1 APPLICATION OF A HIGH RESISTANCE GROUNDING (HRG) UNIT TO AN ESP WITHIN A HAZARDOUS AREA 2014 EUALF
2 INTRODUCTION When conventional attempts to eliminate electrical discharge activity in a zone 1 hazardous area associated with an earth faulted ESP failed, the system was isolated and the back-up system brought online. When the backup system failed an alternative approach to the problem was attempted. This presentation will look at the following: How the fault led to above surface electrical discharge activity How the application of a High Resistance Grounding Unit eliminated the problem 2
3 BACKGROUND Well completed as a dual ESP operated via a Variable Speed Drive (VSD) Primary ESP developed earth fault within first weeks of operation Floating neutral VSD system allowed for continued operation of faulted ESP Gauge of backup ESP connected to maintain downhole data After 16 months operation electrical discharge noticed in wellbay area during routine checks Well taken offline and investigations commenced earlier earth faulted had further degraded Three leg electrical penetrator Electrical discharge from instrument pipework 3
4 CONVENTIONAL SOLUTIONS Tree earthing checked and supplemented Equipotential bonding applied to all extraneous metalwork Backup gauge system isolated (remove alternative power sources) Backup ESP system isolated (removed circulating current paths) Voltage in offline ESP system checked Electrical discharge potential still present measurable as voltage difference between adjacent bonded metalwork 4
5 INTERIM OPERATION Primary ESP mothballed due to discharge Backup ESP brought into operation Well operated for further 22 months until backup ESP failure (suspect motor bearing failure) Opportunity to to re-use primary ESP if electrical discharge potential could be eliminated Sharp increase in amps prior to eventual failure 5
6 FURTHER INVESTIGATIONS Time Domain Reflectrometry employed to determine location of fault Information indicates low impedance earth fault located high in completion (immediately below or within tree) Repair attempted by replacing intermediate connectors but ineffective required completion to be pulled Multiple additional earth bonding jumpers attached to tree and pipework no success Fault location and severity causing capacitive charging of local earth plane Capacitive charge unable to dissipate as supply system (VSD) unearthed 6
7 ALTERNATIVE SOLUTION Fault current requires return path to prevent capacitive charging VSD not suitable for operating with earthed star point High Resistance Grounding Unit (HRGU) being evaluated to extend run life of earth faulted ESP wells Decision to employ HRGU to provide return path for fault current 7
8 HIGH RESISTANCE GROUNDING UNIT HV/LV transformer in Star/Broken Delta configuration HV star point grounded to provide earth fault current return path Open Delta secondary winding closed using high power rating resistor Current flow in primary matched (at transformer ratio) with current flow in secondary Secondary winding resistor limits primary (fault) current 8
9 9 HIGH RESISTANCE GROUNDING UNIT-BETA UNIT
10 10 HIGH RESISTANCE GROUNDING UNIT-METERS WITH GROUND FAULT
11 11 HIGH RESISTANCE GROUNDING UNIT PRODUCTION UNIT
12 INITIAL OPERATION HRGU connected in parallel with VSD output-at VSD VSD operated at low output voltage to determine fault levels HRGU instrumentation indicates earth fault impedance near zero Secondary winding resistor value altered to limit fault current to ~2 Amps VSD run up to operating voltage and frequency Electrical discharge potential voltages still present in well bay area 12
13 REVISED OPERATION Analysis of installation indicates parallel earth paths to HRGU through platform metalwork and supply cable braid Need to provide preferential path for earth fault current Low impedance path provided from close to fault site to HRGU (large diameter earth conductor following path of main conductors) Makes the Tree the New Earth Fault Location No Stray Currents thru Piping! VSD run up to operating voltage and frequency No electrical discharge potential voltages measurable in well bay area 13
14 EXTENDED RUN-LIFE Well brought back online at production rate of ~980 BOPD Well operated for further 10 days Suspect motor failed mechanically (i.e. not directly related to earth fault) Cost of HRGU purchase and installation recouped within first 3 days of additional production HRGU technology and application proven electrical discharge potential from earth faulted ESP eliminated 8.4Mbo additional production 14
15 15 ACKNOWLEDGEMENTS
Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.
8.3 Induced Voltage Purpose The purpose of this instruction is to provide awareness of Electrostatic and Electromagnetic induced voltages and the method required to reduce or eliminate it. An induced voltage
More informationMINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES
MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES White Paper Tim Wylie, Ampcontrol s Chief Technology Officer discusses the impact of Variable Speed Drives (VSDs) on earth fault limited networks.
More informationGrounding for Power Quality
Presents Grounding for Power Quality Grounding for Power Quality NEC 250.53 states that ground resistance should be less than 25 ohms. Is this true? Grounding for Power Quality No! NEC 250.53 states
More informationSpecialists in HV and MV test and diagnostics. Testing in Substations
Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies
More information12604 N New Reflection Dr Marana, AZ, FAX
12604 N New Reflection Dr Marana, AZ, 85658 520 780 9030 206 219 4205 FAX HighVoltage@Highvoltageprobes.com www.highvoltageprobes.com Bare Probe Manual October 21, 2012 1 Safety High Voltage Safety is
More informationSection 3. Test Procedures
Section 3. Information contained within this section shall be read in conjunction with all sections of this manual Non - Compliant Test Results Where acceptable results are not attained in accordance with
More informationLCM100 USER GUIDE. Line Carrier Modem INDUSTRIAL DATA COMMUNICATIONS
USER GUIDE INDUSTRIAL DATA COMMUNICATIONS LCM100 Line Carrier Modem It is essential that all instructions contained in the User Guide are followed precisely to ensure proper operation of equipment. Product
More information2 Grounding of power supply system neutral
2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the
More informationthepower to protect the power to protect i-gard LITERATURE Low and medium voltage
thepower to protect i-gard LITERATURE Low and medium voltage distribution systems Arc Flash Hazards and High Resistance Grounding Grounding of Standby and Emergency Power Systems Neutral Grounding Resistors
More informationTech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems
701880MAC0010.1177/0020294017701880 research-article2017 Contributed Paper Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems
More informationCHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT
CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT A. General In a hazardous location grounding of an electrical power system and bonding of enclosures of circuits and electrical equipment in the
More informationProduct Classroom. Introduction. Grounding Systems. TN system. Title. Grounding System Introduction. Date October, 2016.
Title Grounding System Introduction Date October, 2016 Related Products Key words All industrial automation products Grounding, Earthing, TN, TT, IT, Introduction The automation industry of today has adopted
More informationELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET
Candidate Code No. ET43 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three
More informationUpgrading Your Electrical Distribution System To Resistance Grounding
Upgrading Your Electrical Distribution System To Resistance Grounding The term grounding is commonly used in the electrical industry to mean both equipment grounding and system grounding. Equipment grounding
More informationGrounding Recommendations for On Site Power Systems
Grounding Recommendations for On Site Power Systems Revised: February 23, 2017 2017 Cummins All Rights Reserved Course Objectives Participants will be able to: Explain grounding best practices and code
More informationEarthing Guidance Notes
Central Networks Earthing Manual Section E2 Earthing Guidance Notes Version: 2 Date of Issue: September 2007 Author: Nigel Johnson Job Title: Earthing Specialist Approver: John Simpson Job Title: Head
More informationSDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01
SEC DISTRIBUTION GROUNDING STANDARD SDCS-03 Part-II Rev.01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING Rev. 01 This specification is property of SEC
More informationCourse No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION. Course Content
Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION Sr. No. Course Content 1.0 Fault Current Calculations 1.1 Introduction to per unit and percentage impedance 1.2
More informationEPG. by Chris C. Kleronomos
April 1994 EFFECTIVE EQUIPMENT GROUNDING ECOS Electronics Corporation by Chris C. Kleronomos The quality of the electrical wiring and grounding in a facility containing sensitive electronic equipment is
More informationThe InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc.
The InterNational Electrical Testing Association Journal FEATURE PROTECTION GUIDE 64S Theory, Application, and Commissioning of Generator 100 Percent Stator Ground Fault Protection Using Low Frequency
More informationGrounding and Bonding of Service Equipment
Grounding and Bonding of Service Equipment 1. Grounding means: attached to an earth ground. 2. Bonding means: physically connected to insure electrical continuity. NEC 250.4 1. Grounding: Electrical Systems
More informationThis webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB
This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays
More informationA DUMMIES GUIDE TO GROUND FAULT PROTECTION
A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding
More informationEvaluating Step and Touch Potential Risks on Earthing Systems of High Voltage Cable Systems TP, THINUS DU PLESSIS ESKOM SOUTH AFRICA HJ, HARTMUT JAGAU
Technology solutions and innovations for developing economies Evaluating Step and Touch Potential Risks on Earthing Systems of High Voltage Cable Systems TP, THINUS DU PLESSIS ESKOM SOUTH AFRICA HJ, HARTMUT
More informationAmerican Electrical Institute
American Electrical Institute Oregon Electricians Continuing Education Grounding & Bonding (Article 250) 4 Hours American Electrical Institute PO Box 31131 Spokane, WA 99223 www.aeitraining.com Article
More informationWisconsin Contractors Institute Continuing Education
IMPORTANT NOTE: You should have received an email from us with a link and password to take your final exam online. Please check your email for this link. Be sure to check your spam folder as well. If you
More informationGuideline for Creating Disconnection Points and Establishing a Not Electrically Connected Area
Guideline for Creating Disconnection Points and Establishing a Not Document Number: Authorised by: Issue Date: 29 June 2012 Previous Document: 12 February 2010 Principal Authors: J Dohmen Powerlink D Brown
More informationNumbering System for Protective Devices, Control and Indication Devices for Power Systems
Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements
More informationElectronic Pipeline Technology
Pipe and Cable Locator Pearson Holiday Detector Model EPT- 1000 Electronic Pipeline Technology Electronic Pipeline Technology 26 Palomino Drive, Richmond Hill, Ontario, Canada, L4C 0P8 Tel: (905) 918-0025
More informationAfrica Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound
Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences
More informationDesign for EMI & ESD compliance DESIGN FOR EMI & ESD COMPLIANCE
DESIGN FOR EMI & ESD COMPLIANCE All of we know the causes & impacts of EMI & ESD on our boards & also on our final product. In this article, we will discuss some useful design procedures that can be followed
More informationPOWERING SUBSEA LOADS OVER LONG DISTANCES
Space optimiced multidirve Solutions PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA TIE-BACK POWERING SUBSEA LOADS OVER LONG DISTANCES January 26, 2011 Slide 1 Presentation Overview History Typical Subsea
More informationSDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01
SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING Rev. 01 This specification is property of SEC and subject to change or modification without any notice
More informationET 51 - Electrician Theory Examination Marking Schedule
ET 51 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A marker
More informationLos A LA-UR Los Alamos National Laboratory Los Alamos, New Mexico 87545
LA-UR-98-1 Los Alamos NationalLaboratory is operated by the University of California for the United States Department of Energy under contract W-7405-ENG-36 TITLE: SUBMITTED TO: Electrical Potential Transfer
More informationTEACHER ASSESSMENT BLUEPRINT ELECTRICAL CONSTRUCTION TECHNOLOGY. Test Code: 5171 Version: 01
TEACHER ASSESSMENT BLUEPRINT ELECTRICAL CONSTRUCTION TECHNOLOGY Test Code: 5171 Version: 01 Specific Competencies and Skills Tested in this Assessment: OSHA Regulations and Electrical Safety Practices
More informationTransmission Line Signal Sampling By Don Steinbach, AE6PM
Transmission Line Signal Sampling By Don Steinbach, AE6PM When I was finalizing the mechanical layout of my remotely-operated 3-position coaxial antenna switch (Fig. 1), I wanted to include a way to bring
More informationAlternator winding pitch and power system design
Our energy working for you. TM Power topic #5981 Technical information from Cummins Power Generation Alternator winding pitch and power system design White Paper Rich Scoggins Applications Engineering
More informationLightning Strikes. Presented to the Greater Norwalk Amateur Radio Corporation Inc. February 8, 2017 Steven M. Simons W1SMS
Lightning Strikes Presented to the Greater Norwalk Amateur Radio Corporation Inc. February 8, 2017 Steven M. Simons W1SMS ARRL CT State Technical Coordinator The Power of Lightning What is a Ground? Design
More informationCONTINUING EDUC ATION
3 CONTINUING EDUC ATION FOR WISCONSIN ELECTRICIANS 2017 NEC Article 250 2 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive Suite 290 Waukesha, WI 53188 262-409-4282 www.wcitraining.com
More informationUnit 27 Three-Phase Circuits
Unit 27 Three-Phase Circuits Objectives: Discuss the differences between threephase and single-phase voltages. Discuss the characteristics of delta and wye connections. Compute voltage and current values
More informationElectromechanical Technology /Electromechanical Engineering Technology CIP Task Grid
1 Secondary Task List 100 DEMONSTRATE KNOWLEDGE OF TECHNICAL REPORTS 101 Identify components of technical reports. 102 Demonstrate knowledge of the common components of technical documents. 103 Maintain
More informationET 61 - Electrician Theory Examination Marking Schedule
ET 61 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A marker
More informationWebinar: An Effective Arc Flash Safety Program
Webinar: An Effective Arc Flash Safety Program Daleep Mohla September 10 th, 2015: 2pm ET Agenda Arc Flash Defined and Quantified NFPA 70E / CSA Z 462 - Recent Updates What is the ANSI Z10 Hierarchy of
More informationArticle 250 Grounding & Bonding
Article 250 Grounding & Bonding AMERICAN ELECTRICAL INSTITUTE N16 W23217 Stone Ridge Dr. Waukesha, WI 53188 855-780-5046 www.aeitraining.com DISCLAIMER NOTE: This course is APPROVED for continuing education
More information815-BR SERVO AMPLIFIER FOR BRUSH SERVOMOTORS
815-BR SERVO AMPLIFIER FOR BRUSH SERVOMOTORS USER GUIDE September 2004 Important Notice This document is subject to the following conditions and restrictions: This document contains proprietary information
More informationGrounding Systems and Their Implementation By: Charles Atkinson Canadian Broadcasting Corporation Toronto, Canada
Grounding Systems and Their Implementation By: Charles Atkinson Canadian Broadcasting Corporation Toronto, Canada and Philip Giddings Engineering Harmonics Toronto, Canada The original document and figures
More informationJake Leahy s Electrical Code Connection. A look at Grounding and Bonding of Electrical Services Article Florida Building Code 5 th Edition
Jake Leahy s Electrical Code Connection A look at Grounding and Bonding of Electrical Services Article 250 2014 Florida Building Code 5 th Edition Wiring Integrity. Completed wiring installations shall
More informationThree Phase Transformers
Three Phase Transformers Theory and Calculations 8/29/2016 Copyright 2016 Dan Dudley & Associates Page 1 DELTA Transformer 8/29/2016 Copyright 2016 Dan Dudley & Associates Page 2 WYE Transformer 8/29/2016
More informationWhite Paper: Electrical Ground Rules
Acromag, Incorporated 30765 S Wixom Rd, Wixom, MI 48393 USA Tel: 248-295-0880 Fax: 248-624-9234 www.acromag.com White Paper: Electrical Ground Rules Best Practices for Grounding Your Electrical Equipment
More informationDevice Interconnection
Device Interconnection An important, if less than glamorous, aspect of audio signal handling is the connection of one device to another. Of course, a primary concern is the matching of signal levels and
More informationAC Voltage- Pipeline Safety and Corrosion MEA 2015
AC Voltage- Pipeline Safety and Corrosion MEA 2015 WHAT ARE THE CONCERNS ASSOCIATED WITH AC VOLTAGES ON PIPELINES? AC concerns Induced AC Faults Lightning Capacitive coupling Safety Code Induced AC Corrosion
More informationIMP/010/011 Code of Practice for Earthing LV Networks and HV Distribution Substations
Version:- 3.0 Date of Issue:- January 2018 Page 1 of 70 IMP/010/011 Code of Practice for Earthing LV Networks and HV Distribution Substations 1. Purpose The purpose of this document is to ensure the company
More informationContents. Warranty and Disclaimer 2 Introduction 3
Contents Warranty and Disclaimer 2 Introduction 3 Physical Dimensions Board Layout 4 Usage Using the Relay board 5 Setting the start address 5 Configuration Jumper 6 Using the Relays 7 Using the DMX connectors
More informationFORTIES ESP FAILURE ANALYSIS EXPERIENCE 2014 EUALF
FORTIES ESP FAILURE ANALYSIS EXPERIENCE 2014 EUALF INTRODUCTION Dismantle Inspection and Failure Analysis (DIFA) has driven a number of key ESP improvements for Apache by properly establishing failure
More informationOverview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.
Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. HP Critical Facility Services delivered by EYP MCF What is VOLTAGE? Difference of Electric Potential
More informationModule Title: Electrical Installation II Laboratory Sheet:
Vocational Training Council Hong Kong Institute of Vocational Education Department of Engineering Module Title: Electrical Installation II Laboratory Sheet: Student name: Course / Year: Subject: Date:
More informationThe Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.
The Importance of the Neutral-Grounding Resistor Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T. Presentation Preview What is high-resistance grounding (HRG)? What is the purpose of HRG? Why
More informationRutherford Electrical Engineering Services. DPI CONFERENCE Sydney 2008 High Voltage, Data and Communications, Electronics, CCTV
Rutherford Electrical Engineering Services DPI Conference Sydney 2008 Rutherford Electrical Engineering Services Presentation Connecting High Voltage Insulation Testers Introduction Electric shock incidents
More informationABB drives. Technical guide No. 5 Bearing currents in modern AC drive systems
ABB drives Technical guide No. 5 Bearing currents in modern AC drive systems 2 Bearing currents in modern AC drive systems Technical guide No. 5 Technical guide No. 5 Bearing currents in modern AC drive
More informationPerkins Statewide Articulation Agreement. Documentation item: Secondary Competency Task List Coversheet
Perkins Statewide Articulation Agreement Documentation item: Secondary Task List Coversheet The Secondary School agrees to: A. Implement the approved PDE Program(s) of Study. B. Provide assessment of student
More informationCurrent Probes. User Manual
Current Probes User Manual ETS-Lindgren Inc. reserves the right to make changes to any product described herein in order to improve function, design, or for any other reason. Nothing contained herein shall
More informationStray Electricity. Occurs as small voltage differences between
Stray Electricity Occurs as small voltage differences between structure and the floor structure and installed equipment floor and equipment or through liquids Voltage difference - current will flow Generally
More informationPower Frequency Withstand Voltage On-site testing of 400 kv GIS
Power Frequency Withstand Voltage On-site testing of 400 kv GIS D. Anaraki Ardakani, A. Omidkhoda, M. Solati High Voltage Engineering Center ACECR Tehran, Iran Da_ardakani@yahoo.com Paper Reference Number:
More informationTechnical Guide No. 5. Bearing Currents in Modern AC Drive Systems
Technical Guide No. 5 Bearing Currents in Modern AC Drive Systems 2 Contents 1 Introduction... General... Avoiding bearing currents... 2 Generating Bearing Currents... High frequency current pulses...
More informationELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET
Candidate Code No. ET37 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three
More informationCapstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:
Phone: (818) 734-5300 Fax: (818) 734-5320 Web: www.capstoneturbine.com Technical Reference Capstone MicroTurbine Electrical Installation 410009 Rev F (October 2013) Page 1 of 31 Capstone Turbine Corporation
More informationSET Installation and Operating Instructions. Level switch for two sensors
Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: + 358 29 006 260 Fax: + 358 29 006 1260 20.2.2013 Internet: www.labkotec.fi 1/14 SET-2000 Level switch for two sensors Copyright 2013 Labkotec
More informationThe importance of partial discharge testing throughout the development and operation of power transformers
The importance of partial discharge testing throughout the development and operation of power transformers Ulrike Broniecki OMICRON Energy Solutions GmbH, Berlin Power transformers are exposed to intense
More informationElectrical Wiring: Commercial, Seventh Canadian Edition
Electrical Wiring Commercial Canadian 7th Edition Mullin SOLUTIONS MANUAL Full download at: https://testbankreal.com/download/electrical-wiring-commercialcanadian-7th-edition-mullin-solutions-manual/ Unit
More informationBroadband Current Probe Series Operation Manual
Broadband Current Probe Series Operation Manual 1 TABLE OF CONTENTS WARRANTY 3 INTRODUCTION 4 GENERAL INFORMATION 5 OPERATING INSTRUCTIONS 6 FORMULAS 7 MAINTENANCE 8 2 WARRANTY INFORMATION A.H. Systems
More informationSummary of the Impacts of Grounding on System Protection
Summary of the Impacts of Grounding on System Protection Grounding System grounding big impact on ability to detect ground faults Common ground options:» Isolated ground (ungrounded)» High impedance ground»
More informationPARALLEL MULTI-AMP KIT for 7200 Series AMPLIFIERS INSTRUCTION SHEET
2 5 0 7 W a r r e n S t r e e t, E l k h a r t, I N 4 6 5 1 6 U S A 5 7 4. 2 9 5. 9 4 9 5 w w w. A E T e c h r o n. c o m PARALLEL MULTI-AMP KIT for 7200 Series AMPLIFIERS INSTRUCTION SHEET Kit Contents:
More information2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit
Current will always try to return to its source In order for there to be current, there must be a complete circuit Current will take as many paths or circuits available to it to return to the source The
More informationContents. Warranty and Disclaimer 2
Contents Warranty and Disclaimer 2 Physical Dimensions Board Layout 3 Usage Using the PWM board 4 Setting the start address 4 Dimming LED s 5,6 Typical hookup 7 Terminator 8 Troubleshooting Ground, termination,
More informationThe SENSE and SIGNAL inputs are very high impedance and are unaffected by the (~384ohm) series resistance of the xx61p barriers.
Hazardous Area Application Note CSW and CPI. Indicator IS Barrier Applications. Ian Fellows LIMITED Introduction When the weight indicator or digitiser is not Intrinsically Safe (all current Ian Fellows
More informationGrounding and Lightning arrestors
CHAPTER - Four Grounding and Lightning arrestors 4.1. Introduction Electrical connection of neutral point of a supply system or the non current carrying part of electrical equipments to the general mass
More informationELECTRICAL POWER TRANSMISSION TRAINER
ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering
More informationBroadband Current Probe Series Operation Manual
Broadband Current Probe Series Operation Manual 1 TABLE OF CONTENTS INTRODUCTION 3 GENERAL INFORMATION 4 OPERATING INSTRUCTIONS 5 FORMULAS 6 MAINTENANCE 7 WARRANTY 8 2 INTRODUCTION CURRENT PROBE SPECIFICATIONS
More informationECP HV METERING EQUIPMENT COMMISSIONING PROCEDURE
THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Document Number: ECP 11-0515 ENGINEERING COMMISSIONING PROCEDURE ECP 11-0515 HV METERING EQUIPMENT COMMISSIONING PROCEDURE
More informationOptions to Improve the MEN System into the 21 st Century
Options to Improve the MEN System into the 21 st Century Chris Halliday Electrical Consulting and Training Pty Ltd, Gladstone NSW, Australia. Email: chris@elect.com.au Web: www.elect.com.au Abstract Network
More informationVOLTAGE AND CURRENT RELATIONS AND POWER PART1: THREE PHASE VOLTAGE AND CURRENT RELATIONSHIPS
Islamic University of Gaza Faculty of Engineering Electrical Engineering department Electric Machine Lab Eng. Omar A. Qarmout Eng. Amani S. Abu Reyala Experiment 2 THREE PHASE AC CIRCUITS: VOLTAGE AND
More informationOPERATING MANUAL SERIES R B F BRUSHLESS RACK SYSTEM
OPERATING MANUAL SERIES R B F BRUSHLESS RACK SYSTEM Version 3.0 (European version 1.3) This is a general manual describing a series of racks receiving Servo Amplifiers having output capability suitable
More informationTechnical White Paper
Technical White Paper Increased Reports of Bearing Damage in AC Motors Operating from Modern PWM VFD's Repair shops and motor manufacturers are seeing an increased number of instances where bearings and
More informationELECTRICIAN S THEORY EXAMINATION 15 November 2014 QUESTION AND ANSWER BOOKLET
Candidate Code No. ET51 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 15 November 2014 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three
More informationTransformer Protection
Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary
More informationUEE11 Electrotechnology. Training Package
UEE11 Electrotechnology Training Package UEENEEJ153A Find and rectify faults in motors and associated controls in refrigeration and air conditioning systems Learner Workbook Version 1 Training and Education
More informationGROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER
GROUNDED ELECTRICAL POWER DISTRIBUTION Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER .0 Conductors for Electrical Power Distribution For single-phase transmission of AC power or
More informationMagnetic Loop Antenna - Topbands
Magnetic Loop Antenna - Topbands Instruction Manual Thank you for purchasing this new product small Magnetic Loop Antenna Topbands. Manual contains important information. Please read all instructions carefully
More informationCable Type 100. CAI Certification Specification
Cable Type 100 CAI Certification Specification Ref: CAI-007-C / 100 / 12-2016 Confederation of Aerial Industries Ltd Communications House 41a Market Street WATFORD Herts WD18 0PN Tel: 01923 803030 Fax:
More informationSPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)
SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor
More information150Hz to 1MHz magnetic field coupling to a typical shielded cable above a ground plane configuration
150Hz to 1MHz magnetic field coupling to a typical shielded cable above a ground plane configuration D. A. Weston Lowfreqcablecoupling.doc 7-9-2005 The data and information contained within this report
More informationOPERATING MANUAL SERIES R B F 400 VAC BRUSHLESS RACK SYSTEM
OPERATING MANUAL SERIES R B F 400 VAC BRUSHLESS RACK SYSTEM Version 1.0 (European 1.0) This is a general manual describing a series of racks receiving Servo Amplifiers having output capability suitable
More informationNational Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56
1. Two Electrical Technicians are discussing markings that are required for AC wiring. Tech A says that AC conductors must be rated for 600 volts and must have their jackets and individual conductors marked
More informationTransformer Trainer. Electrical Power Systems PSL20. Learning Outcomes. Key Features. Key Specifications
Electrical Power Systems PSL2 Investigates the principles and operating characteristics of single-phase and three-phase power and distribution transformers Key Features Educational transformers with fully
More informationTable K. Input/Output Ratings & External Wiring Requirements for the Powerware /80 Rating 50/60 Hz. kva kw VOLTS VOLTS / /220
Table K. Input/ Ratings & External Wiring Requirements for the 9390-/ Units Rating 50/0 Hz Basic Unit Rating at 0.9 lagging pf load Input and Bypass Input Rectifier (0.98 min. pf) plus Recharge Current
More informationStray Voltage and Swimming Pools
Stray Voltage and Swimming Pools Marty L. Page, P.E. Southern Company malpage@southernco.com October 19 th 2009 2009 Jodie Lane National Conference for Stray Voltage Detection, Mitigation & Prevention
More informationInstallation Manual DOC R1 Date: 05/27/99. Plug-in Meter Installation Manual
Installation Manual DOC-4004-5015-R1 Date: 05/27/99 Plug-in Meter Installation Manual Document Number: Doc-4004-5015-R1 Document Release Date: 5/99 Copyright 1999 TeCom Inc. All rights reserved. No part
More informationAC/DC Power Supply Series APPLICATION NOTE
-350 + -700 AC/DC Power Supply Series APPLICATION NOTE NV350_NV700 App notes 69498 12.doc Document Number 69498 Page 1 of 17 1. INPUT... 3 AC INPUT LINE REQUIREMENTS... 3 2. DC OUTPUT... 3 OUTPUT VOLTAGES...
More informationCable Type 125. CAI Certification Specification
Cable Type 125 CAI Certification Specification Ref: CAI-008-C / 125 / 12-2016 Confederation of Aerial Industries Ltd Communications House 41a Market Street WATFORD Herts WD18 0PN Tel: 01923 803030 Fax:
More information