LIFE EXPECTANCY VS ACTUAL LIFE OF THE MAIN TRANSFORMERS FOR THE 3.4 MW POWER SUPPLY SUMMARY

Size: px
Start display at page:

Download "LIFE EXPECTANCY VS ACTUAL LIFE OF THE MAIN TRANSFORMERS FOR THE 3.4 MW POWER SUPPLY SUMMARY"

Transcription

1 SLACTN6820 C. A. Harris July 16, 1968 not to be abstracted, quoted oz further diaolosedwithout > LFE EXPECTANCY VS ACTUAL LFE OF THE MAN TRANSFORMERS FOR THE 3.4 MW POWER SUPPLY SUMMARY One of the two 2,000 kva rectifier transformers in the 3.4 MW power supply failed after only about 200 hours of operation at maximum temperatures. These transfo.mers had been energized for about 446 hours total. A measurement of the resistance change of the kv primary windings taken before the insulation failure had indicated that the winding temperatures were excessive. A study was underway at the time of failure to estimate the life expectancy of the insulation and to recommend some practical changes to extend the life. This study predicted a maximum temperature of 330 C and an expected life 1 of from 100 to 300 hours. l

2 NTRODUCTON The two 2,000 kva transformers under discussion are the main rectifier transformers for the 3.4 MW power supply (340 v at 10,000 amps. ) The kv primary winding insulation is t Nomextl (made by Du Pont) a dry type insulation with naturalconuectioncooling. The secondary windings have water cooled hollow conductors andare not of concern in this report. These transformers have a long history of overheating. There have been other winding failures, but we had not tried to find a correlation between temperature and life before the present investigation. Blowers had been installed to increase the cooling of the primary windings for the previous set of trans formers; these blowers were in operation at the time of this last coil failure. High Voltage Coil Configuration Figures 1 and 2 shows the type of primary winding connections used. Note that this is a 3 phase transformer with an extended delta primary. The transformer has a Wye and a delta secondary to produce a 12 phase rectifier output. Two such transformers were used with the extentions in opposite senses to produce a 24 phase rectifier output. Average Resistance Change Due to Heating Figure 3 shows the details of the construction of the primary windings. Table shows the approximate resistances of the windings in each coil and the final resistance expected because of the calculated temperature rises. The expected resistances between terminals H2 and H3, (see Fig. 2) would thus be 1.20 ohms when hot; this hot resistance corresponds to an average temperature 225OC. 2

3 TABLE coil identification (Figure 3) Ti Maximum coil temperatures 215 C Maximum verage coil 1 :mperatures 180 Cav Coil dentification (Figure 2) R3t Coil resistance 20 C ohms Coil resistance hot ohms 0.33 Tii 145Oc Tiv TV Tvi 215Oc 255 C 155Oc 208 Cav R6t Tix 220 C TX 330 c 2 70 Cav Rgt Txi 260 C H2 to H Measured Resistance Change of the Primary Windings The resistance from H2 to H3 was measured on April 4, 1968 after an extended operation at 100% rated current. This should represent the conditions used by ). Walz for his thermal calculations. Measurements of this type must be made shortly after turn off, but the measured data must be corrected because the coil is cooling rapidly at this time. The value of resistance at the time of turn off is determined by measuring the resistance vs time and extrapolating the data back to zero time. Figure 4 shows just such a cooling curve plotted as the actual resistance for two transformers in parallel with a scale showing the corresponding temperatures vs time. t shows the average temperature at turnoff to be about 23O C. 3

4 Note that the measured hot resistance for one transformer is then 0.63 X 2 = 1.26 ohms, and that this is close to what would be expected using the temperature data of D. Walz. The fact that the measured hot resistance is slightly above the calculated hot resistance can be explained because the average temperature of the cooling air at the surface of the coils will be higher than the input air to the power supply. This difference is due to the temperature rise of the air as it passes through the ventilation ducts. The close correspondence shown between the calculated average temperature rise and that determined empirically allows us to use the Hot spot temperature of 330 C shown in Table, as an accurate temperature, Life Expectancy The life of this insulation should be based upon 330 C and the operating voltage gradient of 75.5 volts ac peak per mil average. (No stress concentrations are considered. ) The major insulation is flnomexll a nylon fibrous material made by Du Pont and is described in their Bulletin N204 February Figure 5 is a copy of their Fig. 10 which shows the expected life of this insulation vs temperature. At 330 C, Nomex would have about a 200 hour life. Figure 6 shows a plot of life vs voltage gradients for several different materials. have dashed in a line showing what would expect for our operating conditions for ttnomexll. This line shows an expected life of only 100 hours for our operating conditions. The reader must keep in mind that these graphs can only be considered approximate averages. A considerable spread of data is to be expected. The Transformer Failure One of the pair of transformers (Type El5109 serial PT853) failed on May 17, 1968 after about 446 total hours of operation of which only about 200 hours ( an estimate) was at full operating temperature. The location of the failure seems to be in coil R7 of phase 1 which is one with the highest temperatures. The coil would have to be unwound to confirm the location of the fault (see Fig. 2). 4

5 The resulting short circuit currents (that were limited by #400E high voltage fuses) caused some mechanical damage tc coil R3. The transformer terminals had been protected from voltage transients with surge capacitors and lightning arresters; therefore believe that this hilure is due to the high temperatures associated with major insulation of the transformer. The power supply was put back into operation on June 27, 1968 with new oil filled transformers purchased for the purpose by SLAC. ACKNOWLEDGEMENTS Credit must be given to the many suggestions offered by M. Berndt, P. Edwards, and D. Walz during the course of this investigation. REFERENCES 1. D. Walz; Temperature Distribution in the Windings of the 3400kW P. S. SLAC TN Bulletin N204 Du Pont Co., February

6 S TO S5 = 315 S2 TO S4 = 315 volts* APPROX volts /turns*, 0 s3 A! SECONDARY \!, 55 H2 S A /a+ RATED 94 AMPS ; \ RATED 52.2 S4 / / / i SECONDARY #2 S6 *APPROXMATE NUMBERS H2,= 12,470 V H3,B = 11,420 V B C = 9,540V H3 C =, 880 V Fig. 1

7 = ul K

8 nner Winding # 8 Square 26.1 Amps/Cond. nsul. Film.0035 Coil Resistance R9 TX1 X TX lx Tx V \\\\)&is\\\\ \\\\\A\\ ~,\\\\\,\\\\\\\,,,,,,,,~ LV Winding Air JD f e Ft/Min 1 Air Duct h Material Press Board Air # 8 Square # 8 Square # 8 Square Thickness in inches T Center Winding V # 8 Square 26.1 Amps/Cond. T nsul. Film.OO35 V Coil Resistance R6 T V SOMCA Air # 8 Square # 8 Square # 8 Square Outer Winding # 9 Rectangular 47 Amps/C&d. nsul. Film.004 Coil Resistance R3 :klnnnn p ~::, ~; ::....:.r..:::..*.:.._... :.t...,_.:,.$i z..:.,..._c\_... i _..L.....,.. Air Up Natural Vent. SOMCA Air # 9 Square # 9 Square Aluminum Press Board FG. 3Schematic Cross Section Through HighVoltage Coil 1095A5

9 ZBE601 AjO ElNklfll ElMOd tl3ljv S3lCNW El tl L 9 C b C 2 0 j EE O lUdV ~N3~8RW 3oL 30 QyuW OO() l 02 SE 0 LE. O ot : 0 09 lb O 7'0 OS Et. si 7 o 001 9NllVtl % 001 Li ! 6, b O 6 i'0 Otl \ El E 091 \ \ E E; 0 \ 081 \ L 5 0 \ 6 \ \ =Jgkj&j3l\w XV R oocz J x

10 FGURE 10 EXTRACTED DUPONT BULLETN N204 FEB FROM Useful Life vs. Temperature Nylon Paper (lomil, Type 410 paper) O6 L Upper 95% Confidence Limit\,, l,,i n5 _ Confidence Limit 160 i TEMPERATURE, C. (Reciprocal AbsoluteTemperature Scale) Fig. 5

11 O year 100, kw P.S. TRANSFORMERS DESGN LEVEL ac Peak Average Stress POLYETHYLENE CABLE LFE Computed From AEE TRANS 5851 (ac Peak) MAX Stress TEST ON ONE SHEET 10 ML AT ROOM TEMPERATURE,+ By Du knt (ac Peak) (Average Stress) year 10, ML NYLON AEE 5470 ac Peak Room Temperature; Average Stress 2 ML MYLAR N AR AEE 5470 Room Temperature (4,800 v/mil Breakdown) (ac RMS) Average Stress month 1, Average \ \ \ \ \ \ \ \ \ \ \ \ \. Stress H, J /, H 3 x O Mils Nomex.0 CABLE (OL PAPER) ac Peak Reference Peek 1929 (Page 248) MAX Stress \ GRADENT n 3,400 kw P.S VOLTAGE GRADENT VOLTS PER ML (pk 1 Fig

Western Mining Electric Association San Antonio TX Layer vs. Disk Windings Discussion NOVEMBER 15, SPX Transformer Solutions, Inc.

Western Mining Electric Association San Antonio TX Layer vs. Disk Windings Discussion NOVEMBER 15, SPX Transformer Solutions, Inc. Western Mining Electric Association San Antonio TX NOVEMBER 15, 2012 PRESENTED BY David L. Harris, PE Customer Technical Executive SPX Transformer Solutions, Inc. Office: 262-521-0166 Cell: 262-617-3039

More information

ACS 1000 Transformer Failure Investigation. Nathan Schachter, Peng

ACS 1000 Transformer Failure Investigation. Nathan Schachter, Peng Investigation Nathan Schachter, Peng Objectives Learn what happened Explain why it happened Discuss solutions Suggest remedies so it does not happen again Prevention is the key to success 2 ACS 1000 VFD

More information

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications Minnesota Power Systems Conference November 3 5, 2009 Earl Brown Heritage Center University of

More information

PES & IAS NY Chapter And NY LMAG June 23 rd, 2015

PES & IAS NY Chapter And NY LMAG June 23 rd, 2015 PES & IAS NY Chapter And NY LMAG June 23 rd, 2015 High Temperature Insulation Systems and their use in Mobile Transformers Myron B. Bell, PE mbell@deltastar.com Delta Star, Inc. June 23 rd 2015 Introduction

More information

Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC)

Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC) Name: Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC) 1. T F In three-phase four-wire delta systems rated 240/120 volts, sometimes

More information

Electrical Design Process

Electrical Design Process Electrical Design Process Jason Varnell Lead Design Engineer Jason.Varnell@spx.com SPX Transformer Solutions, Inc. September 26, 2018 Agenda 1. Bid Design Process Parameters Affecting Bid Design 2. Final

More information

DETAIL SPECIFICATION SHEET CABLES, RADIO FREQUENCY, SEMIRIGID, COAXIAL, SEMI-AIR-DIELECTRIC,.875 TO INCHES OUTSIDE DIAMETER, 50 OHMS

DETAIL SPECIFICATION SHEET CABLES, RADIO FREQUENCY, SEMIRIGID, COAXIAL, SEMI-AIR-DIELECTRIC,.875 TO INCHES OUTSIDE DIAMETER, 50 OHMS INCH-POUND MIL-DTL-22931/11B 21 August 2013 SUPERSEDING MIL-C-22931/11A 20 January 1972 DETAIL SPECIFICATION SHEET CABLES, RADIO FREQUENCY, SEMIRIGID, COAXIAL, SEMI-AIR-DIELECTRIC,.875 TO 1.005 INCHES

More information

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS SECTION 16461C - DRY TYPE TRANSFORMERS PART 1 - GENERAL 1.1 This section includes design and performance requirements for dry-type transformers rated for use on secondary distribution systems rated 600

More information

Howard Smart Transformer Specification Guide

Howard Smart Transformer Specification Guide Howard Smart Transformer Specification Guide General Requirements Overhead pole-type smart distribution transformers shall be single phase, 60 Hz, mineral-oil filled and self-cooled and shall conform as

More information

Electrical Description

Electrical Description History of this Document Rev. no.: Date: Description of change 0 First edition 2 2003-10-08 Section 3: The rated power of the transformer can be increased by 40% if they are equipped with 6 fans for forced

More information

Connection Impact Assessment Application

Connection Impact Assessment Application Connection Impact Assessment Application This form is for generators applying for Connection Impact Assessment (CIA) and for generators with a project size >10 kw. Please return the completed form by email,

More information

+ 24V 3.3K - 1.5M. figure 01

+ 24V 3.3K - 1.5M. figure 01 ELECTRICITY ASSESSMENT 35 questions Revised: 08 Jul 2013 1. Which of the wire sizes listed below results in the least voltage drop in a circuit carrying 10 amps: a. 16 AWG b. 14 AWG c. 18 AWG d. 250 kcmil

More information

MV network design & devices selection EXERCISE BOOK

MV network design & devices selection EXERCISE BOOK MV network design & devices selection EXERCISE BOOK EXERCISES 01 - MV substation architectures 02 - MV substation architectures 03 - Industrial C13-200 MV substation 04 - Max. distance between surge arrester

More information

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length

More information

3-phase short-circuit current (Isc) at any point within a LV installation

3-phase short-circuit current (Isc) at any point within a LV installation 3-phase short-circuit current (Isc) at any point within a LV installation In a 3-phase installation Isc at any point is given by: where U 20 = phase-to-phase voltage of the open circuited secondary windings

More information

86 chapter 2 Transformers

86 chapter 2 Transformers 86 chapter 2 Transformers Wb 1.2x10 3 0 1/60 2/60 3/60 4/60 5/60 6/60 t (sec) 1.2x10 3 FIGURE P2.2 2.3 A single-phase transformer has 800 turns on the primary winding and 400 turns on the secondary winding.

More information

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T. The Importance of the Neutral-Grounding Resistor Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T. Presentation Preview What is high-resistance grounding (HRG)? What is the purpose of HRG? Why

More information

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class GE Ventilated Dry-Type Transformers Secondary Substation Transformers - 5 and 15kV Class GE ventilated dry-type transformers are designed for indoor or outdoor applications in schools, hospitals, industrial

More information

Three Phase Transformers

Three Phase Transformers Three Phase Transformers Theory and Calculations 8/29/2016 Copyright 2016 Dan Dudley & Associates Page 1 DELTA Transformer 8/29/2016 Copyright 2016 Dan Dudley & Associates Page 2 WYE Transformer 8/29/2016

More information

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012 SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM Unit Objectives Describe the structure of an atom. Identify atoms with a positive charge and atoms with a negative charge. Explain

More information

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces 1 Prediction of Transient Transfer Functions at Cable-Transformer Interfaces Joe Y. Zhou, Member, IEEE and Steven A. Boggs, Fellow, IEEE Joe Zhou participated in this work while completing his Ph.D. at

More information

Particulate Control O&M Training. APC/PCUG Conference July 12-16, 2009 The Woodlands, TX

Particulate Control O&M Training. APC/PCUG Conference July 12-16, 2009 The Woodlands, TX Particulate Control O&M Training APC/PCUG Conference July 12-16, 2009 The Woodlands, TX WPCA Particulate Training Seminar July 11, 2009 ESP Power Supply Choices Slide No 1 Precipitator Power Supplies Conventional

More information

Transformer Questions & Answers

Transformer Questions & Answers Transformer Questions & Answers. What is a transformer and how does it work? A transformer is an electrical apparatus designed to convert alternating current from one voltage to another. It can be designed

More information

Dry Type Transformers Full Line Catalog. jeffersonelectric.com

Dry Type Transformers Full Line Catalog. jeffersonelectric.com Dry Type Transformers Full Line Catalog jeffersonelectric.com The Transformer Authority PIONEER TRANSFORMERS: Why us? Scale We produce over 100,000 transformers every year. With this high level of production

More information

Regional Technical Seminar SHORT CIRCUIT FORCES

Regional Technical Seminar SHORT CIRCUIT FORCES Regional Technical Seminar SHORT CIRCUIT FORCES Short Circuit Forces Wallace Exum Electrical Design Engineer wallace.exum@spx.com Agenda 1. What is Short Circuit 2. Types of Faults 3. How to Calculate

More information

Transformer Questions & Answers

Transformer Questions & Answers Transformer Questions & Answers. What is a transformer and how does it work? A transformer is an electrical apparatus designed to convert alternating current from one voltage to another. It can be designed

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

Regional Technical Seminar SHORT CIRCUIT FORCES

Regional Technical Seminar SHORT CIRCUIT FORCES Regional Technical Seminar SHORT CIRCUIT FORCES Douglas W Reed Principal Electrical Design Engineer douglas.reed@spx.com SPX Transformer Solutions, Inc. June 20th, 2018 Agenda 1.Review transformers: How

More information

LOI Progress Report -- Summary of Experiment in January

LOI Progress Report -- Summary of Experiment in January LOI Progress Report -- Summary of Experiment in January 2010 -- LOI-7 February 18, 2010 1. Introduction Following the previous experiments in October, 2009, a new method to improve the RF waveform distortions

More information

2013 Applied Power Electronics Conference (APEC) Page 1 of 8

2013 Applied Power Electronics Conference (APEC) Page 1 of 8 This presentation describes AC capacitors that are manufactured with film with aluminum foil, dielectric technology and applied in medium voltage systems. We are defining these medium voltage systems as

More information

(2) New Standard IEEE P (3) Core : (4) Windings :

(2) New Standard IEEE P (3) Core : (4) Windings : (d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.

More information

TUTORIAL Inductor Database in the Thermal Module

TUTORIAL Inductor Database in the Thermal Module TUTORIAL Inductor Database in the Thermal Module October 2016 1 A typical inductor consists of three main parts: core, bobbin (also called coil former), and winding, as shown below. To construct an inductor

More information

Description & Applications Questions & Answers Selection Charts Single Phase Selection Charts Three Phase...

Description & Applications Questions & Answers Selection Charts Single Phase Selection Charts Three Phase... SECTION BUCK-BOOST TRANSFORMERS A simple and economical way to correct offstandard voltages... from 95 to 500 volts; single and three phase, in sizes up to 60 kva. Simplified buck-boost rating charts make

More information

Curve accuracy (enough data points to be statistically significant): See Attachment B.

Curve accuracy (enough data points to be statistically significant): See Attachment B. Curve accuracy (enough data points to be statistically significant): See Attachment B. /11.0 proposals Mar 2006.doc /11.0 proposals Mar 2006.doc ATTACHMENT A New Business By Subhash Tuli Waukesha Electric

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

R Distribution Transformers. Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections. Reference Data

R Distribution Transformers. Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections. Reference Data Distribution Transformers Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections R201-90-2 Reference Data CONTENTS POPULAR DlSTRIBUTlON TRANSFORMER AND CIRCUIT VOLTAGES... 1 2400-Volt Systems

More information

The Variable Threshold Neutral Isolator (VTNI)

The Variable Threshold Neutral Isolator (VTNI) The Variable Threshold Isolator (VTNI) Installation Instructions INTRODUCTION The is designed specifically for installation between the primary neutral of a power utility distribution system and the secondary

More information

Application Note. Applicable Product: AC Drives

Application Note. Applicable Product: AC Drives Application Note Application Note Guidelines For The Use Of 400-600 Volt AC Drives In Medium Voltage Applications Applicable Product: AC Drives 4kV Step-down Transformer AC Drive 400-600V Output Filter

More information

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian) PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian) 1.0 General This specification covers the electrical characteristics and

More information

Short-Circuit Current Calculations

Short-Circuit Current Calculations Basic Point-to-Point Calculation Procedure Step. Determine the transformer full load amps (F.L.A.) from either the nameplate, the following formulas or Table : Multiplier = 00 *% Z transformer Step 2.

More information

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method Calculation of Isc by the impedance method In a 3-phase installation Isc at any point is

More information

Insulation resistance testing

Insulation resistance testing Insulation resistance testing Application Note Introduction Insulation resistance testers can be used to determine the integrity of windings or cables in motors, transformers, switchgear, and electrical

More information

Conventional Paper-II-2011 Part-1A

Conventional Paper-II-2011 Part-1A Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance

More information

K Factor Power Transformers

K Factor Power Transformers Ashley-Edison AsiaElectricTransformers (UK) K Factor Power Transformers DTKF series Low Voltage Dry Type K Factor Power Transformers AET-DTKF-2004-01: Page 1 Asia Electric Transformers, Entrepreneur Business

More information

Distributed by: www.jameco.com 1-800-831-4242 The content and copyrights of the attached material are the property of its owner. LM1851 Ground Fault Interrupter General Description The LM1851 is designed

More information

GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW

GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW Electric Utility Contact Information DTE Energy Interconnection Coordinator One Energy Plaza, SB

More information

~=E.i!=h. Pre-certification Transformers

~=E.i!=h. Pre-certification Transformers 7 Transformers Section 26 of the electrical code governs the use and installations of transformers. A transformer is a static device used to transfer energy from one alternating current circuit to another.

More information

Prolific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2

Prolific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2 Plot No. A-267, MIDC, Road No. 6A, Opp. ESIS Hospital, Wagle Industrial Estate, Thane (West) - 400 604 CORE DETAILS Date: 4/2/206 Design No. mahati Step No. SIDES Figure - I B L- Wt- CENTRE Figure - II

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices

More information

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone

More information

Ripple & Max. capacitive Output Current

Ripple & Max. capacitive Output Current 0 Watts xxx Series Wide 4: Input Range Single Output Industry Standard /4 Brick -40 C to +0 C Operation 0 VDC Isolation Output Trim ±0% Remote On/Off Year Warranty Dimensions: QSC0:. x.4 x 0. (.9 x. x.

More information

APPENDIX 4 TYPICAL LAYOUT, VALUES AND CONSTANTS

APPENDIX 4 TYPICAL LAYOUT, VALUES AND CONSTANTS 109 APPENDIX 4 TYPICAL LAYOUT, VALUES AND CONSTANTS TYPICAL LAYOUT The purpose of a transformer is to transfer energy from the input to the output through the magnetic field. The layout of a partial typical

More information

Industrial Electricity. Answer questions and/or record measurements in the spaces provided.

Industrial Electricity. Answer questions and/or record measurements in the spaces provided. Industrial Electricity Lab 10: Building a Basic Power Supply ame Due Friday, 3/16/18 Answer questions and/or record measurements in the spaces provided. Measure resistance (impedance actually) on each

More information

Electric Power Quality: Voltage Sags Momentary Interruptions

Electric Power Quality: Voltage Sags Momentary Interruptions Slide 1 Electric Power Quality: Voltage Sags Momentary Interruptions Ward Jewell Wichita State University ward.jewell@wichita.edu Slide 2 Power Quality Events Voltage sags Outages/interruptions Voltage

More information

UNISONIC TECHNOLOGIES CO., LTD

UNISONIC TECHNOLOGIES CO., LTD UNISONIC TECHNOLOGIES CO., LTD GROUND FAULT INTERRUPTER DESCRIPTION The UTC GM1851 can specially provide ground fault protection for AC power outlets in consumer and industrial environments. As ground

More information

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved. Pomona, CA, May 24 & 25, 2016 Tertiary Winding Design in wye-wye Connected Transformers Scope of Presentation > Tertiary vs. Stabilizing Winding? Tertiary vs. Stabilizing Winding? Need for Stabilizing

More information

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1 GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

HPS Universal BUCK-BOOST TRANSFORMERS

HPS Universal BUCK-BOOST TRANSFORMERS BUCK-BOOST TRANSFORMERS Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...

More information

2.5. Contents Description Motor Drive Isolation Transformers... Mini Power Centers... Totally Enclosed Non-Ventilated Transformers

2.5. Contents Description Motor Drive Isolation Transformers... Mini Power Centers... Totally Enclosed Non-Ventilated Transformers .5 Transformers Distribution Transformers Three-Phase Type DT-3E Totally Enclosed Non-Ventilated Totally Enclosed Non-Ventilated Transformers Product Description Note: The following pages provide listings

More information

WDBR Series (RoHS compliant)

WDBR Series (RoHS compliant) WDBR Series (RoHS compliant) This new range of thick film planar power resistors on steel, offering high pulse withstand capability, compact footprint and low profile, to many demanding applications including

More information

High Frequency Sinewave Guardian TM Filter

High Frequency Sinewave Guardian TM Filter High Frequency Sinewave Guardian TM Filter 380V 480V TECHNICAL REFERENCE MANUAL FORM: SHF-TRM-E REL. April 2015 REV. 001 2015 MTE Corporation Caution Prior to start up; confirm the drive operation mode

More information

Dry-Type Transformers

Dry-Type Transformers Dry-Type Transformers 600 Volt Class Bulletin 7700-99 ISO 9002 Registered 1 Federal Pacific Federal Pacific History During 1987, the Electro-Mechanical Corporation acquired the dry-type transformer division

More information

Introduction. AC or DC? Insulation Current Flow (AC) 1. TECHNICAL BULLETIN 012a Principles of Insulation Testing. Page 1 of 10 January 9, 2002

Introduction. AC or DC? Insulation Current Flow (AC) 1. TECHNICAL BULLETIN 012a Principles of Insulation Testing. Page 1 of 10 January 9, 2002 Page 1 of 10 January 9, 2002 TECHNICAL BULLETIN 012a Principles of Insulation Testing Introduction Probably 80% of all testing performed in electrical power systems is related to the verification of insulation

More information

TEACHER ASSESSMENT BLUEPRINT ELECTRICAL CONSTRUCTION TECHNOLOGY. Test Code: 5171 Version: 01

TEACHER ASSESSMENT BLUEPRINT ELECTRICAL CONSTRUCTION TECHNOLOGY. Test Code: 5171 Version: 01 TEACHER ASSESSMENT BLUEPRINT ELECTRICAL CONSTRUCTION TECHNOLOGY Test Code: 5171 Version: 01 Specific Competencies and Skills Tested in this Assessment: OSHA Regulations and Electrical Safety Practices

More information

Insulation Resistance Testing

Insulation Resistance Testing Testing Application Note Introduction detailed information on leakage resistance testers can currents and resistance tests see be used to determine the integ- the following sections: What Is & Leakrity

More information

Safety through proper system Grounding and Ground Fault Protection

Safety through proper system Grounding and Ground Fault Protection Safety through proper system Grounding and Ground Fault Protection November 4 th, 2015 Presenter: Mr. John Nelson, PE, FIEEE, NEI Electric Power Engineering, Inc. Event to start shortly Scheduled time:

More information

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N S C I E N C E P A S S I O N T E C H N O L O G Y HVDC Transmission Michael Muhr Graz University of Technology Austria www.tugraz.at 1 Definition HV High Voltage AC Voltage > 60kV 220kV DC Voltage > 60kV

More information

FERRORESONANCE SIMULATION STUDIES USING EMTP

FERRORESONANCE SIMULATION STUDIES USING EMTP FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in

More information

440 (12) 416 (12) 416 (12) 440 (12)

440 (12) 416 (12) 416 (12) 440 (12) ALTERNATOR DATA SHEET Frame Size LVSI804X CHARACTERISTICS No of Bearings 2 WEIGHTS: Stator Assembly: 10141 lb 4 kg Rotor Assembly: 4184 lb 1898 kg Complete Assembly: 18289 lb 8296 kg MAXIMUM SPEED: 2250

More information

Transformer Design: Economics & Reliability

Transformer Design: Economics & Reliability Transformer Design: Economics & Reliability Weidmann-ACTI Inc. Technical Conference New Diagnostic Concepts for Better Asset Management November 8 10, 2004 Holiday Inn Capitol Plaza, Sacramento, CA H.

More information

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy Interconnection Coordinator 1945

More information

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8] Code No: RR320205 Set No. 1 1. (a) Explain about Bewley s Lattice diagrams and also mention the uses of these diagrams. [6+2] (b) A line of surge impedance of 400 ohms is charged from a battery of constant

More information

Hendrix Tap, Tie & Ground Wire

Hendrix Tap, Tie & Ground Wire Hendrix Tap, Tie & Ground Wire MADE IN U.S.A. 53 Old Wilton Road Milford, NH 03055-3119 603-673-2040 www.marmonutility.com A Marmon Wire & Cable/Berkshire Hathaway Company Tap Wire Description Hendrix

More information

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design IEEE PES Transmission and Distribution Conference 2008 Panel Session Large Wind Plant Collector Design Wind Farm Collector System Grounding by Steven W. Saylors, P.E. Chief Electrical Engineer Vestas Americas

More information

Generation of Sub-nanosecond Pulses

Generation of Sub-nanosecond Pulses Chapter - 6 Generation of Sub-nanosecond Pulses 6.1 Introduction principle of peaking circuit In certain applications like high power microwaves (HPM), pulsed laser drivers, etc., very fast rise times

More information

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A Group F : No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS Table : A No. Description 1. Make & Manufacturer 2. Place of Manufacturer 3. Voltage Ratio 4. Rating

More information

CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION

CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION 18 CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION 2.1 INTRODUCTION Transformers are subjected to a variety of electrical, mechanical and thermal stresses during normal life time and they fail when these

More information

ArresterFacts-002. Field Testing Arresters ArresterWorks.com. ArresterFacts are information modules pertaining to the arrester world.

ArresterFacts-002. Field Testing Arresters ArresterWorks.com. ArresterFacts are information modules pertaining to the arrester world. ArresterFacts are information modules pertaining to the arrester world. This Field Testing of Arresters module will clarify the many questions about assessing the quality of an installed high voltage arrester

More information

SECTION TRANSFORMERS

SECTION TRANSFORMERS SECTION 16460 - TRANSFORMERS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Section

More information

HOT SPOT STUDIES FOR SHEET WOUND TRANSFORMER WINDINGS

HOT SPOT STUDIES FOR SHEET WOUND TRANSFORMER WINDINGS HOT SPOT STUDIES FOR SHEET WOUND TRANSFORMER WINDINGS Sheldon P. Kennedy, Thomas Gordner Niagara Transformer Jean-Noel Bérubé Qualitrol / Neoptix Robert Ringlee, Jacques Aubin Consultant ABSTRACT Application

More information

Universal AC Input, 5 Volt Output, 10 Watt Power Supply

Universal AC Input, 5 Volt Output, 10 Watt Power Supply Design Note DN05064/D Universal AC Input, 5 Volt Output, 10 Watt Power Supply Device Application Input Voltage Output Power Topology I/O Isolation NCP1124 NCP431 Smart Meters, Electric Meters, White Goods

More information

ANSI DESIGN TEST REPORT Report No. EU1295-H-00 Type PVN Station Class Surge Arrester

ANSI DESIGN TEST REPORT Report No. EU1295-H-00 Type PVN Station Class Surge Arrester ANSI DESIGN TEST REPORT Report No. EU1295-H-00 Type PVN Station Class Surge Arrester This report records the results of the design tests made on Type PVN Station Class surge arresters in accordance with

More information

AC Current Monitor model ACM-2

AC Current Monitor model ACM-2 1.0 Safety Warnings The ACM-2 AC Current Monitor should be installed only by qualified technical personnel with knowledge of industrial electrical wiring and the requirements of the national and local

More information

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation M. Kondalu1, Dr. P.S. Subramanyam2 Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering College,

More information

Application and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16

Application and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16 Application and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16 COMMISSIONING 17-22 WIRING DIAGRAM 23 1. INTRODUCTION

More information

Pacific Crest Transformers

Pacific Crest Transformers April 2013 Multi-voltage Testing Transformers Anyone familiar with Pacific Crest Transformers is aware that the company offers a wide range of specialty transformers to suit a host of load applications.

More information

PANELMDP Main Distribution Panel. Descriptions Energy Efficient Transformer

PANELMDP Main Distribution Panel. Descriptions Energy Efficient Transformer PANELMDP Main Distribution Panel Eaton Corp Catalog Number Manufacturer Description Weight per unit Product Category Descriptions Product Type PANELMDP Eaton Corp 1.0 (lbs/each) Three Phase Energy Efficient

More information

Variable Transformers Product Design & Engineering Data

Variable Transformers Product Design & Engineering Data Variable Transformers Product Design & Engineering Data Product Design & Engineering Data Type 1010B Cutaway General Information STACO ENERGY PRODUCTS CO. is a leading manufacturer of variable transformers,

More information

APPENDIX 1 to LGIP INTERCONNECTION REQUEST FOR A LARGE GENERATING FACILITY

APPENDIX 1 to LGIP INTERCONNECTION REQUEST FOR A LARGE GENERATING FACILITY APPENDIX 1 to LGIP INTERCONNECTION REQUEST FOR A LARGE GENERATING FACILITY 1. The undersigned Interconnection Customer submits this request to interconnect its Large Generating Facility with Transmission

More information

Subject: Drive isolation transformers. VFD definition: History the short version. February 2012

Subject: Drive isolation transformers. VFD definition: History the short version. February 2012 February 2012 Subject: Drive isolation transformers This paper is designed to provide BASIC information on the application of transformers designed to manage secondary loads comprised largely of alternating

More information

CONTENTS. 1. Introduction Generating Stations 9 40

CONTENTS. 1. Introduction Generating Stations 9 40 CONTENTS 1. Introduction 1 8 Importance of Electrical Energy Generation of Electrical Energy Sources of Energy Comparison of Energy Sources Units of Energy Relationship among Energy Units Efficiency Calorific

More information

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS AMENDMENT NO. 1 SEPTEMBER 2011 TO IS 15086 (Part 1) : 2001/IEC 60099-1 (1991) SURGE ARRESTORS PART 1 NON-LINEAR RESISTOR TYPE GAPPED SURGE ARRESTORS FOR a.c. SYSTEMS (The Amendment was originally published

More information

Industrial Electrician Level 3

Industrial Electrician Level 3 Industrial Electrician Level 3 Industrial Electrician Unit: C1 Industrial Electrical Code I Level: Three Duration: 77 hours Theory: Practical: 77 hours 0 hours Overview: This unit is designed to provide

More information

Generator Advanced Concepts

Generator Advanced Concepts Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves

More information

Primary Metering. What is Primary Metering?

Primary Metering. What is Primary Metering? NWEMS Primary Metering August 22, 2018 Bill Unbehaun, Tacoma Power Exchanging Expertise Since 1893 What is Primary Metering? Metering energy flow past a point at high voltage above 600v Both PTs and CTs

More information

TECHNICAL BULLETIN 004a Ferroresonance

TECHNICAL BULLETIN 004a Ferroresonance May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques

More information

VariSTAR Type AZU heavy-duty distribution-class under-oil MOV surge arrester

VariSTAR Type AZU heavy-duty distribution-class under-oil MOV surge arrester Surge Arresters Catalog Data CA235016EN Supersedes TD235001EN September 2014 COOPER POWER SERIES VariSTAR Type AZU heavy-duty distribution-class under-oil MOV surge arrester General Eaton's Cooper Power

More information

Tutorial #2: Simulating Transformers in Multisim. In this tutorial, we will discuss how to simulate two common types of transformers in Multisim.

Tutorial #2: Simulating Transformers in Multisim. In this tutorial, we will discuss how to simulate two common types of transformers in Multisim. SCHOOL OF ENGINEERING AND APPLIED SCIENCE DEPARTMENT OF ELECTRICAL AND COMPUTER ENGINEERING ECE 2115: ENGINEERING ELECTRONICS LABORATORY Tutorial #2: Simulating Transformers in Multisim INTRODUCTION In

More information