Electric Power Quality Monitoring and Analysis at a Tri-generation Plant under Development

Size: px
Start display at page:

Download "Electric Power Quality Monitoring and Analysis at a Tri-generation Plant under Development"

Transcription

1 Electric Power Quality Monitoring and Analysis at a Tri-generation Plant under Development IOANA PISICĂ, LAURENŢIU CONSTANTIN LIPAN, PETRU POSTOLACHE, CORNEL TOADER Department of Power Systems University Politehnica of Bucharest Splaiul Independentei 1 ROMANIA ioanapisica@gmail.com GHEORGHE COMĂNESCU Department of Electric Power Generation and Use University Politehnica of Bucharest Splaiul Independentei 1 ROMANIA gheorghe.comanescu@gmail.com DAN CONSTANTIN DAŞU OMV Petrom SA ROMANIA dan_dasu@yahoo.com Abstract: - The aim of the study presented within this paper is the monitoring and analysis of electric power quality supplied to a tri-generation plant. The measurements were made before commissioning the plant, while investment work was still in progress. The main objective of the study was to certify that the voltage values are kept within the limits imposed by contract between the user and the supplier. In order to accomplish this objective, the electrical power supplied at the location of interest was monitored at two measurement points, one in the 10 kv grid, at the interface with the supply network and one in the 20 kv substation owned by the beneficiary. The analysis was based on a complete set of parameters that were monitored alongside voltage values: power factors, harmonics, flicker, voltage and current unbalances and others. Key-Words: - power quality, voltage measurement, power system harmonics, power system monitoring 1 Introduction The site is supplied from a 10 kv substation through two underground power lines. Another substation, owned by the beneficiary, is connected to the 10 kv substation through a short underground power line. This substation has only two bays: one dedicated to the connection with the supplier substation and one equipped with a 10/20 kv transformer. Both substations are placed at the same location. The transformer supplies the 20kV substation owned by the beneficiary and has the following characteristics: Rated power 2500 kva; Turns ratio 20 kv şi ± 2,5 %/ V; Connexion type Yyn0; Short circuit voltage 7 %. The supplier electricity billing meter is located on the connection between the two substations. The following measurement points were established, where class A power quality monitoring devices were installed: - one measurement point at 10 kv in the secondary winding of the potential transformer (turn ratio V) connected to the bus bar from beneficiaryowned substation and in the secondary winding of the current transformer (turn ratio 75/5 A) from the 10/20 kv transformer; - one measurement point in the secondary winding of the potential transformer (turn ratio V) from the bus bar of the 20 kv beneficiary-owned substation and in the secondary winding of the current transformer (turn ratio 150/1 A) from the 20 kv side of the 10/20 kv ISSN: / ISSN: ISBN:

2 transformer. For space reasons, only data collected from the first measurement point (10 kv) are presented in this paper. 2 Measured Data Analysis Power quality has been a puzzling problem over the last years, mainly due to the use of power electronics, but also because of sensitive equipment that is being used. Power quality distortion phenomena can be subdivided into the following categories [1]: - harmonic distortion - transients - voltage dips - voltage swells - flicker - voltage asymmetry (unbalance) - frequency variations. 2.1 Analysis of voltage values Voltage values measured throughout a working day are presented in Fig. 1, in order to check whether voltage limits are violated. Fig.1. Daily variation of line voltage values The chart in Fig. 1 shows that two of the line voltages are quasi-equal, while the third is always lower than the others. Therefore, a voltage unbalance can be observed. A full analysis for the 9 days of measurements reveals a maximum difference between the phase voltage values of 61 V and of 10 V between the highest and lowest line voltage values. These differences are lower than 1% of the rated voltage. The first conclusion is that the voltage unbalance between the three phases is placed within acceptable limits. In order to check the extent to which the voltage values are kept within admissible limits set by contract, the chart in Fig. 2 presents the variation of the line voltage with the highest values. The variation is expressed in percents of rated voltage (10000 V). Fig.2. Daily voltage variation, Uca [%] The chart shows that line voltages (for the sample day) do not exceed 106% from the rated voltage, and therefore the voltage values are limited within the admissible strip of U n ± 10 %. A full analysis based on data recorded for 9 days reveals the following minimum and maximum values: o For phase voltages - minimum value: 576,58 V, respectively 99,71 % of V n ; - maximum value: 618,18 V, respectively 106, % of V n ; o For line voltages - minimum value 9957,40 V, respectively 99,57 % of U n ; - maximum value: 1069,4 V, respectively 106,9 % of U n. The second conclusion that can be drawn is that the supplied voltages during the entire time frame of measurements are maintained within 99.5% and +107% of the rated voltage. These values define a strip between -0.5% and +7%. A graphical representation of all line voltages for the full time frame of measurements would become unreadable. In order to obtain a chart easy to follow, only the variation of voltage Uca is presented in figure, for the full monitored period, with 1296 sets of measurements. Fig.. Variation of line voltage Uca ISSN: / ISSN: ISBN:

3 Fig. highlights the daily voltage peaks, which are observed during night hours (between 2 and 4 AM) and the minimum voltage values, recorded during evening hours (19-21). The currents on the three phases have similar values, showing a small current unbalance. The currents on each phase are presented in figure 8, for the full monitored time frame. 2.2 Anlysis of other collected data The equipment used for power quality monitoring during this study also records: currents on each phase, active, reactive and apparent power, power factor for each phase, total current harmonic distortion factor (THD-I), total voltage harmonic distortion factor (THD- U), current and voltage harmonics, flicker and unbalances [2-5]. Taking into consideration the large amount of measured and computed values, some conclusions regarding the supplied power quality are presented in the following. The first analysis concerns the powers absorbed by the beneficiary equipment at the measurement point.. Figures 4 through 7 present, respectively, the variations of apparent powers on each phase, total active, reactive and apparent powers and active (P) and reactive (Q) powers on each phase, during the full monitored period. Fig. 6. Active powers P [kw] variations on each phase. Fig. 7. Variation of reactive powers Q [kvar] on each phase. Fig. 4. Apparent powers on each phase. Fig. 8. Variation of currents at 10 kv busbar. Fig. 9 presents the variation of currents during a working day. Fig. 5. Total active, reactive and apparent powers. During the period of study, the energy consumption is low, and therefore the reactive power values are low. Most of the time, the reactive powers are injected into the supplier network, suggesting the characteristics of a capacitive load. Fig. 9. Variation of currents during a working day ISSN: / ISSN: ISBN:

4 Data presented in figures 10 and 11 reveal low flicker levels, within acceptable limits imposed by norms. Higher voltage variations can be observed on phase b, alongside higher flicker levels. Pst and Plt curves at the point of measurement have similar trends. Busbar voltages are quasi-sinusoidal, having a total harmonic distortion factor lower than the maximum acceptable limit (THD acc = 6%). The total harmonic distortion factor was during measurements between 1,5 and.7% ( Fig. 12). generated by connecting loads that produce distortions, like power electronics. The average values are limited to 0-40%, which represent also high values. Fig. 1.Current total harmonic distortion factor (THD I). Fig.10 Short-term flicker levels (Pst). a. Fig. 11. Long-term flicker levels (Plt). b. Fig. 14. Current harmonic spectra for the three phases. c. Fig. 12. Voltage total harmonic distortion factor measured on phases a, b, c. The current total harmonic distortion factor (THD I) is presented in Fig. 1, showing high values that highlight the existence of important current harmonic components. The current harmonic spectra for the three phases are presented in Fig. 14,a,b,c. Harmonic components of order 5 and 7 reach up to 70-80%. These high values can be High values of harmonics of order 5 and 7 and therefore high values of total harmonic distortion factor (THD-I) indicate the existence of distorting loads. The beneficiary should consider installing filters for current waveforms at the connection point when the consumption levels increase. The power factor variation for each phase during the measurements time frame, when the monitoring device was in service, is presented in Fig. 15. As it can be ISSN: / ISSN: ISBN:

5 observed, the chart highlights reactive power flows from the installations at the beneficiary location towards the supplier network. In general, the power factor has values close to 1. Fig. 15. Power factor variation for phases a, b and c. Fig. 16 shows the variation of the voltage unbalance factor. It can be observed that the negative unbalance factor: U k s (1) U where U is the negative sequence voltage, and U + is the positive sequence voltage, has values lower than the maximum admissible negative unbalance factor (<2%). The variation of current unbalances is presented in Fig 17. The negative unbalance factor was computed by using (2): I I k s (2) where I is the negative sequence current component, and I + positive sequence current component. Conclusion.1 Regarding voltage levels During the entire monitoring time, the voltages supplied at the 10 kv busbar were maintained within the limits 99.5 % 107 % of rated voltage. This leads to a voltage strip of -0.5% - +7%. The supplied voltage levels supplied were therefore conforming to the values stipulated by contract. The voltage variations at the 20 kv busbar are shifted up with almost one percent, meaning that the voltage strip was between 100% and 109%. This is most probably due to reactive power generated by underground cables while the active energy consumption was low, as the site was under construction. As all loads of the beneficiary at the point of interest are connected to the 20 kv bus bar, it would be advisable to change the plot of the 10/20 kv transformer to -2.5%, for the moment..2 Regarding voltage unbalances Two types of voltage unbalances were studies. First, a difference between the lowest and the highest voltage values were computed and resulted into values lower than 1% for both line and phase voltages. These values were determined for the 10 kv and the 20 kv bus bars. Secondly, the unbalance was computed by the monitoring device, based on negative and positive sequence components. The resulted values are between 1.% and 1.5%. The conclusion is that the operating state is normal and no further action is required. Fig. 16. Negative voltage unbalance factor (k s ).. Regarding the voltage waveform The analysis of voltage harmonic components led to similar results in both cases (10kV and 20 kv). The total harmonic distortion factor for voltage, THD-U, was found have values placed between 1.5% and.5 %, below the admissible value of 6%. From this point of view, we can conclude that the power quality is satisfactory..4 Regarding the flicker level Flicker levels are a measure of fast voltage fluctuations that can produce harmful effects upon devices, especially artificial lighting. Data analysis of recorded values for the two measurement points shows low flicker levels, of around 0.%- 0.5 %. The monitored values are below the admissible level, of 0.9%. The power quality is therefore satisfactory from this point of view. Fig. 17. Negative current unbalance factor (k s ). ISSN: / ISSN: ISBN:

6 .5 Regarding currents Currents on the three phases were monitored at both points of measurement. The measured current values are low (14-18 A) at 10 kv and half of these at 20 kv. However, this is irrelevant, as it is only the load at this stage. The computed power quality indicator was the unbalance, showing whether the phases are equally loaded or not. The unbalance factor, computed as a fraction between the negative and positive sequence components, resulted in values between % and 9%, values larger than the ones for voltages. These values are high, but a perfect balancing of the currents requires a perfect distribution of load over the phases, which is impossible to obtain in practice. Furthermore, the installations are already put in place and it would be very hard to re-arrange them. The most important aspect regarding currents is the total harmonic distortion factor, which reaches frequently values up to 60%-70%. In other words, the current waveform is very distorted. The harmonic components of highest values have the orders 5 and 7. This problem should be solved sooner or later, as it leads to unwanted effects in the network. A solution at first glance would be to install a harmonic filter at the 20 kv substation. It is possible for the supplier to bill the distortions injected into the network..6 Regarding powers A first important aspect concerns the reactive power. In comparison with the active power, the values of reactive powers are low. This leads to a power factor near to the value of 1, which is desirable. On the other hand, there is a frequent excess of reactive power at the 20 kv substation that is injected into the supplier network. This is the cause for higher voltage levels at the 20 kv substation, but also at the 10 kv one. A detailed analysis for implementing a reactive power management system including harmonic filters for 5 and 7 th order harmonics should be undertaken only after starting the operation at full capacity. It is possible that the problem will be resolved by self when all consumers and generators will be in service. References: [1] Baggini, Angelo: Handbook of power quality. West Sussex, John Wiley and Sons, 2008 [2]Stanescu, Carmen, Vatra, F., Poida, Ana, Postolache P., Power quality in romanian electricity market, 9th International Conference on Electric Power Quality and Utilisation, EPQU-2007, Barcelona, oct []Chicco G., Postolache P., Toader C., Analysis of Three-Phase Systems With Neutral Under Distorted and Unbalanced Conditions in the Symmetrical Component-Based Framework, IEEE Transactions on Power Delivery, Volume 22, Issue 1, Jan. 2007, pag [4] Spain K. Strunz. Developing Benchmark Models for Studying the Integration of Distributed Energy Resources. Power Engineering Society General Meeting, June [5] IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems. Biographies Ioana Pisică. Born in Bucharest (Romania), on March 5 th, Graduated from University Politehnica of Bucharest, Faculty of Power Engineering in She has begun her final year of Ph.D studies in Electrical Power Engineering. Present position: Teaching assistant in Electrical Engineering Politehnica University of Bucharest, Department of Electric Power Systems. Fields of activity include: Teaching (and research) Electrical Networks, Numerical Methods, Artificial Intelligence Techniques, Electronic Devices and SCADA systems in Power Engineering. Laurenţiu Constantin Lipan. Born in Hunedoara (Romania), on June 28, Graduated from the Politehnica University of Bucharest, Power Engineering Faculty in Ph.D in Electrical Power Field in Present position: Lecturer in Electrical Engineering Politehnica University of Bucharest, Department of Electric Power Systems. Fields of activity include: Teaching (and research) the Electricity Use in Industry, Management of Electricity, Energy Efficiency, Large Industrial Consumers Supply, Modern Electrical Technologies. He is currently carrying out Post-Doctoral research studies, and his contributions to this paper were financially supported by the POSDRU contract POSDRU/89/1.5/S/ Dan Constantin Daşu. Born on March 29, He graduated from University of Petrol and Gas, Ploiesti, specialization Automation and Industrial Informatics and is pursuing his Master degree in Advanced Automation. He is currently with OMV Petrom as head of operators department at the trigeneration site Petrom City, Bucharest. Gheorghe Comănescu. Born in Novaci (Romania), on June 9, Graduated from the Politehnica University of Bucharest, Power Engineering Faculty in Ph.D in Electrical Power Field in Present position: Professor in Electrical Engineering Politehnica University of Bucharest, Department of Energy Generation and Use. Didactic activities on Electrical Part of Power Plants and Electrical Substations. Research activities on Design, Operation and Economical Optimization of Electricity Distribution Networks and Electrical Switchgear for Power Plants and Substations. Petru Postolache. Born June 28, 1940 in Chisinau. Graduated from University Politehnica of Bucharest in 1966 and obtained his Ph.D in Member of IEEE, CIRED, ASRO, IRE, SIER and other scientific organizations. Current position: Professor in Electrical Engineering University Politehnica of Bucharest, Department of Electric Power Systems. His fields of interest include: Power Quality, Sustainable Development, Renewable Energy Sources, Energy Efficiency. Cornel Toader. Born July 17, Graduated from University Politehnica of Bucharest in Ph.D in Electrical Power Systems in Member of IEEE, ASRO, IRE, SIER and other scientific organizations. Current position: Professor in Electrical Engineering University Politehnica of Bucharest, Department of Electric Power Systems. His fields of interest include: Power Quality, Energy Efficiency, Energy Audits, Energy Management. ISSN: / ISSN: ISBN:

Modern Techniques for Power Quality Analysis Using LabVIEW Environment

Modern Techniques for Power Quality Analysis Using LabVIEW Environment International Journal of Energy Engineering 2017, 7(3): 79-89 DOI: 10.5923/j.ijee.20170703.03 Modern Techniques for Power Quality Analysis Using LabVIEW Environment Claudiu-Ionel Nicola *, Marcel Nicola,

More information

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de

More information

UNBALANCED CURRENT BASED TARRIF

UNBALANCED CURRENT BASED TARRIF UNBALANCED CURRENT BASED TARRIF Hossein ARGHAVANI Tehran Electricity Distribution (TBTB) Co.-Iran hosein.argavani@gmail.com ABSTRACT The voltage &current unbalance are serious power quality problems with

More information

ELECTROMAGNETIC POLLUTION PRODUCED BY THE INDUSTRIAL FREQUENCY CRUCIBLE INDUCTION FURNACES IN THE POWER SUPPLY NETWORK

ELECTROMAGNETIC POLLUTION PRODUCED BY THE INDUSTRIAL FREQUENCY CRUCIBLE INDUCTION FURNACES IN THE POWER SUPPLY NETWORK 1 2 ELECTROMAGNETIC POLLUTION PRODUCED BY THE INDUSTRIAL FREQUENCY CRUCIBLE INDUCTION FURNACES IN THE POWER SUPPLY NETWORK Angela IAGĂR 1, Ioan ŞORA 2, Caius PĂNOIU 1, Cristian ABRUDEAN 1 1 POLITEHNICA

More information

UNIT-4 POWER QUALITY MONITORING

UNIT-4 POWER QUALITY MONITORING UNIT-4 POWER QUALITY MONITORING Terms and Definitions Spectrum analyzer Swept heterodyne technique FFT (or) digital technique tracking generator harmonic analyzer An instrument used for the analysis and

More information

Sizing the neutral wire cross-section and minimization of neutral currents using microgeneration in low voltage networks

Sizing the neutral wire cross-section and minimization of neutral currents using microgeneration in low voltage networks Sizing the neutral wire cross-section and minimization of neutral currents using microgeneration in low voltage networks André Braga Instituto Superior Técnico Av. Rovisco Pais, 1049-001 Lisbon, Portugal

More information

Power Quality Survey in a Distribution System, Standard Procedures and Limitations. H. Mokhtari S. Hasani and M. Masoudi

Power Quality Survey in a Distribution System, Standard Procedures and Limitations. H. Mokhtari S. Hasani and M. Masoudi THD Voltage Ubc Power Quality Survey in a Distribution System, Standard Procedures and Limitations H. Mokhtari S. Hasani and M. Masoudi Associate Professor Department of Electrical Engineering Sharif University

More information

Power Quality Control on The Romanian Energy Market

Power Quality Control on The Romanian Energy Market Power Quality Control on The Romanian Energy Market A. S.JUDE 1, P. EHEGARDNER 2, P. ANDEA 3, D. VATAU 4, F.M. FRIGURA-ILIASA 5 Power Systems Department POLITEHNICA University of Timisoara, Faculty of

More information

A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards

A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards Indian Journal of Science and Technology, Vol 9(30), DOI: 10.17485/ijst/2016/v9i30/99034, August 2016 ISSN (Print) : 0974-6846 ISSN (Online) : 0974-5645 A Power Quality Survey on a 22 kv Electrical Distribution

More information

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant CASE STUDY Implementation of Ford Motor Company SA Silverton Plant 1 SCENARIO Ford Motor Company is a global automotive and mobility company based in Dearborn, Michigan. Ford Motor Company of Southern

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment s Evaluating Methods, Power Quality and s Assessment regarding Voltage Dip Immunity of Equipment ANTON BELÁŇ, MARTIN LIŠKA, BORIS CINTULA, ŽANETA ELESCHOVÁ Institute of Power and Applied Electrical Engineering

More information

Power factor improvement in three-phase networks with unbalanced inductive loads using the Roederstein ESTAmat RPR power factor controller

Power factor improvement in three-phase networks with unbalanced inductive loads using the Roederstein ESTAmat RPR power factor controller IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Power factor improvement in three-phase networks with unbalanced inductive loads using the Roederstein ESTAmat RPR power factor

More information

Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces. H.A. Khalik, M. A. Aziz, and E. Farouk.

Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces. H.A. Khalik, M. A. Aziz, and E. Farouk. , 2011;4(12) Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces H.A. Khalik, M. A. Aziz, and E. Farouk. Electrical power and Machines Engineering

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS George Adam, Alina G. Stan (Baciu) and Gheorghe Livinţ Department of Electrical Engineering Technical University of Iaşi 700050, Iaşi, Romania E-mail:

More information

POWER QUALITY REPORT

POWER QUALITY REPORT Power Quality Research Lab., I-7, Wyb. Wyspiaoskiego 27, 50-370 Wrocław, Poland phone +48713202626, fax +48713202006, email: zbigniew.leonowicz@pwr.wroc.pl Facility: XXX POWER QUALITY REPORT Start Monitoring:

More information

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY POWER QUALITY IMPROVEMENT OF GRID CONNECTED WIND ENERGY SYSTEM BY USING STATCOM Mr.Mukund S. Mahagaonkar*, Prof.D.S.Chavan * M.Tech

More information

Active Power Filters: A Comparative Analysis of Current Control Techniques for Four-Leg Full-Bridge Voltage Source Inverters

Active Power Filters: A Comparative Analysis of Current Control Techniques for Four-Leg Full-Bridge Voltage Source Inverters Active Power Filters: A Comparative Analysis of Current Control Techniques for Four-Leg Full-Bridge Voltage Source Inverters Juan Rueda, Ernesto Pieruccini, María Mantilla, Member, IEEE and Johann Petit,

More information

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO Krasimir Marinov Ivanov, Technical University of Gabrovo, Gabrovo, BULGARIA Georgi Tsonev

More information

Mitigation of Voltage Sag and Swell using D-STATCOM to improve Power Quality

Mitigation of Voltage Sag and Swell using D-STATCOM to improve Power Quality Mitigation of Voltage Sag and Swell using D-STATCOM to improve Power Quality Deeksha Bansal 1 Sanjeev Kumar Ojha 2 Abstract This paper shows the modelling and simulation procedure for power quality improvement

More information

Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions

Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions Fernando Bastião and Humberto Jorge Department of Electrical Engineering and Computers

More information

A robust voltage unbalance allocation methodology based on the IEC/TR guidelines

A robust voltage unbalance allocation methodology based on the IEC/TR guidelines University of Wollongong Research Online Faculty of Engineering - Papers (Archive) Faculty of Engineering and Information Sciences 2009 A robust voltage unbalance allocation methodology based on the IEC/TR

More information

1. Introduction to Power Quality

1. Introduction to Power Quality 1.1. Define the term Quality A Standard IEEE1100 defines power quality (PQ) as the concept of powering and grounding sensitive electronic equipment in a manner suitable for the equipment. A simpler and

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

METHOD TO DETERMINE CONTRIBUTION OF THE CUSTOMER AND THE POWER SYSTEM TO THE HARMONIC DISTURBANCE

METHOD TO DETERMINE CONTRIBUTION OF THE CUSTOMER AND THE POWER SYSTEM TO THE HARMONIC DISTURBANCE C I R E D 17 th International Conference on Electricity Distribution Barcelona, 1-15 May 3 METHOD TO DETERMINE CONTRIBUTION OF THE CUSTOMER AND THE POWER SYSTEM TO THE HARMONIC DISTURBANCE Olivier GONBEAU

More information

Some aspects regarding harmonic s distortions propagation in large medium voltage distribution system

Some aspects regarding harmonic s distortions propagation in large medium voltage distribution system Some aspects regarding harmonic s distortions propagation in large medium voltage distribution system L. E. PETREAN 1, D. C. PETER 1, M. HORGOŞ 1, A. BUCHMANN 1, L. PETREAN 2 1 Electrical Engineering Department,

More information

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side 1 Jaykant Vishwakarma, 2 Dr. Arvind Kumar Sharma 1 PG Student, High voltage and Power system, Jabalpur

More information

Enhancement of Power Quality Using Advanced Series Active Power Filters

Enhancement of Power Quality Using Advanced Series Active Power Filters Enhancement of Power Quality Using Advanced Series Active Power Filters Manoj siva kumar 1, P.Rayalakshmi 2 Associate Professor, Dept. of EEE, PBRVITS, Kavali, SPSR Nellore, A.P, India 1 M.Tech Student,

More information

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial

More information

HARMONIC distortion complicates the computation of. The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus

HARMONIC distortion complicates the computation of. The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus 1592 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005 The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus Ahmed Faheem Zobaa, Senior Member, IEEE Abstract A

More information

Fundamental Tarification of Electricity

Fundamental Tarification of Electricity Fundamental arification of Electricity Fundamental arification of Electricity Alex Van den Bossche, Bart Meersman and Lieven Vandevelde Department of Electrical Energy, Systems and Automation Ghent University

More information

Digital Fault Recorder Deployment at HVDC Converter Stations

Digital Fault Recorder Deployment at HVDC Converter Stations Digital Fault Recorder Deployment at HVDC Converter Stations On line continuous monitoring at HVDC Converter Stations is an important asset in determining overall system performance and an essential diagnostic

More information

Harmonic Distortion Evaluations

Harmonic Distortion Evaluations Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion

More information

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION International Journal of Electrical, Electronics and Data Communication, ISSN: 23284 Volume, Issue-4, April14 INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION 1 V.S.VENKATESAN, 2 P.CHANDHRA

More information

AGN 022 Conditions for Parallel Operation

AGN 022 Conditions for Parallel Operation Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 022 Conditions for Parallel Operation SYNCHRONISATION The parallel operation of Generating Sets is common, to share

More information

Modelling Parameters. Affect on DER Impact Study Results

Modelling Parameters. Affect on DER Impact Study Results Modelling Parameters Affect on DER Impact Study Results Agenda Distributed Energy Resources (DER) Impact Studies DER Challenge Study Steps Lessons Learned Modeling Reverse Power Transformer Configuration

More information

POWER QUALITY AND SAFETY

POWER QUALITY AND SAFETY POWER QUALITY AND SAFETY Date : November 27, 2015 Venue : 40 th IIEE Annual National Convention and 3E XPO 2015 PRESENTATION OUTLINE Power Quality I. INTRODUCTION II. GRID CODE REQUIREMENTS III. ERC RESOLUTION

More information

Improvement of Electricity Distribution Services Using a DVR with a Constant DC Voltage Source Instaled in MV Connection Substations

Improvement of Electricity Distribution Services Using a DVR with a Constant DC Voltage Source Instaled in MV Connection Substations Improvement of Electricity Distribution Services Using a DVR with a Constant DC Voltage Source Instaled in MV Connection Substations Gheorghe Ioan Nicolaescu, Horia Andrei, Stefan Radulescu Electrical

More information

Principles and Operation of Three-phase Systems

Principles and Operation of Three-phase Systems Unit 62: Principles and Operation of Three-phase Systems Unit code: QCF Level 3: Credit value: 10 Guided learning hours: 60 Aim and purpose H/600/7116 BTEC Nationals This unit provides learners with knowledge

More information

Thyristorised Automatic Power Factor

Thyristorised Automatic Power Factor Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor

More information

Auxiliary DC Voltage

Auxiliary DC Voltage THE 9 th INTERNATIONAL SYMPOSIUM ON ADVANCED TOPICS IN ELECTRICAL ENGINEERING May 7-9, 2015 Bucharest, Romania DVR with Auxiliary DC Voltage Source Provided by A High Power Diode Based Rectifier Used in

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

Development of Multilevel Inverters for Control Applications

Development of Multilevel Inverters for Control Applications International Research Journal of Engineering and Technology (IRJET) e-issn: 2395-56 Volume: 3 Issue: 1 Jan-216 www.irjet.net p-issn: 2395-72 Development of Multilevel Inverters for Control Applications

More information

Harmonic distortion Blackouts Under or over voltage Dips (or sags) and surges, Transients.

Harmonic distortion Blackouts Under or over voltage Dips (or sags) and surges, Transients. Power Quality Standards in India Power Quality is a measure of an ideal power supply system. It can be defined as any power problem manifested in voltage, current and frequency deviations that result in

More information

Charge Pump Phase Locked Loop Synchronization Technique in Grid Connected Solar Photovoltaic Systems

Charge Pump Phase Locked Loop Synchronization Technique in Grid Connected Solar Photovoltaic Systems IOSR Journal of Computer Engineering (IOSR-JCE) e-issn: 2278-0661, p- ISSN: 2278-8727Volume 16, Issue 1, Ver. VII (Feb. 2014), PP 91-98 Charge Pump Phase Locked Loop Synchronization Technique in Grid Connected

More information

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER Rajesh Kr. Ahuja 1, Aasha Chauhan 2, Sachin Sharma 3 Rajesh Kr. Ahuja Faculty, Electrical & Electronics Engineering Dept.

More information

An Introduction to Power Quality

An Introduction to Power Quality 1 An Introduction to Power Quality Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation 3 Today s Presenter n Andy Sagl Megger

More information

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS 66 CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS INTRODUCTION The use of electronic controllers in the electric power supply system has become very common. These electronic

More information

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES C.E.T. Foote*, G.W. Ault*, J.R. McDonald*, A.J. Beddoes *University of Strathclyde, UK EA Technology Limited, UK c.foote@eee.strath.ac.uk

More information

A REVIEW PAPER ON REGULATION TECHNIQUE FOR VOLTAGE SAG AND SWELL USING DVR

A REVIEW PAPER ON REGULATION TECHNIQUE FOR VOLTAGE SAG AND SWELL USING DVR A REVIEW PAPER ON REGULATION TECHNIQUE FOR VOLTAGE SAG AND SWELL USING DVR 1 Ms.Santoshi Gupta, 2 Prof.Paramjeet Kaur 1 M.Tech Scholar, 2 Associate Professor Department of Electrical and Electronics Engineering

More information

IEEE sion/1547revision_index.html

IEEE sion/1547revision_index.html IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html

More information

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation Maher G. M. Abdolrasol maher_photo@yahoo.com Dept. of Electrical Engineering University of Malaya Lembah Pantai, 50603

More information

Quality of supply regulation in Norway c

Quality of supply regulation in Norway c Quality of supply regulation in Norway c Kjell Sand, Gerd H. Kjølle SINTEF Energy Research Oct. 2005/ Aug. 2006 updated April 2009 SINTEF Energy Research 1 Electrical energy consumption per capita x 1

More information

Dietrich Bonmann, ABB Monselice Transformer Days, May 5, 2010 Optimized AC transmission solutions with phase-shifting transformers and shunt reactors

Dietrich Bonmann, ABB Monselice Transformer Days, May 5, 2010 Optimized AC transmission solutions with phase-shifting transformers and shunt reactors Dietrich Bonmann, ABB Monselice Transformer Days, May 5, 2010 Optimized AC transmission solutions with phase-shifting transformers and shunt reactors May 11, 2010 Slide 1 Why phase-shifting transformers

More information

Key-Words: - NARX Neural Network; Nonlinear Loads; Shunt Active Power Filter; Instantaneous Reactive Power Algorithm

Key-Words: - NARX Neural Network; Nonlinear Loads; Shunt Active Power Filter; Instantaneous Reactive Power Algorithm Parameter control scheme for active power filter based on NARX neural network A. Y. HATATA, M. ELADAWY, K. SHEBL Department of Electric Engineering Mansoura University Mansoura, EGYPT a_hatata@yahoo.com

More information

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Ishwar Lal Yadav Department of Electrical Engineering Rungta College of Engineering and Technology Bhilai, India

More information

UPQC (Unified Power Quality Conditioner)

UPQC (Unified Power Quality Conditioner) A Unified Power Quality Conditioner (UPQC) is a device that is similar in construction to a Unified Power Flow Conditioner (UPFC). The UPQC, just as in a UPFC, employs two voltage source inverters (VSIs)

More information

ELECTRICITY tariff structures in Egypt are fairly complex,

ELECTRICITY tariff structures in Egypt are fairly complex, 912 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005 The Most Economical Power Factor Correction According to Tariff Structures in Egypt Ahmed Faheem Zobaa, Senior Member, IEEE, and Mohamed

More information

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics Power Quality Monitor Individual Harmonics measurement upto 56th Harmonics True representation of Voltage & Current waveforms. Phasor Representation of All 3 phases for system analysis Real Time Clock

More information

Power Analysis Summary

Power Analysis Summary Power Analysis Summary Introduction This is a summary of the power conditions measured with these setup parameters: Measurement File: C:\Users\fhealy\Documents\Fluke\Power Analyze\Core 2 Recording.odn

More information

Investigation of Geomagnetic Induced Current Effects on Power Transformer

Investigation of Geomagnetic Induced Current Effects on Power Transformer International Research Journal of Engineering and Technology (IRJET) e-issn: 2395-56 Investigation of Geomagnetic Induced Current Effects on Power Transformer Roshni.R.Jethani 1, Dr.Harikumar Naidu 2,

More information

A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer

A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer IJIRST International Journal for Innovative Research in Science & Technology Volume 3 Issue 07 December 2016 ISSN (online): 2349-6010 A Novel Method to Analyse the Effects of Geomagnetic Induced Current

More information

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008 Welcome to the rd Annual Northern Ohio 3 rd Energy Management Conference September 30, 2008 Recover Lost Dollars Demand Side Electrical Energy Savings By Improving Distribution System Efficiency, Capacity

More information

Power Factor and Power Factor Correction

Power Factor and Power Factor Correction Power Factor and Power Factor Correction Long gone are the days when only engineers that worked with large electric motors and high power electric loads need worry about power factor. The introduction

More information

Harmonics Reduction of 3 Phase Diode Bridge Rectifier by Implementing P-Q Theory with Active Filter

Harmonics Reduction of 3 Phase Diode Bridge Rectifier by Implementing P-Q Theory with Active Filter IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 07, 2016 ISSN (online): 2321-0613 Harmonics Reduction of 3 Phase Diode Bridge Rectifier by Implementing P-Q Theory with

More information

Power Quality improvement of a three phase four wire system using UPQC

Power Quality improvement of a three phase four wire system using UPQC International Research Journal of Engineering and Technology (IRJET) e-issn: 2395-56 Volume: 2 Issue: 4 July-215 www.irjet.net p-issn: 2395-72 Power Quality improvement of a three phase four wire system

More information

Grid Converters for Photovoltaic

Grid Converters for Photovoltaic Grid Converters for Photovoltaic and Wind Power Systems by R. Teodorescu, M. Liserre and P. Rodriguez ISBN: 978 0 470 05751 3 Copyright Wiley 2011 Chapter 3 Grid Requirements for PV Grid connection requirements

More information

Power supply circuit Through an external power supply unit V ac / 12 V dc. Operating temperature ºC. Humidity of operation

Power supply circuit Through an external power supply unit V ac / 12 V dc. Operating temperature ºC. Humidity of operation Portable Description Features Measures all of the main electrical parameters of an electricity network Measurement in true root mean square Built-in energy meter With 4 voltage channels and 4 current channels

More information

Understanding Power Quality

Understanding Power Quality Understanding Power Quality Produced by Dr Bruce Girdwood For Energy Mad Ltd Version 1: 23 October 2007 The electronics revolution and the growing number of utility programmes promoting compact fluorescent

More information

Power Quality enhancement of a distribution line with DSTATCOM

Power Quality enhancement of a distribution line with DSTATCOM ower Quality enhancement of a distribution line with DSTATCOM Divya arashar 1 Department of Electrical Engineering BSACET Mathura INDIA Aseem Chandel 2 SMIEEE,Deepak arashar 3 Department of Electrical

More information

Tripping of circuit breakers in PV installations due to zero sequence field impedance

Tripping of circuit breakers in PV installations due to zero sequence field impedance Tripping of circuit breakers in PV installations due to zero sequence field impedance B. Verhelst 1,2, C. Debruyne 1,2, J. Desmet 1,2 1 dept. Electrical Engineering - Lemcko HoWest Kortrijk, Belgium bart.verhelst@howest.be

More information

Power Quality Testing

Power Quality Testing Power Quality Testing INTRODUCTION TO POWER QUALITY Both natural and manmade drivers are spurring not only technological growth but are changing the nature of the electric grid. Concerns over global warming

More information

MODELING AND CONTROLLING OF AC VOLTAGE STABILIZER USING SERIES ACTIVE POWER FILTER

MODELING AND CONTROLLING OF AC VOLTAGE STABILIZER USING SERIES ACTIVE POWER FILTER MODELING AND CONTROLLING OF AC VOLTAGE STABILIZER USING SERIES ACTIVE POWER FILTER Pratyenja Ganorkar 1, D.A.Shahakar 2 1 PG Scholar, Electrical Engineering Department, P.R.Pote (Patil) College of Engineering

More information

Roadmap For Power Quality Standards Development

Roadmap For Power Quality Standards Development Roadmap For Power Quality Standards Development IEEE Power Quality Standards Coordinating Committee Authors: David B. Vannoy, P.E., Chair Mark F. McGranghan, Vice Chair S. Mark Halpin, Vice Chair D. Daniel

More information

Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System

Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System Kolli Nageswar Rao 1, C. Hari Krishna 2, Kiran Kumar Kuthadi 3 ABSTRACT: D-STATCOM (Distribution Static Compensator)

More information

Power quality measurements in a singlehouse

Power quality measurements in a singlehouse 24th International Conference & Exhibition on Electricity Distribution (CIRED) 12-15 June 2017 Session 2: Power quality and electromagnetic compatibility Power quality measurements in a singlehouse microgrid

More information

by Cornel Stanescu, Cristian Dinca, Radu Iacob and Ovidiu Profirescu, ON Semiconductor, Bucharest, Romania and Santa Clara, Calif., U.S.A.

by Cornel Stanescu, Cristian Dinca, Radu Iacob and Ovidiu Profirescu, ON Semiconductor, Bucharest, Romania and Santa Clara, Calif., U.S.A. Internal LDO Circuit Offers External Control Of Current Limiting ISSUE: May 2012 by Cornel Stanescu, Cristian Dinca, Radu Iacob and Ovidiu Profirescu, ON Semiconductor, Bucharest, Romania and Santa Clara,

More information

Voltage and Current Waveforms Enhancement using Harmonic Filters

Voltage and Current Waveforms Enhancement using Harmonic Filters Voltage and Current Waveforms Enhancement using Harmonic Filters Rajeb Ibsaim rabsaim@yahoo.com, Azzawia University, Libya Amer Daeri ibnjubair1@yahoo.co.uk Azzawia University, Libya Abstract The demand

More information

A Novel Ultra High Fidelity Power Quality and Energy Management Software Using NI LabVIEW

A Novel Ultra High Fidelity Power Quality and Energy Management Software Using NI LabVIEW A Novel Ultra High Fidelity Power Quality and Energy Management Software Using NI LabVIEW Shishir Sarkar 1, Dr. S. Chatterji 2, Shimi S.L 3, Sonia Rawat 4 1 M.E Student, Electrical Engineering Department,

More information

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives 2 TECHNICAL GUIDE NO. 6 GUIDE TO HARMONICS WITH AC DRIVES Guide to harmonics This guide is part of ABB s technical guide series, describing

More information

Induction Machine Test Case for the 34-Bus Test Feeder -Distribution Feeders Steady State and Dynamic Solutions

Induction Machine Test Case for the 34-Bus Test Feeder -Distribution Feeders Steady State and Dynamic Solutions Induction Machine Test Case for the 34-Bus Test Feeder -Distribution Feeders Steady State and Dynamic Solutions Induction Machine Modeling for Distribution System Analysis panel IEEE PES General Meeting

More information

Power Quality Improvement in Fourteen Bus System using UPQC

Power Quality Improvement in Fourteen Bus System using UPQC International Journal of Electrical Engineering. ISSN 0974-2158 Volume 8, Number 4 (2015), pp. 419-431 International Research Publication House http://www.irphouse.com Power Quality Improvement in Fourteen

More information

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller This paper deals with the general problem of utilizing of renewable energy sources to generate electric

More information

Do You Have a Harmonic Problem?

Do You Have a Harmonic Problem? ??????? Do You Have a Harmonic Problem? Forster Electrical Engineering, Inc. 550 N. Burr Oak Ave, Oregon, WI 53575 (608) 835-9009 (608) 835-9039 fax 1 March 1999 What is THD? Total Harmonic Distortion

More information

IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs

IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs Mr. P. Biswas, ABB ABSTRACT The Indian Railways employ single phase 25 kv Traction sub-station (TSS) for supplying power

More information

The Influence of Voltage Flicker for the Wind Generator upon Distribution System

The Influence of Voltage Flicker for the Wind Generator upon Distribution System The Influence of Voltage Flicker for the Wind Generator upon Distribution System Jin-Lung Guan, Jyh-Cherng Gu, Ming-Ta Yang, Hsin-Hung Chang, Chun-Wei Huang, and Shao-Yu Huang Digital Open Science Index,

More information

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Harmonics Reduction using 4-Leg Shunt Active Power Filters Harmonics Reduction using 4-Leg Shunt Active Power Filters K Srinivas Assistant Professor & Department of EEE & JNTUH CEJ Telangana, India. Abstract Harmonics in power system are caused by highly non-linear

More information

Influence of Switching Elements on Harmonics and Power Factor Improvement

Influence of Switching Elements on Harmonics and Power Factor Improvement International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 7, Issue 12 (July 2013), PP. 18-24 Influence of Switching Elements on Harmonics

More information

BED INTERCONNECTION TECHNICAL REQUIREMENTS

BED INTERCONNECTION TECHNICAL REQUIREMENTS BED INTERCONNECTION TECHNICAL REQUIREMENTS By Enis Šehović, P.E. 2/11/2016 Revised 5/19/2016 A. TABLE OF CONTENTS B. Interconnection Processes... 2 1. Vermont Public Service Board (PSB) Rule 5.500... 2

More information

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System G. Laxminarayana 1, S. Raja Shekhar 2 1, 2 Aurora s Engineering College, Bhongir, India Abstract: In this

More information

2020 P a g e. Figure.2: Line diagram of series active power filter.

2020 P a g e. Figure.2: Line diagram of series active power filter. Power Quality Improvement By UPQC Using ANN Controller Saleha Tabassum 1, B.Mouli Chandra 2 (Department of Electrical & Electronics Engineering KSRM College of Engineering, Kadapa.) (Asst. Professor Dept

More information

Power Quality Improvement of Grid Connected Wind Energy System by Statcom for Balanced and Unbalanced Linear and Nonlinear Loads

Power Quality Improvement of Grid Connected Wind Energy System by Statcom for Balanced and Unbalanced Linear and Nonlinear Loads International Journal of Engineering Research and Development e-issn: 2278-67X, p-issn: 2278-8X, www.ijerd.com Volume 3, Issue 1 (August 212), PP. 9-17 Power Quality Improvement of Grid Connected Wind

More information

BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP

BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP The BEST Group THE BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP -Winter Lecture Series HARMONICS Presented by: Syed Khundmir T Department of Electrical Engineering University at Buffalo khundmir@buffalo.edu

More information

ASSESSMENT OF HARMONIC DISTORTION LEVELS IN LV NETWORKS WITH INCREASING PENETRATION LEVELS OF INVERTER CONNECTED EMBEDDED GENERATION

ASSESSMENT OF HARMONIC DISTORTION LEVELS IN LV NETWORKS WITH INCREASING PENETRATION LEVELS OF INVERTER CONNECTED EMBEDDED GENERATION ASSESSMENT OF HARMONIC DISTORTION LEVELS IN LV NETWORKS WITH INCREASING PENETRATION LEVELS OF INVERTER CONNECTED EMBEDDED GENERATION Adam DYŚKO, Graeme M. BRT, James R. McDONALD niversity of Strathclyde

More information

Power Quality Enhancement of Grid Connected Non-Conventional Energy System using STATCOM with PI Controller

Power Quality Enhancement of Grid Connected Non-Conventional Energy System using STATCOM with PI Controller International Journal of Latest Trends in Engineering and Technology (IJLTET) Power Quality Enhancement of Grid Connected Non-Conventional Energy System using STATCOM with PI Controller Shanmukha Sriram

More information

NEQUAL -WEB-BASED VOLTAGE QUALITY MONITORING IN SWITZERLAND

NEQUAL -WEB-BASED VOLTAGE QUALITY MONITORING IN SWITZERLAND NEQUAL -WEB-BASED VOLTAGE QUALITY MONITORING IN SWITZERLAND Jan MEYER Hansjörg HOLENSTEIN Stefan EGGER Etienne GASCH, Max DOMAGK Association of St. Gallisch-Appenzellische Technische Universitaet Dresden

More information

VOLTAGE OPTIMIZATION FOR INDUSTRY, TRADE, BUSINESS AND LOCAL NETWORKS

VOLTAGE OPTIMIZATION FOR INDUSTRY, TRADE, BUSINESS AND LOCAL NETWORKS VOLTAGE OPTIMIZATION FOR INDUSTRY, TRADE, BUSINESS AND LOCAL NETWORKS Employing a voltage control system in a low-tension network provides independence from network fluctuations. In addition, energy-using

More information

Advantages There are many diverse advantages of a portable analyzer for the user. The most important is information.

Advantages There are many diverse advantages of a portable analyzer for the user. The most important is information. Portable s CIRCUTOR offers a wide range of portable analyzers designed to measure, display and/or record the most important parameters of an electrical network. With the analysis of the electrical parameters,

More information

THD Reduction Using Series Transformer Connection In A STATCOM Within Mosul Ring System

THD Reduction Using Series Transformer Connection In A STATCOM Within Mosul Ring System Al-Nimma: THD reduction using series transformer connection in a STATCOM within THD Reduction Using Series Transformer Connection In A STATCOM Within Mosul Ring System Dhaiya A. Al-Nimma Majed S. Al-Hafid

More information