PD Monitoring of MV/HV Power Cables December 2016
|
|
- Gerald Francis
- 5 years ago
- Views:
Transcription
1 PD Monitoring of MV/HV Power Cables December 216 Malcolm Seltzer-Grant
2 Introduction to HVPD Our global presence Introduction to HVPD Ltd HVPD are experts in the growing industry of on-line partial discharge (OLPD) condition monitoring and condition based maintenance (CBM) of high voltage networks. We supply portable and permanent OLPD surveying, diagnostic test and continuous monitoring solutions, and a complimentary range of on-site services, monitoring services and training. Over 4 customers in 1 countries trust our technology.
3 Contents Introduction to partial discharge in power cables Measurement equipment Continuous monitoring Partial discharge location methods Case studies
4 Partial Discharge Detection Theory Available Waveform Display PDs are incepted by the high voltage applied to cable. Chan PD pulses are short duration impulses (ns µs) that propagate in both directions away from PD site between cable core and sheath Time (msec) Signals can be detected on both the core and earth screen at terminations. End A End B
5 MV/HV Cable Faults - Causes and Effects Common Causes Poor workmanship (at cable accessories) Mechanical damage caused by poor installation practices (including damage to cable sheath during cable pulling and minimum cable bend radius being exceeded) Poor quality or poorly manufactured cables and cable accessories Aging of insulation Effects Electrical trees and interfacial surface tracking Localised heating/moisture ingress into the cable (caused by damage to the armour/outer sheath) Infant Mortality and premature failure within the firs years of operation
6 PD Damage to HV Cable Transformer Terminations Tracking on 11 kv Termination (PD detected before failure) Failed 11 kv Termination (same type as opposite)
7 Insufficient Mastic Around Connector in 33 kv Joint
8 Trees on 66kV paper cable
9 Why and When to Perform PD Testing At Manufacture Quality Assurance Type/routine tests, e.g. IEEE/IEC standard At Commissioning To check for transport damage To ensure the installation has been made to a good standard, for example attachment of terminations and joints to power cables Service Life Detection of issues that emerge over time Condition Based Maintenance
10 Survey - Detection Identify equipment with PD in network Simple instrumentation can be susceptible to noise Low level of training Usually only on-line Diagnostic/Location Testing Detailed test result more advanced instruments Higher level of training to perform Off-line and On-line Spot Test: Surveying vs Diagnostic Testing Use survey to identify equipment with PD and diagnostic testing only where PD is identified
11 Spot Testing vs Monitoring Spot Test Snapshot of the condition Doesn t take into account variations with operating stress Labour resource to perform testing Monitoring Continuous evaluation of the condition Detect variations with operating stresses (e.g. temperature/ humidity) Less labour requirement after set-up Usually deployed on critical plant or plant with high PD in spot test
12 Test Equipment Detection Simple handheld detectors, give indication if PD detected and its level Diagnostic More advanced detector, often with PC software More information type of PD, locations Monitoring Portable or permanent logging of PD Interface to plant control system (SCADA)
13 Aspects of Testing MV and HV Cables MV HV Equipment at primary substation and ring main units Cross-bonding less common Some tolerance to PD activity Strong safety motivation for sealing ends Equipment and substations, cable termination, cable joints Very little tolerance to PD activity
14 PD Detection Energies for Different Points in Cable System Corona at metal contacts Electrical charge RF Electromagnetic radiation Acoustic Ultraviolet Ozone Discharges on insulator surface Electrical charge RF Electromagnetic radiation Acoustic Ultraviolet Ozone Partial discharge in termination insulation system Electrical charge RF Electromagnetic radiation (local) Acoustic (local) Partial discharge in cable insulation or joint Electrical charge RF Electromagnetic radiation (local) Acoustic (local)
15 High Frequency Current Transformer (HFCT) Sensors Detect PD in cables and connected plant Wide bandwidth (from 1 khz to 2 MHz) Attach to power cables at terminations and earthing links of HV equipment Installation inside or outside of cable box Temporary or permanent
16 HFCT Sensor Attachment to Power Cables The HFCT sensor should be attached to intercept either the conductor PD current (i+) or the earth PD current (i-) 1 HFCT on Earth (i-) 1 HFCT on cable with Earth brought back through (i+) 2 HFCT around cable (i- + i+ = ) 3 2
17 HFCT Attachment at Cross-bond Points on 132 kv Cables
18 PD Against Phase for Power Cables On-line Detection Single Core Cable Available Waveform Display Three Core Belted Cable with HFCT on Common Screen Available Waveform Display Chan Time (msec) Chan Time (msec)
19 Modern PD Detection Systems PD Sensors Hardware Filtering/ Amplification Digitiser/DSO PD Data Analysis Software Trigger signal
20 Noise Reduction Performed with the Kronos Software Raw Data PD Event Recognition Apply Expert De-noising Rules De-noised PD Data Indicated Condition The Kronos automatically 1,121,68 21,183,18 (before more noise HVPD training) pulses (1%) implements recognises are rejected. data the 1,182,992 rules on the software 61,924 point (6%) PD acquired data points pulses Indicated (.2%) as possible correctly over 33,941 PD pulses identified and rejects Condition power the cycles remainder as noise
21 Data Analysis Data before analysis/noise rejection Data after analysis/noise rejection
22 Data Analysis
23 Continuous Monitoring
24 Continuous PD Monitoring Aspects Detect cyclic changes in activity Load varying activity on PILC cables Humidity related activity from surface discharges Detect changes that relate to incipient faults Gradual rise Sudden rise Sudden drop Carried out on: key circuits, circuits with suspected cyclic PD changes, circuits with high spot-test results
25 PD and Load Relations Although PD incepted by voltage, load can have effect Mostly on PILC cables Load variations Movement of oil/impregnant Expansion of conductors S S M T W T F S S M T W T F
26 1kV PILC Cables Prozess Datum : : : : : : : : : : : : : : : : : : : : : : : : :3 PD burns PD in burns a hot in cable: a cold electrodes cable (9% expand of cases): - possible fluid shrinks, movements voids inside appear, accessories local PD in lead voids to increased field strengths in dielectrics PD in accessories
27 Examples of PD rises to Failure 45, 4, 35, 3, 25, 2, 15, 1, 5, Number above threshold 1 (start date=12/7/99) Time (Days) Signal levels (mv) Peak, ave, and No above thresholds (start date=29/11/ Chan=18) 36, 34, 32, 3, 28, 26, 24, 22, 2, 18, 16, 14, 12, 1, 8, 6, 4, 2, Time (Days) 5 6 Thresh 1
28 On-line Cable Mapping (PD Site Location)
29 PD Detection Theory PD Pulse Propagation and Attenuation Cables act as waveguides for PD pulses and as low-pass filters. PD pulses attenuate and disperse as they travel down the cable PD sensor must have a good low frequency response to detect long distance PD. Increasing the number of test points gives more conclusive results. A study was carried out using ~5 pc calibration pulses injected into 2 km, 4 kv cable to determine attenuation and measurement range the pulse was successfully detected 2 km from the source. Reference: S.Sutton, R. Plath and G. Shröder, The St.Johns Wood Elstree Experience Testing a 2km Long 4kV XLPE- Insulated Cable System After Installation, Jicable 27-7 th International Conference on Insulated Power Cables, Paris Versailles, June 27.
30 PD Location in Power Cables Direct Pulse Reflected Pulse ΔT = Time difference between direct and reflected pulses. L = Cable Return Time for cable Measurement End PD event Remote End Direct pulse ΔT Reflected pulse L PD Site Location ΔT PD% = 1 1 L
31 Single-ended Cable Mapping Only possible for long distances when the tested cable s far end impedance change is HIGH (e.g. if the end of the cable goes into a transformer and/or the circuit breaker at the far end of the cable is OPEN).
32 OLPD Location on Power Cables In many on-line cases reflected PD pulses are often not visible: Attenuation is too large to measure reflected pulses from the far end (long cables) Waveforms too difficult to interpret (noisy signals) Teed or jointed cables Cables with many ring main units or switches Cables with no change in impedance at the far end Cross-bonded cable circuits multiple reflections
33 Double-ended Cable Mapping (Range up to 5 km or 3 RMUs) Necessary when the tested cable s far end impedance change is LOW (e.g. if the far end circuit breaker is CLOSED). The HVPD Portable Transponder system amplifies PD signals, allowing the HVPD Longshot at the other end of the cable to receive and interpret the relative arrival times of pulses at each end of the cable to give an accurate location. The cable earth strap must be accessible at both ends of the cable in order to perform double-ended mapping.
34 On-line PD Location on Power Cables Example of Usage Without Transponder ΔT Reflection may not be clearly visible (e.g. due to noise) With Transponder The large transponder pulse removes any confusion ΔT ΔT tr ΔT = Time between direct and reflected PD pulses ΔTtr = Transponder time delay
35 On-line PD Location on Power Cables Example Results 15 Direct PD Pulse Voltage (mv) Reflected PD Pulse Transponder Time Delay Reflectogram showing PD and transponder pulses Transponder Pulse Time (usec) All Phases PD (pc) PD location map for all PD pulses in cable section under test Location (% along cable)
36 CASE STUDY: OLPD TESTING AND CABLE MAPPING OF 33 KV XLPE CABLES IN METRO NETWORK
37 Case Study: Introduction OLPD testing was carried out in response to a number recent faults* of 33 kv cable joints within the customer s network. The faults led to disruption of the power supply to the rail system. The purpose of the testing was to measure and locate any PD activity within the cables with particular focus on the cable joints. * It should be noted that this was a newly installed cable system that had been inservice for just over 12 months before the faults started to occur.
38 Case Study : OLPD Testing Equipment and Methodology On-line Cable PD Mapping using the HVPD Longshot test unit and Portable transponder. Tests started with calibration testing with pulse injection HFCTs.
39 Case Study: Test Results Cable PD signals have been detected on Blue Phase with cross-talk (lower magnitude) on Red and Yellow phases. The source of PD was located to Joint Number 2 (Jt2) using the on-line PD mapping technique. The faulty joint on this cable was replaced and re-tested using the HVPD Longshot test unit to verify the repair was good
40 Case Study: Top 2 Worst Performing Circuits Out of the 5+ circuits tested, Major PD was detected within cable accessories on the three of the circuits (6%) as shown in RED in the Table below. The levels of discharges detected put these 33 kv cables into RED category, Major concern, locate PD and then repair or replace. Criticality Number Circuit Comments Peak Cable PD Level (pc) Local PD Level (db) Cumulative Cable PD Level (nc/cycle) OLPD Criticality (%) Maintenance Action 1. DUB to MPS1 C2 B Phase < ABS to AH C2 B / Y Phase 9729 < Major concern, 3. BUR to HCC C2 B / Y Phase 3781 < locate PD and 4. BUR to HCC C1 B / Y Phase 3245 < then repair or 5. ABS to AH C1 B / Y Phase 292 < replace. 6. NHD to QYD C2 R Phase 2849 < ALQ to AHS C2 B Phase 1733 < Some concern, 8. MPS3 to BNS C2 R / B Phase 1337 < repeat test and 9. NHD to QYD C1 R Phase 887 < regular 1. HCC to CRK C1 Y / B Phase 759 < monitoring 11. AHS to SLD Y / R Phase 75 < recommended. 12. STD to ABH Y Phase 238 < ALR to BNS C1 B Phase 184 < ALR to BRJ No PD detected <1 15. ALG to PMD No PD detected <1 16. ALG to KBW No PD detected <1 17. AQD to AQ2 No PD detected <1 18. JDD to CRK No PD detected <1 19. ODM to JDF C1 No PD detected <1 2. ODM to JDF C2 No PD detected <1 Re-test in 12 months.
41 CASE STUDY: OLPD Testing, Location, Monitoring with Preventative Maintenance on a 33 kv Land- Sea Offshore Wind Farm Export Cable (UK)
42 Case Study: Circuit Details 33kV Grid Substation Offshore Wind farm 33kV Switching Substation Circuit 1 Circuit 2 Offshore 33kV GIS Switchgear Land Cables 3 x single core Land-Subsea Cable Joints 3 core Subsea Cables 1.7 km single core XLPE land cable 9.6/11.5 km 3 core XLPE subsea cable
43 Case Study: OLPD Test and Mapping Data L1 L2 L3 PD Magnitude (pc) Cable PD Phase of Pow er Cycle (deg) PD Magnitude (pc) Cable PD Phase of Pow er Cycle (deg) PD Magnitude (pc) Cable PD 1, 5, -5, -1, Phase of Pow er Cycle (de High levels of PD (of up to 1, pc / 1 nc) measured on Circuit B, Phase L3.
44 Case Study: PDMap Graph Showing PD Location Switching Substation Joint Pit 7 Land-sea Transition Joint , Location (meters) 1,2 1,4 1,6
45 Case Study: PD Signals Before and After Joint Replacement BEFORE High PD detected on L3 PD Located , 1,2 Location (meters) 1,4 1,6 Joint 7 with PD removed and replacement cable section installed Lower-level sporadic PD signals from different site after joint replacement AFTER
46 Case Study: Circuit B Evidence of Surface Degradation Due to Bad Fitting Heatshrink Stress Control
47 Case Study: OLPD testing of 11 kv XLPE cables and terminations for oil refinery client (Slovakia)
48 Condition Assessment Following the failure of two 11 kv transformer cable terminations, OLPD testing on the other cable terminations of same type was carried out.
49 Failed 11 kv Transformer Cable Termination
50 Test Set-up and Results PD Magnitude (pc) Cable PD Phase of Pow er Cycle (deg) 36 PD Magnitude (pc) Cable PD Phase of Pow er Cycle (deg) PD Magnitude (pc) Cable PD Phase of Pow er Cycle (deg) 36 HFCT L1 Earth Strap HFCT L2 Earth Strap HFCT L3 Earth Strap Cable PD Segment Waveform Significant levels of PD activity (of up to 4 pc) were detected on Phase L2. Volts (mv) Time us 2 3
51 Forensic Investigation L2 termination was eventually replaced 15 months after the initial tests were made. Investigation showed evidence of severe tracking. The cable had not yet failed i.e. the OLPD testing gave a very good early warning of 15 months against the incipient fault.
52 End of Presentation Thank you for your time Any Questions? Malcolm Seltzer-Grant
PD Solutions. On-Line PD Measurement Devices
On-Line PD Measurement Devices 1. Longshot Device (see Figure 1) The measurement system applied is based around the wideband (0-400 MHz) HVPD- Longshot partial discharge test unit which utilizes a high-speed
More informationAfrica Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound
Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences
More informationNETWORK INNOVATION COMPETITION ANGLE-DC PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT
NETWORK INNOVATION COMPETITION PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT NOVEMBER 17 Version: 1.0 Authored by: Andrew Moon Engineering Consultant and Project Manager Kevin Smith Lead
More informationTesting and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl
Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May 26 2011 St Pete Beach, Fl HDW ELECTRONICS, INC. THE BEST IN CABLE FAULT LOCATING TECHNOLOGY by Henning Oetjen Frank
More informationON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM
ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM D. Clark¹ R. Mackinlay² M. Seltzer-Grant² S. Goodfellow² Lee Renforth² Jamie McWilliam³ and Roger
More informationPERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE
PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE Fred STEENNIS, KEMA, (the Netherlands), fred.steennis@kema.com Peter VAN DER WIELEN, KEMA,
More informationPartial discharge diagnostics on very long and branched cable circuits
11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA
More informationOn-line Partial Discharge Assessment and Monitoring of MV to EHV Cables
On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables William Higinbotham, Neil Davies and Victor Chan EA Technology LLC, New Jersey; USA, EA Technology Pty Ltd, Brisbane Australia; EA
More informationPD Testing Considerations for MV Plant Cables
PD Testing Considerations for MV Plant Cables Cable Testing Philosophy Damage Mistake Aging Repair Manufacturing Transportation Installation Operation Power frequency 50/60 Hz Power frequency 50/60 Hz
More informationPartial Discharge Measurement and Monitoring on High Voltage XLPE Cables
21, rue d Artois, F-75008 PARIS AUCKLAND 2013 http : //www.cigre.org Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables Michael Krüger, Rene Hummel, Stefan Böhler, OMICRON Austria
More informationThe University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge
The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits
More informationDoble Solutions for Partial Discharge. Greg Topjian Solutions Manager
Doble Solutions for Partial Discharge Greg Topjian Solutions Manager 617-393-3129 gtopjian@doble.com Why do we need to conduct PD measurements PD a major cause of early failure for HV insulation. Partial
More informationOnline Localisation of Partial Discharge Using Pulse Propagation Parameters in Medium Voltage Cable Network
2015 17th UKSIM-AMSS International Conference on Modelling and Simulation Online Localisation of Partial Discharge Using n Parameters in Medium Voltage Cable Network Tauqeer Ahmed Shaikh, Abdulrehman Al-Arainy,
More informationSENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES
SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES Frank WESTER, Edward GULSKI, Johan SMIT, Edwin GROOT*, Mark VAN VLIET* Delft University of Technology The Netherlands * NUON The Netherlands
More informationTHE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.
THE POWER OF LIFE WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk. Mr. Neal Yang Pro.E.E. Engineer About Us The flaw of dielectric material
More informationSpecialists in HV and MV test and diagnostics. Testing in Substations
Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies
More informationIN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY
IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY Avinash Raj 1, Chandan Kumar Chakrabarty 1, Rafidah Ismail 1 and Basri Abdul Ghani 2 1 College of Engineering, University Tenaga
More informationNEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY
NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY Lorenzo PERETTO Luigi FODDAI Simone ORRU Luigi PUDDU Altea Switzerland ENEL Italy ENEL Italy REPL Italy lperetto@alteasolutions.com
More informationEI HIGH VOLTAGE INSULATION TESTING POLICY
Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and
More informationTHE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE
THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales
More informationONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM,
ONLINE OFFLINE VERSUS FEATURE PARTIAL DISCHARGE TESTING FOR CABLE ASSESSMENT B Y WIL L IAM H IG INBOT H AM, EA Technology, LLC Medium voltage cables have three distinct phases to their lifecycle: (1) new
More informationWhy partial discharge testing makes good sense
Why partial discharge testing makes good sense PD measurement and analysis have proven to be reliable for detecting defects in the insulation system of electrical assets before major damage or a breakdown
More informationInternational Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer
Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 7, July -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 Comparison
More informationECP HV INSULATION TESTING
Document Number: ECP 11-0006 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE EPN, LPN, SPN ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing
More informationFault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 1. Introduction Fault location on communication and power cables
More informationSMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE
SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE Fred STEENNIS Paul WAGENAARS Denny HARMSEN DNV GL the Netherlands DNV GL the
More informationPartial Discharge Trends in Medium Voltage Cables measured while in-service with PDOL
1 Partial Discharge Trends in Medium Voltage Cables measured while in-service with PDOL André N. Cuppen, E. Fred Steennis, and Peter C. J. M. van der Wielen, Member, IEEE Abstract-- This paper presents
More informationAssuring the Reliability of Critical Power Cable Systems
Assuring the Reliability of Critical Power Cable Systems Presented by: Benjamin Lanz Manager of Application Engineering IMCORP Power Cable Reliability Consulting & Diagnostics Some of the technologies
More informationTHE EVOLUTION OF NON-INTRUSIVE PARTIAL DISCHARGE TESTING OF MV SWITCHGEAR
THE EVOLUTION OF NON-INTRUSIVE PARTIAL DISCHARGE TESTING OF MV SWITCHGEAR Neil DAVIES and Chris LOWSLEY EA Technology Ltd. - United Kingdom Neil.Davies@eatechnology.com INRODUCTION The trend for extending
More informationTECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets
TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets Who we are TECHIMP is one of the leading providers of Condition Assessment Services Data Acquisition and Test Equipment
More informationPARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES
PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES Engr. IÑIGO V. ESCOPETE, JR. ITC Level 2 Certified Thermographer PHIL-NCB NDT-UT Level 2 Partial Discharge testing is a Condition Based Maintenance tool
More informationCable Data Collector (CDC): Application Guide
Cable Data Collector (CDC): Application Guide Contents 1. Introduction... 1 2. PD in cables... 1 3. Principle of operation... 2 4. Advantages and disadvantages... 6 5. Assessing circuit suitability...
More informationNOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV
NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV Paul P. SEITZ, Seitz Instruments AG, (Switzerland), pps@seitz-instruments.ch Ben QUAK, Seitz Instruments AG, (Switzerland),
More informationUltraTEV Locator Portable Partial Discharge (PD) investigation system.
UltraTEV Locator Portable Partial Discharge (PD) investigation system Locates, measures and records PD activity in all substation assets including cables www.eatechnologyusa.com Benefits Locating and measuring
More informationOFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES
OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES Hein PUTTER Frank PETZOLD Philipp LEGLER Megger Germany Megger Germany Megger - Germany hein.putter@megger.com frank.petzold@megger.com philipp.legler@megger.com
More informationECP HV INSULATION TESTING
Document Number: ECP 11-0006 Network(s): Summary: All ENGINEERING COMMISSIONING PROCEDURE ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing of new and
More informationUSING DAMPED AC VOLTAGES
MODERN & TESTING DIAGNOSIS OF POWER CABLES USING DAMPED AC VOLTAGES BY EDWARD GULSKI AND ROGIER JONGEN, Onsite HV Solutions ag, Switzerland AND RALPH PATTERSON, Power Products & Solutions LLC, United States
More informationEquipment under Measurement: 6.6kV Alstom AIS Switchgear. Date of Measurement: 10 th August 2017
Case History - 24: Online PD measurement using TEV, Ultrasonic Inductive UHF & HFCT Sensors Equipment under Measurement: 6.6kV Alstom AIS Switchgear Date of Measurement: 10 th August 2017 Sensor Used:
More informationSimultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics
Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics Dominique Bolliger, Ph.D. HV TECHNOLOGIES, Inc. Manassas, VA, USA d.bolliger@hvtechnologies.com Abstract In
More informationBasics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015
Basics of Partial Discharge Prepared for 2015 Phenix RSM Meeting January 2015 Definitions and History Standard Definitions Fundamentally, what is a Partial Discharge An electric discharge which only partially
More informationAdvancements in online partial discharge monitoring and assessment of MV through EHV Substation assets
Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets Abstract: For decades it has been recognized that partial discharge assessment is an excellent method
More informationApplication Note. Detection of Partial Discharge Using Ultrasound. Detection of Partial Discharge Using Ultrasound. Problem. iriss.
Detection of Partial Discharge Using Ultrasound Problem In electrical systems, especially above 1,000 Volts, sufficient and properly maintained equipment insulation helps ensure equipment longevity. However,
More informationVLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing
Cable Testing & Diagnostics Solutions for Medium Voltage Networks (1 kv - 36 kv) VLF Partial Discharge DC DAC tandelta Cable Testing Cable Diagnostics? There are two main applications for cable testing:
More informationPartial Discharge, Survey or Monitor?
July 2014 Partial Discharge, Survey or Monitor? 24-7 Partial Discharge monitoring is the ultimate tool for finding insulation weaknesses before they fail. Introduction It s well established that Partial
More informationPartial discharge trends in medium voltage cables measured while in-service with PDOL Cuppen, A.N.; Steennis, E.F.; van der Wielen, P.C.J.M.
Partial discharge trends in medium voltage cables measured while in-service with PDOL Cuppen, A.N.; Steennis, E.F.; van der Wielen, P.C.J.M. Published in: Proceedings of the IEEE PES Transmission and Distribution
More informationPractical aspects of PD localization for long length Power Cables
Practical aspects of PD localization for long length Power Cables M. Wild, S. Tenbohlen University of Stuttgart Stuttgart, Germany manuel.wild@ieh.uni-stuttgart.de E. Gulski, R. Jongen onsite hv technology
More informationPRY-CAM BREAKTHROUGH TECHNOLOGY FOR CONDITION ASSESSMENT AND ASSET MANAGEMENT
PRY-CAM BREAKTHROUGH TECHNOLOGY FOR CONDITION ASSESSMENT AND ASSET MANAGEMENT WELCOME TO PRY-CAM A REVOLUTION IN PARTIAL DISCHARGE MANAGEMENT The worlds of partial discharge (PD) measurement, asset management
More informationEPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY
EPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY EPS AUSTRALIA SERVICES COMPANY OVERVIEW EPS is a recognised company specialising in Electrical, Instrumentation, Structural, Mechanical and
More informationSoftware System for Finding the Incipient Faults in Power Transformers
Software System for Finding the Incipient Faults in Power Transformers Nikolina Petkova Technical University of Sofia, Department of Theoretical Electrical Engineering, 1156 Sofia, Bulgaria Abstract In
More informationAspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen
Aspects of PD interpretation in HV power cables by Edward Gulski, Piotr Cichecki, Rogier Jongen General There are several aspects having influence on the diagnostic information and the condition judgment
More informationTitle: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS
TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 4.0 Sectionalizer Construction... 4 5.0 Mechanism... 6 6.0 Solid Dielectric
More informationCHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN
75 CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 5.1 INTRODUCTION Partial Discharge (PD) detection is an important tool for monitoring insulation conditions in high voltage (HV) devices in power systems.
More informationBY JASON SOUCHAK, Megger
IMPROVING SYSTEM RELIABILITY WITH OFFLINE PD TESTING BY JASON SOUCHAK, Megger Partial discharge (PD) testing is a new generation of diagnostic testing for medium- and high-voltage underground power cable
More informationUltraTEV Locator. Portable PD (Partial Discharge) investigation system. benefits. features. FACT: 85% of disruptive substation failures are PD-related
UltraTEV Locator Portable PD (Partial Discharge) investigation system Locates, measures and records PD activity in all substation assets including cables benefits Locating and measuring PD activity to
More informationLong lengths transmission power cables on-site testing up to 500 kv by damped AC voltages
Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages Paul P. SEITZ, Ben QUAK, Seitz Instruments AG, Niederrohrdorf, Switzerland, pps@seitz-instruments.ch Edward GULSKI,
More informationPartial Discharge (PD) techniques for measuring the condition of ageing HV/MV switchgear
3100 words with case studies (US) Partial Discharge (PD) techniques for measuring the condition of ageing HV/MV switchgear By Neil Davies, Director, EA Technology International Throughout the world, the
More informationPARTIAL DISCHARGE MEASUREMENT
PARTIAL DISCHARGE MEASUREMENT Partial Discharges are small electrical sparks which occur predominantly at insulation imperfection. It is the phenomenon which occurs in the insulation on application of
More informationInvestigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages
Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages F. Petzold, H.T. Putter, D. Götz, H. Schlapp, S. Markalous SebaKMT GmbH Baunach/Radeburg,
More informationDirectional Sensing for Online PD Monitoring of MV Cables Wagenaars, P.; van der Wielen, P.C.J.M.; Wouters, P.A.A.F.; Steennis, E.F.
Directional Sensing for Online PD Monitoring of MV Cables Wagenaars, P.; van der Wielen, P.C.J.M.; Wouters, P.A.A.F.; Steennis, E.F. Published in: Nordic Insulation Symposium, Nord-IS 05 Published: 01/01/2005
More informationInvestigation of PD Detection on XLPE Cables
Investigation of PD Detection on XLPE Cables Hio Nam O, T.R. Blackburn and B.T. Phung School of Electrical Engineering and Telecommunications The University New South Wales, Australia Abstract- The insulation
More informationExtending the Functionality of On-line PD Monitoring Equipment for MV Power Cables
24 th Nordic Insulation Symposium on Materials, Components and Diagnostics 152 Extending the Functionality of On-line PD Monitoring Equipment for MV Power Cables Y. Li 1, P.A.A.F. Wouters 1, P. Wagenaars
More informationINVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES
INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES Gonzalo MAIZ, Iberdrola Distribución, (Spain), gmaiz@iberdrola.es Armando RODRIGO, Instituto
More informationEFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento
Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of
More informationCable testing and diagnostics
Cable testing and diagnostics To ensure the flow Cost-optimised maintenance through cable diagnostics The sheath and cable testing supports you in assessing whether a cable system is safe and ready to
More informationUnderground System Design TADP 547
Underground System Design TADP 547 Industry Standards, Specifications and Guides Presentation 6.4 Instructor: Frank Frentzas Industry Organizations Several professional organizations develop standards
More informationPractical Experience in On-Line Partial Discharge Measurements of MV Switchgear Systems
Practical Experience in On-Line Partial Discharge Measurements of MV Switchgear Systems Z. Berler, I. Blokhintsev, A. Golubev, G. Paoletti, V. Rashkes, A. Romashkov Cutler-Hammer Predictive Diagnostics
More informationAbstract. 1 Introduction
Using optical couplers to monitor the condition of electricity infrastructure S.G. Swingler, L. Hao, P.L. Lewin and D.J. Swaffield The Tony Davies High Voltage Laboratory, University of Southampton, Southampton
More informationThe Application of Partial Discharge Measurement and Location on CGIS
International Journal on Electrical Engineering and Informatics Volume 4, Number 3, October 2012 The Application of Partial Discharge Measurement and Location on CGIS Min-Yen Chiu¹, Keng-Wei Liang¹, Chang-Hsing
More informationUHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES
UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES D. Götz*, H.T. Putter* *Megger Germany INTRODUCTION High voltage termintions are essential components in high voltage cable
More information9 Specifications. Specifications NOMINAL CHARACTERISTICS
9 Specifications Specifications NOMINAL CHARACTERISTICS WARRANTED CHARACTERISTICS Nominal characteristics describe parameters and attributes that are guaranteed by design, but do not have associated tolerances.
More informationCable fault location in power cables. Systematics for cable testing, diagnosis and cable fault location
Cable fault location in power cables Systematics for cable testing, diagnosis and cable fault location CABLE JOINTS, CABLE TERMINATIONS, CABLE GLANDS, CABLE CLEATS FEEDER PILLARS, FUSE LINKS, ARC FLASH,
More informationCondition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology
Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of
More informationOPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM ELPIS J SINAMBELA
1 OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM A thesis submitted to the Faculty of Electrical Power Engineering
More informationBEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES
BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES HEIN PUTTER Productmanager cable testing and -diagnosis Megger Site Germany 1 13 th Insucon conference 16-18 th Mai 2017, Birmingham, UK Agenda Introduction
More informationPARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS
PARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS by K.K.JEMBU KAILAS and W. ADITHYA KUMAR L&T CONSTRUCTION L&T CONSTRUCTION KKJK@LNTECC.COM
More informationType Test of a 145 kv Termination Type TS 145-II
Test Report No 2009-125/2 Type Test of a 145 kv Termination Type TS 145-II Client: 3 M Deutschland GmbH Carl-Schurz-Str.1 41453 Neuss Reporter: Dr.-Ing. R. Badent Dr.-Ing. B. Hoferer This report includes
More information10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY
9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor
More informationPARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM
Abstract PARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM Q. SU Department of Electrical & Computer Systems Engineering Monash University, Clayton VIC 3168 Email: qi.su@eng.monash.edu.au
More informationI P I OUT R L. Applications. Standards. N 52.D ; Page 1/8
Ref: ATO-10-B225-D10/SP3 r = 10 A ATO series is a split core current transformer for the electronic measurement of AC waveform current with galvanic separation between the primary circuit (power) and the
More informationportable affordable CDS Series Cable Fault Locators Thumpers - Surge Generators
portable CDS Series Cable Fault Locators Thumpers - Surge Generators HVI offers the most complete fault locator packages available for primary cable. HVI offers the only VLF Thumper combination ideal for
More informationPD Diagnostic Applications and TechImp solutions
PD Diagnostic Applications and TechImp solutions Condition Assessment Solutions for Electrical Systems. PD based innovative tools for the Condition Based Maintenance. MD-04.05.004 - rev. 00-29/08/2006
More informationI P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017
Ref: ART-B22-D70, ART-B22-D125, ART-B22-D175, ART-B22-D300 Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and
More informationStatistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage
Journal of Energy and Power Engineering 9 () 3-3 doi:.7/93-897/.3. D DAVID PUBLISHIG Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage
More informationPartial Discharge Monitoring and Diagnosis of Power Generator
Partial Discharge Monitoring and Diagnosis of Power Generator Gao Wensheng Institute of High Voltage & insulation tech. Electrical Eng. Dept., Tsinghua University Wsgao@tsinghua.edu.cn Currently preventive
More informationWIRE AND CABLE ENGINEERING GUIDE
Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime
More informationHigh Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland
High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland Company HV Diagnostics Sarl is a Swiss based company in the field of high voltage test equipment for cable testing and diagnosis.
More informationFurther Experience in the Use of Existing RTDs in Windings of Motors and Generators for the Measurement of Partial Discharges
Further Experience in the Use of Existing RDs in Windings of Motors and Generators for the Measurement of Partial Discharges Claude Kane Eaton Electrical Predicative Diagnostics 5421 Feltl Road Suite 190
More informationElectrical Switchgear & Power Transformer Testing. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E
Electrical Switchgear & Power Transformer Testing H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E www.ictd.ae ictd@ictd.ae Course Introduction: This will provide you with practical knowledge
More informationOMICRON Seminar on Partial Discharge Diagnostics on HV Assets. January 30, 2018 Beirut, Lebanon
OMICRON Seminar on Partial Discharge Diagnostics on HV Assets January 30, 2018 Beirut, Lebanon Substation Asset Testing and Diagnosis LOW ACCURACY LEVEL HIGH Take better maintenance decisions through accurate
More informationMONTRANO. Continuous monitoring system for power transformers
MONTRANO Continuous monitoring system for power transformers Condition monitoring to extend transformer life Knowing the dielectric condition of insulation is vital Dielectric flashover of insulation in
More informationThe R Portable Device for Partial Discharge Measurement and Analysis in High Voltage Equipment Insulation
The R2200 - Portable Device for Partial Discharge Measurement and Analysis in High Voltage Equipment Insulation DIMRUS Ltd. www.dimrus.ru 1 The R2200 Device is for Effective Partial Discharge (PD) Measurement
More informationTesting of 400 kv GIS
Testing of 400 kv GIS Robert le Roux, Dermot Dorgan, Brian Perry ESB International - Ireland Paper 028 1 Introduction The 400 kv transmission is designed for critical periods of low loading. Due to critical
More informationT/3000 T/3000. Substation Maintenance and Commissioning Test Equipment
T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY
More informationName: Craig Goodwin. Company Name: HV Diagnostics Inc
Name: Craig Goodwin Company Name: HV Diagnostics Inc Trip Out of Cable Circuit: Over Current, Ground Fault, Differential protection or Fuse blows. Try to establish if the cable has in fact failed or has
More informationI Pr I P I OUT R L. Applications. Standards
Ref: ATO-XXX-B225-D10 I Pr = 10, 15, 16, 20, 30, 32, 50, 60, 63, 75 A ATO series is a split core current transformer for the electronic measurement of AC waveform current with galvanic separation between
More informationCITY SERIES. Compact, fully equipped cable fault location, test and diagnostic systems
CITY SERIES Compact, fully equipped cable fault location, test and diagnostic systems Tailored to fit to small vehicles Easy operation in restricted spaces Centrally controlled, fully automatic system
More informationThe importance of partial discharge testing throughout the development and operation of power transformers
The importance of partial discharge testing throughout the development and operation of power transformers Ulrike Broniecki OMICRON Energy Solutions GmbH, Berlin Power transformers are exposed to intense
More informationCONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES
CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES Hao ZHANG, Transgrid, (Australia), hao.zhang@transgrid.com.au Zhao LIU, University of NSW, (Australia), z.liu@unsw.edu.au Toan
More informationTD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location
HAEFELY HIPOTRONICS Technical Document Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location P. Treyer, P. Mraz, U. Hammer Haefely Hipotronics, Tettex Instruments
More informationDigital Fault Recorder Deployment at HVDC Converter Stations
Digital Fault Recorder Deployment at HVDC Converter Stations On line continuous monitoring at HVDC Converter Stations is an important asset in determining overall system performance and an essential diagnostic
More information