conductor Extruded Cross - Linked Polyethylene Insulated (XLPE) Power Cable Rated Voltage U 0 /U = 12/20 kv U 0 /U = 18/30 kv

Size: px
Start display at page:

Download "conductor Extruded Cross - Linked Polyethylene Insulated (XLPE) Power Cable Rated Voltage U 0 /U = 12/20 kv U 0 /U = 18/30 kv"

Transcription

1 Israel Electric Corporation Ltd. - Customer Division - National Network Unit Issued date: February 2018 THE ISRAEL ELECTRIC CORPORATION LTD. National Network Unit Specification No. NPS for Single Core Aluminum and Copper conductor Extruded Cross - Linked Polyethylene Insulated (XLPE) Power Cable Rated Voltage U 0 /U = 12/20 kv U 0 /U = 18/30 kv This issue supersedes specification NPS - 74, NPS-111, NPS-112 Haifa, Israel February, 2018

2 Page No. 1 of 25 Contents 1 - General 2 - The IECo. catalogue Numbers 3 - Documents to be supplied with the Proposal 4 - Standards 5 - Technical Requirements 6 - Tests 7 - Marking 8 - Packing 9 - Quality Requirements 10 - Prototype approval 11- Questionnaire Appendix A - Test requirements for cables manufactured according to I.E.C. Appendix B - Acceptance Test requirements Appendix "C" - Quality Requirements for Contracts Execution Appendix "D" - Schedule up to prototype approval APPENDIX "E" Statement of manufacturer experience Prepared by: A. Lavian (- signed ) Approved by: N. Grinberg (- signed )

3 Page No. 2 of General Scope This specification defines the technical requirements of power cables with single core copper and aluminum conductor, extruded solid cross-linked polyethylene insulation (XLPE) of rated voltage U 0 /U=12/20kV and U 0 /U=18/30kV (henceforth referred to as Cables ). The cables are designated to be installed in outdoor or underground networks as follows: a) In system with neutral point normally earthed via Peterson coil with the "Highest System Voltage" Um=24kV (IEC Publication clause category 2). b) In system with neutral point solidly grounded, with the "Highest System Voltage" Um=36kV (IEC Publication 60183, clause 4.1 category 1). 2 - The IECo. catalogue Numbers The IECo. catalogue numbers vs relevant conductor cross-section: Table 1 Type of Cable Conductor Cross Section (mm 2 ) Rated Voltage (kv) IEC Cat. No. N2XS (F) 2Y 50 Cu 18/ N2XS (F) 2Y 150 Cu 18/ N2XS (F) 2Y 300 Cu 18/ NA2XS (F)2Y 150 Al 18/ NA2XS (F)2Y 300 Al 18/ NA2XS (F)2Y 50 Al 12/ NA2XS (F)2Y 240 Al 12/ N2XS (F)2Y 300 Cu 12/

4 Page No. 3 of Documents to be Supplied with the Proposal The Proposer shall submit all the following documents to the IECo. with the bid documents. 3.1 Complete and fill in Questionnaire ; 3.2 A complete Type Test Reports, according to Israeli standard IS , issued within the last 7 years preceding the date of the bid, for the proposed cable or for a similar* cable. 3.3 Certificate issued by the Standards Institution of Israel (SII) or any agreed accredited institution, attesting that the Manufacturer meets the requirements of the Israeli Standard IS for MV power cables (identical to IEC standard part 2) 3.4 Cross-section drawings including dimensions; 3.5 Approval of conformance with ISO 9001 requirements shall be in a form of a certificate issued by a Certification Body (CB) which is accredited by an Accreditation Body (AB). The certificate should bare the logo of the CB and of its AB and/or the logo of the IAF. The certificate shall be valid on the date set for submission of the proposal. The certificate shall be valid for the scope of activities requested in the request for proposal. 3.6 Document approving experience: the manufacturer actively produced and supplied at least 150 km of the proposed cable or similar* cable during a period of at least 3 years during the last 7 years preceding the date of the bid. Additionally, The Proposer shall submit reference list indicating the quantities of the cables manufactured and sold during these years; * Similar cable: Same construction, same conductor cross-section or bigger, the conductor may be either copper or aluminum. ** All the above documents shall be in English.

5 Page No. 4 of Standards 4.1 Standards referenced in this specification, and in supplements to this specification, form an integral part of this specification. 4.2 All the standards referred to the most current issue, including all amendments, and supplements, as of the date of the bid. 4.3 The cables that are provided under this specification, shall be designed, manufactured inspected, tested and preserved in compliance with the standards as specified herein. 4.4 Relevant standards: Israeli Standard IS 65 (IEC Publication 60228) "Conductors of Insulated Cables"; IEC Publication "Impulse Test on Cables & their Accessories" Israeli Standard (IEC ) "Extruded Solid Dielectric Insulated Power Cable for Rated Voltages from 1kV up to 30kV" IEC Publication "Common Test Methods for Insulating and Sheathing of Electric Cables " IEC Publication "Test Methods for Partial discharge Measurements on Length of Extruded Power Cables" IEC Publication Guide to the Short Circuit Temperature limits of Electric Cables with a Rated Voltage from 1.8/3 kv to 18/30 kv HD 620 part 5-C "Cross-linked PE Insulated Cables" HD 605 part A1 "Additional Test Method" DIN Delivery Drums In case of differences between the present specification and the above standards, the present specification is mandatory.

6 Page No. 5 of Technical Requirements 5.1 Operating Temperatures Maximum rated conductor temperature: 90 C Short circuit maximum conductor temperature (for duration up to 5 sec): 250 C The conductor temperature under emergency condition: 130 C for duration of 8 hours continuously. The total duration of such overloads may exceed 100 hours per annual. 5.2 Construction Conductor Material: The conductor shall consist of plain annealed copper / aluminum wires Form: The conductor shall be circular compacted stranded Dimensions: Table 2 hereafter sets out the cross-sectional areas and characteristics of the Table 2 Nominal Cross- Section (mm 2 ) conductors covered by this specification. Rated Voltage (kv) Diameter Range (mm) Minimum Number of Wires Max. DC Resistance at 20 0 C ( /km) 50 Cu 18/ Cu 18/ Cu 18/ Al 18/ Al 18/ Al 12/ Al 12/ Cu 12/

7 Page No. 6 of Conductor Screen The conductor screen shall consist of an extruded cross-linked semi-conducting compound layer (HD 620, part 5-c subclause 2.2). This inner-semiconducting layer shall not penetrate into the inner wire layers of the conductor and shall be easily removable during installation. The wall thickness of the inner-semiconducting layer shall be at least 0.3 mm The irregularities in the conductor screen, shall be of sizes specified in subclause 2.5 of the standard HD 620, part 5-c The Resistivity both before and after aging, shall not exceed 1000 m Insulation The insulation shall be of extruded cross-linked polyethylene (XLPE) The process of cross-linking or vulcanization may be achieved by any method except "Curing in Steam" process The nominal thickness, not including the thickness of any separator or semiconducting screen on the conductor and over the insulation, shall be 5.5 mm for cables with rated voltage U0/U = 12/20 kv and 8 mm for cables with rated voltage U0/U = 18/30 kv The average thickness of the insulation shall not be less than the specified nominal value The thickness at any place may however be less than the specified nominal value provided that the difference does not exceed 0.1 mm +10% of the specified nominal value (IEC , sub-clause ) Wall thickness difference of the insulation between the lowest and the highest values in one measured plane shall not exceed 0.9 mm (HD 620-5c).

8 Page No. 7 of The diameter over the insulation cover shall fall within the limit values specified in Table 3: Nominal Cross- Section (mm 2 ) Table 3 Rated voltage (kv) Nominal Thickness (mm) Minimum Insulation Diameter (mm) Maximum Insulation Diameter (mm) 50 Cu 18/ Cu 18/ Cu 18/ Al 18/ Al 18/ Al 12/ Al 12/ Cu 12/ The irregularities (voids, impurities) in the insulation shall not exceed 0.2 mm as specified in subclause 3.3 of standard HD 620 part 5-C.

9 Page No. 8 of Non-Metallic Insulation Screen The semi-conducting screen shall be applied directly over the insulation and shall consist of an extruded cross linked polyethylene. The semi-conducting screen shall be non-peelable (bonded) The maximum thickness of the semi-conducting screen shall be of 0.6 mm for all the cables covered by this specification The minimum thickness of the semi-conducting screen shall be of 0.3 mm for all the cables covered by this specification The diameter difference over the non-metallic insulation screen between the lowest and the highest value shall be maximum 0.5 mm The inner and the outer semi-conducting layers shall not present any surface roughness, it shall be smooth, and shall adhere perfectly to the insulation all along its periphery The electric Resistivity of the layers, both before and after aging, shall not exceed 500 m at 20 0 C Conductor screen, insulation and insulation screen shall be laid by triple extrusion process Semi-conductive Bedding Tape A swelling semi-conductive bedding tape shall be applied (lapped) all over the non-metallic insulation screen Metallic Screen A metallic screen shall be applied helical over the bedding semi-conductive tape. The screen shall consist of a concentric layer made of copper wires, bounded together with one or two copper tapes, having thickness of at least 0.1mm and a minimum cross-sectional area of l mm 2. The copper tape shall be applied helical so that the helix lay will not be greater than the cable diameter underneath the concentric layer of copper wires times 4.

10 Page No. 9 of The metallic screen dimensions and characteristics for each conductor shall be as specified in Table 4 hereafter of this specification. Table 4 conductor Cross- Sectional area [mm 2 ] Rated Voltage (Kv) Total Cross- Sectional Area of the Screen Wires [mm 2 ] Wires Minimum Diameter [mm] Max DC Resistance of the Screen at 20 0 C [ /km] 50 Cu 18/ Cu 18/ Cu 18/ Al 18/ Al 18/ Al 12/ Al 12/ Cu 12/ Watertight Measures The cables shall be longitudinally watertight protected on the screen area The watertight layer shall be made of special swelling tape Oversheath The oversheath shall be made of HDPE polyethylene compound, ST7 type (IEC publication table 4) The color of the oversheath shall be black The nominal thickness shall be 2.5 mm and the minimum thickness shall be not less than 2.03 mm for all the cables covered by this specification.

11 Page No. 10 of The external diameter of the oversheath shall fall within the limits specified in Table 5 hereafter: Table 5 Conductor Cross-Sectional area [mm 2 ] Rated Voltage (kv) Min. Oversheath Diameter [mm] Max. Oversheath Diameter [mm] 50 Cu 18/ Cu 18/ Cu 18/ Al 18/ Al 18/ Al 12/ Al 12/ Cu 12/

12 Page No. 11 of Tests 6.1 General Tests shall be performed in accordance with the requirements of Annex A of this specification and will meet the latest published recommendations of the standards prescribed under clause 4 of this specification, by and at the expense of the Contractor. In case that the Proposer has a type test of one of the said standards, he will complete the tests according to Annex A. 6.2 Type Tests 6.1 Type Test Within 3 months after from the date on which a binding contractual obligation has been created, the Contractor shall submit type test report that was performed on the first manufactured batch of the cable to be supply to the IECo. The type test shall be performed according to Annex "A" in an independent authorized laboratory (ISO/IEC or EN approved). The IECo. reserves the right to attend during the performance of the Type Test Exemption: If the Contractor had supplied identical cable to the IECo. during the last 7 years preceding the date of the present bid, and if the manufacturing method was not changed, the Contractor can introduce type test report if it was approved by the IECo. in the former supply. 6.2 Routine Tests The Contractor shall perform and submit test reports for all routine tests for each cable that is wrapped on each drum. The Contractor shall submit to IE Co. the routine test reports for approval prior to delivery of the cable The cable shall be delivered only after approval of the routine test report of the cable.

13 Page No. 12 of Acceptance Test Acceptance tests shall be performed according to the standards in para. 3 and shall include tests required in Appendix "B" In case that the cable under test will not fulfill all requirements specified in Appendix "B" the IECo. has the right to reject the consignment. 6.4 The tests shall be performed by and at the expense of the Contractor. The contractor shall make all the necessary arrangements to enable the IECo. s inspectors to be present at the tests. 6.5 The following data shall be indicated on each test certificate: Manufacturer's name; Name and address of the testing laboratory; Serial number of the test certificate; The certificate issue date; Test report of special test shall specify the pertained batch number of the cables; A signature of the person responsible for tests and his position. 6.6 The test certificate should contain results for each test according to the test requirements with reference to appropriate Clauses and Sub-clauses of standards and this specification.

14 Page No. 13 of Marking 7.1 Throughout whole cable length, at intervals not exceeding 100 cm, the following identification marks shall be indelibly imprinted in white color, embossed or by reproduction in relief on the outer sheath. a) Manufacturer s name or trade mark (logo) b) The structure: " N2XS (F) 2Y - l x (cross-sectional area in mm 2 ), 18/30 kv " c) Year of production d) "Property of the Israel Electric Corp." e) Running length (in meters) No. marked on each one of the cable ends (the first and the last No.) 7.2 The following data shall be printed legibly on a tag strongly attached onto each drum: f) Manufacturer's Name g) Manufacturer's Plant address h) The IECo. Order No. i) Drum Serial No. j) Manufacturing Date k) Cable Type l) Cross Sectional Area in mm2 m) Cable Length n) Gross Weight o) Cable Standard p) The IECo. Catalog No. q) The IECo. Specification No. (NPS-361)

15 Page No. 14 of Packaging 8.1 The cables shall be furnished in lengths of 500 (±5) meters wound on seaworthy metal drums. The cable on the drum shall be protected against damage by a suitable cover easy to remove, mounted around the drum flanges, so that the drum shall be closed from all sides. 8.2 The supplied drums shall be according to DIN with max. flange diameter 2240 mm and max. overall width 1200 mm. 8.3 The cable's ends shall be supplied with hermetically sealed with watertight caps that shall prevent the ingress of humidity and fine dust into the cable's ends. 8.4 COT attesting the purity and composition of the conductor raw material shall be attached to each consignment. 8.5 The loosed cable end shall be fastened to the drum's flange, with a proper steel band. 8.6 In order to install an electronic drum-locator device, a niche of 130 mm X 65 mm with depth of 20 mm should be carved out on the side of one of the wooden flanges (if relevant). 9- Quality Requirements For quality system and other specific quality requirements, see Appendix A: Q-APP-02. Bidder shall submit with his proposal the following (In English): Quality system Certificate; Quality manual; Certificates that demonstrate the Bidder's compliance with the requirements specified or implied in this specification; Example of an inspection & test plan and/or Quality plan which pertain to the cable to be supplied; Formal confirmation that he will conform to the requirements of Q-APP-02.

16 Page No. 15 of PROTOTYPE APPROVAL 10.1 Prototype approval for new suppliers. New supplier Supplier that didn t supply the ordered item to the IECorp. in the last five (5) years In a period of max three (3) months from the date on which a binding contractual obligation has been created, and before production for IEC of all ordered items, the Contractor shall perform Prototype Approval For purposes of the Prototype approval, the manufacturer shall perform the complete type tests as required in this specification The contractor shall be responsible to conduct successfully all the necessary tests, and to deliver to the Israel Electric Corp. all the necessary required reports, in a manner, which will not interfere with or delay any of the time schedules, pertaining to any action or undertaking, required of the winning bidder, including, but not limited to delivery schedule. Such responsibility shall include proper and reasonable advance notifications to the Israel Electric Corp., prior to any action, required of it. If type and special tests have already been conducted with reference to the identical cable which is offered by the proposed and the Israel Electric Corp. approves the reports, pertaining to such tests, the Israel Electric Corp. shall have a right (but not a duty) to waive all or part of the required tests The Israel Electric Corp. reserves the right to cancel the order for the supply of equipment if the prototype will not be approved by the Israel Electric Corp. In any case, the contractor shall not resume manufacture of the rest of the ordered equipment before receiving the Israel Electric final approval of the prototype Required schedule up to prototype approval (after notification of award) is attached in APPENDIX: "D".

17 Page No. 16 of Prototype approval for existing suppliers. Existing supplier Supplier who supplied the ordered item to the IECorp. in the last five (5) years Existing supplier is exempted from prototype if in the technical bid the supplier will provide to IE Corp. a letter with the following data: - The period and type of the ordered item supplied to IECorp. - A statement that was no any changes in the production line.

18 Page No. 17 of Questionnaire Tender No.: Subject Name of Proposer : Insert all data in this column Manufacturer s name and address: Specify the standards that the cable will comply with: 1 Cable 1.1 Coding 1.2 Rating voltage (U0/U) (kv) 1.3 Current rating (in soil having 1 km/w at 30 0 C at a load factor of 1.0 laying depth 0.7 m) (A) 1.4 Short circuit rating current for 1 sec duration (A) 1.5 Corona level (pc/kv) 1.6 Inductive resistance at 50 Hz (Ω /km) 1.7 AC effective resistance at 90 0 C (Ω /km) 1.8 Capacitance ( F/km) 2 Conductor 2.1 Material 2.2 Nominal cross-sectional area (mm 2 ) 2.3 Number and nominal diameter of wires (mm) 2.4 Designed diameter (mm) 2.5 Max DC resistance at 20 0 C (Ω/km)

19 Page No. 18 of Max permissible continuous temp. ( 0 C) 2.7 Max permissible Short circuit temp. ( 0 C) 3 - Conductor Screen 3.1 Material 3.2 Min thickness (mm) 3.3 Max electrical resistivity at operating temp. (Ohm/km) 3.4 The irregularities sizes (mm) 4 - Insulation 4.1 Material 4.2 Nominal thickness (mm) 4.3 Nominal diameter (mm) 4.4 Difference between lowest and highest value of wall thickness in one measured plain (mm) 4.5 Dielectric permeability 5 - Non-Metallic Insulation Screen 5.1 Material 5.2 Extruded layer peelable / non-peelable 5.3 Thickness (min max) (mm) 5.4 Max electrical resistivity at operating temp. (Ohm/km) 5.5 Difference between lowest and highest value of wall thickness in one measured plane (mm) 6 - Bedding semi-conductive tape is applied on the nonmetallic insulation screen (yes/no) 7 - Metallic Screen 7.1 Number and diameter of wires (mm) 7.2 Number, thickness and width of tapes (mm) 7.3 Nominal cross-sectional area (mm 2 ) 7.4 Electrical resistance at 20 0 C (Ω /km)

20 Page No. 19 of A swelling tape shall be applied over the metallic screen (yes/no) 9 - Outer Sheath 9.1 Material 9.2 Nominal thickness (mm) 9.3 Nominal diameter (mm) 9.4 Difference between lowest and highest value of wall thickness in one measured plane (mm) 9.5 Color 9.6 Marking embossed according subclause General Data 10.1 Cable weight (kg/m) 10.2 Permissible bending radius (m) 10.3 Permissible pulling force (kg) 11 - Drum 11.1 Type 11.2 Material 11.3 Weight of empty drum (kg) 11.4 Flange diameter (cm) 11.5 Barrel diameter (cm) 11.6 Overall Width (cm) 11.7 Gross weight (drum with cable) (kg) 11.8 Length of cable per drum (m) 12- Packing 12.1 A tag with all details as required in subclause 8.1 shall be attached (Yes/No) 12.2 The cable shall have sealing caps (Yes/No) 12.3 The drum shall be protected as required in clause 8.2 (Yes/No)

21 Page No. 20 of Attached Documents 13.1 Valid ISO 9001 certificate (Yes / No) 13.2 Catalogue (Yes / No) 13.3 Cable drawing (Yes / No) 13.4 Certificate issued by the Standards Institution of Israel (Yes /No) Proposer s address: address: Contact : Tel. No. : Cellular : Fax. No. : Date: Signature:

22 Page No. 21 of 25 Annex "A" TEST REQUIREMENTS for MEDIUM VOLTAGE CABLES

23 Page No. 22 of 25 Annex "B" SPECIFICATION for ACCEPTANCE TESTS of MEDIUM VOLTAGE CABLES Haifa - Israel

24 Page No. 23 of 25 ANNEX "C" ORGANIZATION, QUALITY AND SAFETY DIVISION QUALITY CONTROL UNIT APPENDIX FOR CONTRACTS / ORDERS REV. 4 Volume 03/ 2011 Spec. No. Q - APP - 02 QUALITY REQUIREMENTS

25 Page No. 24 of 25 Appendix. D Schedule for prototype approval

26 Page No. 25 of 25 APPENDIX "E" - STATEMENT OF MANUFACTURING EXPERIENCE I, (Enter name), do hereby state the following: 1. I am a position holder at ("The factory") occupying the position of (Enter job title and description, i.e. partner, production manager, sales manager, etc.) 2. I have been occupying this position since (Enter date). 3. I give this statement in regards to I.E.C Tender number ("The Tender"). 4. The facts/details given in this statement have been checked and verified by me. 5. (The factory) has actively produced and supplied at least 150 km of the proposed cable or similar* cable during a period of at least 3 years during the last 7 years prior to submission. * Similar cable: Same construction, same conductor cross-section or bigger, the conductor may be either copper or aluminum. 6. I hereby undertake to provide, upon IEC's request and at its sole discretion, any other documents (reference list, quantity,dates of supply, letter of recommendations etc ) or other information requested for this Tender for purposes of proving said experience. Signature Date

11-SDMS-03 REV. 02 SPECIFICATIONS FOR

11-SDMS-03 REV. 02 SPECIFICATIONS FOR 11-SDMS-03 REV. 02 SPECIFICATIONS FOR XLPE INSULATED POWER CABLES FOR RATED VOLTAGES FROM 15 KV UP TO 36 KV (U m ) This specification is property of SEC and subject to change or modification without notice

More information

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED)

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm 2 + 80mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of, 3C x95mm 2 +

More information

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES 1. Qualifying Requirement of AB Cable Manufacture/Supplier The manufacturer should have manufactured, successfully type tested

More information

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid. 1. Scope This specification defines the methods, the procedures and the requirements to verify the cables manufactured according to I.E.C. Specifications NPS361. 2. Standards All the standards referred

More information

JULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

JULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum. FOREWORD This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C, N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared

More information

Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES. 11 kv XLPE-Insulated Three-Core Underground Cables

Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES. 11 kv XLPE-Insulated Three-Core Underground Cables Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES ( Data Sheets ) 11 kv XLPE-Insulated Three-Core Underground Cables (3x240 mm 2 ) ADWEA/ADDC/AADC STANDARD : D-AAA-CAB-11-3Cx240

More information

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION)

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION) 012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 8051 Fax: +94 11 232 5387 CONTENTS Page 1.0

More information

REPORT OF PERFORMANCE TIC

REPORT OF PERFORMANCE TIC REPORT OF PERFORMANCE TIC 1580-13 OBJECT TYPE Three-core power cable 18/30(36) kv, 3x500 mm2, 2XWY(P)-FR XLPE Rated voltage, U 0/U (U m) 18/30 (36) kv Conductor material Cu Conductor cross-section 3x500

More information

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION December 2016 SPECIFICATION 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION

More information

1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured)

1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured) WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (A Govt. of West Bengal Enterprise) Office of the Chief Engineer, Procurement & Contracts Department Vidyut Bhavan, 4 th. floor, Bidhannagar,

More information

Technical Specification. for 1.1 KV Copper Control Cable

Technical Specification. for 1.1 KV Copper Control Cable WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (A Govt. of West Bengal Enterprise) Office of the Chief Engineer, Procurement & Contracts Department Vidyut Bhavan, 4 th. floor, Bidhannagar,

More information

76 / 132 (145) kv 1x1200 mm 2 CU/XLPE/CWS/AL/HDPE

76 / 132 (145) kv 1x1200 mm 2 CU/XLPE/CWS/AL/HDPE 09-1026 TYPE TEST CERTIFICATE OF COMPLETE TYPE TEST OBJECT single-core power cable TYPE 76 / 132 (145) kv 1x1200 mm 2 CU/XLPE/CWS/AL/HDPE Rated voltage, U o /U (U m ) 76/132 (145) kv Conductor material

More information

Medium Voltage Power Cables

Medium Voltage Power Cables N2XSY 6/0, /20, /30 NA2XSY 6/0, /20, /30 N2XS2Y 6/0, /20, /30 NA2XS2Y 6/0, /20, /30 N2XS(F)2Y 6/0, /20, /30 NA2XS(F)2Y 6/0, /20, /30 N2XSEY 3 x 6/0 Medium Voltage Power Cables Photo: HELUKABEL Q 47 Medium

More information

Date: / TECHNICAL SPECIFICATIONS FOR 11 KV XLPE INSULATED UNDERGROUND CABLES

Date: / TECHNICAL SPECIFICATIONS FOR 11 KV XLPE INSULATED UNDERGROUND CABLES 1 Date:19.09.2013/08.01.2014 TECHNICAL SPECIFICATIONS FOR 11 KV XLPE INSULATED UNDERGROUND 1.0 SCOPE: CABLES 1.1 The scope of this specification covers the design, manufacture, stage inspection at works,

More information

SANS 1339:2010 Electric cables Cross-linked polyethylene (XLPE) insulated cables for rated voltages 3,8/6,6 kv to 19/33 kv

SANS 1339:2010 Electric cables Cross-linked polyethylene (XLPE) insulated cables for rated voltages 3,8/6,6 kv to 19/33 kv DRAFT SOUTH AFRICAN STANDARD (DSS): PUBLIC ENQUIRY STAGE Document number: 66/1339/4 Reference: SANS 1339 Date of circulation: 2009-12-08 Closing date: 2010-02-08 Number and title: SANS 1339:2010 Electric

More information

001: 2007 CEB STANDARD

001: 2007 CEB STANDARD 001: 2007 CEB STANDARD ALUMINIUM RE-DRAW RODS FOR ELECTRICAL PURPOSES CEYLON ELECTRICITY BOARD SRI LANKA Specification for ALUMINIUM RE-DRAW RODS FOR ELECTRICAL PURPOSES CEB Standard 001: 2007 CEYLON ELECTRICITY

More information

XLPE CABLE (33KV) September Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

XLPE CABLE (33KV) September Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED XLPE CABLE (33KV) September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN: U40101WB2007SGC113474;

More information

SPECIFICATION FOR RUBBER INSULATING GLOVES FOR LOW VOLTAGE 500V

SPECIFICATION FOR RUBBER INSULATING GLOVES FOR LOW VOLTAGE 500V Page no.: 1 SPECIFICATION FOR RUBBER INSULATING GLOVES FOR LOW VOLTAGE 500V ( חתום Bar-David( Prepared by: I. Checked by: (חתום) Brodetsky.A ( חתום ( Liberman Approved by: N. Page no.: 2 Contents: 1. General

More information

EDS KV SINGLE CORE XLPE CABLES

EDS KV SINGLE CORE XLPE CABLES THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Document Number: EDS 02-0034 ENGINEERING DESIGN STANDARD EDS 02-0034 33KV SINGLE CORE XLPE CABLES Network(s): EPN, LPN,

More information

This Certificate consists of 75 pages in total.

This Certificate consists of 75 pages in total. Object Heat shrinkable indoor termination 1086-16 Type MZDNK-3-15-C Rated voltage, U 0 /U (U m ) 8,7/15 (17,5) kv Conductor material Cu Conductor cross-section 3 x 185 mm 2 Insulation material XLPE Manufacturer

More information

MV water-proof and water tree retardant power cable

MV water-proof and water tree retardant power cable MV water-proof and water tree retardant power cable 1 Standard GB/T16-8 1kV 35kV, IEC The products should be manufactured according to standard GB/T16-8 and also as per IEC, BS and HD as requested. 2 Application

More information

MESP TECHNICAL SPECIFICATION FOR MURL JUMPER WIRE HARD-DRAWN COPPER 19/ mm 2

MESP TECHNICAL SPECIFICATION FOR MURL JUMPER WIRE HARD-DRAWN COPPER 19/ mm 2 Engineering Specification Electrical Networks MESP 130400-07 TECHNICAL SPECIFICATION FOR Version: 1 Issued: February 2017 Owner: Engineering Division Approved By: Andrew Russack Head of Engineering (Electrical)

More information

MESP TECHNICAL SPECIFICATION FOR CATENARY WIRE HARD-DRAWN COPPER 37/ mm 2

MESP TECHNICAL SPECIFICATION FOR CATENARY WIRE HARD-DRAWN COPPER 37/ mm 2 Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR CATENARY WIRE HARD-DRAWN COPPER 37/2.5 181mm 2 Version: 3 Issued: February 2017 Owner: Engineering Division Approved By: Andrew

More information

MESP TECHNICAL SPECIFICATION FOR BARE FLEXIBLE ANNEALED COPPER JUMPER WIRE 37/7/ mm 2

MESP TECHNICAL SPECIFICATION FOR BARE FLEXIBLE ANNEALED COPPER JUMPER WIRE 37/7/ mm 2 Engineering Specification Electrical Networks MESP 130400-04 TECHNICAL SPECIFICATION FOR BARE FLEXIBLE ANNEALED COPPER JUMPER WIRE 37/7/0.70 100mm 2 Version: 2 Issued: February 2016 Owner: Engineering

More information

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL Issued by: Approved by: Engineering Department Energy+ Inc. September 2016 Shawn Jackson, P.Eng. Approval is given in accordance with

More information

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM Technical Specification of Back Clamp for LT Cross Arm (MS) Back clamp for LT Cross Arm made out of 50 x 6mm MS Flat suitable for 8m X 300 Kg PSC poles. After fabrication the cross arm shall be painted

More information

EDS KV TRIPLEX CABLE RATING

EDS KV TRIPLEX CABLE RATING Document Number: EDS 02-0027 Network(s): Summary: EPN, LPN, SPN ENGINEERING DESIGN STANDARD EDS 02-0027 11KV TRIPLEX CABLE RATING This engineering design standard provides the cable ratings and important

More information

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...

More information

SPECIFICATION FOR SAFETY POLE SIGNS & ACCESSORIES

SPECIFICATION FOR SAFETY POLE SIGNS & ACCESSORIES KP/3CB/TSP/0/00 04-09-9 Page of 9 TABLE OF CONTENTS 0. Circulation List 0. Amendment Record FOREWORD. SCOPE. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6. MARKING, LABELLING

More information

THE KENYA POWER AND LIGHTING CO. LTD. SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT

THE KENYA POWER AND LIGHTING CO. LTD. SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT THE KENYA POWER AND LIGHTING CO. LTD SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT NAME DESIGNATION SIGNATURE DATE Compiled by Ephantus Nyagah Ag. Senior Engineer Checked by Eng. Thagichu Kiiru Deputy

More information

NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations

NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations Version: 3.1 Date of Issue: September 2016 Page: 1 of 21 NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations 1. Purpose The purpose of this document is to detail the technical requirements

More information

Specification for pvc-insulated cables for electricity supply

Specification for pvc-insulated cables for electricity supply KENYA STANDARD KS 194: 2018 ICS 29.035.01 Specification for pvc-insulated cables for electricity supply (Third Revision, 2018) PUBLIC REVIEW DRAFT, FEBRUARY 2018 TECHNICAL COMMITTEE REPRESENTATION The

More information

EDS LV WAVEFORM MAINS CABLE RATINGS

EDS LV WAVEFORM MAINS CABLE RATINGS Document Number: EDS 02-0033 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 02-0033 LV WAVEFORM MAINS CABLE RATINGS EPN, LPN, SPN This standard details the technical and practical information required

More information

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994

More information

Tratos High Voltage cables

Tratos High Voltage cables March 2013 Tratos High Voltage cables Cables for a moving world www.tratos.eu Introduction High Voltage Cables Tratos is an international manufacturer and supplier of High & Extra High Voltage cable up

More information

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS 006: 2008 CEB SPECIFICATION COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS CEYLON ELECTRICITY BOARD SRI LANKA Specification for COMBINED METERING TRANSFORMERS (OUTDOOR TYPE) FOR

More information

Plant Client Contract Code Document ID Contract No. TECHNICAL SPECIFICATIONS DC SHUNT Rev 00 Page 1 of 2

Plant Client Contract Code Document ID Contract No. TECHNICAL SPECIFICATIONS DC SHUNT Rev 00 Page 1 of 2 TECHNICAL SPECIFICATIONS Rev 00 Page 1 of 2 0 IFI Release for Enquiry 14/12/18 SSS 14/12/18 HGG 14/12/18 RBU - Rev. Status Description Date Prepared Date Checked Date Approved AC Based on: PIN-QMC-03-F101

More information

079 : 2000 CEB STANDARD ALUMINIUM BINDING WIRE

079 : 2000 CEB STANDARD ALUMINIUM BINDING WIRE 079 : 2000 CEB STANDARD ALUMINIUM BINDING WIRE CEYLON ELECTRICITY BOARD SRI LANKA Specification for ALUMINIUM BINDING WIRE CEB Standard 079 : 2000 CEYLON ELECTRICITY BOARD No. 50, Sir Chittampalam A. Gardener

More information

EC 200 CHARACTERISTICS D A T A S H E E T. Kabelwerk EUPEN AG cable. M e c h a n i c a l c h a r a c t e r i s t i c s

EC 200 CHARACTERISTICS D A T A S H E E T. Kabelwerk EUPEN AG cable. M e c h a n i c a l c h a r a c t e r i s t i c s EC 200 EC200 - Rev. 3-23.06.11 Characteristic impedance 50 ± 2 Material copper wire Nominal capacity (pf/m) 80.5 Construction - Relative propagation velocity (%) 83 Diameter (mm) 1.05 Inductance (µh/m)

More information

TECHNICAL SPECIFICATION FOR. CONTACT WIRE HARD-DRAWN COPPER 161mm2

TECHNICAL SPECIFICATION FOR. CONTACT WIRE HARD-DRAWN COPPER 161mm2 Engineering Specification Electrical TECHNICAL SPECIFICATION FOR CONTACT WIRE HARD-DRAWN COPPER 161mm2 Version: 2 Issued: May 2018 Owner: Engineering Approved by: Andrew Russack, Head of Engineering Electrical

More information

MESP TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/ mm 2

MESP TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/ mm 2 Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/2.14 70mm 2 Version: 1 Issued: January 2015 Owner: Engineering Division Approved By: Pat

More information

MESP TECHNICAL SPECIFICATION FOR FLEXIBLE DROPPER WIRE TIN-BEARING COPPER 7/7/ mm 2

MESP TECHNICAL SPECIFICATION FOR FLEXIBLE DROPPER WIRE TIN-BEARING COPPER 7/7/ mm 2 Engineering Specification Electrical Networks MESP 130400-02 TECHNICAL SPECIFICATION FOR FLEXIBLE DROPPER WIRE TIN-BEARING COPPER Version: 1 Issued: November 2015 Owner: Engineering Division Approved By:

More information

High Voltage Instrumentation Cables for the ITER Superconducting Magnet Systems

High Voltage Instrumentation Cables for the ITER Superconducting Magnet Systems High Voltage Instrumentation Cables for the ITER Superconducting Magnet Systems Summary for Call for Nominations 1. Background and scope ITER will be the world's largest experimental facility to demonstrate

More information

Kerman & Kavian Cable Industries ( KCI )

Kerman & Kavian Cable Industries ( KCI ) KCI Kerman & Kavian Cable Industries ( KCI ) KCI Cables for control and instrumentation circuits 150/250 V (300 V) According to of IEC 60092-376 (2003) Electrical installations in ships - Part 376: Kerman

More information

POLYIMIDE INSULATED WIRES AND CABLES, LOW FREQUENCY, 600V, -200 TO +200 C BASED ON TYPE SPL. ESCC Detail Specification No.

POLYIMIDE INSULATED WIRES AND CABLES, LOW FREQUENCY, 600V, -200 TO +200 C BASED ON TYPE SPL. ESCC Detail Specification No. Page 1 of 23 POLYIMIDE INSULATED WIRES AND CABLES, LOW FREQUENCY, 600V, -200 TO +200 C BASED ON TYPE SPL ESCC Detail Specification Issue 3 May 2013 Document Custodian: European Space Agency see https://escies.org

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION 1. SCOPE : TECHNICAL SPECIFICATION FOR LIGHTNING ARRESTORS 1.1. This Specification covers design, manufacture, testing at manufacturer's Works, packing, supply, delivery of 42 KV

More information

ASSEMBLY TOOLS FOR SCREWS & NUTS. Part 1: Insulated hand operated socket drive wrenches and screw drivers

ASSEMBLY TOOLS FOR SCREWS & NUTS. Part 1: Insulated hand operated socket drive wrenches and screw drivers Doc. KP1/3CB/TSP/09/088-1 1 Page 1 of 21 TABLE OF CONTENTS 0.1 Circulation List 0.2 Amendment Record FOREWORD 1. SCOPE 2. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6.

More information

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS -1- INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION June 2013 SPECIFICATION No 150 kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS I. SCOPE This specification

More information

CERTIFICATE OF CONFORMANCE

CERTIFICATE OF CONFORMANCE CERTIFICATE OF CONFORMANCE This is to confirm that Honeywell Airports Business have verified Tinned Copper Braided Screened Primary Cable supplied by PT Jembo Cable Company Tbk (Indonesia) for airfield

More information

BBD7267 Version 1 PRIEVIEW COPY ONLY

BBD7267 Version 1 PRIEVIEW COPY ONLY INDEX SECTION CONTENTS PAGE 1.0 SCOPE 3 2.0 REFERENCES 3 3.0 APPENDICES 3 4.0 METHOD OF TENDERING 3 5.0 MATERIAL 3 6.0 MARKING 3 7.0 SIZE AND LENGTH 4 8.0 DRUMS AND WINDING 4 9.0 MARKING OF DRUMS 4 10.0

More information

P Low Voltage Catalogue Cables Australia Powering your Project

P Low Voltage Catalogue Cables Australia Powering your Project P +61 8 9367 8978 Low Voltage Catalogue Cables Australia Powering your Project CABLES AUSTRALIA PTY LTD LOW VOLTAGE CATALOGUE ABOUT US Cables Australia is a locally owned and operated distributor of high

More information

Cable Type 100. CAI Certification Specification

Cable Type 100. CAI Certification Specification Cable Type 100 CAI Certification Specification Ref: CAI-007-C / 100 / 12-2016 Confederation of Aerial Industries Ltd Communications House 41a Market Street WATFORD Herts WD18 0PN Tel: 01923 803030 Fax:

More information

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Cables

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Cables Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Cables NO: 452-1 Office

More information

TPS 49 EDITION 2 JUNE 2009

TPS 49 EDITION 2 JUNE 2009 TPS 49 EDITION 2 JUNE 2009 Interim arrangements & guidance on the interpretation of IEC 61672 Sound Level Meters - Periodic Tests CONTENTS SECTION PAGE 1 Purpose and duration 2 2 Statement 2 3 Specific

More information

TABLE OF CONTENTS FOREWORD... 3 INTRODUCTION SCOPE NORMATIVE REFERENCES... 4

TABLE OF CONTENTS FOREWORD... 3 INTRODUCTION SCOPE NORMATIVE REFERENCES... 4 TITLE SPECIFICATION FOR CRIMPED CONNECTING LUGS AND FERRULES PAGE: 1 OF 29 ISION DATE: SEPTEMBER 2014 TABLE OF CONTENTS Page FOREWORD... 3 INTRODUCTION... 4 1 SCOPE... 4 2 NORMATIVE S... 4 3 REQUIREMENTS...

More information

SECTION MEDIUM-VOLTAGE CABLES

SECTION MEDIUM-VOLTAGE CABLES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 13 MEDIUM-VOLTAGE CABLES SPEC WRITER NOTE: Delete between //-----// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

Cable Type 125. CAI Certification Specification

Cable Type 125. CAI Certification Specification Cable Type 125 CAI Certification Specification Ref: CAI-008-C / 125 / 12-2016 Confederation of Aerial Industries Ltd Communications House 41a Market Street WATFORD Herts WD18 0PN Tel: 01923 803030 Fax:

More information

Testing Manual for Electrical Equipment

Testing Manual for Electrical Equipment EPPM, Singapore, 20-21 Sep 2011 Abstract Testing Manual for Electrical Equipment Nahed Al-Hajeri 1 and Anantha Madhavan 2 Quality Assurance (QA) refers to a program for the systematic monitoring and evaluation

More information

INTERNATIONAL OIML R 103 RECOMMENDATION

INTERNATIONAL OIML R 103 RECOMMENDATION INTERNATIONAL OIML R 103 RECOMMENDATION Edition 1992 (E) Measuring instrumentation for human response to vibration (with reference to International Standards 8041 and 5347 of the International Organization

More information

DNVGL-CP-0400 Edition December 2015

DNVGL-CP-0400 Edition December 2015 CLASS PROGRAMME Type approval DNVGL-CP-0400 Edition December 2015 The electronic pdf version of this document, available free of charge from http://www.dnvgl.com, is the officially binding version. FOREWORD

More information

Notes 3 Explanatory Information 4-10

Notes 3 Explanatory Information 4-10 Low Voltage Cables Section Three SECTION THREE - LOW VOLTAGE CABLES PAGE Notes 3 Explanatory Information 4-10 Construction 4 Current Ratings 5 Rating Factors 6 Voltage Drops 8 Selection Procedures 10 Minimum

More information

Reactor and inductor are names used interchangeably for this circuit device.

Reactor and inductor are names used interchangeably for this circuit device. Recommended Design Criteria for Air-Cooled Reactor for Line and Track Circuits Revised 2015 (7 Pages) A. Purpose This Manual Part recommends design criteria for an air-cooled reactor for line and track

More information

Tests on Extruded Cables

Tests on Extruded Cables Tests on Extruded Cables Pierre Argaut Chairman of CIGRE SC B1 October 26 th, 2011 At least, once in your life, you have heard these words: Development Tests Long-term Tests Prequalification Tests Extension

More information

ELECTRICAL R&D LABORATORY SPECIFICATION FOR TESTS OF COMPRESSION AND MECHANICAL CONNECTORS AND TERMINAL LUGS FOR POWER CABLES WITH COPPER

ELECTRICAL R&D LABORATORY SPECIFICATION FOR TESTS OF COMPRESSION AND MECHANICAL CONNECTORS AND TERMINAL LUGS FOR POWER CABLES WITH COPPER Israel Electric Corp. Ltd. Strategic Resources Group Planning Development & Technology Division ELECTRICAL R&D LABORATORY SPECIFICATION FOR TESTS OF COMPRESSION AND MECHANICAL CONNECTORS AND TERMINAL LUGS

More information

TECHNICAL SPECIFICATION FOR G.I. WIRE AND G.I. STAY WIRE

TECHNICAL SPECIFICATION FOR G.I. WIRE AND G.I. STAY WIRE WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED OFFICE OF THE MATERIAL CONTROLLER : CENTRAL STORES & PURCHASE DEPARTMENT VIDYUT BHAVAN (4TH FLOOR) : BIDHANNAGAR : KOLKATA-700091 TECHNICAL SPECIFICATION

More information

VOLUME - 4 (GENERAL TECHNICAL SPECIFICATIONS)

VOLUME - 4 (GENERAL TECHNICAL SPECIFICATIONS) TENDER DOCUMENT NIT No. DLI/C&E/WI-665/535R FOR Tender for Supply of 3CX185 mm2, 11 KV (UE) grade, Power Cable for Augmentation of Raw Material Handling Receipt and Handling Facilities with new OHP Part

More information

EXTREMELY LOW MAGNETIC FIELD (ELMF) XLPE INSULATED CABLES, TYPE N2XY/FR1 0.6/1 KV

EXTREMELY LOW MAGNETIC FIELD (ELMF) XLPE INSULATED CABLES, TYPE N2XY/FR1 0.6/1 KV CABLE DESCRIPTION Single- or multi-phase electric cable for creating a weak external magnetic field,so as to obtain a cable wherein at last one of the conductors is assembled from two or more insulated

More information

NPS/002/003 Technical Specification for Protection Tile, Protection Tape, Cable Ducting and Route Markers

NPS/002/003 Technical Specification for Protection Tile, Protection Tape, Cable Ducting and Route Markers Version: 6.0 Date of Issue: March 2018 Page: 1 of 21 NPS/002/003 Technical Specification for Protection Tile, Protection Tape, Cable Ducting and Route Markers 1. Purpose The purpose of this specification

More information

TECHNICAL DATA SHEET FOR Single Mode Optical Fibre Cable Direct Burial Application

TECHNICAL DATA SHEET FOR Single Mode Optical Fibre Cable Direct Burial Application TECHNICAL DATA SHEET FOR Single Mode Optical Fibre Cable Direct Burial Application (SM 12 Fibers) Product: Single Mode Optical Fiber Cable Customer: Date: Write by: Kevin Zhou / technical engineer International

More information

GLOBAL STANDARD Page 1 of 66 UNDERGROUND MEDIUM VOLTAGE CABLES UNDERGROUND MEDIUM VOLTAGE CABLES

GLOBAL STANDARD Page 1 of 66 UNDERGROUND MEDIUM VOLTAGE CABLES UNDERGROUND MEDIUM VOLTAGE CABLES GLOBAL STANDARD Page 1 of 66 Countries I&N Argentina Brazil Chile Colombia Italy Peru Romania Spain R. De Antoni V. Robadey D. Gonzalez J. C. Gomez L. Giansante R. Sanchez V. Obrejan J. Gonzalez Elaborated

More information

CUSTOM DESIGN COAXIAL CABLES BY SICAB

CUSTOM DESIGN COAXIAL CABLES BY SICAB CUSTOM DESIGN COAXIAL CABLES BY SICAB. COAX RG 58 C/U Application: Coaxial Cable 50 Ohm For indoor installation as well as in industrial areas in conduits and cable ducts, for transmission of high frequency

More information

THE PATHWAY TO POWER HIGH-VOLTAGE CABLES

THE PATHWAY TO POWER HIGH-VOLTAGE CABLES THE PATHWAY TO POWER HIGH-VOLTAGE CABLES TABLE OF CONTENTS HIGH-VOLTAGE CABLES 3 Advantages of XLPE-insulated cable systems 3 PROPOSAL 4 Cable systems 4 Providing System Solutions 4 Continuous temperature

More information

شركة الوقت للكهرباء والمقاوالت ذ.م.م.

شركة الوقت للكهرباء والمقاوالت ذ.م.م. CONTRACTING COMPANY W.L.L. is a leading corporate in the United Arab Emirates offering quality services in the field of High Voltage Electrical work 400, 132 & 33 kv and Medium Voltage Power Distribution

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 1. Introduction Fault location on communication and power cables

More information

Signal converter for electromagnetic flowmeters

Signal converter for electromagnetic flowmeters Quick Start Signal converter for electromagnetic flowmeters Electronic revision: ER 3.0.xx The documentation is only complete when used in combination with the relevant documentation for the flow sensor.

More information

TwenCombi Cat-5E FTP(3x) - Coax 9 - EIBA - tube PE 5 mm

TwenCombi Cat-5E FTP(3x) - Coax 9 - EIBA - tube PE 5 mm name: TKF article number: 10305 description Nr.: POE- PS- 10305 PT F F F 800 B C 1 2 3 4 5 6 7 Assembly: 1. Primary tube 5 mm 2. CAT 5 E FTP cable 3. CAT 5 E FTP cable 4. Bus cable 5. Coax 9 cable 6. Separation

More information

50-SDMS-01 SPECIFICATIONS FOR

50-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR CURRENT TRANSFORMERS UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice C O N T E N T S CLAUSE TITLE PAGE NO. ------------ --------

More information

ECP HV INSULATION TESTING

ECP HV INSULATION TESTING Document Number: ECP 11-0006 Network(s): Summary: All ENGINEERING COMMISSIONING PROCEDURE ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing of new and

More information

INTRODUCTION NUHAS OMAN QUALITY & RELIABILITY.

INTRODUCTION NUHAS OMAN QUALITY & RELIABILITY. INTRODUCTION Nuhas Oman LLC, an integral part of The Al Bahja Group of Companies, is a Quality producer of: HV, MV and LV Cables Enamelled Copper Wires Oxygen Free Continuous Cast Copper Wire Rods Drawn

More information

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT

More information

HO7RN-F 450/750V BS EN Highly Flexible Rubber Cable

HO7RN-F 450/750V BS EN Highly Flexible Rubber Cable Rubber Insulation and Rubber Sheathed Application Range Heavy duty flexible cables for medium mechanical stress For dry and wet applications Can be used for domestic electric tools According to HD 516

More information

METRISO. Analog Insulation, Low Resistance and Voltage Measurement Instrument /9.14

METRISO. Analog Insulation, Low Resistance and Voltage Measurement Instrument /9.14 3-349-813-3 1/9.14 Insulation measurement per EN 61557-2/VDE 413, part 2 Test voltages: 5 V, 1 V, 25 V, 5 V and 1 V Analog display of measured values and limit values Intelligent filter precise and measurement-dependent

More information

Electric cables. Cranes

Electric cables. Cranes Electric cables. Cranes Electric cables for mobile connections. Aristoncavi spa reserve the right to modify the data in this catalogue without notice. 01/2012 Copyright Drawings and technical descriptions

More information

INDEX OF REVISIONS DESCRIPTION AND/OR AFFECTED SHEETS

INDEX OF REVISIONS DESCRIPTION AND/OR AFFECTED SHEETS E&P Pag. 1 / 14 Pre-salt Standard Steel Tube Umbilical Types Umbilical Electrical Cable Element DPT-SUB/ES/DCT INDEX OF REVISIONS REV DESCRIPTION AND/OR AFFECTED SHEETS 0 Original ORIGINAL REV. A REV.

More information

STANDARD SPECIFICATION FOR INSTRUMENT CABLES AND RELATED ACCESSORIES DOCUMENT NO : 44-LK /J.02/0014-A4

STANDARD SPECIFICATION FOR INSTRUMENT CABLES AND RELATED ACCESSORIES DOCUMENT NO : 44-LK /J.02/0014-A4 Page 1 of 12 STANDARD SPECIFICATION FOR INSTRUMENT CABLES DOCUMENT NO : 44-LK-5100-00/J.02/0014-A4 Rev No. Issue Date Pages Rev Description Prepared A 12-08-08 12 Issued for Comments / Approval By Checked

More information

CAT 5e UTP Cable: NETSET BOX [305m], indoor

CAT 5e UTP Cable: NETSET BOX [305m], indoor Code: E08_05 CAT 5e UTP Cable: NETSET BOX [05m], indoor NETSET BOX UTP 5e Ethernet cable far exceeds the requirements for Category 5e twisted pair cables. View of the cable box - inside 05m of the cable.

More information

United Nations Development Programme

United Nations Development Programme Tax on Price Quotation Payment Terms (max. advanced payment is 20% of total price) must be inclusive of VAT and other applicable indirect taxes must be exclusive of VAT and other applicable indirect taxes

More information

a Nexans company Catalogue 2009

a Nexans company Catalogue 2009 a Nexans company Catalogue 009 EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium voltage

More information

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS 1.0 SCOPE 2.0 BONDING METHODS 2.1 Introduction 2.2 Design 2.3 Single-Point Bonding 2.4 Cross Bonding 2.5 Sheath Sectionalizing Joints 2.6 Sheath Standing Voltage 2.7 Sheath Voltage at Through Fault 2.8

More information

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD. Our Ref.: 14/2018- Date : Messrs: Dear sir, Tender 14/2018 11& 33 KV Lightning Arrestors. You are kindly requested to quote for the supply and delivery to our stores in Shufat Jerusalem, (DDP) of the following

More information

IEC Standard Caledonian Offshore & Marine Cables

IEC Standard Caledonian Offshore & Marine Cables Power Copper s According to IEC 60228 Tinned conductors Cross section cl.2 cl.5 Cross section cl.2 cl.5 mm² Ohm/km Ohm/km mm² Ohm/km Ohm/km 1.0 18.2 20 70 0.270 0.277 1.5 12.2 13.7 95 0.195 0.210 2.5 7.56

More information

Y-CY-JZ flexible, CU-screened, transparent, EMC-preferred type, meter marking

Y-CY-JZ flexible, CU-screened, transparent, EMC-preferred type, meter marking Y-CY-JZ flexible, CU-screened, transparent, EMC-preferred type, meter marking A Technical data Special PVC control cables, adapted to DINVDE0 part3 Temperature range flexing -5 C ) to +0 C fixed installation

More information

LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED LIGHTNING ARRESTOR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, SectorII, Bidhannagar, Kolkata 700091. CIN: U40101WB2007SGC113474;

More information

COPPER + LWL RAW CABLES

COPPER + LWL RAW CABLES COPPER + LWL RAW Twisted Pair Cables... 112 TV/SAT Cables... 116 Fiber Optic Raw Cables... 120 DIGITUS CAT 7 twisted pair installation cable 4x2xAWG23 S-FTP CAT 7 1000 MHz LSZH installation cable For installation

More information

SECTION - II BID DATA SHEET

SECTION - II BID DATA SHEET SECTION - II BID DATA SHEET Kenya Power and Lighting Company II - 1 Contract: A36 SECTION -II BID DATA SHEET The following bid-specific data for the plant and equipment to be procured shall amend and/or

More information

MEDIUM VOLTAGE TERMINATIONS CATALOGUE 2017

MEDIUM VOLTAGE TERMINATIONS CATALOGUE 2017 MEDIUM VOLTAGE TERMINATIONS CATALOGUE 01 NEXANS NETWORK SOLUTIONS DIV. EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated

More information

EI HIGH VOLTAGE INSULATION TESTING POLICY

EI HIGH VOLTAGE INSULATION TESTING POLICY Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and

More information

SECTION WIREWAYS FOR RADIOLOGY EQUIPMENT

SECTION WIREWAYS FOR RADIOLOGY EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 36 WIREWAYS FOR RADIOLOGY EQUIPMENT SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable

More information

(R) Aerospace First Article Inspection Requirement FOREWORD

(R) Aerospace First Article Inspection Requirement FOREWORD AEROSPACE STANDARD AS9102 Technically equivalent to AECMA pren 9102 Issued 2000-08 Revised 2004-01 REV. A Supersedes AS9012 (R) Aerospace First Article Inspection Requirement FOREWORD In December 1998,

More information

Substation HV Cables. Document Number: 1-11-FR-07

Substation HV Cables. Document Number: 1-11-FR-07 Substation HV Cables Document Number: 1-11-FR-07 VERSION 1.0 June 2018 This functional requirements document is in line with the organisation's 1-11-ACS-07 Substation HV Cables Asset Class Strategy Intellectual

More information