METERING REQUIREMENTS FOR INTERCONNECTION POINTS OF SERVICE

Size: px
Start display at page:

Download "METERING REQUIREMENTS FOR INTERCONNECTION POINTS OF SERVICE"

Transcription

1 METERING REQUIREMENTS FOR INTERCONNECTION POINTS OF SERVICE Author: AXLIU Origination Date: 05/07/2010 Version: 8.3 Revised By: Approver s Name: OXPAIS REROMAK REROMAK 1 PURPOSE Revision Date: 9/12/2016 Review By: 09/01/2017 Approver s Signature (If required by Std) Approval Date: 6/01/ To provide guidelines for SRP s requirements for revenue metering at the point(s) of interconnection with other entities. The revenue metering shall include the meter(s), associated current transformers (CTs) and voltage transformers (VTs), and any applicable associated equipment. 1.2 This document addresses compliance of NERC Standards and is posted on the OASIS website: Standard Requirement Description Effective Date BAL b R 12.3 Balancing Authorities shall install common metering equipment where Dynamic Schedules or Pseudo-Ties are implemented between two or more Balancing Authorities to deliver the output of Jointly Owned Units or to serve remote load. 5/13/ Requirements are defined in Section 5: Subsection Title Page 5.1 REVENUE METERS POLARITY STANDARD INSTRUMENT TRANSFORMERS METERING DATA TRANSFER & COLLECTION 6-7 Page 1 of 8

2 2 REFERENCES 2.1 IEEE Std. C IEEE Standard Requirements for Instrument Transformers 2.2 SRP Substation Construction Standard GS06.02 Instrument Transformers, Secondary Wire Designations 2.3 SRP Substation Construction Standard GS11.02 Instrument Transformer Schematic Diagram, Auxiliary Current and Potential Transformer Grounding 3 TERMS AND DEFINITIONS 3.1 CT: Current Transformer 3.2 VT: Voltage (Potential) Transformer 3.3 INSTRUMENT TRANSFORMERS: Current and voltage transformers that are associated with the revenue metering. 3.4 REVENUE METERING: All equipment involved to measure the power/energy flow and provide metering data. It shall include meter(s), current transformers, voltage transformers, communication path and protection equipment. 3.5 RTU: Remote Terminal Unit 3.6 SCADA: Supervisory Control And Data Acquisition 3.7 DNP: Distributed Network Protocol 3.8 CMS: Customer Metering Services to include Metering and Field Customer Services and Meter Engineering Support Page 2 of 8

3 4 RESPONSIBILITIES 4.1 Customer Metering Services (CMS) Provide guidance for Revenue Metering Requirements for Interconnection Metering. 1. Specify and approve metering equipment to be installed 2. Coordinate with other SRP groups and entities to provide required output data from the revenue meter(s) 3. Review and approve design of revenue metering circuits 4. Test and maintain revenue meters 5 REQUIREMENTS 5.1 REVENUE METERS Revenue grade metering equipment shall be required at each point of interconnection with the SRP system. 1. Depending on the expected load, meter(s) shall have a class 10 rating (accurate from A RMS) or a class 20 rating (accurate from A RMS) 2. Meters shall have a 0.3% or better accuracy rating 3. Meters shall be capable of measuring and providing additional parameters such as per phase quantities (i.e., volts, amps), frequency, etc. dependent on meter specifications and interconnection application requirements The revenue meter(s) shall consist of a single meter supplied and installed by either SRP or the interconnecting entity capable of measuring bidirectional, four quadrant watt and var parameters. 1. The point of revenue metering installation shall be at the point of interconnection between entities wherever possible. 2. If the point of interconnection or boundary is located at a remote point that prohibits feasible metering equipment installation, the metering equipment shall be installed at the closest practical point. Page 3 of 8

4 3. The meter shall be programmatically compensated to account for impedance and losses between the physical metering point and the defined interconnection/boundary point. If a meter is compensated, the compensation values and calculations will be reviewed and mutually agreed to between all interconnection entities In cases where backup metering is determined as a requirement, the backup meter can be added to the same set of CTs and VTs. Consult CMS for approval. 5.2 POLARITY STANDARD The metering diagram shown below in Figure 1 depicts the standard polarity position for CTs and metering interfaces as they relate to power providers and power consumers. If a need arises to reverse polarity due to provider and consumer reassignments, the meter(s) shall be able to do so by changing the parameters in the meter program. 1. When the current flows through the polarity side of the CTs, the meter shall register a positive (+) instantaneous value and a forward direction accumulator value. Accordingly, the meter shall register kwh delivered in the billing load profile. 2. Vice versa, when the current flows through the non polarity side of the CTs, the meter shall register a negative (-) instantaneous value and a reversed direction accumulator value. In such case, the meter shall register kwh received in the billing load profile. Figure 1 Page 4 of 8

5 5.2.2 It is important to note what constitutes power/energy flow in/out of SRP s Balancing Authority Area (BAA). Therefore the revenue meters and CTs shall be connected per following applications as depicted in Figure 2 shown below. 1. For SRP owned/operated Generation plant or Generation plant that is in SRP s BAAs. a. The revenue meter(s) and the CTs shall be connected such that the net generation at the plant would be measured as delivered and positive (+) power. The auxiliary power that is consumed by the plant would be measured as received and reverse(-) power. 2. For energy flow between BAAs, the connection manner below should apply. a. Energy flow into SRP BAAs from another BAA i. The revenue meter(s) and the CTs shall be connected such that the power/energy flow would be measured as received and reverse (-) power. ii. In such cases, the power/energy parameter in telemetry (i.e. in DNP) should show negative (-) and the kwh received would be registered in the billing load profile. b. Energy flow from SRP BAAs to another BAA i. The revenue meter(s) and the CTs shall be connected such that the power/energy flow would be measured as positive and forward (+) power. ii. In such case, the power/energy parameter in telemetry (ie. in DNP) should show positive (+) and the kwh delivered would be registered in the billing load profile. Figure 2 Page 5 of 8

6 5.3 INSTRUMENT TRANSFORMERS Instrument transformers shall be revenue grade with a rating of 0.3% accuracy or better at full load and 0.6% accuracy or better at light load. Burden specifications of instrument transformers shall meet or exceed the expected total burden ratings of connected revenue meters and other connected devices. Typical burden is B CTs shall have a primary current rating equal to the bus capacity where installed. Secondary current rating shall be 5 amperes at full primary current. 1. In applications where normal operating conditions will cause the primary current to be below the 10% light load rating, higher accuracy and extended range CTs will be required for accurate power measurement The secondary terminals of the CTs and VTs shall be connected only to revenue metering or other monitoring devices such as transducers. Exceptions for this requirement shall be mutually agreed upon between interconnecting entities. 5.4 METERING DATA TRANSFER & COLLECTION Revenue meter(s) installed at interconnection point(s) shall be accessible via phone line, Ethernet, or secured radio communications to retrieve hourly data for billing purposes. The number of telephone or ethernet circuits required will be determined and specified on a site by site basis Revenue meter(s) shall be able to provide measured power/energy parameters to the RTUs, other SCADA equipment, station computers, or other system control equipment through DNP and/or Modbus protocol. Typical data requirements are shown below: 1. Analog Points a. MW IN/OUT b. MVAR IN/OUT c. Net MW IN/OUT(for Generation Site) d. Net MVAR (Generation Site) e. Auxiliary MVAR (bi-directional) f. A Phase Amp g. PF h. Frequency Page 6 of 8

7 2. Accumulator Points or Digital pulse outputs a. Net MWh In/Out b. Net MVARh In/Out c. Auxiliary KWh (if applicable) Usage data registered by the interconnection revenue meter may be used for the following: 1. Automatic Generation Control/Power Dispatch Operation (AGC/PDO) 2. Transmission Generation Control (TGO) 3. Transmission related bill calculation Page 7 of 8

8 VERSION HISTORY Version Date Action Change Tracking Revised By 1 05/07/10 Created N/A Andrew Liu 2 11/10/11 Updated 3 08/06/12 Updated 4 03/08/13 Updated 5 08/08/13 Updated 6 9/11/13 Updated 7 11/11/13 Updated 8 8/12/14 Updated POLARITY STANDARD ADDED METERING DATA TRANSFER & COLLECTION TERMS AND DEFINITIONS POLARITY STANDARD METERING DATA TRANSFER & COLLECTION ADDED DESCRIPTION FOR STANDARD/REQUIREMENTS UPDATED STANDARD VERSION AND EFFECTIVE DATE UPDATED STANDARD VERSION AND EFFECTIVE DATE FOR FAC UPDATED FIGURE 1 IN SECTION AND UPDATED VERBAGE IN Andrew Liu James Statzer/ Rob Romak 8.1 8/10/15 Updated UPDATED VERBIAGE IN /6/2016 Updated UPDATED SECTION 1.2, UPDATED FIGURE 1 IN 5.2.1, AND ADDED FIGURE 2 IN /12/2016 Updated UPDATED DEFINITIONS Page 8 of 8

Standard BAL-005-0b Automatic Generation Control

Standard BAL-005-0b Automatic Generation Control A. Introduction 1. Title: Automatic Generation Control 2. Number: BAL-005-0b 3. Purpose: This standard establishes requirements for Balancing Authority Automatic Generation Control (AGC) necessary to calculate

More information

\NYISO REVENUE METERING REQUIREMENTS MANUAL

\NYISO REVENUE METERING REQUIREMENTS MANUAL \NYISO REVENUE METERING REQUIREMENTS MANUAL 1.0 Operating Procedures The operating practices presented herein include: Meter Certification for Participants of the NYISO NYISO Guidelines for The Installation,

More information

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2 PART 1 PART 2 PRODUCTS 2.01 MANUFACTURERS A. Eaton products B.. C.. The listing of specific manufacturers above does not imply acceptance of their products that do not meet the specified ratings, features

More information

Brianna Swenson Alliant Energy Minnesota Power Systems Conference November 8, 2017

Brianna Swenson Alliant Energy Minnesota Power Systems Conference November 8, 2017 Brianna Swenson Alliant Energy Minnesota Power Systems Conference November 8, 2017 Topics Brief history of interties and regulations Who is involved? What exactly are we doing? Why is it important? Project

More information

Standard BAL b3 Automatic GenerationBalancing Authority Control DRAFT

Standard BAL b3 Automatic GenerationBalancing Authority Control DRAFT A. Introduction 1. Title: Balancing Authority ControlAutomatic Generation Control 2. Number: BAL-005-30.2b 3. Purpose: This standard establishes requirements for acquiring necessary data for the Balancing

More information

Standard BAL b Automatic Generation Control

Standard BAL b Automatic Generation Control A. Introduction 1. Title: Automatic Generation Control 2. Number: BAL-005-0.2b 3. Purpose: This standard establishes requirements for Balancing Authority Automatic Generation Control (AGC) necessary to

More information

Standard BAL b Automatic Generation Control

Standard BAL b Automatic Generation Control A. Introduction 1. Title: Automatic Generation Control 2. Number: BAL-005-0.2b 3. Purpose: This standard establishes requirements for Balancing Authority Automatic Generation Control (AGC) necessary to

More information

Calculating and Using Reporting ACE in a Tie Line Bias Control Program

Calculating and Using Reporting ACE in a Tie Line Bias Control Program Calculating and Using Reporting ACE in a Tie Line Bias Control Program Introduction: Tie Line Bias 1 (TLB) control has been used as the preferred control method in North America for 75 years. In the early

More information

Project Balancing Authority Reliability-based Controls Reliability Standard BAL-005-1

Project Balancing Authority Reliability-based Controls Reliability Standard BAL-005-1 Implementation Plan Project 2010-14.2.1 Balancing Authority Reliability-based Controls Reliability Standard BAL-005-1 Requested Approval s Requested Retirement BAL-005-0.2b Automatic Generation Control

More information

Table 1 - Assignment of BA Obligations... 8

Table 1 - Assignment of BA Obligations... 8 Dynamic Transfer Reference Guidelines Version 2 June 2010 Table of Contents Table of Contents Chapter 1 Overview... 3 Purpose... 3 Terms... 3 Chapter 2 Dynamic Schedule Versus Pseudo-tie Fundamentals...

More information

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR SMALL GENERATION INTERCONNECTIONS

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR SMALL GENERATION INTERCONNECTIONS TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR SMALL GENERATION INTERCONNECTIONS Puget Sound Energy, Inc. PSE-ET-160.60 October 30, 2007 TABLE OF CONTENTS 1. INTRODUCTION...1 1.1 GENERAL

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Description of Current Draft

More information

Integra 1560 and 1580 Digital Transducer Systems

Integra 1560 and 1580 Digital Transducer Systems Integra 1560 and 1580 multi function transducers provide high accuracy

More information

Reliability Guideline Integrating Reporting ACE with the NERC Reliability Standards

Reliability Guideline Integrating Reporting ACE with the NERC Reliability Standards Reliability Guideline Integrating Reporting ACE with the NERC Reliability Standards Applicability: Balancing Authorities (BAs) Introduction and Purpose: It is in the public interest for NERC to develop

More information

Data Sheet. RISH Master Record %THD

Data Sheet. RISH Master Record %THD Data Sheet %THD Application : measures important electrical parameters & replaces the multiple analog panel meters. It measures electrical parameters like AC current, Voltage, frequency, active energy

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements Section 502.8 SCADA Technical and Operating Requirements Applicability 1 Subject to subsections 2 and 3 below, section 502.8 applies to: (a) (c) (d) the legal owner of a generating unit or an aggregated

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements Section 502.8 SCADA Technical and Operating Applicability 1 Section 502.8 applies to: (a) the legal owner of a generating unit: (i) connected to the transmission facilities in the balancing authority area

More information

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF LARGE GENERATION FACILITIES. Document 9020

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF LARGE GENERATION FACILITIES. Document 9020 TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF LARGE GENERATION FACILITIES Document 9020 Puget Sound Energy, Inc. PSE-TC-160.50 December 19, 2016 TABLE OF CONTENTS

More information

GREAT RIVER ENERGY GREAT RIVER ENERGY GENERATION INTERCONNECTION GUIDELINES. Revision 4

GREAT RIVER ENERGY GREAT RIVER ENERGY GENERATION INTERCONNECTION GUIDELINES. Revision 4 GREAT RIVER ENERGY GREAT RIVER ENERGY GENERATION INTERCONNECTION GUIDELINES Revision 4 December, 2010 TABLE OF CONTENTS General Requirements... 1 A, Purpose... 1 B, MISO Interconnection Requirements...2

More information

Document C-29. Procedures for System Modeling: Data Requirements & Facility Ratings. January 5 th, 2016 TFSS Revisions Clean Open Process Posting

Document C-29. Procedures for System Modeling: Data Requirements & Facility Ratings. January 5 th, 2016 TFSS Revisions Clean Open Process Posting Document C-29 Procedures for System Modeling: January 5 th, 2016 TFSS Revisions Clean Open Process Posting Prepared by the SS-37 Working Group on Base Case Development for the Task Force on System Studies.

More information

Company Directive STANDARD TECHNIQUE: TP6F/1. Power Measurement Conventions

Company Directive STANDARD TECHNIQUE: TP6F/1. Power Measurement Conventions Company Directive STANDARD TECHNIQUE: TP6F/1 Power Measurement Conventions Summary This document specifies the conventions that are used for the direction of Power Flow within Western Power Distribution

More information

Embedded Generation Information Package

Embedded Generation Information Package Embedded Generation Information Package Remote Monitoring (RM) Remote Shutdown (RS) Prepared by: Station Design and Standards Embedded Generation Revision: 1.6 December 2015 Page 1 of 10 1. Background:

More information

Southern Company Interconnection Requirements for Inverter-Based Generation

Southern Company Interconnection Requirements for Inverter-Based Generation Southern Company Interconnection Requirements for Inverter-Based Generation September 19, 2016 Page 1 of 16 All inverter-based generation connected to Southern Companies transmission system (Point of Interconnection

More information

Voltage and Reactive Procedures CMP-VAR-01

Voltage and Reactive Procedures CMP-VAR-01 Voltage and Reactive Procedures CMP-VAR-01 NERC Standards: VAR-001-2 VAR-002-1.1b Effective Date: 07/31/2012 Document Information Current Revision 2.0 Review Cycle Annual Subject to External Audit? Yes

More information

GUIDELINES FOR UTILIZATION OF FREQUENCY AND TIME ERROR DEVICES AND CALIBRATING TIE LINE SIGNAL

GUIDELINES FOR UTILIZATION OF FREQUENCY AND TIME ERROR DEVICES AND CALIBRATING TIE LINE SIGNAL Document name Category Document date March 11, 2003 Adopted/approved by GUIDELINES FOR UTILIZATION OF FREQUENCY AND TIME ERROR DEVICES AND CALIBRATING TIE LINE SIGNAL ( ) Regional Reliability Standard

More information

Area Control Error (ACE) Equation Special Cases

Area Control Error (ACE) Equation Special Cases Area Control Error (ACE) Equation Special Cases Purpose: It is the obligation of each Balancing Authority to manage its Area Control Error in accordance with NERC reliability standards. This Standard provides

More information

Functional Specification Revision History

Functional Specification Revision History Functional Specification Revision History Revision Description of Revision By Date V1D1 For Comments Yaoyu Huang October 27, 2016 V1 For Issuance Yaoyu Huang November 21, 2016 Section 5.3 updated Transformer

More information

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS CONNECTED TO THE DISTRIBUTION SYSTEM ORANGE AND ROCKLAND

More information

Implementation Plan Project Balancing Authority Reliability-based Controls - Reserves

Implementation Plan Project Balancing Authority Reliability-based Controls - Reserves Implementation Plan Project 2010-14.1 Balancing Authority Reliability-based Controls - Reserves Implementation Plan for Approvals Required Prerequisite Approvals None Revisions to Glossary Terms The following

More information

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features: (With All Display Parameters) Application : RISH EM 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network

More information

Overview of Metering Assurance in the Capacity Market

Overview of Metering Assurance in the Capacity Market Public Overview of Metering Assurance in the Capacity Market 21 February 2017 Iain Nicoll EMRS Tushar Singh EMR Delivery Body Joy Nnamani EMRS Matthew Johnson ESC What we will cover today? Topic Roles

More information

Contents. Introduction and description Package contents Device identification PM Options... 80

Contents. Introduction and description Package contents Device identification PM Options... 80 Contents 1 Introduction and description Package contents... 77 Device identification... 77 2 Characteristics PM500... 78 Options... 80 3 Installation Front-panel cut-out... 82 Mounting... 82 4 Connections

More information

EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1. Three phase multifunction din rail energy meter

EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1. Three phase multifunction din rail energy meter SDM630MCT-RJV-333mV SDM630MCT-RJA-00mA Three phase multifunction din rail energy meter Plug-in solution; labor saving; wiring mistake free Measures kwh KVarh, KW, Kvar, KVA, P, F, PF, Hz, dmd, V, A, THD,etc.

More information

HOOSIER ENERGY REC, INC. Requirements for Connection of Generation Facilities. to the HE Transmission System

HOOSIER ENERGY REC, INC. Requirements for Connection of Generation Facilities. to the HE Transmission System HOOSIER ENERGY REC, INC Requirements for Connection of Generation Facilities to the HE Transmission System January 2009 Table of Contents 1.0 INTRODUCTION...1 2.0 TYPES OF CONNECTED CIRCUIT CONFIGURATIONS...6

More information

ENGLISH 3 Phase Multi-function Power Meter 1/5A MID MID

ENGLISH 3 Phase Multi-function Power Meter 1/5A MID MID Professionally approved products. Datasheet Stock Number: 144-0527 3 Phase Multi-function Power Meter 1/5A MID 96mm² Panel Mounted Power Meter. MID UK Specifications The 144-0527 is a new generation modern

More information

ReliabilityFirst Regional Criteria 1. Disturbance Monitoring and Reporting Criteria

ReliabilityFirst Regional Criteria 1. Disturbance Monitoring and Reporting Criteria ReliabilityFirst Regional Criteria 1 Disturbance Monitoring and Reporting Criteria 1 A ReliabilityFirst Board of Directors approved good utility practice document which are not reliability standards. ReliabilityFirst

More information

ATTACHMENT - AESO FUNCTIONAL SPECIFICATION

ATTACHMENT - AESO FUNCTIONAL SPECIFICATION ATTACHMENT - AESO FUNCTIONAL SPECIFICATION Functional Specification Revision History Revision Description of Revision By Date D1 For internal Comments Yaoyu Huang January 8, 2018 D2 For external Comments

More information

Wind Power Facility Technical Requirements CHANGE HISTORY

Wind Power Facility Technical Requirements CHANGE HISTORY CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical

More information

GENERATOR INTERCONNECTION APPLICATION Category 3 For All Projects with Aggregate Generator Output of More Than 150 kw but Less Than or Equal to 550 kw

GENERATOR INTERCONNECTION APPLICATION Category 3 For All Projects with Aggregate Generator Output of More Than 150 kw but Less Than or Equal to 550 kw GENERATOR INTERCONNECTION APPLICATION Category 3 For All Projects with Aggregate Generator Output of More Than 150 kw but Less Than or Equal to 550 kw ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy

More information

Digital Multifunction Instrument - Rish Master 3440

Digital Multifunction Instrument - Rish Master 3440 Application Rish Master 3440 measures important electrical parameters in 3 phase and single phase etwork & replaces the multiple analog panel meters. It measures electrical parameters like AC current,

More information

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS AND MEDIUM-SIZE FACILITIES (5,000-25,000KW) CONNECTED

More information

Lecture 15 EMS Application II Automatic Generation Contol. Davood Babazadeh

Lecture 15 EMS Application II Automatic Generation Contol. Davood Babazadeh Lecture 15 EMS Application II Automatic Generation Contol Davood Babazadeh 2015-12-03 Outline Generation Control - Why - How AGC design - Area Control Error - Parameter Calculation 2 Course road map 3

More information

MultiCube Multi-Function Electricity Meter. Installation and Operation

MultiCube Multi-Function Electricity Meter. Installation and Operation MultiCube Multi-Function Electricity Meter Installation and Operation PREFACE MultiCube Operating Guide Revision 1.08 Jan 2007 This manual represents your meter as manufactured at the time of publication.

More information

Multimeter 500CVD21 RTU500 series

Multimeter 500CVD21 RTU500 series Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase

More information

HSIANG CHENG ELECTRIC CORP.

HSIANG CHENG ELECTRIC CORP. DWG NO. : 26298001 VER : 3.0 METER Introduction About ower Meter The is conceptualized and designed to revolutionize the approach to traditional power metering. Each is a compact, electronically advanced

More information

FACILITY RATINGS METHOD TABLE OF CONTENTS

FACILITY RATINGS METHOD TABLE OF CONTENTS FACILITY RATINGS METHOD TABLE OF CONTENTS 1.0 PURPOSE... 2 2.0 SCOPE... 3 3.0 COMPLIANCE... 4 4.0 DEFINITIONS... 5 5.0 RESPONSIBILITIES... 7 6.0 PROCEDURE... 8 6.4 Generating Equipment Ratings... 9 6.5

More information

BED INTERCONNECTION TECHNICAL REQUIREMENTS

BED INTERCONNECTION TECHNICAL REQUIREMENTS BED INTERCONNECTION TECHNICAL REQUIREMENTS By Enis Šehović, P.E. 2/11/2016 Revised 5/19/2016 A. TABLE OF CONTENTS B. Interconnection Processes... 2 1. Vermont Public Service Board (PSB) Rule 5.500... 2

More information

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication:

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication: Application : RISH Master 3490 SS is a 96mm x 96mm panel mounted kilowatt hour meter it measures active energy with class 1.0 accuracy having auto-resetting 8 digit seven segment LED counter. The unit

More information

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES)

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES) Alpha Series www.sifamtinsley.co.uk Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers Analogue Panel Meters Shunts ALPHA

More information

GIMA Multi-Function Electricity Meter OPERATOR S MANUAL

GIMA Multi-Function Electricity Meter OPERATOR S MANUAL GIMA Multi-Function Electricity Meter OPERATOR S MANUAL SIMPSON ELECTRIC COMPANY 520 Simpson Avenue Lac du Flambeau, WI 54538 715-588-3311 FAX: 715-588-7930 Printed in U.S.A. Part No. 06-117285, Edition

More information

Energy Division

Energy Division Energy Division http://energy.tycoelectronics.com Installation and Operating Manual Integra 1560 and 1580 Digital Metering and Transducer Systems Tyco Electronics UK Limited Crompton Instruments Freebournes

More information

IMPLEMENTATION OF ADVANCED DISTRIBUTION AUTOMATION IN U.S.A. UTILITIES

IMPLEMENTATION OF ADVANCED DISTRIBUTION AUTOMATION IN U.S.A. UTILITIES IMPLEMENTATION OF ADVANCED DISTRIBUTION AUTOMATION IN U.S.A. UTILITIES (Summary) N S Markushevich and A P Berman, C J Jensen, J C Clemmer Utility Consulting International, JEA, OG&E Electric Services,

More information

Table of Contents. Introduction... 1

Table of Contents. Introduction... 1 Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...

More information

G20 Capacity Market Metering Statement

G20 Capacity Market Metering Statement G20 Capacity Market Metering Statement EMRS Guidance Public Version: 4.0 Date: 20 July 2018 Table of Contents Change Amendment Record 3 1. Introduction 4 2. Purpose 4 3. Metering Statement Guidance 4 4.

More information

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED SECTION 16280 LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED PART 1 - GENERAL 1.1 SUMMARY This specification defines the requirements for active harmonic filter systems in order to meet IEEE-519-2014

More information

Oklahoma Gas and Electric Co. Facility Connection Requirements MAINTAINED BY. Transmission Planning Engineering Department

Oklahoma Gas and Electric Co. Facility Connection Requirements MAINTAINED BY. Transmission Planning Engineering Department Oklahoma Gas and Electric Co. Facility Connection Requirements MAINTAINED BY Transmission Planning Engineering Department Table of Contents Transmission and Generation Facility Interconnections... 3 Attachment

More information

OPERATING PROCEDURE. Table of Contents

OPERATING PROCEDURE. Table of Contents Table of Contents PURPOSE... 1 1.0 CAISO DISPATCHER RESPONSIBILITIES... 2 Monitor Loads and Generators... 2 Monitor Balancing Areas... 2 Operate CAISO Controlled Grid Voltage Equipment... 3 Voltage Schedules...

More information

Technical Data Sheet

Technical Data Sheet Technical Data Sheet parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters. Special Features Pulse/Limit Switch output (optional) Number of interruption Application

More information

RISH Master Digital Multifunction Instrument with onsite pluggable output options. Application : Product Features:

RISH Master Digital Multifunction Instrument with onsite pluggable output options. Application : Product Features: Application : RISH Master 3430 measures important electrical parameters in 3 phase and single phase Network & replaces the multiple analog panel meters. It measures electrical parameters like AC current,

More information

Transmission Interconnection Requirements for Inverter-Based Generation

Transmission Interconnection Requirements for Inverter-Based Generation Transmission Requirements for Inverter-Based Generation June 25, 2018 Page 1 Overview: Every generator interconnecting to the transmission system must adhere to all applicable Federal and State jurisdictional

More information

Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES PURPOSE The following is PG&E's procedure for pre-energization inspections. For PG&E to provide the Load

More information

Operating Guide October 2006

Operating Guide October 2006 Operating Guide October 2006 Safety 1 Safety This manual represents your meter as manufactured at the time of publication. It assumes standard software. Special versions of software may be fitted, in which

More information

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION Document 9022 Puget Sound Energy, Inc. PSE-TC-160.70 December

More information

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49 TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument True RMS measurement User-friendly programing Four different types for optimal specification RS485 interface For 3- or 4-wire connection Compact

More information

Power Meter Series PM3200 Functions and characteristics

Power Meter Series PM3200 Functions and characteristics Functions and characteristics PB108433 This PowerLogic Power meter offers basic to advanced measurement capabilities. With compact size and DIN rail mounting, the PM3200 allows mains and feeders monitoring

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Balancing and Settlement Code. Code of Practice Two

Balancing and Settlement Code. Code of Practice Two Balancing and Settlement Code Code of Practice Two CODE OF PRACTICE FOR THE METERING OF CIRCUITS WITH A RATED CAPACITY NOT EXCEEDING 100 MVA FOR SETTLEMENT PURPOSES. Issue 4 Version 9.0 DATE: 24 June 2010

More information

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone

More information

Smart Grid Panel Presentation

Smart Grid Panel Presentation Smart Grid Panel Presentation Robert J. Thomas Cornell University PSerc Summer Workshop Lake Tahoe, CA August 4, 2008 Smart Grid Values (Why are we doing this?) Some reasons A more reliable grid - power

More information

Centrale de mesure Power Meter PM500 Merlin Gerin

Centrale de mesure Power Meter PM500 Merlin Gerin Notice d'installation et d'utilisation Installation and user manual Centrale de mesure Power Meter PM500 Merlin Gerin 059473_D Introduction and description Package contents c one PM500 power meter with

More information

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants Martin Best and Stephanie Mercer, UC Synergetic, LLC Abstract Wind generating plants employ several

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June

More information

POWER QUALITY AND REVENUE METER EM920. Operation Manual. BG0482 Rev. A4

POWER QUALITY AND REVENUE METER EM920. Operation Manual. BG0482 Rev. A4 POWER QUALITY AND REVENUE METER EM920 Operation Manual BG0482 Rev. A4 LIMITED WARRANTY The manufacturer offers the customer a 24-month functional warranty on the instrument for faulty workmanship or parts

More information

Energy Division

Energy Division Energy Division http://energy.tycoelectronics.com Installation and Operating Manual Integra 1560 and 1580 Digital Metering and Transducer Systems Tyco Electronics UK Limited Crompton Instruments Freebournes

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

Balancing and Settlement Code. Code of Practice One

Balancing and Settlement Code. Code of Practice One Balancing and Settlement Code Code of Practice One CODE OF PRACTICE FOR THE METERING OF CIRCUITS WITH A RATED CAPACITY EXCEEDING 100MVA FOR SETTLEMENT PURPOSES Issue 2 Version 12.0 DATE: 2 November 2017

More information

DUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES. Transmission Planning

DUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES. Transmission Planning DUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES Transmission Planning TABLE OF CONTENTS I. SCOPE 1 II. TRANSMISSION PLANNING OBJECTIVES 2 III. PLANNING ASSUMPTIONS 3 A. Load Levels 3 B. Generation

More information

IEEE Major Revision of Interconnection Standard

IEEE Major Revision of Interconnection Standard IEEE 1547-2018 - Major Revision of Interconnection Standard NRECA & APA s Emerging Priorities in Energy Research Day, Anchorage, AK Charlie Vartanian PE Secretary, IEEE 1547 Working Group October 31, 2018

More information

Acuvim-X Series Multifunction Power Meter

Acuvim-X Series Multifunction Power Meter Series Multifunction Power Meter Power System Metering W a v e f o r m C a p t u r e O v e r L i m i t A l a r m emote Switch Control Power Quality Detection E n e r g y TO U C o u n t T r e n d e c o

More information

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number:  Address: NORTH CAROLINA INTERCONNECTION REQUEST Utility: Designated Contact Person: Address: Telephone Number: Fax: E-Mail Address: An is considered complete when it provides all applicable and correct information

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission

More information

Standard VAR Voltage and Reactive Control

Standard VAR Voltage and Reactive Control A. Introduction 1. Title: Voltage and Reactive Control 2. Number: VAR-001-3 3. Purpose: To ensure that voltage levels, reactive flows, and reactive resources are monitored, controlled, and maintained within

More information

New Redundant Automatic Voltage Regulator (AVR) Solution

New Redundant Automatic Voltage Regulator (AVR) Solution White Paper New Redundant Automatic Voltage Regulator (AVR) Solution Author: David R. Brown, Turbomachinery Control Solutions Senior Consultant, Invensys Operations Management What s Inside: 1. Introduction

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the Board of Trustees. Description

More information

Energy Meters for DIN Rail Mounting Electric energy meter WS0101, WS0102,WS1102 WS0301, WS0302,WS1302

Energy Meters for DIN Rail Mounting Electric energy meter WS0101, WS0102,WS1102 WS0301, WS0302,WS1302 Energy Meters for DIN Rail Mounting Electric energy meter WS0101, WS0102,WS1102 WS0301, WS0302,WS1302 Direct connection up to 65 A (WSx10x) Connection with current transformer (WSx30x) Industrial or meters

More information

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy Interconnection Coordinator 1945

More information

South African Distribution Code

South African Distribution Code South African Distribution Code Metering Code Version 6.0 July 2014 This document is approved by the National Energy Regulator of South Africa (NERSA) Issued by: RSA Grid Code Secretariat Contact: Mr.

More information

1 In This Document Elspec

1 In This Document Elspec 1. Change to read: 10/12 Continuous Non-Overlapping Cycles. a. changed in doc - if I redo the pdf it will delete all my comments. see 2nd doc attached. mpm 1 In This Document Elspec IN THIS DOCUMENT I.

More information

CAISO Restricted - Do Not Distribute Outside of RC Project LOI and NDA Entities Page 1 of 24

CAISO Restricted - Do Not Distribute Outside of RC Project LOI and NDA Entities Page 1 of 24 RC0120A - RC IRO-010 Data Specification NOTE: Changes from Peak's Attachment A are highlighted in red in columns C through G Section Category Number Responsible Pa Data Item Data Transfer Method 1.1 Transmission

More information

RISH Master 3430 DIGITAL MULTI-FUNCTION TRANSDUCER. Electro-Meters

RISH Master 3430 DIGITAL MULTI-FUNCTION TRANSDUCER. Electro-Meters measures important electrical parameters in phase and single phase etwork & replaces the multiple analog panel meters. It measures electrical parameters like AC current, Voltage, frequency, Power, Energy

More information

(Circuits Subject to Requirements R1 R5) Generator Owner with load-responsive phase protection systems as described in

(Circuits Subject to Requirements R1 R5) Generator Owner with load-responsive phase protection systems as described in A. Introduction 1. Title: Transmission Relay Loadability 2. Number: PRC-023-3 3. Purpose: Protective relay settings shall not limit transmission loadability; not interfere with system operators ability

More information

Balancing and Settlement Code. Code of Practice One

Balancing and Settlement Code. Code of Practice One Balancing and Settlement Code Code of Practice One CODE OF PRACTICE FOR THE METERING OF CIRCUITS WITH A RATED CAPACITY EXCEEDING 100MVA FOR SETTLEMENT PURPOSES Issue 2 Version 8.0 DATE: 24 June 2010 Balancing

More information

Issue Date: Effective Date: Supersedes: S-E-06 (rev. 6)

Issue Date: Effective Date: Supersedes: S-E-06 (rev. 6) Specifications Category: ELECTRICITY Specification: S-E-06 (rev. 7) Page: 1 of 22 Issue Date: 2017-02-01 Effective Date: 2017-02-01 Specification for the approval of type of electricity meters and auxiliary

More information

Meters. Ampere Meter. Volt Meter. Watt Meter. Var. Meter. Power Factor Meter. Frequency Meter. Demand Meter. Meter Relay.

Meters. Ampere Meter. Volt Meter. Watt Meter. Var. Meter. Power Factor Meter. Frequency Meter. Demand Meter. Meter Relay. Meters Ampere Meter Volt Meter Watt Meter Var. Meter Power Factor Meter Frequency Meter Outside Connection (Watt, PF, Var) 3 2 7 Receive Indicator Meter Demand Meter Meter Relay Meter Dimensions Meter

More information

MT 560/UMT TRANSDUCER & ANALYZER

MT 560/UMT TRANSDUCER & ANALYZER MT 560/UMT 560 - TRANSDUCER & ANALYZER USE The MT 560/UMT 560 multi transducer and analyzer is used for a permanent analysis of electricity supply quality in compliance with the SIST EN 50160 standard.

More information

Introduction to Solid State Meter Testing. Terms and Definitions

Introduction to Solid State Meter Testing. Terms and Definitions NWEMS Introduction to Solid State Meter Testing 2017 Northwest Electric Meter School Presented by: Marcus Zickefoose Radian Research Inc. Terms and Definitions Term Definition Accuracy Calibration Class

More information

Measuring centers MC3x0 series Energy Meters with Power Display Energy Meter WQ0217 & WQ1217 Energy Meter with analogue pointer WQ0207 & WQ2207

Measuring centers MC3x0 series Energy Meters with Power Display Energy Meter WQ0217 & WQ1217 Energy Meter with analogue pointer WQ0207 & WQ2207 Measuring centers MC3x0 series Energy Meters with Power Display Energy Meter WQ0217 & WQ1217 Energy Meter with analogue pointer WQ0207 & WQ2207 o 7 digits electromechanical register o Up to 2 registers

More information

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection NERC Protection Coordination Webinar Series

More information

Network Monitoring and Visibility Summary

Network Monitoring and Visibility Summary Network Monitoring and Visibility Summary This article reviews the shortfalls in legacy monitoring and what will be needed to manage the changing nature of the distribution network. This includes a particular

More information