UL Selector and Submittal Generator User Guide

Size: px
Start display at page:

Download "UL Selector and Submittal Generator User Guide"

Transcription

1 UL Selector and Submittal Generator User Guide 1

2 UL Selector and Submittal Generator User Guide The new Hilti UL System Selector and Firestop Submittal Generator tool is available on Hilti Online in the Technical Library. This new tool will allow our customers to quickly identify the appropriate firestop systems and directly include them into a submittal. The advanced list of filters allows the user to search beyond the typical search criteria and address secondary attributes that differentiate Hilti s product performance. Smoke, sound, water, and movement characteristics are now growing concerns in the construction industry and we have the tools to help supply the customer the proper solution. Step 1 Step 2 Search by known UL System Number or Search by application criteria Create a submittal with selected UL Systems 2

3 UL Selector and Submittal Generator User Guide Section Description Page 1.0 Finding the UL System Selector on HOL Searching for Systems Searching by a Known System Number Searching by Application Criteria Understanding the Filters Understanding the Logos Creating a Submittal Saving and Recalling Submittals Frequently Asked Questions 25 3

4 Finding the UL System Selector on HOL Go to and click on the Technical Library button. Click on the Firestop system details tab. 4

5 Finding the UL System Selector on HOL The page will appear with the following: 1 1. The search box 2. The filter list 3. The systems list 3 2 5

6 Searching for Systems While searching for systems, all matches will appear in the systems list. Each system listing includes details for the system as well as a Download document button which will open the Full UL Detail PDF version of the system. 6

7 Searching for Systems For more system details and downloading options, click the More info button. In the expanded window, more details are shown as well as links to download the alternate Trade Detail Drawings and AutoCAD Drawing Files. 7

8 Searching by a Known System Number Enter the UL system number in the search box and click on the magnifying glass. The system will recognize the following formats; C-AJ-1226, CAJ1226, or CAJ If you enter only a portion of the system s name the program will populate all systems that start with that name Example: WL1 populates WL1054, WL1056, WL1058 FA5 populates FA5009, FA5015, FA5016 The matching system(s) will appear in the UL System pane. 8

9 Searching by Application Criteria Select either the Joint or Penetration option to view all of the filters associated with that system type. 9

10 Searching by Application Criteria To view the options for a filter, click on the filter name. In the drop down list, click on a filter option to activate it. Only the systems that match the option selected will appear. 10

11 Searching by Application Criteria When a filter is activated, the option that is selected will replace the filter name in the filter list. To remove a filter or to change filter options, select the option and click on the original filter name at the top of the drop down list. 11

12 Searching by Application Criteria Options that appear grey have all matching systems filtered out by an active filter. Remove the previous filter to reactivate the options. To clear all active filters, click Deselect all. 12

13 Understanding the Filters Term Website Filter Effect Definition F-Rating Barrier Type Product Application Method Air Leakage Rating STC Rating Mold and Mildew Resistance Seismic Performance Trade Displays systems that match or exceed the selected F-Rating. For example, if 2 Hour is selected, 3 Hour and 4 Hour systems that also match the requirements will be displayed. Displays only the systems that include the selected barrier type. Displays only the systems that include the selected product. Displays only the systems that include the selected application method. Displays systems that match or exceed the selected air leakage rating. Displays only the systems that include the selected STC Rating. Displays systems that are best suited to resist mold and mildew. Displays systems that perform well in seismic conditions. Displays only the systems that are typically used by the selected trade. The time a firestop system prevents the passage of flame through an opening and successfully passes the hose stream test as determined by ASTM E-814 and UL A continuous membrane, either vertical or horizontal, such as a wall or floor assembly that is designed and constructed with a specified fire resistance rating to limit the spread of fire and restrict the movement of smoke. A material or device designed to confine or limit the spread of fire and toxic gases. A firestop material, such as sealant, putty, device, etc. An optional measurement of the rate of air leakage through test samples resulting from a specified air pressure difference applied across the surface of the test samples. Sound Transmission Class an established way to determine how well a building partition attenuates airborne sound. Determined by ASTM E 90. The ability of a product to protect itself against mold and mildew as determined by ASTM G 21. If not protected against mold, the product can potentially lose its ability to protect an assembly against the spread of fire and toxic gases. The ability of a product to perform under seismic conditions by resisting dynamic movement and cycle fatigue. Predetermined list of UL systems that best match typical applications relating to the mechanical, electrical, plumbing, telecom, drywall, curtain wall and carpenter trades 13

14 Understanding the Filters - Penetration Term Website Filter Effect Definition Penetrating Item Minimum Annular Space Maximum Annular Space Displays only the systems that include penetrating items. Displays systems that match the selected minimum annular space. Displays systems that match the selected maximum annular space. Any item passing completely through a wall or floor, such as pipes, conduits, cables, etc. The region, measured in a straight line, between the penetrants, or between the outer most portion of the penetrants and the inside periphery of a circular opening or the sides of a rectangular opening. Example: a pipe with an outside diameter of 4.5 centered in a 6 diameter hole has an annular space of (6 4.5) / 2 = 3/4. See Minimum Annular Space above. Sleeve Insulation Type Maximum Percent Fill T-Rating Water Rating Displays only the systems that include the selected sleeve option. Displays only the systems that include the selected insulation type. Displays systems that match the selected maximum percent fill. Displays only the systems that include the selected T-Rating. Displays only the systems that include the selected water rating. Metal insert that lines the inner periphery of a penetration. Thermal or acoustic insulating material surrounding a pipe. The cross-sectional area of an opening that is occupied by a penetrating item(s). Typically found in UL systems containing cables. Percent fill may be calculated with the following formulas: Percent Fill (% f ) = (A w / A o ) x 100 N = number of wires Area of Wire (A w ) = [3.14 x (r c2 )] x N r c = radius of wire Area of opening (A o ) = 3.14 x (r o2 ) r o = radius of opening The time for the temperature of the unexposed surface of the firestop system or any penetrating item to rise 325 F above its initial temperature as determined by ASTM E-814 and UL An optional rating for through penetrations firestop systems. Determines the effectiveness of a firestop system to restrict the flow of water. Class 1 rated firestops have been shown to resist up to 3 feet of water column for 72 hours. 14

15 Understanding the Filters - Joint Term Website Filter Effect Definition Joint Type Maximum Joint Width Curtain Wall Type Movement Capability Displays only the systems that include the selected joint type. Displays systems that match the selected maximum joint width. Displays only the systems that include the selected curtain wall type. Displays systems that match the selected movement capability. A joint system is a specific construction consisting of adjacent wall and/or floor assemblies and the materials designed to help prevent the spread of fire through a linear opening between the wall and/or floor. The maximum joint width allowed as measured at time of installation. Non structural outer walls of a building that do not carry any dead load weight from the building. The ability of a firestop joint system to provide movement. Usually provided as a percentage of the maximum joint width at time of installation. 15

16 Understanding the Logos Moisture Proper Installation Movement Smoke Sound Hilti firestop products have the ability to withstand the effects of water and moisture not only in the completed, occupied building, but also during the construction phase. UL Systems that contain the water icon are Class 1 W-rated firestops that have been shown to resist up to 3 feet of water column for 72 hours. In addition, Hilti products are also mold and mildew resistant and have been tested per ASTM G21. All firestop products must be installed as shown on the UL system to ensure the product behaves as expected in a fire. Many of Hilti s innovative products have been specially designed to ease the installation process for the Contractor. These innovations provide both productivity gains for the Contractor and peace of mind that the installation has been done right. Products that contain the easy to install icon bring additional benefits in the installation process. These products include the CP 653 Speed Sleeve, CP 680 Cast-in Firestop Device, CFS-DID Firestop Drop-in Device, and CFS-BL Firestop Block. Construction joints and the service components (i.e. pipes, ducts, etc.) inside of a building can move or shift over time. This movement can be a result of temperature fluctuations, wind loads, vibration or earthquakes, etc. Hilti has many UL Systems for construction joints that allow for movement. The movement capabilities for Hilti firestop joint systems can be easily accessed by referencing the Movement Capability field after clicking the More info link. Additionally, Hilti has tested our through penetration firestop products to understand how they perform after a seismic event (i.e. after pipe movement has occurred). Products that contain the movement icon have shown the best performance in the simulated seismic firestop tests conducted in the Hilti research laboratory. The quasi-static cyclic loads according to the FEMA 461 protocol were applied directly to the penetrant. The tests revealed that the Hilti pre-formed devices such as the CP 653 Speed Sleeve, CP 680 Cast-in Firestop Device, CFS-DID Firestop Drop-in Device, and CFS-BL Firestop Block maintained their firestopping performance in these conditions. The smoke and gas tightness of firestop products is of utmost importance in the event of fire as it may save lives. Additionally, products designed to impede the passage of air also plays an important role in the thermal insulation of buildings and the prevention of infectious disease in critical buildings such as hospitals. UL Systems that contain the air tightness icon have undergone the optional testing to measure the rate of air leakage through the assembly. This measurement is shown as a L-rating on the UL system and is typically measured as volumetric flow rate in units of cfm/sq. ft. (or cfm/device) for through penetrations and cfm/lin. ft. for joints. Sound insulation in buildings are of great significance to the health and well-being of the occupants. Specific regulations exist for certain buildings such as schools, hotels, and offices. Many Hilti firestop products have been tested and have a sound transmission class rating (STC rating). Products that contain the sound icon help reduce the passage of sound through the application and have a STC rating available. 16

17 Creating a Submittal To add systems to a submittal, click the box next to the system name. Once all of the desired systems have been added, click on the Go to Submittal Generator button. 17

18 Creating a Submittal In the first section of the submittal generator, all of the selected systems appear. Next to each system, there are boxes that can be used to remove systems from the submittal. 18

19 Creating a Submittal Clicking the Add Systems button will save the currently selected systems and return to the UL Selector. The second section contains the products listed in the selected systems. Next to each product, there are boxes that can be used to remove the products documents from the submittal. 19

20 Creating a Submittal The third section contains the submittal s general options for the cover page and page numbers. The Hilti Cover Page option can be used to add a form which is filled in with submittal-specific information or a custom cover page can be uploaded. 20

21 Creating a Submittal The Include Page Numbers option will determine if page numbers are placed at the bottom of all the documents in the submittal. To complete a submittal, click on either the Generate Submittal button to create a PDF of the submittal or the Save as favorite button to save the submittal. 21

22 Saving and Recalling Submittals In order to save a submittal, you must first be logged into your account. After clicking the Save as favorite button, enter the submittal name and click Save as favorite. 22

23 Saving and Recalling Submittals Submittals can then be accessed from the Favorites lists in My Account by clicking on My submittals. From here, saved submittals can be reopened by clicking on the submittal name. 23

24 Saving and Recalling Submittals This will return to the Submittal Generator page where adjustments can be made to the submittal. Other options available from the My submittals page are renaming the submittal, deleting the submittal, or creating the submittal PDF using the same settings. 24

25 Frequently Asked Questions Q: How do I a submittal once it is created? A: To a submittal, create and save it as a PDF file. The PDF can then be attached to an . Q: How do I create a product based submittal without including the UL systems? A: To create a submittal that includes only products, use the general Submittal Generator at Using this application, submittals can be built for firestop, anchor systems, and direct fastening Hilti products. Q: How do I load additional documents into the submittal (like an Engineering Judgment form)? A: To load additional documents, create and save the submittal as a PDF. Next, using Adobe Acrobat, you are able to insert the additional pages. Q: How do I create a submittal using the Trade version of the system instead of the Full UL detail version? A: To change the Full UL details versions with Trade versions, create and save the submittal using the Full UL detail versions as a PDF. Next, download each system s Trade version form the UL Selector page. Then, using Adobe Acrobat, you are able to replace the Full UL detail version pages with the Trade versions. 25

26 Frequently Asked Questions Q: To save submittals, do I use my login information from the old submittal generator? A: No, the new submittal generator is part of the Hilti Online website. This means you will just have to login into your Hilti Online account in order to save and recall submittals. Q: Are my saved submittals on the old submittal generator transferred to the new one? A: Unfortunately, the old submittals cannot be transferred to the new system. However, the new Trade filter has pre-packaged groups of typical UL systems for common trades. 26

Sam Keung Regional Manager (BU Fire Protection), Hilti Corporation February, 2018 Sydney

Sam Keung Regional Manager (BU Fire Protection), Hilti Corporation February, 2018 Sydney FIRESTOPPING & SMOKE SEAL FOR CURTAIN WALL Sam Keung Regional Manager (BU Fire Protection), Hilti Corporation February, 2018 Sydney POOR FIRE PROTECTION MEASURES RESULTED IN FIRE ON THE 21 ST FLOOR TO

More information

SECTION WIREWAYS FOR RADIOLOGY EQUIPMENT

SECTION WIREWAYS FOR RADIOLOGY EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 36 WIREWAYS FOR RADIOLOGY EQUIPMENT SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable

More information

Ductwork Controls and Instrumentation Outlets (HVAC) HVAC Control System.

Ductwork Controls and Instrumentation Outlets (HVAC) HVAC Control System. SECTION 15910 DUCT ACCESSORIES PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15890 - Ductwork. 2. 15900 - Controls and Instrumentation. 3. 15940 - Outlets (HVAC). 4. 15970 - HVAC Control System.

More information

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700 SECTION 23 3113 - LOW PRESSURE DUCTWORK PART 1 - GENERAL 1.1 SCOPE OF WORK: A. The work required under this section includes all work necessary for a complete installation of ductwork and accessories.

More information

CUTTING, NOTCHING, AND BORING OF WOOD FRAMING MEMBERS (Unless an alternate design is provided by a licensed Engineer or Architect)

CUTTING, NOTCHING, AND BORING OF WOOD FRAMING MEMBERS (Unless an alternate design is provided by a licensed Engineer or Architect) INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: 91.2320 Effective: 5-23-00 DOCUMENT NO. P/BC 2002-007 Revised: 2-01-01 Previously Issued As: IB ST-14 CUTTING, NOTCHING, AND BORING OF WOOD

More information

A. Radius elbows with a construction radius of 1.5 the duct width are preferred to square elbows.

A. Radius elbows with a construction radius of 1.5 the duct width are preferred to square elbows. SECTION 233100 DUCTWORK 1.0 Acoustical duct lining in any part of the duct system is prohibited. All ductwork requiring insulation shall be externally insulated (Refer to the Sheet Metal Ductwork Insulation

More information

SECTION LOW PRESSURE DUCTWORK

SECTION LOW PRESSURE DUCTWORK SECTION 15841 LOW PRESSURE DUCTWORK PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 07270 - Firestopping and Fire and Smoke Barrier Caulking. 2. 15260 - Vibration Isolation. 3. 15280 - Thermal Insulation

More information

SECTION PANELBOARDS

SECTION PANELBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section

More information

FS 5800 EXPANSION JOINT EJ FIRE BARRIER* Installation Instructions

FS 5800 EXPANSION JOINT EJ FIRE BARRIER* Installation Instructions Thermal Structures Inc. FS 5800 EXPANSION JOINT EJ FIRE BARRIER* Installation Instructions Attached Flange & Double Barrier System FLOOR TO FLOOR (F) ROOF TO ROOF (R) FLOOR TO WALL (FW) ROOF TO WALL (RW)

More information

Submittal Exchange Design Team User Guide

Submittal Exchange Design Team User Guide Submittal Exchange Design Team User Guide Version 17 November 2017 Contents About This Guide... 9 Access/Permissions... 11 What is Submittal Exchange for Design?... 11 How Can I Get Submittal Exchange

More information

UFGS-16553N (Septermber 1999) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS-16553N (Septermber 1999) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 55 80.00 20 (April 2006) -------------------------------- Preparing Activity: NAVFAC Replacing without change UFGS-16553N (Septermber 1999) UNIFIED FACILITIES GUIDE

More information

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Never fill any required clearance space with insulation or any other building materials surrounding the chimney.

Never fill any required clearance space with insulation or any other building materials surrounding the chimney. INSTALLATION AND MAINTENANCE INSTRUCTIONS 1700ºF Air-Cooled Temp/Guard Chimney Sizes 8-16 Listing No. MH8251 Tested to UL103/ULC-S604 A MAJOR CAUSE OF RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCE

More information

H05Z-K / H07Z-K BS EN LSZH Wire

H05Z-K / H07Z-K BS EN LSZH Wire Application: In pipes or ducts and internal wiring of appliances with maximum operating temperatures of 90 C, and generally in areas (such as public and government buildings) where smoke and toxic fumes

More information

1.) Type: VL-F Single compartment rectangular smoke extraction ducts and fittings

1.) Type: VL-F Single compartment rectangular smoke extraction ducts and fittings 1.) Type: VL-F Single compartment rectangular smoke extraction ducts and fittings 2.) Manufacturer / Place of manufacture: AEROPRODUKT Zrt., 6640 Csongrád, Szegedi út 1., HUNGARY 3.) Function: The smoke

More information

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications Minnesota Power Systems Conference November 3 5, 2009 Earl Brown Heritage Center University of

More information

Pyroscat Duct Wrap Single Layer Installation

Pyroscat Duct Wrap Single Layer Installation Pyroscat Duct Wrap Single Layer Installation Product Data & Installation Guide 1. Product Description Pyroscat Duct Wrap is a flexible fire barrier system designed for grease ducts, ventilation air ducts,

More information

SECTION CABLE TRAYS

SECTION CABLE TRAYS SECTION 16139 CABLE TRAYS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Storefront Installation Guide

Storefront Installation Guide Storefront General Notes: 1. Check Contract Documents and Shop Drawings. Understand and clarify any Field Verify Notes and approvals of drawings and products to be familiar with the project. Installation

More information

U1500E Gas Fireplace

U1500E Gas Fireplace Model U1500E-NG U1500E-LP Fuel Type Natural Gas Propane Minimum Supply Pressure 5 W.C. (1.25 kpa) 11 W.C. (2.73 kpa) Manifold Pressure - High 3.5 W.C. (0.87 kpa) 10 W.C. (2.48 kpa) Manifold Pressure -

More information

METALWORKS TARTAN PANELS General Installation Instructions

METALWORKS TARTAN PANELS General Installation Instructions CEILING SYSTEMS METALWORKS TARTAN PANELS General Installation Instructions 1. GENERAL 1.1. Product Description MetalWorks Tartan system is a combination of metal ceiling panels available in a range of

More information

A. Section includes administrative provisions for coordinating construction operations on Project including, but not limited to, the following:

A. Section includes administrative provisions for coordinating construction operations on Project including, but not limited to, the following: SECTION 01 31 00 PROJECT MANAGEMENT AND COORDINATION PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

ARCHICAD Introduction Tutorial

ARCHICAD Introduction Tutorial Starting a New Project ARCHICAD Introduction Tutorial 1. Double-click the Archicad Icon from the desktop 2. Click on the Grey Warning/Information box when it appears on the screen. 3. Click on the Create

More information

Archibus Space Console

Archibus Space Console Archibus Space Console Space Console Overview General Navigation Retrieving Floor Plans and Data Displaying Floor Plans and Data Reviewing Data Exporting Floor Plans to PDF Use the table of contents hyperlinks

More information

Residential Construction Checklist Single and Two Family Construction

Residential Construction Checklist Single and Two Family Construction DATE: _ Building Inspection Submittal Requirements Residential Construction Checklist Single and Two Family Construction Submit a City of Big Spring Permit Application, checklist, and 3 complete hard copy

More information

INFUSIONS and METALWORKS Wings Accent and Acoustical Clouds

INFUSIONS and METALWORKS Wings Accent and Acoustical Clouds INFUSIONS and METALWORKS Wings Accent and Acoustical Clouds Assembly and Installation Instructions 1. GENERAL 1.1 Product Description Wings is a decorative ceiling element consisting of a 10 foot long

More information

METALWORKS Wings Accent and Acoustical Clouds Installation Instructions

METALWORKS Wings Accent and Acoustical Clouds Installation Instructions CEILING SYSTEMS Between us, ideas become reality METALWORKS Wings Accent and Acoustical Clouds Installation Instructions 1. GENERAL 1.1. Product Description MetalWorks Wings is a decorative ceiling element

More information

CHAPTER 5 ARCHITECTURE

CHAPTER 5 ARCHITECTURE CHAPTER 5 ARCHITECTURE 5.1 GENERAL... 4 5.2 CONCEPT/PROJECT DEFINITION DESIGN (30%) SUBMITTAL REQUIREMENTS... 4 5.2.1 DESIGN ANALYSIS... 4 5.2.1.1 Design Criteria... 4 5.2.1.2 Narratives... 4 5.2.1.2.1

More information

Sturdi-Wall Design Manual for SW46, SW66, SW63, SW64, SW60, SW83, SW84, and SW80 Models

Sturdi-Wall Design Manual for SW46, SW66, SW63, SW64, SW60, SW83, SW84, and SW80 Models Sturdi-Wall Design Manual for SW46, SW66, SW63, SW64, SW60, SW83, SW84, and SW80 Models Project Number ME086-05 by Brent Leatherman, P.E. Timber Tech Engineering, Inc E-Mail: bl@timbertecheng.com January

More information

Window Frame Installation Instructions For Nail-on and Block Frames

Window Frame Installation Instructions For Nail-on and Block Frames General The key to any window or door installation is preparation. This extends from storage of the product to the final installation and to all points in between. Careful planning and attention to detail

More information

Introduction to QTO. Objectives of QTO. Getting Started. Requirements. Creating a Bill of Quantities. Updating an existing Bill of Quantities

Introduction to QTO. Objectives of QTO. Getting Started. Requirements. Creating a Bill of Quantities. Updating an existing Bill of Quantities QTO User Manual Contents Introduction to QTO... 5 Objectives of QTO... 5 Getting Started... 5 QTO Manager... 6 QTO Layout... 7 Bill of Quantities... 8 Measure Folders... 9 Drawings... 10 Zooming and Scrolling...

More information

FIRE RATED DOOR AND FRAME GENERAL REQUIREMENTS

FIRE RATED DOOR AND FRAME GENERAL REQUIREMENTS FIRE RATED DOOR AND FRAME GENERAL REQUIREMENTS These requirements apply to all fire rated doors, frames, and windows. Requirements for the installation of these assemblies are included in the Standard

More information

Installation and Maintenance Manual IM 770-1

Installation and Maintenance Manual IM 770-1 Installation and Maintenance Manual IM 770-1 Group: Applied Air Systems Part Number: IM 770 Date: March 2014 Skyline Outdoor Air Handler Roof Curb Table of Contents General Description... 3 Curb-Ready

More information

FIRE RATED DOOR AND FRAME GENERAL REQUIREMENTS

FIRE RATED DOOR AND FRAME GENERAL REQUIREMENTS ` FIRE RATED DOOR AND FRAME GENERAL REQUIREMENTS These requirements apply to all fire rated doors, frames, and windows. Requirements for the installation of these assemblies are included in the Standard

More information

SECTION BULLET- RESISTANT DOORS

SECTION BULLET- RESISTANT DOORS 1 SECTION 08 3950 BULLET- RESISTANT DOORS PART 1- GENERAL 1.01 SUMMARY A. This Section Includes: 1. Bullet- resistant steel door and frame systems. 2. Door hardware for bullet- resistant steel door and

More information

TYPE "B" GAS VENT. Do not connect gas vent to a solid or liquid fuelled appliance or any appliance requiring a chimney.

TYPE B GAS VENT. Do not connect gas vent to a solid or liquid fuelled appliance or any appliance requiring a chimney. TYPE "B" GAS VENT SD (sizes 3", 4", 5", 6", 7") INSTALLATION INSTRUCTIONS Type "B" Gas Vents are strictly for interior or enclosed exterior use or exterior use above a roof line. Read vent and appliance

More information

Round Casserole Carrier

Round Casserole Carrier Round Casserole Carrier What a dish! This Round Casserole Carrier is perfect for sharing side dishes, desserts, and casseroles at the next potluck dinner or family gathering. Carry it in style by its sturdy

More information

INSUL-FLUE is used to reduce the danger of radiant heat from smoke pipe, flue pipe, gas vents, etc. igniting combustibles.

INSUL-FLUE is used to reduce the danger of radiant heat from smoke pipe, flue pipe, gas vents, etc. igniting combustibles. INSUL-FLUE OWNER S MANUAL (6 inch) High Heat Resistant Thimble and Insulating Sleeve for Smoke Pipe When Passing Through Any Combustible Wall September 1993, Revision A INTRODUCTION CONGRATULATIONS ON

More information

Power Processor - Series 700F 10KVA to 150KVA

Power Processor - Series 700F 10KVA to 150KVA Power Processor - Series 700F 10KVA to 150KVA Power Conditioning and Regulation for Commercial & Industrial Equipment General Specifications PART 1 - GENERAL 1.1 DESCRIPTION This specification defines

More information

PERFORMANCE SPECIFICATION SHEET

PERFORMANCE SPECIFICATION SHEET INCH-POUND 10 August 2016 SUPERSEDING 16 November 2011 PERFORMANCE SPECIFICATION SHEET CONNECTORS, RECEPTACLE, ELECTRICAL, COAXIAL, RADIO FREQUENCY, SERIES SMB (CABLED, PIN CONTACT, JAMNUT MOUNTED, REAR

More information

B. Terracotta Precast Facade Assembly consisting of single-leaf, through body color terracotta clay tiles.

B. Terracotta Precast Facade Assembly consisting of single-leaf, through body color terracotta clay tiles. SECTION 07 4229 TERRACOTTA CLAY TILE IN PRECAST SPECIFICTION FOR TERRART SOLID PART 1 GENERAL 1.1 SECTION INCLUDES A. Drawings and general provisions of the Contract, including General and Supplementary

More information

Thru Wall Floor Seals For New Installation

Thru Wall Floor Seals For New Installation The O-Z/Gedney Thruwall and Floor Seals provide a positive means of sealing pipe, conduit or tube where they pass through a concrete foundation of a structure below grade or below ground water level or

More information

GENERAL INSTALLATION GUIDELINES

GENERAL INSTALLATION GUIDELINES 1551 MT. ROSE AVENUE YORK PA 17403-2909 (717) 849-8100 GENERAL INSTALLATION GUIDELINES For Receptor Systems Approved 9/29/2017 Installation Guideline Disclaimer This document contains general installation

More information

STEAM BRANDING GUIDELINES. Revised December 6, 2017

STEAM BRANDING GUIDELINES. Revised December 6, 2017 STEAM BRANDING GUIDELINES Revised December 6, 2017 CONTENTS Branding Assets 1 General Guidelines 2 1 STEAM SYMBOL AND LOGO Hardware Application 4 On-screen and Printed Applications 6 2 STEAM MACHINES LOGO

More information

B. Sequencing: Schedule installation to keep sheathing exposure to UV within the manufacturer s recommended limits.

B. Sequencing: Schedule installation to keep sheathing exposure to UV within the manufacturer s recommended limits. SECTION 06 16 43 GYPSUM SHEATHING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Exterior GMF gypsum sheathing. 2. Joint treatment materials. 3. Panel and penetration joint and fastener treatment.

More information

GENERAL INSTALLATION GUIDELINES

GENERAL INSTALLATION GUIDELINES 1551 MT. ROSE AVENUE YORK PA 17403-2909 (717) 849-8100 GENERAL INSTALLATION GUIDELINES For Receptor Systems Approved 08/31/2018 Installation Guideline Disclaimer This document contains general installation

More information

SECTION MECHANICAL IDENTIFICATION

SECTION MECHANICAL IDENTIFICATION SECTION 15190 MECHANICAL IDENTIFICATION PART 1 GENERAL 1.01 SECTION INCLUDES A. Section Includes: 1. Nameplates. 2. Tags. 3. Stencils. 4. Pipe Markers. 1.02 SUBMITTALS A. Submit valve chart and schedule,

More information

REQUEST FOR INFORMATION (RFI) RFI NO: /WJG

REQUEST FOR INFORMATION (RFI) RFI NO: /WJG (RFI) RFI NO: 15-219/WJG WASHINGTON METROPOLITAN AREA TRANSIT AUTHORITY 600 FIFTH STREET, NW WASHINGTON DC 20001 ( WMATA OR AUTHORITY ) 1 ⅝ INCH RADIATING COAXIAL CABLE DATE: AUGUST 7, 2015 Contents Introduction...

More information

Power Cables and their Application

Power Cables and their Application Power Cables and their Application Parti Materials Construction Criteria for Selection Project Planning Laying and Installation Accessories Measuring and Testing Editor: Lothar Heinhold 3rd revised edition,

More information

MODEL SETUP FOR RENOVATION PROJECTS INSTRUCTIONS AND TUTORIALS

MODEL SETUP FOR RENOVATION PROJECTS INSTRUCTIONS AND TUTORIALS MODEL SETUP FOR RENOVATION PROJECTS INSTRUCTIONS AND TUTORIALS WHAT S INSIDE INTRODUCTION 1 PART ONE LAYERS AND CLASSES FOR RENOVATION PROJECT 1 OVERVIEW 1 SETTING UP LAYERS AND CLASSES 1 CREATING OBJECT

More information

MATERIAL COMBINATION NUMBER 2: Corrosive environment requiring harder, wear-resistant seating faces and resistance to dezincification.

MATERIAL COMBINATION NUMBER 2: Corrosive environment requiring harder, wear-resistant seating faces and resistance to dezincification. Cast Iron Slide Gates Spec Sheet General The contractor shall furnish and install the following cast iron slide gate assemblies as listed on the Gate Schedule and detailed on the manufacturer s drawings.

More information

*************************************************************************************************************

************************************************************************************************************* 15890 DUCTWORK ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 23 33 13 *************************************************************************************************************

More information

Opening the Door to Curtain Walls in AutoCAD Architecture, Part I

Opening the Door to Curtain Walls in AutoCAD Architecture, Part I Opening the Door to Curtain Walls in AutoCAD Architecture, Part I David Driver, President 4D Architects, Ltd. AB210-3 This class gives you a kit of parts and a set of rules methodology for understanding

More information

NON-PENETRATING ROOFTOP HANGERS AND SUPPORTS

NON-PENETRATING ROOFTOP HANGERS AND SUPPORTS SECTION 15062 NON-PENETRATING ROOFTOP HANGERS AND SUPPORTS For best results, display hidden notes to specifier. PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe supports. B. Conduit supports. C. Duct supports,

More information

MECHANICAL BACK FASTENED SYSTEMS INSTALLATION DATA

MECHANICAL BACK FASTENED SYSTEMS INSTALLATION DATA MECHANICAL BACK FASTENED SYSTEMS INSTALLATION DATA 7/16 PETRARCH ARCHITECTURAL WALL PANELS APPLIED OVER A STUDWALL BY MEANS OF A FIELD ASSEMBLED BACK FASTENED SYSTEM DESIGN CONCEPT 7/16 panels may be installed

More information

Contemporary Collection

Contemporary Collection HZ5E Gas Fireplace Model HZ5E-NG1 HZ5E-LP1 Fuel Type Natural Gas Propane Gas Minimum Supply Pressure 5 W.C.(1.5 kpa) 1 W.C. (.98 kpa) Manifold Pressure - High 3.5 W.C. (.87 kpa) 1 W.C. (.9 kpa) Manifold

More information

General Information...SA1-SA4

General Information...SA1-SA4 SECTION S INDEX Product Description Page Number General Information................................................................SA1-SA4 Type FSK Thruwall & Floor Seal For Conduit, Pipe or Tubing............................

More information

Method of Build 1. Fire. Sound

Method of Build 1. Fire. Sound Method of Build 1 General Viso Fire & Acoustic in the solid form differs from most other systems as it can be erected using 12.5mm & 15.0mm boards within the same Aluminium framework. Also hidden fix board

More information

Office of Physical Resources & Planning

Office of Physical Resources & Planning Office of Physical Resources & Planning www.oprp.fas.harvard.edu Centerstone Quick Tips Self-service for FAS Space and Building Floorplans Space Management and Planning Contacts: Celia Kent, Director,

More information

INTRODUCTION NUHAS OMAN QUALITY & RELIABILITY.

INTRODUCTION NUHAS OMAN QUALITY & RELIABILITY. INTRODUCTION Nuhas Oman LLC, an integral part of The Al Bahja Group of Companies, is a Quality producer of: HV, MV and LV Cables Enamelled Copper Wires Oxygen Free Continuous Cast Copper Wire Rods Drawn

More information

Serial ATA (SATA) Connector

Serial ATA (SATA) Connector Product 108-51052 Specification PRE: Tay Aik Poh 20 MAY 11 Rev G APP: Leong See Fan DCR No. D20110520030314_706049 Serial ATA (SATA) Connector 1.0 SCOPE This specification covers the requirements for product

More information

Installation and Maintenance Manual

Installation and Maintenance Manual Installation and Maintenance Manual IM770 Group: pplied ir Part Number: IM770 Date: pril 2003 Roof Curb for Skyline TM Outdoor ir Handlers 2013 Daikin pplied IM 770 Page 1 Table of Contents General Description...

More information

Slope Floor. Measurement Methods

Slope Floor. Measurement Methods Slope Floor Measurement Methods Many chair installations are on sloped floors. Hussey Seating uses five different feet for floor mount chairs based on the degree of slope. The slope of the floor is a critical

More information

Definitions and Design Considerations... W-CR-2

Definitions and Design Considerations... W-CR-2 General Information SECTION DIRECTORY Definitions and Design Considerations... W-CR-2 Combination Assembly Recommendations and Limitations Typical Sealant... W-CR-4 Single-Unit Opening... W-CR-4 Two-Way

More information

Powder Actuated Fasteners - Drive Pins

Powder Actuated Fasteners - Drive Pins 122 Drive Pins Standard Pins Drive pins with a.300 diameter head are designed for permanently fastening a fixture to concrete, some types of masonry and A36 structural steel. Drive pins are manufactured

More information

Module 1C: Adding Dovetail Seams to Curved Edges on A Flat Sheet-Metal Piece

Module 1C: Adding Dovetail Seams to Curved Edges on A Flat Sheet-Metal Piece 1 Module 1C: Adding Dovetail Seams to Curved Edges on A Flat Sheet-Metal Piece In this Module, we will explore the method of adding dovetail seams to curved edges such as the circumferential edge of a

More information

Contemporary Collection

Contemporary Collection HZ4STE Gas Fireplace Model HZ4STE - NG1 HZ4STE-LP1 Fuel Type Natural Gas Propane Gas Minimum Supply Pressure 5 W.C.(1.5 kpa) 1 W.C. (.98 kpa) Manifold Pressure - High 3.5 W.C. (.87 kpa) 1 W.C. (.49 kpa)

More information

Electronic Document Review (EDR)

Electronic Document Review (EDR) Electronic Document Review (EDR) Submittal Requirements Table of Contents Introduction... 3 Electronic Document Review Submittals:... 4 Plans... 4 Plat... 4 Forms... 4 Correspondence... 5 Plan Revisions...

More information

ERRATA AND REVISIONS to the CANADIAN PLUMBING CODE

ERRATA AND REVISIONS to the CANADIAN PLUMBING CODE NATONAL RESEARCH COUNCL OF CANADA ASSOCATE COMMTTEE ON THE NATONAL BULDNG CODE ERRATA AND REVSONS to the CANADAN PLUMBNG CODE 1970 (ncorporating changes from Change Series No.2 to the National Building

More information

The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this Section.

The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this Section. SECTION 23 31 13 METAL HVAC DUCTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in

More information

Equipment EQ ID SOP. Filename: Equipment EQ ID SOP (OFPC) Process_ docx Date: Page 1 of 6

Equipment EQ ID SOP. Filename: Equipment EQ ID SOP (OFPC) Process_ docx Date: Page 1 of 6 Equipment EQ ID SOP Purpose: To facilitate the efficient and timely transfer of equipment information to all FOM to have equipment and PM instructions in FAMIS by substantial completion (SC) and be prepared

More information

Units. In the following formulae all lengths are expressed in centimeters. The inductance calculated will be in micro-henries = 10-6 henry.

Units. In the following formulae all lengths are expressed in centimeters. The inductance calculated will be in micro-henries = 10-6 henry. INDUCTANCE Units. In the following formulae all lengths are expressed in centimeters. The inductance calculated will be in micro-henries = 10-6 henry. Long straight round wire. If l is the length; d, the

More information

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details.

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details. SECTION 081113 - HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: For each type of product indicated.

More information

LOW PRESSURE STEEL DUCTWORK Mechanical Systems Insulation Outlets (HVAC) Testing and Balancing.

LOW PRESSURE STEEL DUCTWORK Mechanical Systems Insulation Outlets (HVAC) Testing and Balancing. SECTION 15841 LOW PRESSURE STEEL DUCTWORK PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15180 - Mechanical Systems Insulation. 2. 15940 - Outlets (HVAC). 3. 15991 - Testing and Balancing. 1.02 SUBMITTALS

More information

Advance Concrete. Tutorial

Advance Concrete. Tutorial Advance Concrete Tutorial Table of contents About this tutorial... 9 How to use this guide... 10 Lesson 1: Creating a building grid... 11 Step 1: Create a default building grid... 11 Step 2: Set the distances

More information

Solid Part Four A Bracket Made by Mirroring

Solid Part Four A Bracket Made by Mirroring C h a p t e r 5 Solid Part Four A Bracket Made by Mirroring This chapter will cover the following to World Class standards: Sketch of a Solid Problem Draw a Series of Lines Finish the 2D Sketch Extrude

More information

1. Setup Output mode. 2. Using a Fixed tile size

1. Setup Output mode. 2. Using a Fixed tile size Tutorial Tiling Software version: Asanti 2.0 Document version: June 23, 2015 This tutorial demonstrates how to use tiling with Asanti. Tiling can only be executed on a system where Acrobat Pro X or later

More information

WOODEN BUILDINGS 6.1 INTRODUCTION 6.2 TYPICAL DAMAGE AND FAILURE OF WOODEN BUILDINGS. Chapter 6

WOODEN BUILDINGS 6.1 INTRODUCTION 6.2 TYPICAL DAMAGE AND FAILURE OF WOODEN BUILDINGS. Chapter 6 Chapter 6 WOODEN BUILDINGS 6.1 INTRODUCTION Wood has higher strength per unit weight and is, therefore, very suitable for earthquake resistant construction. But heavy cladding walls could impose high lateral

More information

Model ABV Pressure Independent Automatic Balancing Valve. Application: Standard Construction: Performance: Configurations Available:

Model ABV Pressure Independent Automatic Balancing Valve. Application: Standard Construction: Performance: Configurations Available: Application: Tag: Project: Location: Date: Engineer: Contractor: Architect: Submitted by: The ABV Automatic maintains a constant airflow volume in HVAC applications. The highly engineered damper blade

More information

A. Provide all finish carpentry needed for a complete and proper installation.

A. Provide all finish carpentry needed for a complete and proper installation. SECTION 06200 - PART ONE GENERAL 1.1 SECTION INCLUDES A. Provide all finish carpentry needed for a complete and proper installation. B. Provide all wood, nails, bolts, screws, and all other items needed

More information

2. All work and materials shall be in full accordance with Local and State ordinance and with any prevailing rules and regulations.

2. All work and materials shall be in full accordance with Local and State ordinance and with any prevailing rules and regulations. General Conditions: 1. Deliver all food service equipment as specified herein, including that which is reasonably inferred, with all related items necessary to complete work shown on contract drawings

More information

3M Air and Vapour Barrier 3015 Technical guide

3M Air and Vapour Barrier 3015 Technical guide 3M Air and Vapour Barrier 3015 Technical guide Product overview Typical physical properties For installation ease and flexibility, 3M Air and Vapour Barrier 3015 High performance 3M acrylic adhesive grabs

More information

Round Duct and Fittings. Standards and Dimensional Data for Air Duct and Fittings

Round Duct and Fittings. Standards and Dimensional Data for Air Duct and Fittings Round Duct and Fittings Standards and Dimensional Data for Air Duct and Fittings www.airsidesheetmetal.com 973-786-6967(office) 973-786-6474(fax) Fabricated by Airside Sheet Metal Fabricators, Inc. - 2017

More information

The Influence of Nails and Plasterboard on the Racking Resistance of Stud Walls

The Influence of Nails and Plasterboard on the Racking Resistance of Stud Walls Building 1 Grosvenor Court, Hipley Street OLD WOKING, SURREY GU22 9LL Tel: +44 (0) 1483 769518 Fax: +44 (0) 1483 770863 E-mail: design@silvatecdesigncom Internet: wwwsilvatecdesigncom The Influence of

More information

ROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION

ROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION ROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION 1. Scope 4. Underlayment 2. 1.1 This roofing application standard has been developed to provide a responsive

More information

Engineering Technology

Engineering Technology Engineering Technology Introduction to Parametric Modelling Engineering Technology 1 See Saw Exercise Part 1 Base Commands used New Part This lesson includes Sketching, Extruded Boss/Base, Hole Wizard,

More information

ROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION

ROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION ROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION 1. Scope 4. Underlayment 2. 1.1 This roofing application standard has been developed to provide a responsive

More information

Quilt-Pro 6. Creating a Panel Quilt

Quilt-Pro 6. Creating a Panel Quilt QP6 Lessons posted Page 1 Creating a Panel Quilt Quilt-Pro 6 I have seen some really beautiful fabric panels that would look absolutely gorgeous in a quilt. Panel quilts can be made quickly or can be as

More information

SECTION PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY

SECTION PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 07312 PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY A. This Section Includes the following: 1. Endureed Dominica PVC thatch shingles. 2. Self- adhering sheet underlayment. B. Related

More information

WAL-MART SUPERCENTER # ; Milwaukie, OR: SPECIFICATIONS. Revisions to Specification Fence

WAL-MART SUPERCENTER # ; Milwaukie, OR: SPECIFICATIONS. Revisions to Specification Fence MILWAUKIE OR #3144-00 ADDENDUM #5 NARRATIVE: 11-08-12 WAL-MART SUPERCENTER #3144-00; Milwaukie, OR: SPECIFICATIONS SPECIFICATIONS Revisions to Specification 02822 Fence Spec division 02822 has been revised

More information

METALWORKS Linear (Interior & Exterior Applications)

METALWORKS Linear (Interior & Exterior Applications) METALWORKS Linear (Interior & Exterior Applications) Assembly and Installation Instructions 1. GENERAL 1.1 Product Description MetalWorks Linear is a linear metal ceiling system with either a Connections

More information

Plasterboard Ceiling Systems

Plasterboard Ceiling Systems Plasterboard Ceiling Systems 400C Issue 1 2 Plasterboard Ceiling Systems Contents Standard Ceilings Design...3-7 Introduction... 3 Fire Ratings... 3 Systems Mass... 3 Decoration... 3 General Construction

More information

GLOSSARY OF TERMS SECTION 8

GLOSSARY OF TERMS SECTION 8 GLOSSARY OF TERMS SECTION 8 Anchor Bolt Angle Base Plate Bay Blocking CCB Centerline Chord Cladding Clip Closure Strip An A-307 steel bolt embedded in the concrete footing to anchor the base plate of the

More information

INTEX Millwork Solutions SECTION EXTERIOR PVC PERGOLAS (IBC Compliant)

INTEX Millwork Solutions SECTION EXTERIOR PVC PERGOLAS (IBC Compliant) SECTION 066030 EXTERIOR PVC PERGOLAS (IBC Compliant) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and other Contract Documents, listed in the agreement between the Owner and Contractor, apply to

More information

SECTION ROUGH CARPENTRY

SECTION ROUGH CARPENTRY SECTION 06100 PART I - GENERAL 1.01 DESCRIPTION A. Scope: Work of this Section shall include all materials and installation necessary to provide Rough Carpentry as shown and detailed on the Drawings and

More information

PIVOT DOOR 3400P INSTALLATION INSTRUCTIONS

PIVOT DOOR 3400P INSTALLATION INSTRUCTIONS Table of Contents I. Tools, Sealant Requirements, Anchor Recommended Table...1 II. Opening, Frame & Panel Verification...2-3 III. Frame Assembly...4 IV. Frame Installation...5-7 V. Glazing Instructions...8

More information

Sections & Details. WOOD SILL and FLOOR CONSTRUCTION NOTES

Sections & Details. WOOD SILL and FLOOR CONSTRUCTION NOTES 2 Sections & Details WOOD SILL and FLOOR CONSTRUCTION NOTES 1 Commonly Used Lumber Common LENGTHS include: 8, 10, 12, 14, 16 NOMINAL SIZES 2 x 4 2 x 6 2 x 8 2 x 10 2 x 12 ACTUAL SIZES 1 ½ x 3 ½ 1 ½ x 5

More information

Mechanical Support Systems, Inc.

Mechanical Support Systems, Inc. Mechanical Support Systems, Inc. CATALOG February, 2014 www.thesmartsupports.com 408.601.0155 1 N E W W E B S I T E.N E W P R O D U C T S Mechanical Support Systems, Inc. is certified as a women s business

More information

ICC INDUSTRIAL CHIMNEY COMPANY INC. ST-JEROME, QUÉBEC, CANADA, J7Y 4B7 TEL: (450) FAX: (450)

ICC INDUSTRIAL CHIMNEY COMPANY INC. ST-JEROME, QUÉBEC, CANADA, J7Y 4B7 TEL: (450) FAX: (450) ICC INDUSTRIAL CHIMNEY COMPANY INC. ST-JEROME, QUÉBEC, CANADA, J7Y 4B7 TEL: (450) 565-6336 FAX: (450)565-6519 www.icc-rsf.com INSTALLATION AND OPERATION INSTRUCTIONS "Model VIP" CHIMNEY TYPE: FACTORY BUILT

More information