Draft Kenya Standard for Balloting Not to be Cited as Kenya Standard

Size: px
Start display at page:

Download "Draft Kenya Standard for Balloting Not to be Cited as Kenya Standard"

Transcription

1 KENYA STANDARD KS :2010 ICS Electrical power transmission and distribution High-voltage operating regulations Part 5: Standard procedure and terminology for the issuing of operating instructions BALLOT DRAFT, MAY 2010 KEBS 2010 First Edition 2010

2 KS :2010 TECHNICAL COMMITTEE REPRESENTATION The following organizations were represented on the Technical Committee: Nairobi City Council, City Engineer s Department. Jomo Kenyatta University of Agriculture and Technology Kenya Polytechnic Kenya Power & Lighting Company Fluid & Power Systems Ltd Ministry of Public Works and Housing Ministry of Energy Kenafric Industries Ltd Power Technics Ltd Rural Electrification Authority The Energy Regulatory Commission Consumer Information Network Kenya Association of Manufacturers Institute of Engineers of Kenya Kenya Electricity Generating Company Ltd ABB LTD Switchgear & Controls Ltd Power Controls Ltd Communications Communication of Kenya Instrument Ltd Kenya Pipeline Company Ltd Telkom Kenya Ltd Meteorological Department Kenya Bureau of Standards Secretariat REVISION OF KENYA STANDARDS In order to keep abreast of progress in industry, Kenya standards shall be regularly reviewed. Suggestions for improvement to published standards, addressed to the Managing Director, Kenya Bureau of Standards, are welcome. Kenya Bureau of Standards, 2010 Copyright. Users are reminded that by virtue of Section 25 of the Copyright Act, Cap. 12 of 2001 of the Laws of Kenya, copyright subsists in all Kenya Standards and except as provided under Section 26 of this Act, no Kenya Standard produced by Kenya Bureau of Standards may be reproduced, stored in a retrieval system in any form or transmitted by any means without prior permission in writing from the Managing Director. ii KEBS 2010 All rights reserved

3 KENYA STANDARD KS :2010 ICS Electrical power transmission and distribution High-voltage operating regulations Part 5: Standard procedure and terminology for the issuing of operating instructions KENYA BUREAU OF STANDARDS (KEBS) Head Office: P.O. Box 54974, Nairobi-00200, Tel.: ( ) , , , Mobile: /8, /2; Fax: ( ) Web: KEBS Coast Region P.O. Box 99376, Mombasa Tel: ( ) , /40 Fax: ( ) KEBS Lake Region P.O. Box 2949, Kisumu Tel: ( ) 23549,22396 Fax: ( ) KEBS North Rift Region P.O. Box 2138, Nakuru Tel: ( ) , KEBS 2010 All rights reserved iii

4 KS :2010 F O R E W O R D This Kenya standard was prepared by the Switchgear and Distribution Equipment in accordance with the procedures of the Bureau and is in compliance with Annex 3 of the WTO/TB Agreement. This part of KS 1859 has been prepared to establish and promote uniform requirements for the issuing of operating instructions for application in the Electricity Distribution Industry. In the development of this standard, the South African Standard, NRS 040-5:2007, Rationalized User Specification High voltage regulations Part 5: Standard procedure and terminology for the issuing of operating instructions, was extensively consulted. Assistance derived from this source is hereby acknowledged. Normative and informative annexes A 'normative' annex is an integral part of a standard, whereas an 'informative' annex is only for information and guidance. Summary of development This Kenya Standard, having been prepared by the Switchgear and Distribution Equipment Technical Committee was first approved by the National Standards Council in June 2010 Amendments issued since publication Amd. No. Date Text affected iv KEBS 2010 All rights reserved

5 Contents KS : Scope Normative references Terms, definitions and abbreviated terms Terms and definitions Abbreviations Requirements Operating process Personal introduction Site and plant identification Scope of work verification System contingency planning Intercontrol arrangements Issue of operating instructions Confirmation of operating instructions Commencement of actual operating Reporting of completed operating Handing over and handing back of apparatus in substations Handing over and handing back of power lines or sections of power lines Control functions National/transmission control or interdistributor control Operating instruction forms Requirements before operating instructions can be issued Operating sequence Dressing control panels Manual VT selection Under-frequency load-shedding equipment Motorized isolators Transformer tap position control Specific operating sequence Returning an interconnected power system (IPS) line to service after maintenance Taking a transformer panel out of service for maintenance Safety test and earth Returning a transformer panel to service after maintenance Taking an interconnected power system transformer panel out of service Taking a bus coupler breaker or bus section breaker out of service Returning a bus coupler breaker or bus section breaker back to service Requirements for handing over and handing back apparatus Control functions after hand over KEBS 2010 All rights reserved v

6

7 KENYA STANDARD KS :2010 Electrical power transmission and distribution High-voltage operating regulations Part 5: Standard procedure and terminology for the issuing of operating instructions 1 Scope This part of KS 1859 defines a procedure and terminology for control and field staff interaction when operating medium-voltage and high-voltage apparatus. NOTE This part of KS 1859 is an extension of legislation. Read this part of KS 1859 in conjunction with legislation. 2 Normative references The following referenced documents are indispensable for the application of this Kenya Standard. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. KS , High-voltage operating regulations Part 3: Model regulations Recommended model regulations relating to power systems for operating, access control and supervision of systems that exceed 1000 V, for the transmission and distribution of electricity. 3 Terms, definitions and abbreviated terms 3.1 Terms and definitions For the purposes of this part of KS 1859, the terms, definitions and abbreviations in KS and the following apply. authorized person person who has, in writing, been delegated defined authority and responsibility in terms of the relevant HV operating regulations bus coupler apparatus used for connecting two sets of busbar bus section breaker apparatus used for connecting two sections of the same busbar controller employee or official on duty at a control centre, who is responsible for the general operation of the power system or of a section thereof security linking contingency configuration of the network where isolation for maintenance could compromise network stability (i.e. redundancy or firm supply requirements) voltage regulator device used for automatic voltage control at a pre-set voltage 3.2 Abbreviations AVR HMI automatic voltage regulator human machine interface KEBS 2010 All rights reserved 1

8 KS :2010 HV IPS MV PTO PTS VT high voltage interconnected power system medium voltage permission to operate permission to sectionalize voltage transformer 4 Requirements 4.1 Operating process The following block diagram depicts the process and communication between control and field staff as discussed in this part of KS Personal introduction At every occasion that contact is established between a control officer and an authorized person in the field, the control officer and the authorized person will introduce one to the other by stating their full names If called for by either party, the identification will be confirmed with additional information like unique or identification numbers. 4.3 Site and plant identification Before operating instructions are being issued or received, the plant description and location will be stated in the following manner: a) the location of the plant will include the name of the line, feeder or substation as it appears on the equipment's nameplate and operating diagram nametag. The line name may be abbreviated; and b) the equipment to be operated will be identified by the standard symbol on the operating diagram and the equipment nameplate on the structure. 2 KEBS 2010 All rights reserved

9 4.4 Scope of work verification KS :2010 Before commencing with the work, the authorized person shall define the proposed scope of work to the control officer. This shall include the operating approach and placement of earths. The scope of work shall correspond with the plant outage documentation submitted to the control centre. 4.5 System contingency planning After the request for a specific outage, the control officer shall verify that a pre-arranged booking has been made. The booking shall specify all risks and hazards associated with the outage. The controller shall then assess the status of the substation and the power system to ascertain whether security linking is necessary. Security linking shall take precedence over any other operation. 4.6 Intercontrol arrangements If, for example, an interdistributor or IPS line is requested for isolation, the controller shall first confirm with the other control centre and then with National Control to verify the viability of the outage and obtain permission for the plant isolation. 4.7 Issue of operating instructions After the necessary discussions and request for permission have been completed, the actual operating instructions shall follow. In electronic operating, only the operating instructions agreed upon and included in the operating schedule will be given. The detailed instructions are discussed under "Requirements to make MV and HV apparatus safe to work on" in KS The authorized person will refer to the controller as "control" while the controller will address the authorized person by his first name and surname. The dialogue will be as follows: Controller: "<First name and surname of authorized person>, at <name of substation>, <nominal voltage, name of the panel >: open (or close) <name of the apparatus>", followed by all consecutive instructions, as necessary. 4.8 Confirmation of operating instructions After the authorized person has received his instructions, he will repeat the instructions to the controller and the controller can verify whether the operator has the instructions correctly. An instruction time is then given. In electronic operating, only the operating instructions agreed upon will be given. The dialogue will be as follows: Controller "<First name and surname of authorized person>, at <name of substation>, <nominal voltage, name of the panel>: I shall <open/close> <name of the apparatus>," followed by all consecutive instructions, 4.9 Commencement of actual operating The authorized person carries out the instructions in the sequence they were given to him or her, in accordance with the network operating regulations in KS A completion time is recorded on the operating instruction form Reporting of completed operating On completion of the operation, the authorized person shall report back to the controller that the operating has been performed. A reported time is issued Handing over and handing back of apparatus in substations Handing over After all isolation and earthing have been completed, the controller shall hand over the apparatus to the authorized person. Handover is an instruction and the operation shall be written out in full by the authorized person on an operating instruction form together with the time of handing over (handing back). KEBS 2010 All rights reserved 3

10 KS : Controller The dialogue shall be as follows: "<First name and surname of authorized person>, at <name of substation>, <nominal voltage, name of the apparatus> has been opened, isolated and earthed at all points of supply, You may commence with the specified work. On completion, remove all tools, equipment and workers and report back to me" Acceptance from the authorized person The dialogue shall be as follows: "<First name and surname of authorized person>, at <name of substation>, <nominal voltage and name of the apparatus> has been opened, isolated and earthed at all points of supply. I may commence with the specified work. On completion remove all tools, equipment and workers and report back to you", 4.12 Handing over and handing back of power lines or sections of power lines Handing over After all isolation and earthing have been completed, the controller shall hand over the apparatus to the authorized person. Handover is an instruction and shall be written out in full by the authorized person on an operating instruction form together with the time of hand over (hand back) Controller The dialogue shall be as follows: "<First name and surname of authorized person>, at <nominal voltage of and name of line>, from <abbreviated pole number> to <abbreviated pole number> the line has been opened and isolated from all points of supply, with a control earth at the point of isolation. You may test and apply working earths, commence with the specified work. On completion, remove all tools and equipment, workers and working earths from the line and hand back the line to me" As acceptance from the authorized person The dialogue shall be as follows: "<First name and surname of authorized person>, at <nominal voltage of and name of line>, from <abbreviated pole number> to <abbreviated pole number> the line has been opened and isolated from all points of supply, with a control earth at the point of isolation. I may test and apply working earths, commence with the specified work. On completion, I shall remove all tools and equipment, workers and working earths from the line and hand back the line to you" Control functions Control shall update the operating diagram according to the changed status of the network apparatus and lines, and record the authorized person's name against the relevant apparatus that has been handed over. Also record a reference number, if applicable National/transmission control or interdistributor control On completion of the necessary operating, an intercontrol handover will take place, thereafter apparatus will be handed out to the relevant authorized persons Operating instruction forms Operating instruction forms shall be in accordance with the examples given in KS Requirements before operating instructions can be issued When an outage is requested by field staff, the scope of work, operating sequence and number of earths required shall be discussed in detail before any instructions are issued. This is necessary to eliminate any misunderstanding or confusion. 4 KEBS 2010 All rights reserved

11 Operating instructions shall be issued and conversed in English Operating sequence Instructions shall be issued in the following sequence: a) switching; b) linking; c) safety testing; and d) earthing. KS : Where technology allows, control and equipment are not installed in separate rooms, switching shall be performed in the following order: a) supervisory facility; b) umbilical cord devices; and c) operating switches on the equipment panel Dressing control panels Auto-reclosing functions Auto-reclose schemes differ from one protection scheme to the next. The breaker's auto-reclose function shall be made inoperable as given in the site-specific procedure Telecontrol and supervisory functions Supervisory schemes differ from substation to substation and each substation requires different treatment. At some stations the supervisory shall be switched OFF before any operating is performed, whilst at others it shall be switched OFF depending on whether operating has been completed or whether operating is conducted remotely, manually or HMI. The requirements shall be stated in the local operating procedure Manual VT selection Where VT selection on busbars are not automated, the VT selection shall be performed manually when a busbar is taken out of service The racking in and out of truck type voltage transformers shall only be carried out under dead conditions. The particular requirements shall be stated in the local operating procedure Under-frequency load-shedding equipment Where a substation is equipped with an under-frequency facility, the selector switch shall be selected to the busbar that remains in service if the other busbar is taken out of service for maintenance purposes Motorized isolators All motorized isolators that are used as isolation points shall be made inoperable by disabling the supply to the motors Transformer tap position control When taking a transformer out of service and when returning it to service, the authorized person shall ensure that the substation auxiliaries and A VR controls are correctly selected as given in the sitespecific procedure. KEBS 2010 All rights reserved 5

12 KS : In the case of voltage regulators, the authorized person shall ensure that the tap changer is in the neutral or mid tap position and manual position before bypassing Specific operating sequence Taking a line breaker out of service for maintenance purposes (alive back) The procedure in to shall be followed when a line breaker is taken out of service for maintenance purposes Switch off supervisory (if relevant) Switch off auto-reclose (where applicable) Open breaker (specify voltage) Check breaker to be open (specify voltage) Open line isolator (specify voltage) Open busbar isolator (specify voltage) Safety test: the following shall be done during a safety test: a) earth busbar side of the breaker (specify voltage); b) earth the line side of the breaker (specify voltage); c) specify the number of earths; and d) obtain a handover from control Returning a line breaker to service after maintenance (alive back) The procedure in to shall be followed when a line breaker is returned to service after maintenance Hand back to control clear of workmen and equipment Remove earths at the busbar and line sides of the breaker (specify voltage), and specify the number of earths Check breaker to be open (specify voltage) Close busbar isolator (specify voltage) Close line isolator (specify voltage) Close breaker (specify voltage) Check line to be on load Switch to auto-reclose (where applicable) Switch to supervisory Verify with control centre that all alarms are clear Taking a line and breaker out of service for maintenance (dead back) The procedure in to shall be followed when a line and breaker are taken out of service for maintenance. NOTE Operating instructions are issued in separate steps because two or more authorized persons are involved. Control centres will co-ordinate operating in conjunction with each other Verify with control centre that all alarms are clear. 6 KEBS 2010 All rights reserved

13 Switch off supervisory (where applicable) Switch off auto-reclose (where applicable) Open breaker (specify voltage). (Supervisory shall be switched on for remote switching.) Check breaker to be open (specify voltage) Open line isolator (specify voltage) Open busbar isolator (specify voltage). NOTE the line. KS :2010 The busbar isolator can be left in the closed position if work is to be done on the line only. Earthing is then necessary only for Control centres to confirm the status of plant with one another Control centres to agree on numbers and positions of required earths Do a safety test: test apparatus for "dead" on all phases Earth busbar side of breaker if the busbar isolator is open (specify voltage) Earth line side of breaker if the busbar isolator is open (specify voltage) Earth on the line (specify voltage) Specify number of earths Control centres to hand over the line with one another as given in KS Control centres to hand over the line to various authorized persons to apply and remove working earth as given in KS Returning a line and breaker to service after maintenance (dead back) The procedure in to shall be followed when a line and breaker are returned to service after maintenance Authorized persons to hand back to control centre Control centres to hand back to each other and co-ordinate removal of earths Remove earths from a) busbar side of breaker, if applied (specify voltage), b) line side of breaker, if applied (specify voltage), c) the line (specify voltage), and specify number of earths removed Control centres to confirm removal of earths from one another and agree on linking Check breaker to be open (specify voltage) Close busbar isolator (specify voltage) Close line isolator (specify voltage) Control centres confirm status and agree on closing and switching of auto-reclose and supervisory Close breaker (specify voltage) Confirm loading Switch on auto-recloser (where applicable) KEBS 2010 All rights reserved 7

14 KS : Switch supervisory ON Verify with control centre that all alarms are clear Taking an interconnected power system (IPS) line out of service for maintenance Outage is sanctioned by National Control and operating instructions will be issued in separate steps as indicated in to This normally involves two control centres who will issue the isolation and earthing instructions in conjunction with each other Authorized persons to contact relevant control centres to commence with the requested outage Control centres to contact National Control and individually request permission to take line out. National Control assesses the situation, checks voltage and loading, and switches out the line at both ends (if required) through supervisory and applies a tag to the breakers. National Control hands out the line to each control centre to issue the necessary operating instructions and, on completion, hand back to National Control Control centres contact each other and co-ordinate the switching OFF of the supervisory and autoreclose and proceed with the isolation of line and busbar isolators. Control centres issue instructions to individual authorized persons Control centres notify each other that isolations are complete and co-ordinate application of earths Control centres issue earthing instructions Control centres hand out the line to each other Each control centre can now hand out the line or panel to the various authorized persons Returning an interconnected power system (IPS) line to service after maintenance The procedure in to shall be followed when an IPS line is returned to service after maintenance Authorized persons to hand line or panel back to control Control centres to hand line back to each other and co-ordinate removal of earths Control centres issue instructions to remove earths and return them to the authorized person Control centres contact National Control individually to hand back the line. clear of all earths National Control will sanction busbar selection and switch ON supervisory to control centres Control centre issues instructions to close busbar and line isolators and switching ON of supervisory to authorized persons. Receive confirmation that linking has been completed as instructed Control centres report back to National Control National Control closes breakers at both ends through the network supervisory system and requests auto-reclose to be switched ON. NOTE Authorized person shall remain on site to verify all remote switching Control centres to notify National Control Taking a transformer panel out of service for maintenance The procedure in to shall be followed when a transformer panel is taken out of service for maintenance. If the HV busbar links are connected to an IPS busbar, sanction from National Control shall be obtained before the transformer panel can be isolated Switch off supervisory Open auxiliary supply (where applicable). 8 KEBS 2010 All rights reserved

15 Open tertiary breaker (where applicable) (specify voltage) Open secondary breaker (specify voltage) Open primary breaker (specify voltage) Check breakers to be open (specify voltage) Test transformer to be dead Open primary busbar isolator (specify voltage) Open secondary busbar isolator (specify voltage) Open tertiary or auxiliary transformer isolator (where applicable) (specify voltage) Safety test and earth KS : In the case of work on transformers and breakers, and on the busbar side of the primary and secondary breakers, the primary, secondary and tertiary windings of the transformer shall be as specified in KS (specify voltages) In the case of work on transformers only, earth the primary, secondary and tertiary sides of the transformer (specify voltages) In the case of work on a breaker only, earth the busbar and transformer sides of the breaker (specify voltage) The control centre shall hand over the apparatus Fully isolate the panel and earth only the apparatus to be worked on. The handout shall be for that apparatus only Returning a transformer panel to service after maintenance The procedure in to shall be followed when a transformer panel is returned to service after maintenance The authorized person hands back the panel to the control centre office clear of workmen and equipment and fit for service If the primary busbar links are connected to an IPS busbar, sanction shall be obtained from National Control before the IPS line can be linked up Control centre issues instructions for the removal of earths Check breakers to be open (specify voltage) Close tertiary or auxiliary transformer isolator (where applicable) (specify voltage) Close primary busbar isolator (specify voltage) Close secondary busbar isolator (specify voltage) Close primary breaker (specify voltage) Close secondary breaker (specify voltage) Close tertiary breaker (where applicable) (specify voltage) Close auxiliary supply (where applicable) Switch supervisory ON. KEBS 2010 All rights reserved 9

16 KS : Taking an interconnected power system transformer panel out of service The operating sequence shall be the same as in the case of a demarcated transformer (taking out and returning to service) Taking a bus coupler breaker or bus section breaker out of service NOTE Some stations have automatic overcurrent and earth-fault protection schemes When changing over busbars from one to the other, start from one end of the busbar, proceed down the busbar closing all necessary isolators and thereafter proceed up the parallel busbar opening all necessary isolators When changing over busbars without a bus coupler, the dead busbar shall be proved healthy by means of a line or transformer breaker where possible The method of closing and opening each panel in turn is only used in special circumstances where the possibility of paralleling two zones through isolators exists. This method shall not be used where a bus coupler is not available On the bus coupler breaker, make sure that it is off overcurrent and earth-fault protection (where applicable). Then follow the steps in (a) to (h): a) link over all the relevant panels from one busbar to the other; b) switch OFF supervisory; c) open the bus section breaker (specify voltage); d) check breaker to be open (specify voltage); e) check bus coupler to be floating; f) switch OFF supervisory; g) open bus coupler breaker (specify voltage); and h) check breaker to be open (specify voltage) On the bus coupler, the following shall apply: a) open bus coupler, busbar 1 isolator (specify voltage); and b) open bus coupler, busbar 2 isolator (specify voltage) On the bus section, the following shall apply: open the relevant busbar isolators (specify voltage) Safety test On the bus coupler, the following shall apply: a) apply on earth busbar 1 on the bus coupler side of the breaker; b) apply on earth busbar 2 on the bus coupler side of the breaker; and c) apply earth on the bus section breaker, earth both sides of the bus section breaker On the busbar, the following shall apply: a) apply earth on the busbar; b) specify number of earths applied; and c) control to hand over apparatus to be worked on only. 10 KEBS 2010 All rights reserved

17 4.30 Returning a bus coupler breaker or bus section breaker back to service NOTE Some stations have automatic overcurrent and earth-fault protection schemes. KS : The procedure in to shall be followed when returning a bus coupler breaker or bus section breaker back to service Hand back apparatus to the control centre Remove all earths On the bus coupler, the following shall apply: a) check the breaker to be open (specify voltage); b) close bus coupler, busbar 1 isolator (specify voltage); c) close bus coupler, bus bar 2 isolator (specify voltage); d) switch on overcurrent and earth-fault protection (where applicable); e) close bus coupler breaker (specify voltage); f) switch off overcurrent and earth-fault protection; g) ensure busbar is alive from voltage indication; and h) switch ON supervisory On the bus section, the following shall apply: a) check the breaker to be open (specify voltage); b) close relevant busbar isolators of the bus section breaker (specify voltage); c) switch on overcurrent and earth-fault protection, where installed; d) close busbar section breaker (specify voltage); e) check breaker to be closed; f) switch off overcurrent and eath-fault protection, where installed; g) switch ON supervisory; and h) link over the required panels Taking a busbar or section of a busbar equipped with a bus coupler or section breaker out of service Switch off supervisory With the bus coupler or the bus section breaker closed and with overcurrent and earth-fault protection switched off, complete steps to Link over the required panels to clear the busbar or section Check that bus coupler or bus section breaker carry no load Open the bus coupler or bus section breakers Open isolators on either side of the breakers Test the relevant busbar or bus section to be dead Apply earths on the busbar or section of busbar according to KS Control centre hands over the busbar to be worked on only. KEBS 2010 All rights reserved 11

18 KS : Returning a bus bar or section of a busbar equipped with a bus coupler or bus section breaker to service Hand back busbar or section of busbar to control centre Remove all earths Specify number of earths Check breakers to be opened Close isolators on either side of the breaker Switch on overcurrent and earth-fault protection, where applicable Close breaker Switch off overcurrent and earth-fault protection Link over required panels Switch on supervisory Check that all alarms are clear Load transfer, isolating or energizing a section of a busbar without a bus coupler or bus section breaker Owing to different technologies and busbar configurations, all operating on unique plant shall be in accordance with local operating procedure Requirements for handing over and handing back apparatus After the apparatus has been earthed in accordance with KS , it shall be handed over to the authorized person. The authorized person shall be responsible for safety testing and for the application and removal of working earths when and where necessary on lines only. The authorized person shall write out the hand over or hand back on an operating instruction form together with the time handed over and time handed back on completion of work. All normal open points that are excluded should, where applicable, be recorded as part of the hand over After a line has been opened, isolated and earthed in accordance with KS between two contral centres, an "intercontral" hand over shall take place. In other words the contral centres shall hand over the line to each other for safety purposes irrespective of whether the contra I centre has work to be done. This is also applicable when working with customers that have recognized control centres Control functions after hand over The intercontrol hand over shall be recorded in both network management centres' operating logs The operating diagrams shall be dressed with the appropriate hand-over labels (i.e., intercontrol or the authorized person's name) The symbols used for dressing the operating diagram shall depend on local requirements. When lines have been handed out between control centres (i.e., intercontral hand over) the lines shall only be handed back when they are ready to be made live and not when work has been completed, i.e., all authorized persons have to hand back first. 12 KEBS 2010 All rights reserved

Draft Kenya Standard for Balloting Not to be Cited as Kenya Standard

Draft Kenya Standard for Balloting Not to be Cited as Kenya Standard KENYA STANDARD KS 2236-3:2010 ICS 03.120.10; 91.140.50 Electricity Supply Quality of supply Part 3: Voltage characteristics, compatibility levels, limits and assessment methods BALLOT DRAFT, MAY 2010 KEBS

More information

KENYA STANDARD DKS 2667: Woven Table cloth and Napery Specification

KENYA STANDARD DKS 2667: Woven Table cloth and Napery Specification KENYA STANDARD DKS 2667: 2016 Woven Table cloth and Napery Specification KEBS 2016 First Edition 2016 DKS2667:2016 TECHNICAL COMMITTEE REPRESENTATION The following organizations were represented on the

More information

SUBJECT HEADING: Switching Programmes ISSUE: 18

SUBJECT HEADING: Switching Programmes ISSUE: 18 SUBJECT: Switchgear/Switching PROCEDURE: S04 SUBJECT HEADING: Switching Programmes ISSUE: 18 DATE: Apr 2017 1. INTRODUCTION 1.1 A written programme of switching operations shall be prepared. This programme

More information

Draft Kenya Standard for Balloting Not to be Cited as Kenya Standard

Draft Kenya Standard for Balloting Not to be Cited as Kenya Standard KENYA STANDARD KS 1859-1:2010 ICS 29.020; 29.240.01 Electrical power transmission and distribution High-voltage operating regulations Part 1: Definitions BALLOT DRAFT, MAY 2010 KEBS 2010 First Edition

More information

SYNCHRONISING AND VOLTAGE SELECTION

SYNCHRONISING AND VOLTAGE SELECTION SYNCHRONISING AND VOLTAGE SELECTION This document is for Relevant Electrical Standards document only. Disclaimer NGG and NGET or their agents, servants or contractors do not accept any liability for any

More information

Draft Kenya Standard for Balloting Not to be Cited as Kenya Standard

Draft Kenya Standard for Balloting Not to be Cited as Kenya Standard KENYA STANDARD KS 2236-4:2010 ICS 91.140.50 Electricity Supply Quality of supply Part 4: Application guidelines for utilities BALLOT DRAFT, MAY 2010 KEBS 2010 First Edition 2010 TECHNICAL COMMITTEE REPRESENTATION

More information

Hamdy Faramawy Senior Application Specialist ABB Sweden

Hamdy Faramawy Senior Application Specialist ABB Sweden Design, Engineering and Application of New Firm Capacity Control System (FCCS) Mohammed Y. Tageldin, MSc. MIET Senior Protection Systems Engineer ABB United Kingdom mohammed.tageldin@gb.abb.com Hamdy Faramawy

More information

KENYA STANDARD DKS 1062:2017 ICS Infants outer wear garments Specification

KENYA STANDARD DKS 1062:2017 ICS Infants outer wear garments Specification KENYA STANDARD DKS 1062:2017 ICS 61.020 Infants outer wear garments Specification TECHNICAL COMMITTEE REPRESENTATION The following organizations were represented on the Technical Committee: Moi University,

More information

Field Instruction Switching Activities. Purpose. Scope. Objective. Safety

Field Instruction Switching Activities. Purpose. Scope. Objective. Safety 8.22 Switching Activities Purpose This instruction provides a safe system for switching on Horizon Powers Low Voltage, High Voltage and or Transmission electrical apparatus/network, where switching operations

More information

Woven interlinings and linings for apparel purposes Specification

Woven interlinings and linings for apparel purposes Specification KENYA STANDARD DKS 214-1: 2017 ICS 59.080 Woven interlinings and linings for apparel purposes Specification Part 1: Woven interlinings for apparal purposes KEBS 2017 SECOND EDITION 2017 TECHNICAL COMMITTEE

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

TS RES - OUTSTANDING ISSUES

TS RES - OUTSTANDING ISSUES TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next

More information

Woven interlinings and linings for apparel purposes Specification

Woven interlinings and linings for apparel purposes Specification KENYA STANDARD DKS 08-21: PART 2: 2017 ICS 59.080 Woven interlinings and linings for apparel purposes Specification Part 2: Woven linings for Apparel Purposes KEBS 2017 SECOND EDITION 2 TECHNICAL COMMITTEE

More information

Greenlining and Bluelining of Ergon Energy Substation Drawings

Greenlining and Bluelining of Ergon Energy Substation Drawings Greenlining and Bluelining of Ergon Energy Table of Contents Purpose and Scope... 1 Responsibilities... 1 Definitions, Abbreviations and Acronyms... 1 References... 1 General... 1 Requirements... 3 Testing

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES

More information

Southern Company Interconnection Requirements for Inverter-Based Generation

Southern Company Interconnection Requirements for Inverter-Based Generation Southern Company Interconnection Requirements for Inverter-Based Generation September 19, 2016 Page 1 of 16 All inverter-based generation connected to Southern Companies transmission system (Point of Interconnection

More information

Distribution transformers Part 2 Ground mounted transformers not closecoupled

Distribution transformers Part 2 Ground mounted transformers not closecoupled PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Technical Specification 35-1 Distribution transformers Part 2 Ground mounted transformers not closecoupled www.energynetworks.org PUBLISHING

More information

ENGINEERING STANDARD FOR INSTRUMENTS ELECTRICAL POWER SUPPLY AND DISTRIBUTION SYSTEMS FIRST EDITION MAY 2013

ENGINEERING STANDARD FOR INSTRUMENTS ELECTRICAL POWER SUPPLY AND DISTRIBUTION SYSTEMS FIRST EDITION MAY 2013 ENGINEERING STANDARD FOR INSTRUMENTS ELECTRICAL POWER SUPPLY AND DISTRIBUTION SYSTEMS FIRST EDITION MAY 2013 This Standard is the property of Iranian Ministry of Petroleum. All rights are reserved to the

More information

Table of Contents. Introduction... 1

Table of Contents. Introduction... 1 Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60214-2 First edition 2004-10 Tap-changers Part 2: Application guide Reference number IEC 60214-2:2004(E) Publication numbering As from 1 January 1997 all IEC publications are

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION IEC TS 60071-5 First edition 2002-06 Insulation co-ordination Part 5: Procedures for high-voltage direct current (HVDC) converter stations Coordination de l isolement - Partie 5:

More information

ESB National Grid Transmission Planning Criteria

ESB National Grid Transmission Planning Criteria ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and

More information

Specification for pvc-insulated cables for electricity supply

Specification for pvc-insulated cables for electricity supply KENYA STANDARD KS 194: 2018 ICS 29.035.01 Specification for pvc-insulated cables for electricity supply (Third Revision, 2018) PUBLIC REVIEW DRAFT, FEBRUARY 2018 TECHNICAL COMMITTEE REPRESENTATION The

More information

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016 PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016 Prepared by System Planning Division Transmission Planning Department PJM 2016 Table of Contents Table of Contents Approval...6

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements Section 502.8 SCADA Technical and Operating Applicability 1 Section 502.8 applies to: (a) the legal owner of a generating unit: (i) connected to the transmission facilities in the balancing authority area

More information

Australian Standard. Switchgear assemblies and ancillary equipment for alternating voltages above 1 kv AS

Australian Standard. Switchgear assemblies and ancillary equipment for alternating voltages above 1 kv AS AS 2067 1984 Australian Standard Switchgear assemblies and ancillary equipment for alternating voltages above 1 kv [Title allocated by Defence Cataloguing Authority: SWITCHGEAR ASSEMBLIES, ELECTRICAL AND

More information

THE GRID CODE OC7.5 INTEGRAL EQUIPMENT TESTS GUIDANCE NOTES

THE GRID CODE OC7.5 INTEGRAL EQUIPMENT TESTS GUIDANCE NOTES THE GRID CODE OC7.5 INTEGRAL EQUIPMENT TESTS GUIDANCE NOTES Issue 9: May 2013 National Grid National Grid Registered Office National Grid Electricity Transmission plc Registered Office: 1-3 Strand London

More information

Australian Standard. Electricity metering equipment (AC) Particular requirements

Australian Standard. Electricity metering equipment (AC) Particular requirements AS 62053.21 2005 AS 62053.21 2005 Australian Standard Electricity metering equipment (AC) Particular requirements Part 21: Static meters for active energy (classes 1 and 2) (IEC 62053-21, Ed.1.0 (2003)

More information

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it.

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it. 1. SCOPE The requirements of this document apply to all Plant, Equipment and Apparatus that are part of, or are Directly connected to, the Company network. Requirements contained herein may be modified

More information

THE GRID CODE OC7.5 INTEGRAL EQUIPMENT TESTS

THE GRID CODE OC7.5 INTEGRAL EQUIPMENT TESTS THE GRID CODE OC7.5 INTEGRAL EQUIPMENT TESTS GUIDANCE NOTES Issue 11: February 2018 National Grid Registered Office National Grid Electricity Transmission plc Registered Office: 1-3 Strand London WC2N

More information

EUROPEAN pr ETS TELECOMMUNICATION February 1996 STANDARD

EUROPEAN pr ETS TELECOMMUNICATION February 1996 STANDARD FINAL DRAFT EUROPEAN pr ETS 300 118 TELECOMMUNICATION February 1996 STANDARD Second Edition Source: ETSI TC-TE Reference: RE/TE-05049 ICS: 33.020 Key words: PSTN, modems Public Switched Telephone Network

More information

RELEVANT ELECTRICAL STANDARDS

RELEVANT ELECTRICAL STANDARDS RELEVANT ELECTRICAL STANDARDS Issue 2 February 2014 National Grid 2014 No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means electronic,

More information

This document is a preview generated by EVS

This document is a preview generated by EVS TECHNICAL REPORT IEC/TR 80002-1 Edition 1.0 2009-09 colour inside Medical device software Part 1: Guidance on the application of ISO 14971 to medical device software IEC/TR 80002-1:2009(E) THIS PUBLICATION

More information

BUS2000 Busbar Differential Protection System

BUS2000 Busbar Differential Protection System BUS2000 Busbar Differential Protection System Differential overcurrent system with percentage restraint protection 1 Typical Busbar Arrangements Single Busbar Double Busbar with Coupler Breaker and a Half

More information

RELEVANT ELECTRICAL STANDARDS

RELEVANT ELECTRICAL STANDARDS RELEVANT ELECTRICAL STANDARDS Issue 2 October 2014 Issue 2 September 2014 National Grid 2014 2014 Copyright owned by National Grid Electricity Transmission plc, all rights reserved. No part of this publication

More information

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements Section 502.8 SCADA Technical and Operating Requirements Applicability 1 Subject to subsections 2 and 3 below, section 502.8 applies to: (a) (c) (d) the legal owner of a generating unit or an aggregated

More information

ELE-CMOS-E-2001 Electrical Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS

ELE-CMOS-E-2001 Electrical Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS 101135-ELE-CMOS-E-2001 Electrical Engineer Holds a B. Sc. in Electrical Power & Machines Engineering and has over 14 years hands-on experience, including 13 years working in operation, maintenance, construction

More information

SWITCHING SAFETY & RELIABILITY CONFERENCE

SWITCHING SAFETY & RELIABILITY CONFERENCE SWITCHING SAFETY & RELIABILITY CONFERENCE JARGON WORKSHEET Energize (v) Energize is the process of applying rated voltage to circuit or equipment. Modified IEEE or OSHA from Adj. to verb. To make a piece

More information

This is a preview - click here to buy the full publication

This is a preview - click here to buy the full publication TECHNICAL REPORT IEC TR 61869-100 Edition 1.0 2017-01 colour inside Instrument transformers Part 100: Guidance for application of current transformers in power system protection INTERNATIONAL ELECTROTECHNICAL

More information

Australian Standard. Electricity metering equipment (AC) Particular requirements. Part 22: Static meters for active energy (classes 0.2 S and 0.

Australian Standard. Electricity metering equipment (AC) Particular requirements. Part 22: Static meters for active energy (classes 0.2 S and 0. AS 62053.22 2005 IEC 62053-22, Ed.1.0 (2003) AS 62053.22 2005 Australian Standard Electricity metering equipment (AC) Particular requirements Part 22: Static meters for active energy (classes 0.2 S and

More information

Revision 24 of Issue 3 of the Grid Code has been approved by the Authority for implementation on 19 th November 2007.

Revision 24 of Issue 3 of the Grid Code has been approved by the Authority for implementation on 19 th November 2007. Our Ref: Your Ref: Date: November 2007 To: All Recipients of the Serviced Grid Code Regulatory Frameworks Electricity Codes National Grid Electricity Transmission plc National Grid House Warwick Technology

More information

This document is a preview generated by EVS

This document is a preview generated by EVS INTERNATIONAL STANDARD ISO 15848-2 Second edition 2015-06-01 Industrial valves Measurement, test and qualification procedures for fugitive emissions Part 2: Production acceptance test of valves Robinetterie

More information

INTERNATIONAL. Medical device software Software life cycle processes

INTERNATIONAL. Medical device software Software life cycle processes INTERNATIONAL STANDARD IEC 62304 First edition 2006-05 Medical device software Software life cycle processes This English-language version is derived from the original bilingual publication by leaving

More information

Identification and recording of 'hot' sites - joint procedure for Electricity Industry and Communications Network Providers

Identification and recording of 'hot' sites - joint procedure for Electricity Industry and Communications Network Providers PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Engineering Recommendation S36 Identification and recording of 'hot' sites - joint procedure for Electricity Industry and Communications

More information

Wind Power Facility Technical Requirements CHANGE HISTORY

Wind Power Facility Technical Requirements CHANGE HISTORY CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical

More information

Guideline for Creating Disconnection Points and Establishing a Not Electrically Connected Area

Guideline for Creating Disconnection Points and Establishing a Not Electrically Connected Area Guideline for Creating Disconnection Points and Establishing a Not Document Number: Authorised by: Issue Date: 29 June 2012 Previous Document: 12 February 2010 Principal Authors: J Dohmen Powerlink D Brown

More information

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT

More information

Network Standard NS

Network Standard NS Network Standard NS 21-2006 Artwork on Western Power Assets Technical Requirements for application to South West Interconnected System (SWIS) DMS #1049174 NS 21-2006 Artwork on Western Power Assets REVISION

More information

South African Distribution Code

South African Distribution Code South African Distribution Code Metering Code Version 6.0 July 2014 This document is approved by the National Energy Regulator of South Africa (NERSA) Issued by: RSA Grid Code Secretariat Contact: Mr.

More information

Complex Solution for the Distribution Substation REF 542plus. Application and Setting Guide

Complex Solution for the Distribution Substation REF 542plus. Application and Setting Guide Complex Solution for the Distribution Substation REF 542plus 1MRS756412 Complex Solution for the Distribution Substation REF 542plus Copyrights The information in this document is subject to change without

More information

Standard for Subsea High Integrity Pressure Protection Systems (HIPPS) API STANDARD 17O SECOND EDITION, JULY 2014

Standard for Subsea High Integrity Pressure Protection Systems (HIPPS) API STANDARD 17O SECOND EDITION, JULY 2014 Standard for Subsea High Integrity Pressure Protection Systems (HIPPS) API STANDARD 17O SECOND EDITION, JULY 2014 Special Notes API publications necessarily address problems of a general nature. With respect

More information

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A. NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A. NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014 BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014 Expiry Year: 2018 APPROVED BY: Original signed by: Paul

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

Differential Protection with REF 542plus Feeder Terminal

Differential Protection with REF 542plus Feeder Terminal Differential Protection with REF 542plus Application and Setting Guide kansikuva_bw 1MRS 756281 Issued: 09.01.2007 Version: A Differential Protection with REF 542plus Application and Setting Guide Contents:

More information

Engineering Recommendation M30 Issue Standard Electricity Network Operator Electricity Smart Meter Configurations

Engineering Recommendation M30 Issue Standard Electricity Network Operator Electricity Smart Meter Configurations PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Engineering Recommendation M30 Standard Electricity Network Operator Electricity Smart Meter s www.energynetworks.org PUBLISHING AND

More information

Notes 1: Introduction to Distribution Systems

Notes 1: Introduction to Distribution Systems Notes 1: Introduction to Distribution Systems 1.0 Introduction Power systems are comprised of 3 basic electrical subsystems. Generation subsystem Transmission subsystem Distribution subsystem The subtransmission

More information

Item designation in electrotechnology

Item designation in electrotechnology AS 3702 1989 Australian Standard Item designation in electrotechnology This Australian Standard was prepared by Committee TE/13, Symbols, Units & Quantities for Electrotechnology. It was approved on behalf

More information

ISO 5459 INTERNATIONAL STANDARD. Geometrical product specifications (GPS) Geometrical tolerancing Datums and datum systems

ISO 5459 INTERNATIONAL STANDARD. Geometrical product specifications (GPS) Geometrical tolerancing Datums and datum systems INTERNATIONAL STANDARD ISO 5459 Second edition 2011-08-15 Geometrical product specifications (GPS) Geometrical tolerancing Datums and datum systems Spécification géométrique des produits (GPS) Tolérancement

More information

What s New in C TM -2015, IEEE Guide for Protective Relay Applications to Transmission Lines

What s New in C TM -2015, IEEE Guide for Protective Relay Applications to Transmission Lines What s New in C37.113 TM -2015, IEEE Guide for Protective Relay Applications to Transmission Lines This paper is a product of the IEEE PSRC D36 Working Group. The working group consisted of the following

More information

ReliabilityFirst Regional Criteria 1. Disturbance Monitoring and Reporting Criteria

ReliabilityFirst Regional Criteria 1. Disturbance Monitoring and Reporting Criteria ReliabilityFirst Regional Criteria 1 Disturbance Monitoring and Reporting Criteria 1 A ReliabilityFirst Board of Directors approved good utility practice document which are not reliability standards. ReliabilityFirst

More information

PROTECTION of electricity distribution networks

PROTECTION of electricity distribution networks PROTECTION of electricity distribution networks Juan M. Gers and Edward J. Holmes The Institution of Electrical Engineers Contents Preface and acknowledgments x 1 Introduction 1 1.1 Basic principles of

More information

This is a preview - click here to buy the full publication

This is a preview - click here to buy the full publication IEC/TR 80002-1 TECHNICAL REPORT Edition 1.0 2009-09 colour inside Medical device software Part 1: Guidance on the application of ISO 14971 to medical device software INTERNATIONAL ELECTROTECHNICAL COMMISSION

More information

P.O (November 2009) This is an unofficial translation of the latest draft of the Spanish grid code. Source: Jason MacDowell, GE Energy

P.O (November 2009) This is an unofficial translation of the latest draft of the Spanish grid code. Source: Jason MacDowell, GE Energy INSTALLATIONS CONNECTED TO A POWER TRANSMISSION SYSTEM AND GENERATING EQUIPMENT: MINIMUM DESIGN REQUIREMENTS, EQUIPMENT, OPERATIONS, COMMISSIONING AND SAFETY. P.O. 12.2 (November 2009) This is an unofficial

More information

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 1T-18

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 1T-18 BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 1T-18 LIVE LINE PERMITS, ASSURANCE OF NO RECLOSE PERMITS AND CAUTION TAGS Supersedes OO 1T-18 issued 13 October 2010 Review Year: 2019 Original signed by:

More information

EDS LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS

EDS LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS ENGINEERING DESIGN STANDARD EDS 08-2109 LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS Network(s): Summary: EPN, LPN, SPN This standard provides guidance on the installation of

More information

ECP GROUND-MOUNTED SWITCHGEAR WITH PROTECTION RELAYS COMMISSIONING PROCEDURE

ECP GROUND-MOUNTED SWITCHGEAR WITH PROTECTION RELAYS COMMISSIONING PROCEDURE ENGINEERING COMMISSIONING PROCEDURE ECP 11-0512 GROUND-MOUNTED SWITCHGEAR WITH PROTECTION RELAYS COMMISSIONING PROCEDURE Network(s): Summary: EPN, LPN, SPN This procedure details the testing and commissioning

More information

National Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance

National Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance National Grid UK Electricity Transmission plc NATIONAL SAFETY INSTRUCTION and Guidance NSI 26 RAILWAY CONNECTION CIRCUITS Copyright National Grid plc 2016, all rights reserved. No part of this publication

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

Insulation co-ordination Part 1: Definitions, principales and rules. IEC 2006 Copyright - all rights reserved

Insulation co-ordination Part 1: Definitions, principales and rules. IEC 2006 Copyright - all rights reserved INTERNATIONAL STANDARD IEC 60071-1 Eight edition 2006-01 Insulation co-ordination Part 1: Definitions, principales and rules IEC 2006 Copyright - all rights reserved No part of this publication may be

More information

Education & Training

Education & Training Distribution System Operator Certificate This program provides you with a proficient working knowledge in modern electric power distribution systems. These four classes are designed to walk students through

More information

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application General Application Information Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application Hydro One Remote Communities Inc. Lori.Rice@hydroone.com 1-807-474-2828 This Application

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

This document is a preview generated by EVS

This document is a preview generated by EVS IEC 61882 Edition 2.0 2016-03 REDLINE VERSION colour inside Hazard and operability studies (HAZOP studies) Application guide IEC 61882:2016-03 RLV(en) THIS PUBLICATION IS COPYRIGHT PROTECTED Copyright

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 14223-1 First edition 2003-07-01 Radiofrequency identification of animals Advanced transponders Part 1: Air interface Identification des animaux par radiofréquence Transpondeurs

More information

EDS FAULT LEVELS

EDS FAULT LEVELS Document Number: EDS 08-1110 Network(s): Summary: EPN, LPN, SPN ENGINEERING DESIGN STANDARD EDS 08-1110 FAULT LEVELS This standard provides guidance on the calculation, application and availability of

More information

Diagrams for the chemical and petrochemical industry. Part 1: Specification of diagrams

Diagrams for the chemical and petrochemical industry. Part 1: Specification of diagrams Provläsningsexemplar / Preview INTERNATIONAL STANDARD ISO 10628-1 First edition 2014-09-15 Diagrams for the chemical and petrochemical industry Part 1: Specification of diagrams Schémas de procédé pour

More information

HIGH VOLTAGE RULES. Document Owner: HV Group. Authorised: Electrical Services Manager Liberty Primary Steel

HIGH VOLTAGE RULES. Document Owner: HV Group. Authorised: Electrical Services Manager Liberty Primary Steel HIGH VOLTAGE RULES Document Owner: HV Group Authorised: Electrical Services Manager Liberty Primary Steel HIGH VOLTAGE RULES Revision 10 INDEX 1.0 GENERAL 1.1 SCOPE 1.2 DUTIES 1.3 SUPPLY AND KNOWLEDGE

More information

DRAFT UGANDA STANDARD

DRAFT UGANDA STANDARD DRAFT UGANDA STANDARD DUS 193-1 First Edition 2018-09-dd Steel wires and wire products for fencing Part 1: Barbed wires Specification Reference number UNBS 2018 Compliance with this standard does not,

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60601-1-6 First edition 2004-06 Medical electrical equipment Part 1-6: General requirements for safety Collateral standard: Usability This English-language version is derived

More information

ISO INTERNATIONAL STANDARD. Petroleum and natural gas industries Offshore production installations Basic surface process safety systems

ISO INTERNATIONAL STANDARD. Petroleum and natural gas industries Offshore production installations Basic surface process safety systems INTERNATIONAL STANDARD ISO 10418 Second edition 2003-10-01 Petroleum and natural gas industries Offshore production installations Basic surface process safety systems Industries du pétrole et du gaz naturel

More information

Recommended Practice for Wet and Dry Thermal Insulation of Subsea Flowlines and Equipment API RECOMMENDED PRACTICE 17U FIRST EDITION, FEBRUARY 2015

Recommended Practice for Wet and Dry Thermal Insulation of Subsea Flowlines and Equipment API RECOMMENDED PRACTICE 17U FIRST EDITION, FEBRUARY 2015 Recommended Practice for Wet and Dry Thermal Insulation of Subsea Flowlines and Equipment API RECOMMENDED PRACTICE 17U FIRST EDITION, FEBRUARY 2015 Special Notes API publications necessarily address problems

More information

Single Line Diagram of Substations

Single Line Diagram of Substations Single Line Diagram of Substations Substations Electric power is produced at the power generating stations, which are generally located far away from the load centers. High voltage transmission lines are

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 62271-100 Edition 1.1 2003-05 Edition 1:2001 consolidated with amendment 1:2002 High-voltage switchgear and controlgear Part 100: High-voltage alternating-current circuit-breakers

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

Australian Standard. High-voltage test techniques. Part 3: Definitions and requirements for on-site testing AS IEC , Ed.

Australian Standard. High-voltage test techniques. Part 3: Definitions and requirements for on-site testing AS IEC , Ed. AS 60060.3 2008 IEC 60060-3, Ed. 1 (2006) AS 60060.3 2008 Australian Standard High-voltage test techniques Part 3: Definitions and requirements for on-site testing This Australian Standard was prepared

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60076-5 Third edition 2006-02 Power transformers Part 5: Ability to withstand short circuit IEC 2006 Copyright - all rights reserved No part of this publication may be reproduced

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60099-4 Edition 2.1 2006-07 Edition 2:2004 consolidated with amendment 1:2006 Surge arresters Part 4: Metal-oxide surge arresters without gaps for a.c. systems IEC 2006 Copyright

More information

ISO INTERNATIONAL STANDARD. Metallic materials Knoop hardness test Part 3: Calibration of reference blocks

ISO INTERNATIONAL STANDARD. Metallic materials Knoop hardness test Part 3: Calibration of reference blocks INTERNATIONAL STANDARD ISO 4545-3 First edition 2005-11-15 Metallic materials Knoop hardness test Part 3: Calibration of reference blocks Matériaux métalliques Essai de dureté Knoop Partie 3: Étalonnage

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 3439.2:2002 IEC 60439-2:2000 AS/NZS 3439.2 Australian/New Zealand Standard Low-voltage switchgear and controlgear assemblies Part 2: Particular requirements for busbar trunking systems (busways)

More information

1

1 Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive

More information

AS/NZS CISPR 14.2:2015

AS/NZS CISPR 14.2:2015 AS/NZS CISPR 14.2:2015 (CISPR 14-2, Ed. 2.0:2015, IDT) Australian/New Zealand Standard Electromagnetic compatibility Requirements for household appliances, electric tools and similar apparatus Part 2:

More information

KENYA ELECTRICITY GENERATING COMPANY LTD

KENYA ELECTRICITY GENERATING COMPANY LTD KENYA ELECTRICITY GENERATING COMPANY LTD TENDER No. KGN-HYD-014-2016 TENDER FOR REHABILITATION OF PROTECTION EQUIPMENT FOR MASINGA HYDRO POWER STATION 20/06/2016 ADDENDUM NO. 1 In accordance with the tender

More information

ISO INTERNATIONAL STANDARD. Industrial fans Specifications for balance quality and vibration levels

ISO INTERNATIONAL STANDARD. Industrial fans Specifications for balance quality and vibration levels INTERNATIONAL STANDARD ISO 14694 First edition 2003-03-15 Industrial fans Specifications for balance quality and vibration levels Ventilateurs industriels Spécifications pour l'équilibrage et les niveaux

More information

This document is a preview generated by EVS

This document is a preview generated by EVS TECHNICAL SPECIFICATION IEC TS 61400-14 First edition 2005-03 Wind turbines Part 14: Declaration of apparent sound power level and tonality values Reference number IEC/TS 61400-14:2005(E) Publication numbering

More information

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Engineering Specification Head of Electrical Engineering MESP 050100-01 TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Version:

More information

Australian Standard. Electricity metering equipment (ac) Particular requirements. Part 23: Static meters for reactive energy (classes 2 and 3)

Australian Standard. Electricity metering equipment (ac) Particular requirements. Part 23: Static meters for reactive energy (classes 2 and 3) AS 62053.23 2006 IEC 62053-23, Ed.1.0 (2003) AS 62053.23 2006 Australian Standard Electricity metering equipment (ac) Particular requirements Part 23: Static meters for reactive energy (classes 2 and 3)

More information

EI HIGH VOLTAGE INSULATION TESTING POLICY

EI HIGH VOLTAGE INSULATION TESTING POLICY Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and

More information