Contents. All Rights Reserved

Size: px
Start display at page:

Download "Contents. All Rights Reserved"

Transcription

1 Code of Practice 290 Issue 1 January 2004 Power Quality Contents 1 Introduction 2 Scope 3 Definitions 4 Elements of Power Quality 5 Power Quality Standards 6 Power Quality Measurement Standards 7 Practical application of standards 8 Documents Referenced 9 Keywords Appendices A to B Approved for issue by the Technical Policy Panel All Rights Reserved The copyright of this document, which contains information of a proprietary nature, is vested in Electricity North West Limited. The contents of this document may not be used for purposes other than that for which it has been supplied and may not be reproduced, either wholly or in part, in any way whatsoever. It may not be used by, or its contents divulged to, any other person whatsoever without the prior written permission of Electricity North West Limited. Electricity North West Limited. Registered in England & Wales. Registered No Registered Office: 304 Bridgewater Place, Birchwood Park, Warrington, WA3 6XG

2

3 Amendment No. Date 0 Issue 1 Amendment Summary Brief Description and Amending Action 05/01/04 Prepared by: D M Talbot. Authorised by the Standards Steering Group and signed on its behalf by: P. J. Whittaker. CP290.doc Issue 1 05/01/04 DMT CP290 Page i of i

4

5 POWER QUALITY 1. INTRODUCTION 1.1 This Code of Practice has been written to improve the understanding of power quality, and the practical application and interpretation of power quality standards. Electricity North West policy on power quality is detailed in EPD 290. This Code of Practice provides more detail on power quality standards and clarifies their relationship with industry standards and statutory requirements. It should be used as a reference for power quality and all power quality measurements with in Electricity North Wes must conform to this Code of Practice. 1.2 Power quality is an expression used to describe the deviation from a perfect power supply. A perfect power supply is one that is never interrupted, always within voltage and frequency tolerances and has a noise free sinusoidal waveform. 1.3 The types of disturbances that affect the power quality of supply are harmonics, supply interruptions (short and long term), flicker, under or over voltage. Each of these disturbances has different causes and effects. Some result from use of customers equipment, whilst others are a product of lightning strikes or system faults. 1.4 Disturbances can propagate up or down the system and could affect other customers. Customers who are supplied from a shared network may experience similar power quality problems depending on the immunity of their equipment. 1.5 Measuring equipment is available to measure all aspects of power quality. Should a problem be identified after monitoring has been completed, then network reconfiguration, reinforcement, mitigation or conditioning can be considered to ensure the standards are met. 2. SCOPE This Code of Practice is to provide guidance on the application of power quality. It will describe the elements of power quality, its causes, effects, measurement and standards, and the practical application of these standards. 3. DEFINITIONS 3.1 ESQCR (2002) Electricity Supply, Quality and Continuity Regulation (2002). 3.2 EMC Electro-Magnetic Compatibility. 3.3 IEC International-technical Committee. 3.4 EN European Norm. 3.5 BS British Standard. 3.6 BS EN British Standard European Norm. 3.7 Distribution Code - Distribution Code of Licensed Distribution Network Operators of Great Britain. 3.8 ER Engineering Report. 3.9 ETR Engineering Technical Report RMS Root Mean Square. CP290.doc Issue 1 05/01/04 DMT CP290 Page 1 of 15

6 3.11 ENA Energy Networks Association DTI Department of Trade & Industry LV Low Voltage is defined in industry standards as a voltage whose upper limit of nominal rms value is 1kV, and in statutory requirements the definition is a voltage exceeding 50 volts but not exceeding 1000 volts MV Medium Voltage is only defined in industry standards as a nominal rms value that lies between 1kV and 35kV. Statutory requirements would consider the range of voltages quoted as part of the high voltage range and all references to mv should be considered as high voltage in this Code of Practice HV High Voltage is defined in industry standards as a nominal rms value that exceeds 35kV, whereas, in statutory requirements high voltage means any voltage exceeding LV. 4. ELEMENTS OF POWER QUALITY 4.1 Dips A sudden reduction or dip in the supply voltage is described by the duration of the retained voltage, i.e. the percentage of the supply voltage retained during the event. A dip is defined as a retained voltage of between 90% and 1% for between 10ms and 1 minute. A change in the supply voltage, resulting in a retained voltage of greater than 90% is not considered as a dip Voltage dips are unpredictable, random events and are caused by disturbances that occur on the system. The disturbances, which could be faults, can occur on all parts of the system and customer installations. Other dips may be caused by switching of large loads, such as starting of large motors. The propagation and frequency of dips will depend on the point at which the event occurred Most equipment manufactured should be resilient to some form of dips. However, some equipment may be more sensitive than others, such as electronic equipment (computers etc). It is possible to increase the resilience of electronic equipment to dips through re-design or specification. The resilience to dips is represented by the Information Technology Industry Council (ITIC) curve. Dips are plotted against the percentage of retained voltage and the duration. Dips that occur outside the boundary line are more like to cause a problem to electronic equipment. 4.2 Interruptions An interruption is when the voltage at the point of supply is lower than 1% of the nominal supply voltage A short interruption is up to three minutes duration and caused by a transient, permanent fault or outage. Transient faults will generally be in terms of seconds with the operation of reclosers. Although some customers initially affected by a permanent fault, may be restored by remote controlled switching within three minutes: assuming they are not within the faulty network A long interruption is greater than three minutes duration caused by a permanent fault or pre-planned outage. CP290.doc Issue 1 05/01/04 DMT CP290 Page 2 of 15

7 4.3 Flicker or Voltage Fluctuation Voltage fluctuations are changes in the voltage amplitude for a time, longer than the period of the voltage. Voltage fluctuations can occur once, several times, randomly or regularly. If the voltage fluctuation occurs at a frequency of approximately 0.005Hz 35Hz, a noticeable flicker will occur in electric lighting. This flicker will increase with the amplitude of the voltage fluctuation, but is also dependent on the frequency with which the voltage fluctuation occurs and on the type of lamp used The human eye is perceptive to this light flicker and the eye is more sensitive at a frequency of around 8Hz. However, once sensitised it may be difficult to satisfy a customer even though the flicker has been reduced Voltage fluctuation usually arises from rapidly changing customer loads, such as, resistance welders, arc furnaces and motor starting. 4.4 Harmonics Harmonic frequencies distort the sinusoidal supply waveform. The harmonic frequencies are integer multiples of the fundamental supply frequency. Using Fourier series analysis the individual frequency components of the distorted waveform can be described in terms of the harmonic order, magnitude and phase of each component. For example, with a fundamental supply frequency of 50Hz, then the 3 rd harmonic would be 150Hz and the 5 th Harmonic would be 250Hz Harmonics occur due to non-linear loads connected to the system. Typically, nonlinear loads are rectifiers, power supplies for electronic equipment and variable speed drives. These loads cause harmonic currents and when coupled with the network impedance result in harmonic voltages being produced Harmonic currents can cause increased loading of neutrals, overheating of transformers, nuisance tripping of circuit breakers, over-stressing of power factor correction capacitors and skin effect Neutral conductor over-heating In equally balanced three-phase systems with pure sinusoidal waveforms, then the current in the neutral will be zero. Some cable systems have been installed with half-sized neutral conductors with respect to the size of the phase conductors. However, the harmonics currents don t cancel out, in fact the odd multiples of three times the fundamental, the triple-n harmonics, add in the neutral conductor resulting in overheating Over-heating of transformers The eddy current losses increase with the square of the harmonic number. A transformer supplying computer equipment would have losses twice that of a transformer supplying an equivalent linear load. This may result in a higher operating temperature and a shorter transformer life Nuisance tripping of circuit breakers Customers may experience problems of nuisance tripping of circuit breakers caused by harmonics. The protection may not sum the high frequency components correctly, resulting in nuisance tripping CP290.doc Issue 1 05/01/04 DMT CP290 Page 3 of 15

8 4.4.7 Over-stressing of power factor correction capacitors It is possible for resonance to occur given the right combination of inductance, capacitance and harmonic frequency. When this happens, large voltages and currents are generated leading to catastrophic failure of the capacitor Skin effect High frequency harmonic currents flow on the outer surface of the conductor (350Hz and above), which causes additional losses and heating in the conductor Harmonic voltages cause voltage distortion, zero-crossing noise and over-heating of induction motors. Additional losses generated by harmonics cause induction motors to over-heat, which is similar to the problem previously identified with transformers. Electronic timers base their timing on zero-crossings. However, a distorted waveform may result in additional zero-crossings affecting the operation of these devices Inter-harmonics An inter-harmonic is a sinusoidal voltage whose frequency is not an integer multiple of the fundamental Experiments conducted previously in the UK have concluded that the most significant effect of inter-harmonics is on flicker levels. When the inter-harmonic voltage is superimposed on the supply voltage a beat frequency can be established. A beat frequency in the 8-10Hz range causes the most pronounced level of flicker. The level of inter-harmonic distortion necessary to cause flicker in excess of Pst = 1.0 is dependent upon the inter-harmonic frequency. Inter-harmonics with a frequency close to 40Hz or 60Hz and a magnitude above 0.1% of the fundamental voltage will result in values of Pst close to The levels of inter-harmonic necessary to distort the function of house hold electronic equipment is so high that the effects of flicker on lighting would be intolerable. Typically, the image on a TV screen only starts to experience distortion when the inter-harmonic magnitude reaches 1.5% and for other appliances (Hi Fi and PC) there was no noticeable reduction in output quality with inter-harmonics up to 5%. 4.5 Under Voltage and Over Voltage The voltage at the supply terminals shall comply with the ESQCR (2002). When the voltage is above the permitted variation it is referred to as an over voltage and below as an under voltage. 4.6 Voltage Unbalance The level of voltage unbalance in a three-phase system is expressed as a percentage between the rms values of the negative sequence component and the positive sequence component of the supply voltage. CP290.doc Issue 1 05/01/04 DMT CP290 Page 4 of 15

9 5. POWER QUALITY STANDARDS 5.1 Background European Directives are prepared by the European Commission to ensure consistency of approach and promote free trade within the European Union. The EMC Directive is supported by IEC EMC standards. CENELEC is the European standards making body and they have used the IEC standards to produce the EN standards. The British standards are based on the EN standard, resulting in a BS EN being produced. The IEC also produces Technical reports to clarify issues Once an IEC standard has been issued it is normally adopted as a BS EN. There is no requirement to adhere to an IEC standard, but if adopted as a BS EN then the standard is mandatory. All BS EN standards referenced are IEC and/or EN standards with the same numeric reference The Electricity Distribution Licence makes reference to the Distribution Code. The Distribution Code requires compliance with the ESQCR (2002) and specific Engineering Recommendations. The Engineering Recommendations make reference back to IEC and BS EN standards Other relevant documents, which focus on practical aspects of power quality, include ETR and ACE reports produced by the ENA. 5.2 Standards The BS EN series of standards and planning levels assist in achieving adequate power quality and in controlling it. While BS EN defines power quality in terms of voltage characteristics that can be supplied under normal conditions. Planning levels exist to limit disturbance levels exceeding compatibility levels and conversely immunity levels should remain above these compatibility levels. Figure 1: Summary of relationships between planning, compatibility and immunity levels. Probability Density Total supply network Compatibility Level Planning levels Immunity (test) levels Immunity levels of local equipment Disturbance CP290.doc Issue 1 05/01/04 DMT CP290 Page 5 of 15

10 Figure 1, shows the probability density disturbance of the total supply network on the left side, while on the right the levels of equipment immunity to these disturbances. Generally, planning levels limit network disturbances exceeding the compatibility level. Immunity levels are set above the compatibility level to ensure functionally of equipment. The compatibility level is the point at which the disturbance will affect the functionally of equipment IEC/BS EN series: Electromagnetic Compatibility (EMC) Part 1 covers general considerations, fundamental principles, definitions and terminology of EMC Part 2 deals with classifications of electromagnetic environment and compatibility levels Part 3 details emission and immunity limits for terminating equipment Part 4 defines testing and measurement techniques used to assess equipment compliance to emissions and immunity to disturbances Part 5 describes installation and mitigation guidelines for building installation systems Part 6 contains generic immunity and emission standards for residential, commercial and industrial environments BS EN 50160: Voltage Characteristics of Electricity Supplied by the Public Distribution Systems The limits quoted in BS EN are in general more in line with compatibility levels and as such the Distribution Code shall be followed for distribution planning and power quality. Where the Distribution Code does not cover a power quality element then the limits set in BS EN should be used. Appendix A summarises the power quality standards, Engineering Recommendations and regulations and the compliance standards are highlighted in bold BS EN does not apply to abnormal conditions, as stated below. Conditions arising as a result of a fault or a temporary supply arrangement adopted to keep customers supplied during maintenance and construction work or to minimise the extent and duration of a loss of supply. In cases of non-compliance of a customer s installation or equipment with the relevant standards or with the technical requirements for connection of loads, established by the electricity supplier (with in the UK this is interpreted as the Distribution Network Operator). In cases of non-compliance of a generator installation with the relevant standards or with the technical requirements for interconnection with an electricity distribution system established by the electricity supplier (e.g. embedded generation). In exceptional situations outside the electricity supplier s control, as outlined in CP290.doc Issue 1 05/01/04 DMT CP290 Page 6 of 15

11 5.2.4 Voltage Harmonisation 5.3 The Distribution Code The CENELEC group responsible for voltage harmonisation has decided to extend the transition period for the tolerances in HD472 S1: Nominal voltage for low voltage public electricity supply voltage up to 1 January This means that the low-voltage tolerances for the UK will remain at 230 volts +10 % -6% until 1 January The Electricity Distribution Licence refers to the Distribution Code, which requires compliance with the ESQCR 2002 for frequency and voltage. While, for voltage disturbances and harmonic distortion then Engineering Recommendations P28, P29 and G5/4 shall be followed In other cases of variations and disturbances to the voltage, then the Distribution Code makes reference to Sections 2 and 3 of BS EN ESQCR (2002) ESQCR (2002) defines a frequency of 50Hz and low voltage supply of 230V with a permitted variation of ±1% for frequency and +10% or 6% for voltage, ±6% for high voltage operating below 132kV, but ±10% for high voltage operating at 132kV or above There is no clear guidance in the ESQCR (2002) on how these quantities are measured and under what operating conditions. BS EN shall be referred to when carrying out measurements of these quantities under normal operating conditions. The 10 minute mean rms value is dedicated to slow variations within the limits and voltages outside of these limits are categorised as either a voltage dip, flicker or over voltage and should be excluded from the 10 minute rms value The ESQCR (2002) refers to exceptional circumstances, but offers no clear explanation of this expression. BS EN should be used to interpret this statement as exceptional situations outside the electricity supplier s control, as stated below. Exceptional weather conditions and other natural disasters. Third party interference. Acts by public authorities. Industrial actions. Force majeure. Power shortages resulting from external events ESQCR (2002) permits the distributor to challenge the consumer in circumstances where connected equipment is causing unacceptable electrical interference on the distributors network. If after the expiry of the specified period the defective equipment has not been repaired or replaced, the distributor may disconnect the supply to the premises or other network or refuse to connect the supply until the problem is rectified. The distributor must restore the supply as soon as practical after the problem has been rectified. In cases where disputes cannot be resolved between the distributor and the consumer, the DTI inspector will investigate the circumstances and bring the dispute to a resolution. CP290.doc Issue 1 05/01/04 DMT CP290 Page 7 of 15

12 5.5 Engineering Recommendations and Technical Reports The power quality elements covered by engineering recommendation and technical reports are flicker, voltage unbalance, harmonics and inter-harmonics Flicker IEC Environment standards cover flicker for environment and compatibility levels. BS EN : Compatibility levels for low frequency conducted disturbance and signalling in public low voltage power supply systems. BS EN : Compatibility levels in industrial plant for low frequency conducted disturbances. BS EN : Compatibility levels for low frequency conducted disturbances and signalling in public medium voltage power supply systems IEC Defines the emission and immunity limits for flicker. BS EN : Limitation of voltage changes, voltage fluctuations and flicker in public low voltage supply systems, for equipment with rated current <= 16A per phase and not subject to conditional connection. BS EN : Limitation of voltage changes, voltage fluctuations and flicker in public low voltage supply systems, for equipment with rated current <= 75A per phase and not subject to conditional connection. IEC TR/ : Limitation of voltage changes, voltage fluctuations and flicker in public low voltage supply systems, for equipment with rated current greater than 16A per phase ER P.28 Planning limits for voltage fluctuations caused by industrial, commercial and domestic equipment in the UK. ER P.28 deals with planning limits for voltage fluctuations caused by industrial, commercial and domestic equipment in the UK. Three IEC standards mainly underpin ER P.28. BS EN which applies to stage 1 assessment in P.28, BS EN which applies to stage 2 assessment in P28 and IEC TR/ which applies to HV connections stage 3 assessment in P28. ER P.28 interprets these standards and there is no requirement to make direct reference. CP290.doc Issue 1 05/01/04 DMT CP290 Page 8 of 15

13 5.5.2 Voltage unbalance IEC Environment standards cover voltage unbalance for environment and compatibility levels. BS EN : Compatibility levels for low frequency conducted disturbance and signalling in public low voltage power supply systems. BS EN : Harmonic Compatibility levels for public MV systems ER P29 - Planning limits for voltage unbalance Harmonics ER P29 deals with planning limits for voltage unbalance by industrial, commercial and domestic equipment in the UK. The levels are defined as a max of 1.3% for voltages up to 33kV and 1% for voltages not exceeding 132kV. For periods up to 1 minute the level may increase to 2% IEC Environment standards cover harmonics for environment and compatibility levels. BS EN : Limits for harmonic current emission (equipment input current to and including 16A per phase). BS IEC : Limitation of emissions of harmonic currents on low-voltage power supply systems for equipment with rated current greater than 16A. IEC/TR : Assessment of emission limits for distorting loads in MV and HV power systems ER G5/4 Planning limits for harmonic voltage distortion and the connection of non-linear equipment to transmission systems and distribution networks in the UK. ER G5/4 deals with planning limits for harmonic voltage distortion caused by non-linear loads. Three IEC standards mainly underpin ER P.28. BS EN which applies to LV connections (stage 1 G5/4), BS EN which applies to stage 2 (G5/4) and IEC TR which applies to HV connections (stage 3 G5/4). ER G5/4 interprets these standards and there is no requirement to directly reference these standards. ETR 122: Guide to the application of engineering recommendation G5/4 planning levels for harmonic distortion and the connection of non-linear load to supply systems in the UK. ETR 122 was published in December It provides guidance on the use of G5/4 in assessing the connection of non-linear loads. CP290.doc Issue 1 05/01/04 DMT CP290 Page 9 of 15

14 5.5.4 Appendix A: Summary of Elements of Power Quality and relating standards highlights the standards, Engineering Recommendations and regulations, which must be followed for power quality compliance and measurement. 6. POWER QUALITY MEASUREMENT STANDARDS 6.1 Measurement standards BS EN : Testing and measurement techniques Power quality measurement methods. This standard defines, in detail, the performance requirements for instruments for all types of disturbances for both compliance and indicative purposes BS EN : General guide on harmonics and inter-harmonics measurements and instrumentation, for power supply systems and equipment connected thereto. This standard defines measurement instruments for harmonic testing BS EN : Flickermeter Functional and design specifications Basic EMC publication. This standard gives the functional and design specification for flicker measurement BS EN 50160: Voltage characteristics of electricity supplied by public distribution systems. EN50160 details how the measurement should be carried out (period etc) The table in Appendix A highlights the standards, Engineering Recommendations and regulations, which must be followed for power quality compliance and measurement. 6.2 Instrument Classification Type A instrument Type A instruments are used where precise measurements are required in cases of verifying compliance with standards and resolving disputes Any Type A instrument must produce matching results within the specified accuracy This type of instrument must be used when providing voltage recordings, whether orally or written, to the customer or third party for compliance with power quality limits Type B instrument Type B instruments are used for surveys and troubleshooting where high accuracy is not required The manufacturer specifies the accuracy and aggregation method to be used for Type B instruments Reference should be sought to BS EN , BS EN , BS EN , BS EN 50160, ER P28, ER P29 and ER G5/4 when carrying out power quality measurements relating to compliance of standards and disputes. CP290.doc Issue 1 05/01/04 DMT CP290 Page 10 of 15

15 7. PRACTICAL APPLICATION OF STANDARDS Planning levels are set above compatibility levels to achieve adequate power quality. Connection of new loads should be checked against these planning levels. Connected loads should have been checked originally against these planning levels. The investigation of a voltage complaint may show that equipment has been connected without approval and should be checked against planning levels. 7.1 Network Design and connection of new loads Network design and connection of new loads must be carried out to the guidance within EPD Any measurements should be carried out in accordance with BS EN and a type A instrument to BS EN Connected loads Voltage complaints When a customer contacts Electricity North Wes to complain of under/over voltage, frequency or voltage distortion then initial investigations will be carried out to determine whether power quality limits have been breached (limits outlined in Appendix A) Corrective actions may be possible to restore some of the power quality elements back within limits without network reinforcement or further investigations. The supply voltage may be corrected through reconfiguring the network, by adjusting transformer tappings, and/or transferring loads to other feeders or phases (refer to ER P29 for voltage unbalance). High impedance or poor connections within the network can cause voltage fluctuations or flicker and attempts should be made to check all available connections by a suitable authorised person Network referral A network referral will be required should these attempts prove unsuccessful or unnecessary due to the nature of the power quality problem. In such cases, a Network Referral form must be completed in full and accompanied by supporting documentation (voltage chart etc). Any reconfiguration of the network should be included in the interim measures already applied on the network referral form together with any further supporting documentation carried out after the completion of these measures It is advisable to locate the source and treat the power quality problem at source, which is more effective than network reconfiguration or reinforcement. It may be useful to carry out investigations, under the referral process, to discover the source or cause of the voltage distortion through the aid of a type B indicative instrument. In all cases, once the source has been located, a type A instrument, must be used to verify the power quality limits. CP290.doc Issue 1 05/01/04 DMT CP290 Page 11 of 15

16 7.3 Enforcement The consumer may be challenged if the connected equipment is causing unacceptable electrical interference on the network. Every effort should be made to work with the consumer to identify the equipment causing the disturbance, explain the problems this equipment is causing to other consumers and discuss possible solutions. The supply may be disconnected under the due process of the ESQCR (2002), which is outlined in section 5.4.4, if the consumer is unwilling to realise a solution. 7.4 Practical Measurements It is important to use the correct type of instrument, as detailed in BS EN , BS EN , BS EN , and use BS EN50160 to determine how the measurements should be carried out and limits that should be used for compliance as outlined in Appendix A. Frequency ESQCR (2002) Voltage ESQCR (2002) Voltage Dips BS EN Flicker ER P28 Harmonics & inter-harmonics ER G5/4 Interruptions BS EN Voltage unbalance ER P The supply voltage, shall be measured by the type of instrument specified in BS EN , e.g. A type A instrument must measure the rms of 10 cycles for 50Hz systems with an accuracy of ± 0.1%. The instrument should be connected for a week and measure at 10 minute intervals (BS EN 50160). The supply voltage shall be measured as outlined in BS EN50160 and be within the limits specified in the ESQCR (2002). This philosophy can be applied to other power quality limits in that measurement should be carried out as outlined in BS EN Type A Instrument A type A instrument must be used when challenging a customer s complaint or for providing recorded data to a customer or third party, either orally or written. A type A instrument should be used in preference to a type B instrument, when a type B instrument has indicated the limits are close to being or have just been breached. It is important that in these situations a high accuracy type A instrument is used Type B Instrument A type B instrument is the only instrument to be used for indicative purposes or troubleshooting only. Consideration must be given when interpreting the recorded data and the accuracy of the instrument before carrying out a solution. On no account must the recorded data be released to a customer or third party, either orally or written. It may be that in some cases the limits are breached, but the instrument shows them within limits and in other cases the opposite may apply Existing instruments CP290.doc Issue 1 05/01/04 DMT CP290 Page 12 of 15

17 7.5 Instrument accuracy Existing instruments that are outside the accuracy of a type A or B instrument may continue to be used until 1 st February Table 1 shows the variation of a voltage measurement at the upper and lower limits based on the accuracy of the measuring instrument. In situations where the supply voltage is around the voltage limits specified in the ESQCR (2002), then the actual voltage may be within the limits, but the instrument being used may record the voltage out of limits. This can result in unnecessary network reconfiguration or even network reinforcement and it is advisable to use a type A instrument (± 0.1%) in these cases. This philosophy can be applied to other power quality limits and measurements To verify compliance with power quality limits, once a solution has been implemented, further monitoring should be carried out by a type A instrument. Table 1: Voltage Measurement Instrument Accuracy Voltage limits (LV) -6% +10% 1% % % % % % % Instrument suppliers Any new power quality instrument purchased should be compared against either a type A or B instrument as detailed in BS EN and be able to carry out power quality measurements to BS EN The instrument type is dependent on the application as is detailed in section 6.2. Appendix B includes a list of power quality instrument manufacturers, but users should be aware that these instruments may be supplied to customers through third party electronic equipment suppliers. It should be noted that this is not a list of approved suppliers or an indication that the instruments they supply are either of type A or type B. It is the responsibility of the individual approving the purchase of an instrument or instruments to confirm compliance with the standards outlined. In addition, consideration should be given to the environment, downloading data (laptop or flashcard), interpretation and display of data (i.e. software, to BS EN501160) and service support. Assistance may be sought, if required, from the Power Quality & Development Manager, Policy and Standards, Asset Management. CP290.doc Issue 1 05/01/04 DMT CP290 Page 13 of 15

18 8. DOCUMENTS REFERENCED 8.1 The Electricity Safety, Quality and Continuity Regulations 2002 (ESQCR). 8.2 Electricity Distribution Licence. 8.3 The Distribution Code of Licensed Distribution Network Operators of Great Britain. 8.4 BS EN 50160: Voltage characteristics of public electricity distribution networks. 8.5 Engineering Recommendation P28: Planning limits for voltage fluctuations caused by industrial, commercial and domestic equipment in the United Kingdom. 8.6 Engineering Recommendation P29: Planning limits for voltage unbalance in the United Kingdom for 132kV and below. 8.7 Engineering Recommendation G5/4: Planning levels for harmonic voltage distortion and the connection of non-linear equipment to transmission and distribution systems in the United Kingdom. 8.8 HD472 S1: Nominal voltage, for low-voltage public electricity supply voltage. 8.9 BS EN Environment 8.10 BS EN : Compatibility levels for low frequency conducted disturbance and signalling in public low voltage power supply systems BS EN : Compatibility levels in industrial plant for low frequency conducted disturbances BS EN : Compatibility levels for low frequency conducted disturbances and signalling in public medium voltage power supply systems BS EN Limits 8.14 BS EN : Limits for harmonic current emission (equipment input current to and including 16A per phase) BS EN : Limitation of voltage changes, voltage fluctuations and flicker in public low voltage supply systems, for equipment with rated current <= 16A per phase and not subject to conditional connection BS IEC : Limitation of emissions of harmonic currents on low-voltage power supply systems for equipment with rated current greater than 16A IEC TR/ : Limitation of voltage changes, voltage fluctuations and flicker in public low voltage supply systems, for equipment with rated current greater than 16A per phase IEC/TR : Assessment of emission limits for distorting loads in MV and HV power systems BS EN : Limitation of voltage changes, voltage fluctuations and flicker In public low voltage supply systems, for equipment with rated current <= 75A per phase and not subject to conditional connection BS EN Testing and measurement techniques CP290.doc Issue 1 05/01/04 DMT CP290 Page 14 of 15

19 8.21 BS EN : Testing and measurement techniques General guide on harmonics and inter-harmonic measurements and instruments, for power supply systems and equipment connected thereto BS EN : Flickermeter Functional and design specifications Basic EMC publication BS EN : Testing and measurement techniques Power quality measurement methods BS EN Installation and mitigation guidelines BS EN Generic standards BS EN : Immunity for residential, commercial and light-industrial environments ETR 122: Guide to the application of engineering recommendation G5/4 planning levels for harmonic distortion and the connection of non-linear load to supply systems in the UK EPD 290: Power Quality. 9. KEYWORDS Compliance; ESQCR; Interruption; Licence; Measurement; Planning; System; Voltage CP290.doc Issue 1 05/01/04 DMT CP290 Page 15 of 15

20 APPENDIX A: SUMMARY OF ELEMENTS OF POWER QUALITY AND RELATING STANDARDS Elements of power quality Voltage Characteristics of electricity supplied by public distribution systems (BS EN 50160) Other relevant EN standards (Electromagnetic Compatibility) Regulations/Engineering Recommendations etc Measurement Standard Class Intervals Accuracy Range Frequency 50Hz ±1% for 99.5% of year 50Hz +4/-6 for 100% of time BS EN Hz, limits Hz, in exceptional circumstances could be 47-52Hz (Dist.Code), 50Hz ±1% (ESQCR) A BS EN B Man. Spec 10 sec ±0.01Hz Hz Man. Spec Hz Voltage Magnitude ±10% for 95% of week, 10 min (between +10/-15%) HD %/-6% LV, ±6% HV, ±10% for 132kV & above (ESQCR) A rms over 10 cycles BS EN B rms over period spec by Man. ±0.1% 0%- 200% ±0.5% 0%- 150% Voltage dips Retained Voltage: 90% to 1% Duration: 10ms 1 min. BS EN , BS EN , BS EN Reference to BS EN50160 (Dist. Code) BS EN A B Refer to BS EN Flicker Long term flicker severity 1 for 95% of time. BS EN (Pst <1 & Plt <0.65), BS EN (Pst <1 & Plt <0.65),BS EN Reference to P.28 (Dist. Code), P.28 Stage 2 Pst < 0.5, Stage 3 Pst <1 and Plt <0.8. BS EN A B BS EN None specified BS EN None specified 0-20 (Pst) None specified CP290.doc Issue 1 05/01/04 DMT CP290 Page A1 of 2

21 Harmonics 2 nd 2%, 3 rd 5%, 4 th 1%, 5 th 6%, 7 th 5%, 9 th 1.5%, 11 th 3.5%, 13 th 3%, 17 th 2%, 19 th & 23 rd 1.5%, (6 th,8 th,10 th,12 th,14 th,15 th,16 th,18 t h,20 th,21 st,22 nd &24 th all 0.5%) THD <= 8% (up to 40 th ) BS EN , BS EN , BS EN , BS EN , BS EN , BS EN Reference to G5/4 (Dist. Code) G5/4 400V THD 5%, 400V+ to 20kV THD 4%, 22kV to 400kV 3%. Percentage of harmonic voltage more stringent (increases higher the voltage) than EN50160 BS EN A B EN BS :2002, Class 1 Man. Spec EN BS :2002, Class 1 Man. Spec Twice values in BS EN , class 3 Man. Spec Interharmonics Level under consideration BS EN , BS EN , BS EN , BS EN , BS EN G5/4 Inter-harmonic frequency in Hz and Voltage distortion as %. <80Hz 0.2%, 80Hz 0.2%, 90Hz 0.5%, >90 & < % BS EN A EN BS :2002, Class 1 EN BS :2002, Class 1 Twice values in BS EN , class 3 B Man. Spec Man. Spec Man. Spec Interruptions Short duration : 3 min Long duration : > 3 min BS EN Short duration : 3 min Long duration : > 3 min (Ofgem) BS EN A B Refer to BS EN Voltage Unbalance 2% for 95% of 10 min rms of week, 3% in some areas BS EN , BS EN Reference to P.29 (Dist. Code) P.29 nominal levels of 1.3% up to 33kV and 1% 33kVto 132kV, short periods (1 minute) may reach 2% BS EN A B rms over 10 cycles, evaluated of sym. comps, see EN (±0.15% neg. and zero sequence) Man. Spec 0-5% CP290.doc Issue 1 05/01/04 DMT CP290 Page A2 of 2

22 APPENDIX B: POWER QUALITY INSTRUMENT SUPPLIERS Alpha Electronics Ametek Power Instruments AVO International Chauvin Arnoux UK Ltd Elcomponent Ltd Enercom Ltd Fluke (UK) Ltd IMH Technologies Ltd LEM HEME Ltd CP290.doc Issue 1 05/01/04 DMT CP290 Page B1 of 1

Southern Company Power Quality Policy

Southern Company Power Quality Policy Southern Company Power Quality Policy Alabama Power Georgia Power Gulf Power Mississippi Power i Table of Contents: Southern Company Power Quality Policy SCOPE AND PURPOSE... 1 DEFINITIONS... 2 I. HARMONICS...

More information

TS RES - OUTSTANDING ISSUES

TS RES - OUTSTANDING ISSUES TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next

More information

Roadmap For Power Quality Standards Development

Roadmap For Power Quality Standards Development Roadmap For Power Quality Standards Development IEEE Power Quality Standards Coordinating Committee Authors: David B. Vannoy, P.E., Chair Mark F. McGranghan, Vice Chair S. Mark Halpin, Vice Chair D. Daniel

More information

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax: POWER CORPORATION Power Quality Specifications and Guidelines for Customers Phone: 403-514-3700 Fax: 403-514-3719 1 GENERAL OVERVIEW........................................ 1.1 WHAT DOES THIS SPECIFICATION

More information

POWER QUALITY AND SAFETY

POWER QUALITY AND SAFETY POWER QUALITY AND SAFETY Date : November 27, 2015 Venue : 40 th IIEE Annual National Convention and 3E XPO 2015 PRESENTATION OUTLINE Power Quality I. INTRODUCTION II. GRID CODE REQUIREMENTS III. ERC RESOLUTION

More information

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC CITY OF LETHBRIDGE ELECTRIC ENGINEERING STANDARDS POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS The City of Lethbridge acknowledges the use of other utility industry and industry committee

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

Power quality report. A Manufacturing Plant

Power quality report. A Manufacturing Plant Power quality report Prepared for A Manufacturing Plant 6 May 2016 by Dr Angelo De Francesco Power Quality Consultant Page 1 Contents 1 EXECUTIVE SUMMARY... 4 2 INTRODUCTION... 5 2.1 SITE MONITORED...

More information

An Introduction to Power Quality

An Introduction to Power Quality 1 An Introduction to Power Quality Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation 3 Today s Presenter n Andy Sagl Megger

More information

Power Quality Report. A Manufacturing Plant

Power Quality Report. A Manufacturing Plant Power Quality Report Prepared for A Manufacturing Plant 6 May 2016 by Dr Angelo De Francesco Power Quality Consultant CHK Power Quality Pty Ltd Page 1 Contents 1 EXECUTIVE SUMMARY... 4 2 INTRODUCTION...

More information

Power Quality Summary

Power Quality Summary Power Quality Summary This article provides an overview of how voltage harmonic distortion is managed on the distribution network and focuses on the current at future issues surround the connection of

More information

Company Directive STANDARD TECHNIQUE: SD1E/2. Technical Requirements for Customer Export Limiting Schemes

Company Directive STANDARD TECHNIQUE: SD1E/2. Technical Requirements for Customer Export Limiting Schemes Company Directive STANDARD TECHNIQUE: SD1E/2 Technical Requirements for Customer Export Limiting Schemes Policy Summary This Standard Technique specifies the requirements for customer owned Export Limitation

More information

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment s Evaluating Methods, Power Quality and s Assessment regarding Voltage Dip Immunity of Equipment ANTON BELÁŇ, MARTIN LIŠKA, BORIS CINTULA, ŽANETA ELESCHOVÁ Institute of Power and Applied Electrical Engineering

More information

APPLICATION NOTE STANDARD EN VOLTAGE CHARACTERISTICS OF ELECTRICITY SUPPLIED BY PUBLIC ELECTRICITY NETWORKS

APPLICATION NOTE STANDARD EN VOLTAGE CHARACTERISTICS OF ELECTRICITY SUPPLIED BY PUBLIC ELECTRICITY NETWORKS APPLICATION NOTE STANDARD EN 50160 VOLTAGE CHARACTERISTICS OF ELECTRICITY SUPPLIED BY PUBLIC ELECTRICITY NETWORKS Antoni Klajn, Marta Bątkiewicz-Pantuła March 2013 ECI Available from www.leonardo-energy.org/node/145851

More information

ELECTRICITY ASSOCIATION SERVICES LIMITED 2001

ELECTRICITY ASSOCIATION SERVICES LIMITED 2001 ELECTRICITY ASSOCIATION SERVICES LIMITED 2001 All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical,

More information

Voltage characteristics of electricity supplied by public distribution networks

Voltage characteristics of electricity supplied by public distribution networks BRITISH STANDARD BS EN 50160:2007 Voltage characteristics of electricity supplied by public distribution networks The European Standard EN 50160:2007 has the status of a British Standard ICS 29.020; 29.240.01

More information

Draft Kenya Standard for Balloting Not to be Cited as Kenya Standard

Draft Kenya Standard for Balloting Not to be Cited as Kenya Standard KENYA STANDARD KS 2236-3:2010 ICS 03.120.10; 91.140.50 Electricity Supply Quality of supply Part 3: Voltage characteristics, compatibility levels, limits and assessment methods BALLOT DRAFT, MAY 2010 KEBS

More information

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION POWER QUALITY A N D Y O U R B U S I N E S S A SUMMARY OF THE POWER QUALITY REPORT PUBLISHED BY THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION H YDRO ONE NETWORKS INC SEPTEMBER 2014

More information

HPC-9DJ

HPC-9DJ Manual: Distribution Design Manual Volume 1 Quality of Electricity Supply Standard Number: HPC-5DC-07-0001-2012 Document Control Author Name: Anthony Seneviratne Position: Senior Standards Engineer Document

More information

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES Technical Requirements for Grid-Tied DERs Projects Division 6/29/2017 Contents 1 Definitions and Acronyms... 1 2 Technical Interconnection

More information

ETSI EN V1.2.1 ( )

ETSI EN V1.2.1 ( ) EN 300 132-3 V1.2.1 (2003-08) European Standard (Telecommunications series) Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 3: Operated by rectified

More information

Power Quality - 1. Introduction to Power Quality. Content. Course. Ljubljana, Slovenia 2013/14. Prof. dr. Igor Papič

Power Quality - 1. Introduction to Power Quality. Content. Course. Ljubljana, Slovenia 2013/14. Prof. dr. Igor Papič Course Power Quality - 1 Ljubljana, Slovenia 2013/14 Prof. dr. Igor Papič igor.papic@fe.uni-lj.si Introduction to Power Quality Content Session 1 Session 2 Session 3 Session 4 1st day 2nd day 3rd day 4th

More information

The development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08

The development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08 The development of the SA grid code on Power Quality emission Dr. Gerhard Botha 2017/08/08 Overview What is the Grid Code? What is Power Quality? Power Quality Management Principles Differences Challenges

More information

Power Analysis Summary

Power Analysis Summary Power Analysis Summary Introduction This is a summary of the power conditions measured with these setup parameters: Measurement File: C:\Users\fhealy\Documents\Fluke\Power Analyze\Core 2 Recording.odn

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission

More information

Immunity Testing for the CE Mark

Immunity Testing for the CE Mark Immunity Testing for the CE Mark Summary The European Union (EU) currently has 25 member countries with 2 additional countries to be added in 2007. The total population at that time will be nearly a half

More information

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality

More information

Understanding Harmonics

Understanding Harmonics Understanding Harmonics Terry Gaiser Sensus What Are Harmonics? 1 » What is Power Quality?» Power quality is the degree to which both the utilization and delivery of electric power affects the performance

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 9

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 9 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 9 POWER QUALITY Power quality (PQ) problem = any problem that causes

More information

Connection of Embedded Generating Plant up to 5MW

Connection of Embedded Generating Plant up to 5MW Engineering Recommendation No.3 of the Electricity Distribution Code Connection of Embedded Generating Plant up to 5MW Version 1.0 30th November 2005 Prepared by: Al Ain Distribution Company, Abu Dhabi

More information

Energy Networks Association

Energy Networks Association The Voice of the Networks Version 1 (ISSUED) Energy Networks Association Insert presentation title here ENA EREC P28 Issue 2 2018 Key Technical Modifications Grid Code and SQSS Mods Name Position Date

More information

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES C.E.T. Foote*, G.W. Ault*, J.R. McDonald*, A.J. Beddoes *University of Strathclyde, UK EA Technology Limited, UK c.foote@eee.strath.ac.uk

More information

POWER QUALITY MONITORING - PLANT INVESTIGATIONS

POWER QUALITY MONITORING - PLANT INVESTIGATIONS Technical Note No. 5 January 2002 POWER QUALITY MONITORING - PLANT INVESTIGATIONS This Technical Note discusses power quality monitoring, what features are required in a power quality monitor and how it

More information

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Single Phase

More information

A Guide to Power Quality Testing

A Guide to Power Quality Testing A Guide to Power Quality Testing Table of Contents What is power quality?... 3 Power quality phenomenon... 3 Under-voltage... 3 Over-voltage... 3 Voltage dips (sags) and swells... 4 Voltage dips (sags)...

More information

EN50160 Individual Report Summary

EN50160 Individual Report Summary EN50160 Individual Report Summary Power Frequency (x.1) Supply Voltage Variations (x.3.x) Rapid Voltage Changes (x.4.1) Flicker (x.4.2) Supply Voltage Dips (x.5) Short Interruption of Supply Voltage (x.6)

More information

Company Directive POLICY DOCUMENT: SD4/7. Relating to 11kV and 6.6kV System Design

Company Directive POLICY DOCUMENT: SD4/7. Relating to 11kV and 6.6kV System Design Company Directive POLICY DOCUMENT: SD4/7 Relating to 11kV and 6.6kV System Design Policy Summary This document describes the standard requirements for the design of the 11kV and 6.6kV systems. Reference

More information

SYNCHRONISING AND VOLTAGE SELECTION

SYNCHRONISING AND VOLTAGE SELECTION SYNCHRONISING AND VOLTAGE SELECTION This document is for Relevant Electrical Standards document only. Disclaimer NGG and NGET or their agents, servants or contractors do not accept any liability for any

More information

Fundamentals of Power Quality

Fundamentals of Power Quality NWEMS Fundamentals of Power Quality August 20 24, 2018 Seattle, WA Track D Anaisha Jaykumar (SEL) Class Content» Introduction to power quality (PQ)» Causes of poor PQ and impact of application» PQ characteristics»

More information

Power Quality Requirements for Connection to the Transmission System

Power Quality Requirements for Connection to the Transmission System Power Quality Requirements for Connection to the Transmission System Revision: 1.0 Date: September 2015 Introduction and Purpose of this Document The purpose of this document is to provide clarity to Customers

More information

Use only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at

Use only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at Reviewed: Sergey Kryuchkov Distribution Engineering Scott Merriman Distribution Standards Valentina Dabic Distribution Planning Warren Quan Distribution Operations, FVO Raj Solanki Distribution Engineering

More information

Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV)

Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV) Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV) IRR-DCC-MV 1. Introduction 1 IRR-DCC-MV 2. Scope 1 IRR-DCC-MV 2.1. General 1 IRR-DCC-MV 2.2. Affected

More information

LIMITS FOR TEMPORARY OVERVOLTAGES IN ENGLAND AND WALES NETWORK

LIMITS FOR TEMPORARY OVERVOLTAGES IN ENGLAND AND WALES NETWORK LIMITS FOR TEMPORARY OEROLTAGES IN ENGLAND AND WALES NETWORK This document is for internal and contract specific use only. Disclaimer NGG and NGET or their agents, servants or contractors do not accept

More information

Power Quality Issues from an EMC Point of View

Power Quality Issues from an EMC Point of View Power Quality Issues from an EMC Point of View Brian Jones BSc (Hons) C Eng MIEE MIEEE Overview What is EMC? How does it apply to power quality? The effects of equipment on power quality The effects of

More information

1. Introduction to Power Quality

1. Introduction to Power Quality 1.1. Define the term Quality A Standard IEEE1100 defines power quality (PQ) as the concept of powering and grounding sensitive electronic equipment in a manner suitable for the equipment. A simpler and

More information

EN 50160:2010 IMPROVEMENTS OF THE REVISED VERSION. TC8X System Aspects of Electricity Supply

EN 50160:2010 IMPROVEMENTS OF THE REVISED VERSION. TC8X System Aspects of Electricity Supply Joint Workshop CEER/ECRB EURELECTRIC on Voltage Quality Monitoring Brussels, 1 st October 2012 EN 50160:2010 IMPROVEMENTS OF THE REVISED VERSION Maurizio Delfanti Politecnico di Milano Dipartimento di

More information

Emicon Engineering Consultants L.L.C.

Emicon Engineering Consultants L.L.C. Emicon Engineering Consultants L.L.C. Power Quality Consulting & Solutions Presentation / Pre-Qualification Emicon, Specialised in Power Quality Consulting and Pollution Control on Electrical Network www.emiconconsultants.com

More information

Coupling modes. Véronique Beauvois, Ir Copyright 2015 Véronique Beauvois, ULg

Coupling modes. Véronique Beauvois, Ir Copyright 2015 Véronique Beauvois, ULg Coupling modes Véronique Beauvois, Ir. 2015-2016 General problem in EMC = a trilogy Parameters Amplitude Spectrum Source (disturbing) propagation Coupling modes Victim (disturbed) lightning electrostatic

More information

UNDERSTANDING POWER QUALITY

UNDERSTANDING POWER QUALITY Technical Note No. 1 June 1998 UNDERSTANDING POWER QUALITY This Technical Note describes the range of problems, what causes them, what they affect and what could be done to manage them. Integral Energy,

More information

Power Quality and Digital Protection Relays

Power Quality and Digital Protection Relays Power Quality and Digital Protection Relays I. Zamora 1, A.J. Mazón 2, V. Valverde, E. Torres, A. Dyśko (*) Department of Electrical Engineering - University of the Basque Country Alda. Urquijo s/n, 48013

More information

22.0 Harmonics in Industrial Power Systems

22.0 Harmonics in Industrial Power Systems 1.0 Harmonics in Industrial Power Systems Harmonic frequencies are multiples of the line (fundamental) frequency, which in North America is usually 60 Hz, while it is 50 Hz elsewhere. Figure 1 shows a

More information

Power Quality in Metering

Power Quality in Metering Power Quality in Metering Ming T. Cheng Directory of Asian Operations 10737 Lexington Drive Knoxville, TN 37932 Phone: (865) 218.5885 PQsynergy2012 www.powermetrix.com Focus of this Presentation How power

More information

Motors and drives. Module B- Introduction to input measurements

Motors and drives. Module B- Introduction to input measurements Motors and drives Module B- Introduction to input measurements Introduction to input measurements There are a number of locations where input measurements may be made Which is the most important location

More information

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron Power Quality and Circuit Imbalances 2015 Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron Summary of IEEE 1159 Terms Category Types Typical Duration

More information

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks 2014 Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks This document specifies the technical requirement for connecting sspv to the low voltage distribution

More information

HV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point

HV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point 2010 MAP Range HV / MV / LV electrical network quality analyzers Class A > Network quality Analyzers PRODUCT ADVANTAGES COMPLIANT with the EN 61000-4-30 standard, Class A DETECTION of the fault LOCATION

More information

INTERNATIONAL TELECOMMUNICATION UNION SERIES K: PROTECTION AGAINST INTERFERENCE

INTERNATIONAL TELECOMMUNICATION UNION SERIES K: PROTECTION AGAINST INTERFERENCE INTERNATIONAL TELECOMMUNICATION UNION ITU-T K.42 TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (05/98) SERIES K: PROTECTION AGAINST INTERFERENCE Preparation of emission and immunity requirements for

More information

Technical Requirements for Resistibility of Telecommunications Equipment to. Overvoltage and Overcurrent

Technical Requirements for Resistibility of Telecommunications Equipment to. Overvoltage and Overcurrent Technical Requirements for Resistibility of Telecommunications Equipment to Overvoltage and Overcurrent TR NO.189001 Edition 2.1 1st, April, 2015 Nippon Telegraph and Telephone Corporation Notice This

More information

This document is a preview generated by EVS

This document is a preview generated by EVS TECHNICAL SPECIFICATION IEC TS 62749 Edition 1.0 2015-04 colour inside Assessment of power quality Characteristics of electricity supplied by public networks IEC TS 62749:2015-04(en) THIS PUBLICATION IS

More information

Wind Power Facility Technical Requirements CHANGE HISTORY

Wind Power Facility Technical Requirements CHANGE HISTORY CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical

More information

Suppliers' Information Note. BT Metallic Path Facility. Interface Description

Suppliers' Information Note. BT Metallic Path Facility. Interface Description SIN 349 Issue 2.5 August 2015 Suppliers' Information Note For The BT Network BT Metallic Path Facility Interface Description Each SIN is the copyright of British Telecommunications plc. Reproduction of

More information

Technical Requirements for Resistibility of Telecommunications Equipment to. Overvoltage and Overcurrent

Technical Requirements for Resistibility of Telecommunications Equipment to. Overvoltage and Overcurrent Technical Requirements for Resistibility of Telecommunications Equipment to Overvoltage and Overcurrent TR NO.189001 Edition 3 1st, April, 2018 Nippon Telegraph and Telephone Corporation Notice This document

More information

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER Presented by Ric Austria, Principal at Pterra Consulting to the IEEE San Francisco Chapter Feb 17, 2016 California Public Utilities Commission,

More information

1C.4.1 Harmonic Distortion

1C.4.1 Harmonic Distortion 2 1 Ja n 1 4 2 1 J a n 1 4 Vo l.1 -Ge n e r a l;p a r tc-p o we r Qu a lity 1. Scope This handbook section contains of PacifiCorp s standard for harmonic distortion (electrical pollution) control, as well

More information

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services edarat group INTRODUCTION Harmonics are a mathematical way of describing distortion

More information

ABB n.v. Power Quality Products, October 2014

ABB n.v. Power Quality Products, October 2014 ABB n.v. Power Quality Products, October 2014 Power Quality Harmonic Basics Problems and solutions March 19, 2015 Slide 1 828m high 160 floors in total Total 113 PQF in this tower, 12000A PQFS 45M IP30

More information

SOURCES OF ERROR IN UNBALANCE MEASUREMENTS. V.J. Gosbell, H.M.S.C. Herath, B.S.P. Perera, D.A. Robinson

SOURCES OF ERROR IN UNBALANCE MEASUREMENTS. V.J. Gosbell, H.M.S.C. Herath, B.S.P. Perera, D.A. Robinson SOURCES OF ERROR IN UNBALANCE MEASUREMENTS V.J. Gosbell, H.M.S.C. Herath, B.S.P. Perera, D.A. Robinson Integral Energy Power Quality Centre School of Electrical, Computer and Telecommunications Engineering

More information

Quality of supply regulation in Norway c

Quality of supply regulation in Norway c Quality of supply regulation in Norway c Kjell Sand, Gerd H. Kjølle SINTEF Energy Research Oct. 2005/ Aug. 2006 updated April 2009 SINTEF Energy Research 1 Electrical energy consumption per capita x 1

More information

GK/GN0653. Guidance on Control of Unwanted Voltages on Telecommunications. Equipment at Stations. Rail Industry Guidance Note for GK/RT0053

GK/GN0653. Guidance on Control of Unwanted Voltages on Telecommunications. Equipment at Stations. Rail Industry Guidance Note for GK/RT0053 GN Published by: Block 2 Angel Square 1 Torrens Street London EC1V 1NY Copyright 2011 Rail Safety and Standards Board Limited GK/GN0653 Telecommunications Equipment at Stations Issue One: December 2011

More information

Design and Development of Protective Circuit against Voltage Disturbances

Design and Development of Protective Circuit against Voltage Disturbances Design and Development of Protective Circuit against Voltage Disturbances Shashidhar Kasthala 1, Krishnapriya 2, Rajitha Saka 3 1,2 Facultyof ECE, Indian Naval Academy, Ezhimala, Kerala 3 Assistant Professor

More information

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO Krasimir Marinov Ivanov, Technical University of Gabrovo, Gabrovo, BULGARIA Georgi Tsonev

More information

Harmonic distortion Blackouts Under or over voltage Dips (or sags) and surges, Transients.

Harmonic distortion Blackouts Under or over voltage Dips (or sags) and surges, Transients. Power Quality Standards in India Power Quality is a measure of an ideal power supply system. It can be defined as any power problem manifested in voltage, current and frequency deviations that result in

More information

Power Quality Evaluation of Electrical Distribution Networks

Power Quality Evaluation of Electrical Distribution Networks Power Quality Evaluation of Electrical Distribution Networks Mohamed Idris S. Abozaed, Suliman Mohamed Elrajoubi Abstract Researches and concerns in power quality gained significant momentum in the field

More information

1C.6.1 Voltage Disturbances

1C.6.1 Voltage Disturbances 2 1 Ja n 1 4 2 1 J a n 1 4 Vo l.1 -Ge n e r a l;p a r tc-p o we r Qu a lity 1. Scope The purpose of this document is to state typical levels of voltage disturbances, which may be encountered by customers

More information

SUBJECT HEADING: Switching Programmes ISSUE: 18

SUBJECT HEADING: Switching Programmes ISSUE: 18 SUBJECT: Switchgear/Switching PROCEDURE: S04 SUBJECT HEADING: Switching Programmes ISSUE: 18 DATE: Apr 2017 1. INTRODUCTION 1.1 A written programme of switching operations shall be prepared. This programme

More information

ECE 528 Understanding Power Quality

ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 19 1 Today Flicker Power quality and reliability benchmarking

More information

BIODEX MULTI- JOINT SYSTEM

BIODEX MULTI- JOINT SYSTEM BIODEX MULTI- JOINT SYSTEM CONFORMANCE TO STANDARDS 850-000, 840-000, 852-000 FN: 18-139 5/18 Contact information Manufactured by: Biodex Medical Systems, Inc. 20 Ramsey Road, Shirley, New York, 11967-4704

More information

IMPLEMENTING A SYSTEMATIC APPROACH TOWARDS SOLVING POWER QUALITY COMPLAINTS FROM A NETWORK OPERATOR S PERSPECTIVE

IMPLEMENTING A SYSTEMATIC APPROACH TOWARDS SOLVING POWER QUALITY COMPLAINTS FROM A NETWORK OPERATOR S PERSPECTIVE IMPLEMENTING A SYSTEMATIC APPROACH TOWARDS SOLVING POWER QUALITY COMPLAINTS FROM A NETWORK OPERATOR S PERSPECTIVE Sharmistha BHATTACHARYYA Endinet The Netherlands sharmirb@yahoo.com ABSTRACT In Europe,

More information

Harmonic control devices. ECE 528 Understanding Power Quality

Harmonic control devices. ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 12 1 Today Harmonic control devices In-line reactors (chokes)

More information

Generation and Load Interconnection Standard

Generation and Load Interconnection Standard Generation and Load Interconnection Standard Rev. 0A DRAFT Name Signature Date Prepared: Approved: VP Acceptance APEGGA Permit to Practice P-08200 TABLE OF CONTENTS 1.0 INTRODUCTION...5 1.1 Purpose...5

More information

SIGNAL PROCESSING OF POWER QUALITY DISTURBANCES

SIGNAL PROCESSING OF POWER QUALITY DISTURBANCES SIGNAL PROCESSING OF POWER QUALITY DISTURBANCES MATH H. J. BOLLEN IRENE YU-HUA GU IEEE PRESS SERIES I 0N POWER ENGINEERING IEEE PRESS SERIES ON POWER ENGINEERING MOHAMED E. EL-HAWARY, SERIES EDITOR IEEE

More information

PowerMonitor 5000 Family Advanced Metering Functionality

PowerMonitor 5000 Family Advanced Metering Functionality PowerMonitor 5000 Family Advanced Metering Functionality Steve Lombardi, Rockwell Automation The PowerMonitor 5000 is the new generation of high-end electrical power metering products from Rockwell Automation.

More information

CHAPTER ELECTROMAGNETIC COMPATIBILITY. Contents of this Chapter...

CHAPTER ELECTROMAGNETIC COMPATIBILITY. Contents of this Chapter... CHAPTER ELECTROMAGNETIC 4 COMPATIBILITY Contents of this Chapter... 4.0 Electromagnetic Compatibility (EMC)............4 2 4.1 Introduction................................4 2 4.2 Applicable Standard Within

More information

IEEE sion/1547revision_index.html

IEEE sion/1547revision_index.html IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html

More information

Tuningintobetter power quality

Tuningintobetter power quality Technology Review Third harmonic filters Tuningintobetter power quality Jouko Jaakkola Your PC screen flickers, stops flickering, starts again... Irritating to be sure, and perhaps the first visible sign

More information

Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions

Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions Fernando Bastião and Humberto Jorge Department of Electrical Engineering and Computers

More information

Emission Limits for Customer Facilities Connected to the Hydro-Québec Transmission System

Emission Limits for Customer Facilities Connected to the Hydro-Québec Transmission System Emission Limits for Customer Facilities Connected to the Hydro-Québec Transmission System Études de réseaux Direction Planification des actifs Hydro-Québec TransÉnergie Original in French dated December

More information

Harmonic Distortion Evaluations

Harmonic Distortion Evaluations Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

INTERNATIONAL STANDARD NORME INTERNATIONALE

INTERNATIONAL STANDARD NORME INTERNATIONALE IEC 60974-10 Edition 2.0 2007-08 INTERNATIONAL STANDARD NORME INTERNATIONALE Arc welding equipment Part 10: Electromagnetic compatibility (EMC) requirements Matériel de soudage à l arc Partie 10: Exigences

More information

POWER QUALITY REPORT

POWER QUALITY REPORT Power Quality Research Lab., I-7, Wyb. Wyspiaoskiego 27, 50-370 Wrocław, Poland phone +48713202626, fax +48713202006, email: zbigniew.leonowicz@pwr.wroc.pl Facility: XXX POWER QUALITY REPORT Start Monitoring:

More information

Emerging Standards for EMC Emissions & Immunity

Emerging Standards for EMC Emissions & Immunity Emerging Standards for EMC Emissions & Immunity Requirements for Industrial, Scientific, Medical & Information Technology Equipment CE Marking requirements are the path to increased market access Powerful

More information

Grid Converters for Photovoltaic

Grid Converters for Photovoltaic Grid Converters for Photovoltaic and Wind Power Systems by R. Teodorescu, M. Liserre and P. Rodriguez ISBN: 978 0 470 05751 3 Copyright Wiley 2011 Chapter 3 Grid Requirements for PV Grid connection requirements

More information

EMC Data Sheet CSD100 Model size 4 to 6. Variable Speed AC drive for permanent magnet motors

EMC Data Sheet CSD100 Model size 4 to 6. Variable Speed AC drive for permanent magnet motors EMC Data Sheet CSD100 Model size 4 to 6 Variable Speed AC drive for permanent magnet motors Safety Warnings A Warning contains information which is essential for avoiding a safety hazard. A Caution contains

More information

ETSI EN V1.1.1 ( )

ETSI EN V1.1.1 ( ) EN 300 471-2 V1.1.1 (2001-05) Candidate Harmonized European Standard (Telecommunications series) Electromagnetic compatibility and Radio spectrum Matters (ERM); Land Mobile Service; Rules for Access and

More information

EUROPEAN CONNECTION CONDITIONS (ECC) CONTENTS. (This contents page does not form part of the Grid Code)

EUROPEAN CONNECTION CONDITIONS (ECC) CONTENTS. (This contents page does not form part of the Grid Code) GC0102 EXTRACT OF EUROPEAN CONNECTION CONDITIONS LEGAL TEXT DATED 08/01/2018 Paragraph No/Title EUROPEAN CONNECTION CONDITIONS (ECC) CONTENTS (This contents page does not form part of the Grid Code) Page

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

PQ Monitoring Standards

PQ Monitoring Standards Characterization of Power Quality Events Charles Perry, EPRI Chair, Task Force for PQ Characterization E. R. Randy Collins, Clemson University Chair, Working Group for Monitoring Electric Power Quality

More information

T-68 Protecting Your Equipment through Power Quality Solutions

T-68 Protecting Your Equipment through Power Quality Solutions T-68 Protecting Your Equipment through Power Quality Solutions Dr. Bill Brumsickle Vice President, Engineering Nov. 7-8, 2012 Copyright 2012 Rockwell Automation, Inc. All rights reserved. 2 Agenda What

More information

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017 Grid codes and wind farm interconnections CNY Engineering Expo Syracuse, NY November 13, 2017 Purposes of grid codes Grid codes are designed to ensure stable operating conditions and to coordinate the

More information