All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.

Size: px
Start display at page:

Download "All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid."

Transcription

1 1. Scope This specification defines the methods, the procedures and the requirements to verify the cables manufactured according to I.E.C. Specifications NPS Standards All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid. Relevant standards: IEC Publication 60060: High Voltage Test Techniques. Israel standard 65 (Identified to IEC Publication 60228: Conductors of Insulated Cables ). IEC Publication 60230: Impulse Test on Cables and their Accessories. Israel standard 1516 (Identified to IEC ) "Extruded Solid Insulated power cable for rated voltages up to 30kV" HD Publication 620 part 5C: Cross linked PE Insulated Cables. DIN VDE : Additional test method. IEC Publication 60811, Common test methods for insulating and sheathing materials of electric cables. IEC Publication : Test methods for partial discharge measurements on lengths of extruded power cables. American Standard ICEA S66524 In case of differences between the present specification and the above the mentioned 3. Requirements for Test Certificates The following information is necessary on each test certificate: The name of the cable factory; The name and address of the testing laboratory (if the testing laboratory does not belong to the cable factory); The test certificate serial number; The certificate issue date;

2 Test reports of the special test shall specify the batch number of the cables to which they pertain; Manufacturer s evaluation of the test results; A signature of the person responsible for tests and his position. The test certificate should contain results for each test according to the test requirements with references to appropriate Clauses and SubClauses of Standards and Specifications. 4. Test Conditions 4.1. Ambient Temperature Test shall be made at an ambient temperature of C Frequency and Waveform of Power Frequency Test Voltages The frequency of the alternating test voltages shall be in the range 49 Hz to 61 Hz. The waveform shall be substantially sinusoidal. The values quoted are r.m.s values Waveform of Impulse Test Voltage In accordance with IEC Publication 60230, the impulse wave shall have a virtual front time between 1 s and 5 s and in other respects shall be in accordance with IEC Publication

3 5. Rounding of the test results The test results shall be rounded in accordance with Appendix C of IEC Publication 60502, part Routine tests 6.1. The routine tests shall be carried out on each manufactured length of the cable on the delivery drum. The routine tests requirements are: a) Measurement of the conductor electrical resistance (SubClause 6.2); b) Partial discharge test (SubClause 6.3); c) Measurement of the metallic screen electrical resistance (SubClause 6.4); d) Highvoltage test (SubClause 6.5); e) Outer protective sheath spark test (SubClause 6.6); f) Outer protective sheath integrity visual inspection (SubClause 6.7) Measurement of the conductor electrical resistance a) The complete cable length shall be kept in the test room, which shall be maintained at a reasonable constant temperature for at least 12 hours before the measurement. The measured value of resistance shall be corrected to the temperature of 20 C and 1 km length in accordance with Clause 6 of IEC Publication b) The dc. resistance of the conductor at 20 C shall not exceed the appropriate maximum value specified in IEC Publication Partial Discharge Test a) The partial discharge test shall be carried out in accordance with IEC Publication b) The magnitude of the partial discharge at 2U 0 shall not exceed 5 pc.

4 6.4. Measurement of the Metallic Screen Electrical Resistance The dc. resistance of the metallic screen at 20 C shall not exceed the appropriate maximum value specified in I.E.C. Specification NPS A.C. High Voltage Test Test Procedure The test voltage shall be applied for 5 minutes between the conductor and the metallic screen Test voltage The test voltage shall be 3.5U Requirement No breakdown of the insulation shall occur Outer Protective Sheath Spark Test a) Test Procedure The cable shall be passed through the electrode (s) while the test voltage is applied between the electrode (s) and the grounded cable metallic screen. The test voltage shall be of 10 kv ac. minimum while the dwell time of the cable in the region of the test electrodes shall be not less than 0.15 s in accordance with the American standard ICEA S66524, NEMA WC 7. b) No breakdown of the outer protective sheath shall occur Outer protective sheath integrity visual inspection a) The test shall be carried out by visual inspection during the final stage of the cable manufacturing or during the cable rewinding onto the delivery drum.

5 b) The sheath has to be reasonably round, its surface has to be smooth, without visible irregularities, cracks, inflates, dents, hollows and so on. 7. Special Tests 7.1. General The special tests shall be performed on the cable samples taken from the cable lengths on the drums belonging to the batches mentioned in SubClause 7.2. The special tests requirements are: a) Conductor Examination (SubClause 7.4); b) Check of Dimensions (SubClause 7.5); c) High Voltage Test (SubClause 7.6); d) Hot Set Test (SubClause 7.7); e) Insulation Imperfection discovering and Measurements (SubClause 7.8).

6 7.2. Sampling for Special Tests Sampling of the cable for the Special Test shall be performed according to the following table: *) Definition Total number of drums in the cable batches *) Repetition of Tests Cables shall be considered of the same batch if they are manufactured continuously without interruption from the same batch of insulation material with no alteration in the setting of the manufacturing machines. If one of the samples fails in any of the special tests, the manufacturer shall immediately inform the purchaser. The decision concerning further sampling and testing shall then be the prerogative of the purchaser, taking into consideration the failure cause. Above up to and including etc. Number of cable drums from which samples shall be tested etc Conductor Examination The conductor construction shall comply with the requirements of I.E.C specifications and shall be examined by visual inspection and by measurement when practicable Check of Dimensions

7 The dimensions of the cables shall be measured as specified in Table 1 of this specification. The test result shall comply with the requirements given in the relevant clauses of NPS361 Specifications. Table 1 Test methods for cable dimensions 1. Conductor screen (HD605, sub clause ) The smallest thickness Irregularities 2. Insulation ((IEC Publication and ) The average thickness The smallest thickness Difference between maximum and minimum value of thickness Diameter over insulation 3. Insulation screen (HD605, sub clause ) The smallest thickness The maximum thickness The difference between the lowest and the highest value over the insulation screen 4. Metallic screen The wire diameter and the tape thickness shall be measured by means of a micrometer having two flat noses to the accuracy of ±0.01 mm. The average copper tape thickness The wire diameter The calculated crosssectional area of the screen

8 Table 1 (continued) Tests 5. Outer protective sheath (IEC Publication and ) The average thickness The smallest thickness 6. Cable outer diameter ((IEC Publication ) The outer diameter, maximum The outer diameter, minimum 7.6. High Voltage Test a) Sampling: The sample shall be a piece of the completed cable at least 5 m in length between the test accessories. b) Procedure: A power frequency test voltage shall be applied for 4 h at a room temperature between the conductor and the metallic screen. c) Test Voltage: The test voltage shall be 4U 0. d) Requirement: 7.7 Hot Set Test No breakdown of the insulation shall occur. The sampling and test procedure shall be carried out in accordance with the IEC Publication , using conditions and requirements given in Table 3 of this Specification.

9 7.7. Imperfection Discovering and Measurement a) The test procedure shall be as follows: The test specimen with the outer semiconducting layer removed shall be placed in a heated air convection oven at the temperature of 80ºC for two hours. Then the test specimen shall be placed in a glass tube filled with hot silicone oil at the temperature of 130ºC or, if necessary, higher up to about 150ºC, until the XLPE insulation becomes fully transparent. The test specimen shall be then examined with the naked eye with the help of lighting and recognized imperfections or irregularities shall be marked on the surface of the specimen. Then the specimen shall be cooled to a room temperature. To enable the measurement of the ascertained imperfections the test specimen shall be cut at the marked points, in thin slices. b) Requirements The imperfections found with the above mentioned procedure shall answer the following requirements: they are only permitted as separate cases; The imperfections with the largest size less than 0.05 mm should not be taken into account; The imperfections with the largest size more than 0.2 mm are not permitted. In the presence of imperfections with the largest size in the range from 0.05 mm to 0.2 mm, the repeated test should be performed; in this test any imperfections with largest size more than 0.05 mm should not be found.

10 8. Type Tests 8.1. General a) The tests shall be carried out on samples of the cable of the same type to be manufactured and supplied. The manufacturer shall submit to the bid type test certificates according to I.E.C Specifications NPS361. b) The type tests shall comprise of the electrical tests on completed cable specified in SubClause 8.2 and the nonelectrical test of the cable components specified in SubClause Electrical Type Tests General a) The electrical type tests shall be performed on samples of completed cable, at least 10 m in length between the test accessories. b) With the exceptions of the provisions of SubClause all the tests listed in SubClause shall be applied successively to the same sample Sequence of Tests The normal sequence of tests shall be: a) Partial discharge test; b) Bending test plus the partial discharge test; c) Tan measurement as a function of the temperature; d) Heating cycle test plus the partial discharge test; e) Impulse withstand test followed by the power frequency voltage test; f) Highvoltage alternating current test; g) Measurements of electric resistivity of the semiconducting layers.

11 Special Provisions a) Test (c and d) may be carried out on different samples from the sample used for the normal sequence of tests listed in SubClause b) A new sample may be taken for test g), provided this test sample is submitted previously to test b) and e) listed in SubClause Test methods and requirements for the electrical type tests are given in Table 2 of this Specification. Table 2 1. Partial Discharge Test (IEC Publication, subclause ) Tests Units Requirements 1.1 Test voltage 1.2 Partial discharge, maximum kv pc 2U Bending Test (IEC Publication, sub clause ) 2.1 Diameter of test cylinder 20 (dd) 5, where: D actual external diameter of the cable; d actual diameter of the cable conductor; 2.2 Number of test cycles 2.3 Partial discharges, maximum mm mm pc Tan measurement as a function of the temperature (IEC Publication. Sub clause ) 3.1 Test voltage 3.2 Tan at ambient temperature, maximum Tan at (90 2) C, maximum kv Table 2 (continued) Tests Units Requirements

12 4. Heating cycle test (IEC Publication. Sub clause ) 4.1 Temperature at the test, maximum 4.2 Time of heating, minimum 4.3 Time of natural cooling, minimum 4.4 Number of heating/cooling cycles 4.5 Partial discharges, maximum C h h pc Impulse withstand test (IEC Publication , SubClause ) 5.1 Conductor temperature 5.2 Impulse form 5.3 Impulse test voltage 5.4 Number of impulses C s kv 90 (5 10) C 1.2/ pos. 10 neg. 6. A.C. voltage test (IEC Publication , SubClause ) 6.1 Test voltage 6.2 Time of the test voltage application kv min 3.5 U High voltage test for 4 h (IEC Publication , SubClause ) 7.1 Test voltage 7.2 Time of the test voltage application kv h 4 U 0 4 Table 2 (continued) Tests Units Requirements 8. Measurements of electric resistivity of the semiconducting layers (IEC Publication Appendix D) 8.1 Resistivity of the conductor screen at 90 C, maximum 8.2 Resistivity of the insulation screen at 90 C, maximum Ohm m Ohm m

13 8.3 NonElectrical Type Test The nonelectrical type tests are listed in the following table: Tests XLPE Insulation ST7 Outer Sheath 1. Check of the cable construction 2. Mechanical properties (tensile strength and elongation): Before aging After aging in an air oven After aging of pieces of the complete cable 3. Hot set test 4. Pressure test at a high temperature 5. Carbon black content 6. Shrinkage test 7. Test of longitudinal water tightness in the screen area

14 8.3.1 Check of the Cable Construction Check of dimensions and the examination of the conductor shall be carried out in accordance with the requirements of SubClause 7.4 and Test methods and requirements for the nonelectrical type tests are given in Table 3 of this Specification Test of longitudinal watertightness in the screen area a) Sample The test shall be made on a 3 m long piece of the cable cut from the sample undergone the bending test described in Clause 2 of Table 2 without additional partial discharge test. b) Test Method The test shall be carried out in accordance with the method described in Appendix F of IEC Publication c) Evaluation During the period of testing no water shall emerge from the ends of the test piece

15 Table 3 Tests Units XLPE Insulation ST7 Outer Sheath 1 Mechanical Properties 1.1 Before ageing (IEC Publication Clause 9) Tensile strength, minimum Elongation at break, minimum N/mm After ageing of test pieces and pieces of complete cable (IEC Publication , Clause 8) Treatment: Temperature for the test pieces; for the complete cable Duration for the test pieces; for the complete cable C C days days Tensile strength: Variation maximum Elongation on break: Residual value, min. 25 variation, maximum Pressure Test at High Temperature (IEC Publication , Clause 8) 2.1 Test temperature 2.2 Time under load 2.3 Depth of indentation, maximum C hours Table 3 (continued) Tests Units XLPE Insulation ST7 Outer Sheath

16 3. Hot set test (IEC Publication , Clause 9). 3.1 Treatment: Air temperature Time under load Mechanical stress 3.2 Elongation under load, maximum C min N/mm Permanent elongation after cooling, maximum Shrinkage test (IEC Publication , Clause 10) 4.1 Treatment: Temperature Duration 4.2 Heating cycles 4.3 Permissible shrinkage, maximum C hours Carbon black content (IEC Publication , Clause 11) Qualification tests Qualification tests are intended to demonstrate the capability of the manufacturer to supply high quality cable with the desired performance characteristics. The Qualification tests shall be performed optionally on samples of a completed cable according to the requirements of the HD Publication 620 part 5c, clause 6.6 or a similar national standard upon agreement between the manufacturer and the purchaser. 9. Acceptance test The acceptance tests shall be performed according to I.E.C. Specification No. S2000/3/7.10.

REPORT OF PERFORMANCE TIC

REPORT OF PERFORMANCE TIC REPORT OF PERFORMANCE TIC 1580-13 OBJECT TYPE Three-core power cable 18/30(36) kv, 3x500 mm2, 2XWY(P)-FR XLPE Rated voltage, U 0/U (U m) 18/30 (36) kv Conductor material Cu Conductor cross-section 3x500

More information

76 / 132 (145) kv 1x1200 mm 2 CU/XLPE/CWS/AL/HDPE

76 / 132 (145) kv 1x1200 mm 2 CU/XLPE/CWS/AL/HDPE 09-1026 TYPE TEST CERTIFICATE OF COMPLETE TYPE TEST OBJECT single-core power cable TYPE 76 / 132 (145) kv 1x1200 mm 2 CU/XLPE/CWS/AL/HDPE Rated voltage, U o /U (U m ) 76/132 (145) kv Conductor material

More information

conductor Extruded Cross - Linked Polyethylene Insulated (XLPE) Power Cable Rated Voltage U 0 /U = 12/20 kv U 0 /U = 18/30 kv

conductor Extruded Cross - Linked Polyethylene Insulated (XLPE) Power Cable Rated Voltage U 0 /U = 12/20 kv U 0 /U = 18/30 kv Israel Electric Corporation Ltd. - Customer Division - National Network Unit Issued date: February 2018 THE ISRAEL ELECTRIC CORPORATION LTD. National Network Unit Specification No. NPS - 361 for Single

More information

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED)

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm 2 + 80mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of, 3C x95mm 2 +

More information

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES 1. Qualifying Requirement of AB Cable Manufacture/Supplier The manufacturer should have manufactured, successfully type tested

More information

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION December 2016 SPECIFICATION 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION

More information

This Certificate consists of 75 pages in total.

This Certificate consists of 75 pages in total. Object Heat shrinkable indoor termination 1086-16 Type MZDNK-3-15-C Rated voltage, U 0 /U (U m ) 8,7/15 (17,5) kv Conductor material Cu Conductor cross-section 3 x 185 mm 2 Insulation material XLPE Manufacturer

More information

11-SDMS-03 REV. 02 SPECIFICATIONS FOR

11-SDMS-03 REV. 02 SPECIFICATIONS FOR 11-SDMS-03 REV. 02 SPECIFICATIONS FOR XLPE INSULATED POWER CABLES FOR RATED VOLTAGES FROM 15 KV UP TO 36 KV (U m ) This specification is property of SEC and subject to change or modification without notice

More information

Testing Manual for Electrical Equipment

Testing Manual for Electrical Equipment EPPM, Singapore, 20-21 Sep 2011 Abstract Testing Manual for Electrical Equipment Nahed Al-Hajeri 1 and Anantha Madhavan 2 Quality Assurance (QA) refers to a program for the systematic monitoring and evaluation

More information

Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES. 11 kv XLPE-Insulated Three-Core Underground Cables

Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES. 11 kv XLPE-Insulated Three-Core Underground Cables Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES ( Data Sheets ) 11 kv XLPE-Insulated Three-Core Underground Cables (3x240 mm 2 ) ADWEA/ADDC/AADC STANDARD : D-AAA-CAB-11-3Cx240

More information

SANS 1339:2010 Electric cables Cross-linked polyethylene (XLPE) insulated cables for rated voltages 3,8/6,6 kv to 19/33 kv

SANS 1339:2010 Electric cables Cross-linked polyethylene (XLPE) insulated cables for rated voltages 3,8/6,6 kv to 19/33 kv DRAFT SOUTH AFRICAN STANDARD (DSS): PUBLIC ENQUIRY STAGE Document number: 66/1339/4 Reference: SANS 1339 Date of circulation: 2009-12-08 Closing date: 2010-02-08 Number and title: SANS 1339:2010 Electric

More information

Tests on Extruded Cables

Tests on Extruded Cables Tests on Extruded Cables Pierre Argaut Chairman of CIGRE SC B1 October 26 th, 2011 At least, once in your life, you have heard these words: Development Tests Long-term Tests Prequalification Tests Extension

More information

TECHNICAL SPECIFICATION FOR. CONTACT WIRE HARD-DRAWN COPPER 161mm2

TECHNICAL SPECIFICATION FOR. CONTACT WIRE HARD-DRAWN COPPER 161mm2 Engineering Specification Electrical TECHNICAL SPECIFICATION FOR CONTACT WIRE HARD-DRAWN COPPER 161mm2 Version: 2 Issued: May 2018 Owner: Engineering Approved by: Andrew Russack, Head of Engineering Electrical

More information

Date: / TECHNICAL SPECIFICATIONS FOR 11 KV XLPE INSULATED UNDERGROUND CABLES

Date: / TECHNICAL SPECIFICATIONS FOR 11 KV XLPE INSULATED UNDERGROUND CABLES 1 Date:19.09.2013/08.01.2014 TECHNICAL SPECIFICATIONS FOR 11 KV XLPE INSULATED UNDERGROUND 1.0 SCOPE: CABLES 1.1 The scope of this specification covers the design, manufacture, stage inspection at works,

More information

CERTIFICATE OF CONFORMANCE

CERTIFICATE OF CONFORMANCE CERTIFICATE OF CONFORMANCE This is to confirm that Honeywell Airports Business have verified Tinned Copper Braided Screened Primary Cable supplied by PT Jembo Cable Company Tbk (Indonesia) for airfield

More information

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS 1.0 SCOPE 2.0 BONDING METHODS 2.1 Introduction 2.2 Design 2.3 Single-Point Bonding 2.4 Cross Bonding 2.5 Sheath Sectionalizing Joints 2.6 Sheath Standing Voltage 2.7 Sheath Voltage at Through Fault 2.8

More information

HO7RN-F 450/750V BS EN Highly Flexible Rubber Cable

HO7RN-F 450/750V BS EN Highly Flexible Rubber Cable Rubber Insulation and Rubber Sheathed Application Range Heavy duty flexible cables for medium mechanical stress For dry and wet applications Can be used for domestic electric tools According to HD 516

More information

NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations

NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations Version: 3.1 Date of Issue: September 2016 Page: 1 of 21 NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations 1. Purpose The purpose of this document is to detail the technical requirements

More information

SUBMERSIBLE PUMP CABLES

SUBMERSIBLE PUMP CABLES 12 SUBMERSIBLE PUMP CABLES 1-450 / 750 V Termoplastic rubber, round orflat flexibe cable ACCORDING TO NF C -102 HD 22.4 S2 Water absorption tests: IEC 811.1.3 VDE 0472 Teil 2 NF C -026 HD 505-1-3 s1 Maximum

More information

Type Test of a 145 kv Termination Type TS 145-II

Type Test of a 145 kv Termination Type TS 145-II Test Report No 2009-125/2 Type Test of a 145 kv Termination Type TS 145-II Client: 3 M Deutschland GmbH Carl-Schurz-Str.1 41453 Neuss Reporter: Dr.-Ing. R. Badent Dr.-Ing. B. Hoferer This report includes

More information

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS -1- INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION June 2013 SPECIFICATION No 150 kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS I. SCOPE This specification

More information

HYDROFIRM (T) Cables. for use in Ground Water and Drinking Water

HYDROFIRM (T) Cables. for use in Ground Water and Drinking Water HYDROFIRM (T) Cables for use in Ground Water and Drinking Water Finely stranded copper conductor EPR insulation Special synthetic rubber sheath Until now, the renowned HYDROFIRM TGK cables were available

More information

MV water-proof and water tree retardant power cable

MV water-proof and water tree retardant power cable MV water-proof and water tree retardant power cable 1 Standard GB/T16-8 1kV 35kV, IEC The products should be manufactured according to standard GB/T16-8 and also as per IEC, BS and HD as requested. 2 Application

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM Technical Specification of Back Clamp for LT Cross Arm (MS) Back clamp for LT Cross Arm made out of 50 x 6mm MS Flat suitable for 8m X 300 Kg PSC poles. After fabrication the cross arm shall be painted

More information

IEC Standard Caledonian Offshore & Marine Cables

IEC Standard Caledonian Offshore & Marine Cables Power Copper s According to IEC 60228 Tinned conductors Cross section cl.2 cl.5 Cross section cl.2 cl.5 mm² Ohm/km Ohm/km mm² Ohm/km Ohm/km 1.0 18.2 20 70 0.270 0.277 1.5 12.2 13.7 95 0.195 0.210 2.5 7.56

More information

SOLARLOK PV BAR Junction Box

SOLARLOK PV BAR Junction Box SOLARLOK PV BAR Junction Box Table of contents 1. SCOPE... 2 1.1. Content... 2 1.2. Qualification... 3 2. APPLICABLE DOCUMENTS... 3 2.1. TE Connectivity Documents... 3 2.2. Commercial Standard... 3 3.

More information

1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured)

1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured) WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (A Govt. of West Bengal Enterprise) Office of the Chief Engineer, Procurement & Contracts Department Vidyut Bhavan, 4 th. floor, Bidhannagar,

More information

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS AMENDMENT NO. 1 SEPTEMBER 2011 TO IS 15086 (Part 1) : 2001/IEC 60099-1 (1991) SURGE ARRESTORS PART 1 NON-LINEAR RESISTOR TYPE GAPPED SURGE ARRESTORS FOR a.c. SYSTEMS (The Amendment was originally published

More information

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL Issued by: Approved by: Engineering Department Energy+ Inc. September 2016 Shawn Jackson, P.Eng. Approval is given in accordance with

More information

GLOBAL STANDARD Page 1 of 66 UNDERGROUND MEDIUM VOLTAGE CABLES UNDERGROUND MEDIUM VOLTAGE CABLES

GLOBAL STANDARD Page 1 of 66 UNDERGROUND MEDIUM VOLTAGE CABLES UNDERGROUND MEDIUM VOLTAGE CABLES GLOBAL STANDARD Page 1 of 66 Countries I&N Argentina Brazil Chile Colombia Italy Peru Romania Spain R. De Antoni V. Robadey D. Gonzalez J. C. Gomez L. Giansante R. Sanchez V. Obrejan J. Gonzalez Elaborated

More information

High Voltage Instrumentation Cables for the ITER Superconducting Magnet Systems

High Voltage Instrumentation Cables for the ITER Superconducting Magnet Systems High Voltage Instrumentation Cables for the ITER Superconducting Magnet Systems Summary for Call for Nominations 1. Background and scope ITER will be the world's largest experimental facility to demonstrate

More information

Medium Voltage Power Cables

Medium Voltage Power Cables N2XSY 6/0, /20, /30 NA2XSY 6/0, /20, /30 N2XS2Y 6/0, /20, /30 NA2XS2Y 6/0, /20, /30 N2XS(F)2Y 6/0, /20, /30 NA2XS(F)2Y 6/0, /20, /30 N2XSEY 3 x 6/0 Medium Voltage Power Cables Photo: HELUKABEL Q 47 Medium

More information

ELECTRICAL R&D LABORATORY SPECIFICATION FOR TESTS OF COMPRESSION AND MECHANICAL CONNECTORS AND TERMINAL LUGS FOR POWER CABLES WITH COPPER

ELECTRICAL R&D LABORATORY SPECIFICATION FOR TESTS OF COMPRESSION AND MECHANICAL CONNECTORS AND TERMINAL LUGS FOR POWER CABLES WITH COPPER Israel Electric Corp. Ltd. Strategic Resources Group Planning Development & Technology Division ELECTRICAL R&D LABORATORY SPECIFICATION FOR TESTS OF COMPRESSION AND MECHANICAL CONNECTORS AND TERMINAL LUGS

More information

7. INSPECTION AND TEST PROCEDURES

7. INSPECTION AND TEST PROCEDURES 7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect

More information

HIGH PRESSURE MOULDING TECHNOLOGY

HIGH PRESSURE MOULDING TECHNOLOGY HIGH PRESSURE MOULDING TECHNOLOGY Romuald Lemaitre, Pierre Gaillard, Franck Tortey, Paul Woodward franck.tortey@alcatel-lucent.fr Alcatel - Lucent, 536 Quai de La Loire 62100 Calais Abstract: The Optical

More information

Testing 320 kv HVDC XLPE Cable System

Testing 320 kv HVDC XLPE Cable System Testing 320 kv HVDC XLPE Cable System H. He, W. Sloot DNV GL, KEMA Laboratories Arnhem, The Netherlands Abstract Two unique test requirements in testing of a high- voltage direct- current (HVDC) cable

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 1. Introduction Fault location on communication and power cables

More information

Specification for pvc-insulated cables for electricity supply

Specification for pvc-insulated cables for electricity supply KENYA STANDARD KS 194: 2018 ICS 29.035.01 Specification for pvc-insulated cables for electricity supply (Third Revision, 2018) PUBLIC REVIEW DRAFT, FEBRUARY 2018 TECHNICAL COMMITTEE REPRESENTATION The

More information

EXTREMELY LOW MAGNETIC FIELD (ELMF) XLPE INSULATED CABLES, TYPE N2XY/FR1 0.6/1 KV

EXTREMELY LOW MAGNETIC FIELD (ELMF) XLPE INSULATED CABLES, TYPE N2XY/FR1 0.6/1 KV CABLE DESCRIPTION Single- or multi-phase electric cable for creating a weak external magnetic field,so as to obtain a cable wherein at last one of the conductors is assembled from two or more insulated

More information

JULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

JULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum. FOREWORD This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C, N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared

More information

Comparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137

Comparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137 ITEM Power factor (tanδ) & Capacitance Measurement Dry 1-minute Power frequency with partial discharge measurement CAN/CSA C88.1-96 IEEE C57.19.00/01 IEC 60137 Requirement Requirement Requirement Clause

More information

RESISTOR, FIXED, CHIP, METAL FOIL BASED ON TYPE SMP-PW, SMS-PW, SMT-PW. ESCC Detail Specification No. 4001/027

RESISTOR, FIXED, CHIP, METAL FOIL BASED ON TYPE SMP-PW, SMS-PW, SMT-PW. ESCC Detail Specification No. 4001/027 Page 1 of 14 RESISTOR, FIXED, CHIP, METAL FOIL BASED ON TYPE SMP-PW, SMS-PW, SMT-PW ESCC Detail Specification Issue 5 November 2017 Document Custodian: European Space Agency see https://escies.org PAGE

More information

Assuring the Reliability of Critical Power Cable Systems

Assuring the Reliability of Critical Power Cable Systems Assuring the Reliability of Critical Power Cable Systems Presented by: Benjamin Lanz Manager of Application Engineering IMCORP Power Cable Reliability Consulting & Diagnostics Some of the technologies

More information

XLPE CABLE (33KV) September Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

XLPE CABLE (33KV) September Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED XLPE CABLE (33KV) September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN: U40101WB2007SGC113474;

More information

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION 1. SCOPE : TECHNICAL SPECIFICATION FOR LIGHTNING ARRESTORS 1.1. This Specification covers design, manufacture, testing at manufacturer's Works, packing, supply, delivery of 42 KV

More information

Pre-printed PVC Cable Markers O-Type, K-type, Z-type, V-Type

Pre-printed PVC Cable Markers O-Type, K-type, Z-type, V-Type RW-2535 Issue 2 Page 1 of 17 Oct 2013 Specification RW-2535 Document Number: 108-121034 Pre-printed PVC Cable Markers O-Type, K-type, Z-type, V-Type SCOPE This quality assurance specification establishes

More information

ISO 783 INTERNATIONAL STANDARD. Metallic materials Tensile testing at elevated temperature

ISO 783 INTERNATIONAL STANDARD. Metallic materials Tensile testing at elevated temperature INTERNATIONAL STANDARD ISO 783 Second edition 1999-08-15 Metallic materials Tensile testing at elevated temperature Matériaux métalliques Essai de traction à température élevée A Reference number ISO 783:1999(E)

More information

On-load tap-changer VACUTAP VRD, VRF, VRG

On-load tap-changer VACUTAP VRD, VRF, VRG www.reinhausen.com On-load tap-changer VACUTAP VRD, VRF, VRG Technical Data TD 237/02 Table of Contents Table of Contents 1 General / Technical data... 3 1.1 On-load tap-changer designations... 3 1.2 Summary

More information

Prepared by Mick Maytum

Prepared by Mick Maytum IEC Technical Committee 109: Standards on insulation co-ordination for low-voltage equipment Warning Prepared by Mick Maytum mjmaytum@gmail.com The document content is of a general nature only and is not

More information

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION)

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION) 012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 8051 Fax: +94 11 232 5387 CONTENTS Page 1.0

More information

MESP TECHNICAL SPECIFICATION FOR CATENARY WIRE HARD-DRAWN COPPER 37/ mm 2

MESP TECHNICAL SPECIFICATION FOR CATENARY WIRE HARD-DRAWN COPPER 37/ mm 2 Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR CATENARY WIRE HARD-DRAWN COPPER 37/2.5 181mm 2 Version: 3 Issued: February 2017 Owner: Engineering Division Approved By: Andrew

More information

DNVGL-CP-0400 Edition December 2015

DNVGL-CP-0400 Edition December 2015 CLASS PROGRAMME Type approval DNVGL-CP-0400 Edition December 2015 The electronic pdf version of this document, available free of charge from http://www.dnvgl.com, is the officially binding version. FOREWORD

More information

INDEX OF REVISIONS DESCRIPTION AND/OR AFFECTED SHEETS

INDEX OF REVISIONS DESCRIPTION AND/OR AFFECTED SHEETS E&P Pag. 1 / 14 Pre-salt Standard Steel Tube Umbilical Types Umbilical Electrical Cable Element DPT-SUB/ES/DCT INDEX OF REVISIONS REV DESCRIPTION AND/OR AFFECTED SHEETS 0 Original ORIGINAL REV. A REV.

More information

SECTION MEDIUM-VOLTAGE CABLES

SECTION MEDIUM-VOLTAGE CABLES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 13 MEDIUM-VOLTAGE CABLES SPEC WRITER NOTE: Delete between //-----// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, and withstand

More information

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s Designed for Partial Discharge Analyzers (PDA s) monitoring rotating machinery or other medium-voltage equipment from 1 to 35 kvac RMS at power-line frequencies of 10 Hz to 1 khz, Mica Capacitor Type 297

More information

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland Company HV Diagnostics Sarl is a Swiss based company in the field of high voltage test equipment for cable testing and diagnosis.

More information

Underground System Design TADP 547

Underground System Design TADP 547 Underground System Design TADP 547 Industry Standards, Specifications and Guides Presentation 6.4 Instructor: Frank Frentzas Industry Organizations Several professional organizations develop standards

More information

CABLE JOINTING KITS &

CABLE JOINTING KITS & CABLE JOINTING KITS & POWER CABLE ACCESSORIES UPTO 36 KV CORE HEATSHRINK PRODUCTS COMPANY National Highway 73, 48, Tyagi Garden, Yamunanagar-135001, Haryana (India) +91-989-6001-519 +91-805-9001-519 +91-1732-260164

More information

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...

More information

TwenCombi Cat-5E FTP(3x) - Coax 9 - EIBA - tube PE 5 mm

TwenCombi Cat-5E FTP(3x) - Coax 9 - EIBA - tube PE 5 mm name: TKF article number: 10305 description Nr.: POE- PS- 10305 PT F F F 800 B C 1 2 3 4 5 6 7 Assembly: 1. Primary tube 5 mm 2. CAT 5 E FTP cable 3. CAT 5 E FTP cable 4. Bus cable 5. Coax 9 cable 6. Separation

More information

INSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT. LTD.

INSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT. LTD. (INDIA) VT. LTD. Clause Requirement Test Results Remarks Verdict 5 Marking and documentation 5.1 Marking 5.1.1 General Markings shall be visible from the exterior, or be visible after removing a cover

More information

Success Depends on the Crimp

Success Depends on the Crimp Success Depends on the Crimp Understanding the UL-486F Standard for Bare and Covered Ferrules Vince Barone, May 12, 2015 1 Agenda 2 What is a Ferrule? Ferrules are terminals that only have a barrel. They

More information

ECP HV INSULATION TESTING

ECP HV INSULATION TESTING Document Number: ECP 11-0006 Network(s): Summary: All ENGINEERING COMMISSIONING PROCEDURE ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing of new and

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

Cable Type 100. CAI Certification Specification

Cable Type 100. CAI Certification Specification Cable Type 100 CAI Certification Specification Ref: CAI-007-C / 100 / 12-2016 Confederation of Aerial Industries Ltd Communications House 41a Market Street WATFORD Herts WD18 0PN Tel: 01923 803030 Fax:

More information

شركة الوقت للكهرباء والمقاوالت ذ.م.م.

شركة الوقت للكهرباء والمقاوالت ذ.م.م. CONTRACTING COMPANY W.L.L. is a leading corporate in the United Arab Emirates offering quality services in the field of High Voltage Electrical work 400, 132 & 33 kv and Medium Voltage Power Distribution

More information

TPS 49 EDITION 2 JUNE 2009

TPS 49 EDITION 2 JUNE 2009 TPS 49 EDITION 2 JUNE 2009 Interim arrangements & guidance on the interpretation of IEC 61672 Sound Level Meters - Periodic Tests CONTENTS SECTION PAGE 1 Purpose and duration 2 2 Statement 2 3 Specific

More information

Substation HV Cables. Document Number: 1-11-FR-07

Substation HV Cables. Document Number: 1-11-FR-07 Substation HV Cables Document Number: 1-11-FR-07 VERSION 1.0 June 2018 This functional requirements document is in line with the organisation's 1-11-ACS-07 Substation HV Cables Asset Class Strategy Intellectual

More information

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

Power Frequency Withstand Voltage On-site testing of 400 kv GIS Power Frequency Withstand Voltage On-site testing of 400 kv GIS D. Anaraki Ardakani, A. Omidkhoda, M. Solati High Voltage Engineering Center ACECR Tehran, Iran Da_ardakani@yahoo.com Paper Reference Number:

More information

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP) Discipline Engineering Standard NSW Category Electrical Title Substation Auxiliary Transformer from Rectifier Transformer Secondary Reference Number PDS 01 (RIC Standard: EP 05 00 00 01 SP) Document Control

More information

ASTA TEST REPORT NO: HEATSHRINK TERMINATIONS 3 CORE 12kV PILC AND XLPE

ASTA TEST REPORT NO: HEATSHRINK TERMINATIONS 3 CORE 12kV PILC AND XLPE ASTA TEST REPORT NO: 2212 HEATSHRINK TERMINATIONS 3 CORE 12kV PILC AND XLPE UNIVERSAL 12kV HEATSHRINK JOINT TO SUIT 3 CORE XLPE / PILC CABLES INLINE OR TRANSITION RECORD OF PROVING TESTS Page 1 of 6 Laboratory

More information

Technical Specification. for 1.1 KV Copper Control Cable

Technical Specification. for 1.1 KV Copper Control Cable WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (A Govt. of West Bengal Enterprise) Office of the Chief Engineer, Procurement & Contracts Department Vidyut Bhavan, 4 th. floor, Bidhannagar,

More information

AEC-Q REV A June 1, 2000

AEC-Q REV A June 1, 2000 ATTACHMENT 4 AEC - Q200-004 - REV A MEASUREMENT PROCEDURES FOR RESETTABLE FUSES Page 1 of 19 NOTICE AEC documents contain material that has been prepared, reviewed, and approved through the AEC Technical

More information

Cable Type 125. CAI Certification Specification

Cable Type 125. CAI Certification Specification Cable Type 125 CAI Certification Specification Ref: CAI-008-C / 125 / 12-2016 Confederation of Aerial Industries Ltd Communications House 41a Market Street WATFORD Herts WD18 0PN Tel: 01923 803030 Fax:

More information

OIML R 75-2 RECOMMENDATION. Edition 2002 (E) ORGANISATION INTERNATIONALE INTERNATIONAL ORGANIZATION

OIML R 75-2 RECOMMENDATION. Edition 2002 (E) ORGANISATION INTERNATIONALE INTERNATIONAL ORGANIZATION INTERNATIONAL RECOMMENDATION OIML R 75-2 Edition 2002 (E) Heat meters Part 2: Type approval tests and initial verification tests Compteurs d énergie thermique Partie 2: Essais d approbation de type et

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD Provläsningsexemplar / Preview INTERNATIONAL STANDARD ISO 13079 First edition 2011-07-15 Laboratory glass and plastics ware Tubes for the measurement of the erythrocyte sedimentation rate by the Westergren

More information

Interference Suppression Film Capacitor - Class X2 Axial MKT 253 V AC - Continuous Across the Line

Interference Suppression Film Capacitor - Class X2 Axial MKT 253 V AC - Continuous Across the Line Interference Suppression Film Capacitor - Class X2 Axial MKT 253 V AC - Continuous Across the Line FEATURES Axial mounting Low building height Material categorization: for definitions of compliance please

More information

INSTRUCTIONS FOR THE SAFE APPLICATION OF CABLES

INSTRUCTIONS FOR THE SAFE APPLICATION OF CABLES THE SAFE APPLICATIO OF CABLES The cables manufactured by S are only appropriate for the transmission of electric energy for supply and signalling purposes. First of all the valid construction and installation

More information

SBCA Industry Standards Subcommittee. Specification for 75 Ω Flexible RF Coaxial Drop Cable for Direct Broadcast Satellite (DBS) Installations

SBCA Industry Standards Subcommittee. Specification for 75 Ω Flexible RF Coaxial Drop Cable for Direct Broadcast Satellite (DBS) Installations SBCA Industry Standards Subcommittee Document: SBCA Series 6 Recommended Practices Date of Issue: Specification for 75 Ω Flexible RF Coaxial Drop Cable for Direct Broadcast Satellite (DBS) Installations

More information

EDS LV WAVEFORM MAINS CABLE RATINGS

EDS LV WAVEFORM MAINS CABLE RATINGS Document Number: EDS 02-0033 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 02-0033 LV WAVEFORM MAINS CABLE RATINGS EPN, LPN, SPN This standard details the technical and practical information required

More information

INTERPLANT STANDARD - STEEL INDUSTRY

INTERPLANT STANDARD - STEEL INDUSTRY INTERPLANT STANDARD - STEEL INDUSTRY SPECIFICATION FOR MOULDED - CASE CIRCUIT-BREAKER FOR VOLTAGES NOT EXCEEDING 1000 V ac OR 1500 V dc (FIRST REVISION) IPSS:1-04-004-11 IPSS BASED ON IS/IEC 60947(Part

More information

EDS KV SINGLE CORE XLPE CABLES

EDS KV SINGLE CORE XLPE CABLES THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Document Number: EDS 02-0034 ENGINEERING DESIGN STANDARD EDS 02-0034 33KV SINGLE CORE XLPE CABLES Network(s): EPN, LPN,

More information

Standard Specification for Rubber Insulating Covers 1

Standard Specification for Rubber Insulating Covers 1 Designation: D 1049 98 (Reapproved 2002) e1 Standard Specification for Rubber Insulating Covers 1 This standard is issued under the fixed designation D 1049; the number immediately following the designation

More information

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD. Our Ref.: 14/2018- Date : Messrs: Dear sir, Tender 14/2018 11& 33 KV Lightning Arrestors. You are kindly requested to quote for the supply and delivery to our stores in Shufat Jerusalem, (DDP) of the following

More information

NXCT 345 kv Test Performance Record For LAPEM

NXCT 345 kv Test Performance Record For LAPEM 2005 NxtPhase T&D Corporation 2635 Lillooet St. Vancouver, Canada, V5M 4P7 www.nxtphase.com Tel: 604 215 9822 Fax: 604 215 9833 NXCT 345 kv Test Performance Record For LAPEM Information in this document

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60099-4 Edition 2.1 2006-07 Edition 2:2004 consolidated with amendment 1:2006 Surge arresters Part 4: Metal-oxide surge arresters without gaps for a.c. systems IEC 2006 Copyright

More information

MESP TECHNICAL SPECIFICATION FOR MURL JUMPER WIRE HARD-DRAWN COPPER 19/ mm 2

MESP TECHNICAL SPECIFICATION FOR MURL JUMPER WIRE HARD-DRAWN COPPER 19/ mm 2 Engineering Specification Electrical Networks MESP 130400-07 TECHNICAL SPECIFICATION FOR Version: 1 Issued: February 2017 Owner: Engineering Division Approved By: Andrew Russack Head of Engineering (Electrical)

More information

IEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4

IEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 IEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 This report records the results of type tests made on H4 series 20 ka Line Discharge Class

More information

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May 26 2011 St Pete Beach, Fl HDW ELECTRONICS, INC. THE BEST IN CABLE FAULT LOCATING TECHNOLOGY by Henning Oetjen Frank

More information

POLYIMIDE INSULATED WIRES AND CABLES, LOW FREQUENCY, 600V, -200 TO +200 C BASED ON TYPE SPL. ESCC Detail Specification No.

POLYIMIDE INSULATED WIRES AND CABLES, LOW FREQUENCY, 600V, -200 TO +200 C BASED ON TYPE SPL. ESCC Detail Specification No. Page 1 of 23 POLYIMIDE INSULATED WIRES AND CABLES, LOW FREQUENCY, 600V, -200 TO +200 C BASED ON TYPE SPL ESCC Detail Specification Issue 3 May 2013 Document Custodian: European Space Agency see https://escies.org

More information

Premoulded cable joint SMPGB

Premoulded cable joint SMPGB Premoulded cable joint SMPGB 362-420 Premoulded for safe and easy installation Active pressure Reliable Joint bodies routinetested according to IEC before delivery Bolt connector technology Compact joint

More information

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L. /9 TECHNICAL SPECIFICATIONS VOLTAGE LOW-POWER TRANSFORMER VS- Rev. Date Revision Description Prepared by Checked by Approved by 0 24/09/2 First issue A. Peretto L. Peretto 24/06/6 All text review E. Scala

More information

2/2 Introduction. Unequipped Distribution Boards 2/5 8GK1 surface and flush-mounting distribution boards

2/2 Introduction. Unequipped Distribution Boards 2/5 8GK1 surface and flush-mounting distribution boards Siemens AG 010 ALPHA 160 - DIN Wall-Mounted Distribution Boards / Introduction Distribution Boards with Built-In Distribution Board Panels /4 8GK1 surface and flush-mounting with quickassembly kits Unequipped

More information

TEST SUMMARY. Prüfbericht - Nr.: Test Report No.: Seite 2 von 27. Page 2 of 27

TEST SUMMARY. Prüfbericht - Nr.: Test Report No.: Seite 2 von 27. Page 2 of 27 15072768 001 Seite 2 von 27 Page 2 of 27 TEST SUMMARY 4.1.1 HARMONICS ON AC MAINS 4.1.2 VOLTAGE CHANGES, VOLTAGE FLUCTUATIONS AND FLICKER ON AC MAINS 4.1.3 MAINS TERMINAL CONTINUOUS DISTURBANCE VOLTAGE

More information

VSD cables in. Working with. industrial & automation applications

VSD cables in. Working with. industrial & automation applications Cable Efficiency in Automation Connectivity Cabinet Control Working with VSD cables in industrial & automation applications Description of a VSD System A functional VSD system consists of at least three

More information

INTRODUCTION NUHAS OMAN QUALITY & RELIABILITY.

INTRODUCTION NUHAS OMAN QUALITY & RELIABILITY. INTRODUCTION Nuhas Oman LLC, an integral part of The Al Bahja Group of Companies, is a Quality producer of: HV, MV and LV Cables Enamelled Copper Wires Oxygen Free Continuous Cast Copper Wire Rods Drawn

More information

A6.6 9 th International Conference on Insulated Power Cables A6.6

A6.6 9 th International Conference on Insulated Power Cables A6.6 Development Process of extruded HVDC cable systems Dominik HÄRING, Gero SCHRÖDER, Andreas WEINLEIN, Axel BOSSMANN Südkabel GmbH, (Germany) dominik.haering@suedkabel.com, gero.schroeder@suedkabel.com, andreas.weinlein@suedkabel.com,

More information