1 F E A T U R E A R T I C L E Cost-Effective Online Partial Discharge Measurements for Electrical Machines: Preventing Insulation Failure Key words: online PD monitoring, diagnosis, insulation assessment, motor, generator Introduction Medium-voltage (11-kV) motors or generators are key pieces of power plant equipment. Insulation failure of a motor or generator can result in severe production losses. Partial discharge (PD) monitoring provides early warning so that maintenance can be undertaken to prevent in-service insulation failure. Figure 1 shows the PD levels in three phases of a generator prior to failure of its insulation. The large difference (more than a factor of 40) between the PD levels of phases in good and poor condition and the increasing levels of PD activity with time strongly suggest the presence of faults in the Red and Yellow phases, which are likely to cause failure in the near future. The results of on-site PD measurements may be used as the basis for preventative maintenance, repair, and planned replacement. The demand for near-continuous operation of key equipment, and constraints on preventative maintenance due to limited capital and human resources, mean that PD measurements for insulation assessment must be cost-effective, conveniently implemented, and widely applicable. Research has shown that 56% of failed high-voltage rotating machines show insulation damage [1]. Cost-effective detection of defects in a small percentage of a large population of assets, using PD techniques, demands that the type of PD sensor used and the ease of its attachment to the equipment under test be carefully considered. The portable online PD measuring system described in this article was developed in New Zealand and has been in use there over the last 15 years. It features noninvasive clamp-on PD sensors, which are easily and rapidly attached [2] [6] and have been used for PD measurements on various types of high-voltage equipment. In this article several on-site applications of the system to generators and motors are described and discussed. The article also shows how the clamp-on PD sensors may be used under various site conditions to obtain informative and reliable online test results. The advantages of this portable system, compared with conventional setups, are highlighted. Yafei Zhou and Yang Qin AP EnerTec Ltd., 9A Delph St., Christchurch, New Zealand Colin Leach PanPac Forest Products Ltd., 1161 SH2 Wairoa Rd., Napier, New Zealand A portable online PD measuring system using noninvasive clamp-on PD sensors is described, and some results obtained using the system are presented. The sensors allow online PD tests to be conducted rapidly and cost effectively. The Online PD Measuring System The portable online PD measurement system consists of inductive clamp-on PD sensors and a portable digital storage oscilloscope. Development of the clamp-on PD sensors started in 1994 [7]. They have been used extensively on-site since then, many incremental improvements of the design having been made along the way. They can be temporarily or permanently attached at several positions on an operating machine, avoiding the need for expensive shutdown or disconnection before testing. They function as high-frequency current transducers, with flat response in the range of 200 khz to 100 MHz. A specially September/October Vol. 26, No /07/$25/ 2010IEEE 23
2 Figure 1. Partial discharge levels in the phases of a generator prior to failure of its insulation. selected ferrite core is used to enhance the sensor sensitivity (exceeding 6 V/A). Similar sensors including Rogowski coils (air core), yoke-coils, or high-frequency current transducers have been used for online PD measurements [8], [9]. The digital oscilloscope is a Tektronix TDS3000, selected on the basis of sampling rates, display, weight and dimensions, ease and flexibility of use, and cost. Importantly, it may be battery operated. Partial discharge tests normally start with phase-resolved PD measurements to determine whether PD is present in each phase. The PD patterns are then recorded. Such tests can be readily carried out using some of the sophisticated functions available on the oscilloscope and provide detailed information on PD levels and phase and frequency of occurrence. They usually allow identification of the type of PD and provide some measure of its severity. Observation of continuous displays of real-time, phase-resolved PD measurements is an essential PD measuring process. It confirms the repeatability of the PD signatures, thus helping to ensure that reliable PD measurements are recorded, and it indicates simultaneously whether it is necessary to filter out noise. Figure 2(a) shows phase-resolved PD measurements on three phases of a generator. Positive pulses dominate each phase, suggesting that slot discharge is occurring. Figure 2(b) shows PDs from a generator and six large evenly distributed (in time) pulses due to the brushes of the generator excitation system. Brush noise is often encountered during online PD measurement. These two signal sources are easily distinguished by viewing the continuous real-time measurement display, and thus the risk of incorrect diagnosis is reduced. Channel 1 shows much higher PD frequencies than the other two channels, suggesting that there are more PD sites, or erosion due to PD is faster, in the relevant phase. The oscilloscope sampling rate (>1 GHz) enables the detailed shape of a PD pulse of 10 ns duration to be recorded and displayed. Thus a PD site in a cable can be located within 0.1 m using the PD incident and reflection pulses. Alternatively, the PD wave front and width can be used for the same purpose and to differentiate between PD and noise. Figure 3(a) shows a PD pulse of 20 ns duration originating at one end of a cable 35 m in length. Its width after reflection from the other end of the cable Figure 2. (a) Phase-resolved partial discharge measurements from the three phases of a generator (channels 1, 3, and 4). The ac phase reference (channel 2) is the phase 1 current measured by a clamp-on ac transducer. (b) Partial discharges from a generator and six large regularly occurring pulses from the brushes of the generator excitation system. The ac phase reference (channel 2) is the phase 4 current measured by a clamp-on ac transducer. In (a) and (b), the vertical scales of channels 1, 3, and 4 are 50.0 mv/division. The common time base is 2 ms/ division. and return to its point of origin (after about 420 ns) is approximately 40 ns. (High-frequency components of the pulse are rapidly attenuated during transit.) Figure 3(b) shows a 500-ns pulse of low-frequency interference noise, originating at the far end of a cable connected to a generator. Its width and shape differ considerably from those of a PD pulse. It can be eliminated by appropriately selecting the frequency band of the filter attached to the PD sensor. 24 IEEE Electrical Insulation Magazine
3 Figure 3. (a) Propagation and reflection of a PD pulse initially of 20 ns duration. The vertical scale of channel 1 is 50.0 mv/division, and the time base is 100 ns/division. (b) A noise pulse with 500-ns pulse width. The vertical scale is 10.0 mv/division, and the time base is 2 μs/division. PD Sensor Positions on a Generator or Motor Installing conventional PD sensors on the high-voltage terminations of operating motors or generators can present considerable difficulty, e.g., the performance of the insulation in a relatively small termination box may be unsatisfactory under lightning impulse or switching overvoltages. Sensor installation may be prohibitively costly and is not practicable for many fully insulated terminations. The portable online PD measuring system with clamp-on sensors is a much more cost-effective solution. Figures 4(a) and 4(b) show a practical, noninvasive method for attaching clamp-on PD sensors for online PD measurements on motors or generators. In Figure 4(a) the cable connected to the high-voltage termination of the generator is used as a PD coupling capacitor. If the cable screen earth leads are brought outside the cable termination box, the clamp-on PD sensor (like a PD measuring impedance) can be attached to the earth lead while the machine is in operation. Alternatively, a ring-type PD sensor can be preinstalled on the screen earth lead inside the termination box. Figure 4(b) shows three preinstalled PD sensors with their signal cables placed in a plastic box. If the cable termination of a generator or motor is accessible, the clamp-on PD sensor can be temporarily attached to the earth end of the cable termination, as shown in Figure 5. In that case the PD sensor behaves similarly to a conventional PD measuring impedance connected at the high-voltage end, which often has a higher signal-to-noise ratio than that at the earth end. The polarity and wave shape of PD generated at the motor differ considerably from those of corona discharge generated at the far-end termination. Partial discharge from the motor is not attenuated in the cable, but any corona discharge or noise from the far end of the cable is significantly attenuated on arrival at the motor end. An additional benefit of attaching the sensor to the earth end of the cable termination is that the terminations can then be examined visually or by using an infrared camera. Such examination sometimes reveals insulation or connection problems that might not have been discovered if the terminations had been covered in the termination box. For a large generator, a bus bar, rather than cables, is installed at the termination box. In that case the earth lead for the bus covering can be used for online PD measurement. Alternative positions for noninvasive attachment of the sensors are (a) to the secondary wires of the bus current transformer (CT) in the vicinity of the high-voltage terminations of the generator, (b) to the earth leads of a lightning protection capacitor or arrester, and (c) to the screen earth of a short cable connecting the generator to the voltage transformer in the termination box. A typical application to a large thermal turbine generator is described in the following. The 600-MW 20-kV generator with fully enclosed inaccessible buses had been operating 24 hours a day for almost a year. Conventional online PD measurement would have necessitated taking the generator off-line while the sensors were being fitted, which was contrary to the operator s wishes. Following inspection of the installation drawing of the generator, the CTs on the bus of each phase of the generator were selected for PD coupling, as shown in Figure 6. The CTs were close to the high-voltage winding, and the stray capacitance between CT winding and bus provided good PD coupling. A clamp-on PD sensor was attached to all secondary wires of the CTs while the generator was in operation, and the insulation assessment was completed in an hour. The online PD measurements for each phase of the generator indicated the state of the insulation of each phase, and the points at which the insulation should be visually examined during the next overhaul. The frequency of PD measurements on a generator should be based on the insulation condition indicated by the PD test September/October Vol. 26, No. 5 25
4 Figure 4. (a) Partial discharge (PD) sensor position and the equivalent circuit of the PD measurement. (b) Three PD sensors installed at the cable screen earth leads for online PD measurement. results. Annual PD tests should be adequate for most machines not showing severe PD. Visual examination would be required if the PD level exceeds 1,000 mv and is increasing with time. Online PD Measurements for Motors Motors are key pieces of equipment for large pulp and paper mills. In one local enterprise, online PD tests of the insulation of aged motors, cables, and switchboards were carried out in Seventeen 11-kV motors and a generator were connected to the switchboards, each through a 30- to 50-m cable. Clamp-on sensors were attached to the three core feeder cable terminations in the termination box on the back of switchboard, as shown in Figure 7. During the PD tests, the terminations of some feeder cables connected to motors were selected for online PD measurements. The PD levels in the motors were usually significantly higher than those in the switchboards and cables. Three motors showed severe PD at a factor of 5 to 10 higher than that in a sound phase. Figure 8 shows a phase-resolved PD measurement on one phase of one of the three motors. The PD level was extremely high (2.52 V) in both positive and negative cycles. 26 IEEE Electrical Insulation Magazine
5 Figure 7. Clamp-on partial discharge (PD) sensors attached to the cable terminations at the rear of the switchboard. The top left inset shows how the clamp-on PD sensors are attached. The red cable is the motor feeder cable. Figure 5. Two clamp-on partial discharge (PD) sensors and a clamp-on ac current transducer attached to the cable termination of an 11-kV motor. The yellow channel on the digital storage oscilloscope shows PD from all three phases, and the magenta channel shows PD from only one phase. In these three motors, white powder was found at the slot ends of the conductor bars, as shown in Figure 9(a). Presumably the powder deposit was due to PD erosion. When the conductor bars were removed from the stator, it was clear that the insulation had been severely eroded by the PD, as illustrated in Figure 9(b). The semiconducting layer of the most affected winding bar had been completely eroded. The erosion could loosen the winding bar in the slot, thereby accelerating the erosion. After the three motors had been rewound, tests showed that the PD levels had been reduced to approximately 3% of the earlier levels, as shown in Figure 10. Clearly the PD tests provided essential information that prompted location and repair of the damaged insulation, thus preventing in-service failure. Figure 6. A clamp-on partial discharge sensor attached to the current transformer secondary wires of one of three phases. Figure 8. Phase-resolved partial discharge (PD) measurement showing severe PD (maximum intensity 2.52 V) from one phase of an 11-kV motor. The vertical scale of channel 3 is 500 mv/ division, and the time base is 2 ms/division. September/October Vol. 26, No. 5 27
6 Figure 10. Phase-resolved partial discharge measurement (channel 1 max 83.6 mv) of one phase of an 11-kV motor after it had been rewound. The vertical scale of channel 1 is 50 mv/division, and the time base is 2 ms/division. Figure 9. (a) White powder at the slot end of the conductor bars of a motor, due to severe partial discharge erosion. (b) Winding bars of a motor with severely eroded semiconducting layers. Conclusions On-site applications of the portable online PD measurement system for generators and motors have demonstrated that it is a noninvasive, fast, and cost-effective form of insulation assessment and monitoring. The sophisticated functions of the oscilloscope allow various PD quantities to be continuously displayed in real time, thus providing essential information for preventative or condition-based maintenance, repairs, and planned replacement. In this way the service lifetime of aged assets is extended, the probability of insulation failure is reduced, and the reliability of power plants and systems is enhanced. References [1] R. Brütsch, M. Tari, K. Fröhlich, T. Weiers, and R. Vogelsang, Insulation failure mechanisms of power generators, IEEE Electr. Insul. Mag., vol. 24, no. 4, pp , July/Aug [2] Y. Zhou, P. Chappell, and Y. Qin, Cost-effective on-line partial discharge measurement for cables, IEEE Electr. Insul. Mag., vol. 22, no. 2, pp , Mar./Apr [3] Y. Zhou, K. Gardner, and Y. Qin, A portable partial discharge measuring device for cost-effective insulation assessment, J. Elect. Electron. Eng., Australia, vol. 22, no. 2, pp , [4] Y. Zhou, A. Gardiner, G. Mathieson, and Y. Qin, A portable partial discharge measuring system for insulation condition monitoring, in Proceeding of the International Symposium on Electrical Insulating Materials, 1998, pp [5] Y. Zhou, A. Gardiner, G. Mathieson, and Y. Qin, Partial discharge measurements on the winding bars from a failed machine, in Proceedings of the IEEE Electrical Insulation Conference, 1997, pp [6] Y. Zhou, A. Gardiner, G. Mathieson, and Y. Qin, New methods of partial discharge measurement for the assessment and monitoring of insulation in large machines, in Proceedings of the IEEE Electrical Insulation Conference, 1997, pp [7] Y. Zhou, G. I. Dix, and P. W. Quaife, Insulation condition monitoring and testing for large electrical machines, in Proceedings of the IEEE International Symposium on Electrical Insulation, 1996, pp [8] M. Muhr, T. Strehl, E. Gulski, K. Feser, E. Gockenbach, W. Hauschild Highvolt, and E. Lemke, Sensors and sensing used for non-conventional PD detection, D1-102 CIGRE [9] L. Renforth, R. Mackinlay, M. Seltzer-Grant, and R. Shuttleworth, Online partial discharge (PD) spot testing and monitoring of high voltage cable sealing ends, B1-205 CIGRE Yafei Zhou obtained his PhD degree from The University of Queensland, Australia, in He spent two years with the Queensland Electricity Commission (now Powerlink) Australia, where he developed infrared and ultrasonic techniques for the detection of faulty insulators in insulator strings. In 1994 he joined Industrial Research Ltd. (IRL) in New Zealand, where he initiated research and development on new online partial discharge measuring techniques for insulation assessment and monitoring. These have been applied to numerous pieces of HV equipment and in substations. He was a principal research scientist and engineer, project manager, and HV 28 IEEE Electrical Insulation Magazine
7 lab manager at IRL. He is an International Accreditation New Zealand-approved signatory for high-voltage and heavy-current tests. He managed projects developing a live-line joint resistance measuring device, new aluminum connectors, and intelligent V/I sensors for HV cable state indication. Working in New Zealand over the last 15 years, he has carried out insulation failure studies for power companies, acted as consultant to manufacturers of high-voltage insulation testing equipment, and provided expert evidence for court cases and insurance companies. Since 2006 he has provided technical services through AP EnerTec Ltd. E- mail: yafei.zhou@gmail.com Yang Qin joined the Electrotec group of Industrial Research Ltd. New Zealand as a research engineer in 1996 and became a contract research engineer in She has many years of R&D experience in partial discharge online measuring techniques and on-site insulation assessment of HV equipment and substations. She has also conducted many high-voltage and heavy-current laboratory tests for various power companies and high-voltage equipment manufacturers. nzy.q@163.com Colin Leach is an electrical engineer with PanPac Forest Products Ltd., Napier, New Zealand. Custom-wound on small and large spools Based in Rhode Island, Conneaut Industries is a global supplier of specialty fibers for electrical insulation. Conneaut offers the world s highest quality poly-glass insulating yarns for magnet wire. Precision-wound with proprietary technology, Conneaut packages are defect-free, consistent and uniform. Plastic spools are available in metered lengths, up to 60 ends. Founded in 1930, Conneaut is known for technological support, on-time shipments and excellent customer support. Call John Santos, President, with inquiries YARN (9276) Fax: ISO 9001: info@conneaut.com Incorporated 1930 Shipping: 89 Hopkins Hill Road, West Greenwich, RI Mail: P.O. Box 1425, Coventry, RI September/October Vol. 26, No. 5 29
PD Solutions. On-Line PD Measurement Devices
On-Line PD Measurement Devices 1. Longshot Device (see Figure 1) The measurement system applied is based around the wideband (0-400 MHz) HVPD- Longshot partial discharge test unit which utilizes a high-speed
More informationPARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM
Abstract PARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM Q. SU Department of Electrical & Computer Systems Engineering Monash University, Clayton VIC 3168 Email: qi.su@eng.monash.edu.au
More informationIRIS POWER TGA-B. Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors
IRIS POWER TGA-B Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors We have not found another test method that produces as much decision support data for generator
More informationThe University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge
The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits
More informationInvesti ations Into the Use of Temperature Detectors as # tator Winding Partial Discharge Detectors
Conference Record of the 2006 IEEE International Symposium on Electrical Insulation Investi ations Into the Use of Temperature Detectors as # tator Winding Partial Discharge Detectors S.R. Campbell, G.C.
More informationPartial Discharge Measurement and Monitoring on High Voltage XLPE Cables
21, rue d Artois, F-75008 PARIS AUCKLAND 2013 http : //www.cigre.org Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables Michael Krüger, Rene Hummel, Stefan Böhler, OMICRON Austria
More informationCondition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology
Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of
More informationSpecialists in HV and MV test and diagnostics. Testing in Substations
Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies
More informationObjective Methods to Interpret Partial-Discharge Data on Rotating-Machine Stator Windings
Objective Methods to Interpret Partial-Discharge Data on Rotating-Machine Stator Windings Greg C. Stone, Fellow, IEEE, and Vicki Warren, Member, IEEE From IEEE Transactions on Industry Applications Vol.
More informationDiagnostic testing of cast resin transformers
Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com
More informationEFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento
Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of
More informationELECTRICAL POWER ENGINEERING
Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation
More informationPractical Experience in On-Line Partial Discharge Measurements of MV Switchgear Systems
Practical Experience in On-Line Partial Discharge Measurements of MV Switchgear Systems Z. Berler, I. Blokhintsev, A. Golubev, G. Paoletti, V. Rashkes, A. Romashkov Cutler-Hammer Predictive Diagnostics
More informationAfrica Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound
Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences
More informationON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM
ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM D. Clark¹ R. Mackinlay² M. Seltzer-Grant² S. Goodfellow² Lee Renforth² Jamie McWilliam³ and Roger
More informationOnline Localisation of Partial Discharge Using Pulse Propagation Parameters in Medium Voltage Cable Network
2015 17th UKSIM-AMSS International Conference on Modelling and Simulation Online Localisation of Partial Discharge Using n Parameters in Medium Voltage Cable Network Tauqeer Ahmed Shaikh, Abdulrehman Al-Arainy,
More informationPARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES
PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES Engr. IÑIGO V. ESCOPETE, JR. ITC Level 2 Certified Thermographer PHIL-NCB NDT-UT Level 2 Partial Discharge testing is a Condition Based Maintenance tool
More informationTHE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.
THE POWER OF LIFE WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk. Mr. Neal Yang Pro.E.E. Engineer About Us The flaw of dielectric material
More informationMEDIUM & HIGH VOLTAGE
MEDIUM & HIGH VOLTAGE TESTING EQUIPMENT VOLTAGE WITHSTAND SGM Series Resonant Systems The SGM series are used for generating high AC voltages at a fixed frequency (mainly 50 or 60 Hz) by means of an excited
More informationOn-line Partial Discharge Assessment and Monitoring of MV to EHV Cables
On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables William Higinbotham, Neil Davies and Victor Chan EA Technology LLC, New Jersey; USA, EA Technology Pty Ltd, Brisbane Australia; EA
More informationOMICRON Seminar on Partial Discharge Diagnostics on HV Assets. January 30, 2018 Beirut, Lebanon
OMICRON Seminar on Partial Discharge Diagnostics on HV Assets January 30, 2018 Beirut, Lebanon Substation Asset Testing and Diagnosis LOW ACCURACY LEVEL HIGH Take better maintenance decisions through accurate
More informationKnowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators
Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery Application of EMI Diagnostics to Hydro Generators James Timperley Doble Global Power Services Columbus, Ohio jtimperley@doble.com
More informationAspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen
Aspects of PD interpretation in HV power cables by Edward Gulski, Piotr Cichecki, Rogier Jongen General There are several aspects having influence on the diagnostic information and the condition judgment
More informationInternational Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer
Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 7, July -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 Comparison
More informationDoble Solutions for Partial Discharge. Greg Topjian Solutions Manager
Doble Solutions for Partial Discharge Greg Topjian Solutions Manager 617-393-3129 gtopjian@doble.com Why do we need to conduct PD measurements PD a major cause of early failure for HV insulation. Partial
More informationEI HIGH VOLTAGE INSULATION TESTING POLICY
Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and
More informationEffect of Shielded Distribution Cable on Very Fast Transients
IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 15, NO. 3, JULY 2000 857 Effect of Shielded Distribution Cable on Very Fast Transients Li-Ming Zhou and Steven Boggs, Fellow, IEEE Abstract Fast transients in
More informationTHE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE
THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales
More informationPERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE
PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE Fred STEENNIS, KEMA, (the Netherlands), fred.steennis@kema.com Peter VAN DER WIELEN, KEMA,
More informationWhy partial discharge testing makes good sense
Why partial discharge testing makes good sense PD measurement and analysis have proven to be reliable for detecting defects in the insulation system of electrical assets before major damage or a breakdown
More informationPartial Discharge Measurements on 110kV Current Transformers. Case Study. Results
2016 International Conference on Electrical Engineering and Automation (ICEEA 2016) ISBN: 978-1-60595-407-3 Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results Cristian DAN
More informationPartial discharge diagnostics on very long and branched cable circuits
11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA
More informationPrediction of Transient Transfer Functions at Cable-Transformer Interfaces
1 Prediction of Transient Transfer Functions at Cable-Transformer Interfaces Joe Y. Zhou, Member, IEEE and Steven A. Boggs, Fellow, IEEE Joe Zhou participated in this work while completing his Ph.D. at
More informationKEYWORDS On-line diagnostics, cable termination, partial discharge (PD), ultra-high frequency (UHF), sensitivity check.
2, rue d Artois, F-758 PARIS B-2 CIGRE 28 http : //www.cigre.org Application of UHF method for on-line PD diagnostics of cable terminations T. KLEIN Pfisterer Kontaktsysteme GmbH Germany D. DENISSOV, W.
More informationPARTIAL DISCHARGE MEASUREMENT
PARTIAL DISCHARGE MEASUREMENT Partial Discharges are small electrical sparks which occur predominantly at insulation imperfection. It is the phenomenon which occurs in the insulation on application of
More informationPROPAGATION OF PARTIAL DISCHARGE AND NOISE PULSES IN TURBINE GENERATORS
PROPAGATION OF PARTIAL DISCHARGE AND NOISE PULSES IN TURBINE GENERATORS M. Henriksen, Technical University of Denmark, DK-2800 Lyngby, Denmark G.C. Stone, M. Kurtz, Ontario Hydro, 800 Kipling Avenue, Toronto,
More informationVoltage Probe Manual and Data North Star High Voltage, Inc. Rev January 2016
561 Rose Loop NE Bainbridge Island, WA, USA 9811 (52)78-93; (26)219-425 FAX http://www.highvoltageprobes.com probes@highvoltageprobes.com Voltage Probe Manual and Data North Star High Voltage, Inc. Rev
More informationAlternative Coupling Method for Immunity Testing of Power Grid Protection Equipment
Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Christian Suttner*, Stefan Tenbohlen Institute of Power Transmission and High Voltage Technology (IEH), University of
More informationFluke MDA-510 and MDA-550 Motor Drive Analyzer
TECHNICAL DATA Fluke MDA-510 and MDA-550 Motor Drive Analyzer Simplify complex motor-drive troubleshooting with guided test setups and automated drive measurements that provide reliable, repeatable test
More informationEffect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers
Voltage (kv) Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers Li-Ming Zhou, Senior Member, IEEE and Steven Boggs, Fellow, IEEE Abstract: The high frequency attenuation
More informationNOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS
NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS Ljubomir KOJOVIC Cooper Power Systems - U.S.A. Lkojovic@cooperpower.com INTRODUCTION In steel facilities that use Electric Arc Furnaces (EAFs) to manufacture
More informationIRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.
IRIS POWER PDTracII Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear. We have not found another test method that produces as much
More informationCoolBLUE Inductive Absorbers NaLA Noise Line Absorbers
CoolBLUE Inductive Absorbers NaLA Noise Line Absorbers Motor Bearing Solution from MH&W International Corp. http://www.coolblue-mhw.com Variable Frequency Motor Drive Systems 1. What is the problem 2.
More informationSingle Line Diagram of Substations
Single Line Diagram of Substations Substations Electric power is produced at the power generating stations, which are generally located far away from the load centers. High voltage transmission lines are
More informationPartial Discharge, Survey or Monitor?
July 2014 Partial Discharge, Survey or Monitor? 24-7 Partial Discharge monitoring is the ultimate tool for finding insulation weaknesses before they fail. Introduction It s well established that Partial
More informationT/3000 T/3000. Substation Maintenance and Commissioning Test Equipment
T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY
More informationThe Application of Partial Discharge Measurement and Location on CGIS
International Journal on Electrical Engineering and Informatics Volume 4, Number 3, October 2012 The Application of Partial Discharge Measurement and Location on CGIS Min-Yen Chiu¹, Keng-Wei Liang¹, Chang-Hsing
More informationCHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN
75 CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 5.1 INTRODUCTION Partial Discharge (PD) detection is an important tool for monitoring insulation conditions in high voltage (HV) devices in power systems.
More informationNANOSECOND PULSE GENERATOR NPG-18/3500(N) USER MANUAL
NANOSECOND PULSE GENERATOR NPG-18/3500(N) USER MANUAL 2014 Megaimpulse Ltd. Copyright 2013 MEGAIMPULSE Ltd. All Rights Reserved. MEGAIMPULSE LTD. PROVIDES THIS MANUAL "AS IS" WITHOUT WARRANTY OF ANY KIND,
More informationIRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.
IRIS POWER PDTracII Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear. We have not found another test method that produces as much
More informationShort form User Manual
Nortech Detection Pty Ltd Unit1, Bldg 5, Forest Central Business Park, 49 Frenchs Forest Road, Frenchs Forest NSW 2086 PO Box 6011, Frenchs Forest DC, NSW 2086 Tel: 02 8977 4047 Fax: 02 9475 4742 email:
More informationRTD as a Valuable Tool in Partial Discharge Measurements on Rotating Machines
RTD as a Valuable Tool in Partial Discharge Measurements on Rotating Machines Z. Berler, I. Blokhintsev, A. Golubev, G. Paoletti, A. Romashkov Cutler Hammer Predictive Diagnostics Abstract: This paper
More informationDielectric response and partial discharge measurements on stator insulation at varied low frequency. Nathaniel Taylor
Dielectric response and partial discharge measurements on stator insulation at varied low frequency Nathaniel Taylor Rotating Electrical Machines : The Stator and its Windings turbo-generator motor hydro-generator
More informationApplication Note. Detection of Partial Discharge Using Ultrasound. Detection of Partial Discharge Using Ultrasound. Problem. iriss.
Detection of Partial Discharge Using Ultrasound Problem In electrical systems, especially above 1,000 Volts, sufficient and properly maintained equipment insulation helps ensure equipment longevity. However,
More informationImmunity Testing for the CE Mark
Immunity Testing for the CE Mark Summary The European Union (EU) currently has 25 member countries with 2 additional countries to be added in 2007. The total population at that time will be nearly a half
More informationII. TRADITIONAL APPROACH OF PD MEASUREMENTS
Advantages of Continuous Monitoring of Partial Discharges in Rotating Equipment and Switchgear Claude Kane Cutler Hammer Predictive Diagnostics 5421 Feltl Road, Suite 190 Minnetonka, MN 55343 Phone: 952-912-1358
More informationPower Frequency Withstand Voltage On-site testing of 400 kv GIS
Power Frequency Withstand Voltage On-site testing of 400 kv GIS D. Anaraki Ardakani, A. Omidkhoda, M. Solati High Voltage Engineering Center ACECR Tehran, Iran Da_ardakani@yahoo.com Paper Reference Number:
More informationNumbering System for Protective Devices, Control and Indication Devices for Power Systems
Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements
More informationPRY-CAM BREAKTHROUGH TECHNOLOGY FOR CONDITION ASSESSMENT AND ASSET MANAGEMENT
PRY-CAM BREAKTHROUGH TECHNOLOGY FOR CONDITION ASSESSMENT AND ASSET MANAGEMENT WELCOME TO PRY-CAM A REVOLUTION IN PARTIAL DISCHARGE MANAGEMENT The worlds of partial discharge (PD) measurement, asset management
More informationAdvanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) CP RC Resonance circuit for GIS testing A new approach to testing gas-insulated switchgear Testing gas-insulated switchgear
More informationN. TEST TEST DESCRIPTION
Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities
More informationVI 3 - i TABLE OF CONTENTS
VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3
More informationOMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates
OMICRON Seminar on Substation Testing and Diagnosis October 23, 2017 Dubai, United Arab Emirates October 24, 2017 Abu Dhabi, United Arab Emirates Time Optimized Substation Asset Testing and Diagnosis Agenda
More informationPartial Discharge Monitoring and Diagnosis of Power Generator
Partial Discharge Monitoring and Diagnosis of Power Generator Gao Wensheng Institute of High Voltage & insulation tech. Electrical Eng. Dept., Tsinghua University Wsgao@tsinghua.edu.cn Currently preventive
More informationInvestigation of PD Detection on XLPE Cables
Investigation of PD Detection on XLPE Cables Hio Nam O, T.R. Blackburn and B.T. Phung School of Electrical Engineering and Telecommunications The University New South Wales, Australia Abstract- The insulation
More informationN. TEST TEST DESCRIPTION
Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities
More informationThe importance of partial discharge testing throughout the development and operation of power transformers
The importance of partial discharge testing throughout the development and operation of power transformers Ulrike Broniecki OMICRON Energy Solutions GmbH, Berlin Power transformers are exposed to intense
More informationPractical aspects of PD localization for long length Power Cables
Practical aspects of PD localization for long length Power Cables M. Wild, S. Tenbohlen University of Stuttgart Stuttgart, Germany manuel.wild@ieh.uni-stuttgart.de E. Gulski, R. Jongen onsite hv technology
More information10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY
9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor
More informationPD Testing Considerations for MV Plant Cables
PD Testing Considerations for MV Plant Cables Cable Testing Philosophy Damage Mistake Aging Repair Manufacturing Transportation Installation Operation Power frequency 50/60 Hz Power frequency 50/60 Hz
More informationFurther Experience in the Use of Existing RTDs in Windings of Motors and Generators for the Measurement of Partial Discharges
Further Experience in the Use of Existing RDs in Windings of Motors and Generators for the Measurement of Partial Discharges Claude Kane Eaton Electrical Predicative Diagnostics 5421 Feltl Road Suite 190
More informationMONTRANO. Continuous monitoring system for power transformers
MONTRANO Continuous monitoring system for power transformers Condition monitoring to extend transformer life Knowing the dielectric condition of insulation is vital Dielectric flashover of insulation in
More informationBack to the Basics Current Transformer (CT) Testing
Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of
More informationCharacteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings
J Electr Eng Technol Vol. 9, No. 1: 280-285, 2014 http://dx.doi.org/10.5370/jeet.2014.9.1.280 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 Characteristics of Insulation Diagnosis and Failure in Gas Turbine
More informationGIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation
GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation W. Buesch 1) G. Palmieri M.Miesch J. Marmonier O. Chuniaud ALSTOM LTD 1) ALSTOM LTD High Voltage Equipment
More informationMAHALAKSHMI ENGINEERING COLLEGE
MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI 621213 QUESTION BANK -------------------------------------------------------------------------------------------------------------- Sub. Code : EE2353 Semester
More informationPartial Discharge Detection of High Voltage Switchgear Using a Ultra High Frequency Sensor
TRANSACTIONS ON ELECTRICAL AND ELECTRONIC MATERIALS Vol. 14, No. 4, pp. 211-215, August 25, 2013 Regular Paper pissn: 1229-7607 eissn: 2092-7592 DOI: http://dx.doi.org/10.4313/teem.2013.14.4.211 Partial
More informationElectrical Equipment Condition Assessment
Feature Electrical Equipment Condition Assessment Using On-Line Solid Insulation Sampling Importance of Electrical Insulation Electrical insulation plays a vital role in the design and operation of all
More informationOn-Site Partial Discharge Monitoring using the differential LEMKE PROBE LDP-5 and its accessories
Workshop 2000, lexandria, Virginia, 13 & 14 September 2000 paper No.: 8 On-Site Partial Discharge Monitoring using the differential LEMKE PROE and its accessories Dirk Russwurm, HV Technologies, Inc. bstract
More informationROTOR FAULTS DETECTION IN SQUIRREL-CAGE INDUCTION MOTORS BY CURRENT SIGNATURE ANALYSIS
ROTOR FAULTS DETECTION IN SQUIRREL-CAGE INDUCTION MOTORS BY CURRENT SIGNATURE ANALYSIS SZABÓ Loránd DOBAI Jenő Barna BIRÓ Károly Ágoston Technical University of Cluj (Romania) 400750 Cluj, P.O. Box 358,
More informationSoftware System for Finding the Incipient Faults in Power Transformers
Software System for Finding the Incipient Faults in Power Transformers Nikolina Petkova Technical University of Sofia, Department of Theoretical Electrical Engineering, 1156 Sofia, Bulgaria Abstract In
More informationBusbars and lines are important elements
CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection
More informationArresterFacts-002. Field Testing Arresters ArresterWorks.com. ArresterFacts are information modules pertaining to the arrester world.
ArresterFacts are information modules pertaining to the arrester world. This Field Testing of Arresters module will clarify the many questions about assessing the quality of an installed high voltage arrester
More informationNANOSECOND PULSE GENERATOR NPG-15/2000(N) USER MANUAL
NANOSECOND PULSE GENERATOR NPG-15/2000(N) USER MANUAL 2013 Megaimpulse Ltd. Copyright 2013 MEGAIMPULSE Ltd. All Rights Reserved. MEGAIMPULSE LTD. PROVIDES THIS MANUAL "AS IS" WITHOUT WARRANTY OF ANY KIND,
More informationNETWORK INNOVATION COMPETITION ANGLE-DC PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT
NETWORK INNOVATION COMPETITION PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT NOVEMBER 17 Version: 1.0 Authored by: Andrew Moon Engineering Consultant and Project Manager Kevin Smith Lead
More informationECP HV INSULATION TESTING
Document Number: ECP 11-0006 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE EPN, LPN, SPN ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing
More informationA New Method for the Calibration of the mv Ranges of an AC Measurement Standard
A New Method for the Calibration of the mv Ranges of an AC Measurement Standard Speaker/Author Neil Faulkner Fluke Corporation PO Box 9090, Everett, WA 98206 Phone: (425) 446-5538 FAX: (425) 446-5649 E-mail:
More informationA DUMMIES GUIDE TO GROUND FAULT PROTECTION
A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding
More informationLecture 36 Measurements of High Voltages (cont) (Refer Slide Time: 00:14)
Advances in UHV Transmission and Distribution Prof. B Subba Reddy Department of High Voltage Engg (Electrical Engineering) Indian Institute of Science, Bangalore Lecture 36 Measurements of High Voltages
More informationCATALOG including...
2002 CATALOG including... http://www.hioki.co.jp/ HIOKI company overview, new products, environmental considerations and other information are available on our website. 1 Advanced Instruments to Meet International
More informationIN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY
IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY Avinash Raj 1, Chandan Kumar Chakrabarty 1, Rafidah Ismail 1 and Basri Abdul Ghani 2 1 College of Engineering, University Tenaga
More informationA1-209 EXPERIENCES IN IDENTIFICATION OF PARTIAL DISCHARGE PATTERNS IN LARGE HYDROGENERATORS
21, rue d'artois, F-75008 Paris http://www.cigre.org A1-209 Session 2004 CIGRÉ EXPERIENCES IN IDENTIFICATION OF PARTIAL DISCHARGE PATTERNS IN LARGE HYDROGENERATORS CARLOS AZUAJE* WILLIAM TORRES C.V.G.
More informationHV AC TESTING OF SUPER-LONG CABLES
HV AC TESTING OF SUPER-LONG CABLES Stefan SCHIERIG, (Germany), schierig@highvolt.de Peter COORS, (Germany), coors@highvolt.de Wolfgang HAUSCHILD, IEC, CIGRE, (Germany), hauschild@highvolt.de ABSTRACT The
More informationApplication of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation
CIGRE SC A1 & D1 JOINT COLLOQUIUM October 24, 2007 Application of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation S. A. BHUMIWAT Independent Consultant
More informationOn-line partial discharge monitoring of statorwindings : comparison of different sensors Pemen, A.J.M.; Leeuw, de, W.; van der Laan, P.C.T.
On-line partial discharge monitoring of statorwindings : comparison of different sensors Pemen, A.J.M.; Leeuw, de, W.; van der Laan, P.C.T. Published in: Proceedings of the 1th International Symposium
More informationRCTrms Technical Notes
RCTrms Technical Notes All measuring instruments are subject to limitations. The purpose of these technical notes is to explain some of those limitations and to help the engineer maximise the many advantages
More informationNOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV
NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV Paul P. SEITZ, Seitz Instruments AG, (Switzerland), pps@seitz-instruments.ch Ben QUAK, Seitz Instruments AG, (Switzerland),
More informationThe Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.
The Importance of the Neutral-Grounding Resistor Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T. Presentation Preview What is high-resistance grounding (HRG)? What is the purpose of HRG? Why
More informationLOW VOLTAGE PWM INVERTER-FED MOTOR INSULATION ISSUES
LOW VOLTAGE PWM INVERTER-FED MOTOR INSULATION ISSUES Copyright Material IEEE Paper No. PCIC-4-15 RAPS-1433 Abstract - The topic of how low voltage IGBT-based PWM inverters create additional insulation
More informationNEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY
NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY Lorenzo PERETTO Luigi FODDAI Simone ORRU Luigi PUDDU Altea Switzerland ENEL Italy ENEL Italy REPL Italy lperetto@alteasolutions.com
More information