NDQ Series. Automatic Transfer Switch. Shanghai Liangxin Electrical CO.,LTD

Size: px
Start display at page:

Download "NDQ Series. Automatic Transfer Switch. Shanghai Liangxin Electrical CO.,LTD"

Transcription

1 Shanghai Liangxin Electrical CO.,LTD Address: No. 668 Heng An Road, Pu Dong New District, Shanghai Zip: Tel: Fax: Shanghai Electrical All rights reserved NDQ Series Automatic Transfer Switch As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication

2 Leading lowvoltage Electrical Component Manufacturer NDQ Series Automatic Transfer Switch Application NDQ1 Series Automatic Transfer Switch Working Condition Operating Procedure of Intelligent Controller Working Mode Selfthrowingselfrestoring Controller (R) Selfthrowingnonselfrestoring Controller (S) Gridgenerator Controller (F) Wiring Schematic of Subcircuit Dimension NDQ2 Series Automatic Transfer Switch Product Features Working Condition Dimension Main Structure and Operating Principle Operating Principle of Controller Test and Function of Controller Indication of Controller Wiring Schematic of Subcircuit Wiring Schematic of External Terminal

3 Table 1 Product Operating Circuit Breaker Frame Size (A) Rated Current (A) Control Mode Number of poles Structure NDM NDM2100 NDM2225 NDM2400H R:Selfthrowing selfrestoring S:Selfthrowing nonselfrestoring F:Gridgenerator 3P 4P Z:Integrated type F:Split type NDM2630H Note: All threepole operating circuit breaker of NDM263, NDM2100 and NDM2225 referred above are Standard type grade of rated ultimate short circuit breaking capacity. NDQ163 NDQ1100 NDQ25 NDQ1400 NDQ1630 Application NDQ Series Automatic Transfer Switch (hereinafter ATS ), which includes NDQ1 series and NDQ2 series, is suitable for transferring between two circuits of power supply (working power supply, standby power supply) with rated voltage up to AC 400V, rated current up to 630A, frequency of 50Hz. NDQ1 series transfer switch take the molded case circuit breaker as the implementation component : NDQ2 series transfer switch take the miniature circuit breaker as the implementation component. Customer can make their choice according to their requirement This ATS is suitable for important places where power breaking is not allowable, such as hospital, mall, bank, hotel, high building. military and fire protection facilities. This product meets the requirements of following standards and specifications: Part 61 Automatic Transfer Switch of GB/T : Low Voltage Switchgear and Controlgear, Fire Protection Specification of Civil High Building and Five Protection Specifications for Architectural Design. Rated ultimate short circuit breaking capacity(ka) Rated voltage Rated insulation voltage Electrical endurance Mechanical endurance Rated voltage of controller OFF/ON delay time Overvoltage switching value Undervoltage switching value Rated working hours Contact switching time AC 400V 690V AC 230V 50H 0.5s~60s (Contiously adjustable) AC 265V (60~85)%Ue (Continuously adjustable) Aroundtheclock working 2S Z NDQ1 Series Automatic Transfer Switch Product Features Working Condition ND Q 1 No. 7 8 Implication Brand code Product code Design code Frame size Control mode Rated current Structure type 7 8 NDQ1 Q Automatic Transfer Switch 1 63, 100, 225, 400, 630 Double protections of reliable mechanical interlock and electrical interlock based on MOTOROLA siglechip microcomputer between two circuit breakers to ensure switching reliably. Fitted with overvoltage protection, undervoltage protection, phase failure protection, automatic switching and intelligent alarm function. Parameters can be set freely from external. Small size, safe and reliable, convenience usage, low energy consumption. Fitted with fireproof control function, when sending fire controlling signal to the intelligent controller, two circuit breakers are in OFF status. Construction of products is made up of high quality cold rolled steel plate with beautiful and novel appearance, coating surface adopt advanced electrostatic powder coating technology with coat layer of good adhesion force and erosion resistance. Temperature: 5 ~40. The average temperature in 24 hours does not exceed 35. Humidity: The relative humidity does not exceed 50% at the maximum temperature of 40. Higder relative humidity are permitted at the lower temperature, e.g: the humidity allow to be 90% under the temperature of 20. Special measures may be required in case of occasional condensation due to the vibration of temperature Altitude: 2000m. Pollution degree: 3 class. Utilization type: AC33B. Electrical apparatus level: CB level.

4 Table 2: Function of selfthrowingselfrestoring controller Controlling Functions Power from working power: Q N ON, Q R OFF Power from working power: Q N ON, Q R OFF, sending out Alarm signal Q NOFF after delay time t1, then Q R ON after delay time t2. Power from standby power. Returns to normal Q R OFF after delay time t1, then Q N ON after delay time t2. Power from working power again. Notes: t1 : switchingoff delay, 0.5s60s adjustable, setting value ar factory is 1.5s (The same applies to Table 3 and Table 4) t2 : switchingon delay, 0.5s60s adjustable, setting value at factory is 1.5s (The same applies to Table 3 and Table 4) Selfthrowingnonselfrestoring Controller (S) Intelligent controller monitors working power and standby power, implement switching automatically. When working power is in abnormal, the working power will be cut off after setting delay time t1. Then the standby power works automatically after delay time t2. When the working power returns to normal condition, the power is still supplied by standby power until the standby power is in abnormal condition. In such condition, the standby power will be cut off after setting delay time t1, then the working power works automatically after delay time t2. The functions of selfthrowingnonself controller are shown in Table 4. Opearting Procedure of Intelligent Controller Table 3: Function of selfthrowingnonselfrestoring controller The intelligent controller keep testing threephase voltage of working power and standby power, compare the defected results with Controlling Functions the setting values, judge the voltage above 5% Ue as overvoltage, the voltage below 60%85%Ue(adjustable) as undervoltage. Once the voltage is judged as in fault condition, the intelligent controller will deliver OFF/ON command to motorized operating mechanism Power from working power: Q N ON, Q R OFF by command relay based on preset delay program. At the same time, the indicators on faceplate display above said detected results. Q NOFF after delay time t1, then Q RON afer delay time t2. Power from standby power. Working Mode Returns to normal Power still from standby power. The ATS has two working modes: manual working mode and automatic working mode. Q OFF after delay time t1, then Q ON after delay time t2. Power from working power again. N R There are three working status of ATS: Working power worksbreak standby power, make working power; Standby power worksbreak working power, make standby power; Power cuttwo breakers are both in OFF position. Automatic working mode: The ATS can automatically switch based on power condition. Under automatic working mode, the ATS can be divided into three versions by controlling function, selfthrowingselfrestoring(r), selfthrowingnonselfrestoring(s) and gridgenerator (F). The first two versions are suitable for gridtogrid power system, the last version is suitable for gridtogenerator power system. Manual working mode: Press standby button, breaker of working power is open and breaker of standby power is closed. Press working button, breaker of standby power is open and breaker of working power is closed. Press reset button, both two breakers are open. If one of breakers trips, pressing reset button will make it reset. Gridgenerator Controller (F) Intelligent controller monitors working power and standby power, implement switching automatically. When the working power is in abnormal condition, Power generation command will be sent out after delay time. When the voltage of selfcondtioned generator is up to 85% of rated voltage Ue, the breaker of working power will be out off. Meanwhile, Unloading command will be sent out to unload the minor loads. Power will turn to be supplied by generator automatically after proper delay time. After the working power returns to normal condition, the system cuts off generator power, returns to the working power for power supply, and sends out command signal to stop the generator. The functions of gridgenerator controller are shown in Table 4. Table 4: Function of gridgenerator controller Working Power Standby Power Controlling Functions Selfthrowingselfrestoring Controller (R) Nongenerating Power from working power: Q N ON, Q R OFF Intelligent controller monitors working power and standby power, implement switch automatically. When both two powers is in normal, power is supplied by working power. When working power is in abnormal (overvoltage, undervoltage, phase default), after the setting delay time t1, the working power will be cut off. Then after setting delay time t2, the standby power works automatically. During this period, common auxiliary terminal will be open and standby auxiliary terminal will be closed. When the working power returns to normal condition, after the setting delay time T1, the standby power will be cut off. Then after setting delay time T2, the working power turn back to work. When the working power supplies power normally but standby power is in abnormal condition, the LED indicator of standby power on contralling faceplate will indicates according to fault type and send out alarming contact signal. The functions of selfthrowingselfrestoring controller are shown in Table 2. Returns to normal Generating Continue genrtating Nongenerating Power generation command will be sent out after delay time to request generating. Q NOFF after delay time t1. Meanwhile, Unloading command will be sent out to unload the minor loads. Then Q ON after delay time t2. Power from generator. R Q R OFF after delay time t1, then Q NON after delay time t2. Power from working power again. Duration delay time t2, Power generation and Unloading commands will be cancelled automatically

5 Please check the following issues before electrified: Phase lines and neutral line should be connected correctly and relieably. ATSE Class: CB Utilisation Catagory: AC33B Undervoltage Setting Delay time for Open Automatically Delay time for Closed Fire Control Alarm Signal Common Auxiliary Standby Auxiliary Connection Schematic of Subcircuit (1) Dimensions Q N: Circuit breaker of working power; Q R : Circuit breaker of standby power; Q NF, Q RF: Auxiliary contact of circuit breaker; Q NB, Q RB: Alarm contact of circult breaker; M: Operating motor; AMP: Cable connector; JX1, JX2: connection terminal; JXN: Npole connection terminal. Neutral line must be connected property in case damaging the intelligent controller. Note: This schematic shows the product in reset OFF position. Warning! NDQ1 Automactic Tansfer Switch ON Trip ON ON The comparison table for function of auxiliary terminals Terminal No. of controller 1, 2 3, 4 5, 6 7, 8 Selfthrowingselfrestoring (R) Selfthrowingnonselfrestoring (S) Fire control Alarm signal Common auxiliary Standby auxiliary GridGenerator (F) Fire control / Generator control Unloading command Shanghai Liangxin Electriacal Co.,Ltd. Automatic Common Standby Reset Shanghai Liangxin Electriacal Co.,Ltd. Intelligent Controller NDQ1 Automactic Tansfer Switch Figure 1:Dimensions for integrated type Auxiliary Terminals ON Trip Delay time for Open Undervoltage Setting Delay time for Closed ON Trip Automatic Common Standby Reset Shanghai Liangxin Electriacal Co.,Ltd. Wiring schematic of 3pole ATS Connection Schematic of Subcircuit (2) Q N: Circuit breaker of working power; Q R : Circuit breaker of sandby power; Q NF, Q RF: Auxiliary contact of circuit breaker; Aperture dimension Q NB, Q RB: Alarm contact of circult breaker; M: Operating motor; AMP: Cable connector; JX1, JX2: Connection terminal. Neutral line must be connected property in case damaging the intelligent controller. Note: This schematic shows the product in reset OFF position. The comparison table for function of auxiliary terminals Figure 2: Control Panel and Dimensions for splite type Terminal No. of controller Selfthrowingselfrestoring (R) Selfthrowingnonselfrestoring (S) GridGenerator (F) 1, 2 3, 4 5, 6 7, 8 Fire control Alarm signal Common auxiliary Standby auxiliary Fire control / Generator control Unloading command Table 5 Dimensions for Integrated Outline Dimensions Installation Dimensions NDQ163 3pole A 4pole 490 B 220 H 3pole/L 152 3pole/M 4pole 160 3pole 430 a 4pole b 200 Φ 8.5 Intelligent Controller NDQ1100 NDQ25 NDQ NDQ Auxiliary Terminals Wiring schematic of 4pole ATS The model, specification, frame size of the operating circuit breaker, number of poles, function of circuit breaker and switching mode and quantity should be noted when ordering. For example: if ordering intergrated type ATS with selfthrowingselfrestoring controller, frame size is 225A, rated current is 200A, 4Pole products, 20 pieces, you can mark NDQ1M225R 200A/4Z, 20PCS

6 Working Condition Ambient temperature: 5 ~40. The average temperature in 24 hours does not exceed 35. Altitude: 2000m Humidity: The relative humidity of the air does not exceed 50% at the maximum temperature of 40. Higher relative humidity may be permited at lower temperature, e.g. 90% at 20. Special measures may be necessary in case of accasional condensation due to variation in temperrature. Electrical apparatus level: CB level Pollution degree: 2 class Installation type: Ⅱ, Ⅲ Utilization type: AC33B NDQ Rated current (A) Ie NDQ2 Series Automatic Transfer Switch Rated operating shortcircuit breaking capacity (ka) ICS 10 Rated working voltage (V) Ue AC 400 ND Q 2 Rated frequency (Hz) 50 Rated insulation voltage (V) Ui 690 Undervoltage switching value 70%U e No. Implication Brand code Product code Design code NDQ2 Q Automatic transfer switch 2 Undervoltage restoring value Switching delay time (s) Tn Return delay time (s) Tr Range of the control voltage 85%U e 1~10 1~10 85%U e ~ 0%U e Frame size Rated current Table 6 Dimensions Note: Controller type is selfthrowingselfrestoring type. 3, 4 Frame Size (A) Outline Dimensions (mm) Length Width Height Installation Dimensions (mm) Length Width Aperture Dimension Product Features The ATS can automatically transfer switch when there is undervoltage or phase failure to ensure the reliable operation of the distribution systerm. The features are as following: Reliable double protections of mechanical interlock and electrical interlock between two circuit breakers. Automatic transfer switching function with undervoltage protection and phase failure protection. Delay parameters can be set from extemal. Small size and convenience usage. Lower energy consumption and operotion without noises. High standardization and universality. The outline and installation dimensions of 3pole and 4pole products are unitied to make customers design and selection more convenient

7 Main Structure and Operating Principle Wiring Schematic of Subcircuit The main structure of ATS is composed of controller, mechanical interlock machine and two miniature circuit breakers. The controller keep testing the operating status of the two power suppliers and send out signal to the electromotor according to demands. The electromotor drives the mechanical interlock machine to operate the two circuit breakers. There are indications of working status of the two power suppliers and the loads status of the two circuit breakers on the faceplate. All the parts are installed in a metal plate. There is a terminal to connect the indications on the faceplate to the panel of electrical controlling box. So it is convenient for the customers to observe the operating status of the ATS. Standby(N) Working(N) Power side (Working) Working power Power side (Standby) Standby power Power side (Working) Working power Power side (Standby) Standby power Operating principle: Working power and standby power are separately connected to two circuit breakers. When working power is normal and the function key is on Automatic, circuit breaker for standby power is open and circuit breaker for working power is closed to ensure the working power supplies the loads. When the voltage of working power drops below 70% Ue, the working power is cut off after setting delay time and the standby power is used (when it is normal). And when the working power returns to normal, the standby power is cut off and return to the working power for power supply after delay time. When there is voltage failure on any one or all three phases of working power, working power will be transferred switching to standby power immediately. When the working power returns to normal, the standby power is cut off and returns to the working power for power supply after delay time. Operating Principle of Controller Controller tests three phases voltages of working power and L1 phase voltage of standby power at the same time. It judges the voltage below 70%Ue as undervoltage and transfer switching. The status of ATS is indicated by four LEDs on the case. The cymbiform switch on the case of controller is used for the transferred switching between autormatically and manually. Two resistance potentimeter (Tn, Tr) are used to adjust the delay time. Tn is for switching delay time and Tr is for return delay time. Load side Wiring schematic of 3pole product Load side Wiring schematic of 4pole product Test and Function of Controller Wiring Schematic of External Terminal ATS is used for transferred switching between working power and standby power. In the normal status, the power is supplied by working power. When there is undervoltage of any one phase of the working power, the power is transferred to be supplied by the standby power after setting delay time. When the working power returns to normal, the standby power will be cut off and retum to the working power for power supply after setting delay time. When there is voltage failure on any one or all three phases of working power, working power will be transferred switching to standby power immediately. When the working power returns to normal, the standby power will be cut off and returns to the working power for power supply after delay time. Indication of Controller Working Working Standby Standby Working Standby Working Working Standby Standby Controlling Status Indication Status Signal led to the panel of switch cabinet Neutral Line input Signal led to the hoand of switch box U n U r Q n Q r Power from working power:q F n ON,Q F r OFF Wiring schematic of external terminal of threepole product Wiring schematic of external terminal of fourpole product Power from working power:q F n ON,Q F r OFF Notes:The connecting terminals have been switched on the power of AC200V, User doesn t need to supply the power. Please cut off the power when wiring Power from working power:q F n OFF,Q F r ON Returns to normal Power from working power:q F n ON,Q F r OFF Note: Q F n The MCB which controls working power Q F r The MCB which controls standby power U n Indicator light of working power U r Indicator light of standby power Q n Indicator light for the making of working power Q r Indicator light for the making of standby power Indicator light is on Indicator light is off Please specify the following informations when ordering: Name and type Rated current In Quantity For example: If the ordered unit is NDQ263 automatic transfer switch with rated current of 40A, 4pole, 200 pieces. It should be marked as NDQ263/40/4, 200 PCS.

NZ7. NZ7 Automatic Transfer Switching Equipment. 2. Type designation. 1. General. 3. Operation conditions N Z 7- /

NZ7. NZ7 Automatic Transfer Switching Equipment. 2. Type designation. 1. General. 3. Operation conditions N Z 7- / Z7 2. Type designation Z 7- / Transfer mode without code: Users can set the matter : self-throwing and self-reset (power network to power network) S: self-throwing and not self-reset (power network to

More information

Circuit Breakers. Excerpt from Master Catalogue. Circuit Breakers. Specifically For You

Circuit Breakers. Excerpt from Master Catalogue. Circuit Breakers. Specifically For You Circuit Breakers Excerpt from Master Catalogue Circuit Breakers Specifically For You Hydraulic-magnetic technology ensures reduced nuisance tripping with temperature variance Always holds 00% rated current

More information

Computer-14d - xx - 144a

Computer-14d - xx - 144a POWER FACTOR REGULATOR Computer-14d - xx - 144a INSTRUCTION MANUAL ( M 981 602 / 98B ) (c) CIRCUTOR S.A. -------- POWER FACTOR REGULATOR COMPUTER- 14d --------- Page 2 1.- POWER FACTOR REGULATORS COMPUTER-14d-144a

More information

ATP Time Switch

ATP Time Switch ATP1006-2 Time Switch (The time switch timing can be set second.) 1. Function and Scope ATP1006-2 time switch (hereinafter referred to as time switch ) is applicable for regularly controlling switch-on

More information

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax : NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata - 700 032, Tel : 033 2477 3126; Fax : 033 2477 2403 www.ntplindia.com SPECIFICATION NTPL MAKE MICRO-CONTROLLER BASED AUTOMATIC 50KV/10A AC HIGH VOLTAGE

More information

Modeion OTHER ACCESSORIES OF MOULDED CASE CIRCUIT BREAKERS

Modeion OTHER ACCESSORIES OF MOULDED CASE CIRCUIT BREAKERS OTHER ACCESSORIES OF MOULDED CASE CIRCUIT BREAKERS P Other accessories DELAY UNIT Type Product code Description Weight [kg] Package [pc] BZ-BX-X230-A 36696 enables to delay the undervoltage release tripping

More information

Page 13-2 Page Page 13-7

Page 13-2 Page Page 13-7 Page -2 Page -6 MINIATURE CIRCUIT BREAKERS UP TO 63A 1P, 1P+N, 2P, 3P and 4P versions IEC rated current In: 1-63A IEC short-circuit capacity Icn: 10kA (6kA for 1P+N) Trip characteristic curve: Type B,

More information

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with

More information

SECTION AUTOMATIC TRANSFER SWITCH

SECTION AUTOMATIC TRANSFER SWITCH SECTION 26 36 23 PART 1 - GENERAL 1.1 THE REQUIREMENT A. Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, withstand and close-on ratings as shown on the plans.

More information

13. Before making a service call Trip information and remedies

13. Before making a service call Trip information and remedies . Before making a service call Trip information and remedies.1 Trip causes/warnings and remedies When a problem arises, diagnose it in accordance with the following table. If it is found that replacement

More information

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM SYSTEM OVERVIEW Pollution monitoring of high voltage insulators in electrical power transmission and distribution systems, switchyards and substations is essential in order to minimise the risk of power

More information

Operating Manual MU2000K

Operating Manual MU2000K ZIEHL industrie elektronik GmbH + Co KG Daimlerstr.13, 74523 Schwäbisch Hall, Germany + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN

More information

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS)

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS) AC CURRENT GENERATOR PERFORMANCES Wide range of current 50 db dynamic range Signal-to-noise ratio: 80 db open loop protection Stability < 0,1% Very low THD distortion < 0,3% External synchronization Build-up

More information

Capacitor Switching Contactors

Capacitor Switching Contactors Capacitor Switching D385E51 Technical catalogues and news under: www.benedict.at Motor-Starter Mini- Overload Relays Capacitor Switching Motor-Starters Modular Circuit Breakers M4-32T... up to 32A M4-32R..

More information

OSS series. Automatic Transfer Switches. O-Sung Electric Machinery CO., LTD.

OSS series. Automatic Transfer Switches. O-Sung Electric Machinery CO., LTD. OSS series Automatic Transfer Switches OSung Electric Machinery CO., LTD. Outstanding technology captivates the world! Superior Quality satisfies our customers! Contents Company History 3 OSS T, TB Type

More information

2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS

2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 0640 807-0 Fax: 0640 807-259 IT system floor-standing distribution cabinet Series -IPS-F/EDS for supplying power to medical locations

More information

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL 1 Contents 1. Application... 5 2. meter set... 6 3. BASIC REQUIREMENTS, OPERATIONAL SAFETy... 6 4. installation... 10 4.1. Mounting... 10 4.2. External

More information

Maintenance/Connection/Installation Service life C/O cyclesx1000

Maintenance/Connection/Installation Service life C/O cyclesx1000 EasyPact MVS 2016 CPB100000 CPB100014 Circuit breaker. Switch disconnector. Common characteristics Number of poles Rated insulation voltage (V) Impulse withstand voltage (kv) Rated operational voltage

More information

3 - Protection components Circuit-breakers

3 - Protection components Circuit-breakers Contents - Protection components Circuit-breakers for the motor protection Selection guide..............................................page /2 Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

90 ReStart AUTOMATIC RECLOSING DEVICES

90 ReStart AUTOMATIC RECLOSING DEVICES RESTART WITH AUTOTEST Technical data TYPE ReStart with Autotest 2P ReStart with Autotest PRO 2P ReStart with Autotest PRO 4P Electrical characteristics Standards: EN 50557, EN 61008-1 Distribution system:

More information

Add-on modules DX 3 63A for MCBs DX 3 1,5 modules per pole

Add-on modules DX 3 63A for MCBs DX 3 1,5 modules per pole 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 Add-on modules DX 3 63A for MCBs CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4.

More information

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELECTRICAL ENGINEERING DIVISION Distribution Network Department SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELA T150.2 en SRA 2250/6 Resistor specification The SRA 2250/6 Resistor is intended to increase

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays. Model Number Structure

DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays. Model Number Structure New Product News Measuring & Monitoring Relays K8AK/K8DS Series DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays Compact 22.5 mm and 17.5 mm housings Resistant to high-frequency

More information

ATS-01 Ver1.2 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

ATS-01 Ver1.2 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL ATS-01 Ver1.2 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL Headquarters : No.3, Lane 201, Chien Fu ST., Chyan Jenn Dist., Kaohsiung, TAIWAN Tel : + 886-7-8121771 Fax : + 886-7-8121775 URL :

More information

General Requirements. Technical Specification LVAC Systems

General Requirements. Technical Specification LVAC Systems Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks LVAC Systems NO: 423-1

More information

Siemens AG Allows easy and consistent configuration with one series of overload relays (for small to large loads)

Siemens AG Allows easy and consistent configuration with one series of overload relays (for small to large loads) Overview Features Benefits 3RU11 3RB20/3RB21 3RB22/3RB23 Sizes Are coordinated with the dimensions, connections S00...S3 S00... S12 S00... S12 and technical characteristics of the other devices in the

More information

NIPSCO Energy Symposium

NIPSCO Energy Symposium Backup Power Automatic Transfer NIPSCO Energy Symposium symposium Backup Power Applications/Considerations Backup Power Types Automatic Transfer Switch Basics Presenters McGill Power - Jeremy Irmeger Eaton

More information

Protection components

Protection components Multifunction protection relays LT-P Environment Conforming to standards IEC 947-4-1, IEC 34-11, IEC 755, VDE 010, VDE 00. &Ãmarking Meets the essential requirements of the Low Voltage equipment (LV) &

More information

TCS2P125. Automatic Transfer Switch Control Unit for 1 Phase System Operation Manual

TCS2P125. Automatic Transfer Switch Control Unit for 1 Phase System Operation Manual TCS2P125 Automatic Transfer Switch Control Unit for 1 Phase System Operation Manual Single Phase 2P 125 Amp Rated Voltage 250 Vac Patent Number : U.S. Pat. No. 7,557,683 KUTAI ELECTRONICS INDUSTRY CO.,

More information

Time over/underfrequency relay with protection assemblies

Time over/underfrequency relay with protection assemblies Time over/underfrequency relay with protection assemblies RXFK 2H and RAFK 509 009-BEN Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970104) (SE970108) Features

More information

Btdin RCD Add-on modules 63A for MCBs 1,5 modules per pole

Btdin RCD Add-on modules 63A for MCBs 1,5 modules per pole Index Pages 1. Descripton... 2 2. Product range... 2 3. Overall dimensions... 2 4. Fixing Connection... 3 5. Generl characteristics... 4 6. Compliance - Approvals... 6 7. Curves... 7 8. Auxiliares and

More information

(1,5 modules per pole)

(1,5 modules per pole) 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 DX 3 MCB 25kA 80A to 125A CONTENTS PAGES 1. Description - Use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

FL ballasts Electronic dimming. PCA T5 ECO lp Y, 3x14/24 W and 4x14/24 W ECO T5

FL ballasts Electronic dimming. PCA T5 ECO lp Y, 3x14/24 W and 4x14/24 W ECO T5 T5 PCA T5 ECO lp Y, x1/ W and x1/ W ECO T5 Product description Processor-controlled ballast with y inside Highest possible energy class CELMA EEI = A1 BAT 1 Noise-free precise control via DSI signal, switchdim

More information

e 2 TANGO-50 Short-Circuit Detector K Data Sheet

e 2 TANGO-50 Short-Circuit Detector K Data Sheet e 2 TANGO-50 Short-Circuit Detector K-31.2.1 Data Sheet We Create Ideas With Power! e 2 TANGO-50 short-circuit detector is a product of ELEKTROMETAL ENERGETYKA SA developed by our engineers with extensive

More information

Miniature circuit breakers. Residential current circuit breakers. Busbar systems. Comfort functions/energy control. Residential enclosures

Miniature circuit breakers. Residential current circuit breakers. Busbar systems. Comfort functions/energy control. Residential enclosures .2..4.5.6.7 Technical data Series ME07 Standard range S, S, 0/690V/AC High performance range H, 0/690V/AC High performance range H/S, 000V/AC Disconnecting switch MET DC circuit breaker ME 6T up to 0V/DC

More information

1-phase AC current Voltages/frequencies Volt Volt 110, 115, , 230, 240 Hz Hz 60 50

1-phase AC current Voltages/frequencies Volt Volt 110, 115, , 230, 240 Hz Hz 60 50 General information AC 01.2 actuator controls for controlling multi-turn actuators of the SA/SAR.2 type range and part-turn actuators of the SQ/SQR type range with Profibus DP interface. Features and functions

More information

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, and withstand

More information

Solid-State Switching Devices

Solid-State Switching Devices SIRIUS Solid-State Switching Devices Contents Pages Introduction.................................. 8/2 Solid-state switching devices General data.................................. 8/3 Solid-state switching

More information

Type 3RW RW40 7. Control electronics Rated values. Terminal. external DC supply (to DIN 19240) through terminals and IN Relay outputs

Type 3RW RW40 7. Control electronics Rated values. Terminal. external DC supply (to DIN 19240) through terminals and IN Relay outputs Function have all the same advantages as the 3RW30/31 soft starters. At the same they come with additional functions and a two-phase control method (Polarity Balancing) that is unique in the rating range

More information

AC 01.2 Modbus TCP/IP

AC 01.2 Modbus TCP/IP General information Actuator controls AC 01.2 for controlling multi-turn actuators of the SA/SAR.2 type range and part-turn actuators of the SQ/SQR.2 type range with interface. Features and functions Power

More information

ELECTRONIC SHEAR PIN MODEL ESP 1 & 2 INSTRUCTION MANUAL

ELECTRONIC SHEAR PIN MODEL ESP 1 & 2 INSTRUCTION MANUAL ELECTRONIC SHEAR PIN MODEL ESP 1 & 2 INSTRUCTION MANUAL ESP Product Warranty Zener Electric warrant the Electronic Shear Pin against defective workmanship and materials for a period of 24 months from the

More information

Protection and safety SQZ3 phase and sequence relay

Protection and safety SQZ3 phase and sequence relay SQZ3 phase and sequence relay Supply voltage [Vn] 400 V a.c. Frequency [Hz] 0/60 SQZ3 2CSC4001F0201 Contact type [A] 1 CO, 20 V, 10 A (cos =1) safety switching Minimum voltage adjustment trimmer [%] 100

More information

SPECIFICATION, CONTROLS AND ACCESSORIES

SPECIFICATION, CONTROLS AND ACCESSORIES AS440 Automatic Voltage Regulator (AVR) SPECIFICATION, CONTROLS AND ACCESSORIES English Original Instructions A043Y697 (Issue 2) Table of Contents 1. DESCRIPTION... 1 2. SPECIFICATION... 3 3. CONTROLS...

More information

1-phase AC current Voltages/frequencies Volt Volt 110, 115, , 230, 240 Hz Hz 60 50

1-phase AC current Voltages/frequencies Volt Volt 110, 115, , 230, 240 Hz Hz 60 50 General information AC 01.2 actuator controls for controlling multi-turn actuators of the SA/SAR.2 type range and part-turn actuators of the SQ/SQR type range with Modbus RTU interface. Features and functions

More information

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Dual-Source Power Supply Addendum to I.B. 17555 Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Table of Contents Page 1.0 Introduction...1 2.0 General

More information

MODEL: M2DYS SEN TRONIC AG

MODEL: M2DYS SEN TRONIC AG Super-mini Signal Conditioners Mini-M Series CURRENT LOOP SUPPLY Functions & Features Powers a 20 ma DC current loop Short circuit protection Applicable to smart transmitters CE marking UL approval Typical

More information

MODEL: M2SES SEN TRONIC AG [3] OUTPUT

MODEL: M2SES SEN TRONIC AG [3] OUTPUT Super-mini Signal Conditioners Mini-M Series HIGH/LOW SELECTOR Functions & Features Monitors two DC input signals and transmits an output signal proportional to the higher or lower input CE marking UL

More information

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink Characteristics variable speed drive ATV12-0.37kW - 0.55hp - 100..120V - 1ph - with heat sink Product availability : Stock - Normally stocked in distribution facility Price* : 191.76 USD Main Range of

More information

Laser Particle Sensor Module PM2006M

Laser Particle Sensor Module PM2006M Laser Particle Sensor Module PM2006M Application Air purifier, air quality monitor Ventilation system, air conditioner with purifying function Auxiliary product of consumer electronic products Description

More information

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol Product datasheet Characteristics ATV12HU22M2 Complementary Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component name Variable

More information

ATS Controller (KSC-5000) Manual

ATS Controller (KSC-5000) Manual Smart ATS Controller (KSC-5000) Manual ( Modify)March. 03, 2015 Kisung Electric Machinery Co., Ltd. 1 1. The Outline KSC-5000 controls ATS (Automatic Transfer Switch) which is to switch the electric load

More information

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 4.0 Sectionalizer Construction... 4 5.0 Mechanism... 6 6.0 Solid Dielectric

More information

AC 01.2 HART Technical data Actuator controls

AC 01.2 HART Technical data Actuator controls General information AC 01.2 actuator controls for controlling multi-turn actuators of the SA/SAR.2 type range and part-turn actuators of the SQ/SQR type range with interface. Power supply Standard voltages

More information

GE Critical Power. GTX Series. Automatic Transfer Switch (ATS)

GE Critical Power. GTX Series. Automatic Transfer Switch (ATS) GE Critical Power GTX Series Automatic Transfer Switch (ATS) GTX Series GE has been providing customers with reliable ATS power switching systems since the 1920 s. GE s GTX Series Automatic Transfer Switches

More information

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator REGULATION Automatic Synchronizer for Generator NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

Laser Particle Sensor Module PM3015

Laser Particle Sensor Module PM3015 Laser Particle Sensor Module PM3015 Application Outdoor air quality monitor. Ventilation system, air conditioner with purifying function Auxiliary product of consumer electronic products Environmental

More information

Transformer differential protection

Transformer differential protection Transformer differential protection Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970883) Features Three phase differential protection with two, three, five or

More information

1-phase AC current voltages/frequencies Volt Volt

1-phase AC current voltages/frequencies Volt Volt General information AC 01.2 actuator controls for controlling multi-turn actuators of the SA/SAR.2 type range and part-turn actuators of the SG/SGR type range with interface. Features and functions Power

More information

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

ATV12H018F1 variable speed drive ATV kW hp V - 1ph Characteristics variable speed drive ATV12-0.18kW - 0.25hp - 100..120V - 1ph Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component

More information

Product Catalog PRODUCT CATALOG. Power supply system & test equipment

Product Catalog PRODUCT CATALOG. Power supply system & test equipment Product Catalog PRODUCT CATALOG 2018 2018 Power supply system & test equipment. 138/79, Moo 2 Tambon Ban Klang, Amphoe Mueang Pathumthani, Pathumthani Province 12000, Thailand. Tel: +66 21475048-9 Fax:

More information

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink Characteristics variable speed drive ATV12-0.37kW - 0.55hp - 100..120V - 1ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application

More information

INTERPLANT STANDARD - STEEL INDUSTRY

INTERPLANT STANDARD - STEEL INDUSTRY INTERPLANT STANDARD - STEEL INDUSTRY SPECIFICATION FOR MOULDED - CASE CIRCUIT-BREAKER FOR VOLTAGES NOT EXCEEDING 1000 V ac OR 1500 V dc (FIRST REVISION) IPSS:1-04-004-11 IPSS BASED ON IS/IEC 60947(Part

More information

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink Characteristics variable speed drive ATV12-4kW - 5hp - 200..240V - 3ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly

More information

Technical catalogue. Emax Low voltage air circuit-breakers. Hotline:

Technical catalogue. Emax Low voltage air circuit-breakers.   Hotline: Technical catalogue Emax Low voltage air circuit-breakers www.alobitanbd.com Hotline: 01711548558 PAGE : 02 The new Emax have received innumerable international certifications and approval by the major

More information

FL ballasts Electronic dimming. PCA T8 ECO lp Y, 3x18 W and 4x18 W ECO T8

FL ballasts Electronic dimming. PCA T8 ECO lp Y, 3x18 W and 4x18 W ECO T8 T8 PCA T8 ECO lp Y, x18 W and x18 W ECO T8 Product description Processor-controlled ballast with y inside Highest possible energy class CELMA EEI = A1 BAT 1 Noise-free precise control via DSI signal, switchdim

More information

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General Section 16621A - AUTOMATIC TRANSFER SWITCH Part 1 General 1.01 One 600 Amp, 3 Phase, 480 Volt Automatic Transfer Switch (ATS) shall be provided with gasketed enclosure. The ATS shall consist of an inherently

More information

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION October 2014 TECHNICAL DESCRIPTION 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES I. SCOPE This

More information

AMU-214 Auxiliary Monitor Unit Operations Manual

AMU-214 Auxiliary Monitor Unit Operations Manual AMU-214 Auxiliary Monitor Unit THIS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE AMU-214 SERIES ITS CABINET AUXILIARY MONITOR UNIT. REVISION: SEPTEMBER 2008 pn 888-0214-001 THE AMU-214 SERIES AUXILIARY

More information

Residual Current Operated Circuit-Breakers (RCCBs)

Residual Current Operated Circuit-Breakers (RCCBs) Product overview Residual Current Operated C ircuit-breakers (RCCBs) Number of poles Rated fault current I n ma Rated current I n A MW Auxiliary switches can be mounted (Type A) (Type B) 5SM1and 5SM3 RCCBs

More information

Micro-controller X Model: PXE4. Operation Manual. INP-TN5A1887a-E

Micro-controller X Model: PXE4. Operation Manual. INP-TN5A1887a-E Micro-controller X Model: PXE4 Operation Manual INP-TN5A1887a-E 2 BEFORE USE Thank you very much for purchasing Fuji s digital controller. (1) Be sure to read this manual and grasp the concept before operating

More information

MODEL: W2DYS SEN TRONIC AG. Mini-MW Series

MODEL: W2DYS SEN TRONIC AG. Mini-MW Series MODEL: WDYS Space-saving Dual Output Signal Conditioners Mini-MW Series CURRENT LOOP SUPPLY Functions & Features Powers a 0 ma DC current loop Short circuit protection Applicable to smart transmitters

More information

Power Processor - Series 700F 10KVA to 150KVA

Power Processor - Series 700F 10KVA to 150KVA Power Processor - Series 700F 10KVA to 150KVA Power Conditioning and Regulation for Commercial & Industrial Equipment General Specifications PART 1 - GENERAL 1.1 DESCRIPTION This specification defines

More information

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL PART I: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. a.

More information

Protective Relays Digitrip 3000

Protective Relays Digitrip 3000 New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer

More information

celduc SILD r e l a i s celpac PATENTED! AC Semiconductor Contactor pitch 22,5mm with Diagnostic compact size and DIN rail mounting.

celduc SILD r e l a i s celpac PATENTED! AC Semiconductor Contactor pitch 22,5mm with Diagnostic compact size and DIN rail mounting. AC Semiconductor Contactor pitch,5mm with Diagnostic compact size and DIN rail mounting. Ready to use SinglePhase Relay: " Install it & Forget it!" Zero cross model : 55VAC 5A back to back thyristors on

More information

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. REGULATION AUTOMATIC SYNCHRONIZER for GENERATOR NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

IRI1-ER - Stabilized Earth Fault Current Relay

IRI1-ER - Stabilized Earth Fault Current Relay IRI1-ER - Stabilized Earth Fault Current Relay TB IRI1-ER 02.97 E 1 Contents 1. Summary 2. Applications 3. Characteristics and features 4. Design 4.1 Connections 4.1.1 Analog inputs 4.1.2 Output relays

More information

Description of CERTO controller Standard

Description of CERTO controller Standard Description of CERTO controller Standard E N E R G Y R E C O V E R Y Page 2 Page 4 Page 6 Page 8 Page 9 Page 11 Page 13 Page 22 Page 26 Page 23 1. Functions of the controller 2. Terminal connection 3.

More information

PowerFlex 400 AC Drive Guide Specification

PowerFlex 400 AC Drive Guide Specification PowerFlex 400 AC Drive Guide Specification Adjustable Frequency Drives 3.0 50HP @ 200 to 240V AC 3.0 350HP @ 380 to 480V AC PART 1 GENERAL 1.01 Quality Assurance A. The manufacturer shall have minimum

More information

Laser Particle Sensor Module PM2105

Laser Particle Sensor Module PM2105 Laser Particle Sensor Module PM2105 Application Air purifier, air quality monitor Ventilation system, air conditioner with purifying function Auxiliary product of consumer electronic products Environmental

More information

AEG Low Voltage Component

AEG Low Voltage Component AEG Low Voltage omponent Technology transfers reliable power We are striving to create a peaceful and comfortable life for you. AEG: We believe that power system can be very simple. Main distribution system

More information

ATS22C21Q soft starter-ats22-control 220V-power 230V(55kW)/ V(110kW)

ATS22C21Q soft starter-ats22-control 220V-power 230V(55kW)/ V(110kW) Characteristics soft starter-ats22-control 220V-power 230V(55kW)/400...440V(110kW) Product availability : Non-Stock - Not normally stocked in distribution facility Price* : 2383.00 USD Main Range of product

More information

UBZ-301 (63-630A) UNIVERSAL INDUCTION MOTOR PROTECTION UNIT

UBZ-301 (63-630A) UNIVERSAL INDUCTION MOTOR PROTECTION UNIT Ltd Intelligent industrial electronics UBZ-301 (63-630A) UNIVERSAL INDUCTION MOTOR PROTECTION UNIT OPERATING MANUAL Quality control system on the development and production complies with requirements ISO

More information

Company Replaces previous document Document ID Issue E.ON Energidistribution AB Ny engelsk utgåva D

Company Replaces previous document Document ID Issue E.ON Energidistribution AB Ny engelsk utgåva D Document type Page Verksamhetsstyrande 1 (9) Company Replaces previous document Document ID Issue E.ON Energidistribution AB Ny engelsk utgåva D17-0008995 3.0 Organisation Valid from Valid until Regionnätsaffärer

More information

Variable Transformers Product Design & Engineering Data

Variable Transformers Product Design & Engineering Data Variable Transformers Product Design & Engineering Data Product Design & Engineering Data Type 1010B Cutaway General Information STACO ENERGY PRODUCTS CO. is a leading manufacturer of variable transformers,

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL. Huazheng Electric Manufacturing(Baoding) Co.,Ltd

HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL. Huazheng Electric Manufacturing(Baoding) Co.,Ltd HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL Huazheng Electric Manufacturing(Baoding) Co.,Ltd Safety Terms and Symbols This manual may contain the terms: Warning! Indicate the conditions

More information

Installation and Operating Instructions. Power IT Power Factor Controller RVC

Installation and Operating Instructions. Power IT Power Factor Controller RVC Installation and Operating Instructions Power IT Power Factor Controller RVC Table of contents Page 1. Read this first... 3 About this Instruction Manual... 3 Safety... 3 Electromagnetic compatibility...

More information

ULTRA-K Series 600K - he

ULTRA-K Series 600K - he 5 kva 500 kva ULTRA-K Series 600K - he High Efficiency K-Rated Power Conditioning Transformers Designed to be used with linear or non-linear loads. Applications: Audio / Video Recording Equipment IT Systems

More information

FL ballasts Electronic dimming. PCA T5 EXCITE lp Y, 3 and 4x14/24 W EXCITE T5

FL ballasts Electronic dimming. PCA T5 EXCITE lp Y, 3 and 4x14/24 W EXCITE T5 T PCA T EXCITE lp Y, and x1/ W EXCITE T Product description Processor-controlled ballast with y inside Highest possible energy class CEMA EEI = A1 BAT 1 oise-free precise control via DAI or DSI signal,

More information

ET-3888 True RMS Clamp Meter. User Manual

ET-3888 True RMS Clamp Meter. User Manual ET-3888 True RMS Clamp Meter User Manual Index Introduction... 3 Safety Notes... 4 Features... 5 Specifications... 6-8 Instrument Layout... 9 Measurement... 10 Maintenance... 11 Page 2 1. Introduction

More information

ES-777-MV-P2_A1 03/01/10

ES-777-MV-P2_A1 03/01/10 ENGINEERING SPECIFICATION SYMCOM MODEL 777-MV-P2 Electronic Overload Relay PART 1 GENERAL 1.1 REFERENCES A. UL 508 Industrial Control Equipment Underwriters Laboratories B. IEC 60947 Low Voltage Switchgear

More information

EIB/KNX Switch Actuators. User manual

EIB/KNX Switch Actuators. User manual EIB/KNX Switch Actuators User manual IT KNT 004 IT KNT 012 Tel.: +34943627988 E-mail: knx@dinuy.com Web: www.dinuy.com Contents 1. Introduction --------------------------------------------------------------------------------------------------------------

More information

celduc SIM Phase angle controller Output : VAC 40A(*) Input : Analog 0-10V celpac r e l a i s Proud to serve you

celduc SIM Phase angle controller Output : VAC 40A(*) Input : Analog 0-10V celpac r e l a i s Proud to serve you Power Solid State Relay With Analog Control, pitch.5mm compact size and DIN rail mounting. Ready to use SinglePhase Relay: Phase angle controller Transfer characterisic :Angle open loop Operating voltage

More information

Btdin RCD Add-on Modules 32A - 63A for M.C.Bs 1 module per pole

Btdin RCD Add-on Modules 32A - 63A for M.C.Bs 1 module per pole Index Pages 1. Descripton... 2 2. Product range... 2 3. Overall dimensions... 2 4. Fixing Connection... 3 5. Generl characteristics.... 4-6 6. Compliance - Approvals... 6 7. Curves... 7 1 / 7 1. DESCRIPTION

More information

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz TAC ATV8, IP55 Variable Speed Drives for Asynchronous Motors. -phase. 80/460 V, 50-60 Hz E-60-24 24 May 2004 ATV 8 IP55 drives are specifically designed for pump and fan applications powered by a three-phase

More information

Phase and neutral overcurrent protection

Phase and neutral overcurrent protection Phase and neutral overcurrent protection Page 1 ssued June 1999 Changed since July 1998 Data subject to change without notice (SE970165) Features Two-phase or three-phase time-overcurrent and earth fault

More information

Harmonic restraint earth fault or single-phase overcurrent protection

Harmonic restraint earth fault or single-phase overcurrent protection Harmonic restraint earth fault or single-phase overcurrent protection Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970885) Features Sensitive earth fault protection

More information

Instantaneous Overcurrent Relay

Instantaneous Overcurrent Relay Midos Type MCRI Instantaneous Overcurrent Relay Features High speed operation Not slowed by dc transients Settings readily adjustable on relay front plate Two phase and earth fault relay Figure 1: Type

More information