System Components. David Mahlmann Spring 2003
|
|
- Oscar Heath
- 6 years ago
- Views:
Transcription
1 System Components David Mahlmann Spring 2003
2 Here s the plan. To describe all of the parts of the system, summarize how they work and interact In the next section on Transmission System Operation we will address how they work together
3 Parts is Parts! Generation Transmission Load System Interactions
4 Generation Reference 2002 Load & Capacity Report
5 Generators provide only two quantities MW - Real Power MVAR Reactive Power Let s look at the the MW first.
6 Generator MW - who needs em? Loads - Energy (aka the money maker) System - Control power distribution on the system System - Provide reserve System - Balance load and losses requirement to control net-interchange We will talk about the system needs for MW, and how they are met as we proceed through this program. Without the system energy can t get to the load and everyone loses.
7 Generators - MW output Equipment Prime Movers Boilers, Gas turbines, Hydro turbines, internal combustion, wind turbines, fuel cells
8 Generators - MW output Equipment
9 Restrictions on MW production Response rate limits thermodynamics Equipment failures tubes, boiler feed pumps, fans, water chemistry control Environmental limits emissions gases, air and water temperature limits On a given day, the generator operator should have a good handle on the MW generation capability.
10 Generator MVAR - who needs em? Load Provide reactive power demands of the load Maintain voltage quality Minimize sub-transmission/distribution losses System - Power Transfer Maintain secure voltage profile on Bulk Power System (BPS) Minimizes transmission losses System - Contingency Response Sustain post-contingency voltages Damp out system voltage and power swings to maintain system stability and avoid voltage collapse
11 Generators - MVAR output Equipment Exciters Automatic Voltage Regulators Power System Stabilizers Limits to MVAR output Generator heating Generator cooling systems Auxiliary system voltage requirements
12 Generators - MVAR output Equipment Stator Windings Field Coils Field Forging Coil Slot
13 Restrictions on MVAR production Stator and rotor heating conditions D-Curve Equipment failures AVR out of service System constraints station service voltages, local system voltage constraints On a given day, the generator operator should have a good handle on the MVAR generation capability.
14 MVARS are controlled along with voltage by adjusting excitation current. Higher Field Current produces LAGGING power factor (Vars out of Generator) Lower Field Current produces LEADING power factor (Generator absorbs Vars) Generator must be operated within the limits of the D Curve
15 Lag Per Unit MVAR PSI 45 PSI 30 PSI Per Unit MW.7.70PF.80PF.90PF PF.98PF.98PF.95PF.90PF.7 Generator D Curve
16 How is generation distributed in New York? By fuel type By location
17 Generation Sources Other Combined Cycle Gas Turbine Steam Oil/Gas Source: 2002 Load & Capacity Data Hydro Steam Nuclear Steam Coal MW % Steam Oil & Gas % Steam Coal % Steam Nuclear % Hydro % Combined Cycle % Gas Turbine % Other 448 1% Total Capability 36342
18 Saunders Chateauguay New York State Transmission System Moses- St. Lawrence Dennison Colton Massena Willis Plattsburgh Sandbar Legend: 765 kv 500 kv 345 kv 230 kv 115 kv Beck Niagara Huntley Stolle Rd. Gardenville Dunkirk Somerset Sta.80 Robinson Rd. Homer City Pannell Meyer Andover Palmiter Watercure Hillside Oswego Complex Oakdale Adirondack Marcy Clay Edic Lafayette Richfield Springs Central - East Hoosick Porter Inghams Fraser Coopers Corners Rock Tavern Gilboa Roseton Rotterdam Buchanan Ramapo W49St/Rainey Whitehall Blissville New Scotland Total - East Farragut Goethals Alps Leeds Pleasant Valley Millwood Sprainbrook Dunwoodie Bennington Shore Rd. E.Garden City
19 Transmission Reference 2002 Load & Capacity Report
20 Transmission - The switchyard and beyond What do I need to know about transmission, and why? What happens to my MW & MVARS when they leave the plant?
21 Transmission NY State - Large sources of generation are located far from heaviest load Bulk Power Transmission System transports energy from source to sink 765, 345, & 230 KV lines make up the Bulk Power System
22 Miles of NY Transmission by KV Class Miles of NY Transmission by KV Class KV Class Miles / KV 500KV 345 KV 230 KV 115/138 KV
23 Saunders Chateauguay New York State Transmission System Moses- St. Lawrence Dennison Colton Massena Willis Plattsburgh Sandbar Legend: 765 kv 500 kv 345 kv 230 kv 115 kv Beck Niagara Huntley Stolle Rd. Gardenville Dunkirk Somerset Sta.80 Robinson Rd. Homer City Pannell Meyer Andover Palmiter Watercure Hillside Oswego Complex Oakdale Adirondack Marcy Clay Edic Lafayette Richfield Springs Porter Inghams Fraser Coopers Corners Rock Tavern Gilboa Roseton Rotterdam Buchanan Ramapo W49St/Rainey Whitehall Blissville Hoosick New Scotland Farragut Goethals Alps Leeds Pleasant Valley Millwood Sprainbrook Dunwoodie Bennington Shore Rd. E.Garden City
24 Transmission Components Conductors - overhead and underground Breakers, disconnects and substation equipment Transformers voltage control, power control Voltage control equip. - capacitors, reactors, SVC
25 Capacitors Circuit Breakers Reactors Transformers
26 Transmission System MW Controls Phase Angle Regulators Flexiable AC Transmission (FACTS) HVDC Transmission HVDC Lines Back to back terminals
27 Transmission System MVAR Controls Load Tap Changing Transformers (LTCs) Supervisory controlled LTCs allow system operators to change tap ratios. Shunt Capacitor and Reactors Unlike AVRs and SVCs, these device provide step changes in the VAR support. Static VAR Compensators (SVCs) Static Var Compensators(SVCs) and STATCOM devices perform a special function of high speed continuous voltage support.
28 Restrictions on Transmission Equipment Heating Overhead wire sag Underground cable heating Transformer overheating Arcing high voltage Insulation breakdown loose connections
29 Transmission Equipment Ratings Normal permissible continuous loading 24/7 Long Term Emergency (LTE) typically 4 hours Short Term Emergency (STE) typically 15 min On a given day, the system operator should have a good handle on the transmission equipment limitations.
30 Load Reference 2002 Load & Capacity Report
31 Load and Losses All end users of energy are load Residential Customers Industrial Customers Pumped Storage units Losses are MW that are used by the system Transformers, wire losses, etc. Average is about 3.5% of system load Takes 900 MW of generation to run the NY system. A recent peak was 30,311 MW. Losses at that time were 1030 MW
32 Load is Variable that must be served Daily Load shape Weekday Weekend/Holiday Summer Winter Today usually similar to yesterday, with variations Daily Load Variations Temperature/humidity Cloud Cover / Wind Speed Economic Conditions Street lighting load in the state MW
33 A Summer Peak Load Pattern 24 Hour Load Profile :00 1:00 2:00 3:00 4:00 5:00 6:00 7:00 8:00 9:00 10:00 11:00 12: :00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00 Time Load (MW)
34 Load (MW) A Typical Fall Weekday 24 Hour Load Profile :00 1:00 2:00 3:00 4:00 5:00 6:00 7:00 8:00 9:00 10:00 11:00 12: :00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00 Time
35 Load (MW) A few days before Christmas 24 Hour Load Profile :00 1:00 2:00 3:00 4:00 5:00 6:00 7:00 8:00 9:00 10:00 11:00 12: :00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00 Time
36 System Interactions Power System Physics 101 Reference 2002 Operating Study
37 Power System Physics ) Power, Losses and voltage level 2) Wires, ground and electric fields 3) Power Distribution 4) Generic Security Constrained Operation 5) Transmission Interfaces
38 1) Power, Losses, and Voltage Level Power is the product of the voltage and the current. The same power transfer occurs with a high voltage/low current as with corresponding low voltage high current. Energy losses to heat on a line increase with the square of the current. Energy is efficiently transferred at high voltage an relatively low current.
39 2) Wires, Ground, and Electric fields Transmission is weird fact of physics #1 Based on the operating voltage and distance between the conductor and ground, transmission lines act like capacitors, generating MVARs
40 2) Wires, Ground and Electric fields (cont.) Transmission is weird fact of physics #2 Based on the conductor size, shape, spacing and current (power) flow, transmission lines act like big inductors, absorbing MVARs
41 2) Wires, Ground and Electric fields (cont.) Combining weird physics facts 1 & 2 MVAR Loading - MW Surge Impedance loading for a 100 mile 230KV line Depending on loading, a transmission line may be generating or absorbing MVARs
42 3) Transmission Flow a) Power flow distribute according to composite network impedance 100 MW 50 MW 50 MW 80 MW 20 MW
43 3) Transmission Flow a) Power flow distribution can be controlled by dispatch A 33 MW B 100 MW 0 MW 67 MW 33 MW A system with six lines of equal length, identical construction 100 MW C Loading per line BC = 33/2 =16.5MW Loading per line AC = 67/2 =33.5MW
44 3) Transmission Flow b) Power flow distribution can be controlled by dispatch 90 MW A 30 MW 3 MW B 10 MW 60 MW 3 MW A system with six lines of equal length, identical construction 100 MW C 30 MW 7 MW Loading per line BC = 37/2 =18.5MW Loading per line AC = 63/2 =31.5MW
45 3) Transmission Flow c) The flow redistributions can be calculated for any transmission or generation outage A 45 MW 2.5 MW 90 MW 10 MW B 45 MW 2.5 MW A system with six lines of equal length, identical construction 100 MW C 45 MW 7.5 MW Loading per line BC = 52.5/2 =26.25MW Loading per line AC = 47.5/1 =47.5MW
46 4) Generic Security Constrained Operation System Monitoring Contingency evaluation Loss of any transmission element Loss of any generator Security Constrained Dispatch & Scheduling Dispatch the system to a level where any single contingency will not cause a system overload (emergency) anywhere in the system
47 LOAD FLOW MAP UPNY Beck Somerset Sta. Oswego Oswego Complex Fitzpatrick Massena vvv Moses Chateauguay Willis Plattsburgh vvv Niagara Somerset Switch yard Sta.80 Pannell Sithe 9mi2 9mi1 Scriba Marcy Volney vvv vvv vvv vvv Porter Adirondack Rotterdam vvv Elm St. Packard Robinson Rd. Stolle Rd. Elbridge Clay DeWitt Edic Gilboa 99 BUS New Scotland Leeds Alps Athens Huntley Gardenville Meyer Watercure Lafayette Fraser Hurley Pleasant Valley Long Mt. Dunkirk Hillside vvv vvv Oakdale Coopers Corners Roseton E. Fishkill Pleasantville Dunwoodie Wood St. Millwood So. Ripley Erie So. \PRESENTATIONS\LOADFLOW_BASE 12/11/00 CHJ Homer City Towanda Legend: 765 kv 500 kv 345 kv 230 kv Rock Tavern Ramapo vvv Shore Rd. Buchanan Rainey Sprainbrook E. 13th W. 49th E.Garden City Tremont Farragut
48 5) Transmission Interfaces The transmission system has characteristics that may limit the amount of energy transfer Thermal Capability - by equipment or interface Megawatt limits A interface may load in way that one element hits a limit before all the lines have reached their limits. Voltage Limits - by equipment Low & High to avoid voltage & equipment damage Stability/Voltage Collapse Limits by interface To keep the system together
49 5) Transmission Interfaces (cont.) Transmission Interfaces are lines or groups of lines that have identified flow characteristics and operating limits Thermal limits System Stability Voltage collapse
50 Transmission Constraints on Central East Winter Operating Study 2001 Thermal Limit MW Emergency Limit 3450 MW Post Contingency Voltage Transfer Limit Dynamic Based on: Loss of Phase II in New England New Scotland #99 Bus Fault Marcy South Tower Fault Stability Limit 3100 MW w/ 3 Oswegos, 6 Sithe, both SVC s 3050 MW w/ #32 Oakdale-Fraser O/S 2900 MW w/ #4 Lafayette-Oakdale O/S
51 PENALTIES ON CENTRAL-EAST Oswego Complex Penalty Min Sithe Units I/S Both I/S Leeds/Fraser SVCs One SVC I/S Both O/S 4 of 5 units I/S of 5 units I/S of 5 units I/S of 5 units I/S of 5 units I/S STABILITY LIMIT = ( )
52 Dysinger East NEW YORK INTERNAL INTERFACES West - Central Central - East NS1 & SR2 Stolle - Meyer 67 Andover - Palmiter 932 Lockport - Telegraph Rd N. Akron N. Akron Oakfield Sweden Sweden 113 Moses South Pannel - Clay 1 & 2 Stolle - Meyer 67 Mortimer - Elbridge 1 & 2 Quaker - Sleight Rd. 13 Pannel - Farmington So. Perry - RGE 906 Clyde - NYSEG Farmington - NMPC Quaker - Macedon 930 Andover - Palmiter 932 Total East Plattsburgh - Vermont PV20 Edic - New Scotland 14 Marcy - New Scottland 18 Porter - Rotterdam 30 & 31 Richfield Springs - Inghams 942 Inghams PAR Inghams R81 (OCB) UPNY - Con Ed Massena - Marcy MSU1 Dennison - Sand Stone 5 Dennison - Colton 4 Alcoa - Browning Moses - Adirondak 1 & 2 Sprain Brook - Dunwoodie South Dunwoodie - Rainy 71 & 72 Dunwoodie - Sherman Creek 31 Dunwoodie So. - E 179th St Sprian Brook - Tremont X28 Sprain Brook - W 49th M51 & M 52 Jamaica - Valley Stream 901 Jamaica - Lake Success 903 Plattsburgh - Vermont PV20 Edic - New Scottland 14 Marcy - New Scottland 18 Porter - Rotterdam 30 & 31 Richfield Springs - Inghams 942 Inghams PAR Inghams R81 (OCB) Fraser - Gilboa GF5-35 West Woodbourne (T1-52) Ramapo - So. Mahwah 69 & 70 Ramapo - Branchburg 5018 Coopers Corners - Rock Tavern 34 & 42 Linden - Gothals A 2253 Hudson - Farragut B 3402 & C 3403 Ramapo - Buchanan 94 Ladentown - Buchanan 88 Roseton - East Fishkill 305 Pleasant Valley - East Fishkill F36 & F37 Pleasant Valley - Wood St. F30 Pleasant Valley - Millwood F31 Fishkill - Sylvan Lake 990 East Fishkill Bank Con Ed LIPA SprianBrook - E. Garden City Y49 Dunwoodie - Shore Rd Y50 Jamaca - Lake Success 901 Jamaca - Valley Stream 903 Northport - Norwalk Harbor 1385
53 NYISO Transmission System Constraints New York State Transmission System 2,500 MW Moses- St. Lawrence Dennison Moses South Colton Saunders Massena Chateauguay Willis Plattsburgh Sandbar 4,400 MW Legend: 765 kv 500 kv 345 kv 230 kv 115 kv Dysinger East Oswego Complex Somerset West - Central Beck Niagara Sta.80 Pannell Homer City Adirondack Marcy Central - East Hoosick Coopers Corners Rock Tavern Roseton Rotterdam Buchanan Ramapo W49St/Rainey Whitehall Blissville New Scotland Farragut Goethals Pleasant Valley Millwood Sprain Brook - Dunwoodie Sprainbrook Dunwoodie Bennington Robinson Rd. Clay Edic Porter Huntley Lafayette Gilboa Alps Stolle Rd. Richfield Inghams Leeds Gardenville Meyer Springs Dunkirk Andover Palmiter 4,700 MW Total - East 5,500 MW Fraser Watercure Hillside Oakdale 8,000 MW Upny - Con Ed Shore Rd. E.Garden City 5,000MW Con Ed-LIPA
54 Unique Features Phase Shifters Gilboa Pumped Storage Gas Turbines Wheel Through Energy Circulation
55 We have looked at the big pieces. Generation Transmission Load System Interactions Next we will go ahead with how the pieces work together to keep the lights on
Transmission Operations & Real Time System Security. David Mahlmann Spring 2003
Transmission Operations & Real Time System Security David Mahlmann Spring 2003 1 Outline Overview of Control Area Operation Basic Control Area Operation Frequency, voltage, reserves, regulation, component
More informationNYISO Fault Current Assessment A Report by the New York Independent System Operator
NYISO Current Assessment 2017 A Report by the New York Independent System Operator April 2017 Caution and Disclaimer The contents of these materials are for informational purposes and are provided as is
More informationNYISO Interface Stability Limit Analysis For All Lines I/S and Outage Conditions
NYISO Interface Stability Limit Analysis For All Lines I/S and Outage Conditions Review of Transient Stability Limits for Transmission Line Outages Central East, Total East, UPNY - ConEd Dysinger East
More informationNYISO CENTRAL EAST AND UPNY-CONED VOLTAGE ANALYSIS FOR ATHENS GENERATING STATION
pproved by NYISO Operating Committee - July 22, 2004 NYISO CENTRL EST ND UPNY-CONED OLTGE NLYSIS FOR THENS GENERTING STTION - 1 - thens Generating Station In-Service 1. INTRODUCTION The is expected to
More informationCentral East Voltage and Stability Analysis for Marcy FACTS Project Phase I
Prepared by NYISO Operations Engineering 1. INTRODUCTION Central East Voltage and Stability Analysis for The Marcy Flexible AC Transmission System (FACTS) project is a joint technology partnership between
More informationCONSOLIDATED EDISON CO. OF NEW YORK, INC 4 IRVING PLACE NEW YORK, N.Y
CONSOLIDATED EDISON CO. OF NEW YORK, INC 4 IRVING PLACE NEW YORK, N.Y. 10003 EP 7000 5 JULY 2009 VOLTAGE SCHEDULE, CONTROL, AND OPERATION OF THE TRANSMISSION SYSTEM PURPOSE This specification describes
More informationWestern New York Transmission Constraints
Western New York Transmission Constraints Wes Yeomans Vice President Operations Market Issues Working Group Rensselaer, NY August 4, 2016 2000-2016 New York Independent System Operator, Inc. All Rights
More informationAC Transmission Cases: Updated Powerflow Analysis
AC Transmission Cases: Updated Powerflow Analysis Zach Smith Director - Transmission Planning New York Independent System Operator New York State Public Service Commission AC Transmission Technical Conference
More informationCentral Hudson Gas & Electric Corporation. Transmission Planning Guidelines
Central Hudson Gas & Electric Corporation Transmission Planning Guidelines Version 4.0 March 16, 2016 Version 3.0 March 16, 2009 Version 2.0 August 01, 1988 Version 1.0 June 26, 1967 Table of Contents
More informationMerchant Transmission and the Reliability of the New York State Bulk Power System Part I: Thermal Transfer Limit Analysis
1 Merchant Transmission and the Reliability of the New York State Bulk Power System Part I: Thermal imit Analysis Mahmoud K. Elfayoumy 1, Member, IEEE, Ramon R. Tapia 2, Member, IEEE, and Roger Clayton
More informationECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control
ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections
More informationEH2741 Communication and Control in Electric Power Systems Lecture 2
KTH ROYAL INSTITUTE OF TECHNOLOGY EH2741 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsno@kth.se Course map Outline Transmission Grids vs Distribution grids Primary Equipment
More informationMarcy FACTS Project. Solutions to Congestion
Marcy FACTS Project Phase II Issues Solutions to Congestion Build new generation near loads Build new transmission to the loads Improve utilization of existing transmission through use of FACTS devices
More informationIDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)
IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone
More informationESB National Grid Transmission Planning Criteria
ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and
More informationUNIT-II REAL POWER FREQUENCY CONTROL. 1. What is the major control loops used in large generators?
UNIT-II REAL POWER FREQUENCY CONTROL 1. What is the major control loops used in large generators? The major control loops used in large generators are Automatic voltage regulator (AVR) Automatic load frequency
More informationEE 742 Power System Components. Y. Baghzouz ECE Department UNLV
EE 742 Power System Components Y. Baghzouz ECE Department UNLV Desire to have a system with high reliability and power quality High reliability ensured by High quality of components High level of system
More informationINTERCONNECTION REQUESTS AND TRANSMISSION PROJECTS / NEW YORK CONTROL AREA Page 1 of 18
Page 1 of 18 13 East Coast Power, LLC Linden 7 3/25/99 100 ST-NG Richmond, NY-NJ J Goethals 345kV CONED 4 2/26/08 None 2005 16 Oak Point Property, LLC Oak Point Yard 4/15/99 500 CC-NG Bronx, NY J Hell
More informationElectrical Power Systems
Electrical Power Systems CONCEPT, THEORY AND PRACTICE SECOND EDITION SUBIR RAY Professor MVJ College of Engineering Bangalore PHI Learning Pfcte tofm Delhi-110092 2014 Preface xv Preface to the First Edition
More informationATC s Mackinac Back to Back. Summary
ATC s Mackinac Back to Back HVDC Project Update Michael B. Marz American Transmission Company Summary The Need For Flow Control at Mackinac Mackinac Flow Control Requirements Available Flow Control Technologies
More informationITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/
ITC Holdings Planning Criteria Below 100 kv * Category: Planning Type: Policy Eff. Date/Rev. # 12/09/2015 000 Contents 1. Goal... 2 2. Steady State Voltage & Thermal Loading Criteria... 2 2.1. System Loading...
More informationCONTENTS. 1. Introduction Generating Stations 9 40
CONTENTS 1. Introduction 1 8 Importance of Electrical Energy Generation of Electrical Energy Sources of Energy Comparison of Energy Sources Units of Energy Relationship among Energy Units Efficiency Calorific
More informationREACTIVE POWER AND VOLTAGE CONTROL ISSUES IN ELECTRIC POWER SYSTEMS
Chapter 2 REACTIVE POWER AND VOLTAGE CONTROL ISSUES IN ELECTRIC POWER SYSTEMS Peter W. Sauer University of Illinois at Urbana-Champaign sauer@ece.uiuc.edu Abstract This chapter was prepared primarily for
More informationQuanta Technology Advancing the Grid. Flexible AC Transmission System (FACTS) BGE Technology - Application Cases January 4, 2008 Q U A N T A SERVI CES
National Conference of State Legislatures The Forum for America s Ideas April 2011 National Association of Regulatory Utility Commissioners Q U A N T A SERVI CES Quanta Technology Advancing the Grid Flexible
More informationHighgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES
Highgate Converter Overview Prepared by Joshua Burroughs & Jeff Carrara IEEE PES Highgate Converter Abstract Introduction to HVDC Background on Highgate Operation and Control schemes of Highgate 22 Why
More informationELEMENTS OF FACTS CONTROLLERS
1 ELEMENTS OF FACTS CONTROLLERS Rajiv K. Varma Associate Professor Hydro One Chair in Power Systems Engineering University of Western Ontario London, ON, CANADA rkvarma@uwo.ca POWER SYSTEMS - Where are
More informationCONNECTING to the TRANSMISSION GRID in TODAY S RTO WORLD
CONNECTING to the TRANSMISSION GRID in TODAY S RTO WORLD Mike Londo, Transmission Reliability Administrator 2018 WPUI RTO conference UW-Madison, WI atcllc.com Objectives Explain the need for a Straits
More informationElectrical Engineering. Power Systems. Comprehensive Theory with Solved Examples and Practice Questions. Publications
Electrical Engineering Power Systems Comprehensive Theory with Solved Examples and Practice Questions Publications Publications MADE EASY Publications Corporate Office: 44-A/4, Kalu Sarai (Near Hauz Khas
More informationBC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A. NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014
BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014 Expiry Year: 2018 APPROVED BY: Original signed by: Paul
More informationOverview of Actuation Thrust
Overview of Actuation Thrust Fred Wang Thrust Leader, UTK Professor Prepared for CURENT Course September 4, 2013 Actuation in CURENT Wide Area Control of Power Power Grid Grid Measurement &Monitoring HVDC
More informationATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for Michigan s Eastern Upper and Northern Lower Peninsulas
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2013 Grid of the Future Symposium ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for
More informationSRI VIDYA COLLEGE OF ENGG AND TECH
EEE6603 PSOC Page 1 UNIT-III REACTIVE POWER VOLTAGE CONTROL 1. List the various components of AVR loop? The components of automatic voltage regulator loop are exciter, comparator, amplifier, rectifier
More informationExperience with Connecting Offshore Wind Farms to the Grid
Oct.26-28, 2011, Thailand PL-22 CIGRE-AORC 2011 www.cigre-aorc.com Experience with Connecting Offshore Wind Farms to the Grid J. FINN 1, A. SHAFIU 1,P. GLAUBITZ 2, J. LOTTES 2, P. RUDENKO 2, M: STEGER
More informationFundamental Concepts of Dynamic Reactive Compensation. Outline
1 Fundamental Concepts of Dynamic Reactive Compensation and HVDC Transmission Brian K. Johnson University of Idaho b.k.johnson@ieee.org 2 Outline Objectives for this panel session Introduce Basic Concepts
More informationKnowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators
Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery Application of EMI Diagnostics to Hydro Generators James Timperley Doble Global Power Services Columbus, Ohio jtimperley@doble.com
More informationInitial Application Form for Connection of Distributed Generation (>10kW)
Please complete the following information and forward to Vector Contact Details Primary Contact (who we should contact for additional information) Contact person Company name Contact numbers Daytime: Cell
More informationJason Harchick, P.E. Sr. Manager, System Planning and Protection Ryan Young Manager, Substation Engineering
DLC s Brady IIB Project Jason Harchick, P.E. Sr. Manager, System Planning and Protection Ryan Young Manager, Substation Engineering Project Need In 2007, PJM and Duquesne Light Company (DLC) transmission
More informationLevel 6 Graduate Diploma in Engineering Electrical Energy Systems
9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,
More informationOverview of Actuation Thrust
Overview of Actuation Thrust Fred Wang Thrust Leader, UTK Professor ECE 620 CURENT Course September 13, 2017 Actuation in CURENT Wide Area Control of Power Power Grid Grid Measurement &Monitoring HVDC
More informationEH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström
EH27401 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsn@ics.kth.se 1 Course map 2 Outline 1. Power System Topologies Transmission Grids vs Distribution grids Radial grids
More informationDocument C-29. Procedures for System Modeling: Data Requirements & Facility Ratings. January 5 th, 2016 TFSS Revisions Clean Open Process Posting
Document C-29 Procedures for System Modeling: January 5 th, 2016 TFSS Revisions Clean Open Process Posting Prepared by the SS-37 Working Group on Base Case Development for the Task Force on System Studies.
More informationDetermination of Optimal Account and Location of Series Compensation and SVS for an AC Transmission System
ISSN (e): 2250 3005 Vol, 04 Issue, 5 May 2014 International Journal of Computational Engineering Research (IJCER) Determination of Optimal Account and Location of Series Compensation and SVS for an AC
More informationGeneration Interconnection Study Data Sheet Synchronous Machines
FOR INTERNAL USE ONLY GTC Project Number: Queue Date: Generation Interconnection Study Data Sheet Synchronous Machines Customers must provide the following information in its entirety. GTC will not proceed
More informationELECTRICAL AND ELECTRONICS ENGINEERING EE1401 POWER SYSTEM OPERATION AND CONTROL -2 MARK QUESTIONS AND ANSWERS
ELECTRICAL AND ELECTRONICS ENGINEERING EE1401 POWER SYSTEM OPERATION AND CONTROL -2 MARK QUESTIONS AND ANSWERS 1. What is the necessity of voltage regulation? All equipments in power system are designed
More informationETM521. Lecture 1 - Power System Overview Barış Sanlı 1 / 72
ETM521 Lecture 1 - Power System Overview Barış Sanlı 1 / 72 Resources 2 / 72 Electricity Energy carrier What is moving? Not an energy source, but proxy Pulse... not electrons Behaves like light Can you
More informationIndustry Webinar. Reactive Power Planning. NERC System Analysis and Modeling Subcommittee (SAMS) March 2017
Industry Webinar Reactive Power Planning NERC System Analysis and Modeling Subcommittee (SAMS) March 2017 Webinar Topics Reliability Guideline on Reactive Power Planning Webinar Topics Fundamentals of
More informationNERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1
NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1 Charles J. Mozina, Consultant Beckwith Electric Co., Inc. www.beckwithelectric.com I. Introduction During the 2003 blackout,
More informationWide Area Voltage Dispatch. - Case studies of ISO New England using NETSS AC XOPF program
Wide Area Voltage Dispatch - Case studies of ISO New England using NETSS AC XOPF program Xiaochuan Luo ISO New England Inc Marija Ilic, Jeff Lang NETSS Inc. EPRI AVC Workshop PJM, Norristown, PA May 19,
More informationPower System Fundamentals
Power System Fundamentals Transmission Facilities PJM State & Member Training Dept. Objectives Given a typical Transmission line and/or cable, describe the equipment design and components that determine
More informationNORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:
NORTH CAROLINA INTERCONNECTION REQUEST Utility: Designated Contact Person: Address: Telephone Number: Fax: E-Mail Address: An is considered complete when it provides all applicable and correct information
More informationECEN 615 Methods of Electric Power Systems Analysis Lecture 8: Advanced Power Flow
ECEN 615 Methods of Electric Power Systems nalysis Lecture 8: dvanced Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering Texas &M University overbye@tamu.edu nnouncements Read Chapter
More informationCHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS
84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial
More informationBE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %
BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and
More informationVIA ELECTRONIC FILING SYSTEM AND ELECTRONIC MAIL
DLA Piper LLP (US) 677 Broadway, Suite 1205 Albany, New York 12207-2996 www.dlapiper.com Jeffrey D. Kuhn jeffrey.kuhn@dlapiper.com T 212.335.4864 F 518.935.9806 January 13, 2016 VIA ELECTRONIC FILING SYSTEM
More informationATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0
ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES 2014-03-31 - Revision 0 EUB Decision 2007-071 Board Direction 52 For questions or comments regarding
More informationIssued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY
WN U-60 Attachment C to Schedule 152, Page 1 SCHEDULE 152 APPLICATION FOR INTERCONNECTING A GENERATING FACILITY TIER 2 OR TIER 3 This Application is considered complete when it provides all applicable
More informationVOLTAGE STABILITY OF THE NORDIC TEST SYSTEM
1 VOLTAGE STABILITY OF THE NORDIC TEST SYSTEM Thierry Van Cutsem Department of Electrical and Computer Engineering University of Liège, Belgium Modified version of a presentation at the IEEE PES General
More informationNumbering System for Protective Devices, Control and Indication Devices for Power Systems
Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements
More informationTransmission Facilities Rating Methodology for Florida
Document title Transmission Facilities Rating Methodology for Florida Document number EGR-TRMF-00001 Applies to: Transmission Engineering, Transmission System Operations, and Transmission Planning Duke
More informationTransmission System Operations TO1. Interconnection Training Program PJM State & Member Training Dept.
Disclaimer This training presentation is provided as a reference for preparing for the PJM Certification Exam. Note that the following information may not reflect current PJM rules and operating procedures.
More informationAppendix 8 - Terminology
Appendix 8 - Terminology GENERAL CONCEPT Absolute error Acceptance tests Accuracy Accuracy class Active energy (WH) meter Actual value Admittance Air gap Alternating current Alternating voltage Ammeter
More informationJoe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation
Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation Slide 1 Excerpt from the BoA BoA: Book of Acronyms MSC/MSR: Mechanically
More informationNew HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations
New HVDC Interaction between AC networks 233 JPE 7-3-6 New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations Chan-Ki Kim, Young-Hun Kwon * and Gil-Soo Jang ** KEPRI,
More informationEast-South HVDC Interconnector II, India : in commercial operation since 2003
8006/0 5 HVDC / FACTS Highlights http://www.siemens.com/facts http://www.siemens.com/hvdc NEW! >>> Welcome to Siemens Highlights & Innovations in Transmission and Distribution East-South HVDC Interconnector
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationChen-Ching Liu. Washington State University
Blackouts EE 521 Analysis of Power Systems Chen-Ching Liu Boeing Distinguished Professor Washington State University Catastrophic Power Outages Sabotage OkC Oak Creek kwisconsin i October 11 th 2004 American
More informationChapter 10: Compensation of Power Transmission Systems
Chapter 10: Compensation of Power Transmission Systems Introduction The two major problems that the modern power systems are facing are voltage and angle stabilities. There are various approaches to overcome
More informationMaine Public Service Reliability Solutions Update
Maine Public Service Reliability Solutions Update Presentation at the Planning Advisory Group 9/17/13 MPS Reliability Solutions Study Review of Previous PAG Updates RLC completed assessment of existing
More informationAMEREN s (On Behalf of Its Transmission Owning Affiliates, Including Ameren Missouri, Ameren Illinois, and Ameren Transmission Company of Illinois)
AMEREN s (On Behalf of Its Transmission Owning Affiliates, Including Missouri, Illinois, and Transmission Company of Illinois) TRANSMISSION PLANNING CRITERIA AND GUIDELINES March 28, 2003 Revised April
More informationDesign and Simulation of Passive Filter
Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements
Section 502.8 SCADA Technical and Operating Applicability 1 Section 502.8 applies to: (a) the legal owner of a generating unit: (i) connected to the transmission facilities in the balancing authority area
More informationGENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW
GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy Interconnection Coordinator 1945
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination Volts Per Hertz (24), Undervoltage (27), Overvoltage (59), and Under/Overfrequency (81) Protection System Protection and Control Subcommittee
More informationIntegration of Wind Generation into Weak Grids
Integration of Wind Generation into Weak Grids Jason MacDowell GE Energy Consulting NERC ERSTF Atlanta, GA December 10-11, 2014 Outline Conventional and Power Electronic (PE) Sources Stability limitations
More informationOPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS
OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS AND MEDIUM-SIZE FACILITIES (5,000-25,000KW) CONNECTED
More informationWind Power Facility Technical Requirements CHANGE HISTORY
CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical
More informationCAISO Restricted - Do Not Distribute Outside of RC Project LOI and NDA Entities Page 1 of 24
RC0120A - RC IRO-010 Data Specification NOTE: Changes from Peak's Attachment A are highlighted in red in columns C through G Section Category Number Responsible Pa Data Item Data Transfer Method 1.1 Transmission
More informationOPERATING PROCEDURE. Table of Contents
Table of Contents PURPOSE... 1 1.0 CAISO DISPATCHER RESPONSIBILITIES... 2 Monitor Loads and Generators... 2 Monitor Balancing Areas... 2 Operate CAISO Controlled Grid Voltage Equipment... 3 Voltage Schedules...
More information1st Qua u r a ter e M e M e e t e in i g 2nd Qua u r a ter e M e M e e t e in i g
2011 SERTP Welcome SERTP 2011 First RPSG Meeting & Interactive Training Session 9:00 AM 3:00 PM 1 2011 SERTP The SERTP process is a transmission planning process. Please contact the respective transmission
More informationIntroduction to HVDC Transmission. High Voltage Direct Current (HVDC) Transmission
Lecture 29 Introduction to HVDC Transmission Series Compensation 1 Fall 2003 High Voltage Direct Current (HVDC) Transmission Update to Edison s Vision AC Power Generation at Relatively Lower Voltage» Step
More informationDietrich Bonmann, ABB Monselice Transformer Days, May 5, 2010 Optimized AC transmission solutions with phase-shifting transformers and shunt reactors
Dietrich Bonmann, ABB Monselice Transformer Days, May 5, 2010 Optimized AC transmission solutions with phase-shifting transformers and shunt reactors May 11, 2010 Slide 1 Why phase-shifting transformers
More informationADDENDUM. (1) Ref. Regulation 33.4 (Page 643): (2) Ref. Regulation 71.2 (Page 676): Annexed as Appendix II to these Regulations at page 697.
ADDENDUM No. AERC. 396/2012/Pt.-III/4.-Assam Electricity Regulatory commission (Terms and Conditions for determination of Multi Year tariff) Regulations, 2015 issued vide notification No. AERC.396/2012/Pt/-II/13
More informationPower Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)
Power Plant and Transmission System Protection Coordination Loss-of of-field (40) and Out-of of-step Protection (78) System Protection and Control Subcommittee Protection Coordination Workshop Phoenix,
More informationCourse ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation
Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission
More informationFACILITY RATINGS METHOD TABLE OF CONTENTS
FACILITY RATINGS METHOD TABLE OF CONTENTS 1.0 PURPOSE... 2 2.0 SCOPE... 3 3.0 COMPLIANCE... 4 4.0 DEFINITIONS... 5 5.0 RESPONSIBILITIES... 7 6.0 PROCEDURE... 8 6.4 Generating Equipment Ratings... 9 6.5
More informationImpact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods
Proceedings of the th WSEAS International Conference on Power Systems, Beijing, China, September -, 200 Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing
More informationOperational Experiences of an HV Transformer Neutral Blocking Device
MIPSYCON NOVEMBER 7, 2017 Operational Experiences of an HV Transformer Neutral Blocking Device Fred R. Faxvog, Emprimus Michael B. Marz, American Transmission Co. SolidGround GIC Neutral Blocker Fully
More informationDUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES. Transmission Planning
DUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES Transmission Planning TABLE OF CONTENTS I. SCOPE 1 II. TRANSMISSION PLANNING OBJECTIVES 2 III. PLANNING ASSUMPTIONS 3 A. Load Levels 3 B. Generation
More informationPower System Stability. Course Notes PART-1
PHILADELPHIA UNIVERSITY ELECTRICAL ENGINEERING DEPARTMENT Power System Stability Course Notes PART-1 Dr. A.Professor Mohammed Tawfeeq Al-Zuhairi September 2012 1 Power System Stability Introduction Dr.Mohammed
More informationVoltage and Reactive Procedures CMP-VAR-01
Voltage and Reactive Procedures CMP-VAR-01 NERC Standards: VAR-001-2 VAR-002-1.1b Effective Date: 07/31/2012 Document Information Current Revision 2.0 Review Cycle Annual Subject to External Audit? Yes
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements
Section 502.8 SCADA Technical and Operating Requirements Applicability 1 Subject to subsections 2 and 3 below, section 502.8 applies to: (a) (c) (d) the legal owner of a generating unit or an aggregated
More informationShunt Reactors. Global Top Energy, Machinery & Plant Solution Provider
Shunt Reactors Global Top Energy, Machinery & Plant Solution Provider Our Business Brief introduction of Hyosung Power & Industrial Systems PG While Hyosung is an established name for world-class electrical
More informationControl of Reactive Shunts- Voltage Stability and Restoration Mohammad Reza Safari Tirtashi
Control of Reactive Shunts- Voltage Stability and Restoration Mohammad Reza Safari Tirtashi Licentiate Thesis Department of Biomedical Engineering 2015 Department of Biomedical Engineering Faculty of Engineering
More informationTampa Electric Company Facility Rating Methodology Approved 11/20/2018
Tampa Electric Company Facility Rating Methodology Approved 11/20/2018 Effective Date: 12/01/2018 Responsible Department: System Planning Review Cycle: 3 Years Last Date Reviewed: 11/16/2018 Next Planned
More informationNERC Protection Coordination Webinar Series June 23, Phil Tatro
Power Plant and Transmission System Protection Coordination Volts Per Hertz (24), Undervoltage (27), Overvoltage (59), and Under/Overfrequency (81) Protection NERC Protection Coordination Webinar Series
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationImpact Assessment Generator Form
Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project
More informationELEC Transmission i and
ELEC-1104 Lecture 5: Transmission i and Distribution ib ti Power System Layout Transmission and Distribution The transmission system is to transmit a large amount of energy from the power stations s to
More informationTechnologies data base and technological innovation needs up to 2050
Session IV : Long-term grid development Technology and operations Technologies data base and technological innovation needs up to 2050 Eric Peirano, Technofi Work Package leader e-highway2050 I Final Conference
More informationApplication of SVCs to Satisfy Reactive Power Needs of Power Systems
1 Application of SVCs to Satisfy Reactive Power Needs of Power Systems H. K. Tyll, Senior Member, IEEE Abstract In the early days of power transmission problems like voltage deviation during load changes
More information