Field Experiences. Partial Discharge Diagnosis on MV Cables. Philipp Legler. XVI. Szigetelésdiagnosztikai Konferencia (

Size: px
Start display at page:

Download "Field Experiences. Partial Discharge Diagnosis on MV Cables. Philipp Legler. XVI. Szigetelésdiagnosztikai Konferencia ("

Transcription

1 Field Experiences Partial Discharge Diagnosis on MV Cables Philipp Legler Technical Support Applications Engineer (Megger Site Germany) XVI. Szigetelésdiagnosztikai Konferencia ( , Sümeg)

2 Introduction Reasons of Cable Faults Most of them are Workmanship Failures Predominantly caused by Service Contractors (Man Power & Time issued) Main Reasons are Time Pressure - need to do xx Joints a Day (mostly caused by Purchase Department) Joint Hole not large enough Especially in Cities: to much other Cables / Pipes Climatic Conditions Not having the Skills / Certificates 2

3 Case Study No. 1 Operator: DREWAG Test Object: 12/20 kv & only XLPE insulated Cable Length: 367 m Joint Type: Tyco MXSU 5131 Measurement History: (only Phase L2) PD Diagnosis with OWTS 3

4 Case Study No. 1 PD Measurement Results of 1 st Diagnosis (2007) L1 L2 L3 Disturbance Level [pc] PDIV [kv rms ] PDEV [kv rms ] PD max [pc] (PDIV) PD avg [pc] (PDIV) PD max [pc] (U 0 ) PD avg [pc] (U 0 ) PD max [pc] (1.7 U 0 ) PD avg [pc] (1.7 U 0 ) Frequency [Hz]

5 Case Study No. 1 PD Mappings U U 0 U 1.7 U 0 DREWAG just started with Diagnosis (less Experiences & kind of missing Conviction for PD) No final Decision further Investigation 5

6 Case Study No. 1 PD Measurement Results of 2 nd Diagnosis (2012) L1 L2 L3 Disturbance Level [pc] PDIV [kv rms ] PDEV [kv rms ] PD max [pc] (PDIV) PD avg [pc] (PDIV) PD max [pc] (U 0 ) PD avg [pc] (U 0 ) PD max [pc] (1.7 U 0 ) PD avg [pc] (1.7 U 0 ) Frequency [Hz]

7 Case Study No. 1 PD Mappings U U 0 U 1.7 U 0 Even more clear Weak Spot Location, but still: NO final Decision further Investigation 7

8 Case Study No. 1 PD Measurement Results of 3 rd Diagnosis (2015) L1 L2 L3 Disturbance Level [pc] PDIV [kv rms ] PDEV [kv rms ] PD max [pc] (PDIV) PD avg [pc] (PDIV) PD max [pc] (U 0 ) PD avg [pc] (U 0 ) PD max [pc] (1.7 U 0 ) PD avg [pc] (1.7 U 0 ) Frequency [Hz]

9 Case Study No. 1 PD Mappings U U 0 U 1.7 U 0 NO Final Decision further Investigation 9

10 Case Study No. 1

11 Case Study No. 1 In the Meantime: Mainly Diagnosing the Cable Network Baseline Study with mostly no final Conclusion Only with Replacements on very important Cables BUT: PD Diagnosis performed on another Cable on the 7 th of May 2015 Clear concentration of PDs detected at several Location NO Action Breakdown on the 11 th of August 2015!!! Phase L1 & L2 (460 m) & Phase L3 (550 m) Turnaround inside DREWAG regarding Necessity of PD Diagnosis 11

12 Case Study No. 1 DECISION MAKING: Replacement of Joint at Phase L2 (210 m) 12

13 Case Study No. 1 13

14 Case Study No. 1 PD Measurement Results of 4 th Diagnosis (2015) PD-free after Replacement 14

15 Case Study No. 2 PD Testing done by ENSO Equipment: TDM-4540 Wave Shape Comparison Mixed MV Power Cable Length: 1335 m

16 Case Study No. 2 PD Measurement Results 16

17 PD Mapping Comparison Case Study No. 2 VLF Sinus DAC - 50 Hz Slope 0 U 1.7 U 0 0 U 1.0 U 0 VLF Sinus DAC - 50 Hz Slope

18 Case Study No. 2 TDR Diagrams L1 L2 L3 18

19 Case Study No m XLPE Cable Drum Operation Voltage: 5.8 kv 3 Customer made Weak Spots Competitor Comparison at Vienna Harness Racing Track with Centrix 2.0 & with integrated TDM-4540 Competitor could not find any Fault even not at higher Test Voltage 19

20 Case Study No. 3 20

21 Case Study No. 3 PD Measurement Results 21

22 Case Study No. 3 Voltage Wave Shape Comparison (PDIV & Weak Spot Location) PD Mapping for U 1.0 U 0 L1 DAC - L2 50 Hz Slope L3 VLF Sinus 22

23 Case Study No. 3 Voltage Wave Shape Comparison (PDIV & Weak Spot Location) PD Mapping for U 1.3 U 0 L1 DAC - L2 50 Hz Slope L3 VLF Sinus 23

24 Case Study No. 3 Voltage Wave Shape Comparison (PDIV & Weak Spot Location) PD Mapping for U 2.0 U 0 L1 DAC - L2 50 Hz Slope L3 VLF Sinus 24

25 VLF 0.1 Hz Sinusoidal vs. 50 Hz AC Case Study No. 4 Cable Information: 12/20 kv XLPE Cable (1992) Length: 1605 m PD Defect in Joint at 850 m Breakdown Channel starts at inner Field Grading Degrading of cable insulation 50 Hz AC PDIV = U 0 = 12 kv RMS VLF 0.1 Hz Sinusoidal PDIV > 2.5 U 0 = 30 kv RMS

26 VLF 0.1 Hz Sinusoidal vs. 50 Hz AC A few more detailed Pictures Case Study No. 4 Treeing at the inner field control section of the splice insulator Channel growth due to surface discharges at the splice insulation material Channel growth due to surface discharge at the cable insulation material Source: VWEW Infotag 2004, contribution E-On 26

27 VLF 0.1 Hz Sinusoidal vs. DAC Comparison Measurement 0.1 Hz & DAC Case Study No. 5 DAC Results PD detected & located 4 km 3.4 km & 3.6 km 3.4 km 27

28 VLF 0.1 Hz Sinusoidal vs. DAC Case Study No. 5 L1 L2 L3 VLF 0.1 Hz Sinusoidal Results PD Mapping up to 2 U0 PD located at L1: PD-free 3.6 km L3: PD-free

29 Case Study No. 5 Comparability & Reproducibility of PD Characteristics A Take Out from a Paper published in 2009 Source: Applied Voltage Frequency Dependence of Partial Discharges in Electrical Trees, N. Jäverberg, H. Edin, Proc. IR-EE-ETK, Stockholm, Sweden,

30 Diagnostic Test: New laid Cable 12 kv 3-single Phase Cable XLPE MV Cabel (NA2XS(F)2Y) Length: 2,308 km (7 Joints) Switch Gear: Driescher (air-insulated) Case Study No. 6 Cable Length: 2,3 km 30

31 TanDelta Measurement on new laid Cable Case Study No Source: IEEE (2013) Table G.1

32 Case Study No. 6 32

33 Case Study No. 6 33

34 Diagnostic Test: Service aged Cable 12/20 kv 3-single Phase Cable Mixed Cable (NEKBA & NA2XS(F)2Y) Length: 653 m (7 Joints) Switch Gear: Air-insulated Case Study No. 7 Cable Length: 2,3 km 34

35 TanDelta Measurement on service aged Cable Case Study No. 7 35

36 Case Study No. 7 PD Mapping Comparison 1.0 U U U 0 50 Hz Slope VLF Sinus 1.0 U U U 0

37 Summary Summary: PDIV of DAC & 50 Hz Slope Technology (VLF CR) with much lower compared to VLF Sin PD depends on Voltage Gradient over Time Lower the Change of Voltage Lower the PD Activity Results of VLF Sin difficult to interprete with PD Activities at Operation Frequency 37

38 38 Question Time

39 39 Let s have a break?

40 Contact Philipp Legler Applications Engineer Technical Support Telephone: +49 (0) Mobil: +49 (0) Köszönöm a figyelmet! 40

41 18/30 kv Medium Voltage Power Cable OWTS Diagnostic Measurement Joint Type: H&S Sucofit (African Manufacturer) Case Study No. 2 1 st PD Measurement: 13 th of November nd PD Measurement: 12 th of October rd PD Measurement: 23 rd of October

42 Case Study No. 2 PD Measurement Results of 1 st Diagnosis (2012) 42

43 PD Mapping Comparison: OWTS vs. PDD U U 0, U 0 = 18 kv RMS Case Study No. 2 U U 0, U 0 = 18 kv RMS 43

44 Case Study No. 2 Final Decision after PD Measurement & Evaluation Excavation of Joint on Phase L2 at 1400 m due to PDIV below U 0 Joints at 2050 m with PDIV above U 0 under Observation New Measurement after 3 Years 44

45 Further Results of Joint Investigation Inclusion of oily Fluidity Case Study No. 2 45

46 Bad Shrinkage of Stress Control Tube Case Study No. 2 Assumption: high Humidity Rating inside Joint Body 46

47 Case Study No. 2 Bad processed Mastic Tape resulting in Air Inclusions Discoloration due to Effect of Heat (bad Connection) 47

48 Case Study No. 2 Clear visible Creases on Insulating Body due to bad Peeling Partial Discharge Trackings over entire Length 48

49 Case Study No. 2 PD Measurement Results of 2 nd Diagnosis (2015) 49

50 PD Mapping Comparison: OWTS vs. PDD U U 0, U 0 = 18 kv RMS Case Study No. 2 U U 0, U 0 = 18 kv RMS 50

51 Case Study No. 2 Final Decision after PD Measurement & Evaluation Excavation of Joint at 2050 m due to PDIV below U 0 Weak Spots at 720 m & 1400 m with PDIV above U 0 under Observation New Measurement after 3 Years 51

52 Case Study No. 2 Moisture on Sheath Wires 52

53 Case Study No. 2 Bad shrinked Field Control 53

54 Case Study No. 2 Clear visible Creases on Insulating Body due to bad Peeling Partial Discharge Trackings over entire Length 54

55 PD Mapping Comparison: OWTS vs. PDD (3rd Measurement) U U 0, U 0 = 18 kv RMS Case Study No. 2 U U 0, U 0 = 18 kv RMS 55

56 Case Study No. 3 How can be a Woudlouse responsible for measuring PD or can cause a Cable Fault? 56

57 Example from the Cabinet of Curiosities Case Study No. 3 57

58 Example from the Cabinet of Curiosities Case Study No. 3

59 Case Study No. 5 VLF 0.1 Hz Sinusoidal vs. 50 Hz AC Research project of Norwegian University of Science & Technology Topic: Condition Assessment of Wind Farm Medium Voltage Cable Joints (by Hans Lavoll Halvorson) a) b) c) a) Dimension Drawing b) Reduced Cross Section c) Insulating Teflon Piece d) Metal Cylinder d)

60 Measurment Results Case Study No. 5 At VLF 0.1 Hz Sinusoidal PD were only detectable at higher Status of Aging Process All Joints PD-free Below 50 Hz no PD detectable Still Differences regarding PDIV 60

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES HEIN PUTTER Productmanager cable testing and -diagnosis Megger Site Germany 1 13 th Insucon conference 16-18 th Mai 2017, Birmingham, UK Agenda Introduction

More information

OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES

OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES Hein PUTTER Frank PETZOLD Philipp LEGLER Megger Germany Megger Germany Megger - Germany hein.putter@megger.com frank.petzold@megger.com philipp.legler@megger.com

More information

VLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing

VLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing Cable Testing & Diagnostics Solutions for Medium Voltage Networks (1 kv - 36 kv) VLF Partial Discharge DC DAC tandelta Cable Testing Cable Diagnostics? There are two main applications for cable testing:

More information

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May 26 2011 St Pete Beach, Fl HDW ELECTRONICS, INC. THE BEST IN CABLE FAULT LOCATING TECHNOLOGY by Henning Oetjen Frank

More information

USING DAMPED AC VOLTAGES

USING DAMPED AC VOLTAGES MODERN & TESTING DIAGNOSIS OF POWER CABLES USING DAMPED AC VOLTAGES BY EDWARD GULSKI AND ROGIER JONGEN, Onsite HV Solutions ag, Switzerland AND RALPH PATTERSON, Power Products & Solutions LLC, United States

More information

Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages

Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages F. Petzold, H.T. Putter, D. Götz, H. Schlapp, S. Markalous SebaKMT GmbH Baunach/Radeburg,

More information

CITY SERIES. Compact, fully equipped cable fault location, test and diagnostic systems

CITY SERIES. Compact, fully equipped cable fault location, test and diagnostic systems CITY SERIES Compact, fully equipped cable fault location, test and diagnostic systems Tailored to fit to small vehicles Easy operation in restricted spaces Centrally controlled, fully automatic system

More information

PD Testing Considerations for MV Plant Cables

PD Testing Considerations for MV Plant Cables PD Testing Considerations for MV Plant Cables Cable Testing Philosophy Damage Mistake Aging Repair Manufacturing Transportation Installation Operation Power frequency 50/60 Hz Power frequency 50/60 Hz

More information

Assuring the Reliability of Critical Power Cable Systems

Assuring the Reliability of Critical Power Cable Systems Assuring the Reliability of Critical Power Cable Systems Presented by: Benjamin Lanz Manager of Application Engineering IMCORP Power Cable Reliability Consulting & Diagnostics Some of the technologies

More information

Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics

Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics Dominique Bolliger, Ph.D. HV TECHNOLOGIES, Inc. Manassas, VA, USA d.bolliger@hvtechnologies.com Abstract In

More information

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland Company HV Diagnostics Sarl is a Swiss based company in the field of high voltage test equipment for cable testing and diagnosis.

More information

Partial discharge diagnostics on very long and branched cable circuits

Partial discharge diagnostics on very long and branched cable circuits 11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA

More information

ECP HV INSULATION TESTING

ECP HV INSULATION TESTING Document Number: ECP 11-0006 Network(s): Summary: All ENGINEERING COMMISSIONING PROCEDURE ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing of new and

More information

NEW. The new Centrix 2.0 sets the standard for testing, diagnosis and fault location of power cables.

NEW. The new Centrix 2.0 sets the standard for testing, diagnosis and fault location of power cables. The new Centrix 2.0 sets the standard for testing, diagnosis and fault location of power cables. NEW Intuitive easygo operation using a touch display Li-ion battery-power supply for the measurement system

More information

BY JASON SOUCHAK, Megger

BY JASON SOUCHAK, Megger IMPROVING SYSTEM RELIABILITY WITH OFFLINE PD TESTING BY JASON SOUCHAK, Megger Partial discharge (PD) testing is a new generation of diagnostic testing for medium- and high-voltage underground power cable

More information

Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen

Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen Aspects of PD interpretation in HV power cables by Edward Gulski, Piotr Cichecki, Rogier Jongen General There are several aspects having influence on the diagnostic information and the condition judgment

More information

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES Gonzalo MAIZ, Iberdrola Distribución, (Spain), gmaiz@iberdrola.es Armando RODRIGO, Instituto

More information

Test systems made by SebaKMT. Don t stress over tests! SebaKMT has the right answers: reliability, speed, economy.

Test systems made by SebaKMT. Don t stress over tests! SebaKMT has the right answers: reliability, speed, economy. Test systems made by SebaKMT Don t stress over tests! SebaKMT has the right answers: reliability, speed, economy. Know how to do it. And what happens next. Test first and save later Connected to the future

More information

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV Paul P. SEITZ, Seitz Instruments AG, (Switzerland), pps@seitz-instruments.ch Ben QUAK, Seitz Instruments AG, (Switzerland),

More information

ECP HV INSULATION TESTING

ECP HV INSULATION TESTING Document Number: ECP 11-0006 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE EPN, LPN, SPN ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing

More information

INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES

INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES Edward GULSKI, Delft University of Technology, (The Netherlands), e.gulski@tudelft.nl Johan J SMIT, Delft University of Technology, (The Netherlands),

More information

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY Avinash Raj 1, Chandan Kumar Chakrabarty 1, Rafidah Ismail 1 and Basri Abdul Ghani 2 1 College of Engineering, University Tenaga

More information

Cable fault location in power cables. Systematics for cable testing, diagnosis and cable fault location

Cable fault location in power cables. Systematics for cable testing, diagnosis and cable fault location Cable fault location in power cables Systematics for cable testing, diagnosis and cable fault location CABLE JOINTS, CABLE TERMINATIONS, CABLE GLANDS, CABLE CLEATS FEEDER PILLARS, FUSE LINKS, ARC FLASH,

More information

EI HIGH VOLTAGE INSULATION TESTING POLICY

EI HIGH VOLTAGE INSULATION TESTING POLICY Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and

More information

Cable diagnostic in MV underground cable networks

Cable diagnostic in MV underground cable networks Cable diagnostic in MV underground cable networks Theoretical background and practical application VLF testing tan delta loss factor measurement Partial discharge localization and measurement Author: Tobias

More information

OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM ELPIS J SINAMBELA

OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM ELPIS J SINAMBELA 1 OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM A thesis submitted to the Faculty of Electrical Power Engineering

More information

Equipment for cable fault location, testing and diagnostics

Equipment for cable fault location, testing and diagnostics Equipment for cable fault location, testing and diagnostics The world leader We are the world leader in cable test, diagnostic and fault location solutions. Featuring groundbreaking performance, robustness

More information

MV Power Cable Testing Training

MV Power Cable Testing Training MV Power Cable Testing Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Since power cables are used

More information

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid. 1. Scope This specification defines the methods, the procedures and the requirements to verify the cables manufactured according to I.E.C. Specifications NPS361. 2. Standards All the standards referred

More information

CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER

CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER Henrik ENOKSEN Espen EBERG Sverre HVIDSTEN SINTEF Energy Research - Norway SINTEF Energy Research - Norway SINTEF Energy Research

More information

PHG 70 TD PD / PHG 80 TD PD

PHG 70 TD PD / PHG 80 TD PD PHG 70 TD PD / PHG 80 TD PD BAUR VLF test and diagnostics system Functions Universal test and diagnostics system flexible, modular, extendable Cutting-edge testing and diagnostics technology: VLF truesinus

More information

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage Journal of Energy and Power Engineering 9 () 3-3 doi:.7/93-897/.3. D DAVID PUBLISHIG Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

More information

Centrix 2.0 The world s most modern and powerful cable test van system

Centrix 2.0 The world s most modern and powerful cable test van system The world s most modern and powerful cable test van system Centrix 2.0 The world s most modern and powerful cable test van system Intuitive easygo operation using a touch display System powered by Li-Ion

More information

Cable testing and diagnostics

Cable testing and diagnostics Cable testing and diagnostics To ensure the flow Cost-optimised maintenance through cable diagnostics The sheath and cable testing supports you in assessing whether a cable system is safe and ready to

More information

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES Frank WESTER, Edward GULSKI, Johan SMIT, Edwin GROOT*, Mark VAN VLIET* Delft University of Technology The Netherlands * NUON The Netherlands

More information

An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley

An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley ArborLec Solutions Inc. CIGRE WG 21:04 in 1994 Purpose of diagnostic test is: To evaluate and locate degradation phenomena

More information

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB MV Power Cable Diagnostics by Frequency Domain Spectroscopy Peter Werelius Programma Electric AB Frequency Domain Spectroscopy Measurements of insulation capacitance and losses in a frequency interval

More information

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables 21, rue d Artois, F-75008 PARIS AUCKLAND 2013 http : //www.cigre.org Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables Michael Krüger, Rene Hummel, Stefan Böhler, OMICRON Austria

More information

PARTIAL DISCHARGE LOCATION Selected Topics

PARTIAL DISCHARGE LOCATION Selected Topics PARTIAL DISCHARGE LOCATION Selected Topics M.S. Mashikian IMCORP ICC Meeting - Fall 2000 TOPICS TESTING PHILOSOPHY Excitation Voltage Test Voltage Level METHOD OF REFLECTOMETRY METHOD OF ARRIVAL TIME TESTING

More information

HVA SERIES VLF TEST SETS. Hipot Testers HVA Series for VLF (0.1 Hz) testing of MV and HV cables.

HVA SERIES VLF TEST SETS. Hipot Testers HVA Series for VLF (0.1 Hz) testing of MV and HV cables. HVA SERIES VLF TEST SETS Hipot Testers HVA Series for VLF (0.1 Hz) testing of MV and HV cables. INNOVATIVE, RELIABLE, ECONOMICAL HIGH VOLTAGE TESTING FROM b2 HIGH VOLTAGE VLF, DC, cable sheath testing

More information

Practical aspects of PD localization for long length Power Cables

Practical aspects of PD localization for long length Power Cables Practical aspects of PD localization for long length Power Cables M. Wild, S. Tenbohlen University of Stuttgart Stuttgart, Germany manuel.wild@ieh.uni-stuttgart.de E. Gulski, R. Jongen onsite hv technology

More information

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM,

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM, ONLINE OFFLINE VERSUS FEATURE PARTIAL DISCHARGE TESTING FOR CABLE ASSESSMENT B Y WIL L IAM H IG INBOT H AM, EA Technology, LLC Medium voltage cables have three distinct phases to their lifecycle: (1) new

More information

WIRE AND CABLE ENGINEERING GUIDE

WIRE AND CABLE ENGINEERING GUIDE Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime

More information

Doble Solutions for Partial Discharge. Greg Topjian Solutions Manager

Doble Solutions for Partial Discharge. Greg Topjian Solutions Manager Doble Solutions for Partial Discharge Greg Topjian Solutions Manager 617-393-3129 gtopjian@doble.com Why do we need to conduct PD measurements PD a major cause of early failure for HV insulation. Partial

More information

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages Paul P. SEITZ, Ben QUAK, Seitz Instruments AG, Niederrohrdorf, Switzerland, pps@seitz-instruments.ch Edward GULSKI,

More information

SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE

SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE Fred STEENNIS Paul WAGENAARS Denny HARMSEN DNV GL the Netherlands DNV GL the

More information

Name: Craig Goodwin. Company Name: HV Diagnostics Inc

Name: Craig Goodwin. Company Name: HV Diagnostics Inc Name: Craig Goodwin Company Name: HV Diagnostics Inc Trip Out of Cable Circuit: Over Current, Ground Fault, Differential protection or Fuse blows. Try to establish if the cable has in fact failed or has

More information

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 1. Introduction Fault location on communication and power cables

More information

PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE

PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE Fred STEENNIS, KEMA, (the Netherlands), fred.steennis@kema.com Peter VAN DER WIELEN, KEMA,

More information

Equipment for cable fault location, testing and diagnostics

Equipment for cable fault location, testing and diagnostics Smart Thump The Smart Thump is the only fault locator with built-in intelligence to interpret the results of the initial test sequence. The Turn & Click rotary button operation allows the user automatically

More information

ICC PES Spring 2011 Meeting, Educational Session Luigi Testa, Alfred Mendelsohn

ICC PES Spring 2011 Meeting, Educational Session Luigi Testa, Alfred Mendelsohn The use of pulse shape in PD testing of cable systems using VLF ICC PES Spring 2011 Meeting, Educational Session Luigi Testa, Alfred Mendelsohn 1 Introduction Hipot VLF testing of power cable systems is

More information

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM D. Clark¹ R. Mackinlay² M. Seltzer-Grant² S. Goodfellow² Lee Renforth² Jamie McWilliam³ and Roger

More information

Partial Discharge Trends in Medium Voltage Cables measured while in-service with PDOL

Partial Discharge Trends in Medium Voltage Cables measured while in-service with PDOL 1 Partial Discharge Trends in Medium Voltage Cables measured while in-service with PDOL André N. Cuppen, E. Fred Steennis, and Peter C. J. M. van der Wielen, Member, IEEE Abstract-- This paper presents

More information

PD Monitoring of MV/HV Power Cables December 2016

PD Monitoring of MV/HV Power Cables December 2016 PD Monitoring of MV/HV Power Cables December 216 Malcolm Seltzer-Grant m.seltzer-grant@hvpd.co.uk Introduction to HVPD Our global presence Introduction to HVPD Ltd HVPD are experts in the growing industry

More information

Transformer condition assessment with an integrated test van

Transformer condition assessment with an integrated test van Transformer condition assessment with an integrated test van 1 2012 SebaKMT Measuring and locating techniques MADE in GERMANY 2 Testing and Standards for Power Transformers CIGRE CIGRE Brochure 342 (SFRA-FRAX)

More information

A Study on the Effect of Performing VLF Withstand Tests on Field Aged Degraded Joints

A Study on the Effect of Performing VLF Withstand Tests on Field Aged Degraded Joints WETS D 15 2.4 Drapeau A Study on the Effect of Performing VLF Withstand Tests on Field Aged Degraded Joints Jean-François DRAPEAU Researcher Expertise Équipement électriques IREQ Jacques CÔTÉ, HQD Simon

More information

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of

More information

IDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy

IDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy IDAX 300 Insulation Diagnostic Analyzer Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy 1 Frequency Domain Spectroscopy Hi V A Lo Ground C HL Measure at several frequencies Use

More information

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences

More information

Dielectric response and partial discharge measurements on stator insulation at varied low frequency. Nathaniel Taylor

Dielectric response and partial discharge measurements on stator insulation at varied low frequency. Nathaniel Taylor Dielectric response and partial discharge measurements on stator insulation at varied low frequency Nathaniel Taylor Rotating Electrical Machines : The Stator and its Windings turbo-generator motor hydro-generator

More information

Medium Voltage Power Cables

Medium Voltage Power Cables N2XSY 6/0, /20, /30 NA2XSY 6/0, /20, /30 N2XS2Y 6/0, /20, /30 NA2XS2Y 6/0, /20, /30 N2XS(F)2Y 6/0, /20, /30 NA2XS(F)2Y 6/0, /20, /30 N2XSEY 3 x 6/0 Medium Voltage Power Cables Photo: HELUKABEL Q 47 Medium

More information

Partial discharge trends in medium voltage cables measured while in-service with PDOL Cuppen, A.N.; Steennis, E.F.; van der Wielen, P.C.J.M.

Partial discharge trends in medium voltage cables measured while in-service with PDOL Cuppen, A.N.; Steennis, E.F.; van der Wielen, P.C.J.M. Partial discharge trends in medium voltage cables measured while in-service with PDOL Cuppen, A.N.; Steennis, E.F.; van der Wielen, P.C.J.M. Published in: Proceedings of the IEEE PES Transmission and Distribution

More information

PD Solutions. On-Line PD Measurement Devices

PD Solutions. On-Line PD Measurement Devices On-Line PD Measurement Devices 1. Longshot Device (see Figure 1) The measurement system applied is based around the wideband (0-400 MHz) HVPD- Longshot partial discharge test unit which utilizes a high-speed

More information

PD-Diagnostics with. Information. Oscillating Wave Test System. Mess- und Ortungstechnik Measuring and Locating Techniques

PD-Diagnostics with. Information. Oscillating Wave Test System. Mess- und Ortungstechnik Measuring and Locating Techniques PD-Diagnostics with OWTS Leitungsortung Line Location PD-Diagnostics with OWTS Oscillating Wave Test System Mess- und Ortungstechnik Measuring and Locating Techniques Elektrizitätsnetze Power networks

More information

On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables

On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables William Higinbotham, Neil Davies and Victor Chan EA Technology LLC, New Jersey; USA, EA Technology Pty Ltd, Brisbane Australia; EA

More information

INFLUENCE OF VOLTAGE WAVEFORMS ON PARTIAL DISCHARGES DEVELOPED IN POWER CABLE INSULATION

INFLUENCE OF VOLTAGE WAVEFORMS ON PARTIAL DISCHARGES DEVELOPED IN POWER CABLE INSULATION INFLUENCE OF VOLTAGE WAVEFORMS ON PARTIAL DISCHARGES DEVELOPED IN POWER CABLE INSULATION LARISA MĂRIUŢ, ELENA HELEREA *1 Key words: Partial discharge, Inception voltage, Step-up voltage test method, Sinusoidal

More information

Characteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings

Characteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings J Electr Eng Technol Vol. 9, No. 1: 280-285, 2014 http://dx.doi.org/10.5370/jeet.2014.9.1.280 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 Characteristics of Insulation Diagnosis and Failure in Gas Turbine

More information

Electromagnetic environment in Electrical Hypersensitives homes and workplaces. Kjell Hansson Mild. National Institute for Working Life, Umeå, Sweden

Electromagnetic environment in Electrical Hypersensitives homes and workplaces. Kjell Hansson Mild. National Institute for Working Life, Umeå, Sweden Electromagnetic environment in Electrical Hypersensitives homes and workplaces National Institute for Working Life, Umeå, Sweden External sources: High voltage power lines, distribution lines magnetic

More information

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets Who we are TECHIMP is one of the leading providers of Condition Assessment Services Data Acquisition and Test Equipment

More information

NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY

NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY Lorenzo PERETTO Luigi FODDAI Simone ORRU Luigi PUDDU Altea Switzerland ENEL Italy ENEL Italy REPL Italy lperetto@alteasolutions.com

More information

H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C

H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C S O L U T I O N S Y O U R S O U R C E F O R T O P Q U A L I T Y T E S T E Q U I P M E N T w w w. h v t e c h n o l o g i e s. c o m Company

More information

Partial Discharge Patterns in High Voltage Insulation

Partial Discharge Patterns in High Voltage Insulation 22 IEEE International Conference on Power and Energy (PECon), 2-5 December 22, Kota Kinabalu Sabah, Malaysia Partial Discharge Patterns in High Voltage Insulation Hazlee Illias, Teo Soon Yuan, Ab Halim

More information

UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES

UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES D. Götz*, H.T. Putter* *Megger Germany INTRODUCTION High voltage termintions are essential components in high voltage cable

More information

NEW APPROACH FOR HIGH VOLTAGE CABLE ON-SITE TESTING

NEW APPROACH FOR HIGH VOLTAGE CABLE ON-SITE TESTING NEW APPROACH FOR HIGH VOLTAGE CABLE ON-SITE TESTING Volker BERGMANN, TU-Berlin, Dep. of HV-Engineering, (Germany), bergmann@ihs.ee.tu-berlin.de Peter MOHAUPT, BAUR Pruef- und Messtechnik GmbH, (Austria),

More information

Insulating oil testing

Insulating oil testing Insulating oil testing Insulating liquids are an important component of many electrical devices. Highly refined mineral oils, silicone oils, vegetable oils (natural ester) and synthetic ester ensure smooth

More information

شركة الوقت للكهرباء والمقاوالت ذ.م.م.

شركة الوقت للكهرباء والمقاوالت ذ.م.م. CONTRACTING COMPANY W.L.L. is a leading corporate in the United Arab Emirates offering quality services in the field of High Voltage Electrical work 400, 132 & 33 kv and Medium Voltage Power Distribution

More information

Specialists in HV and MV test and diagnostics. Testing in Substations

Specialists in HV and MV test and diagnostics. Testing in Substations Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies

More information

Quality Control of XLPE Cables by means of Impulse Voltage Test

Quality Control of XLPE Cables by means of Impulse Voltage Test Abstract Quality Control of XLPE Cables by means of Impulse Voltage Test R. Woschitz, M. Muhr, Ch. Sumereder High voltage cable lines are rated among the most expensive investments in the electric energy

More information

ABSTRACT INTRODUCTION DIAGNOSTIC TESTS. MAIN CHARACTERISTICS AND CONDITIONS OF 9 kv NETWORK

ABSTRACT INTRODUCTION DIAGNOSTIC TESTS. MAIN CHARACTERISTICS AND CONDITIONS OF 9 kv NETWORK LABORATORY AND ON SITE TESTS FOR THE DETERMINATION OF THE AGEING CONDITION OF MV PILC CABLES Nikola Kuljaca; Sergio Meregalli; Giuseppe Rizzi CESI RICERCA Italy sergio.meregalli@cesiricerca.it ABSTRACT

More information

3 THE REVIEW OF DISSERTATION

3 THE REVIEW OF DISSERTATION BUDAPEST UNIVERSITY OF TECHNOLOGY AND ECONOMICS DEPARTMENT OF ELECTRIC POWER ENGINEERING APPLICATION OF COMPLEX INSULATION DIAGNOSTICS ON LOW VOLTAGE CABLES PHD THESIS ZOLTÁN ÁDÁM TAMUS SUPERVISOR: PROFESSOR

More information

B Cut the Old Terminal from the Harness. Replace the terminal. 2. Select the correct replacement terminal with lead, from the supply parts.

B Cut the Old Terminal from the Harness. Replace the terminal. 2. Select the correct replacement terminal with lead, from the supply parts. B 27 Step 3. Existing terminal Replace the terminal. 1. Cut the Old Terminal from the Harness. Use the new wire lead as a guide for proper length. NOTE: If the length of wire removed is not approximately

More information

Off-Line Field Diagnostics for MV and HV Oil-Paper Insulated Cables

Off-Line Field Diagnostics for MV and HV Oil-Paper Insulated Cables 163 24 th Nordic Insulation Symposium on Materials, Components and Diagnostics Off-Line Field Diagnostics for MV and HV Oil-Paper Insulated Cables Sarajit Banerjee, Ali Naderian Kinectrics Inc., Toronto,

More information

Why partial discharge testing makes good sense

Why partial discharge testing makes good sense Why partial discharge testing makes good sense PD measurement and analysis have proven to be reliable for detecting defects in the insulation system of electrical assets before major damage or a breakdown

More information

Type Test of a 145 kv Termination Type TS 145-II

Type Test of a 145 kv Termination Type TS 145-II Test Report No 2009-125/2 Type Test of a 145 kv Termination Type TS 145-II Client: 3 M Deutschland GmbH Carl-Schurz-Str.1 41453 Neuss Reporter: Dr.-Ing. R. Badent Dr.-Ing. B. Hoferer This report includes

More information

Tests on Extruded Cables

Tests on Extruded Cables Tests on Extruded Cables Pierre Argaut Chairman of CIGRE SC B1 October 26 th, 2011 At least, once in your life, you have heard these words: Development Tests Long-term Tests Prequalification Tests Extension

More information

Diagnostic testing of cast resin transformers

Diagnostic testing of cast resin transformers Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com

More information

Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES. 11 kv XLPE-Insulated Three-Core Underground Cables

Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES. 11 kv XLPE-Insulated Three-Core Underground Cables Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES ( Data Sheets ) 11 kv XLPE-Insulated Three-Core Underground Cables (3x240 mm 2 ) ADWEA/ADDC/AADC STANDARD : D-AAA-CAB-11-3Cx240

More information

Wire System Aging Assessment and Condition Monitoring NKS-R WASCO

Wire System Aging Assessment and Condition Monitoring NKS-R WASCO Wire System Aging Assessment and Condition Monitoring NKS-R WASCO Paolo F. Fantoni OECD Halden Reactor Project Institutt for energiteknikk Halden, Norway Paolo.Fantoni@hrp.no NKS-R and NKS-B Joint Summary

More information

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Dr. Michael Krüger, Alexander Kraetge, OMICRON electronics GmbH, Austria Alexander

More information

Field Detected Cable Manufacturing Defects:

Field Detected Cable Manufacturing Defects: Field Detected Cable Manufacturing Defects: What do you do when it s the cable that s faulty? Steven Thomas, P.E. Sr. Electrical Engineer - HV Systems May 7, 2018 IMCORP Technology Users Group Meeting

More information

GENERATOR TESTING APPLICATION GUIDE. reliable. precision.

GENERATOR TESTING APPLICATION GUIDE.  reliable. precision. GENERATOR TESTING APPLICATION GUIDE www.haefely-hipotronics.com reliable. precision. 2 GENERATOR TESTING CONTENTS Product Line Overview 3 AC Hipot Testing 4 Partial Discharge Measurement 5 DC Hipot Testing

More information

Underground System Design TADP 547

Underground System Design TADP 547 Underground System Design TADP 547 Industry Standards, Specifications and Guides Presentation 6.4 Instructor: Frank Frentzas Industry Organizations Several professional organizations develop standards

More information

Ieee Guide For Partial Discharge Testing Of Shielded Power

Ieee Guide For Partial Discharge Testing Of Shielded Power Ieee Guide For Partial Discharge Testing Of Shielded Power We have made it easy for you to find a PDF Ebooks without any digging. And by having access to our ebooks online or by storing it on your computer,

More information

Online Localisation of Partial Discharge Using Pulse Propagation Parameters in Medium Voltage Cable Network

Online Localisation of Partial Discharge Using Pulse Propagation Parameters in Medium Voltage Cable Network 2015 17th UKSIM-AMSS International Conference on Modelling and Simulation Online Localisation of Partial Discharge Using n Parameters in Medium Voltage Cable Network Tauqeer Ahmed Shaikh, Abdulrehman Al-Arainy,

More information

GTRI/DOE Disclaimer. Cable Diagnostic Focused Initiative. Outline. CDFI Background. ICC Education Session. Nigel Hampton Rick Hartlein Joshua Perkel

GTRI/DOE Disclaimer. Cable Diagnostic Focused Initiative. Outline. CDFI Background. ICC Education Session. Nigel Hampton Rick Hartlein Joshua Perkel GTRI/DOE Disclaimer ICC Education Session Cable Diagnostic Focused Initiative Nigel Hampton Rick Hartlein Joshua Perkel Spring 9 Meeting The information contained herein is to our knowledge accurate and

More information

CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS

CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS 136 CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS H. van Jaarsveldt* and R. Gouws** School of Electrical, Electronic and Computer Engineering, North-West

More information

MATEFU Insulation co-ordination and high voltage testing of fusion magnets

MATEFU Insulation co-ordination and high voltage testing of fusion magnets Stefan Fink: MATEFU Insulation co-ordination and high voltage testing of fusion magnets Le Chateau CEA Cadarache, France April 7th, 29 Insulation co-ordination Some principle considerations of HV testing

More information

CIGRE- AORC Technical Meeting 2016 and International Conference on Global Trends in the Development of Power T&D System including Smart Grid

CIGRE- AORC Technical Meeting 2016 and International Conference on Global Trends in the Development of Power T&D System including Smart Grid CIGRE- AORC Technical Meeting 2016 and International Conference on Global Trends in the Development of Power T&D System including Smart Grid DEMANDS OF DIELECTRIC TESTING OF HVAC AND HVDC POWER CABLES

More information

EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE

EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE Ju-Chu Hsieh 1, Cheng-Chi Tai 1, Ching-Chau Su 1, Chien-Yi Chen 1, Ting-Cheng Huang 1, Yu-Hsun Lin 2 1 Department

More information