1 SECTION LOW PRESSURE STEEL DUCTWORK PART 1 GENERAL 1.01 SUMMARY A. Related Sections: Mechanical Systems Insulation Outlets (HVAC) Testing and Balancing SUBMITTALS A. Properly identified manufacturer's data and shop drawings before starting work REFERENCES A. Sheet Metal and Air-conditioning Contractors National Association (SMACNA) Low Velocity Duct Manual. B. National Fire Protection Association (NFPA) 90-A Standard for Air-conditioning and Ventilating Systems. PART 2 PRODUCTS 2.01 EQUIPMENT A. Ductwork: 1. Galvanized steel ductwork, designed according to the latest Edition of SMACNA, Low Velocity Duct Manual and as shown on drawings. a. Cross-break flat areas over 18 inches in duct dimension. 2. Gage Stamp: Fabricated ductwork shall have manufacturer's gage stamp intact. ****** ***** **** *** ** * ** *** **** ***** ****** NOTE TO SPECIFIER: Choose either the paragraph above or below that best meets project conditions. ****** ***** **** *** ** * ** *** **** ***** ****** B. Ductwork: Project No. SPECIFICATION GUIDELINES
2 1. Includes supply ductwork from air handling units, ventilating units and exhaust, outside and return air ductwork. 2. Construction: a. Galvanized steel, designed and constructed according to the more stringent requirements of either the latest edition of SMACNA Low Velocity Duct Construction Standards or as specified. 1) Ductwork gages shall comply with the following: Greatest Dimension US Gage 0" to 12" 26 13" to 30" 24 31" to 60" 22 61" to 90" 20 over 90" 18 2) Ductwork dimensions shown on the drawings are clear inside dimensions. b. Flexible Collar Connections: Make connections to and from units with flexible collars not less than 4 inches long, secured by peripheral strap iron, using 30 ounce neoprene coated glass fabric by Ventglas or accepted equivalent. c. Hangers: 1) Hang horizontal ducts at intervals not exceeding 8 feet, with hangers of 16 gage by 1 inch wide galvanized band iron on ducts up to and including 30 inches wide and 12 gage by 1-1/2" wide galvanized band iron on ducts over 30 inches wide. 2) Extend hangers down and fasten underneath duct in addition to both sides of duct. d. Splitters and Dampers: 1) Provide as necessary for proper regulation of air distribution system. a) Locate splitters and dampers to be easily adjustable after work is completed. Provide a set screw locking device for each splitter or damper. b) On insulated ducts, place locking device on Project No. SPECIFICATION GUIDELINES
3 a bracket so set screw is on surface of insulation and is easily operable. c) Use Ventlock or Young Regulator. 2) Sheet Metal Gage: Construct splitters and dampers of galvanized steel 1 gage heavier than installed duct. e. Standing Seams: 1) 1 inch on widths of 24 inches to 48 inches. 2) 1-1/2" on widths over 48 inches. 3) Provide reinforcing bars or angles on widths of 60 inches and over. f. Longitudinal Seams and Transverse Joints: Make flat and smooth inside. g. Slip Joints: Make flat and smooth and in direction of air flow. h. Exhaust, Supply, and Return Duct System Joint Sealing Tape: Permaceil #691AF. i. Plenums: 1) Construct, design, and test plenums according to SMACNA as specified. 2) Make joints angle reinforced pocket type and provide fully gasketed joints between plenums and filter sections. 3) Internally line surfaces of plenums as specified in Section C. Grilles, Registers, and Diffusers: 1. Aluminum construction complete with specified accessories and baked enamel finish. 2. Acceptable Manufacturers: a. Air Guide. b. Carnes. c. Krueger. d. Metalaire. e. Price. f. Titus. D. Joint Sealant: Flexomastic No.210 with fiberglass membrane for weatherproofing as manufactured by Weatherproofing Products, Inc. or accepted equivalent. E. Ductwork Supports and Hangers: Project No. SPECIFICATION GUIDELINES
4 1. Supports: Galvanized steel angles or channels. a. Provide minimum support sizes as follows: Duct Width Angle Size To 24" 1-1/4" X 1-1/4" X 1/8" 25" to 36" 1-1/2" X 1-1/2" X 1/8" 37" to 54" 2" X 2" X 3/16" Above 54" 2" X 2" X 1/4" 2. Hangers: Galvanized steel straps. F. Fire Dampers: Provide fire dampers as indicated on Construction Documents for ducts penetrating fire separations. 1. Construct dampers and install according to UL 555 and NFPA 90-A FABRICATION a. Fire Dampers: 100 percent free area, blade out of airstream type unless otherwise indicated, UL listed. b. Fire Dampers for Vertical Air Flow: Actuate by 2 stainless steel springs exerting force 2-1/2 times greater than required to close damper. c. Provide access doors. A. Fabricate work according to SMACNA manuals, except as otherwise indicated. B. Seams and Joints: Make airtight as possible. Seal joints with 4 inch wide cloth tape with bonding agent, except ductwork exposed to weather shall have joints sealed with specified joint sealant. PART 3 EXECUTION 3.01 INSPECTION A. Do not proceed with the work of this section until conditions detrimental to the proper and timely completion of the work have been corrected in an acceptable manner INSTALLATION A. Install ductwork materials and accessories according to the Project No. SPECIFICATION GUIDELINES
5 latest edition of SMACNA Low Velocity Duct Construction Standards as specified. These written specifications shall take precedence in case of conflict. B. Thoroughly clean ductwork before attempting test and balance. C. Where interferences arise during construction, make transition or division of ductwork on a basis of pressure drop equivalent to the original size. Obtain acceptance from A/E before fabrication. D. Apply cloth tape with bonding agent to joints of ductwork installed in interior spaces. E. Apply Flexomastic weatherproofing with smooth finish to joints of ductwork exposed to weather as recommended by joint sealant manufacturer, with at least 2 final coats of No.210. F. Install strap hangers from inserts, clip angles, or clamps secured to structure. 1. Do not hang from expansion bolts in tension. 2. Bend hangers under ductwork at least 2 inches. 3. Secure hangers for ducts 48 inches wide and over to bottom and sides of duct at 6 inches on center. G. Support vertical ducts at each floor with minimum of 2 angle or channel supports secured to duct and spanning shaft opening. 1. Fasten structural members to floor in a manner acceptable to A/E. END OF SECTION Project No. SPECIFICATION GUIDELINES
SECTION LOW PRESSURE DUCTWORK
SECTION 15841 LOW PRESSURE DUCTWORK PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 07270 - Firestopping and Fire and Smoke Barrier Caulking. 2. 15260 - Vibration Isolation. 3. 15280 - Thermal Insulation
More information*************************************************************************************************************
15890 DUCTWORK ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 23 33 13 *************************************************************************************************************
More informationPRESTON HEALTH SERVICES ARCHITECT S NO. 2700
SECTION 23 3113 - LOW PRESSURE DUCTWORK PART 1 - GENERAL 1.1 SCOPE OF WORK: A. The work required under this section includes all work necessary for a complete installation of ductwork and accessories.
More informationA. Radius elbows with a construction radius of 1.5 the duct width are preferred to square elbows.
SECTION 233100 DUCTWORK 1.0 Acoustical duct lining in any part of the duct system is prohibited. All ductwork requiring insulation shall be externally insulated (Refer to the Sheet Metal Ductwork Insulation
More informationDuctwork Controls and Instrumentation Outlets (HVAC) HVAC Control System.
SECTION 15910 DUCT ACCESSORIES PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15890 - Ductwork. 2. 15900 - Controls and Instrumentation. 3. 15940 - Outlets (HVAC). 4. 15970 - HVAC Control System.
More informationThe General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this Section.
SECTION 15800! AIR DISTRIBUTION PART 1! GENERAL 1.01 RELATED DOCUMENTS The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this
More informationThe General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this Section.
SECTION 23 31 13 METAL HVAC DUCTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in
More informationSECTION AIR DISTRIBUTION SYSTEM
SECTION 23 30 00 AIR DISTRIBUTION SYSTEM PART 1 - GENERAL 1.1 Scope of Work: The work covered by this section consists of providing all labor, equipment and materials and performing all operations necessary
More informationSECTION COMMON WORK RESULTS FOR HVAC
SECTION 23 05 00 COMMON WORK RESULTS FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Ball Valve. 2. Hangers and Supports. 3. Identification Tags and Sleeves. 1.2 INCLUDED SECTIONS A. Section
More informationSECTION HVAC DUCTS PART I - GENERAL 1.1 RELATED DOCUMENTS
SECTION 23 31 00 - HVAC DUCTS PART I - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationSHEET METAL FLASHING AND TRIM Christ on the Mountain
SECTION 076200 - SHEET METAL FLASHING AND TRIM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Compatibly with the bumping of flashings and trim as identified in the Membrane Roofing Section 075000.
More informationAPPENDIX A, UMC STANDARD 6-5 STANDARD FOR INSTALLATION OF FACTORY-MADE AIR DUCTS
STANDARD FOR INSTALLATION OF FACTORY-MADE AIR DUCTS Sealing of fibrous glass duct board to the sheet metal sleeve must be made with glass fabric and mastic, except where operating pressure is less than
More informationUFGS (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCESA / NASA UFGS-27 05 28.36 40 (August 2011) ----------------------------------- Preparing Activity: NASA Superseding UFGS-27 05 28.36 40 (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationSECTION SHEET METAL FLASHING AND TRIM
SECTION 07620 PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Formed roof drainage sheet metal fabrications. 2. Formed low-slope roof sheet metal fabrications. 1.2 SUBMITTALS A. Shop Drawings: Show
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-27 05 28.36 40 (May 2017) --------------------------------- Preparing Activity: NASA Superseding UFGS-27 05 28.36 40 (August 2014) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationCOMMERCIAL KITCHEN HOOD WORKSHEET/ CHECKLIST
COMMERCIAL KITCHEN HOOD WORKSHEET/ CHECKLIST Two copies of this worksheet/checklist must accompany plans sets submitted with commercial kitchen application. The applicant is responsible for assuring the
More informationSECTION WIREWAYS FOR RADIOLOGY EQUIPMENT
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 36 WIREWAYS FOR RADIOLOGY EQUIPMENT SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable
More informationCSP PSYCHIATRIC SERVICES UNIT SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT
SECTION 23 05 53 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe Markers. 2. Valve Tags. 3. Equipment Nameplates. 4. Underground Marking Tape. 5. Duct
More informationSECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSheet Metal Worker Level 2
Level 2 Unit: B1 Welding 2 (GMAW and SMAW) Level: Two Duration: 25 hours Theory: Practical: 5 hours 20 hours Overview: Upon completion of this unit of instruction the apprentice will demonstrate knowledge
More informationCHAPTER 6 DUCT SYSTEMS
CHAPTER 6 DUCT SYSTEMS 601.0 Scope General. 601.1 General Applicability. Ducts and plenums that are portions of a heating, cooling, absorption or evaporative cooling, or product-conveying system shall
More informationTechnical Development Program
Technical Development Program COMMERCIAL DISTRIBUTION SYSTEMS PRESENTED BY: Ray Chow Duct Design Level 1 Fundamentals Sales Engineer Menu Section 1 Section 2 Section 3 Section 4 Section 5 Introduction
More informationExcavating, Backfilling, and Compaction for Utilities Piping (Plumbing).
SECTION 15047 - IDENTIFICATION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Identification including necessary accessories indicated on Construction Documents and specified in this section or as required
More informationFLUOROPOLYMER COATED DUCT FOR CAUSTIC ENVIRONMENTS
DIVISION 23 FLUOROPOLYMER COATED DUCT FOR CAUSTIC ENVIRONMENTS Part I General 1.1 Related Documents A. All terms and general provisions of contract, General and Supplementary Conditions, and Specification
More information25 / 35 / 45. Rectangular Duct Connection System. Strong and Virtually Leak Free. Simple to install No additional sealing required
D U C T M A T E 25 / 35 / 45 Rectangular Duct Connection System Strong and Virtually Leak Free Simple to install No additional sealing required Available in specialty metals Consistent connections 25 /
More information4. Metal roof jacks at penetrations and attachments
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - SECTION 07 61 00 METAL SHINGLE ROOFING - - - - - - - - - - -
More informationB. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details.
SECTION 081113 - HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: For each type of product indicated.
More informationVinyl Windows and Doors Manufactured by VPI Quality Windows
Vinyl Windows and Doors Manufactured by VPI Quality Windows Part Number: 511_Installation ENDURANCE CASEMENT\AWNING\PW INSTALLATION INSTRUCTIONS Installation Instructions for Typical Construction These
More informationSECTION STEEL LIGHTING STANDARDS. 1. Electrical conduit and fittings; Section
02760-1 of 5 SECTION 02760 STEEL LIGHTING STANDARDS 02760.01 GENERAL A. Description Steel lighting standards shall include, but not necessarily be limited to, furnishing and installing steel lighting poles,
More informationA. Product Data: For each electrical identification product indicated.
SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION CABLE TRAYS
SECTION 16139 CABLE TRAYS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-08 33 13 (May 2009) Change 2-11/12 --------------------------- Preparing Activity: USACE Nontechnical Title Revision (August 2015) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationGE Monogram. Installation. Instructions. 36" Vent Hood. Model ZV750. Call anywhere in the US and Canada -
at :: rangehoods. com GE Monogram Instructions Model ZV750 GE Monogram at:: rangehoods. com is a division of CAUTION WARNING Before you begin Read these instructions completely and carefully. IMPORTANT:
More informationSt. Monica Food Pantry
St. Monica Food Pantry 23 3300-1 HVAC WORK DIVISION 23 SECTION 233300 HVAC AIR DUCT ACCESSORIES PART 1. GENERAL 1.1 WORK INCLUDES A. Gravity Operated Backdraft Dampers B. Volume dampers C. Motor operated
More informationDOCUMENT ADDENDUM NO. 4. Issued to all Bidders: Date: October 14, Contract Name: Electrical Installation. Contract Number: C8410
DOCUMENT 009104 - ADDENDUM NO. 4 Issued to all Bidders: Date: October 14, 2015 Contract Name: Electrical Installation Contract Number: C8410 This addendum forms a part of the Bid described above. The original
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017
SECTION 23 0553 - MECHANICAL SYSTEMS IDENTIFICATION GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationKS SERIES - VERTICAL INSTALLATION
CS-DS-01-KSV CS DISCLAIMER CS-PJ-01-KSV KS42SL EXPANDED PANEL JOINT CS-PJ-02-KSV KS42SL ENGAGED PANEL JOINT CS-PJ-03-KSV KS45SL EXPANDED PANEL JOINT CS-PJ-04-KSV KS45 FLAT ENGAGED PANEL JOINT CS-PJ-05-KSV
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION MECHANICAL SCOPE OF WORK PART 1 - GENERAL
SECTION 23 00 10 - MECHANICAL SCOPE OF WORK PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01
More informationFlowBar Architectural Linear Diffusers F L- 1 0 / F L-15 / FL-2 0 F L- 2 5 / F L-30 I NSTA LL AT IO N & OPER AT I ON M AN UA L
I NSTA LL AT IO N & OPER AT I ON M AN UA L FlowBar Architectural Linear Diffusers F L- 1 0 / F L-15 / FL-2 0 F L- 2 5 / F L-30 I OM F L-1 0/ FL- 15 /FL-20 /FL-25/FL-3 0 FlowBar Installed During Hard Ceiling
More informationC. Samples for Initial Selection: Manufacturer's color charts showing the full range of colors available.
SECTION 105113 - METAL LOCKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationIOM 004 Effective 3/29/04 Rev A. MULTI-VENT Laminar Flow Panels Installation Operation and Maintenance
IOM 004 Effective 3/29/04 Rev A MULTI-VENT Laminar Flow Panels Installation Operation and Maintenance Contents Batten Arrangements...3 Slip-On Battens...4 Ceiling Opening...5 Installation...5 Hanger Bracket
More informationInstallation Instructions for Vista Air Vertically Folding Walls
Installation Instructions for Vista Air Vertically Folding Walls Use these instructions in conjunction with your shop drawings to see the specifics that are particular to the model you are installing.
More informationTENANT IMPROVEMENT 16 FEBRUARY WEST 27TH STREET, 4TH FLOOR 100% CD OWNER/BID ADD 1-03/08/2018
SECTION 055000 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationSunTrackerTwo Preparation
TOLL FREE:(888)29-2705 FAX:(941)77-9460 info@eco-smart.com SunTrackerTwo Preparation Cutting Holes and Preparing Curbs T.G.I Or Truss CIRALIGHT INSTALLATION MANUAL Page 1 Cutting Holes and Preparing Curbs
More information1. Show the following information with additional information necessary to indicate shop compliance with the requirements of this section.
SECTION 12360 LIBRARY SHELVING PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 06100 - Carpentry. 2. 09200 - Metal Studs, Lath, Suspension Ceiling, Plaster and Stucco. 3. 09660 - Resilient Tile Flooring.
More informationPiping & Equipment Identification
Piping & Equipment Identification Part 1 General 1.01 Description of Work A. Work in this section includes: Identification materials, including necessary accessories indicated on Contract Documents and
More informationDESIGNER SERIES GUTTER SYSTEM INSTALLATION INSTRUCTIONS
DESIGNER SERIES GUTTER SYSTEM INSTALLATION INSTRUCTIONS GENERAL DESCRIPTION: The Designer Series Gutter System is a specially designed roof edge drainage product for industrial, commercial, and high end
More informationSECTION MECHANICAL IDENTIFICATION
PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions Specification Sections, apply to this Section. B. Related Sections:
More informationRS/2/C/003MR Published August RATING STANDARD for the certification of Rigid Metallic Ductwork Systems with Rectangular Cross-section
RATING STANDARD for the certification of Rigid Metallic Ductwork Systems with Rectangular Cross-section Editing (date): Marie-Clémence DEGALLAIX (30/05/2016) Checking (date): Jean FOURCROY (02/06/2016)
More informationSECTION SHEET METAL FLASHING AND TRIM
SECTION 07620 SHEET METAL FLASHING AND TRIM PART 1 GENERAL 1.1 SUMMARY A. Section includes flashings and counterflashings, sheet metal roofing and fabricated sheet metal items, as indicated in Schedule.
More informationMetal & Vinyl, Flush Mount and Recessed Fin Windows Recommended Installation Instructions
PO Box 480 Ph: 417-235-7821 Monett, MO 65708 Fax: 417-737-7140 Metal & Vinyl, Flush Mount and Recessed Fin Windows Recommended Installation Instructions These installation instructions are recommendations
More informationDesign and Construction Standards SECTION ATHLETIC LOCKERS
SECTION 10505 ATHLETIC LOCKERS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The provisions of the General Conditions, Supplementary Conditions, and the Sections included under Division 1, General Requirements,
More informationUL 580 Construction No: ½ in Snap Lock w/ Clip
Test Type: Testing Authority: Test Name: UL 580 Construction No: 589 Underwriters Laboratories Wind Uplift Test Date: Test Completed By: Testing Laboratory Type: Width: Clip Spacing: Decking Construction:
More informationSECTION CARPENTRY
SECTION 06100 CARPENTRY PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Carpentry work including grounds, nailers, blocking, miscellaneous framing, plywood backing panels, plywood sheathing, preservative
More informationVinyl Windows Manufactured by VPI Quality Windows
Vinyl Windows Manufactured by VPI Quality Windows Part Number: 531&591 Installation 531 & 591 SERIES SLIDING AND HUNG WINDOW INSTALLATION INSTRUCTIONS Installation Instructions for Typical Construction.
More informationFIRE STATION NO TH STREET NORTH ST. PETERSBURG, FL M-1 SCOPE OF WORK SYMBOL DESCRIPTION SYMBOL DESCRIPTION HVAC SYMBOL LEGEND
HVAC SYMBOL LEGEND HVAC PIPING AND VALVES LEGEND HVAC GENERAL NOTES SCOPE OF WORK SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION PHASING OF WORK HVAC ABBREVIATIONS ABBREVIATION
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION DUCTWORK PART 1 - GENERAL 1.1 RELATED DOCUMENTS:
SECTION 23 31 13 - DUCTWORK PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01 00, "Mechanical
More informationINTEX Millwork Solutions SECTION EXTERIOR PVC PERGOLAS (IBC Compliant)
SECTION 066030 EXTERIOR PVC PERGOLAS (IBC Compliant) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and other Contract Documents, listed in the agreement between the Owner and Contractor, apply to
More information8/7/ HP SWING DOOR INSTALLATION INSTRUCTIONS
8/7/17 1200 HP SWING DOOR INSTALLATION INSTRUCTIONS Installation Instructions for Typical Construction These instructions were developed and tested for use with typical construction in a wall system designed
More informationCSI Section DMI Light Gage Structural Steel Framing Systems. Blocking Fire Rated Pre-cut (Proprietary) Furring Wall Preservative Treated
DMI Database CCF5IF9HGLPD-QB (4,88) $14,775.00 CSI Section 05400 DMI Light Gage Structural Steel Framing Systems Angle Framing Bridging Channel Flat Strapping Furring Clip Angle Soffit/Fascia/Deck Framing
More information.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1.
PAGE 1 PART 1 GENERAL 1.1 REFERENCE.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1. 1.2 RELATED WORK SPECIFIED ELSEWHERE.1 Installation
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-08 51 69.10 (April 2006) ----------------------------- Preparing Activity: NAVFAC Replacing without change UFGS-08582 (August 2001) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationCROSSBAR RAFTER ISOMETRIC
Super Sky Products' typical glazing system consists of glass panels or "lites" which are attached to the main framing members using extruded aluminum "retainers" or "pressure plates". These retainers are
More information2. All work and materials shall be in full accordance with Local and State ordinance and with any prevailing rules and regulations.
General Conditions: 1. Deliver all food service equipment as specified herein, including that which is reasonably inferred, with all related items necessary to complete work shown on contract drawings
More informationSeries Sloped glazed Curtain wall. Installation Instructions
Series 5600 Sloped glazed Curtain wall Installation Instructions Part NO. Y308 February 2013 SECTION TABLE OF CONTENTS PAGE I. General Notes & Guidelines. 3-4 II. Gutter and Mullion Assembly.. 5 III. End
More informationSECTION CABLE TRAYS FOR ELECTRONIC SAFETY AND SECURITY
SECTION 26 05 36 CABLE TRAYS FOR ELECTRONIC SAFETY AND SECURITY PART 1 -GENERAL 1.1 SUMMARY A. Section includes cable tray. 1.2 REFERENCES A. ASTM A 123 Standard Specification for Zinc (Hot-Dip Galvanized)
More informationRound Duct and Fittings. Standards and Dimensional Data for Air Duct and Fittings
Round Duct and Fittings Standards and Dimensional Data for Air Duct and Fittings www.airsidesheetmetal.com 973-786-6967(office) 973-786-6474(fax) Fabricated by Airside Sheet Metal Fabricators, Inc. - 2017
More informationSECTION IDENTIFICATION OF HVAC PIPING AND EQUIPMENT. A. Section includes nameplates, tags, stencils and pipe markers.
SECTION 23 05 53 IDENTIFICATION OF HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes nameplates, tags, stencils and pipe markers. B. Related Sections: 1. Section 09 05 00 Common
More informationTesting. Material testing will be according to applicable AASHTO, ASTM or Department methods as specified.
907.01 Section 907. FENCING MATERIALS 907.01 General Requirements. Materials for use in fencing property, right-of-way and other installations must comply with this section. 907.02 Testing. Material testing
More informationPIPE/CONDUIT SUPPORTS
PIPE/CONDUIT SUPPORTS Pipe/Conduit Clamps...102-105 Unicushion... 106 Pipe & Tubing (Cush-A-Clamp ) Clamps...107-110 Pipe Hangers... 111 Pipe Rollers...111-112 Pipe Brackets... 113 Reference Tables...114-120
More informationGENERAL INSTALLATION GUIDELINES
1551 MT. ROSE AVENUE YORK PA 17403-2909 (717) 849-8100 GENERAL INSTALLATION GUIDELINES For Receptor Systems Approved 9/29/2017 Installation Guideline Disclaimer This document contains general installation
More informationDRYSTAND INSTALLATION MANUAL
DRYSTAND INSTALLATION MANUAL WWW.ROOFSCREEN.COM Toll Free 866 766 3727 Introduction... 2 This manual... 2 Application... 2 System Overview... 2 Components... 2 Round Post Supports (BS50)... 2 Telescoping
More informationGENERAL INSTALLATION GUIDELINES
1551 MT. ROSE AVENUE YORK PA 17403-2909 (717) 849-8100 GENERAL INSTALLATION GUIDELINES For Receptor Systems Approved 08/31/2018 Installation Guideline Disclaimer This document contains general installation
More informationUL 580 Construction No: ½ in Mechanical Lock w/ Clip
Test Type: Testing Authority: Test Name: UL 580 Construction No: 588 Underwriters Laboratories Wind Uplift Test Date: Test Completed By: Testing Laboratory Panel Type: Greg Rezek Underwriters Laboratories
More informationYES 40 FS/FI Storefront System Installation Manual
Installation Manual 2014 YKK AP America Inc. is a subsidiary of YKK Corporation of America. TABLE OF CONTENTS Installation Notes... Page ii PARTS DESCRIPTION YES 40 FS Framing Members... Page 1 YES 40
More informationSide and rear window, assembly overview
64-7 Side and rear window, assembly overview 1 - Side/rear window Removing Unbroken Page 64-9 Broken Page 64-11 Installing Page 64-13 Curing time Page 64-21 Re-sealing Page 64-25 2 - PUR adhesive sealant
More informationHIGH PERFORMANCE CONNECTION
HIGH PERFORMANCE CONNECTION Duct Connection Products Hangers and Strapping Access Doors Product Catalog Edition 7 Table of Contents Introduction...3 Duct Connection Products Flange...4 Corner...5 Cleat...5
More informationMECHANICAL BACK FASTENED SYSTEMS INSTALLATION DATA
MECHANICAL BACK FASTENED SYSTEMS INSTALLATION DATA 7/16 PETRARCH ARCHITECTURAL WALL PANELS APPLIED OVER A STUDWALL BY MEANS OF A FIELD ASSEMBLED BACK FASTENED SYSTEM DESIGN CONCEPT 7/16 panels may be installed
More informationSECTION SWINGING AUTOMATIC ENTRANCES
SECTION 084229.33 SWINGING AUTOMATIC ENTRANCES IN-GROUND, AUTOMATIC SWING DOOR OPERATOR CONVERTER ADAPTED TO IR/DOR-O-MATIC SENIOR SWING & ASTRO SWING OPERATOR PART 1-GENERAL 1.01 DESCRIPTION A. This section
More informationAMPCO PRODUCTS, INC. TECHNICAL SPECIFICATIONS SOLID PHENOLIC CORE TOILET COMPARTMENTS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS TECHNICAL SPECIFICATIONS SOLID PHENOLIC CORE TOILET COMPARTMENTS A. Drawings and General Provisions of Contract, including General and Supplementary Conditions and
More informationM1.0 MECHNANICAL FLOOR PLAN
GENERAL NOTES A. CONTRACTORS AND SUB CONTRACTORS SHALL CAREFULLY REVIEW THE CONSTRUCTION DOCUMENTS. INFORMATION REGARDING THE COMPLETE WORK IS DISPERSED THROUGHOUT THE DOCUMENT SET AND CANNOT BE ACCURATELY
More informationSECTION HOLLOW METAL DOORS AND FRAMES
SECTION 081113 HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: Include construction details, material
More informationDear Contractor, I am glad that you are interested in our window rebate program.
Dear Contractor, I am glad that you are interested in our window rebate program. I have included three documents with this letter. One is our form to indicate your intention to participate in the program.
More informationInstallation Guidelines
Installation Guidelines Tando Building Products provides these instructions as general guidelines only. Tando Building Products neither installs exterior cladding nor has any control over any installation.
More informationStorefront Installation Guide
Storefront General Notes: 1. Check Contract Documents and Shop Drawings. Understand and clarify any Field Verify Notes and approvals of drawings and products to be familiar with the project. Installation
More informationSECTION CUSTOM FABRICATED EQUIPMENT
SECTION 11401 CUSTOM FABRICATED EQUIPMENT PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 05500 - Metal Fabrications. 2. 10100 - Chalkboards, Markerboards, Tackboards, and Bulletin Board Cabinets.
More informationASSEMBLY, INSTALLATION AND OPERATION MANUAL
ASSEMBLY, INSTALLATION AND OPERATION MANUAL - 1-312 SOUTH HWY. 73, PO BOX 398 FALLS CITY, NE 68355-0398 800-500-9777 PO Box 398 Falls City, NE 68355 800-500-9777 Version Date 03/07/2007 P/N 94000100 Revision
More informationPhone # La Jolla Doors. Block Frame Installation Manual Aluminum Frame with either Vinyl or Aluminum Panels
Phone # 800-440-8785 www.lajolladoors.com La Jolla Doors Block Frame Installation Manual Aluminum Frame with either Vinyl or Aluminum Panels Thank you for choosing La Jolla Doors In this manual you will
More informationB. Samples: For color, letter style, and graphic representation required for each identification material and device.
PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
More informationINSTALLATION MANUAL STOREFRONT DOORS
INSTALLATION MANUAL STOREFRONT DOORS www.aluflam-usa.com SYSTEM DESCRIPTION - Extruded and filled aluminum framing, tested and approved by UL - 3-3/8 frame depth - Clear, fire-rated safety glazing - Door
More informationINS A KSCR INSTALLATION INSTRUCTIONS STANDARD PROCEDURE. 1. Unpacking the KSCR Splicing the KSCR (If Required)...
INS-88.500-0A KSCR INSTALLATION INSTRUCTIONS STANDARD PROCEDURE 1. Unpacking the KSCR... 2 2. Splicing the KSCR (If Required)... 4 3. Assemble Curb and Rail Corners... 5 4. Install Cross Bracing (If Required)...
More informationGRILLE AND REGISTER OPTIONS AND ACCESSORIES
GRILLE ND REGISTER OPTIONS ND CCESSORIES PRODUCT OVERVIEW OPTIONS ND CCESSORIES FOR FSTENING ND MOUNTING FRMES Up to four methods of fastening available for most models. Sub-frame available for professionally
More informationSECTION MEDICAL AND SURGICAL LIGHTING FIXTURES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 55 71 MEDICAL AND SURGICAL LIGHTING FIXTURES SPEC WRITER NOTES: 1. Delete between // ---- // if not applicable to project. Also delete any other item or paragraph
More information1. Section : Rough Carpentry 2. Section : Exterior Insulation and Finishing Systems 3. Section : Metal Roof Panels
SECTION 06 16 00 SHEATHING PART 1 GENERAL 1.1 SUMMARY A. Section includes: 1. Roof and Wall Sheathing. B. Related Sections: Documents relating to the work of this section include, but are not limited to,
More information14000 I/O Series Flush Glaze. Fabrication and Installation Instructions
14000 I/O Series Flush Glaze Fabrication and Installation Instructions Last saved on 12/18/2009 Table of Contents GENERAL CONSTRUCTION NOTES...3 EXTRUDED ALUMINUM PARTS...4 ACCESSORIES...5 OVERVIEW...6
More informationYSG 40/50/50T Window Wall System Installation Manual
Installation Manual 2004 YKK AP America Inc. is a subsidiary of YKK Corporation of America. TABLE OF CONTENTS Installation Notes........................................ Page ii PARTS DESCRIPTION YSG 40
More informationTOILET ROOM ACCESSORIES Concrete Unit Masonry Carpentry Ceramic Tile Solid Plastic Toilet Partition.
SECTION 10800 TOILET ROOM ACCESSORIES PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 04220 - Concrete Unit Masonry. 2. 06100 - Carpentry. 3. 09310 - Ceramic Tile. 4. 10170 - Solid Plastic Toilet Partition.
More informationWAL-MART SUPERCENTER # ; Milwaukie, OR: SPECIFICATIONS. Revisions to Specification Fence
MILWAUKIE OR #3144-00 ADDENDUM #5 NARRATIVE: 11-08-12 WAL-MART SUPERCENTER #3144-00; Milwaukie, OR: SPECIFICATIONS SPECIFICATIONS Revisions to Specification 02822 Fence Spec division 02822 has been revised
More informationMAGNUM BOARD INTERIOR INSTALLATION GUIDELINES
TECHNICAL BULLETIN No.: 090509-1405 Subject: Issue Date: September 4, 2009 Issue No.: II MAGNUM BOARD INTERIOR INSTALLATION GUIDELINES 1. CUTTING MAGNUM BOARD You can easily cut Magnum Board with carbide
More informationSECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT
SECTION 23 05 53 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More information