Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen
|
|
- Annice Ford
- 6 years ago
- Views:
Transcription
1 Aspects of PD interpretation in HV power cables by Edward Gulski, Piotr Cichecki, Rogier Jongen General There are several aspects having influence on the diagnostic information and the condition judgment criteria for HV power cables: 1. Connection setting of the testing and diagnostic setup: earth connection configuration, where the earthing was connected? Close to sealing end or to main substation ground? 2. Background noise level: measurements in close substation and open substation in close distance to corona discharges sources will differ. In many cases background noise level can extend over 100pC so than PD pattern characteristics play major role in describing defect. Also in situation when high noise level is present, measurements are performed in comparative basis way (comparison of PD levels between cable phases). 3. Specific situation: e.g.: in some countries there is a lot of XLPE cables from 50 s and 60 s This cable suffer from water treeing and electrical treeing as the result they fail often. In other countries the XLPE cables were introduced in 80 and they have already improved water barrier protection so we do not face the problem of water treeing. Some countries have more problems e.g. with gas pressure and oil-filled cables instead of XLPE cables. 4. What type of cable is measured: mass impregnated/ oil filled (low or high pressure)/gas pressure cable. Each type of cable has own PD and tan delta characteristics. Moreover serviced aged cables may differ as the load and service condition are always different. Important is the age of the cable, operational history and failure history. Criteria of PD acceptance for HV power cables With regard to the criteria of PD acceptance for HV power cables the following has to be considered: 1. In general, due to significantly higher electric field strengths in the insulation and the accessories of HV power cables the degradation processes of discharging defects are much faster than those in MV power cables. 2. Therefore, at nominal voltage U 0 (during operation) the insulation of all HV XLPE cables should be PD free! Due to the fact that there are no international standards or guidelines for on-site PD detection and PD level acceptance for HV power cables the on the one hand and due to the fact that cable and accessories manufactures are delivering PD-free systems on the other hand the PD freedom of XLPE HV cables is important. 3. 1
2 4. Nevertheless it is possible that in certain type of insulation e.g. massimpregnated insulation or certain type of HV cables accessories the PD may occur during service life. But in general the HV cables are supposed to be PD free during operation [14]. 5. On the other hand we must be aware of local problems like water/electric treeing, background noise level. Important is to do analysis of VHF (TDR localization) record so there we can see real PD pulse characteristic. In case of PD we are not sure try to do TDR analysis and localize the problem. Practical aspects If PD are repetitive and it is confidence regarding PDIV level e.g: PDIV < U 0 (50kV) in next step must be distinguished if PD pulse is internal or external (noise) indicators: Increase of PD level in function of test voltage, PD pattern characteristics, TDR analysis. If PD is stable and possible localization than such PD level in [pc] must be recorded. Regarding interpretation some field experience values for HV power cables are shown in Table 1: Table 1: Cable type Safe Semi safe Dangerous XLPE new/old Localized PD in the cable insulation HV XLPE have to be PD free with a background noise level in the range of 25pC..30pC or lower. XLPE old Localized PD in accessories <25pC <100pC > 100pC Only as an Not localized PD <100pC <500pC >1000pC Only as an Oil-paper (oilfiled low pressure) old Oil-paper (oilfiled Localized PD in low cable insulation pressure) old and accessories Gas cable Not localized <25pC <300pC >500pC Gas cable Localized in cable <25pC insulation and accessories <50pC <200pC >200pC Only as an HV Gas pressure have to be PD free with a background noise level in the range of 25pC and lower The above table has relation to PD inception at test voltage > U 0. Moreover thie following has to be considered: - If the HV power cables is PD free up to 1.7 U 0 it can be concluded that no dangerous PD activity is active now and the quality insulation of this particular cable is high. - If the PDIV is below 1.7 U 0 and higher than 1.2 U 0 the cable can still be considered as PD-free and the quality insulation of this particular cable is good. - If the HV power cable has PDIV =< U 0 the cable is not PD free and extensive interpretation and application of cable typical knowledge is necessary to estimate the hazard of these PD s. 2
3 Power cable system: cable insulation and cable accessories (joints, terminations) are defect free. Power cable can withstand operational stresses without any impact to quality of the energy delivery (scenario for new and serviced aged circuits which were tested on-site and threshold limits for diagnostic parameters were not exceeded; breakdown did not occur during on-site voltage test or condition assessment test). Power cable fulfilled requirements for the factory tests but on-site after-laying test showed that there is defect present in cable system. In this situation two other scenarios are possible: a. Defect is present below nominal (U 0 ) voltage of the cable (U 0 ). Decision regarding repair, or maintenance (periodical monitoring measurements) has to be taken to avoid un-expected breakdown in service. b. Defect is present above nominal voltage (1.1U U 0 ) In this case (if defect has destructive character), defect prosperities described by diagnostic parameters may change in time. This can result in lowering dielectric strength of the cable accessory or cable insulation and lead to breakdown. Power cable failed (breakdown or weak-spots localized in the circuits) during afterlaying test, condition assessment or after repair test. Without maintenance decisions no further safe service operation is possible. Test Measurement Procedure e.g. OWTS HV150 The measurement is performed according to the scheme as shown in table 2. The test voltage is raised in steps of 10 kv and three shots at each voltage level are performed. During the damped AC voltage PD and dielectric losses is measured. Table 2: No. U rms [kv] U peak [kv] x U U peak [kv x Uo 3
4 During the test the following parameters will be estimated: PD inception voltage in kv PD level at PDIV in pc PD level at U0 in pc Depending on the PD level at Uo at each voltage higher than Uo a decision will be considered about the further increase of the test voltage. According to the IEEE400 documentation 50 damped AC excitations can be applied at maximum acceptable test voltage (equivalent of the voltage withstand test). According to the IEC60840 for new installed 110 kv power cables the test voltage after installation is 128 kv rms (2 U 0 ). For service aged cables the maximum test voltage has to be considered with the cable owner and is dependant on the history of the cable life (operational load, maintenance, failures, age). The following norms are applicable: IEC : High Voltage test techniques Part 3: Definitions and requirements for on-site testing; IEEE 400: Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems; IEEE 400.3: Guide for PD Testing of Shielded Power Cable Systems in a Field Environment; IEC 60270: Partial discharges measurements; IEC : Test methods for partial discharges measurements on lengths of extruded power cable; IEC 60840: Power cables with extruded insulation and the accessories for rated voltages above 30kV up to 150kV Test methods and requirements; IEC 62067: Power cables with extruded insulation and the accessories for rated voltages above 150kV; IEC 60141: Tests on oil-filled and gas-pressure cables and their accessories up to and including 400kV part 2; 4
5 References [1] Cigre Working Group B1.04, Brochure 279 Maintenance for HV Cables and Accessories [2] Cigre Working Group B1.09, Brochure 358 Remaining Life Management of Existing Underground Lines [3] Cigre Working Group D1.11, Brochure 228, Service Aged Insulation Materials [4] P.P. Seitz, B. Quak, E. Gulski, J.J. Smit, P. Cichecki, F. de Vries, F. Petzold, Novel Method for On-site Testing and Diagnosis of Transmission Cables up to 250kV, Proceedings JiCable '07. 7th Intern. Conf. Insulated Power Cables, Versailles, France, Paper 16, 2007 [5] F.J. Wester, E. Gulski and J.J. Smit, Detection of PD at Different AC Voltage Stresses in Power Cables, IEEE Electr. Insul. Mag., Vol. 23, No. 4, pp , 2007 [6] E. Gulski, E. Lemke, M. Gamlin, E. Gockenbach, W. Hauschild, E. Pultrum, Experiences in partial discharge detection of distribution power cable systems. Cigre, Vol 208 Electra, pp , 2003 [7] E. Gulski. P. Cichecki, E.R.S. Groot, J.J. Smit, F. de Vries, J. Slangen, Slangen. E.R.S.Groot, J. Pellis, D. van Houwelingen, T.J.W.H. Hermans, B. Wegbrands and L. Lamballais, Conditon Assessment of Service Aged HV Power Cables, Cigre, Paper D1-206, 2008 [8] J. Popma J. Pellis, Diagnostics for high voltage cable systems, proceedings ERA conference on HV plant life extension, Belgium, November, [9] J. Densley, Ageing Mechanisms and Diagnostics for Power Cables An Overview, IEEE Electrical Insulation Magazine, Vol. 17 Nr. 1 pp14-21, Jan/Feb 2001 [10] E. Gulski, E, F.J. Wester, Ph. Wester, E.R.S. Groot, J.W. van Doeland, Condition assessment of high voltage power cables. Proceedings CIGRE 2004 Session, paper D [11] E. Gulski, J.J. Smit, P. Cichecki, P.P. Seitz, B. Quak, F. de Vries, F. Petzold, Insulation Diagnosis of HV Power Cables, Proceedings Jicable '07. 7th International Conference on Insulated Power Cables, France, Versailles, June 2007, paper 51. [12] E. Gulski, P. Cichecki, J.J. Smit, F. de Vries, Vries. Bodega, Th. Hermans, P.P. Seitz, Dielectric loss diagnosis of service aged HV power cables, Proceedings of Cigre D1 Colloquium, Hungary Budapest, 2009 [13] E. Gulski, P.P. Seitz, B. Quak, F. Petzold, F. de Vries, (2008). Dedicated on-site condition monitoring of high voltage power cables up to 150kV. International journal of emerging electric power systems, 9(3), 1-15 [14] P. Cichecki, R.A. Jongen, E. Gulski, J.J. Smit, (2008). Statistical approach in power cables diagnostic data analysis. IEEE transactions on dielectrics and electrical insulation, 15(6), [15] E. Gulski, P. Cichecki, F.J. Wester, J.J. Smit, R. Bodega, T.J.W.H. Hermans, P.P. Seitz, B. Quak, F. de Vries, (2008). On-site testing and PD diagnosis of high voltage power cables. IEEE transactions on dielectrics and electrical insulation [16] IEC60502 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (Um = 1,2 kv) up to 30 kv (Um = 36 kv) - Part 1: Cables for rated voltages of 1 kv (Um = 1,2 kv) and 3 kv (Um = 3,6 kv) [17] E. Gulski, P. Cichecki, J.J. Smit, F. de Vries, J. Pellis, D. van Houwelingen, F. Wester, R. Bodega, Th. Hermans, Condition Assessment of Transmission Power Cables, Cigre 2010, paper D1 205_2010 5
Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages
Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages Paul P. SEITZ, Ben QUAK, Seitz Instruments AG, Niederrohrdorf, Switzerland, pps@seitz-instruments.ch Edward GULSKI,
More informationINSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES
INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES Edward GULSKI, Delft University of Technology, (The Netherlands), e.gulski@tudelft.nl Johan J SMIT, Delft University of Technology, (The Netherlands),
More informationNOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV
NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV Paul P. SEITZ, Seitz Instruments AG, (Switzerland), pps@seitz-instruments.ch Ben QUAK, Seitz Instruments AG, (Switzerland),
More informationTesting and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl
Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May 26 2011 St Pete Beach, Fl HDW ELECTRONICS, INC. THE BEST IN CABLE FAULT LOCATING TECHNOLOGY by Henning Oetjen Frank
More informationUSING DAMPED AC VOLTAGES
MODERN & TESTING DIAGNOSIS OF POWER CABLES USING DAMPED AC VOLTAGES BY EDWARD GULSKI AND ROGIER JONGEN, Onsite HV Solutions ag, Switzerland AND RALPH PATTERSON, Power Products & Solutions LLC, United States
More informationInvestigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages
Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages F. Petzold, H.T. Putter, D. Götz, H. Schlapp, S. Markalous SebaKMT GmbH Baunach/Radeburg,
More informationKurzfassung. Abstract. 1 Introduction
Untersuchung von Teilentladungsverhalten mit Wechselspannung und gedämpfter Wechselspannung Investigation of partial discharge behaviour with alternating current and damped alternating current Manuel Wild,
More informationSENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES
SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES Frank WESTER, Edward GULSKI, Johan SMIT, Edwin GROOT*, Mark VAN VLIET* Delft University of Technology The Netherlands * NUON The Netherlands
More informationStatistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage
Journal of Energy and Power Engineering 9 () 3-3 doi:.7/93-897/.3. D DAVID PUBLISHIG Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage
More informationSimultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics
Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics Dominique Bolliger, Ph.D. HV TECHNOLOGIES, Inc. Manassas, VA, USA d.bolliger@hvtechnologies.com Abstract In
More informationPartial discharge diagnostics on very long and branched cable circuits
11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA
More informationOFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES
OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES Hein PUTTER Frank PETZOLD Philipp LEGLER Megger Germany Megger Germany Megger - Germany hein.putter@megger.com frank.petzold@megger.com philipp.legler@megger.com
More informationINFLUENCE OF VOLTAGE WAVEFORMS ON PARTIAL DISCHARGES DEVELOPED IN POWER CABLE INSULATION
INFLUENCE OF VOLTAGE WAVEFORMS ON PARTIAL DISCHARGES DEVELOPED IN POWER CABLE INSULATION LARISA MĂRIUŢ, ELENA HELEREA *1 Key words: Partial discharge, Inception voltage, Step-up voltage test method, Sinusoidal
More informationPD Testing Considerations for MV Plant Cables
PD Testing Considerations for MV Plant Cables Cable Testing Philosophy Damage Mistake Aging Repair Manufacturing Transportation Installation Operation Power frequency 50/60 Hz Power frequency 50/60 Hz
More informationEstimating the Impact of VLF Frequency on Effectiveness of VLF Withstand Diagnostics
Estimating the Impact of VLF on Effectiveness of VLF Withstand Diagnostics Nigel Hampton (1), Jean Carlos Hernandez-Mejia (2), Marina Kuntsevich (3), Joshua Perkel (1), Vivek Tomer (3) 1 - NEETRAC, Atlanta,
More informationIN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY
IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY Avinash Raj 1, Chandan Kumar Chakrabarty 1, Rafidah Ismail 1 and Basri Abdul Ghani 2 1 College of Engineering, University Tenaga
More informationBEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES
BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES HEIN PUTTER Productmanager cable testing and -diagnosis Megger Site Germany 1 13 th Insucon conference 16-18 th Mai 2017, Birmingham, UK Agenda Introduction
More informationCable testing and diagnostics
Cable testing and diagnostics To ensure the flow Cost-optimised maintenance through cable diagnostics The sheath and cable testing supports you in assessing whether a cable system is safe and ready to
More informationOPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM ELPIS J SINAMBELA
1 OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM A thesis submitted to the Faculty of Electrical Power Engineering
More informationVLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing
Cable Testing & Diagnostics Solutions for Medium Voltage Networks (1 kv - 36 kv) VLF Partial Discharge DC DAC tandelta Cable Testing Cable Diagnostics? There are two main applications for cable testing:
More informationPHG 70 TD PD / PHG 80 TD PD
PHG 70 TD PD / PHG 80 TD PD BAUR VLF test and diagnostics system Functions Universal test and diagnostics system flexible, modular, extendable Cutting-edge testing and diagnostics technology: VLF truesinus
More informationTesting of 400 kv GIS
Testing of 400 kv GIS Robert le Roux, Dermot Dorgan, Brian Perry ESB International - Ireland Paper 028 1 Introduction The 400 kv transmission is designed for critical periods of low loading. Due to critical
More informationHV AC TESTING OF SUPER-LONG CABLES
HV AC TESTING OF SUPER-LONG CABLES Stefan SCHIERIG, (Germany), schierig@highvolt.de Peter COORS, (Germany), coors@highvolt.de Wolfgang HAUSCHILD, IEC, CIGRE, (Germany), hauschild@highvolt.de ABSTRACT The
More informationBasics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015
Basics of Partial Discharge Prepared for 2015 Phenix RSM Meeting January 2015 Definitions and History Standard Definitions Fundamentally, what is a Partial Discharge An electric discharge which only partially
More informationSpecialists in HV and MV test and diagnostics. Testing in Substations
Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies
More informationPractical aspects of PD localization for long length Power Cables
Practical aspects of PD localization for long length Power Cables M. Wild, S. Tenbohlen University of Stuttgart Stuttgart, Germany manuel.wild@ieh.uni-stuttgart.de E. Gulski, R. Jongen onsite hv technology
More informationBY JASON SOUCHAK, Megger
IMPROVING SYSTEM RELIABILITY WITH OFFLINE PD TESTING BY JASON SOUCHAK, Megger Partial discharge (PD) testing is a new generation of diagnostic testing for medium- and high-voltage underground power cable
More informationSMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE
SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE Fred STEENNIS Paul WAGENAARS Denny HARMSEN DNV GL the Netherlands DNV GL the
More informationINVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES
INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES Gonzalo MAIZ, Iberdrola Distribución, (Spain), gmaiz@iberdrola.es Armando RODRIGO, Instituto
More informationPartial Discharge Measurement and Monitoring on High Voltage XLPE Cables
21, rue d Artois, F-75008 PARIS AUCKLAND 2013 http : //www.cigre.org Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables Michael Krüger, Rene Hummel, Stefan Böhler, OMICRON Austria
More informationEI HIGH VOLTAGE INSULATION TESTING POLICY
Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and
More informationAssuring the Reliability of Critical Power Cable Systems
Assuring the Reliability of Critical Power Cable Systems Presented by: Benjamin Lanz Manager of Application Engineering IMCORP Power Cable Reliability Consulting & Diagnostics Some of the technologies
More informationHigh Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland
High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland Company HV Diagnostics Sarl is a Swiss based company in the field of high voltage test equipment for cable testing and diagnosis.
More informationCIGRE- AORC Technical Meeting 2016 and International Conference on Global Trends in the Development of Power T&D System including Smart Grid
CIGRE- AORC Technical Meeting 2016 and International Conference on Global Trends in the Development of Power T&D System including Smart Grid DEMANDS OF DIELECTRIC TESTING OF HVAC AND HVDC POWER CABLES
More informationECP HV INSULATION TESTING
Document Number: ECP 11-0006 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE EPN, LPN, SPN ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing
More informationPartial Discharge Patterns in High Voltage Insulation
22 IEEE International Conference on Power and Energy (PECon), 2-5 December 22, Kota Kinabalu Sabah, Malaysia Partial Discharge Patterns in High Voltage Insulation Hazlee Illias, Teo Soon Yuan, Ab Halim
More informationFault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 1. Introduction Fault location on communication and power cables
More informationECP HV INSULATION TESTING
Document Number: ECP 11-0006 Network(s): Summary: All ENGINEERING COMMISSIONING PROCEDURE ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing of new and
More informationMV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB
MV Power Cable Diagnostics by Frequency Domain Spectroscopy Peter Werelius Programma Electric AB Frequency Domain Spectroscopy Measurements of insulation capacitance and losses in a frequency interval
More informationCable diagnostic in MV underground cable networks
Cable diagnostic in MV underground cable networks Theoretical background and practical application VLF testing tan delta loss factor measurement Partial discharge localization and measurement Author: Tobias
More informationReprint E Two Years of Experience with a Mobile Resonant Test System for Testing of Installed Medium- and High Voltage Power Cables
Two Years of Experience with a Mobile Resonant System for ing of Installed Medium- and High Voltage Power Cables P. Schikarski M. Gamlin J. Rickmann P. Peeters P. v.d. Nieuwendijk R. Koning Reprint ISH
More informationField Experiences. Partial Discharge Diagnosis on MV Cables. Philipp Legler. XVI. Szigetelésdiagnosztikai Konferencia (
Field Experiences Partial Discharge Diagnosis on MV Cables Philipp Legler Technical Support Applications Engineer (Megger Site Germany) XVI. Szigetelésdiagnosztikai Konferencia (19. - 20.10.2016, Sümeg)
More informationUnderground System Design TADP 547
Underground System Design TADP 547 Industry Standards, Specifications and Guides Presentation 6.4 Instructor: Frank Frentzas Industry Organizations Several professional organizations develop standards
More informationPD Diagnostic Applications and TechImp solutions
PD Diagnostic Applications and TechImp solutions Condition Assessment Solutions for Electrical Systems. PD based innovative tools for the Condition Based Maintenance. MD-04.05.004 - rev. 00-29/08/2006
More informationWhy partial discharge testing makes good sense
Why partial discharge testing makes good sense PD measurement and analysis have proven to be reliable for detecting defects in the insulation system of electrical assets before major damage or a breakdown
More informationDiagnostic testing of cast resin transformers
Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com
More informationTHE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE
THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales
More informationAn Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley
An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley ArborLec Solutions Inc. CIGRE WG 21:04 in 1994 Purpose of diagnostic test is: To evaluate and locate degradation phenomena
More informationMV Power Cable Testing Training
MV Power Cable Testing Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Since power cables are used
More informationPower Transformer Condition Assessment Based on Standard Diagnosis
Power Transformer Condition Assessment Based on Standard Cattareeya Suwanasri Abstract The diagnostic techniques of electrical and insulating oil testing are proposed to assess the internal condition of
More informationCondition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology
Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of
More informationA6.6 9 th International Conference on Insulated Power Cables A6.6
Development Process of extruded HVDC cable systems Dominik HÄRING, Gero SCHRÖDER, Andreas WEINLEIN, Axel BOSSMANN Südkabel GmbH, (Germany) dominik.haering@suedkabel.com, gero.schroeder@suedkabel.com, andreas.weinlein@suedkabel.com,
More informationTests on Extruded Cables
Tests on Extruded Cables Pierre Argaut Chairman of CIGRE SC B1 October 26 th, 2011 At least, once in your life, you have heard these words: Development Tests Long-term Tests Prequalification Tests Extension
More informationCIGRE General Session, Paris 2014 Group Meeting SC B1 Insulated Cables, 27th August, 2014 Results of CAG Questionnaire
1 1. Number of Questionnaires Returned 23 2. Number of suggestions for work 64 3. Suggestions for new work within the scope of SCB1 or for additional work by current Working Groups in? 3.1 cable system
More informationAfrica Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound
Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences
More informationA Study on the Effect of Performing VLF Withstand Tests on Field Aged Degraded Joints
WETS D 15 2.4 Drapeau A Study on the Effect of Performing VLF Withstand Tests on Field Aged Degraded Joints Jean-François DRAPEAU Researcher Expertise Équipement électriques IREQ Jacques CÔTÉ, HQD Simon
More informationPERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE
PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE Fred STEENNIS, KEMA, (the Netherlands), fred.steennis@kema.com Peter VAN DER WIELEN, KEMA,
More informationThe University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge
The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits
More informationA New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol
A New Approach for Transformer Bushing Monitoring Emilio Morales Technical Application Specialist Qualitrol Abstract Transformer bushings are one of the most critical components of a transformer. Up to
More informationONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM,
ONLINE OFFLINE VERSUS FEATURE PARTIAL DISCHARGE TESTING FOR CABLE ASSESSMENT B Y WIL L IAM H IG INBOT H AM, EA Technology, LLC Medium voltage cables have three distinct phases to their lifecycle: (1) new
More informationTECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets
TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets Who we are TECHIMP is one of the leading providers of Condition Assessment Services Data Acquisition and Test Equipment
More informationTECHIMP Power Transformer Monitoring
TECHIMP Power Transformer Monitoring Kontakt: Martin Hesse Techimp Germany GmbH i.g. E-Mail: mhesse@techimp.com Tel.: +49 5724 391 007 Mobil: +49 170 2364 735 PD Monitoring of Power Transformers Power
More informationWIRE AND CABLE ENGINEERING GUIDE
Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime
More informationMONTRANO. Continuous monitoring system for power transformers
MONTRANO Continuous monitoring system for power transformers Condition monitoring to extend transformer life Knowing the dielectric condition of insulation is vital Dielectric flashover of insulation in
More informationIs Fault Location Killing Our Cable Systems?
Is Fault Location Killing Our Cable Systems? Benjamin Lanz, Member, IEEE; Eugene Sanchez, Member, IEEE Abstract Power outages caused by faults in underground cable systems can be difficult to locate, however
More informationTest systems made by SebaKMT. Don t stress over tests! SebaKMT has the right answers: reliability, speed, economy.
Test systems made by SebaKMT Don t stress over tests! SebaKMT has the right answers: reliability, speed, economy. Know how to do it. And what happens next. Test first and save later Connected to the future
More informationOff-Line Field Diagnostics for MV and HV Oil-Paper Insulated Cables
163 24 th Nordic Insulation Symposium on Materials, Components and Diagnostics Off-Line Field Diagnostics for MV and HV Oil-Paper Insulated Cables Sarajit Banerjee, Ali Naderian Kinectrics Inc., Toronto,
More informationField Measurement of Transmission Cable Dissipation Factor
Workshop 2000, Alexandria, Virginia, 13 & 14 September 2000 paper No.: 1 Field Measurement of Transmission Cable Dissipation Factor John H. Cooper, Power Delivery Consultants, Inc. Abstract This presentation
More informationType Test of a 145 kv Termination Type TS 145-II
Test Report No 2009-125/2 Type Test of a 145 kv Termination Type TS 145-II Client: 3 M Deutschland GmbH Carl-Schurz-Str.1 41453 Neuss Reporter: Dr.-Ing. R. Badent Dr.-Ing. B. Hoferer This report includes
More informationTransformer condition assessment with an integrated test van
Transformer condition assessment with an integrated test van 1 2012 SebaKMT Measuring and locating techniques MADE in GERMANY 2 Testing and Standards for Power Transformers CIGRE CIGRE Brochure 342 (SFRA-FRAX)
More informationUHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES
UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES D. Götz*, H.T. Putter* *Megger Germany INTRODUCTION High voltage termintions are essential components in high voltage cable
More informationH V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C
H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C S O L U T I O N S Y O U R S O U R C E F O R T O P Q U A L I T Y T E S T E Q U I P M E N T w w w. h v t e c h n o l o g i e s. c o m Company
More informationPD Monitoring of MV/HV Power Cables December 2016
PD Monitoring of MV/HV Power Cables December 216 Malcolm Seltzer-Grant m.seltzer-grant@hvpd.co.uk Introduction to HVPD Our global presence Introduction to HVPD Ltd HVPD are experts in the growing industry
More informationPULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS
PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS Anne Pfeffer 1*, Stefan Tenbohlen 1 and Stefan Kornhuber 2 1 Institute of Power Transmission and High Voltage Technology, Pfaffenwaldring
More informationCITY SERIES. Compact, fully equipped cable fault location, test and diagnostic systems
CITY SERIES Compact, fully equipped cable fault location, test and diagnostic systems Tailored to fit to small vehicles Easy operation in restricted spaces Centrally controlled, fully automatic system
More informationInvestigation of PD Detection on XLPE Cables
Investigation of PD Detection on XLPE Cables Hio Nam O, T.R. Blackburn and B.T. Phung School of Electrical Engineering and Telecommunications The University New South Wales, Australia Abstract- The insulation
More informationPartial Discharge Trends in Medium Voltage Cables measured while in-service with PDOL
1 Partial Discharge Trends in Medium Voltage Cables measured while in-service with PDOL André N. Cuppen, E. Fred Steennis, and Peter C. J. M. van der Wielen, Member, IEEE Abstract-- This paper presents
More informationInternational Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer
Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 7, July -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 Comparison
More informationTesting 320 kv HVDC XLPE Cable System
Testing 320 kv HVDC XLPE Cable System H. He, W. Sloot DNV GL, KEMA Laboratories Arnhem, The Netherlands Abstract Two unique test requirements in testing of a high- voltage direct- current (HVDC) cable
More informationGENERATOR TESTING APPLICATION GUIDE. reliable. precision.
GENERATOR TESTING APPLICATION GUIDE www.haefely-hipotronics.com reliable. precision. 2 GENERATOR TESTING CONTENTS Product Line Overview 3 AC Hipot Testing 4 Partial Discharge Measurement 5 DC Hipot Testing
More informationHVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N
S C I E N C E P A S S I O N T E C H N O L O G Y HVDC Transmission Michael Muhr Graz University of Technology Austria www.tugraz.at 1 Definition HV High Voltage AC Voltage > 60kV 220kV DC Voltage > 60kV
More informationCONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER
CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER Henrik ENOKSEN Espen EBERG Sverre HVIDSTEN SINTEF Energy Research - Norway SINTEF Energy Research - Norway SINTEF Energy Research
More informationTRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS
1.0 SCOPE 2.0 BONDING METHODS 2.1 Introduction 2.2 Design 2.3 Single-Point Bonding 2.4 Cross Bonding 2.5 Sheath Sectionalizing Joints 2.6 Sheath Standing Voltage 2.7 Sheath Voltage at Through Fault 2.8
More informationA COMPARISON OF AC AND DC PARTIAL DISCHARGE ACTIVITY IN POLYMERIC CABLE INSULATION *
Morris, E.A. and Siew, W.H. (2018) A comparison of AC and DC partial discharge activity in polymeric cable insulation. In: 2017 IEEE 21st International Conference on Pulsed Power (PPC). IEEE, Piscataway,
More informationJean Carlos Hernández Mejía International Conference of Doble Clients Boston, MA, USA March 25 - March 30, GTRI/DoE Disclaimer
Overview of the Cable Diagnostic Focused Initiative Project NEETRAC National Electric Energy Testing Research and Applications Center Jean Carlos Hernández Mejía 2012 International Conference of Doble
More informationCost-Effective Online Partial Discharge Measurements for Electrical Machines: Preventing Insulation Failure
F E A T U R E A R T I C L E Cost-Effective Online Partial Discharge Measurements for Electrical Machines: Preventing Insulation Failure Key words: online PD monitoring, diagnosis, insulation assessment,
More informationIDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy
IDAX 300 Insulation Diagnostic Analyzer Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy 1 Frequency Domain Spectroscopy Hi V A Lo Ground C HL Measure at several frequencies Use
More informationPartial discharge trends in medium voltage cables measured while in-service with PDOL Cuppen, A.N.; Steennis, E.F.; van der Wielen, P.C.J.M.
Partial discharge trends in medium voltage cables measured while in-service with PDOL Cuppen, A.N.; Steennis, E.F.; van der Wielen, P.C.J.M. Published in: Proceedings of the IEEE PES Transmission and Distribution
More informationTRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH
TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH Giuseppe Cappai, Bernhard Heinrich, Giuseppe Simioli, Leonardo Trevisan Weidmann Electrical Technology AG, Switzerland Abstract: A large solar
More informationFrequency Spectrum Analysis of Electromagnetic Waves Radiated by
Frequency Spectrum Analysis of Electromagnetic Waves Radiated by Electrical Discharges HYEON-KYU CHA, SUN-JAE KIM, DAE-WON PARK, GYUNG-SUK KIL Division of Electrical and Electronics Engineering Korea Maritime
More informationInnovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers
Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Dr. Michael Krüger, Alexander Kraetge, OMICRON electronics GmbH, Austria Alexander
More informationABB Power Products Service
Raben Naidoo, Technology days, May 21-22th, 2014, Cape Town, South Africa, Enhanced availability of transformers via transformer remote monitoring - TEC ABB Power Products Service Why a session on availability?
More informationMEDIUM & HIGH VOLTAGE
MEDIUM & HIGH VOLTAGE TESTING EQUIPMENT VOLTAGE WITHSTAND SGM Series Resonant Systems The SGM series are used for generating high AC voltages at a fixed frequency (mainly 50 or 60 Hz) by means of an excited
More informationCONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES
CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES Hao ZHANG, Transgrid, (Australia), hao.zhang@transgrid.com.au Zhao LIU, University of NSW, (Australia), z.liu@unsw.edu.au Toan
More informationOn-line Partial Discharge Assessment and Monitoring of MV to EHV Cables
On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables William Higinbotham, Neil Davies and Victor Chan EA Technology LLC, New Jersey; USA, EA Technology Pty Ltd, Brisbane Australia; EA
More informationHigh-Voltage Test and
Eberhard Wolfgang Hauschild Lemke High-Voltage Test and Measuring Techniques ^ Springer Contents 1 Introduction 1 1.1 Development of Power Systems and Required High-Voltage Test Systems 1 1.2 The International
More informationPartial Discharge Measurements on 110kV Current Transformers. Case Study. Results
2016 International Conference on Electrical Engineering and Automation (ICEEA 2016) ISBN: 978-1-60595-407-3 Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results Cristian DAN
More informationOMICRON Seminar on Partial Discharge Diagnostics on HV Assets. January 30, 2018 Beirut, Lebanon
OMICRON Seminar on Partial Discharge Diagnostics on HV Assets January 30, 2018 Beirut, Lebanon Substation Asset Testing and Diagnosis LOW ACCURACY LEVEL HIGH Take better maintenance decisions through accurate
More informationPOWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009
POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power
More informationIeee Guide For Partial Discharge Testing Of Shielded Power
Ieee Guide For Partial Discharge Testing Of Shielded Power We have made it easy for you to find a PDF Ebooks without any digging. And by having access to our ebooks online or by storing it on your computer,
More information