System Components. David Mahlmann Spring 2003

Size: px
Start display at page:

Download "System Components. David Mahlmann Spring 2003"

Transcription

1 System Components David Mahlmann Spring 2003

2 Here s the plan. To describe all of the parts of the system, summarize how they work and interact In the next section on Transmission System Operation we will address how they work together

3 Parts is Parts! Generation Transmission Load System Interactions

4 Generation Reference 2002 Load & Capacity Report

5 Generators provide only two quantities MW - Real Power MVAR Reactive Power Let s look at the the MW first.

6 Generator MW - who needs em? Loads - Energy (aka the money maker) System - Control power distribution on the system System - Provide reserve System - Balance load and losses requirement to control net-interchange We will talk about the system needs for MW, and how they are met as we proceed through this program. Without the system energy can t get to the load and everyone loses.

7 Generators - MW output Equipment Prime Movers Boilers, Gas turbines, Hydro turbines, internal combustion, wind turbines, fuel cells

8 Generators - MW output Equipment

9 Restrictions on MW production Response rate limits thermodynamics Equipment failures tubes, boiler feed pumps, fans, water chemistry control Environmental limits emissions gases, air and water temperature limits On a given day, the generator operator should have a good handle on the MW generation capability.

10 Generator MVAR - who needs em? Load Provide reactive power demands of the load Maintain voltage quality Minimize sub-transmission/distribution losses System - Power Transfer Maintain secure voltage profile on Bulk Power System (BPS) Minimizes transmission losses System - Contingency Response Sustain post-contingency voltages Damp out system voltage and power swings to maintain system stability and avoid voltage collapse

11 Generators - MVAR output Equipment Exciters Automatic Voltage Regulators Power System Stabilizers Limits to MVAR output Generator heating Generator cooling systems Auxiliary system voltage requirements

12 Generators - MVAR output Equipment Stator Windings Field Coils Field Forging Coil Slot

13 Restrictions on MVAR production Stator and rotor heating conditions D-Curve Equipment failures AVR out of service System constraints station service voltages, local system voltage constraints On a given day, the generator operator should have a good handle on the MVAR generation capability.

14 MVARS are controlled along with voltage by adjusting excitation current. Higher Field Current produces LAGGING power factor (Vars out of Generator) Lower Field Current produces LEADING power factor (Generator absorbs Vars) Generator must be operated within the limits of the D Curve

15 Lag Per Unit MVAR PSI 45 PSI 30 PSI Per Unit MW.7.70PF.80PF.90PF PF.98PF.98PF.95PF.90PF.7 Generator D Curve

16 How is generation distributed in New York? By fuel type By location

17 Generation Sources Other Combined Cycle Gas Turbine Steam Oil/Gas Source: 2002 Load & Capacity Data Hydro Steam Nuclear Steam Coal MW % Steam Oil & Gas % Steam Coal % Steam Nuclear % Hydro % Combined Cycle % Gas Turbine % Other 448 1% Total Capability 36342

18 Saunders Chateauguay New York State Transmission System Moses- St. Lawrence Dennison Colton Massena Willis Plattsburgh Sandbar Legend: 765 kv 500 kv 345 kv 230 kv 115 kv Beck Niagara Huntley Stolle Rd. Gardenville Dunkirk Somerset Sta.80 Robinson Rd. Homer City Pannell Meyer Andover Palmiter Watercure Hillside Oswego Complex Oakdale Adirondack Marcy Clay Edic Lafayette Richfield Springs Central - East Hoosick Porter Inghams Fraser Coopers Corners Rock Tavern Gilboa Roseton Rotterdam Buchanan Ramapo W49St/Rainey Whitehall Blissville New Scotland Total - East Farragut Goethals Alps Leeds Pleasant Valley Millwood Sprainbrook Dunwoodie Bennington Shore Rd. E.Garden City

19 Transmission Reference 2002 Load & Capacity Report

20 Transmission - The switchyard and beyond What do I need to know about transmission, and why? What happens to my MW & MVARS when they leave the plant?

21 Transmission NY State - Large sources of generation are located far from heaviest load Bulk Power Transmission System transports energy from source to sink 765, 345, & 230 KV lines make up the Bulk Power System

22 Miles of NY Transmission by KV Class Miles of NY Transmission by KV Class KV Class Miles / KV 500KV 345 KV 230 KV 115/138 KV

23 Saunders Chateauguay New York State Transmission System Moses- St. Lawrence Dennison Colton Massena Willis Plattsburgh Sandbar Legend: 765 kv 500 kv 345 kv 230 kv 115 kv Beck Niagara Huntley Stolle Rd. Gardenville Dunkirk Somerset Sta.80 Robinson Rd. Homer City Pannell Meyer Andover Palmiter Watercure Hillside Oswego Complex Oakdale Adirondack Marcy Clay Edic Lafayette Richfield Springs Porter Inghams Fraser Coopers Corners Rock Tavern Gilboa Roseton Rotterdam Buchanan Ramapo W49St/Rainey Whitehall Blissville Hoosick New Scotland Farragut Goethals Alps Leeds Pleasant Valley Millwood Sprainbrook Dunwoodie Bennington Shore Rd. E.Garden City

24 Transmission Components Conductors - overhead and underground Breakers, disconnects and substation equipment Transformers voltage control, power control Voltage control equip. - capacitors, reactors, SVC

25 Capacitors Circuit Breakers Reactors Transformers

26 Transmission System MW Controls Phase Angle Regulators Flexiable AC Transmission (FACTS) HVDC Transmission HVDC Lines Back to back terminals

27 Transmission System MVAR Controls Load Tap Changing Transformers (LTCs) Supervisory controlled LTCs allow system operators to change tap ratios. Shunt Capacitor and Reactors Unlike AVRs and SVCs, these device provide step changes in the VAR support. Static VAR Compensators (SVCs) Static Var Compensators(SVCs) and STATCOM devices perform a special function of high speed continuous voltage support.

28 Restrictions on Transmission Equipment Heating Overhead wire sag Underground cable heating Transformer overheating Arcing high voltage Insulation breakdown loose connections

29 Transmission Equipment Ratings Normal permissible continuous loading 24/7 Long Term Emergency (LTE) typically 4 hours Short Term Emergency (STE) typically 15 min On a given day, the system operator should have a good handle on the transmission equipment limitations.

30 Load Reference 2002 Load & Capacity Report

31 Load and Losses All end users of energy are load Residential Customers Industrial Customers Pumped Storage units Losses are MW that are used by the system Transformers, wire losses, etc. Average is about 3.5% of system load Takes 900 MW of generation to run the NY system. A recent peak was 30,311 MW. Losses at that time were 1030 MW

32 Load is Variable that must be served Daily Load shape Weekday Weekend/Holiday Summer Winter Today usually similar to yesterday, with variations Daily Load Variations Temperature/humidity Cloud Cover / Wind Speed Economic Conditions Street lighting load in the state MW

33 A Summer Peak Load Pattern 24 Hour Load Profile :00 1:00 2:00 3:00 4:00 5:00 6:00 7:00 8:00 9:00 10:00 11:00 12: :00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00 Time Load (MW)

34 Load (MW) A Typical Fall Weekday 24 Hour Load Profile :00 1:00 2:00 3:00 4:00 5:00 6:00 7:00 8:00 9:00 10:00 11:00 12: :00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00 Time

35 Load (MW) A few days before Christmas 24 Hour Load Profile :00 1:00 2:00 3:00 4:00 5:00 6:00 7:00 8:00 9:00 10:00 11:00 12: :00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00 Time

36 System Interactions Power System Physics 101 Reference 2002 Operating Study

37 Power System Physics ) Power, Losses and voltage level 2) Wires, ground and electric fields 3) Power Distribution 4) Generic Security Constrained Operation 5) Transmission Interfaces

38 1) Power, Losses, and Voltage Level Power is the product of the voltage and the current. The same power transfer occurs with a high voltage/low current as with corresponding low voltage high current. Energy losses to heat on a line increase with the square of the current. Energy is efficiently transferred at high voltage an relatively low current.

39 2) Wires, Ground, and Electric fields Transmission is weird fact of physics #1 Based on the operating voltage and distance between the conductor and ground, transmission lines act like capacitors, generating MVARs

40 2) Wires, Ground and Electric fields (cont.) Transmission is weird fact of physics #2 Based on the conductor size, shape, spacing and current (power) flow, transmission lines act like big inductors, absorbing MVARs

41 2) Wires, Ground and Electric fields (cont.) Combining weird physics facts 1 & 2 MVAR Loading - MW Surge Impedance loading for a 100 mile 230KV line Depending on loading, a transmission line may be generating or absorbing MVARs

42 3) Transmission Flow a) Power flow distribute according to composite network impedance 100 MW 50 MW 50 MW 80 MW 20 MW

43 3) Transmission Flow a) Power flow distribution can be controlled by dispatch A 33 MW B 100 MW 0 MW 67 MW 33 MW A system with six lines of equal length, identical construction 100 MW C Loading per line BC = 33/2 =16.5MW Loading per line AC = 67/2 =33.5MW

44 3) Transmission Flow b) Power flow distribution can be controlled by dispatch 90 MW A 30 MW 3 MW B 10 MW 60 MW 3 MW A system with six lines of equal length, identical construction 100 MW C 30 MW 7 MW Loading per line BC = 37/2 =18.5MW Loading per line AC = 63/2 =31.5MW

45 3) Transmission Flow c) The flow redistributions can be calculated for any transmission or generation outage A 45 MW 2.5 MW 90 MW 10 MW B 45 MW 2.5 MW A system with six lines of equal length, identical construction 100 MW C 45 MW 7.5 MW Loading per line BC = 52.5/2 =26.25MW Loading per line AC = 47.5/1 =47.5MW

46 4) Generic Security Constrained Operation System Monitoring Contingency evaluation Loss of any transmission element Loss of any generator Security Constrained Dispatch & Scheduling Dispatch the system to a level where any single contingency will not cause a system overload (emergency) anywhere in the system

47 LOAD FLOW MAP UPNY Beck Somerset Sta. Oswego Oswego Complex Fitzpatrick Massena vvv Moses Chateauguay Willis Plattsburgh vvv Niagara Somerset Switch yard Sta.80 Pannell Sithe 9mi2 9mi1 Scriba Marcy Volney vvv vvv vvv vvv Porter Adirondack Rotterdam vvv Elm St. Packard Robinson Rd. Stolle Rd. Elbridge Clay DeWitt Edic Gilboa 99 BUS New Scotland Leeds Alps Athens Huntley Gardenville Meyer Watercure Lafayette Fraser Hurley Pleasant Valley Long Mt. Dunkirk Hillside vvv vvv Oakdale Coopers Corners Roseton E. Fishkill Pleasantville Dunwoodie Wood St. Millwood So. Ripley Erie So. \PRESENTATIONS\LOADFLOW_BASE 12/11/00 CHJ Homer City Towanda Legend: 765 kv 500 kv 345 kv 230 kv Rock Tavern Ramapo vvv Shore Rd. Buchanan Rainey Sprainbrook E. 13th W. 49th E.Garden City Tremont Farragut

48 5) Transmission Interfaces The transmission system has characteristics that may limit the amount of energy transfer Thermal Capability - by equipment or interface Megawatt limits A interface may load in way that one element hits a limit before all the lines have reached their limits. Voltage Limits - by equipment Low & High to avoid voltage & equipment damage Stability/Voltage Collapse Limits by interface To keep the system together

49 5) Transmission Interfaces (cont.) Transmission Interfaces are lines or groups of lines that have identified flow characteristics and operating limits Thermal limits System Stability Voltage collapse

50 Transmission Constraints on Central East Winter Operating Study 2001 Thermal Limit MW Emergency Limit 3450 MW Post Contingency Voltage Transfer Limit Dynamic Based on: Loss of Phase II in New England New Scotland #99 Bus Fault Marcy South Tower Fault Stability Limit 3100 MW w/ 3 Oswegos, 6 Sithe, both SVC s 3050 MW w/ #32 Oakdale-Fraser O/S 2900 MW w/ #4 Lafayette-Oakdale O/S

51 PENALTIES ON CENTRAL-EAST Oswego Complex Penalty Min Sithe Units I/S Both I/S Leeds/Fraser SVCs One SVC I/S Both O/S 4 of 5 units I/S of 5 units I/S of 5 units I/S of 5 units I/S of 5 units I/S STABILITY LIMIT = ( )

52 Dysinger East NEW YORK INTERNAL INTERFACES West - Central Central - East NS1 & SR2 Stolle - Meyer 67 Andover - Palmiter 932 Lockport - Telegraph Rd N. Akron N. Akron Oakfield Sweden Sweden 113 Moses South Pannel - Clay 1 & 2 Stolle - Meyer 67 Mortimer - Elbridge 1 & 2 Quaker - Sleight Rd. 13 Pannel - Farmington So. Perry - RGE 906 Clyde - NYSEG Farmington - NMPC Quaker - Macedon 930 Andover - Palmiter 932 Total East Plattsburgh - Vermont PV20 Edic - New Scotland 14 Marcy - New Scottland 18 Porter - Rotterdam 30 & 31 Richfield Springs - Inghams 942 Inghams PAR Inghams R81 (OCB) UPNY - Con Ed Massena - Marcy MSU1 Dennison - Sand Stone 5 Dennison - Colton 4 Alcoa - Browning Moses - Adirondak 1 & 2 Sprain Brook - Dunwoodie South Dunwoodie - Rainy 71 & 72 Dunwoodie - Sherman Creek 31 Dunwoodie So. - E 179th St Sprian Brook - Tremont X28 Sprain Brook - W 49th M51 & M 52 Jamaica - Valley Stream 901 Jamaica - Lake Success 903 Plattsburgh - Vermont PV20 Edic - New Scottland 14 Marcy - New Scottland 18 Porter - Rotterdam 30 & 31 Richfield Springs - Inghams 942 Inghams PAR Inghams R81 (OCB) Fraser - Gilboa GF5-35 West Woodbourne (T1-52) Ramapo - So. Mahwah 69 & 70 Ramapo - Branchburg 5018 Coopers Corners - Rock Tavern 34 & 42 Linden - Gothals A 2253 Hudson - Farragut B 3402 & C 3403 Ramapo - Buchanan 94 Ladentown - Buchanan 88 Roseton - East Fishkill 305 Pleasant Valley - East Fishkill F36 & F37 Pleasant Valley - Wood St. F30 Pleasant Valley - Millwood F31 Fishkill - Sylvan Lake 990 East Fishkill Bank Con Ed LIPA SprianBrook - E. Garden City Y49 Dunwoodie - Shore Rd Y50 Jamaca - Lake Success 901 Jamaca - Valley Stream 903 Northport - Norwalk Harbor 1385

53 NYISO Transmission System Constraints New York State Transmission System 2,500 MW Moses- St. Lawrence Dennison Moses South Colton Saunders Massena Chateauguay Willis Plattsburgh Sandbar 4,400 MW Legend: 765 kv 500 kv 345 kv 230 kv 115 kv Dysinger East Oswego Complex Somerset West - Central Beck Niagara Sta.80 Pannell Homer City Adirondack Marcy Central - East Hoosick Coopers Corners Rock Tavern Roseton Rotterdam Buchanan Ramapo W49St/Rainey Whitehall Blissville New Scotland Farragut Goethals Pleasant Valley Millwood Sprain Brook - Dunwoodie Sprainbrook Dunwoodie Bennington Robinson Rd. Clay Edic Porter Huntley Lafayette Gilboa Alps Stolle Rd. Richfield Inghams Leeds Gardenville Meyer Springs Dunkirk Andover Palmiter 4,700 MW Total - East 5,500 MW Fraser Watercure Hillside Oakdale 8,000 MW Upny - Con Ed Shore Rd. E.Garden City 5,000MW Con Ed-LIPA

54 Unique Features Phase Shifters Gilboa Pumped Storage Gas Turbines Wheel Through Energy Circulation

55 We have looked at the big pieces. Generation Transmission Load System Interactions Next we will go ahead with how the pieces work together to keep the lights on

Transmission Operations & Real Time System Security. David Mahlmann Spring 2003

Transmission Operations & Real Time System Security. David Mahlmann Spring 2003 Transmission Operations & Real Time System Security David Mahlmann Spring 2003 1 Outline Overview of Control Area Operation Basic Control Area Operation Frequency, voltage, reserves, regulation, component

More information

NYISO Fault Current Assessment A Report by the New York Independent System Operator

NYISO Fault Current Assessment A Report by the New York Independent System Operator NYISO Current Assessment 2017 A Report by the New York Independent System Operator April 2017 Caution and Disclaimer The contents of these materials are for informational purposes and are provided as is

More information

NYISO Interface Stability Limit Analysis For All Lines I/S and Outage Conditions

NYISO Interface Stability Limit Analysis For All Lines I/S and Outage Conditions NYISO Interface Stability Limit Analysis For All Lines I/S and Outage Conditions Review of Transient Stability Limits for Transmission Line Outages Central East, Total East, UPNY - ConEd Dysinger East

More information

NYISO CENTRAL EAST AND UPNY-CONED VOLTAGE ANALYSIS FOR ATHENS GENERATING STATION

NYISO CENTRAL EAST AND UPNY-CONED VOLTAGE ANALYSIS FOR ATHENS GENERATING STATION pproved by NYISO Operating Committee - July 22, 2004 NYISO CENTRL EST ND UPNY-CONED OLTGE NLYSIS FOR THENS GENERTING STTION - 1 - thens Generating Station In-Service 1. INTRODUCTION The is expected to

More information

Central East Voltage and Stability Analysis for Marcy FACTS Project Phase I

Central East Voltage and Stability Analysis for Marcy FACTS Project Phase I Prepared by NYISO Operations Engineering 1. INTRODUCTION Central East Voltage and Stability Analysis for The Marcy Flexible AC Transmission System (FACTS) project is a joint technology partnership between

More information

CONSOLIDATED EDISON CO. OF NEW YORK, INC 4 IRVING PLACE NEW YORK, N.Y

CONSOLIDATED EDISON CO. OF NEW YORK, INC 4 IRVING PLACE NEW YORK, N.Y CONSOLIDATED EDISON CO. OF NEW YORK, INC 4 IRVING PLACE NEW YORK, N.Y. 10003 EP 7000 5 JULY 2009 VOLTAGE SCHEDULE, CONTROL, AND OPERATION OF THE TRANSMISSION SYSTEM PURPOSE This specification describes

More information

Western New York Transmission Constraints

Western New York Transmission Constraints Western New York Transmission Constraints Wes Yeomans Vice President Operations Market Issues Working Group Rensselaer, NY August 4, 2016 2000-2016 New York Independent System Operator, Inc. All Rights

More information

AC Transmission Cases: Updated Powerflow Analysis

AC Transmission Cases: Updated Powerflow Analysis AC Transmission Cases: Updated Powerflow Analysis Zach Smith Director - Transmission Planning New York Independent System Operator New York State Public Service Commission AC Transmission Technical Conference

More information

Central Hudson Gas & Electric Corporation. Transmission Planning Guidelines

Central Hudson Gas & Electric Corporation. Transmission Planning Guidelines Central Hudson Gas & Electric Corporation Transmission Planning Guidelines Version 4.0 March 16, 2016 Version 3.0 March 16, 2009 Version 2.0 August 01, 1988 Version 1.0 June 26, 1967 Table of Contents

More information

Merchant Transmission and the Reliability of the New York State Bulk Power System Part I: Thermal Transfer Limit Analysis

Merchant Transmission and the Reliability of the New York State Bulk Power System Part I: Thermal Transfer Limit Analysis 1 Merchant Transmission and the Reliability of the New York State Bulk Power System Part I: Thermal imit Analysis Mahmoud K. Elfayoumy 1, Member, IEEE, Ramon R. Tapia 2, Member, IEEE, and Roger Clayton

More information

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections

More information

EH2741 Communication and Control in Electric Power Systems Lecture 2

EH2741 Communication and Control in Electric Power Systems Lecture 2 KTH ROYAL INSTITUTE OF TECHNOLOGY EH2741 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsno@kth.se Course map Outline Transmission Grids vs Distribution grids Primary Equipment

More information

Marcy FACTS Project. Solutions to Congestion

Marcy FACTS Project. Solutions to Congestion Marcy FACTS Project Phase II Issues Solutions to Congestion Build new generation near loads Build new transmission to the loads Improve utilization of existing transmission through use of FACTS devices

More information

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone

More information

ESB National Grid Transmission Planning Criteria

ESB National Grid Transmission Planning Criteria ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and

More information

UNIT-II REAL POWER FREQUENCY CONTROL. 1. What is the major control loops used in large generators?

UNIT-II REAL POWER FREQUENCY CONTROL. 1. What is the major control loops used in large generators? UNIT-II REAL POWER FREQUENCY CONTROL 1. What is the major control loops used in large generators? The major control loops used in large generators are Automatic voltage regulator (AVR) Automatic load frequency

More information

EE 742 Power System Components. Y. Baghzouz ECE Department UNLV

EE 742 Power System Components. Y. Baghzouz ECE Department UNLV EE 742 Power System Components Y. Baghzouz ECE Department UNLV Desire to have a system with high reliability and power quality High reliability ensured by High quality of components High level of system

More information

INTERCONNECTION REQUESTS AND TRANSMISSION PROJECTS / NEW YORK CONTROL AREA Page 1 of 18

INTERCONNECTION REQUESTS AND TRANSMISSION PROJECTS / NEW YORK CONTROL AREA Page 1 of 18 Page 1 of 18 13 East Coast Power, LLC Linden 7 3/25/99 100 ST-NG Richmond, NY-NJ J Goethals 345kV CONED 4 2/26/08 None 2005 16 Oak Point Property, LLC Oak Point Yard 4/15/99 500 CC-NG Bronx, NY J Hell

More information

Electrical Power Systems

Electrical Power Systems Electrical Power Systems CONCEPT, THEORY AND PRACTICE SECOND EDITION SUBIR RAY Professor MVJ College of Engineering Bangalore PHI Learning Pfcte tofm Delhi-110092 2014 Preface xv Preface to the First Edition

More information

ATC s Mackinac Back to Back. Summary

ATC s Mackinac Back to Back. Summary ATC s Mackinac Back to Back HVDC Project Update Michael B. Marz American Transmission Company Summary The Need For Flow Control at Mackinac Mackinac Flow Control Requirements Available Flow Control Technologies

More information

ITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/

ITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/ ITC Holdings Planning Criteria Below 100 kv * Category: Planning Type: Policy Eff. Date/Rev. # 12/09/2015 000 Contents 1. Goal... 2 2. Steady State Voltage & Thermal Loading Criteria... 2 2.1. System Loading...

More information

CONTENTS. 1. Introduction Generating Stations 9 40

CONTENTS. 1. Introduction Generating Stations 9 40 CONTENTS 1. Introduction 1 8 Importance of Electrical Energy Generation of Electrical Energy Sources of Energy Comparison of Energy Sources Units of Energy Relationship among Energy Units Efficiency Calorific

More information

REACTIVE POWER AND VOLTAGE CONTROL ISSUES IN ELECTRIC POWER SYSTEMS

REACTIVE POWER AND VOLTAGE CONTROL ISSUES IN ELECTRIC POWER SYSTEMS Chapter 2 REACTIVE POWER AND VOLTAGE CONTROL ISSUES IN ELECTRIC POWER SYSTEMS Peter W. Sauer University of Illinois at Urbana-Champaign sauer@ece.uiuc.edu Abstract This chapter was prepared primarily for

More information

Quanta Technology Advancing the Grid. Flexible AC Transmission System (FACTS) BGE Technology - Application Cases January 4, 2008 Q U A N T A SERVI CES

Quanta Technology Advancing the Grid. Flexible AC Transmission System (FACTS) BGE Technology - Application Cases January 4, 2008 Q U A N T A SERVI CES National Conference of State Legislatures The Forum for America s Ideas April 2011 National Association of Regulatory Utility Commissioners Q U A N T A SERVI CES Quanta Technology Advancing the Grid Flexible

More information

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES Highgate Converter Overview Prepared by Joshua Burroughs & Jeff Carrara IEEE PES Highgate Converter Abstract Introduction to HVDC Background on Highgate Operation and Control schemes of Highgate 22 Why

More information

ELEMENTS OF FACTS CONTROLLERS

ELEMENTS OF FACTS CONTROLLERS 1 ELEMENTS OF FACTS CONTROLLERS Rajiv K. Varma Associate Professor Hydro One Chair in Power Systems Engineering University of Western Ontario London, ON, CANADA rkvarma@uwo.ca POWER SYSTEMS - Where are

More information

CONNECTING to the TRANSMISSION GRID in TODAY S RTO WORLD

CONNECTING to the TRANSMISSION GRID in TODAY S RTO WORLD CONNECTING to the TRANSMISSION GRID in TODAY S RTO WORLD Mike Londo, Transmission Reliability Administrator 2018 WPUI RTO conference UW-Madison, WI atcllc.com Objectives Explain the need for a Straits

More information

Electrical Engineering. Power Systems. Comprehensive Theory with Solved Examples and Practice Questions. Publications

Electrical Engineering. Power Systems. Comprehensive Theory with Solved Examples and Practice Questions. Publications Electrical Engineering Power Systems Comprehensive Theory with Solved Examples and Practice Questions Publications Publications MADE EASY Publications Corporate Office: 44-A/4, Kalu Sarai (Near Hauz Khas

More information

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A. NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A. NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014 BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014 Expiry Year: 2018 APPROVED BY: Original signed by: Paul

More information

Overview of Actuation Thrust

Overview of Actuation Thrust Overview of Actuation Thrust Fred Wang Thrust Leader, UTK Professor Prepared for CURENT Course September 4, 2013 Actuation in CURENT Wide Area Control of Power Power Grid Grid Measurement &Monitoring HVDC

More information

ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for Michigan s Eastern Upper and Northern Lower Peninsulas

ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for Michigan s Eastern Upper and Northern Lower Peninsulas 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2013 Grid of the Future Symposium ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for

More information

SRI VIDYA COLLEGE OF ENGG AND TECH

SRI VIDYA COLLEGE OF ENGG AND TECH EEE6603 PSOC Page 1 UNIT-III REACTIVE POWER VOLTAGE CONTROL 1. List the various components of AVR loop? The components of automatic voltage regulator loop are exciter, comparator, amplifier, rectifier

More information

Experience with Connecting Offshore Wind Farms to the Grid

Experience with Connecting Offshore Wind Farms to the Grid Oct.26-28, 2011, Thailand PL-22 CIGRE-AORC 2011 www.cigre-aorc.com Experience with Connecting Offshore Wind Farms to the Grid J. FINN 1, A. SHAFIU 1,P. GLAUBITZ 2, J. LOTTES 2, P. RUDENKO 2, M: STEGER

More information

Fundamental Concepts of Dynamic Reactive Compensation. Outline

Fundamental Concepts of Dynamic Reactive Compensation. Outline 1 Fundamental Concepts of Dynamic Reactive Compensation and HVDC Transmission Brian K. Johnson University of Idaho b.k.johnson@ieee.org 2 Outline Objectives for this panel session Introduce Basic Concepts

More information

Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators

Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery Application of EMI Diagnostics to Hydro Generators James Timperley Doble Global Power Services Columbus, Ohio jtimperley@doble.com

More information

Initial Application Form for Connection of Distributed Generation (>10kW)

Initial Application Form for Connection of Distributed Generation (>10kW) Please complete the following information and forward to Vector Contact Details Primary Contact (who we should contact for additional information) Contact person Company name Contact numbers Daytime: Cell

More information

Jason Harchick, P.E. Sr. Manager, System Planning and Protection Ryan Young Manager, Substation Engineering

Jason Harchick, P.E. Sr. Manager, System Planning and Protection Ryan Young Manager, Substation Engineering DLC s Brady IIB Project Jason Harchick, P.E. Sr. Manager, System Planning and Protection Ryan Young Manager, Substation Engineering Project Need In 2007, PJM and Duquesne Light Company (DLC) transmission

More information

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Level 6 Graduate Diploma in Engineering Electrical Energy Systems 9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,

More information

Overview of Actuation Thrust

Overview of Actuation Thrust Overview of Actuation Thrust Fred Wang Thrust Leader, UTK Professor ECE 620 CURENT Course September 13, 2017 Actuation in CURENT Wide Area Control of Power Power Grid Grid Measurement &Monitoring HVDC

More information

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström EH27401 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsn@ics.kth.se 1 Course map 2 Outline 1. Power System Topologies Transmission Grids vs Distribution grids Radial grids

More information

Document C-29. Procedures for System Modeling: Data Requirements & Facility Ratings. January 5 th, 2016 TFSS Revisions Clean Open Process Posting

Document C-29. Procedures for System Modeling: Data Requirements & Facility Ratings. January 5 th, 2016 TFSS Revisions Clean Open Process Posting Document C-29 Procedures for System Modeling: January 5 th, 2016 TFSS Revisions Clean Open Process Posting Prepared by the SS-37 Working Group on Base Case Development for the Task Force on System Studies.

More information

Determination of Optimal Account and Location of Series Compensation and SVS for an AC Transmission System

Determination of Optimal Account and Location of Series Compensation and SVS for an AC Transmission System ISSN (e): 2250 3005 Vol, 04 Issue, 5 May 2014 International Journal of Computational Engineering Research (IJCER) Determination of Optimal Account and Location of Series Compensation and SVS for an AC

More information

Generation Interconnection Study Data Sheet Synchronous Machines

Generation Interconnection Study Data Sheet Synchronous Machines FOR INTERNAL USE ONLY GTC Project Number: Queue Date: Generation Interconnection Study Data Sheet Synchronous Machines Customers must provide the following information in its entirety. GTC will not proceed

More information

ELECTRICAL AND ELECTRONICS ENGINEERING EE1401 POWER SYSTEM OPERATION AND CONTROL -2 MARK QUESTIONS AND ANSWERS

ELECTRICAL AND ELECTRONICS ENGINEERING EE1401 POWER SYSTEM OPERATION AND CONTROL -2 MARK QUESTIONS AND ANSWERS ELECTRICAL AND ELECTRONICS ENGINEERING EE1401 POWER SYSTEM OPERATION AND CONTROL -2 MARK QUESTIONS AND ANSWERS 1. What is the necessity of voltage regulation? All equipments in power system are designed

More information

ETM521. Lecture 1 - Power System Overview Barış Sanlı 1 / 72

ETM521. Lecture 1 - Power System Overview Barış Sanlı 1 / 72 ETM521 Lecture 1 - Power System Overview Barış Sanlı 1 / 72 Resources 2 / 72 Electricity Energy carrier What is moving? Not an energy source, but proxy Pulse... not electrons Behaves like light Can you

More information

Industry Webinar. Reactive Power Planning. NERC System Analysis and Modeling Subcommittee (SAMS) March 2017

Industry Webinar. Reactive Power Planning. NERC System Analysis and Modeling Subcommittee (SAMS) March 2017 Industry Webinar Reactive Power Planning NERC System Analysis and Modeling Subcommittee (SAMS) March 2017 Webinar Topics Reliability Guideline on Reactive Power Planning Webinar Topics Fundamentals of

More information

NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1

NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1 NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1 Charles J. Mozina, Consultant Beckwith Electric Co., Inc. www.beckwithelectric.com I. Introduction During the 2003 blackout,

More information

Wide Area Voltage Dispatch. - Case studies of ISO New England using NETSS AC XOPF program

Wide Area Voltage Dispatch. - Case studies of ISO New England using NETSS AC XOPF program Wide Area Voltage Dispatch - Case studies of ISO New England using NETSS AC XOPF program Xiaochuan Luo ISO New England Inc Marija Ilic, Jeff Lang NETSS Inc. EPRI AVC Workshop PJM, Norristown, PA May 19,

More information

Power System Fundamentals

Power System Fundamentals Power System Fundamentals Transmission Facilities PJM State & Member Training Dept. Objectives Given a typical Transmission line and/or cable, describe the equipment design and components that determine

More information

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number:  Address: NORTH CAROLINA INTERCONNECTION REQUEST Utility: Designated Contact Person: Address: Telephone Number: Fax: E-Mail Address: An is considered complete when it provides all applicable and correct information

More information

ECEN 615 Methods of Electric Power Systems Analysis Lecture 8: Advanced Power Flow

ECEN 615 Methods of Electric Power Systems Analysis Lecture 8: Advanced Power Flow ECEN 615 Methods of Electric Power Systems nalysis Lecture 8: dvanced Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering Texas &M University overbye@tamu.edu nnouncements Read Chapter

More information

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial

More information

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 % BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and

More information

VIA ELECTRONIC FILING SYSTEM AND ELECTRONIC MAIL

VIA ELECTRONIC FILING SYSTEM AND ELECTRONIC MAIL DLA Piper LLP (US) 677 Broadway, Suite 1205 Albany, New York 12207-2996 www.dlapiper.com Jeffrey D. Kuhn jeffrey.kuhn@dlapiper.com T 212.335.4864 F 518.935.9806 January 13, 2016 VIA ELECTRONIC FILING SYSTEM

More information

ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0

ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0 ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES 2014-03-31 - Revision 0 EUB Decision 2007-071 Board Direction 52 For questions or comments regarding

More information

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY WN U-60 Attachment C to Schedule 152, Page 1 SCHEDULE 152 APPLICATION FOR INTERCONNECTING A GENERATING FACILITY TIER 2 OR TIER 3 This Application is considered complete when it provides all applicable

More information

VOLTAGE STABILITY OF THE NORDIC TEST SYSTEM

VOLTAGE STABILITY OF THE NORDIC TEST SYSTEM 1 VOLTAGE STABILITY OF THE NORDIC TEST SYSTEM Thierry Van Cutsem Department of Electrical and Computer Engineering University of Liège, Belgium Modified version of a presentation at the IEEE PES General

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

Transmission Facilities Rating Methodology for Florida

Transmission Facilities Rating Methodology for Florida Document title Transmission Facilities Rating Methodology for Florida Document number EGR-TRMF-00001 Applies to: Transmission Engineering, Transmission System Operations, and Transmission Planning Duke

More information

Transmission System Operations TO1. Interconnection Training Program PJM State & Member Training Dept.

Transmission System Operations TO1. Interconnection Training Program PJM State & Member Training Dept. Disclaimer This training presentation is provided as a reference for preparing for the PJM Certification Exam. Note that the following information may not reflect current PJM rules and operating procedures.

More information

Appendix 8 - Terminology

Appendix 8 - Terminology Appendix 8 - Terminology GENERAL CONCEPT Absolute error Acceptance tests Accuracy Accuracy class Active energy (WH) meter Actual value Admittance Air gap Alternating current Alternating voltage Ammeter

More information

Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation

Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation Slide 1 Excerpt from the BoA BoA: Book of Acronyms MSC/MSR: Mechanically

More information

New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations

New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations New HVDC Interaction between AC networks 233 JPE 7-3-6 New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations Chan-Ki Kim, Young-Hun Kwon * and Gil-Soo Jang ** KEPRI,

More information

East-South HVDC Interconnector II, India : in commercial operation since 2003

East-South HVDC Interconnector II, India : in commercial operation since 2003 8006/0 5 HVDC / FACTS Highlights http://www.siemens.com/facts http://www.siemens.com/hvdc NEW! >>> Welcome to Siemens Highlights & Innovations in Transmission and Distribution East-South HVDC Interconnector

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Chen-Ching Liu. Washington State University

Chen-Ching Liu. Washington State University Blackouts EE 521 Analysis of Power Systems Chen-Ching Liu Boeing Distinguished Professor Washington State University Catastrophic Power Outages Sabotage OkC Oak Creek kwisconsin i October 11 th 2004 American

More information

Chapter 10: Compensation of Power Transmission Systems

Chapter 10: Compensation of Power Transmission Systems Chapter 10: Compensation of Power Transmission Systems Introduction The two major problems that the modern power systems are facing are voltage and angle stabilities. There are various approaches to overcome

More information

Maine Public Service Reliability Solutions Update

Maine Public Service Reliability Solutions Update Maine Public Service Reliability Solutions Update Presentation at the Planning Advisory Group 9/17/13 MPS Reliability Solutions Study Review of Previous PAG Updates RLC completed assessment of existing

More information

AMEREN s (On Behalf of Its Transmission Owning Affiliates, Including Ameren Missouri, Ameren Illinois, and Ameren Transmission Company of Illinois)

AMEREN s (On Behalf of Its Transmission Owning Affiliates, Including Ameren Missouri, Ameren Illinois, and Ameren Transmission Company of Illinois) AMEREN s (On Behalf of Its Transmission Owning Affiliates, Including Missouri, Illinois, and Transmission Company of Illinois) TRANSMISSION PLANNING CRITERIA AND GUIDELINES March 28, 2003 Revised April

More information

Design and Simulation of Passive Filter

Design and Simulation of Passive Filter Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements Section 502.8 SCADA Technical and Operating Applicability 1 Section 502.8 applies to: (a) the legal owner of a generating unit: (i) connected to the transmission facilities in the balancing authority area

More information

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy Interconnection Coordinator 1945

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Volts Per Hertz (24), Undervoltage (27), Overvoltage (59), and Under/Overfrequency (81) Protection System Protection and Control Subcommittee

More information

Integration of Wind Generation into Weak Grids

Integration of Wind Generation into Weak Grids Integration of Wind Generation into Weak Grids Jason MacDowell GE Energy Consulting NERC ERSTF Atlanta, GA December 10-11, 2014 Outline Conventional and Power Electronic (PE) Sources Stability limitations

More information

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS AND MEDIUM-SIZE FACILITIES (5,000-25,000KW) CONNECTED

More information

Wind Power Facility Technical Requirements CHANGE HISTORY

Wind Power Facility Technical Requirements CHANGE HISTORY CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical

More information

CAISO Restricted - Do Not Distribute Outside of RC Project LOI and NDA Entities Page 1 of 24

CAISO Restricted - Do Not Distribute Outside of RC Project LOI and NDA Entities Page 1 of 24 RC0120A - RC IRO-010 Data Specification NOTE: Changes from Peak's Attachment A are highlighted in red in columns C through G Section Category Number Responsible Pa Data Item Data Transfer Method 1.1 Transmission

More information

OPERATING PROCEDURE. Table of Contents

OPERATING PROCEDURE. Table of Contents Table of Contents PURPOSE... 1 1.0 CAISO DISPATCHER RESPONSIBILITIES... 2 Monitor Loads and Generators... 2 Monitor Balancing Areas... 2 Operate CAISO Controlled Grid Voltage Equipment... 3 Voltage Schedules...

More information

1st Qua u r a ter e M e M e e t e in i g 2nd Qua u r a ter e M e M e e t e in i g

1st Qua u r a ter e M e M e e t e in i g 2nd Qua u r a ter e M e M e e t e in i g 2011 SERTP Welcome SERTP 2011 First RPSG Meeting & Interactive Training Session 9:00 AM 3:00 PM 1 2011 SERTP The SERTP process is a transmission planning process. Please contact the respective transmission

More information

Introduction to HVDC Transmission. High Voltage Direct Current (HVDC) Transmission

Introduction to HVDC Transmission. High Voltage Direct Current (HVDC) Transmission Lecture 29 Introduction to HVDC Transmission Series Compensation 1 Fall 2003 High Voltage Direct Current (HVDC) Transmission Update to Edison s Vision AC Power Generation at Relatively Lower Voltage» Step

More information

Dietrich Bonmann, ABB Monselice Transformer Days, May 5, 2010 Optimized AC transmission solutions with phase-shifting transformers and shunt reactors

Dietrich Bonmann, ABB Monselice Transformer Days, May 5, 2010 Optimized AC transmission solutions with phase-shifting transformers and shunt reactors Dietrich Bonmann, ABB Monselice Transformer Days, May 5, 2010 Optimized AC transmission solutions with phase-shifting transformers and shunt reactors May 11, 2010 Slide 1 Why phase-shifting transformers

More information

ADDENDUM. (1) Ref. Regulation 33.4 (Page 643): (2) Ref. Regulation 71.2 (Page 676): Annexed as Appendix II to these Regulations at page 697.

ADDENDUM. (1) Ref. Regulation 33.4 (Page 643): (2) Ref. Regulation 71.2 (Page 676): Annexed as Appendix II to these Regulations at page 697. ADDENDUM No. AERC. 396/2012/Pt.-III/4.-Assam Electricity Regulatory commission (Terms and Conditions for determination of Multi Year tariff) Regulations, 2015 issued vide notification No. AERC.396/2012/Pt/-II/13

More information

Power Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)

Power Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78) Power Plant and Transmission System Protection Coordination Loss-of of-field (40) and Out-of of-step Protection (78) System Protection and Control Subcommittee Protection Coordination Workshop Phoenix,

More information

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission

More information

FACILITY RATINGS METHOD TABLE OF CONTENTS

FACILITY RATINGS METHOD TABLE OF CONTENTS FACILITY RATINGS METHOD TABLE OF CONTENTS 1.0 PURPOSE... 2 2.0 SCOPE... 3 3.0 COMPLIANCE... 4 4.0 DEFINITIONS... 5 5.0 RESPONSIBILITIES... 7 6.0 PROCEDURE... 8 6.4 Generating Equipment Ratings... 9 6.5

More information

Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods

Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods Proceedings of the th WSEAS International Conference on Power Systems, Beijing, China, September -, 200 Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing

More information

Operational Experiences of an HV Transformer Neutral Blocking Device

Operational Experiences of an HV Transformer Neutral Blocking Device MIPSYCON NOVEMBER 7, 2017 Operational Experiences of an HV Transformer Neutral Blocking Device Fred R. Faxvog, Emprimus Michael B. Marz, American Transmission Co. SolidGround GIC Neutral Blocker Fully

More information

DUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES. Transmission Planning

DUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES. Transmission Planning DUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES Transmission Planning TABLE OF CONTENTS I. SCOPE 1 II. TRANSMISSION PLANNING OBJECTIVES 2 III. PLANNING ASSUMPTIONS 3 A. Load Levels 3 B. Generation

More information

Power System Stability. Course Notes PART-1

Power System Stability. Course Notes PART-1 PHILADELPHIA UNIVERSITY ELECTRICAL ENGINEERING DEPARTMENT Power System Stability Course Notes PART-1 Dr. A.Professor Mohammed Tawfeeq Al-Zuhairi September 2012 1 Power System Stability Introduction Dr.Mohammed

More information

Voltage and Reactive Procedures CMP-VAR-01

Voltage and Reactive Procedures CMP-VAR-01 Voltage and Reactive Procedures CMP-VAR-01 NERC Standards: VAR-001-2 VAR-002-1.1b Effective Date: 07/31/2012 Document Information Current Revision 2.0 Review Cycle Annual Subject to External Audit? Yes

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements Section 502.8 SCADA Technical and Operating Requirements Applicability 1 Subject to subsections 2 and 3 below, section 502.8 applies to: (a) (c) (d) the legal owner of a generating unit or an aggregated

More information

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider Shunt Reactors Global Top Energy, Machinery & Plant Solution Provider Our Business Brief introduction of Hyosung Power & Industrial Systems PG While Hyosung is an established name for world-class electrical

More information

Control of Reactive Shunts- Voltage Stability and Restoration Mohammad Reza Safari Tirtashi

Control of Reactive Shunts- Voltage Stability and Restoration Mohammad Reza Safari Tirtashi Control of Reactive Shunts- Voltage Stability and Restoration Mohammad Reza Safari Tirtashi Licentiate Thesis Department of Biomedical Engineering 2015 Department of Biomedical Engineering Faculty of Engineering

More information

Tampa Electric Company Facility Rating Methodology Approved 11/20/2018

Tampa Electric Company Facility Rating Methodology Approved 11/20/2018 Tampa Electric Company Facility Rating Methodology Approved 11/20/2018 Effective Date: 12/01/2018 Responsible Department: System Planning Review Cycle: 3 Years Last Date Reviewed: 11/16/2018 Next Planned

More information

NERC Protection Coordination Webinar Series June 23, Phil Tatro

NERC Protection Coordination Webinar Series June 23, Phil Tatro Power Plant and Transmission System Protection Coordination Volts Per Hertz (24), Undervoltage (27), Overvoltage (59), and Under/Overfrequency (81) Protection NERC Protection Coordination Webinar Series

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

ELEC Transmission i and

ELEC Transmission i and ELEC-1104 Lecture 5: Transmission i and Distribution ib ti Power System Layout Transmission and Distribution The transmission system is to transmit a large amount of energy from the power stations s to

More information

Technologies data base and technological innovation needs up to 2050

Technologies data base and technological innovation needs up to 2050 Session IV : Long-term grid development Technology and operations Technologies data base and technological innovation needs up to 2050 Eric Peirano, Technofi Work Package leader e-highway2050 I Final Conference

More information

Application of SVCs to Satisfy Reactive Power Needs of Power Systems

Application of SVCs to Satisfy Reactive Power Needs of Power Systems 1 Application of SVCs to Satisfy Reactive Power Needs of Power Systems H. K. Tyll, Senior Member, IEEE Abstract In the early days of power transmission problems like voltage deviation during load changes

More information