GTRI/DOE Disclaimer. Cable Diagnostic Focused Initiative. Outline. CDFI Background. ICC Education Session. Nigel Hampton Rick Hartlein Joshua Perkel

Size: px
Start display at page:

Download "GTRI/DOE Disclaimer. Cable Diagnostic Focused Initiative. Outline. CDFI Background. ICC Education Session. Nigel Hampton Rick Hartlein Joshua Perkel"

Transcription

1 GTRI/DOE Disclaimer ICC Education Session Cable Diagnostic Focused Initiative Nigel Hampton Rick Hartlein Joshua Perkel Spring 9 Meeting The information contained herein is to our knowledge accurate and reliable at the date of publication. Neither GTRC nor The Georgia Institute of Technology nor NEETRAC will be responsible for any injury to or death of persons or damage to or destruction of property or for any other loss, damage or injury of any kind whatsoever resulting from the use of the project results and/or data. GTRC, GIT and NEETRAC disclaim any and all warranties both express and implied with respect to analysis or research or results contained in this report. It is the user's responsibility to conduct the necessary assessments in order to satisfy themselves as to the suitability of the products or recommendations for the user's particular purpose. No statement herein shall be construed as an endorsement of any product or process or provider Any opinions, findings and conclusions or recommendations expressed in this material are those of the author(s) and do not necessarily reflect the views of the Department of Energy This material is based upon work supported by the Department of Energy under Award No DE-FC-4CH7 Outline CDFI Background/Overview Cable System Failure Process SAGE Concept Case Study: Roswell Diagnostic Accuracies Diagnostic Testing Technologies Accuracies Really Matter The Things We Know Now That We Did Not Know Before Selecting a Diagnostic Testing Technology Summary CDFI Background Rick Hartlein 4

2 Why do we need diagnostics? Composition of US MV system Underground cable system infrastructure is aging (and failing). Much of the system is older than its design life. Not enough money / manufacturing capacity to simply replace cable systems because they are old. Need diagnostic tools that can help us decide which cables/accessories to replace & which can be left in service. Cable Failures per Year Installed Capacity (%) Always remember that we are talking about the cable SYSTEM, not just cable. PILC HMWPE XLPE EPR TRXLPE UNKNOWN CDFI Background/Overview CDFI Background/Overview 6 Failure Split Overview Unknown.% Terminations.6% In the CDFI, NEETRAC worked with 7 utilities, manufacturers and diagnostic providers to achieve the objective of clarifying the concerns and defining the benefits of diagnostic testing. Splices 7.% Cable 6.% Phase has almost exclusively focused on aged medium voltage systems. This is the largest coherent study of cable system diagnostics anywhere. CDFI Background/Overview 7 CDFI Background/Overview 8

3 NEETRAC Members Non NEETRAC Members Diagnostic Providers CDFI Supporters Dept of Energy Participants American Electric Power HV Technologies Ameren Hydro Quebec Cablewise / Utilx CenterPoint Energy Con Edison Cooper Power Systems IMCORP NRECA PacifiCorp (added mid ) Pacific Gas & Electric (added Jan 6) Duke Power Company PEPCO Exelon (Commonwealth Edison & PECO) Oncor (TXU) First Energy Prysmian Florida Power & Light Public Service Electric & Gas Georgia Tech Tyco / Raychem GRESCO HDW Electronics Southern California Edison Southern Company HV Diagnostics Southwire CDFI Background/Overview 9 CDFI Background/Overview CDFI - Primary Activities CDFI Activities ) Technology Review ) Analysis of Existing (Historical) Data ) Collection and Analysis of Field (New) Data 4) Verification of VLF Test Levels ) Defect Characterization 6) Develop Knowledge Based System 7) Quantify Economic Benefits 8) Reports, Update Meetings and Tech Transfer Seminars Analyses are data / results driven Analysis Lab Studies CDFI Field Studies Dissemination CDFI Background/Overview CDFI Background/Overview

4 CDFI Activities CDFI Activities Analysis Lab Studies CDFI Field Studies Dissemination Lab Studies Value / Benefit VLF Withstand Georgia Power Handbook Accuracies Tan δ Duke Publications VLF Withstand Tan δ PD Utility Data PD Meetings IEEE Std Work Knowledge Based Systems Industry CDFI CDFI Background/Overview Test Time Test Voltage Forensics Time Stability Voltage Stability Non-Uniform Degradation Neutral Corrosion Calibration Phase Pattern Feature Extraction Classification CDFI Background/Overview 4 Georgia Power XLPE Jkt & UnJkt Conductor Miles CDFI Activities Field Studies Duke XLPE & Paper Jkt & UnJkt 9 Conductor Miles CDFI Activities Analysis 89, Conductor Miles Offline PD (.Hz) Offline PD (6Hz) Tan δ Monitored Withstand Offline PD (.Hz) Tan δ Monitored Withstand Value / Benefit Accuracies Utility Data IEEE Std Work Knowledge Based Systems Evans Macon Roswell Charlotte * Cincinnati Clemson Morresville CDFI Background/Overview Economic Model SAGE DC Withstand Offline PD Online PD Tan δ VLF Withstand 4 Omnibus 4. VLF Survey Expert System Application CDFI Background/Overview 6 4

5 CDFI Activities Utility Data CDFI Activities Utility Data Con Ed Com Ed PPL Alabama Power Keyspan FPL PEPCO PG&E ONCOR Ameren DC Withstand Online PD VLF Withstand Offline PD (6Hz) Online PD Tan Delta VLF Withstand Offline PD (.Hz) Tan Delta Online PD Offline PD (.Hz) Tan Delta Offline PD (6Hz) VLF Withstand Offline PD (6Hz) Offline PD (.Hz) Online PD VLF Withstand Offline PD (6Hz) Online PD Tan δ Offline PD (6Hz) Online PD Offline PD (6Hz) CDFI Background/Overview 7 CDFI Background/Overview 8 Data Type Diagnostic Technique DC Withstand Monitored Withstand PD Offline PD Online Tan δ VLF Withstand Dataset Sizes Laboratory [Conductor miles] Field [Conductor miles] 78, ,8 Benefits from Diagnostic Programs Decreasing failures associated with diagnostics and actions Log Cumulative Failures Program Initiated IRC. - Service Performance ALL 89, 8 9 Time [Days] CDFI Background/Overview 9 CDFI Background/Overview

6 At the Start For many utilities, the usefulness of diagnostic testing was unclear. The focus was on the technique, not the approach. The economic benefits were not well defined. There was almost no independently collated and analyzed data. There were no independent tools for evaluating diagnostic effectiveness. Where we are today (). Diagnostics work they tell you many useful things, but not everything.. Diagnostics do not work in all situations.. Diagnostics have great difficulty definitively determining the longevity of individual devices. 4. Utilities HAVE to act on ALL replacement/repair recommendations to get improved reliability.. The performance of a diagnostic program depends on Where you use the diagnostic When you use the diagnostic What diagnostic you use What you do afterwards CDFI Background/Overview CDFI Background/Overview Where we are today () Overview 6. Quantitative analysis is complex BUT is needed to clearly see benefits. 7. Diagnostic data require skilled interpretation to establish how to act. 8. No one diagnostic is likely to provide the detailed data required for accurate diagnoses. 9. Large quantities of field data are needed to establish the accuracy/limitations of different diagnostic technologies..important to have correct expectations diagnostics are useful but not perfect! In the CDFI, NEETRAC worked with 7 utilities, manufacturers and diagnostic providers to achieve the objective of clarifying the concerns and defining the benefits of diagnostic testing. CDFI Background/Overview We have come a long way wrt the project objective. Analysis driven by data / results Developed a good understanding that diagnostic testing can be useful, but the technologies are not perfect. Developed ways to define diagnostic technology accuracy and found ways to handle inaccuracies. Developed diagnostic technology selection and economic analysis tools. Understand that there is yet more to learn. CDFI Background/Overview 4 6

7 Failures by Equipment How things fail and what fails have a big impact on the selection of diagnostics Cable System Failure Process Rick Hartlein Disbursement of Failures (%) Cable - all (%) Splice - all (%) Terminations - all (%) Unknown - all (%) Cable System Failure Process 6 Major Cable Components Defect Types in Extruded Cables Conductor Conductor or Strand Shield Insulation Insulation Shield Metallic Shield/Neutral Jacket (Recommended) Cable System Failure Process 7. Cavity at shield(s). Cavities due to shrinkage. Insulation shield defect 4. Contaminant (poor adhesion). Protrusions at shield(s) 6,7 Splinter/Fiber 8. Contaminants in insulation or shields Cable System Failure Process 8 7

8 Conversion of Water to Electrical Trees Defect Types in Extruded Cable Accessories Electrical tree growing from water tree Acts as a stress enhancement or protrusion (non-conducting) Water tree increases local electric field Water tree also creates local mechanical stresses If electrical and mechanical stresses high enough electrical tree initiates Electrical tree completes the failure path rapid growth Cable System Failure Process 9 Cable System Failure Process Diagnostics used in Challenging Areas Summary Cable system aging is a complex phenomenon. Multiple factors cause systems to age. Increases in dielectric loss and partial discharge are key phenomenon. The aging process is nonlinear. Diagnostics must take these factors into consideration. Cable System Failure Process 8

9 Diagnostic Program Phases - SAGE SAGE Approach to Diagnostic Programs Nigel Hampton Selection Data compilation and analysis needed to identify circuits that are at-risk for failure (at-risk population). Action Determine what actions can be taken on circuits based on the results of diagnostic testing. Generation Conduct diagnostic testing of the at-risk population. Evaluation Monitor at-risk population after testing to observe/improve performance of diagnostic program. SAGE Concept 4 Failures [#] SAGE at Work Selection Action When to deploy diagnostics Increasing Failures Decreasing Failures Generation Evaluation Cable System Performance Commissioning Operational Stress Condition Assessment Time (Years) 4 SAGE Concept Time 6 9

10 Context is important Data Generation from Diagnostic Measurement Local Context Comparisons within one area Case Study Roswell, GA November 8 & January 9 Nigel Hampton Global Context Comparison with many tests Databases Standards TDR Tan Delta Monitored Withstand Offline PD SAGE Concept 7 8 Roswell Map SELECTION Case Study: Roswell 9 Case Study: Roswell 4

11 Roswell Background Info. 98 vintage XLPE feeder cable, kcmil, 6 mils wall, jacketed. Knowledge Based Selection System Failures have occurred over the years no data on source Recently experienced very high failure rates of splices on this section: 8 failures / miles / yr. Overall there have been - failures of these splices in last two years on a variety of GPC feeders. Splice replacement may be acceptable if there is a technical basis. Case Study: Roswell 4 Selecting a Diagnostic Technology 4 Summary for Diagnostic Selection Economic Details prior to testing Action Scenario DC Withstand VLF Mins VLF Mins Diagnostic Technique VLF 6 Mins HV DC Leakage Monitored Withstand Tan Delta PD Online PD Offline TDR & Historical Records ONLY Complete System Replacement $,, approx Complete Splice Replacement $6, Test time (determined by switching) - 4 Days Selection Costs $, Splice Replacement 7 Days Retest after remediation Day Replace Small Portion Replace Segment Replace Accessories Monitored Withstand, Offline PD and VLF ( mins) offer economic benefit over doing nothing. Have a shortlist of three techniques Case Study: Roswell 4 Case Study: Roswell 44

12 Scenario Assessment before Testing Offline PD If,ft is tested.% fails on test, no customer interrupted site /,ft (median) 4% discharges in cable Estimate fails on test discharge sites cable, accessories splices < failure in months from test Monitored Withstand If,ft is tested <4% fails on test, no customer interrupted 7% of loss tests indicate no further action Estimate < fails on test assessed for further consideration by loss. failure in months from test ACTION 4 Case Study: Roswell 46 Initial Corrective Action Options Replace splices only no detailed records assume splices. Complete system replacement. GENERATION Case Study: Roswell 47 Case Study: Roswell 48

13 Overhead and Cabinet Terminations Monitored Withstand Case Study: Roswell 49 Case Study: Roswell If this had been a Simple Withstand Monitored Withstand - Stability 8 Segments Tested Pass - Stable Loss Pass - Un Stable Loss No Failures On Test min test 8 Segments Tested 6 min test 4 6 Length Tested (miles) Sequence of Lengths Tested (miles) 8 Case Study: Roswell Case Study: Roswell

14 Test Results - Local Perspective Test Results Global Perspective Tip Up in Tan Delta {.Uo -.Uo} (e-) Numbers indicate Segment ID's Length Along Feeder (ft) Measurement Stability STABLE UNSTABLE 6 7 Tan Uo (e-)... Stability STABLE UNSTABLE Splice Error Range of instability in monitored withstand Termination Damage 6 Panel variable: Phase. Tip Up.Uo -. Uo (e-) Case Study: Roswell Case Study: Roswell 4 Targeted Offline PD Test Segment 6 Phase A - Targeted Offline PD TDR B - C - Open symbols represent the anomalous TDR reflections A - PD (Approx Positions) B - C - Distance from Cubicle (ft) 4 4 Case Study: Roswell Case Study: Roswell 6 4

15 PD Inception local perspective VLF Test Voltage (kv) A - B - PD in of 9 splices C PD in of 9 splices Probability of Splice Inception (%) Position of PD (ft) PD in of 7 splices Position from Cubicle (ft) Panel variable: Phase PD Inception (kv) EVALUATION Case Study: Roswell 7 Case Study: Roswell 8 Evaluation after Testing Offline PD,ft actually tested Estimate discharge sites 6 cable, 9 accessories 6 splices < failure in months from test Actual 7 discharge sites cable, 7 accessories splices failure 4 months from test Monitored Withstand,ft actually tested Estimate fails on test assessed for further consideration by loss. failure in months from test Actual fails on test 6 assessed for further consideration by stability, tip up & loss failure (cable) months from test After Testing Actions have been performed by GPC. Suspect splice investigated, actually broken neutral. Damaged termination replaced. Test excavations & Ground Penetrating Radar tests conducted, concluded that it was not practical to replace splices as planned System Re enforcements Planned. All tested circuits have been left in service and are being monitored by GPC. 9 Case Study: Roswell 6

16 Performance of Diagnostics Performance evaluation primarily focuses on diagnostic accuracy. Diagnostic Accuracies Nigel Hampton Diagnostic accuracies quantify the diagnostic s ability to correctly assess a circuit s condition. Accuracy must be assessed based on pilot type field test programs in which no actions are performed. Circuits must be tracked for a sufficient period of time. 6 6 Diagnostic Accuracies Objective of Diagnostic Tests The target population contains both Good and Bad components Good Will not fail within diagnostic time horizon Bad Will fail within diagnostic time horizon Bad Components Target Population Good Components Diagnostic Operation Applying the diagnostic will separate the population into: No Action Required group Action Required group But the diagnostic is imperfect... 6 Diagnostic Accuracies 64 Diagnostic Accuracies 6

17 Perspective Bad Means Failure Accuracies Diagnostics make measurements in the field and find Anomalies. Detecting the presence of an Anomaly is, in our view, not sufficient. The goal, in our view, is to detect an Anomaly which leads to reduced reliability (failure in service) or compromised performance (severed neutrals stray voltage). Diagnostic Accuracy No Action Accuracy Action Accuracy In accuracy estimates we have used failures in service and interpreted the diagnostics as Bad Means Failure Dataset 6 Diagnostic Accuracies 66 Diagnostic Accuracies All Accuracies Diagnostic Accuracy [%] Diagnostic Testing Technologies Nigel Hampton Action Accuracy No Action Accuracy Overall Accuracy Diagnostic Accuracies

18 Introduction A wide range of diagnostic techniques are commercially available. Tests are performed either offline (circuit de-energized)) or online (energized) and by service providers or utility crews. Utility Use of Diagnostics Different voltage sources may be used to perform the same measurement. DC 6 Hz. AC Very Low Frequency (VLF) AC Damped AC (DAC) Diagnostic Testing Technologies 69 Diagnostic Testing Technologies 7 Diagnostic Survey Survey of Use of Diagnostics A survey of CDFI participants in 6 was conducted to determine how diagnostics were employed. Survey was updated at the end of % 4.7% Survey results focused CDFI work on technologies currently used in the USA..6% No Testing Testing - one technique Testing - > one technique Diagnostic Testing Technologies 7 7 8

19 Survey of Use of Diagnostics Lengths Tested More than one technique used No testing One technique used. 7. PD Median 84 ft Tan D Median 48 ft. 4.% Testing.% Percent... VLF Withstand 7. Median ft Panel variable: Technique No Testing No Testing Occasional use Regularly used Some testing Diagnostic Testing Technologies 96.% 7.% 7... Cable Length - log (ft) Based on diagnostic data supplied to CDFI Diagnostic Testing Technologies 74 Context Diagnostic Context Data Generation from Diagnostic Measurement OK Not Proven either way NOT OK Local Context Comparisons within one area Global Context Comparison with many tests Databases Standards Extreme conditions are easy to decide what to do about. What to do about the ones in the middle? How to define the boundaries? SAGE Concept 7 Diagnostic Testing Technologies 76 9

20 Simple Dielectric Withstand Test Description Application of voltage above normal operating voltage for a prescribed duration. Attempts to drive weakest location(s) within cable segment to failure while segment is not in service. Field Application Offline test that may use: DC 6 Hz. AC VLF AC Damped AC Testing may be performed by a service provider or utility crew. Voltage INITIAL Withstand Test Process t = HOLD Voltages and Times for VLF covered in IEEE 4. t Test The goal is to have circuit out of service, test it such that imminent service failures are made to occur on the test and not in service Time Diagnostic Testing Technologies 77 Diagnostic Testing Technologies 78 VLF Test Voltages Test Voltage (kv) 6 4 Cosine-rectangular Sinusoidal Data Generation from Diagnostic Measurement Variable Peak Voltage (kv) Peak Voltage (kv) Peak Voltage (kv) RMS Voltage (kv) Use Acceptance Installation Maintenance Acceptance RMS Voltage (kv) Installation RMS Voltage (kv) Maintenance Cable Rating (kv) Diagnostic Testing Technologies 79 Diagnostic Testing Technologies 8

21 Test Sequences Withstand Test Outcomes 6 7 Simple VLF Withstand to IEEE4. Levels Time of failure in mins for failures > mins Local Context Comparisons within one area Cumulative Length Tested in One Year (Miles) 4 Diagnostic Testing Technologies 8 Diagnostic Testing Technologies 8 Separation with Simple VLF Outcomes Failures on Test [% of Tested] Area is clearly different from the others. Overall Area 4 Global Context Comparison with many tests Databases Standards 8 Diagnostic Testing Technologies 84

22 Withstand Testing Experience Test Performance for Different Utilities Survivors [% of Total LengthsTested] Time on Test [Minutes] 97 Conductor Miles > Conductor Miles. Conductor Miles IEEE Recommendation IEEE 4. Range 6 7 Failures on Test [% of ft Segments].. Utility A A D I ft Length Adj.... Time on Test [Minutes] 6.7%.% 4.4%.%. Diagnostic Testing Technologies 8 Diagnostic Testing Technologies 86 Service Failures [% of Total Tested]. Service Experience Test Conditions 6 Conductor Miles Time to Failure % [Days] U 47 U Days 67 Days 47 Days Time to Failure [Days since test] Time to Failure % [Days] Days % % Dielectric Loss (Tan δ) Test Description Measures total cable system loss (cable, elbows, splices & terminations). May be performed at one or more frequencies (dielectric spectroscopy). May be performed at multiple voltage levels. Monitoring may be conducted for long durations. Field Application Offline test that may use: 6 Hz. AC VLF AC Damped AC Testing may be performed by a service provider or utility crew. Diagnostic Testing Technologies 87 Diagnostic Testing Technologies 88

23 Dielectric losses - Tan δ: I V Dielectric Loss (Tan δ) The cable insulation system is represented by an equivalent circuit In its simplest form it consists of two parameters; a resistor and a capacitor [IEEE Std. 4] When voltage is applied to the cable, the total current will be the contributions of the capacitor current and the resistor current I R I I R C I tan( δ ) = DF = = I IC ωrc C δ Cable System Equivalent Cable system (cable, splices, and terminations) is reduced to simple circuit. Diagnostic Testing Technologies I R θ V 89 Cable System Failure Process 9 Tan δ Test Data Data Generation from Diagnostic Measurement Tan-delta [e-] Voltage [p.u.]....7 Tip Up Mean Time [min] Scatter (represented by Standard Deviation - IQR could be used) 4 Diagnostic Testing Technologies 9 Diagnostic Testing Technologies 9

24 Tan δ Data for EPR Cable Systems Highest Concern Local Context Comparisons within one area Tan Delta (e-) Lowest Concern Voltage (kv) 9 Diagnostic Testing Technologies 9 Diagnostic Testing Technologies 94 Segments within a Feeder Lengths within a Locality Tip Up in Tan Delta {.Uo -.Uo} (e-) Stable STABLE UNSTABLE Phase = 6 7 Tan Delta (e-) Length Along Feeder (ft) 4 6 Length (ft)

25 Testing at Reduced Voltages. Regression 9% C I 9% PI.. 4 Global Context Comparison with many tests Databases Standards Uo [E-].... CI: Confidence Interval PI: Prediction Interval.. Uo [E-]...7. Diagnostic Testing Technologies 97 Cool Wall 98 Tan Delta - 6 Tan δ Interpretation Based on 8 Conductor Miles Action Required Further Study No Action Time Domain Reflectometry (TDR) Test Description Measures changes in the cable impedance as a function of circuit length by observing the pattern of wave reflections. Used to identify locations of accessories, faults, etc. Field Application Offline test that uses a low voltage, high frequency pulse generator. Testing may be performed by a service provider or utility crew. - - Tip Up - Diagnostic Testing Technologies 99 Diagnostic Testing Technologies

26 TDR Principles Online Partial Discharge Near End TDR Equipment L Joint Far End Test Description Measurement and interpretation of discharge and signals on cable segments and/or accessories. Signals captured over minutes / hours. Monitoring may be conducted for long durations. Joint Field Application Online test that does not require external voltage supply. Testing typically only be performed by a service provider. Assessment criteria are unique to each embodiment of the technology Diagnostic Testing Technologies Discharge Occurrence Data Generation from Diagnostic Measurement No PD PD Diagnostic Testing Technologies 4 Diagnostic Testing Technologies 6

27 Distribution of PD along Lengths ft. portion of sample feeder Mixture of different PD levels for different sections and accessories. Local Context Comparisons within one area Cable Section Accessory No PD PD Diagnostic Testing Technologies Diagnostic Testing Technologies 6 Diagnostic Results (Overall) Accessory 6 Conductor Miles Cable 4.8% 4.9%.%.% 4.4% 4.8%.%.4% Global Context Comparison with many tests Databases Standards 66.6% 68.% Diagnostic Testing Technologies 7 Diagnostic Testing Technologies 8 7

28 Offline Partial Discharge Test Description Measurement and interpretation of partial discharge signals above normal operating voltages. Signal reflections (combined with TDR information) allows location to be identified within cable segment. Field Application Offline test that may use: 6 Hz. AC service provider VLF AC utility crew Damped AC utility crew Diagnostic Testing Technologies 9 Amplitude [mv] Near End Detection Equipment P P P PD PD Activity Time P-P Time P-P P P P Time [μs] Far End Diagnostic Testing Technologies PD Pulse Data Generation from Diagnostic Measurement 4 mv 8 pc Diagnostic Testing Technologies Diagnostic Testing Technologies 8

29 PD Phase Resolved Pattern PD Magnitude.E- 4.E- 6 -.E- -6 Amplitude [pc] PD Level (pc) Max Limit for 97's production Individual Measurement from the field -.E- 8 Phese [Deg] - 6. Max allowed for current production.7.. PD Measurement Voltage (Uo) 4 PD Charge Magnitude Distributions XLPE Local Context Comparisons within one area Percent 4 Apparent Charge Magnitude [pc] 6 Diagnostic Testing Technologies Diagnostic Testing Technologies 6 9

30 PD Inception Voltage 8 6 XLPE 4 Percent Apparent Inception Voltage [U].4 Global Context Comparison with many tests Databases Standards 7 Diagnostic Testing Technologies 8 Location of PD Offline PD Test Sequence 6.6% of PD sites detected in accessories Conductor Miles Testing sequence for 6, ft. T ermination 6.% Cable 9.4% Splice 4.% No PD PD Diagnostic Testing Technologies 9

31 PD Location PD Sites per Length 8 6 Terminations Median =.96 PD Sites/ ft Approx. PD Site/ ft Percent Cable & Splices PD Sites per feet Location [% of Circuit Length] 7 9 Diagnostic Testing Technologies Isothermal Relaxation Current Recovery Voltage Test Description Measures the time constant of trapped charges within the insulation material as they are discharged. Discharge current is observed for - minutes. Field Application Offline test that uses DC to charge the cable segment up to kv. Testing is performed by a service provider. Test Description Similar to IRC only voltage is monitored instead of current Field Application Offline test that requires initial charging by DC source up to kv. Testing is performed by a service provider. Diagnostic Testing Technologies 4 Diagnostic Testing Technologies

32 Survey of Use of Diagnostics Combined Diagnostics 7.8% 4.7% Multiple degradation mechanisms mean that two diagnostics are often better than one.6% No Testing Testing - one technique Testing - > one technique Diagnostic Testing Technologies 6 Multiple Diagnostics.% Category Tan Delta / PD VLF / Tan Delta Data Generation from Diagnostic Measurement 7.% Diagnostic Testing Technologies 7 8 Diagnostic Testing Technologies

33 Monitored Withstand - Data Monitored Withstand Data - Elbow Tan-delta [e-].8 Optional Ramp Up gives Tan-delta.7 vs. Voltage Stability of Tan-delta monitored through the minute withstand Time [min] Voltage [p.u.]...7 Tan-delta [e-] Voltage [p.u.]....7 Elbow Failure Hampton Leas Segment HL Tan-delta vs Voltage Before Failure 4 Time [min] After Failure Failure Tan-delta Stability 6 7 Diagnostic Testing Technologies 9 Cool Wall Monitored Withstand Global Context Comparison with many tests Databases Standards Withstand Test Outcomes UNSTABLE High TU Poor Stability High Loss Monitored VLF Withstand to IEEE4. Levels Time of failure in mins Cumulative Length Tested in One Year (Miles) 7 Simple VLF Withstand to IEEE4. Levels 9 Diagnostic Testing Technologies Teste

34 Cost [$] Diagnostic Program Costs Accuracies Revisited Why do they matter? Josh Perkel Corrective Actions Consequence Total Diagnostic Program Cost Diagnostic Selection Accuracies Really Matter 4 Recall the Example... Incorrect Diagnosis No Action Required Action Required No Action Required Action Required Avoided Corrective Actions Avoided service failures Future service failures Unneeded Corrective Actions Accuracies Really Matter 6 Accuracies Really Matter 4

35 Cost [$] Benefit and Loss Considerations Diagnostic program economic calculations are based on ability to predict future failures. BENEFIT Consequence Corrective Actions Diagnostic Alternate Program LOSS Alternate Program Total diagnostic program cost is more sensitive to certain elements than others. Failure Rate Diagnostic Accuracy Failure Consequence Selection Accuracies Really Matter 7 Accuracies Really Matter 8 Diagnostic Accuracy Complications Time is a critical factor in the assessment of accuracy. Failures do not happen immediately after testing. Two approaches to computing diagnostic accuracy. Bad Means Failure Approach Probabilistic Approach Accuracy Over Time Bad Means Failure Accuracy [%] No Action Required Accuracy Action Required Accuracy? System Changes Additional Aging Increased Load Time [Years] Accuracies Really Matter 9 4 Accuracies Really Matter

36 Probabilistic Approach Tan δ Probabilistic Approach - PD Failures in Service [% of Tested Segments]. Action_ Action_ Act Act No Action No Action 7.4%.9% Percent PD Class No PD PD FOT Elasped Time at Oct 8 (Month). Days Between Test & Failure Accuracies Really Matter 4 Accuracies Really Matter 4 By Diagnostic Technique VLF DC Tan Delta The Things We Know Now That We Did Not Know Before PD On PD Off TDR IRC DAC Category No Use Occasional Standard Testing 4 44 Diagnostic Testing Technologies 6

37 Dielectric Withstand CDFI Dielectric Withstand Josh Perkel Withstand techniques are most widely used diagnostic in the USA. Most utilities use VLF (either sine or cosine-rectangular) in their withstand programs. Test duration and voltage are critical to performance on test and in service. Explored the concept of Monitored Withstand tests. CDFI Research 4 CDFI Research 46 Length Distribution (Overall) Median Length = ft Length Effects Comparison of withstand failure on test rates must include length adjustments. ft. Percent Failure Wide variability in circuit lengths ft. ft. ft. ft Circuit Length [Conductor ft] 7 84 Censored CDFI Research 47 CDFI Research 48 7

38 Utility I Hybrid System Effect of Test Voltage Failures on Test [%] Length Adjustment Feet Feet NONE Performance at longer test times can be predicted. Length Weighted Average FOT Mins.7% 6 Mins.%... Time on Test [Minutes]. 7.% 4.%.4% Survivors [% of Tested] IEEE Rec. Level PILC Extruded Mixed (PILC and Extruded) NEETRAC Extruded... Test Voltage (U = Rated Voltage) CDFI Research 49 CDFI Research. VLF Lab Program Josh Perkel Overview Test program combining aging at U with multiple applications of high voltage VLF. Uses field aged cable samples - one area within one utility. Evaluate the effects of Voltage and time on the performance on test and Subsequent reliability during service voltages. Primary Metric Survival during aging and testing Secondary Metrics Before and after each VLF application, PD at U Between Phase A & B IRC, PD (AC.U, DAC), Tan δ CDFI Research CDFI Research 8

39 : No Withstand : VLF.U Min Withstand Testing Periods (variable durations) : No Withstand : VLF.U Min No aging failures for any condition No Fails 4 Survive No Fails 4 Survive : VLF.6U Min 4: VLF.U 6 Min Aging Periods Phase A End : VLF.6U Min 4: VLF.U 6 Min VLF Fails Survive VLF Fails Survive : VLF.U Min 6: 6 Hz..6U. Min Failures are the primary metric for evaluation : VLF.U Min 6: 6 Hz..6U. Min No Fails 4 Survive 6 Hz. Fails Survive CDFI Research T T T T4CDFI Research 4 Time of Failure on Test Voltage of Failure on Test Percent of ft Samples Failing 99 Scale Failure Censor 8 Correlation Shape.468 No Failures Before mins After 6 mins 6 Mins Max Time 6 Percent 99 Shape Scale F ailure Censor 8 Correlation More failures occur at higher test voltages Time on VFL Test (min) Testing Voltage (Uo) CDFI Research CDFI Research 6 9

40 Failure Analyses - Trees & Defects in Cables Failed Samples D C B A DEFECT LARGE WATER TREE MEDIUM WATER TREE SMALL WATER TREE VLF Test Program Summary Analysis of Phase A is complete. Phase B (U aging, 4 C Cosine Rectangular) underway. Phases A & B show that no VLF exposed samples have failed under 6 Hz Uo & Uo. Phase B tests showed two samples without VLF exposure failed during 6 Hz Uo. All failures occurred at the appropriate time. i.e. within the VLF testing periods. Distance Along Cable (ft) 8% (4 out of ) of VLF failures between and 6 mins CDFI Research 7 CDFI Research 8 KBS Selecting the right diagnostic is not easy. Selecting a Diagnostic Technology Knowledge-Based System Nigel Hampton No one diagnostic covers everything. How you measure is influenced by what you do with the results. The KBS captures the experience and knowledge of people who have been operating in the field Selecting a Diagnostic Technology 9 6 Selecting a Diagnostic Technology 4

41 Knowledge Based Systems Extruded Cable Diagnostics Knowledge-Based Systems are computer systems that are programmed to imitate human problem-solving. Uses a combination of artificial intelligence and reference to a database of knowledge on a particular subject. KBS are generally classified into: Expert Systems Case Based Reasoning Fuzzy Logic Based Systems Neural Networks Selecting a Diagnostic Technology 6 Selecting a Diagnostic Technology 6 KBS Example Short Listing of Diagnostic Approaches Experts Recommending a Diagnostic Technique (%) RECOMMENDED BY MOST EXPERTS RECOMMENDED BY FEWEST EXPERTS Discharge Monitored Withstand Simple Withstand Dielectric Discharge Historical Data Simple Withstand Monitored Withstand Simple Withstand Selecting a Diagnostic Technology 6 64 Selecting a Diagnostic Technology 4

42 Impact of Remedial Action Hybrid Cable System Most service failures occur in Accessories Usual remediation is by replacement of cable sections System Component Portion [%] Service Failure Rate Age [yrs] PE Medium - EPR 4 Low - Paper High 4 - Selecting a Diagnostic Technology 6 Hybrid Cable System Most Recommended Selecting a Diagnostic Technology 4 Expert Recommendation (%) Dielectric Discharge History & TDR Monitored W ithstand Simple Withstand Replace Replace Accessories Accessories Dielectric Discharge History & TDR Monitored W ithstand Simple Withstand Replace Replace Segment Segment Dielectric Discharge History History & & TDR TDR Monitored Monitored Withstand Withstand Simple Simple Withstand Withstand Replace Replace Small Small Section Section Summary Rick Hartlein 67 What we have learned about diagnostics (). A developing database of field failure diagnostic data shows that different diagnostic techniques can provide some indication about cable system condition.. Even if the diagnostics themselves are imprecise, diagnostic programs can be beneficial.. Benefits can be quantified, however this is not simple and requires effort. 4. Many different data analysis techniques, including some non conventional approaches, are needed to assess diagnostic effectiveness.. Utilities HAVE to act on ALL replacement/repair recommendations to get improved reliability. 68 Summary

43 What we have learned about diagnostics () 6. PD, VLF, DC and Tan δ & VLF withstand tests detect problems in the field and can be used to improve system reliability. 7. It is very difficult to predict whether or not the problems/defects detected by PD and Tan δ will lead to failure in the short/medium term. What we have learned about diagnostics ().Interpretation of PD measurements is more complex than interpretation of Tan δ measurements..irc & RV are particularly difficult to deploy in the field. 8. PD assessments are good at establishing groups of cable system segments that are not likely to fail. 9. Tan δ measurements provide a number of interesting features for assessing the condition of cable systems..tan δ & PD measurements require interpretation to establish how to act. Summary 69 Summary 7 Reflections Approach to data analysis established in CDFI Many questions answered, there still remain gaps in our understanding of: Benefits Distinguishing anomalies from weaknesses Answers will come with continued analysis of field test data (diagnostic tests followed by circuit performance monitoring) as well as controlled laboratory tests. The potential value of continued analysis is high. 7 Summary 4

GTRI/DOE Disclaimer. Cable Diagnostic Focused Initiative Regional Meeting NEETRAC. CDFI Contributors. Presenters

GTRI/DOE Disclaimer. Cable Diagnostic Focused Initiative Regional Meeting NEETRAC. CDFI Contributors. Presenters GTRI/DOE Disclaimer Cable Diagnostic Focused Initiative Regional Meeting NEETRAC Hosted by Pacific Gas and Electric San Ramon, CA August 9-, 9 The information contained herein is to our knowledge accurate

More information

Cable Diagnostic Focused Initiative Regional Meeting NEETRAC

Cable Diagnostic Focused Initiative Regional Meeting NEETRAC Cable Diagnostic Focused Initiative Regional Meeting NEETRAC Hosted by Pacific Gas and Electric San Ramon, CA August 19-20, 2009 1 1 GTRI/DOE Disclaimer The information contained herein is to our knowledge

More information

Jean Carlos Hernández Mejía International Conference of Doble Clients Boston, MA, USA March 25 - March 30, GTRI/DoE Disclaimer

Jean Carlos Hernández Mejía International Conference of Doble Clients Boston, MA, USA March 25 - March 30, GTRI/DoE Disclaimer Overview of the Cable Diagnostic Focused Initiative Project NEETRAC National Electric Energy Testing Research and Applications Center Jean Carlos Hernández Mejía 2012 International Conference of Doble

More information

Cable Diagnostic Focused Initiative Regional Meeting NEETRAC

Cable Diagnostic Focused Initiative Regional Meeting NEETRAC Cable Diagnostic Focused Initiative Regional Meeting NEETRAC Hosted by Consolidated Edison Company of New York New York, NY October 28-29, 2009 1 1 GTRI/DOE Disclaimer The information contained herein

More information

(other than Historical PD Tests) )

(other than Historical PD Tests) ) Diagnostic Testing Techniques for Distribution and Transmission Cables (other than Historical PD Tests) ) Experience with available techniques ICC Education Session - May 2011 Nigel Hampton, Josh Perkel

More information

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May 26 2011 St Pete Beach, Fl HDW ELECTRONICS, INC. THE BEST IN CABLE FAULT LOCATING TECHNOLOGY by Henning Oetjen Frank

More information

Estimating the Impact of VLF Frequency on Effectiveness of VLF Withstand Diagnostics

Estimating the Impact of VLF Frequency on Effectiveness of VLF Withstand Diagnostics Estimating the Impact of VLF on Effectiveness of VLF Withstand Diagnostics Nigel Hampton (1), Jean Carlos Hernandez-Mejia (2), Marina Kuntsevich (3), Joshua Perkel (1), Vivek Tomer (3) 1 - NEETRAC, Atlanta,

More information

Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics

Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics Dominique Bolliger, Ph.D. HV TECHNOLOGIES, Inc. Manassas, VA, USA d.bolliger@hvtechnologies.com Abstract In

More information

CHAPTER 4. How to Start

CHAPTER 4. How to Start CHAPTER 4 How to Start Nigel Hampton This chapter represents the state of the art at the time of release. Readers are encouraged to consult the link below for the version of this chapter with the most

More information

Assuring the Reliability of Critical Power Cable Systems

Assuring the Reliability of Critical Power Cable Systems Assuring the Reliability of Critical Power Cable Systems Presented by: Benjamin Lanz Manager of Application Engineering IMCORP Power Cable Reliability Consulting & Diagnostics Some of the technologies

More information

An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley

An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley ArborLec Solutions Inc. CIGRE WG 21:04 in 1994 Purpose of diagnostic test is: To evaluate and locate degradation phenomena

More information

CHAPTER 14. Glossary

CHAPTER 14. Glossary CHAPTER 14 Glossary Nigel Hampton and Jean Carlos Hernandez-Mejia This chapter represents the state of the art at the time of release. Readers are encouraged to consult the link below for the version of

More information

PD Testing Considerations for MV Plant Cables

PD Testing Considerations for MV Plant Cables PD Testing Considerations for MV Plant Cables Cable Testing Philosophy Damage Mistake Aging Repair Manufacturing Transportation Installation Operation Power frequency 50/60 Hz Power frequency 50/60 Hz

More information

USING DAMPED AC VOLTAGES

USING DAMPED AC VOLTAGES MODERN & TESTING DIAGNOSIS OF POWER CABLES USING DAMPED AC VOLTAGES BY EDWARD GULSKI AND ROGIER JONGEN, Onsite HV Solutions ag, Switzerland AND RALPH PATTERSON, Power Products & Solutions LLC, United States

More information

Cable diagnostic in MV underground cable networks

Cable diagnostic in MV underground cable networks Cable diagnostic in MV underground cable networks Theoretical background and practical application VLF testing tan delta loss factor measurement Partial discharge localization and measurement Author: Tobias

More information

WIRE AND CABLE ENGINEERING GUIDE

WIRE AND CABLE ENGINEERING GUIDE Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime

More information

OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES

OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES Hein PUTTER Frank PETZOLD Philipp LEGLER Megger Germany Megger Germany Megger - Germany hein.putter@megger.com frank.petzold@megger.com philipp.legler@megger.com

More information

A Study on the Effect of Performing VLF Withstand Tests on Field Aged Degraded Joints

A Study on the Effect of Performing VLF Withstand Tests on Field Aged Degraded Joints WETS D 15 2.4 Drapeau A Study on the Effect of Performing VLF Withstand Tests on Field Aged Degraded Joints Jean-François DRAPEAU Researcher Expertise Équipement électriques IREQ Jacques CÔTÉ, HQD Simon

More information

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland Company HV Diagnostics Sarl is a Swiss based company in the field of high voltage test equipment for cable testing and diagnosis.

More information

PARTIAL DISCHARGE LOCATION Selected Topics

PARTIAL DISCHARGE LOCATION Selected Topics PARTIAL DISCHARGE LOCATION Selected Topics M.S. Mashikian IMCORP ICC Meeting - Fall 2000 TOPICS TESTING PHILOSOPHY Excitation Voltage Test Voltage Level METHOD OF REFLECTOMETRY METHOD OF ARRIVAL TIME TESTING

More information

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES HEIN PUTTER Productmanager cable testing and -diagnosis Megger Site Germany 1 13 th Insucon conference 16-18 th Mai 2017, Birmingham, UK Agenda Introduction

More information

Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen

Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen Aspects of PD interpretation in HV power cables by Edward Gulski, Piotr Cichecki, Rogier Jongen General There are several aspects having influence on the diagnostic information and the condition judgment

More information

Partial discharge diagnostics on very long and branched cable circuits

Partial discharge diagnostics on very long and branched cable circuits 11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA

More information

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM,

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM, ONLINE OFFLINE VERSUS FEATURE PARTIAL DISCHARGE TESTING FOR CABLE ASSESSMENT B Y WIL L IAM H IG INBOT H AM, EA Technology, LLC Medium voltage cables have three distinct phases to their lifecycle: (1) new

More information

ABSTRACT KEYWORDS INTRODUCTION CLASSIC RELIABILITY ANALYSES

ABSTRACT KEYWORDS INTRODUCTION CLASSIC RELIABILITY ANALYSES Decision Making & Forecasting using the data available to Utilities Pitfalls, Challenges, and Case Studies of ways forward Detlef Wald (1), Joshua Perkel (2), Nigel Hampton (2) 1 Eifelkabel, Villmergen,

More information

BY JASON SOUCHAK, Megger

BY JASON SOUCHAK, Megger IMPROVING SYSTEM RELIABILITY WITH OFFLINE PD TESTING BY JASON SOUCHAK, Megger Partial discharge (PD) testing is a new generation of diagnostic testing for medium- and high-voltage underground power cable

More information

Is Fault Location Killing Our Cable Systems?

Is Fault Location Killing Our Cable Systems? Is Fault Location Killing Our Cable Systems? Benjamin Lanz, Member, IEEE; Eugene Sanchez, Member, IEEE Abstract Power outages caused by faults in underground cable systems can be difficult to locate, however

More information

VLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing

VLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing Cable Testing & Diagnostics Solutions for Medium Voltage Networks (1 kv - 36 kv) VLF Partial Discharge DC DAC tandelta Cable Testing Cable Diagnostics? There are two main applications for cable testing:

More information

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES Gonzalo MAIZ, Iberdrola Distribución, (Spain), gmaiz@iberdrola.es Armando RODRIGO, Instituto

More information

Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages

Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages F. Petzold, H.T. Putter, D. Götz, H. Schlapp, S. Markalous SebaKMT GmbH Baunach/Radeburg,

More information

Cable testing and diagnostics

Cable testing and diagnostics Cable testing and diagnostics To ensure the flow Cost-optimised maintenance through cable diagnostics The sheath and cable testing supports you in assessing whether a cable system is safe and ready to

More information

On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables

On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables William Higinbotham, Neil Davies and Victor Chan EA Technology LLC, New Jersey; USA, EA Technology Pty Ltd, Brisbane Australia; EA

More information

Cable fault location in power cables. Systematics for cable testing, diagnosis and cable fault location

Cable fault location in power cables. Systematics for cable testing, diagnosis and cable fault location Cable fault location in power cables Systematics for cable testing, diagnosis and cable fault location CABLE JOINTS, CABLE TERMINATIONS, CABLE GLANDS, CABLE CLEATS FEEDER PILLARS, FUSE LINKS, ARC FLASH,

More information

Name: Craig Goodwin. Company Name: HV Diagnostics Inc

Name: Craig Goodwin. Company Name: HV Diagnostics Inc Name: Craig Goodwin Company Name: HV Diagnostics Inc Trip Out of Cable Circuit: Over Current, Ground Fault, Differential protection or Fuse blows. Try to establish if the cable has in fact failed or has

More information

Specialists in HV and MV test and diagnostics. Testing in Substations

Specialists in HV and MV test and diagnostics. Testing in Substations Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies

More information

Dielectric Response Measurements Using DC Voltage

Dielectric Response Measurements Using DC Voltage Dielectric Response Measurements Using DC Voltage Jean-François DRAPEAU Researcher Expertise Équipement électriques IREQ ICC Spring 2011 - St Pete Education Session 2011-05-25 OUTLINE Introduction DC charging

More information

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB MV Power Cable Diagnostics by Frequency Domain Spectroscopy Peter Werelius Programma Electric AB Frequency Domain Spectroscopy Measurements of insulation capacitance and losses in a frequency interval

More information

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages Paul P. SEITZ, Ben QUAK, Seitz Instruments AG, Niederrohrdorf, Switzerland, pps@seitz-instruments.ch Edward GULSKI,

More information

OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM ELPIS J SINAMBELA

OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM ELPIS J SINAMBELA 1 OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM A thesis submitted to the Faculty of Electrical Power Engineering

More information

MV Power Cable Testing Training

MV Power Cable Testing Training MV Power Cable Testing Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Since power cables are used

More information

7. INSPECTION AND TEST PROCEDURES

7. INSPECTION AND TEST PROCEDURES 7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect

More information

PHG 70 TD PD / PHG 80 TD PD

PHG 70 TD PD / PHG 80 TD PD PHG 70 TD PD / PHG 80 TD PD BAUR VLF test and diagnostics system Functions Universal test and diagnostics system flexible, modular, extendable Cutting-edge testing and diagnostics technology: VLF truesinus

More information

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of

More information

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage Journal of Energy and Power Engineering 9 () 3-3 doi:.7/93-897/.3. D DAVID PUBLISHIG Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

More information

IDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy

IDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy IDAX 300 Insulation Diagnostic Analyzer Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy 1 Frequency Domain Spectroscopy Hi V A Lo Ground C HL Measure at several frequencies Use

More information

Field Measurement of Transmission Cable Dissipation Factor

Field Measurement of Transmission Cable Dissipation Factor Workshop 2000, Alexandria, Virginia, 13 & 14 September 2000 paper No.: 1 Field Measurement of Transmission Cable Dissipation Factor John H. Cooper, Power Delivery Consultants, Inc. Abstract This presentation

More information

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM D. Clark¹ R. Mackinlay² M. Seltzer-Grant² S. Goodfellow² Lee Renforth² Jamie McWilliam³ and Roger

More information

IN USE: CABLE AGING MANAGEMENT

IN USE: CABLE AGING MANAGEMENT IN USE: CABLE AGING MANAGEMENT ISSUE STATEMENT Concerns exist that cable aging-related failures may impact nuclear plant safety and reliability. As a result, plant owners and regulators are requiring the

More information

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales

More information

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES Frank WESTER, Edward GULSKI, Johan SMIT, Edwin GROOT*, Mark VAN VLIET* Delft University of Technology The Netherlands * NUON The Netherlands

More information

Practical aspects of PD localization for long length Power Cables

Practical aspects of PD localization for long length Power Cables Practical aspects of PD localization for long length Power Cables M. Wild, S. Tenbohlen University of Stuttgart Stuttgart, Germany manuel.wild@ieh.uni-stuttgart.de E. Gulski, R. Jongen onsite hv technology

More information

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of

More information

Field Experiences. Partial Discharge Diagnosis on MV Cables. Philipp Legler. XVI. Szigetelésdiagnosztikai Konferencia (

Field Experiences. Partial Discharge Diagnosis on MV Cables. Philipp Legler. XVI. Szigetelésdiagnosztikai Konferencia ( Field Experiences Partial Discharge Diagnosis on MV Cables Philipp Legler Technical Support Applications Engineer (Megger Site Germany) XVI. Szigetelésdiagnosztikai Konferencia (19. - 20.10.2016, Sümeg)

More information

AMR Current Sensors for Evaluating the Integrity of Concentric Neutrals in In-Service Underground Power Distribution Cables

AMR Current Sensors for Evaluating the Integrity of Concentric Neutrals in In-Service Underground Power Distribution Cables AMR Current Sensors for Evaluating the Integrity of Concentric Neutrals in In-Service Underground Power Distribution Cables Michael Seidel Dept. of Mechanical Engineering mjseidel@berkeley.edu Kanna Krishnan

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 1. Introduction Fault location on communication and power cables

More information

INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES

INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES Edward GULSKI, Delft University of Technology, (The Netherlands), e.gulski@tudelft.nl Johan J SMIT, Delft University of Technology, (The Netherlands),

More information

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Dr. Michael Krüger, Alexander Kraetge, OMICRON electronics GmbH, Austria Alexander

More information

Field Detected Cable Manufacturing Defects:

Field Detected Cable Manufacturing Defects: Field Detected Cable Manufacturing Defects: What do you do when it s the cable that s faulty? Steven Thomas, P.E. Sr. Electrical Engineer - HV Systems May 7, 2018 IMCORP Technology Users Group Meeting

More information

Cable test vans and systems

Cable test vans and systems Cable test vans and systems Prepared for anything BAUR s cable fault location and diagnostics systems Would you like to test and assess new installations and existing cable locations efficiently? To rectify

More information

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems Romeo C. Ciobanu, Cristina Schreiner, Ramona Burlacu, Cristina Bratescu Technical

More information

Cable test vans and systems

Cable test vans and systems Cable test vans and systems Prepared for anything BAUR s cable fault location and diagnostics systems Would you like to test and assess new installations and existing cable locations efficiently? To rectify

More information

L. B. Gordon Space Power Institute 231 Leach Center Auburn University, Alabama 36849

L. B. Gordon Space Power Institute 231 Leach Center Auburn University, Alabama 36849 FAILURE MODES OF LAMINATE STRUCTURES L. B. Gordon Space Power Institute 231 Leach Center Auburn University, Alabama 36849 Abstract Laminate structures composed of alternating thin layers of conductor and

More information

The importance of partial discharge testing throughout the development and operation of power transformers

The importance of partial discharge testing throughout the development and operation of power transformers The importance of partial discharge testing throughout the development and operation of power transformers Ulrike Broniecki OMICRON Energy Solutions GmbH, Berlin Power transformers are exposed to intense

More information

UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES

UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES D. Götz*, H.T. Putter* *Megger Germany INTRODUCTION High voltage termintions are essential components in high voltage cable

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits

More information

Simulation Model of Partial Discharge in Power Equipment

Simulation Model of Partial Discharge in Power Equipment Simulation Model of Partial Discharge in Power Equipment Pragati Sharma 1, Arti Bhanddakkar 2 1 Research Scholar, Shri Ram Institute of Technology, Jabalpur, India 2 H.O.D. of Electrical Engineering Department,

More information

Partial Discharge, Survey or Monitor?

Partial Discharge, Survey or Monitor? July 2014 Partial Discharge, Survey or Monitor? 24-7 Partial Discharge monitoring is the ultimate tool for finding insulation weaknesses before they fail. Introduction It s well established that Partial

More information

SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE

SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE Fred STEENNIS Paul WAGENAARS Denny HARMSEN DNV GL the Netherlands DNV GL the

More information

PARTIAL DISCHARGE MEASUREMENT

PARTIAL DISCHARGE MEASUREMENT PARTIAL DISCHARGE MEASUREMENT Partial Discharges are small electrical sparks which occur predominantly at insulation imperfection. It is the phenomenon which occurs in the insulation on application of

More information

EI HIGH VOLTAGE INSULATION TESTING POLICY

EI HIGH VOLTAGE INSULATION TESTING POLICY Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and

More information

Measurement Of Partial Discharge (PD) In High Voltage Power Equipment

Measurement Of Partial Discharge (PD) In High Voltage Power Equipment First International Conference on Emerging Trends in Engineering, Management and Scineces December 28-3, 214 (ICETEMS-214)Peshawar,Pakistan Measurement Of Partial Discharge (PD) In High Voltage Power Equipment

More information

Introduction. AC or DC? Insulation Current Flow (AC) 1. TECHNICAL BULLETIN 012a Principles of Insulation Testing. Page 1 of 10 January 9, 2002

Introduction. AC or DC? Insulation Current Flow (AC) 1. TECHNICAL BULLETIN 012a Principles of Insulation Testing. Page 1 of 10 January 9, 2002 Page 1 of 10 January 9, 2002 TECHNICAL BULLETIN 012a Principles of Insulation Testing Introduction Probably 80% of all testing performed in electrical power systems is related to the verification of insulation

More information

Analysis of Partial Discharge Patterns for Generator Stator Windings

Analysis of Partial Discharge Patterns for Generator Stator Windings American Journal of Electrical Power and Energy Systems 2015; 4(2): 17-22 Published online March 11,2015 (http://www.sciencepublishinggroup.com/j/epes) doi: 10.11648/j.epes.20150402.11 ISSN: 2326-912X

More information

H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C

H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C S O L U T I O N S Y O U R S O U R C E F O R T O P Q U A L I T Y T E S T E Q U I P M E N T w w w. h v t e c h n o l o g i e s. c o m Company

More information

Why partial discharge testing makes good sense

Why partial discharge testing makes good sense Why partial discharge testing makes good sense PD measurement and analysis have proven to be reliable for detecting defects in the insulation system of electrical assets before major damage or a breakdown

More information

ABSTRACT. VLF TAN δ MEASUREMENTS KEYWORDS INTRODUCTION. repeated tests programs.

ABSTRACT. VLF TAN δ MEASUREMENTS KEYWORDS INTRODUCTION. repeated tests programs. Repeated Field Tests Utility Case Studies of the Value of Trending J. Perkel (), Y. Del Valle (), J.C. Hernández (2), and R. N. Hampton (), - NEETRAC, Atlanta, GA, USA, josh.perkel@neetrac.gatech.edu,

More information

Effective maintenance test techniques for power transformers

Effective maintenance test techniques for power transformers Effective maintenance test techniques for power transformers by Alexander Dierks, Herman Viljoen, Alectrix, South Africa, and Dr. Michael Krüger, Omicron Electronics, Austria Due to ever-increasing pressure

More information

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015 Basics of Partial Discharge Prepared for 2015 Phenix RSM Meeting January 2015 Definitions and History Standard Definitions Fundamentally, what is a Partial Discharge An electric discharge which only partially

More information

CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS

CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS 136 CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS H. van Jaarsveldt* and R. Gouws** School of Electrical, Electronic and Computer Engineering, North-West

More information

Underground System Design TADP 547

Underground System Design TADP 547 Underground System Design TADP 547 Industry Standards, Specifications and Guides Presentation 6.4 Instructor: Frank Frentzas Industry Organizations Several professional organizations develop standards

More information

Partial Discharge Theory, Modeling and Applications To Electrical Machines

Partial Discharge Theory, Modeling and Applications To Electrical Machines Partial Discharge Theory, Modeling and Applications To Electrical Machines V. Vahidinasab, A. Mosallanejad, A. Gholami Department of Electrical Engineering Iran University of Science and Technology (IUST)

More information

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 75 CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 5.1 INTRODUCTION Partial Discharge (PD) detection is an important tool for monitoring insulation conditions in high voltage (HV) devices in power systems.

More information

3MElectrical Markets Division

3MElectrical Markets Division 3MElectrical Markets Division Contents Summary 3 Purpose... 3 Test Specimen 3 Test Deviations... 4 Test Results 5 Impulse Test Oscillograms... 10 Specimen Photographs.. 11 Equipment Documentation: Impulse

More information

CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER

CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER Henrik ENOKSEN Espen EBERG Sverre HVIDSTEN SINTEF Energy Research - Norway SINTEF Energy Research - Norway SINTEF Energy Research

More information

ICC PES Spring 2011 Meeting, Educational Session Luigi Testa, Alfred Mendelsohn

ICC PES Spring 2011 Meeting, Educational Session Luigi Testa, Alfred Mendelsohn The use of pulse shape in PD testing of cable systems using VLF ICC PES Spring 2011 Meeting, Educational Session Luigi Testa, Alfred Mendelsohn 1 Introduction Hipot VLF testing of power cable systems is

More information

Error vs. Uncertainty Historical Perspective

Error vs. Uncertainty Historical Perspective 1 Error vs. Uncertainty Historical Perspective Jim McBride Chairman PSIM Committee Vice-Chairman HVTT Subcommittee IEEE PES SPDC Fall 2017 Clearwater, FL Discussions on Uncertainty PSIM - HVTT Subcommittee

More information

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY Avinash Raj 1, Chandan Kumar Chakrabarty 1, Rafidah Ismail 1 and Basri Abdul Ghani 2 1 College of Engineering, University Tenaga

More information

Partial Discharge Patterns in High Voltage Insulation

Partial Discharge Patterns in High Voltage Insulation 22 IEEE International Conference on Power and Energy (PECon), 2-5 December 22, Kota Kinabalu Sabah, Malaysia Partial Discharge Patterns in High Voltage Insulation Hazlee Illias, Teo Soon Yuan, Ab Halim

More information

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol A New Approach for Transformer Bushing Monitoring Emilio Morales Technical Application Specialist Qualitrol Abstract Transformer bushings are one of the most critical components of a transformer. Up to

More information

Investigation of PD Detection on XLPE Cables

Investigation of PD Detection on XLPE Cables Investigation of PD Detection on XLPE Cables Hio Nam O, T.R. Blackburn and B.T. Phung School of Electrical Engineering and Telecommunications The University New South Wales, Australia Abstract- The insulation

More information

ABSTRACT INTRODUCTION DIAGNOSTIC TESTS. MAIN CHARACTERISTICS AND CONDITIONS OF 9 kv NETWORK

ABSTRACT INTRODUCTION DIAGNOSTIC TESTS. MAIN CHARACTERISTICS AND CONDITIONS OF 9 kv NETWORK LABORATORY AND ON SITE TESTS FOR THE DETERMINATION OF THE AGEING CONDITION OF MV PILC CABLES Nikola Kuljaca; Sergio Meregalli; Giuseppe Rizzi CESI RICERCA Italy sergio.meregalli@cesiricerca.it ABSTRACT

More information

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV Paul P. SEITZ, Seitz Instruments AG, (Switzerland), pps@seitz-instruments.ch Ben QUAK, Seitz Instruments AG, (Switzerland),

More information

HV AC TESTING OF SUPER-LONG CABLES

HV AC TESTING OF SUPER-LONG CABLES HV AC TESTING OF SUPER-LONG CABLES Stefan SCHIERIG, (Germany), schierig@highvolt.de Peter COORS, (Germany), coors@highvolt.de Wolfgang HAUSCHILD, IEC, CIGRE, (Germany), hauschild@highvolt.de ABSTRACT The

More information

portable affordable CDS Series Cable Fault Locators Thumpers - Surge Generators

portable affordable CDS Series Cable Fault Locators Thumpers - Surge Generators portable CDS Series Cable Fault Locators Thumpers - Surge Generators HVI offers the most complete fault locator packages available for primary cable. HVI offers the only VLF Thumper combination ideal for

More information

INFLUENCE OF VOLTAGE WAVEFORMS ON PARTIAL DISCHARGES DEVELOPED IN POWER CABLE INSULATION

INFLUENCE OF VOLTAGE WAVEFORMS ON PARTIAL DISCHARGES DEVELOPED IN POWER CABLE INSULATION INFLUENCE OF VOLTAGE WAVEFORMS ON PARTIAL DISCHARGES DEVELOPED IN POWER CABLE INSULATION LARISA MĂRIUŢ, ELENA HELEREA *1 Key words: Partial discharge, Inception voltage, Step-up voltage test method, Sinusoidal

More information

Evaluation of Distribution Line Spacers Located Near the Coast

Evaluation of Distribution Line Spacers Located Near the Coast Evaluation of Distribution Line Spacers Located Near the Coast WALTER PINHEIRO ARNALDO G. KANASHIRO 2 GERALDO F. BURANI 2 Consultant Engineer University of São Paulo Av. Prof. Luciano Gualberto, 289, São

More information

Partial Discharge Monitoring and Diagnosis of Power Generator

Partial Discharge Monitoring and Diagnosis of Power Generator Partial Discharge Monitoring and Diagnosis of Power Generator Gao Wensheng Institute of High Voltage & insulation tech. Electrical Eng. Dept., Tsinghua University Wsgao@tsinghua.edu.cn Currently preventive

More information

ELEC-E8409 High Voltage Engineering. Condition Monitoring of Power Cables

ELEC-E8409 High Voltage Engineering. Condition Monitoring of Power Cables ELEC-E8409 High Voltage Engineering Condition Monitoring of Power Cables ON-SITE DC MEASUREMENTS Measurements quick and simple, several kv voltage, does not require expensive equipment Insulation Resistance

More information

PD Solutions. On-Line PD Measurement Devices

PD Solutions. On-Line PD Measurement Devices On-Line PD Measurement Devices 1. Longshot Device (see Figure 1) The measurement system applied is based around the wideband (0-400 MHz) HVPD- Longshot partial discharge test unit which utilizes a high-speed

More information

1. Introduction to Power Quality

1. Introduction to Power Quality 1.1. Define the term Quality A Standard IEEE1100 defines power quality (PQ) as the concept of powering and grounding sensitive electronic equipment in a manner suitable for the equipment. A simpler and

More information