REVISIONS. App Thom. App Sud. App PC IG 2014/09/19

Size: px
Start display at page:

Download "REVISIONS. App Thom. App Sud. App PC IG 2014/09/19"

Transcription

1 /0 REVISIONS Rev Description Rev n by Sud PC Thom VB LH Clyd Act Issue Date YYYY/MM/DD Gen. updates to content, format and spec number. Previously FF 204/09/9 IG 204/09/9 N/A N/A N/A N/A N/A N/A 204/09/23 Sud = Sudbury, Ontario, PC = Port Colborne, Thom = Thompson, Manitoba, VB = Voisey s Bay, LH = Long Harbour, Act = Acton, England, Clyd = Clydach, Wales, N/A = Not licable

2 2/0.0 PURPOSE This specification, in conjunction with project design criteria, describes the minimum requirements for instrumentation systems at Vale. Unless otherwise approved by Vale in writing, any new or modified instrumentation installation shall not deviate from this standard. 2.0 APPLICATION This specification, applies at any Vale locations indicated with approval on the cover page, with the following exceptions: 2. EXCEPTIONS None. 3.0 REFERENCE DOCUMENTATION The following documents were used in the development of this document or have instructions and procedures applicable to it. They shall be used in their most recent revision. SPEC-0800 SPEC SPEC SPEC-5600 SPEC SPEC SPEC SPEC SPEC SPEC Design and Layout General Requirements Instrumentation Drawings Construction Electrical and Instrumentation General Requirements Process Measurement - Flow Process Measurement - Pressure Process Measurement - Temperature Process Measurement Level Fluids and Solids Process Control Valves Power Supply and Grounding Power Supply and Grounding DCS & PLC Systems 4.0 APPLICABLE CODES AND STANDARDS Design shall comply with the latest editions of the Codes, Regulations, Standards and other references applicable in the Province of Ontario unless specifically stated otherwise in writing. In the event of conflicting requirements, the most stringent shall apply.

3 3/0 5.0 DRAWINGS AND DATA A complete set of detail engineering drawings and instrument data sheets shall be prepared for all instrumentation systems as outlined in specification SPEC Data sheets shall be supplied in electronic format for archiving purposes complete with make and model number and, if applicable, CRN number once such information is known. 6.0 UNITS AND MEASUREMENT Pressure: - kpa, mm.h2o Flow: - l/s, m3/hr, kg/hr, tonne/hr Temperature: - ºC Level: - % Angular Speed: - rpm Linear Velocity: - m/s Density: - SG, % solids Weight: - kg, tonne Motor Power: - kw, HP 7.0 ENVIRONMENTAL CONDITIONS Field mounted instruments shall be capable of withstanding the following conditions as a minimum unless site or project conditions warrant a wider range: - Indoor: +5 to +40 deg Celsius - Outdoor: 40 to 40 deg Celsius - 00% relative humidity 8.0 NUMBERING SYSTEMS 8. INSTRUMENT NUMBERING Each instrument shall be identified with an instrument tag. The instrument tag shall consist of function code letters followed by a loop number. The function code letters shall be in accordance with the latest edition of Instrumentation Systems and Automation Society, ISA S5. and as modified by Vale for project requirements.

4 4/0 Example: PIT-2345 Function Loop Number Vale shall assign instrument loop numbers as required upon request. 8.2 CONTROL LOOP NUMBERING A control loop is a combination of two or more interconnected instruments arranged to measure or control a process variable. The components of a control loop shall be identified by a group of code letters followed by a common loop number. Example: A pressure control loop with a pressure indicating transmitter PIT-2345 could have a pressure indicating controller PIC-2345 and a pressure control valve PV-2345 with associated positioner PY-2345 Where there are two or more instruments with the same code letters in a loop, sequential letter suffixes from A to Z shall be added to the loop number. 8.3 CABLE AND WIRE NUMBERING Cables serving loops or multiconductor/multipair cables serving a junction box or control panel shall be identified by a number consisting of the loop or panel number followed by a suffix according to the following: -S, -S2, etc. for all low level analog signal cables -C, -C2, etc. for discrete control cables -P, -P2, etc. for power supply cables -T, -T2, etc. for instrument tubing Examples: JB-2345-C for a control cable serving a junction box PIT-2345-S for a signal cable serving a pressure transmitter The identification of individual wires of a cable serving a loop shall consist of the loop number followed by sequential numbers -, -2, etc. The same wire number shall be used as far as the wire is electrically continuous.

5 5/0 8.4 CONTROL PANEL AND JUNCTION BOX NUMBERING Control panel and junction box numbering shall consist of the equipment number or loop number they are associated with followed prefixed according to the following: CP- for single control panels or CP-, CP2-, etc. for multiple control panels JB- for single junction boxes or JB-, JB2-, etc. for multiple junction boxes Examples: CP-2345 for a single control panel associated with a piece of equipment or loop number CP-2345, CP2-2345, etc. for multiple control panels associated with a piece of equipment or loop number For field junction boxes used as a marshalling point for multiple field instruments, the lowest instrument loop number present in the JB can be used as the JB number. 9.0 TAGS AND MARKERS All instruments shall be identified by their tag number inscribed on a metal tag and riveted, or otherwise securely attached, to the instrument. Attachment to removable instrument covers is not permitted. All cables are to be identified at both ends with permanent, weather, oil and solvent resistant markers. Eg. K-Type PVC Cable Markers and Carrier Strips ty-rapped to the cable. All wires are to be identified at both ends with permanent, weather, oil and solvent resistant markers. Eg. Z-Type PVC Wire Markers. Terminal blocks are to be identified with the wire tag number. Supply control panels and junctions boxes with lamacoid nameplates generally with black lettering (/4 minimum) cut into a white background. Refer to panel or junction box layout drawings for details. Labels shall be permanently and securely attached without compromising the enclosure rating. 0.0 POWER SUPPLIES AND GROUNDING Refer to requirements as outlined in specifications SPEC and SPEC

6 6/0.0 TRANSMISSION SIGNALS Preferred interface signals between field instruments and the control system shall be as follows: Analog: Analog: Analog: Discrete: Pneumatic: 4-20 ma DC c/w Hart Protocol RTD mv (thermocouple) 20 VAC, 60 Hz kpa (3-5 psig) 2.0 INSTRUMENT AIR AND INSTRUMENT TUBING 2. GENERAL Clean, dry and oil free air for pneumatic instruments and actuators shall be in accordance with ISA-S7.0.0 Quality Standard for Instrument Air. Each instrument or actuator requiring an air supply shall be provided with a combination filter/regulator with an output pressure gage. For instrument sizing, instrument air provided as part of the plant utility system can be assumed to be: Minimum: - 45kPa (60 psig) Normal: - 620kPa (90 psig) Maximum: - 825kPa (20 psig) Protect tubing in areas where the possibility of abuse exists. Provide a sleeve for tubing penetrations through floors and walls. Instrument purge lines are to be angled downward and fitted with mufflers. Instrument air isolation valves shall be lockable. 2.2 MATERIAL Tubing shall be seamless 36 stainless steel instrument air tubing. Fittings shall be 36 stainless steel compression type for ¼ to ½ stainless steel instrument air tubing.

7 7/0 2.3 TUBE SIZING (MINIMUM, VERIFY PLANT PREFERENCE) ¼ O.D. tubes - for pneumatic signals and air supplies to instruments. ⅜ O.D. tubes - for air supplies to final actuators such as control valves, cylinders, etc. ½ O.D. tubes - as required. 3.0 ENCLOSURES Provide Nema 4X rated enclosures for indoor, outdoor and all underground installations. Junction boxes for indoor use may be polycarbonate. Use stainless steel junction boxes for outdoor installations. Provide Nema 2 control panels for electrical room installations. Cable entry or conduit connection must be made with approved fittings. Cable entries shall be from the bottom. For indoor installation side entry is acceptable. Marshalling panels shall be provided for terminating DCS and PLC I/O field connections. The terminations in marshalling panels shall be wired to the corresponding I/O modules or termination units via pre-wired cables supplied with the equipment. All shield wires shall be grounded only at one end, preferably at the marshalling panel. Warning nameplates required by Provincial and other Inspection Authorities shall be provided in accordance with Codes and Regulations. Size panels with 20% spare. 4.0 CABLE AND WIRING Single pair, multi-pair and triad cables shall be galvanized steel armoured, twisted, with individual and overall shield as applicable, stranded wires with minimum 600 V, 90 deg C flame-retardant insulation, FT-4 rated. Use wire size #6 AWG for single pair and single triad cables and #8 for multi-pair and multi-triad cables. Multiconductor cables shall be galvanized steel armoured, #4 AWG stranded wires with minimum 600 V, 90 deg C flame retardant insulation, FT-4 rated. Outer jacket colour coding shall be as follows: Grey for DC power and signal cables Black for AC power and signal cables

8 8/0 Red is reserved for underground blasting cable Wire colour coding shall be as follows: Black and white for paired wires Black, white and red for triads Thermocouple extension cables shall be galvanized steel armoured, single pair, twisted, shielded, #8 AWG, stranded wires with 600 V, 90 deg C flame retardant insulation, FT-4 rated with ISA colour coded outer jacket. Special unarmoured cables, i.e. co-ax, etc. that must be run through the plant shall be run in liquid seal flexible conduit. AC and DC signals shall not be combined in the same cable. 5.0 CABLE TRAY (Ref Vale Eng Std SPEC-50002) Generally, the same cable trays shall be used for both instrumentation cables and instrument tubing. Electrical motor control and lighting cables shall be kept out of these trays wherever possible. In the event that electrical cables are installed in instrumentation cable trays, the voltage in the cables shall not exceed 600 volts. Cable trays shall be sized such that they are initially filled to 75% of capacity to allow for future expansion. 6.0 FIELD INSTRUMENTS (Ref Eng Stds SPEC-5600 to SPEC-56005) The action of controllers, alarm contacts, final control devices, etc., shall be such that the system is failsafe. (Upon failure of air supply or power, the final control device shall move in the direction that presents the least hazard.) Transmitters shall be used in place of discrete switches whenever practical. Transmitters shall be configured to fail low (below normal signal lower limit) as a default unless this conflicts with safety or operating requirements. Fail Status shall be noted on Instrument Data Sheets. Transmitters shall have an integral indicator displayed in engineering units as standard.

9 9/0 Accuracy of measurement shall be adequate for the specific application. In general, the normal accuracy of ± 0.5% of full-scale range shall apply. Scale ranges shall be selected such that the normal measurement signal indicates within 50-75% of scale calibration for linear scales, and 70-85% for square root scales. Scales and recorder charts shall be direct reading, i.e., calibrated in engineering units. Each field mounted pneumatic controller, transmitter and valve positioner shall be furnished with a lockable air isolation valve, adjustable air filter/regulator with output gauge All instruments, which are in contact with the process, shall be fabricated from a material that conforms to or exceeds the piping specification used for the process line. Pressure and temperature ratings of the instruments shall conform to the ratings of the process system of which they are a part. Field instruments shall be suitably protected from mechanical damage and mounted on building steel or on separate stand or supports with due consideration given to remoteness from heat or vibration sources as well as water and material spillage. Accessibility shall be adequate for both maintenance and operation. Items that require frequent access for maintenance shall have access from the floor or by platforms or catwalks. All field-mounted instruments shall be enclosed in gasketted, dust and moisture proof cases, suitable for continuous satisfactory operation under plant ambient conditions. Special enclosures or intrinsically safe instruments shall be provided for use in hazardous areas where applicable. Control valves shall be lockable. VFD s shall be used over throttling control valves in pump flow control applications. Refer to the plant or mine site for preferred instrument manufacturers. 7.0 APPENDICES endix A: Revision and Transition Notes endix B: Keywords

10 0/0 endix A: Revision and Transition Notes (Revisions are listed in reverse chronological order with most recent revision at the top. Revision notes describe: what was changed, why it was changed, and the plan to implement the change, including whether changes are retroactive) Revision General updates to content, format and spec number. Previously Rev 4. (was also temporarily numbered SPEC-4000-now obsolete) endix B: Keywords

REVISIONS. App Thom. App Sud. App PC IG 2014/09/19

REVISIONS. App Thom. App Sud. App PC IG 2014/09/19 GENERAL /7 REVISIONS Rev Description Rev n by Sud PC Thom VB LH Clyd Act Issue Date YYYY/MM/DD Gen. updates to content, format and spec number. Previously 5653-00.0.0 FF 204/09/9 IG 204/09/9 N/A N/A N/A

More information

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

VARIABLE FREQUENCY DRIVE SPECIFICATION

VARIABLE FREQUENCY DRIVE SPECIFICATION VARIABLE FREQUENCY DRIVE SPECIFICATION 1.0. SUMMARY The use of variable frequency drives (VFDs) in conjunction with wastewater lift stations has been identified as a means improve efficiency and to moderate

More information

Note: Do not bury sulphur dioxide lines Use stainless steel pipe and fittings only where specified on project drawings.

Note: Do not bury sulphur dioxide lines Use stainless steel pipe and fittings only where specified on project drawings. 1/7 1.0 APPLICATION This specification describes the minimum requirements for piping systems for the following service: Liquid and High Pressure Gaseous Dry Sulphur Dioxide (Less than 100 ppm of water)

More information

Non-Submersible Industrial Pressure Transducer

Non-Submersible Industrial Pressure Transducer Non-Submersible Industrial Pressure Transducer KPSI Transducers Series 27, 28, 30 FEATURES Custom Pressure Ranges up to 2000 (13,790 kpa) Accuracy to ±0.10% FS Analog Outputs of 4-20 ma or VDC Welded 316

More information

Field Devices and Wiring

Field Devices and Wiring Field Devices and Wiring Slide 2-1 Field Device and Wiring Overview The control system interfaces to the process through field devices. Our ability to control a process is limited to the accuracy of measurement

More information

User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters

User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters Table of Contents Page Introduction 1 Description 1 Specifications 2 Installation 3 Calibration 4 General Maintenance

More information

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS SECTION 16461C - DRY TYPE TRANSFORMERS PART 1 - GENERAL 1.1 This section includes design and performance requirements for dry-type transformers rated for use on secondary distribution systems rated 600

More information

User's Manual: Series 450T AC Current Input (External Sensor), AC-Powered Transmitters

User's Manual: Series 450T AC Current Input (External Sensor), AC-Powered Transmitters User's Manual: Series 450T AC Current Input (External Sensor), AC-Powered Transmitters Table of Contents Page Introduction 1 Description 1 Specifications 2 Installation 3 Calibration 4 General Maintenance

More information

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION)

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION) GENERAL MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION) SUBMITTED BY SASHIKUMAR G BHARAT HEAVY ELECTRICALS LIMITED INDUSTRIAL SYSTEMS GROUP Prof. C. N. R. Rao Circle I. I. Sc. POST Malleswaram Bangalore

More information

STANDARD SPECIFICATION FOR INSTRUMENT CABLES AND RELATED ACCESSORIES DOCUMENT NO : 44-LK /J.02/0014-A4

STANDARD SPECIFICATION FOR INSTRUMENT CABLES AND RELATED ACCESSORIES DOCUMENT NO : 44-LK /J.02/0014-A4 Page 1 of 12 STANDARD SPECIFICATION FOR INSTRUMENT CABLES DOCUMENT NO : 44-LK-5100-00/J.02/0014-A4 Rev No. Issue Date Pages Rev Description Prepared A 12-08-08 12 Issued for Comments / Approval By Checked

More information

This specification describes the minimum requirements for piping systems for the following service:

This specification describes the minimum requirements for piping systems for the following service: SPEC-3004 1/7 1.0 APPLICATION This specification describes the minimum requirements for piping systems for the following service: Service Water Design Conditions Operating Conditions 10 PSIG @ 33 o F to

More information

Model Q40CT. System Features. Toroidal Conductivity Monitor...

Model Q40CT. System Features. Toroidal Conductivity Monitor... ATI s Model Q40CT toroidal conductivity system is designed for on-line monitoring of chemically aggressive process solutions. This blind, analog version is ideally suited for applications where reliable

More information

Positioner with HART Communication Type 3780

Positioner with HART Communication Type 3780 Positioner with HART Communication Type 780 Application Single-acting or double-acting positioner for attachment to pneumatic control valves. Supplied with an electric input signal from to 20 ma Travels

More information

This specification describes the minimum requirements for piping systems for the following service:

This specification describes the minimum requirements for piping systems for the following service: 201/01/13 1/ 1.0 APPLICATION This specification describes the minimum requirements for piping systems for the following service: Service Air Design Conditions Operating Conditions Blast Air (see Note 1)

More information

Magnetostrictive Level Transmitter

Magnetostrictive Level Transmitter Magnetostrictive Level Transmitter The Model KMD is an advanced, state-of-the-art, two-wire, Magnetostrictive-based level transmitter suitable for a wide range of process applications. The latest in microprocessor

More information

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL Roline L1 Series Humidity - Temperature Transmitters INSTRUCTION MANUAL 20030314 CONTENTS Overview... 3 Operation... 5 Power supply... 5 Operating range and limits... 5 Temperature compensation of the

More information

Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters

Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters Class l, Division 1 Group A-D IIC T4 As our products are continuously improved, we reserve the right to make any change in the stated

More information

KENCO Loop Powered Magnetostrictive Transmitter. KMD SERIES Operation and Installation Manual. Table of Contents

KENCO Loop Powered Magnetostrictive Transmitter. KMD SERIES Operation and Installation Manual. Table of Contents KENCO ENGINEERING COMPANY P.O. BOX 470426, TULSA, OK 74147-0426 PHONE: (918) 663-4406 FAX: (918) 663-4480 http://www.kenco-eng.com e-mail: info@kenco-eng.com KENCO Loop Powered Magnetostrictive Transmitter

More information

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888

More information

2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER

2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER SAFE INSTALLATION MANUAL (FM APPROVAL) -WIRE UNIVERSAL TEMPERATURE TRANSMITTER (HART communication, intrinsically safe/explosion-proof) MODEL B6U/B6U-B BEFORE USE... SAFETY PRECAUTIONS This manual describes

More information

Submersible pressure sensor For water and wastewater Model LW-1

Submersible pressure sensor For water and wastewater Model LW-1 Replacement product: Model LF-1 Level measurement Submersible pressure sensor For water and wastewater Model LW-1 WIKA data sheet LM 40.03 Applications Level measurement in rivers and lakes Deep well and

More information

This specification describes the minimum requirements for service water piping systems (ie: cooling water, process water, etc.), located on surface.

This specification describes the minimum requirements for service water piping systems (ie: cooling water, process water, etc.), located on surface. SPEC-3500 1/9 1.0 PURPOSE This specification describes the minimum requirements for service water piping systems (ie: cooling water, process water, etc.), located on surface. Note: This specification does

More information

This specification describes the minimum requirements for piping systems for the following service:

This specification describes the minimum requirements for piping systems for the following service: SPEC-3501 1/ 1.0 APPLICATION This specification describes the minimum requirements for piping systems for the following service: Instrument Air Design Conditions 150 PSIG @ 180 F Operating Conditions 125

More information

SECTION WIRE AND CABLES. A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents.

SECTION WIRE AND CABLES. A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents. SECTION 26 05 19 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents. 1.2 CONTRACTOR SUBMITTALS A. The

More information

TECHNICAL SPECIFICATION FOR ANNUBAR (DELTA TUBE)

TECHNICAL SPECIFICATION FOR ANNUBAR (DELTA TUBE) TECHNICAL SPECIFICATION FOR ANNUBAR (DELTA TUBE) SPEC NO.: PE-SS-999-145-I009 REV. NO. 01 DATE : 20.04.2012 SHEET 1 OF 4 1.0 SCOPE This specification covers the Design, Manufacture, Inspection and Testing

More information

IP26 Series Current to Pneumatic Converter

IP26 Series Current to Pneumatic Converter Product Specifications 06.2016 PSS EVE0403 A-(en) IP26 Series Current to Pneumatic Converter The IP26 (current to pressure) transducer converts a 4 20mA electrical current signal to a proportional linear

More information

KMS305W. ManuFlo Page 1 MANU ELECTRONICS PTY LTD Flow Measurement Products. Electromagnetic Wafer Flowmeters with S300 display

KMS305W. ManuFlo Page 1 MANU ELECTRONICS PTY LTD Flow Measurement Products. Electromagnetic Wafer Flowmeters with S300 display Electromagnetic Wafer Flowmeters with S300 display for corrosive chemicals/acids & slurries (sizes: 2.5mm to 100mm) 0BFEATURES: For aggressive chemicals, slurries, oxides, grouts & dosing applications

More information

Submersible pressure sensor For oils and fuels Model LF-1

Submersible pressure sensor For oils and fuels Model LF-1 Level measurement Submersible pressure sensor For oils and fuels Model LF-1 WIKA data sheet LM 40.04 Applications Level measurement in vessel and storage systems for oils and fuels Overfilling and dry-run

More information

LT3000 ULTRASONIC LEVEL TRANSMITTER

LT3000 ULTRASONIC LEVEL TRANSMITTER LT3000 ULTRASONIC LEVEL TRANSMITTER Owner s Manual Specifications Installation Calibration Troubleshooting Warranty Drawings Distributed By: iprocessmart.com 14262 Doolittle Drive San Leandro, CA 94577

More information

Service Instructions. The Conductor Controls. Conductor DC15-A, Enclosed Unit CH15-A, Open Chasis Unit

Service Instructions. The Conductor Controls. Conductor DC15-A, Enclosed Unit CH15-A, Open Chasis Unit Service Instructions The Conductor Controls Conductor DC15-A, Enclosed Unit CH15-A, Open Chasis Unit Table of Contents General Section Page Safety Instructions.. 4 Introduction 5 Inspection and Long-Term

More information

FH CMF Coriolis Mass Flow Meters

FH CMF Coriolis Mass Flow Meters FH CMF Coriolis Mass Flow Meters 1. Introduction Coriolis Mass Flow Meters patented and developed by our company (Chinese Patent No. 03119685.3, 03149996.1) are the leading meters for precision flow measurement.

More information

SMART TEMPERATURE TRANSMITTERS. smar

SMART TEMPERATURE TRANSMITTERS. smar SMART TEMPERATURE TRANSMITTERS FEATURES Single unit accepts signal from: - Standart RTDs and Thermocouples - Single ended or differential sensing - mv signals from radiation pyrometers, load cells, etc.

More information

600T Series Transmitters. Specification Sheet. Model 653T Electronic temperature transmitter (PC programmable)

600T Series Transmitters. Specification Sheet. Model 653T Electronic temperature transmitter (PC programmable) Specification Sheet 600T Series Transmitters Model 65T Electronic temperature transmitter (PC programmable) High flexibility and wide rangeability Single transmitter accepts RTD/THC/mV/ohm Galvanically

More information

Installation guide 854 XTG Level Gauge

Installation guide 854 XTG Level Gauge Installation guide 854 XTG Level Gauge July 2008 Part no. 4416.276 Rev. 5 Enraf B.V. P.O. Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701 100 Fax : +31 15 2701 111 E-mail : enraf-nl@honeywell.com

More information

Signal converter for electromagnetic flowmeters

Signal converter for electromagnetic flowmeters Quick Start Signal converter for electromagnetic flowmeters Electronic revision: ER 3.0.xx The documentation is only complete when used in combination with the relevant documentation for the flow sensor.

More information

TEK-TEMP 2100A. Explosion-Proof Temperature Transmitter. TEMPERATURE. Technology Solutions

TEK-TEMP 2100A. Explosion-Proof Temperature Transmitter.   TEMPERATURE. Technology Solutions Technology Solutions TEK-TEMP 2100A Explosion-Proof Temperature Transmitter TEMPERATURE www.tek-trol.com Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys Introduction Tek-Trol s Explosion-Proof

More information

A representative from Occupational Health is to be involved in the commissioning process to address any Respiratory Protection Program requirements.

A representative from Occupational Health is to be involved in the commissioning process to address any Respiratory Protection Program requirements. SPEC-3017 1/8 1.0 PURPOSE This specification describes the minimum requirements for the installation of breathing air distribution systems (indoor and outdoor) up to the connection to the breathing air

More information

Dynamo Brushless DC Motor and GreenDriveTM Manual

Dynamo Brushless DC Motor and GreenDriveTM Manual Dynamo Brushless DC Motor and GreenDriveTM Manual This manual was developed as a guide for use by FIRST Robotics Teams using Controller Part Number 840205-000 in conjunction with the Nidec Dynamo BLDC

More information

RHE11. Hazardous Area Multifunction Coriolis Flow Transmitter. Features. Applications. Benefits

RHE11. Hazardous Area Multifunction Coriolis Flow Transmitter. Features. Applications. Benefits RHE11 Hazardous Area Multifunction Coriolis Flow Transmitter Features Wall or Pipe Bracket Mount Built in safety barriers allow operation with RHM sensor in hazardous area Selectable Metric and English

More information

INTERPLANT STANDARD - STEEL INDUSTRY. MEASUREMENT OF MOISTURE CONTENT (Second Revision) IPSS: (Second Revision)

INTERPLANT STANDARD - STEEL INDUSTRY. MEASUREMENT OF MOISTURE CONTENT (Second Revision) IPSS: (Second Revision) INTERPLANT STANDARD - STEEL INDUSTRY IPSS MEASUREMENT OF MOISTURE CONTENT (Second Revision) IPSS: 2-07-077-13 (Second Revision) No Corresponding IS Formerly: IPSS:2-07-077-93 0. FOREWORD 0.1 This Interplant

More information

M1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL

M1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL M1 Series Humidity - Temperature Transmitter INSTRUCTION MANUAL 20031110 -2- CONTENTS Overview... 3 Operation... 4 Power supply... 4 Operating range and limits... 4 Temperature compensation of the humidity

More information

Monocrystalline silicon smart differential pressure transmitter. High stability. Benefits. application DRS

Monocrystalline silicon smart differential pressure transmitter. High stability. Benefits. application DRS DRS 300 1 Monocrystalline silicon smart differential pressure transmitter DRS300 High stability Detailed Information application the flow of gas, vapor and liquid measurement with device (volume or mass

More information

RHE12. Hazardous Area Coriolis Mass Flow Transmitter. Features. Applications. Benefits

RHE12. Hazardous Area Coriolis Mass Flow Transmitter. Features. Applications. Benefits RHE12 Hazardous Area Coriolis Mass Flow Transmitter Features Field mounting Compact, pressure safe housing ATEX and CSA approvals for installation in hazardous areas 24 VDC power supply Configurable analog

More information

Industrial Pipe Marking

Industrial Pipe Marking Industrial Pipe Marking Pipe and Valve Identification Specialists SPECIFICATIONS ASME (ANSI) Standard A13.1-2007 The ASME (ANSI) Standard for pipe identification is a widely used guideline in determining

More information

Installation guide 971 SmartRadar LTi

Installation guide 971 SmartRadar LTi Installation guide 971 SmartRadar LTi March 2009 Part no. 4416.715 Revision 3 Enraf B.V. P.O. Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701 100 Fax : +31 15 2701 111 E-mail : enraf-nl@honeywellenraf.nl

More information

PowerFlex 400 AC Drive Guide Specification

PowerFlex 400 AC Drive Guide Specification PowerFlex 400 AC Drive Guide Specification Adjustable Frequency Drives 3.0 50HP @ 200 to 240V AC 3.0 350HP @ 380 to 480V AC PART 1 GENERAL 1.01 Quality Assurance A. The manufacturer shall have minimum

More information

PROGRAMMABLE FIELD TEMPERATURE TRANSMITTER

PROGRAMMABLE FIELD TEMPERATURE TRANSMITTER Configuration Code TM01 Series 642 Programmable HART Field Temperature The Series 642 programmable HART field temperature transmitter is a 2-wire unit with analog output. It includes input for RTDs; resistance

More information

FC Series Signal Conditioners

FC Series Signal Conditioners FC Series Signal Conditioners FC-33 DC Selectable Signal Conditioner with 3-way isolation Field configurable input and output ranges of 0-5V, 0-10 V, 0-20 ma and 4-20 ma with 1500 VDC isolation between

More information

U5300 Industrial Pressure Transducer

U5300 Industrial Pressure Transducer Superior Accuracy and Total Error Band Instrument Grade CE Compliant Compact Variety of Pressure Ports and Electrical Configurations Optional Stainless Steel Snubber Weatherproof Gage, Sealed, Absolute,

More information

Rosemount Specifications. Product Data Sheet , Rev BA February 2009 PERFORMANCE SPECIFICATIONS

Rosemount Specifications. Product Data Sheet , Rev BA February 2009 PERFORMANCE SPECIFICATIONS Rosemount 2051 Product Data Sheet PERFORMANCE SPECIFICATIONS Specifications For zero based spans, reference conditions, silicone oil fill, SST materials, Coplanar flange () or 1 /2 in. - 14 NPT () process

More information

DOCUMENT ADDENDUM NO. 4. Issued to all Bidders: Date: October 14, Contract Name: Electrical Installation. Contract Number: C8410

DOCUMENT ADDENDUM NO. 4. Issued to all Bidders: Date: October 14, Contract Name: Electrical Installation. Contract Number: C8410 DOCUMENT 009104 - ADDENDUM NO. 4 Issued to all Bidders: Date: October 14, 2015 Contract Name: Electrical Installation Contract Number: C8410 This addendum forms a part of the Bid described above. The original

More information

Nuclear Qualified Weed Instrument Model N7030 RTD and N7040 Thermocouple Analog Temperature Transmitter

Nuclear Qualified Weed Instrument Model N7030 RTD and N7040 Thermocouple Analog Temperature Transmitter DELIVERING CRITICAL MEASUREMENTS Nuclear Qualified Weed Instrument Model N7030 RTD and N7040 Thermocouple Analog Temperature Transmitter True Analog Transmitter Qualified per IEEE 323 Class 1E Mild Environment

More information

Model Sono-Trak Transit Time

Model Sono-Trak Transit Time Model Sono-Trak Transit Time Ultrasonic Flow Meter Engineered for performance excellence, the Sono-Trak Transit Time ultrasonic meter combines non-invasive, bi-directional measurement with advanced ultrasonic

More information

ENRAF SERVO GAUGE 854 ATG Setting the standard in gauging.

ENRAF SERVO GAUGE 854 ATG Setting the standard in gauging. ENRAF SERVO GAUGE 854 ATG Setting the standard in gauging. Technical Specifications Data Communication Honeywell Bi-phase mark (Pos 2 = E and I) 1200 / 2400 bps > 1,500 V Full galvanic separation via isolating

More information

KMS-2 Exia Magnetostrictive Level Transmitter

KMS-2 Exia Magnetostrictive Level Transmitter KMS-2 Exia Magnetostrictive Level Transmitter Revision B 11/10/2017 Installation and operating manual Please retain for future use Contents Symbols Used... 1 Safety information... 1 Introduction... 2 Outputs...

More information

Servo Gauge 854 XTG. Global Experience. Locally Applied. Cut costs, not repeatability.

Servo Gauge 854 XTG. Global Experience. Locally Applied. Cut costs, not repeatability. Servo Gauge 854 XTG Cut costs, not repeatability. Honeywell Enraf s 854 XTG servo gauge is a high performance alternative to other tank level measurement technologies such as radar tank level gauges. It

More information

SATRON VB Pressure Transmitter

SATRON VB Pressure Transmitter SATRON VB pressure transmitter belongs to the series V transmitters. SATRON VB is userfriendly, through the ball valve mounted transmitter which is used for 04 kpa... 03 MPa ranges. The transmitter communicates

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PRESSURE GAUGES, Section 15130

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PRESSURE GAUGES, Section 15130 PART 1 GENERAL 1.01 SUMMARY Section 15130 PRESSURE GAUGES, This Section includes the furnishing and subsequent installation of pressure gauges and pressure level transmitters as shown on Plans and specified

More information

Electromagnetic Flow Transmitter

Electromagnetic Flow Transmitter Electromagnetic Flow Transmitter Sensor in solid state technology Working as a transmitter and/or as an On/Off controller Automatic-calibration of full scale: Teach-In Clean in place (CIP) Type can be

More information

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section ELECTRICAL IDENTIFICATION

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section ELECTRICAL IDENTIFICATION PART 1 GENERAL 1.01 SUMMARY Section 16195 A. This Section includes electrical identification for the following: 1. Nameplates and labels 2. Wire and cable markers 3. Conduit markers 4. Cable tray markers

More information

This specification describes the minimum requirements for piping systems for the following service:

This specification describes the minimum requirements for piping systems for the following service: 201/11/2 1/9 1.0 APPLICATION This specification describes the minimum requirements for piping systems for the following service: Underground Service Water Note: This specification does not apply to piping

More information

SECTION EQUIPMENT WIRING

SECTION EQUIPMENT WIRING PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 26 27 17 EQUIPMENT WIRING A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General Provisions,

More information

DOWNSTREAM POWER, CONTROL & INSTRUMENTATION CABLES

DOWNSTREAM POWER, CONTROL & INSTRUMENTATION CABLES DOWNSTREAM POWER, CONTROL & INSTRUMENTATION CABLES DOWNSTREAM FACILITY CABLES El Dorado, Arkansas Made in America CIR (Crush & Impact Resistant) CIR is a next-generation cable designed to replace older-technology

More information

Submersible pressure sensor For superior applications Model LF-1

Submersible pressure sensor For superior applications Model LF-1 Level Submersible pressure sensor For superior applications Model LF-1 WIKA data sheet LM 40.04 Applications Level measurement in vessel and storage systems Overfilling and no-load operation monitoring

More information

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA The following standard specification is intended to be edited according to the specifics of the project. Brackets [ ] and areas shaded in gray [e.g. format] indicate requirements that are optional depending

More information

Owner Operator Guide to Emerging Smart Technology

Owner Operator Guide to Emerging Smart Technology Owner Operator Guide to Emerging Smart Technology Fluor s SmartPlant Implementation Initiative 2013 Fluor. All Rights Reserved. By: John Dressel Instrument Technological Revolution Process Measurement

More information

The Rosemount 848T Wireless Temperature Transmitter

The Rosemount 848T Wireless Temperature Transmitter Rosemount 88T Family February 0 The Rosemount 88T Wireless Temperature Transmitter The Rosemount 88T is the premier choice for Wireless High Density measurements. Four independently configurable inputs

More information

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL MicroChem Water Analysis System The MicroChem is a versatile multi-parameter instrument capable of being configured as a transmitter or PID controller. Specifically designed for drinking and wastewater

More information

Installation and Operating Instructions Differential pressure transmitter for potentially explosive areas. MG-1000-EEx USAGE STRUCTURE AND DESIGN

Installation and Operating Instructions Differential pressure transmitter for potentially explosive areas. MG-1000-EEx USAGE STRUCTURE AND DESIGN Installation and Operating Instructions Differential pressure transmitter for potentially explosive areas Mimablad: 176GB/1999-10-25 Ersätter: MG-1000-EEx USAGE MG-1000-EEx is suitable for use in measurement

More information

} Max. Load Resistance : 750Ω when power supply voltage is 24V DC (Max. load resistance (Ω) = 50x Power Supply Voltage -450 ).

} Max. Load Resistance : 750Ω when power supply voltage is 24V DC (Max. load resistance (Ω) = 50x Power Supply Voltage -450 ). ISO-14001 ISO-9001 SPECIFICATION SHEET CP SERIES 2-WIRE TYPE DO TRANSMITTER Models: DCP-20T FEATURES Rigid aluminium enclosure with free angle mounting. Simple operation offers free range setting, auto-calibration,

More information

Ultrasonic level transmitter, non-contact

Ultrasonic level transmitter, non-contact Ultrasonic level transmitter, non-contact Type 8175 can be combined with... Compact, remote versions for level measurement up to 10 m Multi language menu control Interference echo filter Automatic calibration:

More information

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL PART I: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. a.

More information

905U Wireless. New Products... New Solutions. The wireless alternative to expensive cabling... Simple but Reliable. Easy to Use

905U Wireless. New Products... New Solutions. The wireless alternative to expensive cabling... Simple but Reliable. Easy to Use Wireless New Products... New Solutions The range of telemetry modules provide remote monitoring and control by radio or twisted-pair wire, over short or long distances. Transducer signals connected at

More information

25 TONNE HYDRAULIC PRESS MODEL NO: AHP 26

25 TONNE HYDRAULIC PRESS MODEL NO: AHP 26 WARNING: Read these instructions before using the machine 25 TONNE HYDRAULIC PRESS MODEL NO: AHP 26 PART NO: 7615115 OPERATION & MAINTENANCE INSTRUCTIONS LS1211 INTRODUCTION Thank you for purchasing this

More information

Installation guide 873 SmartRadar Control Unit & Antenna Unit

Installation guide 873 SmartRadar Control Unit & Antenna Unit Installation guide 873 SmartRadar Control Unit & Antenna Unit Rev. 7 January 2006 Part no. 4416.569 Enraf BV PO Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701 100 Fax : +31 15 2701 111 E-mail : info@enraf.nl

More information

HI 2204LT Loop Powered Level Weight Transmitter OPERATION AND INSTALLATION MANUAL

HI 2204LT Loop Powered Level Weight Transmitter OPERATION AND INSTALLATION MANUAL Loop Powered Level Weight Transmitter OPERATION AND INSTALLATION MANUAL Corporate Headquarters 9440 Carroll Park Drive San Diego, CA 92121 Phone: (858) 278-2900 FAX: (858) 278-6700 Web-Site: http://www.hardysolutions.com

More information

APT3200L SMART PRESSURE TRANSMITTER. Application Areas: WITH DIAPHRAGM SEAL

APT3200L SMART PRESSURE TRANSMITTER. Application Areas: WITH DIAPHRAGM SEAL WITH DIAPHRAGM SEAL APT3200L Application Areas: Nuclear Water & Wastewater Chemicals Petrochemical Oil & Gas Pulp & Paper Food & Beverage, Pharmaceutical Power Renewable Energy Alternate Fuel Autrol America

More information

Signal converter for electromagnetic flowmeters

Signal converter for electromagnetic flowmeters IFC 100 Quick Start Signal converter for electromagnetic flowmeters Electronic revision: ER 3.1.2_ The documentation is only complete when used in combination with the relevant documentation for the flow

More information

Digital flow ELEMENT transmitter for continuous flow measurement

Digital flow ELEMENT transmitter for continuous flow measurement Digital flow ELEMENT transmitter for continuous flow measurement Type 8036 can be combined with... DN06 to DN65 fluidic process connection Programmable outputs : one or two transistor output(s) and single

More information

SWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

SWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) SWF DV/DT Solutions Sinewave Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Does your application use variable frequency drives for improved

More information

Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual

Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual T3111 TRANSMITTER Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual Instruction manual for use of T3111 transmitters Transmitter

More information

Modus M Series. General Eastern Differential Pressure Transmitters. GE Sensing

Modus M Series. General Eastern Differential Pressure Transmitters. GE Sensing The Modus M Series family of differential pressure transmitters measure low pressures, and feature a variety of analog signal outputs with low power consumption. A wide selection of standard pressure ranges

More information

Chapter 7 Introduction to Instrumentation

Chapter 7 Introduction to Instrumentation Chapter 7 Introduction to Instrumentation Control Automático 3º Curso. Ing. Industrial Escuela Técnica Superior de Ingenieros Universidad de Sevilla Summary Introduction Basic concepts Properties of measurement

More information

Digital flow ELEMENT transmitter for continuous flow measurement

Digital flow ELEMENT transmitter for continuous flow measurement ELEMENT Transmitter Digital flow ELEMENT transmitter for continuous flow measurement Type can be combined with... PN10, DN15 to DN400 fluidic process connection Programmable outputs : one or two transistor

More information

Transducer transmitter BILT 4 II 2(1) G. Technical Manual

Transducer transmitter BILT 4 II 2(1) G. Technical Manual GB Transducer transmitter BILT 4 II 2(1) G Technical Manual Transducer transmitter BILT 4 Contents Introduction General... 3 Ex.safety description... 4 Technical data... 5 Installation General... 6 Mechanical

More information

Model RFT9709 Transmitter Instruction Manual

Model RFT9709 Transmitter Instruction Manual Model RFT9709 Transmitter Instruction Manual March 1999 Model RFT9709 Transmitter Instruction Manual For technical assistance, phone the Micro Motion Customer Service Department: In the U.S.A., phone

More information

MZB SERIES. Intrinsically Safe Shunt Diode Safety Barriers. Phone: Fax: Web: -

MZB SERIES. Intrinsically Safe Shunt Diode Safety Barriers. Phone: Fax: Web:  - MZB SERIES Intrinsically Safe Shunt Diode Safety Barriers Turck of Intrinsically Safe Shunt Diode Safety Barriers New series of Zener Barriers include a wider product range for more flexibility in more

More information

TxBlock-USB Transmitter

TxBlock-USB Transmitter Transmitter TEMPERATURE TRANSMITTER - OPERATING MANUAL V1.0x I INTRODUCTION The TxBlock-USB is a 4-20 ma 2-wire temperature transmitter for head mount, powered by the current loop. The output current is

More information

SECTION COMMON WORK RESULTS FOR HVAC

SECTION COMMON WORK RESULTS FOR HVAC SECTION 23 05 00 COMMON WORK RESULTS FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Ball Valve. 2. Hangers and Supports. 3. Identification Tags and Sleeves. 1.2 INCLUDED SECTIONS A. Section

More information

General Purpose Toroidal Conductivity Sensors

General Purpose Toroidal Conductivity Sensors Product Data Sheet PDS 71-226/228/revE December 2009 Model 226 and 228 General Purpose Toroidal Conductivity Sensors NON-CONTACTING (TOROIDAL) SENSORS resist corrosion and fouling SENSORS ARE IDEAL for

More information

Model 144H NEW. PC-Programmable Temperature Transmitter. Product Data Sheet

Model 144H NEW. PC-Programmable Temperature Transmitter. Product Data Sheet Product Data Sheet 00813-0101-4796 Model 144H PC-Programmable Temperature Transmitter FEATURES Configurable using the Model 144C Configuration Interface hardware and software Programmable via standard

More information

RH/RHT Series. Relative Humidity and Temperature Transmitters. GE Sensing & Inspection Technologies. Features

RH/RHT Series. Relative Humidity and Temperature Transmitters. GE Sensing & Inspection Technologies. Features GE Sensing & Inspection Technologies RH/RHT Series Relative Humidity and Temperature Transmitters The Relative Humidity (RH) and Temperature transmitters are designed for continuous monitoring of relative

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices

More information

Worcester Controls PB SMART PRODUCTS

Worcester Controls PB SMART PRODUCTS PB 935-5 SMART PRODUCTS SMART POSITIONER An Electronic Positioner with a Built-in Microcontroller For precise process control The DataFlo P Positioner, controlled by a 4-20 ma analog signal from a PLC

More information

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1.

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1. General data Mounting On linear actuators On quarter turn actuators ARCA-integrated or to VDI/VDE 3847-1 or IEC 534-6 (NAMUR) Range of stroke: 3... 130 mm Integrated to VDI/VDE 3847-2 or VDI/VDE 3845 Angle

More information

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL SINGLE PHASE INSTRUCTION MANUAL DIAGRAM D This manual applies to all single-phase buck & boost transformers sold by Larson Electronics. Please refer to the connection diagram on pages 4-6 for properly

More information

SALES SERVICE +358 (0)

SALES SERVICE +358 (0) SALES SERVICE +358 (0)17 262 3555 info@econosto.fi ADCATROL ELECTRO-PNEUMATIC POSITIONERS PE 986 (ATEX) DESCRIPTION The ADCATROL PE986 positioner requires an input signal of 4 20 ma for proportional control

More information

2. All work and materials shall be in full accordance with Local and State ordinance and with any prevailing rules and regulations.

2. All work and materials shall be in full accordance with Local and State ordinance and with any prevailing rules and regulations. General Conditions: 1. Deliver all food service equipment as specified herein, including that which is reasonably inferred, with all related items necessary to complete work shown on contract drawings

More information