ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM

Size: px
Start display at page:

Download "ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM"

Transcription

1 ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM D. Clark¹ R. Mackinlay² M. Seltzer-Grant² S. Goodfellow² Lee Renforth² Jamie McWilliam³ and Roger Shuttleworth¹ ¹University of Manchester, UK, ²HVPD, UK, ³Scottish Power, UK INTRODUCTION The service performance of power cables depends on a number of factors, and as yet the quantitative dependence on the obvious factors has not yet been established. This is a clear failure of the research, but in the defence of the researchers, the dependence of the cable service life on the various factors, is not a simple cumulative outcome to establish. The other large difficulty is that the timescales for degradation and failure in cables tend to be very long. The cables often live longer than the researchers. In this paper we are looking at the relationship between failures in service, and partial discharge (PD) activity in power cables. In addition, we report progress in making locations of PD pulses using pulse shape methods. This allows simple measurements to reveal locations of PD events, and whilst this turns out to be not as accurate as the double ended methods (e.g. transponders etc), they are nevertheless a worthy addition to the armoury of diagnostics for high voltage cables. In making comparisons of service performance of power cables, and the PD activity, there are several things which must be taken into account. Firstly, PD activity (especially in paper insulated cables), is the main reason for long term degradation of the insulation in power cables. Chemical changes of course exist, but these are generally associated with ingress of moisture or oxidizing agents, and are normally put down to mechanical failure [1]. Cracking of the outer lead sheath in paper cables is not normally regarded as an insulation failure (although clearly it must be in the end), and is really a mechanical failure of the cable components. In such a way, the very large majority of insulation failures in paper insulated cables (and to a lesser extent, polymer insulated cables) is due to degradation from partial discharge action [2]. Looking at the PD activity essentially looks forward to the death of the parts of the cable responsible for the PD activity. However, the service record looks back at the past performance of the cables, and only in a statistical way, will this be related to the future failure rates. Manufacturing defects distributed along the cables would be a case where the failure performance may also act as a predictor of future performance. In general, there is no such link, and this makes this study a bit like economics, where we know almost everything about the past, and are prepared to say almost nothing about the future. This paper is an attempt at reconciling the two views of cable performance, with the possibility of edging ahead of the economists in the prediction stakes. PARTIAL DISCHARGE AND WORST PERFORMING CIRCUITS One of our authors has helped to produce figures for the worst performing paper insulated lead covered (PILC) cable circuits. These are failure records for a consecutive number of years. They refer to both 11 kv and 33 kv cables. In this programme, some of the worst performing circuits were tested using the on-line PD methods from HVPD. From any given substation, testing all circuits on-line, allows for both the worst performing cables (i.e. our target cables), and the 'non worst' cables to be investigated. This has provided a mix of both of these cable types which is the subject of the present study. TABLE 1 Failure Statistics for 113 circuits over 7 years Total Circuit (km) Average Circuit Length Average No of Faults/Year Average Faults/100km/Year Table 1 shows the failure statistics for a set of 113 circuits over a period of seven years. Note the Average fault rate is over 11 faults/100km/year. For 'normal' circuits the failure rates would likely be 10 times smaller than this, but these cables represent the worst performing circuits. We have introduced the more statistical idea of the chance of failure of a circuit, say P i for any circuit i. This is simply related to the failure rate per 100 km/year as per Equation ii. Where F i and L i are the circuit failure rates/100km/year, and circuit length (in km) respectively. From the failure statistics, i.e. the number of failures occurring in any particular year, we may draw out the chances of a circuit failing zero, one, two, three times etc. These are all directly related to P i.

2 Number of circuits Number of Occurances Frequency of Failures / Year The on-line PD measurements were made using high frequency current transformers (HFCT's) on the cable earth straps, or the cables themselves, above the earth strap take off point. Figure 2 shows the typical arrangement for the HFCT's on an 11 kv installation. Note the requirement for an insulated gland to get good quality PD data Number of failures in a year Figure 1 Cable failure occurrences, for 61 of the worst performing circuits over seven years Figure 1 shows such a picture for 61 circuits taken over seven continuous years. The ratio of no failures to one failure is given by Equation ii. The data of the PD testing is summarised in Figure 3, where the peak PD levels are shown for various PD magnitude bands Distribution of PD magnitudes Worst Perf Non Worst >5000 PD magnitude band (pc) From this the failure probability can be calculated, and hence the failures/100km/year. For the data in Figure 1, the probability P i = Using an average circuit length of 7.0 km, gives F i = 5.7 failures/100km/year. Note that the data in Figure 1 is different to the data averages in Table 1, and the average circuit length for the data in Figure 1 is not known. The interesting part about Figure 1 is that even in the case of the worst performing circuits, the most likely outcome is that in any particular year, the circuits do not fail. This may not be expected for the worst circuits in a distribution network. In making a link between the failure records of circuits, and the PD measurements made on-line, some link must be made between the past failure data, and the future performance as measured by the on-line PD results. In this work, some 56 circuits were tested for on-line PD, 13 circuits of which were in the 'worst performing' list, and 43 circuits which were not. Figure 3 Distribution of PD sizes for 56 on-line 11 kv and 33 kv cable measurements The cables cited in the worst performing circuits are clear, but those not in this class, are simply a random selection of circuits. In no sense are they 'best performing'. To make some sense of the data of Figure 3, it should be established if there exists any statistical difference between the two classes of circuits (i.e. worst performing or not). To do this, one may use the ratio of the number of circuits with discharges to the number of circuits without discharges, and compare these between the two classes. HVPD has some rules of thumb about PILC cables, which states that any cable with less than 2500 pc of partial discharge activity is deemed to be within acceptable limits of PD activity. For our purposes, we have used a figure less than this, i.e pc, on the basis that this should provide more sensitive results. Hence if we compare the number of circuits with PD less than 1000 pc with the number of circuits with PD over 1000 pc, the two classes of circuits should be directly comparable. TABLE 2 Comparison of the worst performing circuits to the non-worst performing circuits Circuit designation Worst performing circuits Non-worst performing circuits Ratio = (No circuits < 1000 pc) /(No circuits > 1000 pc) Figure 2 High frequency current transformer sensor attachment Table 2 shows the two ratios. Hence it is clear that the meaning of the worst performing circuits is clearly

3 demonstrated in the on-line PD results. In making some simple deductions about the on-line PD data, the ideas of time to failure and PD initiation must be made. It has long been argued that PD is the only long term deterioration mechanism for cable insulation. (this does not include sheath deterioration, and water ingress which are separate causes and only weakly related to long term deterioration of the insulation). If we make an assumption about an initiation rate say M k, (k is a sort of cable position index) the rate of introduction of failure sites in a cable. If the time to failure of these sites are T k, and of course we make no mention of the rates or gradients of T k with time, then simple thought experiments leads one to the conclusion that the introduction of a T k merely delays the appearance of a failure to a later date. If all the T k 's were short, or instant, then the failures would be distributed according to the initiation rate M k. Looking at the PD data, for the non worst performing circuits (and actually to some extent the worst performing as well), the huge majority of circuits do not show any PD activity. This has the instant implication that if the long term deterioration and failure is PD related, the times to failure T k must be short. If T k = 10 years say, then the worst performing circuits would all show PD activity throughout their seven year failure data, and they clearly do not as over half show no PD at all. This implies that the time to failures must be short, and statistically less than two years to give the large majority of 'low or zero PD' results which are observed. This will only really be confirmed if the cables are followed up and future PD measurements made, confirming this behaviour. Anecdotally, there is some evidence that low level deterioration happens over a long time in PILC cables, followed by a much more rapid growth to failure. Confirmation of this (or not) would be a large advance in the understanding of circuit performance. The next section is the important area of PD location using only a single on-line sensor. PULSE PROPAGATION IN POWER CABLES Power system transients such as PD pulses are often made up of a broad frequency spectrum, typically ranging from DC to MHz. Discharge processes produce fast-fronted, short duration pulses which propagate, with some frequency-dependent velocity along the cable conductor, and earth. Understanding how PD pulses propagate from the discharge site to the measurement position is important for locating defective areas of cable insulation, and also to assess the severity of the insulation breakdown process at work. Pulse amplitude attenuation and broadening ensure that as the PD pulse travels along the cable to the measurement point it becomes distorted from its original shape. Changes in the PD waveform are frequency dependent and are predominately due to skin-effect losses due to the presence of semiconductive layers within the cable, which severely attenuate the high-frequency components of the PD pulses. To describe the changes experienced by an individual PD pulse it is possible to use a form of the frequencydependent propagation constant, given in Equation iii. (iii) (iv) Equation iv is another form of expressing the frequency-dependent attenuation (α) and phase constant (β). Incorporation of the basic cable elements, i.e. resistance (R), inductance (L), conductance (G) and the capacitance (C) into the formula allows the pulse attenuation, and broadening to be computed, if such parameters were all known. For many cables these parameters can be determined by measurement, but are generally not quoted by manufacturers. Instead the method adopted was to use the frequency-dependent transfer function given in Equation v to describe the distortion of the pulse. (v) (vi) Equation vi represents the ratio of the pulses at some distance l and 0 (at source), both expressed in the frequency-domain. Pulse attenuation and broadening is determined by the behaviour of the real and imaginary parts of the transfer function given in Equation ii, which are directly related to the geometry of the cable and the dielectric properties of the insulation [3]. Splitting the transfer function into its real and imaginary parts is an application of Levy s method, and can help to understand the behaviour of the parameters with frequency. As a PD pulse travels along a cable parameters such as the pulse rise time, fall time, width, amplitude and energy all alter due to the dispersive effects of the transmission line; a power cable in this case [4]. Exactly how these pulse parameters alter as a function of distance propagated is fundamental to making single-ended PD locations based on pulse shape analysis. Applying the propagation constant in the frequencydomain allows estimations of PD pulse shape, and characteristics at various distances along the power cable to be approximated. Such pulse propagation modelling can assist in single-ended discharge site locations, and also help to understand the severity of the discharge location at source. Pulse injection experiments were initially carried out on RG223 coaxial type cable to establish the reliability of the pulse propagation modelling technique. Using the input pulse it was possible to replicate the pulse at 200 metres as shown in Figure 4.

4 Rise time (ns) transmission coefficients ( and T respectively) can distort the PD pulse shape, and parameters, the significant impedance of the transformer ensures that at the transformer end of the circuit, the pulse encounters what may be considered to be a virtual open circuit condition, and hence reflects and retains much of its energy. To illustrate the change in PD pulse shape with distance propagated, the increase in measured and simulated PD pulse rise time is shown in Figure 6. Figure 4 Measured and predicted pulses at 200 m Given the co-axial structure of medium voltage power cables, it was possible to extend the pulse propagation modelling technique to actual power cables. The next section goes on to present two case studies from online PD testing on UK 33 kv distribution networks, where the discharge sites were located using timedomain reflectometry (TDR) techniques and also confirmed with the theoretical approach described above RG223 MS Distance Propagated (m) CASE STUDIES Case Study 1 Partial discharge activity testing and locating on a UK 33 kv distribution network On-line PD measurements were carried out on two 33 kv cables; cable A and cable B that supply step-down transformers, Tx A. Cable A is approximately 1762 metres long. Failures of the cables over the years has meant that sections of the PILC-type cables have been replaced with 25 metre sections of XLPE cable. Measured PD pulses from cable A are shown in Figure 5. Figure 6 Simulated Pulse and PD Pulse Rise Time plotted against distance propagated Polynomial curves shown in Figure 6 were fitted to plots of the simulated (carried out on RG223 co-axial cable) and measured PD pulse pulses. An increase in the pulse rise time with distance occurs due to attenuation of the high-frequency components of the pulse, which constitute the fast fronted edge of the pulse. Figure 5 Partial Discharge Pulses measured on a 33 kv feeder - Cable A Using a combination of the PD mapping software, and wave-shape analysis described in it was possible to determine the parameters of the individual direct, and reflected PD pulses shown in Figure 5, as well as an approximate location for the discharge site, and hence knowledge of approximate pulse propagation distances. From Figure 5 and it was possible to compute the parameters of each of the four pulses, thus allowing calculations of pulse parameters against distance propagated to be made. Although the reflection and Figure 7 Partial discharge pulses measured and predicted at 1347 m from a 33 kv feeder cable Figure 7 above shows the direct and reflected PD pulses as measured with a high-frequency current transformer (HFCT) sensor. Using the equations that describe pulse attenuation and broadening it was possible to reproduce the PD pulse measured at 1347 metres, based on the reflection from the far end of the cable. Case Study 2 33kV Mixed Cable type circuits Two 33/6.6 kv, 14 MVA distribution transformers; T1 and T2 are fed from a tee-cable circuit. Circuit 1 is

5 2677 metres long with 28 joints, and made up of a combination of 185 mm² PILC, XLPE and EPR cable lengths of between 150 and 3 meters in length, some dating back to Circuit 2 is 926 metres, 240 mm² Copper, XLPE cable with five joints and has been operational since High levels of discharge activity were detected by a pre-installed PD monitoring unit, which initiated a PD location project, the results of which are presented here. Discharge location work shows that there were two active PD sites upon Circuit 1 at the following approximate locations, the first site was at 1564 m from the primary substation, and the second site at 1681 m. The locations may correspond to a trifurcating joints at positions 1575 m (SJ8699/27) from primary substation, and a further trifurcating joint at 1695 m (SJ8699/18). Figure 8 shows the PD location map indicating the two different sites of PD activity. Figure 8 Partial discharge locations for Circuit 1 Location work revealed that the discharge sites upon the cable corresponded well to joints positions. Waveforms from the PD sites are shown in Figure 9 Figure 9 Partial discharge pulses from two different locations on Circuit 1 With reference to Figure 9, pulse 1 was determined to be from joint 27 at 1575 m, and pulse 2 from joint 18 at 1695 m. This case study shows the applicability of online PD location work. CONCLUSIONS A study of some of the worst performing circuits in a distribution has been made. On-line PD methods were used to characterise the circuits, and a comparison and analysis of the statistics and the PD data has been made. On-line TDR methods of PD activity locations have also been made, can be supported by single-ended pulse shape analysis. The conclusions are as follows:- Statistics of failure of the worst performing circuits are presented which show that even for this class of circuit, the most likely outcome in any given year is no failures. The relationship between the probability of failure and the number of failures/100km/year is shown. The probability of failure is sometimes more useful in a statistical analysis. The difference between on-line PD results in the worst performing circuits, and the non worst performing circuits is shown. These show remarkable differences, implying that the PD results really do distinguish between the worst performing cables and not. From the number of PD measurements which were zero, or less than 1000 pc, it is clear that the time to failure of PD circuits must be relatively short, and typically less than two years from the initiation of a large PD site which eventually fails. The waveshape of PD events on PILC cables can be calculated from cable parameters, and used to calculate the locations of the PD events. These are not as accurate as transponder methods, but can be achieved with a single ended measurement. References 1. Renforth, L, Mackinlay, R and Seltzer-Grant, M, Deployment of Distributed On-line Partial Discharge Monitoring Devices on Medium-Voltage Electricity Networks, 20 th International Conference on Electricity Distribution (CIRED) Prague, 8-11 th June, Renforth, L, Mackinlay, R, Seltzer-Grant, M, Clark, D and Shuttleworth, R, Experiences from over 15 years of On-line Partial Discharge Testing of Inservice MV and HV Cables, Switchgear, Transformers and Rotating Machines, in IEEE IX Latin American Conference on Automatic Control and Industry Applications (LARC)1-4 th October, Mackinlay, R, Michel, M and Walton, C, W, Tools for Partial Discharge Testing MV cables and Plant, 18 th International Conference on Electricity Distribution (CIRED) Turin,6-9 th June, Wagenaars, P, Integration of Online Partial Discharge Monitoring and Defect Location in Medium-Voltage Cable Networks. Ph. D Thesis, Technische Universiteit Eindhoven, 2010.

6

Online Localisation of Partial Discharge Using Pulse Propagation Parameters in Medium Voltage Cable Network

Online Localisation of Partial Discharge Using Pulse Propagation Parameters in Medium Voltage Cable Network 2015 17th UKSIM-AMSS International Conference on Modelling and Simulation Online Localisation of Partial Discharge Using n Parameters in Medium Voltage Cable Network Tauqeer Ahmed Shaikh, Abdulrehman Al-Arainy,

More information

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales

More information

Investigation of PD Detection on XLPE Cables

Investigation of PD Detection on XLPE Cables Investigation of PD Detection on XLPE Cables Hio Nam O, T.R. Blackburn and B.T. Phung School of Electrical Engineering and Telecommunications The University New South Wales, Australia Abstract- The insulation

More information

PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE

PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE Fred STEENNIS, KEMA, (the Netherlands), fred.steennis@kema.com Peter VAN DER WIELEN, KEMA,

More information

PD Monitoring of MV/HV Power Cables December 2016

PD Monitoring of MV/HV Power Cables December 2016 PD Monitoring of MV/HV Power Cables December 216 Malcolm Seltzer-Grant m.seltzer-grant@hvpd.co.uk Introduction to HVPD Our global presence Introduction to HVPD Ltd HVPD are experts in the growing industry

More information

Practical aspects of PD localization for long length Power Cables

Practical aspects of PD localization for long length Power Cables Practical aspects of PD localization for long length Power Cables M. Wild, S. Tenbohlen University of Stuttgart Stuttgart, Germany manuel.wild@ieh.uni-stuttgart.de E. Gulski, R. Jongen onsite hv technology

More information

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY Avinash Raj 1, Chandan Kumar Chakrabarty 1, Rafidah Ismail 1 and Basri Abdul Ghani 2 1 College of Engineering, University Tenaga

More information

SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE

SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE Fred STEENNIS Paul WAGENAARS Denny HARMSEN DNV GL the Netherlands DNV GL the

More information

On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables

On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables William Higinbotham, Neil Davies and Victor Chan EA Technology LLC, New Jersey; USA, EA Technology Pty Ltd, Brisbane Australia; EA

More information

Extending the Functionality of On-line PD Monitoring Equipment for MV Power Cables

Extending the Functionality of On-line PD Monitoring Equipment for MV Power Cables 24 th Nordic Insulation Symposium on Materials, Components and Diagnostics 152 Extending the Functionality of On-line PD Monitoring Equipment for MV Power Cables Y. Li 1, P.A.A.F. Wouters 1, P. Wagenaars

More information

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of

More information

Directional Sensing for Online PD Monitoring of MV Cables Wagenaars, P.; van der Wielen, P.C.J.M.; Wouters, P.A.A.F.; Steennis, E.F.

Directional Sensing for Online PD Monitoring of MV Cables Wagenaars, P.; van der Wielen, P.C.J.M.; Wouters, P.A.A.F.; Steennis, E.F. Directional Sensing for Online PD Monitoring of MV Cables Wagenaars, P.; van der Wielen, P.C.J.M.; Wouters, P.A.A.F.; Steennis, E.F. Published in: Nordic Insulation Symposium, Nord-IS 05 Published: 01/01/2005

More information

Comparison of measurement methods for partial discharge measurement in power cables

Comparison of measurement methods for partial discharge measurement in power cables Comparison of measurement methods for partial discharge measurement in power cables L. W. van Veen Supervisor: Prof. dr. J. J. Smit Daily supervisor: Dr.ir. A. Rodrigo Mor April 2014 INTELLIGENT ELECTRICAL

More information

Specialists in HV and MV test and diagnostics. Testing in Substations

Specialists in HV and MV test and diagnostics. Testing in Substations Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies

More information

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences

More information

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES Frank WESTER, Edward GULSKI, Johan SMIT, Edwin GROOT*, Mark VAN VLIET* Delft University of Technology The Netherlands * NUON The Netherlands

More information

PDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics

PDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics PDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics CASE STUDY 1 (Doble Client Conference 2011, ACCA committee meeting) Dissolved Gas Analysis (DGA)

More information

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May 26 2011 St Pete Beach, Fl HDW ELECTRONICS, INC. THE BEST IN CABLE FAULT LOCATING TECHNOLOGY by Henning Oetjen Frank

More information

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 75 CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 5.1 INTRODUCTION Partial Discharge (PD) detection is an important tool for monitoring insulation conditions in high voltage (HV) devices in power systems.

More information

Effect of Shielded Distribution Cable on Very Fast Transients

Effect of Shielded Distribution Cable on Very Fast Transients IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 15, NO. 3, JULY 2000 857 Effect of Shielded Distribution Cable on Very Fast Transients Li-Ming Zhou and Steven Boggs, Fellow, IEEE Abstract Fast transients in

More information

USING DAMPED AC VOLTAGES

USING DAMPED AC VOLTAGES MODERN & TESTING DIAGNOSIS OF POWER CABLES USING DAMPED AC VOLTAGES BY EDWARD GULSKI AND ROGIER JONGEN, Onsite HV Solutions ag, Switzerland AND RALPH PATTERSON, Power Products & Solutions LLC, United States

More information

The Application of Partial Discharge Measurement and Location on CGIS

The Application of Partial Discharge Measurement and Location on CGIS International Journal on Electrical Engineering and Informatics Volume 4, Number 3, October 2012 The Application of Partial Discharge Measurement and Location on CGIS Min-Yen Chiu¹, Keng-Wei Liang¹, Chang-Hsing

More information

Partial discharge diagnostics on very long and branched cable circuits

Partial discharge diagnostics on very long and branched cable circuits 11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA

More information

Partial Discharge Trends in Medium Voltage Cables measured while in-service with PDOL

Partial Discharge Trends in Medium Voltage Cables measured while in-service with PDOL 1 Partial Discharge Trends in Medium Voltage Cables measured while in-service with PDOL André N. Cuppen, E. Fred Steennis, and Peter C. J. M. van der Wielen, Member, IEEE Abstract-- This paper presents

More information

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets Abstract: For decades it has been recognized that partial discharge assessment is an excellent method

More information

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers Voltage (kv) Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers Li-Ming Zhou, Senior Member, IEEE and Steven Boggs, Fellow, IEEE Abstract: The high frequency attenuation

More information

PARTIAL DISCHARGE LOCATION Selected Topics

PARTIAL DISCHARGE LOCATION Selected Topics PARTIAL DISCHARGE LOCATION Selected Topics M.S. Mashikian IMCORP ICC Meeting - Fall 2000 TOPICS TESTING PHILOSOPHY Excitation Voltage Test Voltage Level METHOD OF REFLECTOMETRY METHOD OF ARRIVAL TIME TESTING

More information

Electric Stresses on Surge Arrester Insulation under Standard and

Electric Stresses on Surge Arrester Insulation under Standard and Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems

More information

Cable Type 100. CAI Certification Specification

Cable Type 100. CAI Certification Specification Cable Type 100 CAI Certification Specification Ref: CAI-007-C / 100 / 12-2016 Confederation of Aerial Industries Ltd Communications House 41a Market Street WATFORD Herts WD18 0PN Tel: 01923 803030 Fax:

More information

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages Session Four: ractical Insulation Co-ordination Session Four: ractical Insulation Co-ordination for Lightning Induced Overvoltages Jason Mayer Technical Director, Energy Services, Aurecon Introduction

More information

PD Solutions. On-Line PD Measurement Devices

PD Solutions. On-Line PD Measurement Devices On-Line PD Measurement Devices 1. Longshot Device (see Figure 1) The measurement system applied is based around the wideband (0-400 MHz) HVPD- Longshot partial discharge test unit which utilizes a high-speed

More information

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk. THE POWER OF LIFE WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk. Mr. Neal Yang Pro.E.E. Engineer About Us The flaw of dielectric material

More information

Cable Type 125. CAI Certification Specification

Cable Type 125. CAI Certification Specification Cable Type 125 CAI Certification Specification Ref: CAI-008-C / 125 / 12-2016 Confederation of Aerial Industries Ltd Communications House 41a Market Street WATFORD Herts WD18 0PN Tel: 01923 803030 Fax:

More information

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location HAEFELY HIPOTRONICS Technical Document Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location P. Treyer, P. Mraz, U. Hammer Haefely Hipotronics, Tettex Instruments

More information

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables 21, rue d Artois, F-75008 PARIS AUCKLAND 2013 http : //www.cigre.org Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables Michael Krüger, Rene Hummel, Stefan Böhler, OMICRON Austria

More information

NETWORK INNOVATION COMPETITION ANGLE-DC PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT

NETWORK INNOVATION COMPETITION ANGLE-DC PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT NETWORK INNOVATION COMPETITION PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT NOVEMBER 17 Version: 1.0 Authored by: Andrew Moon Engineering Consultant and Project Manager Kevin Smith Lead

More information

Cable fault location in power cables. Systematics for cable testing, diagnosis and cable fault location

Cable fault location in power cables. Systematics for cable testing, diagnosis and cable fault location Cable fault location in power cables Systematics for cable testing, diagnosis and cable fault location CABLE JOINTS, CABLE TERMINATIONS, CABLE GLANDS, CABLE CLEATS FEEDER PILLARS, FUSE LINKS, ARC FLASH,

More information

PD Testing Considerations for MV Plant Cables

PD Testing Considerations for MV Plant Cables PD Testing Considerations for MV Plant Cables Cable Testing Philosophy Damage Mistake Aging Repair Manufacturing Transportation Installation Operation Power frequency 50/60 Hz Power frequency 50/60 Hz

More information

Software System for Finding the Incipient Faults in Power Transformers

Software System for Finding the Incipient Faults in Power Transformers Software System for Finding the Incipient Faults in Power Transformers Nikolina Petkova Technical University of Sofia, Department of Theoretical Electrical Engineering, 1156 Sofia, Bulgaria Abstract In

More information

Name: Craig Goodwin. Company Name: HV Diagnostics Inc

Name: Craig Goodwin. Company Name: HV Diagnostics Inc Name: Craig Goodwin Company Name: HV Diagnostics Inc Trip Out of Cable Circuit: Over Current, Ground Fault, Differential protection or Fuse blows. Try to establish if the cable has in fact failed or has

More information

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland Company HV Diagnostics Sarl is a Swiss based company in the field of high voltage test equipment for cable testing and diagnosis.

More information

Sources of transient electromagnetic disturbance in medium voltage switchgear

Sources of transient electromagnetic disturbance in medium voltage switchgear Sources of transient electromagnetic disturbance in medium voltage switchgear Dennis Burger, Stefan Tenbohlen, Wolfgang Köhler University of Stuttgart Stuttgart, Germany dennis.burger@ieh.uni-stuttgart.de

More information

CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES

CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES Hao ZHANG, Transgrid, (Australia), hao.zhang@transgrid.com.au Zhao LIU, University of NSW, (Australia), z.liu@unsw.edu.au Toan

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits

More information

CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER

CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER Henrik ENOKSEN Espen EBERG Sverre HVIDSTEN SINTEF Energy Research - Norway SINTEF Energy Research - Norway SINTEF Energy Research

More information

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB MV Power Cable Diagnostics by Frequency Domain Spectroscopy Peter Werelius Programma Electric AB Frequency Domain Spectroscopy Measurements of insulation capacitance and losses in a frequency interval

More information

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces 1 Prediction of Transient Transfer Functions at Cable-Transformer Interfaces Joe Y. Zhou, Member, IEEE and Steven A. Boggs, Fellow, IEEE Joe Zhou participated in this work while completing his Ph.D. at

More information

Partial Discharge Theory, Modeling and Applications To Electrical Machines

Partial Discharge Theory, Modeling and Applications To Electrical Machines Partial Discharge Theory, Modeling and Applications To Electrical Machines V. Vahidinasab, A. Mosallanejad, A. Gholami Department of Electrical Engineering Iran University of Science and Technology (IUST)

More information

Lab 1: Pulse Propagation and Dispersion

Lab 1: Pulse Propagation and Dispersion ab 1: Pulse Propagation and Dispersion NAME NAME NAME Introduction: In this experiment you will observe reflection and transmission of incident pulses as they propagate down a coaxial transmission line

More information

IEEE Transactions on Power Delivery. 15(2) P.467-P

IEEE Transactions on Power Delivery. 15(2) P.467-P Title Author(s) Citation Detection of wide-band E-M signals emitted from partial discharge occurring in GIS using wavelet transform Kawada, Masatake; Tungkanawanich, Ampol; 河崎, 善一郎 ; 松浦, 虔士 IEEE Transactions

More information

HV AC TESTING OF SUPER-LONG CABLES

HV AC TESTING OF SUPER-LONG CABLES HV AC TESTING OF SUPER-LONG CABLES Stefan SCHIERIG, (Germany), schierig@highvolt.de Peter COORS, (Germany), coors@highvolt.de Wolfgang HAUSCHILD, IEC, CIGRE, (Germany), hauschild@highvolt.de ABSTRACT The

More information

Transient calibration of electric field sensors

Transient calibration of electric field sensors Transient calibration of electric field sensors M D Judd University of Strathclyde Glasgow, UK Abstract An electric field sensor calibration system that operates in the time-domain is described and its

More information

Analysis of Propagation Paths of Partial Discharge Acoustic Emission Signals

Analysis of Propagation Paths of Partial Discharge Acoustic Emission Signals Analysis of Propagation Paths of Partial Discharge Acoustic Emission Signals Prathamesh Dhole, Tanmoy Sinha, Sumeet Nayak, Prasanta Kundu, N.K.Kishore Abstract Transformers are one of the most important

More information

WAVELET TRANSFORM ANALYSIS OF PARTIAL DISCHARGE SIGNALS. B.T. Phung, Z. Liu, T.R. Blackburn and R.E. James

WAVELET TRANSFORM ANALYSIS OF PARTIAL DISCHARGE SIGNALS. B.T. Phung, Z. Liu, T.R. Blackburn and R.E. James WAVELET TRANSFORM ANALYSIS OF PARTIAL DISCHARGE SIGNALS B.T. Phung, Z. Liu, T.R. Blackburn and R.E. James School of Electrical Engineering and Telecommunications University of New South Wales, Australia

More information

Partial Discharge Patterns in High Voltage Insulation

Partial Discharge Patterns in High Voltage Insulation 22 IEEE International Conference on Power and Energy (PECon), 2-5 December 22, Kota Kinabalu Sabah, Malaysia Partial Discharge Patterns in High Voltage Insulation Hazlee Illias, Teo Soon Yuan, Ab Halim

More information

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 2, APRIL 2002 569 Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System Li-Ming Zhou, Senior Member, IEEE,

More information

Partial discharge trends in medium voltage cables measured while in-service with PDOL Cuppen, A.N.; Steennis, E.F.; van der Wielen, P.C.J.M.

Partial discharge trends in medium voltage cables measured while in-service with PDOL Cuppen, A.N.; Steennis, E.F.; van der Wielen, P.C.J.M. Partial discharge trends in medium voltage cables measured while in-service with PDOL Cuppen, A.N.; Steennis, E.F.; van der Wielen, P.C.J.M. Published in: Proceedings of the IEEE PES Transmission and Distribution

More information

Non-intrusive Measurement of Partial Discharge and its Extraction Using Short Time Fourier Transform

Non-intrusive Measurement of Partial Discharge and its Extraction Using Short Time Fourier Transform > REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 1 Non-intrusive Measurement of Partial Discharge and its Extraction Using Short Time Fourier Transform Guomin Luo

More information

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES Gonzalo MAIZ, Iberdrola Distribución, (Spain), gmaiz@iberdrola.es Armando RODRIGO, Instituto

More information

A COMPARISON OF AC AND DC PARTIAL DISCHARGE ACTIVITY IN POLYMERIC CABLE INSULATION *

A COMPARISON OF AC AND DC PARTIAL DISCHARGE ACTIVITY IN POLYMERIC CABLE INSULATION * Morris, E.A. and Siew, W.H. (2018) A comparison of AC and DC partial discharge activity in polymeric cable insulation. In: 2017 IEEE 21st International Conference on Pulsed Power (PPC). IEEE, Piscataway,

More information

NOISE REDUCTION OF PARTIAL DISCHARGE SIGNALS USING LINEAR PREDICTION AND WAVELET TRANSFORM

NOISE REDUCTION OF PARTIAL DISCHARGE SIGNALS USING LINEAR PREDICTION AND WAVELET TRANSFORM NOISE REDUCTION OF PARTIAL DISCHARGE SIGNALS USING LINEAR PREDICTION AND WAVELET TRANSFORM Babak Badrzadeh and S.M.Shahrtash Department of electrical engineering Iran University of Science and Technology

More information

GIS Disconnector Switching Operation VFTO Study

GIS Disconnector Switching Operation VFTO Study GIS Disconnector Switching Operation VFTO Study Mariusz Stosur, Marcin Szewczyk, Wojciech Piasecki, Marek Florkowski, Marek Fulczyk ABB Corporate Research Center in Krakow Starowislna 13A, 31-038 Krakow,

More information

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of

More information

Underground System Design TADP 547

Underground System Design TADP 547 Underground System Design TADP 547 Industry Standards, Specifications and Guides Presentation 6.4 Instructor: Frank Frentzas Industry Organizations Several professional organizations develop standards

More information

Cable Data Collector (CDC): Application Guide

Cable Data Collector (CDC): Application Guide Cable Data Collector (CDC): Application Guide Contents 1. Introduction... 1 2. PD in cables... 1 3. Principle of operation... 2 4. Advantages and disadvantages... 6 5. Assessing circuit suitability...

More information

Chapter 1. Overvoltage Surges and their Effects

Chapter 1. Overvoltage Surges and their Effects Chapter 1 Overvoltage Surges and their Effects 1.1 Introduction Power equipment are often exposed to short duration impulse voltages of high amplitude produced by lightning or switching transients. These

More information

EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE

EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE Ju-Chu Hsieh 1, Cheng-Chi Tai 1, Ching-Chau Su 1, Chien-Yi Chen 1, Ting-Cheng Huang 1, Yu-Hsun Lin 2 1 Department

More information

SDMF based Interference Rejection and PD Interpretation for Simulated Defects in HV Cable Diagnostics

SDMF based Interference Rejection and PD Interpretation for Simulated Defects in HV Cable Diagnostics SDMF based Interference Rejection and PD Interpretation for Simulated s in HV Cable Diagnostics Xiaosheng Peng, Jinyu Wen, Zhaohui Li, Guangyao Yang State Key Laboratory of Advanced Electromagnetic Engineering

More information

TileCal Analogue Cable Measurement Report

TileCal Analogue Cable Measurement Report Weiming Qian w.qian@rl.ac.uk +44-1235-446128 Rutherford Appleton Laboratory, UK 25 August 2005 Contents Contents... 2 1 Scope... 3 2 Impedance measurements... 3 2.1 Test setup... 3 2.2 Differential mode

More information

ABSTRACT 1 INTRODUCTION

ABSTRACT 1 INTRODUCTION ELECTROMAGNETIC ANALYSIS OF WIND TURBINE GROUNDING SYSTEMS Maria Lorentzou*, Ian Cotton**, Nikos Hatziargyriou*, Nick Jenkins** * National Technical University of Athens, 42 Patission Street, 1682 Athens,

More information

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM,

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM, ONLINE OFFLINE VERSUS FEATURE PARTIAL DISCHARGE TESTING FOR CABLE ASSESSMENT B Y WIL L IAM H IG INBOT H AM, EA Technology, LLC Medium voltage cables have three distinct phases to their lifecycle: (1) new

More information

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages Paul P. SEITZ, Ben QUAK, Seitz Instruments AG, Niederrohrdorf, Switzerland, pps@seitz-instruments.ch Edward GULSKI,

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 1. Introduction Fault location on communication and power cables

More information

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Christian Suttner*, Stefan Tenbohlen Institute of Power Transmission and High Voltage Technology (IEH), University of

More information

BY JASON SOUCHAK, Megger

BY JASON SOUCHAK, Megger IMPROVING SYSTEM RELIABILITY WITH OFFLINE PD TESTING BY JASON SOUCHAK, Megger Partial discharge (PD) testing is a new generation of diagnostic testing for medium- and high-voltage underground power cable

More information

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage Journal of Energy and Power Engineering 9 () 3-3 doi:.7/93-897/.3. D DAVID PUBLISHIG Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

More information

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI UNIT II TRANSMISSION LINE PARAMETERS

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI UNIT II TRANSMISSION LINE PARAMETERS Part A (2 Marks) UNIT II TRANSMISSION LINE PARAMETERS 1. When does a finite line appear as an infinite line? (Nov / Dec 2011) It is an imaginary line of infinite length having input impedance equal to

More information

Statistical analysis of overvoltages due to the energisation of a 132 kv underground cable

Statistical analysis of overvoltages due to the energisation of a 132 kv underground cable University of Wollongong Research Online Faculty of Engineering and Information Sciences - Papers: Part A Faculty of Engineering and Information Sciences 2009 Statistical analysis of overvoltages due to

More information

PARTIAL DISCHARGE MEASUREMENT

PARTIAL DISCHARGE MEASUREMENT PARTIAL DISCHARGE MEASUREMENT Partial Discharges are small electrical sparks which occur predominantly at insulation imperfection. It is the phenomenon which occurs in the insulation on application of

More information

Abstract. 1 Introduction

Abstract. 1 Introduction Using optical couplers to monitor the condition of electricity infrastructure S.G. Swingler, L. Hao, P.L. Lewin and D.J. Swaffield The Tony Davies High Voltage Laboratory, University of Southampton, Southampton

More information

ON-LINE PARTIAL DISCHARGE MEASUREMENT AND CONTROL

ON-LINE PARTIAL DISCHARGE MEASUREMENT AND CONTROL REPRINT 19TH INTERNATIONAL CONFERENCE AND EXHIBITION ON ELECTRICITY DISTRIBUTION REED MESSE WIEN CONGRESS CENTER, VIENNA MAY 21-24, 2007 ON-LINE PARTIAL DISCHARGE MEASUREMENT AND CONTROL Kristian Winter,

More information

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 7, July -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 Comparison

More information

Why partial discharge testing makes good sense

Why partial discharge testing makes good sense Why partial discharge testing makes good sense PD measurement and analysis have proven to be reliable for detecting defects in the insulation system of electrical assets before major damage or a breakdown

More information

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems) Transmission Line Transient Overvoltages (Travelling Waves on Power Systems) The establishment of a potential difference between the conductors of an overhead transmission line is accompanied by the production

More information

The influence of environment on condition of location damage in screen of the coaxial cable. 1. Introduction

The influence of environment on condition of location damage in screen of the coaxial cable. 1. Introduction Computer Applications in Electrical Engineering The influence of environment on condition of location damage in screen of the coaxial cable Wiesław Tarczyński Opole University of Technology 45-233 Opole,

More information

Pulse Transmission and Cable Properties ================================

Pulse Transmission and Cable Properties ================================ PHYS 4211 Fall 2005 Last edit: October 2, 2006 T.E. Coan Pulse Transmission and Cable Properties ================================ GOAL To understand how voltage and current pulses are transmitted along

More information

CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS

CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS 136 CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS H. van Jaarsveldt* and R. Gouws** School of Electrical, Electronic and Computer Engineering, North-West

More information

EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT

EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT Akihiro AMETANI, Tomomi OKUMURA, Naoto NAGAOKA, Nobutaka, MORI Doshisha University - Japan

More information

OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM ELPIS J SINAMBELA

OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM ELPIS J SINAMBELA 1 OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM A thesis submitted to the Faculty of Electrical Power Engineering

More information

Pre location: Impulse-Current-Method (ICE)

Pre location: Impulse-Current-Method (ICE) 1 ICE (Impulse current method three phased 2 1.1 Ionisation delay time 2 1.2 DIRECT MODE 2 1.3 Output impedance of the generator 2 Surge generator as impulse source 3 High voltage test set as impulse source

More information

Assuring the Reliability of Critical Power Cable Systems

Assuring the Reliability of Critical Power Cable Systems Assuring the Reliability of Critical Power Cable Systems Presented by: Benjamin Lanz Manager of Application Engineering IMCORP Power Cable Reliability Consulting & Diagnostics Some of the technologies

More information

Pulse Arrested Spark Discharge (PASD) Wiring Diagnostic**

Pulse Arrested Spark Discharge (PASD) Wiring Diagnostic** 8 th Joint FAA/DoD/NASA Conference on Aging Aircraft February, 5 Pulse Arrested Spark Discharge (PASD) Wiring Diagnostic** Larry X Schneider *, M. Dinallo, R. K. Howard, S. F. Glover, G. E. Pena **, T.

More information

Distance Protection of Cross-Bonded Transmission Cable-Systems

Distance Protection of Cross-Bonded Transmission Cable-Systems Downloaded from vbn.aau.dk on: April 19, 2019 Aalborg Universitet Distance Protection of Cross-Bonded Transmission Cable-Systems Bak, Claus Leth; F. Jensen, Christian Published in: Proceedings of the 12th

More information

Power Quality and Reliablity Centre

Power Quality and Reliablity Centre Technical Note No. 8 April 2005 Power Quality and Reliablity Centre TRANSIENT OVERVOLTAGES ON THE ELECTRICITY SUPPLY NETWORK CLASSIFICATION, CAUSES AND PROPAGATION This Technical Note presents an overview

More information

EC 200 CHARACTERISTICS D A T A S H E E T. Kabelwerk EUPEN AG cable. M e c h a n i c a l c h a r a c t e r i s t i c s

EC 200 CHARACTERISTICS D A T A S H E E T. Kabelwerk EUPEN AG cable. M e c h a n i c a l c h a r a c t e r i s t i c s EC 200 EC200 - Rev. 3-23.06.11 Characteristic impedance 50 ± 2 Material copper wire Nominal capacity (pf/m) 80.5 Construction - Relative propagation velocity (%) 83 Diameter (mm) 1.05 Inductance (µh/m)

More information

Chapter 7 Conclusion 7.1 General

Chapter 7 Conclusion 7.1 General Chapter 7 7.1 General The mechanical integrity of a transformer winding is challenged by several mechanisms. Many dielectric failures in transformers are direct results of reduced mechanical strength due

More information

AM BASIC ELECTRONICS TRANSMISSION LINES JANUARY 2012 DEPARTMENT OF THE ARMY MILITARY AUXILIARY RADIO SYSTEM FORT HUACHUCA ARIZONA

AM BASIC ELECTRONICS TRANSMISSION LINES JANUARY 2012 DEPARTMENT OF THE ARMY MILITARY AUXILIARY RADIO SYSTEM FORT HUACHUCA ARIZONA AM 5-306 BASIC ELECTRONICS TRANSMISSION LINES JANUARY 2012 DISTRIBUTION RESTRICTION: Approved for Pubic Release. Distribution is unlimited. DEPARTMENT OF THE ARMY MILITARY AUXILIARY RADIO SYSTEM FORT HUACHUCA

More information

Strathprints Institutional Repository

Strathprints Institutional Repository Strathprints Institutional Repository Given, M and Mason, Ronald and Judd, Martin and Mcglone, Phillip and Timoshkin, Igor and Wilson, Mark () Comparison between RF and electrical signals from the partial

More information

Generation of Sub-nanosecond Pulses

Generation of Sub-nanosecond Pulses Chapter - 6 Generation of Sub-nanosecond Pulses 6.1 Introduction principle of peaking circuit In certain applications like high power microwaves (HPM), pulsed laser drivers, etc., very fast rise times

More information

Estimating the Impact of VLF Frequency on Effectiveness of VLF Withstand Diagnostics

Estimating the Impact of VLF Frequency on Effectiveness of VLF Withstand Diagnostics Estimating the Impact of VLF on Effectiveness of VLF Withstand Diagnostics Nigel Hampton (1), Jean Carlos Hernandez-Mejia (2), Marina Kuntsevich (3), Joshua Perkel (1), Vivek Tomer (3) 1 - NEETRAC, Atlanta,

More information