Open Access Application of Partial Discharge Online Monitoring Technology in ± 660kV Converter Transformer

Size: px
Start display at page:

Download "Open Access Application of Partial Discharge Online Monitoring Technology in ± 660kV Converter Transformer"

Transcription

1 Send Orders for Reprints to 784 The Open Automation and Control Systems Journal, 2015, 7, Open Access Application of Partial Discharge Online Monitoring Technology in ± 660kV Converter Transformer He Ninhui 1,*, Wang Bo 1,2, Zhang Tao 1,2 and Guo Fei 1 1 Power Science Research Institute of State Grid Ningxia Power Co., Yingchuan Ningxia , China 2 School of Electrical Engineering Wuhan University, Hubei Wuhan , China Abstract: The partial discharge detection technology (UHF) is specially used in YD-B Phase of ± 660kV converter transformer pole I system, in connection with overheating failure problems. Through analysis by PRPD map to strengthen the monitoring for partial discharge defective of converter transformer, the continuous tracking for the running state of converter transformer can be achieved. Application results show that: the signal of partial discharge characteristics can be effectively found inside the converter transformer through UHF Online Monitoring techniques, which has good sensitivity and Interference capability, providing guarantee for safe and stable running of power equipment. Keywords: UHF, On-line Monitor, Partial Discharge, PRPD Map. 1. INTRODUCTION With the increasing of voltage grade of DC transmission, the insulator for ultra high voltage direct current (UHVDC) equipments is becoming more and more outstanding. As the most important electrical equipment in DC system, the convert transformer will influence the whole system directly. Turn-on and cut-off of the rectifying valve will produce impulse voltage with high amplitude and steep waveform. When the impulse voltage superimposed on the winding voltage, it will form a kind of compound voltage that is similar to sinusoidal AC waveform, which is composed by direct voltage and alternating voltage (exists many harmonic waves) with heavy distortion. At the same time, the valve side winding have to endure the lighting impulse and voltage operation. What's more, the short circuit impedance and loss of converter transformer will make the equipment heat up more than ordinary transformer. And the internal temperature of converter transformer is 20% higher than the ordinary transformer s. Therefore, the insulator failure rate of converter transformer coil is higher than the ordinary transformer. As the research shows, too hot insulator medium caused by partial discharge is the main factor that causes insulator failure.in this way, observing the partial discharge of converter transformer by installing Ultra High Frequency (UHF) partial discharge equipment will have high significance of improving the safe operation level of converter transformer., 2. HF PARTIAL DISCHARGE DETECTION TECH- NOLOGY 2.1. The Principle of UHF Partial Discharge Detection Technology Insulator strength and breakdown field strength of electronic equipment s insulator are relatively high. When the partial discharge happens within a tight trading range, the breakdown process is fast, and it will produce very steep pulse current whose rise time will be less than 1ns and radiate a kind of electromagnetic wave with a frequency up to GHz. The method of UHF partial discharge detection was put forward by Central Electricity Generating Board Laboratory in the early 1980s. Its basic principle is to use UHF sensor to detect the signal of UHF electromagnetic wave (300MHz f 3GHz) produced by the partial discharge (PD) of power equipment. This method can detect the signals of PD, and realize PD monitoring. According to different field devices, we can apply Built-in UHF sensor and external UFH sensor. Built-in UFH senor detects signals generally by oil drain valve, flange plate and standardized medium window into the transformer from inside, which can provide high detection sensitivity and strong anti-interference capacity. External UHF senor detects signals generally by Coupling with small amount of electromagnetic leaking from outlet port and seams, which can be easy to install and doesn't influence transformer s internal electric field. As the corona interference is focused on the frequency band below 300MHz, the method of UHF can have a good ability of avoiding the corona interference effectively, and realize PD on-line detection, positioning and flaw detection [1] / Bentham Open

2 Application of Partial Discharge Online Monitoring Technology The Open Automation and Control Systems Journal, 2015, Volume Fig. (1). The monitoring system of UHF partial discharge The Contrast of UHF Detection Methods and Traditional PD Methods Comparing with other PD online techniques, UHF detection methods have many prominent advantages: 1) High detection sensitivity The signals of UHF electromagnetic waves generated by PD will fade out in the process of converter transmission. If ignoring the influence of the insulator, the signal of UHF electromagnetic waves with 1GHz can only be reduced to 3~5dB/km. And when electromagnetic waves reflect on the inner discontinuity of converter transformer, it will cause resonance in the shell of converter transformer to make the oscillation time of PD signals longer and easier to be detected. Therefore, UHF detection methods have high sensitivity. Furthermore, comparing to ultra-sonic detection, UHF detection methods can detect more effective range and need less necessary sensor data to detect converter transformer online [2]. 2) Strong anti-interference capacity As there is a large number of electric interference when the convert transformer works, it will bring some difficulties to partial discharge detection. The corona interference between high voltage transmission line and equipment is the most common field interference. The frequency of discharge energy is mainly below 200MHz. Detection frequency band of UHF method is usually 300MHz~3GHz. So it effectively avoids the field corona interference, and has strong anti interference ability. 3) Benefit for insulation defect recognition For different types of insulation defect, their UHF signals, produced by PD, have different frequency spectra. So, the time domain signal distribution of conventional method can be utilized. Also, it can be combined with Frequency distribution characteristics of UHF signal for PD type recognition, and realize diagnosis of insulation defect types. According to the propagation property of UHF electromagnetic waves, we know that applying Built-in UHF sensor to detect signals has higher sensitivity and stronger antiinterference ability than external UFH sensor, by extending the sensor into transformer through the oil discharge valve, flange and the standardization of dielectric window. 3. ANALYSIS OF UHF PD ONLINE MONITORING FOR CONVERTER TRANSFORMER APPLICATION EFFECT 3.1. Case In , oil chromatography online monitoring system found that YD-B occur the phenomenon of excessive acetylene. Subsequently, hydrogen, acetylene and hydrocarbon components rapidly grew. Through theoretical analysis, it was confirmed that B-phase of the equipment exists inner overheat Fault. When shifting from converter to running state, the monitoring is too simple. In order to guarantee the safety and stable operation of convert transformer, we use UHF PD monitoring technology and install SIM3-PD portable PD online monitoring device. UHF signal sensor is installed on the oil valve at the top of converter transformer, and it is used to monitoring PD of B-phase whose oil chromatography is abnormal [3]. The date of intelligent monitoring unit in field is uploaded to the integrated processing unit by CAN2.0B Field Bus. Integrated processing unit deals with the date. Then the field monitoring unit uploads to station CAC (Status information of the access controller) by the way of MMS, through the LAN based on IEC61850 Communication Protocol. It can also upload to the backstage diagnosis center. The system structure of UHF PD monitoring is shown in Fig. (1) Analysis of Application Effect By analyzing monitoring data from July 3 to July 25, during this time, continuous typical PD signals related with power frequency voltage were basically not found. But there had been short continuous time (2-3 hours), during which B- phase happened, and had typical PD signals as shown in

3 786 The Open Automation and Control Systems Journal, 2015, Volume 7 Ninhui et al. Fig. (2). The persistence abnormal PD signal in the B phase during 18:00 on July 4 th to 11:00 on July 5 th. Fig. (3). Only three hours abnormal PD signal in the B-phase during 14:00 to 15:00 on July 14 th. Fig. (2). At the same time, B-phase monitored unnormal signal that is unrelated with power frequency voltage. It often occurred between 18:00-11:00 the next day as shown in Fig. (3). But it did not occurred every day. 1) The effect of switch position on Partial discharge signal From July 25 th to July 30 th, pole I operate reducing power to 1200MW, meanwhile the swich will be changed from by

4 Application of Partial Discharge Online Monitoring Technology The Open Automation and Control Systems Journal, 2015, Volume Fig. (4). Similar characteristics PRPD map during 20:00 on July 26 th to 5:00 on July 27. Fig. (5). The PRPD map of pole system YD-B phase at 15:00 on August 25. the previous automatic regulating state to manually adjusting state, so that the switch operate in "22, 23, 24" gear for two days. During this period, there is Partial discharge characteristic signal shown in PRPD maps through UHF on-line monitoring device from from 8 p.m to 7 a.m every day, and presents the obvious characteristics of the phase, the discharge intensity of peak and average less than -65 dbm, taking the PRPD maps at 20:00 on the 26 th - at 5:00 on the 27 th for example, as shown in Fig. (4). The high frequency signal strength keep up -80dBm in PRPD map during other period, only occasional signal pulse is weak, but there is no correlation with the frequency of the voltage, not having obvious characteristics of the discharge phase [4]. 2) The effect of current load on Partial discharge signal At 1:00 on August 25, the system will run for three days with raising the power to 1600MW (80% load), at 1:00 on August 28, the power will be raised to 2000MW (100% load). After six days of following observation, no continued and fundamental typical PD signal associated with frequency voltage be found, but the daily 19:00 to 6:00 the next day, a signal with typical characteristic of PD appeared, which had been confirmed that the signal caused by Highvoltage Sodium lamp in firewall of Converter transformer indoor. From 8:00 on August 25 to 18:00 on August 25 th, it has similar PRPD map features during this period, shown in Fig. (5). From 19:00 on August 25 to 6:00 on August 26, it has similar PRPD map features during this period, as shown in Table 1 and Fig. (6). From 0:00 on August 28 to 6:00 on August 28, it has similar PRPD map features during this period, as shown in Fig. (7).

5 788 The Open Automation and Control Systems Journal, 2015, Volume 7 Ninhui et al. Fig. (6). The PRPD map of pole system YD-B phase at 19:00 on August 25. Fig. (7). The PRPD map of pole system YD-B phase at 0:00 on August 28. Table 1. PD parameters of pole system as the power raised to 1600MW (80% load). Time Peak Discharge (dbm) Mean Discharge (dbm) Pulses Number ( / ) Phase Features (%)

6 Application of Partial Discharge Online Monitoring Technology The Open Automation and Control Systems Journal, 2015, Volume Table 1. contd Time Peak Discharge (dbm) Mean Discharge (dbm) Pulses Number ( / ) Phase Features (%) Table 2. PD parameters of pole system as the power raised to 2000MW (100% load). Time Peak Discharge (dbm) Mean Discharge (dbm) Pulses Number ( / ) Phase Features (%)

7 790 The Open Automation and Control Systems Journal, 2015, Volume 7 Ninhui et al. Fig. (8). The PRPD map of pole system YD-B phase at 18:00 on August 28. From 7:00 on August 28 to 18:00 on August 28, it has similar PRPD map features during this period, as shown in Table 2 and Fig. (8). 4. ANALYSIS OF PARTIAL DISCHARGE DATA After PRPD maps and dates acquired from July 13th to August 30th were analyzed, it s determined as the following: For the abnormal signal of B-phase not related to frequency voltage during July 13 to July 25 (usually appear between 18:00-11:00 the next day, but there will not be everyday), due to the abnormal signals are not appear in the C- phase and B-phase as the same time, the interference from external space of Converter transformers can be ruled out; due to the abnormal signal is not synchronized with the power frequency voltage, and no interference caused by commutated and rectifier of thyristor, the interference generated by SCR can be exclude; whether that be caused by load change of Converter transformers, it need for further analysis. The signal with the typical features of partial discharge appear at 19:00 to 6:00 every night from July 25 to July 30 and August 25 to August 30, which have significant phase characteristics, the peak discharge and mean discharge are less than -65 dbm (the equivalent discharge amount not exceed hundreds of pc, will not affect the insulating properties of the transformer). Because the load of conversion transformer remained unchanged during this period, the impact of load changes can be excluded; Secondly, the impact of bad contact of tap changer can be excluded for tap-free operation. Although the signal appear in the C-phase and B-phase meantime, and keep synchronous with the frequency voltage, only in a fixed period of time, the interference of the SCR commutated rectifier outside converter transformer can be excluded. After analysis test, it s determined that the signal comes from the influence of high-voltage sodium lamps of converter transformer interior. The PRPD from the July 25 to July 30 and August 25 to August 30, UHF signal strength keep stable of -78dBm and there is not obvious pulse signal during other period daily. Since August 28 the power of poleⅠrose to 2000MW, the online monitoring discharge PRPD maps and discharge intensity, phase data and power YD-B phase of polo Ⅰ system compared to 1600MW, the amplitude of the partial discharge signal increased 2 ~ 3dBm, but the peak discharge and mean discharge less than -65 dbm, will not affect the performance of the transformer insulation. CONCLUSION After the conversion transformer in fault of overheating, there is no significant partial discharge and UHF signal strength are lower than -65 dbm, only occasional weak partial discharge characteristics appear in PRPD map, it suggest that monitoring system have strong anti-interfere capability. UHF partial discharge monitoring combined with a variety of oil chromatography effectively ensure security of conversion transformer in fault operation. CONFLICT OF INTEREST The authors confirm that this article content has no conflict of interest. ACKNOWLEDGEMENTS Declared none. REFERENCES [1] R. Zhang, X. Wu, and P. Ding, UHF partial discharge monitoring of 750kV main transformer, Ningxia Electric Power, vol. 25, no. 7, pp , [2] P. Wang, The Research of Partial Discharge UHF Characteristics in Converter Transformer and Monitoring Sensors, MS thesis, Chongqing University, China, 2013.

8 Application of Partial Discharge Online Monitoring Technology The Open Automation and Control Systems Journal, 2015, Volume [3] J. Li, P. Wang, T. Jiang, L. Bao, and Z. He, UHF stacked hilbert antenna array for partial discharge detection, IEEE Transactions on Antennas and Propagation, vol. 16, no. 3, pp , [4] L. Liang, The Corresponding Relation Between Typical Partial Discharge Defects of Transformer and Dissolved Gas in Oil, Chongqing University, Chongqing, Received: September 16, 2014 Revised: December 23, 2014 Accepted: December 31, 2014 Ninhui et al.; Licensee Bentham Open. This is an open access article licensed under the terms of the Creative Commons Attribution Non-Commercial License ( which permits unrestricted, non-commercial use, distribution and reproduction in any medium, provided the work is properly cited.

Open Access Partial Discharge Fault Decision and Location of 24kV Composite Porcelain Insulator based on Power Spectrum Density Algorithm

Open Access Partial Discharge Fault Decision and Location of 24kV Composite Porcelain Insulator based on Power Spectrum Density Algorithm Send Orders for Reprints to reprints@benthamscience.ae 342 The Open Electrical & Electronic Engineering Journal, 15, 9, 342-346 Open Access Partial Discharge Fault Decision and Location of 24kV Composite

More information

Open Access Partial Discharge Fault Decision and Location of 24kV Multi-layer Porcelain Insulator based on Power Spectrum Density Algorithm

Open Access Partial Discharge Fault Decision and Location of 24kV Multi-layer Porcelain Insulator based on Power Spectrum Density Algorithm Send Orders for Reprints to reprints@benthamscience.ae 342 The Open Electrical & Electronic Engineering Journal, 15, 9, 342-346 Open Access Partial Discharge Fault Decision and Location of 24kV Multi-layer

More information

PD Solutions. On-Line PD Measurement Devices

PD Solutions. On-Line PD Measurement Devices On-Line PD Measurement Devices 1. Longshot Device (see Figure 1) The measurement system applied is based around the wideband (0-400 MHz) HVPD- Longshot partial discharge test unit which utilizes a high-speed

More information

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of

More information

Design of Meander Antenna for UHF Partial Discharge Detection of Transformers

Design of Meander Antenna for UHF Partial Discharge Detection of Transformers Sensors & Transducers 204 by IFSA Publishing, S. L. http://www.sensorsportal.com Design of Meander Antenna for UHF Partial Discharge Detection of Transformers Mengjie Li, Chuangxin Guo, 2 Ziping Peng College

More information

Partial Discharge Monitoring and Diagnosis of Power Generator

Partial Discharge Monitoring and Diagnosis of Power Generator Partial Discharge Monitoring and Diagnosis of Power Generator Gao Wensheng Institute of High Voltage & insulation tech. Electrical Eng. Dept., Tsinghua University Wsgao@tsinghua.edu.cn Currently preventive

More information

A Compiler Design Technique for EMS Test CS115

A Compiler Design Technique for EMS Test CS115 Send Orders for Reprints to reprints@benthamscience.ae The Open Automation and Control Systems Journal, 2014, 6, 1451-1455 1451 A Compiler Design Technique for EMS Test CS115 Open Access Wang-zhicheng

More information

Suppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and Waveform Characteristics

Suppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and Waveform Characteristics Journal of Energy and Power Engineering 9 (215) 289-295 doi: 1.17265/1934-8975/215.3.8 D DAVID PUBLISHING Suppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and

More information

Open Access Parallel Resonant DC Link Inverter for Thermoacoustic Power Generation

Open Access Parallel Resonant DC Link Inverter for Thermoacoustic Power Generation Send Orders for Reprints to reprints@benthamscience.ae The Open Electrical & Electronic Engineering Journal, 2014, 8, 379-389 379 Open Access Parallel Resonant DC Link Inverter for Thermoacoustic Power

More information

Open Access Research of Dielectric Loss Measurement with Sparse Representation

Open Access Research of Dielectric Loss Measurement with Sparse Representation Send Orders for Reprints to reprints@benthamscience.ae 698 The Open Automation and Control Systems Journal, 2, 7, 698-73 Open Access Research of Dielectric Loss Measurement with Sparse Representation Zheng

More information

C I R E D 21 st International Conference on Electricity Distribution Frankfurt, 6-9 June 2011

C I R E D 21 st International Conference on Electricity Distribution Frankfurt, 6-9 June 2011 Use and Problems of On-line PD Measurement Technology on Switchgears in Guangzhou Distribution System XIONG Jun, WANG Yong, HUANG Huihong, HUANG Yanguang,LU Guojun,WU Bihua (Central Test and Researches

More information

Open Access Pulse-Width Modulated Amplifier for DC Servo System and Its Matlab Simulation

Open Access Pulse-Width Modulated Amplifier for DC Servo System and Its Matlab Simulation Send Orders for Reprints to reprints@benthamscience.ae The Open Electrical & Electronic Engineering Journal, 25, 9, 625-63 625 Open Access Pulse-Width Modulated Amplifier for DC Servo System and Its Matlab

More information

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk. THE POWER OF LIFE WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk. Mr. Neal Yang Pro.E.E. Engineer About Us The flaw of dielectric material

More information

Diagnostic testing of cast resin transformers

Diagnostic testing of cast resin transformers Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com

More information

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales

More information

Open Access Design of Diesel Engine Adaptive Active Disturbance Rejection Speed Controller

Open Access Design of Diesel Engine Adaptive Active Disturbance Rejection Speed Controller Send Orders for Reprints to reprints@benthamscience.ae The Open Automation and Control Systems Journal, 05, 7, 49-433 49 Open Access Design of Diesel Engine Adaptive Active Disturbance Rejection Speed

More information

PARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS

PARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS PARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS by K.K.JEMBU KAILAS and W. ADITHYA KUMAR L&T CONSTRUCTION L&T CONSTRUCTION KKJK@LNTECC.COM

More information

Open Access Research on Fast Response Characteristic of Magnetic Control Reactor

Open Access Research on Fast Response Characteristic of Magnetic Control Reactor Send Orders for Reprints to reprints@benthamscience.ae 966 The Open Automation and Control Systems Journal, 2014, 6, 966-974 Open Access Research on Fast Response Characteristic of Magnetic Control Reactor

More information

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets Who we are TECHIMP is one of the leading providers of Condition Assessment Services Data Acquisition and Test Equipment

More information

Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results

Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results 2016 International Conference on Electrical Engineering and Automation (ICEEA 2016) ISBN: 978-1-60595-407-3 Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results Cristian DAN

More information

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables 21, rue d Artois, F-75008 PARIS AUCKLAND 2013 http : //www.cigre.org Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables Michael Krüger, Rene Hummel, Stefan Böhler, OMICRON Austria

More information

PARTIAL DISCHARGE DETECTION - AN OVERVIEW

PARTIAL DISCHARGE DETECTION - AN OVERVIEW PARTIAL DISCHARGE DETECTION - AN OVERVIEW 1 MR. N. J. PATEL, 2 PROF. K. K. DUDANI, 3 PROF. A. K. JOSHI 1 M.E. [Power System] P.G. Student, Department of Electrical Engineering, L. E. College of Engineering,

More information

The R Portable Device for Partial Discharge Measurement and Analysis in High Voltage Equipment Insulation

The R Portable Device for Partial Discharge Measurement and Analysis in High Voltage Equipment Insulation The R2200 - Portable Device for Partial Discharge Measurement and Analysis in High Voltage Equipment Insulation DIMRUS Ltd. www.dimrus.ru 1 The R2200 Device is for Effective Partial Discharge (PD) Measurement

More information

UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES

UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES D. Götz*, H.T. Putter* *Megger Germany INTRODUCTION High voltage termintions are essential components in high voltage cable

More information

APPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS

APPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS APPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS David Larochelle NDB Technologies Reasons leading to acoustic testing are different weather it is a manufacturing or field environment

More information

Partial Discharge Monitoring of Power Transformers by UHF Sensors

Partial Discharge Monitoring of Power Transformers by UHF Sensors Partial Discharge Monitoring of Power Transformers by UHF Sensors S. Tenbohlen 1, M. Siegel², M. Beltle² 1 Institute of Power Transmission and High Voltage Technology (IEH), University of Stuttgart Pfaffenwaldring

More information

Research Article Design of a UHF Antenna for Partial Discharge Detection of Power Equipment

Research Article Design of a UHF Antenna for Partial Discharge Detection of Power Equipment Sensors, Article ID 839386, 8 pages http://dx.doi.org/1.1155/214/839386 Research Article Design of a UHF Antenna for Partial Discharge Detection of Power Equipment Youyuan Wang, Junfeng Wu, Weigen Chen,

More information

Application of High-Voltage Power Supply on Electrostatic Precipitator

Application of High-Voltage Power Supply on Electrostatic Precipitator World Journal of Engineering and Technology, 2017, 5, 269-274 http://www.scirp.org/journal/wjet ISSN Online: 2331-4249 ISSN Print: 2331-4222 Application of High-Voltage Power Supply on Electrostatic Precipitator

More information

TECHIMP Power Transformer Monitoring

TECHIMP Power Transformer Monitoring TECHIMP Power Transformer Monitoring Kontakt: Martin Hesse Techimp Germany GmbH i.g. E-Mail: mhesse@techimp.com Tel.: +49 5724 391 007 Mobil: +49 170 2364 735 PD Monitoring of Power Transformers Power

More information

PARTIAL DISCHARGE MEASUREMENT

PARTIAL DISCHARGE MEASUREMENT PARTIAL DISCHARGE MEASUREMENT Partial Discharges are small electrical sparks which occur predominantly at insulation imperfection. It is the phenomenon which occurs in the insulation on application of

More information

Research Article Study on Noise Prediction Model and Control Schemes for Substation

Research Article Study on Noise Prediction Model and Control Schemes for Substation e Scientific World Journal, Article ID 6969, 7 pages http://dx.doi.org/10.1155/201/6969 Research Article Study on Noise Prediction Model and Control Schemes for Substation Chuanmin Chen, Yang Gao, and

More information

Study on the Technology of Leakage Protection

Study on the Technology of Leakage Protection Send Orders for Reprints to reprints@benthamscience.ae 41 The Open Electrical & Electronic Engineering Journal, 014, 8, 41-418 Study on the Technology of Leakage Protection Open Access Shen Zixing 1,*,

More information

Research Article A New Kind of Circular Polarization Leaky-Wave Antenna Based on Substrate Integrated Waveguide

Research Article A New Kind of Circular Polarization Leaky-Wave Antenna Based on Substrate Integrated Waveguide Antennas and Propagation Volume 1, Article ID 3979, pages http://dx.doi.org/1.11/1/3979 Research Article A New Kind of Circular Polarization Leaky-Wave Antenna Based on Substrate Integrated Waveguide Chong

More information

Software System for Finding the Incipient Faults in Power Transformers

Software System for Finding the Incipient Faults in Power Transformers Software System for Finding the Incipient Faults in Power Transformers Nikolina Petkova Technical University of Sofia, Department of Theoretical Electrical Engineering, 1156 Sofia, Bulgaria Abstract In

More information

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 75 CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 5.1 INTRODUCTION Partial Discharge (PD) detection is an important tool for monitoring insulation conditions in high voltage (HV) devices in power systems.

More information

SAMPLE. Determining the health of your power transformer begins with Transformer Clinic s SAMPLE testing programs.

SAMPLE. Determining the health of your power transformer begins with Transformer Clinic s SAMPLE testing programs. Keep Powering On SAMPLE Determining the health of your power transformer begins with Transformer Clinic s SAMPLE testing programs. Overheating, arcing, partial discharge, and other active or slow-evolving

More information

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage Journal of Energy and Power Engineering 9 () 3-3 doi:.7/93-897/.3. D DAVID PUBLISHIG Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

More information

Hybrid Simulation of ±500 kv HVDC Power Transmission Project Based on Advanced Digital Power System Simulator

Hybrid Simulation of ±500 kv HVDC Power Transmission Project Based on Advanced Digital Power System Simulator 66 JOURNAL OF ELECTRONIC SCIENCE AND TECHNOLOGY, VOL. 11, NO. 1, MARCH 213 Hybrid Simulation of ±5 kv HVDC Power Transmission Project Based on Advanced Digital Power System Simulator Lei Chen, Kan-Jun

More information

Research on Transformer On-line Monitoring System of 500 kv Transformer Substation based on Vibration Method

Research on Transformer On-line Monitoring System of 500 kv Transformer Substation based on Vibration Method Sensors & Transducers 2013 by IFSA http://www.sensorsportal.com Research on On-line Monitoring System of 500 kv Substation based on Vibration Method 1 Wang Wen-Xing North China University of Water Resources

More information

Diagnosis of Water Tree Aging in XLPE Cable by the Loss Current Harmonic Component Under Variable Frequency Power

Diagnosis of Water Tree Aging in XLPE Cable by the Loss Current Harmonic Component Under Variable Frequency Power Journal of Electrical and Electronic Engineering 2015; 3(6): 208-214 Published online January 9, 2016 (http://www.sciencepublishinggroup.com/j/jeee) doi: 10.11648/j.jeee.20150306.16 ISSN: 2329-1613 (Print);

More information

Insulation Level and Test Technology of. 1000kV Power Transformer

Insulation Level and Test Technology of. 1000kV Power Transformer Insulation Level and Test Technology of 1000kV Power Transformer Li Guangfan, Wang Xiaoning, Li Peng et al HIMALAYAL - SHANGHAI - CHINA Abstract: The insulation coordination for the first 1000kV UHVAC

More information

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS Anne Pfeffer 1*, Stefan Tenbohlen 1 and Stefan Kornhuber 2 1 Institute of Power Transmission and High Voltage Technology, Pfaffenwaldring

More information

DEVELOPMENT OF HIGH-POWER, HIGH-FREQUENCY AND HIGH- VOLTAGE POWER SUPPLY SYSTEM FOR ELECTROSTATIC PRECIPITATOR

DEVELOPMENT OF HIGH-POWER, HIGH-FREQUENCY AND HIGH- VOLTAGE POWER SUPPLY SYSTEM FOR ELECTROSTATIC PRECIPITATOR ICESP X Australia 2006 Paper 11B2 DEVELOPMENT OF HIGH-POWER, HIGH-FREQUENCY AND HIGH- VOLTAGE POWER SUPPLY SYSTEM FOR ELECTROSTATIC PRECIPITATOR GUO JUN, QIU JIANXIN, CHEN YIN, XIE XIAO JIE AND LIANJINXIN

More information

HV AC TESTING OF SUPER-LONG CABLES

HV AC TESTING OF SUPER-LONG CABLES HV AC TESTING OF SUPER-LONG CABLES Stefan SCHIERIG, (Germany), schierig@highvolt.de Peter COORS, (Germany), coors@highvolt.de Wolfgang HAUSCHILD, IEC, CIGRE, (Germany), hauschild@highvolt.de ABSTRACT The

More information

Research Article Modified Dual-Band Stacked Circularly Polarized Microstrip Antenna

Research Article Modified Dual-Band Stacked Circularly Polarized Microstrip Antenna Antennas and Propagation Volume 13, Article ID 3898, pages http://dx.doi.org/1.11/13/3898 Research Article Modified Dual-Band Stacked Circularly Polarized Microstrip Antenna Guo Liu, Liang Xu, and Yi Wang

More information

The Open Automation and Control Systems Journal, 2015, 7, Application of Fuzzy PID Control in the Level Process Control

The Open Automation and Control Systems Journal, 2015, 7, Application of Fuzzy PID Control in the Level Process Control Send Orders for Reprints to reprints@benthamscience.ae The Open Automation and Control Systems Journal, 205, 7, 38-386 38 Application of Fuzzy PID Control in the Level Process Control Open Access Wang

More information

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N S C I E N C E P A S S I O N T E C H N O L O G Y HVDC Transmission Michael Muhr Graz University of Technology Austria www.tugraz.at 1 Definition HV High Voltage AC Voltage > 60kV 220kV DC Voltage > 60kV

More information

Partial Discharge Detection of High Voltage Switchgear Using a Ultra High Frequency Sensor

Partial Discharge Detection of High Voltage Switchgear Using a Ultra High Frequency Sensor TRANSACTIONS ON ELECTRICAL AND ELECTRONIC MATERIALS Vol. 14, No. 4, pp. 211-215, August 25, 2013 Regular Paper pissn: 1229-7607 eissn: 2092-7592 DOI: http://dx.doi.org/10.4313/teem.2013.14.4.211 Partial

More information

process has few stages and is highly repeatable. Excellent mechanic properties and electro-magnetic compatibility. Planar design gives the height lowe

process has few stages and is highly repeatable. Excellent mechanic properties and electro-magnetic compatibility. Planar design gives the height lowe PARTIAL DISCHARGE IN PLANAR TRANSFORMER Ing. Anar MAMMADOV, Doctoral Degreee Programme (1) Dept. of Microelectronics, FEEC, BUT E-mail: xmamed00@stud.feec.vutbr.cz Supervised by Dr. Jaroslav Boušek ABSTRACT

More information

How to Analyze and Test the Location of Partial. Discharge of Single-winding Transformer Model

How to Analyze and Test the Location of Partial. Discharge of Single-winding Transformer Model How to Analyze and Test the Location of Partial Discharge of Single-winding Transformer Model Huang Wangjun, Chen Yijun HIMALAYAL - SHANGHAI - CHINA Abstract: In order to detect transformer fault accurately

More information

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS Authored by: Sanjay Srivastava, Chief Engineer (HE&RM), Rakesh Kumar, Director (HE&RM), R.K. Jayaswal, Dy. Director (HE&RM)

More information

The Occurrence of Faults in Permanent Magnet Synchronous Motor Drives and its Effects on the Power Supply Quality

The Occurrence of Faults in Permanent Magnet Synchronous Motor Drives and its Effects on the Power Supply Quality The Occurrence of Faults in Permanent Magnet Synchronous Motor Drives and its Effects on the Power Supply Quality J. O. Estima A. J. Marques Cardoso University of Coimbra, FCTUC/IT Department of Electrical

More information

The importance of partial discharge testing throughout the development and operation of power transformers

The importance of partial discharge testing throughout the development and operation of power transformers The importance of partial discharge testing throughout the development and operation of power transformers Ulrike Broniecki OMICRON Energy Solutions GmbH, Berlin Power transformers are exposed to intense

More information

PDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics

PDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics PDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics CASE STUDY 1 (Doble Client Conference 2011, ACCA committee meeting) Dissolved Gas Analysis (DGA)

More information

FAULT DIAGNOSIS AND PERFORMANCE ASSESSMENT FOR A ROTARY ACTUATOR BASED ON NEURAL NETWORK OBSERVER

FAULT DIAGNOSIS AND PERFORMANCE ASSESSMENT FOR A ROTARY ACTUATOR BASED ON NEURAL NETWORK OBSERVER 7 Journal of Marine Science and Technology, Vol., No., pp. 7-78 () DOI:.9/JMST-3 FAULT DIAGNOSIS AND PERFORMANCE ASSESSMENT FOR A ROTARY ACTUATOR BASED ON NEURAL NETWORK OBSERVER Jian Ma,, Xin Li,, Chen

More information

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 7, July -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 Comparison

More information

OMICRON Seminar on Partial Discharge Diagnostics on HV Assets. January 30, 2018 Beirut, Lebanon

OMICRON Seminar on Partial Discharge Diagnostics on HV Assets. January 30, 2018 Beirut, Lebanon OMICRON Seminar on Partial Discharge Diagnostics on HV Assets January 30, 2018 Beirut, Lebanon Substation Asset Testing and Diagnosis LOW ACCURACY LEVEL HIGH Take better maintenance decisions through accurate

More information

Fault Detection in Transformer Using Frequency (Sweep) Response Analysis

Fault Detection in Transformer Using Frequency (Sweep) Response Analysis Fault Detection in Transformer Using Frequency (Sweep) Response Analysis Miss. Kajal R. Pachbhai PG Student at Ballarpur Institute of Technology, Ballarpur-442701 India kajalpachbhai86@gmail.com Mr. Sagar

More information

ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS

ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS Pantelis D. AGORIS 1, Sander MEIJER 1, Edward GULSKI 1, Johan J. SMIT 1, A. Jos L.M. KANTERS 2 1 Delft University of Technology - The Netherlands 2 TenneT

More information

Research on State Estimation and Information Processing Method for Intelligent Substation

Research on State Estimation and Information Processing Method for Intelligent Substation , pp.89-93 http://dx.doi.org/10.14257/astl.2015.83.17 Research on State Estimation and Information Processing Method for Intelligent Substation Tongwei Yu 1, Xingchao Yang 2 1 Electric Power Research Institute,

More information

HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL. Huazheng Electric Manufacturing(Baoding) Co.,Ltd

HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL. Huazheng Electric Manufacturing(Baoding) Co.,Ltd HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL Huazheng Electric Manufacturing(Baoding) Co.,Ltd Safety Terms and Symbols This manual may contain the terms: Warning! Indicate the conditions

More information

PARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER

PARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER PARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER N. R. Bhasme 1 and Bhushan Salokhe 2 1 Associate Prof., 2 M.E. Student, Dept. of Electrical Engg., Govt. College of Engineering

More information

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May 26 2011 St Pete Beach, Fl HDW ELECTRONICS, INC. THE BEST IN CABLE FAULT LOCATING TECHNOLOGY by Henning Oetjen Frank

More information

Influence of Impurity Concentration on Insulation Strength of Insulating Oil under Different Voltage Types

Influence of Impurity Concentration on Insulation Strength of Insulating Oil under Different Voltage Types 2017 2 nd International Conference on Artificial Intelligence and Engineering Applications (AIEA 2017) ISBN: 978-1-60595-485-1 Influence of Impurity Concentration on Insulation Strength of Insulating Oil

More information

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser,

More information

Why partial discharge testing makes good sense

Why partial discharge testing makes good sense Why partial discharge testing makes good sense PD measurement and analysis have proven to be reliable for detecting defects in the insulation system of electrical assets before major damage or a breakdown

More information

MONTRANO. Continuous monitoring system for power transformers

MONTRANO. Continuous monitoring system for power transformers MONTRANO Continuous monitoring system for power transformers Condition monitoring to extend transformer life Knowing the dielectric condition of insulation is vital Dielectric flashover of insulation in

More information

Comparison of capacitive and inductive sensors designed for partial discharges measurements in electrical power apparatus

Comparison of capacitive and inductive sensors designed for partial discharges measurements in electrical power apparatus Comparison of capacitive and inductive sensors designed for partial discharges measurements in electrical power apparatus Michał Kunicki 1,* 1 Opole University of Technology, ul. Prószkowska 76, 45-758

More information

Fushun Power Supply Company, Liaoning Electric Power Company Limited, State Grid, China

Fushun Power Supply Company, Liaoning Electric Power Company Limited, State Grid, China 2nd International Conference on Automation, Mechanical Control and Computational Engineering (AMCCE 2017) Harm and Preventive Measures of Transformer Outlet Short Circuit Hua Zhang1, Qinghao Wang 1, Guobin

More information

PARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM

PARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM Abstract PARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM Q. SU Department of Electrical & Computer Systems Engineering Monash University, Clayton VIC 3168 Email: qi.su@eng.monash.edu.au

More information

IGBT Induction Heater Profiles

IGBT Induction Heater Profiles IGBT Induction Heater Profiles United Induction Heating Machine Limited UIHM is experienced in Induction Heating Machine and Induction Heating Power Supply,induction heating equipments can be used in induction

More information

VARIABLE FREQUENCY RESONANT TEST SYSTEM

VARIABLE FREQUENCY RESONANT TEST SYSTEM VARIABLE FREQUENCY RESONANT TEST SYSTEM 400kV,1200kVA Tank Type Reactor for Outdoor Cable Test Field 650kV, 5850kVA, Cylinder Type Reactors for Onsite Testing of GIS and Cable PHENIX Variable Frequency

More information

IEEE Transactions on Power Delivery. 15(2) P.467-P

IEEE Transactions on Power Delivery. 15(2) P.467-P Title Author(s) Citation Detection of wide-band E-M signals emitted from partial discharge occurring in GIS using wavelet transform Kawada, Masatake; Tungkanawanich, Ampol; 河崎, 善一郎 ; 松浦, 虔士 IEEE Transactions

More information

Transient calibration of electric field sensors

Transient calibration of electric field sensors Transient calibration of electric field sensors M D Judd University of Strathclyde Glasgow, UK Abstract An electric field sensor calibration system that operates in the time-domain is described and its

More information

OMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates

OMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates OMICRON Seminar on Substation Testing and Diagnosis October 23, 2017 Dubai, United Arab Emirates October 24, 2017 Abu Dhabi, United Arab Emirates Time Optimized Substation Asset Testing and Diagnosis Agenda

More information

Investigation of PD Detection on XLPE Cables

Investigation of PD Detection on XLPE Cables Investigation of PD Detection on XLPE Cables Hio Nam O, T.R. Blackburn and B.T. Phung School of Electrical Engineering and Telecommunications The University New South Wales, Australia Abstract- The insulation

More information

Field Test and Analysis of Partial Discharge. on GIS Under Impulse Voltage

Field Test and Analysis of Partial Discharge. on GIS Under Impulse Voltage Field Test and Analysis of Partial Discharge on GIS Under Impulse Voltage HIMALAYAL - SHANGHAI - CHINA Sun Qiang, Dong Ming Abstract: It is shown that many GIS devices still have insulating faults even

More information

Research on the Effect of High Power Microwave on Low Noise Amplifier and Limiter Based on the Injection Method

Research on the Effect of High Power Microwave on Low Noise Amplifier and Limiter Based on the Injection Method J. Electromagnetic Analysis & Applications, 2010, 2: 111-115 doi:10.4236/jemaa.2010.22016 Published Online February 2010 (www.scirp.org/journal/jemaa) Research on the Effect of High on Low Noise Amplifier

More information

A New TEM Horn Antenna Designing Based on Plexiglass Antenna Cap

A New TEM Horn Antenna Designing Based on Plexiglass Antenna Cap Journal of Applied Science and Engineering, Vol. 21, No. 3, pp. 413 418 (2018) DOI: 10.6180/jase.201809_21(3).0012 A New TEM Horn Antenna Designing Based on Plexiglass Antenna Cap Lin Teng and Jie Liu*

More information

Open Access Sparse Representation Based Dielectric Loss Angle Measurement

Open Access Sparse Representation Based Dielectric Loss Angle Measurement 566 The Open Electrical & Electronic Engineering Journal, 25, 9, 566-57 Send Orders for Reprints to reprints@benthamscience.ae Open Access Sparse Representation Based Dielectric Loss Angle Measurement

More information

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location HAEFELY HIPOTRONICS Technical Document Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location P. Treyer, P. Mraz, U. Hammer Haefely Hipotronics, Tettex Instruments

More information

Open Access On Improving the Time Synchronization Precision in the Electric Power System. Qiang Song * and Weifeng Jia

Open Access On Improving the Time Synchronization Precision in the Electric Power System. Qiang Song * and Weifeng Jia Send Orders for Reprints to reprints@benthamscience.ae The Open Electrical & Electronic Engineering Journal, 2015, 9, 61-66 61 Open Access On Improving the Time Synchronization Precision in the Electric

More information

Autotransformer Condition Monitoring Systems

Autotransformer Condition Monitoring Systems Autotransformer Condition Monitoring Systems The Bidders shall offer separately the following systems of par.1 Integrated Condition Monitoring System and par.2 UHF PD Monitoring System. Two systems following

More information

High Voltage DC Transmission 2

High Voltage DC Transmission 2 High Voltage DC Transmission 2 1.0 Introduction Interconnecting HVDC within an AC system requires conversion from AC to DC and inversion from DC to AC. We refer to the circuits which provide conversion

More information

Simulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault of 10kV Power Grid

Simulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault of 10kV Power Grid 5th International Conference on Computer Sciences and Automation Engineering (ICCSAE 2015) Simulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault

More information

A Broadband High-Efficiency Rectifier Based on Two-Level Impedance Match Network

A Broadband High-Efficiency Rectifier Based on Two-Level Impedance Match Network Progress In Electromagnetics Research Letters, Vol. 72, 91 97, 2018 A Broadband High-Efficiency Rectifier Based on Two-Level Impedance Match Network Ling-Feng Li 1, Xue-Xia Yang 1, 2, *,ander-jialiu 1

More information

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Christian Suttner*, Stefan Tenbohlen Institute of Power Transmission and High Voltage Technology (IEH), University of

More information

Sources of transient electromagnetic disturbance in medium voltage switchgear

Sources of transient electromagnetic disturbance in medium voltage switchgear Sources of transient electromagnetic disturbance in medium voltage switchgear Dennis Burger, Stefan Tenbohlen, Wolfgang Köhler University of Stuttgart Stuttgart, Germany dennis.burger@ieh.uni-stuttgart.de

More information

Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission

Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission 17th World Conference on Nondestructive Testing, 25-28 Oct 2008, Shanghai, China Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission Oswaldo G. SANTOS FILHO 1, Sergio L. ZAGHETTO

More information

J.-H. Ryu Agency for Defense Development Yuseong, P. O. Box 35-5, Daejeon , Korea

J.-H. Ryu Agency for Defense Development Yuseong, P. O. Box 35-5, Daejeon , Korea Progress In Electromagnetics Research M, Vol. 16, 95 104, 2011 ELETROMAGNETIC SIMULATION OF INITIALLY CHARGED STRUCTURES WITH A DISCHARGE SOURCE J.-H. Ryu Agency for Defense Development Yuseong, P. O.

More information

Research Article CPW-Fed Wideband Circular Polarized Antenna for UHF RFID Applications

Research Article CPW-Fed Wideband Circular Polarized Antenna for UHF RFID Applications Hindawi International Antennas and Propagation Volume 217, Article ID 3987263, 7 pages https://doi.org/1.1155/217/3987263 Research Article CPW-Fed Wideband Circular Polarized Antenna for UHF RFID Applications

More information

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES Gonzalo MAIZ, Iberdrola Distribución, (Spain), gmaiz@iberdrola.es Armando RODRIGO, Instituto

More information

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems Romeo C. Ciobanu, Cristina Schreiner, Ramona Burlacu, Cristina Bratescu Technical

More information

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements EMEL ONAL Electrical Engineering Department Istanbul Technical University 34469 Maslak-Istanbul TURKEY onal@elk.itu.edu.tr http://www.elk.itu.edu.tr/~onal

More information

Research Article Miniaturized Circularly Polarized Microstrip RFID Antenna Using Fractal Metamaterial

Research Article Miniaturized Circularly Polarized Microstrip RFID Antenna Using Fractal Metamaterial Antennas and Propagation Volume 3, Article ID 7357, pages http://dx.doi.org/.55/3/7357 Research Article Miniaturized Circularly Polarized Microstrip RFID Antenna Using Fractal Metamaterial Guo Liu, Liang

More information

Research on Bamboo Hat ATC Control Design and Adjustment

Research on Bamboo Hat ATC Control Design and Adjustment Send Orders for Reprints to reprints@benthamscience.ae 1450 The Open Automation and Control Systems Journal, 2015, 7, 1450-1454 Open Access Research on Bamboo Hat ATC Control Design and Adjustment Tang

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits

More information

Research Article A Rectangular Planar Spiral Antenna for GIS Partial Discharge Detection

Research Article A Rectangular Planar Spiral Antenna for GIS Partial Discharge Detection Antennas and Propagation, Article ID 985697, 7 pages http://dx.doi.org/1.1155/21/985697 Research Article A Rectangular Planar Spiral Antenna for GIS Partial Discharge Detection Xiaoxing Zhang, 1 Yefei

More information

Coherence and time-frequency analysis of impulse voltage and current measurements

Coherence and time-frequency analysis of impulse voltage and current measurements Coherence and time-frequency analysis of impulse voltage and current measurements Jelena Dikun Electrical Engineering Department, Klaipeda University, Klaipeda, Lithuania Emel Onal Electrical Engineering

More information