cosø 1 Dp= K1 (cosø) 2 DV= K2 cosø

Size: px
Start display at page:

Download "cosø 1 Dp= K1 (cosø) 2 DV= K2 cosø"

Transcription

1 POWER FACTOR CORRECTION The power factor correction of electrical loads is a problem common to all industrial companies. Every user which utilizes electrical power to obtain work in various forms continuously asks the mains to supply a certain quantity of active power, together with reactive power. This reactive power is not transformed or used by the user, but the electricity supply company is forced to produce it, using generators, wires to carry and distribute it, transformers, switching gear, and so on. A= P cosø Naturally, as the cosø increases, the size of the plant is reduced. 2) The Power Loss (Dp) on the line is given by: G Active power M Reactive power 1 Dp= K1 (cosø) 2 The natural consequence is that the electricity supply company requires users to comply with a minimum power factor (cosø) below which a surcharge is imposed. where K1 is a ratio coefficient. It is immediately clear that an increase in the cosø leads to a considerable reduction in the power loss (Joule effect), and so the plant will cost less and last longer. 3) VOLTAGE DROP (DV) on line is as follows: DV= K2 1 cosø G Active power M Reactive power where K2 is a proportionality factor. This case too shows that an increase of cos reduces the online voltage drop, thus producing a better performance of the users since the voltage along the line is closer to the rated power. Moreover, the power factor correction can have other important results. 1) For any given Active Power (KW) the Apparent Power (KVA) is in reverse proportion to the cosø. A power factor correction system is properly dimensioned when both the quantitative and the qualitative aspects are considered. Thus, knowing the following items is necessary: 1) the power factor correction rate to be installed to eliminate surcharges, thanks to the consumption analysis; 2) ambient conditions as well as rating of the mains the condenser is going to operate on, in particular if any harmonics are present in the line. 2

2 Calculating of the kvar required Distributed power factor correction 1) Threephase induction motor: it is one of the most commonly found loads. In table 1 here below the power factor correction power required. The advantage is a power supply cable run by a lower current. HP Rated power KW THREEPHASE INDUCTION MOTOR 2 poles 00 rpm operation without load poles rpm operation without load poles rpm operation without load poles 7 rpm Tab. 1 operation without load Centralised power factor correction To achieve a precise calculation of the power factor correction needs for a system, the following items are needed: the maximum used power and the cos of the system; these values may be calculated from the invoices of the electricity supplier or by carrying out the necessary measurements. After calculating the cos value desired in the plant, by means of table 3 the coefficient K is determined: it is used to multiply the used kws to calculate the power factor correction kvar. For example: a plant using P = kw with cosø = 0.70 requires power factor correction to cosø = From the table 3 we obtain K = 0.66, and so the plant requires Q = x 0.66 = 6 kvar, at the mains voltage. If the power of the proposed power factor correction system refers to a voltage different from that of the mains, it should be accounted for by means of the following: For motors having wound rotor, these values should be increased by %. QVrif= QVrete Vrif Vrete 2 2) Idle transformer losses: idle running of the MT/BT transformer, possible during the night or holidays, absorbs low cos power and needs to undergo power factor correction. The necessary power may be calculated from table 2 if the rated power of the transformer and its primary voltage are known. Tab. 2 KVAR required for power factor correction of the losses without load of a MV/LV transformer For example: if the power of 6 kvar amounts to V and the power factor correction proposed is 4V, at least the following will have to be considered: Transformer power KVA PRIMARY VOLTAGE 6 kv 16 kv = 799kVAr 2 to compensate the load. advanced technology for electrical installations 3

3 POWER FACTOR CORRECTION ER = Reactive Energy EA = Active Energy tanj i = ER/EA tanji cosji KCoefficient to calculate reactive power cosj f values Tab The problem of harmonics Harmonics are produced by non linear loads, i.e.: office appliances (PCs, photocopy machines, etc.), gas discharge lamp, UPS, engines controlled by static converters, static converters, arch furnaces Harmonics produce a nonsinusoid voltage and current wave as shown in the picture below: i 1 Ýi p wt Shape of a harmonic wave The harmonics created on line by nonlinear loads overload the power factor correction condensers, the dimensions of which should be such as to effectively bear the added stress L1 L2 L PROTECTION FUSES DAMPENING INDUCTANCE CONTROL SWITCH DISCHARGE RESISTOR CONDENSER Standard battery wiring diagram 4

4 W Inductive impedance To avoid this danger, there is a need to implement dedicated power factor correction systems including antiresonance reactances Hz L1 L2 L3 Capacitative impedance PROTECTION FUSES Impedance behaviour for a condenser bank in relation to the frequency ANTIRESONANCE REACTANCE When on line distortion reaches high levels the danger of parallel resonances between power factor correction system and mains becomes apparent. I.e., a current may arise such as to seriously damage condensers and other on line appliances. Knowing the short circuit power of the system (S in kva) and the power factor correction condenser power (Q in kvar), calculating the parallel resonance frequency is possible by means of the following: CONTROL SWITCH DISCHARGE RESISTOR CONDENSER Wiring diagram of antiresonance reactance battery fr = f1 S Q where fr and f1 are the parallel resonance frequency and the fundamental frequency (/ Hz). If the calculated frequency is near the frequency of a harmonic present in the system, a parallel resonance between condensers and system takes place according to the frequency of the harmonic. W 0 Inductive impedance 0 Capacitative impedance Behaviour of a condenser bank including an antiresonance reactance in relation to the frequency Hz 0 1 As shown in the picture above, in the case of frequencies higher than the reactancecondense frequency, the power factor correction bank is treated by the system as an inductance, thus eliminating the danger of a resonance within the distribution system Hz Resonance advanced technology for electrical installations

5 MCE MCM Singlephase Capacitors Connecting leads Discharge resistors Connection dumping reactors Housing expansion zone ( mm) for overpressure Selfhealing capacitors. Low dielectric losses. Easy heat dispersal. Specifications constant over time. Strict control of most sensitive processes (winding, sprying, impregnation). Each capacitor is equipped with an overpressure circuitbreaker tripped in case of failures which cannot be repaired by selfhealing (antiexplosion device). Discharge resistor to reduce the capacitor's residual voltage to less than Volts in 3 min. (CEI 33.). Connection dumping reactor to attenuate transient currents (only MCM type). Impregnated with a nontoxic, biodegradable substance. Standard reference: CEI EN 831/12, IEC 831/12 and VDE /4. Parallel and triangleconnected, mounted on bar hold, MCM and MCE capacitors can be used to build up the capacitive steps of any power factor correction bank with automatic regulation. In particular, they can be used as spares on ELCONTROL ENERGY equipments. GENERAL SPECIFICATIONS 64 H L Rated frequency: Hz (Hz on request) Capacitance tolerance: % +% Max. voltage: 1.1 Vn Max. permitted current: 1.3 In 12. Dielectric: Metal polypropilene Dielectric losses: 0.4 W/Kvar R Ambient temperature class: /D ( + C) MCM Standard reference: CEI EN 831/12, IEC 831/12, 64 VDE /4 TECHNICAL SPECIFICATIONS AND MODELS Kvar Vn In Cn (uf) Homologation (Øxh mm) Tang (gr) MCE MCM x 64x 388 MCE MCM x 64x MCE MCM x 64x 3 22 MCE 0.83 MCM x1 64x1 8 MA MCE 1.67 MCM x1 64x MCE 3.33 MCM x 64x MCE MCM x1 64x1 8 MA MCE MCM x1 64x MCE MCM x 64x MCE MCM x 64x 38 MCE MCM x 64x MCE 3.33 MCM x 64x 363 6

6 MCT Threephase Capacitors Capacitors for the fixed power factor connection of transformers or single motors, or for power factor correction with automatic regulation. In addition to the features listed for MCM, the MCT threephase capacitor is equipped with a plastic lid which covers the capacitor terminals in order to protect against accidental contacts (IP33 protection). MCT capacitors have approval. Higher power capacitors (up to max. kvar 2V or kvar, 4, V), can be constructed by combining two or more MCT capacitors, which are parallelconnected using aluminium busbars (supplied in the kit). The parallel connection bars are also protected by the lids of the individual MCT units. Threephase capacitor complete with support and mounting base and protective lid; 3 bars of parallelconnection of 2 MCTs; screws for connection of 2 adjacent bases if required; washer nuts for parallel connection M8 27. GENERAL SPECIFICATIONS Rated frequency: Hz (Hz on request) Capacitance tolerance: % +% Max. voltage: 1.1 Vn Max. permitted current: 1.3 In Dielectric: Polipropilene metallizzato Dielectric losses: 0,4W/Kvar Ambient temperature class: /D ( + C) Standard reference: CEI EN 831/12, IEC 831/12, VDE /4 3 R S T R S T MT M TECHNICAL SPECIFICATIONS AND MODELS Kvar Vn In Cn (uf) Homologation MCT x 2 MCT x 2.3 MCT 7.2 3x MCT x MCT x MCT x MCT x MCT.3 3x MCT.6 3x advanced technology for electrical installations 7

7 STPF QAMF The metal structure is suitable for indoor installation in dustfree environments protected against accidental shock, heat sources and direct sunlight taking care that adequate ventilation is provided. IP protection class with closed doors. Colour RAL 70. Reference standards CEI EN 4391, CEI 17/131 and IEC 439/12 where applicable. Power supply cables enter from above, to be connected directly to the terminals of the threepole load break switch with door interlock. On the front of the panel a green lamp illuminates when the power supply is connected and a red lamp when the safety fuses have blown. Protection using triad of fuses with high breaking power complete with signalling device. Power factor correction banks in a single step constructed using selfhealing, metalcoated polypropylene film capacitors impregnated with nontoxic, biodegradable liquid; each element is singlephase and is enclosed in a metal casing with overpressure device and discharge resistor. Class D. Complies with CEI EN 831/12, IEC 831/12 and VDE /4 standards. Ambient temperature must be between C and + C, maximum relative humidity 90% at C and altitude less than 0 m. For loads with maximum current harmonic distortion % Power at 2V For networks at 2V Hz STPF 2 STPF 2 STPF 2 STPF 2 STPF 2 QAMF 2 QAMF 2 QAMF 2 QAMF 2 QAMF x2x6 38x2x6 x270x700 x270x For loads with maximum current harmonic distortion % Power at V STPF/R 6. STPF/R 12. STPF/R 18. STPF/R STPF/R 37. QAMF/R QAMF/R 62. QAMF/R QAMF/R QAMF/R x2x6 38x2x6 x270x700 x270x

8 Fixed power factor correction equipments For networks at V Hz For loads with no harmonic content (...) For loads with maximum current harmonic distortion % (...4) at V at 4V Power type V type 4V STPF STPF STPF STPF STPF STPF 3 STPF STPF STPF QAMF 70 QAMF QAMF STPF 4 STPF 4 STPF 4 STPF 4 STPF 4 STPF 34 STPF 4 STPF 4 STPF 4 QAMF 704 QAMF 4 QAMF x2x6 38x2x6 38x2x6 38x2x6 x270x700 x270x For loads with maximum current harmonic distortion % Power at 4V STPF/R 7.4 STPF/R 4 STPF/R 22.4 STPF/R 4 STPF/R 37.4 STPF/R 44 QAMF/R 2.4 QAMF/R 4 QAMF/R 4 QAMF/R 904 QAMF/R x2x6 38x2x6 38x2x6 x270x700 x270x For loads with maximum current harmonic distortion % Power at 4V STPF/S 134 STPF/S 4 STPF/S 4 STPF/S 4 QAMF/S 4 QAMF/S 4 QAMF/S 4 QAMF/S x2x6 38x2x6 x270x advanced technology for electrical installations 9

9 PFCD PFR PFRMD Automatic regulators All regulators are able to carry on measurements in varmetric modality and are supplied with filter for cosfi regulation even in presence of high harmonic disturbance. The TA to be used must have secondary of A. PFCD Automatic power factor regulator for DIN Rail mounting Automatic or manual functionning. Insertion time sec, or sec. on request. LED Signalling of following functions: mainson condition, inductive/capacitive load, bank of capacitors connected, overheating alarm with discharge of the batteries in case that the temperature is above C and automatic reinsertion at the minimum threshold of 4 C. Sensitivity adjustment. Cosø adjustment from 0.8 inductive to 0.9 capacitive. CESI approved PFR Automatic power factor regulator in 144x144 dimensions Automatic or manual functionning. LED Signalling of following functions: mainson condition, inductive/capacitive load, bank of capacitors connected. Cosfi adjustment from 0.8 inductive to 0.9 capacitive. CESI approved PFRF PFRFI PFRT PFRTI PFRHTA Insertion time from 6 to sec. Insertion time from 6 to sec. Indication of istantaneous cosfi through LED Fixed insertion time at sec. Fixed insertion time at sec. Indication of istantaneous cosfi through LED Fixed insertion time at sec. Harmonic overload control device with LED indication and disconnection of the capacitor banks, automatic reconnection at preset threshold. PFRMD Microprocessorbased power factor regulator in 144x144 dimensions Automatic or manual functionning. LED Signalling of following functions: mainson condition, inductive/capacitive load, bank of capacitors connected, minimum and maximum temperature intervention, harmonic distortion, resonance control. Management of display: cosø of the network, cosø selected, voltage, current, temperature. Automatic sensitivity adjustment. Cosfi adjustment from 0.8 inductive to 0.9 capacitive. Equalization of the number of step operations. Additional alarms for: lack of P.F. correction, mains failure, weighting not possible, high applied voltage. The model PFRMDOF is equipped with a serial output for PC connection able to monitoring the network. CESI approved Further specifications are showed on the catalogue about automatic power factor regulators.

10 STP Automatic power factor correction equipments The structure is suitable for indoor installation in nondusty environments, protected against accidental impacts, heat sources and direct sunlight, taking care that adequate ventilation is provided. Protection degree IP with doors closed. Colour RAL70. The metal structure is in pregalvanized steel plate with removable plasticcoated steel plate front panel and safety screws. It is also equipped with air inlets for natural ventilation on front up to size mm and also on the sides in size 38x2x6 mm. The structure is wallmounted using the brackets provided. Reference rules: CEI EN 4391, CEI 17/13 1 and IEC 439/12 as far as applicable. Power supply cables enter from above and are directly connected to the terminals of the load break switch, which is of threepole main switch type with door interlock and preopening limit stop. The regulator is PFCD series. The capacitor banks are protected by HBC fuses. Power factor correction banks on several steps, each controlled by a dedicated switch. The capacitors are MCE series. The ambient service conditions must be: temperature between C and + C, maximum relative humidity of 90% at C and altitude less than 0 meters above sea level. On request: PFCD with battery insertion at sec. Protection degree IP4. advanced technology for electrical installations 11

11 QAM Automatic power factor correction equipments The structure is suitable for indoor installation in nondusty environments, protected against accidental impacts, heat sources and direct sunlight, taking care that adequate ventilation is provided. Protection degree IP with doors closed. Colour RAL70. The metal structure is in pregalvanized steel plate with removable painted steel plate front panel and safety screws. It is also equipped with air inlets for natural ventilation (forced by means of a fan for h = 1 mm) on cover and on sides. Reference rules: CEI EN 4391, CEI 17/131 and IEC 439/12 as far as applicable. The power supply is provided from above, directly to the terminals of the load break switch, which is of threepole main switch type with door interlock and preopening limit stop. Power factor correction banks, with various steps, each controlled by a dedicated switch and including preswitch coils. The regulator is PFCD series. The capacitor banks are protected by HBC fuses. The capacitors are MCE series. The ambient service conditions must be: temperature between C and + C, maximum relative humidity of 90% at C and altitude less than 0 meters above sea level. On request: PFCD with battery insertion at sec. Protection degree IP4. 12

12 ARCM Automatic power factor correction equipments The structure is suitable for indoor installation in nondusty environments, protected against accidental impacts, heat sources and direct sunlight, taking care that adequate ventilation is provided. Protection degree IP with doors closed. Colour RAL70. The metal structure is in pressed steel plate for fixing to the floor, painted with drystate epoxy resins after phosphating to prevent rust. Lifting eyebolts are provided. Ventilation is by means of air intakes and fans controlled by temperature sensors. Reference rules: CEI EN 4391, CEI 17/131 and IEC 439/12 as far as applicable. Cables enter from above for h= mm, from below for h=0 mm. They are directly connected to the terminals of the load break switch, which is of threepole main switch type with door interlock and preopening limit stop. The regulator is PFR or PFRMD series. The capacitor banks are protected by HBC fuses. The capacitors are installed on plates which can be removed from the front of the panel, separate from the control and protective devices. Their feeding is implemented by means of noninsulated electrolytic copper bars with sharp edges, connected in series. Each battery is controlled by a dedicated switch, inductances are also present to limit switching current peaks. The capacitors are MCE series. The ambient service conditions must be: temperature between C and + C, maximum relative humidity of 90% at C and altitude less than 0 meters above sea level. On request: Protection degree IP31, IP, IP4. PFR regulator different from the standard one or PFRMD. advanced technology for electrical installations 13

13 Automatic power factor correction equipments For loads with maximum current harmonic distortion of % STP 2 STP 12.2 STP 17.2 STP 2 QAM 2 QAM 2/A QAM 42 QAM 2 QAM 2/A QAM 2 QAM 902 ARCM 2 ARCM 2/A16 ARCM 12 ARCM 12/A1 ARCM 12 ARCM 12 ARCM 22 ARCM 22/A270 ARCM 22 ARCM 2702 ARCM 02 ARCM 32 ARCM 32/A4 ARCM 42 ARCM 42 ARCM 42/A0 ARCM 2 ARCM 02 Power at 2V Capacitors: MCExx2 Standard regulator: PFRT on ARCM, PFCD on STP and QAM ** (ampli. with n. 1 M2 2) * (ampli. with n. 1 M1 2) * (ampli. with n. 1 MR1 2) * (ampli. with n. 1 MR1 2) * (ampli. with n. 1 MR1 2) 1 11* (ampli. with n. 2 MR1 2) * (ampli. with n. 2 MR1 2) Steps n. x kvar 4x2. x2. 7x2. x 6x 6x 9x 6x 6x x 9x 7x 7x 8x 8x x x 7x 7x 8x 9x x 12x 12x 14x 16x 16x 9x x x2x6 38x2x6 x270x700 x270x1 x270x1 x270x Modules for equipments expansion THD <% Power at 2V M1 2 M2 2 MR1 2 1 x270x x270x xx Modules for equipments expansion THD <% Power at V M1/R MR1/R MR1/R 3 6 x270x xx2 xx Modules for equipments expansion THD >% Power at V MR1/H xx

14 for networks at 2V Hz For loads with maximum current harmonic distortion of % QAM/R 37. QAM/R 62. QAM/R QAM/R /A QAM/R 112. ARCM/R 1 ARCM/R 1/A1 ARCM/R 1 ARCM/R 1 ARCM/R ARCM/R 2 ARCM/R 262. ARCM/R 0 ARCM/R 0/A3 ARCM/R 3 ARCM/R 4 ARCM/R ARCM/R 0 ARCM/R 6 ARCM/R 7 Power at V Capacitors: MCE 3,383 Standard regulator: PFCD on QAM, PFRT on ARCM Steps n. x kvar x x x * (ampli. with n. 1 M1/R ) 6X x x * (ampli. with n. 1 MR1/R ) x x12. 7x 8x x x x * (ampli. with n. 1 MR1/R ) 8x x x x x x 111 x x270x700 x270x1 x270x For loads with high harmonic distortion Power at V Steps n x kvar ARCM/H 4x 1 14 ARCM/H /A1 * (ampli. with n. 1 MR1/H ) 4x 1 14 ARCM/H x 1 7 ARCM/H /A1 * (ampli. with n. 1 MR1/H ) x 1 14 ARCM/H 1 1 7x ARCM/H 8x ARCM/H x ARCM/H x ARCM/H 2/A3 2 * (ampli. with n. 2 MR1/H ) 12x ARCM/H 2 2 7x ARCM/H 3 3 8x ARCM/H 3 3 9x ARCM/H x ARCM/H x Capacitors: MCE 3,383 Antiresonance reactance: LC tuning frequency 189 Hz with threephase capacitors in core consisting of lowloss sheets with oriented cristals and high linearity Standard regulator: PFRMD advanced technology for electrical installations

15 Automatic power factor correction equipments For loads with maximum current harmonic distortion of % Power at 4V Steps n. x kvar STP 4 STP 12.4 STP 17.4 STP 4 STP 34 STP 4 STP 4 QAM 4 QAM 4/A1 QAM 4 QAM 4/A1 QAM 4 QAM 4/A1 QAM 14 QAM 14/A QAM 14 QAM 4 QAM 14 ARCM 4 ARCM 4/A2 ARCM 24 ARCM 24/A0 ARCM 24 ARCM 24 ARCM 24 ARCM 04 ARCM 34 ARCM 34/A4 ARCM 4 ARCM 4/A0 ARCM 44 ARCM 04 ARCM 4 ARCM 04 ARCM 64 ARCM 7004 ARCM 74 ARCM 04 ARCM 9004 ARCM ** (ampli. with n. 1 M2 4) * (ampli. with n. 1 M1 4) * (ampli. with n. 1 M1 4) * (ampli. with n. 1 M1 4) * (ampli. with n. 1 MR1 4) * (ampli. with n. 1 MR1 4) * (ampli. with n. 1 MR1 4) * (ampli. with n. 1 MR1 4) 4x2. x2. 7x2. x 7x 4x x 6x 6x 8x 8x x x 6x 6x 7x 8x 9x x x 11x 11x 12x 13x 14x x 7x 7x 8x 8x 9x x 11x 12x 13x 14x x 16x 18x x x2x6 38x2x6 38x2x6 x270x700 x270x1 x270x1 x270x1 x270x1 x270x1 x270x For power factor correction with no harmonic distortion use V series. Ex.: STP 17,. Capacitors: MCExx for... series, MCExx4 for...4 series. Standard regulators: PFCD on STP and QAM, PFRT on ARCM. Modules for equipments expansion THD 0% M1 M2 MR1 MR1 THD % M1 M2 4 MR1 4 MR1 4 Power at /4V x270x x270x xx2 xx

16 for networks at V Hz For loads with maximum current harmonic distortion of % QAM/R 37.4 QAM/R 37.4/A82. QAM/R 2.4 QAM/R 4 QAM/R 904 QAM/R 904/A1 QAM/R 4 QAM/R 14 QAM/R 134 ARCM/R 14 ARCM/R 14/A2 ARCM/R 14 ARCM/R 24 ARCM/R 24 ARCM/R 2704 ARCM/R 2704/A3 ARCM/R 34 ARCM/R 34 ARCM/R 34/A4 ARCM/R 4 ARCM/R 44 ARCM/R 494 ARCM/R 4 ARCM/R 84 ARCM/R 4 ARCM/R 64 ARCM/R 74 ARCM/R 764 ARCM/R 84 ARCM/R 9004 Power at 4V ** (ampli. with n. 1 M2/R 44) 7. * (ampli. with n. 1 M1/R 4) * (ampli. with n. 1 MR1/R 4) * (ampli. with n. 1 MR1/R 44) * (ampli. with n. 1 MR1/R 904) Steps n. x kvar x7. x7. 7x7. x 6x 6x 7x 8x 9x x x 12x 14x 8x 6x4 6x4 7x4 8x4 8x4 9x4 x4 11x4 12x4 13x4 14x4 x4 16x4 17x4 9x90 x x270x700 x270x1 x270x1 x270x1 x270x Capacitors: MCE 3,004. Standard regulator: PFCD on QAM, PFRT on ARCM. Modules for equipments expansion THD % Power at 4V M1/R 4 M2/R 44 MR1/R 44 MR1/R 4 MR1/R x270x x270x xx2 xx2 xx M2 STP STP 3 QAM QAM 1 QAM 1 1 ARCM 0 ARCM 3 0 ARCM advanced technology for electrical installations 17

17 Automatic power factor correction equipments For loads with maximum current harmonic distortion of % Power at 4V Steps n. x kvar QAM/S 31.4 QAM/S 4 QAM/S 4/A QAM/S 4 QAM/S 4/A QAM/S 4 QAM/S ARCM/S 14 ARCM/S 14/A2 ARCM/S 14 ARCM/S 14/A0 ARCM/S 4 ARCM/S 4/A2 ARCM/S 14 ARCM/S 14/A2 ARCM/S 4 ARCM/S 4/A2 ARCM/S 24 ARCM/S 24/A0 ARCM/S 24 ARCM/S 04 ARCM/S 34 ARCM/S 34 ARCM/S 4 ARCM/S 44 ARCM/S 44 ARCM/S 4 ARCM/S 4 ARCM/S 04 ARCM/S 64 ARCM/S 64 ARCM/S 74 ARCM/S 04 ARCM/S * ampli. with n. 1 M1/S * ampli. with n. 1 M1/S ** ampli. with n. 2 MR1/S 4 ** ampli. with n. 2 MR1/S 4 * ampli. with n. 1 MR1/S 4 * ampli. with n. 1 MR1/S 4 * ampli. with n. 1 MR1/S 4 * ampli. with n. 1 MR1/S 4 x6. 4x12. 4x12. 6x12. 6x12. 8x12. 9x12. 6x 6x 7x 7x 8x 8x 9x 9x x x 11x 11x 13x x 16x 9x x 11x 12x 13x 14x x 16x 17x 9x x 12x x270x700 x270x1 x270x1 x270x1 x270x1 x0x Capacitor: MCE 3,33. Standard regulator: PFCD on QAM, PFRHTA on ARCM. Modules for equipments expansion THD % M1/S 4 MR1/S 4 Power at /4V 9 x270x xx2 16 MR2 18

18 for networks at V Hz For loads with maximum current harmonic distortion of % Power at 4V Steps n. x kvar ARCM/LH x 1 ARCM/LH 904/A1 90 * ampli. with n. 1 MR1/LH 4 3x 1 ARCM/LH x 3 1 ARCM/LH 14/A1 1 * ampli. with n. 1 MR1/LH 4 4x 3 1 ARCM/LH 14 1 x 192 ARCM/LH 14/A2 1 * ampli. with n. 1 MR1/LH 4 x 192 ARCM/LH x 2 23 ARCM/LH 14/A2 1 * ampli. with n. 1 MR1/LH 4 6x 2 23 ARCM/LH x ARCM/LH x 7 0 ARCM/LH x 34 3 ARCM/LH x 384 ARCM/LH x 422 ARCM/LH x 4 0 ARCM/LH x ARCM/LH x ARCM/LH x 6 ARCM/LH x ARCM/LH x ARCM/LH x ARCM/LH x ARCM/LH x 921 x0x0 8 0 ARCM/LH x 997 x0x0 9 0 ARCM/LH x 74 x0x0 9 0 ARCM/LH x 11 x0x ARCM/LH x 1227 x0x0 4 0 ARCM/LH x 14 2x0x ARCM/LH x x0x ARCM/LH x 148 2x0x ARCM/LH x 34 2x0x0 0 ARCM/LH x x0x0 3 0 Capacitor: MCE 3,334. Antiresonance reactance: LC tuning frequency 189 Hz with threephase capacitors in core consisting of lowloss sheets with oriented cristals and high linearity. Standard regulator: PFRTI. Modules for equipments expansion THD % MR1/LH 4 Power at /4V 6 xx2 22 MR1/LH advanced technology for electrical installations 19

Low Pass Harmonic Filters

Low Pass Harmonic Filters Exclusive e-rated Provider PRODUCT SHEET HARMITIGATOR TM Low Pass Harmonic Filters A solution for electrical distribution systems that require stable, reliable power, characterized by unparalleled power

More information

Automatic capacitor banks with detuned filters

Automatic capacitor banks with detuned filters الکتروه م ند Power factor correction and harmonic filtering Automatic capacitor banks with detuned filters www.electrohamand.com Automatic capacitor banks with detuned filters Introduction R5/6-3 R.5 -

More information

Automatic capacitor banks with detuned filters

Automatic capacitor banks with detuned filters Power factor correction and harmonic filtering 5 R. /6 Automatic capacitor banks with detuned filters R. 5 /6 Automatic capacitor banks with detuned filters Introduction R5/6-3 R.5 - Automatic capacitor

More information

DATA SHEET POWER CAPACITOR

DATA SHEET POWER CAPACITOR Issued August 2009 10470 DATA SHEET POWER CAPACITOR General Data * POWER FACTOR CORRECTION The power factor of a load is defined as the ratio of active power to apparent power, i.e. kw : kva and is referred

More information

Power factor correction and harmonic filtering. Harmonic filters and EMI

Power factor correction and harmonic filtering. Harmonic filters and EMI Power factor correction and harmonic filtering Harmonic filters and EMI Introduction 3 R.7 - Harmonic filters and EMI Filtering unit selection guide 12 LCL Harmonic filter for power converters 13 LCL-TH

More information

Reactive Energy Management

Reactive Energy Management Energy management Reactive Energy Management Low Voltage Components Catalogue 2010 Reactive Energy Management Main contents Power Factor Correction guideline 2 Low Voltage capacitors 3-9 Detuned reactors

More information

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA SETTING UP REACTIVE POWER COMPENSATION DEVICES SELECTING A REACTIVE POWER COMPENSATION DEVICE To effectively compensate the

More information

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Part 1 - General Scope and Product Description 1.0 This specification contains the minimum design

More information

NSL-10 STANDARD LIFE MODULAR CAPACITORS

NSL-10 STANDARD LIFE MODULAR CAPACITORS ADVANCE P.F. CORRECTION SOLUTIONS FROM NEPTUNE-DUCATI Channel Partner Ph: 02621-234524, 99242 04524 Industrial Trading Co. 10B Dharma Super Market, Kim Char Rasta, Contact : Paresh Gandhi (98241 31205)

More information

Reactors for filtering

Reactors for filtering NEW ZEALAND WWW.LPINZ.CO.NZ Unit 6/22 Moselle Ave, Henderson, Auckland, New Zealand PO Box 21-872, Henderson, Auckland, New Zealand Phone:+64 9 833 5749 Email:info@LPINZ.co.nz Web: www.lpinz.co.nz Reactors

More information

LV Compensation & Filtering Products

LV Compensation & Filtering Products GE Grid Solutions LV Compensation & Filtering Products Providing Power Quality and Energy Efficiency Low (LV) reactive power compensation and harmonic filtering solutions help customers to improve the

More information

SWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

SWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) SWF DV/DT Solutions Sinewave Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Does your application use variable frequency drives for improved

More information

Power IT LV Active Filters PQFA - PQFL - PQFT

Power IT LV Active Filters PQFA - PQFL - PQFT Power IT LV Active Filters PQFA - PQFL - PQFT The ABB comprehensive solution for active filtering of harmonics Pst Harmonics and Power Quality Harmonics caused by non-linear electrical loads such as variable

More information

Varplus 2 capacitors installation guide

Varplus 2 capacitors installation guide 2006 Varplus 2 capacitors installation guide Contents Reactive power Power definition 3 Electrical network pollution Choice of compensation type 4 Choice of detuned reactor tuning frequency 6 Control and

More information

Series P. Applications

Series P. Applications Ratings 25 800 VA Voltage Primary 230 / 400 / 460 V range Secondary 6 / 12 V 12 / 24 V 24 / 48 V 115 / 230 V Voltage selection by means of metal connection bridges, offering the full rated power at any

More information

Orbital GFI Inverter Series

Orbital GFI Inverter Series Orbital GFI Inverter Series Datasheet Key Features One, split or three phases and up to 25 kva Superior efficiency of 95% CAN Bus control and DAQ Power quality and EMC compliance in accordance with European

More information

Power Factor. Power Factor Correction.

Power Factor. Power Factor Correction. Power Factor. Power factor is the ratio between the KW and the KVA drawn by an electrical load where the KW is the actual load power and the KVA is the apparent load power. It is a measure of how effectively

More information

Thyristorised Automatic Power Factor

Thyristorised Automatic Power Factor Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor

More information

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics Power IT LV Active Filters PQFI PQFM PQFK The ABB comprehensive solution for active filtering of harmonics Harmonics and Power Quality Power Quality relates to the amplitude, frequency and distortion of

More information

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS. 1 PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS. DEFINATIONS Working /Active Power: Normally measured in kilowatts (kw). It does the "work" for the system--providing the motion, torque,

More information

Welcome. Power Survey International

Welcome. Power Survey International Welcome Company profile Established since 1948 Manufacturer of low and medium voltage products: Power Factor correction system Harmonic Filter system Steel Cabinet customized to your needs Other products

More information

High voltage shunt capacitor banks HIGH VOLTAGE COMPENSATION AND HARMONIC FILTERING PRODUCTS

High voltage shunt capacitor banks HIGH VOLTAGE COMPENSATION AND HARMONIC FILTERING PRODUCTS High voltage shunt capacitor banks Alstom Grid high voltage shunt capacitor bank offering is divided in: By bank construction HV open rack capacitor banks HV enclosed capacitor banks By bank design HV

More information

Power factor correction and harmonic filtering. Automatic power factor regulators

Power factor correction and harmonic filtering. Automatic power factor regulators Power factor correction and harmonic filtering Automatic power factor regulators Automatic power factor reguladors R.1 - Automatic power factor regulators Selection table R1-4 computer Plus-T Intelligent

More information

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS 1.0 SCOPE The following specification describes the features, design, and application of the Series 7200A

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

PFCC-1000 series. Powerful Flexibility Durability - Quality. Medium Voltage Metal Enclose 5,15,25,35kV Power Factor Correction & Harmonic Filter

PFCC-1000 series. Powerful Flexibility Durability - Quality. Medium Voltage Metal Enclose 5,15,25,35kV Power Factor Correction & Harmonic Filter PFCC-1000 series Medium Voltage Metal Enclose 5,15,25,35kV Power Factor Correction & Harmonic Filter Powerful Flexibility Durability - Quality email.us.at:.quotes@tanddproducts.com www.tanddproducts.com

More information

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company P2 Power Solutions Pvt. Ltd. An ISO 9001:2008 Company Quality Power within your Reach P2 Power Magnetics P2 Power Solutions Pvt. Ltd. P2 Power Solutions Pvt. Ltd. provides EMC and power quality solutions,

More information

Reactive Energy Management

Reactive Energy Management Power Factor Correction Reactive Energy Management Low Voltage components Catalogue 2013 Reactive Energy management Your requirements. Optimize energy consumption By reducing electricity bills, By reducing

More information

Generator Advanced Concepts

Generator Advanced Concepts Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves

More information

Phoenix DX Clean Power (18 Pulse) AC Drive

Phoenix DX Clean Power (18 Pulse) AC Drive PHOENIX DX Phoenix DX Clean Power (18 Pulse) AC Drive Poor power quality can be costly. Nonlinear loads, including AC Drives, introduce undesirable harmonic currents into the power system that can damage

More information

Power factor correction and harmonic filtering. Automatic power factor regulators R.1

Power factor correction and harmonic filtering. Automatic power factor regulators R.1 Power factor correction and harmonic filtering Automatic power factor regulators R.1 R.1 Automatic power factor regulators R.1 - Automatic power factor regulators Selection table R1-4 computer Plus-T Intelligent

More information

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) APQline Active Harmonic Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Power electronic equipment and AC-DC power conversion equipment contribute

More information

High-Voltage Capacitive Compensation Unit for Transformer and Shunt Reactor Testing, Type HVCC

High-Voltage Capacitive Compensation Unit for Transformer and Shunt Reactor Testing, Type HVCC HIGHVOLT Prüftechnik Dresden GmbH Marie-Curie-Straße 1 1139 Dresden, Germany Phone +49 351 8425-7 Fax +49 351 8425-679 E-mail sales@highvolt.de Website www.highvolt.de Data Sheet 8.81-1/1 High-Voltage

More information

Computer-14d - xx - 144a

Computer-14d - xx - 144a POWER FACTOR REGULATOR Computer-14d - xx - 144a INSTRUCTION MANUAL ( M 981 602 / 98B ) (c) CIRCUTOR S.A. -------- POWER FACTOR REGULATOR COMPUTER- 14d --------- Page 2 1.- POWER FACTOR REGULATORS COMPUTER-14d-144a

More information

Technical Application Papers No.8 Power factor correction and harmonic filtering in electrical plants

Technical Application Papers No.8 Power factor correction and harmonic filtering in electrical plants Technical Application Papers No.8 Power factor correction and harmonic filtering in electrical plants Index Technical Application Papers Power factor correction and harmonic filtering in electrical plants

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

SIMEAS-T. Operating Instructions Transducer without auxiliary power. 7KG6111 and 7KG6101. Operating Instructions

SIMEAS-T. Operating Instructions Transducer without auxiliary power. 7KG6111 and 7KG6101. Operating Instructions Operating Instructions SIMEAS-T s Operating Instructions Transducer without auxiliary power for alternating current for alternating voltage for alternating voltage with expanded end range 7KG6111 and 7KG6101

More information

AccuSine PCS Active Harmonic Filter. Cruise through rough waves in your electrical network

AccuSine PCS Active Harmonic Filter. Cruise through rough waves in your electrical network AccuSine PCS Active Harmonic Filter Cruise through rough waves in your electrical network How Can Active Harmonic Filters Solve Power Quality Issues in Your Facility? Power electronic devices that have

More information

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 690 Volts, 50Hz

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 690 Volts, 50Hz POWER QUALITY INSTRUCTION MANUAL Type SWF Sine Wave Filters 690 Volts, 50Hz Page 2 of 24 Contents 1. Introduction & SAFETY 2. Theory of operation 3. Typical results of the Sine Wave Filters 4. Transportation,

More information

Gutor PxW AC UPS Designed for North American Market

Gutor PxW AC UPS Designed for North American Market Gutor PxW AC UPS Designed for North American Market PEW 5 200 kva single phase PDW 10 220 kva three phase Higher ratings upon request schneider-electric.com 2 schneider-electric.com schneider-electric.com

More information

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED SECTION 16280 LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED PART 1 - GENERAL 1.1 SUMMARY This specification defines the requirements for active harmonic filter systems in order to meet IEEE-519-2014

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION Single-Phase Low Voltage Dry- Type Transformers 5-400 kva Three-Phase Low Voltage Dry- Type Transformers 7.5-1000 kva TECHNICAL INFORMATION TABLE OF CONTENTS Introduction...3 Technical Explanations...4

More information

High Frequency Sinewave Guardian TM Filter

High Frequency Sinewave Guardian TM Filter High Frequency Sinewave Guardian TM Filter 380V 480V TECHNICAL REFERENCE MANUAL FORM: SHF-TRM-E REL. April 2015 REV. 001 2015 MTE Corporation Caution Prior to start up; confirm the drive operation mode

More information

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units BETA Switching Transformers, Bells and Socket Outlets /2 Product overview /3 4AC3 0, 4AC3 1 bell transformers /5 4AC3 4... 4AC3 transformers for permanent loads /8 4AC2 4 power supply units / 7LQ2 2 bells

More information

SHARDA Make Harmonics Filter

SHARDA Make Harmonics Filter SHARDA Make Harmonics Filter SHARDA offers perfect solution to minimize Harmonics level of industries where non-linear load like, VFD, Electronics load, Convertors, Voltage booster equipment s are present.

More information

Commissioning and Maintenance of Power Factor Correction Systems

Commissioning and Maintenance of Power Factor Correction Systems Dear Customer, We would like to thank you for choosing a power factor correction system from FRAKO Kondensatoren- und Anlagenbau GmbH. It is a pleasure to welcome you into the ever-expanding circle of

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities

More information

PRODUCT CATALOGUE. amelec Electronic GmbH CH-8157 Dielsdorf QUALITY MADE IN ITALY

PRODUCT CATALOGUE.   amelec Electronic GmbH CH-8157 Dielsdorf QUALITY MADE IN ITALY 2014 PRODUCT CATALOGUE PARTS AND TRA AYS POWER FACTOR CORRECTION LV QUALITY MADE IN ITALY ICAR Means Capacitors ICAR S.p.A. is synonym of capacitor from 1946, coniugated over its multiple applications.

More information

PRODUCT CATALOGUE QUALITY MADE IN ITALY

PRODUCT CATALOGUE QUALITY MADE IN ITALY 2016 PRODUCT CATALOGUE PARTS AND TRA AYS POWER FACTOR CORRECTION LV QUALITY MADE IN ITALY ICAR: products and solutions Founded in 1946, ICAR is a leading manufacturer of capacitors and power factor correction

More information

COMPACT LED DRIVERS. ComfortLine Selectable Current (LEDset) ComfortLine SELECTABLE CURRENT LEDset ,

COMPACT LED DRIVERS. ComfortLine Selectable Current (LEDset) ComfortLine SELECTABLE CURRENT LEDset , COMPACT LED DRIVERS ComfortLine SELECTABLE CURRENT LEDset 186650, 186664 Typical Applications Built-in in compact luminaires for Shop lighting Downlights ComfortLine with selectable current SELECTABLE

More information

Power supply CP-D 24/4.2 Primary switch mode power supply

Power supply CP-D 24/4.2 Primary switch mode power supply Data sheet Power supply CP-D 24/4.2 Primary switch mode power supply The CP-D range of modular power supply units in MDRC design (modular DIN rail components) is ideally suited for installation in distribution

More information

HARMONICS CAUSES AND EFFECTS

HARMONICS CAUSES AND EFFECTS HARMONICS CAUSES AND EFFECTS What is Harmonics? Harmonics is defined as the content of the signal whose frequency is an integral multiple of the system frequency of the fundamentals. Harmonics current

More information

McGill Power Sales & Engineering, INC.

McGill Power Sales & Engineering, INC. 1 McGill Power Sales & Engineering, INC. Power Factor Correction Terry McGill President McGill Power Sales & Engineering Inc. 2007 Eaton Corporation. All rights reserved. Agenda What is power factor? What

More information

Power Factor Correction

Power Factor Correction Power Quality Power Factor Correction Low Voltage components Catalogue 2017 Power Quality Your requirements. Optimize energy consumption By reducing electricity bills, By reducing power losses, By reducing

More information

+ 24V 3.3K - 1.5M. figure 01

+ 24V 3.3K - 1.5M. figure 01 ELECTRICITY ASSESSMENT 35 questions Revised: 08 Jul 2013 1. Which of the wire sizes listed below results in the least voltage drop in a circuit carrying 10 amps: a. 16 AWG b. 14 AWG c. 18 AWG d. 250 kcmil

More information

LV PFC Basics. Power Factor Correction - Basics FK PC PM PFC Januar 07 Page: 1

LV PFC Basics. Power Factor Correction - Basics FK PC PM PFC Januar 07 Page: 1 LV PFC Basics Power Factor Correction - Basics FK PC PM PFC Januar 07 Page: 1 What are the different types of loads? Ohmic loads Lighting bulbs Iron Resistive heating Capacative loads Capacitors Underground

More information

Chapter L Power factor correction and harmonic filtering

Chapter L Power factor correction and harmonic filtering Chapter L Power factor correction and 1 2 3 4 5 6 7 8 9 10 Contents Reactive energy and power factor 1.1 The nature of reactive energy L2 1.2 Equipment and appliances requiring reactive energy L2 1.3 The

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELECTRICAL ENGINEERING DIVISION Distribution Network Department SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELA T150.2 en SRA 2250/6 Resistor specification The SRA 2250/6 Resistor is intended to increase

More information

Onsite Mobile AC High Voltage Test System

Onsite Mobile AC High Voltage Test System TSGMF(T) series Onsite Mobile AC High Voltage Test System Onsite mobile AC high voltage test systems are used for withstand voltage testing, partial discharge measurement, tan delta measurement to instrument

More information

APPLICATIONS. AFQ Active Multi-Function Filter. AFQ solves thousands of problems in countless types of installations, in particular the following:

APPLICATIONS. AFQ Active Multi-Function Filter. AFQ solves thousands of problems in countless types of installations, in particular the following: APPLICATIONS AFQ solves thousands of problems in countless types of installations, in particular the following: Data processing centres (DPC) Airports Banking institutions Telecommunications centers Presses

More information

METRAClip87 and 88 Clamp Multimeters

METRAClip87 and 88 Clamp Multimeters 3-349-795-03 1/7.14 Current and frequency measurement via clamp meter: METRAClip87: 1500 A AC TRMS and 1500 A DC METRAClip88: 2000 A AC TRMS and 3000 A DC Multimeter functions via connector sockets: V

More information

Electromagnetic Harmonic Filters Technical Guide

Electromagnetic Harmonic Filters Technical Guide Eliminator Series Electromagnetic Harmonic Filters Technical Guide Neutral Current Eliminator TM (NCE TM ) Parallel connected, 3-phase, 4-wire passive electromagnetic device that diverts 3rd and other

More information

ENCORE 300 SERIES INSTALLATION AND OPERATING INSTRUCTIONS

ENCORE 300 SERIES INSTALLATION AND OPERATING INSTRUCTIONS ENCORE 300 SERIES INSTALLATION AND OPERATING INSTRUCTIONS Copyright 2002-2006 PRI Ltd. 9600-3004-2 Issue C Information contained within this document is subject to change without notice and does not represent

More information

CHAPTER 4 HARMONICS AND POWER FACTOR

CHAPTER 4 HARMONICS AND POWER FACTOR 4.1 Harmonics CHAPTER 4 HARMONICS AND POWER FACTOR In this research a comparative study of practical aspects of mixed use of diode and Thyristor converter technologies in Aluminium Smelters has been carried

More information

شركة الوقت للكهرباء والمقاوالت ذ.م.م.

شركة الوقت للكهرباء والمقاوالت ذ.م.م. CONTRACTING COMPANY W.L.L. is a leading corporate in the United Arab Emirates offering quality services in the field of High Voltage Electrical work 400, 132 & 33 kv and Medium Voltage Power Distribution

More information

Smart Power Relay E I...

Smart Power Relay E I... Smart Power Relay E-48-8I... Description The Smart Power Relay E-48-8I.- is a remotely controllable electronic load disconnecting relay with three functions in a single unit: l electronic relay l electronic

More information

High Frequency SineWave Guardian TM Filter

High Frequency SineWave Guardian TM Filter High Frequency SineWave Guardian TM Filter 380V 480V TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference

More information

Central Inverter SUNNY CENTRAL 200 / 250 / 250HE / 350

Central Inverter SUNNY CENTRAL 200 / 250 / 250HE / 350 Central Inverter SUNNY CENTRAL 200 / 250 / 250HE / 350 Installation Guide SC20_25_35-IEN094521 98-4004821 Version 2.1 EN SMA Solar Technology AG Table of Contents Table of Contents 1 Notes on this Manual..............................

More information

Installation and Operating Instructions. Power IT Power Factor Controller RVC

Installation and Operating Instructions. Power IT Power Factor Controller RVC Installation and Operating Instructions Power IT Power Factor Controller RVC Table of contents Page 1. Read this first... 3 About this Instruction Manual... 3 Safety... 3 Electromagnetic compatibility...

More information

CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS

CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS 40 CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS 3.1 INTRODUCTION The low power factor effects on transmission line, switchgear, transformers etc. It is observed that if the power

More information

Real Time Power Factor Correction Units (Transient Free Switching)

Real Time Power Factor Correction Units (Transient Free Switching) Real Time Power Factor Correction Units (Transient Free Switching) Designers and Manufacturers of Power Factor Correction Equipment and Harmonic Filters 1016 34 AV SE Calgary, AB T2G 1V4 Canada Tel: 403

More information

ELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET

ELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET Candidate Code No. ET37 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three

More information

Power supply circuit Through an external power supply unit V ac / 12 V dc. Operating temperature ºC. Humidity of operation

Power supply circuit Through an external power supply unit V ac / 12 V dc. Operating temperature ºC. Humidity of operation Portable Description Features Measures all of the main electrical parameters of an electricity network Measurement in true root mean square Built-in energy meter With 4 voltage channels and 4 current channels

More information

Analysis of Harmonic Distortion in Non-linear Loads

Analysis of Harmonic Distortion in Non-linear Loads Analysis of Harmonic Distortion in Non-linear Loads Anne Ko Department of Electrical Power Engineering Mandalay Technological University, Mandalay, Myanmar.Phone:+95-09-2225761 anneko101082@gmail.com Wunna

More information

Type CP-S, CP-C & CP-A Switch mode

Type CP-S, CP-C & CP-A Switch mode Switch mode power CP-S, CP-C & CP-A Switch mode Characteristics CP-S and CP-C range Output current 5 A, 10 A and 20 A Integrated power reserve of up to 50 % 5 A and 10 A devices with pluggable connecting

More information

APPLICATION NOTE. Applying Type DD60 Capacitors in Harmonic Filter Applications. Total Power Factor PF = cosine ɸ

APPLICATION NOTE. Applying Type DD60 Capacitors in Harmonic Filter Applications. Total Power Factor PF = cosine ɸ APPLICATION NOTE SEPTEMBER 12, 2017 F-AN-001 FRAKO North America W67N222 Evergreen Bvd Suite 209 Cedarburg, WI 53012 Phone: 1-262-618-2403 Fax: 1-262-618-2303 www.frako.de Applying Type DD60 Capacitors

More information

Electronic Circuit Breaker ESS20-0..

Electronic Circuit Breaker ESS20-0.. Description Electronic circuit breaker type ES-0.. is designed to ensure selective disconnection of individual loads in systems which are powered by a DC 4 V switch-mode power supply. DC 4 V power supplies,

More information

Transformers, Power Supply Units and Socket Outlets

Transformers, Power Supply Units and Socket Outlets Transformers, Power Supply Units and Socket Outlets /2 Introduction /3 4AC3 bell transformers /4 4AC3 safety transformers /5 4AC2 power supply units /6 5TE6 REG socket outlets For further technical product

More information

1 INTRODUCTION ORDER CODE / INFORMATION

1 INTRODUCTION ORDER CODE / INFORMATION INTRODUCTION ORDER CODE / INFORMATION 269/269Plus * * * * * * 269/269Plus SV D/O.4 ORDER CODE / INFORMATION Motor management relay Standard version Drawout version Phase CT Ground CT (required for D/O

More information

Experiment 45. Three-Phase Circuits. G 1. a. Using your Power Supply and AC Voltmeter connect the circuit shown OBJECTIVE

Experiment 45. Three-Phase Circuits. G 1. a. Using your Power Supply and AC Voltmeter connect the circuit shown OBJECTIVE Experiment 45 Three-Phase Circuits OBJECTIVE To study the relationship between voltage and current in three-phase circuits. To learn how to make delta and wye connections. To calculate the power in three-phase

More information

MID. Energy Management Energy Analyzer Type EM11 DIN. Product Description. How to order EM11 DIN AV8 1 X O1 PF. Type Selection EM11 DIN

MID. Energy Management Energy Analyzer Type EM11 DIN. Product Description. How to order EM11 DIN AV8 1 X O1 PF. Type Selection EM11 DIN Energy Management Energy Analyzer Type EM11 DIN Other versions available (not certified, option X): see how to order on the next page Product Description Class 1 (kwh) according to EN62053-21 Class B (kwh)

More information

Voltage Transformers type UMZ User s Manual, Operation and Maintenance

Voltage Transformers type UMZ User s Manual, Operation and Maintenance Voltage Transformers type UMZ User s Manual, Operation and Maintenance ÿþþ Safety at first Safety instructions: Installation, connecting, operation and maintenance should be carried out by the authorised

More information

Power Quality Solutions

Power Quality Solutions Power Quality Solutions What is Power Quality? For electrical systems to function in their intended manner without significant loss of performance or life, they require a supply of electricity that is

More information

Power supply CP-D 24/1.3

Power supply CP-D 24/1.3 2CDC 271 027 F0t07 a OUTPUT ++/ : terminals output Features Rated output voltage 24 V DC Output voltage adjustable via front face potentiometer OUTPUT Adjust Rated output current 1.3 A Rated output power

More information

QUINT-PS/ 3AC/24DC/10

QUINT-PS/ 3AC/24DC/10 Primary-switched power supply with SFB technology, 3 AC, output current 10 A INTERFACE Data sheet 103131_en_01 1 Description PHOENIX CONTACT - 09/2009 Features QUINT POWER power supply units Maximum system

More information

Low voltage circuit breakers

Low voltage circuit breakers Comprehensive Catalogue 2006 Super Solution Low voltage circuit breakers A-4. Technical information TD & TS MCCB Index Temperature derating Power dissipation / Resistance Application Primary use of transformer

More information

Cast resin transformers HARMONY TM

Cast resin transformers HARMONY TM Cast resin transformers HARMONY TM HARMONY TM the optimum solution for higher performance At a time when we are all seeking to preserve our way of life, the production of equipment whilst ensuring safety

More information

Fluke 345. Power Quality Clamp Meter. The ideal meter for commissioning and troubleshooting modern electrical loads

Fluke 345. Power Quality Clamp Meter. The ideal meter for commissioning and troubleshooting modern electrical loads Fluke 345 Power Quality Clamp Meter Technical Data The ideal meter for commissioning and troubleshooting modern electrical loads With a bright color display to analyze the harmonic spectrum, a low-pass

More information

Power supply CP-D 12/2.1

Power supply CP-D 12/2.1 2CDC 271 025 F0t07 a OUTPUT ++/ : terminals output Features Rated output voltage 12 V DC Output voltage adjustable via front face potentiometer OUTPUT Adjust Rated output current 2.1 A Rated output power

More information

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications:

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications: SGMF(T) series Onsite Mobile AC High Voltage Test System On-site AC high voltage test systems are used for voltage withstanding test, partial discharge measurement, tan delta measurement on those instrument

More information

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W ADC5000 SERIES AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications 60W, 125W and 250 W Input voltage 230/115 VAC voltages 12, 24, 36 or 48 VDC Statistical MTBF >3 000

More information

PTC-resistor relay type MS 220 K and MSR 220 K PTC-resistor trip device

PTC-resistor relay type MS 220 K and MSR 220 K PTC-resistor trip device MINIPAN digital panel meters, temperature- and mains controlling, special purpose instruments for customer requirements www.ziehl.com Operating manual PTC-resistor relay type MS 220 K and MSR 220 K PTC-resistor

More information

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers SPECIFICATION GUIDE ABB VACUUM CAST COIL DRY TRANFORMERS CONTENTS 1. General 1.1. Codes and standards 1.2. Service conditions 1.3. System characteristics 1.4. Documentation 2. Design and construction 2.1.

More information

MAVOWATT 4 Multifunction Power Meter

MAVOWATT 4 Multifunction Power Meter Operating nstructions MAVOWATT 4 Multifunction Power Meter 3-348-721-02 3/3.04 1 2 A V 3 4 5 6 Figure 1 2 GOSSEN METRAWATT GMBH Operating controls 1 Connection terminals Current, Voltage,, 2 Mirror scale

More information

Technical catalogue. Emax Low voltage air circuit-breakers. Hotline:

Technical catalogue. Emax Low voltage air circuit-breakers.   Hotline: Technical catalogue Emax Low voltage air circuit-breakers www.alobitanbd.com Hotline: 01711548558 PAGE : 02 The new Emax have received innumerable international certifications and approval by the major

More information

These true on-line inverters incorporate pulse width modulation (PWM) control combined with high frequency igbt power transistors.

These true on-line inverters incorporate pulse width modulation (PWM) control combined with high frequency igbt power transistors. Industrial Inverter The Gentec inverter systems, OND2 SERIES, provide safe, pure sine wave, reliable power to critical control equipment. These inverters are online type, usually the load is fed by the

More information

AccuSine PCS Active Harmonic Filter. Cruising through rough waves in your electrical network

AccuSine PCS Active Harmonic Filter. Cruising through rough waves in your electrical network AccuSine PCS Active Harmonic Filter Cruising through rough waves in your electrical network The Schneider Electric AccuSine power correction system (PCS) injects harmonic current to cancel harmonic current

More information

Power Processor - Series 700F 10KVA to 150KVA

Power Processor - Series 700F 10KVA to 150KVA Power Processor - Series 700F 10KVA to 150KVA Power Conditioning and Regulation for Commercial & Industrial Equipment General Specifications PART 1 - GENERAL 1.1 DESCRIPTION This specification defines

More information

Tuningintobetter power quality

Tuningintobetter power quality Technology Review Third harmonic filters Tuningintobetter power quality Jouko Jaakkola Your PC screen flickers, stops flickering, starts again... Irritating to be sure, and perhaps the first visible sign

More information