EQUIPMENT SPECIFICATIONS

Size: px
Start display at page:

Download "EQUIPMENT SPECIFICATIONS"

Transcription

1 EQUIPMENT SPECIFICATIONS EDUCATIONAL LABORATORY AT PAKISTAN INSTITUTE OF ENGINEERING AND APPPLIED SCIENCES (PIEAS) (RADIATION DETECTION EQUIPMENT LAB) 1 P age

2 1 BACKGROUND The IAEA wishes to engage a contractor (hereinafter referred to as the Contractor ) to supply the required equipment, provide training for staff, and maintenance services. This document will outline the various types of equipment, systems, systems integration, to be supplied for the laboratory at Pakistan Institute of Engineering and Applied Sciences (PIEAS). 1.1 Site Information The laboratory building is located in Department of Nuclear Engineering (DNE), at PIEAS. PIEAS is located in Islamabad at Nilore, a beautiful and picturesque valley, about 25 km from zero point of Islamabad. The campus is spread over an area of about 600,000 m Project Outline Standards All the equipment and associated accessories mentioned in this SOW shall meet relevant European applicable Standards. 2. SCOPE OF WORK The scope of the work includes the following: General Obligations (please refer to Section 2.1 below); Supply and Installation of Equipment (please refer to Section 2.2 below); Documentation and Manuals (please refer to Section 2.3 below); Training of Personnel at PIEAS (please refer to Section 2.4 below); Warranty, Preventive and Unscheduled Maintenance Services (please refer to Section 2.5 below); 2.1 General Obligations The Contractor shall deliver all systems and equipment as a complete turn-key solution meaning that it shall include all equipment and material mentioned in this SoW as well as necessary related technical and administrative manpower to install, test and provide the required systems to be delivered in full working order. Furthermore, the Contractor shall provide details for the testing against a particular claim for the performance of the equipment. 2 P age

3 The Contractor shall visit PIEAS (to ascertain conditions and gather information pertaining to the work, including: i. The location, type of the building, as well as infrastructure; ii. All pertinent national, local laws and rules, in particular building permissions and construction regulations; The Contractor shall allow PIEAS/IAEA to perform inspections of equipment and sensors to be provided under this SoW after delivery, installation and operation. PIEAS/IAEA shall verify that the equipment and other devices are in accordance with the terms of the contract concluded with the Contractor. 2.2 Supply and Installation of Equipment a. The Contractor shall deliver and test the equipment and systems according to the specifications, requirements, locations and quantities of equipment specified in the following paragraphs. b. The Contractor shall clearly state in the offer that they will deliver all systems and accessories including all equipment mentioned in this SoW as well as equipment and manpower needed for the installation and proper functioning thereof as well as all of the necessary related technical and administrative manpower to install, test and provide the required systems to be delivered in full working. c. The Contractor shall nominate a technical representative(s) for a period of 14 days to participate in the equipment acceptance testing to be performed by IAEA with participation of PIEAS and the Contractor. The work and equipment can only be accepted and fully paid after successful completion of the acceptance testing Generic Specifications applying to all components and systems The laboratory equipment shall be provided keeping in mind that they are intended for teaching, demonstration and experimental use. All components of desktop systems shall be easily replaceable to ensure that new equipment replacement does not reduce the system functionality. All replacements shall be available for the instrument s life time of 10 years Provide surge protection devices for power conditioning requirements for all sensitive electronics equipment installed. Surge protection circuits shall be provided close to the equipment (maximum 2-3 m). 3 P age

4 All installed equipment and systems shall have protection against humidity 10-80% at non condensing conditions and temperature ranges from 0 o C to 50 o C Educational Laboratory Equipment (Requirements and Specifications) Mechanical Requirements: The equipment shall tolerate vibration, micro phonics, impact, mechanical shocks and drop test etc. as per standards (factory test certificates shall be provided). Design Requirements of Radiation Detection Equipment: The detection equipment shall be clearly marked with type, model, manufacturer, serial number, date of manufacture, and type/value of power supply required. The reference point of the instruments detector (each one for every probe shall also be indicated). The detection equipment shall be based on modular design. A local maintenance provider should be able to perform repairs and replacements The detection equipment shall have the availability of rechargeable and backup of nonrechargeable standard size batteries. Instruments operating from main power shall be operable from main power at V AC, Hz. Data Transfer and Software Requirements o Communication of the instrument with a PC shall be by standard industrial link to a computer by USB or wireless to transfer spectra (detection information) and change instrument setup using IAEA ASCII string spectrum format or translation software. o The detection equipment shall be supplied with the following software products: A computer based, easy to use Windows software to transfer and view spectra; Expert software for post-processing of the spectra data if input of spectra into commercially available programs is not possible; Translation software to IAEA standard ASCII format and ANSI format to get downloaded, or translated, by provided software; and File conversion utility to IAEA ASCII (*.spe) format with detector specific setup and calibration parameters if the detection equipment software includes a proprietary file format. 4 P age

5 The detection equipment shall produce data in an exportable, human readable format (no proprietary files) that can be downloaded for event recording and can be analyzed to check the performance consistency of the equipment. The detection equipment shall feature ENGLISH language. The detection equipment shall have count rate in the range of 10-10,000 cps with ±50% conventionally true value in the continuous gamma energy range from 30 kev to 3 MeV. Neutron detection instruments shall not misinterpret gamma radiation as neutrons. Neutron detectors must be insensitive to a gamma radiation field produced by a Co-60 source exposing the detector with 100 µsv/h Specification and Quantities The layout of Radiation detection lab is attached in Annex. A. Radiation detection and processing equipment: Detailed specifications on NIM Bin components are given in APPENDIX I. Each NIM bin system shall be complete and operational. In case of minor mistakes (e.g.: wrong cables, or missing accessory) in the SoW, a correction by the supplier is allowed to bring the system to operation. S/No Description Qty Details 1.a NaI(Tl) complete with MCA, Spectroscopy amplifier, high voltage Three sets supply, and software Annex-B 2. BF 3 /He-3DetectorsAssembly with all necessary nuclear electronics Three sets & accessories. Detector Diameter 1inch 2.a Preamplifier for the BF 3 tube Three sets 2.b High voltage supply for BF 3 tube. (NIM-2) Three sets 2.c Timing Single Channel Analyzer for BF3 proportional counter. Three sets Annex- C 2.d Rate meter for BF 3 proportional counter Three sets 2.e CCNIM timer and counter for BF 3 proportional counter (requires Three sets interface option for computer operation). 2.f Neutron Probes/detector of He-3(Neutron probe/detector of 1 inch dia.) Three sets 5 P age

6 Timing Single Channel Analyzer (TSCA) Three sets 3. Independence ULD, LLD and TSCA output; precise threshold discrimination Exponential stability-dc coupled input; External base line sweep input; Dynamic range 1000:1 Source matched logic output. 3.a NIM Bin and 160 W power supply (±6 V, ± 12 V and ± 24 V) 3.b HV power supply ±3kV Three sets Delay Amplifier: Adjustable linear or logic delay from.25 to 4.75 Three sets 4. µsec, inverted or non-inverted output selection. Output range control:3v, 5v,or10v, Gain normalizing control, DC off set control. 4.a NaI(Tl) detector (2 inch diameter, well type probe/detector for 4π Three sets geometry) 5. Counter/Timer: Timer and scalar operation; Solid state LED display; Three sets Built in integral discriminator; Must accept positive or negative inputs. Pulse pair resolution less than 40 µs; Seven decayed count capability with built in pre-scalar. 6. MCA Card: 16k-Channel versions, with 8-µs fixed conversion time, Three sets ADC, -PCI MCA Emulation software, operating under Windows XP or up model in 32 or 64 bits, and featuring full networking all current software applications. Linear/Log Rate Meter: Two full-scale log ranges; Ten full scale Three sets 7. linear ranges; Large Panels meter Alarm Delay. Cables 8. RG58A/U 50 Ω with 2 BNC plugs (1feet) 12 RG62A/U 93 Ω with 2 BNC plugs (2feet) 14 RG58A/U 50 Ω with 2 BNC plugs (2feet) 14 RG62A/U 93 Ω with 2 BNC plugs (4feet) 14 RG58A/U 50 Ω with 2 BNC plugs (4feet) 12 RG62A/U 93 Ω with 2 BNC plugs (12feet) 14 RG58A/U 50 Ω with 2 BNC plugs (12feet) 12 Annex-D 6 P age

7 9. BNC T-Connector Terminators 100 Ω BNC male Plug Terminators 50 Ω BNC male Plug BNC Union BNC Connector female to female 10. Portable contamination Monitor (Berthold LB or NE PRM or equivalent) with following specification LB 1230 Basic Unit or equivalent LB 1231 Beta Gamma Probe or equivalent LB 1232 Alpha Beta Probe or equivalent LB 1236 Proportional Counter Probe or equivalent LB 123-K Case, LB 1250 and LB 1250-E1 or equivalent LB 123-p2 Test source (LB-1231 & LB-1232) or equivalent. 11. HPGe Detector System with Dewar for liquid nitrogen and all related nuclear electronics, cables, shielding to keep low background and req. accessories for sample analysis. Relevant software with radio-isotope library for radio-isotope identification MCA channel range: 16K channel FWHM: less than 600 ev at 122 kev Efficiency > 80% for low activity measurement. 12. Gamma Detection System: (Sodium Iodide NaI (Tl) detector 2-inch dia crystal attached with photomultiplier tube and PMT base preamplifier with independent and separate modules of spectroscopy amplifier, counter timer, and compatible NIMBIN, cables, connectors, software and manuals). Geiger Muller (G.M) Detector with all necessary electronics and 15. accessories. Quenching gas-halogen, Diameter 3.5cm. GM Pulse Inverter, One input provides two equal half amplitude 16. output; 50 Ω terminator; Input Power 1 W; Rise Time 1ns. Compatible with above mentioned GM Detector Three sets Two sets Three sets Three sets Three sets Annex-E Annex- F Annex- G 7 P age

8 Accessories required for Radiation Detection Laboratory The following is the list of equipment required for smooth running of Radiation Detection experiments. All of the accessories are required for conducting radiation detection experiments by MS Students. S/No. Description Qty 1. Computers to install cards and software of Multi Channel Analyzers and for demonstration of radionuclide energy vs counts spectrum and data acquisition. Requirements for the computer: Intel Dual Core or Core i7 technology, min. 2.5 GHz min. 4 GB DDR RAM, min. 500 GB HD, or better operational system W7 32 bit in English language English keyboard 22 LCD monitor. 08 each 2. Lead source containers of 15cm high with thickens at least 10 cm (To keep the radiation sources preferably shielded and lockable safe status) 3. SS/Metallic Stands (To place detectors like NaI, BF 3 and GM) above radiation source during experiments 4. Lead Collimators (with different holes to make fine collimated radiation beams) for experiments and lead source container drawer units to keep sources while using in the laboratory during the experiments. 5. Water Tank of glass or perspex, dimensions 4ft x4ft x 5ft (to study the shielding and reflecting characteristics of neutron in water or wax while being diffused) 6. Pulse Generator, Function Generators, CRO 100 Mhz for pulse shape studies as well as signal processing in radiation detection experiments. 7. Lead Bricks (9 x4 x2, 5 x5 x2, 10 x10 x2.5, 10 x10 x0.5 ) for back ground shielding & radiation protection purposes during use of radiation sources in experiments and to demonstrate the shielding effect of thickness and material to attenuate radiations 8. Iron Plate (9 x9 x1, 9 x9 x0.5 ) to be used in experiments to demonstrate the students the effect of thickness and material in attenuation of radiations and their shielding by various materials. 9. Stainless Steel Plate (9 x9 x1, 9 x9 0.5 ) for multi-layered radiation shielding experiments and to demonstrate the students the effect of thickness and material in attenuation of radiations and their shielding by various materials. 10. Copper plate (9 x9 x1, 9 x9 x0.5 ) to be used in experiments to demonstrate the students the effect of thickness and material in attenuation of radiations and their shielding by various materials. 11. Multi-shelf rack of steel/metallic cabinet for placement of NIMBINs and CROs 02 each 12 each 05 each 02 each 06 each 04 dozen 03 dozen 03 dozen 03 dozen 12 shelves 8 P age

9 12. Tongs (6 feet, 3 feet, 2 feet). This equipment is used to handle the radiation sources maintaining some distance between source and handler. 13. Tweezers of variable length. This equipment is used fine placement and handling of the radiation sources in the experiments. 03 each 25 each 2.3 Documentation Operating and Installation Manuals and Handbooks The Contractor shall provide standard maintenance, administration, operating and installation manuals for each piece of equipment or software installed (in English). Testing of equipment procedures or manuals. The Contractor shall prepare and provide administration, operation and maintenance manuals for each separate equipment and sensor (in English). Tabular list of all equipment and its location A test certificate for each system, tested in combination with the required detectors 2.4 Acceptance Testing of Equipment PNRA expert(s) and trainee (s) from PIEAS shall perform acceptance testing of all equipment received from the vendor (s) under the project at Nuclear Support Unit (NSU)-IAEA. 2.5 Training of Personnel at PIEAS The Contractor shall provide training to PIEAS faculty and laboratory personnel on the operation, installation, testing and maintenance of all equipment as mentioned in this SoW. The training shall be a combination of formal and on-the-job training. The contractor shall prepare and provide the operational and training manuals (in English). 2.6 Warranty, Preventive and Corrective Maintenance Services Warranty Starting from the date of the final PIEAS acceptance for completion of work, the contractor shall provide one (1) year of full warranty, including replacement of any faulty parts, labor cost, travelling cost, transportation cost, for all equipment under this SoW. The Contractor warrants that the equipment supplied by the company and its sub-contractors or suppliers under this Order shall be new and free from defect in workmanship, material and design and shall operate in accordance with the manufacturer s most current standards. 9 P age

10 The Contractor shall, at no charge to the IAEA, remedy any defect, whether due to faulty design, material or manufacture, impairing the functioning of the equipment or parts thereof in order to restore the required operation of the equipment or parts thereof. Any parts replaced shall become the property of the Contractor. The warranty does not apply to the natural wear and tear as well as the damage due to negligent or improper storage or handling, overloading, and operation by personnel of the counterpart contrary to the instructions of the Contractor s supervisors or to the indications of the technical documentation supplied by the Contractor. It also does not cover damages due to non-fulfilment of the technical instructions of the Contractor and/or due to the abnormal operation of the equipment. It shall be noted that abuse to or misuse of the equipment shall be outside the warranty and maintenance agreement and shall be repaired, replaced or covered by the PIEAS Preventive and Corrective Maintenance Services Starting from the date of the final PNRA acceptance for completion of work, the Contractor shall provide preventive and corrective maintenance services for 3 (three) years. The 3-year preventive and corrective maintenance services shall be based on the Contractor s provided and/or recommended list of spare parts (e.g. equipment component or entire equipment) and the associated labour cost. The Contractor s maintenance service shall include at least: (i) Annual preventive maintenance visits with: a. Inspection of electronic components and connections; b. battery check and replacement (if needed); c. voltage checks and comparisons; d. cleaning of appropriate electronic components; e. performance testing of equipment; f. system adjustments for peak performance as required; g. Replacement parts as necessary, including temporary substitution parts as required; (ii) A list of 10% spare parts will be provided to IAEA and PIEAS in the offers. Purchase of replacement parts, including temporary substitution parts as required. A stock of 10% spare parts shall be stored on-site. (iii) The contractor shall provide a fixed price quotation for preventive maintenance for the second and third year. First year shall be covered by Section Warranty. Maintenance costs and services shall be based on the recommended list of spare parts and include all associated labour costs. 10 P age

11 2.6.3 Equipment Cost Estimate Post Maintenance Period After completion of the three year maintenance period (Section above), PIEAS shall be fully responsible for ensuring the on-going and continued use and effectiveness of the equipment. The Contractor shall provide a cost estimate of the preventive and corrective maintenance for the equipment under this SoW. Such cost estimate shall be for a period of three (3) years (Year 4 to 6) of equipment s life, starting from the completion date of the Contractor s three (3) year maintenance period. 3. REPORTING REQUIREMENTS The Contractor shall prepare and submit to PIEAS and IAEA the following reports in order to provide an adequate assurance of accomplished work. Deliverable No. Deliverable Description Deliverable due date 1. The Contractor shall provide a technical report with the full details of equipment under this SoW. The report shall define any foreseeable medium and long-term sustainability needs including equipment maintenance. The report shall describe acceptance testing results. With handing over the equipment to PIEAS 2. Year 1: The Contractor shall report any corrective maintenance, as well as warranty coverage for the equipment to PIEAS, as mentioned in section of SoW. 1 year from acceptance and delivery of equipment. 3. Year 2: The Contractor shall report any corrective maintenance, as well as warranty coverage for the equipment, as mentioned in section of SoW. 2 years from acceptance and delivery of equipment. 4. Year 3: The Contractor shall report any corrective maintenance, as well as warranty coverage for the equipment, as mentioned in section of SoW. 3 years from acceptance and delivery of equipment 11 P age

12 12 P age

13 Radiation Detection Lab Layout Annex-A These figures describe the layout of Radiation Detection labs and experimental arrangements of the equipment. Radiation Detection lab dimensions (length, width, height) = 35ft x 30ft x 11ft 13 P age

14 Annex B NaI Detector with buit in electronic modules For Item no. 1 in Table(a) as given in section of Equipment Specifications, IAEA suggested an integerated system of NaI detector with inbuilt electronics. PIEAS accepted the offer and expected to receive three NaI detector with built in electronics (i.e. no separate NIM Bin, amplifier, TSCA etc.). Connectivity to a computer and to the installed software is required, to read out the measurement data. Integrated NaI detector Integrated associated electronics and accessories Sodium Iodide detector 14 P age

15 Annex C Neutron Detection System This Annex explains the equipment from item 2 to item 2f in the Table (a) as given in section of SoW. The following experimental setup will be used to demonstrate concepts of neutron detection to students. In view of large number of students, PIEAS expects to receive three neutron detection system so that six students (two per setup) could perform lab experiments at a time. Figure 1 explains the block diagram with specific components. The picture of an existing system with complete setup is shown in Figure 2. Whereas Table 1 illustrates requirednumber of experimental setups to perform neutron detection experiment.the overall summary of equipment required for item no. 2 to item 2f is detailed in Table 2 of this annexure. Oscilloscope BF 3 Detector Detector Preamplifier Amplifier High Voltage supply ±3kV PC Figure 1: Block Diagram for Neutron Detection System 15 P age

16 MCA Oscilloscope Amplifier NIM BIN Preamplifier PC Counter/Timer TSCA High Voltage BF3 Detector Figure 2: Picture of existing system for neutron detection Table 1: Required number of experimental setups for six students. Set # 1 Set # 2 Set # 3 Two Students Two Students Two Students Table 2: Summary of components required for three neutron detection systems Sr No. Equipment Quantity 1 BF 3 Detector He Detector 03 3 Preamplifier 03 4 NIM BIN 03 5 High Voltage Supply 03 6 Spectroscopy Amplifier 03 7 TSCA 03 8 Counter/Timer 03 9 MCA Oscilloscope 03 ** PC are non-radiation related electronic items hence are included in a separate list. 16 P age

17 Three extra 3 He Detectors mentioned in the item 2f of Table (a) would be integrated neutron detection systems (i.e. detectors along with built-in electronics). So, PIEAS expects to receive three integrated 3 He Detector with built in electronics and another three BF 3 Detectors with separate electronic modules as detailed in the table given above. 17 P age

18 Annex D This Annex will explain the item 3 to item 7 of the Table (a) as given in section of the Equipment Specifications. The equipment detailed under said item nos. will be used to demonstrate students about the basic concepts of radiation shielding via different lab experiments. Also, same equipment will be used to demonstrate students about characteristics and operational use of individual electronic modules through separate parts related to detected radiation pulse shaping and signal processing experiments. Moreover, these may also be standby spare modules to be used in any experimental setup where ever needed. The overall details of the equipment required for item no. 3 to item no. 7 is given in Table 1. Table 1: Summary of components required for item 3 to item 7 of table (a) of Section of Equipment Specifications Sr No. Equipment Quantity 1 NaI Detector 03 2 NIM BIN 03 3a HV power supply ±3kV 3 TSCA 03 4 Delay Amplifier 03 5 MCA 03 6 Counter/Timer 03 7 Linear/Log Rate meter P age

19 HPGe Detector System Annex E This Annex will deal with the details of item 11 of the Table (a) as given in section of SoW. PIEAS expected to get two complete HPGe detection systems with all necessary electronic modules as shown in Figure 1.Dual 5kVdetector bias supply (ORTEC Part No. 660) is desired for the HPGe detector system. The overall summary of equipment required for item 11of the Table (a), as given in section of SoW, is provided in Table 1 of this annexure. Oscilloscope HPGe Amplifier SCA/TSCA Counter/Timer with 4 counter inputs High Voltage supply ±5kV MCA PC Figure 1: Block Diagram for HPGe Detector System Table 1: Summary of components required for three HPGe Detector Systems Sr No. Equipment Quantity HPGe Detector NIM BIN High Voltage Supply ±5kV Spectroscopy Amplifier SCA/TSCA Counter/Timer MCA Oscilloscope P age

20 Annex F Gamma Detection System This Annex will provide the details of equipment required regarding the item no. 12 of Table (a) as given in section of SoW. The block diagram of experimental setup for gamma detection system is shown in Figure 1 and the actual picture of the setup components is presented in Figure 2. Three such systems would be placed in Nuclear Security lab to cater six students at a time i.e. two students per setup. This setting is further elaborated in Table 1 below. In the end, Table 2 details the overall list of equipment required for the system described in item 12 of Table (a) as given in section of SoW. Oscilloscope NaI Detector Amplifier SCA/TSCA Counter/Timer with 4 counter inputs High Voltage supply ±3kV MCA ORTEC Part No. 927 PC Figure 1: Block Diagram for Gamma Detection System 20 P age

21 MCA Oscilloscope Amplifier NIM BIN PC Counter/Timer TSCA High Voltage NaI Detector Figure 2: Picture of existing setup for Gamma detection system Table 1: Required number of experimental setups for six students. Set # 1 Set # 2 Set # 3 Two Students Two Students Two Students Table 2: Summary of components required for three Gamma Detection Systems Sr No. Equipment Quantity 1 NaI Detector 03 2 NIM BIN 03 3 High Voltage Supply 03 4 Spectroscopy Amplifier 03 5 SCA/TSCA 03 6 Counter/Timer 03 7 MCA 03 8 Oscilloscope P age

22 Annex G GM Detector with Accessories This Annex will explain the item no. 15 & 16 of Table (a) as given in section of SoW. Figure 1 shows the block diagram of GM detector along with required electronics modules. The pictorial description of the experimental setup is provided in Figure 2. Similar to neutron and gamma detection system, three setups of this system will be placed in Nuclear Security Lab to cater six students at a time i.e. two students per setup. This setting is further illustrated in Table 1. Overall list of equipment required for item 15 and 16 of Table (a) as given in section of SoWis given in Table 2. Oscilloscope GM Detector Pulse Invertor SCA/TSCA Counter/Timer with 4 counter inputs High Voltage PC supply ±3kV Figure 1: Block Diagram for GM detector experiment 22 P age

23 Pulse Invertor Oscilloscope NIM BIN GM Detector Counter/Timer TSCA High Voltage Figure 2: Picture of desired setup GM detector experiment. Table 1: Required number of experimental setups for six students. Set # 1 Set # 2 Set # 3 Two Students Two Students Two Students Table 2: Summary of components required for three GM Detector Systems Sr No. Equipment Quantity 1 GM Detector 03 2 GM Pulse Invertor 03 3 NIM BIN 03 3 High Voltage Supply 03 5 SCA/TSCA 03 6 Counter/Timer 03 7 Oscilloscope P age

24 Annex H Neutron Detection System (modular type, Annex-C) Gamma Detection System (Annex-F) Portable Detection Equipment Demonstration, HPGe, Protection equipment, Pulse Shaping Experiments, Separate standby modules, etc. Radiation Detection Laboratory to be used in the courses of Method and instrumentation for Nuclear and other radioactive material measurements (NS-4), Effect of radiation, Safety and Radiation Protection (NS-5), Nuclear Material Accounting and control (NS-13) etc. GM Detector System (Annex-G) BF3/He3 Detectiion System (integrated type, Annex-B) Sodium Iodide System (integrated type, Annex-B) 24 P age

25 Annex I List of Detectors mentioned in section of Equipment Specifications. Remarks with Serial No. Item Quantity reference to Section of SoW. 1 NaI (Tl) detector with built in electronics (Integrated system) 03 Serial No BF 3 detector 03 Serial No He detector with built in electronics (Integrated system) NaI (Tl) detector 2-inch dia crystal attached with photomultiplier tube and PMT base pre-amplifier 03 Serial No. 2f 06 Serial No. 4a Serial No HPGE Detector System 02 Serial No GM Detector 03 Serial No P age

26 Electronics (This electronic equipment is included in the setups of section of Equipment Specifications.) Serial No. Item Quantity Remarks with reference to Section of SoW Serial No. 02 Serial No. 3a 1 NIM BIN 14 Serial No. 11 Serial No. 12 Serial No. 15 Serial No. 2b 2 High Voltage Supply 09 Serial No. 12 Serial No High Voltage Supply for HPGe detector 02 Serial No. 11 Serial No Amplifier 08 Serial No. 11 Serial No. 12 Serial No. 2c Serial No SCA/TSCA 14 Serial No. 11 Serial No. 12 Serial No. 15 Serial No. 2e 6 Counter/Timer 14 Serial No. 05 Serial No P age

27 Serial No. 12 Serial No. 15 Serial No MCA 11 Serial No. 06 Serial No. 11 Serial No Linear/Log Rate Meter 03 Serial No Delay Amplifier 03 Serial No. 04 Serial No Oscilloscope 11 Serial No. 11 Serial No. 12 Serial No Preamplifier for BF 3 detector 03 Serial No. 2a 12 GM Pulse Inverter 03 Serial No. 16 Item number 8, 9, 10, 13 and 14 of section of of SoW are self-explanatory. 27 P age

28 Specifications for NIM Bin modules and oscilloscope: APPENDIX I The SoW already contains some requirements for the instruments needed. The technical specifications of this appendix shall provide more information for the following equipment: NIM bin frame and power supply Spectroscopic Amplifier High Voltage Power Supply up to ±3 kv High Voltage Power Supply up to ±5 kv Timing Single Channel Analyzer TSCA Multi Channel Analyzer Counter/Timer/Rate Meter Oscilloscope All equipment parts listed parts shall have: A warranty period on parts and labors according to the SoW Manuals in English language Computer based graphical user interface (GUI), if required, in English language Minimum temperature range 0 to 50 C. NIM bin frame and power supply: The function of the 19 NIM bin frame is to mount up to 12 standard NIM modules and to distribute power to each module. Module connectors specified by DOE/ER-0457 norm. The essential features for the equipment are: AC input V, Hz DC power output of minimum 160W, built in, or directly attached to the frame Regulated DC output for ± 6V, ±12 V and ± 24 V applications and regulated 115 V DC output Maximum output current at maximum 50 C: 10 A for ± 6 V 3,0 A for ±12 V 1,5 A for ± 24 V, and additional 0,5 A for a 115 V AC output Overload protection by warning indicator at 95 C and automatic shutdown of power supply if temperature exceeds 110 C. Wiring: The connectors and cable shall have the following setup: All connectors for DC output wired by parallel cables, or by copper bus bars. All connectors wired according DOE/ER0457T pin assignment High level ground Power-return ground A control panel on the frame shall have an ON/OFF switch and power and thermal warning lamps. 28 P age

29 Spectroscopic Amplifier: NIM module: High performance energy spectroscopy amplifier for Germanium, Si(Li), scintillation detectors and proportional counters. The essential features of this equipment are: Designed to accept positive and negative input signal from preamplifier, and to deliver a positive signal output from 0 to 10 V, which shall be suitable for single channel and multichannel pulse high analyser. Coarse and fine gain adjustment shall deliver continuously variable gain values from 2.5 to The pulse shaping time shall have minimum six positions with 0.5, 1, 2, 3, 6, and 10 micro seconds, or 0.5, 1, 2, 4, 8 and12 micro seconds. The amplifier shall have an automatic pole zero adjustment, activated by a button with status indication by light(s). An additional manual PZ adjustment shall be available, based on a 20-turn potentiometer for screwdriver. The front panel shall have UNIPOLAR and BIPOLAR outputs, with the selection option between triangular or Gaussian pulse shape on the unipolar channel. High efficient pile up rejector with light indicator at the front panel to indicate the pulse pile-up losses related to low, moderate and high count rates. The front panel shall have NORM and DIFFERENTIAL input, as well as a switch for polarity selection for both inputs. Other connectors, located at front or rear panel: INHIBIT: to accept reset signals from preamplifiers PREAMPLIFIER: to provide power to the preamplifier Module connectors specified by DOE/ER-0457 norm. The spectroscopic amplifier shall have the following minimum performance details: Spectrum stability for MeV line and 2 µs shaping time: For count rates up to 100 kcps the peak position shall not shift more than ±0.018%, and ±0.05% for count rates up to 200kcps. Spectrum broadening: For the 1332 kev line of Co-60 for MeV line and 2 µs shaping time: For count rates up to 100 kcps the broadening of the FWHM shall not be more than 8%, and 15% for count rates up to 200kcps. Overload recovery: Unipolar and bipolar Outputs shall recover to within 2% of the rated output from X1000 overload in 2.5 non overloaded pulse widths at maximum gain. Temperature efficient in the range between 0 and 50 C shall be less than ±0.005% per C for the gain stability and ±7.5 µv per C for the unipolar output, and ±0.007% per C for the gain stability and ±30 µv per C for the bipolar output Integral non linearity shall be less than ±0.025% over whole output range (0 till +10V) at 2 micro seconds shaping time Noise shall be less than 5 µv rms for gain more than 100 and shaping time 2 µs Bipolar Crossover walk shall be less than ±3 ns over a 50:1 dynamic range High Voltage Power Supply up to ±3 kv NIM module to power PM-tubes, proportional counters and GM tubes The essential features of this equipment are: 29 Page

30 The HV Power supply shall provide very stable, continuous adjustable, well regulated HV with low noise in an output range from 50 to 3000 V for both, positive and negative polarity (selection of the polarity by mechanical switch). The output current shall go up to 10 ma. Voltage shall be available at two SHV connectors simultaneously. Noise on the output shall be less than 15 mv (peak to peak, at 20 Hz to 20 MHz). Input power shall be taken direct from the AC power line with 115 to 240 V and Hz. The power supply shall have an overload and short-circuit protection. A digital display shall allow to monitor either the output Voltage in V or kv units, or the current in ma (selection by mechanical switch at the front panel). A power switch the front panel shall energize the unit, an additional LED shall indicate the status. The adjustment of the output voltage shall happen at the front panel via mechanical switch(es) and/or a precision potentiometer(s). High Voltage Power Supply up to ±5 kv NIM module with two independent adjustable bias power supply elements for germanium and silicon detectors. The essential features of this equipment are: Each of the two HV Power supply shall provide very stable, continuous adjustable, well regulated HV with low noise in an output range from 0 to 5000 V and from 0 to 500 V. Each outputs shall be able to deliver positive and negative HV polarity (selection of the polarity by mechanical switch). The output current shall go up to 100 µa. Voltage shall be available at SHV connectors for 5kV and 500V output, for each of the two power supply element. Noise on the output shall be less than 10 mv (peak to peak, at 5 Hz to 50 MHz). Input power shall be taken direct from the NIM bin power supply (±12 and ±24 V DC). For each element a digital display or a segment bar graph shall allow to monitor the output Voltage. LEDs shall indicate the selected output polarity before the HV ON/OFF switch is turned on. A remote shutdown feature shall protect germanium or silicon detectors when warming up. For this purpose a shutdown input, to receive the signal from the preamplifier, a LED to indicate the shutdown and a reset button to manually cancel the shutdown mode shall be implemented in each element of the NIM module. The shutdown feature shall be compatible to TTL logic level output signals of certain detectors. In case any of the detectors demands excessive output current, the HV outputs shall be automatically protected against overload. The overload shall be indicated by a light. After overload the module shall recover automatically. The adjustment of the output voltage shall happen at the front panel via precision potentiometer(s). Timing Single Channel Analyser TSCA This NIM module shall performs single channel pulse high analysis and timing signal derivation. The essential features of this equipment are: The TSCA shall process bipolar and unipolar signals and shall operate in three different modes: Integral (UL is disabled and LL sets a single discriminator threshold between 0 and 10 V), Normal (LL and UL as independent adjustable levels within 0 to 10 V) and Window (LL as baseline level between 0 and 10V, UL sets window width (1-10V)) mode. To select the modes a mechanical switch at the front panel shall be installed. 30 P age

31 The selection of the Low level (LL) shall be done via turn potentiometer for continuous adjustment from 0 till +10 V. The manipulation of the Upper level (UL) shall be done via turn potentiometer for continuous adjustment from 0 till +10 V in normal mode, or 0 till +1 V in windows mode. The selection of the time delay shall happen via turn potentiometer for continuous adjustment of the output delay range between 0.1 up to 11 µs. To compensate the walk an adjustment screw at the front panel shall be available The DC input, a SCA output with positive polarity and a SCA output with negative polarity shall be available as BNC connectors at the front and rear side. Additionally, the module shall have LL and UL NIM output standards. The dynamic rang shall be minimum 200:1 Multi Channel Analyser NIM module: Dual-input Multichannel Analyser System with interface connection option to a computer. The essential features of this equipment are: Each of both inputs shall process the signal via a fast 16k ADC and store data in sufficient on-board memory. The conversion time shall be less than 1.5 µs, and the resolution shall be adjustable for 16k, 8k, 4k, 2k, 1k, or 512 channel applications. The module shall have dead time correction methods, including Gedcke-Hale and ZDT method. The input shall accept positive unipolar gated integrator, or positive leading bipolar analog pulses, and shall operate in the PUR (Pile up rejection), BUSY and ADC GATE input modes. The module shall communicate with a MCA emulator software, installed on a computer. The connection to a computer shall be established via a standard USB-2.0 interface. The emulator software shall be supplied with the MCA and shall have the following essential features: Fully operational at Windows XP and W7 32 bit systems. True live data display GUI easy to operate Real time/live time selection Create Region of Interests with information on centroid, peak count, integral count Data stored on the computer shall have a standard universal readable (e.g.: by text editor) format, proprietor files (just readable by own software) are not allowed. Counter/Timer/Rate Meter NIM Bin module for counting pulses and displaying the actual values and cps rate by a count rate meter (CRM). The essential features of this equipment are: The module shall be able to process count rates up to 200 MHz. It shall consists of 4 counters and 2 timers. It shall have a pulse capacity of 32 bit and a pulse pair resolution of 7 ns or better. The module shall have minimum four front panel counter inputs, which accepts analog and digital pulses up to ±5 V in amplitude. Furthermore it shall have up to six front panel inputs, which accept TTL signals, and minimum two outputs which act as TLL output. All signal inputs and outputs shall be BNC connectors. Each counter or timer shall have a 128 word First in first out buffer. Counting thresholds shall be computer adjustable. 31 P age

32 A standard USB-2.0 plug shall be available at the rear panel to connect the module with a computer to transfer and display the collected information to a Counter/Timer/Rate Meter Software. Software shall also be responsible to adjust and store setup parameters. The Counter/Timer/Rate Meter software shall be supplied with the counter/timer module and shall have the following essential features: Fully operational at Windows XP and W7 32 bit systems. Easy to operate GUI for all input signals Each counter shall display the actual digital counter value, an analogue CRM (graph in the design of a tachometer with selectable logarithmic or linear units, a CRM showing counts per second (cps) rates, input selection, threshold alarm light and a reset button Setup of parameters for each counter (signal threshold, polarity, alarm threshold and impedance) Oscilloscope The compact digital oscilloscope shall have the following essential features: Minimum bandwidths of 100 MHz Two channels Sample Rate 1.0 GS/s Real Time, or better 34 Automatic Measurements Advanced triggers including pulse width trigger and line-selectable video trigger Colour LCD Display (optional: additional monochrome mode), minimum 7 with minimum resolution of 800x480 pixel. Built in zoom function (x10) Dual window FFT to monitor simultaneously time and frequency mode Dual channel frequency counter Removable Data Storage via Front Panel USB Port PC Connectivity via second USB Device Port and additional software to display User interface and manuals in English language. 32 P age

DSA-LX. Digital Signal Analyzer. Radiation Safety. Amplified.

DSA-LX. Digital Signal Analyzer. Radiation Safety. Amplified. Radiation Safety. Amplified. DSA-LX Digital Signal Analyzer Nuclear Healthcare Homeland Security & Defense Labs and Education Industrial and Manufacturing KEY FEATURES Integrated desktop MCA based on Digital

More information

ORTEC. Research Applications. Pulse-Height, Charge, or Energy Spectroscopy. Detectors. Processing Electronics

ORTEC. Research Applications. Pulse-Height, Charge, or Energy Spectroscopy. Detectors. Processing Electronics ORTEC Spectroscopy systems for ORTEC instrumentation produce pulse height distributions of gamma ray or alpha energies. MAESTRO-32 (model A65-B32) is the software included with most spectroscopy systems

More information

Gamma Ray Spectroscopy with NaI(Tl) and HPGe Detectors

Gamma Ray Spectroscopy with NaI(Tl) and HPGe Detectors Nuclear Physics #1 Gamma Ray Spectroscopy with NaI(Tl) and HPGe Detectors Introduction: In this experiment you will use both scintillation and semiconductor detectors to study γ- ray energy spectra. The

More information

Model 863 Quad Timing Filter Amplifier Operating and Service Manual

Model 863 Quad Timing Filter Amplifier Operating and Service Manual Model 863 Quad Timing Filter Amplifier Operating and Service Manual Printed in U.S.A. ORTEC Part No. 733960 0411 Manual Revision C Advanced Measurement Technology, Inc. a/k/a/ ORTEC, a subsidiary of AMETEK,

More information

nanomca 80 MHz HIGH PERFORMANCE, LOW POWER DIGITAL MCA Model Numbers: NM0530 and NM0530Z

nanomca 80 MHz HIGH PERFORMANCE, LOW POWER DIGITAL MCA Model Numbers: NM0530 and NM0530Z datasheet nanomca 80 MHz HIGH PERFORMANCE, LOW POWER DIGITAL MCA Model Numbers: NM0530 and NM0530Z I. FEATURES Finger-sized, high performance digital MCA. 16k channels utilizing smart spectrum-size technology

More information

nanomca datasheet I. FEATURES

nanomca datasheet I. FEATURES datasheet nanomca I. FEATURES Finger-sized, high performance digital MCA. 16k channels utilizing smart spectrum-size technology -- all spectra are recorded and stored as 16k spectra with instant, distortion-free

More information

ORTEC. AN34 Experiment 14 Nuclear Lifetimes and the Coincidence Method. Equipment Needed from ORTEC. Equipment Required from Other Manufacturers

ORTEC. AN34 Experiment 14 Nuclear Lifetimes and the Coincidence Method. Equipment Needed from ORTEC. Equipment Required from Other Manufacturers Equipment Needed from ORTEC Two 113 Scintillation Preamplifiers Two 266 Photomultiplier Tube Bases 4001A/4002D Bin and Power Supply 414A Fast Coincidence Two 551 Timing Single-Channel Analyzers 567 Time-to-Amplitude

More information

nanomca-sp datasheet I. FEATURES

nanomca-sp datasheet I. FEATURES datasheet nanomca-sp 80 MHz HIGH PERFORMANCE, LOW POWER DIGITAL MCA WITH BUILT IN PREAMPLIFIER Model Numbers: SP0534A/B to SP0539A/B Standard Models: SP0536B and SP0536A I. FEATURES Built-in preamplifier

More information

Electronic Instrumentation for Radiation Detection Systems

Electronic Instrumentation for Radiation Detection Systems Electronic Instrumentation for Radiation Detection Systems January 23, 2018 Joshua W. Cates, Ph.D. and Craig S. Levin, Ph.D. Course Outline Lecture Overview Brief Review of Radiation Detectors Detector

More information

Purpose This experiment will use the coincidence method for time correlation to measure the lifetime in the decay scheme of 57

Purpose This experiment will use the coincidence method for time correlation to measure the lifetime in the decay scheme of 57 Equipment Required Two 113 Scintillation Preamplifiers Two 266 Photomultiplier Tube Bases 4001A/4002D Bin and Power Supply 414A Fast Coincidence Two 551 Timing Single-Channel Analyzers 567 Time-to-Amplitude

More information

NIM. ADCs (Peak Sensing) Analog Pulse Processors Amplifiers (Fast) Amplifiers (Spectroscopy) Attenuators Coincidence/Logic/Trigger Units

NIM. ADCs (Peak Sensing) Analog Pulse Processors Amplifiers (Fast) Amplifiers (Spectroscopy) Attenuators Coincidence/Logic/Trigger Units The NIM-Nuclear Instrumentation Module standard is a very popular form factor widely used in experimental Particle and Nuclear Physics setups. Defined the first time by the U.S. Atomic Energy Commission

More information

IDM-200-P. High Purity Germanium (HPGe) Interchangeable Detector Module. Intelligent, Modular Solutions for Nuclear Security Monitoring Systems

IDM-200-P. High Purity Germanium (HPGe) Interchangeable Detector Module. Intelligent, Modular Solutions for Nuclear Security Monitoring Systems IDM-200-P High Purity Germanium (HPGe) Interchangeable Detector Module Intelligent, Modular Solutions for Nuclear Security Monitoring Systems The ORTEC Interchangeable Detector Module (IDM-200-P) sets

More information

ORTEC Experiment 13. Gamma-Gamma Coincidence with Angular Correlation. Equipment Required

ORTEC Experiment 13. Gamma-Gamma Coincidence with Angular Correlation. Equipment Required ORTEC Experiment 13 Equipment Required Two 905-3 2-in. x 2-in. NaI(Tl) Scintillation Detector Assemblies. Two 266 Photomultiplier Tube Bases. Two 113 Scintillation Preamplifiers. Two 556 High Voltage Power

More information

Model 3102D 0-2 kv H.V. Power Supply

Model 3102D 0-2 kv H.V. Power Supply Features Compact single width NIM package Regulated up to ±2000 V dc. 1 ma output Noise and ripple 3 mv peak to peak Overload and short circuit protected Overload, inhibit and polarity status indicators

More information

Analog-to-Digital-Converter User Manual

Analog-to-Digital-Converter User Manual 7070 Analog-to-Digital-Converter User Manual copyright FAST ComTec GmbH Grünwalder Weg 28a, D-82041 Oberhaching Germany Version 2.0, July 7, 2005 Software Warranty FAST ComTec warrants proper operation

More information

LUDLUM MODEL MODEL AND MODEL GAMMA SCINTILLATORS. June 2017

LUDLUM MODEL MODEL AND MODEL GAMMA SCINTILLATORS. June 2017 LUDLUM MODEL 44-20 MODEL 44-20-1 AND MODEL 44-20-3 GAMMA SCINTILLATORS June 2017 LUDLUM MODEL 44-20 MODEL 44-20-1 AND MODEL 44-20-3 GAMMA SCINTILLATORS June 2017 STATEMENT OF WARRANTY Ludlum Measurements,

More information

SPECTROMETRIC DETECTION PROBE Model 310. Operator's manual

SPECTROMETRIC DETECTION PROBE Model 310. Operator's manual SPECTROMETRIC DETECTION PROBE Model 310 Operator's manual CONTENTS 1. INTRODUCTION... 3 2. SPECIFICATIONS... 4 3. DESIGN FEATURES... 6 4. INSTALLATION... 10 5. SAFETY AND PRECAUTIONS... 13 6. THEORY OF

More information

Model 9302 Amplifier-Discriminator Operating and Service Manual

Model 9302 Amplifier-Discriminator Operating and Service Manual Model 9302 Amplifier-Discriminator Operating and Service Manual Printed in U.S.A. ORTEC Part No. 733690 1202 Manual Revision C Advanced Measurement Technology, Inc. a/k/a/ ORTEC, a subsidiary of AMETEK,

More information

LUDLUM MODEL 421 AND PMT BASE WITH PREAMPLIFIER/BIAS SUPPLY. October 2014 Serial Number and Succeeding Serial Numbers

LUDLUM MODEL 421 AND PMT BASE WITH PREAMPLIFIER/BIAS SUPPLY. October 2014 Serial Number and Succeeding Serial Numbers LUDLUM MODEL 421 AND 421-3 PMT BASE WITH PREAMPLIFIER/BIAS SUPPLY October 2014 Serial Number 200000 and Succeeding Serial Numbers LUDLUM MODEL 421 AND 421-3 PMT BASE WITH PREAMPLIFIER/BIAS SUPPLY October

More information

Dual 500ns ADC User Manual

Dual 500ns ADC User Manual 7072 Dual 500ns ADC User Manual copyright FAST ComTec GmbH Grünwalder Weg 28a, D-82041 Oberhaching Germany Version 2.3, May 11, 2009 Copyright Information Copyright Information Copyright 2001-2009 FAST

More information

NIM INDEX. Attenuators. ADCs (Peak Sensing) Discriminators. Translators Analog Pulse Processors Amplifiers (Fast) Amplifiers (Spectroscopy)

NIM INDEX. Attenuators. ADCs (Peak Sensing) Discriminators. Translators Analog Pulse Processors Amplifiers (Fast) Amplifiers (Spectroscopy) NIM The NIM-Nuclear Instrumentation Module standard is a very popular form factor widely used in experimental Particle and Nuclear Physics setups. Defined the first time by the U.S. Atomic Energy Commission

More information

Model 9305 Fast Preamplifier Operating and Service Manual

Model 9305 Fast Preamplifier Operating and Service Manual Model 9305 Fast Preamplifier Operating and Service Manual This manual applies to instruments marked Rev 03" on rear panel. Printed in U.S.A. ORTEC Part No.605540 1202 Manual Revision B Advanced Measurement

More information

NEEP 427 PROPORTIONAL COUNTERS. Knoll, Chapters 6 & 14 Sect. I & II

NEEP 427 PROPORTIONAL COUNTERS. Knoll, Chapters 6 & 14 Sect. I & II NEEP 427 PROPORTIONAL COUNTERS References: Knoll, Chapters 6 & 14 Sect. I & II a proportional counter the height of the output pulse is proportional to the number of ion pairs produced in the counter gas.

More information

nanomca-ii-sp datasheet

nanomca-ii-sp datasheet datasheet nanomca-ii-sp 125 MHz ULTRA-HIGH PERFORMANCE DIGITAL MCA WITH BUILT IN PREAMPLIFIER Model Numbers: SP8004 to SP8009 Standard Models: SP8006B and SP8006A I. FEATURES Finger-sized, ultra-high performance

More information

Model 9307 pico-timing Discriminator Operating and Service Manual

Model 9307 pico-timing Discriminator Operating and Service Manual Model 9307 pico-timing Discriminator Operating and Service Manual Printed in U.S.A. ORTEC Part No. 764020 1202 Manual Revision C Advanced Measurement Technology, Inc. a/k/a/ ORTEC, a subsidiary of AMETEK,

More information

GAMMA-GAMMA CORRELATION Latest Revision: August 21, 2007

GAMMA-GAMMA CORRELATION Latest Revision: August 21, 2007 C1-1 GAMMA-GAMMA CORRELATION Latest Revision: August 21, 2007 QUESTION TO BE INVESTIGATED: decay event? What is the angular correlation between two gamma rays emitted by a single INTRODUCTION & THEORY:

More information

Model 533 Dual Sum and Invert Amplifier Operating and Service Manual

Model 533 Dual Sum and Invert Amplifier Operating and Service Manual Model 533 Dual Sum and Invert Amplifier Operating and Service Manual Printed in U.S.A. ORTEC Part No. 733410 1202 Manual Revision B Advanced Measurement Technology, Inc. a/k/a/ ORTEC, a subsidiary of AMETEK,

More information

nanodpp datasheet I. FEATURES

nanodpp datasheet I. FEATURES datasheet nanodpp I. FEATURES Ultra small size high-performance Digital Pulse Processor (DPP). 16k channels utilizing smart spectrum-size technology -- all spectra are recorded and stored as 16k spectra

More information

ScintiPack Model 296 Photomultiplier Base with Preamplifier and High Voltage Power Supply Operating and Service Manual

ScintiPack Model 296 Photomultiplier Base with Preamplifier and High Voltage Power Supply Operating and Service Manual ScintiPack Model 296 Photomultiplier Base with Preamplifier and High Voltage Power Supply Operating and Service Manual WARNING This equipment generates, uses, and can radiate radio frequency energy, and

More information

Model 673 Spectroscopy Amplifier and Gated Integrator Operating and Service Manual

Model 673 Spectroscopy Amplifier and Gated Integrator Operating and Service Manual Model 673 Spectroscopy Amplifier and Gated Integrator Operating and Service Manual Printed in U.S.A. ORTEC Part No. 675590 0202 Manual Revision B $GYDQFHG 0HDVXUHPHQW 7HFKQRORJ\,QF a/k/a/ ORTEC, a subsidiary

More information

Fast first practical help -- detailed instructions will follow- preliminary Experiment F80

Fast first practical help -- detailed instructions will follow- preliminary Experiment F80 Fast first practical help -- detailed instructions will follow- preliminary Experiment F80 Measurement Methods of Nuclear and Particle Physics Introduction: This experiment is going to introduce you to

More information

INDEX. Firmware for DPP (Digital Pulse Processing) DPP-PSD Digital Pulse Processing for Pulse Shape Discrimination

INDEX. Firmware for DPP (Digital Pulse Processing) DPP-PSD Digital Pulse Processing for Pulse Shape Discrimination Firmware for DPP (Digital Pulse Processing) Thanks to the powerful FPGAs available nowadays, it is possible to implement Digital Pulse Processing (DPP) algorithms directly on the acquisition boards and

More information

Model 935 Quad Constant-Fraction 200-MHz Discriminator Operating and Service Manual

Model 935 Quad Constant-Fraction 200-MHz Discriminator Operating and Service Manual Model 935 Quad Constant-Fraction 200-MHz Discriminator Operating and Service Manual U.S. Patent No. 4,179,644 Printed in U.S.A. ORTEC Part No. 753770 0503 Manual Revision H ii $GYDQFHG0HDVXUHPHQW7HFKQRORJ\,QF

More information

ORTEC Experiment 1. Introduction to Electronic Signal Analysis in Nuclear Radiation Measurements. Equipment Required: Purpose. Electronic Circuits

ORTEC Experiment 1. Introduction to Electronic Signal Analysis in Nuclear Radiation Measurements. Equipment Required: Purpose. Electronic Circuits ORTEC Experiment 1 Equipment Required: 480 Pulser 113 Scintillation Preamplifier 4001A/4002D NIM Bin and Power Supply 575A Spectroscopy Amplifier 996 Timer and Counter 551 Timing Single-Channel Analyzer

More information

Model 7000 Low Noise Differential Preamplifier

Model 7000 Low Noise Differential Preamplifier Model 7000 Low Noise Differential Preamplifier Operating Manual Service and Warranty Krohn-Hite Instruments are designed and manufactured in accordance with sound engineering practices and should give

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) A.H. Systems Model Active Monopole Antennas Active Monopole Antenna Series Operation Manual 1 TABLE OF CONTENTS INTRODUCTION

More information

Photon Counters SR430 5 ns multichannel scaler/averager

Photon Counters SR430 5 ns multichannel scaler/averager Photon Counters SR430 5 ns multichannel scaler/averager SR430 Multichannel Scaler/Averager 5 ns to 10 ms bin width Count rates up to 100 MHz 1k to 32k bins per record Built-in discriminator No interchannel

More information

Lynx Digital Signal Analyzer

Lynx Digital Signal Analyzer Features Integrated rack mountable MCA based on Digital Signal Processing (DSP) technology Two groups of 32K channel conversion gain/spectral memory Operates in pulse height analysis (PHA), multichannel

More information

e t Development of Low Cost γ - Ray Energy Spectrometer

e t Development of Low Cost γ - Ray Energy Spectrometer e t International Journal on Emerging Technologies (Special Issue on NCRIET-2015) 6(2): 315-319(2015) ISSN No. (Print) : 0975-8364 ISSN No. (Online) : 2249-3255 Development of Low Cost γ - Ray Energy Spectrometer

More information

Portable Multi-Channel Recorder Model DAS240-BAT

Portable Multi-Channel Recorder Model DAS240-BAT Data Sheet Portable Multi-Channel Recorder The DAS240-BAT measures parameters commonly found in process applications including voltage, temperature, current, resistance, frequency and pulse. It includes

More information

R AMP TEK Landed on Mars July 4, 1997 All Solid State Design No Liquid Nitrogen Be Window FET Detector Temperature Monitor Cooler Mounting Stud FEATURES Si-PIN Photodiode Thermoelectric Cooler Beryllium

More information

Comparisons Between Digital Gamma-Ray Spectrometer (DSPec) and Standard Nuclear Instrumentation Methods (NIM) Systems

Comparisons Between Digital Gamma-Ray Spectrometer (DSPec) and Standard Nuclear Instrumentation Methods (NIM) Systems LA-13393-MS Comparisons Between Digital Gamma-Ray Spectrometer (DSPec) and Standard Nuclear Instrumentation Methods (NIM) Systems Los Alamos N A T I O N A L L A B O R A T O R Y Los Alamos National Laboratory

More information

Model 416A Gate and Delay Generator Operating and Service Manual

Model 416A Gate and Delay Generator Operating and Service Manual Model 416A Gate and Delay Generator Operating and Service Manual Printed in U.S.A. ORTEC Part No. 733160 1202 Manual Revision E Advanced Measurement Technology, Inc. a/k/a/ ORTEC, a subsidiary of AMETEK,

More information

ORTEC ORTEC. Modular Pulse- Processing Electronics. What s in this Catalog? Who Needs this Catalog?

ORTEC ORTEC. Modular Pulse- Processing Electronics.   What s in this Catalog? Who Needs this Catalog? ORTEC Modular Pulse- Processing Electronics What s in this Catalog? Tutorial Information makes this more than just a catalog. "What You Need to Know About Modular Electronic Instruments" takes you through

More information

Amptek sets the New State-of-the-Art... Again! with Cooled FET

Amptek sets the New State-of-the-Art... Again! with Cooled FET Amptek sets the New State-of-the-Art... Again! with Cooled FET RUN SILENT...RUN FAST...RUN COOL! Performance Noise: 670 ev FWHM (Si) ~76 electrons RMS Noise Slope: 11.5 ev/pf High Ciss FET Fast Rise Time:

More information

Model 480 Pulser Operating and Service Manual

Model 480 Pulser Operating and Service Manual Model 480 Pulser Operating and Service Manual Printed in U.S.A. ORTEC Part No. 733390 1202 Manual Revision B Advanced Measurement Technology, Inc. a/k/a/ ORTEC, a subsidiary of AMETEK, Inc. WARRANTY ORTEC*

More information

Variable-Gain High Speed Current Amplifier

Variable-Gain High Speed Current Amplifier Features Transimpedance (gain) switchable from 1 x 10 2 to 1 x 10 8 V/A Bandwidth from DC up to 200 MHz Upper cut-off frequency switchable to 1 MHz, 10 MHz or full bandwidth Switchable AC/DC coupling Adjustable

More information

Quad Analog-to-Digital Converter Technical Documentation

Quad Analog-to-Digital Converter Technical Documentation 7074 Quad AnalogtoDigital Converter Technical Documentation copyright FAST ComTec GmbH Grünwalder Weg 28a, D82041 Oberhaching Germany Version 2.2, February 25, 2005 Table of Contents Table of Contents

More information

PX4 Frequently Asked Questions (FAQ)

PX4 Frequently Asked Questions (FAQ) PX4 Frequently Asked Questions (FAQ) What is the PX4? The PX4 is a component in the complete signal processing chain of a nuclear instrumentation system. It replaces many different components in a traditional

More information

PD32-32 Channel Piezo Driver Manual and Specifications

PD32-32 Channel Piezo Driver Manual and Specifications PD32-32 Channel Piezo Driver Manual and Specifications PiezoDrive Pty. Ltd. www.piezodrive.com Contents 1 Introduction... 3 2 Warnings / Notes... 3 3 Specifications... 4 4 Output Voltage Range... 5 4.1

More information

Model 855 Dual Spectroscopy Amplifier Operating and Service Manual

Model 855 Dual Spectroscopy Amplifier Operating and Service Manual Model 855 Dual Spectroscopy Amplifier Operating and Service Manual This manual applies to instruments marked Rev. 03" on rear panel. Printed in U.S.A. ORTEC Part No. 717490 0406 Manual Revision C $GYDQFHG0HDVXUHPHQW7HFKQRORJ\,QF

More information

Model 427A Delay Amplifier Operating and Service Manual

Model 427A Delay Amplifier Operating and Service Manual Model 427A Delay Amplifier Operating and Service Manual This manual Applies to instruments marked Rev 22" on rear panel Printed in U.S.A. ORTEC Part No. 733210 1202 Manual Revision B Advanced Measurement

More information

Radiation Detection Instrumentation

Radiation Detection Instrumentation Radiation Detection Instrumentation Principles of Detection and Gas-filled Ionization Chambers Neutron Sensitive Ionization Chambers Detection of radiation is a consequence of radiation interaction with

More information

TB-5 User Manual. Products for Your Imagination

TB-5 User Manual. Products for Your Imagination TB-5 User Manual 1 Introduction... 2 1.1 TB-5 Description... 2 1.2 DP5 Family... 2 1.3 Options and Variations... 3 2 Specifications... 3 2.1 Spectroscopic Performance... 3 2.2 Processing, physical, and

More information

Model 542 Linear Gate and Stretcher Operating and Service Manual

Model 542 Linear Gate and Stretcher Operating and Service Manual Model 542 Linear Gate and Stretcher Operating and Service Manual NOTE: A substitution for the dual diode package (MSD6100) may have been made in this unit. If so, two 1N4153 diodes were used to replace

More information

Directed Energy, Inc Oakridge Dr., Suite 100, Fort Collins, CO

Directed Energy, Inc Oakridge Dr., Suite 100, Fort Collins, CO PCO-7121 Laser Diode Driver Module Operation Manual Directed Energy, Inc. 1609 Oakridge Dr., Suite 100, Fort Collins, CO 80525 sales@ixyscolorado.com www.ixyscolorado.com Contents Contents... 3 Safety...

More information

Gamma Spectrometer Initial Project Proposal

Gamma Spectrometer Initial Project Proposal Gamma Spectrometer Initial Project Proposal Group 9 Aman Kataria Johnny Klarenbeek Dean Sullivan David Valentine Introduction There are currently two main types of gamma radiation detectors used for gamma

More information

Model 113 Scintillation Preamplifier Operating and Service Manual

Model 113 Scintillation Preamplifier Operating and Service Manual Model 113 Scintillation Preamplifier Operating and Service Manual Printed in U.S.A. ORTEC Part No. 717560 1202 Manual Revision B Advanced Measurement Technology, Inc. a/k/a/ ORTEC, a subsidiary of AMETEK,

More information

Model 439 Digital Current Integrator Operating Manual

Model 439 Digital Current Integrator Operating Manual Model 439 Digital Current Integrator Operating Manual Printed in U.S.A. ORTEC Part No. 733240 0908 Manual Revision K Advanced Measurement Technology, Inc. a/k/a/ ORTEC, a subsidiary of AMETEK, Inc. WARRANTY

More information

SIGNAL RECOVERY. Model 7265 DSP Lock-in Amplifier

SIGNAL RECOVERY. Model 7265 DSP Lock-in Amplifier Model 7265 DSP Lock-in Amplifier FEATURES 0.001 Hz to 250 khz operation Voltage and current mode inputs Direct digital demodulation without down-conversion 10 µs to 100 ks output time constants Quartz

More information

AMP-13 OPERATOR S MANUAL

AMP-13 OPERATOR S MANUAL AMP-13 OPERATOR S MANUAL Version 2.0 Copyright 2008 by Vatell Corporation Vatell Corporation P.O. Box 66 Christiansburg, VA 24068 Phone: (540) 961-3576 Fax: (540) 953-3010 WARNING: Read instructions carefully

More information

Model 460 Delay Line Amplifier Operating and Service Manual

Model 460 Delay Line Amplifier Operating and Service Manual Model 460 Delay Line Amplifier Operating and Service Manual Printed in U.S.A. ORTEC Part No. 733320 1202 Manual Revision C Advanced Measurement Technology, Inc. a/k/a/ ORTEC, a subsidiary of AMETEK, Inc.

More information

Multiple Instrument Station Module

Multiple Instrument Station Module Multiple Instrument Station Module Digital Storage Oscilloscope Vertical Channels Sampling rate Bandwidth Coupling Input impedance Vertical sensitivity Vertical resolution Max. input voltage Horizontal

More information

SPECTRA 5011, SPECTRA 5041 PORTABLE ALPHA-BETA-GAMMA SURFACE INVESTIGATOR SURFACE INVESTIGATOR PRO SPECTROMETER

SPECTRA 5011, SPECTRA 5041 PORTABLE ALPHA-BETA-GAMMA SURFACE INVESTIGATOR SURFACE INVESTIGATOR PRO SPECTROMETER SPECTRA 5011, SPECTRA 5041 PORTABLE ALPHA-BETA-GAMMA SPECTROMETER SURFACE INVESTIGATOR SURFACE INVESTIGATOR PRO User s Manual (Short description 08/2002) Page 2 Page 3 1 UNPACKING 4 1.1 PACKING LIST: 4

More information

K 223 Angular Correlation

K 223 Angular Correlation K 223 Angular Correlation K 223.1 Aim of the Experiment The aim of the experiment is to measure the angular correlation of a γ γ cascade. K 223.2 Required Knowledge Definition of the angular correlation

More information

CR10 Combined Charge-sensitive Pre-amplifier and Shaping Amplifier User Manual

CR10 Combined Charge-sensitive Pre-amplifier and Shaping Amplifier User Manual CR10 Combined Charge-sensitive Pre-amplifier and Shaping Amplifier User Manual Pyramid Technical Consultants, Inc. 1050 Waltham Street Suite 200, Lexington MA 02421 USA US: TEL: (781) 402 1700 FAX: (781)

More information

ORTEC Experiment 19. Gamma-Ray Decay Scheme and Angular Correlation for 60 Co. Equipment Required. Purpose. Introduction

ORTEC Experiment 19. Gamma-Ray Decay Scheme and Angular Correlation for 60 Co. Equipment Required. Purpose. Introduction ORTEC Experiment 19 Equipment Required Two 905-3 NaI(Tl) 2- x 2-in. Detectors with Phototubes. Two 266 PMT Bases. Two 556 High Voltage Power Supplies. Two 113 Scintillation Preamplifiers. Two 575A Amplifiers.

More information

Calibrating Radioactive Monitors

Calibrating Radioactive Monitors 1 Calibrating Radioactive Monitors William Hackeman, Todd Averett April 18, 2008 1. Introduction This research will focus on the calibration of five radiation monitors. Two of the monitors are made by

More information

GAMMA-RAD5 User Manual

GAMMA-RAD5 User Manual GAMMA-RAD5 User Manual 1 Introduction... 2 1.1 Gamma-Rad5 Description... 2 1.2 DP5 Family... 2 1.3 Options and Variations... 3 2 Specifications... 4 2.1 Spectroscopic Performance... 4 2.2 Processing, physical,

More information

Model 428 Detector Bias Supply Operating and Service Manual

Model 428 Detector Bias Supply Operating and Service Manual Model 428 Detector Bias Supply Operating and Service Manual Printed in U.S.A. ORTEC Part No. 733220 1202 Manual Revision C Advanced Measurement Technology, Inc. a/k/a/ ORTEC, a subsidiary of AMETEK, Inc.

More information

LUDLUM MODEL 182 RADON FLASK COUNTER. June 2011 Serial Number PR and Succeeding Serial Numbers

LUDLUM MODEL 182 RADON FLASK COUNTER. June 2011 Serial Number PR and Succeeding Serial Numbers LUDLUM MODEL 182 RADON FLASK COUNTER June 2011 Serial Number PR206794 and Succeeding Serial Numbers LUDLUM MODEL 182 RADON FLASK COUNTER June 2011 Serial Number PR206794 and Succeeding Serial Numbers LUDLUM

More information

PCS-150 / PCI-200 High Speed Boxcar Modules

PCS-150 / PCI-200 High Speed Boxcar Modules Becker & Hickl GmbH Kolonnenstr. 29 10829 Berlin Tel. 030 / 787 56 32 Fax. 030 / 787 57 34 email: info@becker-hickl.de http://www.becker-hickl.de PCSAPP.DOC PCS-150 / PCI-200 High Speed Boxcar Modules

More information

WaveStation Function/Arbitrary Waveform Generators

WaveStation Function/Arbitrary Waveform Generators Function/Arbitrary Waveform Generators Key Features High performance with 14-bit waveform generation, up to 500 MS/s sample rate and up to 512 kpts memory 2 channels on all models Large color display for

More information

ORTEC Experiment 3. Gamma-Ray Spectroscopy Using NaI(Tl) Equipment Required. Purpose. Gamma Emission

ORTEC Experiment 3. Gamma-Ray Spectroscopy Using NaI(Tl) Equipment Required. Purpose. Gamma Emission ORTEC Experiment 3 Equipment Required Electronic Instrumentation o SPA38 Integral Assembly consisting of a 38 mm x 38 mm NaI(Tl) Scintillator, Photomultiplier Tube, and PMT Base with Stand o 4001A/4002D

More information

Model 566 Time-to-Amplitude Converter (TAC) Operating and Service Manual

Model 566 Time-to-Amplitude Converter (TAC) Operating and Service Manual Model 566 Time-to-Amplitude Converter (TAC) Operating and Service Manual Printed in U.S.A. ORTEC Part No. 678950 0411 Manual Revision F Advanced Measurement Technology, Inc. a/k/a/ ORTEC, a subsidiary

More information

Figure 1-1. The ISIS Neutron Beam Monitor scintillator array. Operational Guide for the ISIS Neutron Beam Monitor

Figure 1-1. The ISIS Neutron Beam Monitor scintillator array. Operational Guide for the ISIS Neutron Beam Monitor Figure 1-1. The ISIS Neutron Beam Monitor scintillator array. Operational Guide for the ISIS Neutron Beam Monitor www.quantumdetectors.com Contents 1. Package contents... 1 2. Quick setup guide... 2 3.

More information

1510A PRECISION SIGNAL SIMULATOR

1510A PRECISION SIGNAL SIMULATOR A worldwide leader in precision measurement solutions Portable signal source for calibrating electronic equipment and machinery monitoring systems. 1510A PRECISION SIGNAL SIMULATOR Voltage Signals Charge

More information

Specifications. PCI Bus. Analog Input Input Characteristics

Specifications. PCI Bus. Analog Input Input Characteristics Specifications A This appendix lists the specifications of the NI 6034E/6035E/6036E. These specifications are typical at 25 C unless otherwise noted. The first section provides the specifications for the

More information

WaveStation Function/Arbitrary Waveform Generators

WaveStation Function/Arbitrary Waveform Generators WaveStation Function/Arbitrary Waveform Generators Key Features High performance with 14-bit, 125 MS/s and 16 kpts 2 channels on all models Large 3.5 color display for easy waveform preview Over 40 built-in

More information

User Guide. SIB Channel MAPMT Interface Board Hamamatsu H7546 series

User Guide. SIB Channel MAPMT Interface Board Hamamatsu H7546 series SIB164-1018 64 Channel MAPMT Interface Board Hamamatsu H7546 series Disclaimer Vertilon Corporation has made every attempt to ensure that the information in this document is accurate and complete. Vertilon

More information

Physical Properties Measurement System (PPMS): Detailed specifications: Basic unit cryogen- free

Physical Properties Measurement System (PPMS): Detailed specifications: Basic unit cryogen- free Physical Properties Measurement System (PPMS): A Cryogen-free Physical Properties Measurement system that operates over a wider range of temperature and magnetic fields: fully automated/computer controlled

More information

ORTEC Experiment 9. Time Coincidence Techniques Applied to Absolute Activity Measurements. Equipment Required. Purpose.

ORTEC Experiment 9. Time Coincidence Techniques Applied to Absolute Activity Measurements. Equipment Required. Purpose. ORTEC Experiment 9 Equipment Required 905-3 2-inch x 2-inch (5.08-cm x 5.08-cm) NaI(Tl) Detector and PM Tube Assembly. 266 PhotoMultiplier Tube Base. Two 113 Preamplifiers. BA-015-050-1000 Partially-Depleted

More information

WORLD-BEAM QS18AFF200 Sensors with Foreground Suppression

WORLD-BEAM QS18AFF200 Sensors with Foreground Suppression WORLD-BEAM QS8AFF00 Sensors with Foreground Suppression Datasheet Compact sensors featuring extended range and foreground suppression mode Exceptional optical performance; up to 00 mm sensing range in

More information

IAEA Coordinated Research Project on Development of Harmonized QA/QC Procedures for Maintenance and Repair of Nuclear Instruments

IAEA Coordinated Research Project on Development of Harmonized QA/QC Procedures for Maintenance and Repair of Nuclear Instruments PROCEDURE: TEST PROCEDURE FOR GEIGER-MUELLER RADIATION DETECTORS Nº: MRNI-501 DECEMBER 2008 PAGE: 1 OF: 17 IAEA Coordinated Research Project on Development of Harmonized QA/QC Procedures for Maintenance

More information

Traditional analog QDC chain and Digital Pulse Processing [1]

Traditional analog QDC chain and Digital Pulse Processing [1] Giuliano Mini Viareggio April 22, 2010 Introduction The aim of this paper is to compare the energy resolution of two gamma ray spectroscopy setups based on two different acquisition chains; the first chain

More information

Model 276L Low-Power Photomultiplier Base Operating and Service Manual

Model 276L Low-Power Photomultiplier Base Operating and Service Manual Model 276L Low-Power Photomultiplier Base Operating and Service Manual Printed in U.S.A. ORTEC Part No. 762870 0702 Manual Revision C $GYDQFHG 0HDVXUHPHQW 7HFKQRORJ\,QF a/k/a/ ORTEC, a subsidiary of AMETEK,

More information

SAS-562B Active Loop Antenna Operation Manual

SAS-562B Active Loop Antenna Operation Manual SAS-562B Active Loop Antenna Operation Manual 1 TABLE OF CONTENTS INTRODUCTION 3 SPECIFICATIONS 5 OPERATING INSTRUCTIONS 7 CALCULATIONS 11 ANTENNA FORMULAS 12 MAINTENANCE 13 WARRANTY 14 2 INTRODUCTION

More information

LUDLUM MODEL Low Energy Beta-Gamma Detector. December 2012 Serial No. PR and Succeeding Serial Numbers

LUDLUM MODEL Low Energy Beta-Gamma Detector. December 2012 Serial No. PR and Succeeding Serial Numbers LUDLUM MODEL 44-21 Low Energy Beta-Gamma Detector Serial No. PR 163027 and Succeeding Serial Numbers LUDLUM MODEL 44-21 Low Energy Beta-Gamma Detector Serial No. PR 163027 and Succeeding Serial Numbers

More information

Product Range Electronic Units

Product Range Electronic Units Pyramid Technical Consultants, Inc. 1050 Waltham Street Suite 200 Lexington, MA 02421 TEL: +1 781 402-1700 TEL (UK): +44 1273 492001 FAX: (781) 402-1750 EMAIL: SUPPORT@PTCUSA.COM Product Range Electronic

More information

Analog Arts SF990 SF880 SF830 Product Specifications

Analog Arts SF990 SF880 SF830 Product Specifications 1 www.analogarts.com Analog Arts SF990 SF880 SF830 Product Specifications Analog Arts reserves the right to change, modify, add or delete portions of any one of its specifications at any time, without

More information

1 Purpose of This Lab Exercise:

1 Purpose of This Lab Exercise: Physics 4796 - Experimental Physics Temple University, Spring 2010-11 C. J. Martoff, Instructor J. Tatarowicz, TA Physics 4796 Lab Writeup Hunting for Antimatter with NaI Spectroscopy 1 Purpose of This

More information

AMP-12 OPERATOR S MANUAL

AMP-12 OPERATOR S MANUAL AMP-12 OPERATOR S MANUAL Version 1.0 Copyright 2002 by Vatell Corporation Vatell Corporation P.O. Box 66 Christiansburg, VA 24068 Phone: (540) 961-3576 Fax: (540) 953-3010 WARNING: Read instructions carefully

More information

CT-2 and CT-3 Channel Taggers OPERATION MANUAL

CT-2 and CT-3 Channel Taggers OPERATION MANUAL CT-2 and CT-3 Channel Taggers OPERATION MANUAL Trilithic Company Profile Trilithic is a privately held manufacturer founded in 1986 as an engineering and assembly company that built and designed customer-directed

More information

Analog Arts SF900 SF650 SF610 Product Specifications

Analog Arts SF900 SF650 SF610 Product Specifications www.analogarts.com Analog Arts SF900 SF650 SF610 Product Specifications Analog Arts reserves the right to change, modify, add or delete portions of any one of its specifications at any time, without prior

More information

Analog Arts SL987 SL957 SL937 SL917 Product Specifications [1]

Analog Arts SL987 SL957 SL937 SL917 Product Specifications [1] www.analogarts.com Analog Arts SL987 SL957 SL937 SL917 Product Specifications [1] 1. These models include: an oscilloscope, a spectrum analyzer, a data recorder, a frequency & phase meter, an arbitrary

More information

CC2 Charge Sensitive Preamplifier: Experimental Results and Ongoing Development

CC2 Charge Sensitive Preamplifier: Experimental Results and Ongoing Development GERDA Meeting at LNGS - 2 / 2010 CC2 Charge Sensitive Preamplifier: Experimental Results and Ongoing Development Stefano Riboldi, Alessio D Andragora, Carla Cattadori, Francesca Zocca, Alberto Pullia Starting

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) Electric and Magnetic Field Measurement For Isotropic Measurement of Magnetic and Electric Fields Evaluation of Field

More information

Digital Signal Processing for HPGe Detectors

Digital Signal Processing for HPGe Detectors Digital Signal Processing for HPGe Detectors David Radford ORNL Physics Division July 28, 2012 HPGe Detectors Hyper-Pure Ge (HPGe) detectors are the gold standard for gamma-ray spectroscopy Unsurpassed

More information

Model Hz to 10MHz Precision Phasemeter. Operating Manual

Model Hz to 10MHz Precision Phasemeter. Operating Manual Model 6610 1Hz to 10MHz Precision Phasemeter Operating Manual Service and Warranty Krohn-Hite Instruments are designed and manufactured in accordance with sound engineering practices and should give long

More information

Operation and Service Manual. 350 MHz Preamplifier SIM914. Stanford Research Systems

Operation and Service Manual. 350 MHz Preamplifier SIM914. Stanford Research Systems Operation and Service Manual Stanford Research Systems Revision 1.8 August 24, 2006 Certification Stanford Research Systems certifies that this product met its published specifications at the time of shipment.

More information