial discharge assessment is an excellent method
More informationTECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets
TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets Who we are TECHIMP is one of the leading providers of Condition Assessment Services Data Acquisition and Test Equipment
More informationPDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics
PDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics CASE STUDY 1 (Doble Client Conference 2011, ACCA committee meeting) Dissolved Gas Analysis (DGA)
More informationThe importance of partial discharge testing throughout the development and operation of power transformers
The importance of partial discharge testing throughout the development and operation of power transformers Ulrike Broniecki OMICRON Energy Solutions GmbH, Berlin Power transformers are exposed to intense
More informationCHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN
75 CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 5.1 INTRODUCTION Partial Discharge (PD) detection is an important tool for monitoring insulation conditions in high voltage (HV) devices in power systems.
More informationAcoustic Emission in power transformers. Ajusco 15, Colonia Portales, Delegación Benito Juárez, C.P , México, D.F.
Acoustic Emission in power transformers 1 More expensive equipment in the substation Many years of operation First indication of a problem: Dissolved Gases Begin investigation to determine the origin of
More informationInternational Conference on Information Sciences, Machinery, Materials and Energy (ICISMME 2015)
International Conference on Information Sciences Machinery Materials and Energy (ICISMME 2015) Research on the visual detection device of partial discharge visual imaging precision positioning WANG Tian-zheng
More informationPARTIAL DISCHARGE MEASUREMENT
PARTIAL DISCHARGE MEASUREMENT Partial Discharges are small electrical sparks which occur predominantly at insulation imperfection. It is the phenomenon which occurs in the insulation on application of
More informationAfrica Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound
Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences
More informationMONTRANO. Continuous monitoring system for power transformers
MONTRANO Continuous monitoring system for power transformers Condition monitoring to extend transformer life Knowing the dielectric condition of insulation is vital Dielectric flashover of insulation in
More informationKnowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators
Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery Application of EMI Diagnostics to Hydro Generators James Timperley Doble Global Power Services Columbus, Ohio jtimperley@doble.com
More informationPractical Experience in On-Line Partial Discharge Measurements of MV Switchgear Systems
Practical Experience in On-Line Partial Discharge Measurements of MV Switchgear Systems Z. Berler, I. Blokhintsev, A. Golubev, G. Paoletti, V. Rashkes, A. Romashkov Cutler-Hammer Predictive Diagnostics
More informationDiagnostic testing of cast resin transformers
Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com
More informationPartial Discharge Detection of High Voltage Switchgear Using a Ultra High Frequency Sensor
TRANSACTIONS ON ELECTRICAL AND ELECTRONIC MATERIALS Vol. 14, No. 4, pp. 211-215, August 25, 2013 Regular Paper pissn: 1229-7607 eissn: 2092-7592 DOI: http://dx.doi.org/10.4313/teem.2013.14.4.211 Partial
More informationCase Studies of Electric Power Equipment Diagnostics Using Acoustic Emission
17th World Conference on Nondestructive Testing, 25-28 Oct 2008, Shanghai, China Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission Oswaldo G. SANTOS FILHO 1, Sergio L. ZAGHETTO
More informationON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS
ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS Pantelis D. AGORIS 1, Sander MEIJER 1, Edward GULSKI 1, Johan J. SMIT 1, A. Jos L.M. KANTERS 2 1 Delft University of Technology - The Netherlands 2 TenneT
More informationThe Weidmann Conference The Aging of America s Transformers
The Weidmann Conference 2006 The Aging of America s Transformers by Jon L. Giesecke, Director, (610) 518-1615 jlgassociatesllc@yahoo.com How Old is Old? The aging of the electrical infrastructure in the
More informationInternational Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer
Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 7, July -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 Comparison
More informationPARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS
PARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS by K.K.JEMBU KAILAS and W. ADITHYA KUMAR L&T CONSTRUCTION L&T CONSTRUCTION KKJK@LNTECC.COM
More informationCHAPTER 3 ACOUSTIC EMISSION TECHNIQUE FOR DETECTION AND LOCATION OF PD
63 CHAPTER 3 ACOUSTIC EMISSION TECHNIQUE FOR DETECTION AND LOCATION OF PD 3.1 INTRODUCTION PD measurements on high-voltage equipment, e.g. transformers, could be grouped into two major tasks. First, evidence
More informationPARTIAL DISCHARGE DETECTION - AN OVERVIEW
PARTIAL DISCHARGE DETECTION - AN OVERVIEW 1 MR. N. J. PATEL, 2 PROF. K. K. DUDANI, 3 PROF. A. K. JOSHI 1 M.E. [Power System] P.G. Student, Department of Electrical Engineering, L. E. College of Engineering,
More informationPartial Discharge Measurements on 110kV Current Transformers. Case Study. Results
2016 International Conference on Electrical Engineering and Automation (ICEEA 2016) ISBN: 978-1-60595-407-3 Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results Cristian DAN
More informationSAMPLE. Determining the health of your power transformer begins with Transformer Clinic s SAMPLE testing programs.
Keep Powering On SAMPLE Determining the health of your power transformer begins with Transformer Clinic s SAMPLE testing programs. Overheating, arcing, partial discharge, and other active or slow-evolving
More informationThe R Portable Device for Partial Discharge Measurement and Analysis in High Voltage Equipment Insulation
The R2200 - Portable Device for Partial Discharge Measurement and Analysis in High Voltage Equipment Insulation DIMRUS Ltd. www.dimrus.ru 1 The R2200 Device is for Effective Partial Discharge (PD) Measurement
More informationDGA Interpretation Example DGA Start-Up Program Completed and Routine DGA Program Started
1 2 DGA Start-Up Program Completed and Routine DGA Program Started DGA Performed Compute Delta Value Update Rate Evaluation All Gases < Table 1 All Deltas < Table 3 All Rates < Table 4 DGA Status 1 Continue
More informationTHE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.
THE POWER OF LIFE WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk. Mr. Neal Yang Pro.E.E. Engineer About Us The flaw of dielectric material
More informationElectrical Equipment Condition Assessment
Feature Electrical Equipment Condition Assessment Using On-Line Solid Insulation Sampling Importance of Electrical Insulation Electrical insulation plays a vital role in the design and operation of all
More informationOpen Access Application of Partial Discharge Online Monitoring Technology in ± 660kV Converter Transformer
Send Orders for Reprints to reprints@benthamscience.ae 784 The Open Automation and Control Systems Journal, 2015, 7, 784-791 Open Access Application of Partial Discharge Online Monitoring Technology in
More informationWhy partial discharge testing makes good sense
Why partial discharge testing makes good sense PD measurement and analysis have proven to be reliable for detecting defects in the insulation system of electrical assets before major damage or a breakdown
More informationONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM,
ONLINE OFFLINE VERSUS FEATURE PARTIAL DISCHARGE TESTING FOR CABLE ASSESSMENT B Y WIL L IAM H IG INBOT H AM, EA Technology, LLC Medium voltage cables have three distinct phases to their lifecycle: (1) new
More informationSoftware System for Finding the Incipient Faults in Power Transformers
Software System for Finding the Incipient Faults in Power Transformers Nikolina Petkova Technical University of Sofia, Department of Theoretical Electrical Engineering, 1156 Sofia, Bulgaria Abstract In
More informationPARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES
PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES Engr. IÑIGO V. ESCOPETE, JR. ITC Level 2 Certified Thermographer PHIL-NCB NDT-UT Level 2 Partial Discharge testing is a Condition Based Maintenance tool
More informationNETWORK INNOVATION COMPETITION ANGLE-DC PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT
NETWORK INNOVATION COMPETITION PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT NOVEMBER 17 Version: 1.0 Authored by: Andrew Moon Engineering Consultant and Project Manager Kevin Smith Lead
More informationBY JASON SOUCHAK, Megger
IMPROVING SYSTEM RELIABILITY WITH OFFLINE PD TESTING BY JASON SOUCHAK, Megger Partial discharge (PD) testing is a new generation of diagnostic testing for medium- and high-voltage underground power cable
More informationThe Generators and Electric Motor Monitoring and Diagnostics Systems
The Generators and Electric Motor Monitoring and Diagnostics Systems MDR and PGU-DM 1 The «MDR» - Motor Diagnostics Relay the Universal System for Insulation Monitoring in Electric Machines PD-Monitor
More informationA1-209 EXPERIENCES IN IDENTIFICATION OF PARTIAL DISCHARGE PATTERNS IN LARGE HYDROGENERATORS
21, rue d'artois, F-75008 Paris http://www.cigre.org A1-209 Session 2004 CIGRÉ EXPERIENCES IN IDENTIFICATION OF PARTIAL DISCHARGE PATTERNS IN LARGE HYDROGENERATORS CARLOS AZUAJE* WILLIAM TORRES C.V.G.
More informationThe Application of Partial Discharge Measurement and Location on CGIS
International Journal on Electrical Engineering and Informatics Volume 4, Number 3, October 2012 The Application of Partial Discharge Measurement and Location on CGIS Min-Yen Chiu¹, Keng-Wei Liang¹, Chang-Hsing
More informationAutotransformer Condition Monitoring Systems
Autotransformer Condition Monitoring Systems The Bidders shall offer separately the following systems of par.1 Integrated Condition Monitoring System and par.2 UHF PD Monitoring System. Two systems following
More informationIN ELECTRICAL ENGINEERING - I C M E T CRAIOVA
Taking into account that power transformer is the major item of equipment in power systems, its correct operation is vital to system operation. It is well known that transformer failures are sometimes
More informationEvaluation of Partial Discharge in Power Transformers by Acoustic Emission Method and Propagation Modeling of Acoustic Signal
Evaluation of Partial Discharge in Power Transformers by Acoustic Emission Method and Propagation Modeling of Acoustic Signal Abdolrahman Peimankar, Arman Kazemi, and Seyed Mohammad Taghi Bathaee Khaje
More informationBest Practice Reducing The Risk of Arc Flash Cross Over
Best Practice Reducing The Risk of Arc Flash Cross Over 1 2 Electrical Systems Are Critical 3 Why Do We Complete Electrical Maintenance Energized?? 4 Which Bulb Is Not Working?? 5 Functioning Correctly
More informationPULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS
PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS Anne Pfeffer 1*, Stefan Tenbohlen 1 and Stefan Kornhuber 2 1 Institute of Power Transmission and High Voltage Technology, Pfaffenwaldring
More informationTECHIMP Power Transformer Monitoring
TECHIMP Power Transformer Monitoring Kontakt: Martin Hesse Techimp Germany GmbH i.g. E-Mail: mhesse@techimp.com Tel.: +49 5724 391 007 Mobil: +49 170 2364 735 PD Monitoring of Power Transformers Power
More informationABB Power Products Service
Raben Naidoo, Technology days, May 21-22th, 2014, Cape Town, South Africa, Enhanced availability of transformers via transformer remote monitoring - TEC ABB Power Products Service Why a session on availability?
More informationApplication Note. Detection of Partial Discharge Using Ultrasound. Detection of Partial Discharge Using Ultrasound. Problem. iriss.
Detection of Partial Discharge Using Ultrasound Problem In electrical systems, especially above 1,000 Volts, sufficient and properly maintained equipment insulation helps ensure equipment longevity. However,
More informationTransformer Factory Testing
Transformer Factory Testing John J. Foschia Test Engineer John.Foschia@spx.com September 2018 Reasons for Testing Compliance with user specifications Assessment of quality and reliability Verification
More informationPartial Discharge Monitoring and Diagnosis of Power Generator
Partial Discharge Monitoring and Diagnosis of Power Generator Gao Wensheng Institute of High Voltage & insulation tech. Electrical Eng. Dept., Tsinghua University Wsgao@tsinghua.edu.cn Currently preventive
More informationEquipment under Measurement: 6.6kV Alstom AIS Switchgear. Date of Measurement: 10 th August 2017
Case History - 24: Online PD measurement using TEV, Ultrasonic Inductive UHF & HFCT Sensors Equipment under Measurement: 6.6kV Alstom AIS Switchgear Date of Measurement: 10 th August 2017 Sensor Used:
More informationPD Diagnostic Applications and TechImp solutions
PD Diagnostic Applications and TechImp solutions Condition Assessment Solutions for Electrical Systems. PD based innovative tools for the Condition Based Maintenance. MD-04.05.004 - rev. 00-29/08/2006
More informationParameters influencing Partial Discharge Measurements and their Impact on Diagnosis, Monitoring and Acceptance Tests of Power Transformers
21, rue d Artois, F-75008 PARIS A2-111 CIGRE 2016 http : //www.cigre.org Parameters influencing Partial Discharge Measurements and their Impact on Diagnosis, Monitoring and Acceptance Tests of Power Transformers
More informationIRIS POWER TGA-B. Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors
IRIS POWER TGA-B Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors We have not found another test method that produces as much decision support data for generator
More informationImproving Distribution Circuit Performance without Circuit Rebuilds. John Lauletta, CEO
Improving Distribution Circuit Performance without Circuit Rebuilds John Lauletta, CEO Maintenance Strategies Reliability Centered Maintenance Reactive Maintenance (Run To Failure) Preventive Maintenance
More informationBasics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015
Basics of Partial Discharge Prepared for 2015 Phenix RSM Meeting January 2015 Definitions and History Standard Definitions Fundamentally, what is a Partial Discharge An electric discharge which only partially
More informationPractical aspects of PD localization for long length Power Cables
Practical aspects of PD localization for long length Power Cables M. Wild, S. Tenbohlen University of Stuttgart Stuttgart, Germany manuel.wild@ieh.uni-stuttgart.de E. Gulski, R. Jongen onsite hv technology
More informationApplication of HFCT and UHF Sensors in On-Line Partial Discharge Measurements for Insulation Diagnosis of High Voltage Equipment
Sensors 2015, 15, 7360-7387; doi:10.3390/s150407360 Article OPEN ACCESS sensors ISSN 1424-8220 www.mdpi.com/journal/sensors Application of HFCT and UHF Sensors in On-Line Partial Discharge Measurements
More informationGENERATOR TESTING APPLICATION GUIDE. reliable. precision.
GENERATOR TESTING APPLICATION GUIDE www.haefely-hipotronics.com reliable. precision. 2 GENERATOR TESTING CONTENTS Product Line Overview 3 AC Hipot Testing 4 Partial Discharge Measurement 5 DC Hipot Testing
More informationCENG4480 Lecture 04: Analog/Digital Conversions
CENG4480 Lecture 04: Analog/Digital Conversions Bei Yu byu@cse.cuhk.edu.hk (Latest update: October 3, 2018) Fall 2018 1 / 31 Overview Preliminaries Comparator Digital to Analog Conversion (DAC) Analog
More informationPartial Discharge Signal Detection by Piezoelectric Ceramic Sensor and The Signal Processing
Journal of Electroceramics, 13, 487 492, 2004 C 2004 Kluwer Academic Publishers. Manufactured in The Netherlands. Partial Discharge Signal Detection by Piezoelectric Ceramic Sensor and The Signal Processing
More informationDesign of Meander Antenna for UHF Partial Discharge Detection of Transformers
Sensors & Transducers 204 by IFSA Publishing, S. L. http://www.sensorsportal.com Design of Meander Antenna for UHF Partial Discharge Detection of Transformers Mengjie Li, Chuangxin Guo, 2 Ziping Peng College
More informationPERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE
PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE Fred STEENNIS, KEMA, (the Netherlands), fred.steennis@kema.com Peter VAN DER WIELEN, KEMA,
More informationPrepared by Mick Maytum
IEC Technical Committee 109: Standards on insulation co-ordination for low-voltage equipment Warning Prepared by Mick Maytum mjmaytum@gmail.com The document content is of a general nature only and is not
More informationTECHNICAL REQUIREMENTS FOR ELECTROMAGNETIC DISTURBANCES EMITTED FROM LIGHTING EQUIPMENT INSTALLED IN TELECOMMUNICATION CENTERS
TR550004 TECHNICAL REQUIREMENTS FOR ELECTROMAGNETIC DISTURBANCES EMITTED FROM LIGHTING EQUIPMENT INSTALLED IN TELECOMMUNICATION CENTERS TR NO. 174001 EDITION 2.1 September 3 rd, 2018 Nippon Telegraph and
More informationSoftware for Partial Discharge and Localization
48 PIERS Proceedings, Taipei, March 25 28, 2013 Software for Partial Discharge and Localization M. Cap, P. Drexler, P. Fiala, and R. Myska Department of Theoretical and Experimental Electrical Engineering
More information- Continuous real-time measurement and PD trend analysis; not multiplexed data collection.
QTMS The transformer monitor shall provide data integration platform, cooling supervision & monitoring. User configurable without need of a technician, a 100% configurable to specific customer requirement.
More informationSuppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and Waveform Characteristics
Journal of Energy and Power Engineering 9 (215) 289-295 doi: 1.17265/1934-8975/215.3.8 D DAVID PUBLISHING Suppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and
More informationPARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER
PARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER N. R. Bhasme 1 and Bhushan Salokhe 2 1 Associate Prof., 2 M.E. Student, Dept. of Electrical Engg., Govt. College of Engineering
More informationAnalysis of Propagation Paths of Partial Discharge Acoustic Emission Signals
Analysis of Propagation Paths of Partial Discharge Acoustic Emission Signals Prathamesh Dhole, Tanmoy Sinha, Sumeet Nayak, Prasanta Kundu, N.K.Kishore Abstract Transformers are one of the most important
More informationLogic families (TTL, CMOS)
Logic families (TTL, CMOS) When you work with digital IC's, you should be familiar, not only with their logical operation, but also with such operational properties as voltage levels, noise immunity, power
More informationPartial discharge diagnostics on very long and branched cable circuits
11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA
More informationFrequency Spectrum Analysis of Electromagnetic Waves Radiated by
Frequency Spectrum Analysis of Electromagnetic Waves Radiated by Electrical Discharges HYEON-KYU CHA, SUN-JAE KIM, DAE-WON PARK, GYUNG-SUK KIL Division of Electrical and Electronics Engineering Korea Maritime
More informationTransient calibration of electric field sensors
Transient calibration of electric field sensors M D Judd University of Strathclyde Glasgow, UK Abstract An electric field sensor calibration system that operates in the time-domain is described and its
More informationOptimize Outage Management and Improve Underground System Reliability
SEL-8301 Underground Distribution Sensor Optimize Outage Management and Improve Underground System Reliability Line current measurement accuracy of 1.5 percent allows for more effective switching decisions
More information1409. Comparison study between acoustic and optical sensors for acoustic wave
1409. Comparison study between acoustic and optical sensors for acoustic wave Malik Abdulrazzaq Alsaedi Department of Electrical, Faculty of Engineering, University of Misan, Amarah, Iraq E-mail: maliksaady@yahoo.com
More informationHZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL. Huazheng Electric Manufacturing(Baoding) Co.,Ltd
HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL Huazheng Electric Manufacturing(Baoding) Co.,Ltd Safety Terms and Symbols This manual may contain the terms: Warning! Indicate the conditions
More informationUnderwater Spark Sources: Some experimental information.
Author: Dr J Nedwell SUBACOUSTECH Ltd Chase Mill Winchester Road Bishop s Waltham Hampshire SO32 1AH Tel:+44 (0) 1489 891850 Fax:+44 (0) 1489 891851 email: subacoustech@subacoustech.com website: www.subacoustech.com
More informationIRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.
IRIS POWER PDTracII Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear. We have not found another test method that produces as much
More informationBenefits of SFRA - Case Studies
6 th International Conference on Large Power Transformers- Modern Trends Benefits of SFRA - Case Studies B B Ahir Gujarat Energy Transmission Corporation Limited 1 Outline Condition Monitoring in GETCO
More informationCHAPTER MAINTENANCE AND TROUBLESHOOTING. In This Chapter... Maintenance and Inspection Troubleshooting...6 3
CHAPTER MAINTENANCE AND 6 TROUBLESHOOTING In This Chapter... Maintenance and Inspection.................6 2 Monthly Inspection:..................................6 2 Annual Inspection....................................6
More informationThe Influence of Antenna Positioning Errors on the Radio-Frequency Localization of Partial Discharge Sources
proceedings Proceedings The Influence of Antenna Positioning Errors on the Radio-Frequency Localization of Partial Discharge Sources José Manuel Fresno,, Guillermo Robles, Brian G. Stewart and Juan Manuel
More informationHigh Sensitivity Interferometric Detection of Partial Discharges for High Power Transformer Applications
High Sensitivity Interferometric Detection of Partial Discharges for High Power Transformer Applications Carlos Macià-Sanahuja and Horacio Lamela-Rivera Optoelectronics and Laser Technology group, Universidad
More informationOn-line Partial Discharge Assessment and Monitoring of MV to EHV Cables
On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables William Higinbotham, Neil Davies and Victor Chan EA Technology LLC, New Jersey; USA, EA Technology Pty Ltd, Brisbane Australia; EA
More informationTest Specification for Type Approval
A2 (1991) (Rev.1 1993) (Rev.2 1997) (Rev. 2.1 July 1999) (Rev.3 May 2001) (Corr.1 July 2003) (Rev.4 May 2004) (Rev.5 Dec 2006) (Rev.6 Oct 2014) Test Specification for Type Approval.1 General This Test
More informationPartial Discharge Classification Using Acoustic Signals and Artificial Neural Networks
Proc. 2018 Electrostatics Joint Conference 1 Partial Discharge Classification Using Acoustic Signals and Artificial Neural Networks Satish Kumar Polisetty, Shesha Jayaram and Ayman El-Hag Department of
More informationEVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE
EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE Ju-Chu Hsieh 1, Cheng-Chi Tai 1, Ching-Chau Su 1, Chien-Yi Chen 1, Ting-Cheng Huang 1, Yu-Hsun Lin 2 1 Department
More informationIRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.
IRIS POWER PDTracII Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear. We have not found another test method that produces as much
More informationApplication of UHF Sensors for PD Measurement at Power Transformers
Application of s for PD Measurement at Power Transformers Martin Siegel, Michael Beltle, Stefan Tenbohlen University of Stuttgart Institute of Power Transmission and High Voltage Technology (IEH) Pfaffenwaldring
More informationHeat sink. Insulator. µp Package. Heatsink is shown with parasitic coupling.
X2Y Heatsink EMI Reduction Solution Summary Many OEM s have EMI problems caused by fast switching gates of IC devices. For end products sold to consumers, products must meet FCC Class B regulations for
More informationHYUNDAI HEAVY INDUSTRIES CO. LTD
HiPDS-G HYUNDAI HEAVY INDUSTRIES CO. LTD Hyundai Intelligent Preventive Diagnostic System for GIS User s Manual Version: 1.20 / 2010.02.10 File: HiPDS-G_UsersManual(ENG).doc Hyundai Heavy Industry HiPDS-G
More informationMonitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers
in cooperation with Monitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers BZ-MS/1 pazifik power Complete Transformer Monitoring System (TMS) ZVCM-1001 Bushing Monitoring
More informationII. TRADITIONAL APPROACH OF PD MEASUREMENTS
Advantages of Continuous Monitoring of Partial Discharges in Rotating Equipment and Switchgear Claude Kane Cutler Hammer Predictive Diagnostics 5421 Feltl Road, Suite 190 Minnetonka, MN 55343 Phone: 952-912-1358
More informationInspection of Wave Propagation Due to Partial Discharge Occurring in Current Transformer Using 3-D Finite Difference Time Domain Based Technique
Inspection of Wave Propagation Due to Partial Discharge Occurring in Current Transformer Using 3-D Finite Difference Time Domain Based Technique R. M. Sharkawy and Tamer Adel Aziz Abstract This work aims
More informationLoad growth coupled with aging transform ers is a disaster wait ing to happen
RISK ASSESSMENT EVENTS Load growth coupled with aging transform ers is a disaster wait ing to happen 96 Jon L. GIESECKE Advanced transformer condition assessment Part I Transformer lifecycle and risk assessment
More informationSEL Phase Comparison Faulted Circuit Indicator (PC FCI) Communicates to line crews using the. Features and Benefits
SEL-8 Phase Comparison ed Circuit Indicator (PC FCI) SEL-8 SEL-8 SEL-8 SEL-8 SEL-8 SEL-8 Communicates to line crews using the Features and Benefits Locates ed Cable Sections Quickly Locate cable failures
More informationDATA ANALYSIS FOR VALVE LEAK DETECTION OF NUCLEAR POWER PLANT SAFETY CRITICAL COMPONENTS
DATA ANALYSIS FOR VALVE LEAK DETECTION OF NUCLEAR POWER PLANT SAFETY CRITICAL COMPONENTS Jung-Taek Kim, Hyeonmin Kim, Wan Man Park Korea Atomic Energy Research Institute 145 Daedeok-daero, Yuseong-gu,
More informationA Comparative Diagnosis Approach on Transformer s Insulating Oil Ming-Jong Lin
Information Technology and Mechatronics Engineering Conference (ITOEC 2015) A Comparative Approach on Transformer s Insulating Oil Ming-Jong Lin No. 11 North Road Nanke, Shanhua District, Tainan City,
More informationRECENT DEVELOPMENTS IN IEEE AND IEC STANDARDS FOR OFF-LINE AND ON-LINE PARTIAL DISCHARGE TESTING OF MOTOR AND GENERATOR STATOR WINDINGS
RECENT DEVELOPMENTS IN IEEE AND IEC STANDARDS FOR OFF-LINE AND ON-LINE PARTIAL DISCHARGE TESTING OF MOTOR AND GENERATOR STATOR WINDINGS Copyright Material IEEE Paper No. PCIC-2014-9 G.C. Stone Meredith
More information