Module Title: Electrical Installation II Laboratory Sheet:
|
|
- Sylvia Bell
- 5 years ago
- Views:
Transcription
1 Vocational Training Council Hong Kong Institute of Vocational Education Department of Engineering Module Title: Electrical Installation II Laboratory Sheet: Student name: Course / Year: Subject: Date: Inspection & Earth Loop Impedance Test for Electrical Installation Objectives: To understand the principles and to have hands-on experience on:- Insulation Tests using a 500V Meggar Tester, Earth Loop Impedance measurement with a Phase-Earth Loop Impedance Tester, Apparatus: 500V Meggar (AVO model BM201) (x1) Phase-Earth Loop Impedance Test (Kyoritsu model 4141) (x1) 13A socket outlets (4 nos.) of correct & incorrect polarities (1 set) Components: a short run of cable with good insulation (x1) a short run of cable with defective insulation (x1) Ver Author(s) Date Remark 1.0 hcho 5-03 For Elect. Installation II Page 1 of 10
2 Part A: Background 1. Introduction Electrical installations may be categorised as being portable or fixed. Fixed electrical installation may be defined as being a low or high voltage electrical installation that is fixed to premises but does not include any electrical equipment that is supplied with electricity after passing through a socket of the installation at which the supply can be disconnected without the use of a tool. Otherwise, the electrical installation may be classified as portable. To ensure safety, all fixed electrical installation, no matter new or alteration, shall satisfy the inspection and testing procedures as set down by the Code of Practice for the Electricity (Wiring) Regulations. In particular, the testing procedures for Low Voltage (<1000 V) electrical installations are particular relevant to general fixed electrical installations. Examples of low voltage fixed electrical installations include distribution boards, lighting installations, socket outlet installations, etc. It is a statutory requirement that all fixed electrical installations, >200A industrial and >100A domestic, are to be tested regularly. Precautionary measures should be taken during testing and the method of tests should be such that no danger to persons or property can occur even if the circuit being tested is defective. The following tests, where relevant, are to be tested preferably in the sequence indicated below:- (i) continuity of ring final circuit conductors, (ii) continuity of protective conductors, including main and supplementary equipotential bonding, (iii) earth electrode resistance, (iv) insulation resistance, (v) polarity, (vi) earth fault loop impedance, (vii) functions of all protective devices, (viii) functions of all items of equipment. In the event of any test indicating failure to comply, that test and those preceding, the results of which may have been influenced by the fault indicated, should be repeated after the fault has been rectified. Among these tests, items (iv) and (vi) are studied in this experiment to highlight the key principles of the inspection and testing of electrical installations. Page 2 of 10
3 2. Insulation resistance The object of the test is to verify that the quality of the insulation is satisfactory and has not deteriorated or short circuited. There are two tests under this heading:- (i) (ii) insulation resistance (IR) between conductors and IR between conductors and earth. Before these tests are carried out, it is essential to disconnect any neons and capacitors from the circuit because they will upset the readings obtained. In addition, any control devices which contain semiconductor components must also be disconnected as they can be damaged by the test. IR between conductors For this test, all lamps have to be removed and all switches closed. The test instrument is then connected between phase and neutral (if the supply is single-phase) and the test voltage applied. The minimum acceptable value of IR is 0.5 MΩ for low voltage installations. In new and otherwise electrically healthy circuits, the reading will be higher than this value. If a zero reading is obtained, this indicates a shortcircuit. If a significant resistance reading is obtained, this might indicate, say, a lamp is left in the circuit (e.g. the filament resistance of a 100W lamp would be in the region of 600Ω). IR between conductors and earth For this test all fuses (or MCBs) should be in place, all switches closed (including the main switch if practicable) together. Again the minimum acceptable value is 1 MΩ. Figure A.1 Test for insulation-resistance to earth Page 3 of 10
4 Figure A.2 Test for insulation-resistance between conductors Table A.1 Minimum values of insulation resistance 3. Earth-fault loop impedance Earth fault loop impedance is the impedance of the earth fault-current loop starting and ending at the point of earth fault (Figure A.3). It comprises the following starting at the point of fault: (i) (ii) (iii) (iv) (v) the circuit protective conductor; the consumer s earthing terminal and earthing conductor; the earth return path (for TT system); the path through the earthed neutral point of the transformer and the transformer winding; the phase conductor from the transformer to the point of fault. Page 4 of 10
5 Figure A.3 Path for earth fault current showing the complete earth fault loop impedance The significance of earth fault loop impedance is that a fast disconnection time of the protective device means that a high fault current is required to blow the fuse or to trip the circuit breaker. In order to allow sufficient fault current to flow in order to trip the protective device, the earth fault loop impedance must have a low value. The instrument commonly used is a phase-earth loop tester which has two indicating lamps, both of which must be ON before a test is carried out. One lamp indicates that the polarity of the circuit is correct, P-N, and the other ensures that a proven earth connection is available, P-E. There is usually a recommendation that there should be at least a 20-second interval between tests. This is to allow any heat generated in the current limiting resistor to dissipate. The instrument passes a current of around 20A into the earth loop path. The reading obtained must be compared with the maximum Z s values given in the table in the COP (Table A.2). These values vary according to the type of overcurrent protective device and its current rating and whether the circuit feeds socket-outlets or fixed equipment. If it exceeds the recommended figure, the circuit must be investigated to find out the underlying reason. The reading obtained should also be compared with the reading of the previous test (if this information is available) to see whether the Z s value is on the increase, which might indicate a potential dangerous condition appearing in the circuit. For example, if the maximum Z s was 2 Ω and the test reading was 1.2 Ω on a previous test but is now 1.8 Ω, this indicates that the next would produce an unacceptable reading with the possibility that an earth fault occurring in the circuit would not produce enough fault current to operate the overcurrent protective device in either 0.4 second and 5 seconds, thus increasing the risk of electric shock to persons using the installation. Page 5 of 10
6 Tables A.2 Maximum Earth Fault Loop Impedance Page 6 of 10
7 Tables A.2 (Cont d) Maximum Earth Fault Loop Impedance Page 7 of 10
8 Part B: Procedures 1. Insulation Test Figure B.1 Connection diagram for insulation test of a cable (i) (ii) (iii) (iv) Test the operation of the 500V meggar by shorting the two terminals. Use the meggar to test the cable with the undamaged insulation and take the reading directly in ohms. Replace the cable with defective insulation and take the reading of the meggar. Repeat the insulation resistance tests with the 30A TPN switch in the laboratory. Take the reading of R-E, R-Y, Y-B, B-R and RYB-N in turns and record all results in Table B.1. No Test Items Meggar Reading (Ω) 1 Cable with perfect insulation 2 Cable with defective insulation 3 30A TPN Switch (i) R-E (ii) Y-E (iii) B-E (iv) R-N (v) Y-N (vi) B-N (vii) R-Y (viii) Y-B (ix) B-R (x) RYB-N (xi) RYB-E Table B.1 Insulation test Remarks Page 8 of 10
9 2. Earth Loop Impedance Test Four socket outlets are provided. Only one of the four is correctly wired. Figure B.2 Connection diagram for earth loop impedance test (i) (ii) The 'Phase-Earth Loop Impedance' Tester is plugged into the 13A socket outlet at the bench. Press the button. The pointer will move the give a reading directly in ohms. This is the phase-earth loop impedance. Repeat procedure (i) for the 4 nos. 13A socket outlets. If the pointer moves to give a reading, record the results. If the pointer does not move or move to give an excessive reading, also note down the observations. Justify the results recorded in Table B.2. 1st 13A S/O 2nd 13A S/O 3rd 13A S/O 4th 13A S/O P-N LED (ON/OFF) Response of the Impedance Tester P-E LED (ON/OFF) Movement of Pointer Table B.2 Earth fault loop impedance Reading (Ω) By measurement, the earth fault loop resistance = Ω Page 9 of 10
10 Part C: Discussions 1. Comment on the results recorded in Table B.1. Suggest the minimum values of the test results to be acceptable. 2. What is the potential problem if the equipment/cable fails the insulation test? 3. Does all the earth fault loop impedance measured for the functional socket outlets in Part B.2 comply with the requirement as laid down in table A.2? - End - Page 10 of 10
2394 EXAM PAPER. 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation
2394 EXAM PAPER 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation 2. There are various documents that are relevant to the Inspection and
More informationC&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations. Earth Fault Loop Impedance Tests
C&G 2395-01 Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations Earth Fault Loop Impedance Tests 1 Revision Inspections are made to verify that the installed
More informationNOTE: This paper relates to a closed book exam & therefore candidates should attempt this exam paper with no study-notes or text books.
City & Guilds Fundamental Inspection & Testing 30 Question Test Sheet (2392-10 Paper No1.) NOTE: This paper relates to a closed book exam & therefore candidates should attempt this exam paper with no study-notes
More informationNATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011
NATIONAL RULES FOR ELECTRICAL INSTALLATIONS Fourth Edition ET 101:2008 Extracts from Amendment No.1:2011 22 June 2011 Page vi: Insert after 1 st Paragraph: Section 710: Medical Locations was prepared by
More informationC&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations
C&G 2395-01 Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations Phase rotation and verification of voltage drop 1 Outcomes of this Session describe how to assess
More information7 o/c4 - To meet the requirements of BS 7671, all fault current protective devices without back-up protection on the supply side must be capable of:
1 PAPER 5 Sample Questions A- C&G 2382 17th Edition Paper A 1 o/c1 BS 7671 does not apply to a equipment of aircraft b photovoltaic systems c marinas d fairgrounds. 2 o/c1 Where protection for persons
More informationLicensed Electricians Practical Assessment (LEP)
Licensed Electricians Practical Assessment (LEP) Surname: Date: Given Names: Time: Assessment Time (includes 10 minutes reading time): At the end of this time you will be asked to stop. 4 hours Have you
More informationreturned to your distributor for attention. 14. Do not operate the function switch while the instrument is connected to a circuit.
1. This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions. KYORITSU will not accept liability for any damage or injury caused by misuse
More informationLicensed Electricians Practical Assessment (LEP)
Licensed Electricians Practical Assessment (LEP) Surname: Given Names: Date: Time: Location: Assessment Time (includes reading and preparation time): At the end of this time you will be asked to stop.
More informationET 61 - Electrician Theory Examination Marking Schedule
ET 61 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A marker
More informationET 40 - Electrician Theory Examination Marking Schedule
ET 40 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A marker
More informationET 51 - Electrician Theory Examination Marking Schedule
ET 51 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A marker
More informationChapter 6. WIRING SYSTEMS Safe Electrical Design
Chapter 6 WIRING SYSTEMS Safe Electrical Design Topic 6-3 CABLE SELECTION BASED ON CURRENT CARRYING CAPACITY REQUIREMENTS INSTALLATION CONDITIONS Current carrying capacity (CCC) is the maximum continuous
More informationLes Hampson Cert Ed FSCTE, Chairman CAI Technical Committee
Making the Bond Les Hampson Cert Ed FSCTE, Chairman CAI Technical Committee After many man hours of deliberation and consultation the Code of Practice Electrical Safety Requirements for Signal Reception
More informationProtective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection)
Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection) FIGURE 1.2 Fig.1 Earth fault loop path. Figure 1 shows the earth fault system which provides
More informationELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET
Candidate Code No. ET43 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three
More informationInstruction Manual for Digital Grounding Resistance Meter
Instruction Manual for Digital Grounding Resistance Meter Instruction Manual for Digital Grounding Resistance Meter Table of Contents I. Overview...2 II. Open-case Inspection...3 III. Safety Precautions...4
More informationCircuits and Circuit Elements
Circuits and Circuit Elements Schematic Diagrams A diagram that depicts the construction of an electrical apparatus is called a schematic diagram These diagrams use symbols to represent the bulb, battery,
More informationEAS Electrical Appliance Serviceperson Answer Schedule
EAS 1083- Electrical Appliance Serviceperson Answer Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions.
More informationInstruction Manual for Digital Grounding Resistance Meter. Table of Contents
I. Overview...2 II. Open-case Inspection...3 III. Safety Precautions...4 IV. Work Principle...7 V. Appearance Description...9 VI. Technical Characteristics 10 VII. Resistance Measurement Method..12 VIII.Battery
More informationFINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes
FINAL - ER 70 Electrician Regulations Answer Schedule Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions.
More informationpower Knowledge The Hager Guide to current thinking on the regulations, protection and control of Klik lighting circuits.
Knowledge is power The Hager Guide to current thinking on the regulations, protection and control of Klik lighting circuits. Written by: Paul Sayer Technical Standards Manager for Hager Contents 2 Conductor
More informationEASQ ELECTRICAL APPLIANCE SERVICEPERSON (QUALIFIED) MARKING SCHEDULE. SECTION 1 Marks Reference Marking notes Qu 1 A 10 MΩ (2 marks)
EASQ ELECTRICAL APPLIANCE SERVICEPERSON (QUALIFIED) MARKING SCHEDULE Notes: 1. (1mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination
More informationPortable Appliance Testers. OmegaPAT MI 2140 BetaPAT MI 2141 User Manual Ver Code No
Portable Appliance Testers OmegaPAT MI 2140 BetaPAT MI 2141 User Manual Ver. 1.2. Code No. 20 750 684 Distributor: Producer: METREL d.d. Ljubljanska 77 SI-1354 Horjul E-mail: metrel@metrel.si http://www.metrel.si
More informationCURRENT FUTURE REGULATIONS PROPOSALS
CURRENT REGULATIONS BS7671 FUTURE PROPOSALS BS7671 AFFECTS YOU. A BITESIZE LOOK at RCDs and parts of the 18th edition DPC. wylexreasons.co.uk CONTENTS. INTRODUCTION. CURRENT REGULATIONS. WHAT IT SAYS ABOUT
More informationINSTRUCTION MANUAL DIGITAL PSC-LOOP TESTER MODEL 4118A KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD.
INSTRUCTION MANUAL DIGITAL PSC-LOOP TESTER MODEL 4118A KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD. CONTENTS 1. SAFE TESTING... 1 2. PROCEDURE OF REMOVING COVER... 4 3. FEATURES... 5 3.1 Instrument Layout...
More informationGROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER
GROUNDED ELECTRICAL POWER DISTRIBUTION Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER .0 Conductors for Electrical Power Distribution For single-phase transmission of AC power or
More informationELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET
Candidate Code No. ET37 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three
More informationResidual Current Operated Circuit-Breakers (RCCBs)
Product Overview Residual Current Operated Circuit-Breakers (RCCBs) Residual current operated circuit-breakers Number of poles Rated current A Rated residual current ma MW Auxiliary contacts can be mounted
More informationSection 3. Test Procedures
Section 3. Information contained within this section shall be read in conjunction with all sections of this manual Non - Compliant Test Results Where acceptable results are not attained in accordance with
More information17TH EDITION BS TH EDITION BS7671 HOW THIS AFFECTS YOU. A BITESIZE LOOK at RCDs and parts of the 18th edition DPC. wylexreasons.co.
BS7671 BS7671 AFFECTS YOU. A BITESIZE LOOK at RCDs and parts of the 18th edition DPC. wylexreasons.co.uk CONTENTS. INTRODUCTION. CHAPTER 31. WHAT IT SAYS ABOUT DIVISION OF THE INSTALLATION. INTRODUCTION
More informationEurotestCOMBO MI 3125 / MI 3125E Short instructions Version 2.2, Code no
EurotestCOMBO MI 3125 / MI 3125E Short instructions Version 2.2, Code no. 20 751 519 Distributor: Manufacturer: METREL d.d. Ljubljanska cesta 77 1354 Horjul Slovenia web site: http://www.metrel.si e-mail:
More informationTN, TT & IT Earthing Arrangements
TN, TT & IT Earthing Arrangements In IT and TN-C networks, residual current devices are far less likely to detect an insulation fault. In a TN-C system, they would also be very vulnerable to unwanted triggering
More informationPreface...x Chapter 1 Electrical Fundamentals
Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5
More informationUnit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21
Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive
More informationInstallation Tester BENNING IT 115. Operating Manual
Installation Tester BENNING IT 115 Operating Manual Manufacturer: BENNING Elektrotechnik und Elektronik GmbH & Co. KG Münsterstraße 135-137 D - 46397 Bocholt Phone: +49 (0) 2871-93 - 0 Fax: +49 (0) 2871-93
More informationIntermediate Physics PHYS102
Intermediate Physics PHYS102 Dr Richard H. Cyburt Assistant Professor of Physics My office: 402c in the Science Building My phone: (304) 384-6006 My email: rcyburt@concord.edu My webpage: www.concord.edu/rcyburt
More informationChapter F Protection against electric shocks
Chapter F Protection against electric shocks 1 2 3 4 5 6 7 8 Contents General 1.1 Electric shock F2 1.2 Protection against electric shock F3 1.3 Direct and indirect contact F3 Protection against direct
More informationMulti-Function Installation Tester MEGGER CM500. User Guide MEGGER
Multi-Function Installation Tester MEGGER CM500 User Guide MEGGER Contents Safety Warnings 3 Initial Setup 4 General Description 6 Features, Controls and Connections 8 Operation 10 Backlight 10 Auto shut-off
More informationMEGGER CM300 MK II, CM400 MK II & CM500
MEGGER CM300 MK II, CM400 MK II & CM500 Multi-Function Installation Testers User Guide MEGGER Contents Safety Warnings 3 Initial Setup 4 General Description 6 Features, Controls and Connections 8 Operation
More informationG SAFETY WARNINGS. LT300 High current loop tester. User guide
M LT300 High current loop tester User guide G SAFETY WARNINGS Safety Warnings and Precautions must be read and understood before the instrument is used. They must be observed during use. The earth loop
More information1. general. 1.1 electric shock. 1.2 direct and indirect contact. electric shock. indirect contact. direct contact
1. general 1.1 electric shock when a current exceeding 30 ma passes through a part of a human body, the person concerned is in serious danger if the current is not interrupted in a very short time. the
More informationE X A M I N A T I O N S C O U N C I L SECONDARY EDUCATION CERTIFICATE EXAMINATION ELECTRICAL AND ELECTRONIC TECHNOLOGY TECHNICAL PROFICIENCY
TEST CODE 01317031/SBA FORM TP 2012069 JUNE 2012 C A R I B B E A N E X A M I N A T I O N S C O U N C I L SECONDARY EDUCATION CERTIFICATE EXAMINATION ELECTRICAL AND ELECTRONIC TECHNOLOGY TECHNICAL PROFICIENCY
More informationG.F.C.I. by Sam Goldwasser -- exerpts from: Sci.Electronics.Repair FAQ:
1 of 6 8/4/2007 6:52 PM This page is from the original Code Check website. To see the latest version choose "Home Page New" Code Check 1998 by Redwood Kardon Home Page New Search What is a GFCI?: G.F.C.I.
More information1. General Instructions 2 2. Safety 2 3. Lamp Starting Test Instrument LSTI 5 3
1. General Instructions 2 2. Safety 2 3. Lamp Starting Test Instrument LSTI 5 3 3.1. Components and Connections of the Front Panel (Fig. 1) 5 3.2. Connection of the Rear Panel (Fig. 2) 7 3.3. Operation
More informationFINAL - EST Electrical Service Technician Answer Schedule
FINAL - EST 2069 - Electrical Service Technician Answer Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions.
More informationInstallation Tester BENNING IT 130. Operating Manual
Installation Tester BENNING IT 130 Operating Manual Manufacturer: BENNING Elektrotechnik und Elektronik GmbH & Co. KG Münsterstraße 135-137 D - 46397 Bocholt Phone: +49 (0) 2871-93 - 0 Fax: +49 (0) 2871-93
More information, Power Industries and Communications Industry Training Board
, Power Industries and Communications Industry Training Board Suite 3 Level 22185 187 Boundary Boundary Rd Rd North Melbourne VIC 3051 Phone VIC 3051 (03) 9654 1299 Phone (03) 9654 1299 Facsimile (03)
More informationINSTRUCTION MANUAL MULTI-FUNCTION TESTER KEW 6016
INSTRUCTION MANUAL MULTI-FUNCTION TESTER KEW 6016 CONTENTS 1. Safe Testing... 1 2. Instruments Layout... 3 3. Accessories... 5 4. Features... 6 5. Specification... 8 5.1 Measurement Specification... 8
More informationForm-IV. Form of Inspection/Test Report. (Under Regulation 43)
Form-IV Form of Inspection/Test Report (Under Regulation 43) 1. Name and address of the Chartered Electrical Safety Engineer 2. Name and address of the consumer (or) Owner(or) supplier: Contact No: E-Mail:
More informationνµθωερτψυιοπασδφγηϕκλζξχϖβνµθωερτ ψυιοπασδφγηϕκλζξχϖβνµθωερτψυιοπα σδφγηϕκλζξχϖβνµθωερτψυιοπασδφγηϕκ χϖβνµθωερτψυιοπασδφγηϕκλζξχϖβνµθ
θωερτψυιοπασδφγηϕκλζξχϖβνµθωερτψ υιοπασδφγηϕκλζξχϖβνµθωερτψυιοπασδ φγηϕκλζξχϖβνµθωερτψυιοπασδφγηϕκλζ ξχϖβνµθωερτψυιοπασδφγηϕκλζξχϖβνµ Physics θωερτψυιοπασδφγηϕκλζξχϖβνµθωερτψ Current and Electricity υιοπασδφγηϕκτψυιοπασδφγηϕκλζξχϖβν
More informationECP GROUND-MOUNTED SWITCHGEAR WITH PROTECTION RELAYS COMMISSIONING PROCEDURE
ENGINEERING COMMISSIONING PROCEDURE ECP 11-0512 GROUND-MOUNTED SWITCHGEAR WITH PROTECTION RELAYS COMMISSIONING PROCEDURE Network(s): Summary: EPN, LPN, SPN This procedure details the testing and commissioning
More information2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit
Current will always try to return to its source In order for there to be current, there must be a complete circuit Current will take as many paths or circuits available to it to return to the source The
More informationSyllabus OP49 Test electrical conduction in a variety of materials, and classify each material as a conductor or insulator
Physics: 14. Current Electricity Please remember to photocopy 4 pages onto one sheet by going A3 A4 and using back to back on the photocopier Syllabus OP49 Test electrical conduction in a variety of materials,
More informationChapter F Protection against electric shocks
Chapter F Protection against electric shocks 1 2 3 4 5 6 7 8 Contents General 1.1 Electric shock F2 1.2 Protection against electric shock F3 1.3 Direct and indirect contact F3 Protection against direct
More informationER 87 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes. (1 mark) ESR 27(2) (2 marks) ESR 74A(1AA)
ER 87 Electrician Regulations Answer Schedule Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions. The
More informationECP GROUND-MOUNTED SWITCHGEAR COMMISSIONING PROCEDURE
Document Number: ECP 11-0511 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0511 GROUND-MOUNTED SWITCHGEAR COMMISSIONING PROCEDURE EPN, LPN, SPN This procedure details the testing and
More information2 Grounding of power supply system neutral
2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the
More informationEI HIGH VOLTAGE INSULATION TESTING POLICY
Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and
More informationFAQ ON EARTHING STANDARDS 16/08/2018
FAQ ON EARTHING STANDARDS 16/08/2018 This document has been updated to include changes made to substation earthing layouts that have been made necessary due to copper theft. The main changes to be aware
More informationGrounding Recommendations for On Site Power Systems
Grounding Recommendations for On Site Power Systems Revised: February 23, 2017 2017 Cummins All Rights Reserved Course Objectives Participants will be able to: Explain grounding best practices and code
More informationBusbars and lines are important elements
CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection
More informationSERVICING & METERING SERVICING AND METERING SECTION 5 SEC5:
SECTION SERVICING AND METERING SECTION 1. SERVICING.... NST IMPEDANCE TESTING.... METERING... General Requirements.... CT METERING... 8 CT Metering General Requirements... 8 Existing Installation Alterations
More informationECE 528 Understanding Power Quality
ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-316-1520 (voice) 1 Today Wiring and grounding Why it s important References Terms and
More informationItem ref: UK MTM01 DIGITAL MULTITESTER. User Manual
Item ref: 600.100UK MTM01 DIGITAL MULTITESTER User Manual Please read this manual thoroughly and ensure all contents are fully understood before using the apparatus. Warning To avoid possible electric
More informationCompany Directive STANDARD TECHNIQUE: SD5R/2. Earth Fault Loop Impedances and Phase to Neutral Loop Impedances at LV Installations
Company Directive STANDARD TECHNIQUE: SD5R/2 Earth Fault oop Impedances and Phase to Neutral oop Impedances at V Installations NOTE: The current version of this document is stored in the WPD Corporate
More informationPEN TYPE DIGITAL MULTIMETER OPERATION MANUAL T8211D
PEN TYPE DIGITAL MULTIMETER OPERATION MANUAL T8211D T8211D 1 1. SAFETY INFORMATION BE EXTREMELY CAREFUL IN THE USE OF THIS METER. Improper use of this device can result in electric shock or destroy of
More informationNOTE: Fully read and understand this manual before using this Digital Multimeter.
ASTROAI USER MANUAL AUTO RANGING DIGITAL CLAMP METER Thank you for purchasing the Auto Ranging Digital Clamp Meter from AstroAI. The AstroAI Auto Ranging Digital Clamp Meter is designed to be safely and
More informationFINAL - ET 60 - Electrician Theory Examination Marking Schedule
FINAL - ET 60 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions.
More informationNATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL WORKMANSHIP NQF LEVEL 3 NOVEMBER 2009
NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL WORKMANSHIP NQF LEVEL 3 NOVEMBER 2009 (12041013) 3 November (X-Paper) 09:00 12:00 This question paper consists of 5 pages. (12041013) -2- NC740(E)(N3)V TIME:
More informationThe future of installation testing is here. The Fluke 1650 Series Multifunction Testers
The future of installation testing is here The Fluke 50 Series Multifunction Testers Fluke 50 Series Safer, easier installation testing. The 50 Series testers verify the safety of electrical installations
More informationThank you again for choosing AstroAI, if you have any questions or concerns regarding your product, please contact us at
ASTROAI USER MANUAL DT132A 4000 Count Auto-Ranging Multimeter Thank you for purchasing the AstroAI DT132A 4000 Count Auto-Ranging Multimeter. It is a 3 ¾ digit, 3999 counts, auto-ranging digital multimeter.
More informationEPG. by Chris C. Kleronomos
April 1994 EFFECTIVE EQUIPMENT GROUNDING ECOS Electronics Corporation by Chris C. Kleronomos The quality of the electrical wiring and grounding in a facility containing sensitive electronic equipment is
More informationResidual Current Operated Circuit-Breakers (RCCBs)
Product overview Residual Current Operated C ircuit-breakers (RCCBs) Number of poles Rated fault current I n ma Rated current I n A MW Auxiliary switches can be mounted (Type A) (Type B) 5SM1and 5SM3 RCCBs
More informationINSTRUCTIONS FOR THE COMMISSIONING AND MAINTENANCE OF DIGITAL GENERATOR PROTECTION 3 I - PRINCIPLES AND APPLICATIONS 4 on 5 6 7 Figure 5 - Inverse time curve (N1) 8 9 1 0 1 1 1 2 1 3 All relays are delivered
More informationlama M:ZSO 2SA 30oM 11ov m
Sentry Technical by Honeywell www.mkelectric.co.uk Standards and approvals All Sentry RCDs are designed to fully comply with the requirements of 8S EN 61008: 1995.1EC 1008:1990 They all feature positive
More informationVCE VET Integrated Technologies
VCE VET Integrated Technologies Written examination End of year Examination specifications Overall conditions The examination will be sat at a time and date to be set annually by the Victorian Curriculum
More informationNumbering System for Protective Devices, Control and Indication Devices for Power Systems
Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements
More informationItem ref: UK MTTR01 TRUE RMS DIGITAL MULTITESTER WITH USB INTERFACE. User Manual
Item ref: 600.104UK MTTR01 TRUE RMS DIGITAL MULTITESTER WITH USB INTERFACE User Manual Please read this manual thoroughly and ensure all contents are fully understood before using the apparatus. WARNING
More informationAutomatic disconnection of lighting circuits from dimming equipment
10 Disconnection of lighting circuits Automatic disconnection of lighting circuits from dimming equipment By Mark Coles Requirements for disconnection under fault conditions Disconnection of lighting circuits
More information3B SCIENTIFIC PHYSICS
3B SCIENTIFIC PHYSICS Digital Multimeter E 1018832 Instruction sheet 12/16 SD/UD 1 probe 1a Finger guards 2 Measurement socket 10 A for current measurement in 10-A (positive) 3 Measurement socket COM (negative)
More informationUser's Guide. AC Circuit Load Tester. Model CT70
User's Guide AC Circuit Load Tester Model CT70 Introduction Congratulations on your purchase of the CT70 AC Circuit Load Tester. This device can detect circuit and wiring problems such as: Poor ground
More informationDVM645BI BENCH MULTIMETER TAFELMULTIMETER MULTIMETRE DE TABLE BANCO MULTÍMETRO TISCHMULTIMETER. User Manual. Gebruikershandleiding
BENCH MULTIMETER TAFELMULTIMETER MULTIMETRE DE TABLE BANCO MULTÍMETRO TISCHMULTIMETER User Manual Gebruikershandleiding Manuel d'utilisation Gebrauchsanleitung Introduction BENCH MULTIMETER This manual
More informationTech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems
701880MAC0010.1177/0020294017701880 research-article2017 Contributed Paper Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems
More informationFINAL - IT 30 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (2 marks) EA 2
FINAL - IT 30 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination
More informationCOOPERATIVE PATENT CLASSIFICATION
CPC H H02 COOPERATIVE PATENT CLASSIFICATION ELECTRICITY (NOTE omitted) GENERATION; CONVERSION OR DISTRIBUTION OF ELECTRIC POWER EMERGENCY PROTECTIVE CIRCUIT ARRANGEMENTS (indicating or signalling undesired
More informationM.I. Cable High Resistance Fault Locator
M.I. Cable High Resistance M.I. Cable High Resistance Cable Health and Safety at Work This product, when used in normal or prescribed applications within the parameters specified for mechanical and electrical
More informationDIGITAL MULTIMETER CONTENTS DIGITAL MULTIMETER CONTENTS
CONTENTS CONTENTS CONTENTS 1. SAFETY INFORMATION...1 1.1 Preliminary...1 1.2 Dos and don ts...2 1.3 Symbols...3 1.4 Precautions...4 2. DESCRIPTION...5 2.1 Names of parts...6 2.2 Switches, buttons and input
More informationChapter 12 Electric Circuits
Conceptual Physics/ PEP Name: Date: Chapter 12 Electric Circuits Section Review 12.1 1. List one way electric current is similar to water current and one way it is different. 2. Draw a circuit diagram
More informationElectronic Circuit Breaker with reset input ESS20-1..
Electronic Circuit Breaker with reset input ESS0-.. Description The special device ESS0-.. is a further extension of the product line electronic circuit breakers. Type ESS0-.. has a width of only. mm and
More informationSubstation Preventive Maintenance
Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS
More informationINSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT. LTD.
(INDIA) VT. LTD. Clause Requirement Test Results Remarks Verdict 5 Marking and documentation 5.1 Marking 5.1.1 General Markings shall be visible from the exterior, or be visible after removing a cover
More informationOPERATOR S INSTRUCTION MANUAL
2 OPERATOR S INSTRUCTION MANUAL CLAMP METER HOLD 20 A 200 A 2 A 600 600 LIGHT ON/OFF Digital Clamp Meter 2 20 200 A khz COM CAT.II MAX 600 CONTENTS 1. General instruction.....1 2. Description...1 2.1 Precautions
More informationECP COMPACT AND MICRO SUBSTATION COMMISSIONING PROCEDURE
Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0507 COMPACT AND MICRO SUBSTATION COMMISSIONING PROCEDURE EPN, LPN, SPN This procedure details the testing and commissioning procedures for
More informationTT W Wireless receiver Inline Switch
TT403 1000W Wireless receiver Inline Switch Product Description The TT403 is a 1000W switchable wireless receiver and can be used to control a lighting system, extractor fan or other appliance. It does
More information3B SCIENTIFIC PHYSICS
3B SCIENTIFIC PHYSICS Analogue Multimeter Escola 100 1013527 Instruction sheet 12/15 SD/JS 1 Display with mirror scale 2 Slotted screw for zero calibration 3 Calibration trimmer for setting centre zero
More informationUnit 15: Electrical Circuits and their Applications
Unit 15: Electrical Circuits and their Applications Level: 3 Unit type: Internal Guided learning hours: 60 Unit in brief This unit covers the principles of electricity, including measurements of electrical
More informationChapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5
Applied Grounding and Bonding Paul Dobrowsky Member NEC Panel 5 1 Introduction This presentation is a representative sample from the following Chapters of Applied Grounding and Bonding. Chapter 1, Introduction
More informationQUICK SETUP GUIDE SECULIFE IP
QUICK SETUP GUIDE SECULIFE IP The SECULIFE IP is capable of executing all measurements for testing the effectiveness of safety measures in electrical systems as required by IEC 60364-4 / VDE 0100-600,
More informationCHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT
CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT A. General In a hazardous location grounding of an electrical power system and bonding of enclosures of circuits and electrical equipment in the
More information