Note The module converts unipolar and bipolar input signals
|
|
- James Black
- 6 years ago
- Views:
Transcription
1 PROGRAMMABLE ANALOG SIGNAL CONVERTER THREE WAY GALVANIC ISOLATOR - 19 input scales - 7 output scales - 1 SPDT alarm contact - input/output isolation 3kV - auxiliary supply output for loop powered sensors - auxiliary supply output for potentiometer function Note The module converts unipolar and bipolar input signals On input section two auxiliary dc output (5V,15V) are available for feeding potentiometers (5V) or remote loop powered sensors (15V), no additional power supply is required, though reducing costs. Connection example: OUTPUT STAGE The output section of the module is suitable for unipolar and bipolar signals (see TAB.2) : LIMITER function is programmable for limiting the output signal to the minimum or maximum scale value in case of input overload or broken wire/sensor. In this case the red LED on front pannel turns on, the relay and its SPDT contact are switched on. The contact output connections are the terminal blocks 5, 6 and 7, and can be used as process alarm. The dimension of 108mm includes the pluggable connection terminal blocks, supplied with the module. * NOTE: the modules are factory calibrated for 4-20mA / 4-20mA. Other possible set-up calibrations are available upon customer request.
2 Ordering information CA-PI/PO cod. XSSAPIPO Input Technical Data Input signal Inpedance voltage/current 19 scales programmmable 1MΩ / 50Ω Output Technical Data Supply voltage 15 36Vdc Current consumption 100mA 24Vdc Auxiliary dc outputs max. current Gain error < full scale Offset error < full scale Linearity error < full scale Zero adj ± full scale Span adj ± full scale Limit frequency 400Hz 1kHz depending on scale Rise time 150mV/µs Bandwidth 1kHz 6dB Phase delay < 10 µs Input/output/power isolation > 3kVac/60sec. Output/contact isolation > 500Vac/60 sec. Continuous input/output isolation 800Vac max. Reference Standards IEC 664-1, DIN VDE Overvoltage cathegory 2 Pollution group 2 Operating temperature C T 5 C Contact rated current 1A /30Vdc, 0,5A /125Vac Protection degree IP30 EMC Standards EN , EN Terminal blocks 2.5mm pluggable Housing material poliamyde 6.6, V0 acc. to UL94 Mounting rail EN Mounting position any, no spacying required Weight 160gr. ca.
3 CA-PI/PO FUNCTION DESCRIPTIONS LIMITER : with input signal lower or higher than standard levels, or input broken wire, limits the output signal at min. or max. scale levels according to the set-up and makes the relay to turn on ; the module is supplied with LIMITER disabled (dip 1, 8 ON, dip 2, 3, 4, 5, 6, 7 OFF on SW4) ; LIMITER cam be activated by setting SW4, see TAB1, according to unipolar / bipolar input and output scale ZERO ADJ : the trimmer adjusts ±10% the lower signal level SPAN : the trimmer adjusts ±10% the higher signal level Note : turning one trimmer, influence the set point of the other, so few regulations of the two trimmers are necessary to achive the best accuracy. BROKEN WIRE DETECTION : the function works only with voltage or 4-20mA input signal ; set-up JM1 in position A (Neg), B (Pos) or C (None), see TAB.4, and set up the LIMITER acc. to input signal JM1 in position A (Neg) : output signal reaches the full scale negative value 10.05V, 5.05V with bipolar signals ; or 0.1V, 0.05mA, 2mA (with 4-20mA) with unipolar signals ; the contact is switched and the red led is on JM1 in position B (Pos) : output signal reaches the positive full scale value 10.1V, 20.05mA either with unipolar or bipolar signals ; the contact is switched and the red led is on JM1 in position C (None) : the function is off ; output signal is like with 0V input signal ; the function works in any case with 4-20mA input signal if LIMITER is setted- up Note : with current input signal, the function broken wire detection is possible only with 4-20mA signal ; the output signal works as in the case of JM1 in position A, but the jumper have to be setted in position C. LIMITER red led : indicates LIMITER is activated by an input overload, signal lower than minimum, or broken wire, if the function is activated or input set-up is 4 20mA ; with current output set-up, it displays also broken wire on the output ; the red led is on, the contact is always switched POWER green led : power ok TERMINAL BLOCK 1 : positive signal input TERMINAL BLOCK 2 : negative signal input TERMINAL BLOCK 3 : 5Vdc/5mA aux. supply output TERMINAL BLOCK 4 : 15Vdc/30mA aux. supply output TERMINAL BLOCK 5 : relay contact 14 output TERMINAL BLOCK 6 : relay contact 11 output TERMINAL BLOCK 7 : relay contact 12 output
4 TERMINAL BLOCK 8 : negative signal output TERMINAL BLOCK 9 : positive signal output TERMINAL BLOCK + : positive power supply input TERMINAL BLOCK - : negative power supply input CA-PI/PO MODULE SET-UP The module is programmable by setting the dip-switches on one side of the module, by adjusting the trimmers ZERO ADJ, SPAN, SW3 switch and JM1 jumper bridge accessible by opening the front pannel. ANALOG CONVERTER / ISOLATOR FAST SET-UP PROCEDURE 1-set up input scale by setting SW1, see TAB.1 2-set up output mode voltage/current by setting SW3 on U / I position, see TAB.4 3-set up output scale by setting SW2, see TAB.2 4-if required set up the LIMITER by setting SW4, see TAB.1, and JM1, see TAB.4 5-if required, set up the function broken wire detection by setting JM1, see TAB.4 This procedure mayght introduce an error up to 2% with unipolar/unipolar conversion, up to 4% with unipolar/bipolar conversion and vice/versa, depending on the type of signal and on the scale difference compared with the factory scale set-up (4-20 / 4-20). ANALOG CONVERTER / ISOLATOR PRECISION SET-UP PROCEDURE To get an error 0.1%, connect the power supply and feed the module for a few minutes warm-up time. The needed instruments are : 15 36Vdc stabilized power supply, analog signal generator or a process calibrator, 4½ digit display U/I meter. For the calibration it is raccomanded to use a process calibrator. The accuracy of the calibration depends on the precision of the instuments Procedure A-disable LIMITER function by setting ON dips 1, 8 and OFF dips 2, 3, 4, 5, 6,7 on SW4 B-set-up input scale by setting SW1, see TAB.1 C-set-up output mode voltage/current by setting SW3 on U / I position, see TAB.4 D-set-up output scale by setting SW2, see TAB.2 F-connect the meter to the output terminal blocks 9 (+), 8 (-) G-connect the power supply to terminal blocks + and - and turn on power H-connect the signal generator to the input terminal blocks ; set-up the signal generator at lower level unipolar signal output, (or at the max. negative level wit bipolar signal), adjust ZERO ADJ trimmer to read 0 on the output meter display (or the max. negative level with bipolar signal) ; (set up the signal generator under the min. scale signal to chek the LIMITER function is operating ok if it is activated). I-set up the signal generator to the max. positive signal level ; adjust SPAN trimmer to read on the meter the same signal applied to the input ; (set up the signal generator over the max. signal level to chek the LIMITER function is operating o.k, if it is activated) L-repeat the procedue on points H and I to get the required accuracy J-LIMITER function set-up: turn OFF power ; set-up SW4, see TAB.3, according to choosen scale ; to chek the function is operating ok, repeat procedure on points H and I K-in case of unipolar to bipolar conversion set-up, or vice/versa, it is raccomanded to chek the calibration also at 0 signal level (middle scale)
5 POTENTIOMETER CONVERSION FAST SET-UP PROCEDURE 1-connect one pole of the potentiometer (value 1kΩ) to terminal block 3 (aux.voltage 5V/5mA potentiometer feeder) 2-connect the cursor of the potentiometer to terminal block 1 (positive signal input) 3-connect the third pole of the potentiometer to the terminal block 2 (negative signal input) 4-set-up input scale to 0-5V by setting SW1, see TAB.1 5-set-up output scale by setting SW3, see TAB.4 and SW2, see TAB.2 6-if required set-up the function LIMITER by setting SW4, see TAB.3 7-if required set-up the function broken wire detection by setting JM1, see TAB.4 8-connect 15 36Vdc power supply to + / - terminal blocks and turn on power POTENTIOMETER CONVERSION FAST SET-UP PROCEDURE To get an error 0.1%, proceed as above up to point 8, then connect to terminal blocks 9 (+) and 8 (-) a 4½ digit display U/I meter for reading the output signal ; wait a few minutes warm-up time, and proceed as follows : 9-turn the potentiometer to 0, adjust ZERO ADJ trimmer for reading 0 on the meter display, or the max. negative value in case of bipolar signal 10-turn the potentiometer to max. and adjust SPAN trimmer for reading the full scale signal on meter display
1-Phase True RMS AC/DC Over and Under Current Types DIC01, PIC01
Monitoring Relays -Phase True RMS AC/DC Over and Under Current Types DIC0, PIC0 DIC0 PIC0 TRMS AC/DC over + under, over+over, under+under current and voltage monitoring relays DC process signal plus/minus
More information5 years! Modular Housings. VariTrans P Warranty
Modular Housings VariTrans P 27000 The Multimeter among the isolators. With 480 switchable calibrated ranges and broad-range power supply. The Task A wide range of measuring signals need to be galvanically
More informationDRG-SC Series Signal Conditioners
DRG-SC Series Signal Conditioners DRG-SC Series 245 Basic unit Models Available for Thermocouples, RTDs, DC Voltage and Current, Frequency, Strain Gage Bridge, AC Voltage and Current Field Configurable
More informationCONTA-ELECTRONICS. Converter Units
CONTA-ELECTRONICS Whether for manufacturing, electrical machine and plant instrumentation, control engineering, power distribution, building automation, or process engineering it is always important to
More informationS200 I/O System Units
S200 I/O System Units S200 I/O is a range of cost effective I/O units which are bus compatible with S200L I/O and can be mixed with them in any order on the same DIN rail. The S200 I/O System features
More informationMCR-VAC-UI-0-DC. Voltage transducer for AC voltages. INTERFACE Data sheet _en_02. 1 Description
Voltage transducer for AC voltages TERFACE Data sheet 006_en_0 PHOENIX CONTACT 00-0- Description The MCR voltage transducer measures AC voltages in several signal ranges from 0... ±4 V AC to 0... ±30 V
More informationMCR-C-UI-UI-DCI MCR 3-Way Isolation Amplifier, Configurable
MCR-C-UI-UI-DCI MCR 3-Way Isolation Amplifier, Configurable 1. Short description configurable inputs and outputs signal conversion/amplification 3-way-isolation zero/span adjustment 17.5 mm ME housing
More informationCoupling Relays and Converters
Overview Area of application In automation and control engineering it will always be necessary to work with analog signals. The interfaces for analog signals that have established themselves as the standard
More informationMonitoring Relays 3-Phase Active power direction Types DWB03, PWB03
Monitoring Relays 3-Phase Active power direction ypes DWB03, PWB03 DWB03 PWB03 RMS active power relays for three phase balanced applications Measuring if active power is within set limits Measure their
More informationAssembly. Front view. DIP switch. LED yellow: Relay output 1. LED yellow: Relay output Power Rail
Current/Voltage Trip Value Features Assembly 1-channel signal conditioner 24 V DC supply (Power Rail) Current and voltage input 2 relay outputs Programmable high/low alarm Configurable via DIP switches
More informationTel: (949) Fax: (949) IAA100 Product Manual
IAA100 Product Manual Table of Contents Default Settings... 3 Connections... 3 Standard Span & Zero Adjustment... 4 Shunt Readings... 5 Digitally Controlled Remote Shunt... 5 Switch Configurations... 6
More informationDSCL, DSCP, SCTP. Industrial Loop Isolators and Transmitters DSCL, DSCP, SCTP. Industrial Loop Isolators and Transmitters
Industrial Loop Isolators and Transmitters DSCL,, SCTP DSCL,, SCTP Industrial Loop Isolators and Transmitters Description Dataforth s DSCL,, and SCTP series of products is a complete family of loop and
More informationDATA SHEET Selectable AC transducer TAS-311DG
DATA SHEET Selectable AC transducer Measuring on AC networks Class 0.5 (IEC688) measurement Supply/measur. voltage up to 690 V Easy configuration via PC interface possible DEIF A/S Frisenborgvej 33 DK-7800
More informationTransducer for Measurement Bridges SCM90, SIGS15
Transducer for Measurement Bridges SCM90, SIGS15 General Description Transducer for measurement bridges for DINrails and for printed circuit boards. Programmable ranges and bridge supply, voltage or current
More informationADAM Isolated DC Input/Output Signal Conditioning Module. User s Manual
ADAM-3014 Isolated DC Input/Output Signal Conditioning Module User s Manual ADAM and the ADAM logo are trademarks of Advantech Part no. 2000014000 Edition 1.1 Printed in Taiwan November 2006 Introduction
More informationTheta 60R. Technical Data Sheet. Special Features. Fig. 2 Theta R, 2 channel version, in housing S17 hole mounting brackets pulled out.
Technical Data Sheet Theta 60R 60 R 60 R Fig. Theta R, channel version, in housing S7 clipped on to a top - hat rail. Fig. Theta R, channel version, in housing S7 hole mounting brackets pulled out. Theta
More informationProcess displays For standard signals, temperature, resistance measurement
Features Inputs: Voltage ±10 V, ±200 V / Current ±20 ma / thermocouples J,K,T,N,Pt100,Pt1000 / resistance measurement / potentiometer Display range can be linearised Two limits output Min, Max functions
More informationAdjustable Digital Process Instrument MDK480
Description The adjustable Digital Process Instrument MDK480 is designed to measure and display process variables in industrial applications.the instrument is panel mounted with front frame dimensions
More informationModicon Momentum automation platform 0
Presentation, description Presentation The Momentum analog input bases enable acquisition of various analog values encountered in industrial applications, including: b b b b Standard high level (± 5 V,
More informationModule Input type Ranges TEDS Filters (LP = lowpass, HP = highpass) Piezoresistive bridge ±0.5 to mv/ma 1 ma exc
HSI Series Modules Selection Guide HSI Series Modules Single channel High bandwidth - for dynamic signals Isolation (all models Analog signal output (±5 V Single channel modularity For DEWETRON systems
More informationSwitching power supplies CP range, Linear power supplies CP-L range. Content
CP range, Linear power supplies CP-L range Content Switching power supplies, primary switch mode, CP range Benefits and advantages... 136 Approvals... 137 Ordering details... 138 Technical data... 11 Dimensional
More informationCAN-IO Custom IO remote module
CAN-IO Custom IO remote module Main characteristics High customization Integrate different types of inputs/ outputs Up to 40 total channels DIN rail mount or plate Main applications Climatic chambers Autoclaves
More informationMonitoring Relay MR 50
Monitoring Relay MR 50 Standard signals 0/4... 20 m, 0/2... 10 V DC Features M Input standard signals 0/4... 20 m, 0/2... 10 V DC M Measuring range programmable M Basic accuracy 0.1 % +/- 1 Digit M Installed
More informationP5201 Universal Programmable Transmitters with Galvanic Isolation
Transmitters - KB0288-2012/09 P5201 Universal Programmable Transmitters with Galvanic Isolation One type of transmitter for all regular resistance and thermocouple sensors. Linearized output signal 4 to
More informationVariTrans P V. Safe and Sound.
1000 V. Safe and Sound. VariTrans P 29000 Compact high-voltage isolation amplifiers with safe galvanic isolation, VariPower broad-range power supply and genuine calibrated range selection. Isolation Amplifiers
More informationTheta Hz. Technical Data Sheet. Special Features
Technical Data Sheet Theta Hz Theta Hz the transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent
More informationMonitoring Relays 3-Phase Load Guard Types DWB01, PWB01
Monitoring Relays 3-Phase Load Guard Types DWB0, PWB0 DWB0 PWB0 TRMS load guard relays for three phase balanced applications Measuring if the power factor is within set limits Measure voltage on own power
More informationDatasheet ACT20M Signal Isolation and Conversion NEW
Datasheet ACT0M Signal solation and Conversion NEW High quality signal isolation and conversion in a slim wide housing format is now available with Weidmuller s ACT0M range. Features include worldwide
More informationBulletin 931 Signal Conditioners Technical Data
Technical Data Table of Contents/Product Line Overview Introduction to..................................4 Catalog Number Explanation.......................................6 Product Overview................................................7
More informationXR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)
XR1 Rotor Earth Fault Relay (May 2007) Manual XR1 (Revision New) Woodward Manual XR1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided
More informationMonitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC71, PPC71
Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC71, PPC71 DPC71 PPC71 TRMS 3-phase over and under voltage, phase sequence, phase loss, asymmetry and tolerance monitoring relay Detect
More informationAssembly. Front view. DIP switch. LED yellow: Relay output I. LED yellow: Relay output II. Potentiometer Hysteresis relay I Power Rail
Current/Voltage Trip Value Features Assembly 1-channel signal conditioner 24 V DC supply (Power Rail) Current and voltage input 2 relay outputs Programmable high/low alarm Configurable via DIP switches
More informationWAVESERIES Signal converters
WAVESERIES Overview WAVESERIES Signal converters Isolation and conversion of analogue signals enclosed in a rail-mounted WAVEBOX housing WAVESERIES products are well suited for users seeking an analogue
More informationElectronic timers CT-S range Selection and ordering details
CT-S range Selection and ordering details Characteristics CT-S range CT-MFS 1SVR 430 010 F 0200 3 multifunction and 21 multi-range Continuous supply voltage range (24-240VAC/DC) or multisupply voltage
More informationFC Series Signal Conditioners
FC Series Signal Conditioners FC-33 DC Selectable Signal Conditioner with 3-way isolation Field configurable input and output ranges of 0-5V, 0-10 V, 0-20 ma and 4-20 ma with 1500 VDC isolation between
More informationTHE SIGNAL CONDITIONING SPECIALISTS
COLTERLEC ELEC TRIC AL ENGINEERING PRODUC TS THE SIGNAL CONDITIONING SPECIALISTS COLTERLEC ELEC TRIC AL ENGINEERING PRODUC T S The Signal Conditioning Specialists SECTION 91 TM THE SIGNAL CONDITIONING
More informationMonitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01, PPC01
Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01, PPC01 DPC01 PPC01 TRMS 3-phase over and under voltage, phase sequence, phase loss, asymmetry and tolerance monitoring relay Detect
More information38 Series - Relay interface modules A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays
More informationHigh Performance Process & Temperature Controllers
C22 C62 C82 C83 High Performance Process & Temperature Controllers C72 C42 R22 01. Multi Color LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. 200 msec Sampling Rate 04. True Universal
More information38 Series - Relay interface modules A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC
More informationC330 / C330X PC-Programmable Universal, 2-wire Transmitter
C330 / C330X PC-Programmable Universal, 2-wire Transmitter The IPAQ C330 transmitter is a universal, isolated, temperature transmitter with additional voltage and resistance input. Its robust design and
More informationMonitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01, PPC01
Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01 Product Description 3-phase or 3-phase+neutral line voltage monitoring relay for phase sequence, phase loss, asymmetry, over and
More informationVariTrans P Compact automation solutions can be implemented thanks to the 17.5 mm modular housing and operation at temperatures up to 70 C.
ProLine Interface Technology Transducers for High Voltage / Shunt Applications Compact high voltage transducers with VariPower broad-range power supply and genuine calibrated range selection. The Task
More informationTheta 20A / 20V. Technical Data Sheet. Special Features
Technical Data Sheet Theta 20A / 20V Theta 20A / 20V is used to measure and convert AC Voltage or Current input into a load independent DC current or voltage output signal. Special Features Available in
More informationR24 DISPLAY MODULE WITH ACTIVE OUTPUT AND RELAY
Čapkova 22 678 01 Blansko tel.: +420 516 416942, 419995 fax: +420 516 416963 R24 DISPLAY MODULE WITH ACTIVE OUTPUT AND RELAY Display module is designed for measuring the resistance, the signal from the
More informationRENATO DESIRÒ PARABIAGO (MI) Via Sant Anna, 51 Tel Fax
A1T ANALOG AMPLIFIER (for load cells on sensor roll) USER MANUAL RENATO DESIRÒ PARABIAGO (MI) Via Sant Anna, 51 Tel. 0331-491452 Fax 0331-493591 Page 1 SPECIFICATIONS POWER SUPPLY Form 20 Vdc to 28 Vdc
More informationHigh-Voltage Isolation Amplifiers / Shunt Isolators. VariTrans P 29000
High-Voltage Isolation Amplifiers / Shunt Isolators VariTrans P 29000 Compact high-voltage isolators with safe galvanic isolation, VariPower broad-range power supply and genuine calibrated range selection.
More informationMINI MCR-SL-UI-I-LP-NC
2-way isolation amplifier Data sheet 105263_en_02 PHOENIX CONTACT 2013-12-13 1 Description The configurable 2-way isolation amplifiers are used to electrically isolate, convert and filter standard signals.
More informationMonitoring Relays 3-Phase Active power Types DWB02, PWB02
Monitoring Relays 3-hase Active power Types DWB02, WB02 DWB02 roduct Description DWB02 and WB02 are precise TRMS active power monitoring relays for 3- phase balanced systems. They can be used for monitoring
More informationMonitoring Relays True RMS 3-Phase, 3-Phase+N, Multi-function Types DPB01, PPB01
Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multi-function Types, TRMS 3-phase over and under voltage, phase sequence and phase loss monitoring relays Detect when all 3 phases are present and have the
More informationMACX MCR-UI-UI-UP(-SP)(-NC)
Configurable 3-way isolating amplifier with safe isolation and wide-range power supply Data sheet 04247_en_02 PHOENIX CONTACT 203-04-0 Description MACX MCR-UI-UI 3-way isolating amplifiers are used to
More informationIsolated DIN Rail Mount Loop-Powered 2-Wire Signal Conditioners. DRLP Series
Isolated DIN Rail Mount Loop-Powered 2-Wire Signal Conditioners DRLP Series U ±0.03% Accuracy (Typical) U ±0.01% Linearity U 1500Vrms Transformer Isolation and 240Vrms Field-Side Protection U Wide Loop
More information3.5 mm contact pin pitch 1 Pole 12 A PCB direct or via socket
41 Series - Low profile PCB relays 8-12 - 16 A Features 41.31 41.52 41.61 1 & 2 Pole - Low profile (15.7 mm height) 41.31-1 Pole 12 A (3.5 mm pin pitch) 41.52-2 Pole 8 A (5 mm pin pitch) 41.61-1 Pole 16
More informationSignal conditioner - MACX MCR-UI-UI-NC
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid
More informationProtection relays and controllers. Types TRANSAL DC-2TF, ACV-3TF, ACI-3TF, PFC-2TF TRANSAL DC-2TB, AVC- 3TB, ACI-3TB, PFC-2TB
Protection relays and controllers Types TRANSAL DC-2TF, ACV-3TF, ACI-3TF, PFC-2TF TRANSAL DC-2TB, AVC- 3TB, ACI-3TB, PFC-2TB 4921250026C Transal TF Transal TB DEIF A/S Available for the following inputs:
More informationRISH Ducer TV 808, 2 channels Isolating amplifier unipolar / bipolar
Fig. 1. Isolating amplifier RISH Ducer TV 808 in housing S 17 clipped onto a top - hat rail or screw hole mounting brackets pulled out. Features and Benefits Electric Isolation between input, and power
More informationType CP-S, CP-C & CP-A Switch mode
Switch mode power CP-S, CP-C & CP-A Switch mode Characteristics CP-S and CP-C range Output current 5 A, 10 A and 20 A Integrated power reserve of up to 50 % 5 A and 10 A devices with pluggable connecting
More informationMultifunction Intelligent 4-wire Isolated Signal Conditioner
Multifunction Intelligent 4-wire Isolated Signal Conditioner IPAQ-4L is a fully universal and intelligent 4- wire (mains powered) transmitter for temperature measurement and signal conditioning applications.
More informationCP-E range Benefits and advantages
Benefits and advantages Characteristics Output voltages 5 V, 12 V, 2 V, 8 V DC Adjustable output voltages Benefits Signalling output/contact Output currents 0.625 A / 0.75 A / 1.25 A / 2.5 A / A / 5 A
More information38 Series - Relay Interface Modules A
Series - Relay Interface Modules 0.1-2 - 6 A - Relay interface modules for use with PLC systems, mm wide - Sensitive DC coil or AC/DC coil version - Supplied with integral coil - Instant removal of relay
More informationAnalog signal converters CC range
Analog signal converters CC range Benefits and advantages 2CDC 28 Fb Product range for analog signal processing CC-U range 8 different standard signal outputs on one device Input and output side universally
More informationXR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)
XR1 Rotor Earth Fault Relay Manual XR1 (Revision C) Woodward Manual XR1 (EN) Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by
More informationAC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300
Monitoring Technique VARIMETER IMD Insulation monitor RN 5897/300 0274214 Your Advantages For mobile generator sets according to DIN VDE 0100-551 Preventive fire and system protection Detection of symmetric
More informationExcellent low-cost Process & Temperature Controllers
C22 C62 C82 C83 Excellent low-cost Process & Temperature Controllers C72 C42 R22 01. High Quality LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. The Fast Sampling Rate in 200
More informationSTT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C
STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C 34-TT-03-07 3/06 PRODUCT SPECIFICATION SHEET OVERVIEW The Honeywell STT170 series of programmable temperature
More informationEnergy Management Energy Meter with plug-in Output Modules Type EM4-DIN
Energy Management Energy Meter with plug-in Output Modules Type EM4-DIN Degree of protection (front): IP 40 Front dimensions: 9 DIN modules RS 422/485 Serial port by means of optional module Dual pulse
More informationFC-33, DC SELECTABLE SIGNAL CONDITIONER
FC-33, DC SELECTABLE SIGNAL CONDITIONER Description. The FC-33 is a DIN rail or side mount, selectable input/output signal conditioner with 1500VDC isolation between input and output, and 1500VDC isolation
More informationMCR-C-UI-UI-DCI. Extract from the online catalog. Order No.:
Extract from the online catalog MCR-C-UI-UI-DCI Order No.: 2810913 MCR 3-way isolating amplifier, with configurable I/O, for the electrical isolation of analog signals, with GL approval, preconfigured.
More informationIsolated High Level Voltage Output 7B22 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM
Isolated High Level Voltage Output 7B22 FEATURES Unity gain single-channel signal conditioning output module. Interfaces and filters a +10 V input signal and provides an isolated precision output of +10V.
More informationConductive Sensors 2 to 4-point level controller Type CL with potentiometer
Conductive Sensors to 4-point level controller Type CL with potentiometer Conductive level controller Adjustment of sensitivity operating resistance from 50Ω to 500KΩ Multiple combinations of filling and
More informationWatts HCP Series
ACDC 6 Watts HCP Series High Efficiency up to 9% xppower.com High Power Density Programmable Output Voltage (%%) Programmable (%%) Parallel Operation Fully Featured Signals & Controls Year Warranty Specification
More informationSINEAX V 604s Programmable multifunctional transmitter
SINEAX V 60s f direct currents, direct voltages, temperature senss, teletransmitters potentiometers 00 SINEAX V60s is a multifunctional transmitter f top-hat rail assembly with the following main characteristics:
More informationn True RMS measurement n Fully onsite programmable input voltage range (for CIP-V)
Tranducers for alternating current/voltage n True RMS measurement n Fully onsite programmable input voltage range (for CIP-V) and input current range (for CIP-I) n Available in single or dual output type
More informationMonitoring Relays 1-Phase True RMS AC/DC Over and Under Current Types DIC01, PIC01
Monitoring Relays -Phase rue RMS AC/DC Over and nder Current ypes DC0, PC0 DC0 PC0 RMS AC/DC over + under, over+over, under+under current and voltage monitoring relays DC process signal plus/minus monitoring
More informationDC Current Transducers
Current Transducers are designed to provide an analog current reading for monitoring, data logging and panel meter applications. NK Technologies current transducers offer a choice of 5 VDC, 1 VDC or ma
More informationMODEL AT-10 ANALOG TRANSMITTER
MODEL AT-10 ANALOG TRANSMITTER INSTALLATION & OPERATING MANUAL Industrial Weighing Systems 9 Richmond Street Picton, Ontario K0K 2T0 Phone: 613-921-0397 Fax: 613-476-5293 Web: www.iwsystems.ca info@iwsystems.ca
More informationMonitoring Relays 1-Phase True RMS AC/DC Over and Under Current Types DIC01, PIC01
Monitoring Relays -Phase rue RMS AC/DC Over and nder Current ypes, PC0 PC0 RMS AC/DC over + under, over+over, under+under current and voltage monitoring relays DC process signal plus/minus monitoring relay
More informationCurrent consumption ma solenoid current consumption ( max 300 ma) Hz % V ma. Housing dimensions mm 120(d) x 99(h) x 23(w)
89 610/112 ED EWM-A-SV ANALOG AMPLIFIER CARD SERVOVALVE CONTROL RAIL MOUNTING TYPE: DIN EN 50022 OPERATING PRINCIPLE This card is designed for a dynamic control of servovalves with the current output controlled
More informationTemperature Transmitters - DIN Rail Mounted
XTD Features - Non-programmable Models Sensor Types: Models for thermocouple Types J, K, or T Models for RTD Type Pt100 3-wire Select from a variety of pre-configured measuring ranges Internal cold junction
More information48 Series - Relay interface modules A. Features
Series - Relay interface modules 8-0 - 6 A Features & Pole relay interface modules, 5.8 mm wide. Ideal interface for PLC and electronic systems.3 - Pole 0 A.5 - Pole 8 A.6 - Pole 6 A coils or sensitive
More informationPulse Scaler for DIN Rail Attachment
Type 651 Pulse Scaler for DIN Rail Attachment Programmable pulse scaling factor up to 2047:1 NAMUR generator input PNP transistor output Max. pulse frequency 5 khz PROGRAMMING The divisor is set in binary
More informationEnergy Management Three-phase energy meter with output modules Type EM4-DIN
Energy Management Three-phase energy meter with output modules Type EM4-DIN Class 1 (active energy) Class 2 (reactive energy) Three-phase multi-function energy meter Back-lighted LCD display 3 1 / 2 DGT
More informationTVA 080 / 100 / 120 / 180 / 200 / 220 Isolation amplifier active
Technical manual BA 0318 Signal converter Isolation amplifier active for galvanic isolation, conversion and adjustment of electrical standard signals Evaluable input signals Direct voltage 0...10V / 0...1V
More informationMODEL: M2XPA3. [2] EXCITATION 2: 4 V DC / 20 ma 3: 8 V DC / 20 ma 4: 12 V DC / 20 ma Configurator software is used to change the excitation value.
Super-mini Signal Conditioners Mini-M Series FREQUENCY TRANSMITTER (PC programmable) Functions & Features Converts the output from a pulse-type transducer into a standard process signal PC programmable
More informationCircuit Breakers. Excerpt from Master Catalogue. Circuit Breakers. Specifically For You
Circuit Breakers Excerpt from Master Catalogue Circuit Breakers Specifically For You Hydraulic-magnetic technology ensures reduced nuisance tripping with temperature variance Always holds 00% rated current
More informationTransmitter / Signal Conditioning
GHM GROUP CORPORATE GHM Messtechnik GmbH Schloßstr. 6 88453 Erolzheim GERMANY Phone +49 7354 937233-76 Fax +49 7354 937233-88 Transmitter / Signal Conditioning System Measuring input Direct connection
More informationMBS AG EMBSIN 120 UV. without auxiliary voltage supply housing for 35 mm DIN rail mounting
EMBSIN 120 UV Measuring transducers for AC current : Sinus-shaped alternating voltage (0 20 A or 0 500 V) : Unipolar output signal measuring principle: Rectifier mean value measurement process economic
More informationPM8005/6 PM8005/6. Panel Meter Panel Meter. AC and DC supply options. 5 digit LED display. Direct access menu
PM8005/6 AC and DC supply options 5 digit LED display Direct access menu Functions for calibration, alarm setting and more Wide range of optional functions Description The PM8000 Series digital panel meters
More informationFor non-electrical quantities
Controlgear 3UG3 monitoring relays 3RS17 interface converters N nsb0346h nsb0348h nsb0775h For electrical quantities For non-electrical quantities 3RS17 interface converter Selection and ordering data
More informationDigital Panel Meters DC/AC Current and Voltage Indicator/Controller Type LDM40
Digital Panel Meters Current and Voltage Indicator/Controller Type LDM40 Multi-input instrument 4-DGT LED 0.1% RDG basic accuracy TRMS AC current and voltage measurements AC/DC current measurements: selectable
More informationAdvanced Ladder Logic Full IEC Languages 25A for <1 24 VDC DC Switched
EXL6 OCS Datasheet for HE- EXL1E0, HE- EXL1E2, HE- EXL1E3, HE- EXL1E4, HE- EXL1E5, HE- EXL1E6 HEXT371C100, HEXT371C112, HEXT371C113, HEXT371C114, HEXT371C115, HEXT371C116 1. Specifications Required Power
More informationProtection and safety SQZ3 phase and sequence relay
SQZ3 phase and sequence relay Supply voltage [Vn] 400 V a.c. Frequency [Hz] 0/60 SQZ3 2CSC4001F0201 Contact type [A] 1 CO, 20 V, 10 A (cos =1) safety switching Minimum voltage adjustment trimmer [%] 100
More informationCP-T range Product group picture
Product group picture /1 ABB Catalog Electronic Products and Relays 1/1 2CDC 110 00 C09 Table of contents CP-T range Product group picture /1 Table of contents /2 Benefits and advantages / Ordering details
More informationElectronic timer CT-AWS Impulse-OFF with 1 c/o contact Data sheet
2CDC 251 121 F0004 1 5 2 4 3 6 Characteristics Single-function impulse-off timer One device includes 10 time ranges, from 0.05 s to 300 h, for the adjustment of the pulse time Remote potentiometer connection
More informationXUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New)
XUA1 AC Voltage and phase balance relay (August 1996) Manual XUA1 (Revision New) Woodward Manual XUA1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time.
More information2-WiRE LEvEL TRansmiTTER PRELEvEL 5343 ConTEnTs
2-wire level transmitter PRelevel 5343 Contents EC declaration of conformity... 14 Application... 15 Technical characteristics... 15 Mounting / installation... 15 Applications... 16 Electrical specifications...
More informationLVDT. Inductive Position Transducer - Hydraulic Series. SM-HYD-F18 Hydraulic-Series. Key-Features:
LVDT Inductive Position Transducer - Hydraulic Series SM-HYD-F18 Hydraulic-Series Key-Features: Content: - M18x1,5 mm integral thread - Operating pressure 150 bar - Ranges 2...200 mm - Linearity up to
More informationAnalogue Signal Processing
Analogue Signal Processing Overview. -.5 DC/DC passive isolator current loop-feed.6 -.7 current loop-feed.8 Loop splitter.9 DC/DC -way isolator Power supply on the output side.10 Double sided power supply.11
More informationEnergy Management Modular Smart Power Transducer Type SPT-90
Energy Management Modular Smart Power Transducer Type SPT-90 Class 0.5 (current/voltage) 16-bit µp-based modular smart power transducer Measurements of: W, Wavg, VA, VAr, PF, Wh, VAh, VArh, Amax (among
More informationISOLATED 4-20 ma TRANSMITTERS
500 SERIES FOR DEMANDING APPLICATIONS Isolated to 1500 V rms Two-Wire 4-20 ma Operation 9-50 V Compliance Turndown Ratio to 10:1 NMV Protection to 120 Vac -40 to +85 C (-40 to 185 F) Operation Shock Resistance
More information