MCR-VAC-UI-0-DC. Voltage transducer for AC voltages. INTERFACE Data sheet _en_02. 1 Description
|
|
- Shanon Barrett
- 5 years ago
- Views:
Transcription
1 Voltage transducer for AC voltages TERFACE Data sheet 006_en_0 PHOENIX CONTACT Description The MCR voltage transducer measures AC voltages in several signal ranges from 0... ±4 V AC to 0... ±30 V AC and converts them to standardized analog signals. The input voltage ranges listed at input terminal blocks to can be varied by ±0% using a calibration potentiometer. The input, output, and power supply are electrically isolated from one another. The voltage transducer is calibrated by default to V AC input and V DC output and is ready for operation when delivered. To use the device with other input or output variables, carry out a ZERO/SPAN adjustment using the potentiometers on the front.. Features 3-way electrical isolation True r.m.s. value measurement Adjustable voltage ranges ZERO/SPAN adjustment ±0%. Method of operation The input circuit divides the AC voltage at terminal blocks to. The resulting signal is electrically isolated and transmitted to the output circuit. This creates the true r.m.s. value and the signal is available at the output as a standardized analog signal..3 Field of application When using the voltage transducer, please ensure that the potential difference between terminal blocks to to ground potential PE or terminal block 8 to ground potential PE U rms does not exceed 440 V (this condition applies to circuits that are not grounded). In AC voltage networks, this potential difference must not exceed U rms = 50 V (this condition applies to circuits that are grounded). When these conditions are met, safe isolation is ensured between the input, output, and power supply. Make sure you always use the latest documentation. It can be downloaded from the product at This data sheet is valid for all products listed on the following page:
2 Table of contents Description.... Features.... Method of operation....3 Field of application... Table of contents... 3 Ordering data Technical data Block diagram Safety notes... 5 Structure Installation Configuration Selecting the input voltage range Opening the module umper settings... 0 ZERO/SPAN adjustment Zero point adjustment (ZERO) Final value adjustment (SPAN) _en_0 PHOENIX CONTACT
3 3 Ordering data Description Type Order No. Pcs./Pkt. MCR voltage transducer, for AC voltages from V AC to V DC, output signal V/0(4)... 0 ma MCR-VAC-UI-0-DC Technical data Voltage measuring input Input voltage range (input resistance) Maximum input voltage V AC (30 kω) V AC (50 kω) V AC (0 kω) V AC (0 kω) V AC (80 kω) V AC (54 kω) V AC (36 kω) V AC (4 kω) 440 V AC (not grounded) 50 V AC (to ground) When these values are observed, safe isolation (EN 508/D EN 508/VDE 060) is ensured between the input, output, and power supply. Voltage output Voltage output signal Maximum voltage output signal Load/output load voltage output Ripple V +5 V > 0 kω < 50 mv PP Current output Current output signal Maximum current output signal Load/output load voltage output Ripple 0(4)... 0 ma +30 ma < 500 Ω < 50 mv PP Power supply Supply voltage range Maximum current consumption 8.5 V DC V DC < 45 ma General data Measuring principle True r.m.s. value measurement Maximum transmission error <.5% (of final value) Zero adjustment ±0% Span adjustment ±0% Step response (0-90%) 50 ms Degree of protection IP0 Pollution degree Width x height x length.5 mm x 99 mm x 4.5 mm Housing version Polyamide PA, non-reinforced, green 006_en_0 PHOENIX CONTACT 3
4 Connection data Conductor cross-section, solid 0. mm....5 mm Conductor cross-section, stranded 0. mm....5 mm Stripping length 8 mm Safe isolation according to EN 508 Surge voltage category III Pollution degree Input/output test voltage 3.3 kv (50 Hz, min.) Input/power supply test voltage 3.3 kv (50 Hz, min.) Output/power supply test voltage kv (50 Hz, min.) Rated insulation voltage Input/output Output/power supply 440 V AC, for ungrounded circuits 300 V AC, for grounded circuits 50 V AC Ambient conditions Ambient temperature (operation) Ambient temperature (storage/transport) -5 C C -40 C C, no condensation Conformance/approvals Conformance UL, USA/Canada CE-compliant u Conformance with EMC Directive 89/336/EEC Noise immunity according to EN Electrostatic discharge EN kv air discharge Electromagnetic HF field EN Amplitude modulation Pulse modulation 3 V/m 3 V/m Fast transients (burst) EN Input/output/power supply: kv/5 khz Surge current loads (surge) EN Input/output: kv/4 Ω Power supply: 0.5 kv/ Ω Conducted interference EN Input/output/power supply: 0 V Noise emission according to EN Noise emission according to EN EN 550 Class A 006_en_0 PHOENIX CONTACT 4
5 5 Block diagram 0-30V 0-0V V 0-54V GND Figure Block diagram for the MCR-VAC-UI-0-DC 6 Safety notes OUT VDC 4+ 4VDC 5 6 CAUTION Installation, operation, and maintenance may only be carried out by qualified electricians. When installing and operating the device, the applicable safety directives (including national safety directives), accident prevention regulations, as well as general technical regulations, must be observed. CAUTION: Electrostatic discharge The module contains components that can be damaged or destroyed by electrostatic discharge. When handling the module, observe the necessary safety precautions against electrostatic discharge (ESD) according to EN and EN Structure 5 4 Figure MCR-VAC-UI-0-DC MCR-VAC -UI-0 -DC Art. -Nr.: Location of the elements Supply voltage Output 3 Potentiometer for adjustment 4 Inputs 5 Upper part of the housing can be removed to set the jumpers 6 Universal snap-on foot for EN D rails 0-30V 0-0V V V 6 GND 8 OUT GND GND 0-30V 0-50V 0-0V 0-0V 0-80V 0-54V 0-36V/0-4V GND APPROBATIONEN / APPROVALS 6 +4VDC +4VDC GND 3 GND VDC + 4VDC _en_0 PHOENIX CONTACT 5
6 8 Installation 9 Configuration A B B B 0-30V 0-0V V V 6 GND Figure 3 Mounting/removal Figure 4 Opening the housing The assignment of the connection terminal blocks is shown in the block diagram. The module can be snapped onto all 35 mm D rails according to EN 605. Install the module in suitable housing to meet the requirements for the protection class. Screw connection Insert the wire into the corresponding connection terminal block. Use a screwdriver to tighten the screw in the opening above the connection terminal block. WARNG: Risk of electric shock Never carry out work when voltage is present. NOTE: Module damage due to excess voltage If the voltage signal exceeds the voltage range specified at the input signal terminal block by more than 5%, the input circuit may be damaged. 9. Selecting the input voltage range Input voltage Adjustment range (±0%) [V AC] Input terminal block umper/ setting V ( ) V ( ) V ( ) V ( ) V ( ) V ( ) V ( ) /setting V (9... 9) /setting (default setting) 006_en_0 PHOENIX CONTACT 6
7 9. Opening the module Using a screwdriver, release the locked upper part of the housing on both sides. The upper part of the housing and the electronics can now be pulled out approximately 3 cm (see Figure 4 on page 6). 9.3 umper settings Insert the jumpers in slots... 3 according to the required input voltage and the current output. Input voltage: Input umper Position 36 V 4 V Current output: Output umper Position V / ma / ma /3 Close the housing again until it engages with a click. Carry out a ZERO/SPAN adjustment each time the input or output range is changed. 0 ZERO/SPAN adjustment Figure 6 Potentiometers MCR-VAC-UI-0-DC 0-30V 0-50V 0V MCR-VAC -UI-0 -DC Art. -Nr.: Location of the potentiometers Allow the module to warm up for 4 minutes before starting the adjustment procedure. The module is calibrated by default to V input and V output. There are two potentiometers on the front of the module for the adjustment: ZERO: Zero point adjustment SPAN: Final value adjustment 0-30V 0-0V V V 6 GND 8 OUT GND GND VDC +4VDC D 3 + 4VDC + 4VDC V 4V Zero point adjustment (ZERO) Connect a calibration device to the input terminal blocks (U ( - ) and GND) and specify a voltage of 0 mv. Set the output signal value using the ZERO potentiometer: Voltage output (0 0 V): U OUT = 0 V Current output (0 0 ma): I OUT = 0 ma Current output (4 0 ma): I OUT = 4 ma 0. Final value adjustment (SPAN) Use the calibration device to specify the maximum voltage used within the input voltage range (see "Selecting the input voltage range" on page 6). Set the output signal value (U OUT = 0 V or I OUT = 0 ma) using the SPAN potentiometer. Figure 5 Location of jumpers _en_0 PHOENIX CONTACT GmbH & Co. KG 383 Blomberg Germany Phone: PHOENIX CONTACT P.O.Box 400 Harrisburg PA -000 USA Phone:
Passive Current Transducers for Sinusoidal Alternate Currents From A/0...5 A MCR-SLP-1/5-UI-0(-SW)
Passive Current Transducers for Sinusoidal Alternate Currents From 0... A/0...5 A (-SW) Passive current transducer without power supply Measuring range A and 5 A AC, reconnectable Available with threshold
More informationMCR-SL-CUC Universal current transducer. Data sheet _en_05. 1 Description
Universal current transducer Data sheet 104059_en_05 PHOENIX CONTACT 2011-03-09 1 Description MCR-SL-CUC-...-I and MCR-SL-CUC-...-U active current transducers convert DC, AC, and distorted currents into
More informationMCR-C-UI-UI-DCI MCR 3-Way Isolation Amplifier, Configurable
MCR-C-UI-UI-DCI MCR 3-Way Isolation Amplifier, Configurable 1. Short description configurable inputs and outputs signal conversion/amplification 3-way-isolation zero/span adjustment 17.5 mm ME housing
More informationMINI MCR-SL-UI-I-LP-NC
2-way isolation amplifier Data sheet 105263_en_02 PHOENIX CONTACT 2013-12-13 1 Description The configurable 2-way isolation amplifiers are used to electrically isolate, convert and filter standard signals.
More informationMINI MCR-SL-UI-f(-SP)
Configurable Analog Frequency Transducer INTERFACE Data Sheet PHOENIX CONTACT - 02/2006 Description The configurable analog frequency transducer MINI MCR-SL-UI-f(-SP) is used to convert analog standard
More informationMINI-PS AC/24DC/1.3
Power supply unit INTERFACE Data sheet 102894_en_03 1 Description PHOENIX CONTACT 2015-11-17 Features MINI POWER power supplies for MCR technology In measurement and control technology (MCR), modular electronics
More informationMINI-PS AC/2X15DC/1
MII-PS-100-240AC/2X15DC/1 Power supply unit ITERFACE Data sheet 100299_en_04 1 Description PHOEIX COTACT - 2010-10-20 Features MII POWER is the extremely slim power supply unit with constructional widths
More informationMACX MCR-UI-UI-UP(-SP)(-NC)
Configurable 3-way isolating amplifier with safe isolation and wide-range power supply Data sheet 04247_en_02 PHOENIX CONTACT 203-04-0 Description MACX MCR-UI-UI 3-way isolating amplifiers are used to
More informationEMD-FL-3V-400. Electronic monitoring relay for voltage monitoring in three-phase networks. INTERFACE Data sheet _en_03. 1 Description.
Electronic monitoring relay for voltage monitoring in three-phase networks INTERFACE Data sheet 102110_en_03 1 Description PHOENIX CONTACT - 09/2009 Features Increasingly higher demands are being placed
More informationRAD-IN/OUT-8D. Digital extension modules for the bidirectional wireless system. INTERFACE Data sheet _en_05. 1 Description
RAD-IN/OUT-D Digital extension modules for the bidirectional wireless system INTERFACE Data sheet 102122_en_0 PHOENIX CONTACT 2010-02-2 1 Description The RAD-ISM-...-SET-BD-BUS-ANT bidirectional wireless
More informationQUINT-PS-24DC/24DC/10
QUINT-PS-24/24/10 QUINT - converter, primary switched mode, input: 24 V, output: 24 V /10 A INTERFACE Data Sheet PHOENIX CONTACT - 02/2006 Description The QUINT - converter 24 V/10 A converts the voltage
More informationMCR-T-UI(/NC) MCR-T-UI-E(/NC)
MCR-T-UI(/) MCR-T-UI-E(/) Programmable Temperature Transducers for Resistance Thermometers and Thermocouples INTERFACE ata Sheet 00_0_en PHOENIX CONTACT - 0/00 escription A universal temperature measuring
More informationQUINT-PS AC/24DC/40
Power supply unit INTERFACE Data sheet 102315_en_02 1 Description PHOENIX CONTACT 2010-04-23 Features QUINT POWER power supply units for plant and special engineering reliably start heavy loads with high
More informationMACX MCR-EX-T-UI-UP. Extract from the online catalog. Order No.:
Extract from the online catalog MACX MCR-EX-T-UI-UP Order No.: 2865654 Freely programmable Ex-i temperature transducer with analog output and 1 limit value relay, standard configuration, resistance thermometer
More informationMCR-C-UI-UI-DCI. Extract from the online catalog. Order No.:
Extract from the online catalog MCR-C-UI-UI-DCI Order No.: 2810913 MCR 3-way isolating amplifier, with configurable I/O, for the electrical isolation of analog signals, with GL approval, preconfigured.
More informationMeasuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC
2CDC 251 244 F0t05 Characteristics Monitoring of DC and AC currents: RMS measuring principle One device includes 3 measuring ranges Over- or undercurrent monitoring configurable Hysteresis adjustable from
More informationUNO-PS/1AC/24DC/150W. Primary-switched power supply unit. Data sheet. 1 Description
Primary-switched power supply unit Data sheet 106261_en_02 PHOEIX COTACT 2015-05-13 1 Description The power supply makes a worldwide impression thanks to maximum energy efficiency. ow idling losses (o
More informationQUINT-PS/ 3AC/24DC/10
Primary-switched power supply with SFB technology, 3 AC, output current 10 A INTERFACE Data sheet 103131_en_01 1 Description PHOENIX CONTACT - 09/2009 Features QUINT POWER power supply units Maximum system
More informationQUINT-PS/ 3AC/24DC/40
Primary-switched power supply unit with SFB technology, 3 AC, output current 40 A INTERFACE Data sheet 103133_en_00 1 Description PHOENIX CONTACT - 07/2009 Features QUINT POWER power supply units Maximum
More informationTRIO-PS/1AC/24DC/ 5. Extract from the online catalog. Order No.:
Extract from the online catalog TRIO-PS/1AC/24DC/ 5 Order No.: 2866310 DIN rail power supply unit, primary-switched mode, 1-phase, output: 24 V DC / 5 A Commercial data EAN 4046356046640 Pack 1 pcs. Customs
More informationPHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.
Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data Sheet 103129_en_01 PHOENIX CONTACT - 05/2008 1 Description QUINT POWER power supply units highest system availability
More informationElectronic timer CT-SDD.22
CDC 099 F0t0 a Rotary switch for the preselection of the time range b Potentiometer with direct reading scale for the fine adjustment of the time delay c U: green LED V control supply voltage applied W
More informationSignal conditioner - MACX MCR-UI-UI-NC
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid
More informationPHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.
Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data Sheet 103383_en_00 1 Description PHOENIX CONTACT - 06/2008 Features QUINT POWER power supply units highest system
More informationPower supply CP-E 48/5.0 Primary switch mode power supply Data sheet
2CDC 271 028 F0008 OUTPUT L+, L+, L-, L-: terminals - output Features Rated output voltage 48 V DC Output voltage adjustable via front-face rotary potentiometer OUTPUT Adjust Rated output current 5 A Rated
More informationPower supply CP-E 24/2.5
2CDC 271 015 F0t06 a OUTPUT L+, L : terminals output b DC OK: terminal signalling output c INPUT L, N, PE: terminals input d OUTPUT OK: green LED output voltage OK e OUTPUT Adjust: potentiometer adjustment
More informationPower supply CP-E 24/20.0
2CDC 271 027 F0008 a OUTPUT L+, L+, L, L-: terminals output b INPUT L, N, PE: terminals input c 13-14: terminals - signalling contact d OUTPUT OK: green LED output voltage OK e OUTPUT LOW: red LED output
More informationPower supply CP-E 24/2.5
2CDC 271 015 F0t06 a OUTPUT L+, L : terminals output b DC OK: terminal signalling output c INPUT L, N, PE: terminals input d OUTPUT OK: green LED output voltage OK e OUTPUT Adjust: potentiometer adjustment
More informationElectronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet
CDC 0 F0t07 Features Rated control supply voltage -8 V DC, -0 V AC Single-function timer with star-delta change-over One device includes 7 time ranges (0.0 s - 0 min) n/o contacts LEDs for status indication
More informationPower supply CP-D 24/1.3
2CDC 271 027 F0t07 a OUTPUT ++/ : terminals output Features Rated output voltage 24 V DC Output voltage adjustable via front face potentiometer OUTPUT Adjust Rated output current 1.3 A Rated output power
More informationPower supply CP-E 12/10.0 Primary switch mode power supply Data sheet
2CDC 271 024 F0008 OUTPUT L+, L+, L-, L-: terminals - output INPUT L, N, PE: terminals - input OUTPUT OK: green LED - output voltage OK OUTPUT LOW: red LED - output voltage too low OUTPUT Adjust: potentiometer
More informationQUINT-PS/ 1AC/24DC/20
Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data sheet 103129_en_04 1 Description PHOENIX CONTACT - 02/2010 Features QUINT POWER power supply units Maximum system
More informationExtract from the online catalog
Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation at http://www.download.phoenixcontact.com. The
More informationPower supply CP-E 24/0.75
2CDC 271 016 F0t06 a OUTPUT L+, L : terminals output b INPUT L, N, PE: terminals input c LOW: red LED output voltage too low d OK: green LED output voltage OK e OUTPUT Adjust: rotary potentiometer output
More informationTRIO-PS-2G/1AC/24DC/5
TRIOPS2G/1AC/24DC/5 Power supply unit Data sheet 105900_en_01 PHOENIX CONTACT 20150831 1 Description TRIO POWER power supplies with standard functionality The power supplies of the TRIO POWER family convince
More informationElectronic timer CT-TGD.22
2CDC 251 097 F0t06 a Rotary switch for the preselection of the time range of the ON time b Potentiometer with direct reading scale for the fine adjustment of the ON time c Rotary switch for the preselection
More informationThree-phase monitoring relays
2CDC 251 046 F0t08 Features Monitoring of three-phase mains for phase sequence, phase failure, phase unbalance Threshold value for phase unbalance adjustable as absolute value Tripping delay can be adjusted
More informationAnalog signal converters CC-E I/I
2CC 281 001 F0b06 Features Loop-powered I/I isolator without external power supply for analog current signals of 0-20 ma and 4-20 ma Electrical isolation between input and output Very low internal voltage
More informationType CP-S, CP-C & CP-A Switch mode
Switch mode power CP-S, CP-C & CP-A Switch mode Characteristics CP-S and CP-C range Output current 5 A, 10 A and 20 A Integrated power reserve of up to 50 % 5 A and 10 A devices with pluggable connecting
More informationCurrent monitoring relays CM-SRS.2 for single-phase AC/DC currents
Data sheet Current monitoring relays CM-SRS.2 for single-phase AC/DC currents For the monitoring of currents in single-phase AC/DC systems, ABB s CM range comprises a wide selection of powerful and compact
More informationABB NEW. Three-phase monitoring relays. CM-PVS.31 and CM-PVS.41 Data sheet. Features J. Approvals. Marks. Order data. Order data - Accessories
2CDC 251 042 F0t08 CM-PVS.31 Features Monitoring of three-phase mains for phase sequence (can be switched off), phase failure, over- and undervoltage Threshold values for over- and undervoltage are adjustable
More informationCM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC
2CDC 251 048 F0t08 CM-MPS.11 2CDC 251 049 F0t08 CM-MPS.21 Features Monitoring of three-phase mains for phase sequence (can be switched off), phase failure, over- and undervoltage as well as phase unbalance
More informationVoltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages For the monitoring of voltages in single-phase AC/DC systems, ABB s CM range comprises a wide selection of powerful and compact
More informationPower supply CP-D 24/4.2 Primary switch mode power supply
Data sheet Power supply CP-D 24/4.2 Primary switch mode power supply The CP-D range of modular power supply units in MDRC design (modular DIN rail components) is ideally suited for installation in distribution
More informationPower supply CP-D 12/2.1
2CDC 271 025 F0t07 a OUTPUT ++/ : terminals output Features Rated output voltage 12 V DC Output voltage adjustable via front face potentiometer OUTPUT Adjust Rated output current 2.1 A Rated output power
More informationSTEP-UPS/24DC/24DC/3. Uninterruptible power supply. Data sheet. 1 Description. Features
Uninterruptible power supply Data sheet 105623_en_00 PHOENIX CTACT 2013-06-07 1 Description Uninterruptible power supply units continue to deliver power even in the event of mains breakdowns or failures.
More informationCurrent monitoring relays CM-SRS.1 for single-phase AC/DC currents
Data sheet Current monitoring relays CM-SRS.1 for single-phase AC/DC currents For the monitoring of currents in single-phase AC/DC systems, ABB s CM range comprises a wide selection of powerful and compact
More informationCurrent monitoring relays CM-SRS.1 For single-phase AC/DC currents
Data sheet Current monitoring relays CM-SRS.1 For single-phase AC/DC currents The CM-SRS.1 is an electronic current monitoring relay that protects single-phase mains (DC or AC) from over- and undercurrent
More informationPower supply CP-T 48/20.0 Primary switch mode power supply
Data sheet Power supply CP-T 48/20.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,
More informationCurrent monitoring relays CM-SRS.2 For single-phase AC/DC currents
Data sheet Current monitoring relays CM-SRS.2 For single-phase AC/DC currents The CM-SRS.2 is an electronic current monitoring relay that protects single-phase mains (DC or AC) from over- and undercurrent
More informationNotes: Note1: Efficiency is tested at nominal input and full load at +25 C ambient. Output Voltage 400VAC 320VAC 360VAC 400VAC 400VAC
Features DIN-Rail 2 and 3-phase operation Input voltage range: 320 575VAC Output trim range: 22.5 29.5VDC High electrical strength; high reliability Permanent overload and short-circuit protection Parallel
More informationMACX MCR-EX-SL-RPSSI-I-UP(-SP)
Supply and input signal conditioner, Ex-i, with wide range supply Data sheet 103561_en_00 PHOENIX CONTACT 2014-08-19 1 Description The MACX MCR-EX-SL-RPSSI-I-UP(-SP) repeater power supply and input signal
More informationPHOENIX CONTACT
Selective circuit breaker CLIPLINE Data sheet 100464_en_05 PHOENIX CONTACT 2009-11-17 1 Description The electronic circuit breaker, which has a design width of just 12.5 mm, selectively protects all 24
More informationVoltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
More informationVoltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages The CM-EFS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
More informationABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks.
2CDC 251 052 F0t08 CM-MPS.23 2CDC 251 053 F0t08 CM-MPS.43 - relay status, timing - fault message - fault message Adjustment of the tripping delay t V Adjustment of the threshold value for overvoltage 6
More informationCoupling Relays and Converters
Overview Area of application In automation and control engineering it will always be necessary to work with analog signals. The interfaces for analog signals that have established themselves as the standard
More informationPower supply CP-T 24/20.0 Primary switch mode power supply
Data sheet Power supply CP-T 24/20.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,
More informationEMD-FL-C-10. Current Monitoring Relay. Data Sheet. Functions. Structure 08/2004
Current Monitoring Relay Data Sheet 08/2004 Functions Structure Current monitoring of direct and alternating current in 1-phase networks with settable threshold values, starting override and response delay
More informationPower supply CP-T 48/5.0 Primary switch mode power supply
Data sheet Power supply CP-T 48/5.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,
More informationNotes: Note1: Efficiency is tested at nominal input and full load at +25 C ambient. Output Voltage 400VAC 400VAC
Features DIN-Rail Description 2 and 3-phase operation Input voltage range: 320 575VAC Output trim range: 22.5 29.5VDC High electrical strength; high reliability Permanent overload and short-circuit protection
More informationPHOENIX CONTACT
Electronic circuit breaker CLIPLINE Data sheet 102898_en_03 PHOENIX CONTACT 2010-12-17 1 Description The electronic circuit breaker can be used in applications that cover all aspects of the switched-mode
More informationPower supply CP-T 24/10.0 Primary switch mode power supply
Data sheet Power supply CP-T 24/10.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,
More informationPower supply CP-T 24/40.0 Primary switch mode power supply
Data sheet Power supply CP-T 24/40.0 Primary switch mode power supply The CP-T range of three-phase power supply units is the youngest member of ABB s power supply family. In terms of design and functionality,
More informationPACT RCP-4000A-UIRO-Dxxx
Configurable current transformer for retrofitting Data sheet 106844_en_01 PHOENIX CONTACT 2016-03-29 1 Description The Rogowski coil is used to measure AC current and is primarily intended for subsequent
More informationMODEL IAMA - UNIVERSAL SIGNAL CONDITIONING MODULE
MODEL IAMA - UNIVERSAL SIGNAL CONDITIONING MODULE 3-WAY ISOLATION OF ANALOG SIGNALS UNIVERSAL CONVERSION MODULE - INPUTS AND OUTPUTS SELECTED VIA DIP SWITC SETTINGS OVER 100 INPUT AND OUTPUT ANALOG CONVERSION
More informationCP-E range Benefits and advantages
Benefits and advantages Characteristics Output voltages 5 V, 12 V, 2 V, 8 V DC Adjustable output voltages Benefits Signalling output/contact Output currents 0.625 A / 0.75 A / 1.25 A / 2.5 A / A / 5 A
More information08/07/2015
17.5 mm - 1 Solid State Relay 0.7A MUS2 Part number 88827004 Multi-function or mono-function Multi-range Multi-voltage Screw or spring terminals LED status indicator (relay version) Possibility of external
More informationABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.
2CDC 251 048 F0t08 CM-MPS.11 2CDC 251 049 F0t08 CM-MPS.21 2CDC 251 050 F0t08 CM-MPS.31 2CDC 251 051 F0t08 CM-MPS.41 R/T: yellow LED - relay status, timing F1: red LED - fault message F2: red LED - fault
More informationModel Number Structure. Ordering Information. Solid-state Power OFF-delay Timer H3DE-H. Model Number Legend. List of Models
Solid-state Power OFF-delay Timer H3DE-H Timers Two delay-time models available. 0.1 to 12 seconds (S Series) 1 to 120 seconds (L Series) Covers wide range of supply voltage. Model Number Structure Model
More informationThree-phase monitoring relay CM-PVE
Data sheet Three-phase monitoring relay CM-PVE The three-phase monitoring relay CM-PVE monitors the phase parameter phase failure as well as over- and undervoltage in three-phase mains. 2CDC 251 006 S0012
More informationHigh precision measurement system for current and voltage IHC-A/B-RM01/03
Measurement Offset-free and low-noise 16 bit data acquisition system ISA-ASIC Internal sample rate 3,500 Hz Communication Standard RS232- or RS485 interface Advantages Direct measurement on the bus bar
More informationElectronic timer CT-SDS.22
CDC 0 F0t07 Features Rated control supply voltage 8 V DC, 0 V AC Single function timer with star delta change over One device includes 7 time ranges (0.0 s 0 min) n/o contacts LEDs for status indication
More informationType: EASY719 DA RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 12 V DC. Description
Type: EASY719 DA RC Article.: 274117 Ordering information Relay outputs Quantity 6 Power supply V DC 12 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
More informationTemperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)
Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,
More informationCurrent monitoring relays CM-SRS.M1 For single-phase AC/DC currents
Data sheet Current monitoring relays CM-SRS.M1 For single-phase AC/DC currents The CM-SRS.M1 is an electronic current monitoring relay that monitors single-phase mains (DC or AC) for over- and undercurrent
More informationPSD-S AE SM DB/1
Siren element, 8 tones, 24 V AC/DC, max. 100 db(a) Data sheet 7944_en_02 PHOENIX CTACT 2015-05-04 1 Description This audible signal element is designed as a component of a modular signal tower. According
More informationCP-T range Product group picture
Product group picture /1 ABB Catalog Electronic Products and Relays 1/1 2CDC 110 00 C09 Table of contents CP-T range Product group picture /1 Table of contents /2 Benefits and advantages / Ordering details
More informationThree-phase monitoring relays CM-PFE and CM-PFE.2
Data sheet Three-phase monitoring relays CM-PFE and CM-PFE.2 The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251
More information"Modular" versions designed for application-specific functions LCD with 4 lines of 18 characters and configurable backlighting
Smart "Compact" range with display CD12 Smart Part number 88974043 "Modular" versions designed for application-specific functions LCD with 4 lines of 18 characters and configurable backlighting Type Input
More informationCustom "Compact" range with display CD20 Custom Part number
Custom "Compact" range with display CD20 Custom Part number 88974051 "Modular" versions designed for Custom application-specific functions (Custom functions) LCD with 4 lines of 18 characters and configurable
More informationElectronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact The CT-TGD.12 is an electronic time relay with the function pulse generator. It is from the CT-D range. With their MDRC profile
More informationSwitching power supplies CP range, Linear power supplies CP-L range. Content
CP range, Linear power supplies CP-L range Content Switching power supplies, primary switch mode, CP range Benefits and advantages... 136 Approvals... 137 Ordering details... 138 Technical data... 11 Dimensional
More informationVoltage monitoring relays CM-ESS.M For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages The CM-ESS.M is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
More informationTMT Series, 10 to 50 Watt. Order Code Output Power Output 1 PCB-Mount Chassis Mount max.
TMT Series, 10 to 50 Watt Features Ultra compact, fully encapsulated plastic case Single-, dual- and triple output models 2 package styles: - with screw terminal block for chassis mount - with solder pins
More informationElectronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts
Data sheet Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts The CT-AHS.22 is an electronic timer from the CT-S range with OFF-delay and 10 time ranges. All electronic timers from the CT-S
More informationRAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL
RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL 1 Contents 1. Application... 5 2. meter set... 6 3. BASIC REQUIREMENTS, OPERATIONAL SAFETy... 6 4. installation... 10 4.1. Mounting... 10 4.2. External
More informationThree-phase monitoring relay
1SR 550 870 F9400 Features Monitoring of three-phase mains for phase failure, over- and undervoltage Device with possibility of neutral monitoring available Device with suitability for monitoring single-phase
More informationPHOENIX CONTACT - 01/2007
Inline Terminal With 2 Analog Input Channels AUTOMATIONWORX Data Sheet 5564_en_03 1 Description PHOENIX CONTACT - 01/2007 The terminal is designed for use within an Inline station. It is used to acquire
More informationPrimary switch mode power supplies Product group picture
Primary switch mode power supplies Product group picture /1 ABB Catalog Electronic Products and Relays 2015 2CDC 110 004 C0210 Primary switch mode power supplies Table of contents Primary switch mode power
More information08/07/2015
17.5 mm - 1 Relay 8A MUR1 Part number 88827105 Multi-function or mono-function Multi-range Multi-voltage Screw or spring terminals LED status indicator (relay version) Possibility of external load connection
More informationSCC-FV01 Frequency Input Module
USER GUIDE SCC-FV01 Frequency Input Module Conventions The SCC-FV01 frequency input module is a frequency-to-voltage converter designed to measure signals from frequency-generating sensors and other periodic
More informationCP-T range Benefits and advantages
Benefits and advantages Characteristics Rated output voltages V, V DC Output voltage adjustable via front-face rotary potentiometer OUTPUT Adjust Rated output currents 5 A, 10 A, A, A Rated output powers
More informationIB IL 24 PWR IN/PS IB IL 24 PWR IN/PS-PAC
IB IL 24 PWR IN/PS IB IL 24 PWR IN/PS-PAC Inline Power Terminal for the System Voltages U M, U S, U L, U ANA Data Sheet 694500 05/2003 $ ' " # ) Features Items IB IL 24 PWR IN/PS and IB IL 24 PWR IN/PS-PAC
More informationThree-phase monitoring relays CM-PVS CM-PVS.31, CM-PVS.41 and CM-PVS.81
Data sheet Three-phase monitoring relays CM-PVS CM-PVS.31, CM-PVS.41 and CM-PVS.81 The three-phase monitoring relays CM-PVS.x1 monitor the phase parameters phase sequence, phase failure as well as over-
More informationSINEAX I 503 / SINEAX U 504 Transducer for AC current or AC voltage
Application The transducers SINEAX I 503/U 504 (Figs. 1 and 2) are designed to convert a sinusoidal AC current or voltage into a load independent DC signal proportional to the measured value. This output
More informationVariTrans P Compact automation solutions can be implemented thanks to the 17.5 mm modular housing and operation at temperatures up to 70 C.
ProLine Interface Technology Transducers for High Voltage / Shunt Applications Compact high voltage transducers with VariPower broad-range power supply and genuine calibrated range selection. The Task
More informationIB IL AI 2/SF. Function. INTERBUS Inline Terminal With Two Analog Input Channels. Data Sheet 5564A
INTERBUS Inline Terminal With Two Analog Input Channels Data Sheet 5564A 06/1999 # # $ " ) This data sheet is intended to be used in conjunction with the INTERBUS Inline System Manual IB IL SYS PRO UM
More information02/11/2015
17.5 mm - 1 Relay 5A EMER8 Part number 88829198 Multifunction or mono-function Multi-range (7 ranges) Multi-voltage or single voltage Screw terminals LED status indicator (1 voltage present LED, 1 timer
More informationLiquid level monitoring relay CM-ENS.2x
Data sheet Liquid level monitoring relay CM-ENS.2x The CM-ENS.2x is served to regulate and control liquid levels and ratios of mixtures of conductive fluids. It can be used for overflow protection, dry
More information