SELF DAMPING TEST ON 1020 KCMIL ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION

Size: px
Start display at page:

Download "SELF DAMPING TEST ON 1020 KCMIL ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION"

Transcription

1 To: Dave Bryant Composite Technology Corporation 2026 McGaw Avenue Irvine, CA USA SELF DAMPING TEST ON 1020 KCMIL ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION Kinectrics North America Inc. Report No.: October 15, 2004 Michael Kastelein Transmission and Distribution Technologies Department 1.0 INTRODUCTION A Self-Damping Test was performed on an Aluminum Conductor, Composite Core Trapezoidal Wires (ACCC/TW) conductor for Composite Technology Corporation (CTC). The conductor is 1020 kcmil with an outside diameter of 28.1 mm (1.108 inch). There are 24 aluminum trapezoidal wires stranded in 2 layers over a single composite fiberglass/carbon fiber core. The specification for the conductor is contained in Appendix A. A 795 kcmil, 28.1 mm (1.108 inch), Drake ACSR conductor with round wires was also tested. The testing was conducted April 20-23, 2004 by Kinectrics North America Inc. personnel at 800 Kipling Avenue, Toronto, Ontario, M8Z 6C4, Canada. Important Note: This report documents the results of Self Damping Tests performed on 1020 kcmil ACCC/TW conductor and 795 kcmil ACSR conductor. The reader should be aware that the aluminum wires are fully annealed, trapezoidallyshaped for the ACCC conductor and are hard drawn, round-shaped for the ACSR conductor. This difference has significant influence on the self-damping characteristics of the conductors. The differences are mostly a function of the shape of the aluminum wires. The core material has less influence on self-damping the conductor than the aluminum wires. The reader is cautioned that, although the results are presented together, direct comparisons should not be made and that interpretations of the self damping characteristics of each conductor should be made in the proper context. PRIVATE INFORMATION Contents of this report shall not be disclosed without authority of the client. Kinectrics North America Inc., 800 Kipling Avenue, Toronto, Ontario M8Z 6C4.

2 2.0 PURPOSE OF TEST The purpose of the Self Damping Test is to measure the power dissipation characteristics of overhead conductors. The data are used to assist in the selection of aeolian vibration dampers for the cable. 3.0 TEST SET-UP The logarithmic decay method was used to perform these tests. The method is described in IEEE Std , IEEE Std and the Transmission Line Reference Book Wind- Induced Conductor Motion, EPRI The general arrangement used for the self damping test is shown in Figure 1. The test was carried out in a temperature-controlled laboratory at 22ºC ± 2ºC. The conductor was tensioned using a cantilever weight arm at one end and a hydraulic cylinder at the other end. A load-cell was placed between the hydraulic cylinder and the deadend to measure the tension in the conductor. The hydraulic cylinder was used to set the initial tension and the weight arm maintained the tension throughout the test. The conductor length between deadend clamps was approximately 32 m (105 ft). The conductor was rigidly clamped to intermediate abutments using square-faced clamps approximately the same diameter as the conductor. The clamping arrangement minimized the loss of vibration energy from of the span. An electromagnetic shaker was positioned near one end on the test span. A function generator providing a sinusoidal output controlled the electromagnetic shaker. An accelerometer measured the freeloop vibration amplitude of the conductor at mid-span. A quick release mechanism was used to detach the conductor from the shaker with minimal disturbances. A digital acquisition system recorded the output from the accelerometer. The calibratable instruments used in the test are listed in Appendix B. 4.0 TEST PROCEDURE Data Collection The conductors were tested at 5 tensions: 15, 20, 25, 30, and 40 percent of the conductor s rated breaking strength (RTS). The conductor was tested several different frequencies. The frequencies tested were the closest test span resonance to the frequencies that are generated in the wind velocity range from km/hr ( mph). The relationship between frequency, wind velocity and conductor diameter is: f(hz) = 50 X wind velocity (km/hr) / conductor diameter (mm) The phase angle between the force signal and the accelerometer s signal was used to indicate when the conductor was at a resonant frequency. After the conductor had stabilized at the resonance for a few minutes the shaker was disconnected. The signal from the accelerometer was integrated in its amplifier so that the output of the amplifier is proportional to velocity. The velocity signal was recorded by a digital data acquisition system while the vibration of the conductor decayed. 2

3 Data Reduction The decay of the free loop velocity (Figure 2) from the test condition at the 25% RTS and Hz is shown in Figure 2. This trace is used to illustrate the response of the conductor after being released from the shaker. The trace shows the envelope of the natural decay of the sinusoidal vibrations. Other test conditions decay at longer or shorter rates. A curve is fitted through the peak values of each cycle in the decay and is used to filter out small disturbances. The resulting fitted curve for the test condition in Figure 2 is shown in Figure 3. The peak-topeak amplitude, Y, of the conductor was calculated from the peak velocity, V. where Y = 1000*V / (π f) Y = peak-to-peak amplitude (mm) V = peak free loop velocity (m/sec) f = frequency (Hz) The decay of the conductor was calculated from the equation of the fitted curve and is expressed in terms of logarithmic decrement. where: δ = 1/n ln(y o /Y n ) δ = log decrement n = number of cycles Y o = peak-to-peak amplitude (mm) Y n = peak-to-peak amplitude at n cycles after Y o (mm) The power dissipated by the conductor s self-damping is calculated by: where: P = ½ f m V o 2 δ P = power dissipated (watts per metre) f = frequency (Hz) m = mass per unit length of the conductor (kg/m) V o = peak loop velocity at amplitude Y o (m/sec) δ = log decrement The power dissipation is plotted as Power versus Normalized Amplitude where: Normalized Amplitude = Y/D where Y = average peak-to-peak amplitude between Y o and Y n = (Y o + Y n )/2 D = conductor diameter (mm) 3

4 5.0 TEST RESULTS Tables 1 to 5 show the data collected for the tests at 15, 20, 25, 30, and 40 percent RTS, respectively. Not all data are reported in the tables in order to make them a manageable size. Figures 4 to 8 show the graphs of the conductor s power dissipation characteristics at 15, 20, 25, 30, and 40 percent RTS, respectively. The self damping of this conductor at 15% and 20% was too high to tune the vibration to a natural frequency for frequencies above 20 Hz and 25Hz, respectively. Only natural frequencies that could locked-in are analyzed. The self damping data for the 795 kcmil, Drake ACSR round wire conductor are plotted in red on Figures 1,3 and 5 for 15%, 25% and 40% RTS. The ACSR round wire conductor has a lower self-damping than the ACCC/TW. Higher self-damping is a benefit of all trapezoidalshaped wire conductors compared to round wire conductors. This is true irrespective of the construction of the core of the conductor. Prepared by: Michael Kastelein Technical Specialist Transmission and Distribution Technologies Department Reviewed by: C.J. Pon Principal Engineer Transmission and Distribution Technologies Department Approved by: Dr. J. Kuffel General Manager Transmission and Distribution Technologies Department MK:JC DISCLAIMER Kinectrics North America Inc., has prepared this report in accordance with, and subject to, the terms and conditions of the contract between Kinectrics North America Inc. and Composite Technology Corporation. Kinectrics North America Inc.,

5 Table 1 Self Damping Data for CTC ACCC/TW 1020 kcmil Conductor at 15% RTS Conductor: CTC ACCC/TW, 1020 kcmil Diameter: 28.1 mm (1.108 inch) Grease: Normal Manufacturing Alum. Strands: Trapezoidal, 2 layers, 24 strands Test Span: 32 m (105 ft) Mass/Length: kgf/m (0.957 lbf/ft) Test Tension: 3048 kgf (6720 lbf) Condition: New 15% RTS Frequency Loop Length Y o V Y n n P Y/D (hz) (m) (mm) (m/s) (mm) (cycles) (mw/m) Notes: Y o = peak-to-peak amplitude (mm) V = peak free loop velocity (m/sec) Y n = peak-to-peak amplitude at n cycles after Y o (mm) P = power dissipated (mw/m) Y/D = normalized amplitude = (Y o + Y n )/2 The power dissipation characteristics for the ACCC/TW 1020 kcmil conductor at 15% RTS is plotted as Power Dissipated, P, versus Normalized Amplitude, Y/D, and is shown in Figure 4. 5

6 Table 2 Self Damping Data for CTC ACCC/TW 1020 kcmil Conductor at 20% RTS Conductor: CTC ACCC/TW, 1020 kcmil Diameter: 28.1 mm (1.108 inch) Grease: Normal Manufacturing Alum. Strands: Trapezoidal, 2 layers, 24 strands Test span: 32 m (105 ft) Mass/Length: kgf/m (0.957 lbf/ft) Test Tension: 4064 kgf (8959 lbf) Condition: New 20% RTS Frequency Loop Length Y o V Y n n P Y/D (hz) (m) (mm) (m/s) (mm) (cycles) (mw/m) Notes: Y o = peak-to-peak amplitude (mm) V = peak free loop velocity (m/sec) Y n = peak-to-peak amplitude at n cycles after Y o (mm) P = power dissipated (mw/m) Y/D = normalized amplitude = (Y o + Y n )/2 The power dissipation characteristics for the ACCC/TW 1020 kcmil conductor at 20% RTS is plotted as Power Dissipated, P, versus Normalized Amplitude, Y/D, and is shown in Figure 5. 6

7 Table 3 Self Damping Data for CTC ACCC/TW 1020 kcmil Conductor at 25% RTS Conductor: CTC ACCC/TW, 1020 kcmil Diameter: 28.1 mm (1.108 inch) Grease: Normal Manufacturing Alum. Strands: Trapezoidal, 2 layers, 24 strands Test span: 32 m (105 ft) Mass/Length: kgf/m (0.957 lbf/ft) Test Tension: 5080 kgf (11199 lbf) Condition: New 25%RTS Frequency Loop Length Y o V Y n n P Y/D (hz) (m) (mm) (m/s) (mm) (cycles) (mw/m) Notes: Y o = peak-to-peak amplitude (mm) V = peak free loop velocity (m/sec) Y n = peak-to-peak amplitude at n cycles after Y o (mm) P = power dissipated (mw/m) Y/D = normalized amplitude = (Y o + Y n )/2 The power dissipation characteristics for the ACCC/TW 1020 kcmil conductor at 25% RTS is plotted as Power Dissipated, P, versus Normalized Amplitude, Y/D, and is shown in Figure 6. 7

8 Table 4 Self Damping Data for CTC ACCC/TW 1020 kcmil Conductor at 30% RTS Conductor: CTC ACCC/TW, 1020 kcmil Diameter: 28.1 mm (1.108 inch) Grease: Normal Manufacturing Alum. Strands: Trapezoidal, 2 layers, 24 strands Test Span: 32 m (105 ft) Mass/Length: kgf/m (0.957 lbf/ft) Test Tension: 6096 kgf (13439 lbf) Condition: New 30% RTS Frequency Loop Length Yo V Yn n P Y/D (hz) (m) (mm) (m/s) (mm) (cycles) (mw/m) Notes: Y o = peak-to-peak amplitude (mm) V = peak free loop velocity (m/sec) Y n = peak-to-peak amplitude at n cycles after Y o (mm) P = power dissipated (mw/m) Y/D = normalized amplitude = (Y o + Y n )/2 The power dissipation characteristics for the ACCC/TW 1020 kcmil conductor at 30% RTS is plotted as Power Dissipated, P, versus Normalized Amplitude, Y/D, and is shown in Figure 7. 8

9 Table 5 Self Damping Data for CTC ACCC/TW 1020 kcmil Conductor at 40% RTS Conductor: CTC ACCC/TW, 1020 kcmil Diameter: 28.1 mm (1.108 inch) Grease: Normal Manufacturing Alum. Strands: Trapezoidal, 2 layers, 24 strands Test Span: 32 m (105 ft) Mass/Length: kgf/m (0.957 lbf/ft) Test Tension: 8128 kgf (17919lbf) Condition: New 40% RTS Frequency Loop Length Y o V Y n n P Y/D (hz) (m) (mm) (m/s) (mm) (cycles) (mw/m) Notes: Y o = peak-to-peak amplitude (mm) V = peak free loop velocity (m/sec) Y n = peak-to-peak amplitude at n cycles after Y o (mm) P = power dissipated (mw/m) Y/D = normalized amplitude = (Y o + Y n )/2 The power dissipation characteristics for the ACCC/TW 1020 kcmil conductor at 40% RTS is plotted as Power Dissipated, P, versus Normalized Amplitude, Y/D, and is shown in Figure 8. 9

10 Hydraulic Ram Deadend Assembly Load Cell Clamp Electromagnitic Shaker Accelerometer Clamp Cantelever Weight Arm 8 10 #REPORTNUMBER Figure 1: Set-up of Self-Damping Test

11 Velocity - m/s Time - Seconds Figure 2 Typical Decay Trace Conductor at 25% RTS, 7 Vibration Loops, Hz 0.6 Peak Velocity - m/s Time - Seconds Figure 3 Curve Fitted Through Peak Value of Vibration Cycles Conductor at 25% RTS, 7 Vibration Loops, Hz 11

12 CTC ACCC/TW 15%RTS (Red represents 795 ACSR round wire conductor) Hz Hz Hz 12 Power Dissipation - mw/m Series Normalized Amplitude - Y/D Figure 4 Power Dissipation Characteristics of CTC 1020 kcmil ACCC/TW at 15% RTS (Logarithmic Decrement Method)

13 CTC ACCC/TW 20%RTS Hz Hz Hz 13 Power Dissipation - mw/m Normalized Amplitude - Y/D Hz Figure 5 Power Dissipation Characteristics of CTC 1020 kcmil ACCC/TW at 20% RTS (Logarithmic Decrement Method)

14 CTC ACCC/TW 25%RTS (Red represents 795kcmil ACSR round wire conductor) Hz 14 Power Dissipation - mw/m Normalized Amplitude - Y/D Hz Hz Hz Hz Hz Hz Hz Figure 6 Power Dissipation Characteristics of CTC 1020 kcmil ACCC/TW at 25% RTS (Logarithmic Decrement Method)

15 CTC ACCC/TW 30%RTS Hz Hz Hz Hz 15 Power Dissipation - mw/m Normalized Amplitude - Y/D Hz Hz Hz Hz Figure 7 Power Dissipation Characteristics of CTC 1020 kcmil ACCC/TW at 30% RTS (Logarithmic Decrement Method)

16 CTC ACCC/TW 40%RTS (Red represents 795 ACSR Round Wire) Hz Hz 16 Power Dissipation - mw/m Normalized Amplitude - Y/D Hz Hz Hz Hz Hz Hz Figure 8 Power Dissipation Characteristics of CTC 1020 kcmil ACCC/TW at 40% RTS (Logarithmic Decrement Method)

17 APPENDIX A DATA SHEET FOR CTC ACCC/TW 1020 KCMIL CONDUCTOR A-1

18 Cable Design for Trapezoidally Shaped Conductor Code Name: 1020 kcmil ACCC/TW Custom Design (24 wire) Type: 14 Governing Standard ASTM or CSA ASTM Total Cross Sectional Area of cndr in² ( mm²) AAC, ACSR, or ACSS ACSS Annular Alum area kcmil Aluminum Cross-Sectional Area kcmil ( mm²) Fill factor 93.8 % Calculated Cable OD in ( mm ) Design Area Alum kcmil Diameter of a strand wire in Core Strand in ( 9.53 mm ) Actual Alum. area kcmil No. Strand(s) in Core 1 No. Al. strands 24 No. of Alum. Wire Layers 2 No. Strands in 1st Layer 9 Al. in 1st layer % No. Strands in 2nd Layer 15 Al. in 2nd layer % No. Strands in 3rd Layer 0 Al. in 3rd layer 0.00 % No. Strands in 4th Layer 0 Al. in 4th layer 0.00 % Steel - GA, MA, HS, MS or S1A or S3A or AW CTC Core Conductivity of outer aluminum (%IACS) 63.0 % ASTM B857 for overall conductor Conductivity of inner core (%IACS).0 % ASTM B609 for 1350 O temper aluminum Frequency of Operation 60 Hz CTC Composite Fiberglass/ Carbon Fiber Core Conductor Design: Diameter of Steel Core.3750 in ( 9.53 mm ) 1st Layer - number of wires = 9 Equiv. Round Wire Dia in ( 5.25 mm ) Area per strand kcmil Diameter Over Layer.7416 in ( mm ) Height "t" in 2nd Layer - number of wires = 15 Equiv. Round Wire Dia in ( 5.23 mm ) Area per strand kcmil Diameter Over Layer in ( mm ) Height "t" in 3rd Layer - number of wires = 0 Equiv. Round Wire Dia in (.00 mm ) Area per strand. kcmil Diameter Over Layer.0000 in (.00 mm ) Height "t" in 4th Layer - number of wires = 0 Equiv. Round Wire Dia in (.00 mm ) Area per strand. kcmil Diameter Over Layer.0000 in (.00 mm ) Height "t" in Mechanical Properties: Aluminum (1350) CTC Core Total Conductor Mass 957 lb/kft 1425 kg/km 86 lb/kft 128 kg/km 1043 lb/kft 1553 kg/km Conductor Area.8012 sq.in sq.mm.1104 sq.in sq.mm.9116 sq.in sq.mm Rated Strength 6540 lb 29.1 kn lb kn lb * kn Tensile Strength Basis 8500 psi psi * value rounded to nearest 100lb unit Strength Derating Factor Thermal Heat Capacity W.s/ft per F per C tbd Electrical 60 Hz Temperature dc Resistance ac Resistance ac Resistance ac Resistance 20 C ohm/kft ohm/kft ohm/mile ohm/km ( ohm/km) 25 C ohm/kft ohm/kft ohm/mile ohm/km 50 C ohm/kft ohm/kft ohm/mile ohm/km 75 C ohm/kft ohm/kft ohm/mile ohm/km 100 C ohm/kft ohm/kft ohm/mile ohm/km 125 C ohm/kft ohm/kft ohm/mile ohm/km 150 C ohm/kft ohm/kft ohm/mile ohm/km 175 C ohm/kft ohm/kft ohm/mile ohm/km 200 C ohm/kft ohm/kft ohm/mile ohm/km A-2

19 ISO-9001 Form: QF11-1 Rev 0, APPENDIX B - INSTRUMENT SHEET Test Description: Self-Damping Test Test Start Date: April 20, 2004 Project Number: K Test Finish Date: April 23, 2004 TEST DESCRIPTION EQUIPMENT DESCRIPTION MAKE MODEL ASSET # or SERIAL # ACCURACY CLAIMED CALIBRATION DATE CALIBRATION DUE DATE TEST USE B-1 Self-Damping Load cell Aries TRC % February 11, 2004 February 11, 2005 Cable Tension Data acquisition National Instruments PCI-603E CCC % September 14, 2003 September 14, 2004 Data recording Accelerometer B&K % August 24, 2003 August 24, 2004 Displacement

AEOLIAN VIBRATION TEST ON 1572 KCMIL BITTERN ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION

AEOLIAN VIBRATION TEST ON 1572 KCMIL BITTERN ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION To: Mr. Dave Bryant Composite Technology Corporation 2026 McGaw Avenue Irvine, CA 92614 USA AEOLIAN VIBRATION TEST ON 1572 KCMIL BITTERN ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION Kinectrics

More information

SEQUENTIAL MECHANICAL TESTING OF 1020 KCMIL DRAKE ACCC/TW CONDUCTOR. Kinectrics North America Inc. Report No.: K RC-0001-R00.

SEQUENTIAL MECHANICAL TESTING OF 1020 KCMIL DRAKE ACCC/TW CONDUCTOR. Kinectrics North America Inc. Report No.: K RC-0001-R00. To: Mr. Dave Bryant CTC Cable Corporation 2026 McGaw Avenue Irvine, CA 92614 USA KINECTRICS NORTH AMERICA INC. TEST REPORT FOR CTC CABLE CORPORATION SEQUENTIAL MECHANICAL TESTING OF 1020 KCMIL DRAKE ACCC/TW

More information

KINECTRICS NORTH AMERICA INC. TEST REPORT FOR 3M TO DETERMINE THE SHEAVE CRITERIA FOR 774 KCMIL 3M TM COMPOSITE CONDUCTOR

KINECTRICS NORTH AMERICA INC. TEST REPORT FOR 3M TO DETERMINE THE SHEAVE CRITERIA FOR 774 KCMIL 3M TM COMPOSITE CONDUCTOR To: Colin McCullough 3M Composite Conductor Program 3130, Lexington Ave. So. Eagan MN 55121-2239 USA KINECTRICS NORTH AMERICA INC. TEST REPORT FOR 3M TO DETERMINE THE SHEAVE CRITERIA FOR 774 KCMIL 3M TM

More information

KINECTRICS NORTH AMERICA INC. TEST REPORT FOR 3M COMPANY TO COMPARE THE LIGHTNING PERFORMANCE OF ACCR TO ACSR CONDUCTORS

KINECTRICS NORTH AMERICA INC. TEST REPORT FOR 3M COMPANY TO COMPARE THE LIGHTNING PERFORMANCE OF ACCR TO ACSR CONDUCTORS To: Colin McCullough 3M Composite Conductor Program 2465 Lexington Ave. South Mendota Heights, MN 5512 USA KINECTRICS NORTH AMERICA INC. TEST REPORT FOR 3M COMPANY TO COMPARE THE LIGHTNING PERFORMANCE

More information

Optical Ground Wire Fiber Optic Cable. Design Qualification Testing IEEE solutions. for the real world

Optical Ground Wire Fiber Optic Cable. Design Qualification Testing IEEE solutions. for the real world Design Qualification Testing Optical Ground Wire Fiber Optic Cable IEEE 1138 solutions for the real world To: AFL 150 Ridgeview Circle Duncan, SC 29334 United States KINECTRICS NORTH AMERICA INC. TEST

More information

2. CONDUCTORS. 2.1 Strand Types. 2.2 Coatings Tensile Strength of Copper Wire Copper Strand Properties. 2.5 Aluminum Strand Properties

2. CONDUCTORS. 2.1 Strand Types. 2.2 Coatings Tensile Strength of Copper Wire Copper Strand Properties. 2.5 Aluminum Strand Properties 2. CONDUCTORS 2.1 Strand Types 2.1.1 Concentric Strand 7 2.1.2 Bunch Strand 7 2.1.3 Rope Strand 8 2.1.4 Sector Conductor 8 2.1.5 Segmental Conductor 8 2.1.6 Annular Conductor 8 2.1.7 Compact Strand 8 2.1.8

More information

COPPERCLAD STEEL WIRE. Dead Soft Annealed Jacketed High Strength. Extra High Strength Composite Conductors Guy Wire

COPPERCLAD STEEL WIRE. Dead Soft Annealed Jacketed High Strength. Extra High Strength Composite Conductors Guy Wire COPPERCLAD STEEL WIRE Dead Soft Annealed Jacketed High Strength Extra High Strength Composite Conductors Guy Wire Founded in 1984, AFL is an international manufacturer providing end-to-end solutions to

More information

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 177 2012 Specification for Braided 75 Ω, Mini-Series Quad Shield Coaxial Cable for CMTS and SDI cables NOTICE

More information

Aeolian vibrations on power line conductors, evaluation of actual self damping

Aeolian vibrations on power line conductors, evaluation of actual self damping 1 Aeolian vibrations on power line conductors, evaluation of actual self damping Suzanne Guérard, Bertrand Godard, Jean-Louis Lilien, Member, IEEE Abstract-- Aeolian vibrations of power lines are induced

More information

Part 2: Second order systems: cantilever response

Part 2: Second order systems: cantilever response - cantilever response slide 1 Part 2: Second order systems: cantilever response Goals: Understand the behavior and how to characterize second order measurement systems Learn how to operate: function generator,

More information

WAVES. Chapter Fifteen MCQ I

WAVES. Chapter Fifteen MCQ I Chapter Fifteen WAVES MCQ I 15.1 Water waves produced by a motor boat sailing in water are (a) neither longitudinal nor transverse. (b) both longitudinal and transverse. (c) only longitudinal. (d) only

More information

Part I. Open Open Pipes. A 35 cm long string is played at its fundamental frequency.

Part I. Open Open Pipes. A 35 cm long string is played at its fundamental frequency. Part I Open Open Pipes A 35 cm long pipe is played at its fundamental frequency. 1. What does the waveform look like inside the pipe? 2. What is this frequency s wavelength? 3. What is this frequency being

More information

Module 7 : Design of Machine Foundations. Lecture 31 : Basics of soil dynamics [ Section 31.1: Introduction ]

Module 7 : Design of Machine Foundations. Lecture 31 : Basics of soil dynamics [ Section 31.1: Introduction ] Lecture 31 : Basics of soil dynamics [ Section 31.1: Introduction ] Objectives In this section you will learn the following Dynamic loads Degrees of freedom Lecture 31 : Basics of soil dynamics [ Section

More information

MIL-STD-202G SHOCK (SPECIFIED PULSE)

MIL-STD-202G SHOCK (SPECIFIED PULSE) SHOCK (SPECIFIED PULSE) 1. PURPOSE. This test is conducted for the purpose of determining the suitability of component parts and subassemblies of electrical and electronic components when subjected to

More information

Sensor Datasheet Collection

Sensor Datasheet Collection ISO 9001 REGISTERED Specials are Our Standard Sensor Datasheet Collection CONTENTS HR-DRO: HIGH RESOLUTION DIGITAL READOUT 3 THE RELS FAMILY: ROD-END LOAD SENSORS 4-15 S-RELS SERIES: STANDARD ROD-END LOAD

More information

sin(wt) y(t) Exciter Vibrating armature ENME599 1

sin(wt) y(t) Exciter Vibrating armature ENME599 1 ENME599 1 LAB #3: Kinematic Excitation (Forced Vibration) of a SDOF system Students must read the laboratory instruction manual prior to the lab session. The lab report must be submitted in the beginning

More information

Free vibration of cantilever beam FREE VIBRATION OF CANTILEVER BEAM PROCEDURE

Free vibration of cantilever beam FREE VIBRATION OF CANTILEVER BEAM PROCEDURE FREE VIBRATION OF CANTILEVER BEAM PROCEDURE AIM Determine the damped natural frequency, logarithmic decrement and damping ratio of a given system from the free vibration response Calculate the mass of

More information

Dynamic Vibration Absorber

Dynamic Vibration Absorber Part 1B Experimental Engineering Integrated Coursework Location: DPO Experiment A1 (Short) Dynamic Vibration Absorber Please bring your mechanics data book and your results from first year experiment 7

More information

TransPowr ACSS Bare Overhead Conductor Aluminum Conductor Steel-Supported Concentric-Lay-Stranded

TransPowr ACSS Bare Overhead Conductor Aluminum Conductor Steel-Supported Concentric-Lay-Stranded 20/7 22/7 24/7 26/7 30/7 30/19 54/7 54/19 45/7 72/7 76/19 84/19 Product Construction: Complete Conductor: ACSS is a composite concentric-lay-stranded cable. ACSS conductors are manufactured in accordance

More information

Pressure Response of a Pneumatic System

Pressure Response of a Pneumatic System Pressure Response of a Pneumatic System by Richard A., PhD rick.beier@okstate.edu Mechanical Engineering Technology Department Oklahoma State University, Stillwater Abstract This paper describes an instructive

More information

Laboratory Experiment #2 Frequency Response Measurements

Laboratory Experiment #2 Frequency Response Measurements J.B.Francis College of Engineering Mechanical Engineering Department 22-403 Laboratory Experiment #2 Frequency Response Measurements Introduction It is known from dynamic systems that a structure temporarily

More information

VIBREC500 Recorders. Advanced Recorders to Measure Conductor Motions. the power connection THE PFISTERER GROUP

VIBREC500 Recorders. Advanced Recorders to Measure Conductor Motions. the power connection THE PFISTERER GROUP Advanced Recorders to Measure Conductor Motions THE PFISTERER GROUP the power connection VIBREC500 Vibration Measurements Aeolian Vibration Aeolian vibrations of overhead line conductors and their detrimental

More information

Slack Span Dead-end. Slack Span Dead-end GENERAL RECOMMENDATIONS NOMENCLATURE 14-23

Slack Span Dead-end. Slack Span Dead-end GENERAL RECOMMENDATIONS NOMENCLATURE 14-23 NOMENCLATURE Dead-end Material Helical Leg Section: Aluminum covered steel. An aluminum alloy version is available for corrosive environment. Contact PLP. Crossover Marks: Indicates starting point for

More information

SOLVING VIBRATIONAL RESONANCE ON A LARGE SLENDER BOAT USING A TUNED MASS DAMPER. A.W. Vredeveldt, TNO, The Netherlands

SOLVING VIBRATIONAL RESONANCE ON A LARGE SLENDER BOAT USING A TUNED MASS DAMPER. A.W. Vredeveldt, TNO, The Netherlands SOLVING VIBRATIONAL RESONANCE ON A LARGE SLENDER BOAT USING A TUNED MASS DAMPER. A.W. Vredeveldt, TNO, The Netherlands SUMMARY In luxury yacht building, there is a tendency towards larger sizes, sometime

More information

Mongoose PT Platform Shale Shaker

Mongoose PT Platform Shale Shaker Mongoose PT Platform Shale Shaker (UL VERSION) Revision: A By: MT Mongoose Platform Page 1 of 10 NOTE: Mongoose PT Platform Shale Shaker The attached is a reference to M-I SWACO s STANDARD Mongoose Platform

More information

CHAPTER 6 INTRODUCTION TO SYSTEM IDENTIFICATION

CHAPTER 6 INTRODUCTION TO SYSTEM IDENTIFICATION CHAPTER 6 INTRODUCTION TO SYSTEM IDENTIFICATION Broadly speaking, system identification is the art and science of using measurements obtained from a system to characterize the system. The characterization

More information

Evaluation of Drywall Resilient Sound Isolation Clips. Dr. Peter D Antonio RPG Diffusor Systems, Inc. January 2010

Evaluation of Drywall Resilient Sound Isolation Clips. Dr. Peter D Antonio RPG Diffusor Systems, Inc. January 2010 Evaluation of Drywall Resilient Sound Isolation Clips by Dr. Peter D Antonio RPG Diffusor Systems, Inc. January 2010 TABLE OF CONTENTS 0 INTRODUCTION 1. THEORY 1.1 TRANSMISSIBILITY 1.2 Static stiffness

More information

Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors 1

Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors 1 Designation: B 258 02 Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors 1 This standard is issued under the

More information

(i) Sine sweep (ii) Sine beat (iii) Time history (iv) Continuous sine

(i) Sine sweep (ii) Sine beat (iii) Time history (iv) Continuous sine A description is given of one way to implement an earthquake test where the test severities are specified by the sine-beat method. The test is done by using a biaxial computer aided servohydraulic test

More information

TransPowr ACSR/TW Bare Overhead Conductor Trapezoidal Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded

TransPowr ACSR/TW Bare Overhead Conductor Trapezoidal Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded TransPowr Bare Overhead Conductor 18/7 20/7 21/7 22/7 36/7 36/19 38/19 39/19 64/19 Product Construction: Complete Conductor: TransPowr is a trapezoidal aluminum conductor steel-reinforced concentric-lay-stranded

More information

Figure 1: The Penobscot Narrows Bridge in Maine, U.S.A. Figure 2: Arrangement of stay cables tested

Figure 1: The Penobscot Narrows Bridge in Maine, U.S.A. Figure 2: Arrangement of stay cables tested Figure 1: The Penobscot Narrows Bridge in Maine, U.S.A. Figure 2: Arrangement of stay cables tested EXPERIMENTAL SETUP AND PROCEDURES Dynamic testing was performed in two phases. The first phase took place

More information

UNIVERSITY OF TORONTO Faculty of Arts and Science MOCK EXAMINATION PHY207H1S. Duration 3 hours NO AIDS ALLOWED

UNIVERSITY OF TORONTO Faculty of Arts and Science MOCK EXAMINATION PHY207H1S. Duration 3 hours NO AIDS ALLOWED UNIVERSITY OF TORONTO Faculty of Arts and Science MOCK EXAMINATION PHY207H1S Duration 3 hours NO AIDS ALLOWED Instructions: Please answer all questions in the examination booklet(s) provided. Completely

More information

MESP TECHNICAL SPECIFICATION FOR MURL JUMPER WIRE HARD-DRAWN COPPER 19/ mm 2

MESP TECHNICAL SPECIFICATION FOR MURL JUMPER WIRE HARD-DRAWN COPPER 19/ mm 2 Engineering Specification Electrical Networks MESP 130400-07 TECHNICAL SPECIFICATION FOR Version: 1 Issued: February 2017 Owner: Engineering Division Approved By: Andrew Russack Head of Engineering (Electrical)

More information

EXPERIMENT 2: STRAIN GAGE DYNAMIC TESTING

EXPERIMENT 2: STRAIN GAGE DYNAMIC TESTING EXPERIMENT 2: STRAIN GAGE DYNAMIC TESTING Objective: In this experiment you will use the strain gage installation from the prior lab assignment and test the cantilever beam under dynamic loading situations.

More information

POWER AMPLIFIERS 4 QUADRANTS 3x500 VA to 3x1500 VA - THREE-PHASES

POWER AMPLIFIERS 4 QUADRANTS 3x500 VA to 3x1500 VA - THREE-PHASES PERFORMANCES High accuracy High stability Fast transients High inrush current facilities Wide bandwidth Very low distortion Quadrant change without transition Very low output impedance Low noise RS232

More information

AGN 008 Vibration DESCRIPTION. Cummins Generator Technologies manufacture ac generators (alternators) to ensure compliance with BS 5000, Part 3.

AGN 008 Vibration DESCRIPTION. Cummins Generator Technologies manufacture ac generators (alternators) to ensure compliance with BS 5000, Part 3. Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 008 Vibration DESCRIPTION Cummins Generator Technologies manufacture ac generators (alternators) to ensure compliance

More information

Analysis of Head Impact Testing Apparatus

Analysis of Head Impact Testing Apparatus Wireless Head Impact Group 16 December 2010 Analysis of Head Impact Testing Apparatus The focus of this document is to quantify the differences between the design options that this group has formulated

More information

MESP TECHNICAL SPECIFICATION FOR BARE FLEXIBLE ANNEALED COPPER JUMPER WIRE 37/7/ mm 2

MESP TECHNICAL SPECIFICATION FOR BARE FLEXIBLE ANNEALED COPPER JUMPER WIRE 37/7/ mm 2 Engineering Specification Electrical Networks MESP 130400-04 TECHNICAL SPECIFICATION FOR BARE FLEXIBLE ANNEALED COPPER JUMPER WIRE 37/7/0.70 100mm 2 Version: 2 Issued: February 2016 Owner: Engineering

More information

Optimizing Performance Using Slotless Motors. Mark Holcomb, Celera Motion

Optimizing Performance Using Slotless Motors. Mark Holcomb, Celera Motion Optimizing Performance Using Slotless Motors Mark Holcomb, Celera Motion Agenda 1. How PWM drives interact with motor resistance and inductance 2. Ways to reduce motor heating 3. Locked rotor test vs.

More information

Woven Steel Wire Fence Type-47. Under the state specification for fencing, ASTM A 116 is called out.

Woven Steel Wire Fence Type-47. Under the state specification for fencing, ASTM A 116 is called out. Woven Steel Wire Fence Type-47 Under the state specification 710.02 for fencing, ASTM A 116 is called out. Go to the steel and fencing certification manual for more information about the basic properties

More information

SHOCK RESPONSE SPECTRUM SYNTHESIS VIA DAMPED SINUSOIDS Revision B

SHOCK RESPONSE SPECTRUM SYNTHESIS VIA DAMPED SINUSOIDS Revision B SHOCK RESPONSE SPECTRUM SYNTHESIS VIA DAMPED SINUSOIDS Revision B By Tom Irvine Email: tomirvine@aol.com April 5, 2012 Introduction Mechanical shock can cause electronic components to fail. Crystal oscillators

More information

Modal Excitation. D. L. Brown University of Cincinnati Structural Dynamics Research Laboratory. M. A. Peres The Modal Shop, Inc Cincinnati, OH

Modal Excitation. D. L. Brown University of Cincinnati Structural Dynamics Research Laboratory. M. A. Peres The Modal Shop, Inc Cincinnati, OH Modal Excitation D. L. Brown University of Cincinnati Structural Dynamics Research Laboratory M. A. Peres The Modal Shop, Inc Cincinnati, OH IMAC-XXVI, Modal Excitation, #356, Feb 04, 2008, Intoduction

More information

Physics 140 Winter 2014 April 21. Wave Interference and Standing Waves

Physics 140 Winter 2014 April 21. Wave Interference and Standing Waves Physics 140 Winter 2014 April 21 Wave Interference and Standing Waves 1 Questions concerning today s youtube video? 3 Reflections A sinusoidal wave is generated by shaking one end (x = L) of a fixed string

More information

Current Probes. User Manual

Current Probes. User Manual Current Probes User Manual ETS-Lindgren Inc. reserves the right to make changes to any product described herein in order to improve function, design, or for any other reason. Nothing contained herein shall

More information

THE UNDER HUNG VOICE COIL MOTOR ASSEMBLY REVISITED IN THE LARGE SIGNAL DOMAIN BY STEVE MOWRY

THE UNDER HUNG VOICE COIL MOTOR ASSEMBLY REVISITED IN THE LARGE SIGNAL DOMAIN BY STEVE MOWRY THE UNDER HUNG VOICE COIL MOTOR ASSEMBLY REVISITED IN THE LARGE SIGNAL DOMAIN BY STEVE MOWRY The under hung voice coil can be defined as a voice coil being shorter in wind height than the magnetic gap

More information

B2-314 MEASUREMENTS ON AEOLIAN VIBRATIONS ON A 3 KM FJORD CROSSING WITH FIBRE-OPTIC BRAGG GRATING SENSORS

B2-314 MEASUREMENTS ON AEOLIAN VIBRATIONS ON A 3 KM FJORD CROSSING WITH FIBRE-OPTIC BRAGG GRATING SENSORS 21, rue d'artois, F-75008 Paris http://www.cigre.org B2-314 Session 2004 CIGRÉ MEASUREMENTS ON AEOLIAN VIBRATIONS ON A 3 KM FJORD CROSSING WITH FIBRE-OPTIC BRAGG GRATING SENSORS L. BJERKAN * and O. LILLEVIK,

More information

TECHNICAL SPECIFICATION FOR. CONTACT WIRE HARD-DRAWN COPPER 161mm2

TECHNICAL SPECIFICATION FOR. CONTACT WIRE HARD-DRAWN COPPER 161mm2 Engineering Specification Electrical TECHNICAL SPECIFICATION FOR CONTACT WIRE HARD-DRAWN COPPER 161mm2 Version: 2 Issued: May 2018 Owner: Engineering Approved by: Andrew Russack, Head of Engineering Electrical

More information

Vibration Transducer Calibration System

Vibration Transducer Calibration System 1 Overview UCON is designed for calibrating sensitivity, frequency response characteristic and amplitude linearity of acceleration transducer. There are three basic operation modes for the calibration

More information

a. Determine the wavelength of the sound. b. Determine the speed of sound in the air inside the tube.

a. Determine the wavelength of the sound. b. Determine the speed of sound in the air inside the tube. 1995B6. (10 points) A hollow tube of length Q. open at both ends as shown above, is held in midair. A tuning fork with a frequency f o vibrates at one end of the tube and causes the air in the tube to

More information

Waves and Sound Practice Test 43 points total Free- response part: [27 points]

Waves and Sound Practice Test 43 points total Free- response part: [27 points] Name Waves and Sound Practice Test 43 points total Free- response part: [27 points] 1. To demonstrate standing waves, one end of a string is attached to a tuning fork with frequency 120 Hz. The other end

More information

Certificate of Accreditation

Certificate of Accreditation Certificate of Accreditation ISO/IEC 17025:1999 Certificate Number L1048 Digital Measurement Metrology Inc. 26 Automatic Road, Unit 4 Raj Sharma Brampton, Ontario L6S 5N7 Canada Is recognized by the Laboratory

More information

PRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another.

PRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another. TRANSMISSION LINES PRELIMINARIES Generators and loads are connected together through transmission lines transporting electric power from one place to another. Transmission line must, therefore, take power

More information

Electronics and Instrumentation Name ENGR-4220 Fall 1999 Section Modeling the Cantilever Beam Supplemental Info for Project 1.

Electronics and Instrumentation Name ENGR-4220 Fall 1999 Section Modeling the Cantilever Beam Supplemental Info for Project 1. Name ENGR-40 Fall 1999 Section Modeling the Cantilever Beam Supplemental Info for Project 1 The cantilever beam has a simple equation of motion. If we assume that the mass is located at the end of the

More information

Western Mining Electric Association San Antonio TX Layer vs. Disk Windings Discussion NOVEMBER 15, SPX Transformer Solutions, Inc.

Western Mining Electric Association San Antonio TX Layer vs. Disk Windings Discussion NOVEMBER 15, SPX Transformer Solutions, Inc. Western Mining Electric Association San Antonio TX NOVEMBER 15, 2012 PRESENTED BY David L. Harris, PE Customer Technical Executive SPX Transformer Solutions, Inc. Office: 262-521-0166 Cell: 262-617-3039

More information

BETA-8A American Standard Series

BETA-8A American Standard Series Specification Nominal Basket Diameter Nominal Impedance* Power Rating** Watts Music Program Resonance Usable Frequency Range*** Sensitivity Magnet Weight Gap Height Voice Coil Diameter Thiele & Small Parameters

More information

ma output signal with transmitter module. - Adjustable frequency output signal with pulse divider module

ma output signal with transmitter module. - Adjustable frequency output signal with pulse divider module / - ; 0 PSI Advantages / Benefits Wireless easy mounting and dismounting of sensor head by a Turn & Lock technique 3-wire Hall version to interface directly with PLC's (both NPN and PNP) Easy to connect:

More information

22.19 To determine the wavelength, use the fact that the speed of a wave is equal to its wavelength times its frequency

22.19 To determine the wavelength, use the fact that the speed of a wave is equal to its wavelength times its frequency hhh.schaums.22.19_22.28 22.19 To determine the wavelength, use the fact that the speed of a wave is equal to its wavelength times its frequency or speed = waveln gth frequency speed is in m/s, wavelength

More information

DEPARTMENT OF DEFENSE TEST METHOD STANDARD METHOD 213, SHOCK (SPECIFIED PULSE)

DEPARTMENT OF DEFENSE TEST METHOD STANDARD METHOD 213, SHOCK (SPECIFIED PULSE) INCH-POUND MIL-STD-202-213 18 April 2015 SUPERSEDING MIL-STD-202G w/change 2 (IN PART) 28 June 2013 (see 6.1) DEPARTMENT OF DEFENSE TEST METHOD STANDARD METHOD 213, SHOCK (SPECIFIED PULSE) AMSC N/A FSC

More information

MESP TECHNICAL SPECIFICATION FOR FLEXIBLE DROPPER WIRE TIN-BEARING COPPER 7/7/ mm 2

MESP TECHNICAL SPECIFICATION FOR FLEXIBLE DROPPER WIRE TIN-BEARING COPPER 7/7/ mm 2 Engineering Specification Electrical Networks MESP 130400-02 TECHNICAL SPECIFICATION FOR FLEXIBLE DROPPER WIRE TIN-BEARING COPPER Version: 1 Issued: November 2015 Owner: Engineering Division Approved By:

More information

Distributed Series Reactor An overview of the conductor impacts of the DSR

Distributed Series Reactor An overview of the conductor impacts of the DSR 1 Distributed Series Reactor An overview of the conductor impacts of the DSR Joseph Goldenburg, P.E. Mechanical Section Lead and Hardware Manager at NEETRAC 2 DSR Technology Overview History Table of Contents

More information

N Male Right Angle Connector Clamp/Solder Attachment For 1/2 inch Annular, 1/2 inch Flexible, PE-1/2FAC. Cable Attachment Method (Shield/Contact)

N Male Right Angle Connector Clamp/Solder Attachment For 1/2 inch Annular, 1/2 inch Flexible, PE-1/2FAC. Cable Attachment Method (Shield/Contact) N Male Right Angle Connector Clamp/Solder Attachment For 1/2 inch Annular, 1/2 inch Flexible, PE-1/2FAC TECHNICAL DATA SHEET N Male Right Angle Connector Clamp/Solder Attachment For 1/2 inch Annular, 1/2

More information

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z & ANSI/NCSL Z

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z & ANSI/NCSL Z SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z540-1-1994 & ANSI/NCSL Z540.3-2006 PCB PIEZOTRONICS INC. 3425 Walden Avenue Depew, NY 14043 David J. Dulanski Phone: 716 684 0002 ext 2617 CALIBRATION

More information

ME 365 FINAL EXAM. Monday, April 29, :30 pm-5:30 pm LILY Problem Score

ME 365 FINAL EXAM. Monday, April 29, :30 pm-5:30 pm LILY Problem Score Name: SOLUTION Section: 8:30_Chang 11:30_Meckl ME 365 FINAL EXAM Monday, April 29, 2013 3:30 pm-5:30 pm LILY 1105 Problem Score Problem Score Problem Score Problem Score Problem Score 1 5 9 13 17 2 6 10

More information

CIR (Crush & Impact Resistant) VFD Power Cable

CIR (Crush & Impact Resistant) VFD Power Cable 37-2 CIRVFD CIR (Crush & Impact Resistant) VFD Power Cable Gexol Insulated Three Conductor 2kV Rated 90 C UL Listed as Type TC-ER Power Conductors (x3) Soft annealed flexible stranded tinned copper per

More information

ELASTIC STRUCTURES WITH TUNED LIQUID COLUMN DAMPERS

ELASTIC STRUCTURES WITH TUNED LIQUID COLUMN DAMPERS ELATIC TRUCTURE WITH TUNED LIQUID COLUMN DAMPER C. Adam, A. Hruska and M. Kofler Department of Civil Engineering Vienna University of Technology, A-1040 Vienna, Austria Abstract: The influence of Tuned

More information

Conductor Splice NOMENCLATURE GENERAL RECOMMENDATIONS (440)

Conductor Splice NOMENCLATURE GENERAL RECOMMENDATIONS (440) Conductor Splice NOMENCLATURE Sub-Sets: Individual rods assembled and gritted into groups (subsets), corresponding to tabular information appearing on catalog page. Center Mark: Establishes recommended

More information

BETA-10A American Standard Series

BETA-10A American Standard Series Specification Nominal Basket Diameter Nominal Impedance* Power Rating** Watts Music Program Resonance Usable Frequency Range*** Sensitivity Magnet Weight Gap Height Voice Coil Diameter Thiele & Small Parameters

More information

TRANSMISSION FACILITIES...7

TRANSMISSION FACILITIES...7 Table of Contents 1. INTRODUCTION...4 1.1. Objective... 4 1.2. NERC FAC-008 Compliance... 4 1.3. Seminole s Normal Rating... 5 1.4. Seminole s Four-Hour Rating... 5 1.5. Seminole s Emergency Rating...

More information

Resonance Tube Lab 9

Resonance Tube Lab 9 HB 03-30-01 Resonance Tube Lab 9 1 Resonance Tube Lab 9 Equipment SWS, complete resonance tube (tube, piston assembly, speaker stand, piston stand, mike with adaptors, channel), voltage sensor, 1.5 m leads

More information

CONTENTS. Cambridge University Press Vibration of Mechanical Systems Alok Sinha Table of Contents More information

CONTENTS. Cambridge University Press Vibration of Mechanical Systems Alok Sinha Table of Contents More information CONTENTS Preface page xiii 1 Equivalent Single-Degree-of-Freedom System and Free Vibration... 1 1.1 Degrees of Freedom 3 1.2 Elements of a Vibratory System 5 1.2.1 Mass and/or Mass-Moment of Inertia 5

More information

RUS Accepted NOMENCLATURE GENERAL RECOMMENDATIONS (440) EN-CA

RUS Accepted NOMENCLATURE GENERAL RECOMMENDATIONS (440) EN-CA NOMENCLATURE RUS Accepted Crossover Marks: Indicate starting point for application. Color Code and Length: Assist in identification of conductor size, corresponding to tabular information appearing on

More information

EE 340 Transmission Lines. Spring 2012

EE 340 Transmission Lines. Spring 2012 EE 340 Transmission Lines Spring 2012 Physical Characteristics Overhead lines An overhead transmission line usually consists of three conductors or bundles of conductors containing the three phases of

More information

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length

More information

OPTIFLUX 5000 Technical Datasheet

OPTIFLUX 5000 Technical Datasheet OPTIFLUX 5000 Technical Datasheet Electromagnetic flowmeter in flanged version Exceptional long-term stability and accuracy For highly aggressive and abrasive fluids Fully vacuum-resistant with high-tech

More information

TransPowr AAC Bare Overhead Conductor All-Aluminum 1350 Conductor Concentric-Lay-Stranded

TransPowr AAC Bare Overhead Conductor All-Aluminum 1350 Conductor Concentric-Lay-Stranded 7 19 37 61 91 Product Construction: Complete Conductor: Bare all-aluminum 1350 conductors (AAC) are concentric-lay-stranded conductors, consisting of one or more layers of wire wrapped helically around

More information

CERTIFICATE OF ACCREDITATION ISO/IEC 17025:2017 ANSI/NCSL Z (R2002)

CERTIFICATE OF ACCREDITATION ISO/IEC 17025:2017 ANSI/NCSL Z (R2002) CERTIFICATE OF ACCREDITATION ANSI-ASQ National Accreditation Board 500 Montgomery Street, Suite 625, Alexandria, VA 22314, 877-344-3044 This is to certify that Kistler Instrument Corporation 75 John Glenn

More information

Cyclic tests of engineered shear walls with different bottom plate and anchor bolt washer sizes (Phase II)

Cyclic tests of engineered shear walls with different bottom plate and anchor bolt washer sizes (Phase II) Cyclic tests of engineered shear walls with different bottom plate and anchor bolt washer sizes (Phase II) Prepared by Rakesh Gupta, Associate Professor Heather Redler, Graduate Research Assistant Milo

More information

MEC751 Measurement Lab 2 Instrumented Cantilever Beam

MEC751 Measurement Lab 2 Instrumented Cantilever Beam MEC751 Measurement Lab 2 Instrumented Cantilever Beam Goal: 1. To use a cantilever beam as a precision scale for loads between 0-500 gr. Using calibration procedure determine: a) Sensitivity (mv/gr) b)

More information

An Introduction to the CSCT as a New Device to Compensate Reactive Power in Electrical Networks

An Introduction to the CSCT as a New Device to Compensate Reactive Power in Electrical Networks An Introduction to the CSCT as a New Device to Compensate Reactive Power in Electrical Networks Mohammad Tavakoli Bina, G.N.Alexandrov and Mohammad Golkhah Abstract A new shunt reactive power compensator,

More information

MESP TECHNICAL SPECIFICATION FOR CATENARY WIRE HARD-DRAWN COPPER 37/ mm 2

MESP TECHNICAL SPECIFICATION FOR CATENARY WIRE HARD-DRAWN COPPER 37/ mm 2 Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR CATENARY WIRE HARD-DRAWN COPPER 37/2.5 181mm 2 Version: 3 Issued: February 2017 Owner: Engineering Division Approved By: Andrew

More information

Conductor Splice NOMENCLATURE GENERAL RECOMMENDATIONS (440) EN-CA

Conductor Splice NOMENCLATURE GENERAL RECOMMENDATIONS (440) EN-CA NOMENCLATURE Sub-Sets: Individual rods assembled and gritted into groups (subsets), corresponding to tabular information appearing on catalog page. Center Mark: Establishes recommended alignment of rods

More information

DELTA PRO-8B Professional Series

DELTA PRO-8B Professional Series Specification Nominal Basket Diameter Nominal Impedance* Power Rating** Watts Music Program Resonance Usable Frequency Range*** Sensitivity Magnet Weight Gap Height Voice Coil Diameter Thiele & Small Parameters

More information

Rejuvenate An Old Tinius Olsen Machine with Computer Data Acquisition Using Its Existing Hardware and LabVIEW

Rejuvenate An Old Tinius Olsen Machine with Computer Data Acquisition Using Its Existing Hardware and LabVIEW Rejuvenate An Old Tinius Olsen Machine with Computer Data Acquisition Using Its Existing Hardware and LabVIEW Jiaxin Zhao Indiana University Purdue University Fort Wayne Abstract Computer data acquisition

More information

CORFLEX VFD CORFLEX VFD Part Number: Drive Cable

CORFLEX VFD CORFLEX VFD Part Number: Drive Cable Part Number: Drive Cable Armored Variable Frequency Drive Cable UL Type MC HL, 600V, 90 C rated - LEAD FREE Description 3 conductor with 3 ground wires, continuous corrugated and welded, impervious aluminum

More information

DISCUSSION OF FUNDAMENTALS

DISCUSSION OF FUNDAMENTALS Unit 4 AC s UNIT OBJECTIVE After completing this unit, you will be able to demonstrate and explain the operation of ac induction motors using the Squirrel-Cage module and the Capacitor-Start Motor module.

More information

Type THAS,ThinPack, Aluminum Electrolytic Capacitor, 105 ºC

Type THAS,ThinPack, Aluminum Electrolytic Capacitor, 105 ºC High Energy Density, REACH and RoHS Compliant At 9 mm thin, type THAS Thinpack offers the highest energy density available in a low profile aluminum electrolytic. It s ideal for the lowest profile circuits

More information

Oscillations. Waves. Sound. Stationary waves. Acoustics of Buildings

Oscillations. Waves. Sound. Stationary waves. Acoustics of Buildings Oscillations Waves & Sound Oscillations Waves Sound Stationary waves Acoustics of Buildings 01. The maximum velocity of a body in S.H.M.is 0.25m/s and maximum acceleration is 0.75m/s 2, the period of S.H.M.

More information

EIA STANDARD TP-27B. Mechanical Shock (Specified Pulse) Test Procedure for Electrical Connectors EIA B ELECTRONIC INDUSTRIES ASSOCIATION

EIA STANDARD TP-27B. Mechanical Shock (Specified Pulse) Test Procedure for Electrical Connectors EIA B ELECTRONIC INDUSTRIES ASSOCIATION ANSI/-1996 Approved: April 17, 1996 EIA STANDARD TP-27B Mechanical Shock (Specified Pulse) Test Procedure for Electrical Connectors (Revision of EIA-364-27A) MAY 1996 ELECTRONIC INDUSTRIES ASSOCIATION

More information

UNIVERSITY OF THESSALY

UNIVERSITY OF THESSALY UNIVERSITY OF THESSALY MECHANICAL ENGINEERING DEPARTMENT Instructor: Dr. S.D. Chouliara e-mail: schoul@uth.gr MACHINE ELEMENTS Task 2 1. Let the bolt in the following Figure be made from cold-drawn steel.

More information

System Inputs, Physical Modeling, and Time & Frequency Domains

System Inputs, Physical Modeling, and Time & Frequency Domains System Inputs, Physical Modeling, and Time & Frequency Domains There are three topics that require more discussion at this point of our study. They are: Classification of System Inputs, Physical Modeling,

More information

Scope of Accreditation For Southwest Metrology, Inc. Calibration

Scope of Accreditation For Southwest Metrology, Inc. Calibration Scope of Accreditation For Southwest Metrology, Inc. 7045 N Camino Martin Tucson, AZ 85741 Dan Beard 520-744-8510 In recognition of a successful assessment to ISO/IEC 17025:2005 and ANSI/NCSL Z540-1: 1994

More information

Experiment 2: Transients and Oscillations in RLC Circuits

Experiment 2: Transients and Oscillations in RLC Circuits Experiment 2: Transients and Oscillations in RLC Circuits Will Chemelewski Partner: Brian Enders TA: Nielsen See laboratory book #1 pages 5-7, data taken September 1, 2009 September 7, 2009 Abstract Transient

More information

C400-NMTM-1M. Jumper Assembly Sample Label. Product Classification. General Specifications. Return Loss/VSWR

C400-NMTM-1M. Jumper Assembly Sample Label. Product Classification. General Specifications. Return Loss/VSWR C400-NMTM-1M Product Classification Brand Product Series Product Type CNT-400 CNT Jumper with interface types N Male and TNC Male, 1m CNT CNT-400 Braided cable assembly General Specifications Body Style,

More information

Distribution Tie. Distribution Tie NOMENCLATURE GENERAL RECOMMENDATIONS (440)

Distribution Tie. Distribution Tie NOMENCLATURE GENERAL RECOMMENDATIONS (440) Distribution (Overhead): Section 13 NOMENCLATURE Distribution Tie Tie Tube: Each tie is furnished with Tie Tube Component. The Tie Tube is detached and applied over the conductor. Tape: Shows catalog number,

More information

Lab E2: B-field of a Solenoid. In the case that the B-field is uniform and perpendicular to the area, (1) reduces to

Lab E2: B-field of a Solenoid. In the case that the B-field is uniform and perpendicular to the area, (1) reduces to E2.1 Lab E2: B-field of a Solenoid In this lab, we will explore the magnetic field created by a solenoid. First, we must review some basic electromagnetic theory. The magnetic flux over some area A is

More information

VIBRATIONAL TESTING OF A FULL-SCALE PILE GROUP IN SOFT CLAY

VIBRATIONAL TESTING OF A FULL-SCALE PILE GROUP IN SOFT CLAY VIBRATIONAL TESTING OF A FULL-SCALE PILE GROUP IN SOFT CLAY Marvin W HALLING 1, Kevin C WOMACK 2, Ikhsan MUHAMMAD 3 And Kyle M ROLLINS 4 SUMMARY A 3 x 3 pile group and pile cap were constructed in a soft

More information

Power Sensors Ltd. PQube 3 AC Analyzer IEC Class 0,2 S Accuracy Compliance Report

Power Sensors Ltd. PQube 3 AC Analyzer IEC Class 0,2 S Accuracy Compliance Report PSL Standards Lab 980 Atlantic Avenue Alameda, CA 94501 USA TEL ++1-510-522-4400 FAX ++1-510-522-4455 www.standards.com Sensors Ltd. PQube 3 AC Analyzer IEC Class 0,2 S Accuracy Compliance Report IEC 62053-22

More information

WATERFLUX 3000 Quick Start

WATERFLUX 3000 Quick Start WATERFLUX 3000 Quick Start Electromagnetic flow sensor The documentation is only complete when used in combination with the relevant documentation for the signal converter. KROHNE CONTENTS WATERFLUX 3000

More information

TransPowr AAC Bare Overhead Conductor All-Aluminum 1350 Conductor Concentric-Lay-Stranded

TransPowr AAC Bare Overhead Conductor All-Aluminum 1350 Conductor Concentric-Lay-Stranded Electric Utility TransPowr AAC Bare Overhead Conductor All-Aluminum 1350 Conductor Concentric-Lay-Stranded Overhead Conductors 7 19 37 61 91 Product Construction: Complete Conductor: Bare all-aluminum

More information

Generator Advanced Concepts

Generator Advanced Concepts Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves

More information