TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

Size: px
Start display at page:

Download "TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS"

Transcription

1

2 1.0 SCOPE 2.0 BONDING METHODS 2.1 Introduction 2.2 Design 2.3 Single-Point Bonding 2.4 Cross Bonding 2.5 Sheath Sectionalizing Joints 2.6 Sheath Standing Voltage 2.7 Sheath Voltage at Through Fault 2.8 Sheath Overvoltages 3.0 ACCESSORIES AND THEIR TESTING FIGURES 3.1 Sheath Sectionalizing Insulator 3.2 Ground Continuity Conductor 3.3 Link Box 3.4 Bonding Lead 3.5 Sheath Voltage Limiter 3.6 Grounding Pit TABLE OF CONTENTS Figure 08-1: Sheath Bonding Arrangements at Ungrounded Terminations Figure 08-2: Sheath Bonding Arrangements at Solidly Bonded Joints in Cross Bonded Systems Figure 08-3: Sheath Bonding Arrangements at SVL Protected Joints in Cross Bonded Systems Figure 08-4: Single-Point Bonding Diagrams for Circuits Comprising One Cable Length Only Figure 08-5: Single-Point Bonding Diagram for Circuits Comprising Three Cable Lengths Figure 08-6: Transposition of Parallel Conductor to Reduce Induced Voltage with Power Cables in Flat Formation or Trefoil Figure 08-7: Sectionalized and Continuous Cross Bonded Cables Figure 08-8: Termination of Cross Bonded System with Single-Point Bonded Length Figure 08-9: Typical Insulating Shroud for Base of Oil Filled Cable Outdoor Sealing End Figure 08-10: Link Box Grounding Arrangement Figure 08-11: Typical Details of Grounding Pit 4.0 BIBLIOGRAPHY PAGE NO. 2 OF 23

3 1.0 SCOPE This Standard provides the guidelines for selection of the bonding and grounding of the insulated metallic sheath of single core power cables of voltage 69kV thru 380kV in the electrical systems of Saudi Electricity Company (SEC), Saudi Arabia. 2.0 BONDING METHODS 2.1 General 2.2 Design Bonding and grounding of the sheath must perform the following functions: Reduce or eliminate the sheath losses thereby optimizing conductor current carrying capacity & size and prevent undue jacket heating Limit sheath voltages to a required value Maintain a continuous sheath circuit to permit fault current return for protective relay operation, and adequate lightning and switching surge protection All requisite direct inter-sheath and sheath-to-ground connections shall be made through approved disconnecting links, bonding leads and sheath voltage limiters(svls), within the link-box Single-core 69kV and 110/115/132 kv cable circuits of length upto 1.5 km in trefoil or flat formation shall be either single-point bonded or cross bonded with prior approval from SEC. For circuit lengths above 1.5km the metallic sheath of the power cables shall be cross-bonded. PAGE NO. 3 OF 23

4 2.2.3 Single-core 230kV and 380kV cable circuits of length upto 1km shall be single-point bonded or cross bonded with prior approval from SEC. For circuit lengths above 1km the metallic sheath of the power cables shall be cross-bonded The design of sheath bonding arrangements shall be per ANSI/IEEE 575 (Guide for the Application of Sheath-Bonding Methods for Single Conductor Cables and the Calculation of Induced Voltages and Currents in Cable Sheath) and considerations must be given to the following: a. Any safety aspect that may arise and any limiting values of sheath voltage as specified subsequently in this document. b. Residual sheath circulating currents in cross bonding system due to a large variation in the cable section lengths or spacings and their effect on the cable ampacity. c. Coordination of the sheath insulation levels in relation with the over voltage due to system transients and faults to which the sheath insulation will be subjected. d. The selection of SVL rating and monitoring and maintenance of the complete sheath insulation system in operation Bonding lead connections to the underground cable sheath shall be preferably soldered. Lead sheath(if present) shall not be injured by hot solder. The area of contact shall be sufficient to prevent the current from melting the solder. In order to prevent corrosion, copper bonding wires connected directly to the lead sheath(if present) shall form a 60 angle with the sheath at the point of soldering as recommended by Underground Systems Reference Book by Edison Electric Institute The sheath bonding bay ground of each cable circuit in two or more circuit scheme shall be separate; and there shall be no metallic connection between them. This requirement shall apply even if these circuits are using a common joint bay. A separate link box shall be used for each circuit as shown in Figure PAGE NO. 4 OF 23

5 2.2.7 For circuits comprising of two or more cables per phase a separate link box shall be provided for each group of three cables. 2.3 Single-Point Bonding In single-point bonding system the sheath of the single-core cables shall be solidly bonded and grounded at one(sealing) end of the cable route. The other end of the cable sheath shall be connected to ground through the SVLs as shown in Figure The bonding arrangements shall be as shown in Figure Single-point bonding system comprising three cable lengths shall be per Figure The single-point bonded cable installation shall be provided with a parallel ground continuity conductor, which shall be solidly grounded as shown in the above-mentioned figures. The spacing of the parallel ground continuity conductor from the cable circuit shall be sufficiently close to limit the voltage rise of the cable sheath during through fault conditions and as shown in Figure The ground continuity conductor shall be transposed at the mid point of each minor section, if the power cables are not transposed (The ground continuity conductor need not to be transposed for cables laid in trefoil formation) In single-point bonding system it shall be preferable to ground the sheath at the end which is subjected to the highest incoming transient voltages. 2.4 Cross Bonding In cross bonding system the cable route shall have at least three minor sections/drum lengths of cable and cross bonding of the cable sheath shall be as shown in Figure Cross bonding of cable sheath without transposition is permitted only in case of cables in trefoil formation. When the number of minor sections are exactly divisible by three (the length of the sections are equal) the sectionalized cross-bonding of the cable sheaths shall be adopted. When the number of minor sections are not exactly divisible by three, the cable sheaths shall be continuous cross bonded. PAGE NO. 5 OF 23

6 2.4.2 In cross bonding system (sectionalized and continuous type) the sheaths of the cables in any one minor section shall be electrically isolated from the sheaths of the cables in the adjacent sections(whether or not they are in the same major section) of the same phase. No parallel ground continuity conductor is needed here and sheath loss due to unequal cable lengths/minor sections shall not exceed the limits specified below: a. 3% for cables laid direct buried. b. 5% for cables installed in ducts The lengths of the minor sections of any one major section shall be as nearly uniform as practicable. Otherwise, cable center spacing is to be varied to adjust the induced sheath voltage in a manner to counteract the effect of length mis-match and to meet required cable ampacity In the event of relocation of terminations on existing circuits which cannot be re-arranged within the constraints of mis-match or continuous cross bonding, single-point bonded sections may be incorporated in otherwise cross bonded circuits as shown in Figure with prior approval from SEC Except for cables in trefoil formation, in cross bonded system the cables shall be regularly transposed at each major and minor sectionalizing position The grounding at the junctions of major sections in the sectionalized cross bonding shall be only by local ground rods as shown in Figure The sheath bonding arrangements at the cable joints in cross bonded system shall be as shown in Figure 08-2 and SVLs shall be connected by the bonding leads of not exceeding 10m of length across the sheath sectionalizing insulators. 2.5 Sheath Sectionalizing Joints Any cable joint, where sheath sectionalizing is required shall incorporate an insulating section and be so arranged that the requisite insulation level is provided both to ground and between the core screens and sheaths of the cables entering and leaving the joint. PAGE NO. 6 OF 23

7 2.5.2 All sheath sectionalizing joints shall be so arranged as to accommodate bonding leads of the concentric type, and the necessary bonding lug shall be located as closely as practicable to the sectionalizing insulation Before a sheath sectionalizing joint is used in the bonding scheme the insulation strength required at the sheath sectionalizing joint must be evaluated by calculating the maximum voltage appearing across the joint due to through faults and lightning and switching surges. 2.6 Sheath Standing Voltage at Emergency Load Condition In a practical installation having variable lengths of minor sections, the sheath standing voltage shall be calculated for the longest minor section The sheath standing voltage shall be calculated for the maximum (emergency) load condition and most stringent portion of installation (duct banks etc.) per the applicable methods and formulae as recommended in clause D2 of Appendix D of ANSI/IEEE575 for single-point and cross bonding systems The sheath bonding and grounding arrangement shall be such that the standing sheath voltage at maximum (emergency)load current shall nowhere exceed the following voltage to ground. a. 65V rms for system voltage upto and including 132 kv. b. 110V rms for system voltage 230 kv and 380 kv When the sheath standing voltage at a sealing end/termination of the cable exceeds 10Vrms, to prevent hand contact with the sheath or metal parts connected to it, resin bonded glass fiber shrouds as shown in Figure 08-9 shall be provided. PAGE NO. 7 OF 23

8 2.7 Sheath Standing Voltage at Through Fault In order to find out the ratings of the SVLs the maximum magnitude of power frequency sheath voltage induced under through fault conditions(3- phase, phase to phase and single phase to ground fault) shall be calculated by the applicable methods and formulae as recommended in clause E3 and E4 of Appendix E of ANSI/IEEE575 for single-point and cross bonding systems. The limiting values of sheath voltage at through fault shall nowhere exceed the following voltage to ground: a. 5kV rms for system voltage upto and including 132 kv. b. 10kV rms for system voltage 230 kv and 380 kv The SVL ratings shall be based on the ultimate short circuit current In case of single-point bonding system, having two cables per phase, and where system may be operated in abnormal condition with only one cable per phase, the sheath voltage calculation shall take into account the division of any ground fault return current between the two ground continuity conductors. 2.8 Sheath Overvoltages It shall be ensured that the insulation requirement of sheath sectionalizing insulators or jacket of the cable shall be sufficient to withstand the sheath overvoltages resulting from steep fronted transient voltage wave (due to switching operations, flashover on or near the cable terminations or lightning impulse in cable circuits connected to overhead lines). To restrict these voltages to acceptable levels as mentioned in clause c and 3.1.4, SVLs shall be installed for single-point and cross bonding systems The travelling transient voltage arising across the sheath and joint sleeve sectionalizing insulation shall be calculated per document no.3 under bibliography. PAGE NO. 8 OF 23

9 3.0 ACCESSORIES AND THEIR TESTING 3.1 Sheath Sectionalizing Insulator These insulators shall consist of two short sections of brass or copper sleeving separated by a non-conducting material having sufficient creepage to prevent current leakage across them Sheath sectionalizing insulators shall be externally insulated to permit 10kV D.C. high voltage testing of the jacket of the cable at site The sheath sectionalizing insulators shall be tested to withstand: a. 10kV D.C. for 1 minute. b. the maximum power frequency voltage arising between sheaths during a system through fault (see clause 2.7.1). c. 1.2/50µsec. impulse voltage as below: Rated Lightning Impulse Withstand Voltage for Cable Insulation(kVpeak) 1.2/50µsec. Impulse Test Voltage (kvpeak) Upto Impulse withstand voltage between the sheath sectionalizing insulator and ground shall be 50% of the impulse test voltage mentioned above. PAGE NO. 9 OF 23

10 3.2 Ground Continuity Conductor The ground continuity conductor shall be of 600/1000V, class 2 stranded copper conductor, XLPE insulated (with minimum average thickness of 3.3mm) conforming to IEC and IEC The minimum size of the conductor cross-section shall be computed per IEC for the ultimate fault current to be carried by the ground continuity conductor for 1 sec. and maximum copper temperature of 250 C. The color of the PVC outer jacket shall be green with yellow stripe. 3.3 Link Box Link box shall be provided and tested per 12-TMSS Bonding Lead The bonding lead shall be a coaxial cable with concentric type, class 2 stranded copper conductors, XLPE insulated ( with minimum average thickness of 3.3mm) conforming to IEC and IEC The minimum size of the conductor cross-section shall be computed per ICEA P for the system fault current to be carried by the bonding lead conductor for 1 sec. and maximum copper temperature of 250 C. The PVC outer jacket shall be graphite coated and embossed with the legend: ELECTRIC CABLE ---BONDING LEAD The length of the bonding lead shall be preferably within 3m, but in no case will exceed 10m. Joints in the bonding lead are not acceptable. The surge impedance of the bonding lead shall not exceed 30Ω Bonding leads shall be marked to indicate sheaths of the concerned cable sections Bonding leads shall be routine tested per IEC The bonding leads shall also be tested per clause The (outer sheath) insulation between outer screen and ground shall be tested per PAGE NO. 10 OF 23

11 3.5 Sheath Voltage Limiter(SVL) Sheath Voltage Limiter(SVL) shall be provided and tested per 12-TMSS Grounding Pit The grounding pit details shall be as shown in Figure Separate grounding pit shall be provided for each cable circuit and for each group of cables (R, Y, B), when two cables per phase are laid. The equivalent resistance(re) of grounding rods for each pit shall be not more than 2Ω. PAGE NO. 11 OF 23

12 4.0 BIBLIOGRAPHY 1. ANSI/IEEE 575, Guide for the application of sheath-bonding methods for single conductor cables and the calculation of induced voltages and currents in cable sheath. 2. ICEA Pub.P , Short Circuit Performance of Metallic Shields and Sheaths of Insulated Cable(Second Edition). 3. IEEE Transactions on Power Apparatus and Systems Vol.PAS-84, No.10, Sheath Overvoltages in H.V. Cables Resulting from Special Sheath- Bonding Connections. 4. Engineering Recommendation C.55/4, Cables Consultancy Group The Electricity Council Engineering Management. 5. Electra (128) CIGRE Study Committee 21, Working Group 7, Guide to the Protection of Specially Bonded Cable Systems against Sheath Overvoltages. 6. Electra (47) CIGRE study committee 21, Working Group 7, The Design of Specially Bonded Cable Circuits (Part II). 7. IEC60228, Conductors of Insulated Cables. 8. IEC60287, Electric Cables-Calculation of Current Rating. 9. IEC60502, Extruded Solid Dielectric Insulated Power Cables for Rated Voltages from 1kV upto 30kV. 10. IEC60949, Calculation of thermally permissible short-circuit currents, taking into account non-adiabatic heating effects TMSS-11, Link Boxes for Sheath Grounding of Underground Power Cables. PAGE NO. 12 OF 23

13 DWG # TE PAGE NO. 13 OF 23

14 DWG # TE PAGE NO. 14 OF 23

15 DWG # TE PAGE NO. 15 OF 23

16 DWG # TE PAGE NO. 16 OF 23

17 DWG # TE PAGE NO. 17 OF 23

18 DWG # TE PAGE NO. 18 OF 23

19 DWG # TE PAGE NO. 19 OF 23

20 DWG # TE PAGE NO. 20 OF 23

21 DWG # TE PAGE NO. 21 OF 23

22 DWG # TE PAGE NO. 22 OF 23

23 DWG # TE PAGE NO. 23 OF 23

Underground System Design TADP 547

Underground System Design TADP 547 Underground System Design TADP 547 Industry Standards, Specifications and Guides Presentation 6.4 Instructor: Frank Frentzas Industry Organizations Several professional organizations develop standards

More information

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables J Electr Eng Technol Vol. 9, No. 2: 628-634, 2014 http://dx.doi.org/10.5370/jeet.2014.9.2.628 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 A Study on Lightning Overvoltage Characteristics of Grounding

More information

Article 250 Grounding & Bonding

Article 250 Grounding & Bonding Article 250 Grounding & Bonding AMERICAN ELECTRICAL INSTITUTE N16 W23217 Stone Ridge Dr. Waukesha, WI 53188 855-780-5046 www.aeitraining.com DISCLAIMER NOTE: This course is APPROVED for continuing education

More information

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid. 1. Scope This specification defines the methods, the procedures and the requirements to verify the cables manufactured according to I.E.C. Specifications NPS361. 2. Standards All the standards referred

More information

Evaluating Step and Touch Potential Risks on Earthing Systems of High Voltage Cable Systems TP, THINUS DU PLESSIS ESKOM SOUTH AFRICA HJ, HARTMUT JAGAU

Evaluating Step and Touch Potential Risks on Earthing Systems of High Voltage Cable Systems TP, THINUS DU PLESSIS ESKOM SOUTH AFRICA HJ, HARTMUT JAGAU Technology solutions and innovations for developing economies Evaluating Step and Touch Potential Risks on Earthing Systems of High Voltage Cable Systems TP, THINUS DU PLESSIS ESKOM SOUTH AFRICA HJ, HARTMUT

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01 SEC DISTRIBUTION GROUNDING STANDARD SDCS-03 Part-II Rev.01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING Rev. 01 This specification is property of SEC

More information

CONTINUING EDUC ATION

CONTINUING EDUC ATION 3 CONTINUING EDUC ATION FOR WISCONSIN ELECTRICIANS 2017 NEC Article 250 2 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive Suite 290 Waukesha, WI 53188 262-409-4282 www.wcitraining.com

More information

11-SDMS-03 REV. 02 SPECIFICATIONS FOR

11-SDMS-03 REV. 02 SPECIFICATIONS FOR 11-SDMS-03 REV. 02 SPECIFICATIONS FOR XLPE INSULATED POWER CABLES FOR RATED VOLTAGES FROM 15 KV UP TO 36 KV (U m ) This specification is property of SEC and subject to change or modification without notice

More information

American Electrical Institute

American Electrical Institute American Electrical Institute Oregon Electricians Continuing Education Grounding & Bonding (Article 250) 4 Hours American Electrical Institute PO Box 31131 Spokane, WA 99223 www.aeitraining.com Article

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 1. Introduction Fault location on communication and power cables

More information

Distance Protection of Cross-Bonded Transmission Cable-Systems

Distance Protection of Cross-Bonded Transmission Cable-Systems Downloaded from vbn.aau.dk on: April 19, 2019 Aalborg Universitet Distance Protection of Cross-Bonded Transmission Cable-Systems Bak, Claus Leth; F. Jensen, Christian Published in: Proceedings of the 12th

More information

Insulation Co-ordination For HVDC Station

Insulation Co-ordination For HVDC Station Insulation Co-ordination For HVDC Station Insulation Co-ordination Definitions As per IEC 60071 Insulation Coordination is defined as selection of dielectric strength of equipment in relation to the operating

More information

Substation HV Cables. Document Number: 1-11-FR-07

Substation HV Cables. Document Number: 1-11-FR-07 Substation HV Cables Document Number: 1-11-FR-07 VERSION 1.0 June 2018 This functional requirements document is in line with the organisation's 1-11-ACS-07 Substation HV Cables Asset Class Strategy Intellectual

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

Surge Protection and Grounding Issues

Surge Protection and Grounding Issues Surge Protection and Grounding Issues Presented to SCTE Chicago Chapter January 21, 2004 By: Nisar Chaudhry VP Electrical Engineering, CTO Introduction Transients caused by disturbances on the power lines

More information

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION December 2016 SPECIFICATION 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION

More information

NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations

NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations Version: 3.1 Date of Issue: September 2016 Page: 1 of 21 NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations 1. Purpose The purpose of this document is to detail the technical requirements

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING Rev. 01 This specification is property of SEC and subject to change or modification without any notice

More information

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment International Research Journal of Engineering and Technology (IRJET) eissn: 23 0056 Volume: 04 Issue: 02 Feb 2017 www.irjet.net pissn: 072 A Review Comprehension: Guideline for Testing of HV, EHV and UHV

More information

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables 21, rue d Artois, F-75008 PARIS AUCKLAND 2013 http : //www.cigre.org Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables Michael Krüger, Rene Hummel, Stefan Böhler, OMICRON Austria

More information

Medium Voltage Power Cables

Medium Voltage Power Cables N2XSY 6/0, /20, /30 NA2XSY 6/0, /20, /30 N2XS2Y 6/0, /20, /30 NA2XS2Y 6/0, /20, /30 N2XS(F)2Y 6/0, /20, /30 NA2XS(F)2Y 6/0, /20, /30 N2XSEY 3 x 6/0 Medium Voltage Power Cables Photo: HELUKABEL Q 47 Medium

More information

SBCA Industry Standards Subcommittee. Specification for 75 Ω Flexible RF Coaxial Drop Cable for Direct Broadcast Satellite (DBS) Installations

SBCA Industry Standards Subcommittee. Specification for 75 Ω Flexible RF Coaxial Drop Cable for Direct Broadcast Satellite (DBS) Installations SBCA Industry Standards Subcommittee Document: SBCA Series 6 Recommended Practices Date of Issue: Specification for 75 Ω Flexible RF Coaxial Drop Cable for Direct Broadcast Satellite (DBS) Installations

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices

More information

ECP HV INSULATION TESTING

ECP HV INSULATION TESTING Document Number: ECP 11-0006 Network(s): Summary: All ENGINEERING COMMISSIONING PROCEDURE ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing of new and

More information

Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES. 11 kv XLPE-Insulated Three-Core Underground Cables

Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES. 11 kv XLPE-Insulated Three-Core Underground Cables Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES ( Data Sheets ) 11 kv XLPE-Insulated Three-Core Underground Cables (3x240 mm 2 ) ADWEA/ADDC/AADC STANDARD : D-AAA-CAB-11-3Cx240

More information

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor

More information

IEC Standard Caledonian Offshore & Marine Cables

IEC Standard Caledonian Offshore & Marine Cables Power Copper s According to IEC 60228 Tinned conductors Cross section cl.2 cl.5 Cross section cl.2 cl.5 mm² Ohm/km Ohm/km mm² Ohm/km Ohm/km 1.0 18.2 20 70 0.270 0.277 1.5 12.2 13.7 95 0.195 0.210 2.5 7.56

More information

Chapter 6. WIRING SYSTEMS Safe Electrical Design

Chapter 6. WIRING SYSTEMS Safe Electrical Design Chapter 6 WIRING SYSTEMS Safe Electrical Design Topic 6-3 CABLE SELECTION BASED ON CURRENT CARRYING CAPACITY REQUIREMENTS INSTALLATION CONDITIONS Current carrying capacity (CCC) is the maximum continuous

More information

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Cables

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Cables Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Cables NO: 452-1 Office

More information

147,LoharChawl,9,TavawalaBuilding,1stFloor,MUMBAI

147,LoharChawl,9,TavawalaBuilding,1stFloor,MUMBAI DEALERSIN:WIRESCABLES&ELECTRICALS 147,LoharChawl,9,TavawalaBuilding,1stFloor,MUMBAI-400002. Tel.:22064216,39567822,22096361.E-mail:dvcable@gmail.com,Web.:www.dvcable.in INTRODUCTION As India marches towards

More information

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT Claus NEUMANN Darmstadt University of Technology Germany claus.neumann@amprion.net Klaus WINTER Swedish Neutral

More information

DESIGN OF A 45 CIRCUIT DUCT BANK

DESIGN OF A 45 CIRCUIT DUCT BANK DESIGN OF A 45 CIRCUIT DUCT BANK Mark COATES, ERA Technology Ltd, (UK), mark.coates@era.co.uk Liam G O SULLIVAN, EDF Energy Networks, (UK), liam.o sullivan@edfenergy.com ABSTRACT Bankside power station

More information

JULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

JULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum. FOREWORD This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C, N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared

More information

EI HIGH VOLTAGE INSULATION TESTING POLICY

EI HIGH VOLTAGE INSULATION TESTING POLICY Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and

More information

Tests on Extruded Cables

Tests on Extruded Cables Tests on Extruded Cables Pierre Argaut Chairman of CIGRE SC B1 October 26 th, 2011 At least, once in your life, you have heard these words: Development Tests Long-term Tests Prequalification Tests Extension

More information

Factors Affecting the Sheath Losses in Single-Core Underground Power Cables with Two-Points Bonding Method

Factors Affecting the Sheath Losses in Single-Core Underground Power Cables with Two-Points Bonding Method International Journal of Electrical and Computer Engineering (IJECE) Vol. 2, No. 1, February 2012, pp. 7~16 ISSN: 2088-8708 7 Factors Affecting the Sheath Losses in Single-Core Underground Power Cables

More information

Transmission of Electrical Energy

Transmission of Electrical Energy Transmission of Electrical Energy Electrical energy is carries by conductors such as overhead transmission lines and underground cables. The conductors are usually aluminum cable steel reinforced (ACSR),

More information

TABLE OF CONTENTS 7.0 CABLE INSTALLATION IN UNDERGROUND STRUCTURES

TABLE OF CONTENTS 7.0 CABLE INSTALLATION IN UNDERGROUND STRUCTURES TABLE OF CONTENTS 1.0 SCOPE 2.0 BURIAL DEPTH 3.0 MINIMUM BENDING RADIUS FOR POWER CABLES 4.0 PULLING TENSIONS AND SIDEWALL PRESSURES 5.0 PARAMETERS OF CABLE PULLING 6.0 DIRECT BURIED CABLE INSTALLATION

More information

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60728-11 Second edition 2005-01 Cable networks for television signals, sound signals and interactive services Part 11: Safety IEC 2005 Copyright - all rights reserved No part

More information

Grounding for Power Quality

Grounding for Power Quality Presents Grounding for Power Quality Grounding for Power Quality NEC 250.53 states that ground resistance should be less than 25 ohms. Is this true? Grounding for Power Quality No! NEC 250.53 states

More information

Power Cables and their Application

Power Cables and their Application Power Cables and their Application Parti Materials Construction Criteria for Selection Project Planning Laying and Installation Accessories Measuring and Testing Editor: Lothar Heinhold 3rd revised edition,

More information

The Variable Threshold Neutral Isolator (VTNI)

The Variable Threshold Neutral Isolator (VTNI) The Variable Threshold Isolator (VTNI) Installation Instructions INTRODUCTION The is designed specifically for installation between the primary neutral of a power utility distribution system and the secondary

More information

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date

More information

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994

More information

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN):

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN): Single Earthed Neutral and Multi Earthed Neutral. SEPTEMBER 6, 2011 5 COMMENTS Single Earthed Neutral and Multi Earthed Neutral: In Distribution System Three Phase load is unbalance and non linear so The

More information

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

Maximum Lightning Overvoltage along a Cable due to Shielding Failure Maximum Lightning Overvoltage along a Cable due to Shielding Failure Thor Henriksen Abstract--This paper analyzes the maximum lightning overvoltage due to shielding failure along a cable inserted in an

More information

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS TRANSFORMER IN GRID When surge arres t ers are installed close to a power transformer, they provide protection against lightning overvoltage ABSTRACT The aim of this research article is to determine the

More information

Transformers connected via a cable Overvoltage protection

Transformers connected via a cable Overvoltage protection A P P L I C AT I O N N OT E 2. 1 Transformers connected via a cable Overvoltage protection The APPLICATION NOTES (AN) are intended to be used in conjunction with the APPLICATION GUIDELINES Overvoltage

More information

Earthing of Electrical Devices and Safety

Earthing of Electrical Devices and Safety Earthing of Electrical Devices and Safety JOŽE PIHLER Faculty of Electrical Engineering and Computer Sciences University of Maribor Smetanova 17, 2000 Maribor SLOVENIA joze.pihler@um.si Abstract: - This

More information

EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT

EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT Akihiro AMETANI, Tomomi OKUMURA, Naoto NAGAOKA, Nobutaka, MORI Doshisha University - Japan

More information

50-SDMS-01 SPECIFICATIONS FOR

50-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR CURRENT TRANSFORMERS UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice C O N T E N T S CLAUSE TITLE PAGE NO. ------------ --------

More information

HV SYSTEMS. Prysmian HV Systems Product Range 66kV & 132 kv

HV SYSTEMS. Prysmian HV Systems Product Range 66kV & 132 kv HV SYSTEMS Prysmian HV Systems Product Range 66kV & 132 kv Prysmian HV Product Range Version: 06/10 The History of Cables 66kV Copper Conductor XLPE Insulated Cables Prysmian Cables & Systmes Ltd is part

More information

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER Analysis of Major Changes to Arrester Standards IEC 60099-4 STEVE BREWER Analysis of Major Changes to Arrester Standard IEC 60099-4 Steve Brewer- Senior Product Manager - HPS Arrester Business Unit Agenda

More information

Wisconsin Contractors Institute Continuing Education

Wisconsin Contractors Institute Continuing Education IMPORTANT NOTE: You should have received an email from us with a link and password to take your final exam online. Please check your email for this link. Be sure to check your spam folder as well. If you

More information

Telephone Cable Locating Techniques

Telephone Cable Locating Techniques Chapter 2 Telephone Cable Locating Techniques Introduction Read Chapter One of this manual to learn more general information about each of the following signal application methods. The following paragraphs

More information

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS SAUDI STANDARD NO. SASO IEC 60669-2-2: 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS Part 2-2: Particular requirements Electromagnetic remote-control switches (RCS) SAUDI ARABIAN

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60287-1-1 Edition 1.2 2001-11 Edition 1:1994 consolidated with amendments 1:1995 and 2:2001 Electric cables Calculation of the current rating Part 1-1: Current rating equations

More information

Testing Manual for Electrical Equipment

Testing Manual for Electrical Equipment EPPM, Singapore, 20-21 Sep 2011 Abstract Testing Manual for Electrical Equipment Nahed Al-Hajeri 1 and Anantha Madhavan 2 Quality Assurance (QA) refers to a program for the systematic monitoring and evaluation

More information

Note: The let-through of the protective device must be equal to or less than the short-circuit current rating of the component being protected.

Note: The let-through of the protective device must be equal to or less than the short-circuit current rating of the component being protected. CONDUCTOR SHORT-CIRCUIT PROTECTION Introduction: This paper analyzes the protection of wire from fault currents. It gives the specifier the necessary information regarding the short-circuit current rating

More information

Fatima Michael college of Engineering and Technology

Fatima Michael college of Engineering and Technology Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric

More information

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. HP Critical Facility Services delivered by EYP MCF What is VOLTAGE? Difference of Electric Potential

More information

Testing 320 kv HVDC XLPE Cable System

Testing 320 kv HVDC XLPE Cable System Testing 320 kv HVDC XLPE Cable System H. He, W. Sloot DNV GL, KEMA Laboratories Arnhem, The Netherlands Abstract Two unique test requirements in testing of a high- voltage direct- current (HVDC) cable

More information

National Radio Astronomy Observatory Socorro, NM EVLA Memorandum 41 Lightning Protection for Fiber Optic Cable. T. Baldwin June 05, 2002

National Radio Astronomy Observatory Socorro, NM EVLA Memorandum 41 Lightning Protection for Fiber Optic Cable. T. Baldwin June 05, 2002 National Radio Astronomy Observatory Socorro, NM 87801 EVLA Memorandum 41 Lightning Protection for Fiber Optic Cable T. Baldwin June 05, 2002 Summary Double-armor triple-sheath fiber optic cable will be

More information

Collection of standards in electronic format (PDF) 1. Copyright

Collection of standards in electronic format (PDF) 1. Copyright Collection of standards in electronic format (PDF) 1. Copyright This standard is available to staff members of companies that have subscribed to the complete collection of SANS standards in accordance

More information

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 4.0 Sectionalizer Construction... 4 5.0 Mechanism... 6 6.0 Solid Dielectric

More information

INTERNATIONAL TELECOMMUNICATION UNION SERIES K: PROTECTION AGAINST INTERFERENCE

INTERNATIONAL TELECOMMUNICATION UNION SERIES K: PROTECTION AGAINST INTERFERENCE INTERNATIONAL TELECOMMUNICATION UNION )454 + TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (10/96) SERIES K: PROTECTION AGAINST INTERFERENCE 2ISK ASSESSMENT OF DAMAGES TO TELECOMMUNICATION SITES DUE

More information

Lightning performance of a HV/MV substation

Lightning performance of a HV/MV substation Lightning performance of a HV/MV substation MAHMUD TAINBA, LAMBOS EKONOMOU Department of Electrical and Electronic Engineering City University London Northampton Square, London EC1V HB United Kingdom emails:

More information

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS 29 th International Conference on Lightning Protection 23 rd 26 th June 2008 Uppsala, Sweden PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS Ivo Uglešić Viktor Milardić Božidar

More information

Notes 3 Explanatory Information 4-10

Notes 3 Explanatory Information 4-10 Low Voltage Cables Section Three SECTION THREE - LOW VOLTAGE CABLES PAGE Notes 3 Explanatory Information 4-10 Construction 4 Current Ratings 5 Rating Factors 6 Voltage Drops 8 Selection Procedures 10 Minimum

More information

DEPARTMENT OF DEFENSE TEST METHOD STANDARD METHOD 301, DIELECTRIC WITHSTANDING VOLTAGE

DEPARTMENT OF DEFENSE TEST METHOD STANDARD METHOD 301, DIELECTRIC WITHSTANDING VOLTAGE INCH-POUND MIL-STD-202-301 18 April 2015 SUPERSEDING MIL-STD-202G w/change 2 (IN PART) 28 June 2013 (see 6.1) DEPARTMENT OF DEFENSE TEST METHOD STANDARD METHOD 301, DIELECTRIC WITHSTANDING VOLTAGE AMSC

More information

Prepared by Mick Maytum

Prepared by Mick Maytum IEC Technical Committee 109: Standards on insulation co-ordination for low-voltage equipment Warning Prepared by Mick Maytum mjmaytum@gmail.com The document content is of a general nature only and is not

More information

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT A. General In a hazardous location grounding of an electrical power system and bonding of enclosures of circuits and electrical equipment in the

More information

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS -1- INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION June 2013 SPECIFICATION No 150 kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS I. SCOPE This specification

More information

Measurements for validation of high voltage underground cable modelling

Measurements for validation of high voltage underground cable modelling Measurements for validation of high voltage underground cable modelling Unnur Stella Gudmundsdottir, Claus Leth Bak, Wojciech T. Wiechowski, Kim Søgaard, Martin Randrup Knardrupgård Abstract-- This paper

More information

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation M. Kondalu1, Dr. P.S. Subramanyam2 Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering College,

More information

Power Quality. Case Study. Conrad Bottu Laborelec January 2008

Power Quality. Case Study. Conrad Bottu Laborelec January 2008 Case Study Electromagnetic compatibility (EMC) study Breakdown of low voltage electronic equipment in a 25 kv substation Conrad Bottu Laborelec January 2008 Power Quality Power Quality 1 Introduction Description

More information

POWER AND COMMUNICATION CABLES Theory and Applications

POWER AND COMMUNICATION CABLES Theory and Applications POWER AND COMMUNICATION CABLES Theory and Applications Edited by R. Bartnikas, Editor Institut de Recherche dhydro-quebec Varennes, Quebec, Canada K. D. Srivastava, Coeditor University of British Columbia

More information

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C 1 Tender Notice No. NESCO Utility / O&M Materials/58 / 8267, dtd.17.7.15 Group-C Sl no. Material Description Unit Quantity 1 33KV C.T. Oil

More information

Tratos High Voltage cables

Tratos High Voltage cables March 2013 Tratos High Voltage cables Cables for a moving world www.tratos.eu Introduction High Voltage Cables Tratos is an international manufacturer and supplier of High & Extra High Voltage cable up

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

ECP HV INSULATION TESTING

ECP HV INSULATION TESTING Document Number: ECP 11-0006 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE EPN, LPN, SPN ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing

More information

Schluter -DITRA-HEAT Repair procedure for the DHE-HK Heating Cable

Schluter -DITRA-HEAT Repair procedure for the DHE-HK Heating Cable Schluter -DITRA-HEAT Repair procedure for the DHE-HK Heating Cable 555758 03/2018 2018 Schluter Systems L.P. DITRA and HEAT E are registered trademarks of Schluter Systems CONTENTS 3 List of tools required

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60728-11 1997 AMENDMENT 1 2000-10 Amendment 1 Cabled distribution systems for television and sound signals Part 11: Safety Amendement 1 Systèmes de distribution par câbles destinés

More information

Circulating sheath currents in flat formation underground power lines

Circulating sheath currents in flat formation underground power lines Circulating sheath currents in flat formation underground power lines J.R. Riba Ruiz 1, Antoni Garcia 2, X. Alabern Morera 3 1 Department d'enginyeria Elèctrica, UPC EUETII-"L'Escola d'adoberia" Plaça

More information

Licensed Electricians Practical Assessment (LEP)

Licensed Electricians Practical Assessment (LEP) Licensed Electricians Practical Assessment (LEP) Surname: Given Names: Date: Time: Location: Assessment Time (includes reading and preparation time): At the end of this time you will be asked to stop.

More information

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED)

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm 2 + 80mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of, 3C x95mm 2 +

More information

Australian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS

Australian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS AS 60044.1 2007 AS 60044.1 2007 Australian Standard Instrument transformers Part 1: Current transformers (IEC 60044-1 Ed.1.2 (2003) MOD) This Australian Standard was prepared by Committee EL-013, Measurement

More information

ULC STANDARDS TECHNICAL WORK PROGRAM (WTO) Last modified on:

ULC STANDARDS TECHNICAL WORK PROGRAM (WTO) Last modified on: CAN/ULC-60743-14 Live Working -- Terminology for Tools, Devices and Equipment Stability Date 29.240.20 29.260.99 29.260 CAN/ULC-60832-09 Insulating Poles (Insulating Sticks) and Universal Tool Attachments

More information

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider Shunt Reactors Global Top Energy, Machinery & Plant Solution Provider Our Business Brief introduction of Hyosung Power & Industrial Systems PG While Hyosung is an established name for world-class electrical

More information

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 177 2012 Specification for Braided 75 Ω, Mini-Series Quad Shield Coaxial Cable for CMTS and SDI cables NOTICE

More information

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013) S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013) 1.0 GENERAL 1.1 This specification covers the electrical and mechanical

More information

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888

More information

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1 GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS M. Kondalu, Dr. P.S. Subramanyam Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering

More information

TS RES - OUTSTANDING ISSUES

TS RES - OUTSTANDING ISSUES TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next

More information

FAQ ON EARTHING STANDARDS 16/08/2018

FAQ ON EARTHING STANDARDS 16/08/2018 FAQ ON EARTHING STANDARDS 16/08/2018 This document has been updated to include changes made to substation earthing layouts that have been made necessary due to copper theft. The main changes to be aware

More information

6. Internal lightning protection

6. Internal lightning protection 6. Internal lightning protection 6.1 Equipotential bonding for metal installations Equipotential bonding according to IEC 60364-4- 41 and IEC 60364-5-54 Equipotential bonding is required for all newly

More information

A. Product Description: Stranded conductor insulated wire.

A. Product Description: Stranded conductor insulated wire. SECTION 16120CPPR CONDUCTORS AND CABLE PART 1 - GENERAL 1.1 SYSTEM DESCRIPTION A. Product Requirements: Provide products as follows: 1. All building wire shall be stranded copper (no aluminum wire). 2.

More information