9. Grid-Connected of Photovoltaic Systems

Size: px
Start display at page:

Download "9. Grid-Connected of Photovoltaic Systems"

Transcription

1 9. Grid-Connected of Photovoltaic Systems H. Boileau Savoie University, FR Learning outcomes After reading this chapter, the user should possess knowledge of: A core description of PV systems connected to the electrical network The additional components on the DC part of PV systems Photovoltaic inverters The additional components on the AC part of PV systems System design and forecast of the electrical production Profitability of photovoltaic installations (TCE method from Bernard Chabot/ADEME) Assessing the compatibility between the photovoltaic field and the inverter Description of PV frames connected to the electrical network Photovoltaic installations connected to the electrical network represent the majority of the photovoltaic installations currently installed in the world (in 2015). Indeed, these photovoltaic installations are the simplest possible, therefore the costs are lower and all of the produced electricity is injected on the grid to be used. These advantages have these photovoltaic systems offering a lower cost per produced kwh, which explains the strong market penetration and commercial interest. In the absence of radiance, there is, of course no energy production, but the network compensates. On the other hand, it should be known that, in absence of voltage, the photovoltaic installation is bypassed for safety reasons, even if there is a strong luminous radiance.

2 Figure 1 - Simplified diagram of a photovoltaic installation Fig. 1 display a simplified diagram of a photovoltaic installation connected to the network with the main elements The photovoltaic field, when under solar irradiation, produces electrical energy in the form of DC current. This DC current is transformed by an inverter into AC to be injected in the grid, with the same amplitude and phase of the AC voltage of the network (typically an amplitude of 230 V and a frequency of 50 Hz in Europe). There may be protection devices installed between the PV installation and the inverter as well, if they are necessary or compulsory due to local regulations. Protective devices can also be inserted between the inverter and the network (inevitably necessary but not imposed by the safety standards). Finally, there usually is an energy meter for the invoicing of produced photovoltaic kwh. It can be useful to insert a feedback system to check how the installation runs because, for minor issues or losses, nothing indicates if the system runs correctly or not. A display can be used for the continuous monitoring of useful information, such as the instantaneous power and the cumulated energy produced.

3 The photovoltaic field The photovoltaic field is the entirety of the photovoltaic modules of a PV installation. The entirety of these photovoltaic modules can be connected in various ways, to one or several inverters. The three principal possible configurations are shown in Figure 2. Figure 2: Principal possible configurations of PV fields. The explanation of Figure 2 follows: a) The entirety of the photovoltaic field is connected to one inverter, which is called the centralized inverter. This configuration is the least expensive but all of the modules must be of the same type, have the same angular position and direction, for the simple reason that the current and voltage produced by each chain of modules must be of the same value. If not, there is a production loss. Each chain obviously needs to have the same number of modules. The influence of a shade on one or more photovoltaic modules can be rather important on the electric production, because the modules of each chain are connected in series and it will change change of current and/or voltage in a chain of modules that is in parallel with the other chains. Other disadvantages include that a breakdown of the inverter causes the complete halt of the PV field, the breakdown of a single PV module is difficult to locate and the voltage of a chain of modules is often high, several hundreds of volts in DC current, which is dangerous for living organisms. b), The entirety of the photovoltaic field is divided into chains of PV modules, each one connected to an inverter. All of the PV modules of the same chain must be of the same type,

4 have the same angular position and direction. On the other hand, from one chain to another, the type and position of the modules can be different. For example, this could be a system on different roofs connected on a single main bus. The influence of shading is less important than in configuration a, as shaded modules will only affect the chain they are installed on. Among other advantages, a breakdown of an inverter causes the complete halt of a chain (but not of the whole PV field) and the breakdown of a single PV module is easier to locate. However, the voltage of a single chain of modules remain often high, several hundreds of volts in DC current, which is dangerous for living organisms. c), In this configuration, each PV module is connected to an inverter, said micro-inverter in this configuration. Here, all the modules can be of different type and positioned differently as well, as they are independent. The breakdown of an inverter causes the stop of only one module, therefore little production loss. The influence of shading is very limited, only to the modules concerned. The high cost is the primary disadvantage of this solution but offers the most advantages. Normative Aspects on the characteristics of PV modules and safety: For instance, we briefly mention the French norms. - NF 61215: skill of the design and approval of crystalline PV modules. - NF 61646: skill of the design and approval of PV modules in thin layer - NF 61730: Characterization of the performances: flash test, NOCT, coefficients, etc. - Mechanical Tests: charges, shock, spindly, etc. - Climatic Tests: hot-cold, UV, etc. - Electric Tests: dielectric, leakage current, etc. The respect of these standards guarantees the quality of the photovoltaic modules and their conditions of use as, for example, a voltage of insulation of volts specifies the maximum number of PV modules in a single chain.

5 The phenomenon of "hot spot'' To explain the phenomenon of hot spot, let us take an example with a photovoltaic module of 72 cells (characteristic CP = 250W c, V mpp = 36V dc, V oc = 45V dc, I mpp = STC). If a cell of this module is shaded (I cell = 0A) or this module is short-circuited (Figure 3): Figure 2: PV Module with one shaded cell. The shaded cell (I cell = 0A, thus it behaves as an open circuit) receives all the voltage in reverse. The opposite breakdown voltage of a cell PV is typically of 25 V dc (Zener voltage), but the operative voltage of the module is V mpp = 36 Vdc. Therefore, the cell is destroyed, because it receives a strong voltage and becomes conducting, resulting to destruction by overload. Let us consider a more realistic case of a photovoltaic field with three chains (or strings) of six modules in series, where one cell of one chain is shaded like before (Figure 4).

6 Figure 3 : Three chains with one shaded cell. The operating voltage of such a string is 36 V dc 6 modules = 216 V dc. Where the cell is shaded (I cell = 0A), this chain is an open circuit, with a no load voltage of 45V dc 6 modules = 270 V dc. The reverse voltage of the shaded cell is then 54 V dc. The Zener effect takes place in this photovoltaic cell and it becomes conductive. The power dissipated in the shaded cell PV is 25V 6A = 150W, but the photovoltaic cell is not designed to dissipate this levels of power (no more than few Watts). This power will be converted to thermal where the photovoltaic cell is the most resistive until carbonizing that point (from where the name of hot spot originates). Figure 5 displays a photograph of a PV panel destroyed by such an effect. Figure 4: Damaged PV Panel, hot spot. The solution to prevent the phenomenon of hot spot is to use diodes, known as bypass diodes, connected in reverse and per about 20 PV cells. In the example of a 12 Volts PV module with 36 cells, a bypass diode is connected per PV 18 cells, as shown in Figure 6:

7 Figure 5 : Operation of a bypass diode. For this 12 volts module, the shaded cell results to the lack of current generation by the cell. Without a bypass diode, the PV module produces a lower or no current, with the risk of a hot spot arising. With the bypass diode, the power generated by the group of 18 unshaded cells can go through the bypass diode but, in the case of our example, the output voltage of the module will be two times lower. However, the diode prevents from having a high voltage in reverse on the shaded cells. For PV modules of silicon crystalline technology, the bypass diodes are cabled in the connecting box (Figure 7). Figure 6 : Connection of a bypass diode. The number of bypass diodes depends on the number of cells in PV module. Generally, two bypass diodes for a module with 36 cells, three bypass diodes for a module with 60 cells (very common type of module) and four bypass diodes for a module with 72 cells. The influence of the shade on a standard 12 Volts module, according to the point of operation, is described by the two following figures:

8 Figure 7 : Current vs voltage for different shades on a cell Figure 8 : Power vs voltage for different shades on a cell If a PV cell on a module is shaded, the module will produce an electric current lower than the rated current. If the load requires a very weak current, the output voltage will be the nominal voltage, but if the current consumed increases higher than what the shaded cell can produce, the voltage will decrease by a factor of two because of the bypass diode. Figure 8 shows that if a cell is shaded, then two points of maximum capacity appear, variable according to the extent of the shading. This phenomenon will thus disturb the operation of the MPPT (Maximum Power Point Tracking) process of the inverters. On a PV module where a cell is defective (shades or similar defect), measurements of the noload voltage and short-circuit current are both good. To detect this kind of defect, it is necessary to generate a current/voltage graph.

9 Protection against reverse currents: Reverse currents are another phenomenon that can deteriorate PV modules besides the phenomenon of hot spot. The phenomenon occurs when the current of a string is reversed when several strings are connected in parallel. In this case, if one of the chains is shaded, the cells do not produce any current. The current produced by the parallel chains now may pass through the chain with the shaded modules, leading to its destruction. With respect to the norms, a module should withstand in reverse twice the current that it is able to produce under STC conditions. When there are more than three chains, it is imperative to put a protective component in series with each chain, like a diode, to avoid this reverse current. Figure 9: Wiring example of three strings of six PV modules with the bypass diodes at the edges of the PV modules and the serial diodes at the end of the strings to protect from reverse currents. The serial diode protects effectively but causes a loss in power (loss of 1 volt if connected in series). In France, UTE C guideline recommends the use of a fuse, which is causing a lower power loss but fuses are irreversibly damaged when actuated. It is important to accurately assess the value of this fuse. Often, the manufacturers of PV modules provide the recommended value of this serial fuse with the electric characteristics of the PV module.

10 Additional Components on the DC part of photovoltaic installations Cables and electric connectors The electric cables used in photovoltaic installations must meet specific criteria (standard UTE C ). Some of these criteria are: a double insulation (class II), resistance to 1000V, resistance to UV and resistance up to a temperature of 90 C. The cross section of these wires is standardized. For example, commercial wires may have a cross section of 1.5 mm², 2.5 mm², 4 mm², 6 mm², etc. The cross section of the wires is selected according to the intensity of the current and the length of wiring. Figure 10 : Cables commonly used in PV installations. The electric connectors are secure (standards UL1703, VDE126-3, etc.). This means that they offer protection against direct contact, they can be lockable (type MC4) or not (MC3) depending on their accessibility, with a good behaviour towards UV and bad weather (IP54). Figure 11: Examples of connectors used in PV installations. Each photovoltaic module has two connectors, male and female, which facilitates the connection in series of those. Additional cables are used to make inter-connections between the strings in parallel and between the PV fields and the inverters. TAKE HEED, because of the continuous solar irradiation during the day, the voltage at the boundaries of the PV field has a magnitude of several hundreds of volts. This voltage can be dangerous during the implementation or the maintenance of a PV installation and, in the case of a circuit breakdown, a maintained electric arc is being created, because there no passage through 0 volts like in the case of the AC voltage. For that reason, the use of circuit breakers specific to photovoltaic is often required (Guideline UTE C in France).

11 Figure 12 : Electric Arc in a PV circuit. Protection against lightning of PV installations The photovoltaic field is by default exposed to the sun and subject to all weather conditions, including direct and indirect lightning impacts. For that, safety standards recommend or impose the use of lightning protector with suitable installation of the ground cable, with its specifications depending on the area where the PV installation is installed (in France, guideline UTE C15 712). Figure 13:Example of a PV installation grounding (source: Diagram Dehn, online: To protect from direct lightning impacts, there is almost no other solution than a lightning protector. For indirect lightning impacts, there are various solutions to decrease the destruction risk of the PV installation components. For example, the wiring of the PV modules can be done in such a manner so as to decrease the surface of the loops (Figure15), reducing the electric field induced in the loop by the strong magnetic variation caused by the amperage of a flash striking the ground in the vicinity.

12 Figure 14: Wiring examples of four PV modules. DC Junction Box A PV field generally is composed of PV modules cabled in series between them, creating strings. This is done to reach a high enough voltage. When the desired voltage has been reached, multiple chains can be connected in parallel (as long as their voltage remains the same), preserving the voltage and increasing the amperage (basic principle of electricity). Dimensioning requires adaptation through a thoughtful arrangement of the PV modules in series and parallel to surface available (on a roof, for example), but especially on the voltage and current intensity specifications of the inverter. Between the PV field and the inverter(s), a junction box is used to connect the chains of modules in parallel between them. The junction box also includes the protection components, such as the lightning protectors, the fuses, DC switches, etc. Figure 15:Example of a junction box with four chains in parallel, two lightning protectors and a DC switch.

13 Photovoltaic Inverters DC to AC inverters used by PV field convert electrical energy from the DC that the PV field generates to AC, compatible in terms of voltage and frequency with the network. The electric symbol of PV inverter is: Various types of inverters: Figure 16 : Inverters for PV fields (Source: SMA) Inverters for PV fields (Figure 17) are typically used for large PV installations on ground or on mounts, rated for several hundreds or thousands of kwc. Their AC output usually is threephase and the input DC voltage is up to a few hundred volts. Figure 17 : Inverters for PV installations (Source: SMA) Inverters for PV installations (Figure 18) are used in small or medium size projects. They are rated from some kwc up to a few hundreds of kwc. The inverter may be connected to one or several strings of PV modules, depending on the model and the size of the installation.

14 Their input DC voltage usually is rated for a few hundreds of volts, while be single or three phase. the AC output may Figure 18: Micro Inverter. The micro inverter (Figure 19) is connected to a single or up to a few PV modules. These inverters are not rated for more than a few hundred watts, while their input voltage usually is not higher than a few tens of volts. The AC output is single phase. Because of the low DC voltage input, these inverters are interesting because of their safety and can be used for small, medium or even large photovoltaic fields. All types of inverters have in common the seeking of the maximum capacity operation point (MPPT Maximum Power Point Tracking), a conversion efficiency from DC to AC of about 95% and automatic disconnection if no AC network voltage is detected (Standard VDE ) to avoid the electrocution of workers in cases of network maintenance. Principle of operation of a PV inverters: The purpose of the PV inverter is to convert the electric output generated by the PV field to an AC output compatible with the network. To that purpose, the MPPT system seeks the point of operation where the power is maximum from all of the possible points of operation (DC voltage) at exit of the PV field. Then a second electronic system, the inverter, converts the DC voltage into AC, compatible in terms of magnitude and phase with that of the network. The inverter's efficiency depends on how well it can match the voltage, frequency and phase of the network, as the portion of power injected to the network to the produced power from the PV field determines the electric losses in the inverter. The electronics of the PV inverter must also take into account the safety standards, such as the disconnection from the network in the event of temporary absence of AC voltage, or avoid the insertion of harmonics to the network that can disturb the operation of sensitive electrical appliances. Part of the performance feedback from a PV installation can also be assured by the inverter, by recording or forwarding to a server its operating information. Electric Characteristics of a photovoltaic inverter: The photovoltaic inverters have electric characteristics to be consulted for their correct operation (Figure 20). The main features are: On the DC (input) side:

15 Maximum capacity input: Maximum P in in Watts Maximum voltage input: Maximum V in in Volts Range of voltage of operation MMPT input: from V mppt min to V mppt max Maximum intensity input: Maximum I in in Ampere On the AC (output) side: Maximum output power: P out in Watts Typical voltage and the operating output range: V ac typ, from V ac min to V ac max Maximum output intensity: I ac max Conversion yield at the nominal output Figure 19 : Photovoltaic example of inverter and its characteristic (Source: SMA) European standardized output of a PV inverter: The PV inverter consumes a small part of the electric energy generated by the PV field (or from the network at night), inducing losses. The output of a PV inverter is generally defined at 100% of its nominal output. However, as solar irradiance during the day varies greatly, the electric production of the PV field will vary accordingly and, ultimately, the power point of operation of the PV inverter will also vary from zero (at night) to a value close to its nominal output under the best conditions of solar irradiance (if correctly dimensioned). To calculate the electric production of a PV installation in a more realistic way, a European average output was defined according to various points of operation with a coefficient for each one of these points of operation. This European output was defined according to the formula found in Figure 21.

16 Figure 20 : European standardized output of a PV inverter. Safety and standard for the photovoltaic inverters: The PV inverters must conform with various standards, the most important of which certainly is the standard VDE0126 that obliges the decoupling of the PV inverter when there is no network voltage. Indeed, if a worker locally disconnects part of the network for interventions/repairs, it is essential that the PV inverter stops the injection of electricity to avoid electrocuting the maintenance workers. Figure 21 : The conditions imposed by standard VDE0126 for France. These conditions can slightly vary from one country to another.

17 Additional Components on the AC side of the photovoltaic installations Network side box with the components of protection: (C Standard for France, consumer side) Figure 22: Network side box with the components of protection. In this box, we find components such as differential circuit breakers (usually rated at 30 ma) lightning arrest switches, disconnecting switches (Figure 24). Figure 23 : Differential circuit breaker (30 ma) lightning arrest switch, disconnecting switch. It is important to affix a descriptive label indicating the connection of a photovoltaic installation inside the electric box, network side, to indicate a potential danger to a technician (Figure 25). Figure 24 : Descriptive label indicating the connection of a photovoltaic installation

18 Electric meters and circuit breaker network side: (Standard C in France, distributer side of the network) The production of photovoltaic electricity must be routed through an electric meter to allow an invoicing of the electrical energy injected in the network, just like the electricity consumption by an individual. These metering elements, along with protection devices like the differential circuit breaker, are generally installed within the property but belong to the electrical energy distribution company. Figure 25 : Example of an electric meter and differential circuit breaker The electric meter allows the counting of the kwh produced by the photovoltaic installations that were injected into the network, as shown in Figure 27: Figure 26 : Dual electric meter connection. Usually, a second electric meter is put in series, but oppositely connected, to meter electric kwh that may be potentially consumed from the network (by the inverters during night time, for example). From the aforementioned setup, a consumer of electrical energy can connect and consume electrical energy locally. In this case, part of the photovoltaic

19 production will be self-consumed, while the surplus will be injected to the network (Figure 28). Figure 27 :Dual electric meter connection (self-consuming setup). It should be noted that to know the quantity of photovoltaic energy self-consumed, it is necessary to add another electric meter in serial to the photovoltaic installation. This meter is not essential for the distributer of electrical energy, it only allows the user to know the electrical energy consumption that the photovoltaic installation provides. In the case where the producer of photovoltaic electricity wishes to inject all the production in the electrical network (in the case of an advantageous tariff agreement), it is necessary to have a second electric network connection for the consumption of electricity from the electrical network (Figure 29). Figure 29: nework configuration for injection Dimensioning or calculation of the photovoltaic yield Depending on the case and purpose of the PV installation, the designer can either assess the electric production of the PV system or to size the installation according to certain power

20 requirements. Very often, especially with PV installations that will be connected to the electrical grid, the peak power P c of the installation is limited by external conditions, such as, for example, the installation surface available. In this case, the peak power P c of the PV installation is known and the annual electricity production is what needs to be assessed. To that end, it is essential to possess data on the annual average irradiation in the vicinity of the PV installations, and to calculate the optimal tilt and orientation of the PV panels. The typical data required for the sizing of PV installations is the annual global irradiation (I GPan ) on the horizontal plane. Software, such as Meteonorm, can determine this value for any site in the world with fair precision, for any given installation tilt and orientation. There are also free data resources, such as PVGIS ( which calculate and offer such data for almost any position in Europe, Africa and Asia by using climatic maps (Figure 30). Figure 30 :PVGIS output example for the site of the INES in Le Bourget du Lac in France The value for the average overall annual irradiation on a plane with a tilt of 30 towards the south is 3.98 kwh/m² per day (BDD classic PVGIS), which is a global irradiation received by the modules equal to: I GPan = = 1452 kwh/m² per annum. The third important data figure is the performance ratio (PR). The PR represents the entirety of the electric losses, which include the losses from the Joule effect in the wiring (~1%), the

21 losses of the PV inverter (~5%) and, most importantly, the losses from the rising temperature of the PV modules under solar radiance (~10% to ~15%). Different types of installations affect the airing of the PV modules and, in extent, their operating temperature under solar irradiation. For example, roof-mounted PV modules may have higher operating temperatures than ground installations on mounts. Depending on the location of the installation and the mounting type, it has been empirically estimated that the PR is close to the following values: Well ventilated Installation (e.g. PV installation on the ground) PR = 0.8 Fairly badly ventilated (e.g. super-installed on roof): PR = 0.75 Badly ventilated (e.g. fully integrated on roof): PR = 0.70 From these three figures, P c, I GPan and PR, the annual electricity production E a of a PV installation can be assessed: E a (in kwh per annum) = Pc (W c ) I GPan (in kwh/m² per annum) PR (dimensionless) This formula appears inhomogeneous but it should be noticed that the peak power P c expresses the electric output of a module under an irradiance of 1000W/m 2 and is not a SI unit. As I GPan expresses the annual solar irradiation in kwh/m 2, it can be assumed that it shows the number of hours that the modules will operate under a theoretical irradiance of 1000W/m 2. In other words, the PV installation will function this number of hours at its P c rating. Remarks: 1) The performance ratio PR represents the ratio of the electric output of the installation, or the electrical energy that is supplied to the grid (E a ) divided by the theoretical electrical energy produced by the PV installation (which is P c I GPan ) 2) The energy conversion output is calculated through the power peak P c, which depends on the surface and the output of the PV module under STC conditions (STC for Standard Test Condition, i.e. a radiance of 1000W/m², a temperature of 25 C and a solar spectrum AM1.5) 3) The above formula is usable only if the electric power output of the PV installation is a linear function of the irradiance, which is not completely true in real-world conditions, but it is sufficient for a quick assessment. To obtain better precision on the produced PV energy, it is necessary to use a simulation software, such as PVsyst or PVSOL that will take into account this nonlinearity. Similarly, it is possible to modify this formula for other time intervals, like a month or a day (in energy): E M (in kwh per month) = P c (W c ) I GPm (in kwh/m ² per month) PR (dimensionless)

22 E j (in kwh per day) = P c (W c ) I GPd (in kwh/m ² per day) PR (dimensionless) Likewise, it is possible to write this formula for one moment t, therefore the operating power P e from the radiance IGP (which is in W/m ²): P e (in kw) = P c (W c ) I GP (in kw/m ²) PR (dimensionless) Or P e (in W) = P c (W c ) I GP (in W/m ²) PR (dimensionless) Example of dimensioning assessment Previously, for the site of INES in Le Bourget du Lac, we calculated the global irradiation on a 30 inclined plane towards south. It is I GPan = 1452 kwh/m² per annum (equivalent to hours with a solar irradiation of 1 kw/m²). For a photovoltaic installation with a power peak of P c = 3 kw c (surface of 30 m² and 10% energy conversion losses), with the installation integrated on a roof and the performance ratio considered equal to 0.7. The annual photovoltaic production E a estimated is: Remark: E a = = kwh 1) The average consumption in specific electricity (without neither heating nor warm water) of a household in France is approximately 3000 kwh per annum, roughly equivalent to the electric production of a photovoltaic installation of 3 kw c. 2) The load factor (number of operating hours at nominal output of the installation, therefore the power peak) is 3049 kwh/3 kw = 1016 hours. This load factor depends on many parameters, the principal one being the solar irradiation. It varies from 800 hours in northern Europe to 1500 hours in southern Europe. The load factor is lower compared to that of wind, approximately 2000 hours, and that of the nuclear power plants, approximately 7000 hours. The better the load factor is, the closer the production of electricity is to the peak output installed. The load factors mentioned above for PV installations are not favourable for their economic profitability, which indicates that the initial investment per power unit will have to be low to remain competitive. Compatibility study between the photovoltaic field and the inverter The dimensioning of a photovoltaic installation usually begins by setting a certain photovoltaic modules number on the supporting mounts (building roof or site on the ground or structure) with a certain tilt and orientation. This process will determine the number of photovoltaic modules to be used, according to the available area, but also reveal the various possible wiring configurations of the modules (number of modules per string and number of strings). The number of photovoltaic modules per string and the number of strings condition the electric output, but also the voltage and the current at exit of the photovoltaic

23 installation. External parameters, such as the solar irradiance and the ambient temperature, should also be taken into account. The inverter connected to the photovoltaic field has operating ranges for input and output voltage, current and power, all of which will have to be compatible with the electric production of the photovoltaic field and the specifications of the load/grid. Compatibility in Power: Due to the fact that solar irradiance under the European latitudes goes up to approximately 1000 W/m² and that the performance ratio generally is about 0.8, the inverter's power is usually selected to fall between 80% and 100% of the photovoltaic field's power peak. To ideally estimate the power of the inverter correctly, the power bar chart at exit of the photovoltaic field is required. This bar chart can be simulated by specialized software, like PVsyst. Let us examine two examples: Example 1. Figure 31 shows the power bar chart of a 3.18 kw c PV field, facing south on a 30 tilt, in Geneva (Swiss). Figure 31 Power bar chart of a 3.18 kwc PV field, facing south on a 30 tilt, in Geneva (Swiss). If the dimensioning of the inverter is equal to 80% of the field's power peak, which is 2.55 kw, the bar chart shows that the plant is under-dimensioned because the power of the field between 2.55 kw and 3 kw is not fully used. It would be more judicious to choose an inverter of 3 kw or 3.2 kw (close to the 100% of power peak of this field).

24 Example 2. Figure 32 shows the power bar chart of a 3.18 kw c PV field, facing south on a 90 tilt, in Geneva (Swiss). Figure 32 : Power bar chart of a 3.18 kwc PV field, facing south on a 90 tilt, in Geneva (Swiss). If the dimensioning of the inverter is equal to 100% of the power peak of the field, that is to say 3.2 kw, it can be seen in Figure 32 that the plant is over-dimensioned because the field does not deliver any power between 2.5 kw and 3.2 kw. It would have been more judicious to choose an inverter of 2.4 to 2.5 kw that is capable of taking advantage of the field's full output. Thus, the ideal is to know the power bar chart, but that is not always possible. Generally, an inverted equal to 80% of the field's power peak is used when the conditions of tilt and orientation are unfavourable (vertical, eastern or western orientation), the average ambient temperatures are rather high and there are conditions of poor solar irradiation, such as in downtown area (pollution) or at the coastline. Similarly, inverters rated at 100% of the field's power peak are selected when the conditions of tilt and orientation are favourable, the average ambient temperatures rather low and there are good solar irradiation conditions, such as in the countryside. It will be perhaps even necessary to over dimension an inverter in locations where the sky is very clear, such as high in the mountains (lower atmosphere density, less pollution, low average temperature and an high albedo). Compatibility in current intensity: The solar irradiation from a clear sky is about 800 to 900 W/m², but under certain conditions with a strong direct radiance and an overcast sky of white clouds (important diffusion), the

25 solar radiance can reach 1300 W/m² for a few minutes some times per annum. Although that is not detrimental for the inverter if it features over current protection, it is recommended to have a safety margin on the acceptable maximum current intensity of the inverter (attention to the fuses of protection that also have to be over dimensioned to avoid having to change them too often. Usually, the ideal is to have a 30% margin (according to the country's legislative recommendations) compared to the STC operation conditions of the photovoltaic modules. Compatibility in no-load voltage: Without any grid voltage, the inverter is disconnected and therefore the current intensity is zero. However, the inverter remains connected to the PV field, where now the voltage is the highest possible. The worst case scenario for the maximum voltage at the input of the inverter needs to take into account that the solar irradiance might reach up to 1300 W/m². This voltage must remain lower than the maximum acceptable voltage by the PV inverter, or there is a risk of damaging it. This is one of the leading causes of inverters breakdowns, especially when the high no-load voltage has not been checked in mountain installations). For that reason, it is recommended to have a safety margin on the maximum no-load voltage, ideally 15% compared to the photovoltaic modules STC conditions (according to the countries legislative recommendations). The photovoltaic modules usually have a maximum operating voltage, often about 1000 volts (check the characteristics of the photovoltaic modules). This value allows to calculate how many modules it is possible to put in a single serial string. Compatibility in operating voltage: Under operation, the inverter adjusts the point of operation at the boundaries of the photovoltaic field to seek the point where the power is maximum (MPPT), selecting the best possible pair of voltage and current intensity. The selected pair varies according to the solar radiance and the cell temperature of the photovoltaic modules. The current intensity under operation varies between zero and the maximum, whereas the operating voltage will vary between a U pvmin value (as soon as the irradiance reaches some tens of W/m²) and a maximum U pvmax value (for a strong irradiation). For good compatibility between the photovoltaic field and the inverter, these two voltage values must be within the V mppt-min and V mppt-max voltages of the photovoltaic inverter (see the electric characteristics of PV inverter). Software such as PVsyst or PVSOL make it possible to simulate all of the operation points of the voltage, current intensity (and, thus, power) over a year. The output can be hourly, using

26 an average weather file, allowing to check compatibility between the PV field and the photovoltaic inverter. For a summary check out, it is possible to take the following conditions: V mppt-min inverter < 80% of the typical STC voltage of the PV field V mppt-max inverter > 115% of the typical STC voltage of the PV field Explanation: 80% of typical STC voltage of the PV field represents the voltage of the PV field for a radiance of 100 W/m² (for a silicon crystalline PV field) and 130% of the typical STC voltage of the PV field represents the voltage of the PV field for a radiance of 1300 W/m² (for a silicon crystalline PV field). Dimensioning example of a small photovoltaic installation Let us assume that we have a roof upon which we want to install PV modules. Eight Photowatt PW modules (Figure 33) can fit on the roof. Figure 33 :Photowatt PW module characteristics. These eight photovoltaic modules are connected to a SMA Sunny Boy 1700 inverter (Figure 34).

27 Figure 34 : SMA Sunny Boy 1700 inverter characteristics By choosing a wiring of two strings in parallel with four modules in series per string attached to the inverter (Figure 35), let us see if this combination is compatible or not. Figure 35 :Two strings in parallel with four modules in series per string attached to an inverter. Let us check the various points: Power check: The photovoltaic installation includes eight Photowatt PW Wc modules, so the total peak power is 1880 W c. The inverter SMA Sunny Boy 1700 has a maximum power input of 1850 Watts. The ratio inverter/field power is equal to 0.98, is between 0.8 and 1 (adapted for a photovoltaic field in good conditions, typically tilted to 30 and directed towards the south). Thus, the selection is OK in terms of power. Current intensity check: The amperage output of the PV installation in the worst case scenario is equal to the typical intensity (STC conditions) multiplied by two (because there are two strings in parallel) and again multiplied by 1.3 (assuming a radiance of 1300 W/m²). This equals to 7.86 A =

28 20.43 A. The maximum current input of the inverter is 12.6 A, which is lower than the current produced by the photovoltaic field. Thus there is a problem with the current intensity. No-load voltage check: The no-load voltage of a module is 37.2 V (STC conditions). With a radiance of 1300W/m², this no-load voltage is 37.2 V 1.15 = V. Knowing that the maximum voltage of the circuit cannot exceed 1000 VDC, thus 1000 V/42.78 V = 23.37, so we can have a maximum kf 23 PV modules in series. In our case, we have only four modules in series. With four PV modules in series, the maximum voltage of the photovoltaic field is 37.2 V = V. This value is lower than the maximum input voltage of the inverter that is 400V. Thus, the maximum voltage no load voltage is OK. Typical voltage operation (MPPT point) check: The typical voltage (not MPPT) of a module is 29.9V (STC conditions). With four PV modules in series and a radiance varying from 100 W/m² to 1,300 W/m², the voltage under operation of the photovoltaic field varies from 29.9V = V to = V. As the operating range of the inverter varies between 147V with 320V, the output voltage of the photovoltaic field is too low for the inverter. Thus, there is a problem with the MPPT operation voltage. To conclude this example of wiring in parallel two strings of four modules each and connecting them to a specific SMA inverter, this combination is not compatible. The voltage is too low and the current too high. A solution would be to seek another inverter or to change the type of the photovoltaic modules, but an obvious solution would be to change the wiring of two strings of four modules into a single string of eight modules in series, increasing the voltage and reducing the current output of the PV field. Let us investigate whether this association is compatible. Power check: The same as before. Thus, the selection is OK in terms of power. Current intensity check: The amperage output of the PV installation in the worst case scenario is equal to the typical intensity (STC conditions and only one string) multiplied by 1.3 (Radiance of 1300 W/m²),

29 which is 7.86 A 1.3 = A. The input current of the inverter is 12.6 A, which is higher than the current produced by the photovoltaic field. Thus, the current intensity is OK. No-load voltage check: The no-load voltage of a module is 37.2 V (STC conditions). With a radiance of 1300W/m², this no-load voltage is 37.2 V 1.15 = V. Knowing that the maximum voltage of the circuit cannot exceed 1000V DC, thus 1000 V/42.78 V = 23.37, so we can have a maximum kf 23 PV modules in series. In our case, we have only eight modules in series. With eight PV modules in series, the maximum no load voltage of the photovoltaic field is 37.2V = V. This value is lower than the maximum input voltage of the inverter that is 400V. Thus, the maximum voltage no load voltage is OK. Typical voltage operation (MPPT point) check: The typical voltage (not MPPT) of a module is 29.9V (STC conditions). With eight PV modules in series and a radiance varying from 100 W/m² to 1300 W/m², the voltage under operation of the photovoltaic field varies from 29.9V = V to = V. As the operating range of the inverter varies between 147V with 320V, the output voltage of the photovoltaic field is compatible with the inverter. Thus, there is no problem with the MPPT operation voltage. Therefore, with the wiring of the eight modules Photowatt in series at the input of an SMA Sunny Boy 1700 inverter, this configuration is compatible. The most important point to check is not to exceed the maximum voltage at the input of the inverter because that can be destructive for the inverter. For the other cases, generally the risk is only to have a lower production than that expected. In this example, compared to the point of operation under STC conditions (radiance of 1000 W/m², spectrum AM1.5 and temperature of 25 C), the maximum intensity is taken with a factor of 1.3, the maximum voltage is taken with a factor of 1.15, and the minimum voltage with a factor of 0.8. These factors are relatively arbitrary but make it possible to simplify the study. For different studies, these variations are calculated by using the temperature coefficients of the photovoltaic module while varying the temperature (e.g. from 0 C to 70 C). This method gives results rather similar to the factors described before. On the other hand, an experienced engineer should be able to realistically adapt these factors for various conditions, such as a desert or the mountain landscape with extreme temperatures and radiances. For the compatibility check between the PV field and the inverter, inverter manufacturers often provide free software..

30 Figure 36 : PV field to inverter compatibility check software (Source: SMA Sunny Design software) Bibliography Weiss, Johnny. "Photovoltaics Design and Installation Manual." (2007): Balfour, John R., and Michael Shaw. Advanced photovoltaic system design. Jones & Bartlett Publishers, 2011.

GRID-CONNECTED SOLAR PV SYSTEMS. Design Guidelines for Accredited Installers NO BATTERY STORAGE. January 2013 (Effective 1 February 2013)

GRID-CONNECTED SOLAR PV SYSTEMS. Design Guidelines for Accredited Installers NO BATTERY STORAGE. January 2013 (Effective 1 February 2013) GRID-CONNECTED SOLAR PV SYSTEMS NO BATTERY STORAGE Design Guidelines for Accredited Installers January 2013 (Effective 1 February 2013) These guidelines have been developed by Clean Energy Council. They

More information

Traditional PWM vs. Morningstar s TrakStar MPPT Technology

Traditional PWM vs. Morningstar s TrakStar MPPT Technology Traditional PWM vs. Morningstar s TrakStar MPPT Technology Introduction: Morningstar MPPT (Maximum Power Point Tracking) controllers utilize Morningstar s own advanced TrakStar Maximum Power Point Tracking

More information

Traditional PWM vs Morningstar s TrakStar MPPT Technology

Traditional PWM vs Morningstar s TrakStar MPPT Technology Traditional PWM vs Morningstar s TrakStar MPPT Technology Morningstar s MPPT charge controllers use our patented TrakStar advanced control MPPT algorithm to harvest maximum power from a Solar Array s peak

More information

Application Note: String sizing Conext CL Series

Application Note: String sizing Conext CL Series : String sizing Conext CL Series 965-0066-01-01 Rev A DANGER RISK OF FIRE, ELECTRIC SHOCK, EXPLOSION, AND ARC FLASH This Application Note is in addition to, and incorporates by reference, the installation

More information

Engineering Thesis Project. By Evgeniya Polyanskaya. Supervisor: Greg Crebbin

Engineering Thesis Project. By Evgeniya Polyanskaya. Supervisor: Greg Crebbin Simulation of the effects of global irradiance, ambient temperature and partial shading on the output of the photovoltaic module using MATLAB/Simulink and ICAP/4 A report submitted to the School of Engineering

More information

Understanding Solar Energy Teacher Page

Understanding Solar Energy Teacher Page Understanding Solar Energy Teacher Page Photovoltaic Power Output & I-V Curves Student Objective The student: will be able to determine the voltage, current and power of a given PV module given the efficiency,

More information

CP /240-MC4 User Manual

CP /240-MC4 User Manual CP-250-60-208/240-MC4 User Manual Chilicon Power LLC Jan 2014 1 CONTENTS Important Safety Instructions... 3 Safety Instructions... 3 CP-250 Microinverter System Introduction... 4 Inverter Label Information...

More information

Your Origin SLIVER system will be supplied with one of the following sets of panels:

Your Origin SLIVER system will be supplied with one of the following sets of panels: SLIVER3000 Solar System Panel Specifications Your Origin SLIVER system will be supplied with one of the following sets of panels: Manufacturer Mono Or Poly Size (Watts) Panels Required To Achieve Minimum

More information

How to Evaluate PV Project Energy Yield

How to Evaluate PV Project Energy Yield How to Evaluate PV Project Energy Yield There are three main characteristics of a PV module that could affect the real energy generation of a PV plant: Temperature coefficient; Low light performance; IAM

More information

BETTER DESIGN BETTER MATERIALS BETTER PROCESSES BETTER MODULES

BETTER DESIGN BETTER MATERIALS BETTER PROCESSES BETTER MODULES BETTER DESIGN BETTER MATERIALS BETTER PROCESSES BETTER MODULES TM FULL RANGE OF CERTIFIED MODULES Mono Crystalline Watt to 50 Watt Poly (Multi) Crystalline Watt to 80 Watt Glass Cells High Efficiency A-Grade

More information

EDC Lecture Notes UNIT-1

EDC Lecture Notes UNIT-1 P-N Junction Diode EDC Lecture Notes Diode: A pure silicon crystal or germanium crystal is known as an intrinsic semiconductor. There are not enough free electrons and holes in an intrinsic semi-conductor

More information

Understanding Potential Induced Degradation for LG NeON Model

Understanding Potential Induced Degradation for LG NeON Model Understanding Potential Induced Degradation for LG NeON Model Table of Contents 2 CONTENTS 1. Introduction 3 2. PID Mechanism 4 3. LG NeON model PID Characterization 5 4. Description 7 6. Test Result 11

More information

Understanding Temperature Effects on Crystalline PV Modules

Understanding Temperature Effects on Crystalline PV Modules Understanding Temperature Effects on Crystalline PV Modules The following is a discussion on temperature and how it affects solar module voltages and power output. This is particularly important in solar-battery

More information

PORTABLE LED FLASHER WITH IMPLEMENTED BYPASS DIODE TESTER

PORTABLE LED FLASHER WITH IMPLEMENTED BYPASS DIODE TESTER PORTABLE LED FLASHER WITH IMPLEMENTED BYPASS DIODE TESTER Daniel Schär 1, Franz Baumgartner ZHAW, Zurich University of Applied Sciences, School of Engineering, IEFE www.zhaw.ch/~bauf, Technikumstr. 9,

More information

Installation requirements

Installation requirements Installation requirements for SUNNY CENTRAL 500U 1 Contents This document describes the requirements which have to be observed for the installation site of the Sunny Central 500U. The installation and

More information

DC PV Arc fault detection Unit

DC PV Arc fault detection Unit DC PV Arc fault detection Unit Installation, usage and other information Author: Peter v. Galen, Product Manager Date: 15-09-2014 Revision: B 1. Introduction The National Electrical Code 2011 states arc-fault

More information

We are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists. International authors and editors

We are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists. International authors and editors We are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists 4, 116, 12M Open access books available International authors and editors Downloads Our authors

More information

APS M1P Single-phase Micro-inverter Installation and User Manual

APS M1P Single-phase Micro-inverter Installation and User Manual APS M1P Single-phase Micro-inverter Installation and User Manual Version: 2.0 ALTENERGY POWER SYSTEM, INC. All rights reserved 1 Contact Information ALTENERGY POWER SYSTEM Inc. 1 Yatai Road, Jiaxing, PR

More information

Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable

Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable TECHNICAL BRIEF Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable Overview This technical brief presents voltage rise guidelines for dedicated PV branch circuits and methods for calculating

More information

7P Series - Surge Protection Device (SPD) Features 7P P P

7P Series - Surge Protection Device (SPD) Features 7P P P Features 7P.09.1.255.0100 7P.01.8.260.1025 7P.02.8.260.1025 SPD Type 1+2 Surge arrester range - single phase system / three phase system Surge arresters suitable in low-voltage applications in order to

More information

CHAPTER 3 CUK CONVERTER BASED MPPT SYSTEM USING ADAPTIVE PAO ALGORITHM

CHAPTER 3 CUK CONVERTER BASED MPPT SYSTEM USING ADAPTIVE PAO ALGORITHM 52 CHAPTER 3 CUK CONVERTER BASED MPPT SYSTEM USING ADAPTIVE PAO ALGORITHM 3.1 INTRODUCTION The power electronics interface, connected between a solar panel and a load or battery bus, is a pulse width modulated

More information

PV Array Commissioning and Troubleshooting with the Solmetric PV Analyzer

PV Array Commissioning and Troubleshooting with the Solmetric PV Analyzer PV Array Commissioning and Troubleshooting with the Solmetric PV Analyzer April 11, 2013 Paul Hernday Senior Applications Engineer paul@solmetric.com cell 707-217-3094 Review of I-V Curves I-V and P-V

More information

APS M1P Single-phase Micro-inverter Installation and User Manual

APS M1P Single-phase Micro-inverter Installation and User Manual APS M1P Single-phase Micro-inverter Installation and User Manual Version: 1.0 ALTENERGY POWER SYSTEM, INC. All rights reserved 1 Contact Information ALTENERGY POWER SYSTEM Inc. 1 Yatai Road, Jiaxing, PR

More information

Achieving accurate measurements of large DC currents

Achieving accurate measurements of large DC currents Achieving accurate measurements of large DC currents Victor Marten, Sendyne Corp. - April 15, 2014 While many instruments are available to accurately measure small DC currents (up to 3 A), few devices

More information

Measurements and simulations of the performance of the PV systems at the University of Gävle

Measurements and simulations of the performance of the PV systems at the University of Gävle FACULTY OF ENGINEERING AND SUSTAINABLE DEVELOPMENT Department of Building, Energy and Environmental Engineering Measurements and simulations of the performance of the PV systems at the University of Gävle

More information

Shade Matters. Peter Hoberg Solmetric Corporation

Shade Matters. Peter Hoberg Solmetric Corporation Shade Matters Peter Hoberg Solmetric Corporation Shade Matters Shade s impact on PV production Cell, module, string, array Example measurements Characterizing shade Why measure shade? Shade measurement

More information

Tel Fax

Tel Fax MAXIMUM POWER POINT TRACKING PERFORMANCE UNDER PARTIALLY SHADED PV ARRAY CONDITIONS Roland BRUENDLINGER ; Benoît BLETTERIE ; Matthias MILDE 2 ; Henk OLDENKAMP 3 arsenal research, Giefinggasse 2, 2 Vienna,

More information

Type EN180-MS EN185-MS EN190-MS EN195-MS EN200-MS 13.5 A. Container Capacity Multiple Packing 40 feet (GP) 700 pcs / 28 pallets

Type EN180-MS EN185-MS EN190-MS EN195-MS EN200-MS 13.5 A. Container Capacity Multiple Packing 40 feet (GP) 700 pcs / 28 pallets Quality criteria and certificates IEC 61215, IEC 61730, CE-Certification, ISO 9001 and ILB-ISO 14001 Tolerance of nominal power (PMPP) 0+5%; classification range is ±2.5W 10 years product-warranty 5 years

More information

CHAPTER-3 Design Aspects of DC-DC Boost Converter in Solar PV System by MPPT Algorithm

CHAPTER-3 Design Aspects of DC-DC Boost Converter in Solar PV System by MPPT Algorithm CHAPTER-3 Design Aspects of DC-DC Boost Converter in Solar PV System by MPPT Algorithm 44 CHAPTER-3 DESIGN ASPECTS OF DC-DC BOOST CONVERTER IN SOLAR PV SYSTEM BY MPPT ALGORITHM 3.1 Introduction In the

More information

Modelling and simulation of PV module for different irradiation levels Balachander. K Department of EEE, Karpagam University, Coimbatore.

Modelling and simulation of PV module for different irradiation levels Balachander. K Department of EEE, Karpagam University, Coimbatore. 6798 Available online at www.elixirpublishers.com (Elixir International Journal) Electrical Engineering Elixir Elec. Engg. 43 (2012) 6798-6802 Modelling and simulation of PV module for different irradiation

More information

Home CSP Inc. Trackers and electronics for home solar energy

Home CSP Inc. Trackers and electronics for home solar energy Home CSP Inc. Trackers and electronics for home solar energy www.homecsp.com csp@homecsp.com TinyTracker version 1.06 reve Thanks for purchasing your TinyTracker from Home CSP Inc. The TinyTracker provides

More information

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY Approximation based on the know-how of SEMAN S.A. The non-linear nature of modern electric loads makes the reception of measures for the confrontation

More information

BIPV System Performance under the Microscope: Analysis of High-Resolution Data

BIPV System Performance under the Microscope: Analysis of High-Resolution Data BIPV System Performance under the Microscope: Analysis of High-Resolution Data A. Driesse 1* and S. Harrison 2 1 Dept. of Electrical Engineering, Queen s University, Kingston, Ontario, K7L 3N6, Canada

More information

Optional Features. Linear Performance Warranty 10 Years product warranty 25 Years linear performance warranty

Optional Features. Linear Performance Warranty 10 Years product warranty 25 Years linear performance warranty Those who dream of a better future can help lead to a more meaningful and enriched world. As a leading solar module manufacturer in Korea, we never stop to achieve competitiveness through differentiation,

More information

CHAPTER 3 MODELLING OF PV SOLAR FARM AS STATCOM

CHAPTER 3 MODELLING OF PV SOLAR FARM AS STATCOM 47 CHAPTER 3 MODELLING OF PV SOLAR FARM AS STATCOM 3.1 INTRODUCTION Today, we are mostly dependent on non renewable energy that have been and will continue to be a major cause of pollution and other environmental

More information

TEST REPORT IEC 61215: nd Edition Crystalline Silicon Terrestrial Photovoltaic (PV) Modules - Design Qualification and Type Approval

TEST REPORT IEC 61215: nd Edition Crystalline Silicon Terrestrial Photovoltaic (PV) Modules - Design Qualification and Type Approval Test Report issued under the responsibility of: TEST REPORT IEC 61215: 2005 2nd Edition Crystalline Silicon Terrestrial Photovoltaic (PV) Modules - Design Qualification and Type Approval Report Reference

More information

LOCATION BASE-MONTHWISE ESTIMATION OF PV MODULE POWER OUTPUT BY USING NEURAL NETWORK WHICH OPERATES ON SPATIO-TEMPORAL GIS DATA

LOCATION BASE-MONTHWISE ESTIMATION OF PV MODULE POWER OUTPUT BY USING NEURAL NETWORK WHICH OPERATES ON SPATIO-TEMPORAL GIS DATA IMPACT: International Journal of Research in Engineering & Technology (IMPACT: IJRET) ISSN(E): 2321-8843; ISSN(P): 2347-4599 Vol. 2, Issue 6, Jun 2014, 133-142 Impact Journals LOCATION BASE-MONTHWISE ESTIMATION

More information

Design and Development of Solar Roof Top PV Power Systems

Design and Development of Solar Roof Top PV Power Systems RESEARCH ARTICLE Design and Development of Solar Roof Top PV Power Systems Y. Pradeep Kumar 1, V.Tejaswitha 2 1 Assistant Professor, Dept. of ECE, Madanapalle Institute of Technology & Science, Madanapalle,

More information

Chapter 4. Impact of Dust on Solar PV Module: Experimental Analysis

Chapter 4. Impact of Dust on Solar PV Module: Experimental Analysis Chapter 4 Impact of Dust on Solar PV Module: Experimental Analysis 53 CHAPTER 4 IMPACT OF DUST ON SOLAR PV MODULE: EXPERIMENTAL ANALYSIS 4.1 INTRODUCTION: On a bright, sunny day the sun shines approximately

More information

An Interleaved High-Power Fly back Inverter for Photovoltaic Applications

An Interleaved High-Power Fly back Inverter for Photovoltaic Applications An Interleaved High-Power Fly back Inverter for Photovoltaic Applications S.Sudha Merlin PG Scholar, Department of EEE, St.Joseph's College of Engineering, Semmencherry, Chennai, Tamil Nadu, India. ABSTRACT:

More information

Teacher Page. Understanding Solar Energy. Photovoltaic Power Output & I-V Curves. Student Objective

Teacher Page. Understanding Solar Energy. Photovoltaic Power Output & I-V Curves. Student Objective Understanding Solar Energy Teacher Page Photovoltaic Power Output & I-V Curves Student Objective The student: current and power of a given PV module will be able to determine the size of the array necessary

More information

14.2 Photodiodes 411

14.2 Photodiodes 411 14.2 Photodiodes 411 Maximum reverse voltage is specified for Ge and Si photodiodes and photoconductive cells. Exceeding this voltage can cause the breakdown and severe deterioration of the sensor s performance.

More information

Proposed test procedure for the laboratory characterisation of gridconnected

Proposed test procedure for the laboratory characterisation of gridconnected Proposed test procedure for the laboratory characterisation of gridconnected micro-inverters. Mac Leod, B., Vorster, FJ., van Dyk, EE. Nelson Mandela Metropolitan University Centre for Renewable and Sustainable

More information

Active: Active probes achieve low input capacitance and high sensitivity by buffering and amplifying the signal close to the point of measurement.

Active: Active probes achieve low input capacitance and high sensitivity by buffering and amplifying the signal close to the point of measurement. Application Note Pico Technology offers many s covering a wide range of voltages, category (CAT) ratings and bandwidths. As the name suggests, these probes have two major features: Active: Active probes

More information

Fast IC Power Transistor with Thermal Protection

Fast IC Power Transistor with Thermal Protection Fast IC Power Transistor with Thermal Protection Introduction Overload protection is perhaps most necessary in power circuitry. This is shown by recent trends in power transistor technology. Safe-area,

More information

Voltage Control of Hybrid Photovoltaic/ Battery Power System for Low Voltage DC Micro grid

Voltage Control of Hybrid Photovoltaic/ Battery Power System for Low Voltage DC Micro grid Voltage Control of Hybrid Photovoltaic/ Battery Power System for Low Voltage DC Micro grid Aalborg University Institute of Energy Technology DRAGOS OVIDIU OLTEANU 0 P a g e Master Thesis Voltage Control

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) Elgar TerraSAS 1kW-1MW Programmable Solar Array Simulator Simulate dynamic irradiance and temperature ranging from a

More information

CHAPTER-2 Photo Voltaic System - An Overview

CHAPTER-2 Photo Voltaic System - An Overview CHAPTER-2 Photo Voltaic System - An Overview 15 CHAPTER-2 PHOTO VOLTAIC SYSTEM -AN OVERVIEW 2.1 Introduction With the depletion of traditional energies and the increase in pollution and greenhouse gases

More information

APPENDIX V PRODUCT SHEETS

APPENDIX V PRODUCT SHEETS National Institutes of Health Building 37 Modernization Bethesda, Maryland APPENDIX V PRODUCT SHEETS Katie L. McGimpsey Mechanical Option 1 of 4 BP 4160 160-Watt Monocrystalline Photovoltaic Module The

More information

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017 Ref: ART-B22-D70, ART-B22-D125, ART-B22-D175, ART-B22-D300 Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and

More information

Fault Evolution in Photovoltaic Array During Night-to-Day Transition

Fault Evolution in Photovoltaic Array During Night-to-Day Transition Fault Evolution in Photovoltaic Array During Night-to-Day Transition Ye Zhao, Brad Lehman Department of Electrical and Computer Engineering Northeastern University Boston, MA, US zhao.ye@husky,neu.edu

More information

Aggravation with voltage?

Aggravation with voltage? Voltage Regulator Aggravation with voltage? At photovoltaic plants, long lines or increasing energy consumption?...then the voltage regulator can help Quick regulation from 300-700 ms Regulation of each

More information

Dr E. Kaplani. Mechanical Engineering Dept. T.E.I. of Patras, Greece

Dr E. Kaplani. Mechanical Engineering Dept. T.E.I. of Patras, Greece Innovation Week on PV Systems Engineering and the other Renewable Energy Systems. 1-10 July 2013, Patras, Greece Dr E. Kaplani ekaplani@teipat.gr Mechanical Engineering Dept. T.E.I. of Patras, Greece R.E.S.

More information

STAND ALONE SOLAR TRACKING SYSTEM

STAND ALONE SOLAR TRACKING SYSTEM STAND ALONE SOLAR TRACKING SYSTEM Rajendra Ghivari 1, Prof. P.P Revankar 2 1 Assistant Professor, Department of Electrical and Electronics Engineering, AITM, Savagaon Road, Belgaum, Karnataka, (India)

More information

Secure your solar investment. inside. 1OO % transparency = 1OO % performance.

Secure your solar investment. inside. 1OO % transparency = 1OO % performance. Secure your solar investment inside 1OO % transparency = 1OO % performance www.sunsniffer.de www.sunsniffer.de page 2 Why 1OO % transparency? With a solar energy system, anybody can produce environmentally

More information

The Nanosolar Utility Panel An Overview of the Solar Panel and its Advantages. May 2010

The Nanosolar Utility Panel An Overview of the Solar Panel and its Advantages. May 2010 May 2010 The Nanosolar Utility Panel 1 Designed for Utility-Scale Performance The Nanosolar Utility Panel is specifically designed for utility-scale systems. Engineered to reduce totalsystem cost, the

More information

Effect of Temperature and Irradiance on Solar Module Performance

Effect of Temperature and Irradiance on Solar Module Performance OS Journal of Electrical and Electronics Engineering (OS-JEEE) e-ssn: 2278-1676,p-SSN: 2320-3331, olume 13, ssue 2 er. (Mar. Apr. 2018), PP 36-40 www.iosrjournals.org Effect of Temperature and rradiance

More information

Spectrally Selective Sensors for PV System Performance Monitoring

Spectrally Selective Sensors for PV System Performance Monitoring Spectrally Selective Sensors for PV System Performance Monitoring Anton Driesse, Daniela Dirnberger, Christian Reise, Nils Reich Fraunhofer ISE, Freiburg, Germany Abstract The main purpose of PV system

More information

FJB/IFB enclosures Photovoltaic string protection and monitoring enclosures for solar parks from 8 to 32 strings

FJB/IFB enclosures Photovoltaic string protection and monitoring enclosures for solar parks from 8 to 32 strings Enclosed products and solutions FJB/IFB enclosures enclosures for solar parks from 8 to 32 strings new The solution for > High-power photovoltaic installations (large buildings, fields, solar parks ranging

More information

The Basics of Insulation Testing

The Basics of Insulation Testing The Basics of Insulation Testing Feature by Jim Gregorec IDEAL Industries, Inc. What Is Insulation Testing? In a perfect world, all the electrical current sent along a conductive wire would reach its intended

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

Test Report. File No.: SHV04007/15-02 Test Report No.: , P.R. China

Test Report. File No.: SHV04007/15-02 Test Report No.: , P.R. China Applicant... : Manufacturer... : Order No.... : Zhejiang ERA Solar Technology Co., Ltd. Sihai Road, Huangyan Economic Development Zone, Taizhou, Zhejiang 318020, P.R. China Zhejiang ERA Solar Technology

More information

TESTING OF SMART PV MODULES

TESTING OF SMART PV MODULES TESTING OF SMART PV Daniel Gfeller, Urs Muntwyler, Christian Renken, Luciano Borgna Berne University of Applied Sciences (BFH), Engineering and Information Technology Photovoltaic Laboratory (PV-Lab),

More information

LOW VOLTAGE CONVERTER WITH THREE POINT GALVANIC INSULATION

LOW VOLTAGE CONVERTER WITH THREE POINT GALVANIC INSULATION EN K09LV LOW VOLTAGE CONVERTER WITH THREE POINT GALVANIC INSULATION General Description The K09LV instrument is a three points galvanic insulator, with input on high sensitivity voltage, and active output.

More information

Analog Electronic Circuits

Analog Electronic Circuits Analog Electronic Circuits Chapter 1: Semiconductor Diodes Objectives: To become familiar with the working principles of semiconductor diode To become familiar with the design and analysis of diode circuits

More information

(2) New Standard IEEE P (3) Core : (4) Windings :

(2) New Standard IEEE P (3) Core : (4) Windings : (d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.

More information

WDBR Series (RoHS compliant)

WDBR Series (RoHS compliant) WDBR Series (RoHS compliant) This new range of thick film planar power resistors on steel, offering high pulse withstand capability, compact footprint and low profile, to many demanding applications including

More information

CHAPTER 7 MAXIMUM POWER POINT TRACKING USING HILL CLIMBING ALGORITHM

CHAPTER 7 MAXIMUM POWER POINT TRACKING USING HILL CLIMBING ALGORITHM 100 CHAPTER 7 MAXIMUM POWER POINT TRACKING USING HILL CLIMBING ALGORITHM 7.1 INTRODUCTION An efficient Photovoltaic system is implemented in any place with minimum modifications. The PV energy conversion

More information

Installation/User Manual

Installation/User Manual Installation/User Manual APS YC500-A Photovoltaic Grid-connected Inverter Version 4.1 1/15 APS America 1015 Hostmark St. Ste 104; Poulsbo, WA 98370 TEL: 206-855-5100 EMAIL: info@apsamerica.com WEB: www.apsamerica.com

More information

Common Mode Susceptibility of Computers

Common Mode Susceptibility of Computers Common Mode Susceptibility of Computers White Paper #9 Revision 1 Executive Summary This White Paper examines and challenges the claims made in literature regarding the alleged high susceptibility of computers

More information

SolarEdge Export Limitation Application Note

SolarEdge Export Limitation Application Note SolarEdge Export Limitation Application Note Europe and APAC Version 2.3 Disclaimers Disclaimers Important Notice Copyright SolarEdge Inc. All rights reserved. No part of this document may be reproduced,

More information

Performance of SolarPod TM Crown Dr. Mouli Vaidyanathan, PhD PE, Eagan Minnesota 55123

Performance of SolarPod TM Crown Dr. Mouli Vaidyanathan, PhD PE, Eagan Minnesota 55123 Performance of SolarPod TM Crown Dr. Mouli Vaidyanathan, PhD PE, Eagan Minnesota 55123 Contents Contents... 1 Introduction:... 1 Purpose:... 1 Literature Review:... 2 Procedure:... 3 Field case 1 (SolarPod

More information

Rec. ITU-R F RECOMMENDATION ITU-R F *

Rec. ITU-R F RECOMMENDATION ITU-R F * Rec. ITU-R F.162-3 1 RECOMMENDATION ITU-R F.162-3 * Rec. ITU-R F.162-3 USE OF DIRECTIONAL TRANSMITTING ANTENNAS IN THE FIXED SERVICE OPERATING IN BANDS BELOW ABOUT 30 MHz (Question 150/9) (1953-1956-1966-1970-1992)

More information

Characterization and Analysis of Photovoltaic Modules and the Solar Resource Based on In-Situ Measurements in Southern Norway Georgi Hristov Yordanov

Characterization and Analysis of Photovoltaic Modules and the Solar Resource Based on In-Situ Measurements in Southern Norway Georgi Hristov Yordanov Characterization and Analysis of Photovoltaic Modules and the Solar Resource Based on In-Situ Measurements in Southern Norway Georgi Hristov Yordanov Supervisor: Prof. Ole-Morten Midtgård (NTNU) Co-supervisor:

More information

Comparative Study of P&O and InC MPPT Algorithms

Comparative Study of P&O and InC MPPT Algorithms American Journal of Engineering Research (AJER) e-issn : 2320-0847 p-issn : 2320-0936 Volume-02, Issue-12, pp-402-408 www.ajer.org Research Paper Open Access Comparative Study of P&O and InC MPPT Algorithms

More information

Power quality measurements in a singlehouse

Power quality measurements in a singlehouse 24th International Conference & Exhibition on Electricity Distribution (CIRED) 12-15 June 2017 Session 2: Power quality and electromagnetic compatibility Power quality measurements in a singlehouse microgrid

More information

Solar Simulation Standards and QuickSun Measurement System. Antti Tolvanen Endeas Oy

Solar Simulation Standards and QuickSun Measurement System. Antti Tolvanen Endeas Oy Solar Simulation Standards and QuickSun Measurement System Antti Tolvanen Endeas Oy 1 Endeas in Brief QuickSun Solar Simulators Technology invented 1996 in Fortum (www.fortum.com) Endeas Oy licenses technology

More information

CoolBLUE Inductive Absorbers NaLA Noise Line Absorbers

CoolBLUE Inductive Absorbers NaLA Noise Line Absorbers CoolBLUE Inductive Absorbers NaLA Noise Line Absorbers Motor Bearing Solution from MH&W International Corp. http://www.coolblue-mhw.com Variable Frequency Motor Drive Systems 1. What is the problem 2.

More information

Earthing of Electrical Devices and Safety

Earthing of Electrical Devices and Safety Earthing of Electrical Devices and Safety JOŽE PIHLER Faculty of Electrical Engineering and Computer Sciences University of Maribor Smetanova 17, 2000 Maribor SLOVENIA joze.pihler@um.si Abstract: - This

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current transducer ITC 2000-S/SP2 N = 2000 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Bipolar and insulated

More information

EC T34 ELECTRONIC DEVICES AND CIRCUITS

EC T34 ELECTRONIC DEVICES AND CIRCUITS RAJIV GANDHI COLLEGE OF ENGINEERING AND TECHNOLOGY PONDY-CUDDALORE MAIN ROAD, KIRUMAMPAKKAM-PUDUCHERRY DEPARTMENT OF ECE EC T34 ELECTRONIC DEVICES AND CIRCUITS II YEAR Mr.L.ARUNJEEVA., AP/ECE 1 PN JUNCTION

More information

U, W, and Y -- MULTIPLE LEG STARBARS, SILICON CARBIDE HEATING ELEMENTS

U, W, and Y -- MULTIPLE LEG STARBARS, SILICON CARBIDE HEATING ELEMENTS U, W, and Y -- MULTIPLE LEG STARBARS, SILICON CARBIDE HEATING ELEMENTS GENERAL DESCRIPTION Made of high density recrystallized silicon carbide, these multiple leg Starbars use the same hot zone and cold

More information

Extraction of Maximum Power from Photovoltaic Array under Partial Shading Conditions

Extraction of Maximum Power from Photovoltaic Array under Partial Shading Conditions Extraction of Maximum Power from Photovoltaic Array under Partial Shading Conditions http://dx.doi.org/10.3991/ijes.v2i2.3660 Aswathy Kanth SNS college of Engineering, Coimbatore, India Abstract The efficiency

More information

Large Area Steady State Solar Simulator - Apollo

Large Area Steady State Solar Simulator - Apollo AllReal APOLLO series steady-state solar simulator are AAA class which is the highest class on the world. AllReal APOLLO solar simulators designed with specific optical technology by tandem Xenon lamps,

More information

TECHNICAL DATA SHEET. smartflower POP. As of: August 2015 Typing and printing errors reserved.

TECHNICAL DATA SHEET. smartflower POP. As of: August 2015 Typing and printing errors reserved. TECHNICAL DATA SHEET smartflower POP. TECHNICAL DATA POWER OUTPUT Nominal output Output through 2-axle tracking POP 2.31 kwp* 3.400 5.700 kwp/a** SYSTEM Modultype Modul power output warranty Module product

More information

Precautions to be considered for use of surge arresters tested according to Class 1 of IEC

Precautions to be considered for use of surge arresters tested according to Class 1 of IEC DATA SHEET No. 1 December 2000 Issued by the French Lightning Protection Association Precautions to be considered for use of surge arresters tested according to Class 1 of IEC 61643-1 Foreword: The protection

More information

CHAPTER 5 MPPT OF PV MODULE BY CONVENTIONAL METHODS

CHAPTER 5 MPPT OF PV MODULE BY CONVENTIONAL METHODS 85 CHAPTER 5 MPPT OF PV MODULE BY CONVENTIONAL METHODS 5.1 PERTURB AND OBSERVE METHOD It is well known that the output voltage and current and also the output power of PV panels vary with atmospheric conditions

More information

Tel: Fax:

Tel: Fax: Grid Tie Solar Inverter Operator's Manual SG-4000 1 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS To reduce the risk of electrical shock and to ensure safe installation and operation of Grid Tie

More information

TYPE SE and TSE, SILICON CARBIDE SPIRAL HEATING ELEMENTS

TYPE SE and TSE, SILICON CARBIDE SPIRAL HEATING ELEMENTS TYPE SE and TSE, SILICON CARBIDE SPIRAL HEATING ELEMENTS GENERAL DESCRIPTION The spiral Starbars are made of special high-density reaction-bonded silicon carbide. A spiral slot in the hot zone reduces

More information

CONTROL OF HARMONICS AND PERFORMANCE ANALYSIS OF A GRID CONNECTED PHOTOVOLTAIC SYSTEM

CONTROL OF HARMONICS AND PERFORMANCE ANALYSIS OF A GRID CONNECTED PHOTOVOLTAIC SYSTEM CONTROL OF HARMONICS AND PERFORMANCE ANALYSIS OF A GRID CONNECTED PHOTOVOLTAIC SYSTEM Rangy Sunny 1, Robins Anto 2 M.Tech Student, Amal Jyothi College of Engineering, Kanjirapally, Kerala, India 1 Asst.

More information

Low performing modules do not limit the string

Low performing modules do not limit the string Voltage = key performance indicator Low performing modules do not limit the string Referring to Paper: Defect Analysis of installed PV-Modules IR-Thermography and In-String Power Measurement, Bavarian

More information

CLOSE-UP EXAMINATION OF PERFORMANCE DATA FOR A GRID-CONNECTED PV SYSTEM

CLOSE-UP EXAMINATION OF PERFORMANCE DATA FOR A GRID-CONNECTED PV SYSTEM CLOSE-UP EXAMINATION OF PERFORMANCE DATA FOR A GRID-CONNECTED PV SYSTEM Anton Driesse, Steve Harrison 2, and Praveen Jain Department of Electrical Engineering, Queen s University, Kingston, Canada 2 Department

More information

Performance Evaluation of Solar Home Systems in Hot Climate Condition: mc-si PWM versus a-si MPPT Charge Controller System

Performance Evaluation of Solar Home Systems in Hot Climate Condition: mc-si PWM versus a-si MPPT Charge Controller System ก ก 2 2729 ก ก 2549 Performance Evaluation of Solar Home Systems in Hot Climate Condition: mcsi PWM versus asi MPPT Charge Controller System Wuthipong Suponthana 1, *, Nipon Ketjoy 2, Wattanapong Rakwichian

More information

Performance of high-eciency photovoltaic systems in a maritime climate

Performance of high-eciency photovoltaic systems in a maritime climate Loughborough University Institutional Repository Performance of high-eciency photovoltaic systems in a maritime climate This item was submitted to Loughborough University's Institutional Repository by

More information

Growatt 2000TL. Input Data Max. DC power Max. DC voltage. PV voltage range MPPT. Full load MPP-Voltage range

Growatt 2000TL. Input Data Max. DC power Max. DC voltage. PV voltage range MPPT. Full load MPP-Voltage range Growatt 2000TL Maximum efficiency of 97% and wide inpunt voltage range Internal DC switch Transformerless GT topology Compact design Multi MPP controller MTL - String Bluetooth / RF technology / ZigBee

More information

60 cell LG300N1K-G4. Key Features. High Power Output. Enhanced Performance Warranty. Outstanding Durability. Aesthetic Roof

60 cell LG300N1K-G4. Key Features. High Power Output. Enhanced Performance Warranty. Outstanding Durability. Aesthetic Roof EN LG300N1K-G4 60 cell LG s new module, NeON 2 Black, adopts Cello technology. Cello technology replaces 3 busbars with 12 thin wires to enhance power output and reliability. NeON 2 Black demonstrates

More information

PV Charger System Using A Synchronous Buck Converter

PV Charger System Using A Synchronous Buck Converter PV Charger System Using A Synchronous Buck Converter Adriana FLORESCU Politehnica University of Bucharest,Spl. IndependenŃei 313 Bd., 060042, Bucharest, Romania, adriana.florescu@yahoo.com Sergiu OPREA

More information

SOLARONIX. Solixon A-1525-V

SOLARONIX. Solixon A-1525-V SOLARONIX Solixon A-1525-V Based on Solaronix' exclusive light engine, our solar simulation equipment delivers a perfect and continuous artificial sunlight 24/7, allowing for accurate stability and performance

More information

Investigation of the Performance of a Large PV system

Investigation of the Performance of a Large PV system FACULTY OF ENGINEERING AND SUSTAINABLE DEVELOPMENT Department of Building, Energy and Environmental Engineering Investigation of the Performance of a Large PV system Júlia Solanes Bosch June 217 Student

More information

Characterisation of a Photovoltaic Module

Characterisation of a Photovoltaic Module Characterisation of a Photovoltaic Module Name MMU ID Unit Leader Subject Unit code Course Mohamed Alsubaie 09562211 Dr. Nader Anani Renewable Power Systems 64ET3901 BEng (Hons) Computer and Communication

More information