2 Voltage and Reactive Power Schedule r10 Revision History Date Description Revision May 19, 2008 Initial E.ON document to establish guidelines applicable to all generator owners connected to /KU r0 May 19, 2009 Derek Rahn transmission system. Annual Review. Added primary and backup measurement location. Adjusted target voltage for Cane Run Switching 138 kv and Paddy s Run 138 kv. May 4, 2010 Derek Rahn Annual Review. Removed OMU Smith Units & added KMPA Feb 11, Michael Toll Update Company name and Voltage 2011 schedules at Cane Run & Paddys Run June, 2012 Delyn Kilpack Widen the tolerance band; added clarification to Ghent #1 voltage schedule; added criteria for generators exempt from schedule; ; added clarification on expected duration for Return To Normal status change July 1, 2013 Delyn Kilpack / October 1, 2014 July 24, 2015 October 1, 2015 July 22, 2016 May 30, 2017 Matthew Burns Updated sections A. and B. of voltage schedule. Added footnote about hourly average voltage. Changed voltage measurement keys at Ghent. Annual Review; Updated to correspond with VAR-001-4; Added voltage schedule for Cane Run 7 Annual Review; Removed Cane Run 4, 5 & 6 from Voltage Schedule Removed Green River 3 & 4 from Voltage Schedule Annual Review; Listed EKPC as owner of Bluegrass units Annual Review; Added Brown Solar and Paris to Exempt list; Added KYMEA to distribution list r1 r2 r3 r4 r5 r6 r7 r8 r9 r10
3 Voltage and Reactive Power Schedule r10 Distribution The document will be reviewed as necessary by the Transmission Operator. The TOP will distribute the document to the following personnel initially and immediately following any permanent revisions to the document: Mgr., Generation Dispatch Operations EKPC Generator Operator KMPA Paducah Primary Generation, Plant Supervisor KYMEA Generator Operator The document will be provided to the TVA Reliability Coordinator and adjacent Transmission Operators within 30 calendar days of a request. 1 1 VAR R1.1
4 Voltage and Reactive Power Schedule r10 Voltage and Reactive Power Schedule The following voltage and reactive power schedules are issued by Louisville Gas and Electric Company ( ) and Kentucky Utilities Company ( KU ) (collectively or the Company ) as Transmission Operator ( TOP ). This schedule may be updated from time-totime, either by (a) re-issuance of this written schedule, which new schedule will permanently supersede this schedule or (b) phone calls from the TOP to the applicable generating plant operator, which schedules will be temporary changes in this schedule to address real-time reliability issues. It should be noted that, as a temporary change, generators adhering to a voltage schedule may be required to operate to a reactive power schedule. The Generator Operator ( GOP ) shall operate each generator connected to the interconnected transmission system in the automatic voltage control mode (with its automatic voltage regulator (AVR) in service and controlling voltage) unless the generator is exempted by the TOP or the GOP has notified the TOP of one of the following: That the generator is being operated in start-up, shutdown, or testing mode pursuant to a Real-time communication or a procedure that was previously provided to the TOP; or That the generator is not being operated in automatic voltage control mode or in the control mode that was instructed by the Transmission Operator for a reason other than start-up, shutdown, or testing. specifies target voltages and tolerance bands on the high voltage side of the generator step-up transformer. High voltage side refers to a location electrically connected to the generator step-up transformer, as designated by the Voltage Controlled Bus in Table 1, that has been determined by for controlling voltage in order to most efficiently protect equipment and allow for the reliable operation of the Interconnection. All on-line generators at a given plant shall control voltage (within the tolerance band) at the specified transmission bus given in the Table 1 below unless: A. While trying to increase the voltage above the lower bound, each on-line generating unit at the facility is operating within five percent of maximum VAR output, or at a Facility Rating. B. While trying to decrease the voltage below the upper bound, each on-line generating unit at the facility is operating within five percent of minimum VAR output, or at a Facility Rating.
5 Voltage and Reactive Power Schedule r10 Table 1 Owner Plant Voltage Controlled Bus Ghent 1 4 Ghent units 2, 3 and 4 Trimble County all units Mill Creek all units Ghent 138 kv Ghent 345 kv Trimble County 345 kv Mill Creek 345 kv EKPC Bluegrass all units Buckner 345 kv Brown more than one unit online Brown only one unit online Cane Run 7 Paddy s Run unit 13 Brown North 138 kv Brown North 138 kv Cane Run CT 138 kv Paddy s Run 138 kv Voltage Measurement (SCADA Name/SCADA Key) Primary 3 Backup Target Voltage (kv) 2 7GHENT KV 7GHENT KV (ALT) See footnote below SEL KV SOUTH BUS SEL KV NORTH BUS TC 345KV A BUS KVOLTS TC 345KV B BUS KVOLTS MC 345KV B KVOLTS MC 345KV A KVOLTS BU-4550 KVOLTS BU-4551 KVOLTS BRNO #2 7BRNO # BRNO #2 7BRNO # CRC-138KV BUS A VOLTAGE A CRC-138KV BUS B VOLTAGE A PR 138KV SEC 1 KVOLTS PR 138KV SEC 2 KVOLTS Tolerance Band kv kv kv kv kv 2 The target voltage and tolerance band is an hourly average voltage. 3 The primary measurement location should be used for controlling voltage. The backup measurement location should only be used if the primary measurement fails. If the primary measurement fails, however, alternate data source is set up in the EMS so that the primary measurement will automatically point to the backup measurement will be displayed next to the primary voltage measurement if the backup voltage measurement is in use). 4 Ghent 1 regulates voltage on the 138 kv while Ghent #2, 3 and 4 regulate voltage on the 345 kv. This creates a potential operational issue with circulating VARs between units 2, 3 and 4 and Ghent 1. Therefore, to eliminate the circulating VAR issues, the GOP for Ghent plant can choose the target voltage for Ghent 1 as long as they do not violate the tolerance band in Table 1.
6 Voltage and Reactive Power Schedule r10 Notification Requirements The GOP shall notify 5 the TOP of any of the following (without intentional time delay): A generator deviates from its voltage or reactive power schedule 6 A generator s AVR is out of service or a generator is not being operated in automatic voltage control mode for any other reason 7 A status change on the AVR, power system stabilizer, or alternative voltage controlling device 8 A change in reactive capability due to factors other than a status change on the AVR, power system stabilizer, or alternative voltage controlling device 9 When notified by the GOP of any of the factors listed above, the TOP will direct the GOP to either maintain or change its voltage and/or reactive power schedule. Criteria for Exempt Generators Generators with a nameplate rating less than 75 MVA or interconnected at voltages less than 100 kv are exempt from annual VAR testing for MOD-025 per the SERC Regional Criteria: Verification of Generator Real and Reactive Power Capability, Revision 2 October 6, Therefore, AND KU has concluded that generators meeting this criteria are exempt from following a voltage or Reactive Power schedule; thus those generators are exempt from the voltage or Reactive Power schedule specified in this document (including without limitation the obligation to comply with this schedule in automatic voltage control mode and the obligation to maintain or change its voltage schedule or reactive power schedule following the loss of automatic voltage regulator control). Generators that are exempt from the voltage or Reactive Power schedule are not required to make any associated notifications. Units exempt from this voltage schedule are: Unit(s) Exempt Zorn Brown Solar Haefling 5 Notification could be made through verbal or electronic communication 6 VAR R5.2 7 VAR R1 8 VAR R3 9 VAR R4
7 Voltage and Reactive Power Schedule r10 Dix Dam Ohio Falls Cane Run 11 Paddy s Run 11 Paddy s Run 12 Paducah Primary (KMPA CT 1 and 2) Paris (KYMEA)
Voltage and Reactive Procedures CMP-VAR-01
Voltage and Reactive Procedures CMP-VAR-01 NERC Standards: VAR-001-2 VAR-002-1.1b Effective Date: 07/31/2012 Document Information Current Revision 2.0 Review Cycle Annual Subject to External Audit? Yes
More informationVAR Generator Operation for Maintaining Network Voltage Schedules
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationVAR Generator Operation for Maintaining Network Voltage Schedules
A. Introduction 1. Title: Generator Operation for Maintaining Network Voltage Schedules 2. Number: VAR-002-4 3. Purpose: To ensure generators provide reactive support and voltage control, within generating
More informationVAR Generator Operation for Maintaining Network Voltage Schedules
A. Introduction 1. Title: Generator Operation for Maintaining Network Voltage Schedules 2. Number: VAR-002-3 3. Purpose: To ensure generators provide reactive support and voltage control, within generating
More informationVAR Generator Operation for Maintaining Network Voltage Schedules
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationVAR Generator Operation for Maintaining Network Voltage Schedules
A. Introduction 1. Title: Generator Operation for Maintaining Network Voltage Schedules 2. Number: VAR-002-3 3. Purpose: To ensure generators provide reactive support and voltage control, within generating
More informationVAR Outreach Presentation
VAR Outreach Presentation Soo Jin Kim, NERC Standards Developer November 4, 2013 Administrative Items NERC Antitrust Guidelines It is NERC s policy and practice to obey the antitrust laws and to avoid
More informationVAR Voltage and Reactive Control
VAR-001-4 Voltage and Reactive Control A. Introduction 1. Title: Voltage and Reactive Control 2. Number: VAR-001-4 3. Purpose: To ensure that voltage levels, reactive flows, and reactive resources are
More informationA. Introduction. VAR Voltage and Reactive Control
A. Introduction 1. Title: Voltage and Reactive Control 2. Number: VAR-001-4.2 3. Purpose: To ensure that voltage levels, reactive flows, and reactive resources are monitored, controlled, and maintained
More informationVAR Voltage and Reactive Control. A. Introduction
VAR-001-5 Voltage and Reactive Control A. Introduction 1. Title: Voltage and Reactive Control 2. Number: VAR-001-5 3. Purpose: To ensure that voltage levels, reactive flows, and reactive resources are
More informationStandard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules. 45-day Formal Comment Period with Initial Ballot June July 2014
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationStandard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationStandard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationAugust 25, 2017 VIA ELECTRONIC FILING
!! August 25, 2017 VIA ELECTRONIC FILING Kirsten Walli, Board Secretary Ontario Energy Board P.O Box 2319 2300 Yonge Street Toronto, Ontario, Canada M4P 1E4 Re: North American Electric Reliability Corporation
More informationAugust 25, Please contact the undersigned if you have any questions concerning this filing.
!! August 25, 2017 VIA ELECTRONIC FILING Ms. Erica Hamilton, Commission Secretary British Columbia Utilities Commission Box 250, 900 Howe Street Sixth Floor Vancouver, B.C. V6Z 2N3 Re: North American Electric
More informationStandard VAR Voltage and Reactive Control
A. Introduction 1. Title: Voltage and Reactive Control 2. Number: VAR-001-3 3. Purpose: To ensure that voltage levels, reactive flows, and reactive resources are monitored, controlled, and maintained within
More informationStandard VAR b Generator Operation for Maintaining Network Voltage Schedules
A. Introduction 1. Title: Generator Operation for Maintaining Network Voltage Schedules 2. Number: VAR-002-1.1b 3. Purpose: To ensure generators provide reactive and voltage control necessary to ensure
More informationgeneration greater than 75 MVA (gross aggregate nameplate rating) Generation in the ERCOT Interconnection with the following characteristics:
A. Introduction 1. Title: Verification of Models and Data for Turbine/Governor and Load Control or Active Power/Frequency Control Functions 2. Number: MOD-027-1 3. Purpose: To verify that the turbine/governor
More informationStandard MOD Verification of Models and Data for Generator Excitation Control System or Plant Volt/Var Control Functions
Standard MOD-026-1 Verification of Models and Data for Generator Excitation Control System or Plant Volt/Var Control Functions A. Introduction 1. Title: Verification of Models and Data for Generator Excitation
More informationBC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A. NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014
BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014 Expiry Year: 2018 APPROVED BY: Original signed by: Paul
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements
Section 502.8 SCADA Technical and Operating Applicability 1 Section 502.8 applies to: (a) the legal owner of a generating unit: (i) connected to the transmission facilities in the balancing authority area
More informationStandard MOD Verification of Models and Data for Generator Excitation Control Sys tem or Plant Volt/Var Control Functions
Standard MOD-026-1 Verification of Models and Data for Generator Excitation Control Sys tem or Plant Volt/Var Control Functions Standard Development Roadmap This section is maintained by the drafting team
More informationUNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION ) )
UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION North American Electric Reliability Corporation ) ) Docket No. PETITION OF THE NORTH AMERICAN ELECTRIC RELIABILITY CORPORATION FOR
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements
Section 502.8 SCADA Technical and Operating Requirements Applicability 1 Subject to subsections 2 and 3 below, section 502.8 applies to: (a) (c) (d) the legal owner of a generating unit or an aggregated
More informationStandard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction
A. Introduction 1. Title: Generator Frequency and Voltage Protective Relay Settings 2. Number: PRC-024-1 3. Purpose: Ensure Generator Owners set their generator protective relays such that generating units
More informationDUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES. Transmission Planning
DUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES Transmission Planning TABLE OF CONTENTS I. SCOPE 1 II. TRANSMISSION PLANNING OBJECTIVES 2 III. PLANNING ASSUMPTIONS 3 A. Load Levels 3 B. Generation
More informationFinal ballot January BOT adoption February 2015
Standard PRC-024-21(X) Generator Frequency and Voltage Protective Relay Settings Standard Development Timeline This section is maintained by the drafting team during the development of the standard and
More informationFACILITY RATINGS METHOD TABLE OF CONTENTS
FACILITY RATINGS METHOD TABLE OF CONTENTS 1.0 PURPOSE... 2 2.0 SCOPE... 3 3.0 COMPLIANCE... 4 4.0 DEFINITIONS... 5 5.0 RESPONSIBILITIES... 7 6.0 PROCEDURE... 8 6.4 Generating Equipment Ratings... 9 6.5
More informationStandard PRC Coordination of Generating Unit or Plant Voltage Regulating Controls with Generating Unit or Plant Capabilities and Protection
Standard Development Roadmap This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed:
More informationITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/
ITC Holdings Planning Criteria Below 100 kv * Category: Planning Type: Policy Eff. Date/Rev. # 12/09/2015 000 Contents 1. Goal... 2 2. Steady State Voltage & Thermal Loading Criteria... 2 2.1. System Loading...
More informationBEFORE THE ALBERTA ELECTRIC SYSTEM OPERATOR
BEFORE THE ALBERTA ELECTRIC SYSTEM OPERATOR NORTH AMERICAN ELECTRIC ) RELIABILITY CORPORATION ) NOTICE OF FILING OF THE NORTH AMERICAN ELECTRIC RELIABILITY CORPORATION OF PROPOSED RELIABILITY STANDARD
More informationTECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF LARGE GENERATION FACILITIES. Document 9020
TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF LARGE GENERATION FACILITIES Document 9020 Puget Sound Energy, Inc. PSE-TC-160.50 December 19, 2016 TABLE OF CONTENTS
More informationMANITOBA HYDRO TRANSMISSION SYSTEM INTERCONNECTION REQUIREMENTS. July 2016 Version 4
MANITOBA HYDRO TRANSMISSION SYSTEM INTERCONNECTION REQUIREMENTS July 2016 Version 4 This page intentionally blank LEGISLATIVE AUTHORITY Section 15.0.3(1) of The Manitoba Hydro Act (C.C.S.M. c. H190) authorizes
More informationTransmission Interconnection Requirements for Inverter-Based Generation
Transmission Requirements for Inverter-Based Generation June 25, 2018 Page 1 Overview: Every generator interconnecting to the transmission system must adhere to all applicable Federal and State jurisdictional
More informationStandard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction. See the Implementation Plan for PRC
A. Introduction 1. Title: Generator Frequency and Voltage Protective Relay Settings 2. Number: PRC-024-2 3. Purpose: Ensure Generator Owners set their generator protective relays such that generating units
More informationOPERATING PROCEDURE. Table of Contents
Table of Contents PURPOSE... 1 1.0 CAISO DISPATCHER RESPONSIBILITIES... 2 Monitor Loads and Generators... 2 Monitor Balancing Areas... 2 Operate CAISO Controlled Grid Voltage Equipment... 3 Voltage Schedules...
More informationSouthern Company Interconnection Requirements for Inverter-Based Generation
Southern Company Interconnection Requirements for Inverter-Based Generation September 19, 2016 Page 1 of 16 All inverter-based generation connected to Southern Companies transmission system (Point of Interconnection
More informationMeeting Notes Project 2016-EPR-02 September 7-9, 2016
Meeting Notes Project 2016-EPR-02 September 7-9, 2016 PJM Audubon, PA Administrative 1. Introductions The meeting was brought to order by the Chair, S. Solis, at 8:35 a.m. Eastern on Tuesday, September
More informationCover Sheet. Technical Justification Retirement of WECC Regional Reliability Standard VAR-002-WECC-2 Automatic Voltage Regulators (AVR)
Cover Sheet Attachment G (AVR) Retirement of WECC Regional Reliability Standard VAR-002-WECC-2 (AVR) Page 1 of 23 Request to Retire White Paper Retirement of WECC Regional Reliability Standard VAR-002-WECC-2
More informationSUBJECT: Voltage Schedules in the Southern Balancing Area (SBA)
BPO Procedure Bulk Power Operations Procedure #: BPO-1 SUBJECT: Voltage Schedules in the Southern Balancing Area (SBA) ASSOCIATED NERC STANDARD(S): VAR-001 (Voltage and Reactive Control) VAR-002 (Generator
More informationDefinition of Bulk Electric System Phase 2
Definition of Bulk Electric System Phase 2 NERC Industry Webinar Peter Heidrich, FRCC, Standard Drafting Team Chair June 26, 2013 Topics Phase 2 - Definition of Bulk Electric System (BES) Project Order
More informationInverter-Based Resource Disturbance Analysis
Inverter-Based Resource Disturbance Analysis Key Findings and Recommendations Informational Webinar February 15, 2018 August 16, 2016 Blue Cut Fire Disturbance Key Findings and Recommendations 2 Western
More information1
Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive
More informationIndustry Webinar. Reactive Power Planning. NERC System Analysis and Modeling Subcommittee (SAMS) March 2017
Industry Webinar Reactive Power Planning NERC System Analysis and Modeling Subcommittee (SAMS) March 2017 Webinar Topics Reliability Guideline on Reactive Power Planning Webinar Topics Fundamentals of
More informationPRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1
PRC-025-1 Generator Relay Loadability A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 Purpose: To set load-responsive protective relays associated with generation Facilities
More informationSUBJECT: Voltage Schedules and Reactive Resources in the Southern Balancing Area (SBA)
BPO Procedure Bulk Power Operations Procedure #: BPO-1 SUBJECT: Voltage Schedules and Reactive Resources in the Southern Balancing Area (SBA) ASSOCIATED NERC STANDARD(S): VAR-001 (Voltage and Reactive
More informationDocument C-29. Procedures for System Modeling: Data Requirements & Facility Ratings. January 5 th, 2016 TFSS Revisions Clean Open Process Posting
Document C-29 Procedures for System Modeling: January 5 th, 2016 TFSS Revisions Clean Open Process Posting Prepared by the SS-37 Working Group on Base Case Development for the Task Force on System Studies.
More informationCentral Hudson Gas & Electric Corporation. Transmission Planning Guidelines
Central Hudson Gas & Electric Corporation Transmission Planning Guidelines Version 4.0 March 16, 2016 Version 3.0 March 16, 2009 Version 2.0 August 01, 1988 Version 1.0 June 26, 1967 Table of Contents
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationStandard BAL-005-0b Automatic Generation Control
A. Introduction 1. Title: Automatic Generation Control 2. Number: BAL-005-0b 3. Purpose: This standard establishes requirements for Balancing Authority Automatic Generation Control (AGC) necessary to calculate
More informationPRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1
A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 Purpose: To set load-responsive protective relays associated with generation Facilities at a level to prevent unnecessary tripping
More informationBulk Electric System Definition Reference Document
Bulk Electric System Definition Reference Document January, 2014 This draft reference document is posted for stakeholder comments prior to being finalized to support implementation of the Phase 2 Bulk
More informationTECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION
TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION Document 9022 Puget Sound Energy, Inc. PSE-TC-160.70 December
More informationStandard TOP Monitoring System Conditions
A. Introduction 1. Title: Monitoring System Conditions 2. Number: TOP-006-2 3. Purpose: To ensure critical reliability parameters are monitored in real-time. 4. Applicability 4.1. Transmission Operators.
More information15.2 Rate Schedule 2 - Payments for Supplying Voltage Support Service
15.2 Rate pport Service This Rate Schedule applies to payments to Suppliers who provide Voltage Support Service to the ISO. Transmission Customers and Customers will purchase Voltage Support Service from
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationMANITOBA HYDRO TRANSMISSION SYSTEM INTERCONNECTION REQUIREMENTS. April 2009 Version 2
MANITOBA HYDRO TRANSMISSION SYSTEM INTERCONNECTION REQUIREMENTS April 2009 Version 2 LEGISLATIVE AUTHORITY Section 15(5) of The Manitoba Hydro Act authorizes Manitoba Hydro to set, coordinate and enforce
More informationJANUARY. DATE ACTIVITY ORC Reference NOTES 1st day of January after election
JANUARY 1st day of January after election January Terms of newly elected board members begin The terms of office of members of each board of education shall begin on the first day of January after their
More informationBulk Electric System Definition Reference Document
Bulk Electric System Definition Reference Document JanuaryVersion 2 April 2014 This technical reference was created by the Definition of Bulk Electric System drafting team to assist entities in applying
More informationBulk Electric System Definition Reference Document
Bulk Electric System Definition Reference Document Version 2 April 2014 This technical reference was created by the Definition of Bulk Electric System drafting team to assist entities in applying the definition.
More informationGREAT RIVER ENERGY GREAT RIVER ENERGY GENERATION INTERCONNECTION GUIDELINES. Revision 4
GREAT RIVER ENERGY GREAT RIVER ENERGY GENERATION INTERCONNECTION GUIDELINES Revision 4 December, 2010 TABLE OF CONTENTS General Requirements... 1 A, Purpose... 1 B, MISO Interconnection Requirements...2
More informationGeneration and Load Interconnection Standard
Generation and Load Interconnection Standard Rev. 0 DRAFT Name Signature Date Prepared: Approved: VP Acceptance APEGGA Permit to Practice P-08200 TABLE OF CONTENTS 1.0 INTRODUCTION...5 1.1 Purpose...5
More informationGeneration and Load Interconnection Standard
Generation and Load Interconnection Standard Rev. 0A DRAFT Name Signature Date Prepared: Approved: VP Acceptance APEGGA Permit to Practice P-08200 TABLE OF CONTENTS 1.0 INTRODUCTION...5 1.1 Purpose...5
More informationHOOSIER ENERGY REC, INC. Requirements for Connection of Generation Facilities. to the HE Transmission System
HOOSIER ENERGY REC, INC Requirements for Connection of Generation Facilities to the HE Transmission System January 2009 Table of Contents 1.0 INTRODUCTION...1 2.0 TYPES OF CONNECTED CIRCUIT CONFIGURATIONS...6
More information1222 First Avenue, San Diego, CA Cycle Distributed: 11/07/2014
Cycle s Project Information Project Nbr: 379530 Title: Living Green Coop MMCC Project Mgr: Gutierrez, Edith (619) 446-5147 egutierrez@sandiego.gov Page 1 of 6 *379530* Reviewing Discipline: LDR-Planning
More informationTECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR SMALL GENERATION INTERCONNECTIONS
TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR SMALL GENERATION INTERCONNECTIONS Puget Sound Energy, Inc. PSE-ET-160.60 October 30, 2007 TABLE OF CONTENTS 1. INTRODUCTION...1 1.1 GENERAL
More informationNORMES DE FIABILITÉ DE LA NERC (VERSION ANGLAISE)
COORDONNATEUR DE LA FIABILITÉ Direction Contrôle des mouvements d énergie Demande R-3944-2015 NORMES DE FIABILITÉ DE LA NERC (VERSION ANGLAISE) Original : 2016-10-14 HQCMÉ-10, Document 2 (En liasse) Standard
More informationTTC Study for: the PEGS-Ambrosia Lake 230 kv Line and the PEGS-Bluewater 115 kv Line
TTC Study for: the PEGS-Ambrosia Lake 230 kv Line and the PEGS-Bluewater 115 kv Line Vince Leung March 27, 2017 Reviewed by Johnny Nguyen Table of Contents Background 2 Objective 3 Base Case Assumptions
More informationNo I am concerned about units that may be individually less than 20 MVA but collectively could eb much larger - wind farms. Yes
Name (34 Responses) Organization (34 Responses) Group Name (19 Responses) Lead Contact (19 Responses) Question 1 (39 Responses) Question 1 Comments (53 Responses) Question 2 (38 Responses) Question 2 Comments
More informationNERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1
NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1 Charles J. Mozina, Consultant Beckwith Electric Co., Inc. www.beckwithelectric.com I. Introduction During the 2003 blackout,
More informationeach time the Frequency is above 51Hz. Continuous operation is required
GC0101 EXTRACT OF EUROPEAN CONNECTION CONDITIONS LEGAL TEXT DATED 08/01/2018. ECC.6 ECC.6.1 ECC.6.1.1 ECC.6.1.2 ECC.6.1.2.1 ECC.6.1.2.1.1 ECC.6.1.2.1.2 ECC.6.1.2.1.3 TECHNICAL, DESIGN AND OPERATIONAL CRITERIA
More informationFinal ballot January BOT adoption February 2015
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationStandard BAL b Automatic Generation Control
A. Introduction 1. Title: Automatic Generation Control 2. Number: BAL-005-0.2b 3. Purpose: This standard establishes requirements for Balancing Authority Automatic Generation Control (AGC) necessary to
More information(Circuits Subject to Requirements R1 R5) Generator Owner with load-responsive phase protection systems as described in
A. Introduction 1. Title: Transmission Relay Loadability 2. Number: PRC-023-3 3. Purpose: Protective relay settings shall not limit transmission loadability; not interfere with system operators ability
More informationStandard PRC Coordination of Generating Unit or Plant Capabilities, Voltage Regulating Controls, and Protection
Standard Development Roadmap This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed:
More informationStandard BAL b Automatic Generation Control
A. Introduction 1. Title: Automatic Generation Control 2. Number: BAL-005-0.2b 3. Purpose: This standard establishes requirements for Balancing Authority Automatic Generation Control (AGC) necessary to
More informationRecently, the SS38 Working Group on Inter-Area Dynamic Analysis completed two study reports on behalf of the UFLS Regional Standard Drafting Team.
December 7 th, 2010 NPCC Full Member Committee; Please find attached a draft revised NPCC Regional Reliability Directory #12 Underfrequency Load Shedding Program Requirements and a draft revised NPCC UFLS
More informationIndustry Webinar Draft Standard
Industry Webinar Draft Standard Project 2010-13.2 Phase 2 of Relay Loadability: Generation PRC-025-1 Generator Relay Loadability December 13, 2012 Agenda Welcome, Introductions and Administrative NERC
More informationOPERATING CODE NO. 5 (OC5)
Paragraph No/Title OPERATING CODE NO. 5 (OC5) TESTING AND MONITORING CONTENTS (This contents page does not form part of the Grid Code) Page Number OC5.1 INTRODUCTION... 2 OC5.2 OBJECTIVE... 3 OC5.3 SCOPE...
More informationImplementation Plan Project Balancing Authority Reliability-based Controls - Reserves
Implementation Plan Project 2010-14.1 Balancing Authority Reliability-based Controls - Reserves Implementation Plan for Approvals Required Prerequisite Approvals None Revisions to Glossary Terms The following
More informationCHAPTER ELECTRIC AND MAGNETIC FIELDS
CHAPTER 62-814 ELECTRIC AND MAGNETIC FIELDS 62-814.100 Intent, Findings, Basis of Standards, and Research Needs 62-814.200 Electric and Magnetic Fields; Definitions 62-814.300 General Technical Requirements
More informationPRC Disturbance Monitoring and Reporting Requirements
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationSolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection
SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection SolidGround TM GIC grid stability and harmonics mitigation
More informationCAISO Restricted - Do Not Distribute Outside of RC Project LOI and NDA Entities Page 1 of 24
RC0120A - RC IRO-010 Data Specification NOTE: Changes from Peak's Attachment A are highlighted in red in columns C through G Section Category Number Responsible Pa Data Item Data Transfer Method 1.1 Transmission
More informationTarget Mchunu and Themba Khoza Eskom Transmission Division, System Operator Grid Code Management
GRID CONNECTION CODE FOR RENEWABLE POWER PLANTS (RPPs) CONNECTED TO THE ELECTRICITY TRANSMISSION SYSTEM (TS) OR THE DISTRIBUTION SYSTEM (DS) IN SOUTH AFRICA Target Mchunu and Themba Khoza Eskom Transmission
More information1st Qua u r a ter e M e M e e t e in i g 2nd Qua u r a ter e M e M e e t e in i g
2011 SERTP Welcome SERTP 2011 First RPSG Meeting & Interactive Training Session 9:00 AM 3:00 PM 1 2011 SERTP The SERTP process is a transmission planning process. Please contact the respective transmission
More informationStandard Development Timeline
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the Board of Trustees. Description
More informationMidAmerican Energy Company 100 kv and Above Facility Ratings Methodology
MidAmerican Energy Company 100 kv and Above Facility Ratings Methodology For NERC Standard FAC-008-3 Version 3.4 1 Contents 1. Scope... 3 2. Establishment and Communication of Facility Ratings:... 3 2.1.
More informationENTSO-E Draft Network Code on High Voltage Direct Current Connections and DCconnected
ENTSO-E Draft Network Code on High Voltage Direct Current Connections and DCconnected Power Park Modules 30 April 2014 Notice This document reflects the work done by ENTSO-E in line with ACER s framework
More informationSAINT VINCENT AND THE GRENADINES TELECOMMUNICATIONS (SPECTRUM MANAGEMENT) REGULATIONS 2007 ARRANGEMENT OF REGULATIONS PART I PRELIMINARY PART II
SAINT VINCENT AND THE GRENADINES Regulation TELECOMMUNICATIONS (SPECTRUM MANAGEMENT) REGULATIONS 2007 ARRANGEMENT OF REGULATIONS 1. Citation 2. Interpretation and Application PART I PRELIMINARY PART II
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements
Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system
More informationDEP 2008 ELECTRIC AND MAGNETIC FIELDS CHAPTER ELECTRIC AND MAGNETIC FIELDS
CHAPTER 62-814 ELECTRIC AND MAGNETIC FIELDS TABLE OF CONTENTS PAGE 62-814.100 Intent, Findings, Basis of Standards, and Research Needs. 2 62-814.200 Electric and Magnetic Fields; Definitions. 3 62-814.300
More informationSystem Operating Limit Definition and Exceedance Clarification
System Operating Limit Definition and Exceedance Clarification The NERC-defined term System Operating Limit (SOL) is used extensively in the NERC Reliability Standards; however, there is much confusion
More informationESB National Grid Transmission Planning Criteria
ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and
More informationOklahoma Gas and Electric Co. Facility Connection Requirements MAINTAINED BY. Transmission Planning Engineering Department
Oklahoma Gas and Electric Co. Facility Connection Requirements MAINTAINED BY Transmission Planning Engineering Department Table of Contents Transmission and Generation Facility Interconnections... 3 Attachment
More informationInterconnection-Wide Oscillation Analysis: Baselining Oscillation Modes in the North American Power System Objective Purpose
Interconnection-Wide Oscillation Analysis: Baselining Oscillation Modes in the North American Power System NERC Synchronized Measurement Subcommittee (SMS) Scope Document Objective The objective of the
More informationSOLAR PV MICROINVERTER/ACM STANDARD PLAN - COMPREHENSIVE Microinverter and ACM Systems for One- and Two- Family Dwellings
SOLAR MICROINVERTER/M STANDARD PLAN - COMPREHENSIVE Microinverter and M Systems for One- and Two- Family Dwellings SCOPE: Use this plan ONLY for systems using utility-interactive Microinverters or Modules
More informationStandard BAL b3 Automatic GenerationBalancing Authority Control DRAFT
A. Introduction 1. Title: Balancing Authority ControlAutomatic Generation Control 2. Number: BAL-005-30.2b 3. Purpose: This standard establishes requirements for acquiring necessary data for the Balancing
More informationDNVGL-CP-0338 Edition October 2015
CLASS PROGRAMME DNVGL-CP-0338 Edition October 2015 The electronic pdf version of this document, available free of charge from http://www.dnvgl.com, is the officially binding version. FOREWORD DNV GL class
More informationSetting and Verification of Generation Protection to Meet NERC Reliability Standards
1 Setting and Verification of Generation Protection to Meet NERC Reliability Standards Xiangmin Gao, Tom Ernst Douglas Rust, GE Energy Connections Dandsco LLC. Abstract NERC has recently published several
More information