ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

Size: px
Start display at page:

Download "ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER"

Transcription

1 Approval Amendment Record Approval Date Version Description 03/05/ Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13

2 Table of Contents 1. Purpose Scope Abbreviations Definitions References & Legislation Standards Latest Issues and Amendments Background General Requirements Operating Conditions Service Conditions Electrical Conditions Ratings & Configurations Winding Connection Construction Transformer Enclosure & Cooling Primary Terminals Secondary Terminals Earthing Terminal Painting Lifting Facility Size Rating Plate Testing Type Test Routine Tests Test Certificates Documentation and Support Documentation Requirements Design Drawings Drawing Format Technical Maintenance Plan Maintenance Manual Installation Instruction Manual Appendix A Transformer Details Terminals and Tappings Appendix B Design Management Requirements Appendix C Technical Data Schedule Form PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 2 of 13

3 1. Purpose This document is the technical specification for a 230V/110V or 400V/110V Transformer for use in MTM s Signalling Network. 2. Scope This document applies to the supply of a single phase Transformer with a primary voltage of 230V phase to neutral (it shall be considered as non-effectively earthed) and secondary voltage of 110V. Alternatively the single phase Transformer can have a primary voltage of 400V phase to phase and secondary voltage of 110V (Table 1). This Transformer may be used to supply signalling equipment off a 230V or 400V Bus. 3. Abbreviations ACCB Alternating Current Circuit Breaker Electrol Electrical Systems Control Centre MTM Metro Trains Melbourne 4. Definitions For all technical terms refer to AS Shall Should Is used as the descriptive word to express a requirement that is mandatory to achieve conformance to the standard. Is used as the descriptive word to express a requirement that is recommended in order to achieve compliance to the standard. Should can also be used if a requirement is a design goal but not a mandatory requirement. 5. References & Legislation 5.1 Standards The Transformer shall comply with all relevant Standards, including: AS 2374 AS Power Transformers Power Transformers Note: All materials and components shall comply with the relevant Australian Standard or, where these do not exist, with the relevant IEC or EN Standard. 5.2 Latest Issues and Amendments Reference to all standards shall be read as a reference to the latest edition of that standard and amendments available at the time of tendering. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 3 of 13

4 6. Background The Transformer will be used for the purpose of converting power from a 400V or 230V supply to a 110V supply for signalling equipment and other purposes. Due to the variable nature of these uses, the following will be specified in a separate Scope of Works document: Primary Voltage (or equivalent table of ratings to that shown in Section 9) Rated Power 7 General Requirements 7.1 The Transformer shall be designed and manufactured to give the highest level of reliability whilst requiring the minimum level of maintenance under continuous operating conditions. 7.2 The Transformer shall be a dry type with enclosed terminals, for an indoor installation or within a field enclosure. 8. Operating Conditions 8.1 Service Conditions The operating conditions in AS shall be applied except that the maximum ambient temperature shall be taken as 45 C. The air may be slightly polluted by dust Transformers designated for indoor installation shall be mounted on a concrete floor inside a substation building or suitable annex. 8.2 Electrical Conditions Supply to the primary winding of the Transformer will be taken from an ACCB. The primary supply will be either 400V phase to phase or 230V phase to neutral, 50 Hz. It shall be considered as non-effectively earthed The secondary winding will be connected to a switchboard via a suitable circuit breaker. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 4 of 13

5 9. Ratings & Configurations This specification covers two primary voltages. The specific ratings and characteristics of each of these are listed in Table 1. Table 1 Transformer ratings and Characteristics. Type 400/110V 230/110V Rated Primary Voltage 400V 230V Rated Secondary Voltage 110V Single phase to Phases neutral Single (shall be phase to considered phase noneffectively earthed) 3kVA 6kVA Typical Rated Power 10kVA 15kVA 20kVA Rated Frequency 50Hz Primary winding highest voltage for equipment <3.6kV Secondary winding highest voltage for equipment <1.1kV Rated primary short-duration power frequency withstand voltage 10kV RMS Rated primary lightning impulse withstand voltage 20kV peak Rated secondary short-duration power frequency withstand voltage 10kV RMS Rated secondary lightning impulse withstand voltage 20kV peak Maximum Sound Power Level 56dBA Short-circuit apparent power of the supply system 1.25MVA Winding Vector Ii0 0.6 pf 4% Percentage Impedance 4% 10. Winding Connection 10.1 All insulation used in the transformers shall be non-hygroscopic and designed to withstand continuously a temperature of one hundred degrees centigrade After winding, the completed coils shall be thoroughly impregnated with an insulating compound under the vacuum process in accordance with Australian Standard Power Transformers AS PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 5 of 13

6 10.3 The composition of the insulating compound shall be such that it will not soften or ooze out under the continued exposure to the maximum working temperatures None of the materials used shall disintegrate under the continued action of heat and shall not carbonise, become brittle or lose their flexibility, with the maximum working temperatures Tappings The primary side shall have only primary voltage of 230V or 400V (depending on what primary is specified) The tappings on the secondary terminals shall allow for 110V, 120V and 125V (refer to appendices) 11. Construction 11.1 Transformer Enclosure & Cooling The Transformer shall be enclosed by a ventilated metallic enclosure cooled by naturally circulated external air. The enclosure shall be suitable for indoor installation or field enclosure The transformer shall be naturally cooled - it shall be Class AN The enclosure shall provide a minimum ingress protection of IP 21 for indoor installations, in accordance with AS The case of the transformer shall be of un-corrugated welded sheet steel not less than 3mm thick The transformer case shall have a top cover so arranged that it can easily be removed when the transformer is in position connected ready for working, but will prevent the ingress of foreign substances. The cover shall also cover the primary terminals Primary Terminals The primary terminals shall be located within the transformer enclosure The terminals shall be at least 400mm from the cable entry point to allow for the unscreened length of a typical cable termination The terminal studs shall be of suitable size to accommodate crimp lugs for the largest cable size (25mm 2 copper cable, minimum stud size should be M8) Appropriate cable supports shall be provided within the enclosure such that the weight of the input cable is not taken by the electrical connections Terminals shall be suitably located to accept cables entering the enclosure from below the transformer, through an appropriate non-ferrous gland. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 6 of 13

7 11.3 Secondary Terminals The secondary terminals shall be located on the opposite side of the transformer enclosure to the primary terminals, externally to the enclosure The terminals shall be suitable for directly connecting to appropriately terminated low voltage cables, suitably sized for the rating of the transformer The terminal studs shall be of suitable size to accommodate crimp lugs for the largest cable size (50mm 2 copper cable, minimum stud size should be M8) Appropriate cable supports shall be provided within the enclosure such that the weight of the output cable is not taken by the electrical connections The terminals shall be suitably located to accept cables entering the enclosure from below the transformer, through an appropriate non-ferrous gland Earthing Terminal The transformer frame shall be directly connected to the room or enclosure earth. Two pre-drilled M12 holes shall be provided on opposite sides of the transformer for this purpose Painting All metal surfaces shall be prepared in accordance with Australian Standard Metal Finishing Preparation and Pre-Treatment of Surfaces AS 1627 prior to the application of protective primer to Australian Standard Paints for Steel Structures Epoxy Primer (two packs) AS The final colour coat shall be Y11 Canary Yellow in accordance with Australian Standard Colour Standards for General Purposes AS 2700S and the transformer shall be supplied with touch-up paint Lifting Facility 11.7 Size The Transformer shall be fitted with a facility for lifting and moving by a forklift The base shall be fitted with two channel section with minimum dimensions of 100 mm x 50 mm suitable for lifting the Transformer with a forklift The transformer and enclosure shall be as compact as possible, and shall occupy a total floor area no greater than approximately 450mm by 450mm The maximum height of the transformer enclosure shall be 450mm from the top of the base channel sections Rating Plate The Transformer Rating Plate shall comply with the requirements of AS The tap link connections and positions shall be clearly shown on the rating plate The rating plate shall be constructed of stainless steel and shall be securely riveted to the body of the transformer. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 7 of 13

8 Recorded information shall be physically etched, embossed or engraved clearly onto the surface of the rating plate and shall be highlighted with black paint. 12. Testing 12.1 Type Test A Type Test Certificate from a design which is representative of the Transformer to be supplied shall be provided with the Tender documentation Routine Tests All routine tests as described in Clause 10 of AS :2005 shall be performed on the Transformer at the manufacturer s factory MTM reserves the right to appoint a representative to witness these tests. Seven working days notification shall be given to MTM of intention to carry out factory testing Test Certificates The results of all tests shall be recorded on test certificates. The test certificates shall clearly show the performance of the equipment and shall be accompanied by tables showing the actually measured values and all calculations The test certificates shall be forwarded to MTM and the results approved by MTM prior to delivery. 13. Documentation and Support 13.1 Documentation Requirements All documentation shall be provided in English One electronic and eight paper copies of the each document shall be provided and the content shall be identical in each copy Every page of the documentation shall be clearly identified in relation to the document to which it belongs and the version of that document. All pages of multipage documents shall be uniquely numbered. It shall be possible to readily determine if all pages of a document are present Manuals shall be A4 size and shall be bound in durable covers or in 4-D ring binders Design Drawings The following drawings must be supplied: i. Construction details of the Transformer including dimensions. ii. iii. Physical layout and arrangement of the components of the Transformer. Mounting requirements for the Transformer. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 8 of 13

9 iv. Physical layout and arrangement of the primary and secondary terminals. v. Drawings of the Transformer Rating Plate and data vi Drawing Format All other drawings required for Installation, Testing, Commissioning, Operation and Maintenance All drawings shall comply with PTV Infrastructure Drafting Standard and shall be submitted for MTM approval prior to manufacturing Files shall be provided in Microstation format on compact disk (CD) Technical Maintenance Plan A Technical Maintenance Plan which establishes the maintenance policy for the Small Power Transformer recommended by the supplier shall be provided. This shall detail the preventative servicing schedules and maintenance intervals and latitudes for all components and systems of the Transformer. The servicing schedules shall reference appropriate detailed instructions in the maintenance manual The Technical Maintenance Plan shall contain a list of any recommended spare parts, detailing price, supplier and procurement lead-times The Technical Maintenance Plan shall detail safe disposal procedures applicable for when the Small Power Transformer is no longer serviceable (recycling, hazardous waste etc.) Maintenance Manual The Maintenance Manual shall detail: a) All of the servicing activities. b) Any overhaul instructions. c) The adjustment procedures. d) The changing of components for repairs, and e) Fault-finding procedures. f) Spares support schedule The Maintenance Manual shall also include a complete set of as-built drawings and a comprehensive parts list for the Transformer Installation Instruction Manual An Installation Instruction Manual shall be provided and shall contain instructions which will enable the Transformer to be properly installed, tested and commissioned. This shall include all necessary drawings. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 9 of 13

10 14. Appendix A Transformer Details 14.1 Terminals and Tappings The following Terminal voltage and marking shall be provided: Figure 1 Terminal Voltage Marking The following name plate and details shall be provided to comply with AS : a) Kind of transformer (for example transformer, auto-transformer, series transformer, etc.) b) Number of this standard. c) Manufacturer's name, country and town where the transformer was assembled. d) Manufacturer's serial number. e) Year of manufacture. f) Number of phases. g) Rated power (in kva or MVA). (For multi-winding transformers, the rated power of each winding shall be given. The loading combinations shall also be indicated unless the rated power of one of the windings is the sum of the rated powers of the other windings.) h) Rated frequency (in Hz). i) Rated voltages (in V or kv) and tapping range. j) Rated currents (in A or ka). k) Connection and phase displacement symbol. l) Short-circuit impedance, measured value in percentage. For multi-winding transformers, several impedances for different two-winding combinations are to be given with the respective reference power values. m) Type of cooling. (If the transformer has several assigned cooling methods, the respective power values may be expressed as percentages of rated power, for example ONAN/ONAF 70/100 %.) n) Total mass. o) Mass and type of insulating liquid with reference to the relevant IEC standard. p) Maximum system short-circuit power or current used to determine the transformer withstand capability if not infinite. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 10 of 13

11 15. Appendix B Design Management Requirements This appendix describes the documentation which should be provided as a minimum at each stage of the procurement process. The documentation shall comply with the specifications above. Tender Submission The following documents shall be provided as part of the tender submission: General Arrangement drawing of the Small Power Transformer which clearly shows: The overall dimensions of the Transformer and details of the enclosure Details of the proposed primary cable terminations Details of the proposed secondary terminations Type Test Certificates The Technical Data Schedule in Appendix B filled in. Contract Documentation One set of PDF copies of the drawings and documentation as described in Clauses 13.2 and 13.6 and any additional documentation detailing the design should be provided for review and approval by MTM four weeks after the Contact Award Date. No manufacture shall commence until the drawings have been approved. An allowance of five working days should be made by the supplier for the review and approval of submitted drawings Pre-Delivery Documentation As part of the deliverables, the supplier shall provide five hard copies of the following documents: Technical Maintenance Plan Installation Instruction Manual Maintenance Manual Storage, handling, loading and off-loading instructions Test results Approved drawings as listed in 13.2 In addition, the supplier shall provide copies of the As Built layouts and Schematic drawings in electronic format (PDF and Microstation) PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 11 of 13

12 16. Appendix C Technical Data Schedule Form The Tenderer shall supply the following information and guaranteed performance thereof. Compliance Does the Transformer fully comply with this specification? Yes No Is a Type Test Certificate attached? Yes No Is a general arrangement sketch attached? Yes No Type Oil Dry Winding Vector Rated Power Primary winding (kva) Rated Voltage Primary windings (V) Secondary windings (V) Rated Current Primary windings (A) Secondary windings (A) Rated Insulation Level Primary Power Frequency Withstand Voltage (kv) Primary Impulse Withstand Voltage (kv) Secondary Power Frequency Withstand Voltage (kv) Secondary Impulse Withstand Voltage (kv) Impedance & Regulation Percentage Impedance at Rated Primary Power (%) Losses Iron Loss (at Rated Primary Voltage) (W) Copper Loss (at Rated Primary Current) (W) Tap Changer Manufacturer Type Voltage Rating (V) Current Rating (A) PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 12 of 13

13 Enclosure Overall Length (mm) Overall Width (mm) Overall Depth (mm) Enclosure material Enclosure thickness (mm) Enclosure finish / colour Weight Mass of Core and Windings (kg) Total mass (kg) Primary Terminals Manufacturer Type Voltage Rating (V) Current Rating (A) Height above base of enclosure (mm) Cable box dimensions (if applicable) (mm) width (mm) depth (mm) height Secondary Terminals Manufacturer Type Voltage Rating (V) Current Rating (A) Height above base of enclosure (mm) Cable box dimensions (if applicable) (mm) width (mm) depth (mm) height PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 13 of 13

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT

More information

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Engineering Specification Head of Electrical Engineering MESP 050100-01 TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Version:

More information

MESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER Version: 3 Issued: February 2018 Owner: Head of Engineering - Electrical Approved By: Andrew Russack Head

More information

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP) Discipline Engineering Standard NSW Category Electrical Title Substation Auxiliary Transformer from Rectifier Transformer Secondary Reference Number PDS 01 (RIC Standard: EP 05 00 00 01 SP) Document Control

More information

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994

More information

Reference Number PPS 05 - (RIC Standard: EP SP)

Reference Number PPS 05 - (RIC Standard: EP SP) Discipline Engineering Standard - NSW Category Electrical Title Low Voltage Isolating Transformer Reference Number PPS 05 - (RIC Standard: EP 17 00 00 11 SP) Document Control Status Date Prepared Reviewed

More information

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date

More information

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS PURCHASE SPECIFICATIONS OF 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS SPECIFICATION NO. : OR12423 REVISION NO. : Rev 00 DATE : 01.03.2011 DISTRIBUTION : PI - 4 copies O/C - 1 copy PREPARED BY

More information

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor

More information

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS 006: 2008 CEB SPECIFICATION COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS CEYLON ELECTRICITY BOARD SRI LANKA Specification for COMBINED METERING TRANSFORMERS (OUTDOOR TYPE) FOR

More information

Status Date Prepared Reviewed Endorsed Approved

Status Date Prepared Reviewed Endorsed Approved Discipline Engineering Standard - NSW Category Signalling Title Reference Number SPS 19 - (RIC Standard: SC 07 40 04 00 SP) Document Control Status Date Prepared Reviewed Endorsed Approved May 05 Standards

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices

More information

Cast resin transformers HARMONY TM

Cast resin transformers HARMONY TM Cast resin transformers HARMONY TM HARMONY TM the optimum solution for higher performance At a time when we are all seeking to preserve our way of life, the production of equipment whilst ensuring safety

More information

General Electricity Company of Libya

General Electricity Company of Libya GES 22214 Technical Specification of GECOL 11/0.4kV Oil Immersed Ground Mounted Three Phase Sealed Type Distribution Transformers (Revision history) Issued on: Jan. 01, 2007 General Electricity Company

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers SPECIFICATION GUIDE ABB VACUUM CAST COIL DRY TRANFORMERS CONTENTS 1. General 1.1. Codes and standards 1.2. Service conditions 1.3. System characteristics 1.4. Documentation 2. Design and construction 2.1.

More information

POWER TRANSFORMERS CATALOGUE

POWER TRANSFORMERS CATALOGUE COMPANY INFORMATION ARTRANS S.A. started off as a small factory in April 2, 1982 located in Mendoza, Argentina. Now, three decades later it is a globally recognized manufacturer of distribution, transmission,

More information

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL Issued by: Approved by: Engineering Department Energy+ Inc. September 2016 Shawn Jackson, P.Eng. Approval is given in accordance with

More information

Distribution transformers Part 2 Ground mounted transformers not closecoupled

Distribution transformers Part 2 Ground mounted transformers not closecoupled PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Technical Specification 35-1 Distribution transformers Part 2 Ground mounted transformers not closecoupled www.energynetworks.org PUBLISHING

More information

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1 GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS SECTION 16461C - DRY TYPE TRANSFORMERS PART 1 - GENERAL 1.1 This section includes design and performance requirements for dry-type transformers rated for use on secondary distribution systems rated 600

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

Earthing Requirements for HV Transmission Structures

Earthing Requirements for HV Transmission Structures Engineering Standard Electrical MEST 000002-07 Earthing Requirements for Transmission Structures Version: 1 Issued: February 2015 Owner: Engineering Approved By: Patrick Kelly Head of Electrical Engineering

More information

DESIGN PRACTICE NOTE DESIGN/REVIEW REQUIREMENTS FOR TRACTION BONDING PLAN

DESIGN PRACTICE NOTE DESIGN/REVIEW REQUIREMENTS FOR TRACTION BONDING PLAN Approval Amendment Record Approval Date Version Description 01/04/2014 1 Initial Issue under MTM PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 7 Table of Contents

More information

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 %

More information

K Factor Power Transformers

K Factor Power Transformers Ashley-Edison AsiaElectricTransformers (UK) K Factor Power Transformers DTKF series Low Voltage Dry Type K Factor Power Transformers AET-DTKF-2004-01: Page 1 Asia Electric Transformers, Entrepreneur Business

More information

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888

More information

Introduction. Centrado leading-edge transformer. Introduction

Introduction. Centrado leading-edge transformer. Introduction Introduction Centrado leading-edge transformer products are designed to optimize safety and produced to deliver a great electrical power experience and solution - for factory, infrastructure, home industry,

More information

TECHNICAL SPECIFICATION FOR. CONTACT WIRE HARD-DRAWN COPPER 161mm2

TECHNICAL SPECIFICATION FOR. CONTACT WIRE HARD-DRAWN COPPER 161mm2 Engineering Specification Electrical TECHNICAL SPECIFICATION FOR CONTACT WIRE HARD-DRAWN COPPER 161mm2 Version: 2 Issued: May 2018 Owner: Engineering Approved by: Andrew Russack, Head of Engineering Electrical

More information

SPECIFICATION FOR SAFETY POLE SIGNS & ACCESSORIES

SPECIFICATION FOR SAFETY POLE SIGNS & ACCESSORIES KP/3CB/TSP/0/00 04-09-9 Page of 9 TABLE OF CONTENTS 0. Circulation List 0. Amendment Record FOREWORD. SCOPE. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6. MARKING, LABELLING

More information

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS

More information

MESP TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/ mm 2

MESP TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/ mm 2 Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR TRANSMISSION WIRE HARD-DRAWN COPPER 19/2.14 70mm 2 Version: 1 Issued: January 2015 Owner: Engineering Division Approved By: Pat

More information

TS RES - OUTSTANDING ISSUES

TS RES - OUTSTANDING ISSUES TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next

More information

.1 Provide dry type cast-resin 11kV/0.420kV transformers in accordance with the Contract Documents.

.1 Provide dry type cast-resin 11kV/0.420kV transformers in accordance with the Contract Documents. PAGE 1/19 DRY TYPE CAST-RESIN 1.0 GENERAL 1.1 Description.1 Provide dry type cast-resin 11kV/0.420kV transformers in accordance with the Contract Documents..2 The manufacturer for dry-type cast resin transformer

More information

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS -1- INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION June 2013 SPECIFICATION No 150 kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS I. SCOPE This specification

More information

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V This specification is property of SEC and subject to change or modification without

More information

50-SDMS-01 SPECIFICATIONS FOR

50-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR CURRENT TRANSFORMERS UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice C O N T E N T S CLAUSE TITLE PAGE NO. ------------ --------

More information

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it.

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it. 1. SCOPE The requirements of this document apply to all Plant, Equipment and Apparatus that are part of, or are Directly connected to, the Company network. Requirements contained herein may be modified

More information

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C 1 Tender Notice No. NESCO Utility / O&M Materials/58 / 8267, dtd.17.7.15 Group-C Sl no. Material Description Unit Quantity 1 33KV C.T. Oil

More information

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class GE Ventilated Dry-Type Transformers Secondary Substation Transformers - 5 and 15kV Class GE ventilated dry-type transformers are designed for indoor or outdoor applications in schools, hospitals, industrial

More information

THE KENYA POWER AND LIGHTING CO. LTD. SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT

THE KENYA POWER AND LIGHTING CO. LTD. SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT THE KENYA POWER AND LIGHTING CO. LTD SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT NAME DESIGNATION SIGNATURE DATE Compiled by Ephantus Nyagah Ag. Senior Engineer Checked by Eng. Thagichu Kiiru Deputy

More information

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION)

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION) GENERAL MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION) SUBMITTED BY SASHIKUMAR G BHARAT HEAVY ELECTRICALS LIMITED INDUSTRIAL SYSTEMS GROUP Prof. C. N. R. Rao Circle I. I. Sc. POST Malleswaram Bangalore

More information

CAST RESIN DRY TRANSFORMER

CAST RESIN DRY TRANSFORMER CAST RESIN DRY TRANSFORMER Majority owned subsidiary company of ELETTROMECCANICA COLOMBO s.a.s., Italy Elettromeccanica India Elettromeccanica India Pvt Ltd (EIPL) is a joint-venture company with Elettromeccanica,

More information

MEDIUM VOLTAGE PRODUCT. KOKM Cable current instrument transformers Instruction for Installation, use and maintenance

MEDIUM VOLTAGE PRODUCT. KOKM Cable current instrument transformers Instruction for Installation, use and maintenance MEDIUM VOLTAGE PRODUCT KOKM Cable current instrument transformers Instruction for Installation, use and maintenance 2 KOKM CABLE CURRENT INSTRUMENT TRANSFORMERS INSTRUCTION FOR INSTALLATION, USE AND MAINTENANCE

More information

MESP TECHNICAL SPECIFICATION FOR BARE FLEXIBLE ANNEALED COPPER JUMPER WIRE 37/7/ mm 2

MESP TECHNICAL SPECIFICATION FOR BARE FLEXIBLE ANNEALED COPPER JUMPER WIRE 37/7/ mm 2 Engineering Specification Electrical Networks MESP 130400-04 TECHNICAL SPECIFICATION FOR BARE FLEXIBLE ANNEALED COPPER JUMPER WIRE 37/7/0.70 100mm 2 Version: 2 Issued: February 2016 Owner: Engineering

More information

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION)

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION) 012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 8051 Fax: +94 11 232 5387 CONTENTS Page 1.0

More information

SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS.

SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS. SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS. 1. SCOPE: This specification covers design, manufacture, testing and supply of 6.64/10.12 KV 24/15.7, 30/19.7

More information

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS This specification is property of SEC and Subject to change or modification without any notice Table of Contents Clause Page 1.0 SCOPE

More information

DISTRIBUTION TRANSFORMER 11 / kv

DISTRIBUTION TRANSFORMER 11 / kv Ministry of Electricity (MOE) Power Distribution Office Baghdad IRAQ SPECIFICATION No. D-26 DISTRIBUTION TRANSFORMER 11 / 0.416 kv 2BREVISION 3BYEAR 2013 1 Table of Contents: Clause : no. 1. Scope of The

More information

CUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv

CUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv CUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv June 2016 Issue 1 1. INTRODUCTION Introduction of contestability and the ability of all major customers to become contestable

More information

SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION THE ELECTRICITY (PEDE) SPECIFICATIONS FOR

SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION THE ELECTRICITY (PEDE) SPECIFICATIONS FOR SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION THE ELECTRICITY () SPECIFICATIONS FOR 20/0.4 KV DISTRIBUTION TRANSFORMER OPEN TERMINAL BUSHINGS AND HERMETICALLY SEALED

More information

TMC Transformers TMC

TMC Transformers TMC TMC Product & Technology Presentation Cast Resin Transformer (CRT) History Cast resin transformers first appeared in Germany during the 1960s. This new style of dry type transformer was developed with

More information

NSP/ 007 / 006 Guidance on Substation Design: Transformer Transport, Delivery and Installation

NSP/ 007 / 006 Guidance on Substation Design: Transformer Transport, Delivery and Installation Version:- 1.0 of Issue:- March 2016 Page 1 of 7 NSP/ 007 / 006 Guidance on Substation Design: Transformer Transport, Delivery and Installation 1. Purpose The purpose of this document is to provide guidance

More information

MESP TECHNICAL SPECIFICATION FOR MURL JUMPER WIRE HARD-DRAWN COPPER 19/ mm 2

MESP TECHNICAL SPECIFICATION FOR MURL JUMPER WIRE HARD-DRAWN COPPER 19/ mm 2 Engineering Specification Electrical Networks MESP 130400-07 TECHNICAL SPECIFICATION FOR Version: 1 Issued: February 2017 Owner: Engineering Division Approved By: Andrew Russack Head of Engineering (Electrical)

More information

Premium 30 Energy Efficient, Low Voltage Transformers General Purpose, Harmonic Mitigating, and K-Rated

Premium 30 Energy Efficient, Low Voltage Transformers General Purpose, Harmonic Mitigating, and K-Rated Premium 30 Energy Efficient, Low Voltage Transformers General Purpose, Harmonic Mitigating, and K-Rated Catalog 7400CT1001 2010 Class 7400 CONTENTS Description.............................................

More information

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS n Bureau of Indian Standards (BIS) is the NATIONAL STANDARD BODY. Established

More information

Products for High Voltage Application. AT35, AT38, AT41 Indoor current transformer for oil-immersed power transformers

Products for High Voltage Application. AT35, AT38, AT41 Indoor current transformer for oil-immersed power transformers Products for High Voltage Application AT35, AT38, AT41 Indoor current transformer for oil-immersed power transformers Technical parameters Value Highest voltage for equipment 1.2 kv Power frequency voltage,

More information

NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations

NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations Version: 3.1 Date of Issue: September 2016 Page: 1 of 21 NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations 1. Purpose The purpose of this document is to detail the technical requirements

More information

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013) S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013) 1.0 GENERAL 1.1 This specification covers the electrical and mechanical

More information

OIL-IMMERSED ARC-SUPPRESSION COILS

OIL-IMMERSED ARC-SUPPRESSION COILS ISO 9001:2000 99-320 Żychlin, ul. Narutowicza 70 ISO 14001:2004 PN-N-18001:2004 www.ftz.pl Secretary s Office Tel.: +48 24 285 46 05, Fax: +48 24 285 46 31 zarzad@ftz.pl Sales and Marketing Department

More information

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER TECHNICAL SPECIFICATION FOR POWER TRANSFORMER NOTE: Vendor to give their offer in line with this data sheet only. Any deviations/additions/deletions shall be brought out in a separate sheet. A TECHNICAL

More information

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems Arild Furnes,ATPA OGP/Petrobras workshop, 22.09.09 Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems September 24, 2009 Slide 1 Transformers for Ships and Offshore -

More information

TECHNICAL SPECIFICATION OF 11 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET OF ACCURACY CLASS 0.5s

TECHNICAL SPECIFICATION OF 11 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET OF ACCURACY CLASS 0.5s TECHNICAL SPECIFICATION OF 11 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET OF ACCURACY CLASS 0.5s IMPORTANT NOTES: 01 Supplier should submit their offer in Annexure I and I-A & I-B only.

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities

More information

MESP TECHNICAL SPECIFICATION FOR CATENARY WIRE HARD-DRAWN COPPER 37/ mm 2

MESP TECHNICAL SPECIFICATION FOR CATENARY WIRE HARD-DRAWN COPPER 37/ mm 2 Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR CATENARY WIRE HARD-DRAWN COPPER 37/2.5 181mm 2 Version: 3 Issued: February 2017 Owner: Engineering Division Approved By: Andrew

More information

AM SGB Sdn Bhd. Company Profile. Transformer First Class

AM SGB Sdn Bhd. Company Profile. Transformer First Class AM SGB Sdn Bhd Company Profile Transformer First Class Company Background AM SGB AM SGB Sdn Bhd was locally incorporated in 1994 and commenced its production in Nilai early 1996. Starkstrom Gerätebau GmbH

More information

TECHNICAL SPECIFICATION OF 11 KV AND 22 KV THREE PHASE FOUR WIRE, THREE

TECHNICAL SPECIFICATION OF 11 KV AND 22 KV THREE PHASE FOUR WIRE, THREE TECHNICAL SPECIFICATION OF 11 KV AND 22 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET IMPORTANT NOTES: 01 Supplier should submit their offer in Annexure I and I-A & I-B only. Separate

More information

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD. Our Ref : 2/2018- Date : Messrs: Dear Sir, Tender 2/2018 Main Transformers You are kindly requested to quote for the supply and delivery DDP to our stores the transformers detailed in the attached schedules

More information

DISTRIBUTION TRANSFORMER kv

DISTRIBUTION TRANSFORMER kv ELECTRICITY COMMISSION PLANNING AND STUDY DEP BAGHDAD, REPUBLIC OF IRAQ SPECIFICATION No. D-26 DISTRIBUTION TRANSFORMER kv REVISION YEAR 2001 DISTRIBUTION TRANSFORMERS 1- SCOPE OF THE TENDER : Tenderer

More information

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

Neutral Earthing. For permanent or temporary neutral earthing in HV systems Neutral Earthing Resistors RESISTORS For permanent or temporary neutral earthing in HV systems For continuous or temporary low-resistance neutral grounding in medium voltage systems Neutral point connection

More information

11-SDMS-03 REV. 02 SPECIFICATIONS FOR

11-SDMS-03 REV. 02 SPECIFICATIONS FOR 11-SDMS-03 REV. 02 SPECIFICATIONS FOR XLPE INSULATED POWER CABLES FOR RATED VOLTAGES FROM 15 KV UP TO 36 KV (U m ) This specification is property of SEC and subject to change or modification without notice

More information

Basic Principles and Operation of Transformer

Basic Principles and Operation of Transformer Basic Principles and Operation of Transformer CONSTRUCTIONAL ASPECTS Cores In order to enhance core s magnetic properties, it is constructed from an iron and silicon mixture (alloy). The magnetic core

More information

ON LOAD TAP CHANGERS RS 6.3 / RS 6 TECHNICAL DATA

ON LOAD TAP CHANGERS RS 6.3 / RS 6 TECHNICAL DATA ON LOAD TAP CHANGERS RS 6.3 / RS 6 TECHNICAL DATA Hyundai Heavy Industries Co. Bulgaria 2017-2 EA 710. /1 EN Contents 1. Basic characteristics... 3 1.1. Basic technical data... 3 1.2. Rated through current

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities

More information

2.14 Main Cable Type HO7RN-F4G10-15 Metres each Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type

2.14 Main Cable Type HO7RN-F4G10-15 Metres each Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type PAGE 2 of 6 2.14 Main Cable Type HO7RN-F4G10-15 Metres each 2.15 (a) O/P Voltage-350V(Max.) (b) O/P Current 150A(Max.) 2.16 Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type 2.17

More information

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED)

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm 2 + 80mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of, 3C x95mm 2 +

More information

(

( (www.xatianhong.com) Introduction to XATH Xi'an Tianhong Electric Co., Ltd. (XATH) is a solely state-owned enterprise, set up by China Shipbuilding Industry Corporation (CSIC). It is one of the largest

More information

ULTRA-K Series 600K - he

ULTRA-K Series 600K - he 5 kva 500 kva ULTRA-K Series 600K - he High Efficiency K-Rated Power Conditioning Transformers Designed to be used with linear or non-linear loads. Applications: Audio / Video Recording Equipment IT Systems

More information

JULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

JULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum. FOREWORD This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C, N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared

More information

MESP TECHNICAL SPECIFICATION FOR FLEXIBLE DROPPER WIRE TIN-BEARING COPPER 7/7/ mm 2

MESP TECHNICAL SPECIFICATION FOR FLEXIBLE DROPPER WIRE TIN-BEARING COPPER 7/7/ mm 2 Engineering Specification Electrical Networks MESP 130400-02 TECHNICAL SPECIFICATION FOR FLEXIBLE DROPPER WIRE TIN-BEARING COPPER Version: 1 Issued: November 2015 Owner: Engineering Division Approved By:

More information

GENERAL PURPOSE DRY-TYPE DISTRIBUTION TRANSFORMERS

GENERAL PURPOSE DRY-TYPE DISTRIBUTION TRANSFORMERS GENERAL PURPOSE DRY-TYPE DISTRIBUTION TRANSFORMERS Acme offers a large selection of Dry-Type Distribution Transformers. Ranging from 600 Volt and below, in both Single and Three Phase, you re sure to find

More information

ECP COMPACT AND MICRO SUBSTATION COMMISSIONING PROCEDURE

ECP COMPACT AND MICRO SUBSTATION COMMISSIONING PROCEDURE Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0507 COMPACT AND MICRO SUBSTATION COMMISSIONING PROCEDURE EPN, LPN, SPN This procedure details the testing and commissioning procedures for

More information

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL PART 1: GENERAL 1. SCOPE This specification covers the design, engineering, manufacture, testing, supply, delivery, offloading and performance requirements of 11/0.433kV distribution transformers for outdoor

More information

Gas-Insulated Medium-Voltage Switchgear siemens.com/8dab12

Gas-Insulated Medium-Voltage Switchgear siemens.com/8dab12 8DB 12 blue GIS Gas-Insulated Medium-Voltage Switchgear siemens.com/8dab12 Features Gas-insulated switchgear (GIS) type 8D/B has been an integral part of the medium-voltage portfolio at Siemens for more

More information

Compact Substation or Prefabricated Substation Inside Totally Enclosed Weatherproof Enclosure COPYRIGHT REGISTERED

Compact Substation or Prefabricated Substation Inside Totally Enclosed Weatherproof Enclosure COPYRIGHT REGISTERED Dial : (033)2677-5835 & 2667-8358 Tele Fax : (033)2667-8358 Manufacturer of Dry Type Transformers E-mail : unimag111@gmail.com Office & Factory : 26/5, Sarat Chatterjee Road, Howrah 711 104, West Bengal,

More information

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with

More information

Liquid-Filled Transformers

Liquid-Filled Transformers Liquid-Filled Transformers Custom Transformers at Standard Prices NIAGARA TRANSFORMER CORP. Induction Furnace Transformer Cycloconverter Rectifier Duty Transformer Arc Furnace Transformer Full Range of

More information

1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured)

1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured) WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (A Govt. of West Bengal Enterprise) Office of the Chief Engineer, Procurement & Contracts Department Vidyut Bhavan, 4 th. floor, Bidhannagar,

More information

POTENTIAL TRANSFORMER

POTENTIAL TRANSFORMER POTENTIAL TRANSFORMER September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:

More information

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment International Research Journal of Engineering and Technology (IRJET) eissn: 23 0056 Volume: 04 Issue: 02 Feb 2017 www.irjet.net pissn: 072 A Review Comprehension: Guideline for Testing of HV, EHV and UHV

More information

Test Report CESI A6/ Approved Page 1. MF Trasformatori s.r.l. - Calcinato (BS) Italy

Test Report CESI A6/ Approved Page 1. MF Trasformatori s.r.l. - Calcinato (BS) Italy A6/028659 Test Report CESI Approved Page 1 Client MF Trasformatori s.r.l. - Calcinato (BS) Italy Tested equipment Non-enclosed three-phase dry-type power transformer with three windings, with encapsulated

More information

SECTION PANELBOARDS

SECTION PANELBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

GENERAL TECHNICAL SPECIFICATION (Turnkey Work)

GENERAL TECHNICAL SPECIFICATION (Turnkey Work) GENERAL TECHNICAL SPECIFICATION (Turnkey Work) March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar,

More information

Plant Client Contract Code Document ID Contract No. TECHNICAL SPECIFICATIONS DC SHUNT Rev 00 Page 1 of 2

Plant Client Contract Code Document ID Contract No. TECHNICAL SPECIFICATIONS DC SHUNT Rev 00 Page 1 of 2 TECHNICAL SPECIFICATIONS Rev 00 Page 1 of 2 0 IFI Release for Enquiry 14/12/18 SSS 14/12/18 HGG 14/12/18 RBU - Rev. Status Description Date Prepared Date Checked Date Approved AC Based on: PIN-QMC-03-F101

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION Single-Phase Low Voltage Dry- Type Transformers 5-400 kva Three-Phase Low Voltage Dry- Type Transformers 7.5-1000 kva TECHNICAL INFORMATION TABLE OF CONTENTS Introduction...3 Technical Explanations...4

More information

CHIEF ENGINEER PROCEDURE MANAGEMENT OF OVERLAPPING DESIGN AGREEMENT

CHIEF ENGINEER PROCEDURE MANAGEMENT OF OVERLAPPING DESIGN AGREEMENT Approval Amendment Record Approval Date Version Description 30/05/2014 1 Initial issue under MTM. This procedure supersedes the Overlapping Design Agreement, Application and Transfer Log documents L2-SIG-PRO-007,

More information

Test description for dry-type transformers chapter for special tests

Test description for dry-type transformers chapter for special tests Test description for dry-type transformers chapter for special tests 1. SCOPE 4 2. STANDARDS 5 3. LIGHTNING IMPULSE TEST 6 4. SOUND LEVEL MEASUREMENT 7 4.1. STANDARD 7 4.2. AIM 7 4.3. THEORETICAL PRINCIPAL

More information

Technical Specifications for Portable 3-Ø Power Analyzer

Technical Specifications for Portable 3-Ø Power Analyzer Technical Specifications for Portable 3-Ø Power Analyzer SCOPE: This specification covers the general specifications of 3-phase power analyzer that can be used to measure the no load and full load losses

More information

Ritz Instrument Transformers GmbH. Welcome

Ritz Instrument Transformers GmbH. Welcome Ritz Instrument Transformers GmbH Welcome About Ritz together with over 200 years of experience in instrument transformer production since 1945 since 1945 since 1945 since 1904 RITZ Group - Organization

More information