1 Electricity Supply to Africa and Developing Economies. Challenges and opportunities. Technology solutions and innovations for developing economies Advances in Power Quality Requirements for RPPs MG BOTHA 1, BB PETERSON 2, H MOSTERT 2, UJ MINNAAR 2 1 North-West University, 2 Eskom SOC South Africa SUMMARY The power quality requirements for RPPs created significant debate when the first RPPs started connecting to the grid. The purpose of this paper is to capture some of the debates around the harmonic emission limits and assessment methods as well as the resulting update to the RPP grid code. KEYWORDS Power quality, harmonics, unbalance, flicker, RPP, Grid Code, grid code compliance 1. INTRODUCTION Since 2011, South Africa has seen a steady increase in independent power producers (RPPs) connecting to the national grid. The South African REIPPPP process has been hailed as a major success for the country [1]. Nevertheless, several teething issues did occur, with the power quality aspects of RPPs being one of the bigger learning curves, especially harmonics. The purpose of this paper is to provide background to the harmonic emission requirements, discuss the issues that were encountered and the solutions provided to date. The changes to the requirements are provided with a view of providing some background to the decisions and further clarification of some requirements. The differences of interpretation of the requirements by NSPs and RPPs and the risks to both parties are highlighted. The primary goal is to marry these differences and minimise the real risks, whilst ensuring fairness to all customers connected anywhere in the network. Whilst criticism remain to the requirements, several RPP installations have already applied the principles successfully to prove compliance and achieve full operational status, most without the need to resort to expensive harmonic filters or other mitigating options.
2 2. BACKGROUND When the first South African Grid Code for Renewable Power Plants (RPPs) was published in November 2012 [2], the power quality (PQ) requirements were based on the processes used for traditional load customers. These were largely derived from the existing Eskom practices at the time, since Eskom had the most experience in dealing with larger customers. The base premise to manage PQ levels is to provide emission limits to customers for the different power quality parameters. The Network Service Provider (NSP) then has the responsibility to manage the resulting PQ, which would be a combination of network strengthening or other network mitigation interventions as well as enforcing contractual limits when PQ problems arise. The emission limits are set based on the IEC/TR /7/13 [3][4][5] documents (as updated), taking local network conditions into account. In terms of harmonic emissions, a key factor is the expected harmonic impedance of the network as seen by the customer. This harmonic impedance affects the resulting voltage harmonics due to harmonic currents injected by customers loads. The default selection of a three-times base harmonic impedance as an envelope created both confusion and conflict. Consultants started engaging with the Eskom PQ departments when the first installations finalised grid code compliance reports. Two aspects became clear: 1) that the PQ requirements were unclear to consultants and 2) difficult to prove and achieve from an RPP point of view. Therefore, a Harmonics Working Group was established under the South African Grid Code secretariat to address the concerns and draft a guideline for consultants and RPP owners. This working group evolved into a PQ working group as more clarity on the harmonic emission requirements were found and additional questions posed around the other parameters. 3. REQUIREMENTS The basic PQ requirements provided for in the grid code are summarised as follows: 1. Which parameters are to be regulated, 2. That the assessment shall be done at the POC, 3. That the NSP (utility) shall calculate appropriate emission limits, along with defining the network conditions under which these requirements shall be met, e.g. PQ levels, fault levels and the infamous three-times impedance envelope, 4. That the RPP generator shall ensure the RPP is appropriately designed and operated. The majority of these requirements were already provided for in the Eskom contracts, the socalled Connection and Use of System Agreement (CUOSA). Firstly, it was required that RPPs be treated the same as traditional customers as far as possible. These were published as part of the grid code as power quality forms part of NSPs licensing conditions and to ensure transparency in that these rules are provided upfront to any prospective RPP.
3 4. POINTS OF CONFLICT 4.1. RPP DEVELOPER CONCERNS Based on the first reports received, as well as interactions between developers and Eskom, the following concerns were evident: 1. The grid code requirements were unclear, since few consultants had sufficient power quality background; a. Added to this was the fact that the first set of connection agreements contained only a selection of voltage harmonic emission limits explicitly, with a paragraph explaining how to obtain the other voltage harmonic and current harmonic emission limits; 2. The requirements were different to those of other countries with established renewable energy sectors e.g. European countries; a. As an example, the IEC apportioning method is not followed in some countries; 3. The compliance is based on the rms harmonic currents; therefore, it is possible that an installation would absorb harmonic voltage and current (and have a beneficial impact on the network) whilst exceeding the allocated current emission limits (i.e. appear non-compliant); 4. The three-times impedance was deemed unrealistic NSP CONCERNS The NSP is legally responsible for the power quality at each customer point of supply (updated as point of connection for power producers). Therefore, the NSP has to manage the power quality, which can be done via the following steps: 1. Limiting the impact of any customer on power quality (generally via contracts such as the CUOSA); 2. Coordinating the combined impact of customers at a point of common coupling (PCC); 3. Monitoring the power quality at all PCCs; 4. Limiting the network s impact on power quality provided to customers; 5. Communicating to customers on all relevant aspects CONTEXT OF CONCERNS Whilst Eskom had reasonable experience in dealing with customers and power quality aspects, it was not adequately prepared to deal with the number of new challenges brought by the RPPs, since only a handful of specialists had sufficient experience in contracting. It should also be noted that most municipalities lack the staff complement and network information to do detailed studies. Therefore, the processes have to take into account the lack of knowledge in South Africa and be easy to implement by inexperienced staff. Furthermore, there are major differences between South African and European networks, e.g. base load generation location, transmission line lengths, overhead vs. underground (affecting system capacitance), use of shunt capacitors and interconnections to other countries. These factors affect the typical system strength and harmonic impedance. It was also found that many of the generators were connecting at relatively weak locations in the network many of the RPPs being connected at a short-circuit ratio as low as 3 times. It is
4 unrealistic to assume that European-based rules and regulations can be implemented as is in South Africa. 5. UPDATING THE REQUIREMENTS It was therefore clear that the requirements had to be updated. However, some aspects appear contradictory, e.g. reducing the harmonic impedance envelope as well as increasing emission limits A BRIEF HISTORY OF POWER QUALITY APPORTIONING The Merriam-Webster dictionary defines apportioning as to divide and share out according to a plan and to make a proportionate division or distribution of. Power Quality apportioning is, therefore, the equitable sharing of power quality levels amongst customers and network operators, according to a plan. Power quality apportionment is based on the IEC technical reports, IEC/TR /7 and 13 [3][4][5]. It means that there is no international consensus on the processes, but it contains the current best practice, philosophies and guidelines that are available. The guiding philosophy is that all customers, as well as the network, contributes to the total PQ levels and appropriate limits should be set for each party s contributions. Edition 1 of these documents considered that emission limits had (most likely) not been allocated before. Therefore, PQ measurements were done to determine the difference between the background levels and planning levels. The appropriate share per customer is based on the size (i.e. notified maximum demand) relative to the available capacity of the connection point. At the time of compiling the RPP grid code, it was understood that several European countries still used this method. Eskom has adopted the latest editions (2008), which proposes a more relaxed apportioning of emission limits than edition 1. For edition 2, the entire planning level is allocated proportionally between all customers already connected, those wanting to connect now as well as likely future customers. This places a heavier burden on NSPs, since customers connected previously may already use more than the fair share as per this calculation. This is especially true in the case of legacy customers, who were connected before such allocations were done. Despite many criticisms of these methods, at this stage, no better options exist. At the time of writing, work on updated apportioning methods is underway and the apportioning may be updated in future when better options exist IMPEDANCE ENVELOPE IEC [3] recommends that the ratio between the voltage and current harmonic emission limits be set based on simulated harmonic impedance at the point of connection. However, the document also allows for simplified approximations, such as the examples provided in Annex A [3] for MV systems. No generic extrapolation is provided for higher voltage levels. A comparison of the recommended 11 kv and 33 kv envelopes are shown in Figure 1 along with the South African proposal of three-times base impedance. The
5 IEC also states that such generalizations are usually not possible at the higher voltage levels. Figure 1: Proposed harmonic impedance envelopes However, a broad generalization has been made in South Africa to deal with industrial and other large customers since the late 1990 s. Given limited skills, resources and network information at the time, an assumption had been made that was generally accepted as reasonable an upper resonance limit of three-times the base impedance was adopted at all points of supply and all voltage levels. In the spirit of treating RPPs the same as traditional load customers (i.e. as customers of the wires business), the three-times base impedance was also adopted in the RPP grid code. Note that this three-times impedance envelope is intended to cover both existing network conditions as well as future changes to the network. Therefore, it manages the risk of existing resonances under network normal and contingency situations, as well as looking forward when the network changes. It means that the NSP also has to manage resonances on the network and the risk to customers due to higher resonance conditions is reduced. The three-times impedance envelope was one of the main factors criticized by RPPs. It is important to note that, while the treatment of RPPs and load customers are the same as far as possible, there is a significant regulatory difference when it comes to PQ requirements: RPPs must prove compliance to all requirements before a license will be approved. Compliance is, therefore, required by using the forward-looking three-times impedance and measured current harmonics, irrespective of existing voltage harmonics at the time of connection. Traditional load customers have to show reasonable assurance of compliance and future problems may be addressed as and when they arise. An RPP is, therefore, required to install adequate filters for problems that may not arise over the 20-year Power Purchase Agreement (PPA) horizon. However, once an RPP has shown compliance and received its license, any future harmonic problems become the responsibility of the NSP, unless there is a change in the RPP s plant and/or equipment, which may be responsible for the harmonic exceedance.
6 In order to see what harmonic impedance envelope would be reasonable, a simulation study was undertaken to evaluate the harmonic impedance in the Eskom network, since widescale measurement of harmonic impedance would be impractical. Digsilent simulations were done for all busbars in the Eskom system, using case files updated for harmonic simulations 1. The harmonic impedance at each busbar was normalized to the 50 Hz impedance for comparison to the three-times envelope. For a system-wide comparison to the three-times envelope, the normalized impedance values of all busbars were aggregated per frequency. Figure 2 shows the 95 th percentile plots for MV and HV nodes respectively vs. linear impedance plots for system normal. MV nodes included 11 kv, 22 kv and 33 kv, whilst 66 kv, 88 kv and 132 kv nodes were included for the HV calculations. It appears that the system impedance at most sites are reasonable at the lower harmonic frequencies for normal operating conditions, however, significant resonances appear at the higher order frequencies for both MV and HV networks. Figure 2: 95th percentile plots of MV and HV system impedance for System Normal. These simulations ignored the potential impact of contingencies, which can be quite significant. Two scenarios are possible, namely that the existing resonance frequency is shifted or that additional resonance frequencies arise. Based on a series of simulations at specific nodes, it was estimated that a typical band of Hz exist around resonant frequencies. By using a 600 Hz (300 Hz in either direction) bandwidth around the 95 th percentile curves, envelopes for the HV and MV impedance are derived as shown in Figure 3. From this, it appears that the three-times envelope may be a reasonable assumption as an interim solution. Both RPPs and the NSP bear additional risks due to this assumption. Several options were discussed for more representative envelopes or even site-specific envelopes. However, consensus could not be reached between the NSP representatives, consultants and the GCAC. Further research is in progress by Eskom to identify more 1 Base case files were used for these simulations. Whilst the case files were updated for harmonic simulations, no other accuracy checks or operational variations were done, e.g. normally open points, shunt capacitor values, generation patterns, line type data, loading etc. The purpose was to obtain an indication of the harmonic impedance envelope, i.e. statistical analysis of simulated results.
7 appropriate impedance envelopes and the RPP grid code will be amended once such proposals are accepted by all stakeholders. Figure 3: 95th percentile plots of MV and HV system impedance with 600Hz contingency bandwidth NETWORK INFORMATION PROVIDED A parallel debate by a different working group was had around network information provided to RPP developers. The network information provided by the NSP is provided in Appendix 12 of the RPP grid code version 2.9. It is noted that harmonic system impedance is required for two aspects, namely ensuring that the RPP installation does not cause excessive resonance and for harmonic filter design should filters be required. It is not appropriate to use the three-times harmonic impedance envelope for such simulations. It is possible that any reduction of the network results in significant inaccuracies when simulating the harmonic impedance. An example of the differences between the harmonic impedance based on the full model and some reduced models are shown in Figure 4. Given the differences seen, it was decided that the NSP will be responsible to provide harmonic impedance simulations for both network normal and a range of system contingencies. No simplified model provided as per Appendix 12 can be used for harmonic impedance simulations.
8 Figure 4: Frequency sweep of base network impedance showing impact of reducing network ASSESSMENT CLARIFICATIONS Basic Power Quality Assessment The NSP manages power quality in terms of measured voltage parameters. The assessment parameter also takes the statistical nature of PQ into account, i.e. situations may arise, usually outside the control of the NSP, where the performance may be significantly worse than expected, albeit for limited time periods. PQ is, therefore, typically assessed as a 95 th percentile aggregated over a sliding weekly scale [3][6]. An RPP, therefore, need to measure for at least one week as per NRS [6] to prove compliance. A realistic assessment will also be representative of typical plant performance [3], e.g. power production profiles, equipment switching etc Harmonic Voltage vs. Harmonic Current According to the IEC, power quality is defined as characteristics of the electric current, voltage and frequencies at a given point in an electric power system, evaluated against a set of reference technical parameters [7]. These reference technical parameters in IEC series document are provided in terms of the voltage. However, current can be seen as the driving force of deviations from the ideal reference, due to the voltage drop caused across the system impedance. Given that the network may change over the timespan of the PPA, the three-times impedance envelope provides the means to assess the RPP s performance over this timespan. Depending on the harmonic impedance at the time of connection and assessment, the assessed voltage harmonic emission may be more or less than the corresponding limit whereas the current emission limit will indicate the likely future performance. The current harmonic emission limits are, therefore, the critical assessment criteria.
9 CT and VT Accuracy IEC/TR recommends a minimum emission limit of 0.1 % for the voltage harmonics, but no recommendation for current harmonic emission limits. However, the emission limits for both voltage and current harmonics calculated for many of the RPPs were less than 0.1 %. Although the NSP could qualify the potential risk to the network, standard transducers are less accurate and the requirement is regarded as unreasonable. The typical CT used has an accuracy specification of 0.2 % and this is specified only at the fundamental frequency. VTs are also known to exhibit potential internal resonance at higher frequencies, typically above the 25 th harmonic. The better solution would be to install specialised transducers with very high accuracies for PQ assessment. However, such costs would be prohibitive and it was agreed that measurements will be done using standard transducers. The minimum emission limits were updated to 0.1 % for voltage emissions and 0.1 A for current emissions respectively. It is expected that future revisions of the RPP grid code will update the harmonic current emission minimum level to 0.1 % as well Assessment Methods The guideline is not intended to prescribe the methods that may be used to assess the PQ performance of the installation, but some recommendations were provided. Should the assessed harmonic current level exceed the emission limit, the following recommended analysis methods were recommended: The impedance slope method, as described in Cigré Technical Report 468, section 4.2.2: Harmonic Emissions Level Compliance Assessment [8]; Negative correlation between harmonic current and voltage (i.e. an increase in harmonic current coinciding with a decrease in harmonic voltage and vice versa); Zero harmonic voltage measured throughout the measurement period, allowing for up to 300% of the current emission limit; The impedance scaling method, where the measured harmonic voltage is scaled according to the ratio of the three-times impedance envelope vs. the simulated system impedance; Group harmonic distortion levels less than group harmonic distortion limits, where individual harmonic emissions may exceed the emission limit by up to 50%. The list is not exhaustive and additional methods may be employed to prove compliance to the emission limits. Further details can be found in the PQ guideline, Appendix 13 of the RPP grid code [2] GUIDELINE The guideline, included as Appendix 13 of the RPP grid code version 2.9, contains details of both the simulation and measurement requirements to prove grid code compliance. The guideline includes the steps to be taken, including flowcharts of the typical process. The concepts around harmonic emissions and the three-times impedance, as discussed in this paper, were included.
10 6. CONCLUSIONS An update to the power quality requirements (clause 9 of the RPP Grid Code) as well as a guideline for power quality compliance was published in version 2.9 towards the end of Key improvements are the clarification of the requirements, high-level guidance for simulating and measuring compliance as well as relaxation of emission limits under certain conditions. Amongst others, emission limits for rapid voltage changes and interharmonics have been removed and a group harmonic emission limit was introduced with allowance up to 150% of individual emission limits when the group harmonic emission limit is met. The preferred analysis methods from the CIGRE C4.109 brochure are discussed, without restricting the analysis methods that may be used. The process was a significant learning curve for both the NSPs and RPP consultants. The guideline is now available to everybody and it is hoped that RPPs will in future be better able to plan appropriately for PQ aspects. It is acknowledged that the PQ requirements and guideline are not yet perfect. Further research and analysis is being done and updates will be published as better solutions are found. 7. REFERENCES [1] Creamer Media Reporter, Tallying the benefits of South Africa s Renewable Energy Power Producer s Procurement Programme, Engineering News, 9TH MAY 2016, online, accessed 2017/10/01, [2] NERSA, Grid Code Requirements for Wind Energy Facilities Connected to Distribution or Transmission Systems in South Africa, version , July July [3] IEC , Electromagnetic compatibility (EMC) - Part 3-6: Limits - Assessment of emission limits for the connection of distorting installations to MV, HV and EHV power systems, Edition 2.0, [4] IEC , Electromagnetic compatibility (EMC) - Part 3-7: Limits - Assessment of emission limits for the connection of fluctuating installations to MV, HV and EHV power systems, Edition 2.0, [5] IEC , Electromagnetic compatibility (EMC) - Part 3-13: Limits - Assessment of emission limits for the connection of unbalanced installations to MV, HV and EHV power systems, Edition 2.0, [6] NRS 048-2, Electricity Supply Quality of Supply: Part 2: Voltage characteristics, compatibility levels, limits and assessment methods, Edition 4, [7] IEV Online, Electropedia: The World's Online Electrotechnical Vocabulary, IEV ref , [8] Arlt, D. et al, Working Group C4.109, Cigré Technical Report 468: Review of Disturbance Emission Assessment Techniques, June 2011, ISBN:
The development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08
The development of the SA grid code on Power Quality emission Dr. Gerhard Botha 2017/08/08 Overview What is the Grid Code? What is Power Quality? Power Quality Management Principles Differences Challenges
More informationSouthern Company Power Quality Policy
Southern Company Power Quality Policy Alabama Power Georgia Power Gulf Power Mississippi Power i Table of Contents: Southern Company Power Quality Policy SCOPE AND PURPOSE... 1 DEFINITIONS... 2 I. HARMONICS...
More informationPower Quality Summary
Power Quality Summary This article provides an overview of how voltage harmonic distortion is managed on the distribution network and focuses on the current at future issues surround the connection of
More informationGRID INTERCONNECTION OF EMBEDDED GENERATION. Part 2: Small-scale embedded generation
ISBN 978-0-626-29938-5 NRS 097-2-3:2014 Edition 1 GRID INTERCONNECTION OF EMBEDDED GENERATION Part 2: Small-scale embedded generation Section 3: Simplified utility connection criteria for low-voltage connected
More informationIntermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV)
Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV) IRR-DCC-MV 1. Introduction 1 IRR-DCC-MV 2. Scope 1 IRR-DCC-MV 2.1. General 1 IRR-DCC-MV 2.2. Affected
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements
Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system
More informationPower Quality Requirements for Connection to the Transmission System
Power Quality Requirements for Connection to the Transmission System Revision: 1.0 Date: September 2015 Introduction and Purpose of this Document The purpose of this document is to provide clarity to Customers
More informationThis document is a preview generated by EVS
TECHNICAL SPECIFICATION IEC TS 62749 Edition 1.0 2015-04 colour inside Assessment of power quality Characteristics of electricity supplied by public networks IEC TS 62749:2015-04(en) THIS PUBLICATION IS
More informationELECTRICITY SUPPLY POWER QUALITY AND RELIABILITY Code of Practice
ICS 29.240:03.120 Zambian Standard ELECTRICITY SUPPLY POWER QUALITY AND RELIABILITY Code of Practice Part 3: Application Guidelines for Enterprises ZAMBIA BUREAU OF STANDARD DATE OF PUBLICATION This Zambian
More informationELECTRICITY ASSOCIATION SERVICES LIMITED 2001
ELECTRICITY ASSOCIATION SERVICES LIMITED 2001 All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical,
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements
Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission
More informationIEEE sion/1547revision_index.html
IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html
More informationRoadmap For Power Quality Standards Development
Roadmap For Power Quality Standards Development IEEE Power Quality Standards Coordinating Committee Authors: David B. Vannoy, P.E., Chair Mark F. McGranghan, Vice Chair S. Mark Halpin, Vice Chair D. Daniel
More informationEnergy Networks Association
The Voice of the Networks Version 1 (ISSUED) Energy Networks Association Insert presentation title here ENA EREC P28 Issue 2 2018 Key Technical Modifications Grid Code and SQSS Mods Name Position Date
More informationDraft Kenya Standard for Balloting Not to be Cited as Kenya Standard
KENYA STANDARD KS 2236-3:2010 ICS 03.120.10; 91.140.50 Electricity Supply Quality of supply Part 3: Voltage characteristics, compatibility levels, limits and assessment methods BALLOT DRAFT, MAY 2010 KEBS
More informationA robust voltage unbalance allocation methodology based on the IEC/TR guidelines
University of Wollongong Research Online Faculty of Engineering - Papers (Archive) Faculty of Engineering and Information Sciences 2009 A robust voltage unbalance allocation methodology based on the IEC/TR
More informationVersion 2.6 October Comments to this document can be forwarded to:
GRID CONNECTION CODE REQUIREMENTS FOR RENEWABLE POWER PLANTS (RPPs) CONNECTED TO THE TRANSMISSION SYSTEM (TS) OR THE DISTRIBUTION SYSTEM (DS) IN SOUTH AFRICA Version 2.6 October 2012 Comments to this document
More informationINTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs
INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES Technical Requirements for Grid-Tied DERs Projects Division 6/29/2017 Contents 1 Definitions and Acronyms... 1 2 Technical Interconnection
More informationHarmonic filter design for IEC compliance
Harmonic filter design for IEC 61000 compliance Marius Jansen ALSTOM Grid Power System Compensation Brisbane, Australia marius.jansen@alstom.com Abstract The paper 1 provides a guideline for the selection
More informationIEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces
IEEE PES Boston Chapter Technical Meeting IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces P1547 Chair David
More informationInsights in the impact of special projects on voltage quality in the HV/EHV networks
Authors: Vladimir Ćuk Konstantinos Tzanakakis Department of Electrical Engineering, Electrical Energy Systems Checked by: prof. J.F.G. (Sjef) Cobben Frans van Erp (Tennet) Date: 05.12.2014. Version: 0.0
More informationExperience in the application of IEC/TR to harmonic allocation in transmission systems
University of Wollongong Research Online Faculty of Engineering and Information Sciences - Papers: Part A Faculty of Engineering and Information Sciences 2006 Experience in the application of IEC/TR 61000-3-6
More informationSTUDY OF THE EFFECTS OF HARMONICS IN THE DESIGN OF TRANSMISSION NETWORK SHUNT COMPENSATORS: NETWORK SIMULATION AND ANALYSIS METHODS
STUDY OF THE EFFECTS OF HARMONICS IN THE DESIGN OF TRANSMISSION NETWORK SHUNT COMPENSATORS: NETWORK SIMULATION AND ANALYSIS METHODS In fulfillment of Master of Science in Electric Power and Energy Systems,
More informationRENEWABLE ENERGY SUB-CODE for Distribution Network connected Variable Renewable Energy Power Plants in Ghana
RENEWABLE ENERGY SUB-CODE for Distribution Network connected Variable Renewable Energy Power Plants in Ghana JANUARY 2015 i Table of Content PART A: 1 1 Introduction 1 1.1 Scope 1 1.2 Status 1 1.3 Terms
More informationHarmonic Planning Levels for Australian Distribution Systems
Abstract Harmonic Planning Levels for Australian Distribution Systems V.J. Gosbell 1, V.W. Smith 1, D. Robinson 1 and W. Miller 2 1 Integral Energy Power Quality Centre, University of Wollongong 2 Standards
More informationINCREASING NETWORK CAPACITY BY OPTIMISING VOLTAGE REGULATION ON MEDIUM AND LOW VOLTAGE FEEDERS
INCREASING NETWORK CAPACITY BY OPTIMISING VOLTAGE REGULATION ON MEDIUM AND LOW VOLTAGE FEEDERS Carter-Brown Clinton Eskom Distribution - South Africa cartercg@eskom.co.za Gaunt CT University of Cape Town
More informationHARMONIC FILTERS Design for IEC compliance
HARMONIC FILTERS Design for IEC 61000 compliance Marius Jansen February 2011 GRID Overview What is a filter Types of harmonic filters What is harmonic compliance Designing for compliance Designing for
More informationON HARMONIC EMISSION ASSESSMENT: A DISCRIMINATIVE APPROACH
Vol.108 (4) December 2017 SOUTH AFRICAN INSTITUTE OF ELECTRICAL ENGINEERS 165 ON HARMONIC EMISSION ASSESSMENT: A DISCRIMINATIVE APPROACH B.B. Peterson*, J. Rens*, M.G. Botha*, J. Desmet** * Faculty of
More informationAssessing network compliance for power quality performance
University of Wollongong Research Online Faculty of Engineering and Information Sciences - Papers: Part A Faculty of Engineering and Information Sciences 214 Assessing network compliance for power quality
More informationVOLTAGE MANAGEMENT BY THE APPORTIONMENT OF TOTAL VOLTAGE DROP IN THE PLANNING AND OPERATION OF COMBINED MEDIUM AND LOW VOLTAGE DISTRIBUTION SYSTEMS
66 SOUTH AFRICAN INSTITUTE OF ELECTRICAL ENGINEERS Vol.97(1) March 2006 VOLTAGE MANAGEMENT BY THE APPORTIONMENT OF TOTAL VOLTAGE DROP IN THE PLANNING AND OPERATION OF COMBINED MEDIUM AND LOW VOLTAGE DISTRIBUTION
More informationRationalized User Specification
ICS 91.140.50 NRS 048-4:1999 Edition 1.1 ISBN 0-626-15418-9 (First edition: Incorporating Amendment No. 1:1999) Rationalized User Specification ELECTRICITY SUPPLY QUALITY OF SUPPLY Part 4: Application
More informationFault Ride Through Technical Assessment Report Template
Fault Ride Through Technical Assessment Report Template Notes: 1. This template is intended to provide guidelines into the minimum content and scope of the technical studies required to demonstrate compliance
More informationDP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation
DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Single Phase
More informationCompany Directive STANDARD TECHNIQUE: SD1E/2. Technical Requirements for Customer Export Limiting Schemes
Company Directive STANDARD TECHNIQUE: SD1E/2 Technical Requirements for Customer Export Limiting Schemes Policy Summary This Standard Technique specifies the requirements for customer owned Export Limitation
More informationGRID CONNECTION CODE FOR RENEWABLE POWER PLANTS
GRID CONNECTION CODE FOR RENEWABLE POWER PLANTS (RPPs) CONNECTED TO THE ELECTRICITY TRANSMISSION SYSTEM (TS) OR THE DISTRIBUTION SYSTEM (DS) IN SOUTH AFRICA Version 2.9 (July 2016) This document is approved
More informationDraft Kenya Standard for Balloting Not to be Cited as Kenya Standard
KENYA STANDARD KS 2236-4:2010 ICS 91.140.50 Electricity Supply Quality of supply Part 4: Application guidelines for utilities BALLOT DRAFT, MAY 2010 KEBS 2010 First Edition 2010 TECHNICAL COMMITTEE REPRESENTATION
More informationCompliance activities
DOCUMENTLOCATIE SO-SOC 13-141 PAGINA 1 van 28 Compliance activities Compliance activities in relation to Connection Requirements Wind Farms System Operations - Version V3.0 January 2014 - PAGINA 2 van
More informationTHE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES
THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES C.E.T. Foote*, G.W. Ault*, J.R. McDonald*, A.J. Beddoes *University of Strathclyde, UK EA Technology Limited, UK c.foote@eee.strath.ac.uk
More informationPower quality report. A Manufacturing Plant
Power quality report Prepared for A Manufacturing Plant 6 May 2016 by Dr Angelo De Francesco Power Quality Consultant Page 1 Contents 1 EXECUTIVE SUMMARY... 4 2 INTRODUCTION... 5 2.1 SITE MONITORED...
More informationPOWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:
POWER CORPORATION Power Quality Specifications and Guidelines for Customers Phone: 403-514-3700 Fax: 403-514-3719 1 GENERAL OVERVIEW........................................ 1.1 WHAT DOES THIS SPECIFICATION
More informationWind Power Facility Technical Requirements CHANGE HISTORY
CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical
More informationTarget Mchunu and Themba Khoza Eskom Transmission Division, System Operator Grid Code Management
GRID CONNECTION CODE FOR RENEWABLE POWER PLANTS (RPPs) CONNECTED TO THE ELECTRICITY TRANSMISSION SYSTEM (TS) OR THE DISTRIBUTION SYSTEM (DS) IN SOUTH AFRICA Target Mchunu and Themba Khoza Eskom Transmission
More informationMr Hans Hoogervorst International Accounting Standards Board 1 st Floor 30 Cannon Street London EC4M 6XH. MV/288 Mark Vaessen.
Tel +44 (0)20 7694 8871 15 Canada Square mark.vaessen@kpmgifrg.com London E14 5GL United Kingdom Mr Hans Hoogervorst International Accounting Standards Board 1 st Floor 30 Cannon Street London EC4M 6XH
More informationLIMITS FOR TEMPORARY OVERVOLTAGES IN ENGLAND AND WALES NETWORK
LIMITS FOR TEMPORARY OEROLTAGES IN ENGLAND AND WALES NETWORK This document is for internal and contract specific use only. Disclaimer NGG and NGET or their agents, servants or contractors do not accept
More informationTable of Contents. Introduction... 1
Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...
More informationMETHOD TO DETERMINE CONTRIBUTION OF THE CUSTOMER AND THE POWER SYSTEM TO THE HARMONIC DISTURBANCE
C I R E D 17 th International Conference on Electricity Distribution Barcelona, 1-15 May 3 METHOD TO DETERMINE CONTRIBUTION OF THE CUSTOMER AND THE POWER SYSTEM TO THE HARMONIC DISTURBANCE Olivier GONBEAU
More informationTechnical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks
2014 Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks This document specifies the technical requirement for connecting sspv to the low voltage distribution
More informationAspects of Network Harmonic Impedance Modelling in High Voltage Distribution Networks
Aspects of Network Harmonic Impedance Modelling in High Voltage Distribution Networks Diptargha Chakravorty Indian Institute of Technology Delhi (CES) New Delhi, India diptarghachakravorty@gmail.com Jan
More informationVAR Voltage and Reactive Control
VAR-001-4 Voltage and Reactive Control A. Introduction 1. Title: Voltage and Reactive Control 2. Number: VAR-001-4 3. Purpose: To ensure that voltage levels, reactive flows, and reactive resources are
More informationA. Introduction. VAR Voltage and Reactive Control
A. Introduction 1. Title: Voltage and Reactive Control 2. Number: VAR-001-4.2 3. Purpose: To ensure that voltage levels, reactive flows, and reactive resources are monitored, controlled, and maintained
More informationVAR Voltage and Reactive Control. A. Introduction
VAR-001-5 Voltage and Reactive Control A. Introduction 1. Title: Voltage and Reactive Control 2. Number: VAR-001-5 3. Purpose: To ensure that voltage levels, reactive flows, and reactive resources are
More informationHarmonic Distortion Evaluations
Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion
More informationWFPS1 WIND FARM POWER STATION GRID CODE PROVISIONS
WFPS1 WIND FARM POWER STATION GRID CODE PROVISIONS WFPS1.1 INTRODUCTION 2 WFPS1.2 OBJECTIVE 2 WFPS1.3 SCOPE 3 WFPS1.4 FAULT RIDE THROUGH REQUIREMENTS 4 WFPS1.5 FREQUENCY REQUIREMENTS 5 WFPS1.6 VOLTAGE
More informationCLEAN DEVELOPMENT MECHANISM CDM-MP58-A20
CLEAN DEVELOPMENT MECHANISM CDM-MP58-A20 Information note on proposed draft guidelines for determination of baseline and additionality thresholds for standardized baselines using the performancepenetration
More informationMax voltage in 400 kv Networks
Max voltage in 400 kv Networks ENTSO-E GC ESC, 08, Brussels 1 Summary NEED TO WITHSTAND WIDE VOLTAGE RANGE 3 EXISTING CONNECTION RULES 4 KEMA REPORT ON RFG 5 STUDIES ABOUT TOV 6 REFERENCE TO EU NC REGULATIONS
More informationHarmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions
Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions Fernando Bastião and Humberto Jorge Department of Electrical Engineering and Computers
More informationWhat does the revision of the OECD Privacy Guidelines mean for businesses?
m lex A B E X T R A What does the revision of the OECD Privacy Guidelines mean for businesses? The Organization for Economic Cooperation and Development ( OECD ) has long recognized the importance of privacy
More informationAustralian/New Zealand Standard
AS/NZS CISPR 11:2011 IEC CISPR 11, Ed. 5.1 (2010) AS/NZS CISPR 11:2011 Australian/New Zealand Standard Industrial, scientific and medical equipment Radio-frequency disturbance characteristics Limits and
More informationGrid Converters for Photovoltaic
Grid Converters for Photovoltaic and Wind Power Systems by R. Teodorescu, M. Liserre and P. Rodriguez ISBN: 978 0 470 05751 3 Copyright Wiley 2011 Chapter 3 Grid Requirements for PV Grid connection requirements
More informationSOUTH AFRICAN NATIONAL STANDARD
ISBN 978-0-626-30950-3 SOUTH AFRICAN NATIONAL STANDARD Electromagnetic compatibility (EMC) Part 4-30: Testing and measurement techniques Power quality measurement methods This national standard is the
More informationPOWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC
CITY OF LETHBRIDGE ELECTRIC ENGINEERING STANDARDS POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS The City of Lethbridge acknowledges the use of other utility industry and industry committee
More informationNETS SQSS Modification Proposal
NETS SQSS Modification Proposal Operational and Planning Criteria for 220kV Transmission Assets Panel Paper by Bless Kuri, SHE Transmission For presentation to the SQSS Panel Meeting on 1 st April 2015
More informationPower Quality in High Density Residential Distribution Grids
Power Quality in High Density Residential Distribution Grids Gustav R. Krüger, Raj M. Naidoo Abstract Research in the field of power quality challenges in distribution grids is gaining a strong foothold.
More informationTHE USE OF A SAFETY CASE APPROACH TO SUPPORT DECISION MAKING IN DESIGN
THE USE OF A SAFETY CASE APPROACH TO SUPPORT DECISION MAKING IN DESIGN W.A.T. Alder and J. Perkins Binnie Black and Veatch, Redhill, UK In many of the high hazard industries the safety case and safety
More informationMEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN
MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN Eugenio PEREA*, Eduardo ZABALA*, J. Emilio RODRÍGUEZ*, Asier GIL DE MURO*, Hugo GAGO * * * Fundación LABEIN,
More informationBED INTERCONNECTION TECHNICAL REQUIREMENTS
BED INTERCONNECTION TECHNICAL REQUIREMENTS By Enis Šehović, P.E. 2/11/2016 Revised 5/19/2016 A. TABLE OF CONTENTS B. Interconnection Processes... 2 1. Vermont Public Service Board (PSB) Rule 5.500... 2
More informationUse only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at
Reviewed: Sergey Kryuchkov Distribution Engineering Scott Merriman Distribution Standards Valentina Dabic Distribution Planning Warren Quan Distribution Operations, FVO Raj Solanki Distribution Engineering
More informationPower Quality Report. A Manufacturing Plant
Power Quality Report Prepared for A Manufacturing Plant 6 May 2016 by Dr Angelo De Francesco Power Quality Consultant CHK Power Quality Pty Ltd Page 1 Contents 1 EXECUTIVE SUMMARY... 4 2 INTRODUCTION...
More informationVoltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment
s Evaluating Methods, Power Quality and s Assessment regarding Voltage Dip Immunity of Equipment ANTON BELÁŇ, MARTIN LIŠKA, BORIS CINTULA, ŽANETA ELESCHOVÁ Institute of Power and Applied Electrical Engineering
More informationVAR Generator Operation for Maintaining Network Voltage Schedules
A. Introduction 1. Title: Generator Operation for Maintaining Network Voltage Schedules 2. Number: VAR-002-4 3. Purpose: To ensure generators provide reactive support and voltage control, within generating
More informationAustralian Standard. Electricity metering equipment (AC) Particular requirements. Part 22: Static meters for active energy (classes 0.2 S and 0.
AS 62053.22 2005 IEC 62053-22, Ed.1.0 (2003) AS 62053.22 2005 Australian Standard Electricity metering equipment (AC) Particular requirements Part 22: Static meters for active energy (classes 0.2 S and
More information8th Floor, 125 London Wall, London EC2Y 5AS Tel: +44 (0) Fax: +44 (0)
Ms Kristy Robinson Technical Principal IFRS Foundation 30 Cannon Street London EC4M 6XH 27 January 2016 Dear Kristy This letter sets out the comments of the UK Financial Reporting Council (FRC) on the
More informationIEEE sion/1547revision_index.html
IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html
More informationAS/NZS IEC :2013
AS/NZS IEC 61000.4.6:2013 IEC 61000-4-6, Ed. 3.0 2008, IDT Australian/New Zealand Standard Electromagnetic compatibility (EMC) Part 4.6: Testing and measurement techniques Immunity to conducted disturbances,
More informationTechnical Brief: Flow Direction of Harmonics and High- order Harmonics
Technical Brief: Harmonics Harmonics are generated by semi- conductor controlled devices in the power supply of equipment as a result of distorted voltage and current waveforms. When the harmonic component
More informationIMPLICATIONS OF APPLYING DIFFERENT VAR SUPPORT TECHNOLOGIES IN THE ESKOM TRANSMISSION NETWORK WITH PARTICULAR EMPHASIS ON THE LIFECYCLE COST
IMPLICATIONS OF APPLYING DIFFERENT VAR SUPPORT TECHNOLOGIES IN THE ESKOM TRANSMISSION NETWORK WITH PARTICULAR EMPHASIS ON THE LIFECYCLE COST Teboho Ken Ramorapeli A research report submitted to the Faculty
More informationCity of Ekurhuleni power quality monitoring system
City of Ekurhuleni power quality monitoring system by Stephen Delport City of Ekurhuleni In a visionary step, the general manager: electricity and energy, Mark Wilson, recommended to the mayoral committee
More informationGRID CONNECTION CODE FOR RENEWABLE POWER PLANTS (RPPs)
GRID CONNECTION CODE FOR RENEWABLE POWER PLANTS (RPPs) 1.0 GRID CONNECTION CODE BASIS 1.1 LEGISLATION 1.1.1 The legal basis for this RPP Code (RPP Code) is specified in terms of the [Electricity] Act 2016
More informationESB National Grid Transmission Planning Criteria
ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and
More informationCharacteristics of power quality disturbances in Australia: voltage harmonics
University of Wollongong Research Online Faculty of Engineering and Information Sciences - Papers: Part A Faculty of Engineering and Information Sciences 2013 Characteristics of power quality disturbances
More informationSouth African Distribution Code
South African Distribution Code Metering Code Version 6.0 July 2014 This document is approved by the National Energy Regulator of South Africa (NERSA) Issued by: RSA Grid Code Secretariat Contact: Mr.
More informationPOWER QUALITY REPORT
Power Quality Research Lab., I-7, Wyb. Wyspiaoskiego 27, 50-370 Wrocław, Poland phone +48713202626, fax +48713202006, email: zbigniew.leonowicz@pwr.wroc.pl Facility: XXX POWER QUALITY REPORT Start Monitoring:
More informationIntimate Communications Hub Interface Specification Report to Secretary of State
Intimate Communications Hub Interface Specification Report to Secretary of State DCC V1.0 28/02/14 Page 1 of 14 Executive Summary 1. DCC is required in accordance with the terms of its Licence to produce,
More informationEmission Limits for Customer Facilities Connected to the Hydro-Québec Transmission System
Emission Limits for Customer Facilities Connected to the Hydro-Québec Transmission System Études de réseaux Direction Planification des actifs Hydro-Québec TransÉnergie Original in French dated December
More informationHPC-9DJ
Manual: Distribution Design Manual Volume 1 Quality of Electricity Supply Standard Number: HPC-5DC-07-0001-2012 Document Control Author Name: Anthony Seneviratne Position: Senior Standards Engineer Document
More informationGeneration and Load Interconnection Standard
Generation and Load Interconnection Standard Rev. 0A DRAFT Name Signature Date Prepared: Approved: VP Acceptance APEGGA Permit to Practice P-08200 TABLE OF CONTENTS 1.0 INTRODUCTION...5 1.1 Purpose...5
More informationECE 528 Understanding Power Quality
ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 19 1 Today Flicker Power quality and reliability benchmarking
More informationAustralian/New Zealand Standard
AS/NZS 61000.6.3:2012 IEC 61000-6-3, Ed.2.1 (2011) AS/NZS 61000.6.3:2012 Australian/New Zealand Standard Electromagnetic compatibility (EMC) Part 6.3: Generic standards Emission standard for residential,
More informationImpact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation
Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation R. S. Al Abri, M. H. Albadi, M. H. Al Abri, U. K. Al Rasbi, M. H. Al Hasni, S. M. Al Shidi Abstract This paper presents an analysis
More informationTS RES - OUTSTANDING ISSUES
TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next
More informationUNIT-4 POWER QUALITY MONITORING
UNIT-4 POWER QUALITY MONITORING Terms and Definitions Spectrum analyzer Swept heterodyne technique FFT (or) digital technique tracking generator harmonic analyzer An instrument used for the analysis and
More informationVAR Generator Operation for Maintaining Network Voltage Schedules
A. Introduction 1. Title: Generator Operation for Maintaining Network Voltage Schedules 2. Number: VAR-002-3 3. Purpose: To ensure generators provide reactive support and voltage control, within generating
More informationStandard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction. See the Implementation Plan for PRC
A. Introduction 1. Title: Generator Frequency and Voltage Protective Relay Settings 2. Number: PRC-024-2 3. Purpose: Ensure Generator Owners set their generator protective relays such that generating units
More informationP.O (November 2009) This is an unofficial translation of the latest draft of the Spanish grid code. Source: Jason MacDowell, GE Energy
INSTALLATIONS CONNECTED TO A POWER TRANSMISSION SYSTEM AND GENERATING EQUIPMENT: MINIMUM DESIGN REQUIREMENTS, EQUIPMENT, OPERATIONS, COMMISSIONING AND SAFETY. P.O. 12.2 (November 2009) This is an unofficial
More informationThis document is a preview generated by EVS
IEC 61000-4-10 Edition 2.0 2016-07 REDLINE VERSION colour inside BASIC EMC PUBLICATION Electromagnetic compatibility (EMC) Part 4-10: Testing and measurement techniques Damped oscillatory magnetic field
More informationLOVAG GENERAL INSTRUCTION G2 MEASUREMENT UNCERTAINTY. This instruction of a general nature and does not relate to specific standards.
LTI-G2 LOVAG GENERAL INSTRUCTION G2 MEASUREMENT UNCERTAINTY This instruction of a general nature and does not relate to specific standards. It provides additional information ensuring a suitable degree
More informationGeneration and Load Interconnection Standard
Generation and Load Interconnection Standard Rev. 0 DRAFT Name Signature Date Prepared: Approved: VP Acceptance APEGGA Permit to Practice P-08200 TABLE OF CONTENTS 1.0 INTRODUCTION...5 1.1 Purpose...5
More informationPQ Monitoring Standards
Characterization of Power Quality Events Charles Perry, EPRI Chair, Task Force for PQ Characterization E. R. Randy Collins, Clemson University Chair, Working Group for Monitoring Electric Power Quality
More informationTasmanian Networks Pty Ltd Guideline. Technical Requirements for the Connection of Embedded Generation
Tasmanian Networks Pty Ltd Guideline Technical Requirements for the Connection of Embedded Generation Revision 08 November 2017 Disclaimer This document has been prepared for the purposes of informing
More informationPOWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009
POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power
More information