MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

Size: px
Start display at page:

Download "MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER"

Transcription

1 Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION

2 Approval Amendment Record Approval Date Version Description 15/07/ Initial Issue. Supersedes parts of L1-CHE-SPE-024(1). 11/08/ Revised to include inrush and efficiency requirements. Tapping, lifting and size requirements clarified. Errors corrected and wording clarified throughout. 14/10/ Winding vectors revised. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 2 of 15

3 Table of Contents 1 Purpose Scope Acronyms and Abbreviations Definitions References & Legislation Standards Latest Issues and Amendments Background General Requirements Operating Conditions Service Conditions Electrical Conditions Ratings & Configurations Winding Connection Construction Transformer Enclosure & Cooling - Dry Type Transformer Transformer Cooling and Other Requirements - Oil Type Transformer Primary Terminals Secondary Terminals Earthing Terminal Painting Lifting Facility Size Rating Plate Testing Type Test Routine Tests Test Certificates Documentation and Support Documentation Requirements Design Drawings Drawing Format Technical Maintenance Plan Maintenance Manual Installation Instruction Manual Appendices Appendix A Design Management Requirements Appendix B Technical Data Schedule Form PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 3 of 15

4 1 Purpose This document is the technical specification for an Essential Services Supply Step Up Transformer, for use in MTM substations. 2 Scope This document applies to the supply of a Power Transformer to supply the MTM Essential Services Distribution System or 2.2kV Signal Power Distribution System from a 400V UPS backed supply in a substation installation as part of the MTM Electrical Network. This Transformer may be integral to the UPS assembly, or separately supplied and installed within the substation. 3 Acronyms and Abbreviations AC Alternating Current ACCB Alternating Current Circuit Breaker AS Australian Standard HV High Voltage MTM Metro Trains Melbourne Pty. Ltd. 4 Definitions For all technical terms refer to AS Essential Services Shall Should Refers to services, apparatus and systems described in L1-CHE-SPE-154. Also refers to the power distribution system supplying these services. Is used as the descriptive word to express a requirement that is mandatory to achieve conformance. Is used as the descriptive word to express a requirement that is recommended in order to achieve compliance. Should can also be used if a requirement is a design goal but not a mandatory requirement. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 4 of 15

5 5 References & Legislation 5.1 Standards The Transformer shall comply with all relevant Standards, including: AS AS 1767 AS 2374 Power Transformers Insulating Liquids Specification for Unused Mineral Insulating Oils for Transformers & Switchgear Power Transformers Note: All materials and components shall comply with the relevant Australian Standard or, where these do not exist, with the relevant IEC or EN Standard. 5.2 Latest Issues and Amendments Reference to all standards shall be read as a reference to the latest edition of that standard and amendments available at the time of tendering. 6 Background The Transformer will be used for the purpose of converting power from the 400V output of a dual convertor UPS to the Essential Services Distribution System or Signal Power Distribution System voltage for Essential Services purposes. The Essential Services Distribution System standard is a 3.3kV three phase 50Hz system, in phase with the 22kV system. Other legacy signal power distribution systems exist, including: 2.2kV single phase, 50 Hz, two wire unearthed, in phase with 22kV white-blue phase 1kV three phase, 50 Hz, earthed, leading 22kV system by 30 degrees 650V single phase, 50 Hz, two wire unearthed, in phase with 22kV white-blue phase Due to the varied installations, a scope of works document will detail specific requirements including but not limited to: Secondary Voltage (or equivalent table of ratings to that shown in section 9) Rated Power Indoor or outdoor installation Type of primary and secondary terminals required Oil insulated or dry type The Essential Services Step Up Transformer forms part of the Essential Services Power Supply system, as shown in Figure 1. 7 General Requirements The Transformer shall be designed and manufactured to give the highest level of reliability whilst requiring the minimum level of maintenance under continuous operating conditions. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 5 of 15

6 22kV Bus 22kV/400V Dyn1 Substation Earth 400V Bus 400V 3 phase UPS Substation L&P 400V Board Static Switch Battery Isolator Synchronisation Logic Battery Bank Manual Bypass Switch Step Up Transformer Essential Services / Signal Switchgear Synchronisation Signal Synchronisation Signal Figure 1: UPS System Interconnections PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 6 of 15

7 8 Operating Conditions 8.1 Service Conditions The service conditions in AS shall be applied except that the maximum ambient temperature shall be taken as 45 C. The air may be slightly polluted by dust. Transformers designated for indoor installation will be mounted on a concrete floor inside a substation building or suitable annex. Transformers designated for outdoor installation will be mounted on a concrete slab, unprotected from the weather. 8.2 Electrical Conditions Supply to the primary winding of the Transformer will be taken via a circuit breaker or fuse from a 400V 3 phase 50Hz supply. The secondary winding will be connected to an ACCB forming part of an Essential Services Switchgear Assembly. The transformer may be subject to significantly unbalanced load, including no load on one phase at all. 9 Ratings & Configurations This specification covers the Essential Services Distribution System and 2.2kV signal power distribution system. The specific ratings and characteristics of each of these are listed in the table below: Type 2.2kV 3.3kV Phases 3 3 Rated Primary Voltage 400V 400V Rated Secondary Voltage 2200V 3300V Standard Values of Rated Power (specified at the time of purchase) 60kVA 120kVA 180kVA 60kVA 120kVA 180kVA Rated Frequency 50Hz 50Hz Primary winding highest voltage for equipment <1.1kV <1.1kV Secondary winding highest voltage for equipment 3.6kV 3.6kV Rated Primary short-duration power frequency withstand voltage 10kV RMS 10kV RMS Rated Primary lightning impulse withstand voltage 20kV peak 20kV peak Rated Secondary short-duration power frequency withstand voltage 10kV RMS 10kV RMS Rated Secondary lightning impulse withstand voltage 20kV peak 20kV peak Earthing of Secondary Unearthed TBA Maximum Sound Power Level Reduced Reduced Level Level Winding Vector (Secondary/HV winding in upper case, Primary/LV in lower case) YNd11 YNd pf 5% 5% Percentage Impedance 4% 4% Maximum Inrush 8x I r 8x I r Minimum Power Efficiency (in accordance with AS ) 97% 97% PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 7 of 15

8 10 Winding Connection Five taps on the secondary (HV) windings shall be provided for the following range: +5.0%; +2.5%; 0%; -2.5%; -5.0%. Alternative tapping arrangements may be considered if suitable for the particular installation and approved by the Head of Engineering Electrical. The selection of the tapping shall be off-load. The tap changing device shall have a continuous rating of 100% of the Transformer full load current. For oil type transformers, the tap position shall be selected by a robustly constructed, external, pad-lockable, manually operated, spring-loaded selector switch, suitable for operation by hand without the use of special tools. The switch positions shall be labelled. For dry type transformers, the tap position may be selected either as described above, or by moveable connection links located on each of the primary windings. Each of these links shall be constructed from a single section of suitable conductor and shall be capable of making all tap settings. The tap links shall be located behind a securely bolted panel. 11 Construction 11.1 Transformer Enclosure & Cooling - Dry Type Transformer The Transformer shall be enclosed by a ventilated metallic enclosure cooled by naturally circulated external air. The enclosure should be suitable for indoor or outdoor installation, unless integral to the UPS in which case it may be suitable for indoor installation only. The transformer shall be naturally cooled - it shall be Class AN. The enclosure shall provide a minimum ingress protection of IP 21 for indoor installations, or IP 43 for outdoor installations, in accordance with AS Transformer Cooling and Other Requirements - Oil Type Transformer The oil preservation system can be freely breathing or sealed type. The transformer shall be naturally cooled (ONAN). The insulating oil shall comply with AS and shall not contain any Polychlorinated Biphenyl (PCB). An oil test for PCB content shall be performed by an independent NATA certified laboratory, and the test results provided to MTM prior to delivery. A concentration of PCB greater than one part per million will result in rejection of the transformer. The transformer shall be equipped with the standard fittings as described below: Oil gauge Drain valve 25mm nominal bore pipe thread with flanged plug Oil filling hole and cap Breathing device of weatherproof type, which may also be used as a filling hole Thermometer pocket Where a fully sealed transformer is offered the oil gauge and thermometer pocket need not be included. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 8 of 15

9 11.3 Primary Terminals The primary terminals shall be one of three configurations as outlined in the table below: Configuration Primary Enclosed Requirements An accessible air insulated cable box shall be provided, suitable for the connection of an insulated cable rising from below. The cable may be up to 50mm 2 of the copper insulated type and will be terminated with appropriate lugs for connection to the bushings. If required, appropriate cable supports shall be provided within the enclosure such that the weight of the output cable is not taken by the electrical connections. Primary Direct Termination For dry type transformers only, the secondary cable shall be terminated directly onto the windings. Appropriate cable supports shall be provided within the enclosure such that the weight of the output cable is not taken by the electrical connections 11.4 Secondary Terminals The secondary terminals shall be located on the opposite side of the transformer enclosure to the primary terminals. The terminals shall be suitable for directly connecting to appropriately terminated LV cables, suitably sized for the rating of the transformer. The secondary terminals shall be one of three configurations as outlined in the table below: Configuration Secondary Enclosed Secondary Direct Termination Requirements An accessible air insulated cable box shall be provided, suitable for the connection of an insulated cable rising from below. The cable may be up to 50mm 2 of the copper insulated type and will be terminated with appropriate lugs for connection to the bushings. If required, appropriate cable supports shall be provided within the enclosure such that the weight of the output cable is not taken by the electrical connections. For dry type transformers only, the secondary cable shall be terminated directly onto the windings. Appropriate cable supports shall be provided within the enclosure such that the weight of the output cable is not taken by the electrical connections 11.5 Earthing Terminal The transformer frame shall be directly connected to the substation earth. Two pre-drilled M12 holes shall be provided on opposite sides of the transformer for this purpose. Each enclosure door (where fitted) shall be adequately connected to the main enclosure by copper earth braids, one located at the top and the other at the bottom of each door. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 9 of 15

10 11.6 Painting Dry type transformer - The enclosure shall be properly prepared and painted so as to be suitable for outdoor installation irrespective of designated installation location. Oil Insulated Transformer - The transformers external tank shall be properly prepared and hot dip galvanised. The final colour coat shall be light grey as described by AS 2700S:2011 (N35), and the transformer shall be supplied with touch-up paint Lifting Facility 11.8 Size The Transformer shall be fitted with a facility for lifting and moving by both a crane and a forklift. The transformer and enclosure shall be as compact as possible Rating Plate The Transformer Rating Plate shall comply with the requirements of AS The tap link connections and positions or tap changer positions shall be clearly shown on the rating plate The rating plate shall be constructed of stainless steel and shall be securely riveted to the body of the transformer. Recorded information shall be physically etched, embossed or engraved clearly onto the surface of the rating plate and shall be highlighted with black paint. 12 Testing 12.1 Type Test A Type Test Certificate from a design which is representative of the Transformer to be supplied shall be provided with the Tender documentation Routine Tests All routine tests as described in Clause 10 of AS :2005 shall be performed on the Transformer at the manufacturer s factory. MTM reserves the right to appoint a representative to witness these tests. Seven working days notification shall be given to MTM of intention to carry out factory testing Test Certificates The results of all tests shall be recorded on test certificates. The test certificates shall clearly show the performance of the equipment and shall be accompanied by tables showing the actually measured values and all calculations. The test certificates shall be forwarded to MTM and the results approved by MTM prior to delivery. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 10 of 15

11 13 Documentation and Support 13.1 Documentation Requirements All documentation shall be provided in English. One electronic and eight paper copies of the each document shall be provided and the content shall be identical in each copy. Every page of the documentation shall be clearly identified in relation to the document to which it belongs and the version of that document. All pages of multi-page documents shall be uniquely numbered. It shall be possible to readily determine if all pages of a document are present. Manuals shall be A4 size and shall be bound in durable covers or in 4-D ring binders Design Drawings The following drawings must be supplied: Construction details of the Transformer including dimensions. Physical layout and arrangement of the components of the Transformer. Mounting requirements for the Transformer. Physical layout and arrangement of the primary and secondary terminals. Drawings of the Transformer Rating Plate and data All other drawings required for Installation, Testing, Commissioning, Operation and Maintenance 13.3 Drawing Format All drawings must comply with the PTV Infrastructure Drafting Standard and shall be submitted for MTM approval prior to manufacturing. Files shall be provided in Microstation format on compact disk (CD) Technical Maintenance Plan A Technical Maintenance Plan which establishes the maintenance policy for the Transformer recommended by the supplier shall be provided. This shall detail the preventative servicing schedules and maintenance intervals and latitudes for all components and systems of the Transformer. The servicing schedules shall reference appropriate detailed instructions in the maintenance manual. The Technical Maintenance Plan shall contain a list of any recommended spare parts, detailing price, supplier and procurement lead-times. The Technical Maintenance Plan shall detail safe disposal procedures applicable for when the Transformer is no longer serviceable (recycling, hazardous waste etc.). PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 11 of 15

12 13.5 Maintenance Manual The Maintenance Manual shall detail: All of the servicing activities. Any overhaul instructions. The adjustment procedures. The changing of components for repairs, and Fault-finding procedures. Spares support schedule The Maintenance Manual shall also include a complete set of as-built drawings and a comprehensive parts list for the Transformer Installation Instruction Manual An Installation Instruction Manual shall be provided and shall contain instructions which will enable the Transformer to be properly installed, tested and commissioned. This shall include all necessary drawings. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 12 of 15

13 14 Appendices Appendix A Design Management Requirements This appendix describes the documentation which should be provided as a minimum at each stage of the procurement process. The documentation shall comply with the specifications above. Tender Submission The following documents shall be provided as part of the tender submission: General Arrangement drawing of the Transformer which clearly shows: The overall dimensions of the Transformer and details of the enclosure Details of the proposed primary terminations Details of the proposed secondary terminations Type Test Certificates The Technical Data Schedule in Appendix B filled in. Contract Documentation One set of PDF copies of the drawings and documentation as described in Clauses 13.2 and 13.6 and any additional documentation detailing the design should be provided for review and approval by MTM four weeks after the Contact Award Date. No manufacture shall commence until the drawings have been approved. An allowance of five working days should be made by the supplier for the review and approval of submitted drawings Pre-Delivery Documentation As part of the deliverables, the supplier shall provide five hard copies of the following documents: Technical Maintenance Plan Installation Instruction Manual Maintenance Manual Storage, handling, loading and off-loading instructions Test results Approved drawings as listed in 13.2 In addition, the supplier shall provide copies of the As Built layouts and Schematic drawings in electronic format (PDF and Microstation) PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 13 of 15

14 Appendix B Technical Data Schedule Form The Tenderer shall supply the following information and guaranteed performance thereof. Compliance Does the Transformer fully comply with this specification? Yes No Is a Type Test Certificate attached? Yes No Is a general arrangement sketch attached? Yes No Type Oil Dry Winding Vector Rated Power Primary winding (kva) Rated Voltage Primary windings (V) Secondary windings (V) Rated Current Primary windings (A) Secondary windings (A) Inrush current (A) Rated Insulation Level Primary Power Frequency Withstand Voltage (kv) Primary Impulse Withstand Voltage (kv) Secondary Power Frequency Withstand Voltage (kv) Secondary Impulse Withstand Voltage (kv) Impedance & Regulation Percentage Impedance at Rated Primary Power (%) Regulation at 0.6 power factor Losses Iron Loss (at Rated Primary Voltage) (W) Copper Loss (at Rated Primary Current) (W) Power Efficiency at 50% load and unity power factor (%) Tap Changer Manufacturer Type Voltage Rating (V) Current Rating (A) PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 14 of 15

15 Oil Type only Volume of Oil (L) Is the Transformer freely breathing? Yes No Is a Conservator fitted? Yes No Is the Transformer a sealed-tank system with gas cushion? Yes No Is the Transformer a sealed, completely filled system? Yes No Tank or Enclosure Thickness (mm)... Enclosure Overall Length (mm) Overall Width (mm) Overall Depth (mm) Enclosure material Enclosure thickness (mm) Enclosure finish / colour Weight Mass of Core and Windings (kg) Total mass (kg) Primary Terminals Manufacturer Type Voltage Rating (V) Current Rating (A) Height above base of enclosure (mm) Cable box dimensions (if applicable) (mm) width (mm) depth (mm) height Secondary Terminals Manufacturer Type Voltage Rating (V) Current Rating (A) Height above base of enclosure (mm) Cable box dimensions (if applicable) (mm) width (mm) depth (mm) height PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 15 of 15

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Engineering Specification Head of Electrical Engineering MESP 050100-01 TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Version:

More information

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...

More information

MESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER Version: 3 Issued: February 2018 Owner: Head of Engineering - Electrical Approved By: Andrew Russack Head

More information

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor

More information

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP) Discipline Engineering Standard NSW Category Electrical Title Substation Auxiliary Transformer from Rectifier Transformer Secondary Reference Number PDS 01 (RIC Standard: EP 05 00 00 01 SP) Document Control

More information

Distribution transformers Part 2 Ground mounted transformers not closecoupled

Distribution transformers Part 2 Ground mounted transformers not closecoupled PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Technical Specification 35-1 Distribution transformers Part 2 Ground mounted transformers not closecoupled www.energynetworks.org PUBLISHING

More information

Reference Number PPS 05 - (RIC Standard: EP SP)

Reference Number PPS 05 - (RIC Standard: EP SP) Discipline Engineering Standard - NSW Category Electrical Title Low Voltage Isolating Transformer Reference Number PPS 05 - (RIC Standard: EP 17 00 00 11 SP) Document Control Status Date Prepared Reviewed

More information

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date

More information

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1 GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS PURCHASE SPECIFICATIONS OF 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS SPECIFICATION NO. : OR12423 REVISION NO. : Rev 00 DATE : 01.03.2011 DISTRIBUTION : PI - 4 copies O/C - 1 copy PREPARED BY

More information

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS 006: 2008 CEB SPECIFICATION COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS CEYLON ELECTRICITY BOARD SRI LANKA Specification for COMBINED METERING TRANSFORMERS (OUTDOOR TYPE) FOR

More information

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL Issued by: Approved by: Engineering Department Energy+ Inc. September 2016 Shawn Jackson, P.Eng. Approval is given in accordance with

More information

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 %

More information

General Electricity Company of Libya

General Electricity Company of Libya GES 22214 Technical Specification of GECOL 11/0.4kV Oil Immersed Ground Mounted Three Phase Sealed Type Distribution Transformers (Revision history) Issued on: Jan. 01, 2007 General Electricity Company

More information

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V This specification is property of SEC and subject to change or modification without

More information

DESIGN PRACTICE NOTE DESIGN/REVIEW REQUIREMENTS FOR TRACTION BONDING PLAN

DESIGN PRACTICE NOTE DESIGN/REVIEW REQUIREMENTS FOR TRACTION BONDING PLAN Approval Amendment Record Approval Date Version Description 01/04/2014 1 Initial Issue under MTM PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 7 Table of Contents

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices

More information

Cast resin transformers HARMONY TM

Cast resin transformers HARMONY TM Cast resin transformers HARMONY TM HARMONY TM the optimum solution for higher performance At a time when we are all seeking to preserve our way of life, the production of equipment whilst ensuring safety

More information

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS n Bureau of Indian Standards (BIS) is the NATIONAL STANDARD BODY. Established

More information

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS Management has tentatively approved your request subject to the following conditions: 1. All distribution materials/equipment must be purchased

More information

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with

More information

POTENTIAL TRANSFORMER

POTENTIAL TRANSFORMER POTENTIAL TRANSFORMER September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:

More information

Introduction. Centrado leading-edge transformer. Introduction

Introduction. Centrado leading-edge transformer. Introduction Introduction Centrado leading-edge transformer products are designed to optimize safety and produced to deliver a great electrical power experience and solution - for factory, infrastructure, home industry,

More information

NSP/ 007 / 006 Guidance on Substation Design: Transformer Transport, Delivery and Installation

NSP/ 007 / 006 Guidance on Substation Design: Transformer Transport, Delivery and Installation Version:- 1.0 of Issue:- March 2016 Page 1 of 7 NSP/ 007 / 006 Guidance on Substation Design: Transformer Transport, Delivery and Installation 1. Purpose The purpose of this document is to provide guidance

More information

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD. Our Ref : 2/2018- Date : Messrs: Dear Sir, Tender 2/2018 Main Transformers You are kindly requested to quote for the supply and delivery DDP to our stores the transformers detailed in the attached schedules

More information

Company Directive ENGINEERING SPECIFICATION EE SPEC: 5/5. Relating to 11kV Distribution Transformers

Company Directive ENGINEERING SPECIFICATION EE SPEC: 5/5. Relating to 11kV Distribution Transformers Company Directive ENGINEERING SPECIFICATION EE SPEC: 5/5 Relating to 11kV Distribution Transformers Policy Summary This specification covers the requirements for Distribution Transformers from 16kVA single

More information

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER TECHNICAL SPECIFICATION FOR POWER TRANSFORMER NOTE: Vendor to give their offer in line with this data sheet only. Any deviations/additions/deletions shall be brought out in a separate sheet. A TECHNICAL

More information

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013) S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013) 1.0 GENERAL 1.1 This specification covers the electrical and mechanical

More information

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS This specification is property of SEC and Subject to change or modification without any notice Table of Contents Clause Page 1.0 SCOPE

More information

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL PART 1: GENERAL 1. SCOPE This specification covers the design, engineering, manufacture, testing, supply, delivery, offloading and performance requirements of 11/0.433kV distribution transformers for outdoor

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS.

SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS. SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS. 1. SCOPE: This specification covers design, manufacture, testing and supply of 6.64/10.12 KV 24/15.7, 30/19.7

More information

50-SDMS-01 SPECIFICATIONS FOR

50-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR CURRENT TRANSFORMERS UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice C O N T E N T S CLAUSE TITLE PAGE NO. ------------ --------

More information

SECTION TRANSFORMERS

SECTION TRANSFORMERS SECTION 16460 - TRANSFORMERS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Section

More information

ECP DISTRIBUTION TRANSFORMER COMMISSIONING PROCEDURE

ECP DISTRIBUTION TRANSFORMER COMMISSIONING PROCEDURE Document Number: ECP 11-0506 ENGINEERING COMMISSIONING PROCEDURE ECP 11-0506 DISTRIBUTION TRANSFORMER COMMISSIONING PROCEDURE Network(s): Summary: EPN, LPN, SPN This procedure details the testing and commissioning

More information

DISTRIBUTION TRANSFORMER 11 / kv

DISTRIBUTION TRANSFORMER 11 / kv Ministry of Electricity (MOE) Power Distribution Office Baghdad IRAQ SPECIFICATION No. D-26 DISTRIBUTION TRANSFORMER 11 / 0.416 kv 2BREVISION 3BYEAR 2013 1 Table of Contents: Clause : no. 1. Scope of The

More information

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888

More information

POWER TRANSFORMERS CATALOGUE

POWER TRANSFORMERS CATALOGUE COMPANY INFORMATION ARTRANS S.A. started off as a small factory in April 2, 1982 located in Mendoza, Argentina. Now, three decades later it is a globally recognized manufacturer of distribution, transmission,

More information

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers SPECIFICATION GUIDE ABB VACUUM CAST COIL DRY TRANFORMERS CONTENTS 1. General 1.1. Codes and standards 1.2. Service conditions 1.3. System characteristics 1.4. Documentation 2. Design and construction 2.1.

More information

CUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv

CUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv CUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv June 2016 Issue 1 1. INTRODUCTION Introduction of contestability and the ability of all major customers to become contestable

More information

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION)

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION) 012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 8051 Fax: +94 11 232 5387 CONTENTS Page 1.0

More information

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS

More information

Earthing Requirements for HV Transmission Structures

Earthing Requirements for HV Transmission Structures Engineering Standard Electrical MEST 000002-07 Earthing Requirements for Transmission Structures Version: 1 Issued: February 2015 Owner: Engineering Approved By: Patrick Kelly Head of Electrical Engineering

More information

K Factor Power Transformers

K Factor Power Transformers Ashley-Edison AsiaElectricTransformers (UK) K Factor Power Transformers DTKF series Low Voltage Dry Type K Factor Power Transformers AET-DTKF-2004-01: Page 1 Asia Electric Transformers, Entrepreneur Business

More information

TECHNICAL SPECIFICATION FOR. CONTACT WIRE HARD-DRAWN COPPER 161mm2

TECHNICAL SPECIFICATION FOR. CONTACT WIRE HARD-DRAWN COPPER 161mm2 Engineering Specification Electrical TECHNICAL SPECIFICATION FOR CONTACT WIRE HARD-DRAWN COPPER 161mm2 Version: 2 Issued: May 2018 Owner: Engineering Approved by: Andrew Russack, Head of Engineering Electrical

More information

DISTRIBUTION TRANSFORMER kv

DISTRIBUTION TRANSFORMER kv ELECTRICITY COMMISSION PLANNING AND STUDY DEP BAGHDAD, REPUBLIC OF IRAQ SPECIFICATION No. D-26 DISTRIBUTION TRANSFORMER kv REVISION YEAR 2001 DISTRIBUTION TRANSFORMERS 1- SCOPE OF THE TENDER : Tenderer

More information

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS -1- INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION June 2013 SPECIFICATION No 150 kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS I. SCOPE This specification

More information

PROJECT: SUPPLY & INSTALL ELECTRICAL SWITCHBOARD AT SENGKURONG EXCHANGE PHASE 1, JLN TUTONG, BSB. SCOPE OF WORK The scope of work under Electrical Services shall include but not limited to the supply,

More information

SPECIFICATION FOR SAFETY POLE SIGNS & ACCESSORIES

SPECIFICATION FOR SAFETY POLE SIGNS & ACCESSORIES KP/3CB/TSP/0/00 04-09-9 Page of 9 TABLE OF CONTENTS 0. Circulation List 0. Amendment Record FOREWORD. SCOPE. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6. MARKING, LABELLING

More information

MESP TECHNICAL SPECIFICATION FOR BARE FLEXIBLE ANNEALED COPPER JUMPER WIRE 37/7/ mm 2

MESP TECHNICAL SPECIFICATION FOR BARE FLEXIBLE ANNEALED COPPER JUMPER WIRE 37/7/ mm 2 Engineering Specification Electrical Networks MESP 130400-04 TECHNICAL SPECIFICATION FOR BARE FLEXIBLE ANNEALED COPPER JUMPER WIRE 37/7/0.70 100mm 2 Version: 2 Issued: February 2016 Owner: Engineering

More information

Howard Smart Transformer Specification Guide

Howard Smart Transformer Specification Guide Howard Smart Transformer Specification Guide General Requirements Overhead pole-type smart distribution transformers shall be single phase, 60 Hz, mineral-oil filled and self-cooled and shall conform as

More information

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it.

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it. 1. SCOPE The requirements of this document apply to all Plant, Equipment and Apparatus that are part of, or are Directly connected to, the Company network. Requirements contained herein may be modified

More information

ECP COMPACT AND MICRO SUBSTATION COMMISSIONING PROCEDURE

ECP COMPACT AND MICRO SUBSTATION COMMISSIONING PROCEDURE Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0507 COMPACT AND MICRO SUBSTATION COMMISSIONING PROCEDURE EPN, LPN, SPN This procedure details the testing and commissioning procedures for

More information

Commissioning Manual Distribution Transformers - Three-phase Oil Filled

Commissioning Manual Distribution Transformers - Three-phase Oil Filled 1LPL000006A2110 rev. 1 Commissioning Manual Distribution Transformers - Three-phase Oil Filled 1LPL000006A2110 rev. 1 2 / 7 Table of contents 1 Commissioning and start-up... 3 1.1 Transformer survey...

More information

SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION THE ELECTRICITY (PEDE) SPECIFICATIONS FOR

SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION THE ELECTRICITY (PEDE) SPECIFICATIONS FOR SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION THE ELECTRICITY () SPECIFICATIONS FOR 20/0.4 KV DISTRIBUTION TRANSFORMER OPEN TERMINAL BUSHINGS AND HERMETICALLY SEALED

More information

Technical Specification for Polemounting Distribution Transformers

Technical Specification for Polemounting Distribution Transformers Joint Ergon Energy/Energex Technical Specification for Polemounting Distribution Transformers JTS02-0-0. Specification JTS02-0-0 Ver 9 Contents. Purpose and Scope... 2. References... 2. Applicable Standards...

More information

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS SECTION 16461C - DRY TYPE TRANSFORMERS PART 1 - GENERAL 1.1 This section includes design and performance requirements for dry-type transformers rated for use on secondary distribution systems rated 600

More information

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

Neutral Earthing. For permanent or temporary neutral earthing in HV systems Neutral Earthing Resistors RESISTORS For permanent or temporary neutral earthing in HV systems For continuous or temporary low-resistance neutral grounding in medium voltage systems Neutral point connection

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

ECP HV INSULATION TESTING

ECP HV INSULATION TESTING Document Number: ECP 11-0006 Network(s): Summary: All ENGINEERING COMMISSIONING PROCEDURE ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing of new and

More information

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C 1 Tender Notice No. NESCO Utility / O&M Materials/58 / 8267, dtd.17.7.15 Group-C Sl no. Material Description Unit Quantity 1 33KV C.T. Oil

More information

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality. PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02

More information

Standard. Extra High Voltage (EHV) Current Transformer Standard R Version 1.0, June Tasmanian Networks Pty Ltd (ABN )

Standard. Extra High Voltage (EHV) Current Transformer Standard R Version 1.0, June Tasmanian Networks Pty Ltd (ABN ) Standard Extra High Voltage (EHV) Current Transformer Standard R522690 Version 1.0, June 2018 Tasmanian Networks Pty Ltd (ABN 24 167 357 299) Authorisations Action Name and title Date Prepared by Michael

More information

Status Date Prepared Reviewed Endorsed Approved

Status Date Prepared Reviewed Endorsed Approved Discipline Engineering Standard - NSW Category Signalling Title Reference Number SPS 19 - (RIC Standard: SC 07 40 04 00 SP) Document Control Status Date Prepared Reviewed Endorsed Approved May 05 Standards

More information

Liquid-Filled Transformers

Liquid-Filled Transformers Liquid-Filled Transformers Custom Transformers at Standard Prices NIAGARA TRANSFORMER CORP. Induction Furnace Transformer Cycloconverter Rectifier Duty Transformer Arc Furnace Transformer Full Range of

More information

OIL-IMMERSED ARC-SUPPRESSION COILS

OIL-IMMERSED ARC-SUPPRESSION COILS ISO 9001:2000 99-320 Żychlin, ul. Narutowicza 70 ISO 14001:2004 PN-N-18001:2004 www.ftz.pl Secretary s Office Tel.: +48 24 285 46 05, Fax: +48 24 285 46 31 zarzad@ftz.pl Sales and Marketing Department

More information

1ZSC AAJ en, Rev. 1. Vacuum on-load tap-changers, type VUBB Technical guide

1ZSC AAJ en, Rev. 1. Vacuum on-load tap-changers, type VUBB Technical guide 1ZSC000562-AAJ en, Rev. 1 Vacuum on-load tap-changers, type VUBB Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible

More information

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax : NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata - 700 032, Tel : 033 2477 3126; Fax : 033 2477 2403 www.ntplindia.com SPECIFICATION NTPL MAKE MICRO-CONTROLLER BASED AUTOMATIC 50KV/10A AC HIGH VOLTAGE

More information

Compact Substation or Prefabricated Substation Inside Totally Enclosed Weatherproof Enclosure COPYRIGHT REGISTERED

Compact Substation or Prefabricated Substation Inside Totally Enclosed Weatherproof Enclosure COPYRIGHT REGISTERED Dial : (033)2677-5835 & 2667-8358 Tele Fax : (033)2667-8358 Manufacturer of Dry Type Transformers E-mail : unimag111@gmail.com Office & Factory : 26/5, Sarat Chatterjee Road, Howrah 711 104, West Bengal,

More information

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION October 2014 TECHNICAL DESCRIPTION 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES I. SCOPE This

More information

THE KENYA POWER AND LIGHTING CO. LTD. SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT

THE KENYA POWER AND LIGHTING CO. LTD. SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT THE KENYA POWER AND LIGHTING CO. LTD SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT NAME DESIGNATION SIGNATURE DATE Compiled by Ephantus Nyagah Ag. Senior Engineer Checked by Eng. Thagichu Kiiru Deputy

More information

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider Shunt Reactors Global Top Energy, Machinery & Plant Solution Provider Our Business Brief introduction of Hyosung Power & Industrial Systems PG While Hyosung is an established name for world-class electrical

More information

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems Arild Furnes,ATPA OGP/Petrobras workshop, 22.09.09 Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems September 24, 2009 Slide 1 Transformers for Ships and Offshore -

More information

TS RES - OUTSTANDING ISSUES

TS RES - OUTSTANDING ISSUES TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next

More information

Technical recommendation for the purchase of Real Time Thermal Rating for transformers

Technical recommendation for the purchase of Real Time Thermal Rating for transformers Version: 1.0 Date of Issue: December 2014 1 Technical recommendation for the purchase of Real Time Thermal Rating for transformers 1 Purpose The purpose of this document is to set out and describe the

More information

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers save energy, it is precious Mfg. of all types of Distribution / Power & Furnace Transformers SYNERGY transformers SAFETY AND EFFICIENCY, COMBINED WITH LONG-TERM RELIABILITY, ARE THE HALLMARKS OF WORLD-RENOWNED

More information

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A Group F : No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS Table : A No. Description 1. Make & Manufacturer 2. Place of Manufacturer 3. Voltage Ratio 4. Rating

More information

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class GE Ventilated Dry-Type Transformers Secondary Substation Transformers - 5 and 15kV Class GE ventilated dry-type transformers are designed for indoor or outdoor applications in schools, hospitals, industrial

More information

DISTRIBUTION TRANSFORMERS

DISTRIBUTION TRANSFORMERS DISTRIBUTION TRANSFORMERS OIL IMMERSED up to 6 MVA www.alfanar.com Contents 1 - General Information 4 2 - Applications 10 3 - Product Portfolio 11 4 - Product Breakdown 12 5 - Transformer Classifications

More information

NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations

NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations Version: 3.1 Date of Issue: September 2016 Page: 1 of 21 NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations 1. Purpose The purpose of this document is to detail the technical requirements

More information

Basic Principles and Operation of Transformer

Basic Principles and Operation of Transformer Basic Principles and Operation of Transformer CONSTRUCTIONAL ASPECTS Cores In order to enhance core s magnetic properties, it is constructed from an iron and silicon mixture (alloy). The magnetic core

More information

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY) E -Tender Notice No. Annexure - VII SOUTHCO/DEPOSIT/3.15 & 5 MVA Power Transformer /02/2015 16 Dt. 02.03.2016 NAME OF THE WORK PROCUREMENT OF33/11 KV, 3.15 MVA & 5 MVA Power Transformer SUPPLIER INFORMATION

More information

PRODUCT FOR HIGH VOLTAGE APPLICATION. Current transformers for Gasinsulated. Instructions for installation, use and maintenance

PRODUCT FOR HIGH VOLTAGE APPLICATION. Current transformers for Gasinsulated. Instructions for installation, use and maintenance PRODUCT FOR HIGH VOLTAGE APPLICATION Current transformers for Gasinsulated switchgear type ELK Instructions for installation, use and maintenance 2 CURRENT TRANSFORMERS FOR GAS-INSULATED SWITCHGEAR TYPE

More information

Mechanical Design. Brian Brinson Mechanical Design Manager.

Mechanical Design. Brian Brinson Mechanical Design Manager. Mechanical Design Brian Brinson Mechanical Design Manager brian.brinson@spx.com September 26, 2018 Agenda 1. Design Process 2. Pre-Approval Drawings Bid Drawings Preliminary Drawings 3. Approval Package

More information

MESP TECHNICAL SPECIFICATION FOR MURL JUMPER WIRE HARD-DRAWN COPPER 19/ mm 2

MESP TECHNICAL SPECIFICATION FOR MURL JUMPER WIRE HARD-DRAWN COPPER 19/ mm 2 Engineering Specification Electrical Networks MESP 130400-07 TECHNICAL SPECIFICATION FOR Version: 1 Issued: February 2017 Owner: Engineering Division Approved By: Andrew Russack Head of Engineering (Electrical)

More information

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION)

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION) GENERAL MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION) SUBMITTED BY SASHIKUMAR G BHARAT HEAVY ELECTRICALS LIMITED INDUSTRIAL SYSTEMS GROUP Prof. C. N. R. Rao Circle I. I. Sc. POST Malleswaram Bangalore

More information

MESP TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/ mm 2

MESP TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/ mm 2 Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/2.14 70mm 2 Version: 1 Issued: January 2015 Owner: Engineering Division Approved By: Pat

More information

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values This is measured to measure the Insulation Resistance of the whole transformer. a) For 33/11 KV Power Transformer

More information

Australian Standard. Switchgear assemblies and ancillary equipment for alternating voltages above 1 kv AS

Australian Standard. Switchgear assemblies and ancillary equipment for alternating voltages above 1 kv AS AS 2067 1984 Australian Standard Switchgear assemblies and ancillary equipment for alternating voltages above 1 kv [Title allocated by Defence Cataloguing Authority: SWITCHGEAR ASSEMBLIES, ELECTRICAL AND

More information

ENGINEERING DRAWINGS MANAGEMENT POLICY (IFC/AS BUILTS)

ENGINEERING DRAWINGS MANAGEMENT POLICY (IFC/AS BUILTS) Approval Amendment Record Approval Date Version Description 15/10/2015 1 This policy takes precedence over L1-NAM-PRO-003 Infrastructure As Built Drawing Management due to business restructures. New Content

More information

Ritz Instrument Transformers GmbH. Welcome

Ritz Instrument Transformers GmbH. Welcome Ritz Instrument Transformers GmbH Welcome About Ritz together with over 200 years of experience in instrument transformer production since 1945 since 1945 since 1945 since 1904 RITZ Group - Organization

More information

Capacitive voltage transformers

Capacitive voltage transformers Capacitive voltage transformers Outdoor operation Oil-paper insulated ECF (72 550) kv General description Capacitive voltage transformers of type ECF are used in high-voltage switchgears from 72 to 550

More information

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL PART I: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. a.

More information

MESP TECHNICAL SPECIFICATION FOR CATENARY WIRE HARD-DRAWN COPPER 37/ mm 2

MESP TECHNICAL SPECIFICATION FOR CATENARY WIRE HARD-DRAWN COPPER 37/ mm 2 Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR CATENARY WIRE HARD-DRAWN COPPER 37/2.5 181mm 2 Version: 3 Issued: February 2017 Owner: Engineering Division Approved By: Andrew

More information

MEDIUM VOLTAGE PRODUCT. KOKM Cable current instrument transformers Instruction for Installation, use and maintenance

MEDIUM VOLTAGE PRODUCT. KOKM Cable current instrument transformers Instruction for Installation, use and maintenance MEDIUM VOLTAGE PRODUCT KOKM Cable current instrument transformers Instruction for Installation, use and maintenance 2 KOKM CABLE CURRENT INSTRUMENT TRANSFORMERS INSTRUCTION FOR INSTALLATION, USE AND MAINTENANCE

More information

Specification Distribution Transformers

Specification Distribution Transformers Specification Distribution Transformers Standard Number: HPC-8DJ-07-0001-2013 Document Control Author Name: Pat Dowdell Position: Senior Electrical Engineer Revision 1 Author Name: Adrian Barnes Position:

More information

Form-IV. Form of Inspection/Test Report. (Under Regulation 43)

Form-IV. Form of Inspection/Test Report. (Under Regulation 43) Form-IV Form of Inspection/Test Report (Under Regulation 43) 1. Name and address of the Chartered Electrical Safety Engineer 2. Name and address of the consumer (or) Owner(or) supplier: Contact No: E-Mail:

More information

NPS/003/021 Technical Specification for Continuous Maximum Rated (CMR) Transformers.

NPS/003/021 Technical Specification for Continuous Maximum Rated (CMR) Transformers. Document Reference :- NPS/003/021 Document Type :- Code of Practice Version :- 4.0 Date of Issue :- November 2016 Page 1 of 43 NPS/003/021 Technical Specification for Continuous Maximum Rated (CMR) Transformers.

More information