1 GENERAL MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION) SUBMITTED BY SASHIKUMAR G BHARAT HEAVY ELECTRICALS LIMITED INDUSTRIAL SYSTEMS GROUP Prof. C. N. R. Rao Circle I. I. Sc. POST Malleswaram Bangalore Industrial Systems Group, Bangalore Page 1/7

2 TABLE OF CONTENTS SECTION DESCRIPTION OF CONTENT PAGE NO SECTION I SITE DATA 3 SECTION II APPLICABLE STANDARDS 4 SECTION III INSPECTION & TESTING 5 SECTION IV CONTRUCTION GUIDELINES 6-7 Industrial Systems Group, Bangalore Page 2/7

3 SECTION I SITE DATA 1 Location Altitude above sea level Charging Aisle and Converter Area 50 to 55 0 C (Indoor) 4 Scrap Aisle / General Shop Floor Area 45 0 C (Indoor) 5 Hot Metal / Liquid Steel Handling Area 55 0 C (Indoor) 6 Under direct incidence of sunrays 50 0 C (Indoor) 7 Electrical Room 32±2 0 C : RH 70% (Air-Conditioned) 8 Control Rooms 25±2 0 C : RH 55% (Air-Conditioned) 9 Cable Tunnels 45 0 C (Ventilated) 10 Relative Humidity ---- The ambient environment as mentioned above shall be maintained in the respective rooms for long and reliable service life of the electrical equipment. Note: The electrical rooms, control rooms will be provided with adequate airconditioning system, all automation equipment shall be designed for an ambient temperature of 45 0 C. In addition to this, for the switchboards, the in-panel temperature as per the enclosure used shall also be considered for derating. 1 System Voltage 415V, 3-phase, 4-wire 2 Frequency 50 Hz 3 Voltage Fluctuation ±6% for 415V 4 Frequency Fluctuation ±3% for all voltage levels 5 Fault Level 50kA for 1 sec for 415V 6 System Grounding Solidly earthed for 415V 7 Voltage level of AC-outlets inside rooms 15A, SPN receptacles 240 V AC 8 Control Voltage of automation equipments 240 V AC Industrial Systems Group, Bangalore Page 3/7

4 SECTION II APPLICABLE STANDARDS The PLC equipment, its accessories and its application shall correspond with the following standards and regulations. 1 NEMA National Electrical Manufacturers Association 2 DIN German Institute for Standardization 3 IEC International Electrotechnical Commission 4 IEEE Institute of Electrical and Electronics Engineers 5 ISA Instrument Society of America 6 ISO International Organization for Standardization 7 IS Indian Standards 8 IPSS Interplant Steel Standards General Specifications for standards: The equipment and accessories shall be in accordance with the latest relevant standards and codes of practice established by the Bureau of Indian Standards (BIS) wherever available, in order that specific aspects under Indian conditions are taken care of. In case where Indian Standards are not available, the equipments and accessories shall conform to the latest standards and codes of practice published by any other recognized National Standards Institutions or latest publications of International Electro-technical Commission (IEC). All electrical equipment shall also conform to the latest Indian Electricity Rules as regards safety, earthing and other essential provisions specified therein for installation and operation of electrical plants. All equipments shall comply with the statutory requirements of the Government of India and the Respective State where the equipment will be installed.. Industrial Systems Group, Bangalore Page 4/7

5 SECTION III INSPECTION & TESTING The Enclosures shall be inspected for complete integrity with respect to the approved dimension drawings. Tests shall be carried out to ensure correct integrated function as a whole. Test/Warranty Certificates for all brought out items and parts used (along with their serial numbers) are to be submitted and verified. Painting certificate for applicable color and type of coating shall be submitted and verified. Routine test certificates as per manufacturer s procedures shall be submitted and verified. Industrial Systems Group, Bangalore Page 5/7

6 SECTION IV CONSTRUCTION GUIDELINES 4.1 Mechanical Regulations The Programmable Logic Controllers (PLC) shall be of rugged, modular construction and plug-in-type. The PLC shall be suitable for reliable, failsafe operation in arduous steel plant environment where electromagnetic noise, high temperature, dust, humidity and mechanical shocks / vibrations are prevalent. All Cabinets are of floor standing Type Enclosures and shall be fabricated from CRCA sheet steel of thickness not less than 2mm with welded/modular construction throughout. Side panels, Top & Bottom Cover shall be of 1.6mm thick steel sheet and all load bearing members inside shall not be less than 2mm thickness. Panels shall be of Rittal Make with standard dimension 2000H x 1200W x 800D(excluding plinth). Marshalling panel of 600W shall be considered additionally wherever required. All welds shall be ground smooth and free from weld spatters. All cabinets to conform IEC 297 and DIN Standards. The front and rear doors (where applicable) shall be with lockable handle (3 levers) and shall open outwards through concealed hinges and shall have degree opening range. Four nos Removable eye bolt lifting lugs shall be furnished for each enclosure. The glass in front door (where applicable) shall be of wide toughened timed glass of 4mm thick with rubber beading all around and clamps at back support. Cable access will be from bottom through removable gland plate of 3mm thickness. Painting shall be of RAL 7035 and powder coated. The enclosure should provide full protection from dirt, dust, moisture and other contaminants and will be of IP-42 Grade. Foundation frame shall be made using MS Channel of 100x50x6 mm and will be painted with RAL mm Thick anti-vibration pad between panel and base is to be provided for all enclosures. Suitable stiffeners shall be provided for all Front / Rear Doors. All cubicles, racks and modules shall be provided with readily visible identification labels. All Cubicles shall be provided with two nos Cooling fan on top and louvers with filters on front/back doors. Industrial Systems Group, Bangalore Page 6/7

7 4.2 Electrical Regulations All wiring inside panels (both Internal & External) shall run through PVC channels with covers. Cable ducts shall have minimum depth of 75mm. PVC wiring channels shall have flammability certification as per UL94V0. PLC I/O Power supplies shall be connected to electrical earth (E1) by minimum 2.5 Sq mm cable. All PLC racks shall be isolated from the body of the Cubicle and connected to Electronic Earth (E2). All Instrument cable screens, etc shall be connected to Instrument/Electronic Earth (E2) All MCBs shall be of D-Curve Characteristic. All Interposing relays (24V DC) shall be of series CS8 with 2No+2NC and of AC15-3A rating. E1 and E2 Earth (30x6mm Cu) are isolated and 16Sq mm cable shall be used for connecting to PLC earth pits. All Power terminals shall be suitably covered with Acrylic sheet. All Internal wiring inside PLC shall be carried out with 1100V Grade multi stranded Copper wires with PVC Insulation. Terminal blocks shall be properly arranged to facilitate easy termination of cables and shall have required clearance to cable gland plates/adjacent terminal rows/panel sides & other installed equipments..color Code: S.NO DESCRIPTION CABLE COLOR CABLE SIZE TB COLOR TB SIZE 1 230V AC PHASE ( UPS - PT1 TO P1 ) RED 6 Sq mm RED 6 Sq mm 2 230V AC NEUTRAL ( UPS - PT1 TO N1) BLACK 6 Sq mm BLACK 6 Sq mm 3 230V AC PHASE ( NON UPS - PT2 TO P2 ) RED 6 Sq mm RED 6 Sq mm 4 230V AC NEUTRAL ( NON UPS - PT2 TO N2 ) BLACK 6 Sq mm BLACK 6 Sq mm 5 230V AC PHASE ( NON UPS - UTILITY ) RED 2.5 Sq mm CONNECTED TO 6 230V AC NEUTRAL ( NON UPS - UTILITY ) BLACK 2.5 Sq mm P2&N2 BUS BAR 7 230V AC PHASE ( UPS -AFTER BUS BAR ) RED 4 Sq mm RED 6 Sq mm 8 230V AC NEUTRAL ( UPS -AFTER BUS BAR ) BLACK 4 Sq mm BLACK 6 Sq mm 9 230V AC PHASE ( NON UPS-AFTER BUS BAR ) RED 4 Sq mm RED 6 Sq mm V AC NEUTRAL ( NON UPS-AFTER BUS BAR ) BLACK 4 Sq mm BLACK 6 Sq mm 11 ELECTRONIC EARTH GREEN 2.5 Sq mm CONNECTED TO E1&E2 12 POWER EARTH YELLOW/GREEN 2.5 Sq mm BUS BAR 13 DIGITAL INPUT SIGNAL YELLOW 0.75 Sq mm GREY 2.5 Sq mm 14 DIGITAL OUTPUT SIGNAL BLUE 0.75 Sq mm GREY 2.5 Sq mm 15 ANALOG INPUT SIGNAL RED-SCREEN 0.5 Sq mm GREY 2.5 Sq mm 16 ANALOG OUTPUT SIGNAL ORANGE-SCREEN 0.5 Sq mm GREY 2.5 Sq mm 17 RTD INPUT SIGNAL BROWN 0.5 Sq mm GREY 2.5 Sq mm 18 24V DC POSITIVE - UP TO BUS BAR ( BB1 ) BLUE 6 Sq mm BLUE 6 Sq mm 19 24V DC NEGATIVE - UP TO BUS BAR ( BB2 ) WHITE 6 Sq mm BLACK 6 Sq mm 20 24V DC POSITIVE - AFTER BUS BAR BLUE 1 Sq mm BLUE 2.5 Sq mm 21 24V DC NEGATIVE - AFTER BUS BAR WHITE 1 Sq mm BLACK 2.5 Sq mm 22 CONTACT WIRING GREY 1.5 Sq mm GREY 2.5 Sq mm Industrial Systems Group, Bangalore Page 7/7

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS PURCHASE SPECIFICATIONS OF 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS SPECIFICATION NO. : OR12423 REVISION NO. : Rev 00 DATE : 01.03.2011 DISTRIBUTION : PI - 4 copies O/C - 1 copy PREPARED BY

More information

VOLUME - 4 (GENERAL TECHNICAL SPECIFICATIONS)

VOLUME - 4 (GENERAL TECHNICAL SPECIFICATIONS) TENDER DOCUMENT NIT No. DLI/C&E/WI-665/535R FOR Tender for Supply of 3CX185 mm2, 11 KV (UE) grade, Power Cable for Augmentation of Raw Material Handling Receipt and Handling Facilities with new OHP Part

More information

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Part 1 - General Scope and Product Description 1.0 This specification contains the minimum design

More information

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888

More information

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS SECTION 16461C - DRY TYPE TRANSFORMERS PART 1 - GENERAL 1.1 This section includes design and performance requirements for dry-type transformers rated for use on secondary distribution systems rated 600

More information

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers SPECIFICATION GUIDE ABB VACUUM CAST COIL DRY TRANFORMERS CONTENTS 1. General 1.1. Codes and standards 1.2. Service conditions 1.3. System characteristics 1.4. Documentation 2. Design and construction 2.1.

More information

INTER PLANT STANDARD STEEL INDUSTRY VARIABLE VOLTAGE VARIABLE FREQUENCY SYSTEM (V.V.V.F.) V/F, VECTOR CONTROL / TORQUE CONTROL

INTER PLANT STANDARD STEEL INDUSTRY VARIABLE VOLTAGE VARIABLE FREQUENCY SYSTEM (V.V.V.F.) V/F, VECTOR CONTROL / TORQUE CONTROL INTER PLANT STANDARD STEEL INDUSTRY VARIABLE VOLTAGE VARIABLE FREQUENCY SYSTEM (V.V.V.F.) V/F, VECTOR CONTROL / TORQUE CONTROL IPSS: 1-10-035-06 IPSS Corresponding IS does not exist 0. FOREWORD 0.1 This

More information

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...

More information

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality. PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02

More information

SRS IT cabinets. Installation height numbering as a standard

SRS IT cabinets. Installation height numbering as a standard Among the core products of BKT ELEKTRONIK are metal IT cabinets and casings and related metal accessories. Cabinets are intended for passive and active network equipment with standard dimensions of 10",

More information

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1. TECHNICAL SPECIFICATIONS for Single Phase, 1 to 3 KVA Power Conditioner with Regulation and Distribution Constant Power 3 (CP3) CP36508A 7/15/04 1.0 General This specification covers the electrical characteristics

More information

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL PART I: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. a.

More information

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994

More information

POTENTIAL TRANSFORMER

POTENTIAL TRANSFORMER POTENTIAL TRANSFORMER September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:

More information

INTERPLANT STANDARD - STEEL INDUSTRY

INTERPLANT STANDARD - STEEL INDUSTRY INTERPLANT STANDARD - STEEL INDUSTRY SPECIFICATION FOR MOULDED - CASE CIRCUIT-BREAKER FOR VOLTAGES NOT EXCEEDING 1000 V ac OR 1500 V dc (FIRST REVISION) IPSS:1-04-004-11 IPSS BASED ON IS/IEC 60947(Part

More information

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date

More information

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING 1.0 General This specification covers the electrical characteristics and general

More information

2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS

2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 0640 807-0 Fax: 0640 807-259 IT system floor-standing distribution cabinet Series -IPS-F/EDS for supplying power to medical locations

More information

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION December 2016 SPECIFICATION 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

Low voltage switchgear

Low voltage switchgear Low voltage switchgear Sivacon S8 and 8PT Withdrawable core structure designed for demanding applications and international markets. SAT8 PU0 Main exchange system for demanding fixed output, industrial

More information

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class GE Ventilated Dry-Type Transformers Secondary Substation Transformers - 5 and 15kV Class GE ventilated dry-type transformers are designed for indoor or outdoor applications in schools, hospitals, industrial

More information

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian) PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian) 1.0 General This specification covers the electrical characteristics and

More information

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS

More information

Standard Product. Free-Stand Cabinets 19-in. Mini-Rack Cabinet, Components and Accessories

Standard Product. Free-Stand Cabinets 19-in. Mini-Rack Cabinet, Components and Accessories Spec-00466 F763.422.2661 763.422.2588 Free-Stand Cabinets 19-in. Mini-Rack Cabinet, Components and Accessories Free-Stand Cabinets 19-in. Mini-Rack Cabinet, Components and Accessories 19-in. Mini-Rack

More information

PROJECT: SUPPLY & INSTALL ELECTRICAL SWITCHBOARD AT SENGKURONG EXCHANGE PHASE 1, JLN TUTONG, BSB. SCOPE OF WORK The scope of work under Electrical Services shall include but not limited to the supply,

More information

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE PAGE 262400-1 SECTION 262400 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

5/2 Introduction. Unequipped Distribution Boards 5/4 Modular distribution boards 5/5 Add-on parts

5/2 Introduction. Unequipped Distribution Boards 5/4 Modular distribution boards 5/5 Add-on parts ALPHA AS Modular Distribution Boards /2 Introduction Unequipped Distribution Boards /4 Modular distribution boards / Add-on parts Assembly Kits for Unequipped Distribution Boards /6 8GK4 assembly kits

More information

19-in. Mini-Rack Cabinet, Type 1

19-in. Mini-Rack Cabinet, Type 1 Spec-00466 19-in. DP FX (763) Mini-Rack 422-2588 422-2661 Cabinet, Components and Accessories Free-Stand Networking Cabinets 19-in. Mini-Rack Cabinet, Type 1 Industry Standards NEMA Type 1 EIA 310-D /

More information

SECTION PANELBOARDS

SECTION PANELBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section

More information

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS 006: 2008 CEB SPECIFICATION COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS CEYLON ELECTRICITY BOARD SRI LANKA Specification for COMBINED METERING TRANSFORMERS (OUTDOOR TYPE) FOR

More information

2.14 Main Cable Type HO7RN-F4G10-15 Metres each Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type

2.14 Main Cable Type HO7RN-F4G10-15 Metres each Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type PAGE 2 of 6 2.14 Main Cable Type HO7RN-F4G10-15 Metres each 2.15 (a) O/P Voltage-350V(Max.) (b) O/P Current 150A(Max.) 2.16 Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type 2.17

More information

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1 GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

LXM32CD18N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw

LXM32CD18N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw Product data sheet Characteristics LXM32CD18N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V - 1.8 kw Main Range of product Lexium 32 Product or component type Device short name

More information

B. Manufacturers: Square-D, G.E. or Westinghosue.

B. Manufacturers: Square-D, G.E. or Westinghosue. SECTION 16470 - PANELBOARDS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

LXM32MD18N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw

LXM32MD18N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw Product data sheet Characteristics LXM32MD18N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V - 1.8 kw Main Range of product Lexium 32 Product or component type Device short name

More information

Solutions AGRICULTURAL LABORATORY & CLASSROOM FURNITURE. Education to Industry. Solutions for Your Workspace & Storage Needs

Solutions AGRICULTURAL LABORATORY & CLASSROOM FURNITURE. Education to Industry. Solutions for Your Workspace & Storage Needs AGRICULTURAL LABORATORY & CLASSROOM FURNITURE Education to Industry for Your Workspace & Storage Needs www.ageducationalsolutions.com 864-256-0621 info@ageducationalsolutions.com Workbenches Potting Benches

More information

K Factor Power Transformers

K Factor Power Transformers Ashley-Edison AsiaElectricTransformers (UK) K Factor Power Transformers DTKF series Low Voltage Dry Type K Factor Power Transformers AET-DTKF-2004-01: Page 1 Asia Electric Transformers, Entrepreneur Business

More information

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

Neutral Earthing. For permanent or temporary neutral earthing in HV systems Neutral Earthing Resistors RESISTORS For permanent or temporary neutral earthing in HV systems For continuous or temporary low-resistance neutral grounding in medium voltage systems Neutral point connection

More information

SECTION DISTRIBUTION SWITCHBOARDS

SECTION DISTRIBUTION SWITCHBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 11 SPEC WRITER NOTES: Use this section only for NCA projects. Delete between // -- // if not applicable to project. Also delete any other item or paragraph

More information

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 %

More information

Btdin RCD Add-on modules 63A for MCBs 1,5 modules per pole

Btdin RCD Add-on modules 63A for MCBs 1,5 modules per pole Index Pages 1. Descripton... 2 2. Product range... 2 3. Overall dimensions... 2 4. Fixing Connection... 3 5. Generl characteristics... 4 6. Compliance - Approvals... 6 7. Curves... 7 8. Auxiliares and

More information

LXM32MU60N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw

LXM32MU60N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw Product data sheet Characteristics LXM32MU60N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V - 0.4 kw Main Range of product Lexium 32 Product or component type Device short name

More information

OIL-IMMERSED ARC-SUPPRESSION COILS

OIL-IMMERSED ARC-SUPPRESSION COILS ISO 9001:2000 99-320 Żychlin, ul. Narutowicza 70 ISO 14001:2004 PN-N-18001:2004 www.ftz.pl Secretary s Office Tel.: +48 24 285 46 05, Fax: +48 24 285 46 31 zarzad@ftz.pl Sales and Marketing Department

More information

4/2 Introduction. Marshaling Boxes 4/8 8GK1 surface-mounting distribution boards

4/2 Introduction. Marshaling Boxes 4/8 8GK1 surface-mounting distribution boards ALPHA 630 - DIN Floor- Mounted Distribution Boards /2 Introduction Unequipped Distribution Boards /5 8GK1 surface-mounting distribution boards, IP3 /6 8GK1 surface-mounting distribution boards, IP55 Marshaling

More information

LXM32AD18M2 motion servo drive - Lexium 32 - single phase supply voltage 115/230V - 0.5/1kW

LXM32AD18M2 motion servo drive - Lexium 32 - single phase supply voltage 115/230V - 0.5/1kW Product data sheet Characteristics LXM32AD18M2 motion servo drive - Lexium 32 - single phase supply voltage 115/230V - 0.5/1kW Main Range of product Lexium 32 Product or component type Device short name

More information

Section five. Connection systems. Isobar 4 Evo MCB pan assemblies Mulitclip busbar and Polybloc 126. Comb busbars 127

Section five. Connection systems. Isobar 4 Evo MCB pan assemblies Mulitclip busbar and Polybloc 126. Comb busbars 127 Connection systems Section five Isobar 4 Evo MCB pan assemblies 122 1 Mulitclip busbar and Polybloc 126 Comb busbars 127 Terminals and installation accessories 128 129 121 Isobar 4 Evo MCB pan assemblies

More information

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads. -156 Purpose & Industrial Control Purpose (1000 kva and Below) mounted dry-type transformers of the two-winding type, self-cooled, with ratings and voltages as indicated on the drawings. shall be manufactured

More information

SHARDA Make Harmonics Filter

SHARDA Make Harmonics Filter SHARDA Make Harmonics Filter SHARDA offers perfect solution to minimize Harmonics level of industries where non-linear load like, VFD, Electronics load, Convertors, Voltage booster equipment s are present.

More information

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Engineering Specification Head of Electrical Engineering MESP 050100-01 TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Version:

More information

Installation requirements

Installation requirements Installation requirements for SUNNY CENTRAL 500U 1 Contents This document describes the requirements which have to be observed for the installation site of the Sunny Central 500U. The installation and

More information

Cablelink Plus Flush Technical

Cablelink Plus Flush Technical Cablelink Plus Flush Technical 107 technical hotline +44 (0)1268 563720 screeded floor systems is designed to provide power and data distribution highways in screeded floors. The robust system offers a

More information

PRODUCT FOR HIGH VOLTAGE APPLICATION. Current transformers for Gasinsulated. Instructions for installation, use and maintenance

PRODUCT FOR HIGH VOLTAGE APPLICATION. Current transformers for Gasinsulated. Instructions for installation, use and maintenance PRODUCT FOR HIGH VOLTAGE APPLICATION Current transformers for Gasinsulated switchgear type ELK Instructions for installation, use and maintenance 2 CURRENT TRANSFORMERS FOR GAS-INSULATED SWITCHGEAR TYPE

More information

2/2 Introduction. Unequipped Distribution Boards 2/5 8GK1 surface and flush-mounting distribution boards

2/2 Introduction. Unequipped Distribution Boards 2/5 8GK1 surface and flush-mounting distribution boards Siemens AG 010 ALPHA 160 - DIN Wall-Mounted Distribution Boards / Introduction Distribution Boards with Built-In Distribution Board Panels /4 8GK1 surface and flush-mounting with quickassembly kits Unequipped

More information

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT

More information

Cast resin transformers HARMONY TM

Cast resin transformers HARMONY TM Cast resin transformers HARMONY TM HARMONY TM the optimum solution for higher performance At a time when we are all seeking to preserve our way of life, the production of equipment whilst ensuring safety

More information

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS 1.0 SCOPE The following specification describes the features, design, and application of the Series 7200A

More information

Maharashtra State Electricity Distribution Co. Ltd.

Maharashtra State Electricity Distribution Co. Ltd. Maharashtra State Electricity Distribution Co. Ltd. SPECIFICATION NO. MSEDCL/ DIST:MSC-III/LT CAP/1/2009/R2(071009) SPECIFICATIONS FOR APP TYPE L.T. CAPACITOR UNITS OF 25 / 30 KVAR CAPACITY (FOR 63 / 100

More information

LXM32AD72N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw

LXM32AD72N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw Product data sheet Characteristics LXM32AD72N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V - 0.4 kw Main Range of product Lexium 32 Product or component type Device short name

More information

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS n Bureau of Indian Standards (BIS) is the NATIONAL STANDARD BODY. Established

More information

Plant Client Contract Code Document ID Contract No. TECHNICAL SPECIFICATIONS DC SHUNT Rev 00 Page 1 of 2

Plant Client Contract Code Document ID Contract No. TECHNICAL SPECIFICATIONS DC SHUNT Rev 00 Page 1 of 2 TECHNICAL SPECIFICATIONS Rev 00 Page 1 of 2 0 IFI Release for Enquiry 14/12/18 SSS 14/12/18 HGG 14/12/18 RBU - Rev. Status Description Date Prepared Date Checked Date Approved AC Based on: PIN-QMC-03-F101

More information

ALPHA DIN Wall-Mounted. Distribution Boards

ALPHA DIN Wall-Mounted. Distribution Boards Siemens AG 008 ALPHA 160 - DIN Wall-Mounted Distribution Boards / Introduction Distribution Boards with Built-In Distribution Board Panels /4 8GK1 surface and flush-mounting with quick-assembly kits Unequipped

More information

SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK

SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK PART 1.0 GENERAL 1.1 SCOPE A. This specification contains the minimum requirements for the design, manufacture and testing of a UL listed,

More information

1995 Metric CSJ SPECIAL SPECIFICATION ITEM Drop/Insert Multiplexor/Demultiplexor

1995 Metric CSJ SPECIAL SPECIFICATION ITEM Drop/Insert Multiplexor/Demultiplexor 1995 Metric CSJ 3256-02-049 1.0 Description SPECIAL SPECIFICATION ITEM 6093 Drop/Insert Multiplexor/Demultiplexor This Item shall govern for the furnishing and installation of intelligent drop/insert multiplexor/demultiplexors

More information

DSM Dynamic Shunt

DSM Dynamic Shunt DSM Dynamic Shunt 401-30286-00 Installation Manual Part Number 108-31058-00 Giddings & Lewis Controls, Measurement & Sensing NOTE Progress is an on going commitment at Giddings & Lewis. We continually

More information

Add-on modules DX 3 63A for MCBs DX 3 1,5 modules per pole

Add-on modules DX 3 63A for MCBs DX 3 1,5 modules per pole 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 Add-on modules DX 3 63A for MCBs CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4.

More information

Series P. Applications

Series P. Applications Ratings 25 800 VA Voltage Primary 230 / 400 / 460 V range Secondary 6 / 12 V 12 / 24 V 24 / 48 V 115 / 230 V Voltage selection by means of metal connection bridges, offering the full rated power at any

More information

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

INSTALLATION, OPERATION AND MAINTENANCE GUIDE INSTALLATION, OPERATION AND MAINTENANCE GUIDE FOR INDOOR/OUTDOOR SINGLE PHASE ENCAPSULATED TRANSFORMERS Indoor/Outdoor Encapsulated Transformers The pictures used in this guide are only a representation

More information

STANDARD SPECIFICATION FOR COLD JUNCTION COMPENSATION BOXES (CJCB)

STANDARD SPECIFICATION FOR COLD JUNCTION COMPENSATION BOXES (CJCB) SHEET 1 of 5 STANDARD SPECIFICATION FOR COLD JUNCTION COMPENSATION BOXES (CJCB) SPECIFICATION NO.: PES- 145-072 BHARAT HEAVY ELECTRICALS LIMITED POWER SECTOR PROJECTS ENGINEERING MANAGEMENT NOIDA INDIA

More information

Temperature controller, 4-channel

Temperature controller, 4-channel , 4-channel Subject to technical modification 716218 Identification Type TR-1-6218 4-channel Part-No. 716218 Use/Area of application Description The temperature controller has 4 separate channels. The

More information

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable: Reclosers NOVA Three-Phase Recloser Functional Specification Guide Functional specification for NOVA three-phase recloser 1. Scope This specification describes the features and ratings of the NOVA recloser.

More information

STAR ELECTRIC COMPANY

STAR ELECTRIC COMPANY STAR ELECTRIC COMPANY STECO manufacturers a complete range of Energy Efficient Mors conforming IS: 325. Efficiency class Improved efficiency PRODUCT RANGE International Standards 60034-1,5 60072 Rotating

More information

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor

More information

Reference Number PPS 05 - (RIC Standard: EP SP)

Reference Number PPS 05 - (RIC Standard: EP SP) Discipline Engineering Standard - NSW Category Electrical Title Low Voltage Isolating Transformer Reference Number PPS 05 - (RIC Standard: EP 17 00 00 11 SP) Document Control Status Date Prepared Reviewed

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

REVISIONS. App Thom. App Sud. App PC IG 2014/09/19

REVISIONS. App Thom. App Sud. App PC IG 2014/09/19 /0 REVISIONS Rev Description Rev n by Sud PC Thom VB LH Clyd Act Issue Date YYYY/MM/DD Gen. updates to content, format and spec number. Previously 560-0.0.0 FF 204/09/9 IG 204/09/9 N/A N/A N/A N/A N/A

More information

Form-IV. Form of Inspection/Test Report. (Under Regulation 43)

Form-IV. Form of Inspection/Test Report. (Under Regulation 43) Form-IV Form of Inspection/Test Report (Under Regulation 43) 1. Name and address of the Chartered Electrical Safety Engineer 2. Name and address of the consumer (or) Owner(or) supplier: Contact No: E-Mail:

More information

SPECIAL SPECIFICATION 1533 Drop/Insert Multiplexor/Demultiplexor

SPECIAL SPECIFICATION 1533 Drop/Insert Multiplexor/Demultiplexor 1993 Specifications CSJ 0177-11-131 SPECIAL SPECIFICATION 1533 Drop/Insert Multiplexor/Demultiplexor 1. Description. This Item shall govern for for the furnishing and installation of intelligent drop/insert

More information

Technical Specifications SECTION C

Technical Specifications SECTION C Page 1 of 19 INSTITUTE FOR PLASMA RESEARCH Technical Specifications SECTION C Design/engineering, manufacture, inspection, testing at vendor s site, delivery, handling at site, erection, precommissioning

More information

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER OPERATOR S MANUAL DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER Masibus Automation & Instrumentation Pvt. Ltd. B/30, GIDC Electronics Estate, Sector-25, Gandhinagar-382044, Gujarat, India Web Site: www..com

More information

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C 1 Tender Notice No. NESCO Utility / O&M Materials/58 / 8267, dtd.17.7.15 Group-C Sl no. Material Description Unit Quantity 1 33KV C.T. Oil

More information

PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator)

PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator) PRODUCT SPECIFICATION FOR A 15 THRU 500 kva, THREE PHASE, MODULAR POWER REGULATOR AND CONDITIONER PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator) 1.0 General This specification covers the electrical

More information

Local control stations for Zone 1 and Zone 21. Features. Description

Local control stations for Zone 1 and Zone 21. Features. Description Local control stations for Zone and Zone Local control stations for Zone and Zone Features The right size/material enclosure Optimum functionality thanks to the great variety of components Customised planning

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices

More information

Central Inverter SUNNY CENTRAL 200 / 250 / 250HE / 350

Central Inverter SUNNY CENTRAL 200 / 250 / 250HE / 350 Central Inverter SUNNY CENTRAL 200 / 250 / 250HE / 350 Installation Guide SC20_25_35-IEN094521 98-4004821 Version 2.1 EN SMA Solar Technology AG Table of Contents Table of Contents 1 Notes on this Manual..............................

More information

(1,5 modules per pole)

(1,5 modules per pole) 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 DX 3 MCB 25kA 80A to 125A CONTENTS PAGES 1. Description - Use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

Your Global Automation Partner. IMX12-DI01 Isolating Switching Amplifier. Safety Manual

Your Global Automation Partner. IMX12-DI01 Isolating Switching Amplifier. Safety Manual Your Global Automation Partner IMX12-DI01 Isolating Switching Amplifier Safety Manual Contents 2 Hans Turck GmbH & Co. KG T +49 208 4952-0 F +49 208 4952-264 more@turck.com www.turck.com Contents 1 About

More information

EMI Installation Guidelines

EMI Installation Guidelines EMI Installation Guidelines Although Red Lion Controls Products are designed with a high degree of immunity to Electromagnetic Interference (EMI), proper installation and wiring methods must be followed

More information

SPECIAL SPECIFICATION 6734 RS-232 Optical Modem

SPECIAL SPECIFICATION 6734 RS-232 Optical Modem 2004 Specifications CSJ 0924-06-244 SPECIAL SPECIFICATION 6734 RS-232 Optical Modem 1. Description. This Item shall govern for the furnishing and installation of Fiber Optic RS- 232 Data Modem (OTR) in

More information

1995 Metric CSJ SPECIAL SPECIFICATION ITEM Add/Drop Multiplexor/Demultiplexor

1995 Metric CSJ SPECIAL SPECIFICATION ITEM Add/Drop Multiplexor/Demultiplexor 1995 Metric CSJ 0113-13-109 SPECIAL SPECIFICATION ITEM 6225 Add/Drop Multiplexor/Demultiplexor 1.0 Description. This Item shall govern for the furnishing and installation of intelligent Add/Drop Multiplexor/Demultiplexor

More information

847H. Description. Features. Specifications

847H. Description. Features. Specifications 847H Bulletin 847H High Performance Industrial Incremental Encoders provide code disk resolutions of up to 65536 pulses per revolution at a signal frequency response of 820 khz. The 847H can provide 65536

More information

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems Arild Furnes,ATPA OGP/Petrobras workshop, 22.09.09 Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems September 24, 2009 Slide 1 Transformers for Ships and Offshore -

More information

SECTION CABLE TRAYS FOR ELECTRONIC SAFETY AND SECURITY

SECTION CABLE TRAYS FOR ELECTRONIC SAFETY AND SECURITY SECTION 26 05 36 CABLE TRAYS FOR ELECTRONIC SAFETY AND SECURITY PART 1 -GENERAL 1.1 SUMMARY A. Section includes cable tray. 1.2 REFERENCES A. ASTM A 123 Standard Specification for Zinc (Hot-Dip Galvanized)

More information

Technical Specifications

Technical Specifications Page 1 of 14 INSTITUTE FOR PLASMA RESEARCH Technical Specifications Design/engineering, manufacture, inspection, testing at vendor s site, delivery at site of resin cast dry type Cast Resin Transformer

More information

SECTION IDENTIFICATION FOR ELECTRONIC SAFETY AND SECURITY

SECTION IDENTIFICATION FOR ELECTRONIC SAFETY AND SECURITY SECTION 280553-IDENTIFICATION FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION A. This specification section covers the furnishing and installation of nameplates, labels, wire markers,

More information

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM Technical Specification of Back Clamp for LT Cross Arm (MS) Back clamp for LT Cross Arm made out of 50 x 6mm MS Flat suitable for 8m X 300 Kg PSC poles. After fabrication the cross arm shall be painted

More information

MODEL: M2SES SEN TRONIC AG [3] OUTPUT

MODEL: M2SES SEN TRONIC AG [3] OUTPUT Super-mini Signal Conditioners Mini-M Series HIGH/LOW SELECTOR Functions & Features Monitors two DC input signals and transmits an output signal proportional to the higher or lower input CE marking UL

More information

Outside Temperature Sensors

Outside Temperature Sensors 1 814 1814P01 Symaro Outside Temperature Sensors QAC31 Active sensors for acquiring the outside temperature Operating voltage AC 24 V or DC 13535 V Signal output DC 010 V or 420 ma Use The QAC31 outside

More information

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W ADC5000 SERIES AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications 60W, 125W and 250 W Input voltage 230/115 VAC voltages 12, 24, 36 or 48 VDC Statistical MTBF >3 000

More information

ZUCCHINI MS - LOW TO MEDIUM POWER BUSBAR

ZUCCHINI MS - LOW TO MEDIUM POWER BUSBAR ZUCCHINI MS - LOW TO MEDIUM POWER BUSBAR The flexibility of the Zucchini MS range during planning and installation makes it ideal for frequently changing requirements in small to medium sized commercial

More information