Challenges of Parallel Operations

Size: px
Start display at page:

Download "Challenges of Parallel Operations"

Transcription

1 GENLINK TM issimilar Pitch Limiter Key Features Inserts >40% impedance in neutral current circulating path Reduces neutral circulating current by >75% Adds <1% saturated impedance to 1-Ph fault path No impedance to 3-Ph fault path Use in 3-wire or 4-wire applications or any parallel source application with a common neutral and dissimilar voltage waveforms Eliminates generator overheating and false protection trips caused by triple frequency circulating currents Easy to install Reliable and proven performance Challenges of Parallel Operations hen paralleling equipment such as generators or other distributed generation sources to each other or the utility supply, it is imperative that voltages produced by the generating equipment are as closely matched as possible. This means not only the RMS voltage values but the actual voltage waveshapes as well. Given the increased usage of this equipment, there are many paralleling applications where the voltage waveshapes can be dissimilar, resulting in high neutral circulating currents. Common reasons for these differences include: 1. Using generators with different pitch configurations made by different manufacturers or by the same manufacturer who has changed its standard pitch designs 2. Solar, wind or other alternative energy sources which use inverters to convert C power to AC for connection to the Utility To solve these challenges, Mirus GENLINK issimilar Pitch Limiter (PNL) is a multiple winding reactor which is installed in the common neutral of paralleled sources. Treating Circulating Current Generators with different pitch configurations will have slightly different voltage waveshapes. These differences can produce phase-to-neutral instantaneous voltages which can introduce heavy neutral circulating currents which are predominantly triple frequency. Mirus GENLINK, once installed in the common neutral of paralleled generators, adds impedance to block the flow of circulating currents while adding only minimal impedance to the flow of fault current. If left untreated, these circulating currents can cause overheating in the generator windings and false tripping of overcurrent protection equipment, especially ground fault detection schemes. Applications GENLINK can be used in both 3-wire and 4-wire systems. In both systems, GENLINK is used when two or more generators of dissimilar pitch are paralleled together or a generator is paralleled with an alternate source, such as the Utility. PNL is then inserted in the neutral between the dissimilar generators or the generator and Utility supply. For 4-wire applications where there is return neutral current from 1-Ph loads, GENLINK must be sized for this current as well as the circulating current. For 3-wire applications where there is no return neutral current from 1-Ph loads, a smaller size GENLINK can be used. In addition to dissimilar pitched generator applications, GENLINK can also be applied to various parallel source applications with common neutral and dissimilar voltage waveforms.

2 General Specifications: 690V or less, 3-phase, 3 or 4 wire, 60 or 50Hz Operating Temp. Rise 130 o C (Max. Ambient of 40 o C) Insulation Class 220 o C System Connection Series connected in the common neutral of generator groups with dissimiliar winding pitches Equiv. Efficiency at Full Load > 99% Through Impedance (%Z) Y-Z Term: ~ 45% X-Y or X-Z Term: ~ 1% (saturated) inding Material Insulating Varnish Impregnation Polyester Resin Audible Sound Level As per NEMA ST-20 & CSA C9 Based on equivalent kva Ventilation Type: Nema-3R, ventilated Temperature Switches 170 o C [ o C] Over-Temperature Alarm ALM2: Over-Temperature Alarm with horn and flashing light (requires separate power, supplied by customer) 'MT & LT' Front View H Side View Return Return MT1 LT1 Circulating Circulating * Estimated values. INSTALLATION IN A 3-IRE SYSTEM INSTALLATION IN A 4-IRE SYSTEM H (Height) [737] [965] [1143] [1308] [1499] MIRUS 31 Sun Pac Blvd Brampton, Ontario Canada L6S 5P6 PNL Rating Table [60Hz] Total Capacity of all Paralleled Sources k [kva] V V V V 68 [85] [312] 320 [400] 360 [450] 160 [] 640 [800] 800 [] 900 [1120] 335 [420] 1280 [1600] 1600 [0] 1800 [2] [625] 0 [2] 2400 [3000] 2720 [3400] 675 [840] 2 [3126] 3 [4000] 3600 [4] 840 [1050] 3 [4000] 4000 [0] 4 [5625] [1] 3800 [4750] 4800 [6000] 5475 [6843] PNL Rating Table [50Hz] Total Capacity of all Paralleled Sources k [kva] V V V V 68 [85] [312] 320 [400] 360 [450] 160 [] 640 [800] 800 [] 900 [1120] 335 [420] 1280 [1600] 1600 [0] 1800 [2] [625] 0 [2] 2400 [3000] 2720 [3400] 675 [840] 2 [3126] 3 [4000] 3600 [4] 840 [1050] 3 [4000] 4000 [0] 4 [5625] [1] 3800 [4750] 4800 [6000] 5475 [6843] Product Code: (idth) [425] [661] [813] [1003] imensions (epth) [381] [495] [534] [648] [762] Size (Return Amps),,, 1 0, 2, 3000 All standard voltages up to 690VAC Tel:(905) Fax:(905) Toll Free: TO MIRUS mirus@mirusinternational.com ebsite: MT1 Center [349] [432] [610] PNL - aaa - vvv - Hz - En issimiliar Pitch Limiter PH A PH B PH C PH A PH B PH C N GEN. 3 ( 2/3 PITCH ) GEN. 1 ( 2/3 PITCH ) GEN. 1 ( 2/3 PITCH ) Y Z X GEN. 2 ( 5/6 PITCH ) 150 [68] 330 [150] 408 [185] [227] 560 [254] 725 [329] 1169 [530] GENLINK (PNL) GEN. 4 GENLINK (PNL) Y Z X MT1 eight* lbs [kg] eight* lbs [kg] 160 [73] 262 [119] 527 [239] 680 [309] 749 [340] 863 [392] 1241 [563] ( 5/6 PITCH ) GEN. 2 ( 5/6 PITCH ) Frequency 50, 60 E0 = No E1 = Standard E1E = Type 3R Enhanced Full Load (atts) Full Load (atts) Center [330] [445] [483] [813] PNL-PS01-A4 Effective: ecember 2012 C Mirus All specifications subject to change without notice. Visit for the latest information.

3 MIRUS 31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6 TECHNICAL ATA PNL ISSIMILAR PITCH NEUTRAL LIMITING REACTOR GENERAL SPECIFICATIONS: VOLTAGE 690V or less, 3-ph, 3 or 4-wire, 60 or 50Hz OPERATING TEMPERATURE RISE 130 C (Max. Ambient of 40 deg C) INSULATION CLASS 220 C SYSTEM CONNECTION Series connected in the common neutral of generator groups with dissimilar winding pitches EQUIV. EFFICIENCY AT FULL LOA > 99% THROUGH IMPEANCE (%Z) [4] Y-Z Term: ~ 45% X-Y or X-Z Term: ~ 1% (saturated) INING MATERIAL INSULATING VARNISH IMPREGNATION Polyester Resin AUIBLE SOUN LEVEL As per NEMA ST-20 & CSA C9 Based on equivalent kva VENTILATION INING MATERIAL ENCLOSURE Type: NEMA-3R, ventilated TEMPERATURE SITCHES 170 C [ C] OVER-TEMPERATURE ALARM ALM2: Over-Temperature Alarm with horn and flashing light (requires separate power, supplied by customer) MT1, ENCLOSURE Sizes [ 60Hz ] Losses Connections Mechanical Lugs Provided PNL Rating [3] Return Circu- Total Capacity of all Paralleled Sources [2] Full k [kva] eight Load lb [kg] [1] (atts) [1] lating V V V V Y and Z Terminals X Terminal [85] [312] 320 [400] 360 [450] MT1 150 [68] 150 MCM-#6 MCM-#6 160 [] 640 [800] 800 [] 900 [1120] 330 [150] MCM-#2 2x600MCM-#2 335 [420] 1280 [1600] 1600 [0] 1800 [2] 408 [185] 515 2x350MCM-#6 4x350MCM-# [625] 0 [2] 2400 [3000] 2720 [3400] [227] 765 Pad Pad [840] 2 [3126] 3 [4000] 3600 [4] 560 [254] 800 Pad Pad [1050] 3 [4000] 4000 [0] 4 [5625] 725 [329] 965 Pad Pad [1] 3800 [4750] 4800 [6000] 5475 [6843] 1169 [530] 1120 Pad Pad PNL Rating [3] Return Circu- Total Capacity of all Paralleled Sources [2] Full k [kva] eight Load lb [kg] [1] (atts) [1] lating V V V V Y and Z Terminals Sizes [ 50Hz ] Losses Connections Mechanical Lugs Provided X Terminal [85] 120 [150] 320 [400] 360 [450] MT1 160 [73] 210 MCM-#6 MCM-#6 160 [] 300 [375] 800 [] 900 [1120] 262 [119] MCM-#2 2x600MCM-#2 335 [420] 620 [775] 1600 [0] 1800 [2] 527 [239] 630 2x350MCM-#6 4x350MCM-# [625] 920 [1150] 2400 [3000] 2720 [3400] 680 [309] 850 Pad Pad [840] 1 [1] 3 [4000] 3600 [4] 749 [340] 1050 Pad Pad [1050] 1540 [1930] 4000 [0] 4 [5625] 863 [392] 1 Pad Pad [1] 1840 [2300] 4800 [6000] 5475 [6843] 1241 [563] 1350 Pad Pad CASE STYLE ENCLOSURE IMENSIONS - Standard Enhanced A B C E F G MT1 MT1-E [737] [425] [381] [483] [349] [330] [495] -E [965] [495] [432] [445] [635] -E [1143] [661] [534] [635] [483] -E [1308] [813] [648] [749], ENCLOSURE Notes: 1. Estimated values. 2. To size the PNL, determine the total capacity in k or kva of all paralleled generators. Select the PNL that corresponds to this value in the appropriate system voltage column. This will size the unit for a return neutral current rating that is at least 50% of the full current rating of the application. For V and V units, the return neutral rating will be at least 85% of the full current rating. 3. It is the Users responsibility to ensure that the actual return neutral current will not exceed the rating of the PNL. If the return neutral current from all phase-to-neutral loads in 4-wire applications is expected to exceed the recommended PNL rating, then select a larger size PNL or use a Mirus NCE-FAI to reduce neutral current (consult factory for sizing). For 3-wire applications, or applications where return neutral current is known to be lower, the next smaller size can be selected. 4. The high impedance between Y-Z terminals prevents the flow of circulating current (predominantly triplen frequency) between the dissimilarly pitched generator groups. X-Y and X-Z impedances are the values to be used for 1-phase fault level calculations and are with core saturated. The PNL will have no effect on 3-phase fault level. 5. PNL is inserted in the common neutral where two or more generators of dissimilar pitch are connected together (see Connection iagrams) or where generators are paralleled with an alternate source, such as the Utility. The PNL is inserted in the neutral between the dissimilar groups. 6. The neutral should be grounded in only one location. If grounded at the switchboard or any other location, terminal X on the PNL should not be grounded. 7. For additional information refer to: Typical Specifications, Application Notes, Internal Layout and Connection iagrams. 8. End User is responsible for ensuring that the PNL installation and wiring satisfies all applicable electrical and safety code requirements. 9. Specifications are subject to change without notice. Mirus [ ] TO MIRUS PNL-S002-A6

4 INVERSINE TM Advanced Universal Sine-wave Filter Problems Associated with PM Inverter Operation Pulse idth Modulated (PM) output voltage waveform of inverter equipped Adjustable Speed rive (AS) systems can greatly stress a standard induction motor. This is primarily due to the rapid change in voltage (high dv/dt) produced by the inverter s switching action. High dv/dt combined with a mismatch between cable and motor surge impedance can result in reflective wave phenomenon back at the motor terminals. s can increase by as much as 2 to 3 times nominal peak levels possibly exceeding the insulation rating of the feeder cables and motor magnetic wire leading to insulation stress, partial discharges and eventual failure. This problem can result with short cable runs but becomes magnified with long cable runs. Key Features Low insertion loss and voltage drop (<2% of rated voltage) No damping resistors required Power delivered to motor >96% Efficiency >98% Improves Power Factor of the motor near unity Reactive power compensation Prevents transient overvoltages at motor terminals Reduces motor noise Filters out high frequency currents while allowing lower fundamental currents to pass Reliable and proven performance Inversine Applications hen Motor does not have adequate insulation for AS duty Using a number of parallel motors Long Motor cable length hen Step-up/Step-down transformer is used between AS and motor There are specific requirements for peak voltage level and dv/dt rise time Motor noise needs to be reduced Maximum safety and reliability is needed in hazardous environments Submersible pumps with long motor cables used in the oil & gas industry Typical problems experienced can include motor and winding failure, motor noise, cable insulation degradation, premature AS failure, common-mode and reflected wave phenomenon and high EMI/RFI. INVERSINE ifferential Mode The Inversine Advanced Universal Sine-wave Filter (AUSF) is designed to address the problems resulting from pulse width modulation. It is a low pass filter with cutoff frequency well below the switching frequency of the inverter. The AUSF is much more than a simple dv/dt filter and will: substantially reduce voltage rise time (dv/dt) convert output voltage to near sinusoidal waveform (<3%) prevent transient overvoltages at motor terminals lower harmonic losses in the motor reduce motor noise reduce motor and cable insulation stress extend life of the motor and AS INVERSINE Common-mode Option Common-mode is the phase-to-ground voltage that appears as a result of the instantaneous sum of the 3-phase voltages of the PM inverter not being zero even when the sum of the average 3-phase voltages is zero. Common-mode voltages will induce common-mode currents to flow through parasitic capacitance in the motor and motor feeder cable. High frequency capacitive coupling exists across the motor bearings and between the feeder conductor or motor winding and ground. Common-mode currents can lead to premature motor bearing failure. The Inversine Common-mode Filter option will: Reduce shaft voltage and bearing currents Reduce cable leakage currents Reduce common-mode voltages throughout power system

5 General Specifications: Standard voltage up to 690V, 3-phase, 60 or 50Hz Overload Capability Suitable for overload of % for 180 seconds every 10 minutes Switching Frequency 2kHz to 8kHz or [8kHz to 16kHz] Motor Frequency 0Hz to 90Hz istortion (TH) Max. 5% (at full load and at 60Hz) Input Current istortion <8% at full load Efficiency >98% inding Material Operating Ambient Temperature -20 o C to +40 o C (-4 o F to 104 o F) Elevation < m (3300ft) above sea level Ventilation Type: Nema-3R, ventilated all Capability: 5 to 125HP Motor Size HP k * Estimated values. 'SU H AUSF Rating Table [60Hz] Output Amps [A] 3Ph/60Hz 480V 600V 690V 'MT, LT LT1 H eight* lbs [kg] 58 [26] 67 [30] 78 [35] 90 [41] 118 [54] 130 [59] 142 [65] 154 [70] 186 [84] 218 [99] 304 [138] 323 [147] 345 [156] 365 [166] 415 [189] 578 [262] 585 [266] 800 [363] 825 [374] 915 [415] 1398 [634] Options Nema-3R Enhanced Outdoor Ventilated Front View Side View Front View Side View Typical INVERSINE TM Configuration Input VS TM INVERSINE AUSF MOTOR SU3 LT1 H (Height) [749] [864] [965] [1143] [1308] [1499] Product Code: Advanced Universal Sine-wave Filter MIRUS 31 Sun Pac Blvd. Brampton, Ontario Canada L6S 5P6 (idth) [286] [336] [514] [661] [813] [1003] All standard voltages up to 690VAC imensions (epth) [286] [324] [406] [495] [534] [648] [762] Motor Horsepower 5 to 600 HP Tel:(905) Fax:(905) Toll Free: TO MIRUS mirus@mirusinternational.com ebsite: Center 9.00 [229] [279] [457] [432] [610] AUSF - HP - vvv - Ff - En - O Switching Frequency 1 = 2 to 8 khz 2 = 8 to 16 khz Center 8.50 [216] [254] [330] [445] [483] [610] Nominal Frequency 5 = 50Hz 6 = 60Hz Options E0 = No E1 = Standard E1E = Type 3R Enhanced AUSF-PS01-A3 Effective: March 2013 C Mirus All specifications subject to change without notice. Visit for the latest information.

6 MIRUS 31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6 TECHNICAL ATA INVERSINE TM _ Advanced Universal Sine-wave Filter (AUSF) 5 to 600HP GENERAL SPECIFICATIONS: RATING For motor/drive system sizes 5HP(3.75k) to 600HP(450k) [8] VOLTAGE Standard voltages up to 690V OVERLOA CAPABILITY Suitable for overload of % for 180 seconds every 10 minutes SITCHING FREQUENCY 2 khz to 8 khz [8kHz to 16kHz] MOTOR FREQUENCY 0 Hz to 90 Hz VOLTAGE ISTORTION (TH) Max. 5% (at Full Load and at 60Hz) INPUT CURRENT ISTORTION < Full Load EFFICIENCY > 98% OPERATING AMBIENT TEMPERATURE -20 C to +40 C (-4 F to 104 F) ELEVATION 3300ft [m] above sea level VENTILATION INING MATERIAL ENCLOSURE Type: NEMA-3R (5 600HP) all Mtg Capability: 5 to 125HP OPTIONS: NEMA-3R Enhanced Outdoor Ventilated Motor Size Filter Rating Standard Output Amps [3] [9] eight HP k lb [kg] [7] 480V 3Ph/60Hz 600V 3Ph/60Hz 690V 3Ph/60Hz [26] [30] [35] [41] [54] [59] [65] [70] [84] [99] [138] [147] [156] [166] [189] [262] [266] [363] [374] [415] LT [634] CASE ENCLOSURE IMENSIONS - STYLE A B C E F G H [286] 8.75 [222] [286] 9.00 [229] 8.50 [216] [305] 9.00 [228] [749] [336] [260] [324] [279] [254] [406] [279] SU [864] [514] [336] [406] [457] [330] [508] [457] [965] [495] [432] [445] [635] [1143] [661] [534] [635] [483] [1308] [813] [648] [749] LT [1499] [1003] [762] [864] [610] [813] SU ENCLOSURE MT, LT ENCLOSURE Notes: 1. Select Inversine Filter based on current rating of the motor for both variable and constant torque applications. 2. here a single Inversine Filter is used to supply multiple motors, the Inversine Filter current rating must sized for the total current rating of all motors. 3. For applications that exceed NEC ratings, use next larger size Inversine Filter. 4. For power inverter applications with isolation transformer or step-up transformer, the Inversine Filter current rating should be equal to or greater than that of the transformer nominal primary current. 5. For AS switching frequency below 2kHz, please consult factory. 6. Short circuit current rating not required under the exception No.1 of UL508A SB Approximate Values. 8. Specifications are subject to change without notice. 9. Cable entry is from left or right side only unless otherwise indicated. 10. For additional information refer to: Typical Specifications, Internal Layout and Connection iagrams. Mirus [ ] TO MIRUS AUSF-S001-A3

Electromagnetic Harmonic Filters Technical Guide

Electromagnetic Harmonic Filters Technical Guide Eliminator Series Electromagnetic Harmonic Filters Technical Guide Neutral Current Eliminator TM (NCE TM ) Parallel connected, 3-phase, 4-wire passive electromagnetic device that diverts 3rd and other

More information

LINEATOR. Advanced Universal Harmonic Filter

LINEATOR. Advanced Universal Harmonic Filter R International Inc. LINEATOR Patented Revolutionary New Reactor esign Advanced Universal Harmonic Filter Wide Spectrum Harmonic Filter for treatment of all harmonics generated by 3-phase diode or thyristor

More information

Lineator-HP High Performance model used where the highest power quality demands must be met

Lineator-HP High Performance model used where the highest power quality demands must be met LINEATOR TM Advanced Universal Harmonic Filter The LINEATOR Advanced Universal Harmonic Filter (AUHF) is a revolutionary advancement in the area of passive harmonic mitigation. No other device on the market

More information

SWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

SWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) SWF DV/DT Solutions Sinewave Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Does your application use variable frequency drives for improved

More information

Electromagnetic Harmonic Filters Technical Guide

Electromagnetic Harmonic Filters Technical Guide Eliminator Series Electromagnetic Harmonic Filters Technical Guide Neutral Eliminator TM (NCE TM ) Parallel connected, 3-phase, 4-wire passive electromagnetic device that diverts 3rd and other triplen

More information

Low Pass Harmonic Filters

Low Pass Harmonic Filters Exclusive e-rated Provider PRODUCT SHEET HARMITIGATOR TM Low Pass Harmonic Filters A solution for electrical distribution systems that require stable, reliable power, characterized by unparalleled power

More information

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company P2 Power Solutions Pvt. Ltd. An ISO 9001:2008 Company Quality Power within your Reach P2 Power Magnetics P2 Power Solutions Pvt. Ltd. P2 Power Solutions Pvt. Ltd. provides EMC and power quality solutions,

More information

Lineator-HP High Performance model used where the highest power quality demands must be met

Lineator-HP High Performance model used where the highest power quality demands must be met LINATOR TM Advanced Universal Harmonic Filter The LINATOR Advanced Universal Harmonic Filter (AUHF) is a revolutionary advancement in the area of passive harmonic mitigation. No other device on the market

More information

MTE training MTE Corporation

MTE training MTE Corporation 1 MTE Corporation Improving the Performance and Reliability of Power Electronic Systems 2 MTE solutions to Long lead dive applications Protection of motors drive cables and Variable frequency inverters

More information

High Frequency SineWave Guardian TM Filter

High Frequency SineWave Guardian TM Filter High Frequency SineWave Guardian TM Filter 380V 480V TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference

More information

High Frequency Sinewave Guardian TM Filter

High Frequency Sinewave Guardian TM Filter High Frequency Sinewave Guardian TM Filter 380V 480V TECHNICAL REFERENCE MANUAL FORM: SHF-TRM-E REL. April 2015 REV. 001 2015 MTE Corporation Caution Prior to start up; confirm the drive operation mode

More information

AF91 Adjustable Frequency Drives Series B

AF91 Adjustable Frequency Drives Series B Effective: January, 00 Page New Information AF9 Adjustable Model AF9 Description Model AF9 Adjustable Frequency AC Drives are designed to provide adjustable speed control of -phase motors. These microprocessor-based

More information

External Drive Hardware

External Drive Hardware US1086e_External Drive Hardware, 08/2010 External Drive Hardware Selection and Application Answers Answers to external hardware questions A soup to nuts list of questions with installation / application

More information

Application Note. Applicable Product: AC Drives

Application Note. Applicable Product: AC Drives Application Note Application Note Guidelines For The Use Of 400-600 Volt AC Drives In Medium Voltage Applications Applicable Product: AC Drives 4kV Step-down Transformer AC Drive 400-600V Output Filter

More information

Harmonic Mitigating Transformer - Technical Guide

Harmonic Mitigating Transformer - Technical Guide Harmonic Mitigating - Technical Guide HARMONY Series s HARMONY-1 www.mirusinternational.com Benefits: Prevent voltage flat-topping while reducing energy costs. Reduce voltage distortion caused by harmonic

More information

Harmonics White Paper

Harmonics White Paper Harmonics White Paper New Breakthrough In PWM Drives Technology Reduces Input Line Harmonics Without the Use of Filtering Devices Harmonic Distortion Damages Equipment and Creates a Host of Other Problems

More information

Power Processor - Series 700F 10KVA to 150KVA

Power Processor - Series 700F 10KVA to 150KVA Power Processor - Series 700F 10KVA to 150KVA Power Conditioning and Regulation for Commercial & Industrial Equipment General Specifications PART 1 - GENERAL 1.1 DESCRIPTION This specification defines

More information

Power Quality Solutions

Power Quality Solutions Power Quality Solutions What is Power Quality? For electrical systems to function in their intended manner without significant loss of performance or life, they require a supply of electricity that is

More information

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads. -156 Purpose & Industrial Control Purpose (1000 kva and Below) mounted dry-type transformers of the two-winding type, self-cooled, with ratings and voltages as indicated on the drawings. shall be manufactured

More information

Tab 2 Voltage Stresses Switching Transients

Tab 2 Voltage Stresses Switching Transients Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles

More information

The Reflective Wave Phenomena

The Reflective Wave Phenomena Application Note The Reflective Wave Phenomena Rev2.doc The Reflective Wave Phenomena Note to Specifiers This application note contains Cutler-Hammer s recommendations for the application of filters for

More information

LOW VOLTAGE PWM INVERTER-FED MOTOR INSULATION ISSUES

LOW VOLTAGE PWM INVERTER-FED MOTOR INSULATION ISSUES LOW VOLTAGE PWM INVERTER-FED MOTOR INSULATION ISSUES Copyright Material IEEE Paper No. PCIC-4-15 RAPS-1433 Abstract - The topic of how low voltage IGBT-based PWM inverters create additional insulation

More information

Dry Type Distribution Transformers NON-LINEAR TRANSFORMER PRESENTATION

Dry Type Distribution Transformers NON-LINEAR TRANSFORMER PRESENTATION NON-LINEAR TRANSFORMER PRESENTATION 1 PROBLEM: HARMONICS CAUSE EXCESSIVE TRANSFORMER HEATING Increased Losses Proximity Skin Effect Stray Losses Circulating Effect Triplen Harmonics Add in Neutral Increased

More information

ULTRA-K Series 600K - he

ULTRA-K Series 600K - he 5 kva 500 kva ULTRA-K Series 600K - he High Efficiency K-Rated Power Conditioning Transformers Designed to be used with linear or non-linear loads. Applications: Audio / Video Recording Equipment IT Systems

More information

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 690 Volts, 50Hz

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 690 Volts, 50Hz POWER QUALITY INSTRUCTION MANUAL Type SWF Sine Wave Filters 690 Volts, 50Hz Page 2 of 24 Contents 1. Introduction & SAFETY 2. Theory of operation 3. Typical results of the Sine Wave Filters 4. Transportation,

More information

WDG 13 - Technical Data Sheet

WDG 13 - Technical Data Sheet LV 804 T WDG 13 - Technical Data Sheet FRAME LV 804 T SPECIFICATIONS & OPTIONS STANDARDS Cummins Generator Technologies industrial generators meet the requirements of BS EN 60034 and the relevant sections

More information

Harmonic Filters for Single Phase Equipment

Harmonic Filters for Single Phase Equipment POWER QUALITY Harmonic Filters for Single Phase Equipment Agriculture Call Centers Casino Slot Machines Computer Centers Distributed Generation Electronic Power Converter Oil & Gas On-Line UPS Power Electronics

More information

General Description & Features Selection Charts Definition of Terms... 42

General Description & Features Selection Charts Definition of Terms... 42 SECTION NON-LINEAR LOAD ISOLATION TRANSFORMERS Special winding techniques minimize eddy current losses. A double sized neutral handles excessive neutral currents. UL Listed for K Factor Loads 4, 1 & 20.

More information

CoolBLUE Inductive Absorbers NaLA Noise Line Absorbers

CoolBLUE Inductive Absorbers NaLA Noise Line Absorbers CoolBLUE Inductive Absorbers NaLA Noise Line Absorbers Motor Bearing Solution from MH&W International Corp. http://www.coolblue-mhw.com Variable Frequency Motor Drive Systems 1. What is the problem 2.

More information

HPS Universal BUCK-BOOST TRANSFORMERS

HPS Universal BUCK-BOOST TRANSFORMERS BUCK-BOOST TRANSFORMERS Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...

More information

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet LV 804 T WDG 12 - Technical Data Sheet FRAME LV 804 T SPECIFICATIONS & OPTIONS STANDARDS Cummins Generator Technologies industrial generators meet the requirements of BS EN 60034 and the relevant sections

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES

MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES White Paper Tim Wylie, Ampcontrol s Chief Technology Officer discusses the impact of Variable Speed Drives (VSDs) on earth fault limited networks.

More information

Phoenix DX Clean Power (18 Pulse) AC Drive

Phoenix DX Clean Power (18 Pulse) AC Drive PHOENIX DX Phoenix DX Clean Power (18 Pulse) AC Drive Poor power quality can be costly. Nonlinear loads, including AC Drives, introduce undesirable harmonic currents into the power system that can damage

More information

Alternator winding pitch and power system design

Alternator winding pitch and power system design Our energy working for you. TM Power topic #5981 Technical information from Cummins Power Generation Alternator winding pitch and power system design White Paper Rich Scoggins Applications Engineering

More information

WDG 71 - Technical Data Sheet

WDG 71 - Technical Data Sheet HV 804 R WDG 71 - Technical Data Sheet FRAME HV 804 R SPECIFICATIONS & OPTIONS STANDARDS Cummins Generator Technologies industrial generators meet the requirements of BS EN 60034 and the relevant sections

More information

WDG 61 - Technical Data Sheet

WDG 61 - Technical Data Sheet HV 804 W WDG 61 - Technical Data Sheet FRAME HV 804 W SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international

More information

WDG 07 - Technical Data Sheet

WDG 07 - Technical Data Sheet LV 804 S WDG 07 - Technical Data Sheet FRAME LV 804 S SPECIFICATIONS & OPTIONS STANDARDS Cummins Generator Technologies industrial generators meet the requirements of BS EN 60034 and the relevant sections

More information

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) APQline Active Harmonic Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Power electronic equipment and AC-DC power conversion equipment contribute

More information

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet LV 804 S WDG 12 - Technical Data Sheet FRAME LV 804 S SPECIFICATIONS & OPTIONS STANDARDS Cummins Generator Technologies industrial generators meet the requirements of BS EN 60034 and the relevant sections

More information

WDG 51 - Technical Data Sheet

WDG 51 - Technical Data Sheet MV 804 S WDG 51 - Technical Data Sheet FRAME MV 804 S SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international

More information

PI734F - Winding 28. Technical Data Sheet APPROVED DOCUMENT

PI734F - Winding 28. Technical Data Sheet APPROVED DOCUMENT - Winding 28 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international standards

More information

PI734E - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI734E - Winding 312. Technical Data Sheet APPROVED DOCUMENT - Winding 312 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international standards

More information

PI734C - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI734C - Winding 312. Technical Data Sheet APPROVED DOCUMENT - Winding 312 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international standards

More information

PI734B - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI734B - Winding 312. Technical Data Sheet APPROVED DOCUMENT - Winding 312 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international standards

More information

Power Quality. Answering Today s Power Challenges. Why Your Existing Transformer May Be Inadequate. How Harmonics Affect Transformers

Power Quality. Answering Today s Power Challenges. Why Your Existing Transformer May Be Inadequate. How Harmonics Affect Transformers Power Quality 13 Answering Today s Power Challenges Jefferson Electric is continually updating its product line to remain on the forefront of transformer technology. Electrical harmonics have become a

More information

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet LV 804 R WDG 12 - Technical Data Sheet FRAME LV 804 R SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international

More information

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet LV 804 W WDG 12 - Technical Data Sheet FRAME LV 804 W SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international

More information

WDG 83 - Technical Data Sheet

WDG 83 - Technical Data Sheet HV 804 R WDG 83 - Technical Data Sheet FRAME HV 804 R SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international

More information

Paralleling Dissimilar Generators: Part 2 Compatible Alternators

Paralleling Dissimilar Generators: Part 2 Compatible Alternators Our energy working for you. TM Power topic #9016 Technical information from Cummins Power Generation Paralleling Dissimilar Generators: Part 2 Compatible Alternators White Paper By Gary Olson, Director

More information

Power Factor. Power Factor Correction.

Power Factor. Power Factor Correction. Power Factor. Power factor is the ratio between the KW and the KVA drawn by an electrical load where the KW is the actual load power and the KVA is the apparent load power. It is a measure of how effectively

More information

Cable Solutions for Servo and Variable Frequency Drives (VFD)

Cable Solutions for Servo and Variable Frequency Drives (VFD) Cable Solutions for Servo and Variable Frequency Drives (VFD) Electric drive systems with continuous torque and speed control are widespread today. They allow an optimal adjustment of the drive with respect

More information

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888

More information

How Harmonics have led to 6 Power Factor Misconceptions

How Harmonics have led to 6 Power Factor Misconceptions Harmonic and Energy Saving Solutions How Harmonics have led to 6 Power Factor Misconceptions Tony Hoevenaars, P.Eng. Power Factor Misconceptions 1. Low power factor is normally caused by electric motors

More information

Generator Advanced Concepts

Generator Advanced Concepts Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves

More information

Operations Manual. Model NT11 & NT11-E. June 18 th 2002

Operations Manual. Model NT11 & NT11-E. June 18 th 2002 Operations Manual Model NT11 & NT11-E June 18 th 2002 3609 North 44 th Street Phoenix, AZ 85018-6023 Internet: www.northstarcontrols.com Fax: (941) 426-0807 Tel: (941) 426-6396 Manual Contents Glossary

More information

PI734F - Winding 07. Technical Data Sheet APPROVED DOCUMENT

PI734F - Winding 07. Technical Data Sheet APPROVED DOCUMENT - Winding 07 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 34 and the relevant sections of other national and international standards

More information

Electrical Submersible Pumping Systems

Electrical Submersible Pumping Systems Electrical Submersible Pumps (ESP) Electrical Submersible Pumping Systems Variable Speed Drive Halliburton s HAL 1200 electrical submersible pumping (ESP) system variable speed drive (VSD) provides a number

More information

PowerFlex 400 Submittal

PowerFlex 400 Submittal PowerFlex 400 Submittal Submittal Date: Project Name: Project Location: Consulting Engineer: Contractor: Contractor PO #: Distributor Name: Distributor Contact: Distributor Reference #: Note: This is general

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit. Current Transducer CTSR 0.6-TP/SP2 I PRN = 600 ma For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit. Features

More information

vacon 100 industrial vacon 100 flow vacon 100 hvac vacon 100 x ac drives du/dt filter technical guide

vacon 100 industrial vacon 100 flow vacon 100 hvac vacon 100 x ac drives du/dt filter technical guide vacon 100 industrial vacon 100 flow vacon 100 hvac vacon 100 x ac drives du/dt filter technical guide vacon 1 TABLE OF CONTENTS Document code: DPD01929A Date: 12.1.2017 1. Introduction... 2 1.1 Intended

More information

Dry Type Transformers Full Line Catalog. jeffersonelectric.com

Dry Type Transformers Full Line Catalog. jeffersonelectric.com Dry Type Transformers Full Line Catalog jeffersonelectric.com The Transformer Authority PIONEER TRANSFORMERS: Why us? Scale We produce over 100,000 transformers every year. With this high level of production

More information

Conventional Paper-II-2011 Part-1A

Conventional Paper-II-2011 Part-1A Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance

More information

Power Commander. Power Commander Plus. Electronic Line Voltage Regulators. 15 kva 150 kva SINGLE PHASE 15 kva 450 kva THREE PHASE SERIES 900

Power Commander. Power Commander Plus. Electronic Line Voltage Regulators. 15 kva 150 kva SINGLE PHASE 15 kva 450 kva THREE PHASE SERIES 900 15 kva 150 kva SINGLE PHASE 15 kva 450 kva THREE PHASE Power Commander SERIES 900 Power Commander Plus SERIES 900 / 200 Electronic Line Voltage Regulators Precise Electrical Power For Critical Loads Automatic

More information

6L]LQJ$8366\VWHP )RU1RQ/LQHDU/RDGV

6L]LQJ$8366\VWHP )RU1RQ/LQHDU/RDGV 6L]LQJ$8366\VWHP )RU1RQ/LQHDU/RDGV SOLIDSTATE CONTROLS, INC. Solidstate Controls Incorporated 875 Dearborn Drive Columbus, Ohio 43085 Tel : (614) 846-7500 Fax: (614) 885-3990 6L]LQJ $ 836 6\VWHP )RU 1RQ/LQHDU

More information

ADJUSTABLE SPEED DRIVES. W7 Series. 18 Pulse

ADJUSTABLE SPEED DRIVES. W7 Series. 18 Pulse ADJUSTABLE SPEED DRIVES W7 Series 18 Pulse Meets or Exceeds Your Specifications Standard Specifications Item Voltage Class 460V Maximum HP 60 75 100 125 150 200 250 300 400 500 600 700 800 Drive Rating

More information

Transformer Questions & Answers

Transformer Questions & Answers Transformer Questions & Answers. What is a transformer and how does it work? A transformer is an electrical apparatus designed to convert alternating current from one voltage to another. It can be designed

More information

HARMONICS CAUSES AND EFFECTS

HARMONICS CAUSES AND EFFECTS HARMONICS CAUSES AND EFFECTS What is Harmonics? Harmonics is defined as the content of the signal whose frequency is an integral multiple of the system frequency of the fundamentals. Harmonics current

More information

Description & Applications Questions & Answers Selection Charts Single Phase Selection Charts Three Phase...

Description & Applications Questions & Answers Selection Charts Single Phase Selection Charts Three Phase... SECTION BUCK-BOOST TRANSFORMERS A simple and economical way to correct offstandard voltages... from 95 to 500 volts; single and three phase, in sizes up to 60 kva. Simplified buck-boost rating charts make

More information

Transformer Questions & Answers

Transformer Questions & Answers Transformer Questions & Answers. What is a transformer and how does it work? A transformer is an electrical apparatus designed to convert alternating current from one voltage to another. It can be designed

More information

PM734D - Winding 312. Technical Data Sheet APPROVED DOCUMENT. Generator Solutions AS

PM734D - Winding 312. Technical Data Sheet APPROVED DOCUMENT. Generator Solutions AS PM734D - Winding 312 Technical Data Sheet PM734D SPECIFICATIONS & OPTIONS STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards and

More information

PM734F - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PM734F - Winding 312. Technical Data Sheet APPROVED DOCUMENT PM734F - Winding 312 Technical Data Sheet PM734F SPECIFICATIONS & OPTIONS STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards and

More information

Energy Efficient Distribution Transformers

Energy Efficient Distribution Transformers Energy Efficient Distribution Transformers Established in 1917, Hammond Power Solutions Inc. (HPS), is an industry leader in magnetic transformer design and development. With our headquarters in Guelph,

More information

MODELLING AND SIMULATION OF DIODE CLAMP MULTILEVEL INVERTER FED THREE PHASE INDUCTION MOTOR FOR CMV ANALYSIS USING FILTER

MODELLING AND SIMULATION OF DIODE CLAMP MULTILEVEL INVERTER FED THREE PHASE INDUCTION MOTOR FOR CMV ANALYSIS USING FILTER MODELLING AND SIMULATION OF DIODE CLAMP MULTILEVEL INVERTER FED THREE PHASE INDUCTION MOTOR FOR CMV ANALYSIS USING FILTER Akash A. Chandekar 1, R.K.Dhatrak 2 Dr.Z.J..Khan 3 M.Tech Student, Department of

More information

Amps Without HGA. Amps With HGA. Amps Without HSD Time (ms)

Amps Without HGA. Amps With HGA. Amps Without HSD Time (ms) Harmonic Solutions HarmonicGuard Active (HGA) Filter Save money and space: a single bus-applied HGA can correct harmonics for multiple loads Reduce current harmonic distortion to less than 5% allowing

More information

The Reflective Wave Phenomenon dv/dt and Reflective Wave unsuppressed causes Motor failures

The Reflective Wave Phenomenon dv/dt and Reflective Wave unsuppressed causes Motor failures TCI s KLC & KLCUL dv/dtguard Output Filters Provide Superior Patented Protection for Motors s the technology of Pulse Width Modulated (PWM) Drives are incorporated into various applications and processes,

More information

TOSHIBA International Corp

TOSHIBA International Corp TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200FA 30 kva CT Internal Battery UPS GUIDE SPECIFICATIONS 1 (30 kva CT) 1.0 SCOPE 1.1 System This specification

More information

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

FGJTCFWPKPUVKVWVGQHVGEJPQNQI[ FGRCTVOGPVQHGNGEVTKECNGPIKPGGTKPI VGG246JKIJXQNVCIGGPIKPGGTKPI FGJTFWP"KPUKWG"QH"GEJPQNQI[" FGRTOGP"QH"GNGETKEN"GPIKPGGTKPI" GG"46"JKIJ"XQNIG"GPIKPGGTKPI Resonant Transformers: The fig. (b) shows the equivalent circuit of a high voltage testing transformer (shown

More information

Power Quality Monitoring and Power Metering Tutorial

Power Quality Monitoring and Power Metering Tutorial Power Quality Monitoring and Power Metering Tutorial Power generation and transmission today are accomplished using three phase alternatingcurrent. To understand electrical power quality monitoring and

More information

A cost effective, compact and reliable PWM drive for 1/4 through 1 HP DC applications

A cost effective, compact and reliable PWM drive for 1/4 through 1 HP DC applications A cost effective, compact and reliable PWM drive for 1/4 through 1 HP DC applications The Micro 100 Drives have been designed with a Pulse Width Modulated (PWM) regulator to produce clean DC current to

More information

An Introduction to Power Quality

An Introduction to Power Quality 1 An Introduction to Power Quality Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation 3 Today s Presenter n Andy Sagl Megger

More information

Table of Contents. Facility EMI Filter Products

Table of Contents. Facility EMI Filter Products Table of Contents Filter Selection Guide Facility EMI Filters...............................................4, 5 Signal/Data/Control Filters........................................6, 7 Technical Notes................................................8,

More information

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing.

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing. 1.0 Scope This document describes the specification for Toshiba 1000 Series On-Line Uninterruptible Power System (UPS). The UPS will supply a computer grade AC output sine wave which is unaffected by the

More information

NSL-10 STANDARD LIFE MODULAR CAPACITORS

NSL-10 STANDARD LIFE MODULAR CAPACITORS ADVANCE P.F. CORRECTION SOLUTIONS FROM NEPTUNE-DUCATI Channel Partner Ph: 02621-234524, 99242 04524 Industrial Trading Co. 10B Dharma Super Market, Kim Char Rasta, Contact : Paresh Gandhi (98241 31205)

More information

BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY

BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY The BE1-87G is a single or three-phase solid-state variable percentage differential relay designed to provide selective, high-speed, differential protection

More information

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services edarat group INTRODUCTION Harmonics are a mathematical way of describing distortion

More information

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL SINGLE PHASE INSTRUCTION MANUAL DIAGRAM D This manual applies to all single-phase buck & boost transformers sold by Larson Electronics. Please refer to the connection diagram on pages 4-6 for properly

More information

PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator)

PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator) PRODUCT SPECIFICATION FOR A 15 THRU 500 kva, THREE PHASE, MODULAR POWER REGULATOR AND CONDITIONER PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator) 1.0 General This specification covers the electrical

More information

TMdrive -XL Series Family Product Application Guide. solar inverters. power generation

TMdrive -XL Series Family Product Application Guide. solar inverters. power generation TMdrive -XL Series Family Product Application Guide metals cranes mining testing oil & gas solar inverters power generation cement TMdrive-XL Series 8 MVA 15 MVA 20 MVA 30 MVA The TMdrive XL series family

More information

AV-300i Specifications. Saftronics Inc. PC10 Product Specifications PC10. Mini Vector AC Drive

AV-300i Specifications. Saftronics Inc.  PC10 Product Specifications PC10. Mini Vector AC Drive Saftronics Inc. www.saftronics.com TM AV-300i Specifications PC10 Product Specifications PC10 Mini Vector AC Drive 1 (1) T hree-phas e 230V input Drive Hp 1/8 1/4 1/2 1 2 3 5 7.5 10 Nominal applicable

More information

S11 Adjustable Speed Drive Engineering Specification

S11 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba S11 AC Variable Frequency Drives, 6 pulse for 3- phase 200-240VAC, 380-500VAC and single phase 200V to 240VAC. 1.1 References A. National

More information

VARIABLE FREQUENCY DRIVE SPECIFICATION

VARIABLE FREQUENCY DRIVE SPECIFICATION VARIABLE FREQUENCY DRIVE SPECIFICATION 1.0. SUMMARY The use of variable frequency drives (VFDs) in conjunction with wastewater lift stations has been identified as a means improve efficiency and to moderate

More information

EN 50178, IEC

EN 50178, IEC Type: DF51 322 1K5 Article No.: 289107 Sales text """Frequency inverter DF51(1,5 kw; 230V) Ordering information Rated voltage U e V Max. rated operational current I e A 7.1 Rated power for motors at 230

More information

Selected Problems of Induction Motor Drives with Voltage Inverter and Inverter Output Filters

Selected Problems of Induction Motor Drives with Voltage Inverter and Inverter Output Filters 9 Selected Problems of Induction Motor Drives with Voltage Inverter and Inverter Output Filters Drives and Filters Overview. Fast switching of power devices in an inverter causes high dv/dt at the rising

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and secondary circuit. Current Transducer LF 510-S I P N = 500 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and secondary circuit. Features Bipolar and insulated

More information

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24 LECTURER-24 GENERATION OF HIGH ALTERNATING VOLTAGES When test voltage requirements are less than about 300kV, a single transformer can be used for test purposes. The impedance of the transformer should

More information

PI734C - Technical Data Sheet

PI734C - Technical Data Sheet PI734C - Technical Data Sheet PI734C SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international

More information

ADJUSTABLE SPEED DRIVES. HX7 Series. 18-Pulse

ADJUSTABLE SPEED DRIVES. HX7 Series. 18-Pulse ADJUSTABLE SPEED DRIVES HX7 Series 18-Pulse Toshiba HX7 In some industrial applications, users need reliable and efficient adjustable speed drives that do not contribute significant harmonic distortion

More information

Drives 101 Lesson 3. Parts of a Variable Frequency Drive (VFD)

Drives 101 Lesson 3. Parts of a Variable Frequency Drive (VFD) Drives 101 Lesson 3 Parts of a Variable Frequency Drive (VFD) This lesson covers the parts that make up the Variable Frequency Drive (VFD) and describes the basic operation of each part. Here is the basics

More information

MODEL 503 DC BRUSHLESS SERVO AMPLIFIER

MODEL 503 DC BRUSHLESS SERVO AMPLIFIER FEATURES Complete torque ( current ) mode functional block Drives motor with 60 or 20 Halls Single supply voltage 8-DC A continuous, 0A peak more than double the power output of servo chip sets Fault protected

More information