Parameter Settings for PowerFlex Drives Using Sine Wave Filters, dv/dt Filters, and Adjustable Voltage

Size: px
Start display at page:

Download "Parameter Settings for PowerFlex Drives Using Sine Wave Filters, dv/dt Filters, and Adjustable Voltage"

Transcription

1 Application Technique Parameter Settings for PowerFlex Drives Using Sine Wave Filters, dv/dt Filters, and Adjustable Voltage PowerFlex 700, 700VC, and 750-Series AC Drives Topic Page About This Document 1 PowerFlex 700 Parameter Settings for Use With Sine Wave Filters 2 PowerFlex 700 Parameter Settings for Use With dv/dt Filters 3 PowerFlex 700VC Parameter Settings for Use With Adjustable Voltage 4 Application With a Sine Wave Filter PowerFlex 753/755 Parameter Settings for Use With Sine Wave Filters 8 PowerFlex 753/755 Parameter Settings for Use With dv/dt Filters 9 PowerFlex 753/755 Parameter Settings for Use With Adjustable Voltage 10 Application About This Document This information applies to PowerFlex 700, PowerFlex 700VC, and PowerFlex 750-Series AC Drives. This document provides information for key parameters that can be adjusted when applying the Adjustable Voltage or V/Hz control methods through a Sine wave filter at the output of a Variable Frequency Drive (VFD). Setting up the drive parameters described in this document modifies the Stability gains, modulation mode, and prevents over reaction to the charging current into the capacitor branch of a Sine wave filter. PFLEX-AT002A-EN-P

2 PowerFlex 700 Parameter Settings for Use With Sine Wave Filters Parameter Name Default Setting Set To P053 Motor Cntl Set 0 (Sensrls Vect) 2 (Custom V/Hz) P056 Compensation Bit 0 - Reflect Wave 1 (enabled) 0 (disabled) Bit 3 - Xsistor Diag 1 (enabled) 0 (disabled) Bit 7 - PWM Freq Lock 0 (disabled) 1 (enabled) P057 Flux Up Mode 0 (manual) 0 (manual) P058 Flux Up Time sec sec P150 Drive OL Mode 3 (both-pwm 1st) 1 (reduce CLim) P151 PWM Frequency 2 or 4 khz see filter instructions P506 Angl Stability Gain 51 0 P507 Volt Stability Gain P524 Modulation Mode 0 (2-phase + SpV) 1 (Space Vector only) P069 Start/Acc Boost xx not too high P070 Run Boost xx per motor P071 Break Voltage xx per need P072 Break Frequency xx per need Do not autotune. Below is list of operational theory that describes why the parameter settings are used. Motor control setting (P053) needs to be V/Hz because, with the filter between the drive and motor, the load no longer looks like a motor to the drive. Therefore, the drive needs to operate in a simple V/Hz mode. Reflected wave (P056, Bit 0) is turned off so that there will be no missing pulses in the output voltage waveform, and to minimize any offsets that could appear. Transistor diagnostics (P056, Bit 3) is turned off because the sequence of turning transistors on and off charges the capacitors in the filter and can cause an instantaneous over-current (IOC) trip. Pulse width modulation (PWM) frequency lock (P056, Bit 7) is on because the filter is tuned to the carrier frequency, and if the carrier frequency were to change, the filter would not work, so the carrier must be fixed. Also, the PWM frequency needs to be set for whatever the filter is tuned to: either 2 or 4 khz. Drive OL mode (P150) is set for reduce current limit, and not the PWM frequency, for the same reason as pulse width modulation frequency lock. Angle stability gain (P506) is set for 0 so it does not try to compensate for the currents it sees going into the filter's capacitors. Voltage stability gain (P507) is set for 10 for the same reason as angle stability gain. Modulation mode (P524) is set for space vector only since 2-phase modulation would degrade the filter's performance. 2 Rockwell Automation Publication PFLEX-AT002A-EN-P - May 2011

3 PowerFlex 700 Parameter Settings for Use With dv/dt Filters Parameter Name Default Setting Set To P053 Motor Cntl Set 0 (Sensrls Vect) V/hz, SVC, or FVC P056 Compensation Bit 0 - Reflect Wave 1 (enabled) 0 (disabled) Bit 3 - Xsistor Diag 1 (enabled) 0 (disabled) Bit 7 - PWM Freq Lock 0 (disabled) 1 (enabled) P057 Flux Up Mode 0 (manual) 0 (manual) P058 Flux Up Time sec sec P150 Drive OL Mode 3 (both-pwm 1st) 1 (reduce CLim) P151 PWM Frequency 2 or 4 khz see filter instructions P506 Angl Stability Gain 51 0 P507 Volt Stability Gain P524 Modulation Mode 0 (2-phase + SpV) 0 or 1 P069 Start/Acc Boost xx not too high P070 Run Boost xx per motor P071 Break Voltage xx per need P072 Break Frequency xx per need Do not autotune. Below is list of operational theory that describes why the parameter settings are used. Motor control setting (P053) can be V/Hz, Sensorless Vector Control (SVC), or Flux Vector Control (FVC). Reflected wave (P056, Bit 0) is turned off so that there will be no missing pulses in the output voltage waveform, and to minimize any offsets that could appear. Transistor diagnostics (P056, Bit 3) is turned off because the sequence of turning transistors on and off charges the capacitors in the filter and can cause an instantaneous over-current (IOC) trip. Pulse width modulation (PWM) frequency lock (P056, Bit 7) is on because the filter is tuned to the carrier frequency, and if the carrier frequency were to change, the filter would not work, so the carrier must be fixed. Also, the PWM frequency needs to be set for whatever the filter is tuned to: either 2 or 4 khz. Drive OL mode (P150) is set for reduce current limit, and not the PWM frequency, for the same reason as pulse width modulation frequency lock. Angle stability gain (P506) is set for 0 so it does not try to compensate for the currents it sees going into the filter's capacitors. Voltage stability gain (P507) is set for 10 for the same reason as angle stability gain. Modulation mode (P524) is set for space vector only since 2-phase modulation would degrade the filter's performance. Rockwell Automation Publication PFLEX-AT002A-EN-P - May

4 PowerFlex 700VC Parameter Settings for Use With Adjustable Voltage Application With a Sine Wave Filter Parameter Name Default Setting Set To P196 [Param Access Lvl] 0 (Basic) 2 (Reserved) P053 (1) Motor Cntl Sel 0 (Sensorless Vector) 5 (Adj Voltage) P056 Compensation xx xx Bit 0 - Reflect Wave 1 (enabled) 0 (disabled) Bit 3 - Xsistor Diag 1 (enabled) 0 (disabled) Bit 7 - PWM Freq Lock (2) 0 (disabled) 1 (enabled) P057 Flux Up Mode 0 (manual) 0 (manual) P058 Flux Up Time sec sec P069 (1) Start/Acc Boost Based on drive rating 0 P070 (1) Run Boost Based on drive rating 0 P071 (1) Break Voltage Motor NP Volts x P072 (1) Break Frequency Motor NP Hertz x P150 Drive OL Mode 3 (both-pwm 1st) 1 (Reduce Climit) P151 PWM Frequency 2 or 4 khz see filter instructions (typically 2 or 4 KHz) Hidden Parameters P506 Angle Stability Gain 51 0 P507 Volt Stability Gain P524 Modulation Mode 0 (2-phase + SUV) 1 (Space Vector) P552 Dead Time Comp (3) 75% 0% (1) Set these parameters (69, 70, 71, and 72) when using mode 5 (Adj Voltage) for P053. (2) In drives with firmware and newer. (3) May be required to adjust setting if there are DC offset voltages at LOAD transformer input windings. Do not autotune. Note: Many, but not all, adjustable voltage applications require a Sine wave filter. Below is list of operational theory that describes why the parameter settings are used. Motor control setting (P053) needs to be set in a form of V/Hz because, with the Sine wave filter between the drive and motor, the load no longer looks like a motor to the drive. The Adjustable Voltage feature set is used in nontraditional/non-motor applications that require independent voltage regulator and frequency regulator power control to the load. The drive output is still a form of V/Hz. Reflected wave (P056, Bit 0) is turned off so that there will be no missing pulses in the output voltage waveform, and to minimize any offsets that could appear. Transistor diagnostics (P056, Bit 3) is turned off because the sequence of turning transistors on and off charges the capacitors in the filter and can cause an instantaneous over-current (IOC) trip. Pulse width modulation (PWM) frequency lock (P056, Bit 7) is on because the filter is tuned to the carrier frequency, and if the carrier frequency were to change, the filter would not work, so the carrier must be fixed. Also, the PWM frequency needs to be set for whatever the filter is tuned to: either 2 or 4 khz. 4 Rockwell Automation Publication PFLEX-AT002A-EN-P - May 2011

5 Drive OL mode (P150) is set for reduce current limit, and not the PWM frequency, for the same reason as pulse width modulation frequency lock. Angle stability gain (P506) is set for 0 so it does not try to compensate for the currents it sees going into the filter's capacitors. Voltage stability gain (P507) is set for 10 for the same reason as angle stability gain. Modulation mode (P524) is set for space vector only since 2-phase modulation would degrade the filter's performance. Note: Dead Time Comp (P552) is best set to 0% when output of the Sine wave filter is fed into a transformer, to prevent or minimize DC Offset voltages. Note: P506, 507, 524, and 552 are only active in Sensorless Vector and Custom V/Hz modes of operation, and therefore require modification when in Sensorless Vector control mode. In order for the drive s current regulator to tolerate the charging currents of the Sine wave filter branch circuit, you must modify some hidden parameters affecting the vector algorithm and sensitivity of the current regulator. See Hidden Parameters Overview on page 5 for more information. Hidden Parameters Overview Some of the parameters necessary to configure the drive for use with a Sine wave filter are hidden from view via the drive s Human Interface Module (HIM). These parameters rarely need to be changed, and for most drive operations, Rockwell Automation recommends that these parameters are not changed. But for rare cases, such as for use with a Sine wave filter, it is necessary to access and configure the hidden parameters via software tools such as DriveExecutive (see Figure 1 and Figure 2 on page 6), or DriveExplorer, communicating through the drive s Device Peripheral Interface (DPI) ports or Ethernet. The hidden parameters are part of the 500 group of parameters under the first menu folder. See Hidden Parameters for Use With Sine Wave Filter on page 7) for the specific parameters that can be changed. Change only the hidden parameters for Sine wave filters shown on page 4 and page 7. All other hidden parameters must not be altered. 1. Access the hidden parameters via the drive HIM, and set parameter 196 [Param Access Lvl] to 2 - Reserved (see Figure 1 on page 6). 2. Configure the hidden parameters to optimize operation of the drive with the Sine wave filter (see Hidden Parameters for Use With Sine Wave Filter on page 7). Rockwell Automation Publication PFLEX-AT002A-EN-P - May

6 Figure 1 - DriveExecutive Parameter List, Parameter Access Level Figure 2 - DriveExecutive Linear List 6 Rockwell Automation Publication PFLEX-AT002A-EN-P - May 2011

7 Hidden Parameters for Use With Sine Wave Filter ATTENTION: To guard against unstable or unpredictable operation, the following parameters must only be changed by qualified service personnel. File Diag-Motor Cntl Group UTILITY Diag-Vector Cntl Diag-DACs No. Parameter Name & Description 508 [Stability Filter] Values The Stability Filter coefficient is used to adjust the Min/Max: bandwidth of a low pass filter. The smaller the value of this coefficient, the lower the bandwidth of the filter. 509 [Lo Freq Reg KpId] This proportional gain adjusts the output voltage at very low frequency in response to the reactive, or d- axis, motor current. A larger value increases the output voltage change. 510 [Lo Freq Reg KpIq] The proportional gain adjusts the output voltage at very low frequency in response to the active, or q- axis, motor current. A larger value increases the output voltage change. 511 [Ki Cur Reg] This integral gain adjusts the output voltage in response to the q and d axis motor currents. A larger value increases the output voltage change. Min/Max: Min/Max: Min/Max: 512 [Kp Cur Reg] This proportional gain adjusts the output voltage in Min/Max: response to the q and d axis motor currents. A larger value increases the output voltage change. 523 [Bus Utilization] This value sets the drive output voltage limit as a percentage of the fundamental output voltage when operating in 6 step mode. Values above 95% increase harmonic content and jeopardize control stability. This output voltage limit is strictly a function of input line and resulting bus voltage. 524 [PWM Type Sel] Min/Max: Allows selection of the active PWM type. A value of 0 Min/Max: is default, and results in a change of PWM method at approximately 2/3 of rated motor frequency. If this is unacceptable for harmonic or audible reasons, a value of 1 disables the change. 525 [Torq Adapt Speed] Selects the operating frequency/speed at which the adaptive torque control regulators become active as a percent of motor nameplate frequency. 549 Flux Braking % (% of normal output voltage) Gain adjustment for Flux Braking mode. 550 Ki Flying Start Integral gaing for Flying Start mode. 551 Ki DC Brake Integral gain for DC Braking mode. 552 Dead Time Comp Voltage compensation for off time between PWM switching events. Min/Max: / / / / / % 85.0/100.0% 0.1% 0 0/ % 0.0/100.0% 0.1% 175 Min/Max: 100/250 % 150 Min/Max: 20/ Min/Max: 0/ Min/Max: 50/100 % PF 70 PF 700 PF700H Rockwell Automation Publication PFLEX-AT002A-EN-P - May

8 PowerFlex 753/755 Parameter Settings for Use With Sine Wave Filters Parameter Name Default Setting Set To P035 Motor Cntl Mode 0 (Sensrls Vect) 2 (Custom V/Hz) P038 PWM Frequency 2 or 4 khz see filter instructions P040 Mtr Options Cfg Bit 5 - Reflect Wave 1 (enabled) 0 (disabled) Bit 8 - AsyncPwmLock 0 (disabled) 1 (enabled) Bit 9 - PWM Freq Lock 0 (disabled) 1 (enabled) Bit 11 - Elec Stab 1 (enabled) 0 (disabled) (Angl Stability Gain Off) (Volt Stability Gain Off) Bit 12 - Xsistor Diag 1 (enabled) 0 (disabled) P043 Flux Up Mode 1 (automatic) 0 (manual) P044 Flux Up Time frame-dependent sec P420 Drive OL Mode 3 (both-pwm 1st) 1 (reduce CLim) Do not autotune. Below is list of operational theory that describes why the parameter settings are used. Motor control mode (P035) needs to be V/Hz because, with the filter between the drive and motor, the load no longer looks like a motor to the drive. Therefore, the drive needs to operate in a simple V/Hz mode. Reflected wave (P040, Bit 5) is turned off so that there will be no missing pulses in the output voltage waveform, and to minimize any offsets that could appear. AsyncPwmLock (P040, Bit 8) is on because the filter is tuned to the carrier frequency, and if the carrier frequency were to change, the filter would not work, so the carrier must be fixed. Also, the pulse width modulation (PWM) frequency needs to be set for whatever the filter is tuned to: either 2 or 4 khz. Elec Stab (P040, Bit 11): This bit affects Angle stability and Voltage stability. Angle stability gain and Voltage stability gain are set for 0 so they do not try to compensate for the currents they see going into the filter's capacitors. Transistor diagnostics (P040, Bit 12) is turned off because the sequence of turning transistors on and off charges the capacitors in the filter and can cause an instantaneous over-current (IOC) trip. Drive OL mode (P420) is set for reduce current limit, and not the PWM frequency, for the same reason as AsyncPwmLock. Note: Modulation mode is left at default space vector, since 2-phase modulation would degrade the filter's performance (P040, Bit 7). 8 Rockwell Automation Publication PFLEX-AT002A-EN-P - May 2011

9 PowerFlex 753/755 Parameter Settings for Use With dv/dt Filters Parameter Name Default Setting Set To P035 Motor Cntl Mode 0 (Sensrls Vect) V/hz, SVC, or FVC P038 PWM Frequency 2 or 4 khz see filter instructions P040 Mtr Options Cfg Bit 5 - Reflect Wave 1 (enabled) 0 (disabled) Bit 8 - AsyncPwmLock 0 (disabled) 1 (enabled) Bit 9 - PWM Freq Lock 0 (disabled) 1 (enabled) Bit 11 - Elec Stab 1 (enabled) 0 (disabled) (Angl Stability Gain Off) (Volt Stability Gain Off) Bit 12 - Xsistor Diag 1 (enabled) 0 (disabled) P043 Flux Up Mode 1 (automatic) 0 (manual) P044 Flux Up Time frame-dependent sec P420 Drive OL Mode 3 (both-pwm 1st) 1 (reduce CLim) Do not autotune. Below is list of operational theory that describes why the parameter settings are used. Motor control mode (P035) can be V/Hz, Sensorless Vector Control (SVC), or Flux Vector Control (FVC). Reflected wave (P040, Bit 5) is turned off so that there will be no missing pulses in the output voltage waveform, and to minimize any offsets that could appear. AsyncPwmLock (P040, Bit 8) is on because the filter is tuned to the carrier frequency, and if the carrier frequency were to change, the filter would not work, so the carrier must be fixed. Also, the pulse width modulation (PWM) frequency needs to be set for whatever the filter is tuned to: either 2 or 4 khz. Elec Stab(P040, Bit 11): This bit affects Angle stability and Voltage stability. Angle stability gain and Voltage stability gain are set for 0 so they do not try to compensate for the currents they see going into the filter's capacitors. Transistor diagnostics (P040, Bit 12) is turned off because the sequence of turning transistors on and off charges the capacitors in the filter and can cause an instantaneous over-current (IOC) trip. Drive OL mode (P420) is set for reduce current limit, and not the PWM frequency, for the same reason as AsyncPwmLock. Note: Modulation mode is left at default space vector, since 2-phase modulation would degrade the filter's performance (P040, Bit 7). Rockwell Automation Publication PFLEX-AT002A-EN-P - May

10 PowerFlex 753/755 Parameter Settings for Use With Adjustable Voltage Application Parameter Name Default Setting Set To P035 Motor Cntl Mode 0 (Sensrls Vect) 9 (Adj Voltage) P038 PWM Frequency 2 or 4 khz see filter instructions P040 Mtr Options Cfg Bit 5 - Reflect Wave 1 (enabled) 0 (disabled) Bit 8 - AsyncPwmLock 0 (disabled) 1 (enabled) Bit 9 - PWM Freq Lock 0 (disabled) 1 (enabled) Bit 11 - Elec Stab 1 (enabled) 0 (disabled) (Angl Stability Gain Off) (Volt Stability Gain Off) Bit 12 - Xsistor Diag 1 (enabled) 0 (disabled) P043 Flux Up Mode 1 (automatic) 0 (manual) P044 Flux Up Time frame-dependent sec P060 Start/Acc Boost frame-dependent 0 P061 Run Boost frame-dependent 0 P062 Break Voltage frame-dependent 0 P063 Break Frequency frame-dependent 0 P420 Drive OL Mode 3 (both-pwm 1st) 1 (reduce CLim) Basic Adjustable Voltage Control Parameters P1131 Adj Vltg Config 1 1 = 3-Phase 0 = 1-Phase P1133 Adj Vltg Select Disabled Preset 1 P1134 Adj Vltg Ref High 0% 100% P1140 Adj Vltg AccTime 0 Secs Required Secs P1141 Adj Vltg DecTime 0 Secs Required Secs P1142 Adj Vltg Preset1 0 VAC Required VAC P1153 Dead Time Comp 100% Vary from 100% to 0% Do not autotune. Below is list of operational theory that describes why the parameter settings are used. The motor control mode (P035) Adjustable Voltage mode is typically a non-motor load control function providing an independent output voltage with an independent output frequency. Break voltage (P062), break frequency (P063), start boost (P060), and run boost (P061) can cause DC offsets in Adjustable Voltage mode. Reflected wave (P040, Bit 5) is turned off so that there will be no missing pulses in the output voltage waveform, and to minimize any offsets that could appear. AsyncPwmLock (P040, Bit 8) is on because the filter is tuned to the carrier frequency, and if the carrier frequency were to change, the filter would not work, so the carrier must be fixed. Also, the pulse width modulation (PWM) frequency needs to be set for whatever the filter is tuned to: either 2 or 4k Hz. 10 Rockwell Automation Publication PFLEX-AT002A-EN-P - May 2011

11 Elec Stab (P040, Bit 11): This bit affects Angle stability and Voltage stability. Angle stability gain and Voltage stability gain are set for 0 so they do not try to compensate for the currents they see going into the filter's capacitors. Transistor diagnostics (P040, Bit 12) is turned off because the sequence of turning transistors on and off charges the capacitors in the filter and can cause an instantaneous over-current (IOC) trip. Drive OL mode (P420) is set for reduce current limit, and not the PWM frequency, for the same reason as AsyncPwmLock. Note: Dead Time Comp (P1153) is best set to 0% when output of the Sine wave filter is fed into a transformer, to prevent or minimize DC Offset voltages. Note: Modulation mode is left at default space vector, since 2-phase modulation would degrade the filter's performance (P040, Bit 7). Rockwell Automation Publication PFLEX-AT002A-EN-P - May

12 U.S. Allen-Bradley Drives Technical Support - Tel: (1) , Fax: (1) , support@drives.ra.rockwell.com, Online: Power, Control and Information Solutions Headquarters Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI USA, Tel: (1) , Fax: (1) Europe/Middle East/Africa: Rockwell Automation, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) , Fax: (32) Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) , Fax: (852) Publication PFLEX-AT002A-EN-P May 2011 Copyright 2011 Rockwell Automation, Inc. All rights reserved. Printed in USA.

GV3000 AC General Purpose (Volts/Hertz) and Vector Duty Drive

GV3000 AC General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual D2-3339-1 GV3000 AC General Purpose (Volts/Hertz) and Vector Duty Drive Version 5.0 Important User Information Solid-state equipment has operational characteristics

More information

GV3000/SE AC Drive HP, 460V AC

GV3000/SE AC Drive HP, 460V AC Hardware Reference, Installation, and Troubleshooting Manual D2-3392-7 GV3000/SE AC Drive 30-200 HP, 460V AC Version 6.07 Important User Information Solid-state equipment has operational characteristics

More information

1336 PLUS II Custom Firmware

1336 PLUS II Custom Firmware Instructions 1336 PLUS II Custom Firmware EN921 - Variable Voltage w/ PI Power/Current Control! ATTENTION: This Custom Firmware has been designed for a specific application and differs from the standard

More information

PowerFlex 400 AC Drive Guide Specification

PowerFlex 400 AC Drive Guide Specification PowerFlex 400 AC Drive Guide Specification Adjustable Frequency Drives 3.0 50HP @ 200 to 240V AC 3.0 350HP @ 380 to 480V AC PART 1 GENERAL 1.01 Quality Assurance A. The manufacturer shall have minimum

More information

Harmonic Mitigation Harmonic Data Comparisons

Harmonic Mitigation Harmonic Data Comparisons Harmonic Data Comparisons 1336 PLUS, 1336 PLUS II, 1336 IMPACT and 1336 FORCE AC Drives with 6-Pulse, 12-Pulse, and 18-Pulse Front-Ends Topologies 6-Pulse drive 12-Pulse drive 18-Pulse drive Harmonic Spectrum

More information

160 Series C Custom Firmware

160 Series C Custom Firmware Instructions 160 Series C Custom Firmware S02 Option FRN 7.06 C004 Introduction The S02 option extends the kw/hp ratings of the standard 160 drive. In addition, the following function changes have been

More information

PowerFlex 400 Submittal

PowerFlex 400 Submittal PowerFlex 400 Submittal Submittal Date: Project Name: Project Location: Consulting Engineer: Contractor: Contractor PO #: Distributor Name: Distributor Contact: Distributor Reference #: Note: This is general

More information

For additional PowerFlex 4 and 40 data and general drive information, refer to the following publications:

For additional PowerFlex 4 and 40 data and general drive information, refer to the following publications: Product Overview Providing users with powerful motor speed control in a compact, space saving design, the Allen-Bradley PowerFlex 4 and 40 AC drives are the smallest and most cost-effective members of

More information

ECET 211 Electric Machines & Controls Lecture 9-1 Adjustable-Speed Drives and PLC Installations (1 of 2)

ECET 211 Electric Machines & Controls Lecture 9-1 Adjustable-Speed Drives and PLC Installations (1 of 2) ECET 211 Electric Machines & Controls Lecture 9-1 Adjustable-Speed Drives (1 of 2) Text Book: Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015. Paul I-Hai Lin,

More information

HPVFP High Performance Full Function Vector Frequency Inverter

HPVFP High Performance Full Function Vector Frequency Inverter Advanced User Manual HPVFP High Performance Full Function Vector Frequency Inverter HP VER 1.00 1. HPVFP Parameter Set Overview...3 1.1. About this section...3 1.2. Parameter Structure Overview...3 1.3.

More information

Reliability Starts Here. PowerFlex TM 7000 Family of MV Drives

Reliability Starts Here. PowerFlex TM 7000 Family of MV Drives Reliability Starts Here. PowerFlex TM 7000 Family of MV Drives PowerFlex TM 7000 Your success depends on it. Superior Evolution As products evolve and technology advances, our customers demand drives that

More information

Using a Combination Sensor with the XM-360 Module

Using a Combination Sensor with the XM-360 Module Application Technique Using a Combination Sensor with the XM-360 Module This Application Technique describes how to wire and configure a sensor with combined temperature and acceleration measurement capability

More information

vacon nxp arfiff30 user manual generator application ac drives

vacon nxp arfiff30 user manual generator application ac drives vacon nxp ac drives arfiff30 generator application user manual vacon 1 Vacon Generator application INDEX Document code: DPD01916A Software code: ARFIFF30V073 Date: 15.11.2016 VACON GENERATOR APPLICATION...

More information

Figure 1 Typical Inverter Block Diagram

Figure 1 Typical Inverter Block Diagram AC Drives and Soft Starter Application Guide Walter J Lukitsch PE, Gary Woltersdorf Jeff Theisen, John Streicher Allen-Bradley Company Milwaukee, WI Abstract: There are usually several choices for starting

More information

NPTEL

NPTEL NPTEL Syllabus Pulse width Modulation for Power Electronic Converters - Video course COURSE OUTLINE Converter topologies for AC/DC and DC/AC power conversion, overview of applications of voltage source

More information

ADJUSTABLE SPEED DRIVES VF-S11 Sords Electric

ADJUSTABLE SPEED DRIVES VF-S11 Sords Electric ADJUSTABLE SPEED DRIVES VF-S11 The Next Generation of Micro Inverters is Here. The S11 provides maximum torque with precise speed control. It features an easy-to-use, quiet and compact design. In addition,

More information

E3 Adjustable Speed Drive Engineering Specification

E3 Adjustable Speed Drive Engineering Specification E3 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba E3 AC Variable Frequency Drives, 6 pulse for 230V and 460V. 1.1 References A. National

More information

A Subsidiary of Regal-Beloit Corporation. AC Inverter Terminology

A Subsidiary of Regal-Beloit Corporation. AC Inverter Terminology AP200-9/01 Acceleration The rate of change in velocity as a function of time. Acceleration usually refers to increasing velocity and deceleration to decreasing velocity. Acceleration Boost During acceleration,

More information

AC Drives and Soft Starter Application Guide

AC Drives and Soft Starter Application Guide Feature AC Drives and Soft Starter Application Guide by Walter J Lukitsch PE, Gary Woltersdorf Jeff Theisen, and John Streicher Allen-Bradley Company Abstract: There are usually several choices for starting

More information

Allen-Bradley. Using the 1756-MO2AE with the AEC (Cat. No ) Application Note

Allen-Bradley. Using the 1756-MO2AE with the AEC (Cat. No ) Application Note Allen-Bradley Using the 1756-MO2AE with the AEC (Cat. No. 4100-2.7) Application Note Important User Information Because of the variety of uses for the products described in this publication, those responsible

More information

ADJUSTABLE SPEED DRIVES. AS1 Drive

ADJUSTABLE SPEED DRIVES. AS1 Drive ADJUSTABLE SPEED DRIVES AS1 Drive Toshiba s New ASD Product Line The AS1 drive builds on Toshiba s history of supplying powerful, reliable, and versatile drives. We have combined our best drive features

More information

Frequently Asked Questions (FAQs) MV1000 Drive

Frequently Asked Questions (FAQs) MV1000 Drive QUESTION 1. What is a conventional PWM Inverter? 2. What is a medium voltage inverter? 3. Are all MV inverters Voltage Source (VSI) design? 4. What is a Current Source Inverter (CSI)? 5. What output power

More information

SWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

SWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) SWF DV/DT Solutions Sinewave Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Does your application use variable frequency drives for improved

More information

VS-616G5 Series (Revision F) Programming Manual. Constant Torque Inverter with Adaptive Vector Control (AVC )

VS-616G5 Series (Revision F) Programming Manual. Constant Torque Inverter with Adaptive Vector Control (AVC ) VS-616G5 Series (Revision F) Programming Manual Constant Torque Inverter with Adaptive Control (AVC ) ! WARNING PRECAUTIONS NOTICE 1) Only turn ON the input power supply after replacing the front cover.

More information

GS1 Parameter Summary Detailed Parameter Listings...4 9

GS1 Parameter Summary Detailed Parameter Listings...4 9 CHAPTER AC DRIVE 4 PARAMETERS Contents of this Chapter... GS1 Parameter Summary...............................4 2 Detailed Parameter Listings..............................4 9 Motor Parameters.........................................4

More information

Application Techniques. PowerFlex 700S and PowerFlex 755 Drives Tuning

Application Techniques. PowerFlex 700S and PowerFlex 755 Drives Tuning Application Techniques PowerFlex 700S and PowerFlex 755 Drives Tuning Important User Information Read this document and the documents listed in the additional resources section about installation, configuration,

More information

PowerFlex 755T Flux Vector Tuning

PowerFlex 755T Flux Vector Tuning Application Technique Original Instructions PowerFlex 755T Flux Vector Tuning Catalog Number 20G; 20J Important User Information Read this document and the documents listed in the additional resources

More information

S11 Adjustable Speed Drive Engineering Specification

S11 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba S11 AC Variable Frequency Drives, 6 pulse for 3- phase 200-240VAC, 380-500VAC and single phase 200V to 240VAC. 1.1 References A. National

More information

MTY (81)

MTY (81) This manual describes the option "d" of the SMT-BD1 amplifier: Master/slave electronic gearing. The general information about the digital amplifier commissioning are described in the standard SMT-BD1 manual.

More information

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation Variable Frequency Drive Packages with Harmonic Mitigation Low Harmonic Drive Packages Engineered by Rockwell Automation What Do I Need to know About Harmonics? What are Harmonics? Harmonics are deviations

More information

S100A40AC SERIES BRUSHLESS SERVO AMPLIFIERS Model: S100A40AC

S100A40AC SERIES BRUSHLESS SERVO AMPLIFIERS Model: S100A40AC S100A-AC Series S100A40AC SERIES BRUSHLESS SERVO AMPLIFIERS Model: S100A40AC FEATURES: Surface-mount technology Small size, low cost, ease of use Optical isolation, see block diagram Sinusoidal drive and

More information

1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control.

1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control. Section 16680 VARIABLE SPEED DRIVE SYSTEMS OR AFD Part I - GENERAL I.01 Description A. This specification is to cover a complete adjustable frequency motor drive consisting of a pulse width modulated (PWM)

More information

AF91 Adjustable Frequency Drives Series B

AF91 Adjustable Frequency Drives Series B Effective: January, 00 Page New Information AF9 Adjustable Model AF9 Description Model AF9 Adjustable Frequency AC Drives are designed to provide adjustable speed control of -phase motors. These microprocessor-based

More information

Application Note. Applicable Product: AC Drives

Application Note. Applicable Product: AC Drives Application Note Application Note Guidelines For The Use Of 400-600 Volt AC Drives In Medium Voltage Applications Applicable Product: AC Drives 4kV Step-down Transformer AC Drive 400-600V Output Filter

More information

PowerFlex DC Field Controller

PowerFlex DC Field Controller Programming Manual Original Instructions PowerFlex DC Field Controller Catalog Number 23PFC Important User Information Read this document and the documents listed in the additional resources section about

More information

Drives 101 Lesson 3. Parts of a Variable Frequency Drive (VFD)

Drives 101 Lesson 3. Parts of a Variable Frequency Drive (VFD) Drives 101 Lesson 3 Parts of a Variable Frequency Drive (VFD) This lesson covers the parts that make up the Variable Frequency Drive (VFD) and describes the basic operation of each part. Here is the basics

More information

ADJUSTABLE SPEED DRIVES. HX7 Series. 18-Pulse

ADJUSTABLE SPEED DRIVES. HX7 Series. 18-Pulse ADJUSTABLE SPEED DRIVES HX7 Series 18-Pulse Toshiba HX7 In some industrial applications, users need reliable and efficient adjustable speed drives that do not contribute significant harmonic distortion

More information

CHAPTER AC DRIVE PARAMETERS. In This Chapter...

CHAPTER AC DRIVE PARAMETERS. In This Chapter... CHAPTER AC DRIVE 4 PARAMETERS In This Chapter... GS2 Parameter Summary....................4 2 Detailed Parameter Listings.................4 11 Motor Parameters........................4 11 Ramp Parameters.........................4

More information

Variable Frequency Drive / Inverter (0.4 ~ 280kW)

Variable Frequency Drive / Inverter (0.4 ~ 280kW) Variable Frequency Drive / Inverter (0.4 ~ 280kW) & Standard Features Configuration Comparison Comparison Table Enclosure IP00 IP20 NEMA 1 Rating Single phase 0.4 2.2kW 0.4 1.5kW Three phase 0.4 4kW Constant

More information

1715 Redundant I/O System Specifications

1715 Redundant I/O System Specifications Technical Data 1715 Redundant I/O System Specifications System Module Catalog Numbers 1715-AENTR, 1715-IB16D, 1715-OB8DE,1715-IF16, 1715-OF8I Base Unit Catalog Numbers 1715-A2A, 1715-A3IO Termination Assembly

More information

Multimeter 500CVD21 RTU500 series

Multimeter 500CVD21 RTU500 series Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase

More information

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Riya Philip 1, Reshmi V 2 Department of Electrical and Electronics, Amal Jyothi College of Engineering, Koovapally, India 1,

More information

HIGH PERFORMANCE CONTROL OF AC DRIVES WITH MATLAB/SIMULINK MODELS

HIGH PERFORMANCE CONTROL OF AC DRIVES WITH MATLAB/SIMULINK MODELS HIGH PERFORMANCE CONTROL OF AC DRIVES WITH MATLAB/SIMULINK MODELS Haitham Abu-Rub Texas A&M University at Qatar, Qatar Atif Iqbal Qatar University, Qatar and Aligarh Muslim University, India Jaroslaw Guzinski

More information

General Purpose Drives

General Purpose Drives AC Variable Speed Drive General Purpose Drives Dedicated to Low Power Applications 0.37kW 11kW / 0.5HP 15HP 200 480V 3 Phase Input AC Variable Speed Drive 0.37kW 11kW / 0.5HP 15HP 110 480V Single & 3 Phase

More information

Bulletin 1402 Line Synchronization Module (LSM)

Bulletin 1402 Line Synchronization Module (LSM) Bulletin 1402 (LSM) Application Notes Table of Contents What is Synchronization?...................................... 2 Synchronization............................................. 3 1771 Modules and

More information

VF-nC1 Adjustable Speed Drive Engineering Specification

VF-nC1 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba VF-nC1 AC Variable Frequency Drives, 6 pulse for 100V single-phase 0.1 to 0.75kW, 200V single-phase 0.2 to 2.2kW and 200V threephase 0.1

More information

ECET Industrial Motor Control. Variable Frequency Drives. Electronic Motor Drives

ECET Industrial Motor Control. Variable Frequency Drives. Electronic Motor Drives ECET 4530 Industrial Motor Control Variable Frequency Drives Electronic Motor Drives Electronic motor drives are devices that control the speed, torque and/or rotational direction of electric motors. Electronic

More information

P-SERIES VFD 1-40HP (200~230VAC), 1-400HP (380~480VAC),3Ø Dual Rated for Constant & Variable Torque Integrated PID Control

P-SERIES VFD 1-40HP (200~230VAC), 1-400HP (380~480VAC),3Ø Dual Rated for Constant & Variable Torque Integrated PID Control P-SERIES VFD 1-40HP (200~230VAC), 1-400HP (380~480VAC),3Ø Dual Rated for Constant & Variable Torque Integrated PID Control NEW FIRMWARE MAKES SETUP A SNAP Application based commissioning allows parameters

More information

A New Family of Matrix Converters

A New Family of Matrix Converters A New Family of Matrix Converters R. W. Erickson and O. A. Al-Naseem Colorado Power Electronics Center University of Colorado Boulder, CO 80309-0425, USA rwe@colorado.edu Abstract A new family of matrix

More information

FUJI Inverter. Standard Specifications

FUJI Inverter. Standard Specifications FUJI Inverter o Standard Specifications Norminal applied motor The rated output of a general-purpose motor, stated in kw. That is used as a standard motor. Rated capacity The rating of an output capacity,

More information

Harmonics White Paper

Harmonics White Paper Harmonics White Paper New Breakthrough In PWM Drives Technology Reduces Input Line Harmonics Without the Use of Filtering Devices Harmonic Distortion Damages Equipment and Creates a Host of Other Problems

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE 98 CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE 6.1 INTRODUCTION Process industries use wide range of variable speed motor drives, air conditioning plants, uninterrupted power supply systems

More information

TMdrive -XL Series Family Product Application Guide. solar inverters. power generation

TMdrive -XL Series Family Product Application Guide. solar inverters. power generation TMdrive -XL Series Family Product Application Guide metals cranes mining testing oil & gas solar inverters power generation cement TMdrive-XL Series 8 MVA 15 MVA 20 MVA 30 MVA The TMdrive XL series family

More information

Application Note of RingCore210 Family. (Optimized Vibration Driver) V1.3 May, 2011

Application Note of RingCore210 Family. (Optimized Vibration Driver) V1.3 May, 2011 RingCore Family Application Note #54 (AN54-V1.3) Application Note of RingCore210 Family (Optimized Vibration Driver) V1.3 May, 2011 CORERIVER Semiconductor reserves the right to make corrections, modifications,

More information

Inverter Drive /Vector Drive Motors & Controls

Inverter Drive /Vector Drive Motors & Controls H2 Inverter/ Encoderless Vector Inverter Drive /Vector Drive & Controls 3/4 thru 50 180-264 VAC 3 Phase - 50/60 Hz 3/4 thru 60 340-528 VAC 3 Phase - 50/60 Hz 3/4 thru 60 515-660 VAC 3 Phase - 60 Hz HVAC

More information

Copyright 2014 YASKAWA ELECTRIC CORPORATION All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or

Copyright 2014 YASKAWA ELECTRIC CORPORATION All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or Copyright 2014 YASKAWA ELECTRIC CORPORATION All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic,

More information

Advanced user guide. Commander SX. IP66/Nema 4X AC Variable Speed Drive en / a. Part Number :

Advanced user guide. Commander SX. IP66/Nema 4X AC Variable Speed Drive en / a. Part Number : Advanced user guide Commander SX IP66/Nema 4X AC Variable Speed Drive Part Number : NOTE CONTROL TECHNIQUES reserves the right to modify the characteristics of its products at any time in order to incorporate

More information

NGS N01 LIMESTONE CRUSHER ELECTRICAL SPECIFICATIONS

NGS N01 LIMESTONE CRUSHER ELECTRICAL SPECIFICATIONS NGS N01 LIMESTONE CRUSHER ELECTRICAL SPECIFICATIONS PART 1 - GENERAL 1.0 Scope This specification shall cover the procurement, installation and factory startup (constant torque application of one VFD controlling

More information

MTY (81)

MTY (81) This manual describes the option "e" of the SMT-BD1 amplifier: Master/slave tension control application. The general information about the digital amplifier commissioning are described in the standard

More information

EE POWER ELECTRONICS UNIT IV INVERTERS

EE POWER ELECTRONICS UNIT IV INVERTERS EE6503 - POWER ELECTRONICS UNIT IV INVERTERS PART- A 1. Define harmonic distortion factor? (N/D15) Harmonic distortion factor is the harmonic voltage to the fundamental voltage. 2. What is CSI? (N/D12)

More information

A NOVEL APPROACH TOWARDS SIX-STEP OPERATION IN OVERMODULATION REGION IN SVPWM VSI

A NOVEL APPROACH TOWARDS SIX-STEP OPERATION IN OVERMODULATION REGION IN SVPWM VSI A NOVEL APPROACH TOWARDS SIX-STEP OPERATION IN OVERMODULATION REGION IN SVPWM VSI Anurag Tripathi 1, Bharti Dwivedi 1 and Dinesh Chandra 2 1 Department of Electrical Engineering, Institute of Engineering

More information

AV-300i Specifications. GE Industrial Systems. Product Specifications. A New Concept in Automation. AV-300i

AV-300i Specifications. GE Industrial Systems. Product Specifications. A New Concept in Automation. AV-300i GE Industrial Systems Product Specifications AV-300i A New Concept in Automation. TM 1 General Item Description Nominal Motor 230V, 3 Phase 15 Hp to 100 Hp 460V, 3 Phase 3/4 Hp to 200 Hp Enclosure, Standard

More information

8510 AC Spindle Drive System

8510 AC Spindle Drive System 8510 AC Spindle Drive System Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application,

More information

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company P2 Power Solutions Pvt. Ltd. An ISO 9001:2008 Company Quality Power within your Reach P2 Power Magnetics P2 Power Solutions Pvt. Ltd. P2 Power Solutions Pvt. Ltd. provides EMC and power quality solutions,

More information

TDE MACNO Spa. AC&DC Drives, Servos and Drive System. AFE converters for Renewable Energies Regenerative (active) power supply (Active Front End)

TDE MACNO Spa. AC&DC Drives, Servos and Drive System. AFE converters for Renewable Energies Regenerative (active) power supply (Active Front End) TDE MACNO Spa AC&DC Drives, Servos and Drive System AFE converters for Renewable Energies Regenerative (active) power supply (Active Front End) Automation and Control Systems OPENDRIVE EXP MINI OPENDRIVE

More information

Load Observer and Tuning Basics

Load Observer and Tuning Basics Load Observer and Tuning Basics Feature Use & Benefits Mark Zessin Motion Solution Architect Rockwell Automation PUBLIC INFORMATION Rev 5058-CO900E Questions Addressed Why is Motion System Tuning Necessary?

More information

DSAE - AAA - B - C - DD - E AAA

DSAE - AAA - B - C - DD - E AAA Pag. 4 GENERALITY The four quadrant converters of the DSAE 150/300 series integrate both the power supply unit and the braking unit and have been realised to exploit the most advanced technology, in particular

More information

U1881A and U1882A Power Measurement Application for InfiniiVision and Infiniium Oscilloscopes

U1881A and U1882A Power Measurement Application for InfiniiVision and Infiniium Oscilloscopes U1881A and U1882A Power Measurement Application for InfiniiVision and Infiniium Oscilloscopes Data Sheet Fast, automatic and reliable characterization of switching mode power devices Today s power supply

More information

[ 4 ] Using pulse train input (F01 = 12)

[ 4 ] Using pulse train input (F01 = 12) [ 4 ] Using pulse train input (F01 = 12) Selecting the pulse train input format (d59) A pulse train in the format selected by the function code d59 can give a frequency command to the inverter. Three types

More information

VFS9 Parameter List for Version110 or later

VFS9 Parameter List for Version110 or later VFS9 Parameter List for Version110 or later Setting Date Customer End user Application Application /Serial Inverter s Type-Form Quantity Inverter s Serial Motor s capacity If user s value is same as shipping

More information

Manual. ihss57-xx. Integrate Stepper Servo Motor.

Manual. ihss57-xx. Integrate Stepper Servo Motor. ihss57-xx Integrate Stepper Servo Motor Manual Shenzhen Just Motion Control Electro-mechanics Co., Ltd TEL:+86-0755-26509689 FAX:+86-0755-26509289 www.jmc-motion.com Email:jmk@jmc-motion.com Address: Floor2,

More information

POWER- SWITCHING CONVERTERS Medium and High Power

POWER- SWITCHING CONVERTERS Medium and High Power POWER- SWITCHING CONVERTERS Medium and High Power By Dorin O. Neacsu Taylor &. Francis Taylor & Francis Group Boca Raton London New York CRC is an imprint of the Taylor & Francis Group, an informa business

More information

user's manual nx frequency converters beam pump application asfiff13

user's manual nx frequency converters beam pump application asfiff13 user's manual nx frequency converters beam pump application asfiff13 2 vacon Introduction INDEX 1. Introduction... 3 2. Commissioning... 4 2.1 Commissioning unbalanced load... 4 2.2 Commissioning balanced

More information

VARIABLE FREQUENCY DRIVE

VARIABLE FREQUENCY DRIVE VARIABLE FREQUENCY DRIVE Yatindra Lohomi 1, Nishank Nama 2, Umesh Kumar 3, Nosheen aara 4, Uday Raj 5 (Assistant Professor in Department of Electrical Engineering GIET Kota2) (Department of Electrical

More information

BOSTON GEAR CONTROLLERS. ACE 20 Series 1/8 through 10 HP Adjustable Frequency AC Motor Controllers. MTY (81)

BOSTON GEAR CONTROLLERS. ACE 20 Series 1/8 through 10 HP Adjustable Frequency AC Motor Controllers. MTY (81) BOSTON GEAR CONTROLLERS ACE 20 Series 1/8 through 10 HP Adjustable Frequency AC Motor Controllers ACE 20 Series Offering full-featured control in high torque, low speed applications from 1/8 to 10 HP,

More information

3KDVH 6LQH *HQHUDWRU ZLWK 9DULDEOH3KDVH&RQWURO

3KDVH 6LQH *HQHUDWRU ZLWK 9DULDEOH3KDVH&RQWURO Digital Motor Control Library 3KDVH 6LQH *HQHUDWRU ZLWK 9DULDEOH3KDVH&RQWURO Component Name: 2-Phase Sine Generator with Variable Phase Control 2-Phase Sine Generator with Variable Phase Control 0 Inputs

More information

High Frequency Sinewave Guardian TM Filter

High Frequency Sinewave Guardian TM Filter High Frequency Sinewave Guardian TM Filter 380V 480V TECHNICAL REFERENCE MANUAL FORM: SHF-TRM-E REL. April 2015 REV. 001 2015 MTE Corporation Caution Prior to start up; confirm the drive operation mode

More information

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing.

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing. 1.0 Scope This document describes the specification for Toshiba 1000 Series On-Line Uninterruptible Power System (UPS). The UPS will supply a computer grade AC output sine wave which is unaffected by the

More information

SV9000 SVReady USER MANUAL CONTENTS OPEN SV9000 USER MANUAL. SV9000 Page 0-1

SV9000 SVReady USER MANUAL CONTENTS OPEN SV9000 USER MANUAL. SV9000 Page 0-1 SV9000 Page 0-1 SV9000 SVReady USER MANUAL CNTENTS A General...0-2 B Application selection...0-2 C Restoring default values of application parameters...0-2 D Language selection...0-2 1 Standard Control

More information

ADJUSTABLE SPEED DRIVES. W7 Series. 18 Pulse

ADJUSTABLE SPEED DRIVES. W7 Series. 18 Pulse ADJUSTABLE SPEED DRIVES W7 Series 18 Pulse Meets or Exceeds Your Specifications Standard Specifications Item Voltage Class 460V Maximum HP 60 75 100 125 150 200 250 300 400 500 600 700 800 Drive Rating

More information

Datasheet SHF D Synthesized Clock Generator

Datasheet SHF D Synthesized Clock Generator SHF Communication Technologies AG Wilhelm-von-Siemens-Str. 23D 12277 Berlin Germany Phone +49 30 772051-0 Fax +49 30 7531078 E-Mail: sales@shf.de Web: http://www.shf.de Datasheet SHF 78210 D Synthesized

More information

5500A. Multi-Product Calibrator. Extended Specifications 2005

5500A. Multi-Product Calibrator. Extended Specifications 2005 5500A Multi-Product Calibrator Extended Specifications 2005 5500A Specifications The following paragraphs detail specifications for the 5500A Calibrator. The specifications are valid after allowing a warm-up

More information

INSTRUCTIONS YASKAWA. Upon receipt of the product and prior to initial operation, read these instructions thoroughly, and retain for future reference.

INSTRUCTIONS YASKAWA. Upon receipt of the product and prior to initial operation, read these instructions thoroughly, and retain for future reference. YASKAWA DUAL ENCODER (PG) FEEDBACK CARD (PG-Z) INSTRUCTIONS Upon receipt of the product and prior to initial operation, read these instructions thoroughly, and retain for future reference. Package Contents:

More information

Selected Problems of Induction Motor Drives with Voltage Inverter and Inverter Output Filters

Selected Problems of Induction Motor Drives with Voltage Inverter and Inverter Output Filters 9 Selected Problems of Induction Motor Drives with Voltage Inverter and Inverter Output Filters Drives and Filters Overview. Fast switching of power devices in an inverter causes high dv/dt at the rising

More information

SimpleBGC 32bit controllers Using with encoders. Last edit date: 23 October 2014 Version: 0.5

SimpleBGC 32bit controllers Using with encoders. Last edit date: 23 October 2014 Version: 0.5 SimpleBGC 32bit controllers Using with encoders Last edit date: 23 October 2014 Version: 0.5 Basecamelectronics 2013-2014 CONTENTS 1. Encoders in the SimpleBGC project...3 2. Installing encoders...4 3.

More information

CNC4PC. C19 A/C FREQUENCY CONVERTER Rev. 4

CNC4PC. C19 A/C FREQUENCY CONVERTER Rev. 4 CNC4PC Manual C19 A/C FREQUENCY CONVERTER Rev. 4 Overview This unit is an easy to use speed controller for routers. It work by modifying the output frequency according to an external control signal. It

More information

NICE900 -Door Drive Setup Manual for Asynchronous / Synchronous Motor with Encoder Feedback (Document Release Dt ) Sr. No

NICE900 -Door Drive Setup Manual for Asynchronous / Synchronous Motor with Encoder Feedback (Document Release Dt ) Sr. No Inova Automation Pvt Ltd., NIBHI Corporate Centre, 3 rd Floor, No.7, CBI Colony, 1 st Main Link Road, Perungudi, Chennai-600096. Ph:-+91 (0)44 4380 0201 Email:- info.inovaindia@inova-automation.com Website:-

More information

6.9 Jump frequency - Avoiding frequency resonance

6.9 Jump frequency - Avoiding frequency resonance E581595.9 Jump frequency - Avoiding frequency resonance : Jump frequency : Jumping width Function Resonance due to the natural frequency of the mechanical system can be avoided by jumping the resonant

More information

THYFREC-VT110S 200V 1PH System 0.4 to 2.2kW 400V 3PH System 0.75 to 2.2kW QUICK START GUIDE

THYFREC-VT110S 200V 1PH System 0.4 to 2.2kW 400V 3PH System 0.75 to 2.2kW QUICK START GUIDE MEIDEN AC SPEED CONTROL EQUIPMENT THYFREC-VT110S 200V 1PH System 0.4 to 2.2kW 400V 3PH System 0.75 to 2.2kW QUICK START GUIDE NOTICE 1. Read this manual thoroughly before using the VT110S, and store in

More information

XC4e PWM Digital Drive

XC4e PWM Digital Drive PWM Digital Drive HyperWire fiber-optic interface Up to 30 A peak output current Integral power supply Amplifiers/Drives Drive brush, brushless, voice coil, or stepper motors Safe torque off (STO) safety

More information

Ac to dc rectifier calculator

Ac to dc rectifier calculator Ac to dc rectifier calculator output will be a DC with 1.4Volts less than the applied DC voltage. The instantaneous value of the voltage applied to the rectifier is given as. Does a sound mimicked by a

More information

INDEX. i 1. B Braking Resistor Dimensions: A 24 Braking Resistors: A 20 Braking Units: A 20. DURAPULSE AC Drive User Manual

INDEX. i 1. B Braking Resistor Dimensions: A 24 Braking Resistors: A 20 Braking Units: A 20. DURAPULSE AC Drive User Manual INDEX A AC Drive Cover: 1 6 Dimensions: 2 4 External Parts and Labels: 1 6 Heat Sink Fins: 1 6 Input Mode Switch (Sink/Source): 1 6 Introduction to DuraPulse GS3 AC drive: 1 3 Keypad: 1 6 Model Number

More information

Keysight Technologies Measuring Group Delay of Frequency Converters with Embedded Local Oscillators. Application Note

Keysight Technologies Measuring Group Delay of Frequency Converters with Embedded Local Oscillators. Application Note Keysight Technologies Measuring Group Delay of Frequency Converters with Embedded Local Oscillators Application Note Introduction Mixers and frequency converters lie at the heart of wireless and satellite

More information

User-selectable output bus voltages for optimized voltage/current matching to load requirements.

User-selectable output bus voltages for optimized voltage/current matching to load requirements. Three Axis Gradient Amplifier 3-Axis 700A Precision Gradient Amplifier System 1500 VDC (OEM adjustable down to 800V) 100% Digital D-SERIES Technology Hi-Speed, Single Fiber-Optic Digital Command Universal

More information

ROLL TO ROLL FUNCTION MANUAL FR-A (0.4K)-04750(90K)-R2R FR-A (0.4K)-06830(280K)-R2R FR-A (315K)-12120(500K)-R2R

ROLL TO ROLL FUNCTION MANUAL FR-A (0.4K)-04750(90K)-R2R FR-A (0.4K)-06830(280K)-R2R FR-A (315K)-12120(500K)-R2R INVERTER ROLL TO ROLL FUNCTION MANUAL FR-A820-00046(0.4K)-04750(90K)-R2R FR-A840-00023(0.4K)-06830(280K)-R2R FR-A842-07700(315K)-12120(500K)-R2R Roll to Roll Function The FR-A800-R2R inverter has dedicated

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

Agilent U1881A and U1882A Power Measurement Application for Agilent InfiniiVision and Infiniium Oscilloscopes

Agilent U1881A and U1882A Power Measurement Application for Agilent InfiniiVision and Infiniium Oscilloscopes Agilent U1881A and U1882A Power Measurement Application for Agilent InfiniiVision and Infiniium Oscilloscopes Data Sheet Fast, automatic and reliable characterization of switching mode power devices Today

More information

SHF Communication Technologies AG

SHF Communication Technologies AG SHF Communication Technologies AG Wilhelm-von-Siemens-Str. 23D 12277 Berlin Germany Phone +49 30 772051-0 Fax +49 30 7531078 E-Mail: sales@shf.de Web: http://www.shf.de Datasheet SHF 78120 D Synthesized

More information

Fluke MDA-510 and MDA-550 Motor Drive Analyzer

Fluke MDA-510 and MDA-550 Motor Drive Analyzer TECHNICAL DATA Fluke MDA-510 and MDA-550 Motor Drive Analyzer Simplify complex motor-drive troubleshooting with guided test setups and automated drive measurements that provide reliable, repeatable test

More information