GRUNDFOS DATA BOOKLET CRE, CRIE, CRNE. Frequency-controlled Multistage Centrifugal Pumps 50 Hz

Size: px
Start display at page:

Download "GRUNDFOS DATA BOOKLET CRE, CRIE, CRNE. Frequency-controlled Multistage Centrifugal Pumps 50 Hz"

Transcription

1 GRUNDFOS DATA BOOKLET Frequency-controlled Multistage Centrifugal Pums z

2 Contents General data E-ums Page Performance range, 9 min Page Performance range, 9 min Page Performance range, 9 min Page Performance range, 9 min Page 7 Performance range, min Page Tye keys Page 9 Codes Page 9 Product range Page Alications Page 9 Pum Page Curve conditions Page Performance curves Page Materials:, and Page Materials: CRE, CRNE and Page Materials: CRE, CRNE,, and 9 Page Oerating range of the shaft seal Page Maximum inlet ressure Page Maximum oerating ressure Page Selection and sizing Selection of ums Page 7 Alications Examles of alications Page Functions Overview of functions Page Control modes Page Control anel Page Setting by means of R Page Menu OPERATION Page Menu STATUS Page Menu INSTALLATION Page External forced-control signals Page External setoint signal Page Indicator lights and signal relay Page 9 Performance curves Technical data CRE, CRIE, CRNE Page CRE, CRIE, CRNE Page CRE, CRIE, CRNE Page CRE, CRNE Page CRE, CRIE, CRNE, min Page CRE, CRNE Page 7 CRE, CRIE, CRNE, min Page 7 CRE, CRNE Page 7 CRE, CRIE, CRNE, min Page CRE, CRNE Page CRE, CRNE Page 9 CRE 9, CRNE 9 Page 9 Electrical data Page 9 Pumed liquids Pumed liquids Page 99 List of umed liquids Page 99 Accessories Piework connection Page CRE counter flanges Page CRNE counter flanges Page PJE coulings Page FlexiClam base connections Page Clam coulings Page Potentiometer Page G-LON interface Page LiqTec Page R Page EMC-filter Page Sensors Page Installation General Page Electrical connection Page Additional rotection Page Other connections Page Cables Page

3 General data E-ums Grundfos ums equied with Grundfos MGE or MMGE motors are called E-ums. CRE, CRIE and CRNE ums belong to the E-ums family. Pums of a motor size u to and including. kw are fitted with the single-hase Grundfos MGE motor. Pums of a motor size of. kw or more are fitted with the three-hase MGE ( kw) or MMGE (- kw) motor. Both the MGE and MMGE motors offer the following features: Built-in PI-controller, otional connection to external control signals, setoint setting on the unit itself, and communication with the Grundfos remote control R. Through frequency control the MGE or MMGE motors enable continuously variable control of the motor seed. Thus the um can oerate in any duty oint in the range between um min. and max. erformance curves. Q [m³/h] with ressure sensor TM 9 99 CRE ums are sulied with or without ressure sensor fitted. Some CRE and CRNE versions are available with increased rated seed ( min ). The comlete roduct range is shown in the table below and in the erformance curves in the following ages: Pum tye Number of hases Pressure sensor fitted Rated seed [min ] Performance curves See age... CRE! Page CRE Page 9 CRE! Page and CRE Page and 7 CRE! Page CRE Page CRIE Page CRIE! Page 9 CRIE Page CRIE! Page CRNE Page CRNE! Page 9 CRNE Page and 7 CRNE! Page and CRNE Page For alications requiring a constant ressure, a CRE with ressure sensor fitted offers a comact solution which is easy to install and start u. The ressure required can be set directly on the um. It is also ossible to change um oerating mode from controlled to uncontrolled (constant seed). E-ums without sensor should be used when there is a need for uncontrolled oeration, or when control arameters are other than the um discharge ressure. Such arameters could be flow, temerature, differential temerature, ressure or differential ressure at any lace in the system. CRE, CRNE ums with increased seed ( min ) offer an ideal solution in alications requiring high head and small dimensions. The increased um seed means that for a given required head the number of um stages and thus the um dimensions can be reduced. Controlled oeration Uncontrolled oeration Uncontrolled oeration set Constant ressure Q Constant curve Q TM 9 9 Constant curve Q TM The fitting of a sensor at a later stage oens the ossibility of control on the basis of ressure, differential ressure, temerature, differential temerature or flow.

4 General data Pressure sensor Performance range, 9 min 9 min Q [m³/h] 7 9 Q [l/s] TM 9 7

5 General data CRE, CRNE Pressure sensor Performance range, 9 min CRE, CRNE 9 min ISO 99 Annex A Q [m³/h] 7 9 Q [l/s] TM

6 - General data Performance range, 9 min 9 min / / 9 - Q [m³/h] 7 9 Q [l/s] TM 9 7

7 General data CRE, CRNE Performance range, 9 min CRE, CRNE 9 min ISO 99 Annex A Q [m³/h] 7 9 Q [l/s] TM 7

8 General data CRE, CRNE Performance range, min CRE / CRNE min / 9 7 Q [m³/h] 7 9 Q [l/s] TM

9 General data Tye keys, and Examle CRE AN -FGJ -A -E - UBE Tye range: Rated flow [m /h] Number of imellers Code for um version Code for ie connection Code for materials Code for rubber arts Code for shaft seal CRE, CRNE and Examle CRE - / -A -FJ -G - AUUE Tye range: CRE, CRNE Rated flow rate [m /h] Number of stages x Number of imellers (only used if the um has fewer imellers than stages) Code for um version Code for ie connection Code for materials Code for shaft seal and rubber arts CRE, CRNE,, and 9 Examle CRE -AN -F -A -E - EUBE Tye range: CRE, CRNE Codes Examle Pum version A Basic version J Pum with different max. seed " N Fitted with sensor Pie connection A Oval flange CA FlexiClam F flange G ANSI flange J JIS flange N Changed diameter of orts P PJE couling Materials A Basic version G Stainless steel arts of. I Stainless steel arts of. Code for rubber arts in um E EPDM V FKM Shaft seal A O-ring seal with fixed driver B Rubber bellows seal E Cartridge with O-ring Balanced cartridge seal B Carbon, synthetic resin-imregnated U Cemented tungsten carbide E EPDM V FKM A - F - A - E - B U B E B U B E " The outut frequency of the frequency converter of the motor differs from the standard z. In this situation the frequency is arox. 7 z. Rated flow rate [m /h] Number of stages Number of reduced diameter imellers Code for um version Code for ie connection Code for materials Code for rubber arts Code for shaft seal 9

10 Order data CRE 9 min CRE, CRE, CRE, 9 min (without sensor) ower P Suly voltage / z [V] Full load current I / [A] CRE, CRE, CRE, 9 min (without sensor) A-FGJ-A-V /ANSI/JIS flange Shaft seal Without sensor A-A-A-V Oval flange Shaft seal UBV UUV UBV UUV CRE -.7 x CRE -7.7 x CRE. x CRE.7 x CRE 9. x CRE -. x CRE -. x CRE -. x CRE -.7 x CRE -7. x CRE.7 x CRE. x CRE 9. x CRE -. x CRE -9. x CRE -. x CRE -.7 x CRE -. x CRE -. x CRE. x CRE. x CRE -. x CRE -9. x CRE -. x ower P Suly voltage / z [V] Full load current I / [A] A-FGJ-A-E /ANSI/JIS flange Shaft seal Without sensor A-A-A-E Oval flange Shaft seal UBE UUE UBE UUE CRE -.7 x CRE -7.7 x CRE. x CRE.7 x CRE 9. x CRE -. x CRE -. x CRE -. x CRE -.7 x CRE -7. x CRE.7 x CRE. x CRE 9. x CRE -. x CRE -9. x CRE -. x CRE -.7 x CRE -. x CRE -. x CRE. x CRE. x CRE -. x CRE -9. x CRE -. x

11 Order data CRE 9 min CRE, CRE, CRE, 9 min (with sensor) ower P Suly voltage / z [V] Full load current I / [A] CRE, CRE, 9 min (without sensor / with sensor) AN-FGJ-A-E /ANSI/JIS flange Shaft seal With sensor AN-A-A-E Oval flange Shaft seal UBE UUE UBE UUE CRE -.7 x CRE -7.7 x CRE. x CRE.7 x CRE 9. x CRE -. x CRE -. x. 9 9 CRE -. x CRE -.7 x CRE -7. x CRE.7 x CRE. x CRE 9. x CRE -. x CRE -9. x CRE -. x. 9 9 CRE -.7 x CRE -. x CRE -. x CRE. x CRE. x CRE -. x CRE -9. x CRE -. x ower P Suly voltage / z [V] Full load current I / [A] A-A-A Oval flange Without sensor A-N-A Oval flange A-F-A flange With sensor AN-F-A flange Shaft seal Shaft seal Shaft seal BUBE AUUE BUBV AUUV BUBE AUUE CRE -/.7 x CRE -.7 x CRE -. x CRE -. x CRE -. x CRE -. x CRE -. x CRE. x CRE. x CRE. x. 9 7 CRE. x. 9 7 CRE - 7. x. 9 7 CRE -/. x CRE -. x CRE -. x CRE -. x CRE - 7. x

12 Order data CRE 9 min CRE, CRE, CRE, CRE 9, 9 min (without sensor / with sensor) Without sensor With sensor A-F-A-V AN-F-A-E ower Suly voltage Full load current flange flange P / z [V] I / [A] Shaft seal Shaft seal EUBV EUUV EUBE EUUE CRE. x CRE. x CRE --. x CRE -. x CRE -. x CRE - 7. x CRE -. x CRE -. x CRE -7. x CRE -. x CRE -9. x CRE. x CRE. x CRE. x CRE. x CRE. x CRE --. x CRE - 7. x CRE -. x CRE -. x CRE -. x CRE -. x CRE. x CRE. x CRE x CRE -. x CRE -. x CRE --. x CRE -. x CRE 9. x CRE 9 7. x CRE 9--. x CRE 9-. x CRE 9--. x CRE 9-. x

13 Order data CRIE 9 min CRIE, CRIE, CRIE, 9 min (without sensor) ower P Suly voltage / z [V] Full load current I / [A] CRIE, CRIE, CRIE, 9 min (with sensor) A-FGJ-I-V /ANSI/JIS flange Without sensor A-P-I-V PJE couling A-CA-I-V FlexiClam Shaft seal Shaft seal Shaft seal UBV UUV UBV UUV UBV UUV CRIE -.7 x CRIE -7.7 x CRIE. x CRIE.7 x CRIE 9. x CRIE -. x CRIE -. x CRIE -. x CRIE -.7 x CRIE -7. x CRIE.7 x CRIE. x CRIE 9. x CRIE -. x CRIE -9. x CRIE -. x CRIE -.7 x CRIE -. x CRIE -. x CRIE. x CRIE. x CRIE -. x CRIE -9. x CRIE -. x ower P Suly voltage / z [V] Full load current I / [A] AN-FGJ-I-E /ANSI/JIS flange With sensor AN-P-I-E PJE couling AN-CA-I-E FlexiClam Shaft seal Shaft seal Shaft seal UBE UUE UBE UUE UBE UUE CRIE -.7 x CRIE -7.7 x CRIE. x CRIE.7 x CRIE 9. x CRIE -. x CRIE -. x CRIE -. x CRIE -.7 x CRIE -7. x CRIE.7 x CRIE. x CRIE 9. x CRIE -. x CRIE -9. x CRIE -. x CRIE -.7 x CRIE -. x CRIE -. x CRIE. x CRIE. x CRIE -. x CRIE -9. x CRIE -. x

14 Order data CRNE 9 min CRNE, CRNE, CRNE, 9 min (without sensor) ower P Suly voltage / z [V] Full load current I / [A] CRNE, CRNE, CRNE, 9 min (with sensor) A-FGJ-G-V /ANSI/JIS flange Without sensor A-P-G-V PJE couling A-CA-G-V FlexiClam Shaft seal Shaft seal Shaft seal UBV UUV UBV UUV UBV UUV CRNE -.7 x CRNE -7.7 x CRNE. x CRNE.7 x CRNE 9. x CRNE -. x CRNE -. x CRNE -. x CRNE -.7 x CRNE -7. x CRNE.7 x CRNE. x CRNE 9. x CRNE -. x CRNE -9. x CRNE -. x CRNE -.7 x CRNE -. x CRNE -. x CRNE. x CRNE. x CRNE -. x CRNE -9. x CRNE -. x ower P Suly voltage / z [V] Full load current I / [A] AN-FGJ-G-E /ANSI/JIS flange With sensor AN-P-G-E PJE couling AN-CA-G-E FlexiClam Shaft seal Shaft seal Shaft seal UBE UUE UBE UUE UBE UUE CRNE -.7 x CRNE -7.7 x CRNE. x CRNE.7 x CRNE 9. x CRNE -. x CRNE -. x CRNE -. x CRNE -.7 x CRNE -7. x CRNE.7 x CRNE. x CRNE 9. x CRNE -. x CRNE -9. x CRNE -. x CRNE -.7 x CRNE -. x CRNE -. x CRNE. x CRNE. x CRNE -. x CRNE -9. x CRNE -. x

15 Order data CRNE 9 min CRNE, CRNE, 9 min (without sensor) ower P Suly voltage / z [V] Full load current I / [A] A-P-G PJE couling Shaft seal Without sensor A-FJ-G /JIS flange Shaft seal BUBV AUUV BUBV AUUV CRNE -/.7 x -.-. CRNE -.7 x CRNE -. x -.-. CRNE -. x CRNE -. x CRNE -. x CRNE -. x CRNE. x CRNE. x CRNE. x. 7 7 CRNE. x. 7 7 CRNE - 7. x. 7 7 CRNE -/. x CRNE -. x CRNE -. x CRNE -. x CRNE - 7. x. 7 7

16 Order data CRNE 9 min CRNE, CRNE, CRNE, CRNE 9, 9 min (without sensor) Without sensor A-F-G-V ower Suly voltage Full load current flange P / z [V] I / [A] Shaft seal EUUV EUBV CRNE. x CRNE. x CRNE --. x CRNE -. x CRNE -. x CRNE - 7. x CRNE -. x CRNE -. x CRNE -7. x CRNE -. x CRNE -9. x CRNE. x CRNE. x CRNE. x CRNE. x CRNE. x CRNE --. x CRNE - 7. x CRNE -. x CRNE -. x CRNE -. x CRNE -. x CRNE. x CRNE. x CRNE x CRNE -. x CRNE -. x CRNE --. x CRNE -. x CRNE 9. x CRNE 9 7. x CRNE 9--. x CRNE 9-. x CRNE 9--. x CRNE 9-. x

17 Order data CRE, CRNE min CRE, CRE, CRE, min (without sensor) ower P Suly voltage / z [V] Full load current I / [A] CRE, CRE, CRE, min (with sensor) CRNE, CRNE, CRNE, min (without sensor) J-F-A flange Shaft seal Without sensor J-F-A-V flange Shaft seal BUBV AUUV EUBV EUUV CRE -. x CRE -. x CRE - 7. x CRE -/. x CRE. x CRE 7. x ower P Suly voltage / z [V] Full load current I / [A] JN-F-A flange Shaft seal With sensor JN-F-A-E flange Shaft seal BUBE AUUE EUBE EUUE CRE -. x CRE -. x CRE - 7. x CRE -/. x CRE. x CRE 7. x ower P Suly voltage / z [V] Full load current I / [A] J-P-G PJE couling Without sensor J-F-G flange J-F-G-V flange Shaft seal Shaft seal Shaft seal BUBV AUUV BUBV EUUV EUBV CRNE -. x CRNE -. x CRNE - 7. x CRNE -/. x CRNE. x CRNE 7. x

18 General data Product range Range CRE CRE CRE CRE CRE CRE CRE CRE CRE 9 Rated flow rate [m /h] 9 Flow range [m /h] Max. ressure [bar] ower Temerature range [ C] to + to + Max. um efficiency [%] Version CRE: Cast iron and!!!!!!!!! stainless steel./aisi CRIE: Stainless steel./aisi!!! CRNE: Stainless steel./aisi!!!!!!!!! CRE ie connection Oval flange (BSP) R R R ¼ Oval flange (BSP) on request R ¼ R ¼ R Flange DN / DN DN / DN DN / DN R ½ R DN DN DN DN DN DN Flange - on request DN DN DN DN CRIE ie connection Oval flange (BSP) R R R ¼ Oval flange (BSP) on request R ¼ R ¼ R Flange DN / DN DN / DN DN / DN PJE couling (Vitaulic)!!! Clam couling!!! CRNE ie connection Flange DN / DN DN / DN DN / DN DN DN DN DN DN DN Flange - on request DN DN DN DN PJE couling (Vitaulic)!!!!! Clam couling!!!!!

19 General data Alications The CRE series is a multi-urose um range suitable for a variety of different alications demanding reliable and cost-efficient suly. CRE handles a variety of liquids from otable water to industrial liquids within a very wide temerature, flow and ressure scale. Below is a list reresenting some general examles of alications: Water suly Filtration and transfer at waterworks Distribution from waterworks Pressure boosting in mains Pressure boosting in high-rise buildings, hotels, etc. Pressure boosting for industrial water suly. Industry Pressure boosting in... rocess water systems, washing and cleaning systems, high-ressure washdown systems, vehicle washing tunnels, fire fighting systems. Liquid transfer in... cooling and air-conditioning systems (refrigerants), boiler feed and condensate systems, machine tools (cooling lubricants), aquafarming. Transfer of... oils and alcohols, acids and alkalis. Water treatment Ultra-filtration systems Reverse osmosis systems Softening, ionising, demineralizing systems Distillation systems Searators Swimming baths. Irrigation Field irrigation (flooding) Srinkler irrigation Dri-feed irrigation. 9

20 General data Pum The CRE um is a non-self-riming, vertical, multistage, centrifugal um fitted with a Grundfos MGE or MMGE motor. The um consists of a base and a um head. The chamber stack and the outer sleeve are secured between the um head and the base by means of staybolts. The base has suction and discharge orts on the same level (in-line). All ums are equied with a maintenance-free mechanical shaft seal. Qmin [%] CR t [ C] TM. If the umed liquid density and/or viscosity is higher than that of water, it may be necessary to use a motor with a higher erformance. Shaft seal Base Curve conditions Pum head Staybolts The guidelines below aly to the erformance curves from age :. All curves state mean values according to ISO 99, Annex A. If secification of minimum erformance is required, individual measurements must be made. The curves aly to a kinematic viscosity of mm²/s ( cst). Measurements were made at a water temerature of C. Test liquid: Air-free water.. The conversion between head (m) and ressure (mpa) alies to water with a density of ρ = kg/m³. In the case of a density other than kg/ m³, the discharge ressure is roortional to the density. The ums should not be used at a minimum flow rate lying outside the areas indicated by the boldfaced curves due to danger of um overheating. The curve below shows the minimum flow rate as a ercentage of the nominal flow rate in relation to the liquid temerature. The dotted line shows a um fitted with a cool to assembly. TM Performance curves The curve charts on the following ages show Q-curves and QP -curves for %, 9%, %, 7%, %, % and % seed. In the Q-chart the %-curve corresonds to the curve for a um fitted with a standard fixed seed motor. In rincile ums with MGE or MMGE motors have an infinite number of erformance curves each reresenting a secific seed. The P chart states um inut ower deending on the flow and the chosen seed. Q [l/s] % % 9 % % 7 % % % Q [m³/h] 7 % % % % 9 % Q [m³/h] TM 7

21 General data CRE, and CRIE, CRNE, and 9 7 TM 9 Materials:, and 7 9 TM 9 Materials: CRE Pos. Descrition Materials /EN Nr. AISI/ASTM Pum head Cast iron EN-GJL- EN-JL ASTM B Shaft Stainless steel. AISI Imeller Stainless steel. AISI Chamber Stainless steel. AISI Outer sleeve Stainless steel. AISI O-ring for outer 7 sleeve Base EPDM or FKM Cast iron EN-GJL- 9 Neck ring PTFE Shaft seal Tye cartridge Rubber arts EPDM or FKM EN-JL ASTM B Materials: CRIE, CRNE Pos. Descrition Materials /EN Nr. AISI/ASTM Pum head Cast iron EN-GJL- EN-JL ASTM B Pum head cover Stainless steel. CF M Shaft Stainless steel.. AISI AISI 9 7 O-ring for outer sleeve EPDM or FKM Base Stainless steel. CF M 9 Neck ring PTFE Shaft seal Tye cartridge Base late Cast iron EN-GJL- " EN-JL ASTM B Rubber arts EPDM or FKM CRIE Imeller Stainless steel. AISI Chamber Stainless steel. AISI Outer sleeve Stainless steel. AISI CRNE Imeller Stainless steel. AISI Chamber Stainless steel. AISI Outer sleeve Stainless steel. AISI "Stainless steel on request

22 General data CRE, CRNE CRE and CRNE and 9 7 TM Materials: CRE, CRNE and 9 7 TM Materials: CRE Materials: CRNE Pos. Descrition Materials /EN Nr. AISI/ASTM Pum head Cast iron EN-GJL- Shaft Stainless steel EN-JL..7 ASTM B AISI AISI Imeller Stainless steel. AISI Chamber Stainless steel. AISI Outer sleeve Stainless steel. AISI 7 Gasket for outer sleeve Asbestos-free fibre Base Cast iron EN-GJL- 9 Neck ring PTFE Shaft seal Rubber arts EPDM or FKM EN-JL ASTM B Pos. Descrition Materials /EN Nr. AISI/ASTM Pum head Cast iron EN-GJL- EN-JL ASTM B Pum head cover Stainless steel. AISI Shaft Stainless steel.. AISI AISI 9 Imeller Stainless steel. AISI Chamber Stainless steel. AISI Outer sleeve Stainless steel. AISI 7 Gasket for outer sleeve Asbestos-free fibre Base Stainless steel. AISI 9 Neck ring PTFE Shaft seal Base late Cast iron EN-GJL- " Rubber arts EPDM or FKM " Stainless steel on request. EN-JL ASTM B

23 General data CRE, CRNE CRE,, and 9 CRNE,, and TM Materials: CRE, CRNE,, and TM 7 Materials: CRE Pos. Descrition Materials /EN Nr. AISI/ASTM Pum head Cast iron EN-GJS--7 EN-JS ASTM -- stool Cast iron EN-GJL- EN-JL ASTM B Shaft Stainless steel.7 AISI Imeller Stainless steel. AISI Chamber Stainless steel. AISI Outer sleeve Stainless steel. AISI O-ring for outer 7 sleeve Base EPDM or FKM Cast iron EN-GJS--7 9 Neck ring Carbon-grahite filled PTFE Shaft seal Bearing ring Bronze Bottom bearing ring TC/TC" Rubber arts EPDM or FKM " TC = Tungsten Carbide (cemented) EN-JS ASTM -- Materials: CRNE Pos. Descrition Materials /EN Nr. AISI/ASTM Pum head Stainless steel. CF M stool Cast iron EN-GJL- EN-JL ASTM B Shaft Stainless steel. Imeller Stainless steel. AISI Chamber Stainless steel. AISI Outer sleeve Stainless steel. AISI 7 O-ring for outer sleeve EPDM or FKM Base Stainless steel. CF M 9 Neck ring Shaft seal Bearing ring Bottom bearing ring Carbon-grahite filled PTFE Chlorosulfonated olyethylene TC/TC " Base late Cast iron EN-GJS--7 Stainless steel Rubber arts EPDM or FKM " TC = Tungsten Carbide (cemented) EN-JS ASTM --

24 General data Oerating range of the shaft seal The actual oerating range of the shaft seal deends on oerating ressure, um tye, tye of shaft seal and liquid temerature. The following curves aly to clean water and water containing glycol. For other liquids, see recommended shaft seals in the "List of umed liquids", age 99., and [bar] Shaft seal UUE UUV UBE UUE UUV CRE, CRNE and UBE / UBV UUE / UUV - - t [ C] Descrition O-ring (cartridge) (balanced seal), TC/TC", EPDM O-ring (cartridge) (balanced seal), TC/TC", FKM O-ring (Cartridge), (balanced seal), TC/carbon, EPDM O-ring /Cartridge), (balanced seal), UBV TC/carbon, FKM " TC = Tungsten carbide (cemented) UBE TM 9 9 Max. tem. range [ C] to +9 to +9 to + to +9 CRE, CRNE,, and 9 [bar] Shaft seal Descrition " TC = Tungsten carbide (cemented) ""On request Max. ress. [bar] TM 9 Max. tem. range [ C] EUUE O-ring (Cartridge), TC/TC", EPDM to +9 EUUV O-ring (Cartridge), TC/TC, FKM to +9 EUBE O-ring (Cartridge), TC/carbon, EPDM to + EUBV O-ring (Cartridge), TC/Carbon, FKM to +9 EUE O-ring (Cartridge), TC/hybrid, EPDM EUV O-ring (Cartridge), TC/hybrid, FKM EUBE O-ring (Cartridge), TC/carbon, EPDM UBE UBV EUUE EUUE EUUV UBE / UBV EUBE / EUBV EUUE / EUUV O-ring (Cartridge) (balanced seal), TC/carbon, EPDM O-ring (Cartridge) (balanced seal), TC/carbon, FKM UBE EUBE - - t [ C] to +9"" to +9"" + to +"" to +"" to +9"" [bar] RUUE RUUV AUUE / AUUV AUUE / AUUV BUBE / BUBV AUUE BUBE - - t [ C] TM 9 Shaft seal Descrition Max. tem. range [ C] RUUE O-ring (balanced seal), TC/TC", EPDM to +9 RUUV O-ring (balanced seal), TC/TC, FKM to +9 AUUE O-ring, TC/TC, EPDM to + AUUV O-ring, TC/TC, FKM to +9 BUBE Bellows, TC/carbon, EPDM to + BUBV Bellows, TC/carbon, FKM to +9 " TC = Tungsten carbide (cemented)

25 General data Maximum inlet ressure The following table shows the maximum ermissible inlet ressure. owever, the actual inlet ressure + the ressure against a closed valve must always be lower than the maximum ermissible oerating ressure CRE, CRNE -/ CRE, CRNE -/ CRE, CRNE CRE, CRNE CRE, CRNE CRE, CRNE [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] [bar] Examle of oerating and inlet ressures The values for oerating and inlet ressures shown in the tables must not be considered individually but must always be comared, see the following examles: Examle : The following um tye has been selected: CRE A-A-A Max. oerating ressure: bar Max. inlet ressure: bar Discharge ressure against a closed valve:. bar, see age. This um is not allowed to start at an inlet ressure of bar, but on the other hand at an inlet ressure of.. =. bar. Examle : The following um tye has been selected: CRE - A-A-A Max. oerating ressure: bar Max. inlet ressure: bar Discharge ressure against a closed valve:. bar, see age. This um is allowed to start at an inlet ressure of bar as the discharge ressure against a closed valve is only. bar which results in an oerating ressure of. +. = 7. bar. On the contrary, the max. oerating ressure of this um is limited to 7. bar as a higher oerating ressure will require an inlet ressure of more than bar.

26 General data Maximum oerating ressure Oval PJE-Clam- TM 79 TM Max. ermissible oerating ressure Liquid temerature range Max. ermissible oerating ressure Liquid temerature range [bar] C - + C [bar] C - + C [bar] C - + C [bar] C - + C [bar] C - + C [bar] C - + C CRE -/, CRNE -/ CRE, CRNE [bar] C - + C CRE, CRNE -/ CRE, CRNE [bar] C - + C CRE, CRNE CRE, CRNE - [bar] C - + C CRE, CRNE -/ CRE, CRNE - [bar] C - + C CRE, CRNE CRE, CRNE -7 [bar] C - + C CRE, CRNE - CRE, CRNE [bar] C - + C CRE, CRNE CRE, CRNE - [bar] C - + C CRE, CRNE - [bar] C - + C CRE, CRNE CRE, CRNE - [bar] C - + C CRE, CRNE 9 CRE, CRNE 9- [bar] C - + C

27 Selection and sizing Selection of ums Pum size and efficiency The um must be able to fulfil the max. required flow and ressure, see oint,, on the curve. : Max. head : Max. flow : Duty oint Normally, E-ums are used in alications characterized by a variable load (flow). Consequently, it is not ossible to select a um which is constantly oerating at otimum efficiency. In order to ensure otimum oerating economy, the um should be selected on the basis of the following criteria: The max. required duty oint (see oint in the chart) should be as close as ossible to the % Qcurve of the um. Point should be ositioned so that is close to the max. oint of the % curve (see oint in the chart). As a rule of thumb ies should be dimensioned in such a way that the velocity of the liquid does not exceed to. m/sec. % 9 % % 7 % % % CRE / CRNE Q [m³/h] % Q [m³/h] The um must be able to fulfil the flow and ressure requirements. Check that the highest efficiency falls within the marked duty range. TM 99 Material The material variant () should be selected on the basis of the liquid to be umed. The roduct range covers three basic tyes. The CRE, CRIE um tyes are suitable for clean, nonaggressive liquids such as otable water, oils, etc. The CRNE um tye is suitable for industrial liquids (see "List of umed liquids", age 99). TM 99 7

28 Selection and sizing Pum connection Selection of um connection deends on rated ressure and iework. To meet any requirement the CRE, CRIE and CRNE ums offer a wide range of flexible connections such as: Oval flange (BSP) flange PJE couling Clam couling Other connections on request. Oval PJE TM Shaft seal As standard, the CRE range is fitted with a Grundfos shaft seal suitable for the most common alications. The following three key arameters must be taken into account, when selecting the shaft seal: tye of umed liquid liquid temerature and maximum ressure. Grundfos offers a wide range of shaft seal variants to meet secific demands (see "List of umed liquids", age 99). TM Inlet ressure and oerating ressure It should be checked whether the ressure conditions are fulfilled. The limit values stated on age and must not be exceeded as regards... maximum inlet ressure maximum oerating ressure. TM

29 Selection and sizing Minimum inlet ressure - Calculation of the inlet ressure "" is recommended when... the liquid temerature is high the flow is significantly higher than the rated flow water is drawn from deths water is drawn through long ies inlet conditions are oor. To avoid cavitation, make sure that there is a minimum ressure on the suction side of the um. The maximum suction lift "" in metres head can be calculated as follows: = b x. f v s b = Barometric ressure in bar. (Barometric ressure can be set to bar). In closed systems, b indicates the system ressure in bar. = Net Positive Suction ead in metres head. (To be read from the curve at the highest flow the um will be delivering). f = Friction loss in suction ie in metres head. (At the highest flow the um will be delivering.) v = Vaour ressure in metres head. (To be read from the vaour ressure scale. " v " deends on the liquid temerature "T m "). s = Safety margin = minimum. metres head. If the "" calculated is ositive, the um can oerate at a suction lift of maximum "" metres head. If the "" calculated is negative, an inlet ressure of minimum "" metres head is required. f Pb v tm ( C), 9,,, 7,,,,,,,,,, Check that the um is not and will not be exosed to cavitation. v (m) TM 97 - TM

30 Alications Examles of alications CRE, CRIE and CRNE ums are the ideal solution in a number of alications characterized by a need for variable flow at constant ressure. The ums are suited for water suly systems and ressure boosting, but also industrial alications such as ressure boosting in water treatment systems are obvious for these ums. Deending on the nature of the alication, the ums offer energy savings, increased comfort or imroved rocessing. A comact one-um booster A comact booster unit is the CRE featuring an integrated sensor and a small diahragm tank. These comonents make u a comlete ressure boosting system which is indeendent of the load and maintains a constant ressure. CRE incororates a sto function to ensure that the um automatically stos if the water demand dros to a very low level or disaears altogether. The method gives good total oerating economy irresective of the water demand, and the um is not subjected to overheating and the subsequent risk of damage to the shaft seal. CRE as the basis of bigger ressure boosting systems Pressure boosting systems based on arallel couled ums of which one or more are CRE ums, also available from Grundfos. This range of boosters has the name ydro and incororates E-ums tye CRE as a very imortant element. The ydro E range includes booster systems solely with seed-controlled ums tye CRE and systems with one or more seed-controlled CRE ums. Two examles: TM TM & TM A ydro E booster system can be used for a number of alications. For further information, see the ydro data booklet or contact Grundfos. E-ums in the service of industry Countless ums are oerating in industry today, and for many of them seed regulation would be an advantage. In industrial cleaning and similar alications a further advantage can be gained by ensuring a constant ressure. Other alications such as circulation of cooling water, ressure boosting or other rocess related um alications would in many cases be good alications for E- ums. Water treatment installation Water treatment is an obvious alication for a seedcontrolled CRNE um. The combination of a stainless steel um and a seed-controlled um makes it ossible to satisfy material secifications, while roviding otimised oerations, minimising energy consumtion, etc. A CRNE um is very suitable as the high-ressure um in a reverse osmosis lant. If exosed to varying umed liquid temerature and thus varying viscosity an uncontrolled um will yield a varying flow. An E-um, however, controlled by a flow sensor ensures a constant flow resulting in imroved system erformance of the reverse osmosis lant. In a system with a seed-controlled suly um a beginning choking u of the filters will not result in a lower caacity of the system. The um will just seed u and maintain a constant flow to the clean water tank. An E-um will also be advantageous as suly um for the clean water tank. A CRE or a CRNE with a ressure transmitter connected can ensure a comfortable constant-ressure water suly. The built-in sto function will ensure that the um is stoed when there is low or no flow in the system. TM

31 Functions Overview of functions E-ums/functions TM 7 9 TM 9 9 with sensor without sensor Setting via control anel: Setoint Start/sto Max. curve Min. curve Reading via control anel: Setoint Oerating indication Fault indication Setting via R: Setoint Start/sto Max. curve Min. curve Controlled/uncontrolled PI-controller Signal relay Oerating range Sto function Reading via R: Setoint Oerating indication Pum status TM Connection to building management system The ums have inuts for BUS communication. The ums can be controlled and monitored via these inuts from a Building Management System or other external control systems. TM 9 External signals. Inuts: Setoint Start/sto Sensor Fitted Digital signals: Max. curve Min. curve External fault Flow switch Oututs: Signal

32 Functions Control modes with sensor CRE ums with integrated ressure sensor enable control of the ressure sulied by the um. The um can be set to two control modes, i.e. constant ressure mode or constant-curve mode. In constant-ressure mode the um will maintain a constant ressure on the discharge side of the um, irresective of the flow. In constant-curve mode, the um is not controlled. The curve can be set within the range from min. curve to max. curve. Controlled oeration Uncontrolled oeration without sensor ums can be connected to an external sensor enabling control of ressure, differential ressure, temerature, differential temerature or flow. ums can be set to two control modes, controlled or uncontrolled oeration. In controlled oerating mode the um is automatically oerating according to the desired setoint of the control arameter. The illustration below shows a um with flow control as an examle of controlled oeration. In uncontrolled oerating mode the um oerates according to the constant curve set. Controlled oeration Uncontrolled oeration set Constant ressure Q Q Constant curve The ums are set to constant-ressure mode from factory. Besides normal duty (constant-ressure and constantcurve) the oerating modes Sto, Min. or Max. are available. TM 9 9 Qset Constant flow The ums are set to uncontrolled oeration from factory. Besides normal duty (constant-flow and constantcurve) the oerating modes Sto, Min. or Max. are available. Q Constant curve Q TM 997 Max. Max. Min. Q TM 7 99 Min. Q TM 7 99 Max. curve mode can be used in connection with venting during installation. Min. curve mode can be used in eriods requiring very low flow. All oerating modes (Sto, Normal, Min., Max.) can be set using the oerating anel on the um terminal box. If the suly voltage to the um is disconnected, um settings are saved. The remote control R offers additional osibilities of settings and status readings. The ums are set to constant ressure from factory. The setoint value corresonds to % of the sensor measuring range. The max. curve can for instance be used in connection with the venting rocedure during installation. The min. curve can be used in eriods in which a minimum flow is required. The oerating modes (Sto, Normal, Min., Max.) can all be set on the control anel on the um terminal box. If the electricity suly to the um is disconnected, the um setting will be stored. The remote control R offers additional ossibilities of setting and status dislays. The ums are set to uncontrolled oeration from factory. The setoint value corresonds to %.

33 Functions Control anel The control anel on the um terminal box incororates the following: Buttons, "+" and " ", for setoint setting. Light fields, yellow, for setoint indication. Indicator lights, green (oeration) and red (fault). Examle: Pum in uncontrolled oerating mode: In uncontrolled oerating mode, the um erformance is set within the range from min. to max. curves. Light fields Buttons TM 77 9 Indicator lights Setoint setting The um setoint is set by ressing the "+" or " " buttons. The light fields on the control anel will indicate the setoint set. See the following two examles. Examle: Pum in controlled-oerating mode (ressure control). The illustration below shows that the light fields and are activated, indicating a desired setoint of bar with a sensor measuring range from to bar. The setting range is equal to the sensor measuring range (see sensor namelate). [bar] TM 7 9 Setting to max. curve duty Press "+" continuously to change over to the max. curve of the um (to light field flashes). To change back, ress " " continuously until the desired setoint is indicated. Q Max. curve Setting to min. curve duty Press " " continuously to change over to the min. curve of the um (bottom light field flashes). To change back, ress "+" continuously until the desired setoint is indicated. TM 7 9 TM 77 9 Q Min. curve TM 7 9 Start/sto of um Sto the um by continuously ressing " " until none of the light fields are activated and the green indicator light flashes. Start the um by continuously ressing "+" until the desired head is indicated.

34 Functions Setting by means of R The um is designed for wireless communication with the Grundfos remote control R. The communication is effected by means of infra-red light. The um transmitter and receiver unit is laced in the control anel. R offers additional ossibilities of um settings and status readings. The dislays are divided into four arallel menus:. GENERAL. OPERATION. STATUS. INSTALLATION TM 7. GENERAL. OPERATION. STATUS. INSTALLATION " " " Only shown for CRE ums without sensor fitted from factory..9. " TM

35 Functions Menu OPERATION Using the R remote control it is ossible to make the following oerating mode settings. Menu STATUS The dislays aearing in this menu are status dislays only. It is not ossible to change or set values.. Setoint setting In this dislay, the desired setoint can be set. The tolerances are stated as a guide in % of the maximum values of the arameters.. Dislay of actual setoint Tolerance: ±% In controlled oerating mode the setting range is equal to the sensor measuring range e.g. to m. In uncontrolled oerating mode the setoint is set in % of max. erformance. The setting range lies between the min. and max. curves.. Setting of oerating mode. Fault indications Select one of the following oerating modes: Sto Min. Normal (duty) Max. If the um is faulty, the cause will aear in the dislay. Too high motor temerature Undervoltage Overvoltage Phase failure (~ ums only) Mains suly failure (~ ums only) Too many restarts (after faults) Overload Sensor signal outside signal range Setoint signal outside signal range Other fault. A fault indication can be reset in this dislay if the cause of the fault has disaeared... Alarm log If faults have been indicated, the last five fault indications will aear in the alarm log. "Alarm log " shows the newest/ latest fault. This dislay shows the actual setoint and the external setoint in % of the range from the minimum value to the setoint set. See "External setoint signal" age.. Dislay of oerating mode Sto Min. Normal (duty) Max. It also shows where this oerating mode was selected (R, um, BUS, External, Stofunction).. Dislay of actual value. Dislay of actual seed. Dislay of actual ower This dislay shows the actual oerating mode: Tolerance: ±% Tolerance: ±% Tolerance: ±% The ower consumtion value is accumulated from the beginning of um oeration, and it cannot be reset. The examle shows the fault indication "Undervoltage", the fault code and the number of minutes the um has been connected to the electricity suly after the fault occurred. The time cannot be dislayed for the three-hase ums.

36 Functions. Dislay of oerating hours Tolerance: ±% The value of oerating hours is an accumulated value and cannot be reset. Menu INSTALLATION. Selection of control mode Select one of the following control modes: with sensor Constant ressure Constant curve CRE, CRIE CRNE without sensor Controlled Uncontrolled. Setting of controller The gain (K) is set within the range from. to. The integral-action time (T i ) is set within the range from. to s. If s is selected, the controller will function as a P-controller The gain (K) and intergral-action time (T i ) of the builtin PI-controller can be changed, should factory settings be inadequate. Furthermore, it is ossible to set the controller to inverse control (if the setoint is increased, the seed will be reduced). In the case of inverse control, the gain (K) must be set within the range from. to.. Selection of external setoint signal Select one of the following tyes: - V (~ ums only) V - ma - ma Not active. If "Not active" is selected, the setoint set by means of the R or the control anel will aly.. Selection of fault, oerating or ready signal relay Note: Alies only to without sensor. The signal relay can be set to activation by: Fault (fault indication), Oeration (oerating indication), Ready (ready indication).. Locking of the buttons on the um The buttons "+" and " " on the um can be set to: Active, Not active.. Allocation of um number A number between and can be allocated to the um. In the case of BUS communication, a number must be allocated to each um..7 Selection of function for digital inut Select one of the following functions: Min. (min. curve) Max. (max. curve) Ext. fault (external fault) Flow switch. The selected function is activated by closing the contact between the following terminals: and 9 of single-hase ums and of three-hase ums. See "Other connetions" age. Min.: When the inut is activated, the um is oerating according to the min. curve. Max.: When the inut is activated, the um is oerating according to the max. curve. Ext. fault: When the inut is activated, a timer is started. If the inut is activated for more than secs., the um is stoed and a fault is indicated. If the connection is disconnected for more than secs., the fault condition will cease and the um can be restarted manually by resetting the fault indication. The tyical alication will be detection of missing inlet ressure or water shortage by means of a ressure switch installed on the suction side of a um. Flow switch: When this function is active, the um will be stoed when a connected flow switch detects a low flow. It is only ossible to use this function if the um is connected to a ressure sensor. When the inut is activated for more than secs., the sto function incororated in the um will take over, see "Setting of sto function" age 7.

37 Functions. Setting of sto function The sto function can be set to: Active Not active. When the sto function is active, the um will be stoed at very low flows to avoid unnecessary ower consumtion. It is only ossible to use this function if the um is connected to a ressure sensor. There are two ossibilities of low-flow detection:. A "low-flow detector" which automatically starts functioning if no flow switch is chosen/connected to the digital inut. The um will check the flow regularly by reducing the seed for a short time, thus checking the change in ressure. If there is no or a small change in ressure, the um will detect a low flow.. A flow switch connected to the digital inut. When the inut is activated for more than secs., the sto function of the um will take over. Unlike the built -in low-flow detector, the flow switch measures the minimum flow at which the um must sto. The um will not check the flow regularly by reducing the seed. When the um detects a low flow, the seed will be increased until the sto ressure (actual setoint +. x ) is reached and the um stos. When the ressure has fallen to the start ressure (actual setoint. x ), the um will restart. indicates the difference between start and sto ressures. The sto function requires a diahragm tank of a certain minimum size. The tank must be installed immediately after the um and the recharge ressure must be.7 x actual setoint. Recommended diahragm tank size when no flow switch is connected. Rated flow of um [m /h] Diahragm tank size [litres] If a diahragm tank of the above size is installed in the system, the factory setting of is the correct setting. If the tank installed is too small, the um will start and sto too often. This can be remedied by increasing..9 Setting of sensor Note: Alies only to without sensor. Select the following: Sensor outut signal (- V (~ ums only), V, - ma or - ma), sensor measuring unit (bar, mbar, m, kpa, si, ft, m /h, m /s, l/s, gm, C, F or %) and sensor measuring range. The setting of the sensor is only carried out in the case of controlled oeration.. Setting of min. and max. curves Note: Alies only to without sensor. Sto ressure Start ressure is factory-set to % of actual setoint. can be set within the range from % to % of actual setoint. Note: The non-return valve must be fitted immediately before the um. If the non-return valve is fitted between um and diahragm tank, the ressure sensor must be fitted after the non-return valve. Correctly installed non-return valve Pum Diahragm tank Q TM 77 9 TM 77 9 Set the min. and max. curves in % of maximum erformance if the oerating range must be reduced. % Max. curve Min. curve % Oerating range The max. curve can be adjusted within the range from maximum erformance (%) to min. curve. The min. curve can be adjusted within the range from max. curve to % of maximum erformance. The um has been factory-set to % of maximum erformance. The oerating range lies between the min. and max. curves. Q TM

38 Functions External forced-control signals The um has inuts for external signals for the forcedcontrol functions: Start/sto of um. Digital function. Functional diagram: Start/sto inut Start/sto (terminals and ) By means of the R, one of the following functions can be selected for the digital inut: Min. curve. Max. curve. External fault. Flow switch. Functional diagram: Inut for digital function Digital function (terminals and 9 for ~ ums) (terminals and for ~ ums) Q Q Q Q Normal duty Sto Normal duty Min. curve External setoint signal By connecting an analog signal transmitter to the inut for the setoint signal (terminal and ), it is ossible to remote-set the setoint. The actual external signal (- V (~ ums only), V, - ma, - ma) must be selected via the R. If uncontrolled oeration is selected by means of the R, the um can be controlled by any controller. In controlled oerating mode, the setoint can be set externally within the range from the lower value of the sensor measuring range to the setoint set on the um or by means of the R. % seed Control arameter Uer value of sensor measuring range Setoint set on um or by means of the R Lower value of sensor measuring range Setoint signal V (~ ums only) V ma ma Examle: At a lower ressure-sensor value of bar, a setoint set of bar and an external setoint of %, the actual setoint will be as follows: actual = ( set - lower ) x % external setoint + lower = ( - ) x % + = bar In uncontrolled oerating mode, the setoint can be set externally within the range from the min. curve to the setoint set on the um or by means of the R. TM 79 9 Q Max. curve % seed Control arameter Max. curve Setoint set on um or by means of the R s Q External fault Min. curve s Q Flow switch Setoint signal V (~ ums) V ma ma TM 79 9

GRUNDFOS DATA BOOKLET. Hydro Multi-E. Grundfos Hydro Multi-E booster systems with 2 to 4 CRE, CRIE or CME pumps

GRUNDFOS DATA BOOKLET. Hydro Multi-E. Grundfos Hydro Multi-E booster systems with 2 to 4 CRE, CRIE or CME pumps GRUNDFOS DATA BOOKLET ydro Multi-E Grundfos ydro Multi-E booster systems with to CRE, CRIE or CME ums ydro Multi-E Table of contents. Introduction Benefits. Product data 5 Performance range 5 Tye key 7

More information

ARI-CORsys. Condensate recovery and return station. ARI-Condensate recovery and return station Volume: liter.

ARI-CORsys. Condensate recovery and return station. ARI-Condensate recovery and return station Volume: liter. ARI-CRsys Condensate recovery and return station ARI-Condensate recovery and return station Volume: 15- liter ARI-CRsys -St Condensate recovery and return station Standard design Ready for oeration condensate

More information

DIGITAL INTELLIGENT POWER FACTOR REGULATOR

DIGITAL INTELLIGENT POWER FACTOR REGULATOR An ISO 9001:2008 Comany DIGITAL INTELLIGENT POWER FACTOR REGULATOR Model - KM-PFR-9-06 / KM-PFR-9-12 The ioneers & leaders in high quality ower factor controllers & maximum demand controllers, now introduce

More information

EXPERIMENT 6 CLOSED-LOOP TEMPERATURE CONTROL OF AN ELECTRICAL HEATER

EXPERIMENT 6 CLOSED-LOOP TEMPERATURE CONTROL OF AN ELECTRICAL HEATER YEDITEPE UNIVERSITY ENGINEERING & ARCHITECTURE FACULTY INDUSTRIAL ELECTRONICS LABORATORY EE 432 INDUSTRIAL ELECTRONICS EXPERIMENT 6 CLOSED-LOOP TEMPERATURE CONTROL OF AN ELECTRICAL HEATER Introduction:

More information

Service instructions. CR, CRI, CRN 10, 15 and /60 Hz 1/3~

Service instructions. CR, CRI, CRN 10, 15 and /60 Hz 1/3~ Service instructions CR, CRI, CRN 10, 15 and 20 50/60 Hz 1/~ 1. Type identification... 2 1.1 Nameplate... 2 1.2 Type key... 1. Code for shaft seal... 4 2. Tightening torques and lubricants... 5. Service

More information

Switching Power Supply Type SPD 480W 3 phases DIN rail mounting

Switching Power Supply Type SPD 480W 3 phases DIN rail mounting Rheinland Product Safety e Switching Power Suly Universal AC 3 hases inut full range Can also be used as single hase 480VAC Installation on DIN rail 7.5 or 15mm PFC as standard High efficiency u to 91%

More information

The complete KASTO program: Economic sawing and storage of metal.

The complete KASTO program: Economic sawing and storage of metal. The comlete KASTO rogram: Economic sawing and storage of metal. EXPERTISE RIGHT DOWN THE LINE. For over 170 years, KASTO has been recognised for quality and innovation, and offers a comlete range of metal

More information

High-efficiency Circulator Pump. Rio-Eco N / Rio-Eco Z N. Type Series Booklet

High-efficiency Circulator Pump. Rio-Eco N / Rio-Eco Z N. Type Series Booklet High-efficiency Circulator Pump Rio-Eco N / Rio-Eco Z N Type Series Booklet Legal information/copyright Type Series Booklet Rio-Eco N / Rio-Eco Z N All rights reserved. The contents provided herein must

More information

OVERVOLTAGE PROTECTIONS FOR PHOTOVOLTAIC SYSTEMS

OVERVOLTAGE PROTECTIONS FOR PHOTOVOLTAIC SYSTEMS OVERVOLTAGE PROTECTIOS FOR PHOTOVOLTAIC SYSTEMS, Combined lightning current and surge voltage arresters - tye 1 tye 2 - DC For rotection of electric networks and equiment against overvoltage from direct

More information

Lowara. Centrifugal pumps with open impeller and flanged connections. SHO Series MARKET SECTORS CIVIL, INDUSTRIAL.

Lowara. Centrifugal pumps with open impeller and flanged connections. SHO Series MARKET SECTORS CIVIL, INDUSTRIAL. Centrifugal pumps with open impeller and flanged connections SHO Series MARKET SECTORS CIVIL, INDUSTRIAL. APPLICATIONS Industrial washing machines. Commercial dishwashers. Washing of metal parts, surface

More information

There are two basic types of FET s: The junction field effect transistor or JFET the metal oxide FET or MOSFET.

There are two basic types of FET s: The junction field effect transistor or JFET the metal oxide FET or MOSFET. Page 61 Field Effect Transistors The Fieldeffect transistor (FET) We know that the biolar junction transistor or BJT is a current controlled device. The FET or field effect transistor is a voltage controlled

More information

Lab 4: The transformer

Lab 4: The transformer ab 4: The transformer EEC 305 July 8 05 Read this lab before your lab eriod and answer the questions marked as relaboratory. You must show your re-laboratory answers to the TA rior to starting the lab.

More information

UNISELB. Self-priming dirty water pump

UNISELB. Self-priming dirty water pump UNISELB Self-priming dirty water pump GB 7 UNISELB benefits that ensure operational safety and cost-effectiveness in continuous operation. TABLE OF CONTENTS Non-clogging system Starting at DN, the non-clogging-system

More information

Insertion Flow sensor for continuous flow measurement

Insertion Flow sensor for continuous flow measurement Insertion Flow sensor for continuous flow measurement Economic integration into pipe systems 2 wire frequency coil (sinusoidal) version 3 wire frequency Hall effect (pulse) version to directly interface

More information

UPA 150C. 50 Hz. Applications. Submersible Borehole Pumps for Well Diameters of 150 mm (6 inches) Operating Data. Design. Designation (Example)

UPA 150C. 50 Hz. Applications. Submersible Borehole Pumps for Well Diameters of 150 mm (6 inches) Operating Data. Design. Designation (Example) Type Series Booklet 3400.52/4 -- 10 Applications Suitable for handling clean or slightly contaminated water in applications such as: -- domestic water supply -- general water supply -- irrigation and spray

More information

Electromagnetic Flow Transmitter

Electromagnetic Flow Transmitter Electromagnetic Flow Transmitter Sensor in solid state technology Working as a transmitter and/or as an On/Off controller Automatic-calibration of full scale: Teach-In Clean in place (CIP) Type can be

More information

DESIGN AND FABRICATION OF A DEEP DRAWING MACHINE: EXPERIMENTAL STUDY OF DRAWING FORCE VS DRAWING STROKE

DESIGN AND FABRICATION OF A DEEP DRAWING MACHINE: EXPERIMENTAL STUDY OF DRAWING FORCE VS DRAWING STROKE DESIGN AND FABRICATION OF A DEEP DRAWING MACHINE: EXPERIMENTAL STUDY OF DRAWING FORCE VS DRAWING STROKE Ahmed Ramahi, ramahi@najah.edu, a_ramahi@yahoo.com. Industrial Engineering Deartment, An-Najah National

More information

Physics. Valve Electronics.

Physics. Valve Electronics. Physics Valve Electronics www.testrekart.com Table of Content 1. Do You Know?. Thermionic Emission and Emitters. 3. Vacuum Tubes and Thermionic Valves. 4. Diode Valve. 5. Triode Valve. 1 1. Do You Know?

More information

MULTIPLE CHOICE QUESTIONS

MULTIPLE CHOICE QUESTIONS MULTIPLE CHOICE QUESTIONS (1) In 1831 Faraday in England and hennery in USA observed that an e.m.f is set u in conductor when it moves across a (a) Electric field (b) Magnetic field (c) Gravitational field

More information

Application of Notch Filtering under Low Sampling Rate for Broken Rotor Bar Detection with DTFT and AR based Spectrum Methods

Application of Notch Filtering under Low Sampling Rate for Broken Rotor Bar Detection with DTFT and AR based Spectrum Methods Alication of Notch Filtering under Low Samling Rate for Broken Rotor Bar Detection with DTFT and AR based Sectrum Methods B. Ayhan H. J. Trussell M.-Y. Chow M.-H. Song IEEE Student Member IEEE Fellow IEEE

More information

User Manual. for. Multi-Handy 2040

User Manual. for. Multi-Handy 2040 User Manual for Multi-Handy 2040 L3160-00-25.00E 1 = 128.6 Multi Handy 2040 ON 0-20 4-20 OFF SI US 1 ( 1-2 ) 2 Q T n Please read the user instructions carefully, before utting the measuring instrument

More information

Full Bridge Single Stage Electronic Ballast for a 250 W High Pressure Sodium Lamp

Full Bridge Single Stage Electronic Ballast for a 250 W High Pressure Sodium Lamp Full Bridge Single Stage Electronic Ballast for a 50 W High Pressure Sodium am Abstract In this aer will be reorted the study and imlementation of a single stage High Power Factor (HPF) electronic ballast

More information

Split case double suction centrifugal pump. Technical data Serie: DPAS C

Split case double suction centrifugal pump. Technical data Serie: DPAS C Split case double suction centrifugal pump Technical data Serie: DPAS C Table of Contents 1 Introduction 1.1 Fields of Application... 1. Pumped Liquids... 1.3 Design... 1. Bearings... 1.5 Shaft Seal...

More information

Improving Performance of an. Energy Efficient Hydraulic Circuit

Improving Performance of an. Energy Efficient Hydraulic Circuit Imroving Performance of an Energy Efficient Hydraulic Circuit A Thesis Submitted to the College of Graduate Studies and Research in Partial Fulfillment of the Requirements for the Degree of Master of Science

More information

KDN GENERAL DATA STANDARDISED CENTRIFUGAL PUMPS BARE SHAFT ON BEDPLATE WITH MOTOR AND COUPLING. Applications. Constructional features of the pump

KDN GENERAL DATA STANDARDISED CENTRIFUGAL PUMPS BARE SHAFT ON BEDPLATE WITH MOTOR AND COUPLING. Applications. Constructional features of the pump KDN STANDARDISED CENTRIFUGAL UMS BARE SAFT ON BEDLATE WIT MOTOR AND COULING GENERAL DATA Applications Enbloc, centrifugal otor-driven pups with coupling designed for a wide range of applications such as:

More information

Series 80 In-Line Mounted Centrifugal Pumps

Series 80 In-Line Mounted Centrifugal Pumps Bulletin B-G Bell & Gossett Series In-Line Mounted Centrifugal Pumps Applications Hydronic Heating & Cooling Systems Industrial Process General Service Pressure Boosting Advantages Close Coupled Space

More information

CHAPTER 5 INTERNAL MODEL CONTROL STRATEGY. The Internal Model Control (IMC) based approach for PID controller

CHAPTER 5 INTERNAL MODEL CONTROL STRATEGY. The Internal Model Control (IMC) based approach for PID controller CHAPTER 5 INTERNAL MODEL CONTROL STRATEGY 5. INTRODUCTION The Internal Model Control (IMC) based aroach for PID controller design can be used to control alications in industries. It is because, for ractical

More information

GLM700ASB family. Tooth sensor module with integrated magnet DATA SHEET

GLM700ASB family. Tooth sensor module with integrated magnet DATA SHEET The sensor modules of the GLM700ASB-Ax family are designed for use with assive measurement scales. The modules combine a GiantMagnetoResistive (GMR) tooth sensor with an integrated bias magnet in a comact

More information

Pumping of clear unfilled liquids in housing, agricultural and industrial sectors.

Pumping of clear unfilled liquids in housing, agricultural and industrial sectors. operating limits Flow rates up to : 98 m 3 /h Head up to : Max. discharge pressure : Max. suction pressure : Temperature range : 25 m CE 16 et 25 bar 1 bar - 15 to +12 C* Max. ambient temperature : + 4

More information

SIGNALS AND ENERGY DATA SYSTEM INTEGRATION POWER QUALITY Products and Solutions

SIGNALS AND ENERGY DATA SYSTEM INTEGRATION POWER QUALITY Products and Solutions System english KBR EnergyManagement SIGNALS AND ENERGY DATA SYSTEM INTEGRATION POWER QUALITY Products and Solutions One System. Best Solutions. monitoring analyzing Recording otimizing Evaluating How comanies

More information

Figure 1 Figure 2 Figure 3

Figure 1 Figure 2 Figure 3 Installation guide Thermal Energy Meter uerstatic 749 Installation The rescritions related in the standard EN1434-6 must be resected when the uerstatic 749 is installed. In the standard version, the integrator

More information

University of Twente

University of Twente University of Twente Faculty of Electrical Engineering, Mathematics & Comuter Science Design of an audio ower amlifier with a notch in the outut imedance Remco Twelkemeijer MSc. Thesis May 008 Suervisors:

More information

Modeling and simulation of level control phenomena in a non-linear system

Modeling and simulation of level control phenomena in a non-linear system www.ijiarec.com ISSN:2348-2079 Volume-5 Issue- International Journal of Intellectual Advancements and Research in Engineering Comutations Modeling and simulation of level control henomena in a non-linear

More information

2-way motor valve. Power consumption. Type 8746 MFC/MFM. Technical data Materials Body Housing Seals 1) Pressure Range 2) < 1 % FS Sensitivity Span

2-way motor valve. Power consumption. Type 8746 MFC/MFM. Technical data Materials Body Housing Seals 1) Pressure Range 2) < 1 % FS Sensitivity Span 2-way motor valve Actuator isolated from flow path Excellent range and fast response times Low power consumption Orifice sizes 1 to 10 mm Versions: Standard, positioner, process controller and high pressure

More information

Paddle wheel flow controller for On/Off control

Paddle wheel flow controller for On/Off control addle wheel flow controller for On/Off control Type 8032 compact Type 8032 can be combined with... Type 8032 remote Indication, monitoring, transmitting and On/Off control in one device. rogrammable outputs

More information

Submittal Data Sheet Wilo MVI - Vertical Multistage Pumps

Submittal Data Sheet Wilo MVI - Vertical Multistage Pumps Wilo MVI Project: Engineer: Contractor: Submitted By: Date: Approved By: Date: Tag # Model # Flow Head HP Cycle Phase Voltage RPM Hz H [ft] ηp [%] P [hp] 7 7.......7..9.......................... MVI -

More information

RCM DIRECT READING FLOWMETER

RCM DIRECT READING FLOWMETER RCM DIRECT READING FLOWMETER Flow Pressure Level Temperature measurement monitoring control Special Features Compact Design Easy to Install For Horizontal or Vertical Pipes Rugged Construction Accuracy:

More information

E l e c t r o m a g n e t i c f l o w m e t e r s

E l e c t r o m a g n e t i c f l o w m e t e r s E l e c t r o m a g n e t i c f l o w m e t e r s P r o v e n A N D R e l i a b l e F l o w M e a s u r e m e n t 2 MJK MagFlux flow meters combine high accuracy, stability and low maintenance. Without

More information

REAL TIME PERFORMANCE ANALYSIS, FAULT DETECTION AND CONTROL IN CONICAL TANK SYSTEM

REAL TIME PERFORMANCE ANALYSIS, FAULT DETECTION AND CONTROL IN CONICAL TANK SYSTEM REAL TIME PERFORMANCE ANALYSIS, FAULT DETECTION AND CONTROL IN CONICAL TANK SYSTEM S.Pooja Dr.S.Vijayachitra 2 (Electronics and Instrumentation Engineering, Anna University, Erode, India, oojainst27@gmail.com)

More information

MEGA - AS-Interface version 3.0

MEGA - AS-Interface version 3.0 NEUMATIC SOOL VALVE ISLANDS by field bus with the following protocol MEGA - AS-Interface version. Installation manual NTERFACE MS-7-6.R GB CONTENTS age. The BUSLINK MEGA system with the AS-Interface protocol.

More information

Servo Mechanism Technique based Anti-Reset Windup PI Controller for Pressure Process Station

Servo Mechanism Technique based Anti-Reset Windup PI Controller for Pressure Process Station Indian Journal of Science and Technology, Vol 9(11), DOI: 10.17485/ijst/2016/v9i11/89298, March 2016 ISSN (Print) : 0974-6846 ISSN (Online) : 0974-5645 Servo Mechanism Technique based Anti-Reset Windu

More information

LAB IX. LOW FREQUENCY CHARACTERISTICS OF JFETS

LAB IX. LOW FREQUENCY CHARACTERISTICS OF JFETS LAB X. LOW FREQUENCY CHARACTERSTCS OF JFETS 1. OBJECTVE n this lab, you will study the -V characteristics and small-signal model of Junction Field Effect Transistors (JFET).. OVERVEW n this lab, we will

More information

2/2 way Proportional Valve (motordriven)

2/2 way Proportional Valve (motordriven) 2/2 way Proportional (motordriven) Actuator isolated from fl ow path Excellent range and fast response times Low power consumption Orifi ce sizes 8 to 25 mm Versions: Standard, positioner, process controller

More information

OPTIFLUX 1000 Technical Datasheet

OPTIFLUX 1000 Technical Datasheet OPTIFLUX 1000 Technical Datasheet Electromagnetic flow sensor in sandwich design Lightweight and compact Excellent price performance ratio Quick and easy to install The documentation is only complete when

More information

(11) Bipolar Op-Amp. Op-Amp Circuits:

(11) Bipolar Op-Amp. Op-Amp Circuits: (11) O-Am Circuits: Biolar O-Am Learning Outcome Able to: Describe and analyze the dc and ac characteristics of the classic 741 biolar o-am circuit. eference: Neamen, Chater 13 11.0) 741 O-Am 11.1) Circuit

More information

Application Note D. Dynamic Torque Measurement

Application Note D. Dynamic Torque Measurement Page 1 of 9 Alication Note 221101D Dynamic Torque Measurement Background Rotary ower sources and absorbers have discrete oles and/or istons and/or gear meshes, etc. As a result, they develo and absorb

More information

Digital flow ELEMENT transmitter for continuous flow measurement

Digital flow ELEMENT transmitter for continuous flow measurement ELEMENT Transmitter Digital flow ELEMENT transmitter for continuous flow measurement Type can be combined with... PN10, DN15 to DN400 fluidic process connection Programmable outputs : one or two transistor

More information

Digital flow transmitter for continuous flow measurement

Digital flow transmitter for continuous flow measurement Digital flow transmitter for continuous flow measurement Compact or remote version for DN 06 to 400, PN10 Shows both flow rate and volume (with two totalizers) Automatic-calibration: TEACH-IN Simulation:

More information

APPLICATIONS. Commercial central heating in housing, office buildings, greenhouses, swimming pools, farms, etc. Air conditioning.

APPLICATIONS. Commercial central heating in housing, office buildings, greenhouses, swimming pools, farms, etc. Air conditioning. V OERATING LIMITS Flow rates up to: Heads up to: Max. service pressure: m/h* 9 m bar Temperature range: - à + C Max. ambient temperature: + 5 C** DN of ports: à * m/h : with both heads operating in parallel

More information

Liquid ring vacuum pumps in compact design

Liquid ring vacuum pumps in compact design Liquid ring vacuum pumps in compact design SIHI extruvac LEME 13, LEME 155 Pressure range: Suction volume flow: 1 to 113 mbar 3 to 17 m³/h CONSTRUCTION TYPE SIHI liquid ring vacuum pumps are displacement

More information

RS /M MZ SERIES

RS /M MZ SERIES The RS 310-410-510-610/M MZ burners series covers a firing range from 1300 to 6300 kw, and it has been designed for use in low or medium temperature hot water boilers, hot air or steam boilers, diathermic

More information

KDN GENERAL DATA STANDARDISED CENTRIFUGAL PUMPS BARE SHAFT ON BEDPLATE WITH MOTOR AND COUPLING. Applications. Constructional features of the pump

KDN GENERAL DATA STANDARDISED CENTRIFUGAL PUMPS BARE SHAFT ON BEDPLATE WITH MOTOR AND COUPLING. Applications. Constructional features of the pump KDN STANDARDISED CENTRIFUGAL UMS BARE SAFT ON BEDLATE WIT MOTOR AND COULING GENERAL DATA Applications Enbloc, centrifugal otor-driven pups with coupling designed for a wide range of applications such as:

More information

Digital inductive conductivity transmitter

Digital inductive conductivity transmitter Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections

More information

INTERNET PID CONTROLLER DESIGN: M. Schlegel, M. Čech

INTERNET PID CONTROLLER DESIGN:  M. Schlegel, M. Čech INTERNET PID CONTROLLER DESIGN: WWW.PIDLAB.COM M. Schlegel, M. Čech Deartment of Cybernetics, University of West Bohemia in Pilsen fax : + 0403776350, e-mail : schlegel@kky.zcu.cz, mcech@kky.zcu.cz Abstract:

More information

SLVE2.8 and SLVG2.8. EPD TVS Diodes For ESD and Latch-Up Protection. PROTECTION PRODUCTS Description. Features. Mechanical Characteristics

SLVE2.8 and SLVG2.8. EPD TVS Diodes For ESD and Latch-Up Protection. PROTECTION PRODUCTS Description. Features. Mechanical Characteristics Descrition The SL series of transient voltage suressors are designed to rotect low voltage, state-of-the-art CMOS semiconductors from transients caused by electrostatic discharge (ESD), cable discharge

More information

State-of-the-Art Verification of the Hard Driven GTO Inverter Development for a 100 MVA Intertie

State-of-the-Art Verification of the Hard Driven GTO Inverter Development for a 100 MVA Intertie State-of-the-Art Verification of the Hard Driven GTO Inverter Develoment for a 100 MVA Intertie P. K. Steimer, H. Grüning, J. Werninger R&D Drives and Power Electronics ABB Industrie AG CH-5300 Turgi,

More information

RClamp2574N. High Power TVS for Ethernet Interfaces. PROTECTION PRODUCTS - RailClamp Description. Features. Mechanical Characteristics.

RClamp2574N. High Power TVS for Ethernet Interfaces. PROTECTION PRODUCTS - RailClamp Description. Features. Mechanical Characteristics. - RailClam Descrition RailClam TS diodes are secifically designed to rotect sensitive comonents which are connected to high-seed data and transmission lines from overvoltage caused by ESD (electrostatic

More information

Control of Grid Integrated Voltage Source Converters under Unbalanced Conditions

Control of Grid Integrated Voltage Source Converters under Unbalanced Conditions Jon Are Suul Control of Grid Integrated Voltage Source Converters under Unbalanced Conditions Develoment of an On-line Frequency-adative Virtual Flux-based Aroach Thesis for the degree of Philosohiae Doctor

More information

Hydro-turbine governor control: theory, techniques and limitations

Hydro-turbine governor control: theory, techniques and limitations University of Wollongong Research Online Faculty of Engineering and Information Sciences - Paers: Part A Faculty of Engineering and Information Sciences 006 Hydro-turbine governor control: theory, techniques

More information

The transducer component converts the measured signal and displays the actual value.

The transducer component converts the measured signal and displays the actual value. Digital inductive conductivity transmitter System Integration Provides low Total Cost of Ownership PEEK/PPA version for CIP applications TEACH IN and SIMULATION Function Approval PVDF Version PEEK Version

More information

FAIRBANKS NIJHUIS 1590 SERIES SINGLE STAGE VERTICAL INLINE PUMP.

FAIRBANKS NIJHUIS 1590 SERIES SINGLE STAGE VERTICAL INLINE PUMP. FAIRBANKS NIJHUIS 0 SERIES SINGLE STAGE VERTICAL INLINE PUMP www.fairbanksnijhuis.com FAIRBANKS NIJHUIS 0 Series Single Stage Vertical Inline Pump Capacities to 00 GPM (,00 m/hr) Heads to 0 Feet ( m) Temperatures

More information

Grundfos Direct Sensor

Grundfos Direct Sensor GRUNDFOS DT OOKLET Grundfos Direct Sensor sensors Grundfos Direct Sensor Table of contents 1. Product introduction 3 Type key 4 2. Relative- sensor, Industry (RPI) 5 RPI / RPI +T general data 5 RPI, 0-0.6

More information

User Manual. for. Multi-Handy 2045

User Manual. for. Multi-Handy 2045 User Manual for Multi-Handy 2045 L3160-00-25.50E 1 = 128.6 Multi Handy 2045 ON 0-20 4-20 OFF n Q 1 2 ( 1-2 ) Memory Scan Printer Start Sto Please read the user instructions carefully, before utting the

More information

Development of an Improved Pedal Powered Hacksaw Machine

Development of an Improved Pedal Powered Hacksaw Machine Journal of Materials Science and Engineering B 6 (11-1) (016) 77-8 doi: 10.1765/161-61/016.11-1.00 D DAVID PUBLISHING Develoment of an Imroved Pedal Powered Hacksaw Machine Mogaji Pius Bamidele Deartment

More information

Self-Driven Phase Shifted Full Bridge Converter for Telecom Applications

Self-Driven Phase Shifted Full Bridge Converter for Telecom Applications Self-Driven Phase Shifted Full Bridge Converter for Telecom Alications SEVILAY CETIN Technology Faculty Pamukkale University 7 Kinikli Denizli TURKEY scetin@au.edu.tr Abstract: - For medium ower alications,

More information

Circular Dynamic Stereo and Its Image Processing

Circular Dynamic Stereo and Its Image Processing Circular Dynamic Stereo and Its Image Processing Kikuhito KAWASUE *1 and Yuichiro Oya *2 *1 Deartment of Mechanical Systems Engineering Miyazaki University 1-1, Gakuen Kibanadai Nishi, Miyazaki 889-2192

More information

Multi Domain Behavioral Models of Smart-Power ICs for Design Integration in Automotive Applications. Dieter Metzner, Jürgen Schäfer, Chihao Xu

Multi Domain Behavioral Models of Smart-Power ICs for Design Integration in Automotive Applications. Dieter Metzner, Jürgen Schäfer, Chihao Xu Multi Domain Behavioral Models of Smart-Power ICs for Design Integration in Automotive Alications Dieter Metzner, Jürgen Schäfer, Chihao Xu Infineon Technologies AG P.O. Box 800949, D-81609 München, Germany

More information

Parallel Operation of Dynex IGBT Modules Application Note Replaces October 2001, version AN AN July 2002

Parallel Operation of Dynex IGBT Modules Application Note Replaces October 2001, version AN AN July 2002 AN5505 Parallel Oeration of Dynex GB odules Alication Note Relaces October 2001, version AN5505-1.2 AN5505-1.3 July 2002 NRODUCON GB modules can be connected in arallel to create a switch with a higher

More information

RS /E-EV BLU SERIES

RS /E-EV BLU SERIES The RS/E and RS/EV series burners are characterised by a modular monoblock structure that means all necessary components can be combined in a single unit thus making installation easier, faster and, above

More information

INSERTION paddle wheel flowmeter for continuous flow measurement

INSERTION paddle wheel flowmeter for continuous flow measurement INSERTION paddle wheel flowmeter for continuous flow measurement Economic integration in pipe systems without any additional piping 3-wire frequency pulse version to directly interface with PLC s (both

More information

THE USE OF INSULATED WIRES MILLIKEN CONDUCTORS IN HIGH VOLTAGE POWER TRANSMISSION UNDERGROUND AC LINES. x y s ABSTRACT

THE USE OF INSULATED WIRES MILLIKEN CONDUCTORS IN HIGH VOLTAGE POWER TRANSMISSION UNDERGROUND AC LINES. x y s ABSTRACT THE USE OF INSULATED WIRES MILLIKEN CONDUCTORS IN HIGH VOLTAGE POWER TRANSMISSION UNDERGROUND AC LINES David DUBOIS, NEXANS, (France), david.dubois@nexans.com Pierre MIREBEAU, NEXANS, (France), ierre.mirebeau@nexans.com

More information

Manufacturing Facilities City of Industry, CA Denver, CO Ft. Worth, TX Pittsburg, CA PRO-X HEADER. LEED v3 for Building and Design Construction

Manufacturing Facilities City of Industry, CA Denver, CO Ft. Worth, TX Pittsburg, CA PRO-X HEADER. LEED v3 for Building and Design Construction Cororate Headquarters 91746 Product Descrition Basic Use is a light gauge steel header that rovides horizontal and vertical load suort. This re-engineered metal framing comonent is designed as a 1- or

More information

Origins of Stator Current Spectra in DFIGs with Winding Faults and Excitation Asymmetries

Origins of Stator Current Spectra in DFIGs with Winding Faults and Excitation Asymmetries Origins of Stator Current Sectra in DFIGs with Wing Faults and Excitation Asymmetries S. Williamson * and S. Djurović * University of Surrey, Guildford, Surrey GU2 7XH, United Kingdom School of Electrical

More information

Carbon film deposited collector electrode for high efficiency TWTs

Carbon film deposited collector electrode for high efficiency TWTs ndian Journal of Pure & Alied Physics Vol.54, February 2016,. 111-115 Carbon film deosited collector electrode for high efficiency TWTs Suneeta Arya 1, A Mercy Latha 1,2 *, S K Ghosh 1,2, Vishnu Srivastava

More information

SONOMETER 2000 Ultrasonic heat meter

SONOMETER 2000 Ultrasonic heat meter SONOMETER 2000 Ultrasonic heat meter Description/Application The SONOMETER 2000 is an ultrasonic heat meter especially designed for measuring the water and energy consumption in district heating networks.

More information

Type PLC Fitting. Valve for Continuous control. Diaphragm valve. Output

Type PLC Fitting. Valve for Continuous control. Diaphragm valve. Output Digital Inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections

More information

OPTIFLUX 5000 Technical Datasheet

OPTIFLUX 5000 Technical Datasheet OPTIFLUX 5000 Technical Datasheet Electromagnetic flowmeter in flanged version Exceptional long-term stability and accuracy For highly aggressive and abrasive fluids Fully vacuum-resistant with high-tech

More information

KFS. Flap-type flow meter. Design and range of application

KFS. Flap-type flow meter. Design and range of application Design and range of application The measuring device operates largely independent of viscosity and is suitable for indicating the flow rate of water, acids, alkaline solutions and gases. Every device is

More information

Flow Switch - 2 programmable thresholds. Stand Alone (Battery) - Battery powered, - 2 totalizers display, - Local flow display,

Flow Switch - 2 programmable thresholds. Stand Alone (Battery) - Battery powered, - 2 totalizers display, - Local flow display, DN 15 - DN 50; PN Advantages / Benefits Easy System integration by Easy LINK provides low cost of ownership Easy commissioning due to multi-language, menu-guided operation TEACH-IN: automatic calibration

More information

Condumax W CLS15 and CLS15D

Condumax W CLS15 and CLS15D Technical Information Condumax W CLS15 and CLS15D Conductivity sensors, analog or digital with Memosens technology, Cell constant k = 0.01 cm -1 or k = 0.1 cm -1 Application Measurement in pure and ultrapure

More information

TPHK Series. Immersible Pump

TPHK Series. Immersible Pump Series Immersible Pump Contents General Data Performance Range Sectional Drawing Performance Curves/Technical Data T T T T Series Immersible Pump Hz Power:. -. kw Head: Up to M Flow: Up to L/min Hz Power:.

More information

Evolutionary Circuit Design: Information Theory Perspective on Signal Propagation

Evolutionary Circuit Design: Information Theory Perspective on Signal Propagation Evolutionary Circuit Design: Theory Persective on Signal Proagation Denis Poel Deartment of Comuter Science, Baker University, P.O. 65, Baldwin City, KS 66006, E-mail: oel@ieee.org Nawar Hakeem Deartment

More information

RS /E-EV BLU SERIES

RS /E-EV BLU SERIES The RS/E and RS/EV series burners are characterised by a modular monoblock structure that means all necessary components can be combined in a single unit thus making installation easier, faster and, above

More information

An Overview of Substrate Noise Reduction Techniques

An Overview of Substrate Noise Reduction Techniques An Overview of Substrate Noise Reduction Techniques Shahab Ardalan, and Manoj Sachdev ardalan@ieee.org, msachdev@ece.uwaterloo.ca Deartment of Electrical and Comuter Engineering University of Waterloo

More information

ELECTRICAL TECHNOLOGY EET 103/4

ELECTRICAL TECHNOLOGY EET 103/4 ELECTRICAL TECHNOLOGY EET 103/4 Define and analyze the rincile of transformer, its arameters and structure. Describe and analyze Ideal transformer, equivalent circuit, and hasor diagram Calculate and justify

More information

Design and applications

Design and applications Design and applications The measuring device operates largely independent of viscosity and is suitable for indicating the flow rate of water, acids, alkaline solutions and gases. Every device is calibrated

More information

High-efficiency of MHz Inverter Constructed from Frequency Multiplying Circuit

High-efficiency of MHz Inverter Constructed from Frequency Multiplying Circuit High-efficiency of MHz Inverter Constructed from Frequency Multilying Circuit Koji Orikawa, Jun-ichi Itoh Deartment of Electrical Engineering Nagaoka University of Technology Nagaoka, Jaan orikawa@vos.nagaokaut.ac.j

More information

RS /E-EV BLU SERIES

RS /E-EV BLU SERIES The RS/E and RS/EV series burners are characterised by a modular monoblock structure that means all necessary components can be combined in a single unit thus making installation easier, faster and, above

More information

SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING

SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING SECTION 230516 - EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Keysight 42030A Four-Terminal Pair Standard Resistor Set

Keysight 42030A Four-Terminal Pair Standard Resistor Set Keysight 42030A Four-Terminal Pair Standard Resistor Set Oeration and Service Manual Agilent 42030A Four-Terminal Pair Standard Resistor Set Oeration and Service Manual Agilent Part No. 42030-90001 Printed

More information

Digital flow ELEMENT transmitter for continuous flow measurement

Digital flow ELEMENT transmitter for continuous flow measurement Digital flow ELEMENT transmitter for continuous flow measurement Type 8036 can be combined with... DN06 to DN65 fluidic process connection Programmable outputs : one or two transistor output(s) and single

More information

Sold by AA Electric Lakeland, FL Lawrenceville, GA East Rutherford, NJ Web :

Sold by AA Electric Lakeland, FL Lawrenceville, GA East Rutherford, NJ Web : 2 Table of Contents, New Products, Doing Business with Us, Our Comany AC Current Transformers 3 AC Current Switches 3 AC Current Transmitters 3 AC Inut Alarms 4 AC Inut Transmitters 4-6 DC Current Switches

More information

OVAL FLOWMETER. Meter Size: 52, 53, 55, 56, 57 Double Case Construction with Powerful Magnetic Coupling ( ) Magnetic coupling Outer Housing

OVAL FLOWMETER. Meter Size: 52, 53, 55, 56, 57 Double Case Construction with Powerful Magnetic Coupling ( ) Magnetic coupling Outer Housing OVAL FLOWMETER : 5, 53,, 56, 57 Double Case Construction with Powerful Magnetic Coupling ( ) Liquid GENERAL SPECIFICATION GS.No.GBB5E 7 GENERAL The OVAL flowmeter is a positive displacement type flowmeter

More information

J Series induq VMZ MAGNETIC INDUCTIVE FLOW SENSORS. DB_Magnetic_Inductive_Flow_Sensors 05/2016

J Series induq VMZ MAGNETIC INDUCTIVE FLOW SENSORS. DB_Magnetic_Inductive_Flow_Sensors 05/2016 J Series induq VMM J Series induq VMI J Series induq VMZ MAGNETIC INDUCTIVE FLOW SENSORS J DB_Magnetic_Inductive_Flow_Sensors 5/216 67 Magnetic inductive flow sensors Principle of operation The smart flow

More information

WATERFLUX 3000 Quick Start

WATERFLUX 3000 Quick Start WATERFLUX 3000 Quick Start Electromagnetic flow sensor The documentation is only complete when used in combination with the relevant documentation for the signal converter. KROHNE CONTENTS WATERFLUX 3000

More information

TPHK Series. Immersible Pump

TPHK Series. Immersible Pump TPHK Series Immersible Pump Contents General Data Performance Range Sectional Drawing Performance Curves/Technical Data TPHK T TPHK T TPHK 8T TPHK T TPHK Series Immersible Pump Hz Power:. -.8 kw Head:

More information

SYSDRIVE 3G3IV High-performance/Low noise General-purpose Inverter Installation/Instruction Manual

SYSDRIVE 3G3IV High-performance/Low noise General-purpose Inverter Installation/Instruction Manual SYSDRIVE 3G3IV High-performance/Low noise General-purpose Inverter Installation/Instruction Manual Revised June 1995 Notice: OMRON products are manufactured for use according to proper procedures by a

More information

RECOMMENDATION ITU-R SF

RECOMMENDATION ITU-R SF Rec. ITU-R SF.1649-1 1 RECOMMENDATION ITU-R SF.1649-1 Guidance for determination of interference from earth stations on board vessels to stations in the fixed service when the earth station on board vessels

More information

SONOMETER TM 1100 Ultrasonic compact energy meter

SONOMETER TM 1100 Ultrasonic compact energy meter Data sheet SONOMETER TM 1100 Ultrasonic compact energy meter Description/Application MID examination certificate no. : DE-10-MI004-PTB003 The SONOMETER 1100 is an ultrasonic static compact energy meter

More information

KFS-EM. Overall length. Al. PTFE coated Alu, painted Al. coated Methacrylate / acrylic nitrite

KFS-EM. Overall length. Al. PTFE coated Alu, painted Al. coated Methacrylate / acrylic nitrite KFS Flap Flow Meter KFS suitable for H, acids, alkalis and gases spring-loaded horizontal or vertical flow direction low pressure loss mainly viscosity independent optional threshold value contacts optional

More information