METHOD TO DETERMINE CONTRIBUTION OF THE CUSTOMER AND THE POWER SYSTEM TO THE HARMONIC DISTURBANCE

Size: px
Start display at page:

Download "METHOD TO DETERMINE CONTRIBUTION OF THE CUSTOMER AND THE POWER SYSTEM TO THE HARMONIC DISTURBANCE"

Transcription

1 C I R E D 17 th International Conference on Electricity Distribution Barcelona, 1-15 May 3 METHOD TO DETERMINE CONTRIBUTION OF THE CUSTOMER AND THE POWER SYSTEM TO THE HARMONIC DISTURBANCE Olivier GONBEAU Luc BERTHET Jean-Louis JAVERZAC Denis BOUDOU Electricité de France France Réseau de Transport Electrique - France Electricité de France - France olivier.gonbeau@edf.fr luc.berthet@edf.fr jean-louis.javerzac@rte-france.fr denis.boudou@edf.fr 1- INTRODUCTION Harmonic levels are becoming an essential element among Power Quality parameters. Indeed, the number of non-linear loads does not stop increasing as well the injection of harmonic currents into the distribution and transmission system. Harmonic voltage levels should be maintained below the compatibility levels so that all the equipment supplied with the public networks can operate under satisfactory conditions. In addition to limits by equipment, there is already a tendency towards the definition of limits by installations. It becomes necessary to be concerned with control methods associated with these limits expressed in term with harmonic current. However, the measured harmonic current at the customer point of common coupling is the vectorial sum of a current emitted by this installation towards the network and a current coming from the network. Within a contractual framework, only the current emitted by a customer s installation towards the network should be taken into consideration. Thus, it is necessary to make use of a measurement method making it possible to extract this current from the current measured at the point of common coupling. To date, there s no method recognized at the international level with this intention. Theoretical work was undertaken on this subject since the beginning of the 9 s [1]. Now, it remains to validate a method (even several) by defining their algorithms, their application field and their limits and then to obtain an international consensus. To be able to determine the exact customer contribution in all cases, EDF studied new estimation methods. In addition, new algorithms for application of these measurement methods, as well as existing methods, were developed. This article s aim is to present these estimation methods and the first results. In this article we present successively: the regulatory context, harmonics, the estimation methods, algorithms for application of all these methods, first results obtained in the network, prospects. - REGULATORY CONTEXT International standards and national decrees are available proposing guidelines to fix harmonic current emission limits in order to respect harmonic compatibility levels. The technical report IEC [] gives general steps to elaborate connection rules for non-linear loads. Thus, the electrical public networks could run under satisfactory conditions for its users. Historically in France, the Émeraude contract was launched in 1995 after a negotiation between the public utility and the representatives of large companies. This contract, approved by the public authorities, was extended to all HV and MV customers whose subscribed power exceeds 5 kva. As far as harmonics are concerned, this contract only gives informative connection rules for the customers. Moreover, the Émeraude contract forecasted that the informative connection rules would become obligatory from More recently, the February law (opening the French electric market) allows connection and access to the electrical power supply networks of the various users (specifically generators). Moreover, this law provides that technical methods of connection must be specified by decrees (already done for generators). Mandatory connection rules will therefore see the light of day in a few months. These rules will describe commitments of the both parties in terms of power quality and particularly harmonics. In conclusion, the evolution of the French national regulatory context will require measurement methods to check the network operator s and users reciprocal commitments. 3- HARMONICS 3.1- Harmonic flow into power supply network Harmonics are a by-product of modern electronics. When this equipment is connected to a 5 Hz sinusoidal voltage, these loads don t absorb a 5 Hz sinusoidal current. Non-linear load connection to the network results in the apparition of a harmonic voltage at the network impedance. Generally, load impedances are definitely larger than the line ones. Harmonic currents tend to circulate towards upstream network. In the industrial installations, capacitor banks are connected in parallel to compensate the reactive power of inductive loads. These capacitor banks can form resonant circuits with line inductances, which can amplify the disturbances and modify the natural harmonic flow of the current. EDF_Gonbeau_A1 Session Paper No 3-1 -

2 C I R E D 17 th International Conference on Electricity Distribution Barcelona, 1-15 May Problematic with the measurement of the currents emitted by installations To check if an installation s harmonic emissions are in conformity with the regulations or standards, it is necessary to differentiate with precision harmonic current emitted downstream from the current measured. Downstream part : C Installation or customer side Ih=Ihs+Ihc Ihs Vh Ihc Upstream part : S Source side Figure 1: Power supply system model at the PCC the "downstream" part stands for the installation. With: Js : Harmonic current from the source side : Harmonic equivalent impedance on source side Jc : Harmonic current from the installation Zc : Harmonic equivalent impedance on the installation side Harmonic measurement are performed following the IEC recommendations [3]. The harmonic voltage and current measurement are the defined by: ( Js Ih(i) ) ( Jc Ih(i) ) Vh(i) =. (1) Vh(i) = Zc. + () According to this model, three methods will be presented. The first one (described in [1]) uses the sign of R eal( Vh Ih). The two others (non-linear regression and iterative methods) were imagined by EDF recently. Unfortunately, the current measured (Ih) at the point of common coupling is the sum of the current emitted by the customer (Ihc) towards the network and the network towards the customer (Ihs). In general, the current emitted by the customer is very dominating but not always; in certain cases, the current from upstream can be notable because of a resonance. 4- ESTIMATION METHODS 4.1- Harmonic single-phase equivalent circuit at the point of common coupling From the network represented by Figure 1, a measurement at the point of common coupling gives: Vh : Complex harmonic voltage, Ih : Complex harmonic current. At this point of measurement, the model of Figure can characterize the network: Ih 4.- Method using the sign of R eal( Vh Ih) The sign of eal( Vh Ih) R determines the side where a parameter variation didn t occur and by this way establishes the impedance value that did not vary [1]. Determination Domain 18 Vh Real sign Ih Determination Domain Zc Figure 3: Impedance determination domains As shown in Figure 3, the ratio Vh Ih provides: The impedance if Vh The impedance Zc if eal( Vh Ih) 4.3- Non linear regression method R < R > Js Vh Zc Jc The problem resolution is to obtain, Zc, Js, Jc through the minimization of the errors defined by these equations: Source Installation Figure : Single-phase equivalent circuit for harmonic analysis. The source stands for the "upstream" part of the measurement point, which often represents on the same voltage level the parallel of the network with other harmonic injections, and e 1 (i) = Vh(i) Js + Ih(i) (3) (i) e We can minimize for example: = Vh(i) ZcJc ZcIh(i) (4) EDF_Gonbeau_A1 Session Paper No 3 - -

3 C I R E D 17 th International Conference on Electricity Distribution Barcelona, 1-15 May 3 1 = (5) i ( ) ( Vh(i) Js + Ih(i) ) e (i) + e (i) i + ( Vh(i) ZcJc ZcIh(i) ) 4.4- Iterative method Equation (1) provides Vh. ( Js Ih) =. This corresponds to an equation with two unknown factors. The principle of the iteration method is to apply the harmonic current and voltage measurements in equation (1) with one unknown factor fixed to a value to calculate the other. Thus, the estimation method allows harmonic impedance network estimation ( ) at one iteration and the harmonic current from source side estimation ( Js ) at the next iteration using the impedance previously computed. 5- ALGORITHMS 5.1- Application fields Harmonic currents and voltages measurements must rely on standard recommendations IEC [3]. The three methods described previously correspond to different application fields but are theoretically complementary. The goal is to obtain for each one an algorithm that controls the results accuracy. Thus, the method using the sign of eal( Vh Ih) R gives good results in case of a significant variation of the harmonic currents and voltages. The results are provided just after the variation. Thus, three consecutive measurement windows are sufficient to obtain an estimate. Concerning the non-linear regression method, the error minimization passes through least squares resolution. This requires a great number of measurements samples without a significant parameters variation. The iterative method follows the evolutions of the estimated parameters with time with or without harmonic variations. 5.- Method using the sign of R eal( Vh Ih) If the system undergoes an abrupt variation from a permanent harmonic state to a new permanent harmonic state without source (or installation) parameters variation, we can define two recording windows ( a and c ) and a data processing corresponding to the permanent harmonic states. The window b corresponds to the transient between the two permanent states. From (1) and () we have: - Stage a permanent harmonic state before the variation Vh(a). Js Ih(a) Vh(a) = Zc. Jc + Ih(a) = ( ) and ( ) - Stage c permanent harmonic state after the variation Vh(c). Js Ih(c) Vh(c) = Zc. Jc + Ih(c) = ( ) and ( ) In the hypothesis of a variation on the downstream side Vh Vh(a) Vh(c) = = (since Js and do not vary). Ih Ih(a) Ih(c) In the hypothesis of a variation on the upstream side Vh Vh(a) Vh(c) = = Zc (since Jc and Zc do not vary). Ih Ih(a) Ih(c) Once the impedance is known, the harmonic current is determined by (1) and () Non linear regression method This method principle is to be applied during steady state operations. The error minimization passes through a least squares resolution. Equation (5) cannot be solved because of Js and Zc Jc terms that would lead to a nonlinear regression problem. The system can be transformed into a linear regression problem by defining two variables Vs and Vc with Vs = Js and Vc = ZcJc. From the minimization, the matrix resolution cannot be carried out without a minimum number of samples. The algorithm requires several minutes of consecutive samples before solving the system. Once the real and imaginary parts are calculated, the parameters, Zc, Js, Jc are reconstituted Iterative method If we consider there is a small variation at the measurement point on the network side, we can use the iterative method. There are two different stages (N-1 and N) with for each one a parameter calculation using the other parameter previously computed. At the stage N-1, the current Js estimation is carried out using the measurement ( Vh(N 1), Ih(N 1) ). With the impedance previously calculated N 1 = N, the current estimation is: Vh(N 1) Js N 1 = + Ih(N 1) (6) N At the stage N, the impedance estimation is carried out using the measurement ( Vh (N), Ih(N) ). With the current previously calculated Js N = Js N 1, the impedance estimation is: N = Js Vh(N) N 1 Ih(N) (7) EDF_Gonbeau_A1 Session Paper No 3-3 -

4 C I R E D 17 th International Conference on Electricity Distribution Barcelona, 1-15 May 3 In order to make the system converging, the initial value can be set by = Vh Ih which can be deducted by the method using the sign of eal( Vh Ih) 6- FIRST RESULTS R Voltage measurement (V) Current measurement (A) 6.1- Networks studied In order to apply the different estimation methods, measurement campaigns have been carried out on installations connected to the transmission and distribution networks. Measurements on the transmission system took place in a 15/4 kv substation where significant harmonic levels were regarded (THD 15 %). This situation was due to the presence of capacitor banks in the customer installation that moved the resonance frequency to 5 Hz. Several tests were realized to get information about the application fields of the various methods (capacitor cut-in/cut-off operations, load variations, steady state operation...). Measurement campaigns on the distribution network were representative of industrial customers connected to MV network. 6.- Measurements at the point of common coupling of an installation connected to the transmission network The measurement device was placed at the point of common coupling of a customer connected to 4 kv. The customer load was a 1 MW arc furnace with 9 Mvar of reactive compensation. Ih Vh Scc 15 kv 4 kv Figure 4: Measurement point model The application of the method using the sign of R eal( Vh Ih) gave fairly accurate results. Figure 5 gives an example of the application algorithm when a harmonic variation occurred. Figure 5: Algorithm with three recording windows For the 5 th and 7 th harmonics the estimation was Vh5 Ih5 =,35 14,9i and Vh7 Ih7 =,16 8,9i. Figure 6 compares the estimated impedances on the installation side with those obtained by simulation. Impedance (Ohm) Harmonic impedance on the installation side Frequency (Hz) Simulation of the harmonic impedance (Ohm) Estimation of harmonic impedance (Ohm) Figure 6: Comparison of impedance obtained by estimation and simulation The shape of the impedance curve is due to the fact that the 9 Mvar capacitor banks were directly connected to the 4 kv. We can notice that the estimated harmonic impedances are very close to those obtained by simulation :, :, :, :, :4, 1:, 1:, 1:4, :, :4, 1:, 1:, 1:4, :, :, :4, 3:, 3:, 3:4, 4:, :, :4, 3:, 3:, 3:4, 4:, Figure 7: Results of the non-linear regression method Using measurement on Figure 7, the non-linear regression method provided for the 5 th harmonic 5 = 13,6Ω and Zc5 = 13,4Ω. The two values show that there is a parallel EDF_Gonbeau_A1 Session Paper No 3-4 -

5 C I R E D 17 th International Conference on Electricity Distribution Barcelona, 1-15 May 3 resonance between inductance of the source and the capacitance of the installation. Harmonic voltage measurements and harmonic impedance simulations confirmed this resonance. Impedance (Ohm) ,5 14,4 14,3 14, 14, ,9 :, :, :4, 1:, 1:, 1:4, :, :, :4, 3:, 3:, 3:4, 4:, 4:, 4:4, 5:, :4,4 :44,4 3:4,4 3:4,4 3:44,4 4:4,4 4:4,4 4:44,4 Harmonic equivalent impedance on source side 5 Current (A) :, :, :4, 1:, 1:, 1:4, :, :, :4, 3:, 3:, 3:4, 4:, 4:, 4:4, 5:, :4,4 :44,4 3:4,4 3:4,4 3:44,4 4:4,4 4:4,4 4:44,4 Harmonic current from source side Js5 Figure 8: Application of the iterative method after a sudden harmonic variation at T=:4,4 The determination of and Js makes it possible to carry out a follow-up of these values by the iterative method. From an initial variation, the graphics on Figure 8 show that it is possible to follow equivalent circuit parameters on the source side ( Js, ) over the time. Once the parameters on the source side are fixed, the iterative method makes it possible to follow their respective value even if a harmonic variation occurs on the installation side. In other terms, the iterative method computes = Vh Ih Measurements at the point of common coupling of an installation connected to the distribution network Two installations connected to the kv distribution network have been instrumented. The first installation (Figure 9) corresponds to a rectifier with an irregular consumption. The second installation (Figure 11) corresponds to an industrial site with a very constant consumption. Js (equations 8 and 9). ( Js + Jc) ( Js Jc) Vh =. Zc. + Zc + (8) Jc = Vh Js (9) Impedance (Ohm) Curent (A) Current (A) th harmonic impedance on source side 5 5th harmonic current from source side :, :8, :16, :4, :3, :4, :48, :56, 1:4, 1:1, 1:, :, 1:8, :8, 1:36, :16, 1:44, :4, 1:5, :3, :, :4, :8, :48, :16, :56, :4, 1:4, :3, 1:1, 1:, :, 1:8, :8, 1:36, :16, 1:44, :4, 1:5, :3, :, :4, :8, :48, :16, :56, :4, 1:4, :3, 1:1, 1:, 1:8, 1:36, 1:44, 1:5, :, :8, :16, :4, :3, Js5 5th harmonic current from installation side Jc5 (mm:ss:ms) Figure 1: 5th harmonic currents Js Jc and network impedance evolutions This application shows the interest of the iterative method when taking for initial value the estimation of = Vh Ih the method makes it possible to follow, Js and Jc (Figure 1). On the second installation, the harmonic fluctuations allowed an application of the method using the sign of R eal Vh Ih for the equivalent parameters. ( ) Sc c 63 kv Scc=1549 MVA Scc Measurement point MVA kv Measurement point Scc=144 MVA kv kv Industrial loads 59 V PdN=66 kw IdN=88 A U dn=75 V ~ = Domestic loads Figure 11: installation model Figure 9: Installation model On the first installation, the harmonic current and load variations allowed a reliable application of the method using the sign of R eal( Vh Ih) for and Js estimation. In this particular case with the assumption of Zc >>, it is possible to calculate Jc according to the values of and During this measurement described on the graphs of Figure 1, the 5 th harmonic variations allowed to find 5 = 16,6Ω. Moreover, other 5 th harmonic variations leaded to Zc5 = 3,6Ω. EDF_Gonbeau_A1 Session Paper No 3-5 -

6 C I R E D 17 th International Conference on Electricity Distribution Barcelona, 1-15 May installation connected to the distribution grid revealed this limit). Thus, this application method on installations with fluctuating harmonic levels is to be proscribed. But, it is interesting to notice that when source and installation side impedances are close to each other the method is reliable. Thus this method will have to be correlated with other results (statistical or with results of the preceding methods). :, :1, :4, :36, :48, 1:, 1:1, 1:4, 1:36, 1:48, :, :1, :4, :36, :48, 3:, 3:1, Vh5 Ih5 3:4, 3:36, 3:48, 4:, 4:1, 4:4, 4:36, 4:48, 5:, Figure 1: 5th harmonic distortion and power measurements Using measurement on Figure 1, the non-linear regression method gives: Zc5 = 4Ω and Jc5 = 6,54A 5 = Ω and Js5 =,11A The results of both estimation methods are in line with those obtained by simulation. Moreover we can note that the current flowing from the installation to the network is larger than the current originating on the source side. 7- PROSPECTS The general objective of this study is to obtain a "standardized" method, which could be used within a contractual framework with customers. To be able to determine the exact customer contribution in all cases, EDF studied new estimation methods of the customer contribution (non-linear regression and iterative methods). In addition, new algorithms for application of these measurement methods, as well as existing methods (method using the sign of R eal( Vh Ih) ), were developed. The definition of algorithms and two dedicated measurement campaigns made it possible to cross a stage. The results of the described methods are encouraging. 1) The method using the sign of R eal( Vh Ih) allowed coherent harmonic impedances estimations when significant harmonic variations occur. Without significant harmonic voltage and current variation the method does not have any utility. We have defined thresholds in terms of harmonic current ( Ih ) and voltage ( Vh ) variations which lead to reliable estimations. These thresholds are around Ih >% Ih in the transmission network and Vh >6%Vh in the distribution network. ) The iterative method enabled interest to follow on line equivalent parameters (impedance and current injection). The results obtained were very conclusive but this method requires a very precise initial value. In this direction the iterative method appears to be a very good complement with the method using the sign of R eal( Vh Ih). 3) The non-linear method did not work if harmonic variations occur (the harmonic fluctuation on the first Lastly, the estimate methods are very sensitive to harmonic phase angle and a procedure should also be specified to reduce measurement errors. 7- CONCLUSION Harmonic current flowing at an installation s metering point results from harmonics originating in this installation and also in other installation connected to the power supply system. This paper presents assessment techniques and algorithms to realize on line harmonic emission evaluation. The basic idea is to define an approach scrutinizing sudden harmonic variations at the point of common coupling in order to apply the method using the sign of R eal( Vh Ih). Once the impedance and current estimation is done the iterative method makes it possible to follow-up these values over the time. To complete the assessment for periods with no significant harmonic variation, a non-linear regression method is described. These methods were tested with encouraging results. We can reasonably think that a method will see the light of day in the medium term allowing to determine the contribution of the installation and the power system to harmonic disturbance with sufficient precision within a contractual framework application. We should be able to give inform about our progress before the next CIRED. REFERENCES [1] H Yang, P. Pirotte, A. Robert, 1994, Assessing the harmonic emission level from one particular customer, Proceedings of PQA 94. [] 1996, Electromagnetic Compatibility, Assessment of emission limits for disturbing load in MV and HV power systems IEC [3], Electromagnetic Compatibility, General guide on harmonic and interharmonics measurements and instrumentation, for power supply systems and equipment connected thereto IEC Ed.. EDF_Gonbeau_A1 Session Paper No 3-6 -

Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions

Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions Fernando Bastião and Humberto Jorge Department of Electrical Engineering and Computers

More information

The development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08

The development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08 The development of the SA grid code on Power Quality emission Dr. Gerhard Botha 2017/08/08 Overview What is the Grid Code? What is Power Quality? Power Quality Management Principles Differences Challenges

More information

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC CITY OF LETHBRIDGE ELECTRIC ENGINEERING STANDARDS POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS The City of Lethbridge acknowledges the use of other utility industry and industry committee

More information

STUDY OF THE EFFECTS OF HARMONICS IN THE DESIGN OF TRANSMISSION NETWORK SHUNT COMPENSATORS: NETWORK SIMULATION AND ANALYSIS METHODS

STUDY OF THE EFFECTS OF HARMONICS IN THE DESIGN OF TRANSMISSION NETWORK SHUNT COMPENSATORS: NETWORK SIMULATION AND ANALYSIS METHODS STUDY OF THE EFFECTS OF HARMONICS IN THE DESIGN OF TRANSMISSION NETWORK SHUNT COMPENSATORS: NETWORK SIMULATION AND ANALYSIS METHODS In fulfillment of Master of Science in Electric Power and Energy Systems,

More information

Southern Company Power Quality Policy

Southern Company Power Quality Policy Southern Company Power Quality Policy Alabama Power Georgia Power Gulf Power Mississippi Power i Table of Contents: Southern Company Power Quality Policy SCOPE AND PURPOSE... 1 DEFINITIONS... 2 I. HARMONICS...

More information

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax: POWER CORPORATION Power Quality Specifications and Guidelines for Customers Phone: 403-514-3700 Fax: 403-514-3719 1 GENERAL OVERVIEW........................................ 1.1 WHAT DOES THIS SPECIFICATION

More information

Power Quality Summary

Power Quality Summary Power Quality Summary This article provides an overview of how voltage harmonic distortion is managed on the distribution network and focuses on the current at future issues surround the connection of

More information

Power Quality Requirements for Connection to the Transmission System

Power Quality Requirements for Connection to the Transmission System Power Quality Requirements for Connection to the Transmission System Revision: 1.0 Date: September 2015 Introduction and Purpose of this Document The purpose of this document is to provide clarity to Customers

More information

Modeling of the behavior of power electronic equipment to grid ripple control signal

Modeling of the behavior of power electronic equipment to grid ripple control signal Modeling of the behavior of power electronic equipment to grid ripple control signal X. Yang, S. Dennetière Abstract The paper presents time domain simulation for power electronic device equivalent impedance

More information

Emission Limits for Customer Facilities Connected to the Hydro-Québec Transmission System

Emission Limits for Customer Facilities Connected to the Hydro-Québec Transmission System Emission Limits for Customer Facilities Connected to the Hydro-Québec Transmission System Études de réseaux Direction Planification des actifs Hydro-Québec TransÉnergie Original in French dated December

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation R. S. Al Abri, M. H. Albadi, M. H. Al Abri, U. K. Al Rasbi, M. H. Al Hasni, S. M. Al Shidi Abstract This paper presents an analysis

More information

Resonances in Collection Grids of Offshore Wind Farms

Resonances in Collection Grids of Offshore Wind Farms Downloaded from orbit.dtu.dk on: Dec 20, 2017 Resonances in Collection Grids of Offshore Wind Farms Holdyk, Andrzej Publication date: 2013 Link back to DTU Orbit Citation (APA): Holdyk, A. (2013). Resonances

More information

Simulation Results on the Currents Harmonics Mitigation on the Railway Station Line Feed

Simulation Results on the Currents Harmonics Mitigation on the Railway Station Line Feed Proceedings of the 7th WSEAS Int. Conf. on Signal Processing, Computational Geometry & Artificial Vision, Athens, Greece, August 4-6, 7 69 Simulation Results on the Currents Harmonics Mitigation on the

More information

Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV)

Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV) Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV) IRR-DCC-MV 1. Introduction 1 IRR-DCC-MV 2. Scope 1 IRR-DCC-MV 2.1. General 1 IRR-DCC-MV 2.2. Affected

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission

More information

QUESTIONNAIRE for Wind Farm Power Stations only

QUESTIONNAIRE for Wind Farm Power Stations only TRANSMISSION SYSTEM OPERATOR QUESTIONNAIRE for Wind Farm Power Stations only To be submitted by the Generation Licensees together with the Application for Connection Certificate according to IEC 61400-21

More information

ELECTRICITY ASSOCIATION SERVICES LIMITED 2001

ELECTRICITY ASSOCIATION SERVICES LIMITED 2001 ELECTRICITY ASSOCIATION SERVICES LIMITED 2001 All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical,

More information

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives 2 TECHNICAL GUIDE NO. 6 GUIDE TO HARMONICS WITH AC DRIVES Guide to harmonics This guide is part of ABB s technical guide series, describing

More information

Chapter 6. Small signal analysis and control design of LLC converter

Chapter 6. Small signal analysis and control design of LLC converter Chapter 6 Small signal analysis and control design of LLC converter 6.1 Introduction In previous chapters, the characteristic, design and advantages of LLC resonant converter were discussed. As demonstrated

More information

Technical Brief: Flow Direction of Harmonics and High- order Harmonics

Technical Brief: Flow Direction of Harmonics and High- order Harmonics Technical Brief: Harmonics Harmonics are generated by semi- conductor controlled devices in the power supply of equipment as a result of distorted voltage and current waveforms. When the harmonic component

More information

A STUDY CASE ON HARMONIC DISTORTION CREATED BY WIND TURBINES

A STUDY CASE ON HARMONIC DISTORTION CREATED BY WIND TURBINES C I R E D 8 th International Conference on Electricity Distribution Turin, 6-9 June 5 A STUDY CASE ON HARMONIC DISTORTION CREATED BY WIND TURBINES Stavros PAPATHANASSIOU Michael PAPADOPOULOS National Technical

More information

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN Eugenio PEREA*, Eduardo ZABALA*, J. Emilio RODRÍGUEZ*, Asier GIL DE MURO*, Hugo GAGO * * * Fundación LABEIN,

More information

Power Factor & Harmonics

Power Factor & Harmonics Power Factor & Harmonics Andy Angrick 2014 Harmonic Distortion Harmonic problems are becoming more apparent because more equipment that produce harmonics are being applied to power systems Grounding Harmonics

More information

Grid Converters for Photovoltaic

Grid Converters for Photovoltaic Grid Converters for Photovoltaic and Wind Power Systems by R. Teodorescu, M. Liserre and P. Rodriguez ISBN: 978 0 470 05751 3 Copyright Wiley 2011 Chapter 3 Grid Requirements for PV Grid connection requirements

More information

Roadmap For Power Quality Standards Development

Roadmap For Power Quality Standards Development Roadmap For Power Quality Standards Development IEEE Power Quality Standards Coordinating Committee Authors: David B. Vannoy, P.E., Chair Mark F. McGranghan, Vice Chair S. Mark Halpin, Vice Chair D. Daniel

More information

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller This paper deals with the general problem of utilizing of renewable energy sources to generate electric

More information

North-West University, 2 Eskom SOC South Africa

North-West University, 2 Eskom SOC South Africa Electricity Supply to Africa and Developing Economies. Challenges and opportunities. Technology solutions and innovations for developing economies Advances in Power Quality Requirements for RPPs MG BOTHA

More information

Some aspects regarding harmonic s distortions propagation in large medium voltage distribution system

Some aspects regarding harmonic s distortions propagation in large medium voltage distribution system Some aspects regarding harmonic s distortions propagation in large medium voltage distribution system L. E. PETREAN 1, D. C. PETER 1, M. HORGOŞ 1, A. BUCHMANN 1, L. PETREAN 2 1 Electrical Engineering Department,

More information

SHUNT ACTIVE POWER FILTER

SHUNT ACTIVE POWER FILTER 75 CHAPTER 4 SHUNT ACTIVE POWER FILTER Abstract A synchronous logic based Phase angle control method pulse width modulation (PWM) algorithm is proposed for three phase Shunt Active Power Filter (SAPF)

More information

Power Quality Measurements and Operating Characteristics of Electric Arc Furnaces.

Power Quality Measurements and Operating Characteristics of Electric Arc Furnaces. 1 Power Quality Measurements and Operating Characteristics of Electric Arc Furnaces. Pedro E. Issouribehere (*),Fernando Issouribehere (*) IEEE Student Member, and Gustavo A. Barbera (*) Abstract Power

More information

IEEE sion/1547revision_index.html

IEEE sion/1547revision_index.html IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html

More information

shunt (parallel series

shunt (parallel series Active filters Active filters are typically used with diode/thyristor rectifiers, electric arc furnaces, etc. Their use in electric power utilities, industry, office buildings, water supply utilities,

More information

Harmonic Distortion Evaluations

Harmonic Distortion Evaluations Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion

More information

Application of a thyristor-controlled series reactor to reduce arc furnace flicker

Application of a thyristor-controlled series reactor to reduce arc furnace flicker ELEKTROTEHNIŠKI VESTNIK 78(3): 112-117, 2011 ENGLISH EDITION Application of a thyristor-controlled series reactor to reduce arc furnace flicker Ljubiša Spasojević, Boštjan Blažič, Igor Papič University

More information

1C.4.1 Harmonic Distortion

1C.4.1 Harmonic Distortion 2 1 Ja n 1 4 2 1 J a n 1 4 Vo l.1 -Ge n e r a l;p a r tc-p o we r Qu a lity 1. Scope This handbook section contains of PacifiCorp s standard for harmonic distortion (electrical pollution) control, as well

More information

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS. 1 PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS. DEFINATIONS Working /Active Power: Normally measured in kilowatts (kw). It does the "work" for the system--providing the motion, torque,

More information

University of Alberta

University of Alberta University of Alberta Harmonic Impedance and Harmonic Source Determination Based on Field Measurements by Edwin Enrique Nino Hernandez A thesis submitted to the Faculty of Graduate Studies and Research

More information

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Code No: R3 R1 Set No: 1 III B.Tech. II Semester Supplementary Examinations, January -14 POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions

More information

The Influence of Voltage Flicker for the Wind Generator upon Distribution System

The Influence of Voltage Flicker for the Wind Generator upon Distribution System The Influence of Voltage Flicker for the Wind Generator upon Distribution System Jin-Lung Guan, Jyh-Cherng Gu, Ming-Ta Yang, Hsin-Hung Chang, Chun-Wei Huang, and Shao-Yu Huang Digital Open Science Index,

More information

The unified power quality conditioner: the integration of series and shunt-active filters

The unified power quality conditioner: the integration of series and shunt-active filters Engineering Electrical Engineering fields Okayama University Year 1997 The unified power quality conditioner: the integration of series and shunt-active filters Hideaki Fujita Okayama University Hirofumi

More information

IMPLICATIONS OF APPLYING DIFFERENT VAR SUPPORT TECHNOLOGIES IN THE ESKOM TRANSMISSION NETWORK WITH PARTICULAR EMPHASIS ON THE LIFECYCLE COST

IMPLICATIONS OF APPLYING DIFFERENT VAR SUPPORT TECHNOLOGIES IN THE ESKOM TRANSMISSION NETWORK WITH PARTICULAR EMPHASIS ON THE LIFECYCLE COST IMPLICATIONS OF APPLYING DIFFERENT VAR SUPPORT TECHNOLOGIES IN THE ESKOM TRANSMISSION NETWORK WITH PARTICULAR EMPHASIS ON THE LIFECYCLE COST Teboho Ken Ramorapeli A research report submitted to the Faculty

More information

Published in: Proceedings of the 2016 IEEE International Conference on Power Electronics, Drives and Energy Systems (PEDES)

Published in: Proceedings of the 2016 IEEE International Conference on Power Electronics, Drives and Energy Systems (PEDES) Aalborg Universitet Voltage Feedback based Harmonic Compensation for an Offshore Wind Power Plant Chaudhary, Sanjay K.; Lascu, Cristian Vaslie; Teodorescu, Remus; Kocewiak, ukasz Published in: Proceedings

More information

, ,54 A

, ,54 A AEB5EN2 Ground fault Example Power line 22 kv has the partial capacity to the ground 4,3.0 F/km. Decide whether ground fault currents compensation is required if the line length is 30 km. We calculate

More information

Long lasting transients in power filter circuits

Long lasting transients in power filter circuits Computer Applications in Electrical Engineering Vol. 12 2014 Long lasting transients in power filter circuits Jurij Warecki, Michał Gajdzica AGH University of Science and Technology 30-059 Kraków, Al.

More information

7/15/2002 PP.AFD.08 1 of 28

7/15/2002 PP.AFD.08 1 of 28 Power Quality Considerations When Applying Adjustable Frequency Drives Explanations and Various Countermeasures 7/15/2002 PP.AFD.08 1 of 28 Power Quality Why the Renewed Interest in Power Quality? Copy

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Power Converters and Power Quality

Power Converters and Power Quality Power Converters and Power Quality Karsten KAHLE, CERN karsten.kahle@cern.ch, Baden (CH) 2 References EN 50160 (2010) IEC 61000 IEC 61000-2-2 IEC 61000-2-4 IEC 61000-2-12 IEC 61000-3-4 IEC 61000-3-6 IEC

More information

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD Scientific Journal of Impact (SJIF): 5.71 International Journal of Advance Engineering and Research Development Volume 5, Issue 04, April -2018 e-issn (O): 2348-4470 p-issn (P): 2348-6406 ANALYSIS AND

More information

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de

More information

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services edarat group INTRODUCTION Harmonics are a mathematical way of describing distortion

More information

Optimum dimensioning of a flicker compensator in three-phase electric-arc furnaces supply systems

Optimum dimensioning of a flicker compensator in three-phase electric-arc furnaces supply systems Optimum dimensioning of a flicker compensator in three-phase electric-arc furnaces supply systems Abstract Three-phase electric arc furnaces, the design power ratings of which are in many cases above 100

More information

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission

More information

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces IEEE PES Boston Chapter Technical Meeting IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces P1547 Chair David

More information

Harmonic Planning Levels for Australian Distribution Systems

Harmonic Planning Levels for Australian Distribution Systems Abstract Harmonic Planning Levels for Australian Distribution Systems V.J. Gosbell 1, V.W. Smith 1, D. Robinson 1 and W. Miller 2 1 Integral Energy Power Quality Centre, University of Wollongong 2 Standards

More information

ELECTRICITY SUPPLY POWER QUALITY AND RELIABILITY Code of Practice

ELECTRICITY SUPPLY POWER QUALITY AND RELIABILITY Code of Practice ICS 29.240:03.120 Zambian Standard ELECTRICITY SUPPLY POWER QUALITY AND RELIABILITY Code of Practice Part 3: Application Guidelines for Enterprises ZAMBIA BUREAU OF STANDARD DATE OF PUBLICATION This Zambian

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

Power quality report. A Manufacturing Plant

Power quality report. A Manufacturing Plant Power quality report Prepared for A Manufacturing Plant 6 May 2016 by Dr Angelo De Francesco Power Quality Consultant Page 1 Contents 1 EXECUTIVE SUMMARY... 4 2 INTRODUCTION... 5 2.1 SITE MONITORED...

More information

Interharmonic Task Force Working Document

Interharmonic Task Force Working Document Interharmonics Definition IEC-61000-2-1 [1] defines interharmonic as follows: Between the harmonics of the power frequency voltage and current, further frequencies can be observed which are not an integer

More information

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar.

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar. Technical Report on Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by Dr. V. R. Kanetkar (February 2015) Shreem Electric Limited (Plot No. 43-46, L. K. Akiwate

More information

Use only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at

Use only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at Reviewed: Sergey Kryuchkov Distribution Engineering Scott Merriman Distribution Standards Valentina Dabic Distribution Planning Warren Quan Distribution Operations, FVO Raj Solanki Distribution Engineering

More information

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR) Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR) Mr. A. S. Patil Mr. S. K. Patil Department of Electrical Engg. Department of Electrical Engg. I. C. R. E. Gargoti I. C. R. E. Gargoti

More information

Design of SVPWM Based Inverter for Mitigation of Harmonics in Power System

Design of SVPWM Based Inverter for Mitigation of Harmonics in Power System Design of SVPWM Based Inverter for Mitigation of Harmonics in Power System 1 Leena N C, 2 B. Rajesh Kamath, 3 Shri Harsha 1,2,3 Department of EEE, Sri Siddhartha Institute of Technology, Tumkur-572105,

More information

Harmonic detection and filtering

Harmonic detection and filtering M M M M Low-voltage expert guides N 4 Harmonic detection and filtering M M M M M M M M Contents General... 5. Definition of harmonics and their origin... 5.. distortion of a sinusoidal signal... 5.. origin

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

Prepared By Pierre Archambault, PEng Power Survey International Inc Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA

Prepared By Pierre Archambault, PEng Power Survey International Inc Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA ATCO Electric Hangingstone Substation HARMONIC STUDY Prepared By Pierre Archambault, PEng Power Survey International Inc. 8025 Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA Rev.: 6 March 2007 TABLE OF

More information

Active Elimination of Low-Frequency Harmonics of Traction Current-Source Active Rectifier

Active Elimination of Low-Frequency Harmonics of Traction Current-Source Active Rectifier Transactions on Electrical Engineering, Vol. 1 (2012), No. 1 30 Active Elimination of Low-Frequency Harmonics of Traction Current-Source Active Rectifier Jan Michalík1), Jan Molnár2) and Zdeněk Peroutka2)

More information

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. Harmonic Mitigation for Variable Frequency Drives HWEA Conference February 15, 2011 Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. 1 OVERVIEW Linear vs. Non- Linear Load Definitions AC Drive Input Current Harmonics

More information

Wind Power Facility Technical Requirements CHANGE HISTORY

Wind Power Facility Technical Requirements CHANGE HISTORY CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical

More information

Electric Power Quality Monitoring and Analysis at a Tri-generation Plant under Development

Electric Power Quality Monitoring and Analysis at a Tri-generation Plant under Development Electric Power Quality Monitoring and Analysis at a Tri-generation Plant under Development IOANA PISICĂ, LAURENŢIU CONSTANTIN LIPAN, PETRU POSTOLACHE, CORNEL TOADER Department of Power Systems University

More information

Harmonic filter design for IEC compliance

Harmonic filter design for IEC compliance Harmonic filter design for IEC 61000 compliance Marius Jansen ALSTOM Grid Power System Compensation Brisbane, Australia marius.jansen@alstom.com Abstract The paper 1 provides a guideline for the selection

More information

Power Quality Notes 3-2 (MT)

Power Quality Notes 3-2 (MT) Power Quality Notes 3-2 (MT) Marc Thompson, Ph.D. Senior Managing Engineer Exponent 21 Strathmore Road Natick, MA 01760 Alex Kusko, Sc.D, P.E. Vice President Exponent 21 Strathmore Road Natick, MA 01760

More information

Voltage Sag Index Calculation Using an Electromagnetic Transients Program

Voltage Sag Index Calculation Using an Electromagnetic Transients Program International Conference on Power Systems Transients IPST 3 in New Orleans, USA Voltage Sag Index Calculation Using an Electromagnetic Transients Program Juan A. Martinez-Velasco, Jacinto Martin-Arnedo

More information

Power Quality in Metering

Power Quality in Metering Power Quality in Metering Ming T. Cheng Directory of Asian Operations 10737 Lexington Drive Knoxville, TN 37932 Phone: (865) 218.5885 PQsynergy2012 www.powermetrix.com Focus of this Presentation How power

More information

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM Dr. Jagdish Kumar, PEC University of Technology, Chandigarh Abstract the proper selection of values of energy storing

More information

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER Presented by Ric Austria, Principal at Pterra Consulting to the IEEE San Francisco Chapter Feb 17, 2016 California Public Utilities Commission,

More information

MERLIN GERIN KNOW HOW. THM filtering and the management of harmonics upstream of UPS

MERLIN GERIN KNOW HOW. THM filtering and the management of harmonics upstream of UPS MERLIN GERIN KNOW HOW THM filtering and the management of harmonics upstream of UPS THM filtering and the control of harmonics upstream of UPSs Authors : S. BERNARD - J.N. FIORINA - B GROS - G. TROCHAIN

More information

SOURCES OF ERROR IN UNBALANCE MEASUREMENTS. V.J. Gosbell, H.M.S.C. Herath, B.S.P. Perera, D.A. Robinson

SOURCES OF ERROR IN UNBALANCE MEASUREMENTS. V.J. Gosbell, H.M.S.C. Herath, B.S.P. Perera, D.A. Robinson SOURCES OF ERROR IN UNBALANCE MEASUREMENTS V.J. Gosbell, H.M.S.C. Herath, B.S.P. Perera, D.A. Robinson Integral Energy Power Quality Centre School of Electrical, Computer and Telecommunications Engineering

More information

Identification of network models parameters for simulating transients

Identification of network models parameters for simulating transients Identification of network models parameters for simulating transients D. Cavallera, J-L. Coulomb, O. Chadebec, B. Caillault, F-X. Zgainski and A.Ayroulet Abstract In case of electrical black-out, one of

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

Insights in the impact of special projects on voltage quality in the HV/EHV networks

Insights in the impact of special projects on voltage quality in the HV/EHV networks Authors: Vladimir Ćuk Konstantinos Tzanakakis Department of Electrical Engineering, Electrical Energy Systems Checked by: prof. J.F.G. (Sjef) Cobben Frans van Erp (Tennet) Date: 05.12.2014. Version: 0.0

More information

High voltage shunt capacitor banks HIGH VOLTAGE COMPENSATION AND HARMONIC FILTERING PRODUCTS

High voltage shunt capacitor banks HIGH VOLTAGE COMPENSATION AND HARMONIC FILTERING PRODUCTS High voltage shunt capacitor banks Alstom Grid high voltage shunt capacitor bank offering is divided in: By bank construction HV open rack capacitor banks HV enclosed capacitor banks By bank design HV

More information

Harmonic distortion from induction furnace loads in a steel production plant

Harmonic distortion from induction furnace loads in a steel production plant Harmonic distortion from induction furnace loads in a steel production plant S.L.Gbadamosi 1* A.O.Melodi 2 1. Department of Electrical and Electronics Engineering, School of Engineering and Engineering

More information

Harmonic Study in Low Voltage Distribution Network in a Real Time Foundry Industry

Harmonic Study in Low Voltage Distribution Network in a Real Time Foundry Industry I J C T A, 9(37) 2016, pp. 769-781 International Science Press Harmonic Study in Low Voltage Distribution Network in a Real Time Foundry Industry D. Ravichandran * and Er. R. Panneerselvam ** Abstract:

More information

A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards

A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards Indian Journal of Science and Technology, Vol 9(30), DOI: 10.17485/ijst/2016/v9i30/99034, August 2016 ISSN (Print) : 0974-6846 ISSN (Online) : 0974-5645 A Power Quality Survey on a 22 kv Electrical Distribution

More information

148 Electric Machines

148 Electric Machines 148 Electric Machines 3.1 The emf per turn for a single-phase 2200/220- V, 50-Hz transformer is approximately 12 V. Calculate (a) the number of primary and secondary turns, and (b) the net cross-sectional

More information

Simulation of H bridge Inverter used for Induction Melting Furnace

Simulation of H bridge Inverter used for Induction Melting Furnace International Journal of Emerging Engineering Research and Technology Volume 2, Issue 3, June 214, PP 4-44 ISSN 2349-4395 (Print) & ISSN 2349-449 (Online) Simulation of H bridge Inverter used for Induction

More information

A Reduction of harmonics at the Interface of Distribution and Transmission Systems by using Current Source active Power Filter

A Reduction of harmonics at the Interface of Distribution and Transmission Systems by using Current Source active Power Filter International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, Volume 8, Issue 6 (September 2013), PP.35-39 A Reduction of harmonics at the Interface of Distribution

More information

Estimation of the Short Circuit Ratio and the Optimal Controller Gains Selection of a VSC System

Estimation of the Short Circuit Ratio and the Optimal Controller Gains Selection of a VSC System Estimation of the Short Circuit Ratio and the Optimal Controller Gains Selection of a VSC System J Z Zhou, A M Gole Abstract-- The optimal control gains of the VSC HVDC converter are very dependent on

More information

Appendix. Harmonic Balance Simulator. Page 1

Appendix. Harmonic Balance Simulator. Page 1 Appendix Harmonic Balance Simulator Page 1 Harmonic Balance for Large Signal AC and S-parameter Simulation Harmonic Balance is a frequency domain analysis technique for simulating distortion in nonlinear

More information

STATCOM, an efficient means for flicker mitigation

STATCOM, an efficient means for flicker mitigation STATCOM, an efficient means for flicker mitigation T. Larsson, Student Member, IEEE ABB Power Systems Västerås, Sweden Formerly with the Royal Institute of Technology Stockholm, Sweden C. Poumarède, Electricité

More information

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead

More information

UPQC (Unified Power Quality Conditioner)

UPQC (Unified Power Quality Conditioner) A Unified Power Quality Conditioner (UPQC) is a device that is similar in construction to a Unified Power Flow Conditioner (UPFC). The UPQC, just as in a UPFC, employs two voltage source inverters (VSIs)

More information

POWER QUALITY REPORT

POWER QUALITY REPORT Power Quality Research Lab., I-7, Wyb. Wyspiaoskiego 27, 50-370 Wrocław, Poland phone +48713202626, fax +48713202006, email: zbigniew.leonowicz@pwr.wroc.pl Facility: XXX POWER QUALITY REPORT Start Monitoring:

More information

PERFORMANCE OF DISTRIBUTION STATIC COMPENSATOR IN LOW VOLTAGE DISTRIBUTION SYSTEM

PERFORMANCE OF DISTRIBUTION STATIC COMPENSATOR IN LOW VOLTAGE DISTRIBUTION SYSTEM PERFORMANCE OF DISTRIBUTION STATIC COMPENSATOR IN LOW VOLTAGE DISTRIBUTION SYSTEM Bhupali P. Kumbhar 1, Prof. V. V. Khatavkar 2 1 PG Student, Dept. of Electrical Engineering, 2 Asst. Professor, Dept. of

More information

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab University of Jordan School of Engineering Electrical Engineering Department EE 219 Electrical Circuits Lab EXPERIMENT 7 RESONANCE Prepared by: Dr. Mohammed Hawa EXPERIMENT 7 RESONANCE OBJECTIVE This experiment

More information

Performance of high voltage transducers for measurement of power quality disturbances modeling and simulation

Performance of high voltage transducers for measurement of power quality disturbances modeling and simulation Performance of high voltage transducers for measurement of power quality disturbances modeling and simulation HÉDIO TATIZAWA 1, ERASMO SILVEIRA NETO 2, GERALDO F. BURANI 1, ANTÔNIO A. C. ARRUDA 1, KLEIBER

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

Power Quality Report. A Manufacturing Plant

Power Quality Report. A Manufacturing Plant Power Quality Report Prepared for A Manufacturing Plant 6 May 2016 by Dr Angelo De Francesco Power Quality Consultant CHK Power Quality Pty Ltd Page 1 Contents 1 EXECUTIVE SUMMARY... 4 2 INTRODUCTION...

More information

Power Quality in High Density Residential Distribution Grids

Power Quality in High Density Residential Distribution Grids Power Quality in High Density Residential Distribution Grids Gustav R. Krüger, Raj M. Naidoo Abstract Research in the field of power quality challenges in distribution grids is gaining a strong foothold.

More information