1 VAR Outreach Presentation Soo Jin Kim, NERC Standards Developer November 4, 2013
2 Administrative Items NERC Antitrust Guidelines It is NERC s policy and practice to obey the antitrust laws and to avoid all conduct that unreasonably restrains competition. This policy requires the avoidance of any conduct that violates, or that might appear to violate, the antitrust laws. Among other things, the antitrust laws forbid any agreement between or among competitors regarding prices, availability of service, product design, terms of sale, division of markets, allocation of customers or any other activity that unreasonably restrains competition. Notice of Open Meeting Participants are reminded that this informational break-out session is public. Please keep in mind that the audience may include members of the press and representatives of various governmental entities, in addition to the industry stakeholders. 2
3 Agenda Introductions Evolving Standards Process/Informal Development FERC directives Major changes to the VAR-001 and VAR-002 standards Upcoming and key dates 3
4 Old Standards Process Took multiple years SAR 30 day Comment Standard Drafting Team Formed Informal Comment Period 30 days Formal Comment Period - 30 day s Formal Comment and Initial Ballot 45 day comment period Evolving Standards Process Multiple Successive Ballot 30 days May 2012: NERC Board adopted SPIG report with recommendations to improve both the timeliness and quality of the standards was adopted. August and November 2012 NERC Board of Trustees Meeting: Recirculation Ballot 10 days NERC Board Adoption FERC commissioners urged the industry to focus on creating a more efficient standards development process (August 2012) NERC CEO expressed there should be a focus on revamping the standards process for more efficiency and quality (August 2012) NERC Board issued a resolution instructing the SPIG, MRC, SC, NERC staff and industry stakeholders to reform its standards program (November 2012) Filing with Regulatory Bodies Evolving Standards Process one year Informal Development SAR and Pro forma standard 30-day comment period SDT Formed Formal Comment & Initial Ballot Period 45 days Recirculation Ballot NERC Board Adoption Filing with Regulatory Bodies 4
5 VAR Directives Five Major FERC Directives to the ERO from Order No. 693 VAR-001-Summary from P 1880 o Expand the applicability to include reliability coordinators and LSEs; Tabled until FERC rules on IRO filing o Include detailed and definitive requirements on established limits and sufficient reactive resources and identify acceptable margins above the voltage instability points; Addressed in an equally effective and efficient manner o Include Requirements to perform voltage stability analysis periodically, using online techniques where commercially available and offline techniques where online techniques are not available, to assist real-time operations, for areas susceptible to voltage instability; Addressed in an equally effective and efficient manner o Include controllable load among the reactive resources to satisfy reactive Requirements; Completed already and o Address the power factor range at the interface between LSEs and the transmission grid; Table until FERC issues a final rulemaking on P81. 5
6 VAR Directives (Cont d) VAR-002- From PP o FERC directed NERC to consider modifying VAR-002 to require more detailed and definitive requirements when defining the time frame associated with an incident of non compliance (i.e., each 4-second scan, 10-minute integrated value, hourly integrated value); Addressed in VAR
7 Reliability Coordinators are NOT included for now. This directive must wait until FERC acts on the IRO filing. We removed policies or procedures that establish, monitor, and control voltage levels and Reactive Power flows. There is a reference to the FAC standards by stating the schedules are part of a plan to operate within SOLs and IROLs. Exemptions can apply to schedules, AVR status, and notifications. TOPs now will provide GOP notifications for deviations from schedules TOPs must provide the criteria used to set schedules for GOPs within 30 days of a request. TOPs must discuss implementation schedule for GOP tap changes. 7 Major VAR-001 Changes Since Last Posting
8 New R1- Major VAR-001 Changes Since Last Posting Each Transmission Operator shall specify a system voltage schedule (which is either a range or a target value with an associated tolerance band) as part of its plan to operate within System Operating Limits and Interconnection Reliability Operating Limits. [Violation Risk Factor: High] [Time Horizon: Operational Planning] 1.1. Each Transmission Operator shall provide a copy of the voltage schedules and associated tolerance bands to its Reliability Coordinator and adjacent Transmission Operators within 30 calendar days of a request. 8
9 New R2- Major VAR-001 Changes Since Last Posting Each Transmission Operator shall schedule sufficient reactive resources to regulate voltage levels under normal and Contingency conditions. Transmission Operators can provide sufficient reactive resources through various means including, but not limited to, reactive generation scheduling, transmission line and reactive resource switching, and using controllable load. [Violation Risk Factor: High] [Time Horizon: Real-time Operations, Same-day Operations, and Operational Planning] 9
10 New R3- Major VAR-001 Changes Since Last Posting Each Transmission Operator shall operate or direct the Real-time operation of devices to regulate transmission voltage and reactive flow as necessary. [Violation Risk Factor: High] [Time Horizon: Real-time Operations, Same-day Operations, and Operational Planning] 10
11 New R4- Major VAR-001 Changes Since Last Posting The Transmission Operator shall specify the criteria that will exempt generators from compliance with the requirements defined in Requirement R5, part 5.1, and any associated notification requirements. [Violation Risk Factor: Lower] [Time Horizon: Operations Planning] 4.1. If a Transmission Operator determines that a generator has satisfied the exemption criteria, it shall notify the associated Generator Operator. 11
12 New R5- Major VAR-001 Changes Since Last Posting Each Transmission Operator shall specify a voltage or Reactive Power schedule (which is either a range or a target value with an associated tolerance band) at either the high voltage side or low voltage side of the Generator Step-Up transformer at the Transmission Operator s discretion. [Violation Risk Factor: Medium] [Time Horizon: Operations Planning] o 5.1. The Transmission Operator shall provide the voltage or Reactive Power schedule to the associated Generator Operator and direct the Generator Operator to comply with the schedule in automatic voltage control mode (the AVR is in service and controlling voltage). o 5.2. The Transmission Operator shall provide the Generator Operator with the notification requirements for deviations from the voltage or Reactive Power schedule. o 5.3. The Transmission Operator shall provide the criteria used to develop voltage schedules and associated tolerance bands to the Generator Operator within 30 days of receiving a request. 12
13 New R6- Major VAR-001 Changes Since Last Posting After consultation with the Generator Owner regarding necessary stepup transformer tap changes and the implementation schedule, the Transmission Operator shall provide documentation to the Generator Owner specifying the required tap changes, a timeframe for making the changes, and technical justification for these changes. [Violation Risk Factor: Lower] [Time Horizon: Operations Planning] 13
14 Major VAR-002 Changes Since Last Posting Exemptions and testing are now written into the requirements for AVR settings. GOPs must meet the notification requirements of the TOPs. The standard now explicitly states it is appropriate for GOPs that do not monitor on the high side of a GSU to use a conversion methodology to determine how to set their AVRs. GOPs still have 15 minutes to restore a status change before reporting an AVR status change. A new requirement has been added requiring GOPs to report reactive capability changes within 30 minutes of becoming aware of the change. 14
15 New R1- Major VAR-002 Changes Since Last Posting The Generator Operator shall operate each generator connected to the interconnected transmission system in the automatic voltage control mode (with its automatic voltage regulator (AVR) in service and controlling voltage) unless the Generator Operator 1) is exempted by the Transmission Operator, or 2) has notified the Transmission Operator of one of the following: [Violation Risk Factor: Medium] [Time Horizon: Real-time Operations] o That the generator is being operated in start-up,1 shutdown, or testing mode pursuant to a Real-time communication or a procedure that was previously provided to the Transmission Operator; or o That the generator is not being operated in the automatic voltage control mode for a reason other than start-up, shutdown, or testing. 15
16 New R2- Major VAR-002 Changes Since Last Posting Unless exempted by the Transmission Operator, each Generator Operator shall maintain the generator voltage or Reactive Power schedule 3 (within each generating Facility s capabilities 4 ) provided by the Transmission Operator, or otherwise shall meet the conditions of notification for deviations from the voltage schedule provided by the Transmission Operator. [Violation Risk Factor: Medium] [Time Horizon: Real-time Operations] 2.1. When a generator s AVR is out of service or the generator does not have an AVR, the Generator Operator shall use an alternative method to control the generator reactive output to meet the voltage or Reactive Power schedule directed by the Transmission Operator When directed to modify voltage, the Generator Operator shall comply or provide an explanation of why the schedule cannot be met Generator Operators that do not monitor the voltage at the location specified in their voltage schedule shall have a methodology for converting the scheduled voltage specified by the Transmission Operator to the voltage point being monitored by the Generator Operator. 16
17 New R3- Major VAR-002 Changes Since Last Posting Each Generator Operator shall notify its associated Transmission Operator of a status change on the AVR, power system stabilizer, or alternative voltage controlling device within 30 minutes of the change. If the status has been restored within the first 15 minutes of such change, then there is no need to notify the Transmission Operator. [Violation Risk Factor: Medium] [Time Horizon: Real-time Operations] 17
18 New R4- Major VAR-002 Changes Since Last Posting Each Generator Operator shall notify its associated Transmission Operator within 30 minutes after becoming aware of a change in reactive capability due to factors other than a status change described in Requirement R3. If the capability has been restored within the first 15 minutes of such change, then there is no need to notify the Transmission Operator. [Violation Risk Factor: Medium] [Time Horizon: Real-time Operations] 18
19 Other Directives Projects Directives Team Jordan Mallory- PER (Training): PER-002 and PER-005 Steven Noess- MOD B (modeling data): MOD-010 through MOD- 015 Darrel Richardson- MOD C (demand data): MOD-016 through MOD-021 Ryan Stewart- MOD A (ATC, TTC, CBM): MOD-001, MOD-004, MOD-008, MOD-028, MOD-029 and MOD
20 Upcoming Key Dates November 4, VAR webinar; please register on the NERC calendar November 25, Successive Ballot Closes December 2-4, VAR team meeting in Portland The VAR SDT hopes to post for a final ballot before the end of the year. 20
21 Contact Information:
A. Introduction. VAR Voltage and Reactive Control
A. Introduction 1. Title: Voltage and Reactive Control 2. Number: VAR-001-4.2 3. Purpose: To ensure that voltage levels, reactive flows, and reactive resources are monitored, controlled, and maintained
More informationVAR Voltage and Reactive Control
VAR-001-4 Voltage and Reactive Control A. Introduction 1. Title: Voltage and Reactive Control 2. Number: VAR-001-4 3. Purpose: To ensure that voltage levels, reactive flows, and reactive resources are
More informationVAR Voltage and Reactive Control. A. Introduction
VAR-001-5 Voltage and Reactive Control A. Introduction 1. Title: Voltage and Reactive Control 2. Number: VAR-001-5 3. Purpose: To ensure that voltage levels, reactive flows, and reactive resources are
More informationVAR Generator Operation for Maintaining Network Voltage Schedules
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationVAR Generator Operation for Maintaining Network Voltage Schedules
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationVAR Generator Operation for Maintaining Network Voltage Schedules
A. Introduction 1. Title: Generator Operation for Maintaining Network Voltage Schedules 2. Number: VAR-002-3 3. Purpose: To ensure generators provide reactive support and voltage control, within generating
More informationVAR Generator Operation for Maintaining Network Voltage Schedules
A. Introduction 1. Title: Generator Operation for Maintaining Network Voltage Schedules 2. Number: VAR-002-3 3. Purpose: To ensure generators provide reactive support and voltage control, within generating
More informationVAR Generator Operation for Maintaining Network Voltage Schedules
A. Introduction 1. Title: Generator Operation for Maintaining Network Voltage Schedules 2. Number: VAR-002-4 3. Purpose: To ensure generators provide reactive support and voltage control, within generating
More informationStandard VAR Voltage and Reactive Control
A. Introduction 1. Title: Voltage and Reactive Control 2. Number: VAR-001-3 3. Purpose: To ensure that voltage levels, reactive flows, and reactive resources are monitored, controlled, and maintained within
More informationAugust 25, 2017 VIA ELECTRONIC FILING
!! August 25, 2017 VIA ELECTRONIC FILING Kirsten Walli, Board Secretary Ontario Energy Board P.O Box 2319 2300 Yonge Street Toronto, Ontario, Canada M4P 1E4 Re: North American Electric Reliability Corporation
More informationUNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION ) )
UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION North American Electric Reliability Corporation ) ) Docket No. PETITION OF THE NORTH AMERICAN ELECTRIC RELIABILITY CORPORATION FOR
More informationAugust 25, Please contact the undersigned if you have any questions concerning this filing.
!! August 25, 2017 VIA ELECTRONIC FILING Ms. Erica Hamilton, Commission Secretary British Columbia Utilities Commission Box 250, 900 Howe Street Sixth Floor Vancouver, B.C. V6Z 2N3 Re: North American Electric
More informationStandard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationStandard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules. 45-day Formal Comment Period with Initial Ballot June July 2014
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationStandard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationIndustry Webinar Draft Standard
Industry Webinar Draft Standard Project 2010-13.2 Phase 2 of Relay Loadability: Generation PRC-025-1 Generator Relay Loadability December 13, 2012 Agenda Welcome, Introductions and Administrative NERC
More informationVoltage and Reactive Procedures CMP-VAR-01
Voltage and Reactive Procedures CMP-VAR-01 NERC Standards: VAR-001-2 VAR-002-1.1b Effective Date: 07/31/2012 Document Information Current Revision 2.0 Review Cycle Annual Subject to External Audit? Yes
More informationMeeting Notes Project 2016-EPR-02 September 7-9, 2016
Meeting Notes Project 2016-EPR-02 September 7-9, 2016 PJM Audubon, PA Administrative 1. Introductions The meeting was brought to order by the Chair, S. Solis, at 8:35 a.m. Eastern on Tuesday, September
More informationStandard VAR b Generator Operation for Maintaining Network Voltage Schedules
A. Introduction 1. Title: Generator Operation for Maintaining Network Voltage Schedules 2. Number: VAR-002-1.1b 3. Purpose: To ensure generators provide reactive and voltage control necessary to ensure
More informationStandard MOD Area Interchange Methodology
A. Introduction 1. Title: Area Interchange Methodology 2. Number: MOD-028-2 3. Purpose: To increase consistency and reliability in the development and documentation of Transfer Capability calculations
More informationFinal ballot January BOT adoption February 2015
Standard PRC-024-21(X) Generator Frequency and Voltage Protective Relay Settings Standard Development Timeline This section is maintained by the drafting team during the development of the standard and
More informationStandard COM Communications
A. Introduction 1. Title: Communications 2. Number: COM-001-2 3. Purpose: To establish capabilities necessary to maintain reliability. 4. Applicability: 4.1. Transmission Operator 4.2. Balancing Authority
More informationWECC Standard VAR-002-WECC-2 Automatic Voltage Regulators
Document Title File Name Category Document date Adopted/approved by Date adopted/approved Custodian (entity responsible for maintenance and upkeep) Stored/filed Previous name/number Status Automatic Voltage
More informationImplementation Plan Project Balancing Authority Reliability-based Controls - Reserves
Implementation Plan Project 2010-14.1 Balancing Authority Reliability-based Controls - Reserves Implementation Plan for Approvals Required Prerequisite Approvals None Revisions to Glossary Terms The following
More informationStandard MOD Verification of Models and Data for Generator Excitation Control Sys tem or Plant Volt/Var Control Functions
Standard MOD-026-1 Verification of Models and Data for Generator Excitation Control Sys tem or Plant Volt/Var Control Functions Standard Development Roadmap This section is maintained by the drafting team
More informationBEFORE THE ALBERTA ELECTRIC SYSTEM OPERATOR
BEFORE THE ALBERTA ELECTRIC SYSTEM OPERATOR NORTH AMERICAN ELECTRIC ) RELIABILITY CORPORATION ) NOTICE OF FILING OF THE NORTH AMERICAN ELECTRIC RELIABILITY CORPORATION OF PROPOSED RELIABILITY STANDARD
More informationStandard Development Timeline
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the Board of Trustees. Description
More informationStandard Development Timeline
PRC-026-1 Relay Performance During Stable Power Swings Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the
More informationStandard PRC Coordination of Generating Unit or Plant Voltage Regulating Controls with Generating Unit or Plant Capabilities and Protection
Standard Development Roadmap This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed:
More informationStandard PRC Coordination of Generating Unit or Plant Capabilities, Voltage Regulating Controls, and Protection
Standard Development Roadmap This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed:
More informationIndustry Webinar. Reactive Power Planning. NERC System Analysis and Modeling Subcommittee (SAMS) March 2017
Industry Webinar Reactive Power Planning NERC System Analysis and Modeling Subcommittee (SAMS) March 2017 Webinar Topics Reliability Guideline on Reactive Power Planning Webinar Topics Fundamentals of
More informationSystem Operating Limit Definition and Exceedance Clarification
System Operating Limit Definition and Exceedance Clarification The NERC-defined term System Operating Limit (SOL) is used extensively in the NERC Reliability Standards; however, there is much confusion
More informationStandard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction
A. Introduction 1. Title: Generator Frequency and Voltage Protective Relay Settings 2. Number: PRC-024-1 3. Purpose: Ensure Generator Owners set their generator protective relays such that generating units
More informationStandard Development Timeline
PRC-026-1 Relay Performance During Stable Power Swings Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the
More informationCover Sheet. Technical Justification Retirement of WECC Regional Reliability Standard VAR-002-WECC-2 Automatic Voltage Regulators (AVR)
Cover Sheet Attachment G (AVR) Retirement of WECC Regional Reliability Standard VAR-002-WECC-2 (AVR) Page 1 of 23 Request to Retire White Paper Retirement of WECC Regional Reliability Standard VAR-002-WECC-2
More informationDate Description Revision May 19, 2008
Voltage and Reactive Power Schedule r10 Revision History Date Description Revision May 19, 2008 Initial E.ON document to establish guidelines applicable to all generator owners connected to /KU r0 May
More informationFinal ballot January BOT adoption February 2015
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationDefinition of Bulk Electric System Phase 2
Definition of Bulk Electric System Phase 2 NERC Industry Webinar Peter Heidrich, FRCC, Standard Drafting Team Chair June 26, 2013 Topics Phase 2 - Definition of Bulk Electric System (BES) Project Order
More informationStandard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction. See the Implementation Plan for PRC
A. Introduction 1. Title: Generator Frequency and Voltage Protective Relay Settings 2. Number: PRC-024-2 3. Purpose: Ensure Generator Owners set their generator protective relays such that generating units
More informationImplementation Plan Project Modifications to PRC Reliability Standard PRC-025-2
Project 2016-04 Modifications to PRC-025-1 Reliability Standard PRC-025-2 Applicable Standard PRC Generator Relay Loadability Requested Retirement PRC 025 1 Generator Relay Loadability Prerequisite Standard
More informationgeneration greater than 75 MVA (gross aggregate nameplate rating) Generation in the ERCOT Interconnection with the following characteristics:
A. Introduction 1. Title: Verification of Models and Data for Turbine/Governor and Load Control or Active Power/Frequency Control Functions 2. Number: MOD-027-1 3. Purpose: To verify that the turbine/governor
More informationNORMES DE FIABILITÉ DE LA NERC (VERSION ANGLAISE)
COORDONNATEUR DE LA FIABILITÉ Direction Contrôle des mouvements d énergie Demande R-3944-2015 NORMES DE FIABILITÉ DE LA NERC (VERSION ANGLAISE) Original : 2016-10-14 HQCMÉ-10, Document 2 (En liasse) Standard
More informationImplementation Plan Project Alignment of Terms
Revisions to Defined Terms in the NERC Glossary of Terms Used in Reliability Standards The drafting team proposes modifying the following Glossary of Terms definitions: Blackstart Resource
More information(Circuits Subject to Requirements R1 R5) Generator Owner with load-responsive phase protection systems as described in
A. Introduction 1. Title: Transmission Relay Loadability 2. Number: PRC-023-3 3. Purpose: Protective relay settings shall not limit transmission loadability; not interfere with system operators ability
More informationTHIS DOCUMENT IS RETIRED BY FERC EFFECTIVE SEPTEMBR 5, 2018.
THIS DOCUMENT IS RETIRED BY FERC EFFECTIVE SEPTEMBR 5, 2018. A. Introduction 1. Title: Automatic Voltage Regulators (AVR) 2. Number: VAR-002-WECC-2 3. Purpose: To ensure that Automatic Voltage Regulators
More informationStandard MOD Verification of Models and Data for Generator Excitation Control System or Plant Volt/Var Control Functions
Standard MOD-026-1 Verification of Models and Data for Generator Excitation Control System or Plant Volt/Var Control Functions A. Introduction 1. Title: Verification of Models and Data for Generator Excitation
More informationStandard Development Timeline
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the NERC Board of Trustees (Board).
More information5. Effective Date: On the first day of the first quarter, after applicable regulatory approval.
A. Introduction 1. Title: Automatic Voltage Regulators (AVR) 2. Number: VAR-002-WECC-2 3. Purpose: To ensure that Automatic Voltage Regulators on synchronous generators and condensers shall be kept in
More informationStandard Development Timeline
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Description of Current Draft
More informationProcedure for ERO Support of Frequency Response and Frequency Bias Setting Standard. Event Selection Process
This procedure outlines the Electric Reliability Organization (ERO) process for supporting the Frequency Response Standard (FRS). A Procedure revision request may be submitted to the ERO for consideration.
More informationStandard TOP Monitoring System Conditions
A. Introduction 1. Title: Monitoring System Conditions 2. Number: TOP-006-2 3. Purpose: To ensure critical reliability parameters are monitored in real-time. 4. Applicability 4.1. Transmission Operators.
More informationPRC Disturbance Monitoring and Reporting Requirements
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationDUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES. Transmission Planning
DUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES Transmission Planning TABLE OF CONTENTS I. SCOPE 1 II. TRANSMISSION PLANNING OBJECTIVES 2 III. PLANNING ASSUMPTIONS 3 A. Load Levels 3 B. Generation
More informationBulk Electric System Definition Reference Document
Bulk Electric System Definition Reference Document January, 2014 This draft reference document is posted for stakeholder comments prior to being finalized to support implementation of the Phase 2 Bulk
More informationStandard BAL Frequency Response and Frequency Bias Setting
A. Introduction Title: and Frequency Bias Setting Number: BAL-003-1 Purpose: To require sufficient from the Balancing (BA) to maintain Interconnection Frequency within predefined bounds by arresting frequency
More informationDocument C-29. Procedures for System Modeling: Data Requirements & Facility Ratings. January 5 th, 2016 TFSS Revisions Clean Open Process Posting
Document C-29 Procedures for System Modeling: January 5 th, 2016 TFSS Revisions Clean Open Process Posting Prepared by the SS-37 Working Group on Base Case Development for the Task Force on System Studies.
More informationOPERATING PROCEDURE. Table of Contents
Table of Contents PURPOSE... 1 1.0 CAISO DISPATCHER RESPONSIBILITIES... 2 Monitor Loads and Generators... 2 Monitor Balancing Areas... 2 Operate CAISO Controlled Grid Voltage Equipment... 3 Voltage Schedules...
More informationAvailable Transfer Capability (ATC) EE 521 Analysis of Power Systems Chen-Ching Liu Washington State University
Available Transfer Capability (ATC) EE 521 Analysis of Power Systems Chen-Ching Liu Washington State University i Available Transfer Capability (ATC) ATC measures the residual transfer capability in the
More informationBulk Electric System Definition Reference Document
Bulk Electric System Definition Reference Document Version 2 April 2014 This technical reference was created by the Definition of Bulk Electric System drafting team to assist entities in applying the definition.
More informationMay 30, Errata to Implementation Plan for the Revised Definition of Remedial Action Scheme Docket No. RM15-13-_
May 30, 2018 VIA ELECTRONIC FILING Ms. Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, D.C. 20426 RE: Errata to for the Revised Definition of Remedial Action
More informationBulk Electric System Definition Reference Document
Bulk Electric System Definition Reference Document JanuaryVersion 2 April 2014 This technical reference was created by the Definition of Bulk Electric System drafting team to assist entities in applying
More informationBAL Standard Project Frequency Response and Frequency Bias Setting Industry Webinar
BAL-003-1 Standard Project 2007-12 Frequency Response and Frequency Bias Setting Industry Webinar Terry L. Bilke Midwest ISO, Inc. David F. Lemmons Xcel Energy, Inc. Sydney L. Niemeyer NRG Texas LP November
More information4.2.1 Generators Transformers Transmission lines. 5. Background:
PRC-026-1 Relay Performance During Stable Power Swings A. Introduction 1. Title: Relay Performance During Stable Power Swings 2. Number: PRC-026-1 3. Purpose: To ensure that load-responsive protective
More informationNPCC Regional Reliability Reference Directory # 12. Underfrequency Load Shedding Program Requirements
NPCC Regional Reliability Reference Directory # 12 Under frequency Load Shedding Program Requirements Task Force on System Studies Revision Review Record: June 26 th, 2009 March 3 rd, 2010 Adopted by the
More informationCAISO Restricted - Do Not Distribute Outside of RC Project LOI and NDA Entities Page 1 of 24
RC0120A - RC IRO-010 Data Specification NOTE: Changes from Peak's Attachment A are highlighted in red in columns C through G Section Category Number Responsible Pa Data Item Data Transfer Method 1.1 Transmission
More informationStandard PRC Coordination of Generating Unit or Plant Capabilities, Voltage Regulating Controls, and Protection
A. Introduction 1. Title: Coordination of Generating Unit or Plant Capabilities, Voltage Regulating Controls, and Protection 2. Number: PRC-019-2 3. Purpose: To verify coordination of generating unit Facility
More informationTECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION
TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION Document 9022 Puget Sound Energy, Inc. PSE-TC-160.70 December
More informationPlanning Criteria. Revision 1.4 MAINTAINED BY: Transmission Working Group System Protection and Control Working Group Supply Adequacy Working Group
Planning Criteria Revision 1.4 MAINTAINED BY: Transmission Working Group System Protection and Control Working Group Supply Adequacy Working Group PUBLISHED: 10/9/2017 LATEST REVISION: Effective 7/25/2017
More informationRecently, the SS38 Working Group on Inter-Area Dynamic Analysis completed two study reports on behalf of the UFLS Regional Standard Drafting Team.
December 7 th, 2010 NPCC Full Member Committee; Please find attached a draft revised NPCC Regional Reliability Directory #12 Underfrequency Load Shedding Program Requirements and a draft revised NPCC UFLS
More informationSeptember 19, Errata to Implementation Plan for the Revised Definition of Remedial Action Scheme
!! September 19, 2017 VIA ELECTRONIC FILING Veronique Dubois Régie de l'énergie Tour de la Bourse 800, Place Victoria Bureau 255 Montréal, Québec H4Z 1A2 RE: Errata to for the Revised Definition of Remedial
More informationTECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF LARGE GENERATION FACILITIES. Document 9020
TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF LARGE GENERATION FACILITIES Document 9020 Puget Sound Energy, Inc. PSE-TC-160.50 December 19, 2016 TABLE OF CONTENTS
More informationReliability Guideline Methods for Establishing IROLs
Reliability Guideline Methods for Establishing IROLs September 2018 NERC Report Title Report Date I Table of Contents Preface... iv Preamble... v Executive Summary... vi Introduction... vii Use of Terminology
More informationUnofficial Comment Form Project Geomagnetic Disturbance Mitigation
Project 2013-03 Geomagnetic Disturbance Mitigation Please DO NOT use this form for submitting comments. Please use the electronic form to submit comments on the Standard. The electronic comment form must
More informationPRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1
A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 Purpose: To set load-responsive protective relays associated with generation Facilities at a level to prevent unnecessary tripping
More informationPRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1
PRC-025-1 Generator Relay Loadability A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 Purpose: To set load-responsive protective relays associated with generation Facilities
More informationLoss of Solar Resources during Transmission Disturbances due to Inverter Settings II
Loss of Solar Resources during Transmission Disturbances due to Inverter Settings II Informational Webinar on Level 2 NERC Alert Ryan Quint, Senior Manager, Advanced Analytics and Modeling Rich Bauer,
More informationCOS MANUAL. March 24, Version 1.2. Outage Coordination Process. Peak Reliability. Version 1.0. NERC Reliability Standard IRO-017-1
Outage Coordination Process Version 1.0 NERC Reliability Standard IRO-017-1 COS MANUAL March 24, 2017 www.peakrc.com. Contents 1. Conventions... 2 2. Introduction... 2 3. Purpose... 2 4. Applicability...
More informationIEEE Std Bulk System Opportunities from New Distributed Energy Resource Interconnection and Interoperability Standards
IEEE Std 1547-2018 Bulk System Opportunities from New Distributed Energy Resource Interconnection and Interoperability Standards Clayton Stice, ERCOT Jens C. Boemer, EPRI (on behalf of SCC21) NERC SPIDER
More informationENTSO-E Draft Network Code on High Voltage Direct Current Connections and DCconnected
ENTSO-E Draft Network Code on High Voltage Direct Current Connections and DCconnected Power Park Modules 30 April 2014 Notice This document reflects the work done by ENTSO-E in line with ACER s framework
More informationProject System Operating Limits Drafting Team Meeting Notes
Notes Tuesday, February 23, 2016 8:30 AM 5:00 PM Wednesday, February 24, 2016 8:30 AM 5:00 PM Thursday, February 25, 2016 8:30 AM 12:00 PM WECC office 155 North 400 West Salt Lake City, Utah 84103 ReadyTalk
More informationStandard BAL b Automatic Generation Control
A. Introduction 1. Title: Automatic Generation Control 2. Number: BAL-005-0.2b 3. Purpose: This standard establishes requirements for Balancing Authority Automatic Generation Control (AGC) necessary to
More informationPublic Art Mural Packet
Public Art Mural Packet October 2016 Thank you for your interest in the process for executing exterior murals on public or private property in within the City of Ashland. The attached documents are intended
More informationTTC Study for: the PEGS-Ambrosia Lake 230 kv Line and the PEGS-Bluewater 115 kv Line
TTC Study for: the PEGS-Ambrosia Lake 230 kv Line and the PEGS-Bluewater 115 kv Line Vince Leung March 27, 2017 Reviewed by Johnny Nguyen Table of Contents Background 2 Objective 3 Base Case Assumptions
More informationAmerican Nuclear Society
American Nuclear Society 1 Unraveling the Mystery of Consensus Standards Presented by: The American Nuclear Society Standards Committee January 31, 2017 Copyright 2017 by American Nuclear Society Purpose
More informationNORTH AMERICAN ELECTRIC RELIABILITY COUNCIL
NORTH AMERICAN ELECTRIC RELIABILITY COUNCIL Princeton Forrestal Village, 116-390 Village Boulevard, Princeton, New Jersey 08540-5731 (Revised) Implementation Plan for Cyber Security Standards The intent
More informationNo I am concerned about units that may be individually less than 20 MVA but collectively could eb much larger - wind farms. Yes
Name (34 Responses) Organization (34 Responses) Group Name (19 Responses) Lead Contact (19 Responses) Question 1 (39 Responses) Question 1 Comments (53 Responses) Question 2 (38 Responses) Question 2 Comments
More informationProject Balancing Authority Reliability-based Controls Reliability Standard BAL-005-1
Implementation Plan Project 2010-14.2.1 Balancing Authority Reliability-based Controls Reliability Standard BAL-005-1 Requested Approval s Requested Retirement BAL-005-0.2b Automatic Generation Control
More informationTransmission Availability Data System Phase II Final Report
Transmission Availability Data System Phase II Final Report Prepared by the Transmission Availability Data System Task Force for the NERC Planning Committee Approved by the Planning Committee on: Table
More information1
Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive
More informationMANITOBA HYDRO TRANSMISSION SYSTEM INTERCONNECTION REQUIREMENTS. July 2016 Version 4
MANITOBA HYDRO TRANSMISSION SYSTEM INTERCONNECTION REQUIREMENTS July 2016 Version 4 This page intentionally blank LEGISLATIVE AUTHORITY Section 15.0.3(1) of The Manitoba Hydro Act (C.C.S.M. c. H190) authorizes
More informationMassive Transient Stability Based Cascading Analysis and On-line Identification of Critical Cascades
1 Massive Transient Stability Based Cascading Analysis and On-line Identification of Critical Cascades Paper Number: 16PESGM2419 Marianna Vaiman, V&R Energy marvaiman@vrenergy.com 2016 IEEE PES General
More informationITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/
ITC Holdings Planning Criteria Below 100 kv * Category: Planning Type: Policy Eff. Date/Rev. # 12/09/2015 000 Contents 1. Goal... 2 2. Steady State Voltage & Thermal Loading Criteria... 2 2.1. System Loading...
More informationSouthern Company Interconnection Requirements for Inverter-Based Generation
Southern Company Interconnection Requirements for Inverter-Based Generation September 19, 2016 Page 1 of 16 All inverter-based generation connected to Southern Companies transmission system (Point of Interconnection
More informationAlberta Reliability Standard Frequency Response and Frequency Bias Setting BAL-003-AB-1.1
1. Purpose The purpose of this reliability standard is to: (a) require sufficient frequency response from the ISO to maintain Interconnection frequency within predefined bounds by arresting frequency deviations
More informationMeeting Notes Project Remedial Action Schemes Standard Drafting Team January 19-22, :00 p.m. 5:00 p.m. PT
Meeting Notes Project 2010-05.3 Remedial Action Schemes Standard Drafting Team January 19-22, 2015 8:00 p.m. 5:00 p.m. PT Southern California Edison Pomona, CA Administrative Introductions and chair remarks
More informationTTC/ATC 1.0 DEFINITIONS
TTC/ATC In this section: Definitions Total Transfer Capability (TTC) Available Transfer Capability (ATC) Counterflow ATC Postbacks in Pre-schedule of Grandfathered Agreements Real-Time Grant Remaining
More informationStandard BAL b Automatic Generation Control
A. Introduction 1. Title: Automatic Generation Control 2. Number: BAL-005-0.2b 3. Purpose: This standard establishes requirements for Balancing Authority Automatic Generation Control (AGC) necessary to
More informationStandard BAL b3 Automatic GenerationBalancing Authority Control DRAFT
A. Introduction 1. Title: Balancing Authority ControlAutomatic Generation Control 2. Number: BAL-005-30.2b 3. Purpose: This standard establishes requirements for acquiring necessary data for the Balancing
More informationUNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION
UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION Revisions to Electric Reliability ) Docket Nos. RM12-6-000 Organization Definition of Bulk Electric System ) RM12-7-000 And Rules
More informationNATS Swanwick. Interface Agreement. Owners: General Manager Swanwick. General Manager XXX
NATS Swanwick Interface Agreement between Swanwick And XXX Airport Owners: General Manager Swanwick General Manager XXX APPROVED BY Title Name Signature Date General Manager LTC Swanwick General Manager
More information