BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A. NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014

Size: px
Start display at page:

Download "BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A. NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014"

Transcription

1 BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014 Expiry Year: 2018 APPROVED BY: Original signed by: Paul Choudhury General Manager, Real Time Operations Denotes Revision

2 Page 2 of GENERAL This order describes the operating procedures for the Northwest Transmission Line (NTL) facilities, added to the North Coast transmission area (7T-30 North Coast Interconnection ). This subsystem is an extension of facilities is between Skeena Bob Quinn, and includes the interconnection of IPP generation (Forrest Kerr), and Transmission Voltage Customers (Red Chris Mine). The Northwest Transmission Line (2L102), and customer owned line (2L387) are scheduled to become operational during the month of July Once energized, the bulk transmission system will provide a secure interconnection into the northwest region of the province. This order provides operating procedures for switching, monitoring and responses for operating the subsystem. Variations from these procedures for specific operating conditions will be provided through additional Operating Plans on a case by case basis. Additional Operating Plans are engineered to support outages and short term operating requirements, superseding as necessary requirements in this order. All RAS information, Reliability Must Run generation requirements, and Operating Limits information are contained in Operating Order 7T-30 North Coast Interconnection for implementation in the Transient Stability Application (TSA-PM). The subsystem s facilities include: 2L102 - a km 287 kv transmission line connecting Skeena (SKA) Substation at Terrace with a new substation Bob Quinn (BQN) near Bob Quinn Lake. Forrest Kerr (FKR) IPP generation station, located about 40 km southwest from Bob Quinn (BQN), owned and operated by AltaGas Ltd. (AltaGas). 2L379 - a 38.7 km 287 kv AltaGas owned transmission line connecting FKR to the BQN 287 kv bus. Red Chris Mine (RDC), a transmission voltage customer s copper/gold mine owned by Imperial. 2L374 - a km transmission line BQN to RDC. FKR is the first IPP project to be connected to the subsystem, with an ultimate capacity of 385 MW. The FKR IPP consists of 3 run-of-the-river hydroelectric generation plant sites: Forrest Kerr (FKR) - nine 26.1 MVA units. Volcano Creek (VOL) - two 10 MVA units, 7 km from tap point to FKR and 1.1 km from tap point to VOL. McLymont (MCY) - three MVA units, 10 km from FKR (to be in service late 2015 in the second stage). 2L374 is expected to be completed by the end of July Once completed, RDC will connect 45 MW load to the BCH transmission system. In addition to the 287 kv substation and 2L374, the RDC site features: An entrance circuit breaker with Point-on-wave switching for converter transformer energization to control voltage sag at the POI. Fibre Optic Cable from Bob Quinn to the Mine site with communication channel for transfer tripping and Remedial Action Schemes (RAS)

3 Page 3 of RESPONSIBILITIES Refer to Operating Orders 1T-11A for Operating Responsibility and Operating Authority assignments for the BC Hydro Control Centre (BCHCC). AltaGas responsibilities to contact the BC Hydro Control Centre are outlined in Operating Order 4T- FRK-01 Sections 2 and 10. Red Chris Mines is responsible for informing BC Hydro of substation equipment status. The BCH Control Centre (BCHCC) Operator is responsible for: Updating the status of the BQN and FKR equipment in the Energy Management System (EMS) when notified of changes by the FKR System Operator. Communicating with the FKR Operators prior to energizing or de-energizing 2L379 or 2L102, so joint action can be taken to minimize the system impacts. Communicating and implementing switching instructions. Issuing and tracking Safety Protection Guarantees and Guarantees of Isolation. Notifying customers of expected system conditions and possible special operating requirements prior to any scheduled separation. 3.0 VOLTAGE CONTROL The BQN normal operating voltage range should be between kv. The system nominal voltage is 287 kv. Voltages must be kept below 315 kv except for short times during switching when higher voltages cannot be avoided. Refer to Section 5.0 for impacts of reactor configurations on voltage when switching 2L102. Also refer to Section 4.0 for reactive equipment considerations and cautions. Bob Quinn Auto-var Control Scheme (BQN AVC) (CURRENTLY NOT IN-SERVICE) BQN should be operated with BQN 2RX22 inserted and manually cut it out when the BQN voltage drops to 290 kv and manually insert when voltage rises to 304 kv. Forrest Kerr Automatic Voltage Regulators (FKR AVRs) The FKR AVRs (generator AVRs) will normally be operated in automatic voltage control mode and used to regulate each generator s terminal voltage. Operation in other control modes (e.g. constant power factor control) must be authorized by BC Hydro. The BC Hydro Control Centre will notify AltaGas whenever the FKR generator AVR voltage set points need to be changed to meet system voltage requirements. AltaGas will comply with this operating request to the full extent of the generator control capabilities considering all safety, and electromechanical constraints and normal power factor requirements. The FKR AVRs will normally be set to regulate the BQN bus voltage at 293 kv (102%). 4.0 EQUIPMENT CONSIDERATIONS Bob Quinn Reactors There are three shunt reactors located within the BQN station and there purpose is to help regulate the high voltages expected under light load periods and low power transfers: BQN 2RX231 (35 Mvar switchable reactor) BQN 2RX22 (15 Mvar switchable reactor )

4 Page 4 of 10 BQN 2RX25 (20 Mvar line reactor tied to 2L374) The BQN 2RX231 (35 Mvar) is operated manually due to a large switching voltage change (i.e. a delta V of approximately 19 kv). Caution: All three BQN reactors shall not be normally in service at same time unless 2L374 is in service. This means that BQN 2RX25 should not be in service unless 2L374 is placed in service, and removed from service when the line is switched out (not normally to be used as a bus reactor). In abnormal conditions, such as any of (SKA 2RX1 or SKA 2RX2 or BQN 2CX1) OOS, the above caution is relaxed provided that 2L102 reactive compensation is undercompensated. See 3T-BQN- 01, Section 2.2. BQN 2RX25 is a line reactor (20 Mvar) and is required for 2L379 operation. When BQN 2D25 is open, BQN 2DRX25 must be opened (cut out). BQN 2SA25 is a sacrificial Surge Arrestor (SSA). It is expected the SSA will fail within ~10 Seconds if DTT to RDC fails following a TOV exceeding 1.16pu (when manual switching or protection operates). See 3T-BQN-01 for detailed information on reactor switching procedures. Bob Quinn Series Capacitor (BQN 2CX1) The series capacitor has been installed within the BQN substation and has been designed to provide 35% of the line series reactance of 2L102. The purpose of the series capacitor is for improving the transmission system angular and voltage stability requirements and the ability to transfer more power across the same transmission circuit. BQN 2CX1 is located on the source side of BQN station (i.e. BQN 2L102 terminal) and when inserted the voltage across the series capacitor will increase the voltage seen on the load side of the BQN substation by approximately 2.3 kv. Automatic Insert Enable/Disable feature: There is an automatic insert control feature is provided for each bank and allows all automatic re-insert protections to be enabled or disabled. This includes the automatic control protection which will insert the bank when 2BP2 is opened. Caution: The automatic control function must be disabled prior to performing any switching. When Auto Insert is Enabled, the capacitor bank will be automatically reinserted after a temporary bypass. When Auto Insert is Disabled (or a permanent bypass), there is no automatic re-insertion and the bank can only can be inserted manually, Bob Quinn 4 th Harmonic Filter (BQN 25HF4) System studies identified a parallel resonance condition near the 4th harmonic as seen looking into the BC Hydro system from the Forrest Kerr Substation. The installation of 4th harmonic filter 25HF4 at BQN is to mitigate high and very slow decaying temporary overvoltage on 1L381 and 1L387 which would result if the fourth harmonic parallel resonance condition is excited. 25HF4 consists of tuned reactors connected in series with a grounded shunt capacitor bank. The capacitor bank has a three phase effective rating of 3.6 MVAR at 27.5kV. Protection for 25HF4 includes a SEL multifunction overcurrent relay for detection of major faults and filter unbalance. Bob Quinn Station Service Equipment BQN primary station service is provided by a 10 MVA step down transformer. The transformer high

5 Page 5 of 10 side voltage is rated to 287 kv. Immediate action will need to be taken to correct voltage deviations greater than plus 10% of this nameplate rating. (i.e. 287 x 110% = 315 kv). If the bus voltages cannot be reduced less than the 315 kv value, the transformer should be off loaded by opening BQN 2DT3 to automatically transfer the station service supply to the standby diesel generator. Abnormal System Configurations For SKA 2B11 outages requirements: Option 1: Open SKA 2CB7, to drop 2L102 under a SKA T2 contingency Option 2: Offload SKA T4 in order to prevent 2L102 power flow through transformer under SKA T2 contingency. However, as a result of this contingency, 2L102 will be open ended at SKA and the line will need to be dropped as the IPP FKR is not design to operate islanded. 5.0 GUIDELINES FOR ENERGIZING CIRCUITS Normal Energization Procedures The following procedures are intended to minimize open-end voltages. With all reactors available no voltages above 315 kv should be encountered except in abnormal situations. During switching, voltages up to 325 kv may be tolerated for no more than two minutes providing a stable voltage no greater than 315 kv will result post switching. This is due the fact that the BQN 2SA25 sacrificial surge arrestor will be placed at risk of failure during prolonged periods with voltage greater than 315 kv. At a voltage of 333 kv, BQN 2SA25 is expected to fail after approximately 10 seconds. The BQN should be operated in accordance with requirements in Section 3.0 during energization procedures. SKA is the lead end terminal to BQN and similarly BQN will the lead terminal to FKR. Under NO circumstances will 2L379 be allowed to be energized from FKR to BQN. Energizing 2L102 2L102 is to be energized from SKA end only. There should be no high voltage issue when all of the reactors are BQN are available (BQN 2RX231, 2RX22 and 2RX25). The SKA 500KV bus voltage should be between KV prior to line energization. The expected open-end voltage on 2L102 will be approximately kV at BQN. Normal pre-switching conditions for re-energizing 2L102 include: The SKA Auto-var control scheme is ON SKA 2CB7: open (SKA 287 Ring OPENED ) SKA 2CB8: open (2L102 OPEN) SKA 2RX1: cut in SKA 2RX2: cut in SKA 2D22: closed BQN 2D23: closed BQN 2RX231: cut in BQN 2BP2: open BQN 2D31: closed BQN 2D32: closed BQN 2CBCX1: closed (Series Capacitor by-passed) BQN 2CB1: open BQN 2CB2: open BQN 2CB3: open BQN 2CB4: open BQN 2CB22: closed BQN 2DT3: closed

6 Page 6 of 10 BQN 2D21: open (2L379 disconnected to FKR) BQN 2D25: open (2L374 disconnected to RDC) Switching Sequence SKA 2CB8: CLOSE Open-end voltage at BQN should be about 305KV (Energizes SKA 2B7, 2RX1/2NRX1, 2RX2/2NRX2, 2L102, BQN 2B3, And 2RX231) SKA 2CB7: CLOSE closing the SKA 287KV bus ring BQN 2CB3: CLOSE BQN 287KV bus voltage will drop to around 298KV (Energizes BQN 2B2, 2RX22 and station service)

7 Page 7 of 10 Energizing of 2L102 for Different Reactor (RX) Configurations When energizing 2L102, and there are reactor outages at SKA and/or BQN, the following preenergization reactor configurations should be observed to protect against high voltage at BQN. The configuration requirements are a function of the pre-switching SKA voltage. The voltage at SKA is controlled in part by the transfers from KIT to MIN (2L103). Table: Expected voltage at BQN and SKA vs RX in-service configuration. With SKA AVC in-service, SKA 500kV bus Voltage: or lower SKA 287kV bus Voltage: or lower: SKA 2RX1 SKA 2RX2 BQN 2RX231 BQN 2RX22 BQN 287kV Bus Voltage SKA 500kV Bus Voltage Energizing 2L379 2L379 can only be energized from the BQN end. The line energizing procedures are outline in FKR local ordering order 4T-FKR-01 under Section 7.1. The following procedure assumes 2L102 and 2L374 are in service. Normal pre-switching conditions for re-energizing 2L379 include: SKA Auto-var control scheme is ON SKA 2CB7: closed (SKA 287 Ring OPENED ) SKA 2CB8: closed SKA 2RX1: cut in SKA 2RX2: cut in SKA 2D22: closed BQN 2D23: closed BQN 2RX231: cut in BQN 2BP2: open BQN 2D31: closed

8 Page 8 of 10 BQN 2D32: closed BQN 2CBC1: open (Series Capacitor inserted) BQN 2CB1: open BQN 2CB2: open BQN 2CB3: closed BQN 2CB4: open BQN 2CB22: closed (BQN 2RX22 cut in) BQN 2DT3: closed BQN 2D21: closed (2L379 connected to FKR) FKR 2CB1: open FKR 2CB4: open Switching Sequence: BQN 2CB2: CLOSE Open-end voltage at FKR should be about 304.5KV (Energizes 2L379) AltaGas permission given to close FKR 2CB1 : CLOSE energize FKR transformer (FKR 2T1) FKR 2CB4 : CLOSE energize FKR transformer (FKR 2T3) Energizing 2L374 2L374 can only be energized from the BQN end. The line energizing procedures are outline in RDC local ordering order 3T-RDC-01 under Section 7.1. The following procedure assumes 2L102 and 2L379 are in service. Normal pre-switching conditions for re-energizing 2L374 include: SKA Auto-var control scheme is ON BQN 2CBCX1: open (Series Capacitor inserted) BQN 2RX231: Cut in BQN 2RX22: Cut in 2L379: Energized (FKR online with a minimum of 15 MVA) BQN 2D25: closed BQN 2DRX25:closed (BQN 2RX25 cut in) BQN 2CB1: open BQN 2CB4: open Switching: BQN 2CB4: CLOSE Open-end voltage at RDC should be about 311KV (Energizes 2L374) BQN 2CB1: CLOSE to close BQN 287 kv bus ring Energizing of 2L374 when BQN 2RX231 is Out Of Service (OOS) and FKR is Offline This section is to be developed.

9 Page 9 of GUIDELINES FOR DE-ENERGIZING CIRCUITS De-Energizing 2L102 Regardless of the DTT status, when manually de-energizing 2L102, best practice is to: offload and open 2L374 to RDC offload and open 2L379 to FKR SKA 2CB8: OPEN (Opening 287 kv SKA Ring) SKA 2CB7: OPEN (Dropping 2L102 to BQN) De-Energizing 2L374 The line de-energizing procedures are outline in RDC local ordering order 3T-RDC-01 under Section 6.1. Open at RDC first then de-energize line from BQN. De-Energizing 2L379 The line de-energizing procedures are outline in FKR local ordering order 4T-FKR-01 under Section 6.1. Open at FKR first then de-energize line from BQN. 7.0 EMERGENCY LINE ENERGIZING REQUIREMENTS Energizing 2L102 To be energized from SKA end ONLY, and there MUST be at least 35 MVAR shunt reactance available at BQN to be switched in PRIOR to picking up the line. 8.0 PROTECTION REQUIREMENTS AND SPECIAL FEATURES Special Requirements For three phase tripping, unsuccessful single-pole-reclose, detection of 2L102 open terminal and receipt of trip signals from 2RX231 and 2CX1 protections, the 2L102 protections will trip into BQN 2L379 protections to trip BQN 2CB1 and BQN 2CB2, and key a DTT to FKR generation. This requirement is necessary to avoid temporary over-voltages for BC Hydro customers, if BQN becomes isolated from SKA. When additional load/generation is connected to the BQN station, these devices 87L/87LS will extend this tripping to include those loads and generation. BQN will receive a non-reclosable DTT from SKA for events including: terminal breaker failure, detection of system over-voltage line connected shunt reactor protection operation. SKA will send BQN a sustained DTT to allow the shunt reactors time for auto isolation. BQN Devices 87L/87LS will block close 2CB1/2CB3 until the received DTT resets. Single Pole Reclosing 2L102 and 2L379 are capable for single pole operation. 2L102 will be operated with reclosing in Position 4 (Trip/Reclose for SLG trips only) at SKA and BQN ends. SKA is designated the lead end. 2L379 will be operated with reclosing in Position 1 (3 pole trip for all faults). BQN is the lead end.

10 Page 10 of 10 Fault Location Acquisition Recorder (FLAR) A FLAR system has been installed to provide fault location data for both 2L102 to SKA (FLAR1) and for 2L379 to Forest Kerr IPP (FLAR2). The communication link to FVO will be an IP based link to the FVOBCTFLAR1 server at FVO. The 3 phase reactor 2LRX23 is installed to block fault wavefronts from the bus side reaching FLAR1. FLAR2 will detect fault wavefronts on the bus side of 2LRX23. FLAR1 and FLAR2 are expected to be part of a development to implement fast bypass switching of the series capacitor 2SC l REVISION HISTORY Revised By Revision Date Summary of Revision SJC,DSM, 7 July 2014 New Order RAC SJC 14 July 2014 Section 3.0 : BQN Auto Var scheme not in service

BC HYDRO GRID OPERATIONS OPERATING ORDER 7T-33. SOUTH INTERIOR SUBSYSTEM Supersedes OO 7T-33 Issued 05 July 2011

BC HYDRO GRID OPERATIONS OPERATING ORDER 7T-33. SOUTH INTERIOR SUBSYSTEM Supersedes OO 7T-33 Issued 05 July 2011 BC HYDRO GRID OPERATIONS OPERATING ORDER 7T-33 SOUTH INTERIOR SUBSYSTEM Supersedes OO 7T-33 Issued 05 July 2011 Expiry Year: 2015 APPROVED BY: Original signed by: Paul Choudhury General Manager, Real Time

More information

Single-Pole Operation Leads to Hazardous Over- Voltage on Adjacent Lines

Single-Pole Operation Leads to Hazardous Over- Voltage on Adjacent Lines 1 Single-Pole Operation Leads to Hazardous Over- Voltage on Adjacent Lines Mukesh Nagpal, Terry Martinich, Ska-Hiish, Tyler Scott, Gurinder Hundal and Apollo Zhang BC Hydro, BC, Canada Abstract BC Hydro

More information

Southern Company Interconnection Requirements for Inverter-Based Generation

Southern Company Interconnection Requirements for Inverter-Based Generation Southern Company Interconnection Requirements for Inverter-Based Generation September 19, 2016 Page 1 of 16 All inverter-based generation connected to Southern Companies transmission system (Point of Interconnection

More information

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES Highgate Converter Overview Prepared by Joshua Burroughs & Jeff Carrara IEEE PES Highgate Converter Abstract Introduction to HVDC Background on Highgate Operation and Control schemes of Highgate 22 Why

More information

ESB National Grid Transmission Planning Criteria

ESB National Grid Transmission Planning Criteria ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and

More information

Transmission Interconnection Requirements for Inverter-Based Generation

Transmission Interconnection Requirements for Inverter-Based Generation Transmission Requirements for Inverter-Based Generation June 25, 2018 Page 1 Overview: Every generator interconnecting to the transmission system must adhere to all applicable Federal and State jurisdictional

More information

Wind Power Facility Technical Requirements CHANGE HISTORY

Wind Power Facility Technical Requirements CHANGE HISTORY CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical

More information

BC HYDRO T&D SYSTEM OPERATIONS SYSTEM OPERATING ORDER 7T-14. BRIDGE RIVER LOWER MAINLAND INTERCONNECTION Supersedes 7T-14 issued 03 April 2017

BC HYDRO T&D SYSTEM OPERATIONS SYSTEM OPERATING ORDER 7T-14. BRIDGE RIVER LOWER MAINLAND INTERCONNECTION Supersedes 7T-14 issued 03 April 2017 BC HYDRO T&D SYSTEM OPERATIONS SYSTEM OPERATING ORDER 7T-14 BRIDGE RIVER LOWER MAINLAND INTERCONNECTION Supersedes 7T-14 issued 03 April 2017 Review Year: 2022 APPROVED BY: Original signed by Bob Cielen

More information

Central Hudson Gas & Electric Corporation. Transmission Planning Guidelines

Central Hudson Gas & Electric Corporation. Transmission Planning Guidelines Central Hudson Gas & Electric Corporation Transmission Planning Guidelines Version 4.0 March 16, 2016 Version 3.0 March 16, 2009 Version 2.0 August 01, 1988 Version 1.0 June 26, 1967 Table of Contents

More information

Technical Interconnection Requirements For Transmission Voltage Customers for Service at 60,000 to 287,000 Volts R XX

Technical Interconnection Requirements For Transmission Voltage Customers for Service at 60,000 to 287,000 Volts R XX Technical Interconnection Requirements For Transmission Voltage Customers for Service at 60,000 to 287,000 Volts R XX May 2018 Disclaimer This document provides general technical interconnection requirements

More information

Transmission System Phase Backup Protection

Transmission System Phase Backup Protection Reliability Guideline Transmission System Phase Backup Protection NERC System Protection and Control Subcommittee Draft for Planning Committee Approval June 2011 Table of Contents 1. Introduction and Need

More information

ITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/

ITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/ ITC Holdings Planning Criteria Below 100 kv * Category: Planning Type: Policy Eff. Date/Rev. # 12/09/2015 000 Contents 1. Goal... 2 2. Steady State Voltage & Thermal Loading Criteria... 2 2.1. System Loading...

More information

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-17. BC - ALBERTA INTERCONNECTION Supersedes 7T-17 dated 07 January 2015

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-17. BC - ALBERTA INTERCONNECTION Supersedes 7T-17 dated 07 January 2015 BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-17 BC - ALBERTA INTERCONNECTION Supersedes 7T-17 dated 07 January 2015 Review Year: 2019 APPROVED BY: Original signed by: Paul Choudhury, General Manager,

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements Section 502.8 SCADA Technical and Operating Applicability 1 Section 502.8 applies to: (a) the legal owner of a generating unit: (i) connected to the transmission facilities in the balancing authority area

More information

Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies

Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies T.G. Martinich, M. Nagpal, A. Bimbhra Abstract-- Technological advancements in high-power

More information

Table of Contents. Introduction... 1

Table of Contents. Introduction... 1 Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...

More information

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 1T-18

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 1T-18 BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 1T-18 LIVE LINE PERMITS, ASSURANCE OF NO RECLOSE PERMITS AND CAUTION TAGS Supersedes OO 1T-18 issued 13 October 2010 Review Year: 2019 Original signed by:

More information

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017 Grid codes and wind farm interconnections CNY Engineering Expo Syracuse, NY November 13, 2017 Purposes of grid codes Grid codes are designed to ensure stable operating conditions and to coordinate the

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements Section 502.8 SCADA Technical and Operating Requirements Applicability 1 Subject to subsections 2 and 3 below, section 502.8 applies to: (a) (c) (d) the legal owner of a generating unit or an aggregated

More information

MANITOBA HYDRO TRANSMISSION SYSTEM INTERCONNECTION REQUIREMENTS. July 2016 Version 4

MANITOBA HYDRO TRANSMISSION SYSTEM INTERCONNECTION REQUIREMENTS. July 2016 Version 4 MANITOBA HYDRO TRANSMISSION SYSTEM INTERCONNECTION REQUIREMENTS July 2016 Version 4 This page intentionally blank LEGISLATIVE AUTHORITY Section 15.0.3(1) of The Manitoba Hydro Act (C.C.S.M. c. H190) authorizes

More information

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event

More information

Generation Interconnection Requirements at Voltages 34.5 kv and Below

Generation Interconnection Requirements at Voltages 34.5 kv and Below Generation Interconnection Requirements at Voltages 34.5 kv and Below 2005 March GENERATION INTERCONNECTION REQUIREMENTS AT 34.5 KV AND BELOW PAGE 1 OF 36 TABLE OF CONTENTS 1. INTRODUCTION 5 1.1. Intent

More information

Generation and Load Interconnection Standard

Generation and Load Interconnection Standard Generation and Load Interconnection Standard Rev. 0A DRAFT Name Signature Date Prepared: Approved: VP Acceptance APEGGA Permit to Practice P-08200 TABLE OF CONTENTS 1.0 INTRODUCTION...5 1.1 Purpose...5

More information

69 kv to 500 kv INTERCONNECTION REQUIREMENTS FOR TRANSMISSION FACILITIES

69 kv to 500 kv INTERCONNECTION REQUIREMENTS FOR TRANSMISSION FACILITIES 69 kv to 500 kv INTERCONNECTION REQUIREMENTS FOR TRANSMISSION FACILITIES Revision: 0.1 10 September 2013 Interconnection Requirements For Transmission Facilities Revision History R 0 April 2008 Initial

More information

MANITOBA HYDRO TRANSMISSION SYSTEM INTERCONNECTION REQUIREMENTS. April 2009 Version 2

MANITOBA HYDRO TRANSMISSION SYSTEM INTERCONNECTION REQUIREMENTS. April 2009 Version 2 MANITOBA HYDRO TRANSMISSION SYSTEM INTERCONNECTION REQUIREMENTS April 2009 Version 2 LEGISLATIVE AUTHORITY Section 15(5) of The Manitoba Hydro Act authorizes Manitoba Hydro to set, coordinate and enforce

More information

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone

More information

Generation and Load Interconnection Standard

Generation and Load Interconnection Standard Generation and Load Interconnection Standard Rev. 0 DRAFT Name Signature Date Prepared: Approved: VP Acceptance APEGGA Permit to Practice P-08200 TABLE OF CONTENTS 1.0 INTRODUCTION...5 1.1 Purpose...5

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission

More information

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines David K Olson Xcel Energy Minneapolis, MN Paul Nyombi Xcel Energy Minneapolis, MN Pratap G Mysore Pratap Consulting Services,

More information

CONSOLIDATED EDISON CO. OF NEW YORK, INC 4 IRVING PLACE NEW YORK, N.Y

CONSOLIDATED EDISON CO. OF NEW YORK, INC 4 IRVING PLACE NEW YORK, N.Y CONSOLIDATED EDISON CO. OF NEW YORK, INC 4 IRVING PLACE NEW YORK, N.Y. 10003 EP 7000 5 JULY 2009 VOLTAGE SCHEDULE, CONTROL, AND OPERATION OF THE TRANSMISSION SYSTEM PURPOSE This specification describes

More information

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016 PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016 Prepared by System Planning Division Transmission Planning Department PJM 2016 Table of Contents Table of Contents Approval...6

More information

Protective Relaying for DER

Protective Relaying for DER Protective Relaying for DER Rogerio Scharlach Schweitzer Engineering Laboratories, Inc. Basking Ridge, NJ Overview IEEE 1547 general requirements to be met at point of common coupling (PCC) Distributed

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

EH2741 Communication and Control in Electric Power Systems Lecture 2

EH2741 Communication and Control in Electric Power Systems Lecture 2 KTH ROYAL INSTITUTE OF TECHNOLOGY EH2741 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsno@kth.se Course map Outline Transmission Grids vs Distribution grids Primary Equipment

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

GridLiance Reliability Criteria

GridLiance Reliability Criteria GridLiance Reliability Criteria Planning Department March 1, 2018 FOREWORD The GridLiance system is planned, designed, constructed, and operated to assure continuity of service during system disturbances

More information

Transmission Availability Data System Definitions

Transmission Availability Data System Definitions Table of Contents Transmission Availability Data System Definitions February 1, 2018 1 of 31 3353 Peachtree Road NE Suite 600, North Tower Atlanta, GA 30326 404-446-2560 www.nerc.com Table of Contents

More information

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS S1. Standard Interconnection Methods with Typical Circuit Configuration for Single or Multiple Units Note: The protection requirements

More information

Appendix C-1. Protection Requirements & Guidelines Non-Utility Generator Connection to Okanogan PUD

Appendix C-1. Protection Requirements & Guidelines Non-Utility Generator Connection to Okanogan PUD A. Introduction Appendix C-1 Protection Requirements & Guidelines to Okanogan PUD The protection requirements identified in this document apply to Non-Utility Generating (NUG) facilities, Independent Power

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

Delayed Current Zero Crossing Phenomena During Switching of Shunt-Compensated Lines

Delayed Current Zero Crossing Phenomena During Switching of Shunt-Compensated Lines Delayed Current Zero Crossing Phenomena During Switching of Shunt-Compensated Lines David K Olson Paul Nyombi Xcel Energy Pratap G Mysore Pratap Consulting Services Minnesota Power Systems Conference St.

More information

Utility Interconnection and System Protection

Utility Interconnection and System Protection Utility Interconnection and System Protection Alex Steselboim President, Advanced Power Technologies, Inc. Utility paralleling vs. isolated operation. Isochronous kw load sharing Reactive power (VAR) sharing

More information

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF LARGE GENERATION FACILITIES. Document 9020

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF LARGE GENERATION FACILITIES. Document 9020 TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF LARGE GENERATION FACILITIES Document 9020 Puget Sound Energy, Inc. PSE-TC-160.50 December 19, 2016 TABLE OF CONTENTS

More information

Functional Specification Revision History

Functional Specification Revision History Functional Specification Revision History Revision Description of Revision By Date V1D1 For Comments Yaoyu Huang October 27, 2016 V1 For Issuance Yaoyu Huang November 21, 2016 Section 5.3 updated Transformer

More information

Notes 1: Introduction to Distribution Systems

Notes 1: Introduction to Distribution Systems Notes 1: Introduction to Distribution Systems 1.0 Introduction Power systems are comprised of 3 basic electrical subsystems. Generation subsystem Transmission subsystem Distribution subsystem The subtransmission

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS AND MEDIUM-SIZE FACILITIES (5,000-25,000KW) CONNECTED

More information

Power Quality Basics. Presented by. Scott Peele PE

Power Quality Basics. Presented by. Scott Peele PE Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement

More information

Phase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.

Phase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star. Summary Of Interconnection Technical Guidelines for Renewable Energy Systems 0-100 kw under Standard Offer Contract (Extract from JPS Guide to Interconnection of Distributed Generation) This document is

More information

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION Document 9022 Puget Sound Energy, Inc. PSE-TC-160.70 December

More information

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

I WP Asset # I ~:2 3. I Review Annual. ~c~~ Date: 'l/j(j/! ZL>IJ,...

I WP Asset # I ~:2 3. I Review Annual. ~c~~ Date: 'l/j(j/! ZL>IJ,... - District Standard - FAC Facility Design, Connections 950.001 and Maintenance CHELAN COUNTY ~ PUBLIC UTILITY DISTRICT Owned By The People~ Serve Facility Connection Requirements Page 1 of 101 EFFECTIVE

More information

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS CONNECTED TO THE DISTRIBUTION SYSTEM ORANGE AND ROCKLAND

More information

This document covers common questions concerning the design of an effectively grounded system.

This document covers common questions concerning the design of an effectively grounded system. This document covers common questions concerning the design of an effectively grounded system. To prevent against temporary overvoltage conditions when a line-to-ground fault occurs on the power grid.

More information

60 kv to 500 kv Technical Interconnection Requirements For Power Generators

60 kv to 500 kv Technical Interconnection Requirements For Power Generators 60 kv to 500 kv Technical Interconnection Requirements For Power Generators Revision: 0 October 2008 COPYRIGHT, BC TRANSMISSION CORPORATION, OCTOBER 2008 Disclaimer This document is not intended as a design

More information

Tab 2 Voltage Stresses Switching Transients

Tab 2 Voltage Stresses Switching Transients Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles

More information

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission

More information

ATTACHMENT - AESO FUNCTIONAL SPECIFICATION

ATTACHMENT - AESO FUNCTIONAL SPECIFICATION ATTACHMENT - AESO FUNCTIONAL SPECIFICATION Functional Specification Revision History Revision Description of Revision By Date D1 For internal Comments Yaoyu Huang January 8, 2018 D2 For external Comments

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

Guide and Requirements for Service. at 69,000 to 287,000 Volts R 0.2

Guide and Requirements for Service. at 69,000 to 287,000 Volts R 0.2 Guide and Requirements for Service at 69,000 to 287,000 Volts R 0.2 September - 2011 Disclaimer This document is not intended as a design specification or as an instruction manual for the Load Customer

More information

Section G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES

Section G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES Section G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES Purpose This section specifies the requirements for protective relays and control devices for Generation Entities interconnecting

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

FACILITY CONNECTION REQUIREMENTS

FACILITY CONNECTION REQUIREMENTS Portland General Electric Facility Connection Requirements - Generation Resources FACILITY CONNECTION REQUIREMENTS FOR GENERATION RESOURCES PORTLAND GENERAL ELECTRIC PORTLAND, OREGON JULY 12, 2013 REVISION

More information

Fixed Series Compensation

Fixed Series Compensation Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Volts Per Hertz (24), Undervoltage (27), Overvoltage (59), and Under/Overfrequency (81) Protection System Protection and Control Subcommittee

More information

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Expo - Nov. 3, 2014 Index Normal Distribution System

More information

Electrical Power Systems

Electrical Power Systems Electrical Power Systems CONCEPT, THEORY AND PRACTICE SECOND EDITION SUBIR RAY Professor MVJ College of Engineering Bangalore PHI Learning Pfcte tofm Delhi-110092 2014 Preface xv Preface to the First Edition

More information

HOOSIER ENERGY REC, INC. Requirements for Connection of Generation Facilities. to the HE Transmission System

HOOSIER ENERGY REC, INC. Requirements for Connection of Generation Facilities. to the HE Transmission System HOOSIER ENERGY REC, INC Requirements for Connection of Generation Facilities to the HE Transmission System January 2009 Table of Contents 1.0 INTRODUCTION...1 2.0 TYPES OF CONNECTED CIRCUIT CONFIGURATIONS...6

More information

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic

More information

OPERATING PROCEDURE. Table of Contents

OPERATING PROCEDURE. Table of Contents Table of Contents PURPOSE... 1 1.0 CAISO DISPATCHER RESPONSIBILITIES... 2 Monitor Loads and Generators... 2 Monitor Balancing Areas... 2 Operate CAISO Controlled Grid Voltage Equipment... 3 Voltage Schedules...

More information

GUIDE FOR GENERATOR INTERCONNECTION THE WIRES OWNER DISTRIBUTION SYSTEM

GUIDE FOR GENERATOR INTERCONNECTION THE WIRES OWNER DISTRIBUTION SYSTEM DATE: 200/06/2 PAGE 1 of GUIDE FOR GENERATOR INTERCONNECTION TO THE WIRES OWNER DISTRIBUTION SYSTEM The intent of this Guide is to establish the interconnection requirements of Distributed Resources with

More information

Customer Standard. Standard for Embedded Generation (5MW and above)

Customer Standard. Standard for Embedded Generation (5MW and above) Standard 01188 Version: 1 Released: 1/10/2014 STANDARD FOR EMBEDDED GENERATION (5MW AND ABOVE) Customer Standard Standard for Embedded Generation If this standard is a printed version, to ensure compliance,

More information

Alberta Interconnected Electric System Protection Standard

Alberta Interconnected Electric System Protection Standard Alberta Interconnected Electric System Protection Standard Revision 0 December 1, 2004 APEGGA Permit to Practice P-08200 Table of Contents Signature Page... 2 Table of Contents... 3 1.0 STAKEHOLDER REVIEW

More information

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections

More information

Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods

Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods Proceedings of the th WSEAS International Conference on Power Systems, Beijing, China, September -, 200 Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing

More information

E N G I N E E R I N G M A N U A L

E N G I N E E R I N G M A N U A L 1 1 1.0 PURPOSE The purpose of this document is to define policy and provide engineering guidelines for the AP operating companies (Monongahela Power Company, The Potomac Edison Company, and West Penn

More information

Arizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan

Arizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan Arizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan Mark Hackney October 5-8, 2009 Amman, Jordan Energy Control Center Layout 2 Energy Control

More information

Power Plant and Transmission System Protection Coordination

Power Plant and Transmission System Protection Coordination Agenda Item 5.h Attachment 1 A Technical Reference Document Power Plant and Transmission System Protection Coordination Draft 6.9 November 19, 2009 NERC System Protection and Control Subcommittee November

More information

Company Directive STANDARD TECHNIQUE: SD1E/2. Technical Requirements for Customer Export Limiting Schemes

Company Directive STANDARD TECHNIQUE: SD1E/2. Technical Requirements for Customer Export Limiting Schemes Company Directive STANDARD TECHNIQUE: SD1E/2 Technical Requirements for Customer Export Limiting Schemes Policy Summary This Standard Technique specifies the requirements for customer owned Export Limitation

More information

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR SMALL GENERATION INTERCONNECTIONS

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR SMALL GENERATION INTERCONNECTIONS TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR SMALL GENERATION INTERCONNECTIONS Puget Sound Energy, Inc. PSE-ET-160.60 October 30, 2007 TABLE OF CONTENTS 1. INTRODUCTION...1 1.1 GENERAL

More information

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application General Application Information Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application Hydro One Remote Communities Inc. Lori.Rice@hydroone.com 1-807-474-2828 This Application

More information

Arrowhead Station Special Equipment Operation. Dudley Maki Minnesota Power

Arrowhead Station Special Equipment Operation. Dudley Maki Minnesota Power Arrowhead Station Special Equipment Operation Dudley Maki Minnesota Power Arrowhead - Equipment Operation Non-Standard Equipment at Arrowhead 345 kv Phase Shifting Transformer (8TR) Voltage Regulating

More information

DUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES. Transmission Planning

DUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES. Transmission Planning DUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES Transmission Planning TABLE OF CONTENTS I. SCOPE 1 II. TRANSMISSION PLANNING OBJECTIVES 2 III. PLANNING ASSUMPTIONS 3 A. Load Levels 3 B. Generation

More information

Table of Contents. 1.0 Intent and Limitations Intent Limitations Contact Information General Requirements...

Table of Contents. 1.0 Intent and Limitations Intent Limitations Contact Information General Requirements... Requirements for Interconnection Facilities Teck Metals Ltd. Transmission Assets: 1. Facility Connection Requirements 2. Technical Performance Requirements References: (Most recent version in each instance)

More information

Hamdy Faramawy Senior Application Specialist ABB Sweden

Hamdy Faramawy Senior Application Specialist ABB Sweden Design, Engineering and Application of New Firm Capacity Control System (FCCS) Mohammed Y. Tageldin, MSc. MIET Senior Protection Systems Engineer ABB United Kingdom mohammed.tageldin@gb.abb.com Hamdy Faramawy

More information

Power System Protection Where Are We Today?

Power System Protection Where Are We Today? 1 Power System Protection Where Are We Today? Meliha B. Selak Power System Protection & Control IEEE PES Distinguished Lecturer Program Preceding IEEE PES Vice President for Chapters melihas@ieee.org PES

More information

ELEMENTS OF FACTS CONTROLLERS

ELEMENTS OF FACTS CONTROLLERS 1 ELEMENTS OF FACTS CONTROLLERS Rajiv K. Varma Associate Professor Hydro One Chair in Power Systems Engineering University of Western Ontario London, ON, CANADA rkvarma@uwo.ca POWER SYSTEMS - Where are

More information

Date Description Revision May 19, 2008

Date Description Revision May 19, 2008 Voltage and Reactive Power Schedule r10 Revision History Date Description Revision May 19, 2008 Initial E.ON document to establish guidelines applicable to all generator owners connected to /KU r0 May

More information

Connection Impact Assessment Application

Connection Impact Assessment Application Connection Impact Assessment Application This form is for generators applying for Connection Impact Assessment (CIA) and for generators with a project size >10 kw. Please return the completed form by email,

More information

BED INTERCONNECTION TECHNICAL REQUIREMENTS

BED INTERCONNECTION TECHNICAL REQUIREMENTS BED INTERCONNECTION TECHNICAL REQUIREMENTS By Enis Šehović, P.E. 2/11/2016 Revised 5/19/2016 A. TABLE OF CONTENTS B. Interconnection Processes... 2 1. Vermont Public Service Board (PSB) Rule 5.500... 2

More information

1

1 Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive

More information

FACILITY RATINGS METHOD TABLE OF CONTENTS

FACILITY RATINGS METHOD TABLE OF CONTENTS FACILITY RATINGS METHOD TABLE OF CONTENTS 1.0 PURPOSE... 2 2.0 SCOPE... 3 3.0 COMPLIANCE... 4 4.0 DEFINITIONS... 5 5.0 RESPONSIBILITIES... 7 6.0 PROCEDURE... 8 6.4 Generating Equipment Ratings... 9 6.5

More information

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström EH27401 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsn@ics.kth.se 1 Course map 2 Outline 1. Power System Topologies Transmission Grids vs Distribution grids Radial grids

More information

Babak Enayati National Grid Thursday, April 17

Babak Enayati National Grid Thursday, April 17 2014 IEEE PES Transmission & Distribution Conference & Exposition Impacts of the Distribution System Renewable Energy Resources on the Power System Protection Babak Enayati National Grid Thursday, April

More information

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006 October 25, 2006 Document name Category MODEL POWER SYSTEM TESTING GUIDE ( ) Regional Reliability Standard ( ) Regional Criteria ( ) Policy ( ) Guideline ( x ) Report or other ( ) Charter Document date

More information

Voltage and Reactive Procedures CMP-VAR-01

Voltage and Reactive Procedures CMP-VAR-01 Voltage and Reactive Procedures CMP-VAR-01 NERC Standards: VAR-001-2 VAR-002-1.1b Effective Date: 07/31/2012 Document Information Current Revision 2.0 Review Cycle Annual Subject to External Audit? Yes

More information

Remedial Action Scheme Definition Development Background and Frequently Asked Questions

Remedial Action Scheme Definition Development Background and Frequently Asked Questions Remedial Action Scheme Definition Development Background and Frequently Asked Questions Project 2010-05.2 Special Protection Systems October 2014 1 3353 Peachtree Road NE Suite 600, North Tower Atlanta,

More information

MidAmerican Energy Company Reliability Planning Criteria for 100 kv and Above

MidAmerican Energy Company Reliability Planning Criteria for 100 kv and Above MidAmerican Energy Company Reliability Planning Criteria for 100 kv and Above March 13, 2018 Issued by: Dehn Stevens, Director System Planning and Services 1.0 SCOPE This document defines the criteria

More information

Assessment of Saturable Reactor Replacement Options

Assessment of Saturable Reactor Replacement Options Assessment of Saturable Reactor Replacement Options D.T.A Kho, K.S. Smith Abstract-- The performance of the dynamic reactive power compensation provided by the existing variable static compensation (STC)

More information