e 2 TANGO-50 Short-Circuit Detector K Data Sheet
|
|
- Janice Williamson
- 5 years ago
- Views:
Transcription
1 e 2 TANGO-50 Short-Circuit Detector K Data Sheet
2
3 We Create Ideas With Power! e 2 TANGO-50 short-circuit detector is a product of ELEKTROMETAL ENERGETYKA SA developed by our engineers with extensive know-how and many years of experience in the industry. Employed solutions and concepts answer challenges which our customer face in their day-to-day operations. These challenges were our key inspiration during design work. We have developed a compact device, functionally optimised and easy to use, designed mainly for use in compensation cabinets and other locations with limited space. Miniature e 2 TANGO-50 is designed to detect phase short-circuits and ground faults in three-phase MV grids. Like all other our products the device can be used in Smart GRIDS. We fully realize the importance of safety in power engineering, this is why this was one of the key aspects we focused on. High quality and reliability of all our products, including e 2 TANGO-50, is confirmed with tests and certifications. e 2 TANGO-50 is a miniature device ideal for locations where use of large protection relays is not possible. We recommend it to our Customers having full confidence of its capabilities.. Tomasz Klonowski Electronics Designer Elektrometal Energetyka SA 3
4 APPLICATION Small and compact e 2 TANGO-50 may be used as an stand-alone device in indoor and outdoor switchgears, container stations and wiring compartments. The device may also be used to provide complementary protection functionality to PLC controllers in small MV switchgears (such as modular switchgears, compact distribution blocks). The device may be used in harsh atmospheric conditions. e 2 TANGO-50 may interoperate with PLCs using MODBUS protocol or operate as a stand-alone device - short-circuit is indicated via relay contact. Fault indication has to be reset manually using a button. Viewing measured values, event history and confirming events (confirm operation status) is possible using communication links. container stations and indoor switchgears indoor and outdoor switchgears line bays wind power plant bays photovoltaic power plant bays 4
5 ADVANTAGES 2 settings banks event recorder records 32 latest events Rogowski coil for phase current measurement the device may use 1 mv/a sensitivity Rogowski coils, measurement measurement measurement available depending on version communication communication with the device is possible using Ethernet or 2-wire RS485 large measurement transformers hole diameter easy threading of large diameter measurement cables real-time clock synchronisation via communication channel, synchronisation stability better than 1 min/24h compact design small size e 2 TANGO-50 devices have 4 settings banks and a recorder which logs 32 events. The device has a real-time clock. Communication with the device is possible using Ethernet or 2-wire RS485. Phase current may be measured using Rogowski coils (e 2 TANGO-50 RC) with 1mV/A sensitivity, alternatively phase current may be measured using current transformers (e 2 TANGO-50 CT). Depending on version the I0 current may be measured or calculated. The device may be adapted for operation with a totalizer calculating U0 voltage based on phase voltages. It is also possible to measure U1, U2, U3 phase voltages using voltage transformers with a standard input voltage of 2/ V 3 or 3.25/ V 3 (e 2 TANGO-50 RCU). 5
6 DESIGN The following variants of e 2 TANGO-50 are available: e 2 TANGO-50 CT, e 2 TANGO-50 RC, e 2 TANGO-50 RCx, e 2 TANGO-50 RCU, e 2 TANGO-50 RCUx. e 2 TANGO-50 CT J4 connector RS485 connection and voltage measurement input I 3 I 2 LED indicators indication of device status, failures and protection operations communication connector Ethernet I 1 reset switch button allows also checking LED operation and restoring default communication settings current transformers I 1, I 2, I 3 measurement current transformer measurement J1 connector device power, signalling relay output e 2 TANGO-50 RC e 2 TANGO-50 RCx J5 connector connection of Rogowski coil for L3 J4 connector RS485 connection and voltage measurement input current transformer current measurement J1 connector device power, signalling relay output J1 connector connection of Rogowski coils for L1, L2 6
7 e 2 TANGO-50 RCU e 2 TANGO-50 RCUx J6 connector U1 voltage transformer connection J5 connector U2, U3 voltage transformer connection J4 connector RS485 communication connector J6 connector U1 voltage transformer connection J5 connector U2, U3 voltage transformer connection J4 connector RS485 communication connector current transformer measures current J3 connector Connection of Rogowski coil for L3 and GND terminal for coil cable screen J1 connector Device power, signalling relay output J2 connector Connection of Rogowski coils for L1, L2 J3 connector Connection of Rogowski coil for L3 and GND terminal for coil cable screen J1 connector Device power, signalling relay output J2 connector Connection of Rogowski coils for L1, L2 SIGNALLING Colour green (intermittent) red orange Cause Overcurrent protections on Stand-by normal operation Overcurrent type protection (I>, I>>) operation. Signalling is turned off on confirmation of the event (using reset button or a command on communication link). Overcurrent type protection pick-up. The LED turns off when pick-up ends. red green TX signalling for RS485 RX signalling for RS485 red orange Device fault signalling (CRC checksum incorrect, etc.). The LED turns off when the cause is removed and event is confirmed (with Reset button or through a communications link). If the device is turned on with Reset button pressed a countdown to restoring communication parameters starts. Default communication settings will be restored after 15 seconds if the button remains pressed afterwards LED turns off (or will continue with current AL signalling). Fast blinking - indicates measurement simulation mode for protection operation testing. Once simulation is complete the LED will operate as normal. green (intermittent) red orange Ground-fault type protections and zero sequence component overvoltage type protections Stand-by status (I0>, U0>, Y0>, Y0k>, I0k>), normal operation. Ground-fault type protections and zero sequence component overvoltage type protections operation (I0>, U0>, Y0>, Y0k>, I0k>). LED is turned off on confirmation of the event (using reset button or a command on communication link). Ground-fault type protections and zero sequence component overvoltage type protections pick-up. The LED turns off when pick-up ends. K1 relay contact Activated by protection operation or AL signal. The signal is maintained until confirmed (using reset button or communication link) or until automatic reset. 7
8 DESIGN e 2 TANGO-50-CT is designed to measure phase currents with current transformers, measure current with measurement transformer or calculate it, measure U0 voltage.. e 2 TANGO-50-RC is designed to measure phase currents using Rogowski coils (1mV/A sensitivity), measure current using measurement transformer or calculate it, measure U0 voltage. e 2 TANGO-50-RCx is designed to measure phase currents using Rogowski coils (1mV/A sensitivity), current is calculated only. e 2 TANGO-50-RCU is designed to measure phase currents using Rogowski coils (1mV/A sensitivity), phase voltages using voltage transformers (standard input voltage 2/ 3 or 3,25/ 3), measure or calculate I0 current, U0 voltage is calculated only. e 2 TANGO-50-RCUx is designed to measure phase currents using Rogowski coils (1mV/A sensitivity), measure phase voltages using voltage transformers (standard input voltage 2/ 3 or 3.25/ 3), U0 voltage is calculated only. DIMENSIONS 62 e 2 TANGO-50 CT e 2 TANGO-50 RC/RCU 23 e 2 TANGO-50 RCx/RCUx H device H e 2 TANGO-50CT 105 e 2 TANGO-50 RC/RCx 108 e 2 TANGO-50 RCU/RCUx 112 PROTECTION FUNCTIONS PROTOCOLS 50/51 50n/51n 59n 21n 21nd 67n short-circuit / overcurrent protections ground-fault protections zero-sequence component overvoltage type protection admittance based directional admittance based zero-component overcurrent directional protection Modbus TCP Modbus RTU 8
9 WIRING DIAGRAMS Ethernet signalling contact RJ46 J1.2 phase currents are measured using current transformers current is measured using Ferranti transformer RS485 (A) (B) J4.1 J4.2 U0 measurement l2(1) J4.3 phase currents are measured using Rogowski coils (wire length should not exceed 10 m) J2.1 l1.(1) I1 measurement J2.3 l2.(1) I2 measurement KI signalling contact 24 V DC power supply J1.2 J5.1 l3(1) I3 measurement (B) J4.2 current is measured using Ferranti transformer U0 measurement l2(1) J4.3 phase currents are measured using Rogowski coils (wire length should not exceed 10 m) J2.1 l1.(1) I1 measurement J2.3 l2.(1) I2 measurement J5.1 l3(1) I3 measurement KI signalling contact J V DC power supply (B) J4.2 U0 measurement l2(1) J4.3 TANGO-50 RCU phase currents are measured using Rogowski coils (wire length should not exceed 10 m) voltage is measured using voltage transformers J2.1 l1.(1) I1 measurement J2.3 l2.(1) I2 measurement J3.1 l3(1) I3 measurement J3.2 l3(2) J3.3 RC-GND J3.4 RC-GND J5.1 U3(1) U1 measurement J5.2 U3(2) J5.3 U2(1) U2 measurement J5.4 U2(2) KI signalling contact J V DC power supply RS485 (A) J4.3 (B) J4.4 J6.1 U1(1) U1 measurement J6.2 U1(2) TANGO-50 RCUx phase currents are measured using Rogowski coils (wire length should not exceed 10 m) voltage is measured using voltage transformers I0 current is measured using Ferranti transformer J2.1 l1.(1) I1 measurement J2.3 l2.(1) I2 measurement J3.1 l3(1) I3 measurement J3.2 l3(2) J3.3 RC-GND J3.4 RC-GND J5.1 U3(1) U3 measurement J5.2 U3(2) J5.3 U2(1) U2 measurement J5.4 U2(2) J6.1 U1(1) U1 measurement J6.2 U1(2) KI signalling contact J V DC power supply RS485 (A) J4.3 (B) J4.4 9
10 e 2 TANGO-STUDIO SOFTWARE e 2 TANGO-50 short-circuit detector is compatible with e 2 TANGO-Studio engineering software which is dedicated for operation of the device and provides tools for its configuration. Viewing measured values, event history and confirming events (resetting operation status) is possible using communication links and e 2 TANGO-Studio software. TECHNICAL PARAMETERS Auxiliary power supply Voltage Maximum power consumption Basic protection parameters Device operate time Current measurement circuits Rated current Rated frequency Phase current measurement range current measurement range Voltage measurement circuits Rated voltage Un Rated phase voltage n 24 V DC ±15% 3 W typically - 35 ms 5 A (1 A option) 50 Hz for CT version: A for RC/RCU version: mv 0,05-10 A 2/ 3 or 3.25/ V Rated frequency 50 Hz voltage measurement range V Measurement accuracy I1, I2, I3 2,5% U1, U2, U3 2,5% 2.5% (5% when calculated) 2.5% (5% when calculated) φ 0 2 Binary output parameters Voltage at open contacts 250 VAC / 110 VDC Constant load 5 A Environmental conditions Operating temperature -40 C C Storage temperature -40 C C Relative humidity 95% Vibration and mechanical shock resistance Class 1 acc. IEC Electromagnetic disturbances Class B acc. IEC Safety Insulation electric strength 1 kv/50 Hz/60 s acc. IEC Dimensions Protection rating IP 20 Weight (CT / RC / RC-x) approx. 300 g / approx. 180 g / approx. 150 g Dimensions (H x W x D) - CT 105 * 62 * 107 mm - RC 108 * 53 * 107 mm - RCx 108 * 23 * 107 mm - RCU 112 * 53 * 107 mm - RCUx 112 * 23 * 107 mm Phase current transformer hole diameter 13 mm current transformer hole diameter 8,5 mm 10
11 e 2 TANGO-50 VERSIONS CT-1 CT-5 RC RC-x RCU RCU-x e 2 TANGO-50 Phase current measurement using current transformers Rated current 1 A 5 A - - Current measurement using Rogowski coils (3xWE) - - measurement (transformer) - calculation based on phase currents measurement - - calculation Angle measurement ( / ) U 1, U 2, U 3 measurement /- available/unavailable STANDARDS PN-EN PN-EN PN-EN Measuring Relays And Protection Equipment. Part 1: Common Requirements 26 Measuring Relays And Protection Equipment. Part 26: Electromagnetic compatibility requirements Measuring Relays And Protection Equipment. Part 27: Product Safety Requirements CERTYFIKATY I NAGRODY IEn compliance certificate no. 003/2016 Mazowsze Quality Award ELEKTROMETAL ENERGETYKA SA QUALITY Implemented Integrated Management System according to: PN-EN ISO 9001 Quality management systems PN-EN ISO Environmental management systems PN-N Occupational health and safety management systems BS OHSAS Occupational health and safety management systems 11
12 ELEKTROMETAL ENERGETYKA SA Warszawa, ul. Mazura 18A tel. (+48) fax (+48)
PD300. Transformer, generator and motor protection Data sheet
PD300 Transformer, generator and motor protection Data sheet DSE_PD300_eng_AO No part of this publication may be reproduced by whatever means without the prior written permission of Ingeteam T&D. One of
More informationRI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters
RI-D440 Three Phase easywire Multifunction DIN Rail Energy Meter Four module DIN rail mounted Energy pulse LED 330mV Input from easywire CTs (or -/1A and -/5A current transformer input with TAS-SCTEWA
More informationNetworks IT, TN, TT networks 3 and 4-phase networks Up to 4 single-phase networks. Measured data memory 256 MByte Flash 32 MB SDRAM
Power quality Colour graphical display Ethernet connection Ethernet-Modbus gateway Graphic programming Alarm management UMG 508 Multifunction power analyser Communication Profibus (DP/V0) Modbus (RTU,
More informationProtection components
Multifunction protection relays LT-P Environment Conforming to standards IEC 947-4-1, IEC 34-11, IEC 755, VDE 010, VDE 00. &Ãmarking Meets the essential requirements of the Low Voltage equipment (LV) &
More informationMULTIFUNCTION GRAPHICAL UNIT MGU 800
MULTIFUNCTION GRAPHICAL UNIT MGU 800 For display, recording and evaluation of process instruments signals (level, temperature, pressure, etc.) 3.5" TFT display, multi-language menu Variety of possible
More informationSide view View from below Rear view
Dimension diagrams All dimensions in mm Side view View from below Rear view Cut out: 138 +0,8 x 138 +0,8 mm Typical connection SPS SPS 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 DSUB-9 5 4 3 2 1 8 7 6 5 4
More informationModbus communication module for TCX2: AEX-MOD
Modbus communication module for TCX2: Communication Specification TCX2 is factory installed in TCX2 series controllers with -MOD suffix, and is also available separately upon request for customer installation
More informationZelio Control Measurement Relays
Selection Guide Application Voltage control Current control Functions 3-phase Single-phase and d.c. Integrated current transformer - Overvoltage and between phases - Overvoltage and between phases and
More informationPM-311x Quick Start Ver PM-311x introduction 1.1. Caution & Warning 1.2. Product Warranty & Customer Support
PM-311x Quick Start Ver. 1.1 1. PM-311x introduction ICP DAS brings the most powerful, cost-effective, advanced Smart Power Meters PM-3000 series that gives you access to real-time electric usage for single-phase
More informationATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol
Product datasheet Characteristics ATV12HU22M2 Complementary Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component name Variable
More informationTable of Contents. HWIO-Gateway User Manual
User Manual HWIO-Gateway INUX AB Katrinedalsg. 3, 504 51 Borås http://www.inux.se Copyright 2009 Uppdaterad 2010-01-12 Copyright 2009 INUX AB 1 Table of Contents 1. Product overview...3 2. License...3
More informationATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink
Characteristics variable speed drive ATV12-4kW - 5hp - 200..240V - 3ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly
More informationRAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL
RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL 1 Contents 1. Application... 5 2. meter set... 6 3. BASIC REQUIREMENTS, OPERATIONAL SAFETy... 6 4. installation... 10 4.1. Mounting... 10 4.2. External
More informationR24 DISPLAY MODULE WITH ACTIVE OUTPUT AND RELAY
Čapkova 22 678 01 Blansko tel.: +420 516 416942, 419995 fax: +420 516 416963 R24 DISPLAY MODULE WITH ACTIVE OUTPUT AND RELAY Display module is designed for measuring the resistance, the signal from the
More informationPower Meter Series PM3200 Functions and characteristics
Functions and characteristics PB108433 This PowerLogic Power meter offers basic to advanced measurement capabilities. With compact size and DIN rail mounting, the PM3200 allows mains and feeders monitoring
More informationTotalizing Counters mini-i
mini-i Type 634/635 Type 634: Counter with high immunity against magnetic interfere Type 635: Counter with high shock stability Miniature size Low power consumption Electrical connections in standard grid
More informationNPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator
REGULATION Automatic Synchronizer for Generator NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds
More informationPQM3000RGW Class A rack 19 power quality analyzer with Rogowski coils
Class A rack 19 power quality analyzer with Rogowski coils Rack 19 mounting Current inputs for direct connection of Rogowski coils Harmonics and interharmonics measurement Data recording for further EN
More informationRelion 605 series Self-Powered Feeder Protection REJ603 Product Guide
Relion 605 series Relion 605 series Self-Powered Feeder Protection Product Guide Contents 1 Description...3 2 Protection functions...3 3 Application...4 4 Self-supervision...4 5 Inputs and outputs...4
More information1-phase AC current voltages/frequencies Volt Volt
General information AC 01.2 actuator controls for controlling multi-turn actuators of the SA/SAR.2 type range and part-turn actuators of the SG/SGR type range with interface. Features and functions Power
More informationPQM4000RGW Class A DIN 192x144 power quality analyzer with Rogowski coils
Class A DIN 192x144 power quality analyzer with Rogowski coils Current inputs for direct connection of Rogowski coils Harmonics and interharmonics measurement Data recording for further EN 50160 analysis
More informationDRTS-6. DRTS-6 has been designed to test: DRTS-6. Advanced Protection Relay Test Set and Measurement System
DRTS-6 Advanced Protection Relay Test Set and Measurement System MULTI-TASKING EQUIPMENT DESIGNED FOR TESTING PROTECTION RELAYS, ENERGY METERS, TRANSDUCERS POWERFUL AND LIGHTWEIGHT HIGH ACCURACY: BETTER
More informationD SERIES LM16. COMPACT DRIVE V/f and SLV CONTROL. LM16 COMPACT DRIVE V/f and SLV CONTROL
D SERIES LM16 COMPACT DRIVE V/f and SLV CONTROL LM16 COMPACT DRIVE V/f and SLV CONTROL 1 2 SERIES 1 2 page 4 page 6 Introduction Fields of application 3 page 7 4 page 8 Designation Product offer 5 6 page
More informationInstantaneous Overcurrent Relay
Midos Type MCRI Instantaneous Overcurrent Relay Features High speed operation Not slowed by dc transients Settings readily adjustable on relay front plate Two phase and earth fault relay Figure 1: Type
More informationUSER S MANUAL POWER SUPPLY - ISOLATOR - SIGNAL CONVERTER ZSP 41 POWER SUPPLY - ISOLATOR - SIGNAL CONVERTER SIGNAL MULTIPLIER ZSP 41/2
(ENG) DECEMBER 2017 USER S MANUAL POWER SUPPLY - ISOLATOR - SIGNAL CONVERTER ZSP 41 POWER SUPPLY - ISOLATOR - SIGNAL CONVERTER SIGNAL MULTIPLIER ZSP 41/2 ISOLATOR - SIGNAL CONVERTER TYPE SP 11 CURRENT
More informationUMG 509-PRO. Multifunction power analyser with RCM
UMG 509-PRO Multifunction power analyser with RCM Power quality RCM Residual current monitoring Ethernet connection Ethernet-Modbus gateway Graphic programming Alarm management Communication Profibus (DP/V0)
More informationSWT 3000 Teleprotection technical data siemens.com
Power network telecommunication SWT 3000 Teleprotection technical data siemens.com Sustainable success for high-voltage power networks The SWT 3000 Teleprotection system has been the first choice for reliable
More informationTheta 20A / 20V. Technical Data Sheet. Special Features
Technical Data Sheet Theta 20A / 20V Theta 20A / 20V is used to measure and convert AC Voltage or Current input into a load independent DC current or voltage output signal. Special Features Available in
More informationNPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.
REGULATION AUTOMATIC SYNCHRONIZER for GENERATOR NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds
More informationHV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point
2010 MAP Range HV / MV / LV electrical network quality analyzers Class A > Network quality Analyzers PRODUCT ADVANTAGES COMPLIANT with the EN 61000-4-30 standard, Class A DETECTION of the fault LOCATION
More informationREE series digital interpolators
Data sheet L-957-939-0-B REE series digital interpolators The REE digital series of interpolators is designed to accompany the RG ( µm) and RG (0 µm) encoder systems by offering a wide range of interpolation
More informationProtection relays and transformers
NEW ZEALAND WWW.LPINZ.CO.NZ Unit 6/22 Moselle Ave, Henderson, Auckland, New Zealand PO Box 21-872, Henderson, Auckland, New Zealand Phone:+64 9 833 5749 Email:info@LPINZ.co.nz Web: www.lpinz.co.nz Protection
More informationES-777-MV-P2_A1 03/01/10
ENGINEERING SPECIFICATION SYMCOM MODEL 777-MV-P2 Electronic Overload Relay PART 1 GENERAL 1.1 REFERENCES A. UL 508 Industrial Control Equipment Underwriters Laboratories B. IEC 60947 Low Voltage Switchgear
More information12/2 Product overview. 12/3 7KT1 14, 7KT1 53 E-counters. 12/9 7KT1 11, 7KT1 12 digital measuring devices. 12/11 7KT1 0 analog measuring devices
BETA Measuring /2 Product overview /3 7KT1 14, 7KT1 53 E-counters /9 7KT1 11, 7KT1 digital measuring devices /11 7KT1 0 analog measuring devices / 7KT5 8 time and pulse counters /14 7KT5 5, 7KT5 6 time
More informationSmart Energy & Power Quality Solutions. Portable energy measurement devices COMPACT FLEXIBLE PRECISE
Portable energy measurement devices COMPACT FLEXIBLE PRECISE Portable energy measurement devices COMPACT FLEXIBLE PRECISE The portable energy measurement devices from Janitza Stay flexible with the portable
More informationPRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID
RI-D140 Three Phase Multifunction DIN Rail Energy Meter (MID Certified) Four module DIN rail mounted Energy pulse LED True RMS measurement Cost effective and accurate Modbus communication -/1A or -/5A
More informationPRELIMINARY DATA SHEET. RI-F400 Series. easywire Single and Three Phase Multifunction Energy Meter
Telephone : 44 (0) 1245 428500 PRELIMIARY DATA SHEET RIF400 Series easywire Single and Three Phase Multifunction Energy Meter DI 96 panel mounted 330mV Input from easywire CTs (or /1A and /5A current transformer
More informationMultimeter 500CVD21 RTU500 series
Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase
More informationINSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W
Page 2 / 16 INDEX: GENERAL TYPES ACESSORIES AND OPTIONS INSTALLATION WIRING DIAGRAMS CONNECTING TERMINALS DIAGRAMS WIRING DIAGRAM DESCRIPTION WORKING DESCRIPTION AND KEYBOARD WORKING DESCRIPTION AND PROGRAMMING
More informationSINEAX B 811 Power Pack with additional Functions
SINEA B 8 for intelligent and conventional s, in housing S7 for rail and wall mounting 002 II () G Application The power supply unit SINEA B 8 (Figure ) provides the DC power supply for s and transfers
More information02/11/2015
Emergency stop and safety guard monitoring 2 channels KNE3-YS Part number 85102436 "Emergency stop" & "Safety gates monitoring" functions Single and 2-channel operation Security with redundancy and feedback
More informationKončar TMS - Bushing monitoring
Končar TMS - Bushing monitoring Many recent studies have shown that bushing failure is one of the most common causes of transformer failure. Thus need for bushing diagnostic and monitoring system has risen.
More informationEnergy Management Energy Meter Type EM111
Energy Management Energy Meter Type EM111 Easy connection or wrong current direction detection Other versions available (not certified, option X: see how to order on the next page Single phase energy meter
More informationEnergy Management Energy Meter Type EM112
Energy Management Energy Meter Type EM112 Easy connection or wrong current direction detection Other versions available (not certified, option X: see how to order on the next page Single phase energy meter
More informationSYNCHRONISM RELAY SYNCRO-96. (Code ) INSTRUCTION MANUAL ( M / 99A ) (c) CIRCUTOR S.A.
SYNCHRONISM RELAY SYNCRO-96 (Code 2 28 913-2 28 914-2 28 915) INSTRUCTION MANUAL ( M 981 196 / 99A ) (c) CIRCUTOR S.A. ----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 1 Synchronism relay
More information1000Vac distribution system for Signalling System applications
1000Vac distribution system for Signalling System applications System for Transforming, Carrying and Distributing 1000Vac electric energy for technological equipment and devices along the railway line.
More informationNOVOHALL Rotary Sensor non-contacting. Series RSC2800 digital SSI, SPI, Incremental
NOVOHALL Rotary Sensor non-contacting Series RSC2800 digital SSI, SPI, Incremental The RSC 2800 sensor utilizes a contactless magnetic measurement technology to determine the measured angle. Unlike conventional
More informationMETERSUK. SmartLink D Y N A M i T E. EM415 MOD Series. User Manual KEY FEATURES INDEX 3. TECHNICAL DESCRIPTION. Single Phase Metering
METERSUK LTD s a l e s @ m e t e r s. c o. u k 0 1 5 2 4 5 5 5 9 2 9 Series Smart Energy Meter KEY FEATURES Single Phase Metering Single phase metering 4 din modules, Standard DIN rail Format (DIN43880)
More informationSmart Energy & Power Quality Solutions. UMG 96RM Universal measurement instrument (EN 50160, IEEE 519, ITIC)
Smart Energy & Power Quality Solutions UMG 96RM Universal measurement instrument (EN 50160, IEEE 519, ITIC) UMG 96RM UMG 96RM Universal measurement instrument Unrivalled in its class The UMG 96RM is a
More informationMeasuring centers MC7x0 series Multifunction Meter MC740
Measuring centers MC7x0 series Multifunction Meter MC740 o Measurements of instantaneous values of more than 130 quantities (U, I, P, Q, S, PF, PA, f, φ, THD, MD, energy, energy cost by tariffs, etc.)
More informationEnergy Management Energy Meter Type EM340
Energy Management Energy Meter Type EM340 Digital input (for tariff management Easy connection or wrong current direction detection Certified according to MID Directive (option PF only: see how to order
More informationSPAD 346 C Stabilized differential relay
SPAD 346 C Stabilized differential relay Stabilized Differential Relay Type SPAD 346 C Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault
More informationsw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS
INSTRUCTIONS MANUAL IM831-U v0.92 HRI-R40W sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INDEX: GENERAL TYPES ACESSORIES AND OPTIONS
More informationRUDOLF Digital power analyzer. Advanced Version
RUDOLF Digital power analyzer Advanced Version Digital power analyzer Advanced Version Company Introduction Bridex Singapore Pte Ltd is founded in 1978 as a manufacturer of instruments transformer for
More informationCircuit Breakers. Excerpt from Master Catalogue. Circuit Breakers. Specifically For You
Circuit Breakers Excerpt from Master Catalogue Circuit Breakers Specifically For You Hydraulic-magnetic technology ensures reduced nuisance tripping with temperature variance Always holds 00% rated current
More informationDIGITAL SYNCHRONIZING UNIT KS3.2 SERVICE MANUAL. 144 x 144 x 77 mm C E R T I F I E D
DIGITAL SYNCHRONIZING UNIT KS3.2 C E R T I F I E D 144 x 144 x 77 mm SERVICE MANUAL 1 CONTENTS 1. APPLICATION... 3 2. DELIVERY SPECIFICATION... 3 3. BASIC SAFETY REQUIREMENTS AND USER S SAFETY... 4 4.
More informationSRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS
ELECTRICAL ENGINEERING DIVISION Distribution Network Department SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELA T150.2 en SRA 2250/6 Resistor specification The SRA 2250/6 Resistor is intended to increase
More informationAC 01.2 Modbus TCP/IP
General information Actuator controls AC 01.2 for controlling multi-turn actuators of the SA/SAR.2 type range and part-turn actuators of the SQ/SQR.2 type range with interface. Features and functions Power
More informationSIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay
Overcurrent Protection / 7SJ46 SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Function overview Fig. /11 Description The SIPROTEC easy 7SJ46 is a numerical overcurrent protection relay which
More informationIndustrial Modbus I/O Modules
Industrial Modbus I/O Modules Modbus I/O Modules Introduction & Features Digital Input / Output Modules Analog Input / Output Modules Modbus I/O Modules The Best Choice For Your SCADA Applications Introduction
More informationFault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice
Issued: April 1999 Status: Updated Version: B/08.11.200 Data subject to change without notice Features Versatile, multifunction line fault indicator for distribution networks Overcurrent, earth-fault and
More informationEnergy Management Energy Meter Type EM21 72R Retro-Fit
Energy Management Energy Meter Type EM21 72R Retro-Fit Including 3 miniature split-core current sensors 10mm (90A), 16mm (150A) and 24mm (250A) diameter holes Class A (kwh) according to EN50470-3 Class
More informationINSTALLATION MANUAL. Model: Smart Analyzer Manufacturer: Smart Impulse. Power meter with consumption breakdown by use 03/12/13
INSTALLATION MANUAL Model: Smart Analyzer Manufacturer: Smart Impulse Power meter with consumption breakdown by use 03/12/13 Table of contents Table of contents... 2 1. Introduction... 3 2. Installation
More informationAC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS)
AC CURRENT GENERATOR PERFORMANCES Wide range of current 50 db dynamic range Signal-to-noise ratio: 80 db open loop protection Stability < 0,1% Very low THD distortion < 0,3% External synchronization Build-up
More informationsatech SynchroStar GPS 200 Series
satech SynchroStar GPS 200 Series KEY BENEFITS Designed with high quality oscillator OCXO the device is characterized by superior frequency stability and improved holdover performance that allows maintaining
More informationRISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics
Power Quality Monitor Individual Harmonics measurement upto 56th Harmonics True representation of Voltage & Current waveforms. Phasor Representation of All 3 phases for system analysis Real Time Clock
More informationClassification Enclosure rating Contact form Contact material
PCB Relay Low-profile power relay with maximum switching of 10 A Low profile: 12.3 mm in height Max. switching capacity: 2,500 VA (NO) Dielectric strength: 5 kv Clearance and creepage distance: 10 mm.
More informationATV12H018F1 variable speed drive ATV kW hp V - 1ph
Characteristics variable speed drive ATV12-0.18kW - 0.25hp - 100..120V - 1ph Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component
More informationSVP CONTROL AND VISUALIZATION OF VOLTAGE, PHASE AND FREQUENCY IN THREE-PHASE LINES WITH NEUTRAL
1/5 CONTROL AND VISUALIZATION OF VOLTAGE, PHASE AND FREQUENCY IN THREE-PHASE LINES WITH NEUTRAL Function Operating mode Voltage control Phase sequence control Control unbalance Ln-Ln Control unbalance
More informationATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink
Characteristics variable speed drive ATV12-0.37kW - 0.55hp - 100..120V - 1ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application
More informationEnergy Management Energy Analyzer Type EM111
Energy Management Energy Analyzer Type EM111 Single phase energy analyzer Class 1 (kwh according to EN62053-21 Class B (kwh according to EN50470-3 Accuracy ±0.5% RDG (current/voltage Direct current measurement
More informationRI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters
RI-F200 Series Single and Three Phase Multifunction Energy Meter DIN 96 panel mounted -/1A or -/5A current transformer input Single phase or three phase network compatible Programmable voltage and current
More informationAMU-214 Auxiliary Monitor Unit Operations Manual
AMU-214 Auxiliary Monitor Unit THIS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE AMU-214 SERIES ITS CABINET AUXILIARY MONITOR UNIT. REVISION: SEPTEMBER 2008 pn 888-0214-001 THE AMU-214 SERIES AUXILIARY
More informationElectronic relays. Monitoring. Monitoring
Electronic relays Neither overload nor underload are particularly good for machines and installations in industrial applications. An unsteady power supply may lead to machine failure and, thus, expensive
More informationENGLISH 3 Phase Multi-function Power Meter 1/5A MID MID
Professionally approved products. Datasheet Stock Number: 144-0527 3 Phase Multi-function Power Meter 1/5A MID 96mm² Panel Mounted Power Meter. MID UK Specifications The 144-0527 is a new generation modern
More informationIRI1-ER - Stabilized Earth Fault Current Relay
IRI1-ER - Stabilized Earth Fault Current Relay TB IRI1-ER 02.97 E 1 Contents 1. Summary 2. Applications 3. Characteristics and features 4. Design 4.1 Connections 4.1.1 Analog inputs 4.1.2 Output relays
More informationData Acquisition Modules/ Distributed IO Modules
User Manual Data Acquisition Modules/ Distributed IO Modules Future Design Controls, Inc. 7524 West 98 th Place / P.O. Box 1196 Bridgeview, IL 60455 888.751.5444 - Office: 888.307.8014 - Fax 866.342.5332
More informationM.3. Electrical measurement and control. Electrical energy meters for partial consumption
M.3 Electrical measurement and control Electrical energy meters for partial consumption M.3 Electrical energy meters for partial consumption M.3 - Electrical energy meters for partial consumption Introduction
More informationPQM3000 Class A rack 19 power quality analyzer for CTs or current clamps
Class A rack 19 power quality analyzer for CTs or current clamps Two different models, for CTs or current clamps Rack 19 mounting Harmonics and interharmonics measurement Data recording for further EN
More informationEnergy Management Energy Analyzer Type EM210
Energy Management Energy Analyzer Type EM210 Multi-use housing: for both DIN-rail and panel mounting applications Current inputs AV option: CT 5A Current inputs MV option: current sensor 333 mv (CTV series)
More informationBU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS
INSTRUCTION MANUAL BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS 1/23 More information than that reported
More informationOvercurrent Protection / 7SJ45
Overcurrent Protection / SJ SIPROTEC easy SJ numerical overcurrent protection relay powered by CTs Fig. / Description SIPROTEC easy SJ numerical overcurrent protection relay powered by current transformers
More informationCurrent consumption ma solenoid current consumption ( max 300 ma) Hz % V ma. Housing dimensions mm 120(d) x 99(h) x 23(w)
89 610/112 ED EWM-A-SV ANALOG AMPLIFIER CARD SERVOVALVE CONTROL RAIL MOUNTING TYPE: DIN EN 50022 OPERATING PRINCIPLE This card is designed for a dynamic control of servovalves with the current output controlled
More informationPLA 33. Power line analyzer. User and service manual. version 2.4
PLA 33 Power line analyzer User and service manual version 2.4 Content. Front control panel and terminal plate...3 7.2.2. System frequency setting...0 2. Device description...4 7.2.3. Password protection...0
More informationTechnical recommendation for the purchase of Real Time Thermal Rating for transformers
Version: 1.0 Date of Issue: December 2014 1 Technical recommendation for the purchase of Real Time Thermal Rating for transformers 1 Purpose The purpose of this document is to set out and describe the
More informationNOVOTURN Multiturn Sensor non-contacting. Series RSM-2800
NOVOTURN Multiturn Sensor non-contacting Series RSM-2800 Special features Non-contacting, magnetic Long life Electrical range 720 up to 5760 in 360 -steps available (2 to 16 turns) True-Power-On System:
More informationB850 Boiler House Energy Monitor
Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without
More informationB850 Boiler House Energy Monitor
Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without
More informationHigh-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime
Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with
More informationMedium Voltage Products. KECA 80 C85 Indoor current sensor
Medium Voltage Products KECA 80 C85 Indoor current sensor Parameters for Application Value Rated primary current of application up to 2 500 A Sensor Parameters Value Highest voltage for equipment, U m
More informationa * example of application MeaSUreMent and ViSUalization of power network parameters Ethernet TCP IP RS-485 USB HOST /SD CARD
3x 0/4...20 ma 8x nd40 ṉ - power network analyzer / recorder Measurement and recording of over 500 electric energy quality parameters acc. to en 50160, en 61000-4-30, en 61000-4-7 standards. Measuring
More informationTechnical Data Sheet. x1000. kwh R Y B
Technical Data Sheet x1000 Von kwh IRev 3600 imp /kwh R Y B is a compact multifunction instrument which is a 96mm x 96mm panel mounted kilowatt hour meter it measures active energy with class 1.0 accuracy
More informationClassification Enclosure rating Contact form Model Standard Flux protection SPST-NO G6RL-1A
PCB Relay Low-profile power relay with maximum switching of 8 A Low profile: 12.3 mm in height Max. switching capacity: 2,500 VA (NO) Dielectric strength: 5 kv Clearance and creepage distance: 10 mm. RoHS
More informationPower quality Harmonics up to 40th harmonic Rotary field components Distortion factor THD-U / THD-I
Memory 256 MB Alarm management Residual current measurement Homepage Ethernet-Modbus gateway BACnet (optional) UMG 96 RM-E Power analyser with Ethernet and RCM Communication Modbus (RTU, TCP, Gateway)
More informationSingle Channel Loop Detector
Single Channel Loop Detector Model LD120T Series The LD120T is a series of single channel inductive loop detectors. The use of microprocessor and surface mount technology enables a large number of functions
More informationDPF-MAC Auto power factor controller
Digital Electric& Electronics System DPF-MAC Auto power factor controller MULTI POWER FACTOR AUTOMATIC MULTI POWER FACTOR AUTOMATIC Introduction DPF-MAC increases usage efficiency by controlling the power
More information10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units
BETA Switching Transformers, Bells and Socket Outlets /2 Product overview /3 4AC3 0, 4AC3 1 bell transformers /5 4AC3 4... 4AC3 transformers for permanent loads /8 4AC2 4 power supply units / 7LQ2 2 bells
More informationCompact Multiprotocol I/O Module for Ethernet 8 Universal Digital Channels, Configurable as PNP Inputs or 0.5A Outputs TBEN-S1-8DXP
PROFINET device, EtherNet/IP device or Modbus TCP slave Integrated Ethernet switch Supports 10 Mbps/100 Mbps 2x M8, 4-pin, Ethernet fieldbus connection Glass fiber reinforced housing Shock and vibration
More information1-phase AC current Voltages/frequencies Volt Volt 110, 115, , 230, 240 Hz Hz 60 50
General information AC 01.2 actuator controls for controlling multi-turn actuators of the SA/SAR.2 type range and part-turn actuators of the SQ/SQR type range with Modbus RTU interface. Features and functions
More information