Best Practice Reducing The Risk of Arc Flash Cross Over
|
|
- Angel Brown
- 5 years ago
- Views:
Transcription
1 Best Practice Reducing The Risk of Arc Flash Cross Over 1
2 2
3 Electrical Systems Are Critical 3
4 Why Do We Complete Electrical Maintenance Energized?? 4
5 Which Bulb Is Not Working?? 5
6 Functioning Correctly Failed System: Does not Work Failed System: Too Bright Functioning Correctly Failed System: Too Dim 6
7 Traditional Electrical Maintenance practices Traditional Maintenance and testing of electrical systems utilize intrusive work practices such as: Tightness / Torque testing Megger / Stress testing Circuit Testing Load Bank Testing Breaker and Isolator Testing Etc These Maintenance Tasks are designed with one outcome in mind: To confirm whether of not the circuits and connections are good and that the system meets its Operational Requirements. THERE IS A BETTER WAY????
8 Electrical Connections must be inspected under load conditions to allow their condition to be validated The Majority of Condition Based Test Equipment Require Energized systems Infrared Scan Measures temperature caused by high resistance connections, load imbalance, etc Ultrasound Scan Records Airborne Emissions at 40 khz to identify Arcing Tracking and Corona. Partial Discharge Identifies cable insulation issues in energized systems of 5kV and above Motor Current Analysis Identifies faulty electrical circuits & components. Can be completed De-energized Ultraviolet Scan Finds Corona issues in energized systems of 5kV and above Visual Inspection Visual identification of system integrity. Can be completed De-energized **NFPA 70B Recommends a Minimum of 40% Load** 8
9 How do we start? CAST 1-9
10 Identify the Components you wish to inspect Cable Connections Bus Bar Connections Isolator or Circuit Breaker Connections 10
11 Good Electrical Connection and Circuit Test Equipment Results Infrared Scan Ultrasound Scan Partial Discharge Motor Current Analysis Ultraviolet Scan Visual Inspection (Voltage Related, Usually used in 5kV Systems or Above) (Voltage Related, Usually used in 5kV Systems or Above) 11
12 Overloaded Electrical Connection and Circuit Test Equipment Results Infrared Scan Ultrasound Scan Partial Discharge Motor Current Analysis Uniform heating of completed Circuit (Voltage Related, Usually used in 5kV Systems or Above) Ultraviolet Scan (Voltage Related, Usually used in 5kV Systems or Above) Visual Inspection In extreme cases we may see heat damage on cables, etc. 12
13 High Resistance Or Loose Electrical Connection Test Equipment Results Infrared Scan Ultrasound Scan Partial Discharge Motor Current Analysis Localized heating at bolted connection May find Arcing or tracking depending on severity of the fault (Voltage Related, Usually used in 5kV Systems or Above) Inspections should show elevated resistance reading in tested circuits. Ultraviolet Scan (Voltage Related, Usually used in 5kV Systems or Above) Visual Inspection In extreme cases we may see heat damage on cables, etc. 13
14 High Resistance Or Loose Cable Lug Connection Test Equipment Results Infrared Scan Ultrasound Scan Partial Discharge Motor Current Analysis Localized heating at Lug/cable connection. May find Arcing or tracking depending on severity of the fault (Voltage Related, Usually used in 5kV Systems or Above) Inspections should show elevated resistance reading in tested circuits. Ultraviolet Scan (Voltage Related, Usually used in 5kV Systems or Above) Visual Inspection 14
15 Partial Discharge or Cable Insulation failure Test Equipment Results Infrared Scan Ultrasound Scan Partial Discharge Motor Current Analysis Depending on severity level this may not produce heat. Should produce corona but is voltage defendant TEV will be present but results are voltage Related, Usually used in 5kV Systems or Above Ultraviolet Scan Corona will be present but results are voltage Related, Usually used in 5kV Systems or Above Visual Inspection In extreme cases the Partial Discharge can be seen as a white residue 15
16 Critical Asset Surveillance Technologies (CAST) CAST 1-16
17 Critical Asset Surveillance Technologies (CAST) Overview: The term CAST refers to a Risk Based, Data Driven 100% Surveillance Repair maintenance model that utilizes condition based monitoring technologies to inspect electrical distribution assets. These surveillance and inspection methods determine the condition of the individual assets or systems being inspected and include but are not limited to: Infrared Thermography Airborne Ultrasound Motor Current Analysis Partial Discharge Testing Power Quality Management Ultraviolet Corona Imaging Vibration Analysis Alignment Testing Oil Analysis Visual Inspections
18 18
19 Common Ways to Interact with Equipment An Electrical Hazard is a state that occurs when exposed parts are present OR when you are interacting with a piece of equipment in such a way that you could be electrocuted or cause an arc flash. Opening or closing doors Removing or replacing a cover Reaching into or leaning into equipment Removing or replacing internal barriers Operating switches or circuit breakers Racking a circuit breaker Using tools or test equipment 19
20 Reducing Maintenance Induced Failures 20
21 Maintenance Inspection Systems 21
22 EMSD Benefit Analysis (IR Window and Ultrasound Ports) 22
23 A Recent Emerson Study on The Effect of Regular, Skilled Preventive Maintenance and Remote Monitoring of Critical Power system Reliability on Mean Time Between Failures (MTBF) showed the following Results: 23
24 The Asset MTBF is increased by 51 times by inspecting once per quarter 24 Source: The Effect of Regular, Skilled preventive Maintenance and Remote Monitoring on Critical Power system Reliability
25 25
26 26
Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound
Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences
More informationDecreasing Substation Failures with Ultrasound Technology
Decreasing Substation Failures with Ultrasound Technology Adrian Messer, Manager of US Operations UE Systems, Inc. Ph: 864-224-4517 Cell: 914-282-3504 Web: www.uesystems.com Email: adrianm@uesystems.com
More informationApplication Note. Detection of Partial Discharge Using Ultrasound. Detection of Partial Discharge Using Ultrasound. Problem. iriss.
Detection of Partial Discharge Using Ultrasound Problem In electrical systems, especially above 1,000 Volts, sufficient and properly maintained equipment insulation helps ensure equipment longevity. However,
More informationUltrasound Condition Monitoring
Ultrasound Condition Monitoring White Paper Author: Alan Bandes UE Systems, Inc 14 Hayes Street Elmsford, NY 10523 info@uesystems.com +914-592-1220 800-223-1325 1 2010 UE Systems, Inc all rights reserved
More informationElectrical Equipment Reliability with Ultrasound & Infrared
Electrical Equipment Reliability with Ultrasound & Infrared Adrian Messer, Manager of US Operations UE Systems, Inc. Ph: 864-224-4517 Cell: 914-282-3504 Web: www.uesystems.com Email: adrianm@uesystems.com
More informationWelcome to the Session on. HT Distribution Network
Welcome to the Session on HT Distribution Network Learning Objective By the end of this session you will be able to: Explain the HT distribution network breakdown maintenance - possible faults, identification
More informationSECTION PANELBOARDS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section
More informationXu Xiao Ming, AP Services, March 2010 Machine services Life expectance analysis program (LEAP)
Xu Xiao Ming, AP Services, March 2010 Machine services Life expectance analysis program (LEAP) April 12, 2010 Slide 1 Content MV Machine Winding Insulation Stress LEAP Methodology LEAP Standard LEAP from
More informationKnowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators
Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery Application of EMI Diagnostics to Hydro Generators James Timperley Doble Global Power Services Columbus, Ohio jtimperley@doble.com
More informationElectrical Equipment Condition Assessment
Feature Electrical Equipment Condition Assessment Using On-Line Solid Insulation Sampling Importance of Electrical Insulation Electrical insulation plays a vital role in the design and operation of all
More informationThe Weidmann Conference The Aging of America s Transformers
The Weidmann Conference 2006 The Aging of America s Transformers by Jon L. Giesecke, Director, (610) 518-1615 jlgassociatesllc@yahoo.com How Old is Old? The aging of the electrical infrastructure in the
More informationBenefits of SFRA - Case Studies
6 th International Conference on Large Power Transformers- Modern Trends Benefits of SFRA - Case Studies B B Ahir Gujarat Energy Transmission Corporation Limited 1 Outline Condition Monitoring in GETCO
More informationEI HIGH VOLTAGE INSULATION TESTING POLICY
Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and
More informationINSTALLATION & TESTING OF UNDERGROUND PRIMARY AND SECONDARY POWER CABLES PRIOR TO ENERGIZATION
TITLE: RECOMMENDED: P. Lemay NO: APPROVED: C. Malone, P.Eng. REV. DATE: 2015-11-02 Working Procedure GCG0001 REV: 3 INSTALLATION & TESTING OF UNDERGROUND PRIMARY AND SECONDARY POWER CABLES PRIOR TO ENERGIZATION
More informationA CASE STUDY OF PARTIAL DISCHARGE AND ELECTRICAL TRACKING IN A 11KV METAL CLAD SWITCHGEAR
A CASE STUDY OF PARTIAL DISCHARGE AND ELECTRICAL TRACKING IN A 11KV METAL CLAD SWITCHGEAR Anil Shrivastava Harsh Vardhana Kabra Abhijit Kumar HOD-Elect,NTPC SSTPS Dy.Manager,NTPC SSTPS Dy.Manager,NTPC
More informationAdvancements in online partial discharge monitoring and assessment of MV through EHV Substation assets
Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets Abstract: For decades it has been recognized that partial discharge assessment is an excellent method
More informationNATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL WORKMANSHIP NQF LEVEL 3 NOVEMBER 2009
NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL WORKMANSHIP NQF LEVEL 3 NOVEMBER 2009 (12041013) 3 November (X-Paper) 09:00 12:00 This question paper consists of 5 pages. (12041013) -2- NC740(E)(N3)V TIME:
More informationPartial Discharge, Survey or Monitor?
July 2014 Partial Discharge, Survey or Monitor? 24-7 Partial Discharge monitoring is the ultimate tool for finding insulation weaknesses before they fail. Introduction It s well established that Partial
More informationMV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 21 25 Sep $3,750 Dubai, UAE In any of the 5 star
More informationFirst Draft Language
110.16 First Draft Language (B) Service Equipment. In addition to the requirements in (A), service equipment shall contain the following information: (1) Nominal system voltage (2) Arc flash boundary (3)
More informationWebinar: An Effective Arc Flash Safety Program
Webinar: An Effective Arc Flash Safety Program Daleep Mohla September 10 th, 2015: 2pm ET Agenda Arc Flash Defined and Quantified NFPA 70E / CSA Z 462 - Recent Updates What is the ANSI Z10 Hierarchy of
More informationAcoustic Emission in power transformers. Ajusco 15, Colonia Portales, Delegación Benito Juárez, C.P , México, D.F.
Acoustic Emission in power transformers 1 More expensive equipment in the substation Many years of operation First indication of a problem: Dissolved Gases Begin investigation to determine the origin of
More informationSAMPLE. Determining the health of your power transformer begins with Transformer Clinic s SAMPLE testing programs.
Keep Powering On SAMPLE Determining the health of your power transformer begins with Transformer Clinic s SAMPLE testing programs. Overheating, arcing, partial discharge, and other active or slow-evolving
More informationEquipment Description Quantity as per drawings Actual quantity
NOTE: SAFETY: Tests must be carried out after the installation, alteration or repair and before putting back to service. At all times maintain suitable clearance to all other electrical equipment and verify
More informationSTANDARDIZING ARC FLASH PPE LABELS
The Electrical Power Engineers Qual-Tech Engineers, Inc. 01 Johnson Road Building #1 Suite 03 Houston, PA 1534-1300 Phone 74-873-975 Fax 74-873-8910 www.qualtecheng.com STANDARDIZING ARC FLASH PPE LABELS
More informationSERVICE OFFERINGS FOR POWER SYSTEM STUDY & CONDITION MONITORING FOR STATIC EQUIPMENT
SERVICE OFFERINGS FOR POWER SYSTEM STUDY & CONDITION MONITORING FOR STATIC EQUIPMENT Page TABLE OF CONTENTS POWER SYSTEM STUDY: 5 DATA COLLECTION AND NETWORK MODELLING 5 LOAD FLOW STUDY 5 SHORT CIRCUIT
More informationADVANCED CIRCUIT BREAKERS OPERATION AND MAINTENANCE SECTOR / ENGINEERING TECHNICAL & CERTIFICATE OF ATTENDANCE TRAINING COURSE
ADVANCED CIRCUIT BREAKERS OPERATION AND MAINTENANCE SECTOR / ENGINEERING TECHNICAL & CERTIFICATE OF ATTENDANCE TRAINING COURSE Circuit Breakers Play An Important Role In The Safe Distribution Of Electrical
More informationElectrical Arc Hazards
Arc Flash Analysis 1996-2009 ETAP Workshop Operation Notes Technology, 1996-2009 Inc. Operation Workshop Technology, Notes: Arc Inc. Flash Analysis Slide 1 Electrical Arc Hazards Electrical Arcs can occur
More information2015 NFPA 70E. SESHA 2015 ARIZONA MINI CONFERENCE December 10, 2015 Intel Corporation
2015 NFPA 70E SESHA 2015 ARIZONA MINI CONFERENCE December 10, 2015 Intel Corporation Introduction Jeffrey A. Pugh, P.E. Pugh Engineering LLC Bachelor of Science Degrees in Electrical Engineering and Computer
More informationIRIS POWER TGA-B. Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors
IRIS POWER TGA-B Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors We have not found another test method that produces as much decision support data for generator
More informationECP HV INSULATION TESTING
Document Number: ECP 11-0006 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE EPN, LPN, SPN ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing
More informationOn-line Partial Discharge Assessment and Monitoring of MV to EHV Cables
On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables William Higinbotham, Neil Davies and Victor Chan EA Technology LLC, New Jersey; USA, EA Technology Pty Ltd, Brisbane Australia; EA
More informationElectrical Switchgear & Power Transformer Testing. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E
Electrical Switchgear & Power Transformer Testing H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E www.ictd.ae ictd@ictd.ae Course Introduction: This will provide you with practical knowledge
More information7. INSPECTION AND TEST PROCEDURES
7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect
More informationElectronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards
Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards The Solo, Select and Sync PWM boards provide a pulse-width modulated (PWM) signal to the EC motor to control fan speed.
More informationThis section is specifically about safety matters
6 4 ) 5 1 5 6 4 1 -, 1 8-4 6-4 1 5 6 4 7 + 6 1 ) 7 ) 5 2 - -,, - 6 - + 6 4. 4. 2 J E? A Thank you for choosing this Mitsubishi transistorized Inverter option. This instruction manual gives handling information
More informationSpecialists in HV and MV test and diagnostics. Testing in Substations
Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies
More informationThis section is specifically about safety matters
6 4 ) 1 6 4 1 -, 1 8-4 6-4 1 6 4 7 + 6 1 ) 7 ) 4 ) 6 1-6 6-4. 4. 0 J E? A Thank you for choosing this Mitsubishi transistorized Inverter option. This instruction manual gives handling information and precautions
More informationPower Supply Device (KLTE-430D) Installation & Operation Manual
9-25-212 modified 6-3-216 KLTE-43DInstallation&Operation (1/15) Power Supply Device (KLTE-43D) Installation & Operation Manual Sept. 25, 212 KLTE-43DInstallation&Operation (2/15) Table of Contents < Rectifier
More informationHZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL. Huazheng Electric Manufacturing(Baoding) Co.,Ltd
HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL Huazheng Electric Manufacturing(Baoding) Co.,Ltd Safety Terms and Symbols This manual may contain the terms: Warning! Indicate the conditions
More informationOnsite Mobile AC High Voltage Test System
TSGMF(T) series Onsite Mobile AC High Voltage Test System Onsite mobile AC high voltage test systems are used for withstand voltage testing, partial discharge measurement, tan delta measurement to instrument
More informationModern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions
1 Transmission transformers are important links in the bulk power system. They allow transfer of power from generation centers, up to the high-voltage grid, and to bulk electric substations for distribution
More informationKey factors to maintaining arc flash safety
APPLICATI TE Key factors to maintaining arc flash safety Arc flash and blast When an arc fault occurs, the result is a massive electrical explosion. The light and heat emitted by the explosion is known
More informationGENERATOR TESTING APPLICATION GUIDE. reliable. precision.
GENERATOR TESTING APPLICATION GUIDE www.haefely-hipotronics.com reliable. precision. 2 GENERATOR TESTING CONTENTS Product Line Overview 3 AC Hipot Testing 4 Partial Discharge Measurement 5 DC Hipot Testing
More informationNFPA-70E. Electrical Safety in the Workplace. Standard for Edition
NFPA-70E Standard for Electrical Safety in the Workplace 2015 Edition NFPA-70E 90.1 Purpose. The purpose of this standard is to provide a practical safe working area for employees relative to the hazards
More informationPD Diagnostic Applications and TechImp solutions
PD Diagnostic Applications and TechImp solutions Condition Assessment Solutions for Electrical Systems. PD based innovative tools for the Condition Based Maintenance. MD-04.05.004 - rev. 00-29/08/2006
More informationEE171. H.H. Sheikh Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E
EE171 Electrical Equipment & Control System: Electrical Maintenance Transformers, Motors, Variable Speed Drives, Generators, Circuit Breakers, Switchgears & Protective Systems H.H. Sheikh Sultan Tower
More information10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY
9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor
More informationUBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS
More informationA Guide to Establish an Arc Flash Safety Program for Electric Utilities
A Guide to Establish an Arc Flash Safety Program for Electric Utilities by Craig Clarke, P.E. Eaton Corporation 50 Soccer Park Rd. Fenton, MO 63026 (636) 717-3406 CraigClarke@Eaton.com Ilanchezhian Balasubramanian,
More informationField Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.
8.3 Induced Voltage Purpose The purpose of this instruction is to provide awareness of Electrostatic and Electromagnetic induced voltages and the method required to reduce or eliminate it. An induced voltage
More informationElectrical testing safety Part 1: Preparing for absence of voltage testing
APPLICATION NOTE Electrical testing safety Part 1: Preparing for absence of voltage testing James R. White, Training Director, Shermco Industries, Inc. OSHA and the NFPA 70E Standard for Electrical Safety
More informationThe Multi-Technology Approach to Motor Diagnostics
The Multi-Technology Approach to Motor Diagnostics Howard W. Penrose, Ph.D. For: ALL-TEST Pro Old Saybrook, CT Introduction There has been a persistent misconception that there is a magic bullet, in the
More informationI P. /dt. di p V S+ Applications. Standards. 1) IEC ed1.0: 2007; IEC : ed1.0: 2012
Ref: ART-B22-D70, ART-B22-D125, ART-B22-D175 Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and the secondary
More informationMECHANICAL MAINTENANCE SKILLS
MECHANICAL MAINTENANCE SKILLS COURSE 700: 5 DAYS: Max 4 Candidates This course provides personnel with the necessary skills to perform mechanical maintenance, including the removal and replacement of equipment
More informationAN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY
The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com AN EXAMPLE OF A STANDARD ARC
More informationArresterFacts-002. Field Testing Arresters ArresterWorks.com. ArresterFacts are information modules pertaining to the arrester world.
ArresterFacts are information modules pertaining to the arrester world. This Field Testing of Arresters module will clarify the many questions about assessing the quality of an installed high voltage arrester
More informationAPPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS
APPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS David Larochelle NDB Technologies Reasons leading to acoustic testing are different weather it is a manufacturing or field environment
More informationElectrical Measurement Safety. Sponsored By:
Electrical Measurement Safety Sponsored By: About the Viewer Panel Slides: Go to the Links tab at the top and click on the link to download the PDF of the slides If you re watching the archive version,
More informationMotor Bearing Damage and Variable Frequency Drives: - Diagnosing the Causes, - Implementing a Cure, and - Avoiding the Pitfalls
Motor Bearing Damage and Variable Frequency Drives: - Diagnosing the Causes, - Implementing a Cure, and - Avoiding the Pitfalls Tim Albers, Director of Product Mgt, NIDEC Motor Corporation Tim Jasina,
More informationPREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!
PREFACE This publication has been prepared as a guide for Architectural and Engineering (A&E) firms in the preparation of documents for the design and construction of new structures and the remodeling
More informationAmpgard The name motor applications rely on
Medium-voltage motor control The name motor applications rely on Oil and gas Mining Water/wastewater Pulp and paper Utility A legacy of reliability for more than 4 decades 1950 1960 1970 1980* 1990 2000
More informationFor Medium Voltage Motors, Generators, Switchgear, Bus Duct and Cable Terminations
InsulGard Product Focus Maximize Your Uptime For Medium Voltage Motors, Generators, Switchgear, Bus uct and Cable erminations InsulGard 1. InsulGard (Front) 2. InsulGard (Back) Why InsulGard?...Economics
More informationPD Solutions. On-Line PD Measurement Devices
On-Line PD Measurement Devices 1. Longshot Device (see Figure 1) The measurement system applied is based around the wideband (0-400 MHz) HVPD- Longshot partial discharge test unit which utilizes a high-speed
More informationECP HV INSULATION TESTING
Document Number: ECP 11-0006 Network(s): Summary: All ENGINEERING COMMISSIONING PROCEDURE ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing of new and
More informationPME specialises in developing, implementing and maintaining solutions to the Mining industry.
+675 325 3533 PME specialises in developing, implementing and maintaining solutions to the industry. Our Services: Engineering & design EPC services High voltage design, installations and testing Installation
More informationFINAL - ET 60 - Electrician Theory Examination Marking Schedule
FINAL - ET 60 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions.
More informationELECTRICAL MAINTENANCE SKILLS
ELECTRICAL MAINTENANCE SKILLS FOR INSTRUMENTATION PERSONNEL COURSE 120: 7 DAYS: Max 8 Candidates The end objectives are identical to those of the Electrical maintenance skills (Course 110) but this starts
More information2017 ELECTRICAL SAFETY SERVICES. Arc Flash Electrical Maintenance Lockout/Tagout And More
2017 ELECTRICAL SAFETY SERVICES Arc Flash Electrical Maintenance Lockout/Tagout And More ABOUT LEWELLYN TECHNOLOGY Improving workplace safety since 1993 Daryn Lewellyn founded Lewellyn Technology more
More informationI P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017
Ref: ART-B22-D70, ART-B22-D125, ART-B22-D175, ART-B22-D300 Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and
More informationREDUCING ARC FLASH HAZARD BY REMOTE SWITCHING
The Electrical Power Engineers Qual-Tech Engineers, Inc. 21 Johnson Road Building #1 Suite 23 Houston, PA 15342-13 Phone 724-873-9275 Fax 724-873-891 www.qualtecheng.com REDUCING ARC FLASH HAZARD BY REMOTE
More informationCause, Effect & Mitigation Strategies
WSU HANDS ON RELAY SCHOOL 2019 Arc Flash Fault Cause, Effect & Mitigation Strategies Joe Xavier, Technical Manager West Region Arc Flash Fault - Agenda What is an Arc Flash? Why and when does Arc Flash
More informationGetting started with the 2 Port Antenna Switch
Getting started with the 2 Port Antenna Switch Many thanks for purchasing this Antenna switch. The switch is designed to be quickly deployed as a way of providing an easy and transparent RF path either
More informationSGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications:
SGMF(T) series Onsite Mobile AC High Voltage Test System On-site AC high voltage test systems are used for voltage withstanding test, partial discharge measurement, tan delta measurement on those instrument
More informationET 51 - Electrician Theory Examination Marking Schedule
ET 51 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A marker
More informationhigh RESISTANCE GROUNDING SYSTEM the power to protect SLEUTH Instruction Manual C-408EM
SLEUTH high RESISTANCE GROUNDING SYSTEM SLEUTH the power to protect Instruction Manual C-408EM HIGH RESISTANCE GROUNDING Sleuth Protecting your equipment and processes from damaging ground faults, a resistor
More informationAN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY
The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com AN EXAMPLE OF A STANDARD ARC
More informationEducation & Training
Distribution System Operator Certificate This program provides you with a proficient working knowledge in modern electric power distribution systems. These four classes are designed to walk students through
More informationThe Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.
The Importance of the Neutral-Grounding Resistor Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T. Presentation Preview What is high-resistance grounding (HRG)? What is the purpose of HRG? Why
More informationCHAPTER MAINTENANCE AND TROUBLESHOOTING. In This Chapter... Maintenance and Inspection Troubleshooting...6 3
CHAPTER MAINTENANCE AND 6 TROUBLESHOOTING In This Chapter... Maintenance and Inspection.................6 2 Monthly Inspection:..................................6 2 Annual Inspection....................................6
More informationArild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems
Arild Furnes,ATPA OGP/Petrobras workshop, 22.09.09 Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems September 24, 2009 Slide 1 Transformers for Ships and Offshore -
More informationMASTECH MS5908. Circuit Analyzer
MASTECH MS5908 Circuit Analyzer Operation Manual 2 General Instructions This circuit analyzer is a special test device designed for AC low-voltage distribution line quick fault location. With simple operation,
More informationET 40 - Electrician Theory Examination Marking Schedule
ET 40 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A marker
More informationELECTRICAL EQUIPMENT. Inspection. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E
ELECTRICAL EQUIPMENT Inspection H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E www.ictd.ae ictd@ictd.ae Course Introduction: The course begins with the fundamental principles that always
More informationSHORE TO SHIP FREQUENCY
POWER SYSTEMS INTERNATIONAL SHORE POWER POWER CONVERSION SYSTEMS 50Hz, 60Hz and 400Hz three phase and single phase There is a growing world focus on energy conservation with the drive towards reducing
More informationArc Flash Mitigation An Overview. Gus Nasrallah, P.E. Electroswitch May 30, 2013
Arc Flash Mitigation An Overview Gus Nasrallah, P.E. Electroswitch May 30, 2013 Agenda Origin of Modern Arc Flash studies Why Now more than before NFPA 70E Standards Protection Zone IEEE 1584 2002 IEEE
More informationHigh Frequency SineWave Guardian TM Filter
High Frequency SineWave Guardian TM Filter 380V 480V TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference
More informationEVERGREEN EM INSTALLATION GUIDE
EVERGREEN INSTALLATION GUIDE A Regal Brand Genteq s Evergreen is designed to replace O X13 ECM motors quickly and easily with no programming required. Evergreen provides the same comfort, lower utility
More informationPole Mount Installation Guide
Pole Mount Installation Guide (No Fine Adjustment) 495R Billerica Ave. North Billerica, MA 01862 USA Tel (978)459-8800 fax (978)459-3310 / 8814 Email: sales@radiowaves.com www.radiowaves.com IMPORTANT!
More informationWATERFLUX 3000 Quick Start
WATERFLUX 3000 Quick Start Electromagnetic flowmeter The documentation is only complete when used in combination with the relevant documentation for the signal converter. KROHNE CONTENTS WATERFLUX 3000
More informationVOLTAGE DETECTING SYSTEMS
INTEGRATED OPTOELECTRIC SYSTEM OF VOLTAGE DETECTION WITH TOTAL SAFETY GUARANTEED BY GALVANIC INSULATION AND INTERNAL FAULT SUPERVISION pag.1 di 13 INDE 1.PREVIEW.. 3 2.GENERAL.. 3 3.STANDARD REFERENCES..
More informationA Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment
International Research Journal of Engineering and Technology (IRJET) eissn: 23 0056 Volume: 04 Issue: 02 Feb 2017 www.irjet.net pissn: 072 A Review Comprehension: Guideline for Testing of HV, EHV and UHV
More informationApplication of DFA Technology for Improved Reliability and Operations
Application of DFA Technology for Improved Reliability and Operations IEEE/IAS Rural Electric Power Conference Columbus, Ohio, 24 April 2017 Robert A. Peterson, P.E., Director Control Center and Emergency
More informationElectrical Overcurrent Studies
Electrical Overcurrent Studies 11-01-2011 Deliverables associated with electrical overcurrent studies are as follow : a. Draft Reports i. Construction Related Projects have the following draft reports
More informationInstructions for Installation. S&C ELECTRIC COMPANY Specialists in Electric Power Switching and Protection TABLE OF CONTENTS INTRODUCTION INSTALLATION
S&C Alduti-Rupter Switches Outdoor Distribution Three-Pole Double-Break Style and Three-Pole Double-Break Integer Style Live Parts Replacement on Switches with Catalog Number Supplement -R10 34.5 kv and
More informationC I R E D 21 st International Conference on Electricity Distribution Frankfurt, 6-9 June 2011
Use and Problems of On-line PD Measurement Technology on Switchgears in Guangzhou Distribution System XIONG Jun, WANG Yong, HUANG Huihong, HUANG Yanguang,LU Guojun,WU Bihua (Central Test and Researches
More informationARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS
The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com ARC FLASH PPE GUIDELINES FOR
More informationIndustrial Electrician Level 3
Industrial Electrician Level 3 Industrial Electrician Unit: C1 Industrial Electrical Code I Level: Three Duration: 77 hours Theory: Practical: 77 hours 0 hours Overview: This unit is designed to provide
More informationPARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES
PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES Engr. IÑIGO V. ESCOPETE, JR. ITC Level 2 Certified Thermographer PHIL-NCB NDT-UT Level 2 Partial Discharge testing is a Condition Based Maintenance tool
More informationArc Flash Analysis and Documentation SOP
Arc Flash Analysis and Documentation SOP I. Purpose.... 2 II. Roles & Responsibilities.... 2 A. Facilities Maintenance (FM).... 2 B. Zone Supervisors/ Shop Foremen... 2 C. PMCS & CPC... 2 III. Procedures...
More information