PARTIAL DISCHARGE LOCATION Selected Topics

Size: px
Start display at page:

Download "PARTIAL DISCHARGE LOCATION Selected Topics"

Transcription

1 PARTIAL DISCHARGE LOCATION Selected Topics M.S. Mashikian IMCORP ICC Meeting - Fall 2000

2 TOPICS TESTING PHILOSOPHY Excitation Voltage Test Voltage Level METHOD OF REFLECTOMETRY METHOD OF ARRIVAL TIME TESTING Branched Circuits On-line - Discussion of ON and OFF-Line Major Concerns - Answers 1

3 TESTING PHILOSOPHY PURPOSE: Reduce Service Failures - Improve Reliability Reduce Cost or Delay Capital Expenditure TEST GOALS: Identify defects that may cause near-term service failures Characterize severity of defects to help prioritize corrective actions Constraint: Minimize likelihood of test-produced damage Other 2

4 TESTING PHILOSOPHY EXCITATION VOLTAGE Use 50/60Hz produced by resonant test set Ramp voltage slowly until PD is detected or max. test voltage is reached Dwell approx. 2 seconds (will be reduced to ~ 10 cycles). Reduce voltage to zero very rapidly. 3

5 RESONANT TRANSFORMER Inductor L 1. Variable air-gap inductor 2. Fixed inductor C Cable U 1 1. U 1 is 50/60 Hz 2. U 1 is variable frequency Resonance: ωl = 1/ωC L ω 4

6 PARTIAL WAVE - 50/60HZ 1/4 or 1/2-cycle 50/60Hz dc PD is detectable only in the quadrants shown 5

7 OSCILLATING WAVE (OSW) dc Frequency dictated by cable capacitance Attenuation depends on cable 6

8 APDAC 50/60 Hz + dc - ALTERNATING POLARITY DC-BIASED AC 7

9 TEST VOLTAGE LEVEL Decide after discussing with client Minimum: 2U 0 recommended Maximum: U 0 Rationale Consider maximum transient voltage that may exist on system: geographic location and system protection. 8

10 CUMULATIVE PD PROBABILITY, 2500km, EXTRUDED CABLE Cumulative PD Probability, % PDIV Range, U DATA BASED ON 960 PD EVENTS IN CABLES At 1.0 U 0, less than 3% of PD events can be identified. 9

11 TEST VOLTAGE LEVEL PDIV varies with type of excitation voltage: With sinusoidal VLF, PDIV may be as high as 2.5 times that at 50/60Hz. Where PD is detected with 50/60Hz voltage, no PD may seem to exist at the same voltage level in PD tests with other types of excitation voltage. 10

12 PRINCIPLES OF PD TESTING PD Site Location Reflectometry (off-line) Arrival-Time Non-branched (2-termination) system Off-Line On-Line Branched system: Off-Line On-Line Frequency-Domain Testing IMCORP Technologies 11

13 REFLECTOMETRY 25 Amplitude, mv t 2 A C B ~ x t 1 PD Site Estimator AC = t 1 t 2 x AB Time, µs 12

14 TEST REPORT Joint and PD Locations Joint PD 13

15 TEST REPORT Joint and PD Locations Joint PD 14

16 PHASE RESOLVED PD DISPLAY PD in Termination 15

17 ARRIVAL-TIME NON-BRANCHED CABLE sensor 1 Principle x sensor 2 t 1 x L-x t 2 x = 1/2[v(t1-t2)+L] ~ Multi- Channel Estimator Sensor 1 Signal Conditioner Actual From SDCT Sensor 2 SDCT SDCT = Signal detection - conditioning - transmission 16

18 ARRIVAL-TIME BRANCHED CABLES Remote #2 Test Transformer Sensor Branched Cable SDCT Remote #3 Signal conditioner Estimator Multi-Channel From #1,2,3 SDCT Remote #1 SDCT 17

19 TESTING 4-TERMINAL CIRCUIT 18

20 PD-LOCATION 19

21 PD TESTING - Major Concerns Is PD test able to locate water trees? All trees? Some trees? See McBride et al. Does PD testing unduly deteriorate or fail Good cables? Defective cables? - Effect of high dc or thumping How effective is ON-LINE testing? How effective is PD testing of PILC cables? Are PD test results obtained by different methods identical? 20

22 McBride et al. (Georgia Power Res., and EPRI) - IEEE Trans. on Power Del. 4/94 70mils 70mils 35x48-mil void 21

23 McBride et al. (Georgia Power Res., and EPRI) - IEEE Trans. on Power Del. 4/94 Inspection of these wafers revealed a large void (35 mils wide and 48 mils high) in the center of the (70 mils diameter and 70 mils high) water tree. There was significant evidence of PD within the interior of the water tree, with darkened areas near the tips of the tree. This was clearly the site of the PD activity. Cable failures near large water trees have occurred in ac breakdown tests 22

24 McBride et al. (Georgia Power Res., and EPRI) - IEEE Trans. on Power Del. 4/94 Seven cables failed while active PD sites were monitored (at higher voltage than PDIV). With the exception of two samples (out of the remaining 7 samples with PD) all other cable failures occurred at the PD inception voltage while (PD site) locations were being performed Failures were associated with the PD sites. The duration of sustained PD ranged from 2 to 80 minutes prior to failure. The theory that PD above operating voltage results in failure at operating voltage is not supported by this data. 23

25 McBride et al. (Georgia Power Res., and EPRI) - IEEE Trans. on Power Del. 4/94 Very few cables contained active PD sites near operating voltage. No PD above 1-3pC was detected in any of the test cables (61 samples) when energized at operating voltage. (PDIV = 8-35kV). Most PD sites were detected at twice operating voltage or higher. The (pc) level of the PD at a site could not be correlated with the likelihood of a failure at or near the site. 24

26 BREAKDOWN AT PD SITE THROUGH VENTED WATER TREE 25

27 IMPROVED RELIABILITY Peter Daly, San Francisco, Jan. 20, BEFORE UPTI TESTING AFTER UPTI TESTING Feeder Cables 0.40 SAIFI Feeder Cables Year NOTE: Only 40% of Recommended Repair Was Completed 26

USING DAMPED AC VOLTAGES

USING DAMPED AC VOLTAGES MODERN & TESTING DIAGNOSIS OF POWER CABLES USING DAMPED AC VOLTAGES BY EDWARD GULSKI AND ROGIER JONGEN, Onsite HV Solutions ag, Switzerland AND RALPH PATTERSON, Power Products & Solutions LLC, United States

More information

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May 26 2011 St Pete Beach, Fl HDW ELECTRONICS, INC. THE BEST IN CABLE FAULT LOCATING TECHNOLOGY by Henning Oetjen Frank

More information

Partial discharge diagnostics on very long and branched cable circuits

Partial discharge diagnostics on very long and branched cable circuits 11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA

More information

BY JASON SOUCHAK, Megger

BY JASON SOUCHAK, Megger IMPROVING SYSTEM RELIABILITY WITH OFFLINE PD TESTING BY JASON SOUCHAK, Megger Partial discharge (PD) testing is a new generation of diagnostic testing for medium- and high-voltage underground power cable

More information

Assuring the Reliability of Critical Power Cable Systems

Assuring the Reliability of Critical Power Cable Systems Assuring the Reliability of Critical Power Cable Systems Presented by: Benjamin Lanz Manager of Application Engineering IMCORP Power Cable Reliability Consulting & Diagnostics Some of the technologies

More information

OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES

OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES Hein PUTTER Frank PETZOLD Philipp LEGLER Megger Germany Megger Germany Megger - Germany hein.putter@megger.com frank.petzold@megger.com philipp.legler@megger.com

More information

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland Company HV Diagnostics Sarl is a Swiss based company in the field of high voltage test equipment for cable testing and diagnosis.

More information

Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages

Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages F. Petzold, H.T. Putter, D. Götz, H. Schlapp, S. Markalous SebaKMT GmbH Baunach/Radeburg,

More information

Practical aspects of PD localization for long length Power Cables

Practical aspects of PD localization for long length Power Cables Practical aspects of PD localization for long length Power Cables M. Wild, S. Tenbohlen University of Stuttgart Stuttgart, Germany manuel.wild@ieh.uni-stuttgart.de E. Gulski, R. Jongen onsite hv technology

More information

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM D. Clark¹ R. Mackinlay² M. Seltzer-Grant² S. Goodfellow² Lee Renforth² Jamie McWilliam³ and Roger

More information

PD Testing Considerations for MV Plant Cables

PD Testing Considerations for MV Plant Cables PD Testing Considerations for MV Plant Cables Cable Testing Philosophy Damage Mistake Aging Repair Manufacturing Transportation Installation Operation Power frequency 50/60 Hz Power frequency 50/60 Hz

More information

Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics

Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics Dominique Bolliger, Ph.D. HV TECHNOLOGIES, Inc. Manassas, VA, USA d.bolliger@hvtechnologies.com Abstract In

More information

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages Paul P. SEITZ, Ben QUAK, Seitz Instruments AG, Niederrohrdorf, Switzerland, pps@seitz-instruments.ch Edward GULSKI,

More information

Partial Discharge, Survey or Monitor?

Partial Discharge, Survey or Monitor? July 2014 Partial Discharge, Survey or Monitor? 24-7 Partial Discharge monitoring is the ultimate tool for finding insulation weaknesses before they fail. Introduction It s well established that Partial

More information

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES Gonzalo MAIZ, Iberdrola Distribución, (Spain), gmaiz@iberdrola.es Armando RODRIGO, Instituto

More information

On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables

On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables William Higinbotham, Neil Davies and Victor Chan EA Technology LLC, New Jersey; USA, EA Technology Pty Ltd, Brisbane Australia; EA

More information

OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM ELPIS J SINAMBELA

OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM ELPIS J SINAMBELA 1 OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM A thesis submitted to the Faculty of Electrical Power Engineering

More information

WIRE AND CABLE ENGINEERING GUIDE

WIRE AND CABLE ENGINEERING GUIDE Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime

More information

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV Paul P. SEITZ, Seitz Instruments AG, (Switzerland), pps@seitz-instruments.ch Ben QUAK, Seitz Instruments AG, (Switzerland),

More information

ICC PES Spring 2011 Meeting, Educational Session Luigi Testa, Alfred Mendelsohn

ICC PES Spring 2011 Meeting, Educational Session Luigi Testa, Alfred Mendelsohn The use of pulse shape in PD testing of cable systems using VLF ICC PES Spring 2011 Meeting, Educational Session Luigi Testa, Alfred Mendelsohn 1 Introduction Hipot VLF testing of power cable systems is

More information

PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE

PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE Fred STEENNIS, KEMA, (the Netherlands), fred.steennis@kema.com Peter VAN DER WIELEN, KEMA,

More information

Online Localisation of Partial Discharge Using Pulse Propagation Parameters in Medium Voltage Cable Network

Online Localisation of Partial Discharge Using Pulse Propagation Parameters in Medium Voltage Cable Network 2015 17th UKSIM-AMSS International Conference on Modelling and Simulation Online Localisation of Partial Discharge Using n Parameters in Medium Voltage Cable Network Tauqeer Ahmed Shaikh, Abdulrehman Al-Arainy,

More information

Is Fault Location Killing Our Cable Systems?

Is Fault Location Killing Our Cable Systems? Is Fault Location Killing Our Cable Systems? Benjamin Lanz, Member, IEEE; Eugene Sanchez, Member, IEEE Abstract Power outages caused by faults in underground cable systems can be difficult to locate, however

More information

NOISE REDUCTION OF PARTIAL DISCHARGE SIGNALS USING LINEAR PREDICTION AND WAVELET TRANSFORM

NOISE REDUCTION OF PARTIAL DISCHARGE SIGNALS USING LINEAR PREDICTION AND WAVELET TRANSFORM NOISE REDUCTION OF PARTIAL DISCHARGE SIGNALS USING LINEAR PREDICTION AND WAVELET TRANSFORM Babak Badrzadeh and S.M.Shahrtash Department of electrical engineering Iran University of Science and Technology

More information

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB MV Power Cable Diagnostics by Frequency Domain Spectroscopy Peter Werelius Programma Electric AB Frequency Domain Spectroscopy Measurements of insulation capacitance and losses in a frequency interval

More information

Investigation of PD Detection on XLPE Cables

Investigation of PD Detection on XLPE Cables Investigation of PD Detection on XLPE Cables Hio Nam O, T.R. Blackburn and B.T. Phung School of Electrical Engineering and Telecommunications The University New South Wales, Australia Abstract- The insulation

More information

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales

More information

PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES

PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES Engr. IÑIGO V. ESCOPETE, JR. ITC Level 2 Certified Thermographer PHIL-NCB NDT-UT Level 2 Partial Discharge testing is a Condition Based Maintenance tool

More information

Partial Discharge Patterns in High Voltage Insulation

Partial Discharge Patterns in High Voltage Insulation 22 IEEE International Conference on Power and Energy (PECon), 2-5 December 22, Kota Kinabalu Sabah, Malaysia Partial Discharge Patterns in High Voltage Insulation Hazlee Illias, Teo Soon Yuan, Ab Halim

More information

Estimating the Impact of VLF Frequency on Effectiveness of VLF Withstand Diagnostics

Estimating the Impact of VLF Frequency on Effectiveness of VLF Withstand Diagnostics Estimating the Impact of VLF on Effectiveness of VLF Withstand Diagnostics Nigel Hampton (1), Jean Carlos Hernandez-Mejia (2), Marina Kuntsevich (3), Joshua Perkel (1), Vivek Tomer (3) 1 - NEETRAC, Atlanta,

More information

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES HEIN PUTTER Productmanager cable testing and -diagnosis Megger Site Germany 1 13 th Insucon conference 16-18 th Mai 2017, Birmingham, UK Agenda Introduction

More information

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets Abstract: For decades it has been recognized that partial discharge assessment is an excellent method

More information

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences

More information

Fundamentals of Partial Discharge in the Context of Field Cable Testing Key words: Partial discharge, power cable, electrical testing

Fundamentals of Partial Discharge in the Context of Field Cable Testing Key words: Partial discharge, power cable, electrical testing Fundamentals of Partial Discharge in the Context of Field Cable Testing Key words: Partial discharge, power cable, electrical testing Steven Boggs, University of Connecticut and University of Toronto John

More information

IRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.

IRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear. IRIS POWER PDTracII Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear. We have not found another test method that produces as much

More information

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015 Basics of Partial Discharge Prepared for 2015 Phenix RSM Meeting January 2015 Definitions and History Standard Definitions Fundamentally, what is a Partial Discharge An electric discharge which only partially

More information

IRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.

IRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear. IRIS POWER PDTracII Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear. We have not found another test method that produces as much

More information

Cable diagnostic in MV underground cable networks

Cable diagnostic in MV underground cable networks Cable diagnostic in MV underground cable networks Theoretical background and practical application VLF testing tan delta loss factor measurement Partial discharge localization and measurement Author: Tobias

More information

HV AC TESTING OF SUPER-LONG CABLES

HV AC TESTING OF SUPER-LONG CABLES HV AC TESTING OF SUPER-LONG CABLES Stefan SCHIERIG, (Germany), schierig@highvolt.de Peter COORS, (Germany), coors@highvolt.de Wolfgang HAUSCHILD, IEC, CIGRE, (Germany), hauschild@highvolt.de ABSTRACT The

More information

Field Experiences. Partial Discharge Diagnosis on MV Cables. Philipp Legler. XVI. Szigetelésdiagnosztikai Konferencia (

Field Experiences. Partial Discharge Diagnosis on MV Cables. Philipp Legler. XVI. Szigetelésdiagnosztikai Konferencia ( Field Experiences Partial Discharge Diagnosis on MV Cables Philipp Legler Technical Support Applications Engineer (Megger Site Germany) XVI. Szigetelésdiagnosztikai Konferencia (19. - 20.10.2016, Sümeg)

More information

GENERATOR TESTING APPLICATION GUIDE. reliable. precision.

GENERATOR TESTING APPLICATION GUIDE.  reliable. precision. GENERATOR TESTING APPLICATION GUIDE www.haefely-hipotronics.com reliable. precision. 2 GENERATOR TESTING CONTENTS Product Line Overview 3 AC Hipot Testing 4 Partial Discharge Measurement 5 DC Hipot Testing

More information

NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY

NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY Lorenzo PERETTO Luigi FODDAI Simone ORRU Luigi PUDDU Altea Switzerland ENEL Italy ENEL Italy REPL Italy lperetto@alteasolutions.com

More information

Comparison of measurement methods for partial discharge measurement in power cables

Comparison of measurement methods for partial discharge measurement in power cables Comparison of measurement methods for partial discharge measurement in power cables L. W. van Veen Supervisor: Prof. dr. J. J. Smit Daily supervisor: Dr.ir. A. Rodrigo Mor April 2014 INTELLIGENT ELECTRICAL

More information

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of

More information

Design and Construction of a150kv/300a/1µs Blumlein Pulser

Design and Construction of a150kv/300a/1µs Blumlein Pulser Design and Construction of a150kv/300a/1µs Blumlein Pulser J.O. ROSSI, M. UEDA and J.J. BARROSO Associated Plasma Laboratory National Institute for Space Research Av. dos Astronautas 1758, São José dos

More information

HVA SERIES VLF TEST SETS. Hipot Testers HVA Series for VLF (0.1 Hz) testing of MV and HV cables.

HVA SERIES VLF TEST SETS. Hipot Testers HVA Series for VLF (0.1 Hz) testing of MV and HV cables. HVA SERIES VLF TEST SETS Hipot Testers HVA Series for VLF (0.1 Hz) testing of MV and HV cables. INNOVATIVE, RELIABLE, ECONOMICAL HIGH VOLTAGE TESTING FROM b2 HIGH VOLTAGE VLF, DC, cable sheath testing

More information

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM,

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM, ONLINE OFFLINE VERSUS FEATURE PARTIAL DISCHARGE TESTING FOR CABLE ASSESSMENT B Y WIL L IAM H IG INBOT H AM, EA Technology, LLC Medium voltage cables have three distinct phases to their lifecycle: (1) new

More information

IEEE (2016) (2016). IEEE.,

IEEE (2016) (2016). IEEE., Corr, Edward and Siew, W. H. and Zhao, Weijia (16) Long term testing and analysis of dielectric samples under DC excitation. In: IEEE Electrical Insulation Conference (16). IEEE., This version is available

More information

GTRI/DOE Disclaimer. Cable Diagnostic Focused Initiative. Outline. CDFI Background. ICC Education Session. Nigel Hampton Rick Hartlein Joshua Perkel

GTRI/DOE Disclaimer. Cable Diagnostic Focused Initiative. Outline. CDFI Background. ICC Education Session. Nigel Hampton Rick Hartlein Joshua Perkel GTRI/DOE Disclaimer ICC Education Session Cable Diagnostic Focused Initiative Nigel Hampton Rick Hartlein Joshua Perkel Spring 9 Meeting The information contained herein is to our knowledge accurate and

More information

The Application of Partial Discharge Measurement and Location on CGIS

The Application of Partial Discharge Measurement and Location on CGIS International Journal on Electrical Engineering and Informatics Volume 4, Number 3, October 2012 The Application of Partial Discharge Measurement and Location on CGIS Min-Yen Chiu¹, Keng-Wei Liang¹, Chang-Hsing

More information

An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley

An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley ArborLec Solutions Inc. CIGRE WG 21:04 in 1994 Purpose of diagnostic test is: To evaluate and locate degradation phenomena

More information

RESONANT TRANSFORMER

RESONANT TRANSFORMER RESONANT TRANSFORMER Whenever the requirement of the test voltage is too much high, a single unit transformer can not produce such high voltage very economically, because for high voltage measurement,

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits

More information

IRIS POWER TGA-B. Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors

IRIS POWER TGA-B. Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors IRIS POWER TGA-B Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors We have not found another test method that produces as much decision support data for generator

More information

Dielectric Response Measurements Using DC Voltage

Dielectric Response Measurements Using DC Voltage Dielectric Response Measurements Using DC Voltage Jean-François DRAPEAU Researcher Expertise Équipement électriques IREQ ICC Spring 2011 - St Pete Education Session 2011-05-25 OUTLINE Introduction DC charging

More information

Surge Generator for MIL-STD 1275

Surge Generator for MIL-STD 1275 Surge Generator for MIL-STD 1275 This generator PG1275 is specially designed for the test of the susceptibility to surges and spikes of military 28 Vdc electric circuits. The equipment allows performing

More information

Kurzfassung. Abstract. 1 Introduction

Kurzfassung. Abstract. 1 Introduction Untersuchung von Teilentladungsverhalten mit Wechselspannung und gedämpfter Wechselspannung Investigation of partial discharge behaviour with alternating current and damped alternating current Manuel Wild,

More information

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY Avinash Raj 1, Chandan Kumar Chakrabarty 1, Rafidah Ismail 1 and Basri Abdul Ghani 2 1 College of Engineering, University Tenaga

More information

PD Diagnostic Applications and TechImp solutions

PD Diagnostic Applications and TechImp solutions PD Diagnostic Applications and TechImp solutions Condition Assessment Solutions for Electrical Systems. PD based innovative tools for the Condition Based Maintenance. MD-04.05.004 - rev. 00-29/08/2006

More information

EI HIGH VOLTAGE INSULATION TESTING POLICY

EI HIGH VOLTAGE INSULATION TESTING POLICY Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and

More information

FREQUENCY RESPONSE OF R, L AND C ELEMENTS

FREQUENCY RESPONSE OF R, L AND C ELEMENTS FREQUENCY RESPONSE OF R, L AND C ELEMENTS Marking scheme : Methods & diagrams : 3 Graph plotting : - Tables & analysis : 2 Questions & discussion : 3 Performance : 2 Aim: This experiment will investigate

More information

Error vs. Uncertainty Historical Perspective

Error vs. Uncertainty Historical Perspective 1 Error vs. Uncertainty Historical Perspective Jim McBride Chairman PSIM Committee Vice-Chairman HVTT Subcommittee IEEE PES SPDC Fall 2017 Clearwater, FL Discussions on Uncertainty PSIM - HVTT Subcommittee

More information

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems Romeo C. Ciobanu, Cristina Schreiner, Ramona Burlacu, Cristina Bratescu Technical

More information

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES Frank WESTER, Edward GULSKI, Johan SMIT, Edwin GROOT*, Mark VAN VLIET* Delft University of Technology The Netherlands * NUON The Netherlands

More information

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage Journal of Energy and Power Engineering 9 () 3-3 doi:.7/93-897/.3. D DAVID PUBLISHIG Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

More information

Off-Line Field Diagnostics for MV and HV Oil-Paper Insulated Cables

Off-Line Field Diagnostics for MV and HV Oil-Paper Insulated Cables 163 24 th Nordic Insulation Symposium on Materials, Components and Diagnostics Off-Line Field Diagnostics for MV and HV Oil-Paper Insulated Cables Sarajit Banerjee, Ali Naderian Kinectrics Inc., Toronto,

More information

CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER

CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER Henrik ENOKSEN Espen EBERG Sverre HVIDSTEN SINTEF Energy Research - Norway SINTEF Energy Research - Norway SINTEF Energy Research

More information

Partial Discharge Trends in Medium Voltage Cables measured while in-service with PDOL

Partial Discharge Trends in Medium Voltage Cables measured while in-service with PDOL 1 Partial Discharge Trends in Medium Voltage Cables measured while in-service with PDOL André N. Cuppen, E. Fred Steennis, and Peter C. J. M. van der Wielen, Member, IEEE Abstract-- This paper presents

More information

Measurement Of Partial Discharge (PD) In High Voltage Power Equipment

Measurement Of Partial Discharge (PD) In High Voltage Power Equipment First International Conference on Emerging Trends in Engineering, Management and Scineces December 28-3, 214 (ICETEMS-214)Peshawar,Pakistan Measurement Of Partial Discharge (PD) In High Voltage Power Equipment

More information

Coherence and time-frequency analysis of impulse voltage and current measurements

Coherence and time-frequency analysis of impulse voltage and current measurements Coherence and time-frequency analysis of impulse voltage and current measurements Jelena Dikun Electrical Engineering Department, Klaipeda University, Klaipeda, Lithuania Emel Onal Electrical Engineering

More information

Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen

Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen Aspects of PD interpretation in HV power cables by Edward Gulski, Piotr Cichecki, Rogier Jongen General There are several aspects having influence on the diagnostic information and the condition judgment

More information

Return to Session BREAKDOWN CAUSED BY ABRUPT DC-VOLTAGE GROUNDING OF XLPE CABLE INSULATION ABSTRACT KEYWORDS INTRODUCTION

Return to Session BREAKDOWN CAUSED BY ABRUPT DC-VOLTAGE GROUNDING OF XLPE CABLE INSULATION ABSTRACT KEYWORDS INTRODUCTION BREAKDOWN CAUSED BY ABRUPT DC-VOLTAGE GROUNDING OF XLPE CABLE INSULATION Erling ILDSTAD, NTNU, (Norway), Erling.Ildstad@elkraft.ntnu.no Mildrid SELSJORD, SINTEF Energy Research, (Norway), Mildrid.Selsjord@sintef.no

More information

Partial Discharge Classification Using Acoustic Signals and Artificial Neural Networks

Partial Discharge Classification Using Acoustic Signals and Artificial Neural Networks Proc. 2018 Electrostatics Joint Conference 1 Partial Discharge Classification Using Acoustic Signals and Artificial Neural Networks Satish Kumar Polisetty, Shesha Jayaram and Ayman El-Hag Department of

More information

Reprint E Two Years of Experience with a Mobile Resonant Test System for Testing of Installed Medium- and High Voltage Power Cables

Reprint E Two Years of Experience with a Mobile Resonant Test System for Testing of Installed Medium- and High Voltage Power Cables Two Years of Experience with a Mobile Resonant System for ing of Installed Medium- and High Voltage Power Cables P. Schikarski M. Gamlin J. Rickmann P. Peeters P. v.d. Nieuwendijk R. Koning Reprint ISH

More information

University of Pittsburgh

University of Pittsburgh University of Pittsburgh Experiment #5 Lab Report Diode Applications and PSPICE Introduction Submission Date: 10/10/2017 Instructors: Dr. Minhee Yun John Erickson Yanhao Du Submitted By: Nick Haver & Alex

More information

Partial Discharge Theory, Modeling and Applications To Electrical Machines

Partial Discharge Theory, Modeling and Applications To Electrical Machines Partial Discharge Theory, Modeling and Applications To Electrical Machines V. Vahidinasab, A. Mosallanejad, A. Gholami Department of Electrical Engineering Iran University of Science and Technology (IUST)

More information

INFLUENCE OF VOLTAGE WAVEFORMS ON PARTIAL DISCHARGES DEVELOPED IN POWER CABLE INSULATION

INFLUENCE OF VOLTAGE WAVEFORMS ON PARTIAL DISCHARGES DEVELOPED IN POWER CABLE INSULATION INFLUENCE OF VOLTAGE WAVEFORMS ON PARTIAL DISCHARGES DEVELOPED IN POWER CABLE INSULATION LARISA MĂRIUŢ, ELENA HELEREA *1 Key words: Partial discharge, Inception voltage, Step-up voltage test method, Sinusoidal

More information

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location HAEFELY HIPOTRONICS Technical Document Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location P. Treyer, P. Mraz, U. Hammer Haefely Hipotronics, Tettex Instruments

More information

SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE

SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE Fred STEENNIS Paul WAGENAARS Denny HARMSEN DNV GL the Netherlands DNV GL the

More information

Exercise 9: inductor-resistor-capacitor (LRC) circuits

Exercise 9: inductor-resistor-capacitor (LRC) circuits Exercise 9: inductor-resistor-capacitor (LRC) circuits Purpose: to study the relationship of the phase and resonance on capacitor and inductor reactance in a circuit driven by an AC signal. Introduction

More information

PD Solutions. On-Line PD Measurement Devices

PD Solutions. On-Line PD Measurement Devices On-Line PD Measurement Devices 1. Longshot Device (see Figure 1) The measurement system applied is based around the wideband (0-400 MHz) HVPD- Longshot partial discharge test unit which utilizes a high-speed

More information

Non-intrusive Measurement of Partial Discharge and its Extraction Using Short Time Fourier Transform

Non-intrusive Measurement of Partial Discharge and its Extraction Using Short Time Fourier Transform > REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 1 Non-intrusive Measurement of Partial Discharge and its Extraction Using Short Time Fourier Transform Guomin Luo

More information

A COMPARISON OF AC AND DC PARTIAL DISCHARGE ACTIVITY IN POLYMERIC CABLE INSULATION *

A COMPARISON OF AC AND DC PARTIAL DISCHARGE ACTIVITY IN POLYMERIC CABLE INSULATION * Morris, E.A. and Siew, W.H. (2018) A comparison of AC and DC partial discharge activity in polymeric cable insulation. In: 2017 IEEE 21st International Conference on Pulsed Power (PPC). IEEE, Piscataway,

More information

Cable testing and diagnostics

Cable testing and diagnostics Cable testing and diagnostics To ensure the flow Cost-optimised maintenance through cable diagnostics The sheath and cable testing supports you in assessing whether a cable system is safe and ready to

More information

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 75 CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 5.1 INTRODUCTION Partial Discharge (PD) detection is an important tool for monitoring insulation conditions in high voltage (HV) devices in power systems.

More information

Insulation Test System

Insulation Test System Component Tests Insulation Test System Brief Overview of Phenomena............... 2 Applicable Standards................... 3 Test System Overview.................. 3 Generator Specifications.................

More information

Although shunt capacitors

Although shunt capacitors INSIDE PQ The Trouble With Capacitors Part 1 Switching capacitors seems like a simple proposition, but it can lead to some very interesting problems By R. Fehr, P.E., Engineering Consultant Although shunt

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) 1 MIG Tester Type MIG2000-6 Technical Specification E-MIG2000-6 revised: 07. May 2009 1 MIG Tester Type MIG2000-6 1

More information

Progress Report on Failures of High Voltage Bushings with Draw Leads By Jim McBride and Larry Coffeen, JMX Services / NEETRAC 7/26/2010

Progress Report on Failures of High Voltage Bushings with Draw Leads By Jim McBride and Larry Coffeen, JMX Services / NEETRAC 7/26/2010 The Team: Jim McBride: IEEE Member Larry Coffeen: IEEE Senior Member President, JMX Services, Inc. Senior Research Engineer, NEETRAC BS EE Georgia Tech BS EE Georgia Tech Testing, DAQ, and Measurement

More information

VLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing

VLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing Cable Testing & Diagnostics Solutions for Medium Voltage Networks (1 kv - 36 kv) VLF Partial Discharge DC DAC tandelta Cable Testing Cable Diagnostics? There are two main applications for cable testing:

More information

High Accuracy Eddy Current Type Displacement Sensor GP-A SERIES. Resolution 0.04 % F.S., Linearity ±0.5 % F.S., IP67G environment resistance

High Accuracy Eddy Current Type Displacement Sensor GP-A SERIES. Resolution 0.04 % F.S., Linearity ±0.5 % F.S., IP67G environment resistance 1 High Accuracy Eddy Current Type Sensor SERIES Related Information General terms and conditions... F-3 Glossary of terms... P.1 guide... P.11~ General precautions... P.19 PHOTO PHOTO MEASURE panasonic.net/id/pidsx/global

More information

CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES

CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES Hao ZHANG, Transgrid, (Australia), hao.zhang@transgrid.com.au Zhao LIU, University of NSW, (Australia), z.liu@unsw.edu.au Toan

More information

Suppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and Waveform Characteristics

Suppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and Waveform Characteristics Journal of Energy and Power Engineering 9 (215) 289-295 doi: 1.17265/1934-8975/215.3.8 D DAVID PUBLISHING Suppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and

More information

IDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy

IDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy IDAX 300 Insulation Diagnostic Analyzer Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy 1 Frequency Domain Spectroscopy Hi V A Lo Ground C HL Measure at several frequencies Use

More information

PHG 70 TD PD / PHG 80 TD PD

PHG 70 TD PD / PHG 80 TD PD PHG 70 TD PD / PHG 80 TD PD BAUR VLF test and diagnostics system Functions Universal test and diagnostics system flexible, modular, extendable Cutting-edge testing and diagnostics technology: VLF truesinus

More information

portable affordable CDS Series Cable Fault Locators Thumpers - Surge Generators

portable affordable CDS Series Cable Fault Locators Thumpers - Surge Generators portable CDS Series Cable Fault Locators Thumpers - Surge Generators HVI offers the most complete fault locator packages available for primary cable. HVI offers the only VLF Thumper combination ideal for

More information

Chapter 31 Alternating Current

Chapter 31 Alternating Current Chapter 31 Alternating Current In this chapter we will learn how resistors, inductors, and capacitors behave in circuits with sinusoidally vary voltages and currents. We will define the relationship between

More information

High Accuracy Eddy Current Type Displacement Sensor GP-A SERIES. Resolution 0.04 % F.S., Linearity ±0.5 % F.S., IP67g environment resistance

High Accuracy Eddy Current Type Displacement Sensor GP-A SERIES. Resolution 0.04 % F.S., Linearity ±0.5 % F.S., IP67g environment resistance 13 High Accuracy Eddy Current Type Sensor SERIES Related Information General terms and conditions... F- Glossary of terms... P.139 Sensor selection guide... P.9~ General precautions... P.1 PHOTO PHOTO

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

NETWORK INNOVATION COMPETITION ANGLE-DC PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT

NETWORK INNOVATION COMPETITION ANGLE-DC PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT NETWORK INNOVATION COMPETITION PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT NOVEMBER 17 Version: 1.0 Authored by: Andrew Moon Engineering Consultant and Project Manager Kevin Smith Lead

More information