Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen

Size: px
Start display at page:

Download "Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen"

Transcription

1 Aspects of PD interpretation in HV power cables by Edward Gulski, Piotr Cichecki, Rogier Jongen General There are several aspects having influence on the diagnostic information and the condition judgment criteria for HV power cables: 1. Connection setting of the testing and diagnostic setup: earth connection configuration, where the earthing was connected? Close to sealing end or to main substation ground? 2. Background noise level: measurements in close substation and open substation in close distance to corona discharges sources will differ. In many cases background noise level can extend over 100pC so than PD pattern characteristics play major role in describing defect. Also in situation when high noise level is present, measurements are performed in comparative basis way (comparison of PD levels between cable phases). 3. Specific situation: e.g.: in some countries there is a lot of XLPE cables from 50 s and 60 s This cable suffer from water treeing and electrical treeing as the result they fail often. In other countries the XLPE cables were introduced in 80 and they have already improved water barrier protection so we do not face the problem of water treeing. Some countries have more problems e.g. with gas pressure and oil-filled cables instead of XLPE cables. 4. What type of cable is measured: mass impregnated/ oil filled (low or high pressure)/gas pressure cable. Each type of cable has own PD and tan delta characteristics. Moreover serviced aged cables may differ as the load and service condition are always different. Important is the age of the cable, operational history and failure history. Criteria of PD acceptance for HV power cables With regard to the criteria of PD acceptance for HV power cables the following has to be considered: 1. In general, due to significantly higher electric field strengths in the insulation and the accessories of HV power cables the degradation processes of discharging defects are much faster than those in MV power cables. 2. Therefore, at nominal voltage U 0 (during operation) the insulation of all HV XLPE cables should be PD free! Due to the fact that there are no international standards or guidelines for on-site PD detection and PD level acceptance for HV power cables the on the one hand and due to the fact that cable and accessories manufactures are delivering PD-free systems on the other hand the PD freedom of XLPE HV cables is important. 3. 1

2 4. Nevertheless it is possible that in certain type of insulation e.g. massimpregnated insulation or certain type of HV cables accessories the PD may occur during service life. But in general the HV cables are supposed to be PD free during operation [14]. 5. On the other hand we must be aware of local problems like water/electric treeing, background noise level. Important is to do analysis of VHF (TDR localization) record so there we can see real PD pulse characteristic. In case of PD we are not sure try to do TDR analysis and localize the problem. Practical aspects If PD are repetitive and it is confidence regarding PDIV level e.g: PDIV < U 0 (50kV) in next step must be distinguished if PD pulse is internal or external (noise) indicators: Increase of PD level in function of test voltage, PD pattern characteristics, TDR analysis. If PD is stable and possible localization than such PD level in [pc] must be recorded. Regarding interpretation some field experience values for HV power cables are shown in Table 1: Table 1: Cable type Safe Semi safe Dangerous XLPE new/old Localized PD in the cable insulation HV XLPE have to be PD free with a background noise level in the range of 25pC..30pC or lower. XLPE old Localized PD in accessories <25pC <100pC > 100pC Only as an Not localized PD <100pC <500pC >1000pC Only as an Oil-paper (oilfiled low pressure) old Oil-paper (oilfiled Localized PD in low cable insulation pressure) old and accessories Gas cable Not localized <25pC <300pC >500pC Gas cable Localized in cable <25pC insulation and accessories <50pC <200pC >200pC Only as an HV Gas pressure have to be PD free with a background noise level in the range of 25pC and lower The above table has relation to PD inception at test voltage > U 0. Moreover thie following has to be considered: - If the HV power cables is PD free up to 1.7 U 0 it can be concluded that no dangerous PD activity is active now and the quality insulation of this particular cable is high. - If the PDIV is below 1.7 U 0 and higher than 1.2 U 0 the cable can still be considered as PD-free and the quality insulation of this particular cable is good. - If the HV power cable has PDIV =< U 0 the cable is not PD free and extensive interpretation and application of cable typical knowledge is necessary to estimate the hazard of these PD s. 2

3 Power cable system: cable insulation and cable accessories (joints, terminations) are defect free. Power cable can withstand operational stresses without any impact to quality of the energy delivery (scenario for new and serviced aged circuits which were tested on-site and threshold limits for diagnostic parameters were not exceeded; breakdown did not occur during on-site voltage test or condition assessment test). Power cable fulfilled requirements for the factory tests but on-site after-laying test showed that there is defect present in cable system. In this situation two other scenarios are possible: a. Defect is present below nominal (U 0 ) voltage of the cable (U 0 ). Decision regarding repair, or maintenance (periodical monitoring measurements) has to be taken to avoid un-expected breakdown in service. b. Defect is present above nominal voltage (1.1U U 0 ) In this case (if defect has destructive character), defect prosperities described by diagnostic parameters may change in time. This can result in lowering dielectric strength of the cable accessory or cable insulation and lead to breakdown. Power cable failed (breakdown or weak-spots localized in the circuits) during afterlaying test, condition assessment or after repair test. Without maintenance decisions no further safe service operation is possible. Test Measurement Procedure e.g. OWTS HV150 The measurement is performed according to the scheme as shown in table 2. The test voltage is raised in steps of 10 kv and three shots at each voltage level are performed. During the damped AC voltage PD and dielectric losses is measured. Table 2: No. U rms [kv] U peak [kv] x U U peak [kv x Uo 3

4 During the test the following parameters will be estimated: PD inception voltage in kv PD level at PDIV in pc PD level at U0 in pc Depending on the PD level at Uo at each voltage higher than Uo a decision will be considered about the further increase of the test voltage. According to the IEEE400 documentation 50 damped AC excitations can be applied at maximum acceptable test voltage (equivalent of the voltage withstand test). According to the IEC60840 for new installed 110 kv power cables the test voltage after installation is 128 kv rms (2 U 0 ). For service aged cables the maximum test voltage has to be considered with the cable owner and is dependant on the history of the cable life (operational load, maintenance, failures, age). The following norms are applicable: IEC : High Voltage test techniques Part 3: Definitions and requirements for on-site testing; IEEE 400: Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems; IEEE 400.3: Guide for PD Testing of Shielded Power Cable Systems in a Field Environment; IEC 60270: Partial discharges measurements; IEC : Test methods for partial discharges measurements on lengths of extruded power cable; IEC 60840: Power cables with extruded insulation and the accessories for rated voltages above 30kV up to 150kV Test methods and requirements; IEC 62067: Power cables with extruded insulation and the accessories for rated voltages above 150kV; IEC 60141: Tests on oil-filled and gas-pressure cables and their accessories up to and including 400kV part 2; 4

5 References [1] Cigre Working Group B1.04, Brochure 279 Maintenance for HV Cables and Accessories [2] Cigre Working Group B1.09, Brochure 358 Remaining Life Management of Existing Underground Lines [3] Cigre Working Group D1.11, Brochure 228, Service Aged Insulation Materials [4] P.P. Seitz, B. Quak, E. Gulski, J.J. Smit, P. Cichecki, F. de Vries, F. Petzold, Novel Method for On-site Testing and Diagnosis of Transmission Cables up to 250kV, Proceedings JiCable '07. 7th Intern. Conf. Insulated Power Cables, Versailles, France, Paper 16, 2007 [5] F.J. Wester, E. Gulski and J.J. Smit, Detection of PD at Different AC Voltage Stresses in Power Cables, IEEE Electr. Insul. Mag., Vol. 23, No. 4, pp , 2007 [6] E. Gulski, E. Lemke, M. Gamlin, E. Gockenbach, W. Hauschild, E. Pultrum, Experiences in partial discharge detection of distribution power cable systems. Cigre, Vol 208 Electra, pp , 2003 [7] E. Gulski. P. Cichecki, E.R.S. Groot, J.J. Smit, F. de Vries, J. Slangen, Slangen. E.R.S.Groot, J. Pellis, D. van Houwelingen, T.J.W.H. Hermans, B. Wegbrands and L. Lamballais, Conditon Assessment of Service Aged HV Power Cables, Cigre, Paper D1-206, 2008 [8] J. Popma J. Pellis, Diagnostics for high voltage cable systems, proceedings ERA conference on HV plant life extension, Belgium, November, [9] J. Densley, Ageing Mechanisms and Diagnostics for Power Cables An Overview, IEEE Electrical Insulation Magazine, Vol. 17 Nr. 1 pp14-21, Jan/Feb 2001 [10] E. Gulski, E, F.J. Wester, Ph. Wester, E.R.S. Groot, J.W. van Doeland, Condition assessment of high voltage power cables. Proceedings CIGRE 2004 Session, paper D [11] E. Gulski, J.J. Smit, P. Cichecki, P.P. Seitz, B. Quak, F. de Vries, F. Petzold, Insulation Diagnosis of HV Power Cables, Proceedings Jicable '07. 7th International Conference on Insulated Power Cables, France, Versailles, June 2007, paper 51. [12] E. Gulski, P. Cichecki, J.J. Smit, F. de Vries, Vries. Bodega, Th. Hermans, P.P. Seitz, Dielectric loss diagnosis of service aged HV power cables, Proceedings of Cigre D1 Colloquium, Hungary Budapest, 2009 [13] E. Gulski, P.P. Seitz, B. Quak, F. Petzold, F. de Vries, (2008). Dedicated on-site condition monitoring of high voltage power cables up to 150kV. International journal of emerging electric power systems, 9(3), 1-15 [14] P. Cichecki, R.A. Jongen, E. Gulski, J.J. Smit, (2008). Statistical approach in power cables diagnostic data analysis. IEEE transactions on dielectrics and electrical insulation, 15(6), [15] E. Gulski, P. Cichecki, F.J. Wester, J.J. Smit, R. Bodega, T.J.W.H. Hermans, P.P. Seitz, B. Quak, F. de Vries, (2008). On-site testing and PD diagnosis of high voltage power cables. IEEE transactions on dielectrics and electrical insulation [16] IEC60502 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (Um = 1,2 kv) up to 30 kv (Um = 36 kv) - Part 1: Cables for rated voltages of 1 kv (Um = 1,2 kv) and 3 kv (Um = 3,6 kv) [17] E. Gulski, P. Cichecki, J.J. Smit, F. de Vries, J. Pellis, D. van Houwelingen, F. Wester, R. Bodega, Th. Hermans, Condition Assessment of Transmission Power Cables, Cigre 2010, paper D1 205_2010 5

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages Paul P. SEITZ, Ben QUAK, Seitz Instruments AG, Niederrohrdorf, Switzerland, pps@seitz-instruments.ch Edward GULSKI,

More information

INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES

INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES Edward GULSKI, Delft University of Technology, (The Netherlands), e.gulski@tudelft.nl Johan J SMIT, Delft University of Technology, (The Netherlands),

More information

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV Paul P. SEITZ, Seitz Instruments AG, (Switzerland), pps@seitz-instruments.ch Ben QUAK, Seitz Instruments AG, (Switzerland),

More information

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May 26 2011 St Pete Beach, Fl HDW ELECTRONICS, INC. THE BEST IN CABLE FAULT LOCATING TECHNOLOGY by Henning Oetjen Frank

More information

USING DAMPED AC VOLTAGES

USING DAMPED AC VOLTAGES MODERN & TESTING DIAGNOSIS OF POWER CABLES USING DAMPED AC VOLTAGES BY EDWARD GULSKI AND ROGIER JONGEN, Onsite HV Solutions ag, Switzerland AND RALPH PATTERSON, Power Products & Solutions LLC, United States

More information

Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages

Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages F. Petzold, H.T. Putter, D. Götz, H. Schlapp, S. Markalous SebaKMT GmbH Baunach/Radeburg,

More information

Kurzfassung. Abstract. 1 Introduction

Kurzfassung. Abstract. 1 Introduction Untersuchung von Teilentladungsverhalten mit Wechselspannung und gedämpfter Wechselspannung Investigation of partial discharge behaviour with alternating current and damped alternating current Manuel Wild,

More information

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES Frank WESTER, Edward GULSKI, Johan SMIT, Edwin GROOT*, Mark VAN VLIET* Delft University of Technology The Netherlands * NUON The Netherlands

More information

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage Journal of Energy and Power Engineering 9 () 3-3 doi:.7/93-897/.3. D DAVID PUBLISHIG Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

More information

Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics

Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics Dominique Bolliger, Ph.D. HV TECHNOLOGIES, Inc. Manassas, VA, USA d.bolliger@hvtechnologies.com Abstract In

More information

Partial discharge diagnostics on very long and branched cable circuits

Partial discharge diagnostics on very long and branched cable circuits 11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA

More information

OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES

OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES Hein PUTTER Frank PETZOLD Philipp LEGLER Megger Germany Megger Germany Megger - Germany hein.putter@megger.com frank.petzold@megger.com philipp.legler@megger.com

More information

INFLUENCE OF VOLTAGE WAVEFORMS ON PARTIAL DISCHARGES DEVELOPED IN POWER CABLE INSULATION

INFLUENCE OF VOLTAGE WAVEFORMS ON PARTIAL DISCHARGES DEVELOPED IN POWER CABLE INSULATION INFLUENCE OF VOLTAGE WAVEFORMS ON PARTIAL DISCHARGES DEVELOPED IN POWER CABLE INSULATION LARISA MĂRIUŢ, ELENA HELEREA *1 Key words: Partial discharge, Inception voltage, Step-up voltage test method, Sinusoidal

More information

PD Testing Considerations for MV Plant Cables

PD Testing Considerations for MV Plant Cables PD Testing Considerations for MV Plant Cables Cable Testing Philosophy Damage Mistake Aging Repair Manufacturing Transportation Installation Operation Power frequency 50/60 Hz Power frequency 50/60 Hz

More information

Estimating the Impact of VLF Frequency on Effectiveness of VLF Withstand Diagnostics

Estimating the Impact of VLF Frequency on Effectiveness of VLF Withstand Diagnostics Estimating the Impact of VLF on Effectiveness of VLF Withstand Diagnostics Nigel Hampton (1), Jean Carlos Hernandez-Mejia (2), Marina Kuntsevich (3), Joshua Perkel (1), Vivek Tomer (3) 1 - NEETRAC, Atlanta,

More information

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY Avinash Raj 1, Chandan Kumar Chakrabarty 1, Rafidah Ismail 1 and Basri Abdul Ghani 2 1 College of Engineering, University Tenaga

More information

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES HEIN PUTTER Productmanager cable testing and -diagnosis Megger Site Germany 1 13 th Insucon conference 16-18 th Mai 2017, Birmingham, UK Agenda Introduction

More information

Cable testing and diagnostics

Cable testing and diagnostics Cable testing and diagnostics To ensure the flow Cost-optimised maintenance through cable diagnostics The sheath and cable testing supports you in assessing whether a cable system is safe and ready to

More information

OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM ELPIS J SINAMBELA

OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM ELPIS J SINAMBELA 1 OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM A thesis submitted to the Faculty of Electrical Power Engineering

More information

VLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing

VLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing Cable Testing & Diagnostics Solutions for Medium Voltage Networks (1 kv - 36 kv) VLF Partial Discharge DC DAC tandelta Cable Testing Cable Diagnostics? There are two main applications for cable testing:

More information

PHG 70 TD PD / PHG 80 TD PD

PHG 70 TD PD / PHG 80 TD PD PHG 70 TD PD / PHG 80 TD PD BAUR VLF test and diagnostics system Functions Universal test and diagnostics system flexible, modular, extendable Cutting-edge testing and diagnostics technology: VLF truesinus

More information

Testing of 400 kv GIS

Testing of 400 kv GIS Testing of 400 kv GIS Robert le Roux, Dermot Dorgan, Brian Perry ESB International - Ireland Paper 028 1 Introduction The 400 kv transmission is designed for critical periods of low loading. Due to critical

More information

HV AC TESTING OF SUPER-LONG CABLES

HV AC TESTING OF SUPER-LONG CABLES HV AC TESTING OF SUPER-LONG CABLES Stefan SCHIERIG, (Germany), schierig@highvolt.de Peter COORS, (Germany), coors@highvolt.de Wolfgang HAUSCHILD, IEC, CIGRE, (Germany), hauschild@highvolt.de ABSTRACT The

More information

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015 Basics of Partial Discharge Prepared for 2015 Phenix RSM Meeting January 2015 Definitions and History Standard Definitions Fundamentally, what is a Partial Discharge An electric discharge which only partially

More information

Specialists in HV and MV test and diagnostics. Testing in Substations

Specialists in HV and MV test and diagnostics. Testing in Substations Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies

More information

Practical aspects of PD localization for long length Power Cables

Practical aspects of PD localization for long length Power Cables Practical aspects of PD localization for long length Power Cables M. Wild, S. Tenbohlen University of Stuttgart Stuttgart, Germany manuel.wild@ieh.uni-stuttgart.de E. Gulski, R. Jongen onsite hv technology

More information

BY JASON SOUCHAK, Megger

BY JASON SOUCHAK, Megger IMPROVING SYSTEM RELIABILITY WITH OFFLINE PD TESTING BY JASON SOUCHAK, Megger Partial discharge (PD) testing is a new generation of diagnostic testing for medium- and high-voltage underground power cable

More information

SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE

SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE Fred STEENNIS Paul WAGENAARS Denny HARMSEN DNV GL the Netherlands DNV GL the

More information

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES Gonzalo MAIZ, Iberdrola Distribución, (Spain), gmaiz@iberdrola.es Armando RODRIGO, Instituto

More information

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables 21, rue d Artois, F-75008 PARIS AUCKLAND 2013 http : //www.cigre.org Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables Michael Krüger, Rene Hummel, Stefan Böhler, OMICRON Austria

More information

EI HIGH VOLTAGE INSULATION TESTING POLICY

EI HIGH VOLTAGE INSULATION TESTING POLICY Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and

More information

Assuring the Reliability of Critical Power Cable Systems

Assuring the Reliability of Critical Power Cable Systems Assuring the Reliability of Critical Power Cable Systems Presented by: Benjamin Lanz Manager of Application Engineering IMCORP Power Cable Reliability Consulting & Diagnostics Some of the technologies

More information

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland Company HV Diagnostics Sarl is a Swiss based company in the field of high voltage test equipment for cable testing and diagnosis.

More information

CIGRE- AORC Technical Meeting 2016 and International Conference on Global Trends in the Development of Power T&D System including Smart Grid

CIGRE- AORC Technical Meeting 2016 and International Conference on Global Trends in the Development of Power T&D System including Smart Grid CIGRE- AORC Technical Meeting 2016 and International Conference on Global Trends in the Development of Power T&D System including Smart Grid DEMANDS OF DIELECTRIC TESTING OF HVAC AND HVDC POWER CABLES

More information

ECP HV INSULATION TESTING

ECP HV INSULATION TESTING Document Number: ECP 11-0006 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE EPN, LPN, SPN ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing

More information

Partial Discharge Patterns in High Voltage Insulation

Partial Discharge Patterns in High Voltage Insulation 22 IEEE International Conference on Power and Energy (PECon), 2-5 December 22, Kota Kinabalu Sabah, Malaysia Partial Discharge Patterns in High Voltage Insulation Hazlee Illias, Teo Soon Yuan, Ab Halim

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 1. Introduction Fault location on communication and power cables

More information

ECP HV INSULATION TESTING

ECP HV INSULATION TESTING Document Number: ECP 11-0006 Network(s): Summary: All ENGINEERING COMMISSIONING PROCEDURE ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing of new and

More information

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB MV Power Cable Diagnostics by Frequency Domain Spectroscopy Peter Werelius Programma Electric AB Frequency Domain Spectroscopy Measurements of insulation capacitance and losses in a frequency interval

More information

Cable diagnostic in MV underground cable networks

Cable diagnostic in MV underground cable networks Cable diagnostic in MV underground cable networks Theoretical background and practical application VLF testing tan delta loss factor measurement Partial discharge localization and measurement Author: Tobias

More information

Reprint E Two Years of Experience with a Mobile Resonant Test System for Testing of Installed Medium- and High Voltage Power Cables

Reprint E Two Years of Experience with a Mobile Resonant Test System for Testing of Installed Medium- and High Voltage Power Cables Two Years of Experience with a Mobile Resonant System for ing of Installed Medium- and High Voltage Power Cables P. Schikarski M. Gamlin J. Rickmann P. Peeters P. v.d. Nieuwendijk R. Koning Reprint ISH

More information

Field Experiences. Partial Discharge Diagnosis on MV Cables. Philipp Legler. XVI. Szigetelésdiagnosztikai Konferencia (

Field Experiences. Partial Discharge Diagnosis on MV Cables. Philipp Legler. XVI. Szigetelésdiagnosztikai Konferencia ( Field Experiences Partial Discharge Diagnosis on MV Cables Philipp Legler Technical Support Applications Engineer (Megger Site Germany) XVI. Szigetelésdiagnosztikai Konferencia (19. - 20.10.2016, Sümeg)

More information

Underground System Design TADP 547

Underground System Design TADP 547 Underground System Design TADP 547 Industry Standards, Specifications and Guides Presentation 6.4 Instructor: Frank Frentzas Industry Organizations Several professional organizations develop standards

More information

PD Diagnostic Applications and TechImp solutions

PD Diagnostic Applications and TechImp solutions PD Diagnostic Applications and TechImp solutions Condition Assessment Solutions for Electrical Systems. PD based innovative tools for the Condition Based Maintenance. MD-04.05.004 - rev. 00-29/08/2006

More information

Why partial discharge testing makes good sense

Why partial discharge testing makes good sense Why partial discharge testing makes good sense PD measurement and analysis have proven to be reliable for detecting defects in the insulation system of electrical assets before major damage or a breakdown

More information

Diagnostic testing of cast resin transformers

Diagnostic testing of cast resin transformers Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com

More information

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales

More information

An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley

An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley ArborLec Solutions Inc. CIGRE WG 21:04 in 1994 Purpose of diagnostic test is: To evaluate and locate degradation phenomena

More information

MV Power Cable Testing Training

MV Power Cable Testing Training MV Power Cable Testing Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Since power cables are used

More information

Power Transformer Condition Assessment Based on Standard Diagnosis

Power Transformer Condition Assessment Based on Standard Diagnosis Power Transformer Condition Assessment Based on Standard Cattareeya Suwanasri Abstract The diagnostic techniques of electrical and insulating oil testing are proposed to assess the internal condition of

More information

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of

More information

A6.6 9 th International Conference on Insulated Power Cables A6.6

A6.6 9 th International Conference on Insulated Power Cables A6.6 Development Process of extruded HVDC cable systems Dominik HÄRING, Gero SCHRÖDER, Andreas WEINLEIN, Axel BOSSMANN Südkabel GmbH, (Germany) dominik.haering@suedkabel.com, gero.schroeder@suedkabel.com, andreas.weinlein@suedkabel.com,

More information

Tests on Extruded Cables

Tests on Extruded Cables Tests on Extruded Cables Pierre Argaut Chairman of CIGRE SC B1 October 26 th, 2011 At least, once in your life, you have heard these words: Development Tests Long-term Tests Prequalification Tests Extension

More information

CIGRE General Session, Paris 2014 Group Meeting SC B1 Insulated Cables, 27th August, 2014 Results of CAG Questionnaire

CIGRE General Session, Paris 2014 Group Meeting SC B1 Insulated Cables, 27th August, 2014 Results of CAG Questionnaire 1 1. Number of Questionnaires Returned 23 2. Number of suggestions for work 64 3. Suggestions for new work within the scope of SCB1 or for additional work by current Working Groups in? 3.1 cable system

More information

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences

More information

A Study on the Effect of Performing VLF Withstand Tests on Field Aged Degraded Joints

A Study on the Effect of Performing VLF Withstand Tests on Field Aged Degraded Joints WETS D 15 2.4 Drapeau A Study on the Effect of Performing VLF Withstand Tests on Field Aged Degraded Joints Jean-François DRAPEAU Researcher Expertise Équipement électriques IREQ Jacques CÔTÉ, HQD Simon

More information

PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE

PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE Fred STEENNIS, KEMA, (the Netherlands), fred.steennis@kema.com Peter VAN DER WIELEN, KEMA,

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits

More information

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol A New Approach for Transformer Bushing Monitoring Emilio Morales Technical Application Specialist Qualitrol Abstract Transformer bushings are one of the most critical components of a transformer. Up to

More information

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM,

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM, ONLINE OFFLINE VERSUS FEATURE PARTIAL DISCHARGE TESTING FOR CABLE ASSESSMENT B Y WIL L IAM H IG INBOT H AM, EA Technology, LLC Medium voltage cables have three distinct phases to their lifecycle: (1) new

More information

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets Who we are TECHIMP is one of the leading providers of Condition Assessment Services Data Acquisition and Test Equipment

More information

TECHIMP Power Transformer Monitoring

TECHIMP Power Transformer Monitoring TECHIMP Power Transformer Monitoring Kontakt: Martin Hesse Techimp Germany GmbH i.g. E-Mail: mhesse@techimp.com Tel.: +49 5724 391 007 Mobil: +49 170 2364 735 PD Monitoring of Power Transformers Power

More information

WIRE AND CABLE ENGINEERING GUIDE

WIRE AND CABLE ENGINEERING GUIDE Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime

More information

MONTRANO. Continuous monitoring system for power transformers

MONTRANO. Continuous monitoring system for power transformers MONTRANO Continuous monitoring system for power transformers Condition monitoring to extend transformer life Knowing the dielectric condition of insulation is vital Dielectric flashover of insulation in

More information

Is Fault Location Killing Our Cable Systems?

Is Fault Location Killing Our Cable Systems? Is Fault Location Killing Our Cable Systems? Benjamin Lanz, Member, IEEE; Eugene Sanchez, Member, IEEE Abstract Power outages caused by faults in underground cable systems can be difficult to locate, however

More information

Test systems made by SebaKMT. Don t stress over tests! SebaKMT has the right answers: reliability, speed, economy.

Test systems made by SebaKMT. Don t stress over tests! SebaKMT has the right answers: reliability, speed, economy. Test systems made by SebaKMT Don t stress over tests! SebaKMT has the right answers: reliability, speed, economy. Know how to do it. And what happens next. Test first and save later Connected to the future

More information

Off-Line Field Diagnostics for MV and HV Oil-Paper Insulated Cables

Off-Line Field Diagnostics for MV and HV Oil-Paper Insulated Cables 163 24 th Nordic Insulation Symposium on Materials, Components and Diagnostics Off-Line Field Diagnostics for MV and HV Oil-Paper Insulated Cables Sarajit Banerjee, Ali Naderian Kinectrics Inc., Toronto,

More information

Field Measurement of Transmission Cable Dissipation Factor

Field Measurement of Transmission Cable Dissipation Factor Workshop 2000, Alexandria, Virginia, 13 & 14 September 2000 paper No.: 1 Field Measurement of Transmission Cable Dissipation Factor John H. Cooper, Power Delivery Consultants, Inc. Abstract This presentation

More information

Type Test of a 145 kv Termination Type TS 145-II

Type Test of a 145 kv Termination Type TS 145-II Test Report No 2009-125/2 Type Test of a 145 kv Termination Type TS 145-II Client: 3 M Deutschland GmbH Carl-Schurz-Str.1 41453 Neuss Reporter: Dr.-Ing. R. Badent Dr.-Ing. B. Hoferer This report includes

More information

Transformer condition assessment with an integrated test van

Transformer condition assessment with an integrated test van Transformer condition assessment with an integrated test van 1 2012 SebaKMT Measuring and locating techniques MADE in GERMANY 2 Testing and Standards for Power Transformers CIGRE CIGRE Brochure 342 (SFRA-FRAX)

More information

UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES

UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES D. Götz*, H.T. Putter* *Megger Germany INTRODUCTION High voltage termintions are essential components in high voltage cable

More information

H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C

H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C S O L U T I O N S Y O U R S O U R C E F O R T O P Q U A L I T Y T E S T E Q U I P M E N T w w w. h v t e c h n o l o g i e s. c o m Company

More information

PD Monitoring of MV/HV Power Cables December 2016

PD Monitoring of MV/HV Power Cables December 2016 PD Monitoring of MV/HV Power Cables December 216 Malcolm Seltzer-Grant m.seltzer-grant@hvpd.co.uk Introduction to HVPD Our global presence Introduction to HVPD Ltd HVPD are experts in the growing industry

More information

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS Anne Pfeffer 1*, Stefan Tenbohlen 1 and Stefan Kornhuber 2 1 Institute of Power Transmission and High Voltage Technology, Pfaffenwaldring

More information

CITY SERIES. Compact, fully equipped cable fault location, test and diagnostic systems

CITY SERIES. Compact, fully equipped cable fault location, test and diagnostic systems CITY SERIES Compact, fully equipped cable fault location, test and diagnostic systems Tailored to fit to small vehicles Easy operation in restricted spaces Centrally controlled, fully automatic system

More information

Investigation of PD Detection on XLPE Cables

Investigation of PD Detection on XLPE Cables Investigation of PD Detection on XLPE Cables Hio Nam O, T.R. Blackburn and B.T. Phung School of Electrical Engineering and Telecommunications The University New South Wales, Australia Abstract- The insulation

More information

Partial Discharge Trends in Medium Voltage Cables measured while in-service with PDOL

Partial Discharge Trends in Medium Voltage Cables measured while in-service with PDOL 1 Partial Discharge Trends in Medium Voltage Cables measured while in-service with PDOL André N. Cuppen, E. Fred Steennis, and Peter C. J. M. van der Wielen, Member, IEEE Abstract-- This paper presents

More information

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 7, July -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 Comparison

More information

Testing 320 kv HVDC XLPE Cable System

Testing 320 kv HVDC XLPE Cable System Testing 320 kv HVDC XLPE Cable System H. He, W. Sloot DNV GL, KEMA Laboratories Arnhem, The Netherlands Abstract Two unique test requirements in testing of a high- voltage direct- current (HVDC) cable

More information

GENERATOR TESTING APPLICATION GUIDE. reliable. precision.

GENERATOR TESTING APPLICATION GUIDE.  reliable. precision. GENERATOR TESTING APPLICATION GUIDE www.haefely-hipotronics.com reliable. precision. 2 GENERATOR TESTING CONTENTS Product Line Overview 3 AC Hipot Testing 4 Partial Discharge Measurement 5 DC Hipot Testing

More information

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N S C I E N C E P A S S I O N T E C H N O L O G Y HVDC Transmission Michael Muhr Graz University of Technology Austria www.tugraz.at 1 Definition HV High Voltage AC Voltage > 60kV 220kV DC Voltage > 60kV

More information

CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER

CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER Henrik ENOKSEN Espen EBERG Sverre HVIDSTEN SINTEF Energy Research - Norway SINTEF Energy Research - Norway SINTEF Energy Research

More information

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS 1.0 SCOPE 2.0 BONDING METHODS 2.1 Introduction 2.2 Design 2.3 Single-Point Bonding 2.4 Cross Bonding 2.5 Sheath Sectionalizing Joints 2.6 Sheath Standing Voltage 2.7 Sheath Voltage at Through Fault 2.8

More information

A COMPARISON OF AC AND DC PARTIAL DISCHARGE ACTIVITY IN POLYMERIC CABLE INSULATION *

A COMPARISON OF AC AND DC PARTIAL DISCHARGE ACTIVITY IN POLYMERIC CABLE INSULATION * Morris, E.A. and Siew, W.H. (2018) A comparison of AC and DC partial discharge activity in polymeric cable insulation. In: 2017 IEEE 21st International Conference on Pulsed Power (PPC). IEEE, Piscataway,

More information

Jean Carlos Hernández Mejía International Conference of Doble Clients Boston, MA, USA March 25 - March 30, GTRI/DoE Disclaimer

Jean Carlos Hernández Mejía International Conference of Doble Clients Boston, MA, USA March 25 - March 30, GTRI/DoE Disclaimer Overview of the Cable Diagnostic Focused Initiative Project NEETRAC National Electric Energy Testing Research and Applications Center Jean Carlos Hernández Mejía 2012 International Conference of Doble

More information

Cost-Effective Online Partial Discharge Measurements for Electrical Machines: Preventing Insulation Failure

Cost-Effective Online Partial Discharge Measurements for Electrical Machines: Preventing Insulation Failure F E A T U R E A R T I C L E Cost-Effective Online Partial Discharge Measurements for Electrical Machines: Preventing Insulation Failure Key words: online PD monitoring, diagnosis, insulation assessment,

More information

IDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy

IDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy IDAX 300 Insulation Diagnostic Analyzer Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy 1 Frequency Domain Spectroscopy Hi V A Lo Ground C HL Measure at several frequencies Use

More information

Partial discharge trends in medium voltage cables measured while in-service with PDOL Cuppen, A.N.; Steennis, E.F.; van der Wielen, P.C.J.M.

Partial discharge trends in medium voltage cables measured while in-service with PDOL Cuppen, A.N.; Steennis, E.F.; van der Wielen, P.C.J.M. Partial discharge trends in medium voltage cables measured while in-service with PDOL Cuppen, A.N.; Steennis, E.F.; van der Wielen, P.C.J.M. Published in: Proceedings of the IEEE PES Transmission and Distribution

More information

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH Giuseppe Cappai, Bernhard Heinrich, Giuseppe Simioli, Leonardo Trevisan Weidmann Electrical Technology AG, Switzerland Abstract: A large solar

More information

Frequency Spectrum Analysis of Electromagnetic Waves Radiated by

Frequency Spectrum Analysis of Electromagnetic Waves Radiated by Frequency Spectrum Analysis of Electromagnetic Waves Radiated by Electrical Discharges HYEON-KYU CHA, SUN-JAE KIM, DAE-WON PARK, GYUNG-SUK KIL Division of Electrical and Electronics Engineering Korea Maritime

More information

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Dr. Michael Krüger, Alexander Kraetge, OMICRON electronics GmbH, Austria Alexander

More information

ABB Power Products Service

ABB Power Products Service Raben Naidoo, Technology days, May 21-22th, 2014, Cape Town, South Africa, Enhanced availability of transformers via transformer remote monitoring - TEC ABB Power Products Service Why a session on availability?

More information

MEDIUM & HIGH VOLTAGE

MEDIUM & HIGH VOLTAGE MEDIUM & HIGH VOLTAGE TESTING EQUIPMENT VOLTAGE WITHSTAND SGM Series Resonant Systems The SGM series are used for generating high AC voltages at a fixed frequency (mainly 50 or 60 Hz) by means of an excited

More information

CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES

CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES Hao ZHANG, Transgrid, (Australia), hao.zhang@transgrid.com.au Zhao LIU, University of NSW, (Australia), z.liu@unsw.edu.au Toan

More information

On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables

On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables William Higinbotham, Neil Davies and Victor Chan EA Technology LLC, New Jersey; USA, EA Technology Pty Ltd, Brisbane Australia; EA

More information

High-Voltage Test and

High-Voltage Test and Eberhard Wolfgang Hauschild Lemke High-Voltage Test and Measuring Techniques ^ Springer Contents 1 Introduction 1 1.1 Development of Power Systems and Required High-Voltage Test Systems 1 1.2 The International

More information

Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results

Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results 2016 International Conference on Electrical Engineering and Automation (ICEEA 2016) ISBN: 978-1-60595-407-3 Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results Cristian DAN

More information

OMICRON Seminar on Partial Discharge Diagnostics on HV Assets. January 30, 2018 Beirut, Lebanon

OMICRON Seminar on Partial Discharge Diagnostics on HV Assets. January 30, 2018 Beirut, Lebanon OMICRON Seminar on Partial Discharge Diagnostics on HV Assets January 30, 2018 Beirut, Lebanon Substation Asset Testing and Diagnosis LOW ACCURACY LEVEL HIGH Take better maintenance decisions through accurate

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

Ieee Guide For Partial Discharge Testing Of Shielded Power

Ieee Guide For Partial Discharge Testing Of Shielded Power Ieee Guide For Partial Discharge Testing Of Shielded Power We have made it easy for you to find a PDF Ebooks without any digging. And by having access to our ebooks online or by storing it on your computer,

More information